Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                
Next Article in Journal
Solar Radiation Forecasting: A Systematic Meta-Review of Current Methods and Emerging Trends
Previous Article in Journal
Generalized Quasi-Static Mooring System Modeling with Analytic Jacobians
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

An Improved Near-State Pulse-Width Modulation with Low Switching Loss for a Permanent Magnet Synchronous Machine Drive System

1
Chongqing University-University of Cincinnati Joint Co-op Institute, Chongqing University, Chongqing 400044, China
2
School of Electrical Engineering, Chongqing University, Chongqing 400044, China
*
Author to whom correspondence should be addressed.
Energies 2024, 17(13), 3157; https://doi.org/10.3390/en17133157
Submission received: 21 May 2024 / Revised: 21 June 2024 / Accepted: 22 June 2024 / Published: 26 June 2024

Abstract

:
Common-mode voltage (CMV) leads to the shaft voltage and shaft current by coupling the capacitor network in the permanent magnet synchronous machine (PMSM), which affects the reliability of the whole motor drive system. Based on the low-CMV modulation strategy for the PMSM drive system, this paper proposed an improved near-state pulse-width modulation (NSPWM) on switching loss. First, the generation mechanism for the switching signals of NSPWM was analyzed, and it was observed that there exists one phase of switches in an inactive state for every sector. Then, to reduce the switching loss of the NSPWM, this paper proposed an improved NSPWM modulation strategy based on power factor angle to adjust switching action, which ensures the switching tubes that have the biggest conduction current have no switching action. In addition, the switching loss analytic formula of the NSPWM was derived to prove the correctness of the proposed method for optimizing switching loss. Finally, the proposed modulation strategy was carried out in the simulation and experimental platform. Under the premise of good steady and dynamic performance, the results show that the proposed modulation strategy has less switching loss.

1. Introduction

Compared to current source inverters (CSIs) and other multilevel inverters, three-phase two-level voltage source inverters (VSIs) have the advantage of a simple structure and bidirectional energy conversion [1,2], so VSIs have been widely used in permanent magnet synchronous machine (PMSM) drive systems [3], and many modulation methods for VSIs have been proposed, such as SPWM, SVPWM, DPWM and dual-vector modulation [4,5]. However, there are some problems that endanger the safe and stable operation of this system. For example, the common-mode voltage (CMV) generated at the neutral point leads to the shaft voltage and shaft current by coupling the capacitor network in the motor [6], which affects the reliability of the whole PMSM drive system [7].
To reduce the CMV of the PMSM drive system fed by VSI, Reference [8] introduces CMV into the cost function and proposes a model predictive control scheme that takes into account CMV. An optimized zero-sequence voltage injection method is proposed [9], and the CMV amplitude can decrease to 50%. In [10], a kind of harmonic elimination pulse-width modulation with a common-mode voltage reduction ability is presented. However, the CMV reduction method proposed in [11] is suitable for multi-level inverters.
For two-level VSIs, a switching tube is introduced to the DC bus, which makes the AC part of the three-phase converter float in the zero state. Through improvements in structure and control strategy, the CMV remains unchanged in the zero state [12]. Reference [13] proposes a three-phase AC-side voltage-doubling topology with an intrinsic buck–boost unit, which suppresses the average CMV to zero by modulating the output phase voltage around its negative bus. However, the above two methods add the hardware circuit in the three-phase two-level VSI, which not only increases costs but also reduces efficiency and reliability. Therefore, reducing CMV through modulation is the most effective means.
Since the amplitude of CMV in zero state is Udc/2, which is 3 times of that in active state, reducing the common-mode voltage of the zero vector or eliminating the zero vector is the most effective modulation method [14]. References [15,16] control the dead time switching tube by current sector determination and switch function direct control, so the CMV amplitude is suppressed by changing the current freewheeling path. Although this method can reserve the zero state, the dead time at the commutation time will cause a zero current clamping effect. Active zero-state PWM (AZSPWM) adopts two opposite AVVs to replace the ZVV, so the high-frequency CMV can be effectively reduced. However, the ripple of the current is too great [17]. In comparison, near-state PWM (NSPWM) adopts three adjacent active vectors to synthesize the reference vector; it can reduce the high- and low-frequency CMV simultaneously, and the steady state under NSPWM is better than that under AZSPWM [18]. It should be noted that no matter where the reference vector is located, there are two vector synthesis methods, and there exists one phase of switches in an inactive state.
Based on the characteristic analysis of NSPWM, to reduce the switching loss, this paper proposed an improved NSPWM modulation strategy based on power factor to adjust the switching action. To ensure the switching tube that has the biggest conduction current has no switching action, the NSPWM with the least switching loss is proposed. In the simulation and experiment part, the effectiveness of the proposed method on steady-state, dynamic-state performance and switching loss optimization is shown.
This paper is organized as follows: Section 2 describes the topology and whole control system. Then, an improved NSPWM scheme is proposed in Section 3. Consequently, the effectiveness and superiority of the proposed scheme are validated by the simulation and experiment results in Section 4 and Section 5. Finally, the conclusion is drawn in Section 6.

