Triconex FTA-MUX Cards - HPTB/32/TR-AI-01
Triconex FTA-MUX Cards - HPTB/32/TR-AI-01
Triconex FTA-MUX Cards - HPTB/32/TR-AI-01
Connections
Wiring Options
Field side Fixed screw terminals
Control side 56-pin ELCO style connector
RS-485 Removable screw terminals
Power Removable screw terminals
Electrical
Mounting 20 – 30 VDC
Power consumption 0.7 W
Power fuse 315mA, 5x20mm
DC isolation of HART 30 VDC
Mechanical
Mounting T type (EN 50022, DIN462777-3) or
G type (EN 50035, DIN462777-1) DIN rail Model Number
Signal Channels Up to 32 unbalanced signal loops HPTB/32/TR-AI-01
Communication port RS-485, differential pair plus GND
Communication speed 9600 or 19200 baud
Max. Conductor diameter 16 AWG (2.5mm2)
Weight 18 oz. (510 g) • Triconex 3700A replacement FTA
Dimensions 10.1” x 4.9” x 3.1” (L x W x H)
w/o mux (256mm x 125mm x 79mm) • Plug n play wiring capabilities
10.1” x 4.9” x 8.2” (L x W x H)
with mux (256mm x 125mm x 208mm) • 2-, 3-wire or self powered transmitters
• Short circuit protected
Environmental
Operating Temperature Range 0ºC to 55ºC (32ºF to 131ºF)
Relative Humidity 5 to 90% non-condensing
The HPTB/32/TR-AI-01is designed for easy 2700
multiplexer integration with Tricon 9 3700A system. With
Triconex I/O Interface
the 2700 Mux integrated into the board and plug-n-
3700A
play option for the DCS equipment, this provides a very
clean access to the HART signals, while reducing the
Installation Instruction need for marshalling cabinets and reducing equipment
Product installation manual www.elconhis.com/customized-triconex.html that require extra cabinet space. The HART termination
board provides a robust solution for on-line HART
communications, interfaces up to 32 field located HART
devices, and it allows the user to replace the standard
DCS field termination panels.
PWR
ON
FAULT HART TX
MUX
2700
32 Channel
Hart ®
Multiplexer
Legend:
Color •= 4-20 mA Signal RS-485 to
RS-232 converter
Color •= HART Signal
www.elconhis.com
HPTB/32/TR-AI-01
Replaceable
Power Supply
Fuses
Connections
RS-485 Connection
Shield Configuration
JP1 B S A
H1
J1 SUPPLY2 SUPPLY1 J2
+
- + - +
RS485
F1 C101
F2
+
X0
U0
M7
2
2
7M
0U
0X
M1
4.90"
[124.46 mm]
Channels Channels
1-16 TB1 17-32
A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A A
A 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
(PWR)
B B B B B B B B B B B B B B B B B B B B B B B B B B B B B B B B
B 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
(PV IN)
www.elconhis.com
C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C
HISHPTB/32/TR-AI-01
EARTH
C 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
(COM -)
Earth Connection
10.10"
[256.54 mm]
DOC. 129-0153A P/N 907916
HPTB/32/TR-AI-01
PRODUCT INSTALLATION MANUAL DOC. 129-0153A PAGE 2 OF 20
MODEL LISTING
Model Part Number Channels / Function
HPTB/32/TR-AI-01 907912 32-AI
To avoid damage, failure, or improper operation, read this manual carefully before installing
and operating the equipment
Disclaimer
While the HART Interface Solution (HIS) Replacement Panels from Pepperl+Fuchs, Inc. (“HIS Replacement
Panels”) are designed to extract the digital HART data from standard 4-20mA loops, the HIS Replacement
Panels may not provide all of the features, or duplicate all the functions, of the panels they replaced, and
Pepperl+Fuchs, Inc. makes no warranty or representation (and specifically disclaims any express or implied
warranty or representation) that such HIS Replacement Panels are identical to, or will provide all of the
same features or duplicate all of the same functions of, the panels they replace. The terms, conditions and
limitations of any product warranties covering HIS Replacement Panels may be obtained from
Pepperl+Fuchs, Inc.
The information set forth in this Manual is designed to assist the Purchaser in the installation, operation and
maintenance of an HIS Replacement Panel. Such information should not be construed as a warranty or
representation, express or implied, regarding the HIS Replacement Panel or its use in, or suitability for, a
particular application, any such warranties or representations being specifically disclaimed. The terms,
conditions and limitations of any product warranties covering HIS Replacement Panels may be obtained
from Pepperl+Fuchs, Inc. Pepperl+Fuchs, Inc. reserves the right to modify or improve the designs,
specifications, features and/or functions of HIS Replacement Panels at any time without notice.
Copyright and Trademark Information
This manual is copyright of Pepperl+Fuchs with all rights reserved. This manual may not be copied, in
whole or in part, without the written consent of Pepperl+Fuchs. Pepperl+Fuchs reserves the right to make
changes to this manual without notice.
Asset Management Solutions (AMS) is a registered trademark of Emerson Process Management. HART is
a registered trademark of the HART Communication Foundation. Windows is a trademark of Microsoft
Corporation. All other marks are property of their respective owners.
