Guide to the IET Wiring Regulations: IET Wiring Regulations (BS 7671:2008 incorporating Amendment No 1:2011)
4/5
()
About this ebook
This revised edition features:
- new material on hot topics such as electromagnetic compatibility (EMC), harmonics, surge protective devices, and new special locations including medical locations, and operative or maintenance gangways;
- highlights the changes that have been made in this latest Amendment and their impact in practice;
- examples of how to comply with the Wiring Regulations;
- fully-integrated colour including sixty brand new colour illustrations, twenty tables and new high-quality photographs.
This essential guide retains its handy format, ideal for practicing electricians, trainee electricians and apprentices to carry with them for quick reference. It is a valuable resource for all users of BS 7671 who want to understand the background to the Regulations; electrical engineers and technicians, installation and design engineers, consulting and building services engineers, also dedicated inspectors and testers.
Related to Guide to the IET Wiring Regulations
Related ebooks
Audel Electrical Trades Pocket Manual Rating: 0 out of 5 stars0 ratingsFundamentals of Fault Current and Grounding in Electrical Systems Rating: 4 out of 5 stars4/5Electromagnetic Compatibility (EMC) Design and Test Case Analysis Rating: 0 out of 5 stars0 ratingsAudel Electrician's Pocket Manual Rating: 5 out of 5 stars5/5Design of Rotating Electrical Machines Rating: 5 out of 5 stars5/5Practical Power Electronics: Applications, Experiments and Animations Rating: 0 out of 5 stars0 ratingsTransients of Modern Power Electronics Rating: 0 out of 5 stars0 ratingsAudel House Wiring Rating: 3 out of 5 stars3/5Circuitbuilding Do-It-Yourself For Dummies Rating: 0 out of 5 stars0 ratingsPractical Electrical Wiring: Residential, Farm, Commercial, and Industrial Rating: 4 out of 5 stars4/5Electromagnetic Compatibility Engineering Rating: 0 out of 5 stars0 ratingsReference Guide To Useful Electronic Circuits And Circuit Design Techniques - Part 1 Rating: 3 out of 5 stars3/5Distribution of Electrical Power: Lecture Notes of Distribution of Electric Power Course Rating: 0 out of 5 stars0 ratingsPower, Testing, and Grounding of Electronic Systems Rating: 0 out of 5 stars0 ratingsThe Homeowner's DIY Guide to Electrical Wiring Rating: 5 out of 5 stars5/5Electrician''s Guide to Control and Monitoring Systems: Installation, Troubleshooting, and Maintenance Rating: 0 out of 5 stars0 ratingsElectrical Projects for Beginners: New projects for high school students Rating: 0 out of 5 stars0 ratingsElectrician's Pocket Manual Rating: 0 out of 5 stars0 ratingsElectrical Installation Designs Rating: 3 out of 5 stars3/5Electricity and Electronics for HVAC Rating: 0 out of 5 stars0 ratingsNEC® 2008 Need to Know Rating: 0 out of 5 stars0 ratingsSimple, Practical Electronics Rating: 5 out of 5 stars5/5The Engineer's Career Guide Rating: 0 out of 5 stars0 ratingsAudel Practical Electricity Rating: 0 out of 5 stars0 ratingsElectrician's Calculations Manual, Second Edition Rating: 0 out of 5 stars0 ratingsUltimate Guide Wiring, Updated 9th Edition Rating: 5 out of 5 stars5/5Theory on DC Electric Circuits Rating: 0 out of 5 stars0 ratingsElectrical Distribution System of a Skyscraper in the United States Rating: 0 out of 5 stars0 ratingsAutoCAD Electrical 2018 Black Book Rating: 0 out of 5 stars0 ratingsAutoCAD Electrical 2020 Black Book Rating: 5 out of 5 stars5/5
Electrical Engineering & Electronics For You
How to Diagnose and Fix Everything Electronic, Second Edition Rating: 4 out of 5 stars4/5Basic Electricity Rating: 4 out of 5 stars4/5The Homeowner's DIY Guide to Electrical Wiring Rating: 5 out of 5 stars5/5The Innovators: How a Group of Hackers, Geniuses, and Geeks Created the Digital Revolution Rating: 4 out of 5 stars4/5Electrician's Pocket Manual Rating: 0 out of 5 stars0 ratingsBeginner's Guide to Reading Schematics, Third Edition Rating: 0 out of 5 stars0 ratingsElectric Circuits Essentials Rating: 5 out of 5 stars5/5Off-Grid Projects: Step-by-Step Guide to Building Your Own Off-Grid System Rating: 0 out of 5 stars0 ratingsElectricity for Beginners Rating: 5 out of 5 stars5/5The Fast Track to Your Technician Class Ham Radio License: For Exams July 1, 2022 - June 30, 2026 Rating: 5 out of 5 