Fieldbus Basics PDF
Fieldbus Basics PDF
Fieldbus Basics PDF
Topics
FOUNDATION fieldbus Architecture H1 fieldbus Overview H1 Technology High Speed Ethernet (HSE) Overview
What is Fieldbus?
A fieldbus is an all-digital, serial two-way, multi-drop communication System. H1 network interface to field equipment:- Sensors, Actuators & I/O. (31.25kbps) HSE provides integration of high speed controllers, subsystems (via Linking Device) and data servers and workstation. (High Speed Ethernet, 100mbps)
Integrated Architecture
Management Information Systems (MIS), Enterprise Resource Planning (ERP), and Human Machine Interface (HMI) access the H1 Fieldbus information via the Data Servers. Fieldbus expands the operators view of the entire process.
Process Automation
H1-Fieldbus
H1 Overview
The Future is Digital
Multiple Variables
Fieldbus supports multiple variables from each device to be brought into the control system for archiving, trend analysis, process optimization, reporting, predictive maintenance and for asset management. MVT Devices: ph Transmitter, Coriolis flowmeter; Valve Positioner; DP Transmitter; Magnetic Flowmeter; Vortex flowmeter;
HSE
Analog Controller PV
4-20mA
I/O Subsystem
Diagnostics
Self Diagnostics and communication capabilities of Fieldbus devices increase asset utilization that helps reduce downtime. Both Plant operation and Maintenance personnel are informed allowing corrective actions to be promptly taken. Process Management is no longer just process control. Its now also asset management using a wealth of information from your assets
HSE
Analog Controller PV
4-20mA
I/O Subsystem
Control Strategy
Standard Function Blocks is used to implement the Control Strategy. Many control system functions such as AI, PID and AO can be performed by the field device through the use of these Standard Function Blocks. Distribution of control into field devices can reduce the amount of hardware and cabinet footprint needed.
HSE
H1 Technology
The Future is Digital
10
H1 Technology
Open Systems Interconnect (OSI) layered communication model is used to model these components
11
Physical Layer
Fieldbus Physical Layer : Mechanism to Transmit and receive signals across the network
IEC 61158-2
Maintenance Workstation
Plant Ethernet
Asset Management
Cables Terminators H1 Power Conditioners Fieldbus Device Couplers Short Circuit Protection Redundancy Considerations Hazardous Area Considerations Up to max 32 devices per segment - depends on several factors Limited to 16 by host Limited to less by distance Limited to less by process cycle time
The Future is Digital
HSE Ethernet
12
Device Communications
i
Device Current Steady-state
10mA
Fieldbus signal
Receiving Transmitting
Device Connections
100 Terminator 1 F
13
Host Computer
FFPS T
T
H1 Interface
Segment Total 1900m Trunk Spurs 120m
Device 1
This concept is typically applied to: Any kind of instrument in the safe (non hazardous) area Ex nA instruments in Zone 2 Ex d instruments in Zone 1
Device 2
Device 3
14
14
Fieldbus Cable
Recommended:-Shielded, twisted-pair cable, designed to a specific impedance to reduce signal reflections and maximize network length The Fieldbus Foundation has a Cable Specification (FF-844) so look for cable with a check mark
IEC 61158-2 Cable Design Type A Shielded, twisted pair 0.8 mm 18AWG 44/km 100 1900 m 20%
Conductor Cross Section * Loop Resistance * (DC current) Impedance @31.25kHz Segment Length (including Spur Length)
* 15
Typical values
Power Conditioning
Instrument bulk power supply must be Conditioned for robust Fieldbus Communications Placing inductance between the power supply and the Fieldbus wiring is a way to isolate the Fieldbus signal from the low impedance of the bulk supply. Provides isolation of the Fieldbus circuits from ground, current limiting to the segment if the cable is shorted Typically installed in load sharing redundant configurations. Host System
18 to 32V
16
Terminate the trunk cable Distribute power to field devices Short circuit protection Test points for maintenance Local LED diagnostics
Each device is connected in parallel Without protection, a short circuit could shut the segment down
17
Segment Terminators
Terminators are required one at each end The wiring between the two terminators is defined as the trunk.
24VDC
Host
FFPS
T
H1 Interface
Trunk
100 1 F Spurs
No more than two terminators may be used Matches the impedance of the cable Ensures a balanced transmission line
Device 1
Device 2
Device 3
18
Segment Terminators
Terminator errors generally occur in the field Junction Box; either not installed (or switched-on) or too many installed. No terminators are to be installed in the Field Device. Terminator at Power Conditioner is built-in Installed by the electrical contractor, not normally aware of the importance of the Terminator. Use Automatic Terminators where possible to eliminate installation errors.