2. Topology and Field-Oriented Control

2.1. Topology of PMSM Control System

According to [18], the NSPWM has a limited linearity region, which means it can only modulate the voltage in that the modulation index M is greater than 0.61. However, when PMSM operates at low speed, the NSPWM generates high CMV and does not modulate the reference voltage correctly. Therefore, to reduce the DC voltage, the buck converter is introduced in the DC side of the PMSM drive system.
Figure 1 shows the topology of the PMSM control system fed by a three-phase voltage source inverter with a buck converter, where u i n represents the DC source voltage; u d c represents the DC-link voltage; C d c , S 0 , D 0 and L d c constitute the buck converter; S 1 , S 2 , S 3 , S 4 , S 5 and S 6 represent the switching tube of the three-phase VSI bridge.

2.2. Mathmatical Model of PMSM

According to [19], in the synchronous rotating frame ( d q frame), the voltage state equations of the PMSM are shown as follows:
u d = R s i d + d ψ d d t ω ψ q
u q = R s i q + d ψ d d t ω ψ d
where u d and u q represent the stator voltage in the d q frame, i d and i q represent the stator current in the d q frame, R s is the stator resistance, ω is the synchronous angle frequency and ψ d and ψ q are the flux linkage in the d q axis.
The equations of electromagnetic flux linkage are shown as [20]
ψ d = L d i d + ψ f
ψ d = L q i q
where L d and L q are the stator inductance in the d q frame and ψ f is the flux linkage of PMSM.
The electromagnetic torque equation is shown as
T e = 3 2 n p [ ψ f i q + ( L d L q ) i d i q ]
where T e represents the electromagnetic torque and n p is the pole pairs.

2.3. Field-Oriented Control

Field-oriented control (FOC) is adopted in this paper; the whole diagram is shown in Figure 2. FOC mainly includes speed closed-loop and current closed-loop control. The given rotational speed is compared with the actual rotational speed, the deviation is passed through the speed PI controller and the i d and i q are compared with the actual value to obtain the deviation to the current PI controller. And the output of the current controller u d and u q are transformed into the α β coordinate system. Through the modulation module output switching signals to the inverter, the inverter outputs three-phase voltage to directly drive the PMSM.

2.4. Conventional NSPWM

NSPWM adapts three neighbor voltage vectors to match the reference voltage. The three voltage vectors are the voltage vectors that are closest to the reference voltage vector and its two neighbors (Figure 3b). The utilized voltage vectors are changed every 60° throughout the space. As shown in Figure 3a, the voltage vector space is divided into six sectors. Defined with indices i, voltage vectors V i 1 , V i , V i + 1 are utilized for region A i .
Utilizing the three near-state voltage vectors, the volt–seconds balance equation and the PWM period constraint for NSPWM are given for region A i in the equations below.
V i 1 t i 1 + V i t i + V i + 1 t i + 1 = V r e f T s
t i 1 + t t + t i + 1 = T s
where T s is the PWM period.
Normalizing the voltage vector, the vector duty cycles can be found as d k = t k T s , where k is i 1 , i, i + 1 . Utilizing the above equations, the duty cycles of the voltage vectors can be calculated for region A i as follows:
d t 1 = 1 2 3 π M i s i n ( θ ( i 2 ) π 3 )
d t 1 = 1 + 3 π M i c o s ( θ ( i 2 ) π 3 ) + 3 3 π M i s i n ( θ ( i 2 ) π 3 )
d t 1 = 1 3 π M i c o s ( θ ( i 2 ) π 3 ) 3 π M i s i n ( θ ( i 2 ) π 3 )
In the above equations, θ is the angle of the reference voltage vector with the α axis and M i is the modulation index which indicates the voltage utilization level M i = V m 2 V d c π . Equations (8)–(10) yield a valid solution only in the colored region shown in Figure 3c, and in the white remaining regions, there is no solution.
The sequence of NSPWM is shown in Table 1 for region definitions of Figure 3a.

