Kaeser Compressor Sigma Control Manual
Kaeser Compressor Sigma Control Manual
Kaeser Compressor Sigma Control Manual
SIGMA CONTROL
Index: BUB 07
GL---No.: BA---7.7000.0---00 V4
Publisher:
Table of Contents
Chapter --- Page
-----------------
1
1
1
2
2
2
2
3
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 --- 6
3.1
3.2
3.3
3.4
3.5
1
1
1
1
1
1
1
1
Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Hardware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Interface pin connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
RS 232 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
RS 485 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Profibus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Short Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Finding the best Type of Pressure Regulation . . . . . . . . . . . . . . . . . . . . . . . . . .
DUAL Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
QUADRO Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
VARIO Control Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3
3
3
3
3
-----------
6
7
8
9
10
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 --- 11
4.1
4.2
4.3
4.3.1
4.3.2
4.3.3
4.3.4
4.3.4.1
4.4
4.4.1
4.4.2
4.4.3
4.4.4
4.5
4.6
4.7
4.8
4.8.1
4.8.2
4.8.3
4.8.4
4.8.5
4.8.5.1
Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
The SIGMA CONTROL System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
EMERGENCY STOP Pushbutton . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Function keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Key functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Light emitting diodes and plain text display . . . . . . . . . . . . . . . . . . . . . . . . . . . .
LED functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Switching the Compressor Package On and Off . . . . . . . . . . . . . . . . . . . . . . . .
Switching on locally . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Switching off locally . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Switching on and off in remote . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Switching on and off with the clock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Resetting Alarm Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Acknowledgement of Warning Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Alarm and Warning Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Frequently Programmed Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Procedure for initial startup (Standard Mode) . . . . . . . . . . . . . . . . . . . . . . . . . . .
Procedure for initial startup (Expert Mode) . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Correcting the package pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Carrying out maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
The compressor package is to be operated with a base load sequencer . . .
MAC 41 as an example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
-----------------------------------------------
11
11
11
12
13
14
15
16
18
18
18
18
18
19
19
20
30
30
33
41
44
47
47
Table of Contents
Chapter --- Page
67
70
72
75
77
78
Main Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Password Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Display and Setup Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Display Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5
5
5
5
---------
83
85
86
86
Status Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Statistics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Print . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Printer clock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Analog data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Operating data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setting/resetting the maintenance interval counter . . . . . . . . . . . . . . . . . . . . . .
6
6
6
6
6
6
6
6
6
-------------------
90
91
92
93
94
96
98
100
102
ii
-------------
4
4
4
4
4
4
4 --- 52
4 --- 58
4 --- 67
Password . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Enter password . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Clock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General description of the clock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
The daily schedule . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
The weekly schedule . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
The yearly schedule . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Clock key: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Pressure settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Compressor configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
System pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Vacuum package . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
System pressure of the vacuum package . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Load control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Control mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DUAL Control settings (normal control) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
-------------------------------------
104
105
106
108
108
109
109
111
112
113
116
116
117
119
119
120
124
124
Table of Contents
Chapter --- Page
7.3.3.2
7.3.3.3
7.3.4
7.3.5
7.3.6
7.3.6.1
7.4
7.4.1
7.4.1.1
7.4.2
7.4.2.1
7.4.3
7.4.4
7.4.5
7.5
7.5.1
7.5.2
7.5.2.1
7.5.2.2
7.5.3
7.5.4
7.6
7.6.1
7.6.2
7.6.3
7.6.4
7.6.5
7.7
7.7.1
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
7
-----------------------------------------------------------
124
125
126
126
128
131
132
133
133
133
134
134
135
135
136
137
137
137
138
138
139
140
141
143
143
144
145
146
147
iii
Table of Contents
Chapter --- Page
iv
Technical Specification
1
Technical specification
1.1
Power Supply
Power supply for SIGMA CONTROL
Rated voltage . . . . . . . . . . . . . . . . . . . . . . . . 24 V DC (stabilized)
Consumption . . . . . . . . . . . . . . . . . . . . 1.3 A (standard controller)
Consumption . . . . . . . . . . . . . . . . . . 2.5 A (with expander board)
Auxiliary voltage for sensors (from the controller)
Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 V DC
All voltages are generated within the compressor package itself
Note
1.2
Sensors
Pressure transducer:
Output signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 --- 20 mA
Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . two wire
Resistance thermometer
Sensing resistance . . . . . . . . . . . . . . . . . . . PT100 to DIN IEC 751
Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . two wire
1.3
Hardware
-
electronic 24 V outputs (common negative rail, short circuit and overload proof)
3 serial interfaces:
-
RS 232 (modem)
Profibus DP
1 --- 1
Technical Specification
1.3.1
1.3.1.1
RS 232
-
Connections
Pin 1
spare
Pin 2
Pin 3
Pin 4
reserved
Pin 5
ground
Pin 6
spare
Pin 7
Pin 8
Pin 9
spare
RS 485
-
Connections
Pin 1
terminating resistor RA
Pin 2
reserved
Pin 3
difference signal B
Pin 4
reserved
Pin 5
reserved
Pin 6
reserved
Pin 7
terminating resistor RB
Pin 8
difference signal A
Pin 9
reserved
Profibus
-
Connections
Pin 1
spare
Pin 2
spare
Pin 3
Profibus connection B
Pin 4
Pin 5
ground
Pin 6
+ 5V for interface P5
Pin 7
spare
Pin 8
Profibus connection A
Pin 9
spare
1 --- 2
Technical Specification
1.4
Software
-
soft PLC
visualization software
user software
1 --- 3
Safety
2
Safety Regulations
2.1
Note
-
This symbol identifies operations and actions to be carried out by the operator or service technician.