TwoTerminators
(Waveform with 300 metres of Cable)
19
Ohms Law is best guide Determine total device draw per segment = Id Include 20% spares allowance Spur Short Circuit current Hand Held Diagnostic Tools Determine cable resistance & length = Rc , Xm Define source voltage = Vp Assume ALL devices are at end of segment Need to ensure that Vd 9V Voltage at device Vd = Vp [ Id +I(HH) +1SC]x Rc x Xm)
DesignMATE Segment design tool at fieldbus.org
20
Device Coupler
Redundant H1 Interface
FFPS
Redundant Trunk
Spurs
Balance between Availability and Reliability Redundant Controller Redundant H1 Interface Redundant Bulk DC Power with Battery Back-up Redundant Fieldbus Power Supply Redundant Field Devices Redundant Trunk Cable Restrict no. of Valves & Devices per segment
The Future is Digital
Device 1
Device 2
Device 3
21
H1 Technology
Open Systems Interconnect (OSI) layered communication model is used to model these components
22
H1Scheduled Communications
Link Active Scheduler (LAS) controls the transmission of messages Recognises and add new devices to the segment Removes non-responsive devices from the segment Polls devices for process loop data at scheduled times; (CD token)
Primarily Loop Control (PV)
CD (a) Trunk
Schedule x y LAS z
Data Subscriber
Data Subscriber
LAS Redundancy; If the current LAS fails, one of the Link Masters will take over the LAS functions and the operation of the fieldbus will continue.
The Future is Digital
23
H1Unscheduled Communications
The LAS grants permission to a device to use the fieldbus by issuing a Pass Token (PT) message to the device. Devices that respond properly to the Pass Token (PT) command will remain in the Live List.
Alarms, &/or Setpoint Changes
PT (x)
Trunk
Data Device x
Data
Whenever a device is added or removed from the Live List, the LAS broadcasts changes to the Live List to all devices. This allows each device to maintain a current copy of the Live List
The Future is Digital
24
H1 Technology
25
Resource Block
The Resource Block describes characteristics of the fieldbus device such as device name, manufacturer and serial number, etc. There is only one Resource Block in a device.
FIM
H1 link interfaces
Transducer Block
Transducer Blocks are used to configure devices. Transducer Blocks are required to Read sensors value and command output value.
FIM
Function Blocks
The Control System Strategy is built using Function Blocks. Each Function Block has an Input, performs a set of operations and produces an output, they can be linked in the device or over the fieldbus. The execution of each Function Blocks is precisely scheduled and there can be many function blocks in a single user application.
AI Block Block AI PID Block Block PID
AO Block Block AO
28
Control Strategy can be built using Function Blocks built into field devices. A flow transmitter may contain an AI function block. A Control Valve might contain a PID function block as well as the expected AO Block. Thus, a complete control loop can be built using a simple transmitter and a control valve.
HSE
Fieldbus Controller
H1 Fieldbus
PID AI AO
29
Example of a complete control loop using Function Blocks located in fieldbus Devices.
loop 110 period of execution Scheduled Scheduled Closed loop control Function Block Execution Scheduled Communication Unscheduled Communication Unscheduled Unscheduled Alarms/Events Maintenance/Diagnostic Information Program Invocation Permissives/Interlocks Display Information Trend Information Configuration
30
31
High Speed Ethernet Compliments H1 Linking Devices (LD) Integrate H1 segments HSE High Speed Control Backbone Provides the Open Interface for Data Servers Standard Function Blocks PLUS Flexible Function Blocks for Discrete/Batch/PLC Redundant HSE Interfaces and Devices Commercial off the shelf Ethernet Hardware (COTS)
MIS
APPLICATION PACKAGES
Data Servers
LD
LD
P L
P L
P L
32
HSE Client
Gateway
I/O Network
Linking Device
H1
P L P L
H1
P L
H1
Plant
Plant
Plant
33
Gateway
I/O Network
Linking Device
H1
P L P L
H1
P L
H1
Plant
Plant
Plant
34
Gateway
I/O Network
Linking Device
H1
P L P L
H1
P L
H1
Plant
Plant
Plant
35
Summary
Proven: FF provides closed loop digital control: sensor to actuator
FOUNDATION H1 has made it possible to "mine" important information from the plant floor. This information empowers operators and technicians to make plant operation and maintenance easier
The technology enables improved asset management using device management software, as many failures can be predicted and faults can be diagnosed in detail
FOUNDATION fieldbus is tried and tested since 15 years
36
www.fieldbus.org
37