3. Optimized NSPWM Strategy

3.1. Conventional NSPWM Redundancy Analysis

NSPWM adopts three near-basic voltage vectors to synthesize the reference voltage vector; it has one phase switch that remains clamped for every PWM period. For example, in A 1 , the voltage vectors u 6 , u 1 and u 2 are adopted, and phase A remains clamped open. Figure 4 shows the three-phase switching signals for all six sectors.
A conventional NSPWM can reduce switching loss by voltage clamping. However, the conventional NSPWM synthesis strategy does not optimize the switching loss. To analyze the switching loss, Figure 5 shows the three-phase reference voltage vector and three-phase current vector in the synchronous station frame ( α - β ) through the Clarke transform in Equation (11).
i = 2 3 ( i a + i b e j 2 π 3 + i c e j 2 π 3 )
In Equation (11), i represents the actual current vector, and i a , i b and i c represent the current magnitude in phases a, b and c.
For PMSM, the current vector i lags reference voltage vector U r e f by power factor angle ( φ ), and the angle between U r e f with α axis is θ . The U r e f location determines the basic synthesized vector group, but it still can be improved. For example, Figure 6 shows the two methods to synthesize the U r e f when U r e f is located near the sector boundary, but the current vector i could be used to optimize the switching loss. In Figure 5b, when φ = θ , the phase A current is maximum. Therefore, to reduce the switching loss, phase A needs clamping, and the best-synthesized group is V 6 , V 1 , V 2 . Actually, when U r e f is located in B 1 , the phase A current magnitude is the biggest phase current, so the best-synthesized vector group for U r e f located in B 1 is V 6 , V 1 , V 2 . In conclusion, when the inverter works in a non-unit power factor, the conventional NSPWM cannot best optimize the switching loss.

3.2. Improved NSPWM on Switching Loss

When an inverter switches, it will cause large switching loss, reduce the working efficiency and cause large heat dissipation. To reduce the switching loss of NSPWM, the improved NSPWM method is proposed. Compared with NSPWM, the proposed method adopts different sector division methods, which introduce angle variable α to dynamically adjust the sector division, as shown in Figure 7a. The synthesized voltage vector sequences for all sectors are shown in Table 2, which are the same as those for the conventional NSPWM.

3.3. Linearity Region

Compared with the conventional NSPWM, the proposed improved NSPWM just optimizes the synthesized vector group; the basic vector synthesis strategy is the same as NSPWM. Therefore, the improved method still has the limited linearity region problem. From the synthesized principle, the linearity region is related to variable α . For example, in Figure 7b, the basic vector group u 6 , u 1 , u 2 can only synthesize the reference voltage vector in the black-lined region, and the linearity region is the light blue region, which is expressed as
π 6 cos ( | α | + 30 ° ) M i 0.907
Therefore, only when α 24.74 ° , 24.74 ° , the improved NSPWM has per-fundamental linearity region. The larger the | α | , the smaller the linearity region. So, choosing α not only relates to switching loss but also relates to the linearity region.