This bullet identifies listings.
Beware of high voltage. Do not touch electrical components; danger of electric shock.
Beware! Machine starts automatically. Machine can start automatically or by
remote start command.
Beware of rotating parts. Do not touch rotating parts as this can cause
pinching/injury.
2 --- 4
Safety
2.2
General Instructions
Before work is carried out on electrical equipment carry out the following
measures in the order shown:
1. Switch off the main switch
2. Lock out the main switch
3. Check that no voltage is present on the equipment
Attention!
Attention!
2.3
Do not pull out or push in components (plugs) on the controller when the compressor package is running. This can cause damage to the controller.
Do not run the compressor package with supplies removed from the controller as irreversible
damage could occur (e.g. feed to the digital outputs with no power supply connected).
Do not apply other voltages to the electronic outputs on the output plug pins (i.e. external
feed via wire jumpers, etc.).
A short circuit at the power supply pins of the Profibus interface can cause irreversible damage to the interface.
2 --- 5
General
3
General
3.1
Short Description
The electronic controller Sigma Control comprises an industrial computer with an Intel processor, a user interface with a background illuminated plain text display, keys, some with integrated LEDs and digital and analog inputs and outputs. Power to the controller is provided by a
stabilised 24 V DC power supply unit.
The controller is provided with a clear, easily understood user interface that allows call---up of information or entry of settings:
-
the plain text display provides the user with information on current events in the selected language
an event information memory records the last 100 events with date and time, e.g. alarm, service and operational messages.
Sigma Control controls, regulates, protects and monitors the compressor package.
The control function provides:
-
automatic changeover from load to idle or standstill ensuring optimum utilisation of the drive
motor according to the users actual air demand.
automatic shutdown of the compressor package if overcurrent, overpressure, overtemperature, etc. occurs, that is, if a fault occurs that can cause damage to the compressor package.
punctual maintenance prompts for oil filter, air filter, V---belts, motor bearings, electrical components and other internal components. All these functions are monitored by service hour
counters and maintenance due is displayed as warning or service messages in the plain text
display.
All important data can be transferred via the Profibus using integrated interface software.
All parameters needed to operate KAESER rotary screw compressors and vacuum packages are
contained in Sigma Control. They are set up at the factory according to compressor model.
These parameters can be displayed or changed with the help of various menus or sub ---menus in
the software (see also chapter 5).
Parameter settings and changes are entered in the Display and Setup level of the software after
input of a password. The type of drive, pressure control mode (DUAL, QUADRO or VARIO), the
model and basic model status, for example, can be entered at this level.
3 --- 6
General
3.2
Run the compressor package for a longer period of time (at least four weeks, or more).
QUADRO control
VARIO control
Note
The type of pressure regulation with maximum duty cycle is the most efficient.
3 --- 7
General
DUAL Control
Pressure
3.3
p
max
p
min
Motor power
Full load
2 3
t1
5
t2
Idle
Standstill
Time
In DUAL control mode (combined idle and start ---stop) the compressor normally runs in load and
idle or standstill.
The controller regulates the compressor package between load and idle.
If the compressor package runs in idle for longer than the preset period (1) to (2), for example t1
= 6 minutes in idle, the drive motor is stopped completely (2). When the lower switching point
p min (3) is reached, the compressor package is automatically started again. Pressure rises to the
upper switching point p max (4), and the compressor package switches to idle. If the pressure falls
again to p min (5) within a shorter period (4) to (5), for example, t2 = 3 min, then the compressor
switches automatically from idle to load.