PRODUCT INSTALLATION MANUAL DOC. 129-0153A PAGE 3 OF 20
Table of Contents
1. GENERAL INFORMATION.......................................................................................................................................4
1.1. INTRODUCTION ........................................................................................................................................................4
1.1.1. System Overview..........................................................................................................................................4
1.1.2. HART Overview ............................................................................................................................................4
1.1.3. Asset Management Solutions (AMS) Software Overview ............................................................................4
1.2. TECHNICAL SPECIFICATIONS ....................................................................................................................................5
1.2.1. MUX 2700 Specifications .............................................................................................................................5
1.2.2. HPTB Termination Board Specifications ......................................................................................................5
1.2.3. RS-485 Line Specifications ..........................................................................................................................6
1.3. QUALITY ASSURANCE ..............................................................................................................................................6
1.4. CERTIFICATIONS AND COMPLIANCE ..........................................................................................................................6
2. INSTALLATION ........................................................................................................................................................7
2.1. STORAGE ................................................................................................................................................................7
2.2. UNPACKING AND INSPECTION ...................................................................................................................................7
2.3. ENVIRONMENTAL CONDITIONS..................................................................................................................................7
2.4. INTRINSIC SAFETY ...................................................................................................................................................8
2.5. MOUNTING ..............................................................................................................................................................8
2.6. CABLES...................................................................................................................................................................8
2.7. WIRING ...................................................................................................................................................................9
2.7.1. Power..........................................................................................................................................................10
2.7.2. Grounding ...................................................................................................................................................10
2.7.3. RS-485........................................................................................................................................................11
2.7.4. Field Connections.......................................................................................................................................12
2.7.5. Control Connections ...................................................................................................................................15
2.7.6. HART Communicator .................................................................................................................................15
3. OPERATION ...........................................................................................................................................................15
3.1. INITIAL SETUP........................................................................................................................................................15
3.1.1. 2700 Settings..............................................................................................................................................15
3.1.2. MUX Addressing.........................................................................................................................................16
3.1.3. Baud Rate...................................................................................................................................................16
3.1.4. RS-232/RS-485 Converter .........................................................................................................................16
3.2. START-UP SEQUENCE ............................................................................................................................................16
3.3. CONFIGURATION ....................................................................................................................................................16
3.4. MUX INDICATORS .................................................................................................................................................16
3.5. MODES OF OPERATION ..........................................................................................................................................17
3.6. SYSTEM OPERATION ..............................................................................................................................................17
4. TROUBLESHOOTING ............................................................................................................................................18
4.1. GENERAL ..............................................................................................................................................................18
4.2. MUX 2700 ...........................................................................................................................................................18
5. MAINTENANCE ......................................................................................................................................................19
6. GLOSSARY.............................................................................................................................................................19
7. CONTACT INFORMATION.....................................................................................................................................20
PRODUCT INSTALLATION MANUAL DOC. 129-0153A PAGE 4 OF 20
1. GENERAL INFORMATION
1.1. INTRODUCTION
This manual provides guidance for the installation, operation, and maintenance of your P+F Multiplexer
2700 and termination board. The solution herein is specifically designed for easy Multiplexer integration with
the Triconex TRICON system. Below is a list of termination boards and the Triconex I/O modules with which
they were designed to interface.
HPTB/32/TR-AI-01 3700/A
The P+F Multiplexer 2700 will be referred to in this manual as the MUX 2700. All further general references
to the listed termination boards will be simply HPTB. When referring to the combination of a MUX 2700 and
an HPTB, they will be called the HART Interface Solution, or simply HIS.
1.1.1. SYSTEM OVERVIEW
Your HART Interface Solution interfaces up to 32 field located HART devices. The MUX 2700 is a HART
signal multiplexer unit which allows access to HART communications on existing 4-20mA wiring. It acts as
a gateway device routing communications between the maintenance workstation PC and the HART
devices. The MUX 2700 uses Manchester encoding of the HART protocol for the RS-485 link to the
maintenance workstation PC. To link to each of the HART devices the MUX 2700 communicates using
Bell 202 Frequency Shift Keying (FSK). It interrogates each HART device, retrieves device information, and
stores it in an internal database. This information is available to the maintenance workstation software. In
this way, the MUX 2700 gives the user access to each HART device as if connected directly at the device
itself. A maintenance workstation PC can use this information for configuration, maintenance, calibration,
diagnostics, and data access.
The termination board design allows the DCS and field device wiring to be brought together with the MUX to
complete the system. Various HPTB board designs allow interface with different I/O cards and may include
configurable options including fused / filtered signal lines, loop or device powered instrument lines and 4-
20mA or 1-5 VDC signals. HART Interface Solutions are supplied by P+F in several models in order to
allow simple and reliable connection between SMART devices and various DCS systems.
1.1.2. HART OVERVIEW
HART is an acronym for "Highway Addressable Remote Transducer". The HART protocol makes use of the
Bell 202 FSK standard to superimpose digital signals at a low level on top of the 4-20mA signal. This
enables two-way communication and makes it possible for additional information beyond just the normal
process variable to be communicated to/from a SMART field instrument. The HART protocol allows a host
application (master) to get two or more digital updates per second from a field device. As the digital FSK
signal is phase continuous, there is no interference with the 4-20mA signal.
1.1.3. ASSET MANAGEMENT SOLUTIONS (AMS) SOFTWARE OVERVIEW
AMS software provides an easy-to-use means for integrating various device management software
packages into a unified system. AMS operates under the Microsoft® Windows® format. It combines the
various device (or asset) management tasks into an application with a common look-and-feel and
centralized data storage.
AMS provides access to functionality available via the HART communications protocol for any HART device
whose Device Description (DD) is registered with the HART Communication Foundation.
For more information on installation of AMS software, consult the AMS Installation Guide.
PRODUCT INSTALLATION MANUAL DOC. 129-0153A PAGE 5 OF 20
2. INSTALLATION
2.1. STORAGE
In case of storage of instruments and accessories, proper care should be taken to protect them from any
possible damage. Always store instruments in their sealed original packaging until they are installed.
Provide adequate protection to prevent damages that may be caused by exposure to:
• Rain, excessive humidity and/or temperature excursions (inadequate sheltering).
• Dust (build-up of a corrosive patina that may cause oxidations and reduce isolation).
• Aggressive and polluting atmospheres with consequent corrosion.
• Access by insects/rodents (damage of packing or content).