3.4. Switching Loss Analysis

In this paper, to evaluate the switching loss of the proposed method and the conventional NSPWM, the current ripple is neglected, and thus, the phase current i p can be assumed as
i p = I cos ( θ φ )
In the equation above, I represents the amplitude of the fundamental current component, φ is the power factor angle and θ represents the electrical angle of the reference voltage.
From [21], the phase average switching loss in one unit for a one-carrier cycle is defined as
P s w _ p = f s w u d c ( E o n + E o f f ) 2 π I r a t e U r a t e [ a b | i p ( θ ) | d θ ]
In the equation above, E o n and E o f f represent the switch-on energy loss and switch-off energy loss under f s w working frequency, I r a t e and U r a t e represent the rated current and rated voltage for the switch and a b represent the interval that the switch does not clamp. For phase a, it has voltage clamping in sectors A 1 and A 4 , so for the improved NPSWM, the switching loss for phase A in a one-carrier cycle is expressed as
P s w _ a = f s w u d c ( E o n + E o f f ) 2 π I r a t e U r a t e [ π 6 5 π 6 | i a ( θ ) | d θ + 7 π 6 11 π 6 | i a ( θ ) | d θ ]
By simplifying the equation above, the switching loss for improved NSPWM can be obtained as follows:
P s w _ a = I f s w u d c ( E o n + E o f f ) π I r a t e U r a t e
It can be seen that the switching loss is proportional to the switching frequency, the DC-link voltage and the phase current. The same conclusion can be obtained in reference [22]. For comparison, in the conventional NPSWM, the switching loss in a one-carrier cycle is expressed as
P s w _ a = f s w u d c ( E o n + E o f f ) 2 π I r a t e U r a t e [ π 6 + φ 5 π 6 + φ | i a ( θ ) | d θ + 7 π 6 + φ 11 π 6 + φ | i a ( θ ) | d θ ]
By simplifying the equation above, the switching loss for the conventional NSPWM can be obtained as follows:
P s w _ a = I f s w u d c ( E o n + E o f f ) π I r a t e U r a t e [ 2 cos ( φ ) ]
It is obvious that the conventional NSPWM switching loss is larger than the improved NSPWM ( P s w _ a < P s w _ a ). The correctness of the proposed method on optimizing the division of the sector by introducing variable α has been theoretically proved. For phases b and c, the switching loss expression is similar.

4. Simulation Results

The simulation models with thermal analysis of the proposed method and the conventional NSPWM are established in the Matlab Simulink(R2023b)/PLECS (4.8.4.) environment. PLECS is a particular tool working in Simulink to analyze the thermal environment of some equipment. The Simulink and PLECS models are both used in this model; the Simulink model mainly works on the signal processing and NSPWM control signal generation, while the PLCES model works mainly on the thermal analysis of the three-phase inverter. The steady state, dynamic performance and switching loss are verified by the simulation results; the PMSM parameters are shown in Table 3.

4.1. Steady-State Experiment

PMSM operates at a rated speed and rated load, and u r e f is located in the at linearity region. α = 30 ° was set for the proposed method; the speed, torque and phase A current waveforms are shown in Figure 8a,b for the conventional NSPWM and the proposed NSPWM, respectively. Because the proposed method just optimizes the division of sectors and does not change the vector synthesis strategy, the results show that both methods operate at good steady-state performance with 6.05% and 5.61% current THD and 0.2283 N·m and 0.2290 N·m torque ripple, respectively. The results prove that the proposed method has the same steady-state performance as the conventional NSPWM.

4.2. Dynamic-State Experiment

To verify the dynamic-state performance of the proposed method, α = 30 ° was set, and PMSM was given a speed control step from static to rated speed without load. The comparison waveforms of speed, load and phase A current are shown in Figure 9a,b for the conventional NSPWM and the proposed method, respectively. The response time of the conventional NSPWM is 5.03 ms, and for the proposed method, it is 4.98 ms. The results show that the proposed method has the same dynamic performance as the conventional NSPWM.

4.3. Switching Loss Analysis

To analyze the switching loss of the IGBT, a thermal model was established in the PLECS environment and a thermal library was established based on the IGBT datasheet in Figure 10. Figure 11a,b show the three-phase inverter conductivity, switching loss and the phase current waveforms for the conventional NSPWM and the proposed method in a one-carrier cycle, respectively. The electrical angle waveforms of PMSM are shown at the top of Figure 11. The switching loss waveform comparison of the inverter show that the proposed method has less energy loss compared with the conventional NSPWM. This further proves that the proposed method optimizes the switching loss by optimizing the division of sectors.

5. Experiment Results

To show the correctness of the proposed method, the experimental platform was set up in Figure 12 according to Table 4. The parameters of the PMSM are presented in Table 3, and a magnetic powder brake with a rated torque of 10 N·m is used as the load of PMSM. The torque and speed are converted into analog signals with a refresh rate of 5 kHz through the DAC module.

5.1. Steady-State Performance

Experimental verification used the same operating conditions as the simulation. For the operational condition, 1000 rpm with a load of 10 N·m, u r e f was located in the linear region of NSPWM. The steady experimental waveforms are shown in Figure 13a,b, and the current THD analysis results are shown in Figure 14a,b for the conventional NSPWM and the proposed method, respectively. The results show that the proposed method has the same steady-state performance as the conventional NSPWM method, operating with good current ripple.
The main harmonic components of the phase current are 5th, 7th, 11th and 13th orders, which are reflected in the 6th and 12th components in the torque. Meanwhile, the current THD of the proposed method is slightly smaller than that of the conventional NSPWM, so the electromagnetic torque THD of the proposed method is 9.62%, which is less than that of the conventional NSPWM.

