6. Mot or St art er
Starter DOL Star-Delta Auto T C VSD HP or KW <13 HP (11KW) 13 HP to 48 HP > 48 HP (37 KW) Starting Current 7 X Full Load Current 3 X Full Load Current 4 X Full Load Current 0.5 to 1.5 X Full Load Current Torque Good Poor Good/ Average Excellent
Motor > 2.2KW Should not connect direct to supply voltage if it is in Delta winding Go back to Rules