• Mechanical shocks or unauthorized packing opening.
• Intense vibrations (loosening of fastened parts, fatigue failures, etc.).
• Any other possible risk.
Make sure the storage temperature does not exceed the limits of –20 to +70°C (-4 to 158°F) for
medium/long term storage (days/months) and -25 to +75°C (-13 to 167°F) for short term storage (a few
hours) during transportation or shipment.
2.2. UNPACKING AND INSPECTION
Upon receipt of the materials, you should check the integrity of the packing and the contents. In case of
damage due to shipping, you should promptly and properly report to the shipper, supplying all necessary
information.
If the instruments are not for immediate use, we recommend that you check that all characteristics shown
on the instrument’s label meet order specifications (model, supply voltage and frequency, input/output
range, certification, tag etc.) as well as the actual application requirements.
If not installed, equipment should be stored following the recommendations of the previous section.
2.3. ENVIRONMENTAL CONDITIONS
HIS products, like most modern electronic equipment, can operate in wide temperature and humidity
ranges. However, practical consideration suggests a guideline on operating environment for best results.
• Keep operating temperature below 35°C (95° F), ideally between 20°C and 25°C (68 and 77°F),
avoiding wide and rapid temperature excursions.
• Control relative humidity within 40 to 60% to avoid risks of static charges or condensation.
• Limit the presence of corrosive atmosphere, fumes and dust, sealing and purifying the control room
area and using air filters in the cabinet air intakes (clean cable entry path), if necessary.
• Reduce vibrations (if any) to safe levels.
PRODUCT INSTALLATION MANUAL DOC. 129-0153A PAGE 8 OF 20
2.7. WIRING
The MUX 2700 is a plug-in unit and is connected to the HPTB by two 40 pin connectors. Therefore, all
electrical connections (supply, field connections, serial lines, etc.) are made at the termination board unit.
Refer to Figure 1 for a simplified representation of the termination board configuration and the overall
outside dimension of the product in inches.
Figure 1 –HPTB Configuration
HPTB/32/TR-AI-01
PRODUCT INSTALLATION MANUAL DOC. 129-0153A PAGE 10 OF 20
2.7.1. POWER
Connect 24 VDC to the 2-pin removable terminal at the end of the HPTB. The connector is polarized, so
you cannot insert it incorrectly. The polarity is marked on the terminals. A reverse polarity shunt diode and
series fuse protection are provided to avoid damaging the module in case of accidentally reversing the
polarity connection. In this case, the reverse voltage is clamped at –1.2 V and the fuse blows. Restore
correct supply polarity and replace the blown fuse. Be certain to reinstall a good, properly sized, new fuse.
WARNING!
Improper supply connections can seriously damage the instrument and result in risk of fire
or explosion in hazardous locations!
DC SUPPLY REQUIREMENTS: The MUX is nominally rated for 24 VDC but will function from
approximately 20-30 VDC. The MUX draws a maximum of 100mA from the supply. If the power LEDs fail
to light check that the polarity of the supply line is correct.
WARNING!
Note that a crude, poorly filtered or unregulated supply can produce destructive (hundreds
of volts) voltage spikes during supply transformer switch-off transient. This could cause
minor problems to electro-mechanical components like relays or solenoids but will surely
degrade or destroy electronic equipment.
SUPPLY CONDUCTORS SIZING: Since these HIS boards supply power for the AI channels, a single unit
can normally require up to 2.56A and its conductors should be sized accordingly. Pepperl+Fuchs
recommends 14 AWG or larger wire be used to power this product.
2.7.2. GROUNDING
The HPTB provides an earth terminal lug for connecting the various shield wires to earth. Also included
with the HPTB is a DIN rail mountable terminal block. Use of the terminal lug and terminal block for earth
grounding will provide the shortest path and best practice for grounding of the HPTB. A 10-14 AWG cable
should be secured between the terminal lug and DIN rail block which provides a single point to properly
ground field wiring cable shields. This terminal may not be necessary to use if best practice grounding
techniques are employed.
The HPTB also provides customer selectable capacitive coupling for the shielding. Setting the shield to be
direct coupled or capacitively coupled is accomplished through jumper shunts. Placing the jumper shunt
across the pins will bypass the capacitor and direct couple the corresponding shield to earth. Refer to
Table 2 for a complete list of the shunts and the associated shield. For best practice any shield should be
direct coupled at one end of the circuit.
Table 2 – Shield Configuration
2.7.3. RS-485
An RS-485 network permits up to 32 devices to communicate over a maximum of 1200m (4000 ft) of cable.
The length of this network can be extended if necessary by using RS-485 repeaters. The communication
occurs via a differential signal over a shielded twisted pair of wires. Per the RS-485 specification the signal
wires should be labeled “A” and “B”, but sometimes a “+” and “-“ are used instead. In these cases connect
the “+” to “B” and the “-“ to “A”.
NOTE: A MUX 2700 that is cross-wired on the RS-485 network will not be damaged, but it
also will not communicate.
Since the MUX 2700 is optically isolated it is important to link the signal grounds of the different network
nodes to the host ground through the cable shield. This helps prevent ground potential differences from
causing a loss of data or damage to equipment on the RS-485 network.
Many cable manufacturers make cable specifically designed for RS-485 networks. Pepperl+Fuchs Elcon
recommends using shielded twisted pair cabling and then utilizing the shield as the RS-485 network ground.
This shield should be grounded at the RS-485 converter if possible.
RS-485 wiring must be connected as shown in Figure 2. These wires carry data from the HIS to the PC via
an RS-485/RS-232 converter cable. Connect the converter to a serial port on the PC as indicated in the
converter’s documentation.