5.2. Dynamic-State Performance

To verify the dynamic performance of the proposed method, the speed step and load step experiments were set up, from static to rated speed without load (Figure 15a,b) and load increasing from no load to rated load at rated speed (Figure 16a,b). The results show that the proposed improved NSPWM has a similar response time to the conventional NSPWM, which proves that the proposed improved NSPWM has a similar dynamic performance to the conventional NSPWM.

5.3. Switching Loss Analysis

The switching loss of the inverter in various operation conditions is collected, as well as for PMSMs operating at rated speeds with different load torques (Figure 17) and for PMSMs operating at rated load torques with different speeds (Figure 18). According to Equations (16) and (18), the switching loss is linearly proportional to the current peak value, so the mathematical switching loss results, the current peak value and the measured switching loss are all shown in these figures. Obviously, the switching loss of the proposed improved NSPWM is less than the conventional NSPWM under all operational conditions. The results show that, with the increase in load torque, the current magnitude increases, so the switching loss is also nearly linearly proportional to the increase. But the speed does not affect the current magnitude, so the switching loss remains nearly the same. Meanwhile, the theortical results from Equations (16) and (18) have little error with the experimental switching loss results, which prove the correctness of the derived switching loss analytic formula (Equations (16) and (18)) for the improved NSPWM and conventional NSPWM.

5.4. Common-Mode Voltage Analysis

To verify the common-mode voltage reduction performance of the proposed method, the steady-state CMV results are collected for the proposed method and SVPWM for comparison in Figure 19a,b. Because of the benefits of the voltage vector synthesizing strategy, the common-mode voltage waveform results show that the proposed improved NSPWM reduces the common-mode voltage peak value by three times compared with SVPWM.

6. Conclusions

To optimize the switching loss of the common-mode voltage suppressing scheme, this paper has proposed an improved near-state pulse-width modulation scheme. The proposed NSPWM optimizes the sector division, introducing a power factor angle to dynamically adjust the sector division and ensure the longest voltage clamping for the largest current. The feasibility and correctness are verified by the simulation and experimental results. The main conclusions can be summarized as follows:
  • The proposed method ensures the switching tube that has the biggest conduction current has no switching action. So, the least switching loss can be obtained.
  • According to the derived switching loss analytic formula, the proposed method has the least switching loss, and it does not relate to the power factor angle.
  • The proposed method has the same steady-state performance and dynamic-state performance as the conventional NSPWM because it only introduces a power factor that does not change the vector synthesized strategy.

Author Contributions

Conceptualization and methodology, P.Q.; simulation, P.Q.; validation and experiment, P.Q. and R.C.; writing and supervision, P.Q. and Q.G.; review and editing, P.Q.; funding acquisition, P.Q. All authors have read and agreed to the published version of the manuscript.

Funding

This research was funded by the Natural Science Foundation of Chongqing, China, grant number CSTB2022NSCQ-MSX0430.

Data Availability Statement

The data presented in this study are available upon request from the corresponding author.

Conflicts of Interest

The authors declare no conflicts of interest.

