Pump Head Calculations For Building # 44: Phase # 1

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

Pump Head Calculations for Building # 44

Maximum Flow rate of Building # 44 on the basis of maximum IT Load

PHASE # 1
Name CRAC In Row RC units Qty 4 21 Unit Flow rate GPM (l/s) 95.5 (6) 16.1 (1.02) Total Flow rate GPM (l/s) 382(24) 338.1 (21.33)

Total Flow Rate = 720.1 Gallons per minute

PHASE # 2
Name In Row RC units Qty 4 Unit Flow rate GPM (l/s) 16.1 (1.02) Total Flow rate GPM (l/s) 64.4 (4.06)

Total Flow Rate = 64.4 Gallons per minute

Total Flow Rate = phase-1 + phase-2

Total Flow Rate = 784.5 Gallons per minute

Future Systems Ltd. - Confidential

Page 1

Pipe Sizing
Flow rate (GPM) 784.5 160 95.5 Pipe (Inch) 8 3 2

Utility Main Supply & Return Cooling Distribution Unit CRAC

Recommendation As per ASHRAE (Reference Attached) As per Manufacture (Reference Attached) As per Manufacture (Reference Attached)

Future Systems Ltd. - Confidential

Page 2

Pump Head Calculations


Total Pump Head Total Pump Head Total Pump Head = = = Supply + 42.54 m 77.22 meter Return + 34.68 m

(Calculations of CDU in Row RC units are also included)

CDU Pressure Drop Calculations


Total Pressure Drop = CDU pressure drop + pressure drop in bends + pressure drop in PEX piping

CDU Pressure Drop CDU pressure drop CDU pressure drop = = Total In Row RC units connected to CDU (reference attached) 16 GPM (39.8 k Pa)

Pressure Drop in Bends Pressure drop in bends Pressure drop in bends Pressure drop in bends As per catalogue Pressure drop in bends = = = = Number of bends in supply + Number of bends in returns 5 + 5 10 bends 3.05 m (29.89 k Pa)

Pressure drop in PEX piping Flow rate in PEX piping Total linear supply distance Total linear return distance Total linear distance Pressure drop in PEX piping Pressure drop in PEX piping = = = = = = 16 GPM (1.67 k Pa /m) 18.22 m 18.22 m 36.24 m 1.67 k Pa /m x 36.24 m 60.5 k Pa

Future Systems Ltd. - Confidential

Page 3

Total Pressure Drop of CDU Total Pressure Drop Total Pressure Drop Total Pressure Drop Total Pump Head = = = 39.8 k Pa + 30 k Pa + 60.5 k Pa 130.3 k Pa 13.3 meter

Total Pump Head =


Total Pump Head = *Include 13% factor of safety Total Pump Head = Total Pump Head

77.22 + 13.3

90.52 meter

102.3 meter = 10 bar

Recommended Pump flow rate 400 GPM @ 10 bar

Future Systems Ltd. - Confidential

Page 4