Hkkjrh; ekud
IS 3043 : 2018
Indian Standard
Hkw&laioZQu osQ fy, jhfr lafgrk
( nwljk iqujh{k.k )
Code of Practice for Earthing
( Second Revision )
ICS 91.140.50
© BIS 2018
Hkkjrh; ekud C;wjks
BUREAU OF INDIAN STANDARDS
ekud Hkou] 9 cgknqj'kkg T+kiQj ekxZ] ubZ fnYyh&110002
MANAK BHAVAN, 9 BAHADUR SHAH ZAFAR MARG
NEW DELHI-110002
www.bis.org.in www.standardsbis.in
November 2018
Price Group 18
IS 3043 : 2018
CONTENTS
Page
FOREWORD ............................................................................................................................................................ (iii)
1. SCOPE ................................................................................................................................................................ 1
2. REFERENCES ....................................................................................................................................................... 1
3. TERMINOLOGY .................................................................................................................................................... 1
4. STATUTORY PROVISIONS FOR EARTHING ................................................................................................................ 5
5. FACTORS INFLUENCING THE CHOICE OF EARTHED OR UNEARTHED SYSTEM ............................................................... 6
6. SAFETY IN EARTHING .......................................................................................................................................... 7
7. RANGE OF TOLERABLE CURRENT .......................................................................................................................... 7
8. TOLERABLE BODY CURRENT LIMIT ....................................................................................................................... 8
9. ACCIDENTAL GROUND CURRENT .......................................................................................................................... 9
10. CRITERIA OF TOLERABLE VOLTAGE ...................................................................................................................... 12
11. SYSTEM EARTHING ............................................................................................................................................ 15
12. EQUIPMENT EARTHING ...................................................................................................................................... 19
13. RESISTANCE TO EARTH ...................................................................................................................................... 20
14. EARTH ELECTRODES .......................................................................................................................................... 24
15. CURRENT DENSITY AT THE SURFACE OF AN EARTH ELECTRODE ............................................................................. 32
16. VOLTAGE GRADIENT AROUND EARTH ELECTRODES .............................................................................................. 36
17. CONNECTIONS TO EARTH ELECTRODES — EARTHING AND PROTECTIVE CONDUCTORS ............................................. 37
18. EARTHING ARRANGEMENTS FOR PROTECTIVE PURPOSES ....................................................................................... 41
19. EARTHING ARRANGEMENTS FOR FUNCTIONAL PURPOSES ....................................................................................... 41
20. EARTHING ARRANGEMENTS FOR COMBINED PROTECTIVE AND FUNCTIONAL PURPOSES ............................................ 42
21. EQUIPOTENTIAL BONDING CONDUCTORS ............................................................................................................. 43
22. TYPICAL SCHEMATIC OF EARTHING AND PROTECTIVE CONDUCTORS ....................................................................... 43
23. EARTH FAULT PROTECTION IN INSTALLATIONS ...................................................................................................... 43
24. SELECTION OF DEVICES FOR AUTOMATIC DISCONNECTION OF SUPPLY .................................................................... 50
25. EARTHING IN POWER STATIONS AND SUBSTATIONS ................................................................................................ 53
26. EARTHING ASSOCIATED WITH OVERHEAD POWER LINES ....................................................................................... 63
27. GUIDELINES ON EARTHING OF INDUSTRIAL AND COMMERCIAL INSTALLATION ........................................................... 64
28. UNEARTHED GENERATING SETS (RATINGS BELOW 10 KW) .................................................................................. 68
29. EARTHING IN STANDBY GENERATING PLANTS (INCLUDING PORTABLE AND MOBILE GENERATORS) ............................ 69
30. PROTECTIVE MEASURES THROUGH EARTHING IN MEDICAL ESTABLISHMENTS ......................................................... 74
31. SUPPLY CHARACTERISTICS AND PARAMETERS ...................................................................................................... 77
32. EARTHING IN POTENTIALLY HAZARDOUS AREAS .................................................................................................. 81
33. TELECOMMUNICATION CIRCUITS AND APPARATUS ................................................................................................. 82
34. BUILDING SITES ................................................................................................................................................ 83
35. MINES AND QUARRIES ....................................................................................................................................... 84
36. STREET LIGHTING AND OTHER ELECTRICALLY SUPPLIED STREET FURNITURE .......................................................... 86
37. EARTHING OF CONDUCTORS FOR SAFE WORKING ................................................................................................. 87
38. MAINTENANCE OF EARTH ELECTRODES ............................................................................................................... 88
39. CALCULATION OF EARTH FAULT CURRENTS ......................................................................................................... 89
40. MEASUREMENT OF EARTH RESISTIVITY ............................................................................................................... 89
41. MEASUREMENT OF EARTH ELECTRODE RESISTANCE ............................................................................................. 92
42. MEASUREMENT OF EARTH LOOP IMPEDANCE ....................................................................................................... 95
43. EARTHING REQUIREMENTS FOR INSTALLATIONS OF DATA PROCESSING EQUIPMENT ................................................... 95
44. EXAMPLE OF THE USE OF TRANSFORMERS ........................................................................................................... 98
(i)
IS 3043 : 2018
Electrical Installations Sectional Committee, ETD 20
FOREWORD
This Indian Standard (Second Revision) was adopted by the Bureau of Indian Standards, after the draft finalized
by the Electrical Installations Sectional Committee, had been approved by the Electrotechnical Division Council.
The Indian Electricity Act, 2003, together with the Central Electricity Authority (Measures Relating to Safety and
Electric Supply) Regulations, 2010 and amendments, govern the electrical installation work in generating stations,
substations, industrial locations, buildings, etc, in the country. To ensure safety of life and apparatus against earth
faults, it was felt necessary to prepare a code of practice for earthing. The code of practice for earthing was
formulated with the intention to serve as a consolidated guide to all those who are concerned with the design,
installation, inspection and maintenance of electrical systems and apparatus.
This standard was first published in 1966 and revised in 1987. Subsequently, several comments were received
and the National Electrical Code was revised in 2011. Also, the Code of practice of Electrical Wiring Installation
(IS 732) has been revised in 2018. Therefore, the revision of this standard was undertaken to align with the latest
practices.
The subject of earthing covers the problems relating to conduction of electricity through earth. The terms earth
and earthing have been used in this Code irrespective of reliance being placed on the earth itself as a low impedance
return path of the fault current. As a matter of fact, the earth now rarely serves as a part of the return circuit but is
being used mainly for fixing the voltage of system neutrals. The earth connection improves service continuity and
avoids damage to equipment and danger to human life.
The object of an earthing system is to provide as nearly as possible a surface under and around a station which
shall be at a uniform potential and as nearly zero or absolute earth potential as possible. The purpose of this is to
ensure that, in general, all parts of apparatus other than live parts, shall be at earth potential, as well as to ensure
that operators and attendants shall be at earth potential at all times. Also by providing such an earth surface of
uniform potential under and surrounding the station, there can exist no difference of potential in a short distance
big enough to shock or injure an attendant when short-circuits or other abnormal occurrences take place. The
recommendations in this Code are made in order that these objects may be carried out.
Earthing associated with current-carrying conductor is normally essential to the security of the system and is
generally known as system earthing, while earthing of non-current carrying metal work and conductor is essential
to the safety of human life, animals and property, and is generally known as equipment earthing.
Since the revision of this standard in 1987, considerable experience has been gained through the implementation
of its various stipulations. Moreover, several new concepts have been introduced the world over, on the
understanding of functional and protective earthing with a view to take into account a variety of complex problems
encountered in actual practice. In the context of increased use of electric power and the associated need for safety
in the design of installations, it had become necessary to prepare an overall revision of the earlier version of the
Code.
In this Code, the terms ‘earthing’ and ‘grounding’ are used synonymously.
This Code includes comprehensive guidelines on choosing the proper size of the various components of the
earthing system, particularly earthing and protective conductors as well as earth electrodes. Guidance included on
determination of relevant ‘k’ factor depending on material properties and boundary conditions, and the associated
minimum cross-sectional area would assist in a more scientific design of the earthing system under various
circumstances.
The Code also includes comprehensive guidelines on earth fault protection in consumers’ premises to commensurate
with the provisions of Central Electricity Authority (Measures Relating to Safety and Electric Supply) Regulations,
2010 and amendments. It includes specific guidelines on earthing system design to achieve the desired degree of
shock hazard protection from earth leakages. The rules given in the Code should be read in conjunction with
corresponding regulations given in the wiring code (see IS 732).
(iii)
IS 3043 : 2018
Protection against shock, both in normal service (direct contact) and in case of fault (indirect contact) can be
achieved by several measures. Details of such protective measures and guidance on their choice are provided in
IS 732. Earth fault/leakage protection sought to be achieved through equipotential bonding and automatic
disconnection of supply is envisaged to prevent a touch voltage from persisting for such a duration that would be
harmful to human beings. Guidance on achieving this protection is covered in this Code.
While detailed guidelines are covered in specific portions of the Code, the following shall be noted:
a)
For solidly grounded systems, it shall be sufficient to check whether the characteristics of protective
device for automatic disconnection, earthing arrangements and relevant impedances of the circuits are
properly coordinated to ensure that voltages appearing between simultaneously accessible, exposed and
extraneous conductive parts are within the magnitudes that would not cause danger;
b) For systems where the earthing is deemed to be adequate, it shall be checked whether the main overcurrent
protective device is capable of meeting the requirements in the wiring code; and
c) Where the main overcurrent protective device did not fulfil the requirements or where the earthing is
considered inadequate, then a separate residual current device would be necessary to be installed the
earth fault loop impedance and the tripping characteristics so chosen that they comply with safe touch
voltage limits.
The revision of the Code aims at consolidating in one volume all the essential guidelines needed for preparing a
good earthing design in an electrical installation. The revision also attempts to be more elaborate than the earlier
version, especially in areas of specific interest keeping in view the need and wide experience gained the world
over.
For convenience of identifying areas of interest by any specific users of the Code, the information contained in
this Code cover the following aspects:
a)
b)
c)
d)
e)
f)
g)
h)
j)
k)
General,
Connections to earth,
Earth-fault protection in consumer’s premises,
Power stations, substations and overhead lines,
Industrial premises,
Standby and other private generating plant,
Medical establishments,
Miscellaneous installations and considerations,
Measurements and calculations, and
Data processing installations.
The major changes in this revision from the previous standard are as follows:
a)
b)
c)
d)
e)
f)
g)
h)
j)
k)
m)
n)
p)
Reference to Static and Lightning Protection Earthing under Section 8, has been removed as separate
BIS Standards IS/IEC 62305 (Part 1 to 4) based on IEC 62305 series on Protection against lightning;
Amendments of the earlier IS 3043 : 1987 have been incorporated;
Updating of cross-referred standards;
Soil treatment and earthing resistivity enhancing materials updated (13.5);
Resistance of an electrode encased in low resistivity material, for example, conducting concrete has been
included (14.2.5);
Matter updated for structural steelwork earthing (14.2.7);
Mesh (grid) resistance added (14.2.10);
Matter for miscellaneous electrodes has been added (14.2.11);
Calculation of ground surface potentials included (16.4);
Earthing for unearthed generating sets (ratings below 10kW) has been included (28);
Supply system for street lights updated (36);
Soil resistance test methods has been updated (40); and
Measurement of earth electrode resistance (Fall of potential method) updated (41).
(iv)
IS 3043 : 2018
In the preparation of the Code, assistance has been taken from the following:
IEC Pub 60364 (all Parts) Electrical installations in buildings. International Electrotechnical Commission.
For the purpose of deciding whether a particular requirement of this standard is complied with, the final value,
observed or calculated, expressing the result of a test or analysis shall be rounded off in accordance with
IS 2 : 1960 ‘Rules for rounding off numerical values (revised)’. The number of significant places retained in the
rounded off value should be the same as that of the specified value in this standard.
(v)
IS 3043 : 2018
Indian Standard
CODE OF PRACTICE FOR EARTHING
( Second Revision )
IS No.
1 SCOPE
to protection against electric
shock
11353 : 1985
Guide for uniform system of
marking and identification of
conductors and apparatus
terminals
13234
Short-circuit currents in threephase a.c. systems:
(Part 0) : 2017
Calculation of currents
(Part 1) : 2017
Factors for the calculation of
short-circuit currents according
to IS 13234 (Part 0)
(Part 2) : 2017
Data of electrical equipment for
short-circuit current calculations
(Part 3) : 2017
Current during two separate
simultaneous line-to-earth short
circuits and partial short-circuit
currents flowing through earth
(Part 4) : 2017
Examples for the calculation of
short-circuit currents
13252 (Part 1) : 2010 Information technology equipment — Safety : Part 1 General
requirements
IS/IEC 60479
Effects of current on human
beings and livestock:
(Part 1) : 2005
General aspects
(Part 2) : 2007
Special aspects
(Part 3) : 1998
Effects of currents passing
through the body of livestock
(Part 4) : 2004
Effects of lightning strokes on
human beings and livestocks
(Part 5) : 2007
Touch voltage threshold values
for physiological effects
IS/IEC 60898-1 :
Electrical accessories — Circuit
2015
breakers for overcurrent
protection for household and
similar installations : Part 1
Circuit-breakers for ac
operation
SP 30 : 2011
National Electrical Code 2011
1.1 This Code of practice provides recommendations
and guidance on meeting the requirements for the
earthing of electrical installation for the purpose of:
a)
protective earthing that is equipment earthing
of low voltage installation to IS 732 to limit
the potential (with respect to the general mass
of earth) of non-current carrying metal work
associated with equipment, apparatus and
appliance connected to the system.
b) system earthing of low voltage installation to
IS 732 to limit the potential (with respect to
general mass of earth) of current carrying
conductor forming part of the electrical
system.
c) protective earthing and changeover switching
arrangement for generator supplying low
voltage installation.
The earthing of an electrical system or installation is
generally provided for reasons of safety.
1.2 This Code applies only to land-based installations
in and around the building.
It does not apply to:
a) ships, aircrafts, off shore installations;
b) equipments sensitive to static electricity; and
c) the internal earthing of the equipment.
2 REFERENCES
2.1 The standards listed below contain provisions
which, through reference in this text, constitute
provisions of this standard. At the time of publication,
the editions indicated were valid. All standards are
subject to revision, and parties to agreements based on
this standard are encouraged to investigate the
possibility of applying the most recent editions of the
standards listed below. In case the standards are to be
referred in this clause they are to be listed as follows:
IS No.
732 : 2018
4736 : 1986
9409 : 1980
Title
Title
Code of practice for electrical
wiring installations (fourth
revision)
Hot dip zinc coatings on mild
steel tubes (first revision)
Classification of electrical and
electronic equipment with regard
3 TERMINOLOGY
For the purpose of this standard, the following
definitions shall apply.
3.1 Arc-Suppression Coil (Peterson Coil) — An
earthing reactor so designed that its reactance is such
1
IS 3043 : 2018
3.10 Earth Fault Loop Impedance — The impedance
of the earth fault current loop (phase-to-earth loop)
starting and ending at the point of earth fault.
that the reactive current to earth under fault conditions
balances the capacitance current to earth flowing from
the lines so that the earth current at the fault is limited
to practically zero.
3.11 Earth Leakage Current — A current which flows
to earth or to extraneous conductive parts in a circuit
which is electrically sound.
3.2 Bonding Conductor — A protective conductor
providing equipotential bonding.
NOTE — This current may have a capacitive component
including that resulting from the deliberate use of capacitors.
3.3 Class I Equipment — Equipment in which
protection against electric shock does not rely on basic
insulation only, but which includes means for the
connection of exposed conductive parts to a protective
conductor in the fixed wiring of the installation.
3.12 Earthed Concentric Wiring — A wiring system
in which one or more insulated conductors are
completely surrounded throughout their length by a
conductor, for example, a sheath which acts as a PEN
conductor.
NOTE — For information on classification of equipment with
regard to means provided for protection against electric shock
(see IS 9409).
3.13 Earthing Conductor — A protective conductor
connecting the main earthing terminal (see 3.2) (or the
equipotential bonding conductor of an installation when
there is no earth bus) to an earth electrode or to other
means of earthing.
3.4 Dead — The term used to describe a device or
circuit to indicate that a voltage is not applied.
3.5 Double Insulation — Insulation comprising both
basic and supplementary insulation.
3.14 Electrically Independent Earth Electrodes —
Earth electrodes located at such a distance from one
another that the maximum current likely to flow through
one of them does not significantly affect the potential
of the other(s).
3.6 Reference Earth — The conductive mass of the
earth, whose electric potential at any point of this mass
of earth is taken as zero with reference to an earthing
system of electrical power system or electrical
installations in a building.
3.15 Equipotential Bonding — Electrical connection
putting various exposed conductive parts and
extraneous conductive parts at a substantially equal
potential.
3.6.1 Earthing System — Arrangement of connections
and devices necessary to earth equipment or a system
separately or jointly.
NOTE — In a building installation, equipotential bonding
conductors shall interconnect the following conductive parts:
a) Protective conductor;
b) Earth continuity conductor; and
c) Risers of air-conditioning systems and heating systems, if
any.
3.6.2 Global Earthing System — Equipment earthing
System created by the interconnection of local earthing
system that ensures, by the proximity of the earthing
system, that there is no dangerous touch voltage.
NOTES
1 Such system permit the devices of the earth fault current in a
way that results in a reduction of the earth potential rise at the
local earthing system. Such a system could be said to form a
quasi equipotential surface.
2 The existence of global earthing system may be determined
by simple measurement or calculation for such system. Typical
examples of global earthing systems are in city centre, urban or
industrial areas with distributed low and high voltage earthing.
3.16 Exposed Conductive Part — A conductive part
of equipment which can be touched and which is not a
live part but which may become live under fault
conditions.
3.17 Extraneous Conductive Part — A conductive
part liable to transmit a potential including earth
potential and not forming part of the electrical
installation.
3.7 Earth Electrode — A conductor or group of
conductors in intimate contact with and providing an
electrical connection to earth.
3.18 Final Circuit — A circuit connected directly to
current-using equipment or to a socket outlet or socket
outlets or other outlet points for the connection of such
equipment.
3.8 Earth Grid — Earth electrode in the form of two
over lapping groups of buried, parallel, horizontal
electrodes usually laid approximately at right angle to
each other with the electrodes bonded at each intersection.
3.19 Functional Earthing — Connection to earth
necessary for proper functioning of electrical equipment
(see 30.1).
Earth grid provides common ground for electrical
devices and metallic structures.
3.20 Live Part — A conductor or conductive part
intended to be energized in normal use including a
neutral conductor but, by convention, not a PEN
conductor.
3.9 Earth Electrode Resistance — The resistance to
earth of an earth electrode or earth grid.
2
IS 3043 : 2018
3.21 Main Earthing Terminal — The terminal or bar
(which is the equipotential bonding conductor)
provided for the connection of protective conductors
and the conductors of functional earthing, if any, to the
means of earthing.
a)
b)
c)
d)
NOTE —The conductors of the functional earthing may be
connected to main earthing terminal (which is the equipotential
bonding conductor) only if the same is recommended by original
electrical equipment manufacturer.
Exposed conductive parts,
Extraneous conductive parts,
Main earthing terminal, and
Earthed point of the source or an artificial
neutral.
3.27 Reinforced Insulation — Single insulation
applied to live parts, which provides a degree of
protection against electric shock equivalent to double
insulation under the conditions specified in the relevant
standard.
3.22 Neutral Conductor — A conductor connected to
the neutral point of a system and capable of contributing
to the transmission of electrical energy.
NOTE — The term ‘single insulation’ does not imply that the
insulation has to be one homogeneous piece. It may comprise
several layers that cannot be tested singly as supplementary or
basic insulation.
3.23 PEN Conductor — A conductor combining the
functions of both protective conductor and neutral
conductor.
3.24 Portable Equipment — Equipment which is
moved while in operation or which can easily be moved
from one place to another while connected to the supply.
3.28 Residual Current Device — A mechanical
switching device or association of devices intended to
cause the opening of the contacts when the residual
current attains a given value under specified conditions.
3.25 Potential Gradient (At a Point) — The potential
difference per unit length measured in the direction in
which it is maximum.
3.29 Residual Operating Current — Residual current
which causes the residual current device to operate
under specified conditions.
NOTES
1 When an electric force is due to potential difference, it is
equal to the potential gradient.
2 Potential gradient is expressed in volts per unit length.
3.30 Resistance Area (for an Earth Electrode only)
— The surface area of ground (around an earth
electrode) on which a significant voltage gradient may
exist.
3.25.1 Earth Potential — Electric potential with respect
to general mass of earth which occurs in, or on the
surface of the ground around an earth electrode when
an electric current flows from the electrode to earth.
3.31 Safety Extra Low Voltage (see IS 9409).
3.32 Simultaneously Accessible Parts — Conductors
or conductive parts which can be touched
simultaneously by a person or, where applicable, by
livestock.
3.25.2 Earth Potential Rise — voltage between an
earthing system and reference earth.
NOTES
1 Simultaneously accessible parts may be:
a) live parts,
b) exposed conductive parts,
c) extraneous conductive parts,
d) protective conductors, and
e) Earth electrodes.
2 This term applies for livestock in locations specifically
intended for these animals.
3.25.3 Hot Site — Substation where the rise of earth
potential under maximum earth fault condition can
exceed the value either 430V or 650 V depending upon
the fault clearance time.
3.25.4 Transferred Potential — Potential rise of an
earthing system caused by a current to earth transferred
by means of a connected conductor (for example a
metallic cable sheath, PEN conductor, pipeline, rail)
into areas with low or no potential rise related to
reference earth resulting in a potential difference
occurring between the conductor and its surroundings.
3.33 Supplementary Insulation — Independent
insulation applied in addition to basic insulation, in
order to provide protection against electric shock in
the event of a failure of basic insulation.
NOTES
1 The definition also applies where a conductor which is
connected to reference earth, leads into the area of the potential
rise.
2 Transferred potential can result in electrocution path through
the human body other than the ‘touch voltage’ path that is hand
to hand.
3.34 Switchgear — An assembly of main and auxiliary
switching apparatus for operation, regulation,
protection or other control of electrical installations.
NOTE — A more comprehensive definition of the term
‘Switchgear’ can be had from IS 1885 (Part 17).
3.26 Protective Conductor — A conductor used as a
measure of protection against electric shock and
intended for connecting any of the following parts:
3.35 Voltage, Nominal — Voltage by which an
installation (or part of an installation) is designated.
3.36 Touch Voltage — Voltage between conductive
3
IS 3043 : 2018
3.36.1 Prospective Touch Voltage — Voltage between
simultaneously accessible conductive parts (exposed
conductive parts when energised under fault condition
and extraneous conductive parts or mass of earth) when
those conductive parts are not touched simultaneously
by a person.
parts when touched simultaneously that is the potential
difference between an earthed conductor part of
equipment, (that is exposed conductive part) which can
be touched and which is not a live part but which may
become live under fault condition and a point on a
conductive part (that is extraneous conductive part)
liable to transmit a potential including earth potential
and not forming part of the electrical installation or a
point on earth’s surface separated by a distance equal
to the maximum normal reach (hand to hand or hand to
foot) approximately one metre (see Fig. 1).
3.37 Step Voltage — The potential difference between
two points on the earth’s surface, separated by distance
of one pace, that will be assumed to be 1 m in the
direction of maximum potential gradient (see Fig. 1).
3.38 Equipotential Line or Contour — The locus of
points having the same potential at a given time.
NOTE — The value of the effective touch voltage may be greatly
influenced by the impedance of the person in electrical contact
with these conductive parts.
FIG. 1 STEP AND TOUCH V OLTAGES
4
IS 3043 : 2018
3.39 Mutual Resistance of Grounding Electrodes —
Equal to the voltage change in one of them produced
by a change of one ampere of direct current in the other
and is expressed in ohms.
the neutral points shall be earthed by not less than two
separate and distinct connections with earth, each
having its own electrode at the generating station or
substation and may be earthed at any other point
provided no interference is caused by such earthing. If
necessary, the neutral may be earthed through suitable
impedance. Where the neutral and protective
conductors of Electricity supply system of Electrical
supply undertaking, are combined it is in protective
multiply earthed (PME) system, also called TN-C-S
system. The PEN conductor, which is referred to as a
combined neutral and earth (CNE) conductor, is earthed
at the source and extremities of the distribution mains
and points in between. The PEN is the most common
system adopted by Electrical supply undertaking.
3.40 Earth Grid — A system of grounding electrodes
consisting of inter-connected connectors buried in the
earth to provide a common ground for electrical devices
and metallic structures.
NOTE — The term ‘earth grid’ does not include ‘earth mat’.
3.41 Earth Mat — A grounding system formed by a
grid of horizontally buried conductors and which serves
to dissipate the earth fault current to earth and also as
an equipotential bonding conductor system.
4 STATUTORY PROVISIONS FOR EARTHING
Multiple earthing of the CNE conductor ensures that if
the conductor becomes open circuit for any reason
(probably cut and snapped), exposed – conductive parts
remain connected to earth; under such condition the
supply voltage between the installation line and neutral
conductor is substantially reduced and consumer will
experience unacceptable voltage variation.
4.1 Earthing shall generally be carried out in accordance
with the requirements of Central Electricity Authority
(Measures Relating to Safety and Electric Supply)
Regulations, 2010, as amended from time-to-time and
the relevant regulations of the Electricity Supply
Authority concerned.
4.2.1 In cases where direct earthing may prove harmful
rather than provide safety (for example, high frequency
and mains frequency coreless induction furnaces),
relaxation may be obtained from the competent authority.
NOTES
1 When the earthing of a consumer’s installation is being
planned, prior consultation should take place between the
consultant or contractor and the supply authority. Where
necessary, precaution will be taken in order to avoid any
interference with the telecommunication system.
2 The regulations made by CEA required that every electrical
network at whatever voltage be connected with earth and that
the connection is maintained under fault conditions in a sound
manner. This requirement is primarily to preserve the security
of the system by ensuring that the potential on each conductor
is restricted to such a value as is consistent with the level of
insulation applied. Every supply neutral conductor of electrical
network of voltage 650 V and below is required to be connected
with earth generally at the source of voltage.
4.3 Earth electrodes shall be provided at generating
stations, substations and consumer premises in
accordance with the requirements of this Code.
4.4 As far as possible, all earth connections shall be
visible for inspection.
4.5 All connections shall be carefully made; if they are
poorly made or inadequate for the purpose for which
they are intended, loss of life or serious personal injury
may result.
Where the neutral and protective conductors of
electricity supply system of Electrical supply
undertaking are combined, it is in protective multiply
earthed (PME) system, also called TN-C-S system. The
PEN conductor, which is referred to as a combined
neutral and earth (CNE) conductor, is earthed at the
source and extremities of the distribution mains and
point in between. The PME is the most common system
adopted by Electrical supply undertakings.
4.6 Each earth system shall be so devised that the testing
of individual earth electrode is possible. It is
recommended that the value of any earth system
resistance shall be such as to conform to the degree of
shock protection desired.
4.7 It is recommended that a drawing showing the main
earth connection and earth electrodes be prepared for
each installation.
Multiple earthing of the CNE conductor ensures that if
the conductor becomes open circuit for any reason
(probably cut or snapped), exposed-conductor parts
remain connected to earth; under such conditions the
supply voltage between the installation line and neutral
conductor is substantially reduced and consumer will
experience unacceptable voltage variations.
4.8 No addition to the current-carrying system, either
temporary or permanent, shall be made which will
increase the maximum available earth fault current or
its duration until it has been ascertained that the existing
arrangement of earth electrodes, earth bus-bar, etc, are
capable of carrying the new value of earth fault current
which may be obtained by this addition.
4.2 All equipment of voltages of 250 V to 650 V shall
be earthed by two separate and distinct connections
with earth. In the case of high and extra high voltages,
4.9 No cut-out, link or switch other than a linked switch
arranged to operate simultaneously on the earthed or
5
IS 3043 : 2018
earthed neutral conductor and the live conductors, shall
be inserted on any supply system. This, however, does
not include the case of a switch for use in controlling a
generator or a transformer or a link for test purposes.
the ground path, thereby providing an easy means of
detection and tripping against phase-to- ground arcing
fault breakdowns.
5.4 Location of Faults
4.10 All materials, fittings, etc, used in earthing shall
conform to Indian Standard specifications, wherever
these exist.
5.4.1 On an unearthed system, a ground fault does not
open the circuit. Some means of detecting the presence
of a ground fault requires to be installed. In earthed
system, an accidental ground fault is both indicated at
least partially located by an automatic interruption of
the accidentally grounded circuit or piece of equipment.
5 FACTORS INFLUENCING THE CHOICE OF
EARTHED OR UNEARTHED SYSTEM
5.1 Service Continuity
5.5 Safety
5.1.1 A number of industrial plant systems have been
operated unearthed at one or more voltage levels. This
is basically guided by the thought of gaining an
additional degree of service continuity varying in its
importance depending on the type of plant. Earthed
systems are in most cases designed so that circuit
protective devices will remove the faulty circuit from
the system regardless of the type of fault. However,
experience has shown that in a number of systems,
greater service continuity may be obtained with earthedneutral than with unearthed neutral systems.
5.5.1 Whether or not a system is grounded, protection
of personnel and property from hazards require thorough
grounding of equipment and structures. Proper grounding
results in less likelihood of accidents to personnel. Other
hazards of shock and fire may result from inadequate
grounding of equipment in unearthed and earthed
systems. However, relatively high fault currents
associated with solidly earthed system may present a
hazard to workers from exposure to hot arc products
and flying molten metal. This protection is, however,
reduced because of use of metal-enclosed equipment.
5.2 Multiple Faults to Ground
5.6 Abnormal Voltage Hazards
5.2.1 While a ground fault on one phase of an unearthed
system generally does not cause a service interruption,
the occurrence of a second ground fault on a different
phase before the first fault is cleared, does result in an
outage. The longer a ground fault is allowed to remain
on an unearthed system, greater is the likelihood of a
second one occurring in another phase and repairs are
required to restore service. With an unearthed system,
an organized maintenance programme is therefore
extremely important so that faults are located and
removed soon after detection.
5.6.1 The possible over-voltages on the unearthed
system may cause more frequent failures of equipment
than the system, earthed. A fault on one phase of an
unearthed or impedance-grounded system places a
sustained increased voltage on the insulation of
unearthed phases in a 3-phase system. This voltage is
about 1.73 times the normal voltage on the insulation.
This or other sustained over-voltages on the ungrounded
system may not immediately cause failure of insulation
but may tend to reduce the life of the insulation. Some
of the more common sources of over-voltages on a
power system are the following:
Experience has shown that multiple ground faults are
rarely, if ever, experienced on earthed neutral systems.
a)
b)
c)
d)
e)
f)
g)
5.3 Arcing Fault Burndowns
5.3.1 In typical cases, an arcing fault becomes
established between two or more phase conductors in
an unearthed system or between phase and ground in a
solidly earthed-neutral system. This would result in
severe damage or destruction to equipment. However,
arcing fault current levels may be so low that phase
overcurrent protective devices do not operate to remove
the fault quickly. Such faults are characteristic of open
or covered fuses, particularly in switchgear or metalenclosed switching and motor control equipment. It is
generally recognized that protection under such
circumstances is possible by fast and sensitive detection
of the arcing fault current and interruption within 1020 cycles. In solidly earthed-neutral systems, this is
possible as an arcing fault would produce a current in
Lightning,
Switching surges,
Static,
Contact with a high voltage system,
Line-to-ground fault,
Resonant conditions, and
Restriking ground faults.
5.6.2 Surge arresters are recommended for lightning
protection. Neutral grounding is not likely to reduce
the total magnitude of over-voltage produced by
lightning or switching surges. It can, however, distribute
the voltage between phases and reduce the possibility
of excessive voltage stress on the phase-to-ground
insulation of a particular phase. A system ground
connection even of relatively high resistance can
6
IS 3043 : 2018
effectively prevent static voltage build-up. Even under
conditions of an HV line breaking and falling on an LV
system, an effectively grounded LV system will hold
the system neutral close to the ground potential thus
limiting the over-voltage. An unearthed system will be
subjected to resonant over-voltages. Field experience
and theoretical studies have shown the world over that
arcing, restriking or vibrating ground faults on
unearthed systems can, under certain conditions,
produce surge voltages as high as 6 times the normal
voltage. Neutral grounding is effective in reducing
transient build up by reducing the neutral displacement
from ground potential and the destructiveness of any
high frequency voltage oscillations following each arc
initiation or restrike.
currents such that high potential gradients may
occur at points at the earth’s surface;
c) presence of an individual at such a point, time,
and position that the body is bridging two
points of high potential difference;
d) absence of sufficient contact resistance or
other series resistance to limit current through
the body to a safe value under circumstances
(a) through (c); and
e) duration of the fault and body contact, and
hence, of the flow of current through a human
body for a sufficient time to cause harm at the
given current intensity.
The relative low frequency of accidents is due largely
to the low probability of coincidence of all the
unfavourable conditions listed above.
5.7 Cost
5.7.1 The cost differential between earthed and
unearthed neutral system will vary, depending on the
method of grounding the degree of protection desired,
and whether a new or an existing system is to be earthed.
7 RANGE OF TOLERABLE CURRENT
Effects of an electric current passing through the vital
parts of a human body depend on the duration,
magnitude, and frequency of this current. The most
dangerous consequence of such an exposure is a heart
condition known as ventricular fibrillation, resulting
in immediate arrest of blood circulation.
6 SAFETY IN EARTHING
6.1 Basic Problem
In principle, a safe grounding design has the following
two objectives:
7.1 Effect of Frequency
a)
to provide means to carry electric currents into
the earth under normal and fault conditions
without exceeding any operating and
equipment limits or adversely affecting
continuity of service.
b) to reduce the risk of a person in the vicinity of
grounded facilities being exposed to the
danger of critical electric shock.
Humans are very vulnerable to the effects of electric
current at frequencies of 50 Hz. Currents of approximately
0.1 A can be lethal. Research indicates that the human
body can tolerate a slightly higher 25 Hz current and
approximately five times higher direct current.
7.2 Effect of Magnitude and Duration
Current of 1 mA is generally recognized as the threshold
of perception; that is, the current magnitude at which a
person is just able to detect a slight tingling sensation
in his hands or fingertips caused by the passing current.
6.2 Condition of Danger
During typical ground fault conditions, the flow of
current to earth will produce potential gradients within
and around a substation. Figure 2 shows this effect for
a substation with a simple rectangular ground grid in
homogeneous soil.
Currents of 1 mA to 6 mA, often termed let-go currents,
though unpleasant to sustain, generally do not impair
the ability of a person holding an energized object to
control his muscles and release it.
Unless proper precautions are taken in design, the
maximum potential gradients along the earth’s surface
may be of sufficient magnitude during ground fault
conditions to endanger a person in the area. Moreover,
dangerous voltages may develop between grounded
structures or equipment frames and the nearby earth.
In the 9 mA to 25 mA range, currents may be painful
and can make it difficult or impossible to release
energized objects grasped by the hand. For still higher
currents muscular contractions could make breathing
difficult. These effects are not permanent and disappear
when the current is interrupted, unless the contraction
is very severe and breathing is stopped for minutes
rather than seconds.
The circumstances that make electric shock accidents
possible can include the following:
a)
relatively high fault current to ground in
relation to the area of ground system and its
resistance to remote earth;
b) soil resistivity and distribution of ground
In the range of 60 mA to 100 mA currents may cause
ventricular fibrillation, stoppage of the heart, or
inhibition of respiration might occur and cause injury
or death.
7
IS 3043 : 2018
F IG. 2 EQUIPOTENTIAL CONTOURS OF TYPICAL GROUND GRID
If shock currents can be kept below this value by a
carefully designed grounding system, injury or death
may be avoided.
shock energy tolerated by a certain percent
of a given population.
8 TOLERABLE BODY CURRENT LIMIT
The non-fibrillating current of magnitude IB at durations
ranging from 0.03 s to 3.0 s is related to the energy
absorbed by the body as described by the following
equation:
SB = IB2 × ts
The magnitude and duration of the current conducted
through a human body at 50 Hz should be less than the
value that can cause ventricular fibrillation of the heart.
8.1 Duration Formula
… (1)
The duration for which a 50 Hz current can be tolerated
by most people is related to its magnitude in accordance
with Equation (1). It is assumed that 99.5 percent of all
persons can safely withstand, without ventricular
fibrillation, the passage of a current with magnitude
and duration determined by the following formula:
where
IB = the rms magnitude of the current through the
body, in A,
ts
SB
= the duration of the current exposure, in sec,
and
= the empirical constant related to the electric
8
IS 3043 : 2018
IB =
k
ts
IB =
… (2)
where, in addition to the terms previously defined for
equation (1)
The formula for the allowable body current for
approximately 50 kg person weight (SB = 0.013 5 and
k 50 = 0.116) becomes
0.116
for 50 kg body weight
ts
… (4)
8.3 Equation (2) indicates that much higher body
currents can be allowed where fast-operating protective
devices can be relied upon to limit the fault duration. A
judgment decision is needed as to whether to use the
clearing time of primary high-speed relays, or that of
the back-up protection, as the basis for calculation.
k = SB
IB =
0.157
for 70 kg body weight
ts
9 ACCIDENTAL GROUND CURRENT
9.1 Resistance of Human Body
… (3)
For d.c. and 50 Hz a.c. currents, the human body can
be approximated by a resistance. The current path
typically considered is from one hand to both feet, or
from one foot to the other one. The internal resistance
of the body is approximately 300 Ω, whereas values of
body resistance including skin range from 500 Ω to
3 000 Ω.
8.2 Alternative Assumptions
Fibrillation current is assumed to be a function of
individual body weight, as illustrated in Fig. 3. The
figure shows the relationship between the critical
current and body weight for several species of animals
and a 0.5 percent common threshold region for
mammals.
Thus, for the purposes of this standard, the following
resistances, in series with the body resistance, are
assumed as follows:
Thus, the formula for the allowable body current for
approximately 70 kg person weight (SB = 0.024 6 and
k70 = 0.157) becomes
a)
Hand and foot contact resistances are equal
to zero.