References

  1. Miao, Y.; Liao, W.; Huang, S.; Liu, P.; Wu, X.; Song, P.; Li, G. DC-Link Current Minimization Scheme for IM Drive System Fed by Bidirectional DC Chopper-Based CSI. IEEE Trans. Transp. Electrif. 2023, 9, 2839–2850. [Google Scholar] [CrossRef]
  2. Roy, T.; Tesfay, M.W.; Nayak, B.; Panigrahi, C.K. A 7-Level Switched Capacitor Multilevel Inverter With Reduced Switches and Voltage Stresses. IEEE Trans. Circuits Syst. II Express Briefs 2021, 68, 3587–3591. [Google Scholar] [CrossRef]
  3. Dong, Z.; Liu, C. Three-Dimension Space Vector Modulation for Three-Phase Series-End Winding Voltage-Source Inverters. IEEE Trans. Ind. Electron. 2024, 71, 82–92. [Google Scholar] [CrossRef]
  4. Ayano, H.; Nakagaki, T.; Iguchi, Y.; Matsui, Y.; Itoh, J.-i. Theoretical Study of Rampwise DPWM Technique to Reduce Motor Acoustic Noise. IEEE Trans. Power Electron. 2023, 38, 8102–8114. [Google Scholar] [CrossRef]
  5. Zhang, X.; Hou, B. Double Vectors Model Predictive Torque Control Without Weighting Factor Based on Voltage Tracking Error. IEEE Trans. Power Electron. 2018, 33, 2368–2380. [Google Scholar] [CrossRef]
  6. Dabour, S.; Abdel-Wahab, S.M.; Rashad, E.M. Common-Mode Voltage Reduction Algorithm with Minimum Switching Losses for Three-Phase Inverters. In Proceedings of the 21st International Middle East Power Systems Conference (MEPCON), Cairo, Egypt, 17–19 December 2019; Volume 9, pp. 1210–1215. [Google Scholar]
  7. Kan, S.; Ruan, X.; Huang, X.; Dang, H. Second Harmonic Current Reduction for Flying Capacitor Clamped Boost Three-Level Converter in Photovoltaic Grid-Connected Inverter. IEEE Trans. Power Electron. 2021, 36, 1669–1679. [Google Scholar] [CrossRef]
  8. Xu, Z.; Wang, Z.; Wang, X. A predictive current control method for a T-type three-level dual three-phase pmsm with zero common-mode voltage. Proc. CSEE 2020, 40, 4301. [Google Scholar]
  9. Xing, X.; Li, X.; Qin, C.; Chen, J.; Zhang, C. An Optimized Zero-Sequence Voltage Injection Method for Eliminating Circulating Current and Reducing Common Mode Voltage of Parallel-Connected Three-Level Converters. IEEE Trans. Ind. Electron. 2020, 67, 6583–6596. [Google Scholar] [CrossRef]
  10. Wu, M.; Xue, C.; Li, Y.W.; Yang, K. A Generalized Selective Harmonic Elimination PWM Formulation With Common-Mode Voltage Reduction Ability for Multilevel Converters. IEEE Trans. Power Electron. 2021, 36, 10753–10765. [Google Scholar] [CrossRef]
  11. Li, W.; Wang, Y.; Hu, J.; Yang, H.; Li, C.; He, X. Common-mode current suppression of transformer-less nested five-level converter with zero common-mode vectors. IEEE Trans. Power Electron. 2019, 34, 4249. [Google Scholar] [CrossRef]
  12. Xiang, Y.; Pei, X.; Wang, M.; Shi, P.; Kang, Y. An Improved H8 Topology for Common-Mode Voltage Reduction. IEEE Trans. Power Electron. 2019, 34, 5352–5361. [Google Scholar] [CrossRef]
  13. Li, P.; Adam, G.P.; Hu, Y.; Holliday, D.; Williams, B.W. Three-Phase AC-Side Voltage-Doubling High Power Density Voltage Source Converter With Intrinsic Buck–Boost Cell and Common-Mode Voltage Suppression. IEEE Trans. Power Electron. 2015, 30, 5284–5298. [Google Scholar] [CrossRef]
  14. Guo, L.; Jin, N.; Gan, C.; Xu, L.; Wang, Q. An Improved Model Predictive Control Strategy to Reduce Common-Mode Voltage for Two-Level Voltage Source Inverters Considering Dead-Time Effects. IEEE Trans. Ind. Electron. 2019, 66, 3561–3572. [Google Scholar] [CrossRef]
  15. Lai, Y.-S.; Shyu, F.-S. Optimal common-mode Voltage reduction PWM technique for inverter control with consideration of the dead-time effects-part I: Basic development. IEEE Trans. Ind. Appl. 2004, 40, 1605–1612. [Google Scholar] [CrossRef]
  16. Guo, Y.; Zhang, J.; Wang, S.; Jin, P. Common-mode voltage suppression strategy of PMSM system using model predictive control. Electr. Mach. Control 2024, 28, 56–65. [Google Scholar]