stars5/5Soldering electronic circuits: Beginner's guide Rating: 4 out of 5 stars4/5Understanding Electricity Rating: 4 out of 5 stars4/5Electrical Engineering Rating: 4 out of 5 stars4/5Upcycled Technology: Clever Projects You Can Do With Your Discarded Tech (Tech gift) Rating: 5 out of 5 stars5/5The Electrician's Trade Demystified Rating: 0 out of 5 stars0 ratingsBeginner's Guide to Reading Schematics, Fourth Edition Rating: 4 out of 5 stars4/5Ramblings of a Mad Scientist: 100 Ideas for a Stranger Tomorrow Rating: 0 out of 5 stars0 ratingsDIY Lithium Battery Rating: 3 out of 5 stars3/5Practical Electrical Wiring: Residential, Farm, Commercial, and Industrial Rating: 4 out of 5 stars4/5Basic Electronics: Book 2 Rating: 5 out of 5 stars5/5Raspberry Pi Projects for the Evil Genius Rating: 0 out of 5 stars0 ratingsProgramming Arduino: Getting Started with Sketches Rating: 4 out of 5 stars4/5Raspberry Pi Electronics Projects for the Evil Genius Rating: 3 out of 5 stars3/5Electronic Circuits for the Evil Genius 2/E Rating: 0 out of 5 stars0 ratingsElectrical Engineering | Step by Step Rating: 0 out of 5 stars0 ratingsTHE Amateur Radio Dictionary: The Most Complete Glossary of Ham Radio Terms Ever Compiled Rating: 4 out of 5 stars4/5Off-Grid Projects: Innovative and Practical Projects for Living Off the Grid Rating: 0 out of 5 stars0 ratingsBuild Your Own Electronics Workshop Rating: 4 out of 5 stars4/5How Do Electric Motors Work? Physics Books for Kids | Children's Physics Books Rating: 0 out of 5 stars0 ratings
Reviews for Guide to the IET Wiring Regulations
2 ratings0 reviews
Book preview
Guide to the IET Wiring Regulations - Electrical Contractors' Association (ECA)
A
BS 7671:2008 Amd No. 1:2011 Requirements for Electrical Installations – Introduction and Overview
A 1 Introduction to BS 7671:2008
BS 7671:2008 Requirements for Electrical Installations was published in January 2008, and amendments were incorporated in 2011.
Although the document is a British Standard, it is also known (and jointly labelled as) as the ‘IET Wiring Regulations Seventeenth Edition’.
c01uf002Throughout this book, BS 7671:2008 incorporating Amendment No. 1:2011 is referred to as BS 7671:2008, BS 7671, the Wiring Regulations, the Regulations, the 17th edition or the Standard, depending upon the particular context.
The British National Committee is obliged to publish the technical intent of the CENELEC harmonization documents (HDs). However the committee have gone further and published the HDs verbatim, except where there is a more up to date International Electrotechnical Commission (IEC) standard and, in a few instances, where national circumstances warrant changes.
The general structure of IEC, CENELEC and BS 7671 is illustrated in Figure A 1.1.
Figure A 1.1 Installation standards at International, European and National levels
c01f001001Most of the document originates from CENELEC in ‘harmonized documents’ (HDs). The parent document is known as the HD 60384 series and includes virtually all parts of the installation standard.
Within BS 7671:2008 there are now only a few regulations that are truly ‘UK only’, although some of the CENELEC parts of HD 60384 have been modified, cut, or expanded upon for BS 7671. Some of the appendices of BS 7671 are home grown.
The Wiring Regulations Committee has also used certain parts of the corresponding IEC document IEC 60364, either modified or virtually unmodified.
A list of the parts of the HD 60384 series used in BS 7671:2008 is shown in Table A 1.1.
Table A 1.1 CENELEC HD 60384 and IEC 6-364 documents used in BS 7671:2008.
c01t0031zcic01t0031zci222A 2 Plan and Layout of BS 7671:2008
Most users will not need to concern themselves with the correct terminology for groups of regulations and chapters etc, but an explanation of this has been added for completeness.
Let’s look at a single regulation such as 411.3.2.1 and provide a diagram of the structure.
Taking the first three digits, they relate as follows:
c01uf003The remaining numbers make up the group, sub-set and regulation, but really only the group is of any significance:
c01uf004There are seven parts to BS 7671:2008, they are as follows:
A 3 Overview of Major Changes
Most of the document has remained unchanged compared to the 16th Edition; many changes were due to formal incorporations of CENELEC drafts required for harmonization.
This section gives an overview of technical changes that will lead to a change in practice, or something that you should be aware of. As stated in the preface, the subject of BS 7671 can be very dry and this part of the book has been kept as short as possible. Readers may wish to skip this part of the book and start with the two key Chapters; these being Chapters C and D.
The following overview notes have been included in order of significance.
Chapter 41 – protection Against Electric Shock
Revision to Chapter 41 is probably the most significant made for the 17th Edition.
The whole structure of the chapter has been modified. The familiar terms used in the 16th Edition of ‘direct contact’ and ‘indirect contact’ have been replaced with ‘basic protection’ and ‘fault protection’ respectfully (see Figure A 3.1). This terminology change by itself had ramifications on many other parts of the Regulations and these brought about logistical modifications. The various measurers are termed ‘protective measurers’.
Figure A 3.1 Basic Protection and Fault Protection
c01f003001The structure of Chapter 41 was modified accordingly. Basic protection (insulation and enclosures) was considered something that designers and installers did not actually ‘consider’ and was shunted towards the rear of the chapter. The extremely rare measurers of ‘placing out of reach’, ‘obstacles’, ‘non-conducting locations’, ‘earth free local equipotential bonding’ and electrical separation were shunted further to the rear of the chapter. Thus the main reading in the front end of Chapter 41 is about automatic disconnection.
There have also been changes to protective device disconnection times. There are not any ‘mixed’ disconnection times and disconnection times for TT earthing systems have been reduced. As protection in TT installations will virtually always require a RCD, the reduced disconnection times in the 17th Edition are easily achieved (0.2 seconds on final circuits).
A very significant new regulation (411.3.3) requires a 30mA RCD additional protection for socket-outlet circuits that are intended for use by ordinary persons. With a few exceptions, this means all domestic installations. Commercial installations will generally remain exempt, as in most situations individuals will have received instruction.
Guidance on the structure, disconnection times and the use of RCDs is given in Chapter C of this book.
Bathrooms 701
The 17th Edition goes a bit further on harmonization with CENELEC for bathroom installations.
The 16th Edition introduced the concept of zones to the regulations for bathrooms but fell short of harmonization with Europe in one key area: socket-outlets in bathrooms.
Section 701 now aligns with the European ethos, there is not any Zone 3. Thus outside of Zone 2, which is 600 mm from the bath or shower outer edge, only the ‘general rules’ of the regulations apply and any equipment is allowed. However, socket-outlets have a special distance specified, which is at least 3m from the boundary of Zone 1.
All bathroom circuits now require 30mA RCD additional protection and a UK modification allows supplementary equipotential bonding to be omitted, under certain conditions.
Tables and Methods of Cable Current-Carrying Capacity (Appendix 4 of BS 7671)
The whole of the first part of this appendix was modified for the 17th Edition and has been further modified by Amendment No. 1 with respect to calculating the current rating of cables laid in the ground.
Swimming Pools and Other Basins (702)
For the 17th Edition, the scope of this section now includes the basins of fountains and areas of natural water including the sea and lakes, where they are specifically designated as swimming areas.
Lighting and Luminaires
A completely new section for the 17th Edition is Section 559 ‘Luminaires and Lighting Installations’; which contains six pages of text and some 36 new regulations.
The new section deals with interior and exterior lighting installations and also applies to highway power supplies and street furniture.
The section specifies regulations for luminaire through-wiring and heat specification of terminal wiring and similar items. Through-wiring is only permitted where the luminaire is specifically designed for it.
Inspecting and Testing
There is a new requirement that insulation resistance is measured between live conductors and the cpc, with the cpc connected to the earthing arrangement.
Periodic Inspection
Whilst the text of Chapter 62 Periodic Inspection and Testing is unchanged, the forms in Appendix 6 have been substantially changed. They now detail extensive inspection requirements.
New Appendix with Current-Carrying Capacity of Busbars
A new appendix has been added giving information on current-carrying capacity and voltage drop limitations for busbars and powertrack.
Chapter 56 – Safety Services
This chapter has been modified and specifies ‘break times’ for standby systems. It sets regulations for subjects like circuitry under fault conditions, parallel operation and specifies the life of certain critical back up batteries.
High Earth Leakage Currents
Correctly termed ‘high protective conductor currents’, the former Section 607 has been incorporated into Chapter 54, with some limited removal of ambiguous regulations.
High Voltage to Low Voltage Faults
This is a new section for the 17th Edition, but this is not particularly significant for installers or designers; the section is only relevant for ‘private’ HV-LV sub-stations and even then the corresponding HV standards will need to be followed. Read Chapter D for a fuller explanation.
Voltage Drop
Whilst in essence the basic requirements of the regulations on voltage drop have not fundamentally changed, a new appendix suggests maximum voltage drops for both utility and private supplies. These voltage drops are separated into suggested limits for lighting and other circuits.
Atmospheric and Switching Overvoltages
There are a few pages of regulations on this subject but they are not of much significance, unless you have overhead distribution cables within your installation.
Surge Protective Devices
Although these are not generally required, there are regulations for installing surge protective devices.
Insulation Monitoring Devices (IMDs) and Residual Current Monitors (RCMs)
Similarly, although not specified, there are regulations for installing these devices. RCMs in particular are becoming more widely specified and there is guidance on this subject provided in Chapter D of this book.
Caravan and Camping Parks (708)
The main modification for the 17th Edition is that pitch socket-outlets are to be individually protected by a 30mA RCD.
New Special Installations or Locations
The following Special Installations sections are new to the 17th Edition:
709 Marinas
711 Exhibitions shows and stands
712 Solar photovoltaic (PV) power supply systems
717 Mobile or transportable units
721 Electrical installations in caravans and motor caravans
740 Temporary electrical installations for structures, amusements and booths at fairgrounds
753 Floor and ceiling heating systems
A 4 Amendment No. 1:2011
The first amendment to BS 7671:2008 was issued on 1 July 2011 and is intended to come into effect on 1 January 2012. Installations designed (but not installed) after 31 December 2011 are to comply with BS 7671:2008 Amd No. 1.
The major changes are as follows:
Section 444 Measures Against Electromagnetic Disturbances
The new section includes mainly advice that consideration should be given to aspects of the installation relating to electromagnetic interference. However, there are also some specific requirements; e.g.
444.5.1.1 all protective and functional earthing conductors of an installation within a building shall be connected to the main earthing terminal
444.4.3.3 where a complete low voltage installation including the transformer is operated only by the user, an installation forming part of a TN-S system shall be installed
444.4.6 for TN or TT multiple-source power supplies to an installation, the system shall be earthed at one point only.
Section 534 Devices for Protection Against Overvoltage
Where Section 443 requires protection against overvoltage, surge protective devices must be selected in accordance with the new Section 534.2. In the UK (see regulation 443.2.2) it is likely that protection against overvoltage will not be required.
Part 6 Inspection and Testing
New detailed periodic inspection report forms are introduced in Appendix 6.
Part 7 New Specialist Installation Section
Section 710 – medical locations
Section 729 – operating and maintenance gangways
Appendices
Appendix 11 (Effect of Harmonic Currents on 3 Phase Systems) and Appendix 12 (Voltage Drop in Consumers’ Installations) have been moved to Appendix 4.
Appendices 11 and 12 have been left blank for future use.
B
Legal Relationship and General Requirements of BS 7671:2008 Amd No. 1:2011
Introduction
It is important to recognize that, for electrical designers and installers, there are legal responsibilities that must be both known and implemented whilst carrying out electrical installation or electrical design work. This chapter provides information and guidance on key UK legalisation relevant to electrical installations. It also provides guidance on some contractual obligations relating to design and installation.
This chapter is neither a full legal guide nor a contractual guide to requirements, but provides a short overview of the subject.
The chapter finishes with notes on the assessment of general characteristics, from the requirements of Part 3 in BS 7671:2008.
B 1 Legal Requirements and Relationship
B 1.1 Key Legal UK Legislation
Legislation can be in the form of an Act of Parliament (e.g. The Health & Safety at Work Act 1974) or a Statutory Instrument (e.g. The Electricity at Work Regulations 1989). Acts are primary legislation and Statutory Instruments are secondary legislation made under a specific Act. In the case of the Electricity at Work Regulations, these were made under the Health & Safety at Work Act. Failing to comply with requirements of an Act of Parliament or a Statutory Instrument is a breach of criminal law and may result in a prosecution.
The following legislation is considered key and relevant to the electrical technical aspects of electrical designs and electrical installations:
The Electricity at Work Regulations 1989
The Electricity Safety, Quality and Continuity Regulations 2002 (as amended)
The Electricity Act 1984
The Building Acts 1984 & 2000 (These apply to England & Wales only and implement the Building Regulations for England & Wales. They include Approved Document Part P – Electrical Safety (dwellings).
The Building (Scotland) Act 2003 (This applies in Scotland only and implements the Building (Scotland) Regulations 2004 (as amended). The requirements of these regulations are outside the scope of this book.
The Electromagnetic Compatibility Regulations 2006
Tort
B 1.2 The Electricity at Work Regulations 1989 (EWR 1989)
The EWR 1989 is one of the most important pieces of legislation that an electrical designer or electrical contractor must be familiar with. You should know the content of this document as well as knowing of its existence.
The EWR 1989 cover the safety to people, including employees, involved in all aspects of electrical and electronic systems in the UK. This includes self-employed electricians working in domestic installations; all ‘electrical personnel’ in commercial installations and construction sites; and (for commercial installations) the end users. It also includes any person undertaking any work activity on or near electrical equipment.
All electrical equipment and systems are encompassed by the legislation, from a battery to the National Super Grid at 400 kV. The legislation covers design, operation, isolation, maintenance, workspace and lighting of equipment. There are regulations on precautions for working on equipment made dead and work on, or near, live conductors. There are also regulations for persons undertaking work to be competent, in order to prevent danger and injury.
Compliance with the EWR 1989 is therefore a fundamental requirement for any organization and it is recommended that organizations have in place a system of training, to ensure compliance with the regulations. Guidance on the EWR is available from the Health & Safety Executive (publication HS(R) 25 – Memorandum of Guidance on the Electricity at Work Regulations 1989), It is recommended that organizations purchase this and implement the guidance provided; it contains the text of the Act as well as HSE guidance on how to achieve the statutory requirements.
The publication consists of 50 pages and can be purchased or freely downloaded from http://www.hse.gov.uk/pubns/ quoting the following reference:
HS(R)25 Memorandum of Guidance on the Electricity at Work Regulations 1989),
ISBN 9780717662289
As well as having a copy of HS(R) 25, organizations must provide adequate training for all staff who work on or near electrical installations.
To supplement this, a dead working policy should be formalized, together with a live working policy for those contractors who carry out live work.
In respect to the ‘making dead’ or ‘live working’ aspects of EWR 1989, the following document is also very useful; if not essential:
HSG 85 Electricity at Work – Safe Working Practices
ISBN 0717621642
This document provides guidance on the policy and procedures for safe working practices. It includes guidance on the following:
assessing safe working practices
deciding whether to work dead or live
actions common to both dead and live working
working dead; and
working live.
B 1.3 The Electricity Safety, Quality and Continuity Regulations 2002 (As Amended)
These statutory regulations are primarily intended for Distribution Network Operators (DNOs), setting statutory limits for voltage and frequency.
The regulations state that PME supplies cannot be used to provide installations supplying caravans or boats. Also, DNOs can take the option not to supply an earth to installations that they feel would be inappropriate. This will possibly be the case on some farms, building sites and petrol filling stations.
For all installations, DNOs will have to take a view on the safety of an installation and will use BS 7671:2008 for this. If the DNO feels that an installation is unsafe, they can refuse to provide a supply or, if connected, disconnect the supply.
B 1.4 The Electricity Act 1984 (As Amended)
This Act is primarily aimed at Distribution Network Operators (DNOs) and (more recently) Meter Operators. However, there is a relevant point for installation designers and contractors to note: the Act gives the DNO or Meter Operator the right to position intakes where they see fit and where they feel appropriate for a given installation.
B 1.5 The Building Act 1984, The Building Regulations and Part P
The Building Act 1984 refers only to England & Wales. As mentioned earlier the requirements for Scotland are not detailed in this publication. This book does not cover all the technical requirements relating to the Building Regulations, but there are numerous guides and books on this subject, including one produced by the ECA and the NICEIC.
However, Part P of the Building Regulations (electrical safety within dwellings) is summarized below:
Legal Standing of Part P
The Building Regulations 2010 are made under the main Act of Parliament, the Building Act 1984. The Building Act is the primary legislation and refers to the Building Regulations 2010, with its various parts on structure, means of escape, spread of fire, ventilation, heat loss and, of course, electrical safety.
The Building Regulations 2010 are statutory and a breach of the regulations in itself is an offence under criminal law and may lead to prosecution.
For guidance on ways of complying with the individual parts of the Building Regulations, the DCLG (Department for Communities and Local Government) produce ‘Approved Documents’ on each part. It is important to recognize that the Approved Documents themselves are not statutory. This is demonstrated in Figure B 1.1 below:
Figure B 1.1 Relationship of Building Act, Statutory Instruments and Approved Documents
c02f001001The wording of the Statutory Instrument and hence the legal requirement of Part P is given in Table B 1.1.
Table B 1.1 Statutory Instrument relating to Part P of the Building Regulations.