FIG. 3 FIBRILLATING CURRENT VERSUS BODY WEIGHT FOR VARIOUS ANIMALS B ASED ON A 3 s
DURATION OF E LECTRICAL SHOCK
9
IS 3043 : 2018
b) Glove and shoe resistances are equal to zero.
Fig. 5. Terminal H is a point in the system at the same
potential as the grid into which the fault current flows
and terminal F is the small area on the surface of the
earth that is in contact with the person’s two feet. The
current Ib, flows from H through the body of the person
to the ground at F. The Thevenin theorem allows us to
represent this two terminal (H, F) network of Fig. 5 by
the circuit shown in Fig. 6.
A value of 1 000 Ω in Equation (5), which represents
the resistance of a human body from hand-to-feet and
also from hand-to-hand, or from one foot to the other
foot, will be used throughout this standard.
RB=1 000 Ω
… (5)
9.2 Accidental Circuit Equivalents
The Thevenin voltage VTh is the voltage between
terminals H and F when the person is not present. The
Thevenin impedance ZTh is the impedance of the system
as seen from points H and F with voltage sources of
the system short-circuited. The current Ib through the
body of a person coming in contact with H and F is
given by:
Using the value of tolerable body current established
either by Equation (3) or (4) and the appropriate circuit
constants, it is possible to determine the tolerable
voltage between any two points of contact.
The following notations are used for the accidental
circuit equivalent shown in Fig. 4:
If
Ig
Ib
is the total fault current, in A;
is the current flowing in the grid, in A;
is the body current (body is part of the
accidental circuit), in A;
RB is the resistance of the body, in W;
U is the total effective voltage of the accidental
circuit (touch or step voltage), in V; and
H and F are points of contact of the body.
Rf =
ρ
4b
Ib =
VTh
ZTh + RB
… (6)
where
RB = the resistance of the human body in Ω.
For most practical cases, the effects of Zsys, grid
resistance and the mutual resistance between the grid
and the person’s feet can be neglected on the total circuit
Thevenin equivalent impedance. Thus, Z Th is
represented by the equivalent impedance of the person’s
feet.
The tolerable body current, IB, defined by Equation (3)
or Equation (4), is used to define the tolerable total
effective voltage of the accidental circuit (touch or step
voltage). The tolerable total effective voltage of the
accidental circuit is that voltage that will cause the flow
of a body current, Ib, equal to the tolerable body
current, IB.
Figure 7 shows the fault current If being discharged to
the ground by the grounding system of the substation.
The current, Ib, flows from one foot F1 through the body
of the person to the other foot, F2. Terminals F1 and F2
are the areas on the surface of the earth that are in
contact with the two feet, respectively. The Thevenin
theorem allows us to represent this two-terminal (F1,
F2) network in Fig. 8. The Thevenin voltage VTh is the
voltage between terminals F1 and F2 when the person
is not present. The Thevenin impedance ZTh is the
Figure 4 shows the fault current If being discharged to
the ground by the grounding system of the substation
and a person touching a grounded metallic structure at
H. Various impedances in the circuit are shown in
F IG. 4 E XPOSURE TO TOUCH VOLTAGE
10
IS 3043 : 2018
FIG. 5 IMPEDANCE TO TOUCH VOLTAGE CIRCUIT
FIG. 6 TOUCH VOLTAGE CIRCUIT
impedance of the system as seen from the terminals F1
and F2 with the voltage sources of the system shortcircuited. The current Ib through the body of a person
is given by Equation (6).
the contact resistance of shoes, socks, etc, is neglected.
The ground resistance in ohms of a metallic disc of
radius b (m) on the surface of a homogeneous earth of
resistivity ρ (Ω-m) is given.
In this standard, the following formulas for the Thevenin
equivalent impedance are used.
Rf =
For touch voltage accidental circuit
ZTh =
ρ
4b
Traditionally, the metallic disc representing the foot is
taken as a circular plate with a radius of 0.08 m. With
only slight approximation, equations for ZTh can be
obtained in numerical form and expressed in terms of
ρ as follows.
Rf
2
And for the step voltage accidental circuit
For touch voltage accidental circuit
Z Th = 2 Rf
ZTh = 1.5ρ
where
Rf = the ground resistance of one foot (with
presence of the substation grounding system
ignored).
For the purpose of circuit analysis, the human foot is
usually represented as a conducting metallic disc and
And for step voltage accidental circuit
ZTh = 6.0ρ
The permissible total equivalent voltage (that is,
tolerable touch and step voltage), using above
Equations, is:
11
IS 3043 : 2018
FIG. 7 EXPOSURE TO TOUCH VOLTAGE
FIG. 8 STEP VOLTAGE CIRCUIT
Etouch = IB (RB + 1.5ρ)
And
person bridging a distance of 1 m with the feet without
contacting any other grounded object.
Etouch = IB (RB + 6.0ρ)
10.1.5 Touch Voltage
The potential difference between the ground potential
rise (GPR) and the surface potential at the point where
a person is standing while at the same time having a
hand in contact with a grounded structure. Touch
voltage measurements can be ‘open circuit’ (without
the equivalent body resistance included in the
measurement circuit) or ‘closed circuit’ (with the
equivalent body resistance included in the measurement
circuit).
10 CRITERIA OF TOLERABLE VOLTAGE
10.1 Criteria of Tolerable Voltage Definitions
10.1.1 Ground Potential Rise (GPR)
The maximum electrical potential that a sub-station
ground grid may attain relative to a distant grounding
point assumed to be at the potential of remote earth.
This voltage, GPR, is equal to the maximum grid current
multiplied by the grid resistance.
10.1.6 Transferred Voltage
10.1.2 Mesh Voltage
A special case of the touch voltage where a voltage is
transferred into or out of the sub station from or to a
remote point external to the substation site.
The maximum touch voltage within a mesh of a ground
grid.
10.1.3 Metal-to-Metal Touch Voltage
10.2 Typical Shock Situations for Air-Insulated Substations
The difference in potential between metallic objects or
structures within the sub-station site that may be bridged
by direct hand-to-hand or hand-to-feet contact.
Figure 9 and Fig. 10 show five basic situations involving
a person and grounded facilities during a fault. For a
foot-to-foot contact, the accidental circuit equivalent
is that of Fig. 7, and its driving voltage U is equal to Es
10.1.4 Step Voltage
The difference in surface potential experienced by a
12
IS 3043 : 2018
(step voltage). For the three examples of hand-to-feet
contact Fig. 9 applies, and U is equal to Et (touch
voltage), E m (mesh voltage), or E trrd (transferred
voltage), respectively. The accidental circuit involving
metal-to-metal contact, either hand-to-hand or handto-feet, is shown in Fig. 11 where U is equal to the
metal-to-metal touch voltage, Emm.
FIG. 9 BASIC SHOCK SITUATIONS
FIG. 10 TYPICAL SITUATION OF EXTENDED TRANSFERRED POTENTIAL
13
IS 3043 : 2018
FIG. 11 T YPICAL METAL TO METAL T OUCH SITUATION IN GIS
where
During a fault, the earth conducts currents that emanate
from the grid and other permanent ground electrodes
buried below the earth’s surface. The resulting potential
gradients have a primary effect on the value of U.
Estep = the step voltage in V,
Etouch = the touch voltage in V,
10.3 Step and Touch Voltage Criteria
The safety of a person depends on preventing the critical
amount of shock energy from being absorbed before
the fault is cleared and the system de-energized. The
maximum driving voltage of any accidental circuit
should not exceed the limits defined as follows. For
step voltage the limit is:
Cs
= 1 due to uniform soil resistivity,
rs
= the resistivity of the surface material in
Ω-m, and
ts
= the duration of shock current in seconds.
If no protective surface layer is used, then ρs = ρ.
With the substitution of ρs = 0 in the foot resistance
terms of Equation Etouch50 and Etouch70, the metal-tometal touch voltage limit is
E=
step
( R B + 2 Rf ) IB
for body weignt of 50 kg
for body weignt of 50 kg
Emm-touch =
0.116
Estep50= (1 000 + 6Cs × ρ s)
ts
116
ts
for body weignt of 70 kg
Emm-touch =
for body weignt of 70 kg
Estep70= (1 000 + 6Cs × ρ s)
0.157
ts
where
Emm is the metal-to-metal touch voltage in V
Similarly, the touch voltage limit is
The actual step voltage, touch voltage, or metal-tometal touch voltage should be less than the respective
maximum allowable voltage limits to ensure safety.
Hazards from external transferred voltages are best
avoided by isolation or neutralizing devices and
labelling these danger points as being equivalent to live
lines.
Rf
Etouch
= ( RB + ) IB
2
for body weignt of 50 kg
Etouch50 = (1 000 + 1.5Cs × ρ s )
0.116
ts
10.4 Effect of Sustained Ground Currents
for body weignt of 70 kg
Etouch70 = (1 000 + 1.5Cs × ρ s )
157
ts
After the safe step and touch voltage limits are
established, the grounding system can then be designed
based on the available fault current and overall clearing
time. The designer should also consider sustained lowlevel (below setting of protective relays) fault
0.157
ts
14
IS 3043 : 2018
magnitudes that may be above the let-go current
threshold. Some sustained faults above the let-go
current, but below the fibrillation threshold, may cause
asphyxiation from prolonged contraction of the chest
muscles. However, it would not be practical to design
against lesser shocks that are painful, but cause no
permanent injury.
phase conductor on an overhead spur line breaks, and
the part remote from the supply falls to the ground, it is
unlikely that any protective gear relying on earthing,
other than current balance protection at the substation,
will operate since the earth-fault current circuit includes
the impedance of the load that would be high relative
to the rest of the circuit.
11 SYSTEM EARTHING
11.0.6 For the purposes of this Code of practice, it is
convenient to consider a system as comprising a source
of energy and an installation; the former including the
supply cables to the latter.
11.0 Basic Objectives
11.0.1 Earthing of system is designed primarily to
preserve the security of the system by ensuring that the
potential on each conductor is restricted to such a value
as is consistent with the level of insulation applied.
From the point of view of safety, it is equally important
that earthing should ensure efficient and fast operation
of protective gear in the case of earth faults. Most high
voltage public supply systems are earthed. Approval
has been given in recent years to unearthed overhead
line systems in certain countries, but these have only
been small 11 kV systems derived from 33 kV mains,
where the capacity earth current is less than 4 A and
circumstances are such that the system will not be
appreciably extended.
11.1 Classification of Systems Based on Types of
System Earthing
11.1.1 Internationally, the earthing systems are
classified as TN System, TT System and IT System. They
are:
a)
TN System — has one or more points of the
source of energy directly earthed, and the
exposed and extraneous conductive parts of
the installation are connected by means of
protective conductors to the earthed point(s)
of the source, that is, there is a metallic path
for earth fault currents to flow from the
installation to the earthed point(s) of the
source. TN systems are further sub-divided
into TN-C, TN-S and TN-C-S systems.
b) TT System — has one or more points of the
source of energy directly earthed and the
exposed and extraneous conductive parts of
the installation are connected to a local earth
electrode or electrodes are electrically
independent of the source earth(s).
c) IT System — has the source either unearthed
or earthed through a high impedance and the
exposed conductive parts of the installation
are connected to electrically independent earth
electrodes.
11.0.2 The limitation of earthing to one point on each
system is designed to prevent the passage of current
through the earth under normal conditions, and thus to
avoid the accompanying risks of electrolysis and
interference with communication circuits. With a
suitable designed system, properly operated and
maintained, earthing at several points may be permitted.
This method of earthing becomes economically
essential in systems at 200 kV and upwards.
11.0.3 The system earth-resistance should be such that,
when any fault occurs against which earthing is
designed to give protection, the protective gear will
operate to make the faulty main or plant harmless. In
most cases, such operation involves isolation of the
faulty main or plant, for example, by circuit-breakers
or fuses.
11.1.2 It is also recognized that, in practice, a system
may be an admixture of type for the purposes of this
Code, earthing systems are designated as follows:
11.0.4 In the case of underground systems, there is no
difficulty whatever but, for example, in the case of
overhead-line systems protected by fuses or circuitbreakers fitted with overcurrent protection only, there
may be difficulty in arranging that the value of the
system earth-resistance is such that a conductor falling
and making good contact with the ground results in
operation of the protection. A low system-earth
resistance is required even in the cases where an arcsuppression coil is installed, as its operation may be
frustrated by too high an earth-electrode resistance.
a)
TN-S System (for 240 V single phase
domestic/ commercial supply) — Systems
where there are separate neutral and protective
conductors throughout the system. A system
where the metallic path between the
installation and the source of energy is the
sheath and armouring of the supply cable (see
Fig. 12).
b) TN-S System (for 415 V three-phase domestic
commercial supply) — An independent earth
electrode within the consumer’s premises is
necessary (see Fig. 13).
11.0.5 Earthing may not give protection against faults
that are not essentially earth faults. For example, if a
15
IS 3043 : 2018
NOTES
1 The protective conductor (PE) is the metallic covering (armour or load sheath of the cable supplying the installation or a separate
conductor).
2 All exposed conductive parts of an installation are connected to this protective conductor via main earthing terminal of the installation.
FIG. 12 TN-S SYSTEM SEPARATE NEUTRAL AND PROTECTIVE C ONDUCTORS THROUGHOUT THE SYSTEM, 230V
S INGLE PHASE. DOMESTIC/COMMERCIAL S UPPLY FOR 3~TN-S (see Fig. 13)
NOTES
1 415 V Three phase domestic/commercial supply having 3 ~ and 1 ~ loads.
2 All exposed conductive parts of the installation are connected to protective conductor via the main earthing terminal of the installation.
An independent earth electrode within the consumer’s premises is necessary.
F IG. 13 INDIAN-TN-S S YSTEM
transformer primary (see Fig. 16).
TT System (for 415V three-phase industrial
supply) — Same as 11.1.1 (b) (see Fig. 17).
g) IT System — Same as 11.1.1 (c) (see Fig. 18).
c)
TN-C System — The neutral and protective
functions are combined in a single conductor
throughout the system (for example earthed
concentric wiring) (see Fig. 14).
d) TN-C-S System — The neutral and protective
functions are combined in a single conductor
but only in part of the system (see Fig. 15).
e) T-TN-S System (for 6·6/11 kV three-phase bulk
supply) — The consumers installation, a TNS system receiving power at a captive
substation through a delta connected
f)
11.1.3 Installation Earthing — 250 V but not Exceeding
650 V Installation Earthing
The purpose of earthing the non-current carrying metal
work of plant and equipment of 250 V but not exceeding
650 V is to:
16
IS 3043 : 2018
NOTE — All exposed conductive parts are connected to the PEN conductor. For 3 ~ consumer, local earth electrode has to be provided
in addition.
FIG. 14 INDIAN TN-C S YSTEM (N EUTRAL AND PROTECTIVE FUNCTIONS COMBINED IN
A S INGLE C ONDUCTOR T HROUGHOUT SYSTEM )
NOTES
1 The usual form of a TN-C-S system is as shown, where the supply is TN-C and the arrangement in the installations in TN-S.
2 This type of distribution is known also as Protective Multiple Earthing and the PEN conductor is referred to as the combined neutral
and earth (CNE) conductor.
3 The supply system PEN conductor is earthed at several points and an earth electrode may be necessary at or near a consumer’s
installation.
4 All exposed conductive parts of an installation are connected to the PEN conductor via the main earthing terminal and the neutral
terminal, these terminals being linked together.
5 The protective neutral bonding (PNB) is a variant of TN-C-S with single point earthing.
F IG. 15 TN-C-S SYSTEM , NEUTRAL AND PROTECTIVE FUNCTIONS COMBINED IN A
SINGLE CONDUCTOR IN A PART OF THE SYSTEM
17
IS 3043 : 2018
NOTE — 6·6/11 kV Three-phase bulk supply.
FIG. 16 T-TN-S SYSTEM
NOTES
1 415 V Three-phase industrial supply having 3 ~ and 1 ~ loads.
2 All exposed conductive parts of the installation are connected to an earth electrode which is electrically independent of the source
earth. Single phase TT system not present in India.
FIG. 17 TT SYSTEM
NOTES
1 All exposed conductive parts of an installation are connected to an earth electrode.
2 The source is either connected to earth through deliberately introduced earthing impedance or is isolated from earth.
FIG. 18 IT SYSTEM
18
IS 3043 : 2018
a)
provide for a low earth fault loop impedance
to facilitate automatic disconnection of supply
in the event of a fault to exposed conductive
parts, and
b) limit the rise of potential under earth-fault
conditions of non-current carrying metal work
with respect to earth to increase safety of
persons and animals in proximity to such metal
work.
Table 1 Marking of Conductors
(Clause 11.2.1)
Designation
Identification by
of
Alphanumeric Graphical
Conductor
Notation
Symbol
Extending the earth arrangement of an installation
within a building by use of protective equipotential
bonding of exposed-conductive parts and extraneousconductive parts increases safety of persons and animals
by reducing touch voltage between such parts and it
can eliminate dangerous sparking.
(1)
(2)
Earth
E
Protective
conductor
PB
(3)
Colour
(4)
No colour other
than colour of
the bare
conductor
Green and yellow
11.2.2 Use of Bi-Colour Combination — Green and
Yellow
The performance requirements for earthing of 250 V
but not exceeding 650 V installation (for example
disconnection times, conductor sizes) are specified in
IS 732.
The bi-colour combination, green and yellow (green/
yellow), shall be used for identifying the protective
conductor and for no other purpose. This is the only
colour code recognized for identifying the protective
conductor.
Where automatic disconnection according to Table 13
of 18.0.5 of IS 732 cannot be achieved, supplementary
equipotential bonding (Local equipotential bonding)
shall be provided in accordance with 18.0.10 and 18.3.4
of IS 732. Also, 19.1 of IS 732 permits RCD protection
to be used to satisfy the requirement of the 18.0.4
and 18.0.5 of IS 732 and maximum values of earth fault
loop impedance are provided in Table 13 for given
touch voltages for two different conditions – (a) Dry
or moist condition, dry skin and significant floor
resistance; and (b) wet locations, wet skin and low floor
resistance.
Bare conductors or bus bars, used as protective
conductors, shall be coloured by equally broad green
and yellow stripes, each 15 mm up to 100 mm wide,
close together, either throughout the length of each
conductor or in each compartment or unit or at each
accessible position. If adhesive tape is used, only bicoloured tape shall be applied.
For insulated conductors, the combination of the
colours, green and yellow, shall be such that, on any
15 mm length of insulated conductor, one of these
colours covers at least 30 percent and not more than
70 percent of the surface of the conductor, the other
colour covering the remainder of that surface.
11.1.4 Equipment Using Current
The purpose of earthing of current–using equipment is
similar to that for earthing electrical installation of
250 V but not exceeding 650 V. Accessible metal parts
of Class I appliances/equipments that may become live
in the event of an insulation fault shall be permanently
and reliably connected to an earthing terminal within
the appliance or to the earthing contact of the appliance
inlet. Earthing terminal and earthing contact shall not
be connected to the neutral terminal.
NOTE — Where the protective conductor can be easily
identified from its shape, construction or position, for example,
a concentric conductor, then colour coding throughout its length
is not necessary but the ends or accessible positions should be
clearly identified by a symbol or the bi-colour combination,
green and yellow.
12 EQUIPMENT EARTHING
12.0 Basic Objectives
However, Class II equipment, in which double
insulation (insulation comprising both basic and
supplementary insulation) or reinforced insulation are
provide, may not have provision for connection of
exposed metal work of the equipment to a protective
conductor and no reliance upon precautions to be taken
in the fixed location of installation.
12.0.1 The basic objectives of equipment grounding
are:
a)
to ensure freedom from dangerous electric
shock voltages exposure to persons in the area;
b) to provide current carrying capability, both in
magnitude and duration, adequate to accept
the ground fault current permitted by the
overcurrent protective system without creating
a fire or explosive hazard to building or
contents; and
11.2 Marking of Earthing/Protective Conductor
11.2.1 The earthing and protective conductor shall be
marked as given in Table 1 (see also IS 11353).
19
IS 3043 : 2018
c)
to contribute to better performance of the
electrical system.
the precautions necessary for safety in the event of
failure of the basic insulation.
12.0.2 Voltage Exposure
13 RESISTANCE TO EARTH
When there is unintentional contact between an
energized electric conductor and the metal frame or
structure that encloses it or is adjacent, the frame or
structure tends to become energized to the same voltage
level as exists on the energized conductor. To avoid
this appearance of this dangerous, exposed shock
hazard voltage, the equipment grounding conductor
must present a low impedance path from the stricken
frame to the zero potential ground junction. The
impedance should also be sufficiently low enough to
accept the full magnitude of the line-to-ground fault
current without creating an impedance voltage drop
large enough to be dangerous.
13.0 Nature of Earthing Resistance
13.0.1 The earthing resistance of an electrode is made
up of:
a) resistance of the (metal) electrode,
b) contact resistance between the electrode and
the soil, and
c) resistance of the soil from the electrode surface
outward in the geometry set up for the flow of
current outward from the electrode to infinite
earth.
The first two factors are very small fractions of an ohm
and can be neglected for all practical purposes. The
factor of soil resistivity is discussed in 13.1.
12.0.3 Avoidance of Thermal Distress
The earthing conductor must also function to conduct
the full ground fault current (both magnitude and
duration) without excessively raising the temperature
of the earthing conductor or causing the expulsion of
arcs and sparks that could initiate a fire or explosion.
The total impedance of the fault circuit including the
grounding conductor should also permit the required
current amplitude to cause operation of the protective
system.
13.1 Soil Resistivity
13.1.1 The resistance to earth of a given electrode
depends upon the electrical resistivity of the soil in
which it is installed. This factor is, therefore, important
in deciding which of many protective systems to adopt.
The type of soil largely determines its resistivity and
examples are given in Table 3. Earth conductivity is,
however, essentially electrolytic in nature and is
affected, by the moisture content of the soil and by the
chemical composition and concentration of salts
dissolved in the contained water. Grain size and
distribution, and closeness of packing are also
contributory factors since they control the manner in
which the moisture is held in the soil. Many of these
factors vary locally and some seasonally so that the
table should only be taken as a general guide.
12.0.4 Preservation of System Performance
The earthing conductor must return the ground fault
current on a circuit without introducing enough
additional impedance to an extent that would impair
the operating performance of the overcurrent protective
device, that is, a higher than necessary ground-circuit
impedance would be acceptable if there is no
impairment of the performance characteristics of the
protective system.
Local values should be verified by actual measurement,
and this is especially important where the soil is
stratified as, owing to the dispersion of the earth current,
the effective resistivity depends not only on the surface
layers but also on the underlying geological formation.
12.1 Classification of Equipment with Regard to
Protection against Electric Shock
12.1.1 Table 2 gives the principal characteristics of
equipment according to this classification and indicates
Table 2 Classification of Equipment
(Clause 12.1.1)
Class 0
Class I
Class II
Class III
Principal characteristics of
equipment
No means of protective
earthing
Protective earthing
means provided
Additional insulation
and no means for
protective earthing
Designed for supply at
safety extra low voltage
Precautions for safety
Earth free environment
Connection to the
protective earthing
None necessary
Connection to safety
extra low voltage
20
IS 3043 : 2018
Table 3 Examples of Soil Resistivity
(Clause 13.1.1)
Sl
No.
(1)
1)
Type of Soil
Probable
Value
Ω.m
(2)
(3)
Climatic Condition
Low Rainfall and
Desert Condition (for
Example, Less than
250 mm a Year)
Underground
Waters (Saline)
Range of values
encountered
Ω.m
(4)
Range of values
encountered
Ω.m
(5)
Range of values
encountered
Ω.m
(6)
1 to 5
Normal and High
Rainfall (for
Example, Greater
than 500 mm a
Year)
i)
Alluvium and lighter clays
5
1)
1)
ii)
Clays (excluding alluvium)
10
5 to 20
10 to 100
iii)
Marls (for example, keuper
marl)
20
10 to 30
50 to 300
iv)
Porous
limestone
example, chalk)
(for
50
30 to 100
v)
Porous
sandstone
(for
example, keuper sandstone
and clay shales)
100
30 to 300
vi)
Quartzites, compact and
crystalline limestone (for
example,
carboniferous
marble, etc.)
300
100 to 1 000
vii)
Clay slates and slatey shales
1 000
300 to 3 000
viii)
ix)
Granite
Fossil slates, schists gneiss
igneous rocks
1 000
2 000
1 000 ards
1 000 upwards
30 to 100
Depends on water level of locality.
stony ground should be avoided, and also all locations
where virgin rock is very close to the surface.
It should also be noted that soil temperature has some
effect (see 13.7), but is only important near and below
freezing point, necessitating the installation of earth
electrodes at depths to which frost will not penetrate.
It is, therefore, recommended that the first 0.5 m of
any earth electrode should not be regarded as being
effective under frost conditions.
13.3 A site should be chosen that is not naturally welldrained. A water-logged situation is not, however,
essential, unless the soil is sand or gravel, as in general
no advantage results from an increase in moisture
content above about 15 to 20 percent. Care should be
taken to avoid a site kept moist by water flowing over
it (for example, the bed of a stream) as the beneficial
salts may be entirely removed from the soil in such
situations.
While the fundamental nature and properties of a soil
in a given area cannot be changed, use can be made of
purely local conditions in choosing suitable electrode
sites and methods of preparing the site selected to secure
the optimum resistivity. These measures may be
summarized as in 13.2 to 13.7.
13.4 Where building has taken place, the site conditions
may be altered by disturbance of the local stratification
and natural geological formation when the electrodes
have to be installed in this disturbed area.
13.2 Where there is any option, a site should be chosen
in one of the following types of soil in the order of
preference given:
If a cut and fill exercise has been carried out then the
top layer may be similar to the natural formation but
increased in depth, whether it is good or bad in terms
of resistivity.
a) Wet marshy ground (see 13.3);
b) Clay, loamy soil, arable land, clayey soil,
clayey soil or loam mixed with small quantities
of sand;
c) Clay and loam mixed with varying proportions
of sand, gravel and stones; and
d) Damp and wet sand, peat.
If an imported fill exercise has been carried out, the
conditions of the upper layers may be altered
considerably.
In these cases, deeper driving of the electrode may be
necessary to reach layers of reasonable resistivity and
Dry sand, gravel chalk, limestone, granite and any very
21
IS 3043 : 2018
also to reach stable ground, such that the value of the
electrode resistance remains stable if the top layers of
the ground dry out.
13.5 Soil treatment to improve earth electrode contact
resistance may be applied in special or difficult
locations, but migration and leaching of applied
chemicals over a period of time reduces the efficiency
of the system progressively, requiring constant
monitoring and replacement of the additives. Ecological
considerations are inherent before such treatment is
commenced and any deleterious effect upon electrode
material has to be taken into account. However, for
some temporary electrical installations in areas of high
ground resistivity, this may be the most economic
method for obtaining satisfactory earth contact over a
short period of working. If a greater degree of
permanence is envisaged, earth electrodes packaged
in material such as bentonite are preferable.
Bentonite or similar material may be used to advantage
in rocky terrain. Where holes are bored for the insertion
of vertical electrodes or where strip electrodes are laid
radially under shallow areas of low resistivity
overlaying rock strata, bentonite packing will increase
the contact efficiency with the general mass of ground.
FIG. 19 V ARIATION OF SOIL RESISTIVITY WITH
MOISTURE C ONTENT
It should be recognized, however, that moisture alone
is not the predominant factor in the low resistivity of
soils; for example, earth electrodes driven directly in
the beds of rivers or mountain streams may present very
high resistance to earth. If the water is relatively pure,
it will be high resistivity and unless the soil contains
sufficient natural elements to form a conducting
electrolyte, the abundance of water will not provide
the soil with adequate conductivity. The value of high
moisture content in soils is advantageous in increasing
the solubility of existing natural elements in the soil,
and in providing for the solubility of ingredients which
may be artificially introduced to improve the soil
conductivity.
There are commercially available materials to achieve
the earth resistivity enhancement effectively but care
should be taken to understand how they work during
installation to ensure that they remain in contact with
the rod or strip and do not shrink or swell away after
drying out. It is to be noted that chemical treatment of
soil has environmental implications and should not be
considered as a long-term solution in order to meet a
specified level of resistance, apart from the risk of
corrosion to the earthing system. Coke breeze should
also not be used due to its highly corrosive nature.
13.6 Effect of Moisture Content on Earth Resistivity
Moisture content is one of the controlling factors in
earth resistivity. Figure 19 shows the variation of
resistivity of red clay soil with percentage of moisture.
The moisture content is expressed in percent by weight
of the dry soil. Dry earth weighs about 1 440 kg/m³and
thus 10 percent moisture content is equivalent to 144 kg
of water per cubic metre of dry soil. It will be seen
from Fig. 19 that above about 20 percent moisture, the
resistivity is very little affected, while below 20 percent
the resistivity increases very abruptly with the decrease
in moisture content. A difference of a few percent
moisture will therefore, make a very marked difference
in the effectiveness of earth connection if the moisture
content falls below 20 percent. The normal moisture
content of soils ranges from 10 percent in dry seasons
to 35 percent in wet seasons, and an approximate
average may be perhaps 16 to 18 percent.
13.6.1 Corrosion Allowance
On an average, steel corrodes about six times as fast as
copper when placed in soil. The extent of corrosion
depends upon the properties of soil. The generally
accepted correlation between the electrical resistivity
of soil and its corrosivity is as indicated in Table 4.
The following methods can be adopted to safeguard
conductor against excessive corrosion:
a) Use of cathodic protection;
b) Use current conducting, corrosion resistant
coating on steel (for example, zinc coating).
The zinc coating on the tubes shall be in
accordance with IS 4736 with coating
thickness 150 microns, Min; and
22
IS 3043 : 2018
therefore, recommended that in areas where the
temperature is expected to be quite low, the earth
electrodes should be installed well below the frost line.
Where winter seasons are severe, this may be about
2 m below the surface, whereas in mild climates the
frost may penetrate only a few centimetres or perhaps
the ground may not freeze at all. Earth electrodes which
are not driven below the first depth may have a very
great variation in resistance throughout the seasons of
the year. Even when driven below the frost line, there
is some variation, because the upper soil, when frozen,
presents a decided increase in soil resistivity and has
the effect of shortening the active length of electrode
in contact with soil of normal resistivity.
Table 4 Soil Resistivity and Corrosion
(Clause 13.6.1)
Sl
No.
(1)
i)
Range of Soil
Resistivity
(Ω.m)
Class of Soil
(2)
(3)
Less than 25
Severely corrosive
ii)
25-50
Moderately corrosive
iii)
iv)
50-100
Above 100
Mildly corrosive
Very mildly corrosive
c)
Use steel conductor with large cross-section
having allowance for corrosion.
Based on the results of the field studies on rates of
corrosion, the following allowances in cross- sectional
area of the earthing conductor are recommended to take
the effect of corrosion into account (see Table 5).
13.8 Artificial Treatment of Soil
Multiple rods, even in large number, may sometime
fail to produce an adequately low resistance to earth.
This condition arises in installations involving soils of
high resistivity. Treatment of soil can be one solution
to these conditions.
Table 5 Allowances in Cross-sectional Area of the
Earthing Conductor to take the Effect of
Corrosion into Account
(Clause 13.6.1)
Sl
No.
Type of Laying of the Earth
Conductor
Allowances to
be Considered
in Sizing
i)
Conductors laid in soils having
resistivity greater than 100 ohmmeters
0
(No
allowance)
ii)
Conductors laid in soils having
resistivity from 25 to 100 ohmmeters
Conductors laid in soils having
resistivity lower than 25 ohmmeters or where treatment of soil
around electrode is carried out
15 percent
iii)
Soil treatment to improve earth electrode contact
resistance may be applied in special or difficult
locations, but migration and leaching of applied
chemicals over a period of time reduces the efficiency
of the system progressively, requiring constant
monitoring and replacement of the additives. Ecological
considerations are inherent before such treatment is
commenced and any deleterious effect upon electrode
material has to be taken into account. However, for
some temporary electrical installations in areas of high
ground resistivity, this may be the most economic
method for obtaining satisfactory earth contact over a
short period of working. If a greater degree of
permanence is envisaged, earth electrodes packaged
in earth enhancing materialare preferable.
30 percent
For the purpose of determining the allowance to be
made for corrosion, the minimum resistivity of the soil
encountered at the location of grounding electrodes to
be considered. The resistivity will be the minimum in
wet weather. Thus, for very mildly corrosive soils, steel
conductors meeting the stability and mechanical
requirement are adequate. However, the steel
conductors in the soil of other types should be at least
6 mm thick if it is steel flat and have a diameter of at
least 16 mm if it is in the form of steel rod.
Earth enhancing material may also be used to advantage
in rocky terrain. Where holes are bored for the insertion
of vertical electrodes or where strip electrodes are laid
radially under shallow areas of low resistivity
overlaying rock strata, earth enhancing material packing
will increase the contact efficiency with the general
mass of ground.
Earth enhancement materials, some with a resistivity
of less than 0.12 Ω.m, are typically placed around the
rod in an augured hole or around grounding conductors
in a trench, in either a dry form or premixed in a slurry.
Some of these enhancement materials are permanent
and will not leach any chemicals into the ground. Other
available ground enhancement materials are mixed with
local soil in varying amounts and will slowly leach into
the surrounding soil, lowering the earth resistivity.There
are commercially available materials to achieve the
earth resistivity enhancement effectively but care should
13.7 Effect of Temperature on Earth Resistance
The temperature coefficient of resistivity for soil is
negative, but is negligible for temperatures above
freezing point. At about 20°C, the resistivity change is
about 9 percent per °C. Below 0°C the water in the soil
begins to freeze and introduces a tremendous increase
in the temperature coefficient, so that as the temperature
becomes lower the resistivity rises enormously. It is,
23
IS 3043 : 2018
be taken to understand how they work during
installation to ensure that they remain in contact with
the rod or strip and do not shrink or swell away after
drying out. It is to be noted that chemical treatment of
soil has environmental implications and should not be
considered as a long term solution in order to meet a
specified level of resistance, apart from the risk of
corrosion to the earthing system. Coke breeze should
also not be used due to its highly corrosive nature.
The alternative is to reduce the resistivity of the soil
immediately surrounding the earth electrode. To reduce
the soil resistivity, it is necessary to dissolve in the
moisture, normally contained in the soil, some
substance which is highly conductive in its water
solution. The most commonly used substances are
sodium chloride (NaCl), also known as common salt,
calcium chloride (CaCl2), sodium carbonate (Na2CO3),
copper sulphate (CuSO4), salt, and soft coke, and salt
and charcoal in suitable proportions.
FIG. 20 V ARIATION OF SOIL RESISTIVITY WITH
SALT (NaCl) CONTENT , CLAY SOIL HAVING
3 PERCENT MOISTURE
13.8.4 In using artificial treatment, the possible
corrosive effect of the salt on the driven rods and
connections should be considered. The possible
contamination of the domestic water supply should also
be considered.
13.8.1 With average or high moisture content, these
agents form a conducting electrolyte throughout a wide
region surrounding the earth electrode. Approximately
90 percent of the resistance between a driven rod and
earth lies within a radius of about 2 m from the rod.
This should be kept in mind when applying the agents
for artificial treatment of soil. The simplest application
is by excavating a shallow basin around the top of the
rod, 1 m in diameter and about 30 cm deep, and
applying the artificial agent in this basin. The basin
should subsequently be filled several times with water,
which should be allowed each time to soak into the
ground, thus carrying the artificial treatment, in
electrolyte form, to considerable depths and allowing
the artificial agent to become diffused throughout the
greater part of the effective cylinder of earth
surrounding the driven rod.
14 EARTH ELECTRODES
14.1 Effect of Shape on Electrode Resistance
With all electrodes other than extended systems, the
greater part of the fall in potential occurs in the soil
within a few feet of the electrode surface, since it is
here that the current density is highest. To obtain a low
overall resistance the current density should be as low
as possible in the medium adjacent to the electrode,
which should be so designed as to cause the current
density to decrease rapidly with distance from the
electrode. This requirement is met by making the
dimensions in one direction large compared with those
in the other two, thus a pipe, rod or strip has a much
lower resistance than a plate of equal surface area. The
resistance is not, however, inversely proportional to the
surface area of the electrode.
13.8.2 The reduction in soil resistivity effected by salt
is shown by the curve in Fig. 20. The salt content is
expressed in percent by weight of the contained
moisture. It will be noted that the curve flattens off at
about 5 percent salt content and a further increase in
salt gives but little decrease in the soil resistivity. The
effect of salt will be different for different kinds of soil
and for various moisture contents but the curve will
convey an idea of how the soil conductivity can be
improved. Decreasing the soil resistivity causes a
corresponding decrease in the resistance of a driven
earth electrode.
14.2 Resistance
Earthelectrodes
of
Common
Types
of
14.2.1 Plates
The approximate resistance to earth of a plate can be
calculated from:
13.8.3 In close texture soils, the artificial treatment may
be effective over a period of many years. However, it
is recommended that annual or biannual measurements
of earth resistivity should be made to find out if
additional treatment is needed.
R=
ρ π
4
A
ohms
where
ρ = resistivity of the soil (assumed uniform)
(in Ω.m), and
A = area of both sides of the plate (in m2).
24
IS 3043 : 2018
Where the resistance of a single plate is higher than
the required value, two or more plates may be used in
parallel and the total resistance is then inversely
proportional to the number employed, provided that
each plate is installed outside the resistance area of any
other. This normally requires a separation of about 10 m
but for sizes of plate generally employed, a separation
of 2 m is sufficient to ensure that the total resistance
will not exceed the value obtained from the above
formula by more than 20 percent. Even at the latter
spacing, it is generally more economical to use two
plates in parallel, each of a given size, than one of twice
that size. The size employed is, therefore, normally not
greater than 1.2 m × 1.2 m.
is at a depth not less than 1·5 m from the surface of the
ground. However, the depth at which plates are set
should be such as to ensure that the surrounding soil is
always damp. Where the underlying stratum is solid,
for example chalk or sandstone and near the surface,
the top of the plate should be approximately level with
the top of the solid stratum.
14.2.2 Pipes or Rods
The resistance of a pipe or rod electrode is given by:
R=
100 ρ
2l
log e
ohms
d
2π l
where
l
= length of rod or pipe, in cm;
d = diameter of rod or pipe, in cm; and
Plate electrodes shall be of the size at least 60 cm ×
60 cm. Plates are generally of cast iron not less than
12 mm thick and preferably ribbed. The earth
connection should be joined to the plate at not less than
two separate points. Plate electrodes, when made of
GI or steel, shall be not less than 6·3 mm in thickness.
Plate electrodes of Cu shall be not less than 3·15 mm
in thickness.
ρ
= resistivity of the soil, in Ω.m (assumed
uniform).
The curves of Fig. 21 are calculated from this equation
for electrodes of 13, 25 and 100 mm diameter
respectively in a soil of l00 Ω.m respectively. Change
of diameter has a relatively minor effect and size of
pipe is generally governed by resistance to bending or
splitting. It is apparent that the resistance diminishes
rapidly with the first few feet of driving, but less so at
depths greater than 2 to 3 m in soil of uniform resistivity.
Suitable methods of jointing are a taper pin driven into
a reamed hole and riveted over or a copper stud screwed
into a tapped hole and riveted. Such joints should be
protected by a heavy coat of bitumen. The connection
between the earth plate and the disconnecting link
should be set vertically and the depth of setting should
be such as to ensure that the surrounding soil is always
damp. The minimum cover should be 600 mm except
that where the underlying stratum is solid, for example,
chalk or sandstone and near the surface, the top of the
plate should be level with the top of the solid stratum.
Sufficient solid stratum should be removed and replaced
with fine soil or other suitable infill to ensure as low a
resistance as possible.
The use of coke breeze as an infill is not recommended
as it may result in rapid corrosion not only of the
electrode itself but also of cable sheaths, etc, to which
it may be bonded.
The resistance R (in Ω) of a 1.2 m × l.2 m plate is given
approximately by the following formula:
R=
FIG. 21 EFFECT OF LENGTH OF PIPE ELECTRODE ON
CALCULATED RESISTANCE FOR SOIL RESISTIVITY OF
100 Ω m (ASSUMED UNIFORM)
ρ
2.75
A number of rods or pipes may be connected in parallel
and the resistance is then practically proportional to
the reciprocal of the number employed so long as each
is situated outside the resistance area of any other. In
practice, this is satisfied by a mutual separation equal
to the driven depth. Little is to be gained by separation
beyond twice the driven depth. A substantial gain is
effected even at 2 m separation. Copper clad mild steel
rods can be used in place of normal mild steel rods
where the soil is corrosive.
For conventional sizes, the resistance is approximately
inversely proportional to the linear dimensions, not the
surface area, that is a 0·9 m × 0·9 m plate would have a
resistance approximately 25 percent higher than a
1.2 m × 1.2 m plate. The current loading capacity of a
1.2 m × 1.2 m plate is of the order of 1 600 A for 2 s
and 1 300 A for 3 s.
Plate electrodes shall be buried such that its top edge
25
IS 3043 : 2018
Pipes may be of cast iron of not less than 100 mm
diameter, 2.5 to 3 m long and 13 mm thick. Such pipes
cannot be driven satisfactorily and may, therefore, be
more expensive to install than plates for the same
effective area. Alternatively, mild steel water-pipes of
38 to 50 mm diameter are sometimes employed. These
can be driven but are less durable than copper rods.
Alternatively, 40 mm diameter GI pipe in treated earth
pit or 40 mm diameter mild steel rod can be directly
driven in virgin soil. The earth rod shall be placed at
1.250 m below ground. The thickness of pipe used for
earthing shall not be less than 1.6 mm thick for
GI/copper/SS pipes.
lengths. Except in special conditions, a number of rods
in parallel are to be preferred to a single long rod.
Deeply driven rods are, however, effective where the
soil resistivity decreases with depth or where substrata
of low resistivity occur at depths greater than those with
rods, for economic reasons, are normally driven. In such
cases the decrease of resistance with depth of driving
may be very considerable as is shown by the
measurements plotted in Fig. 22 for a number of sites;
for curves A1 and A2, it was known from previously
sunk boreholes that the soil down to a depth between
6 m and 9 m consisted of ballast, sand and gravel below
which occurred London clay. The rapid reduction in
resistance, when the electrodes penetrated the latter,
was very marked. The mean resistivity up to a depth of
8 m in one case was 150 Ω.m; at 11 m the mean value
for the whole depth was 20 Ω m moving to the low
resistivity of the clay stratum. Similarly for curve C,
the transition from gravely soil to clayey at a depth of
about 1.5 m was very effective. In the case of curve B,
however, no such marked effect occurred, although
there was a gradual reduction in average resistivity with
increase in depth, as can be seen by comparison with
the dotted curves, which are calculated on the
assumption of uniform resistivity.
Driven rods generally consist of round copper, steelcored copper or galvanized steel 13, 16 or 19 mm in
diameter from 1 220 mm to 2 440 mm in length.
Cruciform and star shaped sections are also available
and are more rigid while being driven, but the apparent
additional surface does not confer a noticeable
advantage in current-carrying capacity or reduction of
resistance. In circumstances where it is convenient to
do so, the addition of radial strips will be advantageous.
Such rods may be coupled together to give longer
FIG. 22 CALCULATED AND EXPERIMENTAL CURVES OF RESISTANCE OF 13 mm DIA DRIVEN ELECTRODES
26
IS 3043 : 2018
generally very effective when consumers’ pipes and water mains
to which they were connected were all metal-to-metal joints,
the use of public water-pipes for this purpose has not been
acceptable for many years because of the use of non-conducting
material for pipes on new installations and for replacement
purposes. Jointing techniques now being used do not ensure
electrical continuity of metallic pipes.
Other factors that affect a decision whether to drive
deep electrodes or to employ several rods or pipes in
parallel are the steep rise in the energy required to drive
them with increase in depth and the cost of couplings.
The former can be offset by reducing the diameter of
the rods, since a 13 mm diameter rod can be driven to
considerable depths without deformation or bending if
the technique of using a large number of comparatively
light blows is adopted rather than a smaller number of
blows with a sledge hammer. Power-driven hammers
suitable for this purpose are available.
In cases where impenetrable strata or high resistivity
soil occur at relatively small depths, considerable
advantage may result from driving rods at an angle of
about 30° to the horizontal, thus increasing the length
installed for a given depth.
14.2.3 Strip or Conductor Electrodes
These have special advantages where high resistivity
soil underlies shallow surface layers of low resistivity.
The minimum cross-sectional area of strip electrodes
shall be according to 12.1.1. If round conductors are
used as earth electrodes, their cross-sectional area shall
not be less than the sizes recommended for strip
electrodes. The resistance R is given by:
R=
FIG. 23 EFFECT OF L ENGTH OF STRIP OR CONDUCTOR
ELECTRODES IN CALCULATED RESISTANCE FOR SOIL
RESISTIVITY OF 100 Ω ⋅ m (A SSUMED UNIFORM)
For new installations, therefore, a public water pipe
may not be used as a means of earthing. Metallic pipe
systems of services other than water service (for
example, for flammable liquids or gases, heating
systems, etc) shall not be used as earth electrodes for
protective purposes. Bonding of the water service with
the exposed metalwork of the electrical installation (on
the consumers’ side of any insulating insert) and any
other extraneous metalwork to the installation earthing
terminal is, however, permissible and indeed necessary
in most circumstances subject to the provision of
earthing facilities that are satisfactory before these
bonding connections are made.
100 ρ
4l
log e
ohms
d
2π l
where
ρ
l
d
= resistivity of soil (Ω.m) (assumed uniform);
= length of the strip in cm; and
= width (strip) or twice the diameter
(conductors); in cm.
Care should be taken in positioning these electrodes,
especially to avoid damage by agricultural operations.
Figure 23 shows the variation of calculated earthresistance of strip or conductor electrodes with length
for a soil resistivity of 100 Ω.m. The effect of conductor
size and depth over the range normally used is very
small.
For existing installations in which a water pipe is used
as a sole earth electrode; an independent means of
earthing should be provided at the first practicable
opportunity.
14.2.5 Resistance of an Electrode Encased in Low
Resistivity Material, for Example, Conducting
Concrete
If several strip electrodes are required for connection
in parallel in order to reduce the resistance, they may
be installed in parallel lines or they may radiate from a
point. In the former case, the resistance of two strips at
a separation of 2.4 m is less than 65 percent of the
individual resistance of cither of them.
The resistance of a backfilled electrode Rb in ohms (Ω)
may be calculated from:
Rb =
14.2.4 Water Pipes
Water pipes shall not be used as consumer earth
electrodes.
1
8L
{( ρ − ρc ) [log e − 1] +
2πL
d
8L
ρc [log e − 1]}
d
where
NOTE — In urban districts and other areas where piped water
supply is available the use of water pipes for consumers’ earth
electrodes has been common in the past. Though this was
ρ
27
= the resistivity of soil, in ohm metres (Ω.m);
IS 3043 : 2018
ρc = the resistivity of the conducting material used
Table 6 Factors for Vertical Electrodes Arranged
in a Hollow Square
(Clauses 14.2.7 and 14.2.11.5)
for the backfill, in ohm metres (Ω.m);
L
= the length of rod, in metres (m);
d
=
the diameter of the rod in metres (m).
Sl
No.
14.2.6 Cable Sheaths
(1)
Where an extensive underground cable system is
available, the lead sheath and armour form a most
effective earth-electrode. In the majority of cases, the
resistance to earth of such a system is less than 1 ΩA
freshly installed jute or hessian served cable is insulated
from earth, but the insulation resistance of the jute
deteriorates according to the moisture content and
nature of the soil. However, cable sheaths arc more
commonly used to provide a metallic path to the fault
current returning to the neutral.
Factor λ
2
3
4
5
6
7
8
9
10
12
14
16
18
20
2.71
4.51
5.46
6.14
6.63
7.03
7.30
7.65
7.90
8.22
8.67
8.95
9.22
9.40
i)
ii)
iii)
iv)
v)
vi)
vii)
viii)
ix)
x)
xi)
xii)
xiii)
xiv)
14.2.7 Structural Steelwork
The resistance to earth of steel frames or reinforced
concrete buildings will vary considerably according to
the type of soil and its moisture content, and the design
of the stanchion bases. For this reason, it is essential to
measure the resistance to earth of any structural
steelwork that it is employing and at frequent intervals
thereafter.
(3)
NOTE — The number of electrodes around the square is
4 ( n −1).
foundation R r in ohms (Ω) may be estimated by
assuming that only the vertical reinforcing rods are
bonded to the building structure or to the earthing
system. It may be assumed that the rods are equally
spaced in symmetrical pattern.
On the assumption that a representative value of a
footing resistance can be obtained, the combined effect
of all similar footings Rtot in ohms (Ω), assumed to be
arranged in an approximately rectangular plan, may be
obtained from the following:
Rtot= R1 ×
Number of Electrodes (n)
Along the Side of the
Square
(2)
=
R
(1 + λα)
n
1
δ
2L
[ ρc − ρ ] log e 1 + + ρ loge
2πL
z
z
where
ρ
ρ
in which α = 2πR s
1
= the resistivity of the soil, in ohm metres
(Ω.m);
ρc = the resistivity of the concrete, in ohm metres
where
(Ω.m);
R1 = the resistance of one footing, in ohms (Ω);
L
=
the length of reinforcing rod below ground
level, in metres (m);
= the resistivity of the soil, in ohm metres
(Ωm);
λ
s
=
the spacing of footings, in metres (m);
= the thickness of the concrete between rods
and soil, in metres (m); and
n
=
the number of footings used as electrodes.
z
=
the geometric mean distance of rod cluster,
in metres (m) (see Table 7).
λ
= the factor from Table 6;
ρ
NOTE — This equation is based on the assumption that the
spacing between adjacent electrodes is such that the ratio
ρ/2πR1s is less than approximately 0.2.
14.2.8 Reinforcement of Piles
At power stations and large substations, it is often
possible to secure an effective earth-electrode by
making use of the reinforcement in concrete piles.
The earth strap should be bonded to a minimum of
four piles and all the piles between the bonds should
be bonded together. Each set of four piles should be
co nne cted to t he main e art hing-strap o f the
substation.
The larger proportion of the resistance is due to the
concrete to earth immediately around the metal work
and is dependent on its moisture content. After
construction and with the passage of time this moisture
content will approach equilibrium with that of the soil,
and will usually be drier than when first laid.
The resistance to earth of a reinforced concrete
28
IS 3043 : 2018
Table 7 Geometric Mean Distance z for Closely Spaced Reinforcing Rods in a Symmetrical Pattern
(Clause 14.2.7)
Key :
a is the radius of a reinforcing rod, in metres (m)
s is the distance between adjacent rods, in metres (m)
z is the geometric mean distance, in metres (m)
NOTE — Special care is necessary where the construction includes prestressed concrete.
14.2.9 Cathodically Protected Structures
to circumstances between bare metal in contact with
ground and metal that has been deliberately coated or
wrapped against corrosion. In the latter case, cathodic
protection is used to supplement the coating and guard
against localized corrosion due to coating flaws or
faults. Protective system current drain is proportional
to the area of bare metal in earth contact and if a normal
earthing electrode is attached to a cathodically protected
structure, the increased drain current taken by the
electrode could be completely unacceptable. This is
especially true where the system has been designed to
protect a well wrapped or coated structure.
Cathodic protection is normally applied to ferrous
structures in order to counteract electrolytic corrosion
at a metal to electrolyte interface.
The electrolyte is generally the ground in which the
structure is either wholly or partially buried and the
protection system relies upon maintaining the
metalwork at a slightly more negative potential than it
would exhibit by half cell measurements, if no
corrective action had been taken.
The application of cathodic protection varies according
29
IS 3043 : 2018
Nevertheless, there may be a necessity to connect earth
electrodes to cathodically protected structures,
especially where the coating or wrapping tends to
electrically insulate the structure from ground, for
example:
only a few which are most likely to try first in order to
achieve the required value are included.
14.2.11.1 Three rods at the vertices of an equilateral
triangle
The resistance Re in ohms (Ω) of three interconnected
rods set out at the vertices of an equilateral triangle
(see Fig. 24) of side s metres length may be calculated
from:
a)
diversion of earth fault currents from electrical
apparatus mounted on the structure;
b) diversion of stray current to ground, a problem
often met where well coated pipelines are
substantially parallel to the route of a high
voltage overhead line;
c) prevention of elevated voltages where
structures encroach into hazardous
(flammable) areas; and
d) prevention of power surges into the apparatus
providing cathodic protection, or similar
invasion of delicate low current
instrumentation circuits.
Re=
1
8L
{2[log e ( ) − 1] − 1 + 2 Ls}
3
d
where
ρ
= resistivity of the soil, in ohm metres (Ω.m);
L
= length of the rod, in metres (m);
d
= diameter of the rod, in metres (m); and
s
= length of one side of the equilateral triangle,
in metres (m).
14.2.11.2 Two strips set at right angles to each other
meeting at one corner
In addition to the guidance given in 14.3, selection of
metals for earth electrodes and determination of their
ground contact area is most important where
cathodically protected structures are involved.
The resistance RL in ohms (Ω) of two strips of equal
length set at 90° with one corner touching (see Fig. 24)
may be calculated from:
The material selected should exhibit a galvanic potential
with respect to ground as nearly equal to that exhibited
by the structure in its natural or unprotected condition.
For ferrous structures, austenitic iron (austenitic cast
nickel chromium alloy with spheroidal graphite present)
is often used. Vertically driven rods of this material are
preferred in order to minimize contact area and thus
reduce cathodic protection drain, whilst obtaining
optimum performance from the electrode. Copper
should be avoided, wherever possible, not only for its
increased drain but also for its ability to become
cathodic to the protected structure. Magnesium or zinc
electrodes have been used successfully, but are anodic
to the protected structure and thus sacrificial in action.
RL =
ρ
2π L
L
log e
1.27hd
where
ρ
= resistivity of soil, in ohm metres (Ω⋅m);
L
= total length of strip, in metres (m);
h
= depth of the burial in metres (m);
d
= diameter of the round conductor or diameter
of the equivalent cross-sectional area of the
strip in metres (m).
14.2.10 Mesh
14.2.11.3 Three strips set at 1200 meeting at the star
point all of equal length
The resistance of mesh (grid) Rm ohms (Ω) may be
calculated from:
The resistance Rs in ohms (Ω) of a star arranged strip
(see Fig. 24) may be calculated from:
R m = 0 .443
ρ
Α
+
ρ
Rs =
L
ρ
L
log e
2π L
0.767hd
where
where
ρ
= the resistivity of the soil, in ohm metres
(Ω.m);
ρ
= the resistivity of soil, in ohm metres (Ω.m);
L
= the total length of strip, in metres (m);
A
= the actual area covered by the mesh, in
square metres (m2); and
h
= the depth of the burial in metres (m); and
d
= the diameter of the round conductor or
diameter of the equivalent cross-sectional
area of the strip in metres (m).
L
= the total length of strip used in the mesh, in
metres (m).
14.2.11 Miscellaneous Electrodes
14.2.11.4 Four strips set in a cruciform
There are many configurations that can be set out, but
The resistance Rcr in ohms (Ω) of four strips set out in
30
IS 3043 : 2018
a cruciform (see Fig. 24) may be calculated from:
Rcr =
where
ρ
L
h
d
14.3 Selection of Metals for Earth-Electrodes
Although electrode material does not affect initial earth
resistance, care should be taken to select a material that
is resistant to corrosion in the type of soil in which it
will be used. Tests in a wide variety of soils have shown
that copper, whether tinned or not, is entirely
satisfactory (subject to the precautions given in this
sub clause), the average loss in weight of specimens
150 mm × 25 mm × 3 mm buried for 12 years in no
case exceed 0·2 percent per year. Corresponding
average losses for unprotected ferrous specimens (for
example, cast iron, wrought iron or mild steel) used in
the tests were as high as 2·2 percent per year.
Considerable and apparently permanent protection
appears to be given to mild steel by galvanizing, the
test showing galvanized mild steel to be little inferior
to copper with an average loss not greater than
0·5 percent per year. Only in a few cases was there any
indication in all these tests that corrosion was
accelerating and in these cases the indications were not
very significant.
ρ
L
log e
0.217
6
hd
2π L
=
=
=
=
the resistivity of soil, in ohm metres (Ω.m);
the total length of strip, in metres (m);
the depth of the burial in metres (m);
the diameter of the round conductor or
diameter of the equivalent cross-sectional
area of the strip in metres (m).
14.2.11.5 Vertical rods in a hollow square
The resistance RTOT of rods set out in a hollow square
(see Fig. 24) may be calculated from:
1 + λρ / 2π Rr s
RTOT = Rr
n
where
Rr = the resistance of one rod, in ohms (Ω);
λ = the factor in Table 6;
ρ
s
n
The possibility on damage to cables and other
underground services and structural metalwork in the
vicinity of earth-electrode due to electrolytic action
between dissimilar materials should not be overlooked
when the material for earth-electrodes is selected.
Materials compatible with other metal structures in the
= the resistivity of soil, in ohm metres (Ω m);
= the spacing of rods, in metres (m); and
= the number of rods used as electrodes
(see note of Table 6).
F IG. 24 M ISCELLANEOUS ELECTRODE CONFIGURATIONS
31
IS 3043 : 2018
vicinity should be selected or other remedial action
taken.
15 CURRENT DENSITY AT THE SURFACE OF
AN EARTH ELECTRODE
It may be essential to use materials of types other than
those mentioned earlier in special circumstances, when
cathodically protected structures such as pipelines are
encountered.
15.1 An earth electrode should be designed to have a
loading capacity adequate for the system of which it
forms a part, that is, it should be capable of dissipating
without failure the energy in the earth path at the point
at which it is installed under any condition of operation
on the system. Failure is fundamentally due to excessive
temperature rise at the surface of the electrode and is
thus a function of current density and duration as well
as electrical and thermal properties of the soil.
A modern high pressure gas pipeline, wrapped and
cathodically protected may have a galvanic potential
of –0.5 V, the accepted material of copper for an earth
electrode with a galvanic potential of –0.2 V decreases
the total galvanic voltage and increases the need for
current from the corrosion protection impressed current
system, when the earth electrode is connected to the
pipeline.
In general, soils have a negative temperature coefficient
of resistance so that sustained current loading results
in an initial decrease in electrode resistance and a
consequent rise in the earth fault current for a given
applied voltage. As soil moisture is driven away from
the soil-electrode interface, however, the resistance
increases and will ultimately become infinite if the
temperature-rise is sufficient.
An earth electrode with a galvanic potential nearer to
the protected structure has to be used to overcome the
above and be certain the pipeline is being protected.
Such a material is termed an austenitic iron and is an
austenitic cast nickel-chromium alloy, with spheroidal
graphite present.
15.2 Three conditions of operation require
consideration, that is, long-duration loading as with
normal system operation; short-time overloading as
under fault conditions in directly earthed systems, and
long-time overloading as under fault conditions in
systems protected by arc-suppression coils.
It may be necessary to earth the pipeline for one or
more of the following reasons:
a)
It should not on its own be a carrier of any
low voltage fault current,
b) It may have low voltage equipment connected
to it, for example, for the purpose of valve
operation;
c) It may have instrumentation connected to it
that require it to be earthed for this purpose
and to provide a signal reference earth as well
as for earthing requirement relative to
electrical equipment used in hazardous areas;
and
d) It may require connection to earth at points to
discharge unwanted induced currents and
voltages from other sources such as overhead
lines.
15.3 The little experimental work which has been done
on this subject by experts at the international level has
been confined to model tests with spherical electrodes
in clay or loam of low resistivity and has led to the
following conclusions:
a)
Long-duration loading due to normal
unbalance of the system will not cause failure
of earth-electrodes provided that the current
density at the electrode surface does not
exceed 40A/m2. Limitation to values below
this would generally be imposed by the
necessity to secure a low-resistance earth.
b) Time to failure on short-time overload is
inversely proportional to the specific loading,
which is given by i2, where i is the current
density at the electrode surface. For the soils
investigated, the maximum permissible current
density, i is given by:
These four points lead to a compromise between the
need to have a low earth value for instrumentation
reference purposes, which may require a lot of buried
metal, and a reasonable earth value for electrical
purposes against the corrosion protection requirement
to have a minimum of buried bare metal connected to
the pipeline, and thus drawing a corrosion protection
current that may be required by the pipeline.
i=
7.57 ×103
A/m 2
ρt
14.4 Typical installations of pipe earth electrode and
plate earth electrode are shown in Fig. 25 and Fig. 26.
where
14.5 Typical Method for Jointing of Conductors —
Methods of jointing conductors are shown from
Fig. 27A to Fig. 27 F.
ρ = resistivity of the soil (in Ω.m).
t = duration of the earth fault (in s); and
Experience indicates that this formula is appropriate
for plate electrodes.
32
IS 3043 : 2018
NOTE — After laying the earth from the earth bus to the electrode through the PVC conduits at the pit entry conduits should be sealed
with bitumen compound.
All dimensions in millimetres.
F IG. 25 TYPICAL ARRANGEMENT OF P IPE ELECTRODE
33
IS 3043 : 2018
All dimensions in millimetres.
26A Earthing with Copper Plate
26B Earthing with Galvanized Iron Plate
All dimensions in millimetres.
FIG. 26 EARTHING WITH PLATE EARTH ELECTRODE
34
IS 3043 : 2018
27A Earthing Arrangement for Motors with Push Button Station/Starter Earth Connections to Starter Looped from Earth
Connections of Motor
27B Arrangement of Double Earth Connection to Equipment (Strip to Conductor Connection)
27C Straight Joint (Strips)
27D ‘T’ Joint (Strips)
FIG. 27 TYPICAL METHODS FOR JOINTING OF CONDUCTORS — (Continued)
35
IS 3043 : 2018
27E Arrangement of Strip to Strip and Strip to Equipment
Connection
27F Conductor to Conductor Joint (Round Conductor)
F IG. 27 TYPICAL METHODS FOR JOINTING OF CONDUCTORS
to a 25 mm diameter pipe electrode is reduced from
85 percent of the total electrode potential when the top
of the electrode is at ground level to 20 and 5 percent
when it is buried 0·3 and 1·0 m respectively.
16 VOLTAGE GRADIENT AROUND EARTH
ELECTRODES
16.1 Under fault conditions, the earth electrode is raised
to a potential with respect to the general mass of the
earth that can be calculated from the prospective fault
current and the earth resistance of the electrode. This
results in the existence of voltages in the soil around
the electrode that may be injurious to telephone and
pilot cables, whose cores are substantially at earth
potential, owing to the voltage to which the sheaths of
such cables are raised; the voltage gradient at the surface
of the ground may also constitute a danger to life,
especially where cattle are concerned. The former risk
arises mainly in connection with large electrode systems
as at power stations and substations.
16.3 Earth electrodes, other than those used for the
earthing of the fence itself, should not be installed in
proximity to a metal fence, to avoid the possibility of
the fence becoming live and thus dangerous at points
remote from the substation or alternatively giving rise
to danger within the resistance area of the electrode by
introducing a good connection with the general mass
of the earth.
16.4 Calculation of Ground Surface Potentials
16.4.1 Vertical Electrodes
16.2 Danger to animals occurs principally with polemounted substations on low-voltage systems. In rural
areas, it is by no means uncommon for the earth-path
resistance to be such that faults are not cleared within
a short period and in such cases, animals, which
frequently congregate nearrm: a pole, are liable to
receive a dangerous shock. The same trouble sometimes
occurs at farms where earth electrodes are provided
for individual appliances. An effective remedy is to
earth the neutral conductor at some point on the system
inaccessible to animals rather than earthing the neutral
at the transformer itself. Alternatively, an effective
method is for pipe or rod electrodes to be buried with
their tops below the surface of the soil and connection
made to them by means of insulated leads. The
maximum voltage gradient over a span of 2 m adjacent
For vertical electrodes, the fraction E of the potential
arising on the electrode(s) which appears at a point P
on the ground surface may be estimated approximately
by the following equation :
n
E=
log
e
[vi + (vi 2 + 1)]
i =1
4L
(1 + λβ ) log e
d
where
vi = L/ ri ;
n = the number of the electrodes;
L = the buried length of an electrode, in metres
(m);
36
IS 3043 : 2018
ri
=
the distance of the point P on the ground
surface to the ith electrode, in metres (m) (r1
is the greater than the radius of an electrode);
λ
=
the grouping factor given in Table 8
L
β=
s log e
4L
d
h
=
the depth of electrodes from the ground
surface, in metres (m);
ri
=
L
=
the length of each electrode, in metres (m);
F
=
the group factor F has the following value:
the distance along the ground surface from
point P to a point vertically above the ith
electrode, in metres (m);
For two lengths, F = 0.5 + [0.078 (s/L)]-0.307
where
d =
the diameter of the electrode(s), in
metres (m);
s =
the spacing between the electrodes in
metres (m) (It is assumed that the
electrodes are evenly spaced).
For three lengths, F = 0.33 + [0.071(s/L)]-0.408
For four lengths, F = 0.25 + [0.067(s/L)]-0.451
Provided that 0.02 < (s/L) < 0.3.
D
=
the diameter of each electrode, in metres (m).
For a strip electrode, d may be obtained from:
NOTE —It is assumed that spacing between electrodes
is not less than two-thirds of the electrode length and
that electrode currents are equal.
d=
For a single electrode, it may be assumed that n = 1,
λ = 0 and E is the fraction of the electrode potential for
an equipotential at a radius r around the electrode.
w
(2)
(3)
i)
ii)
iii)
iv)
v)
vi)
vii)
viii)
ix)
2
3
4
5
6
7
8
9
10
1.00
1.66
2.15
2.54
2.87
3.15
3.39
3.61
3.81
NOTE — These equations assume that electrode depth is small
compared with its length and that electrode currents are equal.
17 CONNECTIONS TO EARTH ELECTRODES
— EARTHING
AND
PROTECTIVE
CONDUCTORS
17.0 General
17.0.1 The materials used for making connections have
to be compatible with the earth rod and the copper
earthing conductor so that galvanic corrosion is
minimized. In all cases, the connections have to be
mechanically strong.
17.0.2 For large earthing installations, such as at major
substations, it is common to make provision for the
testing of earth electrodes. This is achieved by
connecting a group of rod driven electrodes to the main
earth grid through a bolted link adjacent to the
electrodes in a sunken concrete box. Simpler
disconnecting arrangements (or none at all) may be
acceptable for small earthing installations.
16.4.2 Horizontal Electrodes
For horizontal electrodes, the fraction E of the electrode
potential, at a point P on a line perpendicular to the
line of the electrodes, may be obtained from the
following equation :
n
E=
∑ log
i =1
e
[ui + (vi 2 + 1)]
17.1 Earthing Conductors
17.1.1 Earthing conductors are protective conductors
and should be sized in the same way as other protective
conductors and shall comply with 17.2.2, but with
specified minimum cross sectional areas when buried
in the ground specified in Table 9.
L2
F log e
hd
where
n
vi =
=
=
the width of a strip electrode, in metres (m).
wherever, there is one electrode, that is n = 1, the group
factor may be assumed to be unity, that is F = 1.
Factor λ
Number of Electrodes (n)
π
where
Table 8 Factors for Vertical Parallel Electrodes
Arranged in a Line
(Clause 16.4.1)
Sl
No.
(1)
2w
the number of electrodes;
NOTES
1 Uncoated buried copper is electro-positive to uncoated buried
steel and when interconnected by a current-carrying conductor,
l
2 ( h 2 + ri 2 )
37
IS 3043 : 2018
these metals form an electrochemical cell that can cause
accelerated corrosion. Aluminium or copper clad aluminium
conductors should not be used for final connection to earth
electrode. Where a copper conductor is to be joined to
Aluminium the proper procedure for joining conductors of
Aluminium to copper should be followed. The connection of
the earthing conductor to the earth electrode or other means of
earthing should be soundly made by the use of compound filled,
encapsulated or substantial clamps of non-ferrous metal. Where
the earthing conductor is to be connected to the metal sheath
and armoured of a cable, the sheath and armour should be
bonded together and the principal connection between the cable
and the earthing conductor should be to the metal sheath and
should be plumbed. Alternatively, if a clamp is used for this
connection it should be so designed and installed as to provide
reliable connection without damage to the cable. Earthing and
bonding clamp should conform to relevant IS.
2 Whilst the connector referred to might be in a link box
underground and therefore not readily accessible, IS 732
stipulates that provision is made in an accessible portion for
disconnecting the main earthing terminal of an installation from
the means of earthing to facilitate measurement of the resistance
of the earthing arrangements.
Where the installation provides electricity supplies to
a number of customers, an independent earth electrode
should also be connected to the MET if the main supply
has a combined neutral and protective conductor.
In the case of TT and IT system, the MET should be
earthed by an independent earth electrode only.
17.2 Circuit Protective Conductors
17.2.1 Types of Protective Conductors
17.2.1.1 Protective conductors may comprise:
a) conductors in multicore cables;
b) insulated or bare conductors in a common
enclosure with live conductors;
c) fixed bare of insulated conductors;
d) metal coverings, for example, the sheaths,
screens and armouring of certain cables
(further requirements under consideration)
(see Note 1);
e) metal conduits or other metal enclosures for
conductors (further requirements under
consideration) (see Note 2); and
f) certain extraneous conductive parts.
Table 9 Minimum Cross-sectional Area of
Earthing Conductors
(Clause 17.1.1)
Protected against
corrosion
Not protected
against corrosion
Mechanically
Protected
According to
17.2.2 with a
minimum of
16 mm2 (Cu)
or (Fe)
Mechanically
Unprotected
NOTES
1 When the metallic sheath of a cable is used as a current
protective conductor, every joint in that sheath should
be made that its current-carrying capacity is not less
than that of the sheath and where non-metallic joint
boxes are used, means such as metal strip having the
same effective current-carrying capacity as the largest
cable entering the box should be provided to maintain
continuity.
When using the metal sheath or armour, attention should
also be paid to the ability of the cable glands and
connections to carry prospective earth fault-current and
it might be necessary to seek advice from the
manufacturers on this aspect. Special precautions may
be considered necessary with the metal parts of the
assembly, particularly gland plates where abrasion
resistant function for example, power coating, are used.
Metallic enclosures for cable, such as conduit, ducting
and trunking, may be used as circuit protective
conductors but where flexible conduit is used, separate
protective conductors should be included inside the
conduit to maintain the integrity of the earth path. Where
conduit and trunking are used a high standard of
workmanship in installation is essential. Joints should
be so made such that their current-carrying capacity is
not less than that of the conduit itself. Joints should
also have the same properties, as regards insulation,
mechanical strength, as those of the wiring system or
conduit of which they are part. Slackness in joints can
result in deterioration and even complete loss of
continuity; plain slip or pin-grip sockets should not be
used. In case of unscrewed conduit, the use of lug-grip
fitting is recommended, but for outdoor installation
where the conduits are subjected to corrosion, screwed
type conduits shall always be used. Painting is to be
done on all conduit systems after the assembly.
Periodical tests to verify the electrical continuity should
be undertaken.
16 mm2 (Cu)
16 mm2 (Fe)
25 mm2 (Cu)
17 mm2 (Fe)
17.1.2 The connection of an earthing conductor to an
earth electrode shall be soundly made and electrically
satisfactory. Where a clamp is used, it shall not damage
the electrode (for example, a pipe) or the earthing
conductor.
17.1.3 Main Earthing Terminals or Bars
A consumer’s electrical installation of voltage 250 V
but not exceeding 650 V supplied from TN distributor
network should have a main earthing terminal (MET)
that is connected to the protective conductor of the
source and via this to earth electrode installed in the
electricity distributor supply system. Functional
earthing conductors should be connected to MET if
required.
The function of MET is to provide a reference point
for the installation, it consists of a terminal or bar
provided for the connection of protective conductors
and conductors for functional earthing.
Although the MET is connected to Earth, it is seldom
at zero potential because of the potential difference
caused by leakage and other current flowing to earth.
38
IS 3043 : 2018
2 Electrolytic corrosion is liable to occur under damp
condition at contacts between dissimilar metals. Copper
and its alloys having high copper content are particularly
liable to cause corrosion under these condition when in
contact with aluminium alloys. When dissimilar metal
form part of an electrical circuit, the joints should be
clean and assembled free of moisture, and then
immediately treated with suitable coating or cover to
protect from moisture.
following formula is not exceeded (applicable only for
disconnection times not exceeding 5 s).
I
1
=k
S
t
where
S = cross-sectional area, in square millimetres;
I = value (ac, rms) of fault current for a fault of
negligible-impedance, which can flow
through the protective device, in amperes;
t
= operating time of the disconnecting device,
in seconds; and
NOTE — Account should be taken of the
current-limiting effect of the circuit
impedances and the limiting capability (joule
integral) of the protective device.
k = factor dependent on the material of the
protective conductor, the insulation and other
parts, and the initial and final
temperatures. Values of k for protective
conductors in various use or service for t =
1 s and 3 s respectively are given in
Table 11A to 11D.
The k factors for protective conductors of copper, steel
and aluminium are shown in Fig. 28 to Fig. 30.
17.2.1.2 The metallic covering including sheaths (bare
or insulated) of certain wiring, in particular the sheaths
of mineral-insulated cables, and certain metallic
conduits and trunking for electrical purposes (types
under consideration) may be used as a protective
conductor for the corresponding circuits, if their
electrical continuity can be achieved in such a manner
ensuring protection against deterioration and they
permit connection of other protective conductors at
predetermined tap off points. Other conduits for
electrical purposes shall not be used as a protective
conductor.
17.2.1.3 Extraneous conductive parts may be used as a
protective conductor if they satisfy the following four
requirements:
a)
their electrical continuity shall be assured
either by construction or by suitable
connections in such a way as to be protective
against mechanical, chemical or
electrochemical deterioration;
b) their conductance shall be at least equal to that
resulting from the application of 17.2.2;
c) unless compensatory measures are provided
precautions shall be taken against their
removal; and
d) they have been considered for such a use and,
if necessary, suitably adapted.
If application of the formula produces non standard
sizes, conductors of the nearest higher standard crosssectional area shall be used.
NOTES
1 It is necessary that the cross-sectional area so calculated be
compatible with the conditions imposed by fault loop
impedance.
2 Maximum permissible temperatures for joints should be taken
into account.
3 Values for mineral insulated cables are under consideration.
The use of metallic water pipes is permitted, provided
the consent of a person or body responsible for the water
system is obtained. Gas pipes shall not be used as
protective conductors.
Method of deriving the factor k
The factor k is determined from the following formula:
k=
17.2.1.4 Extraneous conductive parts shall not be used
as PEN conductors.
Qc( B + 20) θt − θ1
In 1 +
δ 20
B + θ1
where
Qc = volumetric heat capacity of conductor
material (J/°C mm3),
B = reciprocal of temperature coefficient of
resistivity at 0°C for the conductor (°C),
δ20 = electrical resistivity of conductor material at
20°C (Ω.mm),
θ1 = initial temperature of conductor (°C), and
θf = final temperature of conductor (°C).
These material constants are given in Table 10.
17.2.2 Minimum Cross-Sectional Area
17.2.2.0 The cross-sectional area of protective
conductors shall either be:
a) calculated in accordance with 17.2.2.1, or
b) selected in accordance with 17.2.2.2.
In both cases, 17.2.2.3 shall be taken into account.
NOTE —The installation should be so prepared that equipment
terminals are capable of accepting these protective conductors.
17.2.2.1 The cross-sectional area shall be so calculated
that the current density value determined by the
39
IS 3043 : 2018
Table 10 Material Constants
(Clause 17.2.2.1)
Qc ( B + 20 )
Material
B (°C)
Qc (J/°C mm3)
δ20 (Ω.mm)
(1)
(2)
(3)
(4)
(5)
234·5
228
230
202
3·45 × 10–3
2·5 × 10–3
1·45 × 10–3
3·8 × 10–3
17·241 × 10–6
28 264 × 10–6
214 × 10–6
138 × 10–6
226
148
42
78
Copper
Aluminium
Lead
Steel
FIG. 28 k F ACTORS
FOR
COPPER PROTECTIVE CONDUCTORS (see 17.2.2.1)
FIG. 29 k F ACTORS FOR STEEL PROTECTIVE CONDUCTORS
40
δ 20
IS 3043 : 2018
FIG. 30 k F ACTORS FOR ALUMINIUM P ROTECTIVE CONDUCTORS
17.2.2.2 The cross-sectional area of the protective
conductor shall be not less than the appropriate value
shown in Table 12. In this case, checking of compliance
with 17.2.2.1 is usually not necessary.
protective conductor, but joints which can be
disconnected for test purposes by use of a tool may be
provided.
17.2.3.4 Where electrical monitoring of earthcontinuity is used, the operating coils shall not be
inserted in protective conductors.
If the application of this table produces non-standard
sizes, conductors having the nearest higher standard
cross-sectional area are to be used.
17.2.3.5 Exposed conductive parts of apparatus shall
not be used to form part of the protective conductor
for other equipment except as allowed by the
preconditions in 17.2.1.2.
The values given in Table 12 are valid only if the
protective conductor is made of the same metal as the
phase conductors. If this is not so, the cross-sectional
area of the protective conductor is to be determined in
a manner which produces a conductance equivalent to
that which results from the application of Table 12
(see also 23.3.3).
18 EARTHING ARRANGEMENTS
PROTECTIVE PURPOSES
FOR
NOTE — For protective measures for various systems of
earthing see 23 and 24.
17.2.2.3 The cross-sectional area of every protective
conductor which does not form part of the supply cable
or cable enclosure shall be, in any case, not less than:
18.1 Protective Conductors Used with Overcurrent
Protective Devices
2·5 mm2, if mechanical protection is provided;
and
b) 4 mm 2 , if mechanical protection is not
provided.
a)
18.1.1 When overcurrent protective devices are used
for protection against electric shock, the incorporation
of the protective conductor in the same wiring system
as the live conductors or in their immediate proximity
is strongly recommended.
17.2.3 Preservation of Electrical Continuity of
Protective Conductors
19 EARTHING ARRANGEMENTS
FUNCTIONAL PURPOSES
17.2.3.1 Protective conductors shall be suitably
protected against mechanical and chemical
deterioration and electrodynamic forces.
FOR
19.1 General
Earthing arrangements for functional purposes shall be
provided to ensure correct operation of equipment or
to permit reliable and proper functioning of
installations. (Further requirements under
consideration).
17.2.3.2 Joints of protective conductors shall be
accessible for inspection and testing except in
compound-filled or encapsulated joints.
17.2.3.3 No switching device shall be inserted in the
41
IS 3043 : 2018
Table 11 Current Rating of Various Protective Earthing Materials
(Clauses 17.2.2.1 and 24.2)
Table 11A Bare Conductor with No Risk of Fire or Danger to any
Other Touching or Surrounding Material
Boundary Conditions: Initial Temperature. 40°C Final temperature 395°C for copper;
325°C for aluminium; 500°C for steel
Copper
Aluminium
Steel
1 s current rating in A/mm2 (k1)
Material
205
126
80
3 s current rating in A/mm2 (k3)
118
73
46
Table 11B Insulated Protective Conductors not Incorporated in Cables
or Bare Conductors Touching Other Insulated Cables
Boundary Conditions: Initial Temperature: 40°C. Final temperature: 160°C for PVC, 220°C
for butyl rubber, 250°C for XLPE/EPR
Material
Insulation
Copper
Aluminium
PVC
Butyl
Rubber
XLPE/
EPR
1 s current rating in A/mm2 (k1)
136
160
3 s current rating in A/mm2 (k3)
79
92
Steel
PVC
Butyl
Rubber
XLPE/
EPR
PVC
Butyl
Rubber
XLPE/
EPR
170
90
106
98
52
61
112
49
58
62
65
28
33
36
Table 11C Protective Conductor as a Core in Multicore Cables
Boundary Conditions
Initial Temperature
Final Temperature
PVC
70°C
160°C
Butyl Rubber
85°C
220°C
XLPE/EPR
90°C
250°C
Material
Insulation
1 s current rating in A/mm2 (k1)
3 s current rating in A/mm2 (k3)
PVC
Copper
Butyl Rubber
XLPE/EPR
PVC
115
66
134
77
143
83
76
44
Aluminium
Butyl Rubber
XLPE/EPR
89
51
94
54
Table 11D Protective Bare Conductors in Hazardous Areas where there is Risk of Fire
from Petroleum Bound Oil or Other Surrounding Material
Boundary Conditions: Initial Temperature: 40°C; Final Temperature l50°C/200°C.
Material
1 s current rating in A/mm2 (k1)
3 s current rating in A/mm2 (k3)
Copper
131/153
76/88
Aluminium
86/101
50/58
Table 12 Cross-section of Protective Conductor
(Clause 17.2.2.2)
Cross-Sectional Area of
Phase Conductors of the
Installations, S
(mm2)
Minimum Cross-Sectional
Area of the Corresponding
Protective Conductor, Sp
(mm2)
(1)
(2)
S < 16
S
16 < S < 35
16
S > 35
See 17.2.2.1
Steel
47/56
27/32
19.2 Low Noise (see 43.2.2)
20 EARTHING ARRANGEMENTS FOR
COMBINED PROTECTIVE AND FUNCTIONAL
PURPOSES
20.1 General
Where earthing for combined protective and functional
purposes is required, the requirements for protective
measures shall prevail.
42
IS 3043 : 2018
Where doubt exists regarding the effectiveness of
supplementary equipotential bonding, it shall be
confirmed that the resistance R between simultaneously
accessible exposed conductor parts and extraneous
conductor parts fulfil the following conditions
20.2 PEN Conductors
20.2.1 In TN systems, for cables in fixed installations
having a cross-sectional area not less than 10 mm2 for
copper and 16 mm2 for aluminium, a single conductor
may serve both as protective conductor and neutral
conductor, provided that the part of the installation
concerned is not protected by a residual currentoperated device.
R < 50 ohms in ac system
R < 120 ohms in dc system
where
IS = the operating current in amperes of the
protective devices.
However, the minimum cross-sectional area of a PEN
conductor may be 4 mm2, provided that the cable is of
a concentric type conforming to Indian Standards and
that duplicate continuity connections exist at all joints
and terminations in the run of the concentric conductors.
21 EQUIPOTENTIAL BONDING CONDUCTORS
21.1 Minimum Cross-sectional Areas
20.2.2 The PEN conductor shall be insulated for the
highest voltage to which it may be subjected to avoid
stray currents.
21.1.1 Equipotential
(see 17.2.2.1)
Bonding
Conductors
21.1.2 Bonding of Water Meters
NOTE — The PEN conductor need not be insulated inside
switchgear and control gear assemblies.
Bonding of water meters is not permitted (see 14.2.4).
20.2.3 If from any point of the installation the neutral
and protective functions are provided by separate
conductors, it is inadmissible to connect these
conductors to each other from that point. At the point
of separation, separate terminals or bars shall be
provided for the protective and neutral conductors. The
PEN conductor shall be connected to the terminal or
bare intended for the protective conductor.
21.2 Non-Earthed Equipotential Bonding (under
consideration)
22 TYPICAL SCHEMATIC OF EARTHING AND
PROTECTIVE CONDUCTORS
22.1 A typical schematic of earthing and protective
conductors is given in Fig. 31.
20.3 Installation and Location of Increased Shock
Risk
23 EARTH FAULT
INSTALLATIONS
PROTECTION
IN
For installation and location of increased shock risk,
additional measures may be considered necessary, these
include:
23.0 Basic Philosophy of Earth Fault Protection
23.0.1 The rules given in this clause are applicable to
installation below 1 000 V ac.
a) supplementary equipotential bonding,
b) RCD with rated residual current of 30 mA,
and
c) Protective extra-low voltage (PELV) and
separated extra-low voltage (SELV)
equipment.
23.0.2 Amongst other things, protection against shock
in case of a fault (protection against indirect contact)
is provided by automatic disconnection of supply. This
protective measure necessitates coordination of the
types of system earthing and the characteristics of the
protective devices. This clause discusses the basic
criteria for achieving this protection.
When an installation supplies number of buildings,
main equipotential bonding is essential in each building,
so that each has a reference point to which are connected
the conductor parts referred in 23.2.2.2. In order to
reduce the voltages occurring in the event of an earth
fault still further, it is sometimes necessary to install
supplementary local equipotential bonding.
23.0.3 Protection against electric shock both in normal
service (protection against direct contact) and in case
of fault (protection against indirect contact) can be
achieved by several measures. Details of achieving
protection through the choice of an appropriate
protective measure is the subject of IS 732. One of such
measures is protection by automatic disconnection of
supply. Automatic disconnection is intended to prevent
a touch voltage persisting for such time that a danger
could arise. This method necessitates co-ordination of
(a) the type of system earthing, and (b) characteristics
of protective devices. Description of the types of system
earthing permitted and the requirements for earthing
20.4 Supplementary Bonding Circuit where
Disconnection Times Cannot be Met
Where the disconnection time of IS 732 cannot be met
(typically 0.4 s and 5 s for 230 V TN supply),
supplementary bonding shall be provided as specified
below:
43
IS 3043 : 2018
arrangements and protective conductors, namely
protection against shock is the subject of this Code.
23.0.4 Protective measure by automatic disconnection
of supply following an insulation fault relies on the
association of two conditions given below:
a)
The existence of a conducting path (fault loop)
to provide for circulation of fault current (this
depends on type of system earthing); and
b) The disconnection of this current by an
appropriate device in a given time.
The determination of this time depends on various
parameters, such as probability of fault, probability of
a person touching the equipment during the fault and
the touch voltage to which a person might thereby be
subjected.
Limits of touch voltage are based on studies on the
effects of current on human body (see IS/IEC 60479).
M
P
C
EE
1
2
3
23.0.5 The study of the electrical impedance of the
human body as a function of touch voltage and
magnitude of current flow in the body as a function of
its duration likely to produce a given effect are two
components which help in establishing a relationship
between prospective touch voltage and its duration
which will not result in harmful physiological effects
for any person.
— exposed conductive parts
— incoming metallic service
— extraneous conductive parts
— earth electrode
— equipotential bonding conductor (in case of small
domestic installations, 1 takes the form of neutral
link)
— protective conductor (in duplicate)
— earthing conductor
Table 13 shows the values of disconnecting times t for
given touch voltages for two most common conditions.
23.0.6 It is necessary, therefore, to apply these results
emanating out of IS 8437 to the various earthing
systems. The disconnecting times specified for different
FIG. 31 EARTHING ARRANGEMENTS AND
PROTECTIVE C ONDUCTORS
Table 13 Disconnecting Times for Different Touch Voltages
(Clause 23.0.5)
Prospective Touch
Voltage Uc
Condition 11)
Condition 22)
Z1
I
t
Z2
I
t
(mA)
(s)
(1)
(Ω)
(2)
(3)
(4)
(Ω)
(5)
(Ω)
(6)
(Ω)
(7)
25
—
—
—
075
23
5
50
1 725
29
5
925
54
0·47
75
1 625
46
0·60
825
91
0·30
90
1 600
56
0·45
780
115
0·25
110
150
1 535
1 475
72
102
0·36
0·27
730
660
151
227
0·18
0·10
220
1 375
160
0·17
575
383
0·035
280
1 370
204
0·12
570
491
0 020
350
1 365
256
0·08
565
620
—
500
1 360
368
0·04
560
893
—
(V)
1)
Dry or moist locations, dry skin and significant floor resistance.
2)
Wet locations, wet skin and low floor resistance.
44
IS 3043 : 2018
RA × Ia < Uc
circuits in this Code follows basically the summary
given in Table 13 in addition taking into account the
likelihood of faults and likelihood of contact.
where
RA = resistance of the earthed system for exposed
conductive parts,
Ia = operating currents of the disconnecting series
device or settings of shunt relays, and
Uc = conventional voltage limit (32 V in case of
relays with time lag).
23.0.7 TN Systems
All exposed conductive parts shall be connected to the
earthed point of the lower system by protective
conductors. The protective conductors shall be earthed
near each power transformer or generator of the
installation. If other effective earth connections exist,
it is recommended that the protective conductors also
be connected to such points, wherever possible.
Earthing at additional points as evenly as possible is
desirable. It is also recommended that protective
conductors should be earthed where they enter any
buildings or premises.
23.0.9 IT Systems
The impedance of the power system earth shall be such
that on the occurrence of a single fault to exposed
conductive parts or to earth, the fault current is of low
value. Disconnection of the supply is not essential on
the occurrence of the first fault. Protective measures
must, however, prevent danger on the occurrence of
two simultaneous faults involving different live
conductors.
The characteristics of the protective devices and the
cross-sectional area of conductors shall be so chosen
that if a fault of negligible impedance occurs anywhere
between a phase conductor and a protective conductor
or exposed conductive part, automatic disconnection
of the supply will occur within the minimum possible
safe time. The time of operation would depend on the
magnitude of the contact potential. As a general rule,
65 V may be cleared within 10 s and voltages of the
order of 240 V and above shall be cleared
instantaneously.
The following condition shall be fulfilled:
RA×Id < Uc
where
RA = resistance of the earthed system for exposed
conductive parts,
Id = operating currents of the disconnecting series
device, and
Uc = conventional voltage limit.
This requirement is met if:
Zs × Ia < Uo
23.0.10 Equipotential Bonding
where
Zs = fault loop impedance,
Ia = current ensuring the automatic operation of
disconnecting device, and
Uo = conventional voltage limits.
If the conditions specified in 23.0.7 to 23.0.9 cannot
be fulfilled for automatic disconnection of supply, it is
necessary to provide local equipotential bonding
(see also 23.3.4). This applies to entire installation or
a part thereof, an item of apparatus or a location. The
protective conductors for local bonding shall also
confirm to 17.2. Where doubt exists regarding
effectiveness of supplementary equipotential bonding,
it shall be confirmed if:
NOTES
1 Zs may be calculated or measured.
2 The duration of Ia permitted depends on the prospective touch
voltage. The touch voltage is calculated from the voltage of the
system and the ratio of the impedance of the source and the
fault loop. Higher touch voltages should be cleared in shorter
times.
Z≤
If this condition cannot be fulfilled, supplementary
bonding in accordance with 23.0.10 may be necessary.
U
Ia
where
Z = impedance between simultaneously
accessible exposed conductive parts and
extraneous conductive parts, and earthing
system;
Ia = operating current of the disconnecting series
device; and
U = conventional voltage limit.
23.0.8 TT Systems
All exposed conductive parts collectively protected by
the same protective device shall be interconnected by
protective conductors with an earth electrode common
to all those parts. Where several protective devices are
used in series, this requirement applies separately to
all the exposed conductive parts protected by each
device. For compliance with the requirement of 23.0.7
(para 2), the following shall be fulfilled:
23.1 Basic Purpose of Earth Fault Protection
The occurrence of an earth fault in an installation
45
IS 3043 : 2018
creates two possible hazards. Firstly, voltages appear
between exposed conductive parts and extraneous
conductive parts, and if these parts are simultaneously
accessible, these voltages constitute a shock hazard,
this condition being known as indirect contact.
a) Safety extra low voltage;
b) The use of Class II equipment or by equivalent
insulation;
c) A non-conducting location;
d) Earth free local equipotential bonding;
e) Electrical separation; and
f) Earthed equipotential bonding and automatic
disconnection of the supply.
Secondly, the fault current that flows in the phase and
protective conductors of the circuit feeding the faulty
equipment (the earth fault may, of course, occur in the
fixed wiring of the circuit itself) may be of such a
magnitude as to cause an excessive temperature rise in
those conductors, thereby creating a fire hazard.
NOTES
1 The primary concern of this Code is (d) and (f) while other
methods of protection against indirect contact are covered in
other relevant Indian Standard / Codes of Practice.
2 Item (a) requires that the nominal voltage of the circuit
concerned does not exceed extra low Voltage that the source
has a high degree of isolation from higher voltage circuits (for
example, a Class II safety isolation transformer) and that live
parts also have a similar degree of isolation or separation from
those circuits. The most important requirement, however, is
that live parts and exposed conductive parts of a safety extra
low Voltage circuit should not be connected to earth, protective
conductors or exposed conductive parts of another circuit.
Where these general requirements are not met but the nominal
voltage still does not exceed extra low voltage, the circuit is
described as a functional extra low voltage circuit and one part
of it may be connected to earth.
3 Item (b) is generally applicable and covers the selection and
use of equipment complying with either insulation encased
Class II equipment (‘all-insulated’) or metal cased Class II
equipment. In some cases, such as factory built assemblies of
switchgear and control gear, the equivalent term used is ‘total
insulation’. Item (b) can also be achieved by the application of
suitable supplementary or reinforced insulation to equipment
on site.
Earthing of the equipment is not required; in fact, by definition
there will be no facility for earthing provided in Class II
equipment.
4 Items (c), (d) and (e) are of limited interest as they can be
applied only in special situations and used under effective
supervision. They all include a high degree of isolation from
earth.
5 In this Clause, detailed consideration is limited to earthed
equipotential bonding and automatic disconnection of the
supply.
The protective measure known as ‘earthed equipotential
bonding and automatic disconnection of the supply is
intended to give a high degree of protection against
both hazards. The choice of protective device used to
give disconnection is influenced by the type of system
of which the installation is part, because either:
a)
the earth fault loop impedance has to be low
enough to allow adequate earth fault current f
low to cause an overcurrent protective device
(for example, a fuse or circuit breaker) in the
faulty circuit to operate in a sufficiently short
time; or
b) where it is not possible to achieve a low
enough earth fault loop impedance,
disconnection may be initiated by fitting a
residual current device (RCD) of 30 mA rating
as specified in IS 732.
23.2 Earthing of Installations
Most installations are part of either a TN system or a
TT system and in both type of installation the exposed
conductive parts of all electrical equipment of an
installation should be connected by means of circuit
protective devices to the main earthing terminals. The
earth fault loop impedance should be sufficiently low
for the protective device (fuse or circuit breaker)
operate in the required time in the event of an earth
fault.
23.2.2.1 Earthed Equipotential Bonding and Automatic
Disconnection of the Supply
The two aims of this protective measure are to:
Class II equipment, whether metal enclosed or
insulation enclosed, embodied in its construction not
only basic insulation but also supplementary or
reinforced insulation, exposed metal work of such
equipment should not be considered to become live
under fault condition that is not considered to be an
exposed-conductive part.
a)
ensure that when an earth fault occurs, the
voltages appearing between exposed
conductive parts and extraneous conductive
parts in the location served by the installation
concerned are minimized; and
b) ensure rapid disconnection of the circuit in
which that earth fault occurs.
Various earthing systems are considered in 11.1
and 11.1.1
In order to meet (a), a zone is created by first connecting
all extraneous conductive parts by means of
equipotential bonding conductors to the main earthing
terminal or earth electrode(s) of the installation.
23.2.1 Protection Against Indirect Contact (Against
Electric Shock in Case of a Fault)
Protection against indirect contact is achieved by the
adoption of one of the following protective measures:
The zone is completed by the connection of all exposed
46
IS 3043 : 2018
conductive parts of the circuits in the installation and
of current-using equipment fed from those circuits to
the main earthing terminal (or installation earth
electrode) using circuit protective conductors.
bonding should be made as per IS/IEC 62305.
Where both main gas pipes and main water pipes enter
a location, a common bonding conductor may be used,
but in such cases that conductor should be continuous
or should be permanently joined (by soldering or
crimping) in order to preserve continuity. Such a
bonding conductor may be also be used in association
with other extraneous parts.
Whilst such a zone is called an equipotential zone, this
does not mean that voltages cannot exist between
conductive parts in that zone when an earth fault occurs.
The voltages referred to earlier (see 23.1) will still exist
between the exposed conductive parts of perfectly
sound equipment and between such parts and
extraneous conductive parts, but the application of
bonding minimizes these voltages in each case.
The main equipotential bonding connections to the
water and gas pipe should be made as near as
practicable to their point of entry into the premises. If
there is an insulating section or insert at that point, the
bonding connection should be made to the metallic
pipes on the consumer’s side of the section or insert
and before branch pipework.
An installation may consist of a number of zones; for
instance, when an installation supplies a number of
buildings, equipotential bonding is necessary in each
building so that each constitutes a zone having a
reference point to which the exposed conductive parts
of the circuits and current-using equipment in that
building are connected.
23.2.3 Extraneous Conductive Parts
The extraneous conductive parts that are required to
be bonded to the main earthing terminal of the
installation (or to the earth electrode of the installation)
include:
The second aim of this protective measure is met by
limiting the upper value of the earth fault loop
impedance of each circuit to a value determined by the
type and current rating of the protective device
concerned such that, on the occurrence of an earth fault
(assumed to be of negligible impedance), disconnection
will occur before the prospective touch voltage reaches
a harmful value.
a)
b)
c)
d)
e)
23.2.2.2 Protective equipotential bonding
NOTE — Connections pipes, ducting and exposed metallic parts
of building structure should be considered most carefully. In
some types of earthing systems, especially TN-C or TN-C-S
systems effectively connect extraneous conducting metalwork
to the supply system neutral and could cause continuously
circulating currents and standing voltages that might result in
electrochemical corrosion or random spark hazards in
potentially flammable atmospheres.
The protective measure of automatic disconnection in
the event of a fault to earth requires :
a)
Automatic disconnection in the event of a fault
to earth,
b) Protective earthing facilitate above, and
c) Protective equequipotentia lnding reduce
touch voltage.
23.2.4 Exposed Conductive Parts
Exposed conductive parts that are required to be
connected by means of protective conductors to the
main earthing terminal (or earth electrode) of the
installation are as follows:
Where the automatic disconnection of supply is
adopted, protective equipotential bonding is
recommended, whatever be type of supply system.
Bonding, by means of main equipotential bonding
conductors, of extraneous-conductive parts the main
earthing terminal of the installations is recommended;
these extraneous-conductor parts includes :
a)
b)
c)
d)
e)
gas pipes,
other service pipes and ducting,
risers and pipes of fire protection equipment,
exposed metallic parts of the building
structure, and
lightening conductors.
a)
All metalwork associated with wiring system
(other than current-carrying parts) including
cable sheaths and armour, conduit, ducting,
trunking, boxes and catenary wires.
b) The exposed metalwork of all Class I fixed
and portable current-using equipment. Even
where at the time of the erection of the
installation this equipment is of Class II
construction or its equivalent, because there
is a possibility that in the life of the installation
the equipment may be replaced by Class I
equipment, all fixed wiring accessories should
incorporate an earthing terminal that is
Water installation pipes,
Gas installation pipework and ducting,
Other installation pipework and ducting,
Exposed metallic structure and part of the
building structure, and
Other metallic parts such as cable trays and
cable ladder racks.
Connection to a lighting protection system to the
protective system to the protective equipotential
47
IS 3043 : 2018
c)
23.3.2 Earthing Conductors
connected to the main earthing terminal by
means of the protective conductors of the
circuits concerned.
The exposed metalwork of transformers used
in the installation other than those that are an
integral part of equipment. The secondary
windings of transformers should also be
earthed at one point of the winding, unless the
transformer is a safety isolating transformer
supplying a part of the installation where the
protective measure ‘electrical separation’ is
being used.
Copper earthing conductors, in general, need not be
protected against corrosion when they are buried in the
ground if their cross-sectional area is equal to or greater
than 25 mm2. In case of buried steel conductors,
appropriate corrosion factors based upon the summed
up corrosion indexes corresponding different
parameters connected with the material for grounding,
environmental conditions, nature of soil, etc, be applied
in determining the size of the earthing conductor,
however, the minimum size should not be less than
50 mm2. If the earthing conductor is of tape or strip,
the thickness should be adequate to withstand
mechanical damage and corrosion.
Exposed conductive parts that (because of their small
dimensions or disposition) cannot be gripped or
contacted by a major surface of the human body (that
is, a human body surface not exceeding 50 mm ×
50 mm) need not be earthed if the connection of those
parts to a protective conductor cannot readily be made
and reliably maintained. Typical examples of such parts
are screws and nameplate, cable clips and lamp caps.
Fixing screws for non-metallic accessories need not be
earthed provided there is no appreciable risk of the
screws coming into contact with live parts.
It should be remembered that plain uncoated copper is
positive to plain uncoated buried steel and when
interconnected by a current carrying conductor, these
metals will form an electrochemical cell that can cause
accelerated corrosion of steel. As a rough guide, a dc
current of 1 A leaving a buried steel structure can
remove nearly 9 kg of metal in one year.
Where such conductors are protected against corrosion
but are not mechanically protected, the minimum crosssectional area is 16 mm2 if the conductor is of copper
or coated steel (Table 9). The determination of the
cross-sectional area where the earthing conductor is
both mechanically protected and protected against
corrosion is considered in a later clause.
Other exposed conductive parts not required to be
earthed are:
a)
Overhead line insulator brackets and metal
parts connected to them if such parts are not
within arm’s reach; and
b) Short lengths of metal conduit or other metal
enclosures used give mechanical protection
equipment of Class II or equivalent
construction
Aluminium or copper clad aluminium conductors
should not be used for final underground connections
to earth electrodes. Where a copper conductor is to be
joined to aluminium, the copper should be tinned, unless
an approved conductor is used.
23.3 Protection against Excessive Temperature Rise
and Mechanical Damage
The connection of the earthing conductor to the earth
electrode or other means of earthing should be readily
accessible and soundly made by the use of soldered
joints or substantial clamps of non-ferrous material.
Where the earthing conductor is to be connected to the
metal armour and sheath of a cable, the armour should
be bonded to the metal sheath and the principal
connection between the cable and the earthing
conductor should be to the metal sheath, and should
preferably be soldered. However, if a clamp is used for
this connection the clamp should be so designed and
installed as to provide reliable connection without
damage to the cable.
23.3.1 General
The protective circuit of an installation includes the
following (see Fig. 32):
a) Circuit protective conductors;
b) Equipotential bonding conductors; and
c) Earthing conductors.
Under certain circumstances, there may also be local
equipotential bonding conductors.
The determination of cross-sectional areas of all these
conductors is the subject of 14 to 23 (see also 23.4)
and here consideration is limited to the types of
conductor that can be used with some indication of the
precautions that should be taken during erection,
particularly those concerned with mechanical and
chemical deterioration and electro-dynamic effects.
23.3.3 Protective Conductors
23.3.3.1 General
The generic term ‘protective conductor’ embraces the
specific types given in 11.1.2. In any particular case,
the function intended should be correctly identified,
because this determines which of the numerous
48
IS 3043 : 2018
conduit, the use of lug-grip fitting is recommended,
but for outdoor installations and where otherwise
subjected to atmosphere corrosion, screwed conduit
should always be used, suitably protected against
corrosion. In screwed conduit installations, the liberal
use of locknuts is recommended. Joints in all conduit
systems should be painted overall after assembly.
requirements prescribed in IS 732 is applicable. IS 732
requires that all protective conductors are suitably
protected against mechanical and chemical
deterioration and electromagnetic effect. Two methods
are given for determining the cross-sectional area
required for a protective conductor. First, the crosssectional area is related empirically to that of the
associated line conductor and is given in Table 2. In
the second method, it is calculated using equation in
accordance with 17.2.2.1.
These precautions should be adequate, but periodical
tests should be made to verify that electrical continuity
is satisfactorily maintained.
23.3.3.2 Circuit protective conductors
23.3.4 Local Equipotential Bonding (see also 23.0.10).
A circuit protective conductor may form part of the
same cable as the associated live conductors, either as
a core of that cable or the metallic sheath or armouring,
or it may be separately run insulated conductor, the
insulation being at least equivalent to that provided for
a single core non-sheathed cable of appropriate size. A
separately run circuit protective conductor having a
cross-sectional area greater than 6 mm2 or of copper
strip is not required to be insulated. All protective
conductors should, however, be protected against
physical damage and other forms of damage, for
example, welding current stray return paths. Where the
sheath of a cable incorporating an uninsulated
protective conductor having a cross-sectional area of
6 mm2 or less is removed at joints and the termination,
the conductor should be protected by insulating
sleeving.
The equipotential zone partially created by the bonding
of extraneous conductive parts to the main earthing
terminal depends for its efficacy on metal-to-metal
contact of negligible impedance. Within a particular
part of the zone where extraneous conductive parts are
simultaneously accessible with either other extraneous
conductive parts or exposed conductive parts or both,
tests may show that it is necessary to carry out local
equipotential bonding between the parts concerned in
order to obtain satisfactory low impedance.
23.3.5 Electrolytic Corrosion
Under damp conditions, electrolytic corrosion is liable
to occur at contacts between dissimilar metals. Copper
and alloys having a high copper content are particularly
liable to cause corrosion under these conditions when
in contact with aluminium based alloys.
When the metallic sheath is used every joint in that
sheath should be so made that its current carrying
capacity is not less than that of the sheath and where
non-metallic joint boxes are used, means such as a metal
strip having a resistance not greater than that of the
corresponding length of sheath of the largest cable
entering the box should be provided to maintain
continuity.
When dissimilar metals form part of an electrical circuit,
the joints should be clean and assembled free of
moisture, and then immediately sealed with a suitable
medium against the ingress of moisture.
Where damp conditions prevail, the fittings, fixing
screws and saddles used to secure aluminium based
alloy conductors, should be made of aluminium alloy
or suitably protected steel (zone coated) and all the
points of contact between them painted.
When using the metallic sheath or armour as a
protective conductor, attention should be paid to the
ability of cable glands and connections to carry
prospective earth fault currents. Particular care should
be taken to avoid problems with non-conducting
finishes.
Particular attention should be paid to pipework because
of the risk of replacement of part of the pipe system by
non-metallic pipes or joints. Metalwork that may
require bonding includes exposed metal pipes, sinks
taps, tanks, radiators, and where practicable and
accessible, structural components.
Metallic enclosures for cables, such as conduit, ducting
and trunking, may be used as circuit protective
conductors but where flexible or pliable conduit is used,
separate protective conductors should be used to
maintain the integrity of the earth path. Where conduit
is used, a high standard of workmanship in installation
is essential. Joints should be so made that their current
carrying capacity is not less than the conduit itself.
Slackness in joints can result in deterioration in and
even complete loss of continuity. Plain slip or pingrip
sockets are considered insufficient to ensure satisfactory
electrical continuity of joints. In the case of unscrewed
23.4 Cross-sectional Areas of the Conductors of an
Installation Protective Circuit
The cross-sectional areas of the conductors of the
protective circuit are influenced by the limitation placed
on earth loop impedances to ensure disconnection of
the circuit in which and earth fault occurs in the
prescribed time, that is, instantaneous disconnection
for higher control potential and disconnection with time
lag for lower voltages.
49
IS 3043 : 2018
Where a protective device concerned is a fuse,
miniature circuit breaker or other types of series overcurrent device, those disconnecting times imply that
the earth fault loop impedances should be such that the
earth fault current is considerably greater than the rated
current of the device (or of the same order as occurring
under shortcircuit conditions). Residual Current
Devices (RCDs) shall be provided to disconnect the
circuit within the same time in case of impedance or
arcing fault conditions. The device setting should be
interlinked with earth fault loop impedance, safe contact
potential and permissible time for disconnection.
measures known as automatic disconnection of supply.
Furthermore, the other protective measures do not
depend on earthing and have very limited application.
Automatic disconnection of supply is a protective
measure in which :
All the constituent conductors of the protective circuit
should therefore be of adequate cross-sectional area to
ensure that the temperatures attained by the conductors
do not exceed their prescribed limiting values.
A brief summary of requirement for automatic
disconnection of supply is given in clauses of IS 732
where automatic disconnection of supply is applied,
Class I and Class II equipment may be used.
a)
basic protection is provided by basic
insulation of live parts or by barriers or
enclosures; and
b) fault protection is provided by protective
earthing, protective equipotential bonding and
disconnection in case of a fault.
In designing the protective system of any installation,
due consideration be given to ensure that periodic
inspection, testing and maintenance can be readily and
safely undertaken.
23.5 Consumers’ Earth Connections (see 11.1.1)
The method of connection of the main earthing terminal
of an installation to earth depends on the type of system
of which that installation is part. The different systems
are described in Fig. 12 to Fig. 18.
24.1 General
In general, every circuit is provided with a means of
overcurrent protection. If the earth fault loop impedance
is low enough to cause these devices to operate within
the specified times (that is, sufficient current can flow
to earth under fault conditions), such devices may be
relied upon to give the requisite automatic
disconnection of supply. If the earth fault loop
impedance does not permit the overcurrent protective
devices to give automatic disconnection of the supply
under earth fault conditions, the first option is to reduce
that impedance. It may be permissible for this to be
achieved by the use of protective multiple earthing or
by additional earth electrodes. There are practical
limitations to both approaches.
When the source of energy is privately owned, there
should be no metallic connection with the general public
supply unless there has been consultation with the
electricity authority concerned.
It should be emphasized that an installation together
with its source of energy may not consist entirely of
one particular type of system. In such cases, each part
of that installation may be required to be treated
separately without detriment to other parts of the same
installation. By and large, the types of system
encountered fall in one or other categories shown in
Fig. 12 to Fig. 18.
24 SELECTION OF DEVICES FOR AUTOMATIC
DISCONNECTION OF SUPPLY
In case of impedance/arcing faults, series protective
devices may be ineffective to clear the faults. An
alternate approach is to be adopted for the complete
safety of the operating personnel and equipment from
the hazards that may result from earth faults. This is to
use residual current devices with appropriate settings
to clear the faults within the permissible time, based
on the probable contact potential. This method is
equally applicable where earth loop impedances cannot
be improved.
24.0 Automatic Disconnection
When an earth fault occurs within an installation,
dangerous voltage can appear between conductive parts
and if these parts are simultaneously accessible they
may constitute a shock hazard. The severity of any
shock experienced by a person at risk depends on,
among other factor, the type of current (a.c. or d.c.) the
magnitude of the voltages and the time which the earth
fault current is allowed to persist.
In TT systems, there is an additional option of the use
of fault voltage operated protective devices. Whilst
these devices will always give protection against shock
risk, provided they are correctly installed, the presence
of parallel earths from the bonding will reduce the
effectiveness of the fire risk protection they offer. These
are, therefore, more suited for isolated installations that
do not have interconnections to other installations. It
The earth fault current can also be of such magnitude
and duration as to cause an excessive temperature rise
in the conductors through which it flows, thereby
creating a fire hazard.
IS 732 includes a number of protective measures which
can be applied for protection against earth fault.
However, IS 732 only considers the protective
50
IS 3043 : 2018
should also be remembered that every socket outlet
circuit that do not have earthing facility in a household
or similar installation should be protected by a residual
current device having a rated residual operating current
not exceeding 30 mA.
necessary to ensure operation of the overcurrent device
within the permissible time of 10 s for a contact
potential of 65 V is found from the characteristic curve
of the device concerned. Application of the Ohm’s Law
then enables the corresponding earth fault loop
impedance to be calculated as provided in the formulae
given in 23.0.3 to 23.0.6.
On all other systems where equipment is supplied by
means of a socket outlet not having earthing facility or
by means of a flexible cable or cord used outside the
protective zone created by the main equipotential
bonding of the installation such equipment should be
protected by a residual current operated device having
an operating current of 30 mA.
For circuits supplying socket outlets, the corresponding
earth fault loop impedance can be found by a similar
calculation for earthed equipment. When equipment are
not earthed and connected to socket outlets without
earthing facility, disconnection should be ensured for
30 mA within 10 s and with appropriate decrements in
time for higher currents.
24.2 Use of Overcurrent Protective Devices for
Earth Fault Protection
This method requires knowledge of the total earth loop
impedance alone (rather than individual components)
and is, therefore, quick and direct in application. Its
simplicity does exclude some circuit arrangements that
could give the required protection.
Where overcurrent protective devices are used to give
automatic disconnection of supply in case of earth fault
in order to give shock risk protection, the basic
requirement is that any voltage occurring between
simultaneously accessible conductive parts during a
fault should be of such magnitude and duration as not
to cause danger. The duration will depend on the
characteristic of the overcurrent device and the earth
fault current which, in turn, depends on the total earth
fault loop impedance. The magnitude will depend on
the impedance of that part of the earth fault loop path
that lies between the simultaneously accessible parts.
While calculations give the maximum earth fault loop
or protective conductor impedance to ensure shock risk
protection under fault conditions it is also necessary to
ensure that the circuit protective earth conductor is
protected against the thermal effects of the fault current.
The earth fault loop impedance should, therefore, be
low enough to cause the protective device to operate
quickly enough to give that protection as well. This
consideration places a second limit on the maximum
earth loop impedance permissible and can be checked
by superimposing on the time current characteristic of
the overload device, the ‘adiabatic’ line having the
equation:
The basic requirement can be met if:
a)
a contact potential of 65 V is within the
tolerable limits of human body for 10 s. Hence
protective relay or device characteristic should
be such that this 65 V contact potential should
be eliminated within 10 s and higher voltages
with shorter times.
b) a voltage of 250 V can be withstood by a
human body for about 100 ms, which requires
instantaneous disconnection of such faults,
giving rise to potential rise of 250 V or more
above the ground potential.
t=
k 2 A2
I t
or A =
I2
k
NOTE — Values of k for typical protective conductor conditions
are given in 17.2.2.1 and Tables 11A to 11D.
Details of the maximum permissible earth loop
impedance for the thermal protection of cables by fuses
can also be computed. However, the time current
characteristics of a miniature circuit breaker are such
that if the loop impedance is low enough to give
automatic disconnection within safe disconnecting time
so providing shock risk protection, it will also give the
necessary thermal protection to the earth conductor
likely to be used with a breaker of that specific rating.
Figure 32 shows the relationship between the adiabatic
line and the characteristic of fuses and miniature circuit
breaker.
The maximum earth fault loop impedance
corresponding to specific ratings of fuse or miniature
circuit breaker that will meet the criteria can be
calculated on the basis of a nominal voltage to earth
(Uo) and the time current characteristics of the device
assuming worst case conditions that is, the slowest
operating time accepted by the relevant standards. Thus,
if these values are not exceeded, compliance with this
Code covering automatic disconnection in case of an
earth fault is assured.
In order that the devices will give thermal protection
to the protective conductor, operation has to be
restricted to the area to the right of point A where these
curves cross. Thus, the maximum earth fault loop
impedance for thermal protection of the cable is that
Where it is required to know the maximum earth fault
loop impedance acceptable in a circuit feeding, a fixed
appliance or set of appliances and protected by an over
current device, the minimum current that may be
51
IS 3043 : 2018
corresponding to the minimum earth fault current for
which the device gives protection. The value of this
current can be read from the curve and the
corresponding loop impedance can be calculated from:
Zs =
24.3 Earth Fault Protective Devices
Residual Current Operated Devices (RCD) is used for
individual non-earthed/earthed (with limited
application) equipment as follows:
Uo
If
Residual Current Operated Devices (RCD) — An RCD
incorporates two component items. A core balance
transformer assembly with a winding for each
recognizing the out of balance current that the fault
produces in the main conductors. This induces a current
that is used to operate the tripping mechanism of a
contact system. For operating currents of 0·5 A or more,
the output from such a transformer assembly can
operate a conventional trip coil directly. For lower
values of operating current, it is necessary to interpose
a relay device, either magnetic or solid state.
where
Zs = earth fault loop impedance,
Uo = nominal voltage to earth, and
If = earth fault current.
For a given application, the maximum permitted earth
fault loop impedance would be the lower of the two
values calculated for shock risk protection or thermal
restraint respectively.
Devices for load currents greater than 100 A usually
comprise a separate transformer assembly with a circuit
breaker or contact relay, mounted together within a
common enclosure. Devices for load currents below
100 A usually include the transformer and contact
system within the same single unit, which is then
described as a residual current operated circuit breaker
(RCB). Such an RCB should be considered a particular
type of RCB although it is the most usual form.
It will be noted that the adiabatic line crosses the
characteristic curve for a miniature circuit breaker at a
second point B. This denotes the maximum fault current
for which a breaker will give thermal protection but it
will generally be found in practice that this value is
higher than the prospective short circuit current that
occurs in the circuit involved and cannot, therefore, be
realized.
A wide choice of operating currents is available (typical
values are between 10 mA and 20 A) RCB’s are
normally non-adjustable whilst RCD’s are often
manufactured so that one of several operating currents
may be chosen. Single phase and multiphase devices
with or without integral overcurrent facilities are
available.
Where residual current breakers of 30 mA operating
current or less are being used, there is a choice between
devices that are entirely electromechanical in operation
and those that employ a solid state detector. The
electromechanical types are generally small and
compact and will operate on the power being fed to the
fault alone whereas the solid state type which tend to
be bulkier to require a power supply to ensure operation.
Where this power supply is derived from the mains, it
may be necessary to take added precaution against
failures of part of that mains supply. Devices suitable
for time grading are more likely to be of the solid state
form as are those having higher through fault capacity.
32A Fuses
As per IS 732, it is required to use electromagnetic type
voltage independent RCD of 30 mA for domestic and
similar application where unskilled persons are
involved.
A test device is incorporated to allow the operation of
the RCD to be checked. Operation of this device creates
an out of balance condition within the device. Tripping
of the RCD by means of the test device establishes the
following:
32B Miniature Current Breaker
F IG. 32 RELATIONSHIP B ETWEEN ADIABATIC LINES AND
CHARACTERISTICS
52
IS 3043 : 2018
a)
the integrity of the electrical and mechanical
elements of the tripping device; and
b) That the device is operating at approximately
the correct order of operating current.
discrimination can be obtained by grading the
sensitivities along the distribution chain.
The maximum permitted operating current depends on
the earth fault loop impedance. The product of the net
residual operating current loop impedance should not
exceed 65 V.
It should be noted that the test device does not provide
a means of checking the continuity of the earthing lead
or the earth continuity conductor, nor does it impose
any test on the earth electrode or any other part of the
earthing circuit.
It is often acceptable on commercial grounds to have
several final circuits protected by the same residual
current devices. This, however, does result in several
circuits being affected if a fault occurs on one of the
circuits so protected and the financial advantages have
to be weighed against the effects of losing more than
one circuit.
Although an RCD will operate on currents equal to or
exceeding its operating current, it should be noted that
it will only restrict the time for which a fault current
flows. It cannot restrict the magnitude of the fault
current which depends solely on the circuit conditions.
It should also be noted that different types of RCD in
different circuits may react differently to the presence
of a neutral to earth fault on the load side. Such an
earth connection together with the earthing of the supply
at the neutral point will constitute a shunt across the
neutral winding on the RCD transformer. Consequently,
a portion of the neutral load current will be shunted
away from the transformer and it may result in the
device tripping. On the other hand, such a shunt may
reduce the sensitivity of the device and prevent its
tripping even under line to earth fault conditions. In
general, therefore, care should be taken to avoid a
neutral to earth fault where RCD’s are in use, although
there are some designs being developed that will detect
and operate under such conditions. On installations with
several RCD’s, care should be taken to ensure that
neutral currents are returned via the same device that
carries the corresponding phase current and no other.
Failure to observe this point could result in devices
tripping even in the absence of a fault on the circuit
they are protecting.
24.4 Selection of Earth Fault Protective Devices
In general, residual current operated devices are
preferred and may be divided into two groups according
to their final current operating characteristics
(see Table 14).
a)
RCD’s Having Minimum Operating Currents
Greater Than 30 mA — These devices are
intended to give indirect shock risk protection
to persons in contact with earthed metal.
b) RCD’s Having Minimum Operating Current
of 30 mA and Below — These devices are
generally referred to as having ‘high
sensitivity’ and can give direct shock risk
protection to persons who may come in contact
with live conductors and earth provided that
the RCD operating times are better than those
given in IS 732. It should be noted that such
RCD’s can only be used to supplement an earth
conductor and not replace one.
Table 14 Maximum Earth Electrode Resistance
for Different Types of Circuit Breakers
(Clause 24.4)
In addition to giving protection against indirect contact
or direct contact RCD’s may also give fire risk
protection, the degree of protection being related to
the sensitivity of the device and magnitude of leakage
current. National Electric Code 2011 and IS 732
recommends use of 300/500 mA RCD for protection
against leakage current to fire in building due to leakage
current.
Type of
Breaker
RCD
An RCD should be chosen having the lowest suitable
operating current. The lower the operating current the
greater the degree of protection given, it can also
introduce possibilities of nuisance tripping and may
become unnecessarily expensive.
RCD
Operating
Current
(mA)
Maximem Earth
Electrode Resistance
(Ω
Ω)
300
166
30
1666
—
500
25 EARTHING IN POWER STATIONS AND
SUBSTATIONS
The minimum operating current will be above any
standing leakage that may be unavoidable on the
system. A further consideration arises if it is intended
to have several devices in series. It is not always
possible to introduce time grading to give
discrimination whereas a limited amount of current
25.1 General
In general earthing installations will be required at
power stations and substations for:
a)
53
The neutral points of each separate electricity
IS 3043 : 2018
system which has to be earthed at the power
station or substation;
b) Apparatus framework or cladding or other
non-current carrying metalwork associated
with each system, for example, transformer
tanks, power cable sheaths; and
c) Extraneous metalwork not associated with the
power systems, for example boundary fences,
sheaths of control or communication cables.
of lightning currents or power system fault currents.
Insulation to this level is rarely practicable.
The choice of using a common earth or separate earths
for the system of different voltages at a transforming
point affect:
a)
the probability of breakdown occurring in a
transformer between the higher and lower
voltage sides due to lighting or other surges;
and
b) the safety of consumers or their property
supplied by any low voltage system distributed
from the station against arise of potential of
the earthed neutral by a high voltage system
earth fault at the station.
For safety, the objective of earth bonding is to ensure
that, in normal or abnormal conditions, any voltage
appearing on equipment to which there is access should
be below a dangerous level. It is not practicable to
ensure that metal parts are earthed and remain near true
earth potential during the passage of earth fault currents,
particularly on high voltage systems with directly
earthed neutrals. The objective should, therefore, be to
provide effective bonding of low impedance and
adequate current-carrying capacity between parts with
which anyone may be in simultaneous contact, and to
arrange, as far as possible, that large fault currents do
not flow between such points.
The former risk is reduced by use of a common earth
system, and the latter danger only arises if the resistance
of the earth electrode system is not sufficiently low to
limit the rise of earth potential to a safe value. There is
advantage in using a common earth where the earth
electrode resistance, including the parallel resistance
of any bonded metalwork, etc, to earth is 1 Ω or less,
as is usual at power stations, large outdoor substations
or substations supplying a network of cables whose
sheaths have a low impedance to earth.
To minimize risk of damage to certain auxiliary plant,
the rise of potential of a station earthing installation
above the potential of true or remote earth should be
as low as practicable, since this potential will be applied
across protective insulation of any plant with
connections to earth external to the substation, for
example, plant with connections to pilot or telephone
cables or cable sheaths. For similar reasons, the
potential difference between earthed points in the
station should also be kept to a minimum. Where surge
protection is provided, the connection of the protective
devices to earth should be as direct as possible. The
discharge of high currents with high-frequency
components requires earth connections of low
resistance and reactance, that is, short connections with
as few changes of direction as possible.
The substation earth system rise of potential will not
be excessive if the resistance of the earth electrode
system is small compared to the total earth fault circuit
impedance. Systems of higher voltage (66 kV and
above) generally have the neutral directly earthed, since
the increase in costs of insulation that would be required
for the transformer winding would be considerable.
In rural situations, where overhead lines are used, it
may, in certain circumstances, be inadvisable to use a
common earth (see 25.2).
The requirements are, therefore, best considered
separately for substations:
a)
where low voltage is confined to auxiliary
supplies within the substation;
b) substations that provide an external low
voltage supply; and
c) power stations.
Where the neutral points of two electrically separate
electricity systems are connected to a common earth
electrode system at a site, there is a coupling of the
systems in the event of an earth fault occurring on either
system by virtue of the rise of earth potential due to the
passage of the fault current through the earth electrode
system. Similarly, if non-current carrying metalwork
is bonded to the same earth electrode as the neutral
point of the supply the metalwork will experience the
same rise of earth potential. If complete separation of
electrical systems were required, it would be essential
that the neutral points of each system and its associated
metalwork be separately earthed. If such a method were
adopted, each earthing system would require insulation
from other earthing systems to withstand the maximum
rise of earth potential occurring in any system by virtue
The use of neutral earthing switchgear in public supply
systems is avoided, where possible, since a direct earth
is simple, reliable and cheaper than a switched earth.
The circumstances in which neutral earthing switchgear
may be necessary are so broad that it is not practicable
to form general rules on type and application.
25.2 General Earthing Arrangement
A typical earthing arrangement for an outdoor
switchyard is shown in Fig. 33. A typical earthing
54
IS 3043 : 2018
NOTE — The number of electrodes and the size of the grid conductor is to be worked out as per 27.6.2.
FIG. 33 TYPICAL EARTHING G RID FOR AN OUTDOOR SUBSTATION (66 kV AND ABOVE)
arrangement for connecting the reinforcement of
foundations of substation building and switchyard RCC
masts is shown in Fig. 34.
In the case of pole mounted transformers on overhead
line systems, difficulties may arise in areas of high soil
resistivity. Here, if the pole carries also isolating
switchgear with low level operating handle, up to three
separately earthed electrode systems may be required.
That for the neutral of the low voltage system is usually
provided not nearer than one pole span away on the
low voltage line. That for the high voltage metalwork
(transformer tank, switch framework, support metal
work), consists of one earth electrode at or near the
pole. Resistances of 5Ω to 50 Ω are sometimes the
The perimeter fence may need to be earthed separately
from the main station earth electrode system
(see 25.6.1).
The tertiary winding of a power transformer should be
connected to the transformer tank by a connection of
sufficient cross-sectional area to carry the primary
short-circuit current.
55
IS 3043 : 2018
NOTES
1 Top ring should be half the size of main vertical reinforcement rod.
2 Two extreme columns should be earthed like this in each substation.
3 This is applicable to RCC masts and equipment supports in OD switchyard.
4 Inserts other than earthing pads may or may not be welded to reinforcement.
F IG. 34 E ARTHING OF FOUNDATION REINFORCEMENT (CONCRETE ENCASED EARTHING ELECTRODE)
minimum economically possible. In addition, an earth
mat should be provided, near the ground surface, in
the position taken up by a person operating the switch
handle; this mat should be connected to the switch
handle. The mat should be electrically separated from
the main electrode; this is considered to be achieved
by spacing the ¼ nearest element of that electrode at
least 1 m from the periphery of the mat and by placing
the two earthing-wires on opposite sides of the pole.
The tops of the main electrodes should be at least
225 mm and preferably 750 mm below the ground, and
the earthing wire to the main electrode of outdoor type
rubber or plastics-insulated cable up to a point 2 m
above ground level. This cable, between the bottom of
the pole and the electrode should be laid in a 50 mm
diameter earthenware duct filled solid with bitumen.
connected stator circuit with an operating voltage up
to about 32 kV, directly connected to a step-up delta/
star transformer, the higher voltage winding generally
operating at 132 kV, 275 kV or 400 kV, with the
transmission system neutral point directly earthed.
The following three methods have been used for
earthing the neutral of the generator windings:
a)
Earthing through the primary winding of a
matching transformer, with resistor connected
across the secondary winding,
b) earthing through a resistor, and
c) earthing through the primary winding of a
voltage transformer.
Method (a) — is current practice, the design being such
that the maximum sub stained earth fault current in the
generator circuit is restricted to 10 to 15 A, thus limiting
the damage at the point of fault. The neutral and earthing
connections, however, are of adequate capacity to
withstand for 3 s the earth fault current that would flow
in the event of the matching transformer terminals
flashing over during an earth fault. The resistor used
25.3 General Earthing Arrangements at Power
Stations of Public Electricity Supplies
25.3.1 Neutral Earthing of Generator Circuits
At large power stations for public electricity supply
the generation circuits generally comprise a star56
IS 3043 : 2018
power stations. Method (b) has certain disadvantages,
such as the complication in arranging for speedy
identification of the individual faulty circuit and the
possible difficulties arising from functioning of the
surge diverter.
for the arrangement is of the metallic grid-non inductive
type.
Method (b) — can be used to achieve the same degree
of fault-current limitation, by design of a suitable highcurrent resistor, but is not preferred on the grounds of
cost and its less robust construction than that of the
equipment used in method (a). It was earlier practice,
however, to individually earth each generator at power
stations by liquid earthing resistors designed to limit
the earth-fault current to about 300 A.
25.4 Equipment Earthing at Power Stations
Practice in equipment earthing at power stations is
identical to that for large substations not giving external
low voltage supplies (see 25.2). A common earth is used
for the neutral earthing of generators and power station
auxiliaries, and for all equipment framework, cladding,
power cables sheaths and extraneous metalwork not
associated with the power systems, other than the
perimeter fence (see 25.6.1).
Method (c) — is now historic, but had the advantage
that minimal damage resulted at an earth fault. If
desired, the generator could remain in circuit while
operational arrangements were made to permit its
withdrawal. However, this imposed a higher voltage
stress on the stator windings and plant on the unfaulted
phases, and the machine design usually imposed
limitations on this. The output from the secondary
winding of the voltage transformer could be arranged
to activate an alarm or trip the generator circuit as
desired. In designing the neutral and earthing
connections to the voltage transformer, the earth-fault
current used was that resulting by flashover of the
voltage transformer during an earth-fault.
25.5 Power Station and Substation Earth Electrodes
25.5.1 General
The required characteristics of earth electrode system
are:
a)
a suitably low resistance, under all variations
due to climatic conditions, for the fault
currents envisaged;
b) current carrying capability for all currents and
durations that may arise in normal operating
conditions or during fault or surge discharge
conditions, without undue increase in
resistance;
c) suitable location in the vicinity of any lighting
discharge devices such that earth connection
conductors from such devices are as short and
straight as possible to minimize surge
impedance; and
d) earth electrode installations should be durable
and of such material and design to avoid
corrosions.
Some old power stations have generators connected
directly to distribution system busbars; in general, the
neutral terminals of such generators have been earthed
via liquid neutral earthing resistors of such a value that
the maximum sustained earth fault current is of the order
of full load current of the generator. Installations of
neutral point switchboards with switching of neutral
points and earthing resistors have been abandoned in
favour of individual unswitched earthing resistors.
25.3.2 Earthing of Power Station Auxiliary Systems
There are, in common use, three methods of earthing
the neutral point in power station auxiliary systems:
For high voltage system earthing, the value of the
resistance of the earth electrode system, with any
adventitious earths due to the bonding of metalwork,
etc, in contact with earth, should be such that the rise
in potential of the electrode system above the potential
of remote earth is as low as economically possible. In
the absence of any specific restriction, attempt should
be made to restrict the rise of potential within safe value.
At some sites, the rise in earth potential will inevitably
exceed these values, and special precautions are
necessary.
a) Solid earthing;
b) Earthing through a voltage transformer (or
voltage relay) with a surge diverter (but not a
fuse) shunting the primary winding (or the
relay); and
c) Resistance earthing.
Methods (a) and (c) involve the automatic
disconnection of the individual fault circuit.
With method (b), an alarm can be arranged to be
operated from the secondary of the voltage transformer
and the scheme enables all auxiliaries to be kept in
service until it is convenient to make the auxiliary
switchboard dead.
Where the soil of a site is hostile by virtue of alkalinity
or acidity it may be necessary to embed earth electrodes
in rammed neutral soil to avoid corrosion.
Earth electrode systems can also represent some hazard
to adjacent underground services or structural steelwork
through electrolytic action between dissimilar metals
Method (a) is normally used in power stations with
smaller generating sets and method (c) used in the larger
57
IS 3043 : 2018
(see 28). Where this danger cannot be avoided by
selection of compatible metals, the adoption of cathodic
protection or other remedial action may be necessary.
The most efficient disposition of earthing conductors
required will depend on the layout of equipment and
the following may be taken as a guide:
At power stations and substations the steel inforcement
in foundations and piles can be used to provide an
effective electrode system, without necessity to provide
further buried electrodes. Where piles are used they
should be bonded by welding and connected to earth
bonding bars at least four points.
a)
Indoor Equipment — A main earth bar should
be provided and connected to the framework
of each item and to the earth-electrodes.
Except for the smallest installations, there
should be a connection to the earth electrodes
at each end of the earth bar or, if this is in the
form of a ring, at several points on the ring.
These connections may, depending on the
layout be buried cables of a size adequate for
the short-circuit current. Where the structure
of a switchboard is extensive or occupies more
than one floor, a further parallel main earth
bar˜ may be required which should be cross
connected to its companion bar at one point
at least in each section of the switchboard.
The main earth bar should be so placed that
cable sheaths can be readily connected to it.
When cables are so connected, the bonds
should be made to the cable gland on which
the lead sheath should be plumbed and the
armouring clamped. The main earth bar should
be accessible for the connection of any
detachable earthing devices provided with the
switchgear.
Branch connections from the main earth bar
should be provided to all accessory equipment,
such as control and relay panels, constructional
steelwork and fire-extinguishing equipment.
Where busbar protection is effected at
switchboards by frame leakage, two main
earth bars are required. The frame bar
interconnecting the framework of the switch
units will be connected to the true earth bar
through a current transformer and bolted links
for test purposes. The true earth bar should
be run separately from the frame earth bar in
convenient position for the connection of cable
sheaths and earthing devices. Where it is
mounted on the switch units, it should be
insulated therefrom by insulation capable of
withstanding a test voltage of 4 kV rms
alternating current for 1 min.
Where insulated cable glands are used, it is
recommended that ‘island’ insulation should
be provided to facilitate testing.
b) Outdoor Equipment (Excluding Pole Mounted
Transformers) — A main earth bar should be
provided, so disposed as to allow of the
shortest subsidiary connections to all major
equipment, such as transformers or circuit
breakers. Wherever possible, this should be
arranged to form a ring round the station. The
Where no substantial adventitious earths exist or where
they are in adequate, it is necessary to install electrodes
(see 14.1, 14.2 and 17.1.1).
All cladding or steel work at a station should be bonded
to the earthing system as should all structural steel work,
but attention is drawn to precautions against undue
reliance on the latter as an electrode.
25.5.2 Choice and Design
Where electrodes of large surface area are necessary
to provide the requisite current carrying capacity, earth
plates are recommended. These are generally of castiron, not less than 12·5 mm thick, and are usually 1·22 m
by 1·22 m. As an alternative to plates, cast iron pipes
may be installed. These are, for example, about 100 mm
in diameter and 3 m long, but are not generally as costeffective as plates for equivalent surface area.
For lower current rating requirements, driven rods are
preferred, usually, of the copper-clad steel type. They
are generally driven in groups, preferably with a spacing
of not less than their length, although this is not always
achievable. Closer spacing reduces their effectiveness.
The use of driven rods is advantageous where the deeper
strata of a site have a lower resistivity than the upper
strata but they may not be suitable if the site is stony or
has rock sub-strata.
At large substation compounds, it is usual to lay a mesh
of underground earth strips to which system neutral
terminals and the earth bonding conductors from aboveground structures are connected. In addition to
providing an approximately equipotential surface over
the substation, the earth strip mesh frequently suffices
to provide an electrode of suitable resistance and
current carrying capacity without augmentation.
25.6 Earthing Conductors for Power Stations and
Substations
25.6.1 Disposition
It is necessary to provide permanent and substantial
connections between all equipment and the earth
electrodes so as to afford a low resistance path for fault
currents both to earth and between items of equipment.
In addition, all other metal plant in or about the station
should be connected to the main station earthing system.
58
IS 3043 : 2018
main earth bar (or ring) should be connected
where required to earth electrodes. For larger
stations, the ring should be reinforced by one
or more cross-connections.
From the main earth bar, branch connections
should be taken to each item of apparatus and
where several such items lie together, a
subsidiary ring with short branches is
preferable to a number of longer individual
branches from the main bar. The aim should
be to provide a mesh system wherever this can
be contrived with reasonable economy.
The operating mechanisms for outdoor air
break switch disconnectors and earth switches
and circuit breaker control kiosks, etc, not
integral with the circuit breaker should be
connected to the main earth grid by a branch
earth connection entirely separate from that
employed for earthing the air-break switchdisconnector or earth switch base, or the circuitbreaker structure. The further contribution to
safety given by an insulated insert in the
mechanism drive is small compared with that
obtained from such a branch earth connection
and, therefore, insulated inserts are notns:
recommended in operating mechanisms of
apparatus installed in substations. While sites
covered with hard core and stone chippings will
constitute a surface layer with a relatively high
specific resistance, in the interests of safety, a
metal grid can be provided at the operating
points to give a level standing area and an earth
connection made from this grid to the operating
handle.
Where it can be proved that the current
carrying capacity of a main aluminium or steel
member or welded sections forming a
structure are at least equal to that of the
required aluminium or copper earth conductor,
the structure may form part of the connection
and there is no need to fix an earth conductor
along this section. A structure made up of
bolted sections should not be relied upon to
form an efficient earth bond between
equipment and the main earth grid, and loops
bonding across structural joints are required.
Connections to metal cladding, steel structure
and metal door frames and windows or any
other metallic panels should be made inside
buildings.
Where the earth wire of an incoming line ends
at the terminal supports and is not connected
to a point on the substation structures, a
subsidiary earth connection should be provided
between the substation earth system and the
base of the support. If the latter lies outside the
substation fence, the earth connection should
be buried where it passes under the fence and
should be kept well clear of the latter.
Earth connections to surge diverters should
be of sample cross-section and as direct as
possible; they should not pass through iron
pipes which would increase the impedance to
surges of the connection. The earth
connections of the diverters should be
interconnected with the main earthing system
since, for the effective protection of the
substation equipment, a definite connection
of low impedance between the equipment and
the diverters is essential.
25.6.2 Design
25.6.2.0 General
The term earthing grid applies only to that part of the
grid which is buried in soil. For design calculations of
the grid resistance to the soil, only the buried part of
the grid is to be taken into account. That part of the
grid which lies embedded in concrete and also
reinforcement connected to the grounding pads do
lower the combined grid resistance but this contribution
may not be taken into account while designing the
earthing grid.
25.6.2.1 Conductors installed above ground
Earthing conductors for power stations and substations
will normally be selected from copper or aluminium or
steel sections adequately rated in size to carry the
designed earth fault or three phase fault current for the
appropriate designed maximum duration without
exceeding a temperature given in Table 11A.
Compliance with this requirement will additionally
ensure satisfactory bonding without excessive voltage
difference along any conductor.
The required cross-sectional area of the earthing
conductor is determined by the choice of conductor
material and the maximum duration of the fault current.
The generally accepted duration for design purposes
are 1 s for voltages above 33 kV and 3 s for lower
voltages. However, 1 s may also be accepted for
voltages upto 33 kV where adequate fast acting earth
fault protection is provided which isolates the system
within 1 s.
25.6.2.2 Conductors buried as strip electrodes
The earthing grid consists of the vertical pipe electrodes
or plate electrodes interconnected by horizontal
conductors which serve as a strip electrode (14.2.3) in
addition to forming an earthing grid. It is recommended
that the duration of earth fault current should be taken
as 1 s for 66 kV and above voltage level substations;
and 3 s while designing earth grids for all other voltage
levels below 66 kV. However, 1 s may also be accepted
59
IS 3043 : 2018
for voltages upto 33 kV where adequate fast acting earth
fault protection is provided which isolates the system
within 1 s.
The other factors which shall be taken as the
consideration while designing the earth grid are given
below:
e)
a)
Factor of safety for the ability of the earth
conductor to carry the fault current during the
period the fault persists, without any thermal
and mechanical damage to the conductor;
b) The relative importance of the installation for
which the earthing system is being designed;
c) The likely increase in the near future in the
fault level in the area where the earth
conductor has been installed;
d) Operating time of the protective devices;
e) Corrosion of the earth conductor;
f) Factor of safety for workmanship in jointing,
etc; and
g) Maximum permissible temperature rise for the
buried part of the grid, which may be taken as
450°C for copper and steel conductors.
f)
25.6.3 Construction
25.6.3.1 General
It is essential for the safety of personnel and plant that
an earth system should remain effective throughout the
life of the plant. It is difficult in many cases to make a
check of continuity after installation. The system,
therefore, has to be robust and protected from
mechanical damage and corrosion, where necessary.
Any joints should be capable of retaining low resistance
after many passages of fault current.
25.6.2.3 Sizing
a)
The cross-section of the area of the grid
conductor shall not be less than the value
stipulated in 17.2.2.1 where the value of k is
to be taken as 80 for steel. This is based on a
reasonable assumption that 1 s and 3 s duration
could not be adequate to bake out the ground
moisture around the electrode especially as
only a part of the current would be flowing
across electrode-soil interface, for corrosion
allowance see 13.6.1.
b) Kt is a coefficient which takes into account
the effect of number n spacing D, diameter d
and depth of burial h of the grid conductors.
1
D2
1
=
+ ln
Kt
ln
2π 16hd π
3 5 7
4 6 8
.........upto ( n − 2 ) terms
c) Ks is a coefficient which is similar to K t
dependent on the mesh width and the number
of parallel conductors given by the empirical
relationship.
=
K
1
25.6.3.2 Laying conductors
Buried bare copper or steel conductors forming part of
the earthing system should be at about 600 mm deep
which, in addition to giving protection to the conductor
and connections, should ensure that it will normally be
below frost line. Aluminium should only be used for
above ground connections.
NOTE — If the indigenous soil is hostile tO copper, that is, acidic
with a pH value of less than 6 or alkaline with a pH value of
more than 10, suitable surrounding soil should be imported.
Where an adequate earthing installation is provided,
the subsidiary connections from the main earth grid to
equipment may be laid at a depth and by routes most
appropriate to site connections. For convenience in
connecting to equipment, they may be laid at a depth
of about 250 mm, and as they are, therefore, in ground
more subject to seasonal or progressive changes of
resistivity, it may be assumed that they make negligible
contribution towards reducing station earth resistance.
On the other hand, they do serve to reduce surface
gradient within the station site. Conversely where these
connections are also required to improve the earth value
of the station, the 600 mm depth is required. The above
recommendations deal mainly with stations on normal
sites. Where ground conditions restrict the installation
depth or where the soil resistivity is excessive,
additional measures may be required beyond the station
boundary to improve the overall earth value.
1
1
1
1
+
+
+
π 2h D + h 2 D 3D
1
+
+
+
.........up to n terms
h D h 2 D 3D
(All lengths in metres)
d) K 1 is an irregularity factor to allow for
nonuniformity of ground, dependent on the
K=s
number of parallel conductors in the ground
used in the mesh.
K1 = 0·65 + 0·172 × n
where n = number of parallel conductors.
Mesh potential: Mesh potential is the potential
difference in Volts from grid conductor to
ground surface at centre of mesh grid.
I
Mesh
=
E Kt K 1 ρ
L
where
I = fault current in amperes, and
L = length of buried conductor.
The duration of fault for calculation of step,
touch and mesh potential shall be the actual
breaker fault clearing time.
ln
60
IS 3043 : 2018
The earthing installation within the station will,
however, bond the station plant and restrict touch
potentials to acceptable limits.
b) Aluminium to aluminium — When possible,
joints on strip conductor should be arc welded
using either the tungsten inert-gas arc (TIC)
or metal inert gas arc (MIG) techniques. Oxyacetylene gas welding or brazing may also be
used.
Ranges of compression fittings and tools are
available for round conductors. Round
conductors can also be flattened and punched
with suitable tools to form a terminal.
Round and rectangular conductors can be
joined with bolted clamps.
Rectangular conductors can be joined or
terminated by drilling and bolting. When
making a bolted type joint, the surface of the
aluminium should be cleaned thoroughly by
wire brushing and greased or an approved
jointing compound applied immediately to
both mating surfaces. Bolts should then be
tightened and all excess grease or compound
wiped off and discarded.
To ensure adequate contact pressure and avoid
overstressing, torque spanners should be used.
The conductor manufacturer’s literature
should be consulted for further details for the
joints and procedures.
Cold pressure welding and explosive bonding
can be used for jointing rectangular conductors.
The appropriate manufacturer should be
consulted for details of these procedures.
c) Aluminium to copper — Joints between
aluminium and copper should be of the bolted
type and be installed in the vertical plane at a
minimum distance of 150 mm above ground
level.
The rating surface of the aluminium should
be cleaned thoroughly by wire brushing and
greased or an approved jointing compound
applied and the copper tinned. Grease or an
approved jointing compound should be
applied to the melting surface of the
aluminium. After bolt tightening by torque
spanner, excess grease or compound should
be wiped off and discarded, and the joint
protected from the ingress of moisture by the
application of suitable plastics compound or
irradiated polyethylene sleeve with mastic
lining. Alternatively, the joint may be
protected by a bitumastic paint.
Aluminium conductor connections to
equipment should, where possible, be in the
vertical plane. Surface preparation of the
aluminium and the making of the joint should
be as previously described. The finished joint
should be protected by a bitumastic paint.
Where bare metal conductor is buried under metal
fencing, and the fencing is independently earthed, the
conductor should be insulated by threading through nonmetallic pipe extending for at least 2 m each side of the
fence or alternatively insulated conductor may be used.
When laying stranded conductor for earthing purposes,
care should be taken to avoid bird caging of the strands.
25.6.3.3 Fixing conductors
In fixing aluminium or copper conductors to structures,
etc, insulated clips should be used to avoid drilling and
prevent electrolytic action. Galvanized clips should not
be used. Fixing should be spaced not more than 1 m
apart.
Earth conductors in trenches containing power and/or
multi-core cables should be fixed to the walls near the
top (for example, 100 mm from the top).
Copper earth strip supported from or in contact with
galvanized steel should be tinned to prevent electrolytic
action.
Sharp bends required in aluminium strip should be
formed by the use of a bending machine.
Aluminium earthing conductors will give satisfactory
performance in contact with concrete, cement, plaster
and brickwork, and may be buried in concrete or plaster,
provided it remains dry after setting. In outdoor
installations, the conductor will weather to a grey
appearance and in marine or industrial atmospheres
slight surface pitting may occur. This will not affect
performance since the sections are relatively large. The
interfaces of all ‘mechanical’ joints should be protected
with a suitable electrical joint compound, particularly
any bimetallic joints. All bimetallic joints should then
be encapsulated in a grease impregnated tape, mastic
compound or bitumastic paint, etc, to exclude moisture.
In general, aluminium should only be used above
ground and the connections to earth electrodes made
above ground with bimetallic joints. Aluminium can
be used below ground only if efficiently protected or
sheathed against contact with soil and moisture.
25.6.3.4 Jointing conductors
a)
General — All crossings of conductors in the
main earth grid should be jointed.
Compression type joints may be used for
stranded conductors. Non-conductor strip
should be drilled for a bolt having a diameter
greater than one-third of the width of the strip.
If this diameter will be exceeded, than a wider
flag should be jointed to the strip.
61
IS 3043 : 2018
the sheaths of the single-core cables at the trifurcating
box or in the case of single-core mains, the end of the
trefoil formation, the cable glands at sealing ends or plant
cable boxes being of the insulated type. The acceptable
level of the maximum sheath voltage is generally taken
as 65V with full rated current flowing in the cable, but
where the ratio of fault current to full rated current is so
high that the voltage developed across an insulated gland
is unacceptable, it is necessary to derate the permissible
voltage to some level lower than 65 V.
d) Copper to copper — The following methods
may be used:
1) Brazing using zinc-free brazing material
with a melting point of at least 600°C;
2) Bolting;
3) Riveting and sweating; and
4) Explosive welding.
e)
f)
Earthing conductor connections to equipment
should, as far as practicable, be made onto
vertical surfaces only. In the case of painted
metal, the paint should be carefully removed.
Earthing conductors should be tinned where
connected to galvanized steelwork. No
connection point should be less than 150 mm
above ground level. In any position, subject
to corrosion, the finished joint should be
protected by bitumastic paint.
Loops for portable earths — Loops of plain
aluminium or copper should be provided on
the earth conductor at each location where
portable earthing leads may be applied. The
loops should not be less than 180 mm long
and 75 mm clear of the earth conductor; they
should be at a convenient height and should
be formed separately, not by bending the earth
strip itself. Loops should be jointed to the earth
conductor using a method given in 25.6.3.4 (d).
Steel — For steel, it is recommended to use
only welded joints.
25.7.3 Single-Core Cable Mains
The choice of termination and earthing arrangements
for single-core cable mains is a matter of economics.
The possible methods of earthing are as follows:
a)
Solid Bonding — In this system, the sheath
bonding and earthing arrangements are such
that the sheaths are maintained near earth
potential throughout their length.
b) Single Point Bonding — This method is as
described in 25.7.2 for single core tails, and
is subjected to practical limitations of cable
lengths permissible.
c) Cross-Bonding — In this method, the cable
length is divided into three equal sections (or
into a multiple of three such sections) and at
each section junction, an insulating joint is
provided. At these joints, the sheath of each
cable section is bonded to the sheath of a
different phase cable of the next section
through lockable link boxes. By suitable
connection, the phasor sum of the longitudinal
sheath voltage is zero, and at the cable
terminations, the sheaths of all three cables
are bonded to earth. It is usual to provide a
three-phase star-connected set of cable
protections at each intermediate insulating
joint; these protectors are non-linear resistors
presenting low impedance to surge currents.
The cross-bonding method permits the full
rating of the cable to be maintained, but incurs
considerable cost in the provision of insulating
joints, link boxes, protectors, etc.
25.8 Miscellaneous Matters in Power Stations and
Substations
25.7 Earthing of High Voltage Cable Sheaths
25.7.1 Three-Core Cables
Modern high voltage power cables are generally
provided with a polymeric insulating over sheaths. The
sheath of solid type cables are generally directly earthed
at their terminations and joints, the cable sheaths being
bonded at joints. The sheath earth connections of
pressure type cables are generally made via a removable
link in a lockable box to permit periodic testing of the
over sheath insulation, the joints being insulated, but
the sheaths bonded through. The test requirement also
means that insulating glands should be provided at the
cable termination boxes of transformers, switchgear,
etc and at cable sealing ends or joints.
If two or more stations are adjacent on what may be
considered to be one site, the earthing systems and the
stations should be interconnected to form a single
earthing system. Where the stations actually adjoin, the
extremities of their earthing systems should be
connected together so that the whole area is enclosed
by the earthing system. Where the separation is too large
to treat as adjoining stations, an interconnecting earth
conductor of substantial cross-section should be run to
ensure that, as far as practicable, fault currents are
25.7.2 Single-Core Cable Tails
The sheaths of single-core cables have a longitudinal
induced voltage, the magnitude of which is directly
proportional to the current flowing in the core. When
both ends of a single-core cable are bonded to earth, a
current flows in the sheath and the thermal effects of
this sheath current derates the capacity of the cable core.
Where this derating is unacceptable and the value of the
standing induced voltage is acceptable, it is usual to earth
62
IS 3043 : 2018
diverted from cable sheaths and armour. This is of
particular importance where fault current flowing in
one station is provided from the adjoining station, for
example, where a switching station adjoins power or
transforming station sites so that an earth fault in the
switchgear causes current flow between the two sites
in order to reach the system neutral at the generators or
transformers. Such interconnections between sites can
include links suitably disposed to assist in testing.
26.3 Lattice Steel Structures
There will often be satisfactory earthing of lattice steel
structures, poles of metallic construction and reinforced
concrete poles through their contact with the ground.
In areas of high earth resistivity, special earthing
arrangements may be necessary; an overhead protective
conductor attached at each support and connected to
the neutral of the supply and of the line may be the
most economical solution. This conductor if positioned
above the live conductors will also provide a measure
of lightning protection.
Except where special insulation is called for, sheaths
of all main cables should be connected to the station
earth system. With multi-core cables the connection is
generally made at the termination.
26.4 Poles of Non-conducting Material
26.4.1 General
Where high earth-fault currents are to be expected, and
an appreciable rise of potential of the station system with
respect to the general body of the earth may ensure,
special care is necessary with connections other than
main cables or lines entering the station, such as water
pipes and telephone or pilot cables, water pipes should
include an insulated section; polymeric piping is often
suitable. In several cases, isolating transformers may be
necessary for telephone connections. British Telecom
provides isolation equipment at their circuit terminations
when the potential rise exceeds 430 V (650 V for high
reliability lines). Pilot cables should be provided with
insulated glands and so disposed as to minimize the
possibility of fault currents being carried by the sheaths.
Where a pole is of non-conducting material, for
example wood or glass-reinforced plastics, the pole will
act against the flow of leakage current and can be
expected to prevent danger near ground level due to
leakage across or failure of any insulator supporting a
line conductor, except where there is intervening
equipment or metalwork that is or may become live.
For the reasons given in 26.4.2 to 26.4.4, there are
advantages in not earthing the pole-top metalwork of
such poles and in not making bonding connections to it.
26.4.2 Omission of Bonding
Where insulators are attached to a pole or to nonconducting cross-arms, etc, attached to the pole,
omission of bonding of pole-top metalwork gives a
greater impulse withstand voltage, so there is less risk
of faults due to phase-to-phase flashover. To reduce
risk of fire, where wooden cross-arms are used, care
should be taken to make close, fire contact between
the cross-arm and the insulator pipe.
Where carrier-current equipment is employed, a further
earth-electrode, normally a driven rod, should be
provided at or immediately adjacent to each structure
supporting the coupling capacitors. This earth electrode
is an additional one for the high frequency equipment
and should be bonded into the main earthing system.
The structures supporting the coupling capacitors
should be earthed in the normal way.
26
EARTHING ASSOCIATED
OVERHEAD POWER LINES
26.4.3 Omission of Earthing
WITH
If pole top metalwork is not earthed, transient faults
due to birds, flying branches, etc, bridging the clearance
between line conductors and the metalwork are greatly
reduced.
26.1 Type of Support
Any consideration of whether metalwork associated
with overhead power lines should be earthed and/or
bonded has to take account of the type of support. Some
overhead lines are supported by lattice towers of
metallic construction, others by poles, which may be
of steel, wood, concrete or of fabricated construction,
for example, glass-reinforced plastics; brackets attached
to buildings are also used to support conductors.
26.4.4 Transformers, Rod-operated Switchgear and
Cable Terminations
In cases where equipment, such as transformers, rodoperated switchgear or cable terminations are mounted
on a wooden or reinforced plastics pole, the impulse
flashover value of the additional insulation provided
by the pole is impaired, and all the metal work on the
pole needs to be bonded and earthed.
26.2 Insulation Failure
Following an insulation failure, a voltage may exist
between any supporting metalwork and earth. The
public are generally protected if no metalwork within
3 m of the ground is liable to become live on failure of
insulation. If the supports are close to buildings, etc,
the particular circumstances have to be considered.
26.5 Stays
To prevent stay corrosion that would otherwise occur
due to passage of small leakage currents occurring even
in normal operation, stay insulators should be fitted in
stay wires on poles.
63
IS 3043 : 2018
No part of the stay insulator should be less than 3 m
above ground; it should be fitted as high up the stay as
possible, but the stay insulator should be so positioned
that there can be no contact below the stay insulator
between the stay wire and any phase conductor
(including a jumper connection), should either of them
break or become loose.
products from public distributor network operated at a
voltage which might be above 650V ac; fault capacities
might also be greater than those encountered in
domestic premises and great care should be exercised
in the design of all protective conductors and their
terminations.
27.1.1 So far as the consumers taking supply at 240 V
are concerned according to the provisions of the basic
statutes, it is the responsibility of the supplier to provide
earthed terminal at the premises of the consumer. In
the cases of consumers taking supply at higher voltages,
earthing scheme should be so designed as to satisfy the
basic statutory requirements and also to provide
adequate protection against ground faults.
26.6 Metal Brackets Attached to Buildings
A metal bracket attached to or adjacent to any
metalwork on or joining part of any building or structure
and supporting a phase conductor needs to be earthed
unless the conductor is both insulated and supported
by an insulator, each form of insulation being suitable
for the conditions under which it will be required to
operate in the event of failure of the other.
27.1.1.1 Earth fault loop impedance
As in the case of voltage supplies of exceeding 650 V,
low resistance paths for the return of earth fault current
in industrial and commercial power supply of 250 V
but not exceeding 650 V is necessary, and the total loop
impedance should be sufficiently low as to allow the
operator of a suitably chosen protective device, fuse,
circuit-breaker or RCD within the disconnection time
given in IS 732.
26.7 Earth Wires and Earth Connection
Any connection between metalwork and earth has to
be of low resistivity, both to provide for prompt
operation of protective equipment and to minimize
inductive interference with communications circuits in
the event of a flow of fault current. Electromagnetic
interference is reduced if the resistance of the earth
return path is small compared with its reactance. At 50
Hz, inductive interference may be caused by the use of
a high-resistivity wire (for example, steel wire) even if
it is perfectly earthed. A single low-resistivity earth wire
made of copper, aluminium etc, should be used and it
should avoid passing close to conductors or cables
belonging to other circuits. It should be protected
against mechanical damage for a distance of 3 m above
ground level.
27.1.1.2 Single-core cables
Where single-core cables are used in low voltage
installations, it is generally preferable to bond and earth
all metallic sheaths or armour at both ends of each run
(solid bonding). Induced voltages in the sheaths or
armours should be reduced to low values and the sheaths
or armours may be used as a protective conductor, in
parallel if necessary with an additional conductor.
Currents circulating in the armour or sheath reduce the
current-carrying capacity of the cables; where the
reduction is not acceptable, sheaths and armours may
be bonded at one end of the run (single-point bonding)
and a separate protective conductor is then necessary.
26.8 Lightning Protection
A lightning conductor attached to a structure and
earthed at its lower end acts to reduce the likelihood of
a lightning strike. An over-running aerial earth-wire on
overhead power line, besides forming part, of the earth
return path, also gives a degree of lightning protection.
The lower the impedance between aerial earth-wire and
earth, the better is the protection since this reduces the
possibility of a back flashover from the earthed
metalwork to line conductors on the occasion of a direct
strike to the earth wire.
27.1.2 The earthing system in the premises of
consumers at voltages above 230 V should be designed
as a PME system with separate protective conductor.
The neutral of the transformer should be connected to
be earth electrodes by duplicate connections and
adequate number of earth electrodes should be provided
with interlinking earth bus for getting an optimum value
of the earth resistance depending upon the setting of
the earth fault/earth leakage relays and also to limit the
extent of rise of potential in the case of solidly earthed
system, the ground fault current can be of the order of
symmetrical short-circuit current and hence the thermal
design of the earth bus and the earthing system should
depend upon the maximum symmetrical short circuit
current available. The duration of the earth fault current
according to the existing design practice is 3 s.
However, in case of installations where adequate
NOTE — The conductors of fundamental earthing may be
connected to the main earthing terminal (which is equipotential
bonding conductor) only if the same is recommended by original
electrical equipment manufacturer.
27 GUIDELINES ON
INDUSTRIAL
AND
INSTALLATION
EARTHING OF
COMMERCIAL
27.1 General
Many industrial installations take their electrical
64
IS 3043 : 2018
protective arrangements have been incorporated so as
to instantaneously isolate the system in the event of a
ground fault, a lesser duration can be considered for
design purposes.
electrodes are then cross verified based upon the
percentage of current which takes the earth return path.
Based upon the above philosophy, the following
guidelines for the design of an earthing system in the
HT consumers premises are issued.
27.1.3 As far as the value of the earth resistance is
concerned, the objective from the point of safety
consideration is not to attain minimum value of the earth
resistance as is sometimes understood. But the
consideration should be whether there is adequate coordination between the practically obtainable value of
the earth resistance and setting of the protective devices.
This aspect is very much relevant in the case of
installations where the value of the earth resistivity
which is to be taken for the calculations is abnormally
high. The disposition of the earth electrodes, and the
extent and size of earth grid will always depend upon
the disposition of plant electrics; the layout should be
done in such a manner as to keep the earth continuity
resistance to within the stipulated figure. The thermal
rating of the earth electrode is specified by this Code
which gives the formula for the maximum allowable
current density in an earth electrode. However, in the
case of a protective multiple earthing system where the
neutral of the supply transformer and the non-current
carrying metal parts in the system are interconnected
by the common earth grid, which is designed for the
prospective fault current, there is no reason to design
the earth electrodes assuming that total earth fault
current is dissipated through the earth electrodes. In
the case of an interconnected system, earth fault current
is returned to the neutral mostly through the
interconnected system, earth fault grid. However,
depending upon the value of the earth resistivity, a
percentage of the current may flow through the mass
of the earth as well. The current, which takes the earth
return path, enters the earth through different earth
electrodes. Hence, while designing the earth electrodes,
the thermal capability of the earth electrodes need be
verified only with reference to the portion of the current
which may take the earth return path, which depends
upon the earth resistivity. In the normal range of earth
resistivities between 10 and 1 000 m, this division of
current is found to be in between 80 percent and
20 percent for design purposes. Hence, depending upon
the disposition of the plant electrics, an optimum
number of earth electrodes are provided as anchorages
for the earth grid. The value of the earth resistance of
the grid so formed is then calculated assuming the bare
interconnected grid as a strip electrode. The value of
the earth resistance so obtained should be within
reasonable limits, otherwise brought down by adding
more electrodes. The ground fault protective device or
the phase fault protective device (in case there is no
ground fault protective device) is set to operate at the
minimum current which is obtainable under a ground
fault condition. The thermal rating of the earth
27.2 Consideration for Earthing
27.2.1 The main earthing conductor will be run in
between standard earth electrodes conforming to
specifications and distributed uniformly around the
working area. All the non-current carrying metal parts
of the equipments, switchboards, etc, will be solidly
connected to this earth grid or equipotential bonding
conductor by duplicate earth connections of adequate
size. For interconnecting switchboards protected by
HRC fuses to this earth grid, the size of interconnection
need not be more than 75 mm2 copper or its equivalent.
In laying out the earth electrodes and the earth
conductors, all efforts should be made to maintain a
uniform potential gradient in and around the work area.
The transformer neutral should be solidly connected
to this grid by duplicate earth connections, one going
directly to earth electrodes and other going to the
common earth bus. The size of the neutral earthing
conductor should in no case be less than that of the
size of the main earthing conductor.
27.2.2 The earth grid should be run at a minimum depth
of 50 cm below ground. When bare conductors are used
as earth grid, this can also be assumed to dissipate the
fault current to the mass of the earth and for calculating
the effective value of the earth resistance of this grid,
this grid can be treated as a strip electrode and the
standard formula can be applied for calculating the earth
resistance of the grid.
27.2.3 The continuity resistance of the earth return path
through the earth grid should be maintained as low as
possible and in no case greater than one ohm.
27.2.4 In the case of EHT substations, where there is
possibility of the ground potential attaining very high
values (of the order of 5 kV and above) in the event of
an earth fault, the earth grid design should be based on
the tolerable limits of the potential gradient in the
substation area, and the step and touch potential due to
fault conditions.
27.2.5 In the case of EHT substations, the earth
conductors should be bare and they should be buried
direct in ground.
27.3 The Earth Electrodes
27.3.1 The earth electrodes are provided to dissipate
the fault current in case of earth faults and to maintain
the earth resistance to a reasonable value so as to avoid
rise of potential of the earthing grid. Practice, which
has been followed until now, is to design the earth
65
IS 3043 : 2018
electrodes for the appropriate thermal withstand
capacity, assuming the total fault current to be passing
through the earth electrodes. This is true in the case of
an earthing system which is not interconnected with
neutral earthing (TT/IT system). But with the adoption
of PME system in industrial distribution where the
neutral is solidly connected to the earthing grid, the
above practice requires revision as has already been
pointed out in 27.1.3 in order to avoid redundancy and
thereby to avoid unnecessary expenditure. The amount
of current that may actually be dissipated through the
earth electrodes depends to a large extent, on the earth
resistivity of the soil. Depending upon the value of the
earth resistivity, the total fault current from the supply
system will return to neutral partially through the earth
grid and partially through the earth return path. The
percentage of current which flows directly through the
earth grid depends on the resistance of the earth return
path in relation to the earth resistivity. The standard
earth resistivity values typically vary in the range
between 10 and 1 000 ohms. In this range of variation,
it can be reasonably assumed that the fault current
division at the point of entry to the earth grid is 20 to
80 percent. For verification of the fault dissipating
capacity of earth electrodes, only the portion of the fault
current which is diverted to the earth electrode need be
taken and under these conditions the maximum
allowable current density as stipulated in this code
should not be exceeded.
calculations is taken as the arithmetic mean of a number
of measured values in the area under consideration. The
figure so obtained seldom projects a realistic value. A
more scientific approach is to measure the earth
resistivity in different radial directions from a central
point which may be taken as the proposed load centre.
With the values so obtained, a polar curve is drawn.
The polar curve is converted to an equivalent circle
(see 40.6). The radius of the circle is taken to be the
average value of the earth resistivity figure which is to
be applied in design calculations. Necessary allowance
should, of course, be given for factors such as variations
in climatic conditions, treatment of soil, etc.
27.5 Design of Earth Bus
27.5.1 Design of earth bus is based upon the general
guidelines given in 14 to 23. The size of the main earth
grid will be decided on the basis of line to ground fault
current assumed to be symmetrical short-circuit current
in the system. This assumption is fairly reasonable in
the case of a solidly earthed system where the ratio
between XO/XI is limited to less than 3 and the ohmic
value of the earth return path to the supply neutral is
reasonably low. The minimum fault level existing at
the supply point will be assumed to be 13·1 kA or the
actual fault current whichever is greater for premises
at voltages above 1 kV.
27.5.2 Bare copper, PVC covered aluminium or GI
subject to relevant restrictions based on the location and
nature of installation may be used as earthing to
conductors. The size of the earthing conductors will be
calculated according to guidelines given in the Code.
The time duration of the fault current as recommended
is 3 s. According to standards developed in this regard,
the size of the earthing conductors will be based upon
current densities as given in 15. A corrosion factor of
5 percent of unit drop in the value of corrosion index up
to –10 is recommended for steel/GI earthing conductors
while designing an earthing scheme, situations of
corrosion index of below –10 should not be allowed.
27.3.2 The number of earth electrodes required for a
particular installation will be basically decided by the
optimum value of the earth resistance which is required
to make the protective system operation. Hence, the
optimum value of the earth resistance depends upon
the reasonable potential rise and setting of the earth
fault isolating devices or the series, protective devices
in case where there is no ground fault detecting devices.
The main criterion is that the value of the earth return
resistance should not be so high as not to produce the
required ground fault current for actuating the
protective devices within the stipulated time. Or in other
words, the optimum value of the earth resistance is
closely related to setting of the earth fault protective
devices used in the system. For a small installation, as
a general rule, in the event of a direct earth fault, the
earth fault current produced should not be less than
five times the highest rating of the maximum protective
fuses or the setting of the earth fault relay if such a
device is provided.
27.5.3 In the case of systems where standard protective
arrangements have been provided for isolating the
ground faults instantaneously, due consideration can
be given to this aspect in deciding upon the size of the
earthing conductor by giving due allowance to lower
duration of the ground fault currents.
27.6 Correlation between Grounding and Earth
Fault Protection
27.6.1 The phase fault protective device normally used
in systems operating at 415 V afford reasonable
protection against arcing ground faults. The ground
fault current depends upon the impedance to zero
sequence current flows and depends to a large extent
on the grounding network and the earth resistivity. The
27.4 Determination of Earth Resistivity
As has already been pointed out, the value of the earth
resistivity plays an important role in the design of the
earth electrodes. In the conventional method, the earth
resistivity which is to be applied in the design
66
IS 3043 : 2018
pickup value of the ground fault relays or the value of
the phase fault protective device should be coordinated
for the required protection for the system. In case the
impedance of the earth return path for ground fault
current cannot be regulated so as to produce adequate
fault current for operating the phase fault protective
devices like fuses, such circuits should be protected by
separate ground fault protective devices. Hence, the
necessity of separate ground fault protection depends
on the grounding network and its effective impedance
and earth grid design is closely related to the
effectiveness of the phase fault protective device in
clearing a ground fault in place where separate ground
fault protective devices are not provided.
d) Arcing ground faults which are not
promptly detected and cleared can be
extremely destructive. A relatively small
investment can provide very valuable
protections.
27.8 Much of the present emphasis on ground fault
protection centres around or circuits below 550 V.
Protective devices have usually fuse switches of circuit
breakers with integrally mounted phase tripping
devices. These protective elements are termed as
overload or fault overcurrent devices because they carry
the current in each phase and clear the circuit only when
the current reaches a magnitude greater than full load
current. To accommodate inrush currents such as motor
starting or transformer magnetising inrush, phase over
current devices are designed with inverse
characteristics, which are rather slow at overcurrent
values upto about 5 times rating. For example, a 1 600
A circuit breaker with conventional phase protection
will clear a 3 200 A fault in about 100 s. Although it
can be adjusted in the range of 30 to 200 s, at this fault
value. A 1 600 A fuse may require 10 min or more to
clear the same 3 200 A fault. These low values of fault
currents are associated predominantly with fault to
ground and have generally received little attention in
the design of earthing systems, until the occurrence of
many serious electric failures in recent years. In
contrast, on grounded systems of 3.3 kV and above, it
has been a standard practice to apply some form of
ground fault protection.
27.7 Grounding and Ground Fault Protection
27.7.1 In recent years, there has been an increasing
interest in the use of ground fault protection in industrial
distribution circuits. This interest has been brought
about by a disturbing number of electric failures. Hence
it is worthwhile to explore the need for better ground
fault protection and to examine the grounding practices
in the light of the required protection.
27.7.2 Distribution circuits which are solidly grounded
or grounded through low impedances require fast
clearing of ground faults. This involves high sensitivity
in detecting low ground fault currents as well as the
co-ordination between main and feeder circuit
protective devices. Fault clearing must be extremely
fast where arcing is present.
27.9 The action initiated by ground fault sensing
devices will vary depending upon the installation. In
some cases, such as services to dwelling, it may be
necessary to immediately disconnect the faulted circuit
to prevent loss of life and property. However, the
opening of some circuits in critical applications may
in itself, endanger life or property. Therefore, each
particular application should be studied carefully before
selecting the action to be initiated by the ground fault
protective devices.
27.7.3 The appeal of effective ground fault protection
is based on the following:
a)
The majority of electric faults involve ground.
Ungrounded systems are also subject to
ground faults and require careful attention to
ground fault detection and ground fault
protections.
b) The ground fault protective sensitivity can be
relatively independent of continuous load
current values and thereby have lower pick
up settings than phase protective devices.
c) Ground fault currents are not transferred
through system, in the case of power
transformers which are connected delta-star,
delta-delta. The ground fault protection for
each system voltage level should be
independent of the protection at other voltage
levels. This permits much faster relaying than
can be afforded by phase protective device
which require co-ordinate using pick up values
and time delays which extend from the load
to the service generators, often resulting in
considerable time delay at some parts in the
system.
27.10 Protection against Arcing Ground Faults and
Earth Leakage
27.10.1 Necessity of arcing ground fault protection
especially for 415 V installations is not very well
understood and protective schemes suggested for
normal industrial installations never give much
importance to this aspect. It is also seen that the fact
that a series protective device like breaker or a fuse
does not offer protection against an earth fault or arcing
ground fault in a 415 V system, is very often forgotten.
In the case of such installations, the avoidance of arcing
ground faults is important from the point of view of
personal safely and equipment damage.
67
IS 3043 : 2018
28 UNEARTHED GENERATING
(RATINGS BELOW 10 kW)
automatic disconnection of supply is adopted as follows:
SETS
a)
One pole of a single phase generator should
be connected to the installation main earthing
terminal.
b) The main earthing terminal should be
connected to an earth electrode (see Fig. 36)
c) The installation should conform to standards
with all exposed-conductive parts and all
extraneous-conductive-parts connected to the
main earthing terminal.
d) The installation should be protected by RCDs.
28.1 General
Small single-phase generators are run as floating
systems, that iswithout the winding connected to the
frame or to earth, see Fig. 35; the generator frame and
enclosure should be bonded to all exposed conductive
parts of the load equipment, using a correctly terminated
protective conductor in the connecting cable.
The earth electrode should have a resistance to earth
not exceeding 200 Ω.
The RCD will not provide protection for faults on the
generator side of the RCD, and consequently
precautions should be taken.
KEY
1 — Unearthed Generator
2 — Plug and Socket
3 — Appliance
NOTES
1 Low-voltage, single phase generating sets are generally
mobile or transportable machines ranging in size from
0.2 kW to 10 kW.
2 Winding connection are normally brought out to a socketoutlet in which the third or protective conductor is
connected to the generator enclosure.
KEY
1 — Unearthed Generator
2 — Electrical Installation
FIG. 35 SMALL LOW VOLTAGE SINGLE PHASE
GENERATOR RUN AS A FLOATING SYSTEM
3 — Isolator
4 — Main Earth Terminal
F IG. 36 S MALL L OW VOLTAGE G ENERATOR SUPPLYING
A FIXED I NSTALLATION
Cables, plugs, socket-outlets and cable couplers should
be suitable for their environmental exposure. Cables
should be a flexible type which includes a metallic braid
or screen suitable for use as a protective conductor.
28.3 Unearthed Generators Supplying a Mobile or
Transportable Unit
Where an unearthed generator is to supply a mobile
installation it is recommended that the protective
measure automatic disconnection of supply be adopted
as follows (see Fig. 37):
If a cable without a metallic screen is used, it should
be flexible with an extruded over sheath, capable of
high abrasion resistance and should contain a separate
protective conductor. Cables, plugs , socket-outlets
should be inspected frequently and if defective should
be replaced, not repaired; equipment and cables that
are in good condition are vital for the continued safety
of an unearthed system and form the first line of
protection against the risk of shock.
a)
28.2 Unearthed Generators (Rating Below 10 kW)
Supplying a Fixed Installation
One pole of a single phase generator should
be connected to the installation main earthing
terminal.
b) The installation should conform to standards
with all exposed-conductive parts and all
extraneous-conductive-parts connected to the
main earthing terminal.
c) The installation should be protected by RCDs.
d) If the unit supplies equipment or socket outlets
outside the unit these circuits should be
protected by RCDs with a rated residual
operating current not exceeding 30 mA and
an operating time not exceeding 40 ms at a
residual current of 5 times rated current I.
Where an unearthed generator is to supply a fixed
installation (see Fig. 36) it is recommended that
If practicable, an earth electrode should be connected
to the main earthing terminal of the unit with a resistance
All cables should be as short as practicable and supply
compactly located loads, since experience has shown
that a compact installation is less likely to suffer
insulation damage, causing earth faults, than an
extensive one.
It should be noted that RCDs will not operate on a first
fault and only on particular second faults.
68
IS 3043 : 2018
the connection to the general mass of earth from the low
voltage energy source has to be consistent with the earth
fault protection provided and shall be as low as possible.
to earth sufficiently low to operate the RCDs. The RCD
will not provide protection for faults on the generator
side of the RCD, and consequently precautions should
be taken.
29.2.2 Single Low Voltage Generator Earthing
(Synchronous Machines)
29.2.2.1 Generator operating in isolation (from the
mains or other supplies)
In this basic arrangement, the generator neutral point
should be connected to the neutral of the low voltage
switchgear which is itself connected through a bolted
link (for test purposes) to an earthing conductor and
the independent earth electrode.
KEY
1 — Unearthed Generator
2 — Mobile Unit
3 — Isolator
29.2.2.2 Standby generator (without paralleling
facility)
F IG. 37 S MALL U NEARTHED GENERATOR SUPPLYING A
MOBILE OR TRANSPORTABLE UNIT
In addition to the earthing requirements stated for a set
operating in isolation from other supplies, special
attention needs to be given to the change-over
arrangement for standby set, which has to ensure that
there can be no inadvertent parallel connection
(see Fig. 38).
29 EARTHING IN STANDBY GENERATING
PLANTS (INCLUDING PORTABLE AND
MOBILE GENERATORS)
29.1 General
In general four-pole changeover switching between the
mains and standby, supplies should be used to provide
isolation of the generator and electricity board neutral
earths. However, in the case of a protective multiple
earthing (PME) supply, three-or four-pole switching
may be used.
The earthing of standby and other private generating
plant is necessary to protect against indirect contact
that may result in electric shock. The objective is to
create a zone in which voltage between exposed
conductive parts and extraneous conductive parts are
minimized in the event of an earth fault.
29.2.2.3 Standby generator (capable of parallel
operation with incoming mains supply)
In this clause the requirement is met by connecting the
generating set frame(s), metallic cable sheaths and
armouring, and all exposed conductive parts to an
earthing conductor, and by connecting the system to
earth (normally at one point only).
Electricity boards will not generally permit continuous
parallel operation of a synchronous machine with the
low voltage mains supply, unless there are no other
consumers on the network. However, short-term parallel
operation for no-break load transfer or testing may be
permitted. Also, if a synchronous machine output is
rectified and connected through mains modulated static
inverter continuous parallel operation will usually be
permitted. In the latter case, the generator neutral
terminal should be connected to the independent earth
electrode and to any electricity board earth.
Except in some special applications, there is, in every
case, need for an independent earth electrode for energy
source earthing at the premises where the generator is
located. (Any suppliers’ protective earth terminal at the
premises should also be connected to the independent
earth electrode).
There are many variations in system design and for any
particular application, the precise method of energy
source earthing is subject to the recommendations of
the machine manufacturers, the system parameters and,
where mains supplies are also involved, the agreement
of the concerned supply authority.
For short-term parallel operation, giving no-break load
transfer, the alternative energy source earthing
arrangements, which may be used, are as described
in 28.2.3.1, except that only one generating set is involved.
29.2.3 Multiple Low Voltage Generator Earthing
(Synchronous Machines)
It may, however, be noted that the guidance included
in this clause, applies to stock protection as well as
protection of equipment.
29.2.3.1 Generator operating in isolation from other
supplies
29.2 Low Voltage (Up to 1 000 V) Generators
When low voltage generating sets are operated in
parallel, the energy source earthing method is
influenced by the magnitude of the circulating currents,
29.2.1 Earth Electrodes
The overall resistance to earth of the electrodes forming
69
IS 3043 : 2018
NOTES
1 Cable sheath earth of provided/ shown
2 PNE link of provided/shown - - 3 Changeover switch could be 3-pole with linked neutral.
FIG. 38 SINGLE LOW VOLTAGE STANDBY GENERATOR (W ITHOUT PARELLELING FACILITY )
particularly third harmonic, which can arise when
generators are connected as four-wire machines. If the
magnitude of the circulating current due to the nature
of the load or the design of the generators is excessive
when the neutrals are connected, then a neutral earthing
transformer or star-point earthing switches are required.
neutral earth connection at all times and under
all possible operating conditions.
29.2.3.2 Standby generators (without mains paralleling
facility)
The alternative neutral earthing arrangements for
standby generators are as set out in 29.2.3.1 for
generators operated in isolation from an electricity
board supply. The earthing arrangements are shown in
the following drawings:
Hence, three alternative neutral earthing arrangements
are possible for parallel operation as follows:
a)
All generator neutrals connected — With this
arrangement, the neutral busbar in the main
low voltage switchgear is connected through
a bolted link to an earthing conductor and
independent earth electrode.
b) Neutral earthing transformer — By providing
a neutral earthing transformer solidly
connected to the busbars, the system neutral
can remain earthed at all times whilst any
number of generators can be connected to the
busbars as three-wire machines.
c) Generator star point switching — When this
arrangement is adopted, it is necessary before
the first generator is started for its star-point/
neutral earthing switch to be closed. When
subsequent sets are started, their star-point
earthing switches remain open. This avoids
the circulating current problem, but it is
essential that electrical and mechanical
interlocks on the starpoint/earth switches
ensure the integrity of the energy source
a) All generator neutrals connected (see Fig. 39);
b) Neutral earthing transformer (see Fig. 40); and
c) Alternator star-point switching (see Fig. 41).
For standby generators with no mains paralleling
facility, the changeover arrangement has to prevent
inadvertent connection of the generator outputs and
electricity board supply.
In general, four-pole changeover switching between the
electricity board supply and the standby supply should
be used to provide isolation of the neutral earths.
However, in the case of a protective multiple earthing
(PME) electricity board supply, three-or four-pole
switching may be used.
29.2.3.3 Standby generators (capable of parallel
operation with the incoming mains supply)
The conditions for which parallel operation of multiple
generating set installations with the mains supply may
be permitted by the electricity board are the same as
70
IS 3043 : 2018
NOTES
1 Cable sheath earth of provided/shown
2 PNE link of provided/shown - - - 3 Changeover switch could be 3-pole with linked neutral.
FIG. 39 LOW VOLTAGE STANDBY GENERATORS WITH NEUTRALS C ONNECTED
b) Three-phase machines should have their
windings connected in star, with the star
connection made available and connected to
earth.
apply for single generators (see 29.2.2.3).
The possible alternative energy source earthing
arrangements are as listed in 29.2.3.2.
29.2.4 Single and Multiple Generator Earthing
(Synchronous Machines)
In all cases, the exposed metalwork of the generator
should be adequately connected to the earth terminal,
preferably with a bolted connection.
The parallel operation of synchronous machines is
generally permitted; such machines are normally
provided where the prime mover is driven by wind,
water or biochemical plant, but may be provided with
any prime mover. Any neutral point of such machine
windings should be earthed, but the machine framework
and any other extraneous metalwork should be
connected to the electricity board earth terminal, if
provided.
The earth electrode should have a minimum crosssection area if it is not protected against corrosion of
25 mm2 for copper and 50 mm2 for steel. Whilst there
is no minimum value of earth electrode resistance, it
should be as low as possible. The upper limit should
not exceed the value required for the protective devices
to operate and disconnect the load in a time not
exceeding the safe value.
29.2.5 Small Portable Low Voltage Generators upto
5 kVA in Rating
NOTE — The selection of devices for the automatic
disconnection of supply is covered in 24 and 25.
Where portable generators are used to provide a supply
and earthing is considered as a means of protection
against electric shock, they are required to be connected
as follows:
For portable generators, residual current devices having
an operating time of 40 ms or less at a residual current
of 250 mA are recommended to a means of providing
additional protection against the effect of electric shock.
However, it is important to test such devices regularly,
particularly when the greater is used in a hostile
environment. The method of connecting a rod used on
the output of a portable generator is shown in Fig. 42.
a)
Single-phase machines should have either a
centre tap on the winding connected to earth
or, if not compatible with the system, one end
connected to earth and designated the neutral.
The Centre tap method reduces the effective
line-earth voltage and is particularly used
where the generator is to feed 110 V portable
tools; and
29.2.6 Mobile Generators
Where a supply is taken from a mobile generator, the
following recommendations, additional to those given
in 29.2.5 shall apply:
71
IS 3043 : 2018
NOTES
1 Cable sheath earth of provided/shown
2 PNE link of provided/shown - - - 3 If a bus section switch is installed a neutral earthing transformer will be required on each section of busbar.
FIG. 40 LOW VOLTAGE STANDBY GENERATORS WITH NEUTRAL EARTHING TRANSFORMERS
a)
The generator neutral should be connected to
the vehicle chassis;
b) The earth terminal at each outlet on the
generator vehicle should be connected
separately to the alternator neutral where the
latter is bonded to the vehicle chassis; and
c) Where an electricity board protective earth
terminal or exposed structural metalwork is
present, it should be connected to the earthing
conductor on the mobile generator.
the earth fault current to the same order of magnitude
as the machine’s full load current. In general, however
earthing via resistors is not necessary for single
generators of 1 MW or less in rating.
29.3.2 Single High Voltage Generator Earthing
(Synchronous Machines with Star Connected
Alternators)
29.3.2.1 Generator operating in isolation (from mains
or other suppliers)
The star-point of the generator should be connected
(via a resistor, if necessary) and through a bolted link
for test purposes to an earthing conductor and the
independent earth electrode.
29.3 High Voltage Generators
29.3.1 Earth Electrodes and Earthing Resistors
Where an earth electrode resistance is 1 Ω or less, a
common earth may be used for the high voltage
generator and for the low voltage system derived
through high voltage/low voltage transformation.
29.3.2.2 Standby generator (without paralleling
facility)
In addition to the earthing requirements described for
a set operating in isolation from other supplies, the
presence of an incoming electricity board supply makes
necessary the interlocking of the standby supply circuit
NOTE — For further information see 25.1 (c).
Where a resistor is used for earthing the star-point of a
high voltage generator, it is normally designed to limit
72
IS 3043 : 2018
NOTES
1 Cable sheath earth of provided/shown
2 PNE link of provided/shown - - - 3
Mechanical interlock to ensure that energy source neutral it always earthed but at one point only.
F IG. 41 LOW VOLTAGE STANDBY GENERATORS WITH STAR POINT SWITCHING
breakers to prevent inadvertent connection
(see Fig. 43).
29.3.3 Multiple High Voltage Generator Earthing
29.3.3.1 Generators operating in isolation from other
supplies
29.3.2.3 Standby generator (capable of parallel
operation with an incoming supply)
When it is required to operate two or more generators
in parallel and the method of energy source earthing is
direct or resistance earthing, then earthing contactors
should be installed between each generator star-point
and the earthing conductor each electrode (as described
in 29.2.3.1). The contactors need to be interlocked so
that only one can be closed to maintain a single energy
source earth.
The operation of a private generator (or generators) in
parallel with an electricity board high voltage system
is subject to the parallel and technical agreement of
the electricity board.
In most cases where parallel operation with an incoming
electricity board is required, an earthing contactor is
necessary between the generator star-point and the
bolted test link (see Fig. 44). The contactor should be
interlocked with the incoming supply circuit breaker
so that it is open during periods of parallel operation
but closes at all times. In the event of the electricity
supply being lost during a period of parallel operation,
the earthing contactor should be arranged to close
automatically. The form of generator earthing (direct
or resistance) is dependent upon the system parameters
and the machine manufacturer’s recommendations.
If a neutral earthing transformer is to be used for energy
source earthings, it should be connected as shown in
Fig. 45 except that in the case of an isolated generating
system, the earthing contactors is not required.
29.3.3.2 Standby generators (without mains parallel
facility)
When the generating sets are not to be operated in
parallel with the mains supply, and have direct or
73
IS 3043 : 2018
FIG. 42 METHOD OF CONNECTING A R ESIDUAL C URRENT DEVICE (R.C.D.) ON THE
OUTPUT OF A PORTABLE OR MOBILE GENERATOR
resistance earthing, the standby generator circuitbreakers and mains circuit-breaker need to be
interlocked.
a considerable voltage drop over the protective earth
conductor of the relevant circuit. Since a reduction of
such a voltage drop by the application of increased
cross-sectional areas of protective conductors is usually
impractical, available solutions are the reduction of the
duration of fault currents to earth by special devices or
the application of a power supply which is isolated from
earth.
If a neutral earthing transformer is used the
requirements are the same as described for a single
standby generator in 29.3.2.2; as shown in Fig. 46, but
without the earthing contactor.
29.3.3.3 Standby generators (capable of parallel
operation with an incoming mains supply)
30.0.3 Generally a power supply system including a
separated protective conductor is required. (TN-S
System) in medical establishment (see 11.1.1).
When the generating sets have direct or resistance
earthing and are used as standby to the mains, earthing
contactors are needed if parallel running is a
requirement. These should be interlocked with the
incoming mains supply circuit-breaker so that they are
open during parallel operation of the set with the mains,
but one is closed at all other times (see Fig. 45).
In addition the following provisions may be required,
depending upon the nature of the examinations or
treatments performed:
a)
Additional requirements concerning
protective conductors and protective devices
to restrict continuous voltage differences.
b) Restriction of voltage differences by
supplementary equipotential bonding. During
the application of equipment with direct
contact to the patient, at least a potential
equalized zone around the patient shall be
provided with a patient centre bonding bar to
which the protective and functional earth
conductors of the equipment are connected.
All accessible extraneous conductive parts in
the zone shall be connected to this potential
equalization bar.
c) Restriction of the potential equalization zone
around one patient, meaning practically
around one operation table or around one bed
in an intensive care room.
d) If more than one patient is present in an area,
connection of the various potential
30 PROTECTIVE MEASURES THROUGH
EARTHING IN MEDICAL ESTABLISHMENTS
30.0.1 General
In the context of this Clause ‘installation’, means any
combination of interconnected electrical equipment
within a given space or location intended to supply
power to electrical equipment used in medical practice.
30.0.2 As such, some parts of the installation may be
present in the patient’s environment, where potential
differences that could lead to excessive currents through
the patient, must be avoided. For this purpose a
combination or earthing of equipment and potential
equalization in the installation seems to provide the
best solution. A disadvantage of such a system is that
in the case of an insulation fault in circuits directly
connected to supply mains, the fault current may cause
74
IS 3043 : 2018
FIG. 43 SINGLE HIGH VOLTAGE STANDBY GENERATING SET NOT SUITABLE FOR PARALLEL O PERATION
FIG. 44 S INGLE HIGH VOLTAGE STANDBY G ENERATING SET SUITABLE FOR
PARALLEL OPERATION WITH INCOMING MAINS S UPPLY
75
IS 3043 : 2018
F IG. 45 MULTIPLE HIGH VOLTAGE STANDBY GENERATING SETS WITH NEUTRAL EARTHING TRANSFORMER SUITABLE
FOR P ARALLEL OPERATION WITH E ACH O THER AND WITH THE I NCOMING M AINS S UPPLY
FIG. 46 MULTIPLE HIGH VOLTAGE STANDBY GENERATING SETS SUITABLE FOR PARALLEL OPERATION
WITH E ACH O THER AND WITH THE I NCOMING M AINS S UPPLY
equalization centres to a central potential
equalization bushes, which should preferably
be connected to the protective earth system
of the power supply for the given area. In its
completed form, the equipotential bonding
network may consist partly of fixed and
permanently installed bonding and partly of a
number of separate bondings which are made
when the equipment is set up near the patient.
The necessary terminals for these bonding
connection should be present on equipment
e)
f)
76
and in the installation.
Restriction of the duration of transient voltage
difference by the application of residual
current operated protective devices (earth
leakage circuit-breakers).
Continuity of power supply to certain
equipment in the case of a first insulation fault
to earth and restriction of transient voltage
differences by application of isolating
transformers.
IS 3043 : 2018
g) Monitoring of first insulation fault to earth in
an IT Systems (see 11.1.1) (the secondary side
of an isolating transformer) with sufficiently
high impedance to earth.
31 SUPPLY CHARACTERISTICS
PARAMETERS
AND
31.0 Exchange of Information
31.0.1 Proper coordination shall be ensured between
the architect, building contractor and the electrical
engineer or the various aspects of installation design.
The necessary special features of installations shall be
ascertained before hand with reference to Table 16.
NOTE — Additional safety measures are required
besides earthing described in this Clause. These cover
fire safety, safety supply systems and interference
suppression. Reference may be made to SP 30.
30.1 Safety Provisions
30.1.1 Safety measures from the point of view of
earthing are divided into a number of provisions as
given in Table 15.
31.1 Circuit Installation Measures for Safety
Provisions (see Table 15, col 3)
30.1.2 Provision P0 shall be applicable to all buildings
containing medically used rooms. Provision P1 shall
be applicable for all medically used rooms.
31.1.1.1 All buildings in the hospital area which contain
medically used rooms shall have a TN-S, TT power
system. The conventional touch voltage limit (LL) is
fixed at 50 V ac.
31.1.1 Provision P0 General
Other requirements of this Clause, need not be complied
with, if:
NOTE — The use of TN-C-S system (in which the PENconductor may carry current in normal condition) can cause
safety hazards for the patients and interfere with the function
of medical electrical equipment, data processing equipment,
and signal transmission lines, etc.
a)
a room is not intended for the use of medical
electrical equipment, or
b) patients do not come intentionally in contact
with medical electrical equipment during
diagnosis or treatment, or
c) only medical electrical equipment is used
which is internally powered or of protection
Class II.
31.1.2 Provision P1: Medical TN-S System
31.1.2.1 The conventional touch voltage limit (LL) is
fixed at 25 V ac.
31.1.2.2 Protective conductors inside a medically used
room shall be insulated; their insulation shall be
coloured green-yellow.
The rooms mentioned under (a), (b) and (c) may be,
for example, massage rooms, general wards, doctor’s
examining room (office, consulting room), where
medical electrical equipment is not used.
31.1.2.3 Exposed conductive parts of equipment being
part of the electrical installation used in the same room
shall be connected to a common protective conductor.
30.1.3 Guidance on the application of the provisions
are given in Table 16.
31.1.2.4 A main equipotential bonding with a main
earthing bar shall be provided near the main service
entrance. Connections shall be made to the following
parts by bonding conductors:
30.1.4 A typical example of an installation in a hospital
is given in Annex C of SP 30.
Table 15 Safety Provisions
(Clauses 30.1.1 and 31.1)
Provisions
(1)
Principal Requirements
(2)
Installation Measures
(3)
P0
P1
Duration of touch voltage restricted to a safe limit
As P0 but additionally : Touch voltages in patient environment
restricted to a safe limit
P2
As P1 but additionally : Resistance between extraneous conductive
parts and the protective conductor busbar of the room not exceeding
0·1 Ω
As P1 or P2 but additionally : Potential difference between exposed
conductive parts and the protective conductor busbar not exceeding 10
mV in normal condition (see Note)
As P1 or P2. Additional protection against electric shock by limitation
of disconnecting time
Continuity of the mains supply maintained in case of a first insulation
fault to earth and currents to earth restricted
TN-S, TT or IT system (see 11.1.1)
Additional to P0 Supply system with
additional requirements for protective
earthing, etc
Additional to P1 : Supplementary
equipotential bonding
P3
P4
P5
77
As P1 or P2: Measurement necessary,
corrective action possibly necessary
Additional to P1 or P2 : Residual current
operated protective device
Additional to P1, P2 or P3 : Isolated supply
system with isolation monitoring
IS 3043 : 2018
Table 16 Examples of Application of Safety Provisions
(Clauses 30.1.3 and 31.0.1)
Sl
No.
Medically Used Rooms
P0/P1
i)
Massage room
M
Protective Measures
P2
P3
P4
P5
0
ii)
Operating wash room
M
x
iii)
Ward, General
M
0
iv)
Delivery room
M
x
x
v)
ECG, EEG, EMG room
M
x
x
vi)
Endoscopic room
M
x
x
Examination or treatment room
Labour room
M
M
0
x
x
x
ix)
Operating sterilization room
M
0
x
x)
Orology room (not being an operating theatre)
M
x
x
xi)
Radiological diagnostic and therapy room, other than mentioned under 20 and 24
M
x
x
xii)
xiii)
Hydrotherapy room
Physiotherapy room
M
M
x
x
x
x
0
xiv)
Anesthetic room
M
x
x
x1
x
xv)
Operating theatre
M
x
x
x1
x
xvi)
Operating preparation room
M
x
x
x1
x
xvii)
Operating plaster room
M
x
x1
x
xviii)
xix)
Operating recovery room
Out-patient operating room
M
M
x
x
x
xl
x1
x
x
vii)
viii)
0
0
0
xx)
Heart catheterization room
M
x
x
x1
x
xxi)
Intensive care room
M
x
0
xl
x
xxii)
Intensive examination room
M
x
0
x1
x
xxiii)
Intensive monitoring room
M
x
0
x1
x
xxiv)
xxv)
Angiographic examination room
Heamodialysis room
M
M
x
x
0
0
x1
x1
x
x
xxvi)
Central monitoring room (see Note)
M
x
0
x1
x
NOTE — Only if such a room is part of a medical room group and, therefore, installed in the same way as an intensive monitoring room.
Central monitoring room having no conductive connection to the mexially used room (for example, by use of isolating coupling devices
for signal transmission) may be installed as non-medically used from (Provision P0 only).
M = mandatory measure;
x = recommended measure;
x1 = as x, but only for insulation monitoring device; and
0 = additional measure may be considered desirable.
area affording equivalent current-carrying capacity in
other metals.
a) lightening conductor;
b) earthing systems of the electric power
distribution system;
c) the central heating system;
d) the conductive water supply line;
e) the conductive parts of the waste water line;
f) the conductive parts of the gas supply; and
g) the structural metal frame work of the
building, if applicable.
31.1.2.5 Each medically used room or room group shall
have its own protective conductor bus bar, which should
have adequate mechanical and electrical properties and
resistance against corrosion.
This busbar may be located in the relevant power
distribution box. The leads connected to terminals of
such a protective conductor bar shall be identified and
shall be similarly designated on drawings of the
installation system.
Main equipotential bonding conductors shall have
cross-sectional areas of not less than half the crosssectional area of the largest protective conductor of the
installation, subject to a minimum of 6 mm2. The crosssectional area, need not, however, exceed 25 mm2 if
the bonding conductor is of copper or a cross-sectional
31.1.2.6 The impedance (Z) between the protective
conductor bar and each connected protective conductor
contact in wall sockets or terminals should not exceed
0·2 Ω, if the rated current of the overcurrent-protective
78
IS 3043 : 2018
2) conductive parts in a non-conductive
enclosure;
b) In locations where the position of the patient
can be predetermined this provision may be
restricted to extraneous conductive parts
within the patient environment [see Annex B
of NEC (Part 3, Section 4)]; and
c) In operating theatres, intensive care rooms,
heart catheterization rooms and rooms
intended for the recording of bioelectrical
action potentials all parts should be connected
to the equipotential bonding bar via direct and
separate conductors.
device is 16 A or less. In case of a rated current
exceeding 16 A, the impedance should be calculated
using the formula:
25
Ω
6 Ir
in all cases Z shall not exceed 0·2 Ω.
Z =
(Ir = rated current of overcurrent protective
device in amperes).
NOTE — The measurement of the protective conductor
impedance should be performed with an ac current not less
than 10 A and not exceeding 25 A from a source of current with
a no-load voltage not exceeding 6 V, for a period of at least 5 s.
31.1.3.3 The following requirements shall be fulfilled:
31.1.2.7 The cross-sectional area of the protective
conductor shall be not less than the appropriate value
shown in Table 12.
a)
The cross-sectional area of every protective conductor
which does not form part of the supply cable or cable
enclosure shall be, in any case, not less than:
NOTE — The measurement of this impedance should
be performed with a current not less than 10 A and not
exceeding 25 A during not less than 5 s from a current
source with a no-load potential not exceeding 6 V ac.
2·5 mm2, if mechanical protection is provided;
and
b) 4 mm 2 , if mechanical protection is not
provided.
a)
b) All equipotential bonding conductors shall be
insulated, the insulation being coloured greenyellow.
NOTE — Insulation of the equipotential bonding
conductors is necessary, to avoid loops by contact and
to avoid picking up of stray currents.
31.1.2.8 It may be necessary to run the protective
conductor separate from the phase conductors, in order
to avoid measuring problems when recording
bioelectric potentials.
c)
Equipotential
conductors
between
permanently installed extraneous conductive
parts and the equipotential bonding bar shall
have a cross-sectional area of not less than
4 mm2 copper or copper equivalent.
d) The equipotential bonding bar, if any, should
have adequate mechanical and electrical
properties, and resistance against corrosion.
e) The conductors connected to the equipotential
bonding bar shall be marked and shall be
similarly designated on drawings of the
installation system.
f) A separate protective conductor bar and an
equipotential bonding bar in a medically used
room or in a room group shall be
interconnected with a conductor having a
cross-sectional area of not less than 16 mm2
copper or copper equivalent (see 31.1.3.1).
g) An adequate number (under consideration) of
equipotential bonding terminals other than
those for protective conductor contact or pins
of socket outlets should be provided in each
room for the connection of an additional
protective conductor of equipment or for
reasons of functional earthing of equipment.
31.1.3 Provision P2: Supplementary Equipotential
Bonding
31.1.3.1 In order to minimize the touch voltage, all
extraneous conductive parts shall be connected to the
system of protective conductors.
An equipotential conductor bar shall be provided. It
should be located near the protective conductor bar
(see also 31.1.2.5). A combined protective conductor
and equipotential bonding bar may be used, if all
conductors are clearly marked according to 31.1.2.5
and 31.1.3.3(e).
31.1.3.2 Connections shall be provided from the
equipotential bonding bar to extraneous conductive
parts such as pipes for fresh water, heating, gases,
vacuum and other parts with a conductive surface area
larger than 0·02 m2 or a linear dimension exceeding 20
cm or smaller part that may be grasped by hand.
Additionally, the following requirements apply:
a)
The impedance between extraneous
conductive parts and the equipotential
bonding bar shall not exceed 0.1 Ω.
Such connections need not be made to:
1) extraneous conductive parts inside of
walls (for example, structural metal work
of buildings) having no direct connection
to any accessible conductive part inside
the room, and
31.1.4 Provision P3: Restriction of Touch Voltage in
Rooms Equipped for Direct Cardiac Application
31.1.4.1 The continuous current through a resistance
79
IS 3043 : 2018
of 1 000 Ω connected between the equipotential
bonding bar and any exposed conductive part as well
as any extraneous conductive part in the patient
environment shall not exceed 10 µA in normal condition
for frequencies from dc to 1 kHz.
mains by use of a residual-current protective device
with I Δ N < 300 mA.
31.1.6 Provision P5: Medical IT-System
31.1.6.0 The use of a medical IT-System for the supply
of medically used room for example, operating theatres,
may be desirable for different reasons:
For a description of patient environment, see Annex B
of SP 30 : 2011 (NEC). Where the measuring device
has impedance and a frequency characteristics, the
current may also be indicated as a continuous voltage
with a limit of 10 mV between the parts mentioned
above.
a)
A medical IT-System increases the reliability
of power supply in areas where an interruption
of power supply may cause a hazard to patient
or user;
b) A medical IT-System reduces an earth fault
current to a low value and thus also reduces
the touch Voltage across a protective
conductor through which this earth fault
current may flow; and
c) A medical IT-System reduces leakage currents
of equipment to a low value, where the
medical IT-System is approximately
symmetrical to earth.
a)
During the test, it is assumed that fixed and
permanently installed medical electrical
equipment is operating.
b) ‘Normal conditions’ means without any fault
in the installation and in the medical electrical
equipment.
NOTE — To comply with this requirement, it may be
necessary to apply one or more of the following methods:
Extraneous conductive parts may be:
a) connected to the equipotential bonding bar by a
conductor of a large cross-sectional area in order to
reduce the voltage drop across such a conductor,
b) insulated so that it is not possible to touch them
unintentionally, and
c) provided with isolating joints at those places where
they enter and leave the room.
Exposed conductive parts of permanently installed
equipment may be isolated from the conductive building
construction.
It is necessary to keep the impedance to earth of the
medical IT-System as high as possible. This may be
achieved by:
a)
restriction of the physical dimensions of the
medical isolating transformer,
b) restriction of the system supplied by this
transformer,
c) restriction of the number of medical electrical
equipment connected to such a system, and
d) high internal impedance to earth of the
insulation monitoring device connected to
such a circuit.
31.1.5 Provision P4: Application of Residual-Current
Protective Devices
31.1.5.1 The use of a residual-current protective device
is not recognized as a sole means of protection and
does not obviate the need to apply the provisions P1
and P2.
If the primary reason for the use of a medical IT-System
is the reliability of the power supply, it is not possible
to define, for such system, a hazard current and an
insulation resistance monitoring device should be used.
31.1.5.2 Each room or each room group shall be
provided with at least one residual-current protective
device.
31.1.5.3 A residual-current protective device shall have
a standard rated operating residual-current
I Δ N < 30 mA.
If, on the other hand, the restriction of leakage current
of equipment is the main reason for the use of the
medical IT-System, an insulation impedance monitoring
device should be used.
31.1.5.4 A medical isolating transformer and the circuits
supplied from it shall not be protected by a residual
current protective device.
31.1.6.1 For each room or each room group at least
one fixed and permanently installed medical isolating
transformer shall be provided.
31.1.5.5 Electrical equipment, for example, general
lighting luminaries, installed more than 2·5 m above
floor level, need not be protected by a residual-current
protective device.
31.1.6.2 A medical isolating transformer shall be
protected against short-circuit and overload.
In case of a short-circuit or a double earth fault in parts
of opposite polarity of the medical IT-System, the
defective system shall be disconnected by the relevant
overcurrent protective device.
31.1.5.6 Fixed and permanently installed electro
medical equipment with a power consumption
requiring an overcurrent protective device of more
than 63 A rated value may be connected to the supply
If more than one item of equipment can be connected
to the same secondary winding of the transformer, at
80
IS 3043 : 2018
least two separately protected circuits should be
provided for reasons of continuity of supply.
the alarm be activated until the fault hazard current
exceeds 0·7 mA.
31.1.6.3 Overcurrent protective devices shall be easily
accessible and shall be marked to indicate the protective
circuit.
NOTE — The value of 2 mA or 0·7 mA are based on practical
experience with 110 to 120 V power supplies. For a 220-240 V
power supply, it may be necessary to increase these values to 4
and 1·4 mA because of the higher leakage current of equipment.
31.1.6.4 An insulation monitoring device shall be
provided to indicate a fault of the insulation to earth of
a live part of the medical IT-System.
During the checking of the response of the monitor to
a fault condition the impedance between the medical
IT-System and earth shall not decrease.
31.1.6.5 Fixed and permanently installed equipment
with a rated power input of more than 5 kVA and all Xray equipment (even with a rated power input of less
than 6 kVA) shall be protected by Provision P4.
Electrical equipment, for example, general lighting,
more than 2·5 m above floor level, may be connected
directly to the supply mains.
32 EARTHING IN POTENTIALLY HAZARDOUS
AREAS
32.1 Earthing and Bonding
32.1.1 Earthing should be in accordance with the
relevant clauses of this Code. The connection between
metal part to be grounded and the grounding conductor
shall be made secure mechanically and electrically by
using adequate metallic fitting. The grounding
conductors shall be sufficiently strong and thick, and
the portions of conductor which are likely to be
corroded or damaged shall be well protected.
Grounding conductors which shall not reach a
hazardous high temperature due to the anticipated
maximum earth fault current flowing shall be used.
31.1.6.6 General requirements for insulation
monitoring devices
A separate insulation resistance or impedance
monitoring device shall be provided for each secondary
system. It shall comply with the requirements of (a) to
(d) below:
a)
It shall not be possible to render such a device
inoperative by a switch. It shall indicate visibly
and audibly if the resistance or impedance of
the insulation falls below the value given in
31.1.6.7 and 31.1.6.8.
b) A test button shall be provided to enable
checking the response of the monitor to a fault
condition as described in 31.1.6.4.
c) The visible indication mentioned in (a) of the
insulation monitoring device shall be visible
in the monitored room or room group.
d) The insulation monitoring device should be
connected symmetrically to the secondary
circuit of the transformer.
32.1.2 Specific guidelines for installations in hazardous
locations are given in IS/IEC 60479. Inter-connection
system with other buried metal services and/or earth
terminations for equipment grounding for the purpose
of equalizing the potential distribution in the ground
should preferably be made below ground.
32.1.3 Portable and transportable apparatus shall be
grounded with one of the cores of flexible cable for
power supply. The earth continuity conductor and the
metallic screen, wherever provided for the flexible
cable, should be bonded to the appropriate metalwork
of the apparatus and to earthing pin of the plug.
32.1.4 Efficient bonding should be installed where
protection against stray currents or electrostatic charges
is necessary.
31.1.6.7 Insulation resistance monitoring device
The ac-resistance of an insulation resistance monitoring
device shall be at least 100 kΩ. The measuring voltage
of the monitoring device shall not exceed 25 V, and
the measuring current (in case of a short-circuit of an
external conductor to earth) shall not exceed 1 mA. The
alarm shall operate if the resistance between the
monitored isolated circuit and earth is 50 kΩ or less,
setting to a higher value is recommended.
32.1.5 Earthing and Bonding of Pipelines and Pipe
Racks
Unless adequately connected to earth elsewhere, all
utility and process pipelines should be bonded to a
common conductor by means of earth bars or pipe
clamps and connected to the earthing system at a point
where the pipelines enter or leave the hazardous area
except where conflicting with the requirements of
cathodic protection. In addition, it is recommended that
steel pipe racks in the process units and off-site areas
should be grounded at every 25 m.
31.1.6.8 Insulation impedance monitoring device
An insulation-impedance monitoring device shall give
reading calibrated in total hazard current with the value
of 2 mA near the centre of the metre scale.
32.2 Permissible Type of Earthing System
32.2.1 Guidance on permissible power systems is given
below:
The device shall not fail to alarm for total hazard
currents in excess of 2 mA. In no case, however, shall
81
IS 3043 : 2018
For additional information, see relevant clauses of this
Code.
a)
If a power system with an earthed neutral is
used, the type TN-S system with separate
neutral (M) and protective conductor (PE)
throughout the system is preferred.
The neutral and the protective conductor shall
not be connected together or combined in a
single conductor in a hazardous area.
A power system of type Indian TN-C (having
combined neutral and protective functions in
a single conductor throughout the system) is
not allowed in hazardous area.
b) If a type IT power system (separate earths for
power system and exposed conductive parts)
is used in Zone 1, it shall be protected with a
residual current device even if it is a safety
extra-low voltage circuit (below 50 V).
However, there are certain pieces of equipment, for
example, some intrinsically safe apparatus, which are
not intended to be connected to the equipotential
bonding system.
33 TELECOMMUNICATION CIRCUITS AND
APPARATUS
33.1 General
In addition to protective earthing which may be required
in accordance with this Code, telecommunication
systems may require functional earths for any or all of
the following purposes:
a)
to complete the circuits of telegraph or
telephone systems employing on-earth path for
signalling purposes;
b) to earth the power supply circuit and stabilize
the potential of the equipment with respect to
earth;
c) for lightning-protective apparatus; and
d) to earth screening conductors to reduce
electrical interference to the telecommunication circuits.
The type TT power system is not permittedr:
in Zone 0.
c) For an IT power system (neutral isolated from
earth or earthed through impedance), an
insulation monitoring device should be used
to indicate the first earth fault. However,
equipment in Zone 0 shall be disconnected
instantaneously in case of the first earth fault,
either by the monitoring device or by a residual
current operated device.
d) For power systems at all voltage levels
installed in Zone 0, due attention should be
paid to the limitation of earth fault currents in
magnitude and duration. Instantaneous earth
fault protection shall be installed.
If equipment requires both a protective earth and a
functional earth connection, it is preferred that the two
earths should be separated within the equipment so that
power system fault currents cannot flow in the
functional earthing conductors. The functional earthing
system and conductors can then be designed solely in
accordance with the requirements of the
telecommunication system. Alternatively, the protective
and functional earth may be connected together within
the equipment but in this case the functional earth
system and conductors should be suitable for the current
they may carry under power system fault conditions.
It may also be necessary to provide instantaneous earth
fault protection devices for certain applications in
Zone 1.
32.2.2 Potential Equalization
To avoid dangerous sparking between metallic parts
of structures, potential equalization is always required
for installations in Zone 0 and Zone 1 areas and may
be necessary for installations in Zone 2 areas.
Therefore, all exposed and extraneous conductive parts
shall be connected to the main or supplementary
equipotential bonding system.
The general recommendations for lightning protection
apply to earth systems for telecommunication lightning
protection.
The telecommunication functional earth should be
obtained from a point which even under power system
fault conditions is unlikely to have a dangerous potential
to remote earth.
The bonding system may include normal protective
conductors, conduits, metal cable sheaths, steel wire
armouring and metallic parts of structures but shall not
include neutral conductors. The conductance between
metallic parts of structures shall correspond to a crosssection of at least 10 mm2 of copper.
The consumer’s earth terminal of a TN-system is
suitable, otherwise a suitable earth electrode system,
separate from the protective earth, should be provided.
33.2 Telecommunication Circuits Association with
High Voltage Supply Systems
Enclosures are not to be separately connected to the
equipotential bonding system if they are secured to and
are in metallic contact with structural parts or piping
which are connected to the equipotential bonding system.
Telecommunication circuits used in any way in
connection with or in close proximity to high voltage
equipment require special attention and due
82
IS 3043 : 2018
consideration should be given to the safeguarding of
such circuits against rise in potential of the supply
system earth-electrodes.
of earth potential, whichever is the greater,
between conductors and earth for 1 min. It is
preferred that the cables have no metallic
sheath, armouring or screen but, if any exists,
it should be isolated either from the rise of
earth potential or from the rest of the
telecommunication network by insulation
capable of withstanding the above test voltage.
The station terminal equipment and wiring
should be isolated from the line by a barrier
designed to withstand the test voltage as
above. All wiring and apparatus connected to
the line side of this barrier should be insulated
from the station earth to withstand the same
test voltage.
d) Any
earth
connection
for
the
telecommunication circuit required on the line
side of isolating barrier should be obtained
from a point outside the earth electrode area
via either a pair in the telecommunication
cable or a cable insulated in accordance with
(c).
When a telecommunication circuit is provided in a
building, where a high voltage system terminates and
the telecommunication circuit is part of or is electrically
connected to a system outside the ‘earth-electrode area’,
precautions should be taken to safeguard personnel and
telecommunication plant against rise of potential of the
earth-electrode system.
The term ‘earth-electrode system’ includes all
metalwork, such as power cable sheaths, pipes,
frameworks of buildings and metal fences, bonded to
the power system earth electrodes and situated within
a distance of 100 m outside the fencing that surrounds
the high voltage compound or compounds; it also
includes the first three supports of any overhead line
leaving the station. The ‘earth-electrode area’ is any
area within 5 m of any part of the earth-electrode
system.
The following practice is recommended:
In practice, (c) and (d) are normally confined to stations
where the neutral of a 33 kV or higher voltage system
is earthed since, at other stations, line faults do not
usually produce dangerous conditions.
a)
In all cases as great a separation as is
practicable should be provided between the
telecommunication cables and the station
earth-electrode system. Nevertheless, within
a station, to prevent the appearance of
potential differences between normally
accessible metal parts, all such parts of the
telecommunication installation should be
connected to the station earth-electrode
system.
b) At stations where the neutral of the high
voltage system is earthed, it is generally
practicable from a knowledge of the
impedance of the earth-electrode system and
of the maximum earth-fault current to estimate
the rise of earth potential that will occur upon
the incidence of a fault. Where the estimate
does not exceed safe values no precaution
additional to that described in (a) is necessary.
This limit may be extended to higher values if
all the power lines contributing to the earth
fault current are in the ‘high-reliability’
category.
34 BUILDING SITES
34.1 In the often damp and rough environment of
building sites, precautions to prevent electrical hazards
have to be robust and regularly inspected and this
particularly applies to the earthing system.
Because of the great difficulty of ensuring that all
incoming metallic services and extraneous metalwork
are bonded to the neutral of the supply system, where
the supply is at 415 V/240 V, to thus satisfy the
requirements of the PME approval, it is unlikely that
the supply authority will offer an earth terminal where
the supply system has a multiple earthed neutral. If the
supply is at a voltage higher than 415 V, the developer
will have to provide the neutral earthing on the low
voltage system.
34.2 The main protection against electrical hazards on
a construction site is the use of a reduced low voltage
system for power tools (110 V between phases and 55 V
to mid-point earth or 65 V to star-point earth) and safety
extra low voltage for supplies to headlamps, etc.
If the estimate is above safe limits (see 25.5.1),
the following additional precautions should be
observed.
c)
The earth fault loop impedances on a reduced voltage
system or on a 240/415 V system serving fixed
equipment should allow disconnection within the safe
duration.
Where the telecommunication circuit lies
within the ‘earth-electrode area’, it should be
run in insulated cable capable of withstanding
the application of a test voltage of 2 200 V dc
(or ac 50 Hz peak) or (1 500 + 2U) V dc (or
ac 50 Hz peak), where U is the estimated rise
34.3 Early discussions with the electricity board are
essential so that agreement on the type of supply,
83
IS 3043 : 2018
including earthing facilities, can be obtained. Where the
supply is provided from the low voltage distribution
system, the increasing use of protective multiple
earthing (PME) will usually prevent an earthing
terminal being provided by the electricity board because
of the developers inability to comply with the
requirements of the PME approval during construction
work.
If the provision of such an earth terminal is
impracticable, then it is imperative that the earth
electrodes at the supply source and consumers’ premises
are maintained such that their resistance to the general
mass of earth is as low as possible, for example, less
than 2 Ω, and appropriate earth fault protection is
provided.
In all cases, the aim should be to maintain earth
electrode resistance, as low as is practicable, taking
account of the site conditions, for example, soil/rock
resistivity. Except, however, for the instance quoted
above, the achievement of a low resistance is not as
important as adequate bonding of all exposed metallic
parts back to the supply source neutral or mid-voltage
point earth electrode.
35 MINES AND QUARRIES
35.1 General
Earthing requirements for mines and quarries are based
on the broad principle that exposed conductive parts
of apparatus should be efficiently connected to earth
or otherwise protected by other equally effective means
to prevent danger resulting from a rise in potential
(above earth) on these conductive parts.
The mains supply system neutral or mid-voltage points
should be earthed at one point only and in the case of
mines, this should be on the surface. The connection to
earth may either be a solid connection or via an
impedance to limit the prospective earth fault current
and in the case of impedance earthed systems, suitable
earth fault provided, that is, capable of detecting the
restricted flow of fault current.
In some mines and certain quarries (quarries include
open cast coal sites), in addition to shock risk, there
are also dangers associated with the possible presence
of flammable gas and explosive materials. In these
cases, separate local earthing may be necessary to avoid
incendive sparks caused by static electrical discharge.
No switch or circuit-breaker or fuse should be placed
in any earthing conductor, although an interlocked
changeover linking device is allowed in certain cases
where two or more earth electrodes are provided. Such
a device would be used to allow periodic testing of an
electrode resistance to the general mass of earth.
35.2 Power System Earthing
At most mines and quarries, the incoming supply is
provided by the supply authority who will install
switchgear and metering for their own purpose. It is
important to clearly establish in all cases, the point at
which the supply authorities’ responsibilities terminate
and where the consumer’s responsibility commence.
35.3 Apparatus Earthing at Coal and Other Mines
Every metallic covering of any cable should be earthed.
This may be considered as forming part of the earthing
conductor except in the case of flexible trailing cables
where specific earthing conductors may also be
required.
If the supply is from a transformer (or generator), that
is, the property of the supply authority, and is on site, a
request should be made for them to facilitate connection
of the consumer’s earthing system to the neutral or midvoltage point. In some cases, the supply authority will
allow the use of their earth electrode for joint use, in
this event the consumer may not have to provide and
maintain his own earth electrode. If the supply is from
a transformer that is not the property of the supply
authority, or if the consumer generates electricity
privately, then the consumer should provide and
maintain the earth electrodes that have the neutral or
mid-voltage points bonded to them.
Earthing conductors installed for that purpose should
have a conductivity throughout (including joints) of not
less than half that of the conductor having the greatest
current carrying capacity, to which that earth conductor
is related and should have a cross-sectional area of not
less than 14 mm2, in the case of flexible cable working
at less than 125 V, the cross-section area need not be
greater than 6 mm2; also a flexible cable on the surface
of the mine supplying a load less than 3 kW need not
have an earth conductor larger than the power
conductors.
If the supply transformer (or generator) is distant from
the consumer’s premises, provision of an earth terminal
at the premises should be requested. Where this is
possible, the earth terminal should be made available
by means of an additional earth conductor in the supply
cable or overhead line.
Cables incorporating steel tape armour (unless
supplementing steel wire), aluminium armour or copper
sheathed (mineral insulated) cables are unsuitable for
use below ground. Generally single or double, steel wire
armoured cables are used. The use of paper-insulated
lead covered cable is also discouraged from use below
NOTE — The supply cable sheath and armouring may serve
the purpose of this earth conductor provided that they are
bonded to the supply source earth, neutral or mid-voltage point
and meet the 50 percent conductivity requirement.
84
IS 3043 : 2018
occur, provided that a transformer is used which has a means
to cut off the supply and prevent danger should a breakdown
occur between the primary and secondary windings. In these
systems the maximum prospective earth fault current does not
usually exceed 2 A and switchgear is set to trip at less than onefifth of this value.
ground owing to the poor mechanical strength of the
paper insulating material.
The following are released from the requirements to
be earthed, when used solely at the surface of the mine:
a)
any lamp holder, that is, efficiently protected
by a covering which is insulated or earthed
and made of fire resisting material;
b) any hand held tool that is double insulated;
c) any portable apparatus working at less than
50 V dc or 30 V ac; and
d) any other non-portable apparatus working at
less than 250 V dc or 125 V ac.
Signalling and telephone circuits may be connected to
earth where safety is enhanced and the method of
connection is approved by the concerned authority for
that type of apparatus.
35.4 Apparatus Earthing at Miscellaneous Mines
and Quarries
Every earthing conductor should have an equivalent
cross-sectional area of not less than 14 mm2 except this
requirement does not apply to an earthing conductor,
that is:
In the case of electrical circuits used for control,
interlocking and indicating instruments, the regulations
allow one pole of the auxiliary transformer secondary
winding serving these circuits to be connected to earth
as an alternative to mid-point earthing.
a)
the metallic covering of a cable, which should
have conductance not less than half that of the
largest current carrying capacity conductor in
that cable;
b) one of the conductors in a multi-core flexible
cable used to supply portable apparatus, in
which case the earth conductor has to be equal
in cross-sectional area to that of the largest
current carrying conductor; and
c) a part of an overhead line on the surface which
should have a cross-sectional area of not less
than 12 mm2.
Where mobile apparatus containing its own source of
electricity, for example, mobile generator sets and
diesel-electric vehicles/cranes, is used on the surface,
then an exception is required from the present
regulations if the requirement to earth these to the main
earth electrode is impracticable. However, the bonding
together of all exposed metallic parts is required.
Below ground, where self-contained mobile apparatus
is used, for example, battery locomotives, these should
be operated as totally insulated systems (to avoid sparks
between metal parts of the apparatus). Warning systems
should be provided to give an indication of leakage to
frame.
Every cable at a miscellaneous mine or quarry operating
at voltages exceeding 250 V dc or 125 V ac, other than
flexible cables and those not required to be covered by
insulating material, should be protected throughout by
a suitable metallic covering that has to be earthed.
Metallic covering is defined in the regulations and it
should be noted that this does not include any metals
other than iron or steel, therefore cables with
armourings or metallic cover made of soft metals such
as aluminium and copper (MICC cable) cannot be used
on these premises where the voltages exceed 250 V dc
or 125 V ac.
At places below ground, where flammable gas may
occur in quantity to indicate danger (usually deemed
to be places where 0·25 percent flammable gas could
be present in the general body of air), then limitation
of the maximum prospective earth fault current is called
for on power systems working at voltages between
250 V and 1 200 V (the range of voltage normally used
for coal winding machinery served by flexible trailing
cables). In these cases, the maximum prospective earth
fault current should be limited (normally by impedance
earthing) to 16 A at voltages between 250 V and 650 V
and to 2 A at voltages between 650 V and 1 200 V. In
either case, the switchgear controlling the circuit should
be able to detect and cut-off the supply of electricity
with less than one-third of the maximum prospective
earth fault current flowing.
Where a cable is provided with a lead sheath, in addition
to the required ‘metallic’ covering, the conductance of
the lead sheath may be taken as contributing to that of
the metallic covering. For such installations, plumbed
joints have to be used where the lead sheath is jointed
or terminated.
Where flexible cable is used to supply portable
apparatus at voltages exceeding 250 V dc or 125 V ac,
such cable should be protected by one of the following:
NOTE — The ratio between maximum prospective earth fault
current and protection settings is known as the ‘tripping ratio’.
In practice it has been found that in order to take account of
voltage depressions occurring when a short circuit coincides
with an earth fault the tripping ratio should be set to at least 5:
1. Multipoint earthing of a power circuit (sometimes referred
to as an ‘insulated’ or ‘free neutral system’) is allowed at any
place in a mine, including places where flammable gas may
a)
85
A metallic covering (flexible wire armouring)
that encloses all the conductors and having a
conductance of not less than half that of the
largest current carrying conductor, or where
IS 3043 : 2018
this is impracticable, having a conductance not
less than that of a 14 mm2 cross-sectional area
copper conductor.
b) A screen of wires to enclose all the conductors
(collectively screened type cable) having a
conductance not less than that of a 14 mm2
cross-sectional area copper conductor.
c) A screen of wires arranged to individually
enclose each conductor (individually screened
type cable), other than the earth conductor.
Cables of this construction for use in quarries
have to be approved by HSE. For
miscellaneous mines, the screens should each
have a conductance of not less than that of
6 mm2 cross-sectional area copper conductor.
Class II should have a circuit protective conductor run
to and appropriately terminated at each point in wiring
and at each accessory.
36.2.2 TN-C-S Systems
An alternative method of supplying and protecting the
street furniture that may be used is by means of a TNC-S system. In such cases a combined neutral and earth
conductor cable may normally be used at the source of
supply (for example to an individual lighting column
or for larger installations a local supply authority PME
supply into a feeder pillar, with cables using separate
line, neutral and protective conductors to feed items of
street furniture in the carriageway).
In the case of circuits feeding more than one item of
street furniture, for example, by looping using a cable
with separate line, neutral and protective conductors,
an earth electrode should be installed preferably both
at the point of supply and at the last or penultimate unit
and this electrode should be such as to make the
resistance to earth of the neutral at any point less than
20Ω, other earth electrodes equally spaced along the
circuit should be installed.
Where flexible cables are used with portable apparatus
at quarries and the size of the conductor is such as to
make the use of one multicore cable impracticable,
single core cables of such construction and bonded in
such a manner as HSE may approve, may be used.
36 STREET LIGHTING AND OTHER
ELECTRICALLY
SUPPLIED
STREET
FURNITURE
36.2.3 TT Systems
NOTE — Street furniture includes fixed lighting columns,
illuminated traffic signs, bollards and other electrically supplied
equipment permanently placed in the street.
There is one further possibility that can arise, in which
case the lighting authority should provide its own
protective earthing electrode(s): that is where the
electricity distributor does not provide an earth terminal
(a TT-System).
36.1 In all cases the local supply authority should be
consulted before design work on new street furniture
is commenced to ascertain the type of system that will
supply the new installation.
In this case it is essential to ensure that both the initial
and continuing impedance of the fault path is
sufficiently low to ensure the operation of the protective
device on the occurrence of a fault in the fixtures.
36.2 Supply System for Street Furniture
Street furniture may normally be fed from TN-S or TNC-S systems.
36.3 Wiring on the load side of the protective device in
the units being supplied should use, unless a special
approval has been obtained, separate phase, neutral and
circuit protective conductors. Exposed extraneous
conductive parts should be bonded to the neutral
terminal by a conductor with a copper equivalent crosssection of 6 mm or the same as that of the supply neutral
conductor if this is less. This requirement does not apply
to small isolated metal parts not likely to come into
contact with exposed metallic or extraneous metal parts
or with earth, for example, small metallic doors and
door frames in concrete or plastics units should not be
so connected.
36.2.1 TN-S Systems
Street furniture may be fed from and protected by a
TN-S system and in such arrangements a supply cable
with separate line, neutral and protective conductors is
required, that is, an SNE cable. In Class I street furniture
the wiring on the load side of the protective device in
the unit should consist of separate line, neutral and
circuit protective conductors. Exposed conductive parts
of the item of street furniture being supplied should be
earthed by connecting them to the earthing terminal
within the equipment. The earthing terminal itself
should be connected to the supply protective conductor.
36.4 In the case of circuits feeding more than one item
of street furniture, for example, by looping, an earth
electrode should be installed at the last or penultimate
unit and this electrode should be such as to make the
resistance to earth of the neutral at any point less than
20 Ω before the connection of any circuit protective or
bonding conductors to the neutral terminal. Should the
If the installation is of Class II, no protective conductor
is required and the wiring on the load side of the
protective device should consist of line and neutral
conductors only.
It is recommended that a circuit supplying one or more
items of class II equipment or a mixture of Class I and
86
IS 3043 : 2018
All phases or conductors of any apparatus or main to
be worked on should be made dead, isolated and earthed
and should remain earthed until work is completed. Due
regard should be taken of changing conditions during
the progress of work which may necessitate revision
of earthing arrangements to ensure the continuity of
safety measures, for example, if a connection is made
to another source of supply, whilst work is in progress,
then additional earths would be necessary as work
proceeds.
provision of one electrode result in not meeting the
20 Ω requirement other earth electrodes equally spaced
along the circuit have to be installed. Alternatively, the
earth electrode may be omitted if it is possible to
connect the neutral at the ultimate unit to a neutral
connected to a different supply system.
There are two further possibilities that may arise:
a)
where the supply system is TN-C but where
the lighting authority wishes to use SNE cable
in the installation and does not wish to use the
supply authority’s CNE conductor as a fault
path, and
b) where the supply authority does not provide
an earth terminal.
Safety earthing equipment may be available as
permanent equipment, such as earthing switches, as part
of permanent equipment such as provision for integral
earthing of a circuit breaker, or as portable earthing
equipment such as portable earthing leads. All such
equipment needs to receive regular maintenance and
should be inspected before use.
36.5 In both of these cases, the lighting authority should
provide its own protective earthing electrode and the
system will be the TT-system. Care is necessary to
ensure that both the initial and continuing impedance
of the fault path is sufficiently low to ensure the
operation of the protective device on the occurrence of
a fault in the fixtures. The neutral earth electrode at the
supply transformer is an important part of the fault loop
but its resistance to earth is not under the control of the
lighting authority. In such circumstances, consideration
should be given to the use of residual current devices
to ensure disconnection of faulty equipment.
Wherever possible, initial earthing should be carried
out via a circuit-breaker of other suitable fault-rated
device.
Earthing leads should, in every case, be of adequate
cross-sectional area to carry with safety, during the time
of operation of the protectiveNo: devices, the maximum
short-circuit current that may flow under fault
conditions. If possible, they should either be flexible,
braided or stranded bare copper conductors or
aluminium conductors suitably protected against
corrosion and mechanical damage.
The use of metallic street light columns or the metal
carcasses of control units, etc, as protective earth
electrodes is not recommended.
In no case, even for the earthing of light current
equipment (for example, high voltage testing
equipment), should the cross-sectional area of the
earthing lead be less than 6 mm2.
37 EARTHING OF CONDUCTORS FOR SAFE
WORKING
It has been found in some cases that a 70 mm2 copper
equivalent earthing lead is the largest that can be
conveniently handled. In such cases, where a larger size
of lead is necessary to carry with safety, the maximum
short-circuit current that can occur, it may be necessary
to use a number of leads of 70 mm2 or other suitable
size in parallel.
37.1 General
This clause deals only with the broad principles of the
earthing of conductors for safety purposes. It is intended
to cover the safety earthing of both light and heavy
current equipment and is generally applicable to high
voltage equipment; however, in some circumstances it
may, where required, be applied as an additional safety
feature to low voltage equipment. Where applicable,
the use of safety earths should be part of overall safe
system of work, which will include isolation, locking
off, permits to work or similar documents and liaison
between parties in control of the supplies and in control
of the work. To ensure that a safe system of work is
clearly set out, a set of detailed rules and procedures
will be necessary in each particular case.
Before earthing leads are applied, it should be verified
that the circuit is dead and, where applicable, a test by
means of a suitable type of voltage indicator should be
applied (the indicator itself being tested immediately
before and after verification) before applying earth
connections.
Earthing leads should first be efficiently bolted or
clamped to the permanent earthing system or to a
substantial electrode of low resistance. Should no
convenient permanent earth electrode be readily
available, a substantial copper earth-spike driven well
into the ground can be utilized to provide a quick and
convenient temporary earth electrode.
37.2 Safety Earthing
When maintenance or repair work, etc, is to be
undertaken on or near to high voltage apparatus or
conductors, precautions in connection with safety
earthing should be taken generally as indicated below.
87
IS 3043 : 2018
Whilst such a spike is not generally adequate as a
primary safety earth, it will give a degree of protection
against energizing by induction.
37.4 Precautions Relating to Overhead Lines
After a line has been made dead, isolated, discharged
and earthed at all points of supply, a working earth
should be securely attached to each phase of the line at
the point or points where work is to be carried out.
Earthing leads should then be securely bolted or
clamped to apparatus of conductors to be worked on
and these connections should be removed in all cases
before the earthing leads are disconnected from the
earth electrode or earthing system.
The provision of a working earth entails a connection
to a continuous earth wire or to a temporary earth
electrode, the resistance of which need not be low. The
application of earths to all phase conductors will, in
addition to earthing the conductors, apply a short-circuit
to all phases.
A suitable insulated earthing pole or device should be
used to apply earthing leads to apparatus or conductors
on which work is to be undertaken.
Earthing leads should be kept as short as possible and
be placed in such a position that they cannot be
accidently disconnected or disturbed whilst work is in
progress.
The connection of the earthing lead to each conductor
of the overhead line should be made using a suitable
mechanical clamp placed round the conductor by means
of an insulated earthing pole which can also be utilized
to secure the clamp tight round the line conductor. When
it is required to remove the working earth from the line,
the mechanical clamp can be unscrewed and released
from the conductor by means of this rod. Even when
an overhead line is earthed at each point of supply, it is
necessary to place a working earth at each and every
position where work is being carried out on the line on
account of the danger of the line becoming energized
by induction from other power lines and to safeguard
against the charging of the line by atmospheric
disturbances. Where the work entails breaking a
conductor, for example, on the jumper at a sectioning
point, it is necessary to provide a working earth on both
sides of the working point.
37.3 Precautions Relating to Apparatus and Cables
In the case of switchgear, phases of the section in which
the work is to be done should be short-circuited and
earthed to the same earthing system. Self-contained or
portable apparatus is generally available for this
purpose. Wherever possible, automatic tripping features
of circuit breakers should be rendered inoperative by
being disconnected from the tripping battery before the
circuit-breaker is closed and the breaker operating
mechanism should be locked in the closed position.
With transformers, if there is any possibility of any
winding becoming inadvertently live, the terminals of
all windings should be earthed so that no danger from
shock can occur. When the neutral points of several
transformers are connected to a common bar, which is
then earthed through a resistance of an arc suppression
coil, the neutral point of any transformer that is to be
worked on should be disconnected and directly earthed
as well as the phase terminals.
37.5 Safety Earthing of Low Voltage Conductors
In some circumstances, it may be necessary to apply
safety earthing to low voltage conductors in order to
prevent danger. Such circumstances may include, for
example, work on capacitors or work on bare overhead
crane trolley wires. Where the earthing of low voltage
conductors is adopted, then the general principles set
out in 37.2, 37.3 and 37.4 should be applied and due
consideration should be taken of fault current levels
(which can be as high or higher than on high voltage
systems), when the size of earth conductor is chosen.
When liquid earthing resistors are to be worked on,
particularly when they are drained for work inside, the
central electrode should be shorted to the tank and not
earthed remotely. This is especially important where
two liquid resistors are located side-by-side and one
remains in commission while the other is opened for
maintenance.
38 MAINTENANCE OF EARTH ELECTRODES
38.1 It is recommended that periodical check tests of
all earth electrodes should be carried out. Records
should be maintained of such checks.
When work is to be carried out on equipment that is
capable of capacitively storing electrical energy, for
example, cables and capacitors, such equipment has to
be discharged to earth prior to work commencing. As,
in some circumstances, charge can reappear on such
apparatus without reconnecting it to a source of supply,
it is important work that the equipment should remain
earthed whilst is in progress. The cutting of a cable
during the course of work may disconnect conductors
from safety earths and precautions should be taken to
prevent this happening.
38.2 Where earth-leakage circuit-breakers are
employed, a check shall be kept on the associated earthelectrode by periodically operating the testing device
which is embodied in the earth leakage circuit-breaker.
38.3 The neighbouring soil to the earth electrode shall
be kept moist, where necessary, by periodically pouring
water through a pipe where fitted alongwith it or by
88
IS 3043 : 2018
pouring water in the immediate vicinity of the earth
electrode.
voltage of the system.
In low-resistance grounded systems, the resistor current
is approximately equal to the current in the fault. Thus
the current is practically equal to the line-to-neutral
voltage divided by the resistance in ohms. This simple
method is only suitable when the earth fault current is
small compared to 3-phase fault current.
38.4 Substations and Generating Stations
38.4.1 Records shall be kept of the initial resistance of
substation and generating station earth electrodes and
of subsequent tests carried out.
38.4.2 Normally annual measurement of earth
resistance of substation shall be carried out but local
circumstances in the light of experience may justify
increase or decrease in this interval but it should not be
less than once in two years.
39.2 In a resistance-earthed system with a single lineto-earth fault, the earth fault current may be computed
from:
Ig =
38.4.3 Periodical visual inspection of all earth electrode
connection, wherever available, shall be carried out to
ensure their rigidity and other signs of deterioration.
3E
X 1 × X 2 + X 0 + 3 ( X n + X GP )
where
Ig = earth fault current in A,
X1 = system + ve sequence reactance in Ω/phase
including the subtransient reactance of the
rotating machines,
X2 = –ve sequence reactance as for X1,
X0 = zero sequence reactance as for X1,
Xn = reactance of neutral grounding reactor,
XGP = reactance of ground return circuits, and
E = line-to-earth voltage in V.
In most industrial and commercial systems without
inplant generator X2 = X1.
38.4.4 In rural substations, particularly those connected
to overhead high-voltage and low-voltage lines, greater
reliance should be placed on the electrode system, and
therefore facilities for testing the resistance of the
electrode to general mass of earth, annually or as
required by experience, should be provided.
38.4.5 Where installations are earthed to a metal sheath
of the supply cable, it shall be verified periodically that
the earth-fault loop is in a satisfactory state.
38.4.6 Where an installation is earthed to a cable sheath
which is not continuous to the substation neutral (that
is, there is an intervening section of overhead line
without earth wire), a supplementary electrode system
may be necessary. The adequacy of the electrode system
shall be checked initially by an earth-fault loop test.
39.3 Solid Earthing
39.3.1 In this case, the fault current can be computed
from:
38.4.7 The neighbouring soil to the earth electrode shall
be kept moist, where necessary by periodically pouring
water through a pipe where fitted alongwith it or by
pouring water in the immediate vicinity of the earth
electrode.
Ig =
3E
X 1 × X 2 + X 0 + 3 X GP
40 MEASUREMENT OF EARTH RESISTIVITY
40.1 Resistivity of the Soil
39 CALCULATION OF EARTH FAULT
CURRENTS
40.1.1 The resistivity of the earth varies within
extremely wide limits, between 1 and 10 000 ohm
metres. The resistivity of the soil at many station sites
has been found to be non-uniform. Variation of the
resistivity of the soil with depth is more predominant
as compared to the variation with horizontal distances.
Wide variation of resistivity with depth is due to
stratification of earth layers. In some sites, the resistivity
variation may be gradual, where stratification is not
abrupt. Highly refined techniques for the determination
of resistivity of homogeneous soil are available. To
design the most economical and technically sound
grounding system for large stations, it is necessary to
obtain accurate data on the soil resistivity and on its
variation at the station site. Resistivity measurements
at the site will reveal whether the soil is homogeneous
or non-uniform. In case the soil is found uniform,
39.0 General
The magnitude of the current that will flow in the event
of a line-to-earth fault on an earthed system is
determined by the impedance from the source to the
fault plus the impedance of the earth return path,
including the impedances of earthing transformers,
resistors and reactors (see IS 13234). For
interconnected systems, the calculation of the current
may be complicated.
39.1 Resistance Earthing
39.1.1 When a single line-to-earth fault occurs on a
resistance grounded system, a voltage appears across
the resistor nearly equal to the normal line-to-neutral
89
IS 3043 : 2018
conventional methods are applicable for the
computation of earth resistivity when the soil is found
non-uniform, either a gradual variation or a two-layer
model may be adopted for the computation of earth
resistivity.
ρ =
2π sV
I
….(8)
40.3.1.2 Earth testers normally used for these tests
comprise the current source and meter in a single
instrument and directly read the resistance. The most
frequently used earth tester is the four-terminal megger
shown in Fig. 47. When using such a megger, the
resistivity may be evaluated from the modified equation
as given below:
40.1.2 The resistivity of earth varies over a wide range
depending on its moisture content. It is, therefore,
advisable to conduct earth resistivity tests during the
dry season in order to get conservative results.
ρ = 2ρ × s R
40.2 Test Locations
… (9)
40.2.1 In the evaluation of earth resistivity for
substations and generating stations, at least eight test
directions shall be chosen from the centre of the station
to cover the whole site. This number shall be increased
for very large station sites of the test results obtained
at various locations show a significant difference,
indicating variations in soil formation.
where
ρ = resistivity of soil in ohm-metres,
s = distance between successive electrodes in
metres, and
R = megger reading in ohms.
40.2.2 In case of transmission lines, the measurements
shall be taken along the direction of the line throughout
the length approximately once in every 4 km.
40.4.1 At the selected test site, in the chosen direction,
four electrodes are driven into the earth along a straight
line at equal intervals, s. The depth of the electrodes in
the ground shall be of the order of 10 to 15 cm. The
megger is placed on a steady and approximately level
base, the link between terminals P1 and C1 opened and
the four electrodes connected to the instrument
terminals as shown in Fig. 47. An appropriate range on
the instrument is thus selected to obtain clear readings
avoiding the two ends of the scale as far as possible.
The readings are taken while turning the crank at about
135 rev/min. Resistivity is calculated by substituting
the value of R thus obtained in the Equation (9). In
case where depth of burial is more than l/20th of
spacing, Equation (7) should be used instead of
Equation (9).
40.4 Test Procedure
40.3 Principle of Tests
40.3.1 Wenner’s four electrode method is recommended
for these types of field investigations. In this method,
four electrodes are driven into the earth along a straight
line at equal intervals. A current I is passed through the
two outer electrodes and the earth as shown in Fig. 47
and the voltage difference V, observed between the two
inner electrodes. The current I flowing into the earth
produces an electric field proportional to its density
and to the resistivity of the soil. The voltage V measured
between the inner electrodes is, therefore, proportional
to the field. Consequently, the resistivity will be
proportional to the ratio of the voltage to current. The
following equation holds for:
40.4.2 Correction for Potential Electrode Resistance
In cases where the resistance of the potential electrodes
(the two inner electrodes) is comparatively high, a
correction of the test results would be necessary
depending on its value. For this purpose, the instrument
is connected to the electrodes as shown in Fig. 48. The
readings are taken as before. The correction is then
effected as follows.
4sπ V
I
ρ=
1+
2s
2
s + 4e
2
−
2s
2
4 s + 4e
….(7)
2
where
ρ
s
V
I
e
= resistivity of soil in ohm-metre,
= distance between two successive electrodes
in metres,
= voltage difference between the two inner
electrodes in Volts,
= current flowing through the two outer
electrodes in amperes, and
= depth of burial of electrode in metres.
40.4.2.1 Let the readings of the megger be Rp with the
connections as shown in Fig. 48 and the electrode
spacing in metres. If the uncorrected value of soil
resistivity is r‘ and the resistance of the voltage circuit
of the instrument used to obtain R (as indicated inside
the scale cover of the meter) is Rv, the corrected value
of the earth resistivity would be:
ρ =
40.3.1.1 If the depth of burial of the electrodes in the
ground d is negligible compared to the spacing between
the electrodes, then
90
ρ ′ × ( Rv + Rp )
Rv
IS 3043 : 2018
40.5 Testing of Soil Uniformity
40.5.1 During the course of above tests, it would be
desirable to get information about the horizontal and
vertical variations in earth resistivity over the site under
consideration for the correct computation of the
resistivity to be used in the design calculations. The
vertical variations may be detected by repeating the
tests at a given location in a chosen direction with a
number of different electrode spacings, increasing from
2 to 250 m or more, preferably in the steps 2, 5, 10, 15,
25 and 50 m or more. If the resistivity variations are
within 20 to 30 percent, the soil in the vicinity of the
test location may be considered uniform. Otherwise a
curve of resistivity versus electrode spacing shall be
plotted and this curve further analyzed to deduce
stratification of soil into two or more layers of
appropriate thickness or a soil of gradual resistivity
variation. The horizontal variations are studied by
taking measurements in various directions from the
centre of the station.
F IG. 48 TEST C ONNECTION TO MEASURE THE S UM OF
THE P OTENTIAL E LECTRODE R ESISTANCE
40.6 Computation of Earth Resistivity of Uniform
Soil
40.6.1 When the earth resistivity readings for different
electrode spacings in a direction is within 20 to 30
percent, the soil is considered to be uniform. When the
spacing is increased gradually from low values, at a
stage, it may be found that the resistivity reading is
more or less constant irrespective of the increase in the
electrode spacing. The resistivity for this spacing is
noted and taken as the resistivity for that direction. In a
similar manner, resistivities for at least eight equally
spaced directions from the centre of the site are
measured. These resistivities are plotted on a graph
sheet in the appropriate directions choosing a scale. A
closed curve is plotted on the graph sheets jointing all
the resistivity points plotted to get the polar resistivity
curve. The area inside the polar resistivity curve is
measured and equivalent circle of the same area is found
out. The radius of this equivalent circle is the average
resistivity of the site under consideration. The average
resistivity thus obtained may be used for the design of
the earthing grid and other computations and the results
will be reasonably accurate when the soil is
homogeneous (see Fig. 49).
FIG. 49 POLAR CURVE
40.7 One Rod Test Method
This is a simpler test than the full Wennner test and
may be used for distribution substations. The resistance
of a single rod that is driven into the ground for a known
depth should be measured. The resistance measurement
and rod dimensions may then be used to calculate the
average soil resistivity required to produce the
measured resistance. The resistance measurement may
be made using the 61.8 percent method. The formula
for calculating the resistance to earth R of a vertical
rod given may be used:
R=
where
R
L
d
ρ
=
=
=
=
ρ
8L
log e − 1
2π L
d
the resistance to earth of a vertical rod;
the length of the electrode, in metres (m);
the diameter in metres (m);
the resistivity of the soil (assumed uniform),
in ohm metres (Ω.m);
Hence
ρ=
2π RL
8L
log e − 1
d
For most distribution substations it is sufficient to drive
the rod to a depth of 2.4 m and use this reading as the
average soil resistivity value (see Fig. 50)
F IG. 47 CONNECTIONS FOR A FOUR -TERMINAL MEGGER
91
IS 3043 : 2018
FIG. 50 ONE ROD S OIL R ESISTIVITY MEASUREMENT
41 MEASUREMENT OF EARTH ELECTRODE
RESISTANCE
41.1 Fall of Potential Method
In this method two auxiliary earth electrodes, besides
the test electrode, are placed at suitable distances from
the test electrode (see Fig. 51). A measured current is
passed between the electrode A to be tested and an
auxiliary current electrode C and the potential
difference between the electrode A and the auxiliary
potential electrode B is measured.
A number of different test methods may be used to
measure a site’s overall resistance which are based on
a fall of potential (FOP) technique. There are situations,
typically in urban areas, where the earth electrode
resistance may not be directly measures practicably.
Alternative methods of assessing the earth resistance
may include computer simulations carried out by
earthing specialists.
The resistance of the test electrode A is then given by:
However, in general the following common test
methods may be used:
R=
V
I
where
R = resistance of the test electrode in ohms,
V = reading of the voltmeter in Volts, and
I = reading of the ammeter in amperes.
41.1.1 If the test is made at power frequency, that is,
50 c/s, the resistance of the Voltmeter should be high
compared to that of the auxiliary potential electrode B
and in no case should be less than 20 000 ohms.
a)
Fall of potential 61.8 percent test — This test
is suitable for simple earth electrode systems
such as found in LV installations and in 11 kV
distribution substations.
b) Fall of potential 61.8 percent test — Test using
a clamp on CT — This test is similar to the
standard 3 terminal FOP test and has the
advantages that it may be used to measure the
resistance of a system without disconnecting
the earthing and can measure the resistance
of an individual electrode (again without
disconnecting).
c) Fall of potential — Slope test — This test is
recommended for earth electrode networks
covering large areas, such as grid and primary
substations sites, but may be used elsewhere
if required.
d) Fall of potential — 90°/180° test — This test
is used in conjunction with the 61.8 percent
or slope method to verify the results obtained.
NOTE — In most cases, there will be stray currents flowing in
the soil and unless some steps are taken to eliminate their effect,
they may produce serious errors in the measured value. If the
testing current is of the same frequency as the stray current,
this elimination becomes very difficult and it is better to use an
earth tester incorporating a hand-driven generator. These earth
testers usually generate direct current, and have rotary currentreverser and synchronous rectifier mounted on the generator
shaft so that alternating current is supplied to the test circuit
and the resulting potentials are rectified for measurement by a
direct reading moving-coil ohm-meter. The presence of stray
currents in the soil is indicated by a wandering of the instrument
pointer, but an increase or decrease of generator handle speed
will cause this to disappear.
92
IS 3043 : 2018
FIG. 51 METHOD OF MEASUREMENT OF E ARTH ELECTRODE RESISTANCE
41.1.2 The source of current shall be isolated from the
supply by a double wound transformer.
To obtain reliable readings the current probe should be
in a straight line with the earth system under test.
41.1.3 At the time of test, where possible, the test
electrode shall be separated from the earthing system.
A 90° / 180° test should be carried out to check the
results.
41.1.4 The auxiliary electrodes usually consist of
12·5 mm diameter mild steel rod driven up to 1 m into
the ground.
A 50 m separation between the earth grid and the probe
may be used and is usually adequate for smaller earth
systems and the resistance measured is equal to the true
value when the voltage probe is positioned at 61.8
percent of the distance between the earth electrode and
the current probe. If the earth electrode system is of
medium size containing rods, then these distances
should be increased (see Table 17 for guidance).
41.1.5 All the test electrodes and the current electrodes
shall be so placed that they are independent of the
resistance area of each other. If the test electrode is in
the form of rod, pipe or plate, the auxiliary current
electrode C shall be placed at least 30 m away from it
and the auxiliary potential electrode B midway between
them.
To confirm the accuracy of the first reading the voltage
probe should be moved to the 50 percent and 70 percent
positions and additional readings taken.
41.1.6 Fall of Potential 61.8 Percent Test
41.1.7 Testing the Resistance of Specific Electrodes
Using a CT Clamp Tester
The 61.8 percent test is the recommended test
procedure for small earth electrode systems where the
electrical centre of the earth system is known,
particularly ground mounted distribution substations
and pole mounted transformers.
Certain test instruments that may be used incorporate a
CT which clamps around the electrode to be tested.
Figure 52 shows a 3-terminal test with CT clamp. The
CT may be used to detect the test current returning via
that specific electrode and allows the resistance of the
electrode to be measured without disconnecting it from
the rest of the earth system.
However, if the resistance of a particular electrode is
required, a CT clamp tester must be used as any cables
connected to the earth grid contributes to the connection
with earth.
Table 17 61.8 Percent Test Probe for Various Grid Sizes
(Clause 41.1.6)
Maximum Dimension of
Earth Grid Under Test
m
(1)
Distance to Current
Electrode from
Centre of Earth
System
m
(2)
50 Percent
Distance
m
(3)
61.8 percent Distance
to Voltage Electrode
from Centre of Earth
System
m
(4)
70 Percent
Distance
37
m
(5)
Small or single electrode
50
25
31
5
100
50
62
70
10
150
75
93
105
20
200
100
124
140
93
IS 3043 : 2018
This test may be used where an electrode is connected
to an earthing system with a much lower overall
resistance than the electrode in question. In effect this
test may be used to measure the loop impedance of the
electrode under test and the rest of the system, it is
connected to.
Critical data points should be measured with the
potential probe placed at 0.2, 0.4 and 0.6 times the
distance to the current probe, at points R1, R2 and R3
respectively.
The slope of coefficient ì showing the rate of change
of slope, can be calculated by:
This may be used to give an approximate resistance
value for the electrode when compared to previous
results, gives an indication of any deterioration of the
electrode. This test may also be used for measuring the
resistance of deep high frequency earth rods when
connected to a larger earth system.
µ=
R3 − R2
R2 − R1
41.1.9 90°/180° Test
This technique should be used in conjunction with the
slope or 61.8 percent method to verify the results
obtained. The test equipment should be set up as shown
in Fig. 53.
The current probe C2 should be positioned as far as
away from the earthing system under test as practicable
and the voltage probe P2 should be positioned at an
angle between 90º / 180º to the current electrode route.
1 — Earth Tester
2 — Installation
A number of tests are carried out at say 0.2dc, 0.4dc,
and 0.6dc. When the graph is drawn, it ought to level
off, but never quite reach the true resistance value; by
extrapolating, the true value may be estimated
(see Fig. 54).
3 — Current Measuring Clamp
4 — Electrode
FIG. 52 3-TERMINAL TESTER WITH CT CLAMP
41.2 Alternative Method
41.1.8 Fall of Potential — Slope Method
41.2.1 The method described in 40.1 may not give
satisfactory results if the test electrode is of very low
impedance (one ohm or less). This applies particularly,
while measuring the combined resistance of large
installations. In these cases, the following method may
be adopted.
NOTE — A large earthing grid, such as underlies a substation
or encircles a transmission tower, has a commensurately large
electric field in the soil. Locating a current test probe beyond
this influence can typically require several hundred feet, which
might be quite impractical. Also the electrical centre of the
earthing system cannot be known if the current probe is not far
enough away, the plotted graph will show the rising resistance
curve associated with the grid running directly into the curve
from the test probe. The slope method permits an estimate of
where the resistance of the electrode under test maximizes.
41.2.2 Two suitable directions, at least 90º apart, are
first selected. The potential lead is laid in one direction
and an electrode is placed 250 to 300 m from the fence.
The current lead is taken in the other direction and the
NOTE—Rest if earth network overall resistance is 0.5Ω.
KEY
1 — Instrument (Reading 10.5 Ω)
2 — Substation
FIG. 53 CLAMP -ON TESTER
94
IS 3043 : 2018
NOTE — Underground metallic objects or cables can produce a misshaped graph which might lead to false results.
FIG. 54 90°/180° TEST
current electrode located at the same distance as the
potential electrode. A reading is taken under this
condition. The current electrode is then moved out in
30-m steps until the same reading is obtained for three
consecutive locations. The current electrode is then left
in the last foregoing position and the potential electrode
is moved out in 30-m steps until three consecutive
readings are obtained without a change in value. The
last reading then corresponds to the true value of earth
resistance.
earth electrodes at consumer’s premises, and substations
and any parallel metallic return to the transformer
neutral as well as the transformer winding. To test the
overall earthing for any installation, depending for
protection on the operation of overcurrent devices, for
example, fuses, it is necessary to measure the impedance
of this loop under practical fault conditions. After the
supply has been connected, this shall be done by the
use of an earth loop impedance tester. The neutral is
used in place of the phase conductor for the purpose of
the test. The open-circuit voltage of the loop tester
should not exceed 32 V.
42 MEASUREMENT OF EARTH LOOP
IMPEDANCE
43 EARTHING REQUIREMENTS FOR
INSTALLATIONS OF DATA PROCESSING
EQUIPMENT
42.1 The current, which will flow under earth fault
conditions and will thus be available to operate the
overload protection, depends upon the impedance of
the earth return loop. This includes the line conductor,
fault, earth-continuity conductor and earthing lead,
43.1 General
43.1.1 This clause covers the special requirements for
95
IS 3043 : 2018
the connection of data processing equipment to the
electrical power installation of buildings, where the data
processing equipment has earth leakage current
exceeding the limit specified in IS 13252 for equipment
connected via a plug and socket.
43.2 Terminology
43.2.1 Data Processing Equipment
Electrically operated machine units that separately or
assembled in systems, accumulate, process and store
data. Acceptance and divulgence of data may or may
not be electronic means.
These requirements are intended to ensure the safety
of personal in the presence of such leakage current.
43.2.2 Low Noise Earth
These rules apply to the installation up to the point of
connection of the equipment as shown in Fig. 55.
An earth connection in which the level of conducted
interference from external sources does not produce
an unacceptable incidence of malfunction in the data
processing or similar equipment to which it is
connected.
These rules do not consider installations for which the
influence of lightning phenomena may exist.
These rules do not consider the interconnection of
equipment on different supply and earthing systems by
data transmission lines.
NOTE — The susceptibility in terms of amplitude/ frequency
characteristics varies depending on the type of equipment.
43.1.2 The requirements of this clause may also be
applied where installations, other than data processing
such as those for industrial control and
telecommunications equipment, carry high leakage
current due to radio-frequency interference suppression
filtering requirements.
43.2.3 High Leakage Current
Earth leakage current exceeding the limit specified in
IS 13252 for equipment connected via a plug and
socket.
43.2.4 General Installation Requirements
NOTE — Radio-frequency interference suppression filters fitted
to data processing equipment may produce high earth leakage
current. In such cases, failure of continuity in the protective
earth connection may cause a dangerous touch voltage. The
main purpose of this Code is to prevent this hazard.
The requirements of this clause apply where equipment
having high leakage current is connected to any type
of power system. The requirements apply to the
installation as shown in Fig. 55.
F IG. 55 EQUIPMENT-I NSTALLATION BOUNDARIES
96
IS 3043 : 2018
having electrical continuity according to
relevant Indian Standard specification on
conduits for electrical purposes, a conductor
of not less than 2.5 mm2 shall be used; and
d) Rigid and flexible metallic conduits, metallic
ducting and metallic screens, and armouring
which meet the requirements of 14 to 23.
Additional requirements are given for IT and TT systems
in 43.2.4.4 and 43.3.
NOTES
1 On TN-C Systems, where the neutral and protective conductors
are contained in a single conductor (PEN conductor) up to the
equipment terminals, leakage current may be treated as load
current.
2 Equipment normally having high earth leakage current may
not be compatible with installations incorporating residual
current protective devices, as well as the standing residual
current due to leakage current. The possibility of nuisance
tripping due to capacitor charging currents at switch-on shall
be considered.
Each conductor specified in (a), (b), (c) and (d) shall
meet the requirements of 14 to 23.
43.2.4.2 Earth integrity monitoring
A protective device shall be provided which will
disconnect the equipment, in the event of a discontinuity
occurring in the earth conductor, within the voltage/
time limits prescribed by relevant standards.
Equipment shall be:
a) stationary, and
b) Either permanently connected to the building
wiring installation or connected via industrial
plugs and sockets.
The protective conductors shall comply with 14 to 23.
NOTE — The aim of the requirements detailed above is to
monitor the continuity of the protective earth connection and
provided means of automatic supply disconnection in case of
failure.
NOTES
1 Industrial plugs and sockets are examples of suitable
plugs and sockets. Plugs and sockets for general use are
not suitable.
2 It is particularly important for equipment with high
leakage current that earth continuity should be checked
at the time it is installed and after any modification to
the installation.
43.2.4.3 Use of double wound transformer
Equipment shall be connected to the supply via a double
wound transformer of other units in which the input
and output circuits are separated, such as motoralternator sets (see 44).
It is also recommended that earth continuity be checked
thereafter at regular intervals.
The secondary circuit should preferably be connected
as a TN-System but an IT-System may be used where
required for the specific application.
Additionally, where leakage current measured in
accordance with IS 13252 exceeds 10 mA, equipment
shall be connected in accordance with one of the three
alternative requirements detailed in 43.2.4.1 to 43.2.4.3.
NOTE — The aim of the requirements above is to localize the
path of the leakage current, and minimize the possibility of a
break in continuity in this path.
NOTE — Leakage current measurements prescribed by
IS 13252 include likely undetected fault conditions within the
equipment.
43.2.4.4 Additional requirements for TT- system
43.2.4.1 High integrity earth connections
The requirements below ensure that the leakage in
normal operation of all equipment protected by one
and the same protective device is less than half of that
required to operate earth fault protective devices for
the installation circuit.
NOTE — The aim of the requirements detailed below is to
provide high integrity earth connections by using robust or
duplicate conductors in association with permanent connections
or robust connectors.
Protective conductors shall comply with the following:
a)
The total leakage current I1 (in amperes), the
resistance of the earth electrode RA (in ohms)
and the nominal operating residual current of
the protective device I∆n (in amperes) shall be
related as follows:
I∆
U
I1 n ≤ L
2
2 RA
b) If the requirements of (a) cannot be met, the
requirements of 42.2.4.3 shall apply.
a)
Where independent protective conductors are,
there shall be one conductor with a crosssectional area of not less than 10 mm2 or two
conductors with independent terminations,
each having a cross-sectional area of not less
than 4 mm2;
b) When incorporated in a multicore cable
together with the supply conductors, the sum
total cross-sectional area of all the conductors
shall be not less than 10 mm 2 and the
protective conductors shall comply with 14
to 23;
c) Where the protective conductor is installed in,
and connected in parallel with a metal conduit
43.3 Additional Requirements for IT-Systems
43.3.1 It is preferred that equipment with high leakage
current is not connected directly to IT -systems because
of the difficulty of satisfying touch voltage requirements
on a first fault.
97
IS 3043 : 2018
Where possible, the equipment is supplied by a TNsystem derived from the mains supply by means of a
double wound transformer.
43.4.2 Other Special Methods
In extreme cases, if the safety requirements of 43.4.1
are fulfilled but electrical noise on the main earthing
terminal of the installation cannot be reduced to an
acceptable level, the installation has to be treated as a
special case.
Where it is possible, the equipment may be connected
directly to the equipment may be connected directly to
the IT-system. This may be facilitated by connecting
all protective earth connections for equipment using
the IT-system directly to the power system earth
electrode.
The earthing arrangement has to provide the same level
of protection as is generally provided by these
requirements and particular attention should be given
to ensure that the arrangement:
43.3.2 Before making direct connection to an IT-system,
installers shall ensure that equipment is suitable for
connection to IT - systems according to the declaration
of the manufacturer.
a)
provides adequate protection against
overcurrent;
b) prevents excessive touch voltages on the
equipment and ensures equipotential between
the equipment and adjacent metal work or
other electrical equipment, under normal and
fault conditions; and
c) meets the requirements relating to excessive
earth leakage current, if appropriate, and does
not invalidate them.
43.4 Safety Requirement for Low Noise Earthing
Connections
NOTE — It may be found that the electrical noise levels on the
protective earthing system of building installations cause an
unacceptable incidence of malfunction on data processing
equipment connected to it.
43.4.1 Whatever measures are taken to provide a lownoise earthing connection, it is required that exposed
conductive parts of data processing shall be connected
to the main earthing terminal.
44
EXAMPLE
TRANSFORMERS
OF
THE
USE
OF
NOTE — The use of separate earth electrodes for simultaneously
accessible exposed conductive parts is not permitted.
44.1 Transformer Incorporated in or Attached to
Unit
This requirement shall also apply to metallic enclosures
of Class II and Class III equipment, and to FELV
circuits when these are earthed for functional reasons.
The transformer shall be connected in accordance with
Fig. 56 in order to confine the earth leakage current in
conductors within the unit.
Earth conductors, which serve functional purposes only,
need not comply with 14 to 23.
NOTE — No further special installation measures are necessary.
Single phase system depicted for ease. System may be 3-phase.
Protection and control arrangements are not shown.
C is the filter capacitance.
L1 and L2 or N are connections to the incoming supply and PE is the connection from accessible parts of the equipment to the main
earthing terminal of installation for both protective conductors of Class I equipment and functional earthing conductors for Class II
equipment.
FIG. 56 METHODS OF CONNECTING DOUBLE-WOUND TRANSFORMERS SITUATED WITHIN OR
ATTACHED TO SINGLE UNITS
98
IS 3043 : 2018
connections between the equipment and the transformer
shall comply with the requirements of 43.2.4.1 or
43.2.4.2.
44.2 Method of Connecting Transformers Physically
Separate from Units
The neutral point for the secondary circuit shall be
connected to earth at the transformer and the earth
Connections shall be as shown in Fig. 57.
Single-phase system depicted for ease. System may be 3-phase.
Primary and secondary circuits must have means of control and protection. These are not shown.
C is the filter capacitance.
L1 and L2 or N are connections to the incoming supply and PE is the connection from accessible parts of the equipment to the main
earthing terminal of the installation for both protective conductors of Class I equipment and functional earthing conductors of Class II
equipment.
FIG. 57 METHOD OF CONNECTING PHYSICALLY S EPARATED TRANSFORMERS
99
Bureau of Indian Standards
BIS is a statutory institution established under the Bureau of Indian Standards Act, 2016 to promote
harmonious development of the activities of standardization, marking and quality certification of goods
and attending to connected matters in the country.
Copyright
BIS has the copyright of all its publications. No part of these publications may be reproduced in any form
without the prior permission in writing of BIS. This does not preclude the free use, in the course of
implementing the standard, of necessary details, such as symbols and sizes, type or grade designations.
Enquiries relating to copyright be addressed to the Director (Publications), BIS.
Review of Indian Standards
Amendments are issued to standards as the need arises on the basis of comments. Standards are also reviewed
periodically; a standard along with amendments is reaffirmed when such review indicates that no changes are
needed; if the review indicates that changes are needed, it is taken up for revision. Users of Indian Standards
should ascertain that they are in possession of the latest amendments or edition by referring to the latest issue of
‘BIS Catalogue’ and ‘Standards : Monthly Additions’.
This Indian Standard has been developed from Doc No.: ETD 20 (6667).
Amendments Issued Since Publication
Amend No.
Date of Issue
Text Affected
BUREAU OF INDIAN STANDARDS
Headquarters:
Manak Bhavan, 9 Bahadur Shah Zafar Marg, New Delhi 110002
Telephones : 2323 0131, 2323 3375, 2323 9402
Website: www.bis.org.in
Telephones
Regional Offices:
Central
: Manak Bhavan, 9 Bahadur Shah Zafar Marg
NEW DELHI 110002
Eastern
: 1/14 C.I.T. Scheme VII M, V. I. P. Road, Kankurgachi
KOLKATA 700054
{
2323 7617
2323 3841
{
{
Northern : Plot No. 4-A, Sector 27-B, Madhya Marg, CHANDIGARH 160019
Southern : C.I.T. Campus, IV Cross Road, CHENNAI 600113
Western
: Manakalaya, E9 MIDC, Marol, Andheri (East)
MUMBAI 400093
2337 8499, 2337 8561
2337 8626, 2337 9120
26 50206
265 0290
{
{
2254 1216, 2254 1442
2254 2519, 2254 2315
2832 9295, 2832 7858
2832 7891, 2832 7892
Branches: A H M E D A B A D . B E N G A L U R U . B H O PA L . B H U B A N E S WA R . C O I M B AT O R E .
D E H R A D U N . D U R G A P U R . FA R I D A B A D . G H A Z I A B A D . G U WA H AT I .
HYDERABAD. JAIPUR. JAMMU. JAMSHEDPUR. KOCHI. LUCKNOW. NAGPUR.
PA RWA N O O . PAT N A . P U N E . R A I P U R . R A J K O T. V I S A K H A PAT N A M .
Published by BIS, New Delhi