  17. Hava, A.M.; Ün, E. Performance Analysis of Reduced Common-Mode Voltage PWM Methods and Comparison With Standard PWM Methods for Three-Phase Voltage-Source Inverters. IEEE Trans. Power Electron. 2009, 24, 241–252. [Google Scholar] [CrossRef]
  18. Qing, P.; Xiong, J.; Ma, F. A Model Predictive Control Scheme with Minimum Common-Mode Voltage for PMSM Drive System Fed by VSI. Machines 2024, 12, 292. [Google Scholar] [CrossRef]
  19. Dong, H.; Zhang, Y. A Low-Complexity Double Vector Model Predictive Current Control for Permanent Magnet Synchronous Motors. Energies 2024, 17, 147. [Google Scholar] [CrossRef]
  20. Yang, R.; Li, L.; Wang, M.; Zhang, C. Force Ripple Compensation and Robust Predictive Current Control of PMLSM Using Augmented Generalized Proportional–Integral Observer. IEEE J. Emerg. Sel. Top. Power Electron. 2021, 9, 302–315. [Google Scholar] [CrossRef]
  21. Ayachit, A.; Kazimierczuk, M.K. Averaged Small-Signal Model of PWM DC-DC Converters in CCM Including Switching Power Loss. IEEE Trans. Circuits Syst. II Express Briefs 2019, 66, 262–266. [Google Scholar] [CrossRef]
  22. Ma, Z.; Pei, Y.; Wang, L.; Yang, Q.; Qi, Z.; Zeng, G. An Accurate Analytical Model of SiC MOSFETs for Switching Speed and Switching Loss Calculation in High-Voltage Pulsed Power Supplies. IEEE Trans. Power Electron. 2023, 38, 3281–3297. [Google Scholar] [CrossRef]
Figure 1. Topology of PMSM fed by three-phase VSI with DC-DC boost converter.
Figure 1. Topology of PMSM fed by three-phase VSI with DC-DC boost converter.
Energies 17 03157 g001
Figure 2. Block diagram of the proposed improved NSPWM based on FOC.
Figure 2. Block diagram of the proposed improved NSPWM based on FOC.
Energies 17 03157 g002
Figure 3. (a). Region division (b). Vector synthesis strategy (c). Linearity region.
Figure 3. (a). Region division (b). Vector synthesis strategy (c). Linearity region.
Energies 17 03157 g003
Figure 4. Switching signals for all six sectors.
Figure 4. Switching signals for all six sectors.
Energies 17 03157 g004
Figure 5. Reference voltage vector and current vector (a). φ θ (b). φ = θ .
Figure 5. Reference voltage vector and current vector (a). φ θ (b). φ = θ .
Energies 17 03157 g005
Figure 6. Synthesized strategies comparison (a). Strategy 1 (b). Strategy 2.
Figure 6. Synthesized strategies comparison (a). Strategy 1 (b). Strategy 2.
Energies 17 03157 g006
Figure 7. Space vector sectors and modulation regions. (a). Space vector sectors. (b). Modulation region.
Figure 7. Space vector sectors and modulation regions. (a). Space vector sectors. (b). Modulation region.
Energies 17 03157 g007
Figure 8. Steady-state performance for PMSM operating at rated speed and rated load. (a). Conventional NSPWM. (b). Improved NSPWM.
Figure 8. Steady-state performance for PMSM operating at rated speed and rated load. (a). Conventional NSPWM. (b). Improved NSPWM.
Energies 17 03157 g008
Figure 9. Dynamic performance for PMSM operating from static to rated speed without load. (a). Conventional NSPWM. (b). Improved NSPWM.
Figure 9. Dynamic performance for PMSM operating from static to rated speed without load. (a). Conventional NSPWM. (b). Improved NSPWM.
Energies 17 03157 g009
Figure 10. Thermal library. (a). Turn-on energy loss. (b). Turn-off energy loss.
Figure 10. Thermal library. (a). Turn-on energy loss. (b). Turn-off energy loss.
Energies 17 03157 g010
Figure 11. Switching loss comparison analysis over one carrier cycle. (a). Conventional NSPWM. (b). Improved NSPWM. (c). Phase current for conventional NSPWM. (d). Phase current for improved NSPWM.
Figure 11. Switching loss comparison analysis over one carrier cycle. (a). Conventional NSPWM. (b). Improved NSPWM. (c). Phase current for conventional NSPWM. (d). Phase current for improved NSPWM.
Energies 17 03157 g011aEnergies 17 03157 g011b
Figure 12. Experimental platform of PMSM control system.
Figure 12. Experimental platform of PMSM control system.
