Load Flow Analysis

This document contains a one-line diagram for performing a load flow analysis of an electrical system with a power factor of 0.7 and 0.8. The diagram shows 18 buses connected by underground cables with various loads connected. It summarizes the apparent power and power factor for each load and the voltage drop along each line.

Uploaded by

sefibot
Copyright
© Attribution Non-Commercial (BY-NC)
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
24 views

Load Flow Analysis

This document contains a one-line diagram for performing a load flow analysis of an electrical system with a power factor of 0.7 and 0.8. The diagram shows 18 buses connected by underground cables with various loads connected. It summarizes the apparent power and power factor for each load and the voltage drop along each line.

Uploaded by

sefibot
Copyright
© Attribution Non-Commercial (BY-NC)
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

One-Line Diagram - OLV1 (Load Flow Analysis)

page 1

Sistema Simulado con un Factor de potencia de 0.7

60-MC-065
3,291 MVAsc

597 kVA
69,9%

Barra 1
0,38 kV

60-MC-066
3,291 MVAsc

Barra 4
0,38 kV

100%

597 kVA
69,9%
CU
Cable1
3 m
9-1/C 500
0,0276+j0,03108 ohms/1000ft

0,1 %Vd

Barra 2
0,38 kV

CU
Cable2
397 m
24-1/C 500

4%
99,9

586 kVA
69,9%

2,8 %Vd

0,0276+j0,03108 ohms/1000ft

Barra 3
0,38 kV

CU
Cable3
3 m
9-1/C 500
0,0276+j0,03108 ohms/1000ft

Barra 5
0,38 kV

596 kVA
69,9%

9%
97,0

579 kVA
70,0%

CU
Cable4
397 m
24-1/C 500
0,0276+j0,03108 ohms/1000ft

Barra 6
0,38 kV

Carga_Conc1
586 kVA
0,38 kV
890,3 A

100%

586 kVA
69,9%

0,1 %Vd

4%
99,9

2,9 %Vd

586 kVA
69,9%

4%
97,1

569 kVA
70,0%

Carga_Conc7
576 kVA
0,38 kV
875,1 A

Sistema Simulado con un Factor de potencia de 0.8

60-MC- 065
3,291 MVAsc

Barra 13
0,38 kV

0,1 %Vd

Barra 14
0,38 kV

2,9 %Vd

Barra 15
0,38 kV

597 kVA
69,9%

60-MC- 066
3,291 MVAsc

100%

597 kVA
69,9%
CU
Cable5
3 m
9-1/C 500
0,0276+j0,03108 ohms/1000ft

596 kVA
69,9%

CU
Cable6
397 m
24-1/C 500
0,0276+j0,03108 ohms/1000ft

9%
97,0

579 kVA
70,0%

Oct 05, 2012

Project File: Estudio_SDI-Calama

0,1 %Vd

Barra 17
0,38 kV

4%
99,9

Carga__Conc1
586 kVA
0,38 kV
890,3 A

12:57:40

Barra 16
0,38 kV

2,8 %Vd

Barra 18
0,38 kV

586 kVA
69,9%

100%

586 kVA
69,9%
CU
Cable7
3 m
9-1/C 500
0,0276+j0,03108 ohms/1000ft
4%
99,9

586 kVA
69,9%

CU
Cable8
397 m
24-1/C 500
0,0276+j0,03108 ohms/1000ft

4%
97,1

569 kVA
70,0%

Carga__Conc7
576 kVA
0,38 kV
875,1 A