Figure 2 – RS-485 Wiring
PRODUCT INSTALLATION MANUAL DOC. 129-0153A PAGE 12 OF 20
HPTB/32/TR-AI-01
Power (+)
A
B 4-20mA
C Shield
Pepperl+Fuchs recommends that all shield drain wires be connected from as close to TB1 as possible to
the nearest grounding point and this point be linked to earth by as short a route as possible.
PRODUCT INSTALLATION MANUAL DOC. 129-0153A PAGE 13 OF 20
HPTB/32/TR-AI-01
Power (+)
A
B 4-20mA
C Common
Pepperl+Fuchs recommends that all shield drain wires be connected from as close to TB1 as possible to
the nearest grounding point and this point be linked to earth by as short a route as possible.
PRODUCT INSTALLATION MANUAL DOC. 129-0153A PAGE 14 OF 20
HPTB/32/TR-AI-01
A
B 4-20mA
C Common
WARNING!
Do not connect the HART Communicator to any Intrinsically Safe field wiring unless the
communicator is approved as Intrinsically Safe and is suitable for the actual classification of
the specific hazardous location. Also consider the HART Communicator safety parameters
and equivalent capacitance and inductance before concluding that you can safely connect it
to the I. S. side of the circuit
3. OPERATION
3.1. INITIAL SETUP
The default settings for each MUX 2700 are as follows:
Address = 1
Baud Rate = 9600
3.1.1. 2700 SETTINGS
The User Switches buffer has eight inputs from a low profile DIP switch reachable through the front label.
The functions of the switches are as follows:
• Switch 7 (T) Reserved for TEST purposes
• Switch 6 (R1) BAUD RATE 1
• Switch 5 (R0) BAUD RATE 0
• Switch 4 (B4) ADDRESS 4
• Switch 3 (B3) ADDRESS 3
• Switch 2 (B2) ADDRESS 2
• Switch 1 (B1) ADDRESS 1
• Switch 0 (B0) ADDRESS 0
Further information is given on the front and side labels. In particular, the side label gives the correct setting
of every DIP switch combination.
PRODUCT INSTALLATION MANUAL DOC. 129-0153A PAGE 16 OF 20
1700
MUXMUX
2700 Block
Block diagram
USER
Channel 1 SWITCHES
M
U
L MICROPROCESSOR
T
I CHANNEL
P SELECT
L
E
X
E From the
Channel 32 R HART
Maintenance
Workstation
RS-485
MODEM CIRCUIT (Through the
SERIAL PORTS RS-485/232
Converter)
PRODUCT INSTALLATION MANUAL DOC. 129-0153A PAGE 18 OF 20
4. TROUBLESHOOTING
4.1. GENERAL
Due to the modular nature of the HIS system, a communication failure may occur anywhere in the data
transfer link from the software to the field device. In order to identify where the loss of communication has
occurred, it is important to understand which components are working correctly. Often, some simple checks
will save hours of troubleshooting. Some of the most common mistakes are: improper wiring connections,
baud rate mismatches, improper network settings, and improper addressing of the MUX 2700.
4.2. MUX 2700
The LEDs on the front of the MUX 2700 provide a convenient indication to the user that the MUX 2700 is
operational. After the MUX 2700 self-test, the <Pwr On> light should be on, the <Fault> light should be off
and the <HART Tx> light may either be off or flashing steadily.
When power to the MUX 2700 is cycled all the lights will come on. Next the green <Pwr On> LED will flash
for approximately 15 seconds while the MUX undergoes a self-test. After the successful completion of the
self-test the LED will go solid on. For the next 60 to 120 seconds, the <HART Tx> light will flash three times
for each channel. During this time, the MUX 2700 is scanning each of the 32 channels. When it is finished,
the <HART Tx> LED will either flash steadily or turn off altogether. If you see all of the above occur, the
MUX 2700 is operating properly.
Note : The MUX 2700A will behave the same except the power LED will not flash during its
self-test.
In addition, the TEST setting on the option switches can be used to gain confidence that the module is
functioning. Follow the procedure below to use this feature:
1. With the power off, set the end switch to the TEST position (ON). The module should not be
connected to the RS-485 network, the RS-485 address switches have no effect. If an RS-485
terminal is connected to the module, the BAUD rate switches should be set.
2. Turn the power on. The LEDs should light for about 1 second each in sequence (RED, YELLOW,
GREEN…).
3. If the LEDs do not flash, there is a fault with the module and it should be returned for replacement.
4. To return to normal operation, remove power to the MUX 2700 and set the TEST switch to the OFF
position. Ensure that the correct BAUD rate is selected and that an RS-485 address is set. Then,
re-apply power.
PRODUCT INSTALLATION MANUAL DOC. 129-0153A PAGE 19 OF 20
If you suspect the MUX 2700 is not functioning properly, please refer to Table 4 below for a summary of
some possible problems.
Table 4 – MUX 2700 Troubleshooting
5. MAINTENANCE
Pepperl+Fuchs apparatus do not require any particular maintenance under normal operating conditions.
They are designed to operate trouble-free and with high stability for long periods.
WARNING!
Any repair made by unauthorized personnel may completely invalidate the safety
characteristics of the unit and could void all warranties. Repair not made by
Pepperl+Fuchs is fully at user's risk and responsibility. In addition, the warranty terms of
the unit will be null and void to all effect.
6. GLOSSARY
DCS Distributed Control System
FSK Frequency Shift Keying
HART® Highway Addressable Remote Transducer
HIS HART Interface Solution
HHT Hand Held Terminal
HPTB HART Panel Termination Board
IS Intrinsic Safety
PLC Programmable Logic Controller
PRODUCT INSTALLATION MANUAL DOC. 129-0153A PAGE 20 OF 20
7. CONTACT INFORMATION
INSTRUCTION MANUAL
MUX2700
MUX 2700G
MULTIPLEXER
FOR MORE INFORMATIONS, VISIT THE DEDICATED HiS WEB SITE: www.elconhis.com
IM-ENG-216/GB
TABLE OF CONTENTS
10. WARRANTY..................................................................................................... “ 23
FOR MORE INFORMATIONS, VISIT THE DEDICATED HiS WEB SITE: www.elconhis.com
WARNING!
This manual is copyright by Elcon Instruments. All rights reserved. No part of manual may be reproduced in part or in
whole without express written consent from Elcon Instruments. Elcon Instruments reserves the right to modify manual
or any part thereof at its discretion without prior notice.
-1-
IM-ENG-216/GB
1. INTRODUCTION
This manual is intended to provide guidance for the installation, operation and maintenance of the Mux2700G HART
Signal Multiplexer (HSM) module. To avoid damage, failure or improper operation the contents of this manual
should be read and understood before installing and operating the instrument.
The Mux2700G HSM is a compact, plug-in module which is able to accept up to 32 HART channels and to feed them
into a single, faster communication line, which is in turn to be connected to a suitable Maintenance Workstation.
The Mux2700G module is intended for use as part of the Elcon HART Interface Solutions (H.I.S.), which provides
appropriate interconnection packages for various applications. H.I.S. makes available a wide set of Termination
Boards – with or without integrated isolators – to support different applications and to directly interface with the
main PLC/DCS equipment. The Mux2700G is simply to be inserted in the selected board to get full HART access to
the relevant field devices while preserving the traditional 4/20 mA analogue loop interfaces.
The Mux2700G use the same effective and compact enclosure of the successful HiD series, including the innovative
“Quick Lock” mechanism to easily insert/remove the unit from the Termination Board without the need for any tool.
Warning !
The Mux2700G unit is not certified for intrinsically safe applications and must not be used to directly interface
with hazardous-area located field devices. In fact, some H.I.S. solutions do allow the mounting of the Mux2700G
on the same board where intrinsically safe isolators are located. In this case, the safety-related application areas
must be addressed by trained personnel which is fully acquainted with the principles of intrinsically safe system.
Elcon Instruments has published a complete tutorial entitled “Guide to Intrinsic Safety” covering most aspect of
intrinsic safety. The book can be obtained from Elcon Instruments free of charge.
-2-
IM-ENG-216/GB
-3-
IM-ENG-216/GB
3. FUNCTIONAL DESCRIPTION
3.1 Overview
The Mux2700G HART Signal Multiplexer (HSM) provides 32 signal channels for connection to field located, “smart”
transmitters or control devices supporting digital communication according to the HART standard. The Mux2700G
acts as a gateway between a Maintenance Workstation (MW) – typically a PC with suitable SW – and the field
instrumentation. The MW connects, in a multi-point configuration, with up to 31 Mux2700G using a fast RS-485 com-
munication channel.
The HART protocol is a widely accepted technique by which standard 4/20 mA field devices can support digital
communication for configuration and maintenance purposes. A modulated, audio-frequency signal (Bell202 FSK) is
in fact superimposed to the analogue current loop providing a 1200 baud, half-duplex communication capability.
The HART protocol, being a widely accepted standard specified up to the application layer, permits an effective
integration, at the Maintenance Workstation level, of field devices from different manufacturers.
The Mux2700G HSM not only uses the HART protocol to communicate with the field devices but also to interface
with the Maintenance Workstation via an RS-485 link. In this way, an highly standardised solution is obtained.
Under the supervision of the Maintenance Workstation, the Mux2700G interrogates each field device, retrieving infor-
mation which are then stored in an internal data-base. This internal data-base can then be accessed in real-time by
the MW which however, when required, can also directly communicate with any specific field device.
-4-
IM-ENG-216/GB
Remote instrument
maintenance
RADIO monitoring for
MODEM unmanned
platform or
remote site
RADIO MODEM
UHF Microwave
CONTROL ROOM
DCS/SCADA SYSTEM P.C. MAINTENANCE WORKSTATION
(Har t or Non Hart
Compatible)
1
NON HAZARDOUS LOCATION
Model
2116/HAT/
up PCU # 1
CATALYTIC CRACKER
to
PORTABLE
NOTEBOOK
32 or LAPTOP
1 Model
2116/HAT/
1 Model
2116/HAT/
1
To
up FROM DCS - PLC I/O up
FIELD CARDS
to DEVICES (To Control Room) to
32 32
To Further
Boards 1
1 Model
ZONE 2
2116/HAT/
RS 485 TANK up
ZONE 1 up PCU # 2
FARM II B
II C BOILER to
to
MUX 2700G
• Hazardous Non Hazardous Locations of Smart Instruments 32
32 • Local or Remote Instruments Maintenance
• Suitable for Existing Smart Field Device Transmitter, Valves, Mas Flow
• Multiple
• Independent to DCS System 1
• ISO 9000 Reporting
1 Model
2116/HAT/
up
PCU # 3 REFORMER
up
to
To Further
to Boards
32
32
To Further To Further
Boards Boards
1 up to 32 1 up to 32 1 up to 32
ZONE 1
NON HAZARDOUS LOCATION II B
FIG. 1
-5-
IM-ENG-216/GB
3.2 Operation
The Mux2700G HSM module implements HART protocol commands and acts as a gateway device between the
Maintenance Workstation (MW) and the field devices. It responds to commands received from the MW (RS-485
interface) as a slave device and issues commands to the HART slaves (field channels) acting as either a Primary
or Secondary Master (according to the HART specification).
A modified version of the HART protocol was implemented on the RS-485 physical layer to obtain a fast and relia-
ble communication with the Maintenance Workstation. In this way, standard HART messages can be used by the
MW for an effective, seamless integration of field devices from different manufacturers.
The Mux2700G can continuously poll each connected field device the get the specified primary (or secondary) HART
variable, automatically updating the internal data-base. This is called scan operation, and can be enabled or disa-
bled by the Maintenance Workstation (the Mux are factory set in the “Scan-Off” condition). When in the “Scan-On”
mode, the MW can generate a warning message whenever a field device stop communicating (e.g. because it is
disconnected from the loop).
At power-up, the Mux2700G always performs a locate activity, that is to say, it polls all the 32 channels to find any
connected – and communicating – field device and to rebuild the required, internal access tables. The locate acti-
vity can be started also by the Maintenance Workstation, and this is usually required to be able to communicate
with a new field device connected to the Mux after power-up. The locate time can range from 15 to 60 seconds,
depending on the specified retry counts (the Mux are factory set with a retry count = 3, resulting in around one
minute of locate time).
In addition to providing access to the HART-capable field instruments, the Mux2700G module is itself, in all respect,
an HART device with parameters and internal functions available to the user (e.g. Tag, Description and unique DIN
– Device Identification Number).
• The Yellow LED should then go Off, unless the scan operation is enabled or the Maintenance Workstation is
directly communicating with a field device.
-6-
IM-ENG-216/GB
A A31
RS-485
B A30
INTERFACE
A32
POWER
SUPPLY
MUX
0.68µF + C32
24V UNIT OPTO CH1
ISOL.
A1 + A
2.2µF
B32
A3 0.68µF
HART
CPU
MODEM + C1
CH32
2.2µF B1
SCREEN
A4,A5,A6
FIG. 2
-7-
IM-ENG-216/GB
A full three-port isolation is also provided. The power supply section is in fact galvanically isolated from both the
analogue multiplexing section and from the RS-485 serial line.
Each input channel is also DC-isolated from the input GND by two non-polarised capacitors. The dual capacitor
solution, usually not to be found on comparable products, avoid the need of having a single common ground for all
input signals. In this way, it is also possible to connect to any “floating” loop without any loss of isolation
In general, the three-port isolation combined with the dual-capacitor approach result in an effective and reliable
solution, with such advantages as:
• undesired ground loops can be easily avoided;
• existing isolation between different ports can be preserved;
• very low risk of disturbing the 4/20 mA loop signal, also in case of fault.
I fact, the Mux2700G architecture is such that any internal single fault never result in any interference with an input
connected 4/20 mA loop. For this reason, the Mux2700G can be used as a monitoring device within safety-sensitive
applications.
-8-
IM-ENG-216/GB
4.1 Presentation
HART Interface Solutions (H.I.S.) makes available a wide set of Termination Boards to support different applica-
tions. There are several styles of interconnection methods available for mounting of the Mux2700G to suit the various
demands of particular installations.These satisfy the basic requirements of:
• general purpose wiring interconnection;
• replacing the function of existing control system termination panels;
• including Intrinsic Safety isolating interfaces.
The details of specific applications can be found in the support documentation for the HART Interface Solutions
(H.I.S.) panels which are custom designed to satisfy these particular needs.
However, the following sections give details of three generic solutions for the mounting of the Mux2700G which are
included to show the scope of these possibilities:
• single Mux2700G mounting on termination panel: 1132/CON-8-H-DS
• multiple Mux2700G mounting on termination panel: 2108/64-HART-D
• Mux2700G integrated with HiD 2000 IS interfaces: 2116/HAT/SACON-HART
-9-
IM-ENG-216/GB
281 mm
RS 485
SHD
DC 1
SUPPLY SPARE
SHD FUSE GND
TERMINALS 2 Bolt
COMMON
SHD
255.5 mm
FIELD CONNECTION
TERMINALS
JP (1 to 31)
or FUSE
JA
(1 to 32)
JB
(1 to 32)
JP (2 to 32)
or FUSE
FIG. 3
- 10 -
IM-ENG-216/GB
To RS485/RS232
16 channels converter
16 channels
16 channels
16 channels
General purpose
1-5 V HART signal inputs
(PHOENIX VARIOFACE style)
FIG. 4
- 11 -
IM-ENG-216/GB
4.4 I.S. Integrated solutions (Mux2700G with HiD2000 Intrinsic Safety interfaces)
FIG. 5A
on Board Mux2700G (up to 32 ch.)
24 Vdc CL 6825
24 Vdc PS1+
16 AI
PS2+
1-5 Volts
IN Ch. 1 DC
Supply
Bus
J10
F +11
+1 ~
~ 14
4 +12
IN +2 ~ F
Ch. 2
~ 15
5 F
+
to DC GND RS485
Supply A (duplicated)
HiD 2026 Bus B
FIG. 5B
- 12 -
IM-ENG-216/GB
5.1 General
A Maintenance Workstation (MW) is to be connected to the installed multiplexers to implement the required, HART-
related configuration and supervision activities. In fact, the Mux2700G basically acts as a gateway between the field
devices and the MW.
The Maintenance Workstation is typically made of a suitable software package loaded on a standard desktop PC
equipped within external RS-232/RS-485 converter. The recommended operating system is Windows NT, but
Windows98/95 is also generally supported. As for required PC features, please refer to the documentation of the
applicable MW software package.
At least one free serial communication line (RS-232) must be available on the Maintenance Workstation to connect
the 232/485 converter. Most MW software packages generally permit the usage of more than one serial line (with
additional 232/485 converters) to increase the total number of accessible field devices.
Up to 31 Mux2700G modules can be connected to a single RS-485 serial line, for a total of 992 accessible field devi-
ces. The Maintenance Workstation is usually able to support more serial lines, so it is possible to effectively mana-
ge a few thousands of field devices without problems.
The recommended RS-232/RS-485 converter is the MD44 model (Westermo). Other equivalent devices can be
found on the market (e.g. from Keithley) but it is better to check their compatibility with the specific Maintenance
Workstation software.
- 13 -
IM-ENG-216/GB
6. MUX2700G SPECIFICATIONS
N.B.: all values are typical unless otherwise specified.
6.1 General
Operating Temperature: 0 to 55 °C (32 to 131 °F)
Storage temperature: -20 to 70 °C (-4 to 158 °F)
Relative humidity (non condensing): 5 to 90 %
EMC: EN50081-2, EN50082-2
Isolation (Supply port to Signal port): 1400 Vac, rms
Isolation (Supply port to Serial port): 1400 Vac, rms
Isolation (Serial port to Signal port): 500 Vac, rms
CE marking carried
6.2 Mechanical
Dimensions: see drawing
Case: HiD style, Policarbonate
Mounting: plug-in on Termination Board (no tool required)
Protection class: IP30
Connectors: 2, plug-in, 40-poles miniature connectors
Hot-plug in: supported
Unit weight: about 140 grams
- 14 -
IM-ENG-216/GB
For additional, more detailed HART-related specifications, please refer to the HART FSK Physical Layer
Specification Rev.8.0 available from the HART Communication Foundation (HCF_SPEC-54), which the Mux2700G
module is generally compliant with.
Notes :
• To minimise input capacitors size and to get an higher output signal level, the Hart signal transmit section is based
on a current generation technique. For this reasons, the output signal level is proportional to the external load,
which should not exceed 500 Ω to avoid possible cross-talk or saturation problems.
• The specified transmit-signal amplitude is a DC value measured at the centre of a waveform semi-period.
• To maximise allowed cable length and to avoid noise problems, you should avoid to connect to the MUX HART
low impedence devices < 250 Ω.
Warning !
A suitable RS-232 to RS-485 converter is required to connect the port with a standard PC (see Fig. 6).
As for RS-485 line detailed specifications, please refer to the relevant standard.
- 15 -
IM-ENG-216/GB
RS-485
Connections
RS 485
SHD
1
SPARE
SHD FUSE
2
GND B A
WESTERMO switch settings
See the Westermo Mod. MD-44 DC
instruction manual for details switch bit
Selection of data rate 19200/9600 S2 1-2-3
Selection of bits
11 S2 4-5
(8 bits odd parity - 1 stop bit)
to DCS Transmission 2-wire S2 6-7
Termination No termination S3 1-2-3-4
HART
PROTOCOL
AND 4-20mA
to DCS
GND
B
A
RS-485
Connections
RS-485
Connections +
A
B
24 Vdc
GND
Supply Line
Cord
54321
9876 RS-232
CABLE PIN OPTIONAL DB9 to Modem
ASSIGNMENT DB25 ADAPTER Cable
Female DB9 Female DB9 DB9 DB25
connector connector Pin No. Pin No.
A Pin No. Pin No.
to PC B 2 TX 2 TX 2 TX 3 TX
HOST STATION GND 3 RX 3 RX 3 RX 2 RX
5 GND 5 GND 5 GND 7 GND
FIG. 6
- 16 -
IM-ENG-216/GB
ELCON INSTRUMENTS
I N T R I N S I C S A F E T Y a n d S P E C I A L I S T S
MUX
PWR
ON 2700G
FAUL HART TX
Ch.1
I A
P
B
GND
I
MUX Ch.32 +
2700G
ON OFF
SW1
SW2
SW3 ADDRESS
SW4
SW5
SW6
SW7 BAUD RATE
SW8 RESERVED
FIG. 7A FIG. 7B
- 17 -
IM-ENG-216/GB
• Address setting
The Mux2700G module operates as a slave device on a multi-point RS-485 serial line. A unique address is therefore
to be specified for each Mux connected to the same serial line. To set the required address, use the first five swit-
ches according to the following table. Please note that the address 0 is reserved and is never to be used.
RS-485 ADDRESS
SW1 SW2 SW3 SW4 SW5
0 OFF OFF OFF OFF OFF
1 ON OFF OFF OFF OFF
2 OFF ON OFF OFF OFF
3 ON ON OFF OFF OFF
4 OFF OFF ON OFF OFF
5 ON OFF ON OFF OFF
6 OFF ON ON OFF OFF
7 ON ON ON OFF OFF
8 OFF OFF OFF ON OFF
9 ON OFF OFF ON OFF
10 OFF ON OFF ON OFF
11 ON ON OFF ON OFF
12 OFF OFF ON ON OFF
13 ON OFF ON ON OFF
14 OFF ON ON ON OFF
15 ON ON ON ON OFF
16 OFF OFF OFF OFF ON
17 ON OFF OFF OFF ON
18 OFF ON OFF OFF ON
19 ON ON OFF OFF ON
20 OFF OFF ON OFF ON
21 ON OFF ON OFF ON
22 OFF ON ON OFF ON
23 ON ON ON OFF ON
24 OFF OFF OFF ON ON
25 ON OFF OFF ON ON
26 OFF ON OFF ON ON
27 ON ON OFF ON ON
28 OFF OFF ON ON ON
29 ON OFF ON ON ON
30 OFF ON ON ON ON
31 ON ON ON ON ON
• Baud-rate setting
RS 485 BAUD RATE
The next two switches permit to set the desired serial line baud-
SW6 SW7
rate. The same baud-rate must be set also on the RS-232/-RS-485
9600 OFF OFF
converter and on the PC RS-232 serial line. Please note that the
remaining SW6/7 configurations are reserved and never to be used. 19200 ON OFF
38400 OFF
OFF ON
• SW8 setting
The SW8 switch must be always set to OFF and its reserved for factory-test usage.
- 18 -
IM-ENG-216/GB
To remove an installed Mux2700G, simply lift the yellow tabs and gently unplug from the panel.
The Mux2700G Multiplexer is an hot plug-in capable module therefore, when required, you can mount it without
disconnecting the power from the relevant Termination Board. At plug-in time, no relevant disturbance is to be
expected on 4/20 mA field signals. Before powering up the unit for the first time, please remember to carefully
check supply voltage level and polarity.
When required, “tag labels” are available to be inserted on the transparent lid located at the top of the module. This
could be useful for general identification purposes.
- 19 -
IM-ENG-216/GB
Warning !
Please remember that – unless the GND signals at both ends are connected to earth – the RS-485 communication
line needs three wires (differential pair plus GND). It is not recommended to use the cable shield as GND connec-
tion (i.e. third wire).
Warning !
Improper supply connections could seriously damage the unit.
RS-485 note:
According to the RS-485 standard you can connected up to 32 devices to a single line of up to 1200 meters (when
your data rate is lower than 100K baud). To get a reliable connection we recommend not to exceed this limits. You
should also verify that the connection cable is compliant with the standard specified requirements (but at low data-
rates you don’t generally have any problem). Finally, don’t forget that for an RS-485 line a suitable termination resi-
stor is required at both ends, and you should switch it On both on the RS232/RS485 converter and on the farthest
Termination Board panel (i.e. on the last device on the RS-485 bus).
- 20 -
IM-ENG-216/GB
8.1 Maintenance
No periodic maintenance or calibration is required for this product, which is also not intended for direct repair from
the end-user. For these reasons, the Mux2700G enclosure was not designed to be easily opened (and a special tool
is in fact required at this purpose).
Warning !
Any attempt to open the unit or to directly repair it will make the warranty null and void.
• When the Mux2700G is powered, the three LEDs should light for about 3 seconds. If, after this time the red
LED remains fixed in the On status, the unit should be returned to Elcon for repair.
• Verify the power-up sequence – as described in section 3.4 – to get more information about the situation.
Note:
Elcon technical support is available to advise about special problems or unclear situations. Please always contact
Elcon before returning any suspected defective unit, either in warranty or not.
- 21 -
IM-ENG-216/GB
Constant improvement is the foundation of Total Quality. Elcon continuously ensures that the performance of pro-
ducts, services, management and the Quality System, meet customer requirements. Improvement can only be
obtained with the active participation and involvement of all personnel and therefore Elcon management recognises
that the human resources of the company play a vital role in the achievement of its objectives.
- 22 -
IM-ENG-216/GB
10. WARRANTY
• General
Elcon Instruments certifies that all the instruments of their manufacture are immune from defects or loss of es-
sential quality, and whenever they are apparatus, Elcon also guarantees proper operation. The duration of the war-
ranty period is indicated in the order confirmation and starts from the date of delivery or on site test (if required).
Unless otherwise specified the warranty is of 12 months, from delivery date.
The action due to the customer for vices, defects, or loss of quality is subject to the terms of articles 1495,1497
C.C. (Italian Civil Code). The denunciation of the, defect or quality loss must be made by the customer by registe-
red mail, telex, fax, or equivalent written form to be sent to the main office of Elcon Instruments.
Such warranty replaces and supersedes any other declared or implicit warranty
- 23 -
IM-ENG-216/GB
11. ACRONYMS
- 24 -
IM-ENG-216/GB
A A31
RS-485
B A30
INTERFACE
A32
POWER
SUPPLY
MUX
0.68µF + C32
24V UNIT OPTO CH1
ISOL.
A1 + A
2.2µF
B32
A3 0.68µF
HART
CPU
MODEM + C1
CH32
2.2µF B1
SCREEN
A4,A5,A6
FIG. 8
Mux2700G ISOLATION STRUCTURE
The galvanic isolation specifications for the Mux2700G are summarised in the following table:
- 25 -
IM-ENG-216/GB
• As better explained in section 12.4, the MUX can tolerate one or more short-failed input capacitors while still
working properly, the probability of loop interference is also very low for a wide range of internal MUX faults.
The MUX input isolation was designed to allow the highest flexibility in connecting the channels to sense the HART
signal. The max 30 Vdc input voltage (specified between all terminals, both belonging to the same channel or not)
makes it possible to connect any MUX terminal to whatever voltage level can be derived from a 24 Vdc supply,
+20% tolerance included.
The input-channels isolation specifications for the Mux2700G are summarised in the following table:
To avoid any possible damage to the sensitive input circuitry, an internal, zener-diode based clamping network
(Fig. 9) was inserted that operates both on common-mode and on differential-mode transients. This is required
because, for relevant input transient or AC signals, the input capacitors could momentarily couple to the input cir-
cuitry with a voltage level higher than the allowed voltage rating (i.e., +/- 5V).
Typically, the clamping network needs only to operate at the MUX unit during plug-in time, when the input capaci-
tors are initially charged. During the capacitors charge time (typically less than 1 ms) the input circuit does in fact
sink a some DC current from the loop, but the induced error on the 4-20 mA signal is so short in time that it is rarely
detected in any situation.
All diodes
are 5V Zeners +
CHx
+
A
+
CHy
FIG. 9
Mux2700G INPUT CLAMPING NETWORK
- 26 -
IM-ENG-216/GB
- 27 -
IM-ENG-216/GB
+ 24 Vdc
Tx
+
CHx R
+
A Tx
+
CHy R
GND
FIG. 10
COMMON-POINT FIELD LOOPS CONFIGURATION
As a final remark, we can observe that, whatever is the field-loops isolation or connection, a single capacitor fault
plus any other possible additional fault within the Mux2700G never results in any errors induced from the Mux2700G
on any 4-20mA loop.
12.5 Conclusions
By this note, it was possible to clarify how the Mux2700G isolation structure is such to guarantee both an high level
of application flexibility and a good reliability and fault tolerance (as for induced errors).
The presence of two series capacitors on each 4-20mA loop was discussed and the advantages of the solution
explained.
Some safety related issues were finally discussed, showing that, with a minimum of application-related analysis,
the Mux2700G can be designed so to minimise the probability of any electrical feedback on the connected 4-20mA
loops.
- 28 -