Energies 17 03157 g012
Figure 13. Steady-state waveform experiment results. (a). Conventional NSPWM. (b). Proposed method.
Figure 13. Steady-state waveform experiment results. (a). Conventional NSPWM. (b). Proposed method.
Energies 17 03157 g013
Figure 14. Steady-state experiment current and load torque THD analysis. (a). Current THD for conventional NSPWM. (b). Current THD for proposed method. (c). Load torque THD for conventional NSPWM (d). Load torque THD for proposed method.
Figure 14. Steady-state experiment current and load torque THD analysis. (a). Current THD for conventional NSPWM. (b). Current THD for proposed method. (c). Load torque THD for conventional NSPWM (d). Load torque THD for proposed method.
Energies 17 03157 g014
Figure 15. Dynamic speed step experiment results. (a). Conventional NSPWM. (b). Proposed method.
Figure 15. Dynamic speed step experiment results. (a). Conventional NSPWM. (b). Proposed method.
Energies 17 03157 g015
Figure 16. Dynamic load step experiment results. (a). Conventional NSPWM. (b). Proposed method.
Figure 16. Dynamic load step experiment results. (a). Conventional NSPWM. (b). Proposed method.
Energies 17 03157 g016
Figure 17. Switching loss at different speeds.
Figure 17. Switching loss at different speeds.
Energies 17 03157 g017
Figure 18. Switching loss at different load torques.
Figure 18. Switching loss at different load torques.
Energies 17 03157 g018
Figure 19. Common-mode voltage. (a). The proposed method. (b). Conventional SVPWM.
Figure 19. Common-mode voltage. (a). The proposed method. (b). Conventional SVPWM.
Energies 17 03157 g019
Table 1. Basic synthesized vector sequence for NSPWM in all sectors.
Table 1. Basic synthesized vector sequence for NSPWM in all sectors.
A 1 A 2 A 3 A 4 A 5 A 6
1st Vector V 2 V 3 V 4 V 5 V 6 V 1
2nd Vector V 1 V 2 V 3 V 4 V 5 V 6
3rd Vector V 6 V 1 V 2 V 3 V 4 V 5
4th Vector V 1 V 2 V 3 V 4 V 5 V 6
5th Vector V 2 V 3 V 4 V 5 V 6 V 1
Table 2. Basic synthesized vector sequence for the improved NSPWM in all sectors.
Table 2. Basic synthesized vector sequence for the improved NSPWM in all sectors.
B 1 B 2 B 3 B 4 B 5 B 6
1st Vector V 2 V 3 V 4 V 5 V 6 V 1
2nd Vector V 1 V 2 V 3 V 4 V 5 V 6
3rd Vector V 6 V 1 V 2 V 3 V 4 V 5
4th Vector V 1 V 2 V 3 V 4 V 5 V 6
5th Vector V 2 V 3 V 4 V 5 V 6 V 1
Table 3. Parameters of PMSM.
Table 3. Parameters of PMSM.
ParametersDescriptionValue
R s ( Ω )Stator resistance1.443
L d (mH)d-axis inductance5.541
L q (mH)q-axis inductance5.541
ψ f (Web)Flux linkage0.2852
i N (A)Rated current4.5
n N (r/min)Rated speed1000
T N (N·m)Rated torque10
n p Pole pairs4
J ( kg · m 2 )Rotational inertia0.00194
u d c (v)DC-bus voltage270
f s (Hz)Carrier frequency10,000
P N (kW)Rated power1.0
U N (V)Rated voltage110
Table 4. Parameters of experimental platform.
Table 4. Parameters of experimental platform.
DescriptionValue (Type)
IGBT moduleFS400R07AE3
Film capacitor400 µF/600 V
DC-link voltage270V
DC sourcePR300-4
Current sensorsACS724-10AB
DSPTMS320F28335
Carrier and sampling frequency10 kHZ
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.

Share and Cite

MDPI and ACS Style

Qing, P.; Chen, R.; Gao, Q. An Improved Near-State Pulse-Width Modulation with Low Switching Loss for a Permanent Magnet Synchronous Machine Drive System. Energies 2024, 17, 3157. https://doi.org/10.3390/en17133157

AMA Style

Qing P, Chen R, Gao Q. An Improved Near-State Pulse-Width Modulation with Low Switching Loss for a Permanent Magnet Synchronous Machine Drive System. Energies. 2024; 17(13):3157. https://doi.org/10.3390/en17133157

Chicago/Turabian Style

Qing, Pei, Ruoyu Chen, and Qiang Gao. 2024. "An Improved Near-State Pulse-Width Modulation with Low Switching Loss for a Permanent Magnet Synchronous Machine Drive System" Energies 17, no. 13: 3157. https://doi.org/10.3390/en17133157

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop