Masterpact NT: User Manual
Masterpact NT: User Manual
Masterpact NT: User Manual
Masterpact NT
Circuit breakers and switch-disconnectors UL 489 Listed from 800 to 1200 A
User manual for circuit breakers and switch-disconnectors Masterpact NT08-12 UL 489 Listed
Contents
Identifying Masterpact
Rating plate Components Components
2 4 6
2 3 4
6 7 8 9 10 11
Discovering the circuit breaker positions Racking Matching a Masterpact circuit breaker with its cradle Locking the switchboard door Locking the circuit breaker in position Locking the safety shutters
14
14 16 19 20 21 24 26 28 30 32 34 36 39 41 44 45 46 48 50
26
32
Initial tests What to do when the circuit breaker trips? Maintenance operations
44
48
GHD12331AA - 06/2009
Identifying Masterpact
Rating plate
DB119736
DB119738
GHD12331AA - 06/2009
Identifying Masterpact
Components
DANGER
ELECTRIC SHOCK, EXPLOSION ORARC FLASH HAZARD b This equipment must be installed and serviced only by qualified electrical personnel. b Turn off all power supplying this equipment before working on or inside equipment. b Always use a properly rated voltage sensing device to confirm power is off. b Replace all devices, doors and covers before turning on power to this equipment. Failure to follow these instructions will result indeath, serious injury or equipment damage.
DB119739
Turn circuit breaker off b if spring is charged, press Push to close button (A) to discharge spring, as indicated by window (B). b press Push to open button (C) to open contacts, as indicated by window (D).
Disconnect power from circuit breaker b for drawout circuit breaker: v rack circuit breaker to disconnected position (A). See Discovering the circuit breaker positions, page 14. b for fixed circuit breaker: v turn off all power supplying this equipment before working on or inside equipment.
GHD12331AA - 06/2009
Discovering Masterpact
Components
A. Padlock provision B. Key interlock C. Racking interlock for open door D. Terminal cover (optional) E. Position indicating contact terminal block F. On/Off contact terminal block G. Auxiliary contact terminal block H. Trip unit terminal block I. Position indicating contact terminal block J. Cradle rejection feature K. Door interlock L. Shutter
GHD12331AA - 06/2009
Discovering Masterpact
Components
GHD12331AA - 06/2009
Using Masterpact
DB119747
GHD12331AA - 06/2009
Using Masterpact
The springs in the circuit breaker operating mechanism must be charged to store the energy required to close the main contacts. The springs may be charged manually using the charging handle or automatically by the optional MCH gear motor.
Manual charging: Pull the handle down seven times until you hear a "clack".
E51347A E46790A
Automatic charging: If the MCH gear motor is installed, the spring is automatically recharged after each closing.
GHD12331AA - 06/2009
Using Masterpact
Closing conditions
Closing (i.e. turning the circuit ON) is possible only if the circuit breaker is "ready to close". The prerequisites are the following: b device open (OFF) b springs charged b no opening order present. The circuit breaker will not close unless it is "ready to close" when the order is given.
Locally (electrical)
BPFE
E60049A
XF
Press the electrical closing pushbutton. By adding an XF closing release, the circuit breaker can be closed locally.
Remotely
XF
DB119751 E51294A
When connected to a remote control panel, the XF closing release can be used to close the circuit breaker remotely.
Anti-pumping function
The purpose of the mechanical anti-pumping function is to ensure that a circuit breaker receiving simultaneous opening and closing orders does not open and close indefinitely. If there is a continuous closing order, after opening the circuit breaker remains open until the closing order is discontinued. A new closing order is required to close the circuit breaker. A new order is not required if the closing release is wired in series with the PF "ready to close" contact.
E51294A
GHD12331AA - 06/2009
Using Masterpact
Remotely Use one of the following solutions: b one or two MX opening releases (MX1 and MX2) b one MN undervoltage release b one MN undervoltage release with a delay unit. When connected to a remote control panel, these releases can be used to open the circuit breaker remotely.
MX1, MX2, MN
E51294A E51296A
DB119751
Delay unit
GHD12331AA - 06/2009
Using Masterpact
The circuit breaker signals a fault trip by: b a mechanical indicator on the front b one or two SDE "fault-trip" indication contacts SDE1, SDE2 (SDE2 is optional). Locally If the circuit breaker is not equipped with the automatic reset option, reset it manually.
DB119752
E60047A
DB119751
Remotely Use the Res electrical remote reset option (not compatible with an SDE2).
E60050A
10
GHD12331AA - 06/2009
Using Masterpact
Lead seal.
Screws.
DB119755
DB119757
DB119756
GHD12331AA - 06/2009
11
Using Masterpact
To disable local and remote circuit-breaker closing, use as needed one to three padlocks or a keylock.
Install one to three padlocks maximum shackle diameter 5 to 8 mm max. (0.2 to 0.3 in. max.)
Locking Open the circuit breaker.
DB106444
12
GHD12331AA - 06/2009
Using Masterpact
PROFALUX
GHD12331AA - 06/2009
13
DB119770
The circuit breaker comprises a safety function, which requires the confirmation of the manual order circuit breaker opening, to be able to insert the handle.
DANGER
ELECTRIC SHOCK, EXPLOSION ORARC FLASH HAZARD b Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices. See NFPA 70E. b This equipment must be installed and serviced only by qualified electrical personnel. Failure to follow these instructions will result indeath, serious injury or equipment damage.
Drawout circuit breaker status This function can be carried out only if the opening button is pushed Connection or disconnection of the drawout circuit breaker requires insertion of the racking handle. If interlocks, padlocks or an open door lock are in place, the racking handle cannot be inserted.
Position indicator
Connector position
Connectors
Clusters Secondary (control)
Engaged
Connected Engaged
DB106447 DB119771
Test
DB106449 DB119772
Disengaged
Engaged
Disengaged
DB106451 DB119773
Disengaged
Disengaged
Withdraw
DB106451 DB119774
Disengaged
Disengaged
14
GHD12331AA - 06/2009
DB119776
GHD12331AA - 06/2009
15
Racking
These operations require that all cradle-locking functions be disabled (see pages 11, 12, 13).
Prerequisites
To connect and disconnect Masterpact, the crank must be used. The locking systems, padlocks and the racking interlock all inhibit use of the crank.
The circuit breaker comprises a safety function, which requires the confirmation of the manual order circuit breaker opening, to be able to insert the handle.
DB106444 DB119777
Change the circuit breaker from the "connected" to "test" position, then to "disconnected" position
The circuit breaker is in "connected" position.
The circuit breaker is in "test" position. Remove the crank or continue to "disconnected" position.
16
GHD12331AA - 06/2009
Racking
For complete information on Masterpact handling and mounting, see the installation manual(s). Before mounting the circuit breaker, make sure it matches the cradle.
Inserting Masterpact
Position the circuit breaker on the rails. Check that it rests on all four supports. Open the circuit breaker (in any case, it opens automatically during connection).
DB110367
DB119783
DB119781
DB119782
If you cannot insert the circuit breaker in the cradle, check that the mismatch protection on the cradle corresponds to that on the circuit breaker.
DB119780
Push the circuit breaker into the cradle, taking care not to push on the control unit.
GHD12331AA - 06/2009
17
Racking
These operations require that all cradle-locking functions be disabled (see pages 11, 12, 13).
Racking the circuit breaker from the "disconnected" to "test" position, then to "connected" position
The device is in "disconnected" position.
DB119784
The circuit breaker comprises a safety function, which requires the confirmation of the manual order circuit breaker opening, to be able to insert the handle.
DB106444
The device is in "test" position. Remove the crank or continue to "connected" position.
18
GHD12331AA - 06/2009
To set up a mismatch-prevention combination for the circuit breaker and the cradle, see the mismatchprevention installation manual.
GHD12331AA - 06/2009
19
The locking device is installed on the left or right-hand side of the cradle. b when the circuit breaker is in "connected" or "test" position, the latch is lowered and the door is locked b when the circuit breaker is in "disconnected" position, the latch is raised and the door is unlocked.
DB119786
DB119787
20
GHD12331AA - 06/2009
To disable connection of the circuit breaker in "disconnected" position in the cradle, use as needed: b one to three padlocks b one or two keylocks b a combination of the two locking systems. If specified when ordering the cradle, this locking function may be adapted to operate in all positions ("connected", "test" and "disconnected"), instead of in "disconnected" position alone.
Disabling connection when the circuit breaker is in "disconnected" position, using one to three padlocks maximum shackle diameter 5 to 8 mm max. (0.2 to 0.3 in. max.)
Locking Circuit breaker in "disconnected" position.
DB119790
GHD12331AA - 06/2009
21
PROFALUX
22
DB118749
GHD12331AA - 06/2009
GHD12331AA - 06/2009
23
Shutter Lock
The shutter lock (A) is used to prevent connection of the circuit breaker by locking the shutter in the closed position. b Standard with shutter accessory. b Padlockable. b To lock: v attach a padlock (B) to the shutter lock (A) inside the cradle.
DB119808
24
GHD12331AA - 06/2009
GHD12331AA - 06/2009
25
b Standard connectors are shown in the table below. For information on non-standard connectors, contact the field office. b For connector dimensions, see the catalogue.
Standard Connectors
Rear-connected "T" Vertical (RCTV)
DB106460
Install Bussing
Bussing requirements by circuit breaker and connector are shown in the table below.
Note: the fitter is responsible for the bus wiring toward the connectors. The bus must be supported by the framework of the commutation equipment, without any weight on the connectors.
Connectors
RCTV RCTH FCF
1200 A
26
GHD12331AA - 06/2009
b Standard connectors are shown in the table below. For information on non-standard connectors, contact the field office. b For connector dimensions, see the catalogue.
Standard Connectors
Rear-connected "T" Vertical (RCTV)
DB106431
Install Bussing
Bussing requirements by circuit breaker and connector are shown in the table below.
Note: the fitter is responsible for the bus wiring toward the connectors. The bus must be supported by the framework of the commutation equipment, without any weight on the connectors.
DB106432
Connectors
RCTV RCTH FCF
1200 A
GHD12331AA - 06/2009
27
DB119809
Function
Connector
OF (1) CD CE CT SDE RES MN MX (2) XF (2) PF MCH
Description
Remote operation
Open/Closed circuit breaker or switch position contacts Disconnected position contacts Connected position contacts Test position contacts Electrical fault alarm contact Remote reset Undervoltage trip device Shunt trip Shunt close Ready-to-close contact Spring-charging motor
(1) OF1, OF2, OF3 and OF4 contacts are standard. (2) When communicating MX1 or XF coils are used, terminal (C3 or A3) must be connected to line even if the communication module is not installed. The bypass circuit through terminal C2/A2 is only momentary duty for 0.5 sec. For continuous duty, use the communications command.
A
b b
P
b b
H
b b
Connector
Com: E1-E6 UC1: Z
Description
Communication Zone-selective Interlocking Z1 = ZSI OUT signal Z2 = ZSI OUT Z3 = ZSI IN signal Z4 = ZSI IN short time Z5 = ZSI IN ground fault Modified differential ground fault (MDGF) External neutral Modified differential ground fault (MDGF) 24 Vdc external power supply External neutral plug External phase voltage sensing Two programmable contacts (internal relay) or six programmable contacts (for connection to external M6C module)
b b b b -
b b b b b b b
b b b b b b b
28
GHD12331AA - 06/2009
DB119809
Function
Connector
OF (1) CD CE CT SDE RES MN MX (2) XF (2) PF MCH
Description
Remote operation
Open/Closed circuit breaker or switch position contacts Disconnected position contacts Connected position contacts Test position contacts Electrical fault alarm contact Remote reset Undervoltage trip device Shunt trip Shunt close Ready-to-close contact Spring-charging motor
(1) OF1, OF2, OF3 and OF4 contacts are standard. (2) When communicating MX1 or XF coils are used, terminal (C3 or A3) must be connected to line even if the communication module is not installed. The bypass circuit through terminal C2/A2 is only momentary duty for 0.5 sec. For continuous duty, use the communications command.
A
b b
P
b b
H
b b
Connector
Com: E1-E6 UC1: Z
Description
Communication Zone-selective Interlocking Z1 = ZSI OUT signal Z2 = ZSI OUT Z3 = ZSI IN signal Z4 = ZSI IN short time Z5 = ZSI IN ground fault Modified differential ground fault (MDGF) External neutral Modified differential ground fault (MDGF) 24 Vdc external power supply External neutral plug External phase voltage sensing Two programmable contacts (internal relay) or six programmable contacts (for connection to external M6C module)
b b b b -
b b b b b b b
b b b b b b b
GHD12331AA - 06/2009
29
Electrical diagrams
The diagram is shown with circuits de-energised, all devices open, connected and charged and relays in normal position. Power
DB119831
Control unit
Remote operation
Control unit
Com UC1 UC2 UC3 UC4 / M2C / M6C
E5 E6 Z5 M1 M2 M3 E3 E4 Z3 Z4 T3 T4 E1 E2 Z1 Z2 T1 T2 F2+ VN F1 V3 / 484 / Q3 V2 / 474 / Q2 V1 / 471 / Q1
Remote operation
184 /
SDE2 / Res
K2
SDE1
84
MN / MX2
D2 / C12
MX1
C2 C3 C1
XF
A2 A3 A1
PF
254 252 251
MCH
B2 B3 B1
182 181 / K1
82 81 D1 / C11
A b b b b b b
P b b
H b b
Control unit Com : E1-E6 communication UC1 : Z1-Z5 zone selective interlocking; Z1 = ZSI OUT SOURCE Z2 = ZSI OUT; Z3 = ZSI IN SOURCE Z4 = ZSI IN ST (short time) Z5 = ZSI IN GF (earth fault) M1 = Vigi module input (Micrologic 7) UC2 : T1, T2, T3, T4 = external neutral; M2, M3 = Vigi module input (Micrologic 7) UC3 : F2+, F1 external 24 V DC power supply VN external voltage connector UC4 : V1, V2, V3 optional external voltage connector or M2C : 2 programmable contacts (internal relay); ext. 24 V DC power supply required or M6C : 6 programmable contacts (external relay); ext. 24 V DC power supply required.
Remote operation SDE2 : Fault-trip indication contact or Res : Remote reset SDE1 : Fault-trip indication contact (supplied as standard) MN : Undervoltage release or MX2 : Shunt release MX1 : Shunt release (standard or communicating) XF : Closing release (standard or communicating) PF : "Ready to close" contact MCH : Gear motor (*)
b b b b b b b b
b b b b b b b b
Note: when communicating MX or XF releases are used, the third wire (C3, A3) must be connected even if the communications module is not installed.
30
GHD12331AA - 06/2009
Electrical diagrams
Indication contacts
DB101406 DB101407
Cradle contacts
Indication contacts
OF4 OF3
44 42 41 34 32 31
Cradle contacts
CD2
824 822 821
OF2
24 22 21
OF1
14 12 11
CD1
814 812 811
CE3
334 332 331
CE2
324 322 321
CE1
314 312 311
CT1
914 912 911
(*) 440/480 V AC gear motor for charging (380 V motor + additional resistor)
E60075A
Key: XXX Drawout device only SDE1, OF1, OF2, OF3, OF4 supplied as standard Interconnected connections (only one wire per connection point)
GHD12331AA - 06/2009
31
DB119811
Protective functions, measurement functions and communications are controlled by the Micrologic trip unit (A) installed in the circuit breaker. The trip unit is field replaceable for easy upgrading of functionality. For complete information on trip unit availability and capabilities, refer to the manual of trip unit which accompans the circuit breaker.
b Depending on the model, control units offer in addition: v fault indications v measurement of electrical parameters (current, voltage, power, etc.) v harmonic analysis v communication.
E46108A
32
E51329A
GHD12331AA - 06/2009
The table below describes the features available on the 3.0 A, 5.0 A and 6.0 A trip units with ammeters, the 5.0 P and 6.0 P power measurement trip units and the 5.0 H and 6.0 H harmonic measurement trip units.
Power
5.0 P b
Harmonics
5.0 H b 6.0 H
5.0 A b
6.0 A
6.0 P
b b b b b b b b b b v b b b b b b b b b v b b b b b b b b b v b b b b b b b b b b b b b b b b b b
b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b b
b b b b b b b b b b b b b b b b b b b b b
b = Standard feature v = Available option (1) Requires M2C or M6C programmable contact module. (2) Requires neutral current transformer for 3-phase, 4-wire system.
b The plugs determine the setting range for the long-time protection.
b M2C: 2 contacts (5 A - 240 V) b M6C: 6 contacts (5 A - 240 V). b Permissible load: v 240 V AC: 5 A at cos = 0.7 v 380 V AC: 3 A at cos = 0.7 v 24 V DC: 1.8 A with L/R = 0 v 48 V DC: 1.5 A with L/R = 0 v 125 V DC: 0.4 A with L/R = 0 v 250 V DC: 0.15 A with L/R = 0 b M2C: 24 V DC 5 % power from control unit b M6C: 24 V DC 5 % external supply b Maximum consumption: 100 mA 33
GHD12331AA - 06/2009
Indication contacts
DANGER
ELECTRIC SHOCK, EXPLOSION ORARC FLASH HAZARD b This equipment must be installed and serviced only by qualified electrical personnel. b Turn off all power supplying this equipment before working on or inside equipment. b Always use a properly rated voltage sensing device to confirm power is off. b Replace all devices, doors and covers before turning on power to this equipment. Failure to follow these instructions will result indeath, serious injury or equipment damage.
b OF contacts indicate the position of the main contacts b They trip when the minimum isolation distance between the main contacts is reached.
b 4 changeover contacts b Breaking capacity at cos = 0.3: v standard, minimum current 10 mA / 24 V V AC 240/380 6 A (rms) 480 6 A (rms) 690 6 A (rms) V DC 24/48 2.5 125 0.5 250 0.3 v low level, minimum current 1 mA / 4 V V AC 24/48 240 380 V DC 24/48 125 250 5 A (rms) 5 A (rms) 5 A (rms) 5 / 2.5 A 0.5 A 0.3 A
b Changeover contact b Breaking capacity at cos = 0.3: v standard, minimum current 10 mA / 24 V V AC 240/380 5 A (rms) 480 5 A (rms) 690 3 A (rms) V DC 24/48 3A 125 0.3 A 250 0.15 A v low level, minimum current 1 mA / 4 V V AC 24/48 240 380 V DC 24/48 125 250 3 A (rms) 3 A (rms) 3 A (rms) 3A 0.3 A 0.15 A
E60054A
b Changeover contact b Breaking capacity at cos = 0.3: v standard, minimum current 10 mA / 24 V V AC 240/380 5 A (rms) 480 5 A (rms) 690 3 A (rms) V DC 24/48 3A 125 0.3 A 250 0.15 A v low level, minimum current 1 mA / 4 V V AC 24/48 240 380 V DC 24/48 125 250 3 A (rms) 3 A (rms) 3 A (rms) 3A 0.3 A 0.15 A
34
GHD12331AA - 06/2009
Indication contacts
E60050A
b Changeover contact b Breaking capacity 50/60 Hz for AC power: V AC 240 380 480 690 V DC 24/48 125 250 10 A (rms) 6 A (rms) 6 A (rms) 3 A (rms) 3A 0.5 A 0.25 A
E51332A
b The contact indicates that the device may be closed because all the following are valid: v circuit breaker is open v spring mechanism is charged v a maintained closing order is not present v a maintained opening order is not present.
b Changeover contact b Breaking capacity at cos = 0.3: v standard, minimum current 10 mA / 24 V V AC 240/380 5 A (rms) 480 5 A (rms) 690 3 A (rms) V DC 24/48 3A 125 0.3 A 250 0.15 A v low level, minimum current 1 mA / 4 V V AC 24/48 240 380 V DC 24/48 125 250 3 A (rms) 3 A (rms) 3 A (rms) 3A 0.3 A 0.15 A
GHD12331AA - 06/2009
35
E46790A
b Power supply: v V AC 50/60 Hz: 48/60 100/130 - 200/240 - 277 400/440 - 480 v V DC: 24/30 - 48/60 100/125 - 200/250 b Operating threshold: 0.85 to 1.1 Un b Consumption: 180 VA or W b Inrush current: 2 to 3 In for 0.1 second b Charging time: 3 seconds max. b Operating rate: aximum 3 cycles per minute b CH contact: see page 35.
E51294A
36
GHD12331AA - 06/2009
E51294A
b Power supply: v V AC 50/60 Hz: 24/48 100/130 - 200/250 240/277 - 380/480 v V DC: 24/30 - 48/60 100/130 - 200/250 b Operating threshold: v opening: 0.35 to 0.7 Un v closing: 0.85 Un b Consumption: v pick-up: 200 VA or W (80 ms) v hold: 4.5 VA or W b Circuit-breaker response time at Un: 40 ms 10.
E51296A
b The unit delays operation of the MN release to eliminate circuit-breaker nuisance tripping during short voltage dips b The unit is wired in series with the MN and must be installed outside the circuit breaker.
b Power supply V AC 50/60 Hz, V DC: v non adjustable: 100/130 - 200/250 v adjustable: 48/60 - 100/130 200/250 - 380/480 b Operating threshold: v opening: 0.35 to 0.7 Un v closing: 0.85 Un b Consumption: v pick-up: 200 VA or W (80 ms) v hold: 4.5 VA or W b Circuit-breaker response time at Un: v non adjustable: 0.25 second v adjustable: 0.5 - 0.9 1.5 - 3 seconds.
E60344A
GHD12331AA - 06/2009
37
Under pick-up conditions, the level of consumption is approximately 150 to 200 VA. Consequently, for low supply voltages (12, 24, 48 V), cables must not exceed a maximum length determined by the supply voltage and the cross-section of the cables. Indicative values for maximum cable lengths (in meters/ft)
12 V
MN
2.5 mm2 1.5 mm2 2.5 mm2 1.5 mm2 2.5 mm2 1.5 mm2 (13 AWG) (15 AWG) (13 AWG) (15 AWG) (13 AWG) (15 AWG)
100 % source voltage 58/190 36/118 85 % source voltage 16/52 10/32 MX-XF 100 % source voltage 21/68 12/39 115/377 70/229 85 % source voltage 10/32 6/19 75/246 44/144 Note: the indicated length is that for each of the two supply wires 280/918 75/246 165/541 45/147
24 V
48 V
38
GHD12331AA - 06/2009
E47341A
E60499A
Escutcheon CDP
b Optional equipment, one CDP per device v for fixed device v for drawout device.
b The CDP increases the degree of protection to IP40 and IK07 (fixed and drawout devices).
E60497A
b Mounted with a CDP, the CCP increases the degree of protection to IP54 and IK10 (fixed and drawout devices).
E60498A
Blanking plate OP
b Optional equipment, one OP per device. b Used with the escutcheon, this option closes off the door cut-out of a cubicle not yet equipped with a device. It may be used with the escutcheon for both fixed and drawout devices.
GHD12331AA - 06/2009
39
Transparent cover for pushbutton locking using a padlock, lead seal or screws
b Optional equipment, one locking cover per device. b The transparent cover blocks access (together or separately) to the pushbuttons used to open and close the device b Locking requires a padlock, a lead seal or two screws.
E60347A
E60346A
E60348A
Ronis
E51286A
Profalux
DB119180
40
GHD12331AA - 06/2009
Cradle accessories
DB106543
Safety shutters
b Standard equipment b Set of shutters for top and bottom drawout, front/rear connection: v 3 poles v 4 poles.
b Mounted on the cradle, the safety shutters automatically block access to the disconnecting contact cluster when the device is in the "disconnected" or "test" positions.
b IP20 for cradle connections b IP40 for the disconnecting contact cluster.
If specified when ordering the cradle, this locking function may be adapted to operate in all positions ("connected", "test" and "disconnected"), instead of in "disconnected" position alone.
Ronis
E51286A E51273A
Profalux
DB119180 DB119191
GHD12331AA - 06/2009
41
Cradle accessories
E60011A
Door interlock
b Optional equipment: one door interlock per cradle.
b This device inhibits opening of the cubicle door when the circuit breaker is in "connected" or "test" position.
E51498A
Racking interlock
b Optional equipment: one racking interlock per cradle.
b This device prevents insertion of the racking handle when the cubicle door is open.
E59190A
Mismatch protection
b Standard equipment: one mismatch protection device per cradle.
b Mismatch protection offers twenty different combinations that the user may select to ensure that only a compatible circuit breaker is mounted on a given cradle.
E60345A
b The shield prevents access to the terminal block of the electrical auxiliaries.
"Connected", "disconnected" and "test" position carriage switches (CE, CD, CT)
b Optional equipment: one to six carriage switches b Standard configuration, 0 to 3 CE, 0 to 2 CD, 0 to 1 CT. v standard v low level. b The carriage switches indicate the three positions: CE: connected position CD: disconnected position (when the minimum isolation distance between the main contacts and the auxiliary contacts is reached) CT: test position. b Changeover contact b Breaking capacity at cos = 0.3: v standard, minimum current 10 mA / 24 V V AC 240 8 A (rms) 380 8 A (rms) 480 8 A (rms) 690 6 A (rms) V DC 24/48 2.5 A 125 0.8 A 250 0.3 A v low level, minimum current 1 mA / 4 V V AC 24/48 240 380 V DC 24/48 125 250 42 5 A (rms) 5 A (rms) 5 A (rms) 2.5 A 0.8 A 0.3 A
E46095A
GHD12331AA - 06/2009
GHD12331AA - 06/2009
43
Initial tests
Procedure
These operations must be carried out in particular before using a Masterpact device for the first time.
DANGER
ELECTRIC SHOCK, EXPLOSION ORARC FLASH HAZARD b This equipment must be installed and serviced only by qualified electrical personnel. b Turn off all power supplying this equipment before working on or inside equipment. b Always use a properly rated voltage sensing device to confirm power is off. b Replace all devices, doors and covers before turning on power to this equipment. Failure to follow these instructions will result indeath, serious injury or equipment damage.
A general check of the circuit breaker takes only a few minutes and avoids any risk of mistakes due to errors or negligence. A general check must be carried out: b prior to initial use b following an extended period during which the circuit breaker is not used. A check must be carried out with the entire switchboard de-energised. In switchboards with compartments, only those compartments that may be accessed by the operators must be de-energised.
Electrical tests
Insulation and dielectric-withstand tests must be carried out immediately after delivery of the switchboard. These tests are precisely defined by international standards and must be directed and carried out by a qualified expert. Prior to running the tests, it is absolutely necessary to: b disconnect all the electrical auxiliaries of the circuit breaker (MCH, MX, XF, MN, Res electrical remote reset) b remove the long-time rating plug on the 7.0 A, 5.0 P, 6.0 P, 7.0 P, 5.0 H, 6.0 H, 7.0 H control units. Removal of the rating plug disconnects the voltage measurement input.
Switchboard inspection
Check that the circuit breakers are installed in a clean environment, free of any installation scrap or items (tools, electrical wires, broken parts or shreds, metal objects, etc.).
Check that the devices conform with the installation diagram: b breaking capacities indicated on the rating plates b identification of the control unit (type, rating) b presence of any optional functions (remote ON/OFF with motor mechanism, auxiliaries, measurement and indication modules, etc.) b protection settings (long time, short time, instantaneous, earth fault) b identification of the protected circuit marked on the front of each circuit breaker.
Check device mounting in the switchboard and the tightness of power connections. Check that all auxiliaries and accessories are correctly installed: b electrical auxiliaries b terminal blocks b connections of auxiliary circuits.
Operation
Check the mechanical operation of the circuit breakers: b opening of contacts b closing of contacts.
Check the control unit of each circuit breaker using the respective user manuals.
44
GHD12331AA - 06/2009
DANGER
ELECTRIC SHOCK, EXPLOSION ORARC FLASH HAZARD b This equipment must be installed and serviced only by qualified electrical personnel. b Turn off all power supplying this equipment before working on or inside equipment. b Always use a properly rated voltage sensing device to confirm power is off. b Replace all devices, doors and covers before turning on power to this equipment. Failure to follow these instructions will result indeath, serious injury or equipment damage.
Faults are signalled locally and remotely by the indicators and auxiliary contacts installed on circuit breakers (depending on each configuration). See from page 34 in this manual and the user manual of the control unit for information on the fault indications available with your circuit breaker.
A circuit must never be reclosed (locally or remotely) before the cause of the fault has been identified and cleared. A fault may have a number of causes: b depending on the type of control unit, fault diagnostics are available. See the user manual for the control unit. b depending on the type of fault and the criticality of the loads, a number of precautionary measures must be taken, in particular the insulation and dielectric tests on a part of or the entire installation. These checks and test must be directed and carried out by qualified personnel.
The circuit breaker can be reset locally or remotely. See page 10 in this manual for information on how the circuit breaker can be reset.
GHD12331AA - 06/2009
45
Maintenance operations
Before undertaking any maintenance work, de-energise the installation and fit locks or warnings in compliance with all applicable safety standards.
DB119812
Arc chutes
b Check the arc chutes: v chamber intact v separators not corroded. If necessary, replace the arc chutes.
3 3
DB119814
b Refit the arc chutes and secure with a tightening torque of 1.5 Nm. (13 Ib-in.)
If the control unit has a maintenance indicator, there is no need to systematically check the contacts. If the contacts are worn, have the concerned poles replaced by the Schneider Electric service centre.
b Remove the arc chutes b Visually check the contacts If necessary, contact Schneider Electric After-sales support.
Disconnecting-contact clusters
b Grease the contacts using the grease recommended on page 48 b Check the contacts as follows: v open the circuit breaker v de-energise the busbars v disconnect the circuit breaker v remove the circuit breaker v check the contact fingers (no sign of copper should be visible). Replace any worn clusters.
46
E60002A
DB119813
2 2
GHD12331AA - 06/2009
GHD12331AA - 06/2009
47
Electrical accessories
The electrical accessories that may require replacement are the following: b MCH gear motor b MX opening release(s) b XF closing release b MN undervoltage release. See pages 36 and 37 in the "Auxiliaries for remote operation" section for their characteristics and part numbers.
E60002A
Arc chutes
b 1 arc chute: v type N v type L1.
E60349A
Front
E60496A
Charging handle
b 1 handle.
b 1 per device
E51336A
Crank
b 1 per device.
E46237A
Disconnecting-contact clusters
b 1 cluster.
48
GHD12331AA - 06/2009
GHD12331AA - 06/2009
49
Problem
Probable causes
b Circuit breaker padlocked or keylocked in the "open" position b Circuit breaker interlocked mechanically in a source changeover system b Circuit breaker not completely connected
Solutions
v check the position of the other circuit breaker in the changeover system v modify the situation to release the interlock v terminate racking in (connection) of the circuit breaker
b The reset button signalling a fault trip has not been reset
v clear the fault v push the reset button on the front of the circuit breaker b Stored energy mechanism not charged v charge the mechanism manually v if it is equipped with a an MCH gear motor, check the supply of power to the motor. If the problem persists, replace the gear motor (MCH) b MX opening shunt release permanently v there is an opening order. supplied with power Determine the origin of the order. The order must be cancelled before the circuit breaker can be closed b MN undervoltage release not supplied with v there is an opening order. power Determine the origin of the order. v check the voltage and the supply circuit (U > 0.85 Un). If the problem persists, replace the release b XF closing release continuously supplied with v cut the supply of power to the XF closing power, but circuit breaker not "ready to close" release, then send the closing order again via (XF not wired in series with PF contact) the XF, but only if the circuit breaker is "ready to close" b Permanent trip order in the presence of a v Disable these protection functions on the Micrologic P or H control unit with minimum voltage Micrologic P or H control unit and minimum frequency protection in Trip mode and the control unit powered Circuit breaker cannot be closed remotely but can be opened locally using the closing pushbutton Unexpected tripping without activation of the reset button signalling a fault trip b Closing order not executed by the XF closing release v check the voltage and the supply circuit (0.85 - 1.1 Un). If the problem persists, replace the XF release b MN undervoltage release supply voltage too low v check the voltage and the supply circuit b Load-shedding order sent to the MX opening (U > 0.85 Un) release by another device v check the overall load on the distribution system v if necessary, modify the settings of devices in the installation b Unnecessary opening order from the MX v determine the origin of the order opening release A fault is present : b overload b earth fault b short-circuit detected by the control unit v determine and clear the causes of the fault v check the condition of the circuit breaker before putting it back into service v see the user manual of the control unit v press the reset button v modify the distribution system or the controlunit settings v check the condition of the circuit breaker before putting it back into service v press the reset button v clear the fault v check the condition of the circuit breaker before putting it back into service v press the reset button
Unexpected tripping with activation of the reset button signalling a fault trip
Instantaneous opening after each attempt to close the circuit b Thermal memory breaker with activation of the reset button signalling a fault trip b Transient overcurrent when closing
b Closing on a short-circuit
50
GHD12331AA - 06/2009
Problem
Probable causes
b Opening order not executed by the MX opening v check the voltage and the supply circuit release (0.7 - 1.1 Un). If the problem persists, replace the MX release b Opening order not executed by the MN v drop in voltage insufficient or residual undervoltage release voltage (> 0.35 Un) across the terminals of the undervoltage release. If the problem persists, replace the MN release b Operating mechanism malfunction or welded contacts b Insufficient supply voltage for the MCH gear motor v contact a Schneider service centre v check the voltage and the supply circuit (0.7 - 1.1 Un). If the problem persists, replace the MCH release v push the reset button in completely v disable the locking function v press the reset button v turn the crank until the circuit breaker is in disconnected position and the reset button out v pull the rails all the way out v check that the cradle corresponds with the circuit breaker v remove the lock(s) v reposition the clusters v disable the cradle locking function v press the reset button v insert the circuit breaker completely so that it is engaged in the racking mechanism v check the circuit breaker position by making sure the reset button is out v remove the crank and store it v contact a Schneider service centre v check the circuit breaker position by making sure the reset button is out v remove the crank and store it
Solutions
Circuit breaker cannot be opened locally Circuit breaker cannot be reset locally but not remotely
Nuisance tripping of the circuit breaker with activation of the reset b Reset button not pushed-in completely button signalling a fault trip Impossible to insert the crank in connected, test or disconnected position Impossible to turn the crank Circuit breaker cannot be removed from chassis b A padlock or keylock is present on the chassis or a door interlock is present b The reset button has not been pressed b Circuit breaker not in disconnected position
b The rails are not completely out b Cradle/circuit breaker mismatch protection b The safety shutters are locked b The disconnecting-contact clusters are incorrectly positioned b Cradle locked in disconnected position b The reset button has not been pressed, preventing rotation of the crank b The circuit breaker has not been sufficiently inserted in the cradle b The circuit breaker is not in the right position b The cranck is still in the cradle b Check that locking in any position is enabled b The circuit breaker is not in the right position b The cranck is still in the cradle
GHD12331AA - 06/2009
51
Notes
52
GHD12331AA - 06/2009
As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication. This document has been printed on ecological paper Design: Schneider Electric Photos: Schneider Electric Printed:
06-2009