3 --- 8
General
Pressure
QUADRO Control
Motor power
3.4
p
max
pmin
Load
Idle
Standstill
1
1
time
tp rise
tp decay
Running
period
Unloaded
period
Venting
period
stop point for running or idle / standstill period
pmax
pmin
tp rise
pressure rise time (the time during which system pressure rises
from the lower to the upper switching point)
tp decay pressure decay time (the time during which system pressure decays
from the upper to the lower switching point)
Function description
Two fixed periods --- the running period and unloaded period --- are taken as the criterion for
selection of the operating mode of the compressor package when system pressure reaches the
upper switching point. These two periods are set according to the maximum permissible starting
frequency of the drive motor.
The running period starts every time the compressor package is switched on. It lasts as long as
the drive motor runs and stops when the compressor package switches to standstill.
The unloaded period starts every time the operating mode changes from load to idle. It runs during idle and also when the compressor package is switched to standstill after the idle period. It
stops when the compressor package switches to load.
Every cut ---out point is delayed by the venting period, so that the compressor package vents.
3 --- 9
General
The following switching cycles are possible:
-
If system pressure decays to the lower switching point, the compressor package switches to
load (1) irrespective of its previous operating mode. If the drive motor was at standstill, the
opening of the inlet valve is delayed to allow an unloaded compressor package start.
If system pressure rises to the upper switching point and the running period has already expired, the compressor package switches off after the run ---on period has expired (2).
If system pressure rises to the upper switching point before the running period has expired,
the pressure decay time of the previous switching cycle is taken as the criterion for the selection of the operating mode:
-- If the pressure decay time tp decay was longer than the idle/standstill period, the compressor
package switches to standstill after the run ---on period has expired (3).
-- If the pressure decay time tp decay was shorter than the period set for the idle / standstill
period, then idle mode is selected (4), that is, the inlet valve closes and the compressor
package is vented with the motor running. When the running period expires the compressor
package is also switched to standstill after the run ---on period has expired (5).
3.5
3 --- 10
Operation
4
Operation
4.1
Control Panel
2
1 SIGMA controller
2 Emergency Stop pushbutton
4.2
4.3
Turn the EMERGENCY STOP button in the direction of the arrow to unlatch it.
Press the acknowledge (reset) key on SIGMA Control to acknowledge the alarm. (See
chapter 4.3.1 for function keys).
4 --- 11
Operation
4.3.1
Function keys
7
11
10
9
6
1
4
1
2
3
4
5
6
4 --- 12
ON key (I)
OFF key (0)
Clock key
Remote key
Load/unload changeover key
Arrow key () (menu down)
3
7
8
9
10
11
Operation
4.3.2
Symbol
Key functions
Item
Description
Function
ON key
Remote ON key
Pressing the key switches between local and remote control of the compressor package.
The LED illuminates in remote mode.
Arrow key
Arrow key
Escape key
Only affects the message in the third line of the display (12):
--- returns to the selected submenu or
--- exits edit mode and saves edited parameters
10
11
Acknowledge (reset)
key
4 --- 13
Operation
4.3.3
13
14
12
15
19
16
17
18
20
12 Four ---line display
13 Alarm LED
14 Communication alarm LED
15 Warning --- maintenance LED
16 Power ON LED (to controller)
4 --- 14
21
17
18
19
20
21
Load LED
Idle LED
Compressor ON LED
Remote ON LED
Timer ON LED
Operation
4.3.4
LED functions
Symbol
EDU &
21. /2$' S
WRWDO
ORDG
Item. Description
Function
12
13
Alarm LED
14
Communication
alarm LED
The red LED illuminates if communication via the Profibus interface is interrupted.
If the communication fault occurs in remote mode, the
compressor package is automatically switched to local
control.
When the reset key (11) is pressed, the LED extinguishes if the alarm is no longer present.
15
Service/warning LED
16
Power ON LED
17
Idle LED
18
Load LED
19
Package on LED
20
Remote control
mode
The green LED illuminates when the package is in remote control mode.
21
The green LED illuminates when the package is switched either on or off by the clock.
4 --- 15
Operation
4.3.4.1
Display
The display (12) used for entry and readout of data and is provided with four lines of 16 characters each.
Example:
EDU
& 5
RII
E
EDU
& 5
NH\2)) S RII
WRWDO K
ORDG
K E
1
2
1
2
3
4
1
2
3
4
Header
Compressor status/menu text
3
4
Active line
Menu text
Line 1 -- header
Current system pressure and airend discharge temperature are displayed in the header.
These values are always shown
-
in setup levels in which parameter changes can be made even though the compressor is
running.
The letters R, S and F identify internal operational modes of the controller and are shown for
servicing purposes.
R means that the controller is in RUN mode and is working perfectly.
S means that the controller has been set to Stop by a programming unit (PG).
F means that there is a program fault.
Note
If an S or an F appears in the display, switch the power off and then back
on again to return to the R status. If this is unsuccessful, contact KAESER
service department for further instructions.
Line 2
Depending on settings, either the current status of the compressor package or menu text is
shown in line 2.
Line 3 -- active line
Note
4 --- 16
Operation
The respective menu text is shown here.
Example:
EDU
& 5
RLO ILOWHU
K
E
5
5
4
If it is possible to move to a submenu or if a parameter can be entered the Return () sign (5)
appears in column 16.
Line 4
The arrows C, 8 or E (4) appear in line 4, column 16 after the menu text and indicate the
direction in which the lines can be scrolled:
-
4 --- 17
Operation
4.4
4.4.1
Do not switch the compressor package on and off with the main switch.
Always switch on with the ON key (1) and off with the OFF key (2). Always
take the permissible motor starting frequency into account when switching
the compressor package on and off.
Switching on locally
The controller runs a selftest. When the selftest is completed the green power ON LED (16) illuminates permanently.
Press the ON key (1) --- the green compressor ON LED (19) illuminates.
LEDs 17 and 18 must be taken into consideration to determine the operational status of the compressor package:
If LED (19) is on -- and both LEDs (17) and (18) are off, the package is
stopped and in standby.
The compressor can start at any moment.
4.4.2
4.4.3
Press the OFF key (2) --- the Package ON LED (19) extinguishes.
Switch off and lock out the main switch.
4.4.4
4 --- 18
Operation
4.5
Reset the alarm with the reset key (11) --- LED (13) extinguishes.
4.6
If the compressor was shut down with the EMERGENCY STOP pushbutton,
ensure that the pushbutton is enabled by turning in the direction of the arrow
before resetting the alarm.
Acknowledge service message with the reset key (11) --- LED (15) extinguishes.
Note
4 --- 19
Operation
4.7
Message2
Type1 Fault
Remedy
access doors
access doors
ADT C
ADT
ADT dT/dt
AI 1 open cct
AI 2 open cct
AI 3 open cct
The connection between analog input 3 and the resistance thermometer for measuring airend discharge
temperature is open circuit
AI 4 open cct
The connection between analog input 4 and the resistance thermometer for measuring drive motor temperature is open circuit
AI 5 open cct
AI 6 open cct
1
2
3
A alarm
W warning
Symbols:
high:C / too high: / low:8 / too low:
Contact authorised KAESER service agent
4 --- 20
Operation
Message2
Type1
Fault
Remedy
AI 7 open cct
AI 8 open cct
airend rotation
air filter dp C
air filter h
back pressure
There is still back pressure in the oil Check the venting line and the venseparator tank because of poor ven- ting valve,
ting (V---belt drive compressors
check the MPCV
only)
back pressure?
There is still back pressure in the oil Check the venting line and the venseparator tank because of poor ven- ting valve,
ting (direct drive compressors only) check the MPCV
bearings h
blowoff prot.
Warning:
The response pressure of the pressure relief valve will soon be exceeded
blowoff prot.
The response pressure of the pressure relief valve on the oil separator
tank is exceeded
buffer battery
condensatedrain
1
2
3
A alarm
W warning
Symbols:
high:C / too high: / low:8 / too low:
Contact authorised KAESER service agent
4 --- 21
Operation
Message2
Type1
Fault
Remedy
condensatedrain
coolingwater low
elect. equip. h C
The default service hours for checking electrical equipment and wiring
have expired
emergency stop
ext.load signal?
ext. message 0
ext. message 0
ext. message 1
ext. message 1
ext. message 2
ext. message 2
ext. message 3
ext. message 3
ext. message 4
ext. message 4
ext. message 5
ext. message 5
1
2
3
A alarm
W warning
Symbols:
high:C / too high: / low:8 / too low:
Contact authorised KAESER service agent
4 --- 22
Remove fault
Remove fault
Remove fault
Remove fault
Remove fault
Remove fault
Remove fault
Remove fault
Remove fault
Remove fault
Remove fault
Remove fault
Operation
Message2
Type1
Fault
Remedy
ext. message 6
Remove fault
ext. message 6
ext. message 7
ext. message 7
fan M2 I
fan M3 I
fan M4 I
flash memory
HT cell
L2DP-controller
A
A
L2DP-timeout
The mains contactor does not pull in The answerback on input 0.6 (24V)
despite an ON command
does nor appear after compressor
start,
check auxiliary contact block on
K1M,
Check 230 V supply to the contactor
(door interlock switch, EMERGENCY
STOP)
The answerback from mains contactor K1M (0.6) is still present, even
though the compressor is at standstill
mains monitor
1
2
3
Remove fault
Remove fault
Remove fault
Investigate cause, then reset the
motor overload trip
A alarm
W warning
Symbols:
high:C / too high: / low:8 / too low:
Contact authorised KAESER service agent
4 --- 23
Operation
Message2
Type1
Fault
mains voltage
mains voltage
model
Model indistinct
modem problem
motor bearings
motor bearings h
The default service interval for repla- Have maintenance carried out3,
cement of the motor shaft bearings Have the motor bearings replaced3
has expired
motor I
Investigate cause,
then reset overload trip
motor T C
motor T
motorstarts /h
1
2
3
A alarm
W warning
Symbols:
high:C / too high: / low:8 / too low:
Contact authorised KAESER service agent
4 --- 24
Remedy
Operation
Message2
Type1
Fault
Remedy
motorstarts /d
no press. buildup
no press. buildup
O 0.6/O 0.7
Check consumer load, line and connections (e.g. solenoid valve), replace defective consumer load
O 1.6/O 1.7
Check consumer load, line and connections (e.g. solenoid valve), replace defective consumer load
oil change h
The default service interval for the oil Carry out an oil change,
change has expired
(see chapter 6.4.1 to reset the service interval counter)
oil content C
Warning:
The oil content for pure air will soon
be reached
oil content C
oil filter dp C
oil filter h
1
2
3
A alarm
W warning
Symbols:
high:C / too high: / low:8 / too low:
Contact authorised KAESER service agent
4 --- 25
Operation
Message2
Type1
Fault
Remedy
oil p
oil T
PD temperature 8
Warning:
package discharge temperature too
low
PD temperature
PD temperature 8
Warning:
package discharge temperature too
high
PD temperature
RAM
RD compr. p
1
2
3
A alarm
W warning
Symbols:
high:C / too high: / low:8 / too low:
Contact authorised KAESER service agent
4 --- 26
Operation
Message2
Type1
Fault
RS485err:chksum
RS485err:dial up
RS485err:initdrv
RS485err:protoc.
1
2
3
Remedy
A alarm
W warning
Symbols:
high:C / too high: / low:8 / too low:
Contact authorised KAESER service agent
4 --- 27
Operation
Message2
Type1
Fault
RS485err:transm.
separator dp C
separator h
separator T
Have the trip device at the oil separator air discharge checked 3,
check the sensor and line to the trip
device, replace defective trip device
set output!
Remedy
sh.cct AI1
The set output test function is acti- End the set output mode.
vated
Short circuit at analog input 1
Check line and connections, check
the transducer that is measuring
system pressure
sh.cct AI2
sh.cct AI3
sh.cct AI4
The connection between analog input 3 and the resistance thermometer for measuring airend discharge
temperature is either short circuit or
shorted to earth
The line between analog input 4 and
a sensor is short circuit or is shorted
to earth
sh.cct AI5
sh.cct AI6
sh.cct AI7
The line between analog input 7 and check sensor, line and connection,
a sensor is short circuit or is shorted have the defective sensor changed3
to earth
sh.cct AI8
The connection between analog input 8 and the resistance thermometer for measuring drive motor temperature is either short circuit or
shorted to earth
1
2
3
A alarm
W warning
Symbols:
high:C / too high: / low:8 / too low:
Contact authorised KAESER service agent
4 --- 28
Operation
Message2
Type1
Fault
Remedy
Sigma Control T
softstart
start T
The airend discharge air temperature (ADT) is too low too allow the
package to be started (resistance
thermometer temperature measurement)
system press.
The system pressure has fallen below the syspress. low value because of leaks, pipe fracture, etc.
system press.
(vacuum packages
only)
The system pressure has fallen below the syspress. high value because of leaks, pipe fracture, etc.
V---belts broken
V---belt tens. h
V---belt tension
VFD
VFD mains
1
2
3
A alarm
W warning
Symbols:
high:C / too high: / low:8 / too low:
Contact authorised KAESER service agent
4 --- 29
Operation
4.8
Base load changeover between two compressor packages with Sigma Control
4.8.1
Initial Startup
Start
Main menu:
language selection
Main menu:
password
Menu:
configuration
general
Select
language
Activate
password level 4
see chapter 7.1.1
4 --- 30
Operation
-
Press and hold the arrow up key (D) until the language setting appears in the third line of the
display.
EDU
2
& 5
(QJOLVK
Enter password
Press the arrow up key () until password appears in the third line of the display.
EDU
& 5
SDVVZRUG
;;;;; /
;;;;; / C
By pressing the return key () a flashing cursor appears below the first X of the password
(XXXXX).
Change the first character with the arrow keys (). Keep pressing the arrow keys until the
first X is replaced by the character required.
Press the return key (), the cursor now jumps to the next character in the password.
EDU
& 5
SDVVZRUG
;;; /
;;;;; / C
Press the return key (), the cursor now jumps to the next character in the password.
4 --- 31
Operation
Using this method, enter the remaining characters of the password for level 4 (12EXP). When the
last character of the password is entered with the return key (), the activated password level is
displayed.
EDU
& 5
SDVVZRUG
;;;;; /
;;;;; / C
Checking settings
Press and hold the arrow keys (D9) until general appears in the third line of the display.
EDU
& 5
PRGHO
'6
31
E
Press the arrow down key (9), and the following details will be displayed sequentially:
-
Model:
Version details:
Press the arrow down key (9), the following parameters will be displayed sequentially and
can be set by pressing the return key () (see chapter 7.3.1):
-
date
time
summer/winter time
date format
time format
unit of pressure
4 --- 32
weekday
unit of temperature
Operation
4.8.2
Note
Use this chapter only after reading the complete service manual in
detail
When the power supply to the controller is switched on the computer starts to boot. Both the display and the green Power ON LED illuminate.
The current system pressure and the airend discharge temperature are then displayed in the first
line. The compressor package can now be started with the ON key.
If personnel are to be given instruction, parameters changed or the settings checked, then the
following procedure is recommended:
4 --- 33
Operation
Start
Main menu
Menu:
configuration
password
Menu:
configuration
general
Select
language
Activate
password level 4
see chapter
7.1.1
Menu:
configuration
pressure setpoint
compressor
Match
system pressure
p1
system pressure
ssetpoint pressure
Menu:
configuration
Set
control mode
control mode
4 --- 34
Operation
Comp. on/off
no
via clock
yes
Menu:
Program clock
clock
Activate clock
key
comp. on/off
Press
clock key
Menu:
configuration
I/O periphery
contacts
End
4 --- 35
Operation
-
Press and hold the arrow up key (D) until the language setting appears in the third line of the
display.
EDU
2
& 5
(QJOLVK
Enter password
Press the arrow up key () until password appears in the third line of the display.
EDU
& 5
SDVVZRUG
;;;;; /
;;;;; / C
By pressing the return key () a flashing cursor appears below the first X of the password
(XXXXX).
Change the first character with the arrow keys (). Keep pressing the arrow keys until the
first X is replaced by the character required.
Press the return key (), the cursor now jumps to the next character in the password.
EDU
& 5
SDVVZRUG
;;; /
;;;;; / C
4 --- 36
Press the return key (), the cursor now jumps to the next character in the password.
Operation
Using this method, enter the remaining characters of the password for level 4 (12EXP). When the
last character of the password is entered with the return key (), the activated password level is
displayed.
EDU
& 5
SDVVZRUG
;;;;; /
;;;;; / C
Checking settings
Press and hold the arrow keys (D9) until general appears in the third line of the display.
EDU
& 5
PRGHO
'6
31
E
Press the arrow down key (9), and the following details will be displayed sequentially:
-
Model:
Version details:
Press the arrow down key (9), the following parameters will be displayed sequentially and
can be set by pressing the return key () (see chapter 7.3.1):
-
weekday
date
time
summer/winter time
date format
time format
unit of pressure
unit of temperature
4 --- 37
Operation
-
In the main menu, press and hold the arrow up key (D) until configuration appears in the
third line of the display.
EDU
& 5
JHQHUDO
SUHVVXUH VHWWLQJV
FRQWURO PRGH
E
Press the return key () when the pressure settings appear in the third line of the display;
compressor now appears in the third line.
Press the return key () to display system pressure in the third line of the display.
Press the return key () again and the following display appears.
EDU
& 5
VHWSRLQW SUHVVXUH
S 63 EDU
6' EDU
Press the return key () and a flashing cursor appears below value p1.
Increase the setpoint pressure p1 with the arrow up key () and decrease it with the arrow
down key().
Enter the changed setpoint pressure with the return key ().
Press the arrow down key once (), so that the switching differential ---SD appears in the
third line of the display.
Press the return key and a flashing cursor appears below the switching differential ---SD.
Increase the switching differential ---SD with the arrow up key () and decrease it with the
arrow down key ().
4 --- 38
Operation
-
Control mode
Keep pressing the arrow keys (D9) in the control mode menu option until local mode appears in the second line of the display and then press the return key ().
EDU
& 5
ORFDO PRGH
4XDGUR
FRQWURO PRGH
E
Sigma Control is provided with various pressure control modes (see also chapter 7.3.3).
Press and hold the arrow keys (D9) in local mode until the required control mode appears in
the third line of the display.
In the main menu, press and hold the arrow up key (D) until clock appears in the third line
of the display.
EDU
& 5
FRPS212))
Press the return key () again and the following display appears.
EDU
FORFN NH\
212)) GD\
& 5
M
Press the arrow down key once (), so that ON/OFF day appears in the third line of the display.
4 --- 39
Operation
Press the return key () to set the first switching point. Four switching points are available.
EDU
& 5
g 212)) GD\
21
2))
8
Press the return key () and a flashing cursor appears below corresponding time.
The time can be increased or decreased with the arrow keys ().
A daily schedule with four switching points is available. In this schedule the compressor package
can be started with the ON time and stopped with the OFF time. The daily schedule can be interrupted by the weekly schedule, a fact that could be useful at weekends, for example. The weekly
schedule can also be interrupted by the yearly schedule (see also chapter 7.2.1).
When all switching points have been set, the menu is exited with the escape esc key.
Press the arrow up key () once, so that clock key: n appears in the third line of the display.
Press the return key (), a flashing cursor appears below the n.
4 --- 40
Operation
4.8.3
Note:
Start
Main menu:
password
Activate
password level 4
see chapter 7.1.1
Menu:
configuration
pressure settings
compressor
system pressure
setpoint pressure p1
Is
pressure p2
no
required?
yes
Menu:
configuration
pressure settings
Change
setpoint pressure p2
compressor
system pressure
setpoint pressure p2
End
4 --- 41
Operation
-
Enter password
Press the arrow up key () until password appears in the third line of the display.
EDU
& 5
SDVVZRUG
;;;;; /
;;;;; / C
By pressing the return key () a flashing cursor appears below the first X of the password
(XXXXX).
Change the first character with the arrow keys (). Keep pressing the arrow keys until the
first X is replaced by the character required.
Press the return key (), the cursor now jumps to the next character in the password.
EDU
& 5
SDVVZRUG
;;; /
;;;;; / C
Press the return key (), the cursor now jumps to the next character in the password.
Using this method, enter the remaining characters of the password for level 4 (12EXP). When the
last character of the password is entered with the return key (), the activated password level is
displayed.
EDU
& 5
SDVVZRUG
;;;;; /
;;;;; / C
4 --- 42
Operation
-
In the main menu, press and hold the arrow up key (D) until configuration appears in the
third line of the display.
EDU
& 5
JHQHUDO
SUHVVXUH VHWWLQJV
FRQWURO PRGH
E
Press the return key () when the pressure settings appear in the third line of the display;
compressor now appears in the third line.
Press the return key () to display system pressure in the third line of the display.
Press the return key () again and the following display appears.
EDU
& 5
VHWSRLQW SUHVVXUH
S 63 EDU
6' EDU
Press the return key () and a flashing cursor appears below value p1.
Increase the setpoint pressure p1 with the arrow up key () and decrease it with the arrow
down key().
Enter the changed setpoint pressure with the return key ().
Press the arrow down key once (), so that the switching differential ---SD appears in the
third line of the display.
Press the return key and a flashing cursor appears below the switching differential ---SD.
Increase the switching differential ---SD with the arrow up key () and decrease it with the
arrow down key ().
4 --- 43
Operation
-
When the switching differential ---SD for setpoint pressure p1 has been set, press the arrow
down key () once. The following display appears:
EDU
& 5
6' EDU
S 63 EDU
6' EDU E
Press the return key () and a flashing cursor appears below value p2.
Increase the setpoint pressure p2 with the arrow up key () and decrease it with the arrow
down key ().
Enter the changed setpoint pressure with the return key ().
Press the arrow down key once (), so that the switching difference ---SD appears in the
third line of the display.
Press the return key () and a flashing cursor appears below the switching differential ---SD.
Increase the switching differential ---SD with the arrow up key () and decrease it with the
arrow down key ().
Note
When the maintenance is complete the remaining interval (3) must be reset
to the default service interval (4).
Password level 4 access is required to carry out changes to the service interval counters.
Enter password
Press the arrow up key () until password appears in the third line of the display.
EDU
& 5
SDVVZRUG
;;;;; /
;;;;; / C
4 --- 44
By pressing the return key () a flashing cursor appears below the first X of the password
(XXXXX).
Change the first character with the arrow keys (). Keep pressing the arrow keys until the
first X is replaced by the character required.
Operation
Press the return key (), the cursor now jumps to the next character in the password.
EDU
& 5
SDVVZRUG
;;; /
;;;;; / C
Press the return key (), the cursor now jumps to the next character in the password.
Using this method, enter the remaining characters of the password for level 4 (12EXP). When the
last character of the password is entered with the return key (), the activated password level is
displayed.
EDU
& 5
SDVVZRUG
;;;;; /
;;;;; / C
The remaining hours in the corresponding service hours counter can be individually reset after
completion of maintenance.
The following service intervals are provided:
Oil filter, oil separator, oil change, air filter, V---belts change, V---belts tensioning, bearings change,
bearings maintenance, electrical equipment.
This means, for example, that when the V---belts have been tensioned, the corresponding service
interval must be reset. The reset for V---belt tensioning is located two lines below the phrase V--belt tension.
Press the arrow down key () 10 times, until maintenance appears in the third line of the
display.
EDU
& 5
RSHUDWLQJ GDWD
PDLQWHQDQFH
EDU
& 5
RLO ILOWHU
K g
K
UHVHW Q E
The service counter is a down counter. The remaining hours to the next service (2) are shown,
together with the service interval (1).
4 --- 45
Operation
By pressing the arrow down key () the other service intervals are displayed.
EDU
& 5
9EHOW WHQVLRQ
K g
K
UHVHW Q E
Press the arrow down key () once, reset appears in the third line of the display.
EDU
& 5
K g
K
UHVHW Q
Change the reset display from n to y with the arrow up key ().
4 --- 46
Press the return key (), a flashing cursor appears below the n.
Confirm with the enter key (). The counter resets to the default service interval. At the same
time the reset display changes from y to n.
Operation
4.8.5
4.8.5.1
MAC 41 as an example
3/6/9/12
MAC 41
2/5/8/11
I 0.7external load/idle
4 --- 47
Operation
Start
Make
electrical
connections
Main menu:
password
Activate
password level 4
see chapter
7.1.1
Menu:
configuration
pressure settings
load control
Activate
load control
from remote key
remote mode
> load RC
remote key: y
Press
remote key on
operating panel
End
4 --- 48
Operation
-
Enter password
Press the arrow up key () until password appears in the third line of the display.
EDU
& 5
SDVVZRUG
;;;;; /
;;;;; / C
By pressing the return key () a flashing cursor appears below the first X of the password
(XXXXX).
Change the first character with the arrow keys (). Keep pressing the arrow keys until the
first X is replaced by the character required.
Press the return key (), the cursor now jumps to the next character in the password.
EDU
& 5
SDVVZRUG
;;; /
;;;;; / C
Press the return key (), the cursor now jumps to the next character in the password.
Using this method, enter the remaining characters of the password for level 4 (12EXP). When the
last character of the password is entered with the return key (), the activated password level is
displayed.
EDU
& 5
SDVVZRUG
;;;;; /
;;;;; / C
4 --- 49
Operation
-
In the main menu, press and hold the arrow up key (D) until configuration appears in the
third line of the display.
EDU
& 5
JHQHUDO
SUHVVXUH VHWWLQJV
FRQWURO PRGH
E
Press the arrow down key () four times, until load control appears in the third line of the
display.
EDU
VHOHFWLRQ
& 5
ORDG FRQWURO
E
Press the arrow down key () seven times and the following appears in the display.
EDU
& 5
UHPRWH PRGH
S
UHPRWH NH\
Q E
Press the arrow keys () until load RC appears in the third line of the display.
4 --- 50
Press the return key (), a flashing cursor appears in the third line of the display.
Operation
-
Press the arrow down key () once until remote key: n appears in the third line of the display.
Press the return key (), a flashing cursor appears below the n.
Confirm activation of the remote key with the return ) key. The following display appears:
EDU
& 5
ORDG 5&
UHPRWH NH\ M
E
(see also chapter 7.3.2.3).
The pressure increase dpI becomes important if the rated package pressure is exceeded because of a period of external load that is too long. It then acts as the upper shutdown value.
4 --- 51
Operation
4.8.5.2
MVS
X4
A
B
A
B
I0.7
I1.3
X4
X4
4 --- 52
It is imperative that output O0.3 control ON is used for the alarm compressor X message to the MVS.
Operation
Start
Make
electrical connections
Main menu:
password
Activate
password level 4
see chapter 7.1.1
Menu:
configuration
pressure settings
compressor
system pressure
setpoint pressure
p2
Note:
Menu:
configuration
pressure settings
load control
Settings
> local mode
> p2
Menu:
configuration
load control
remote mode
loc.---loadRC
remote key: y
Press
remote key
on
operating
panel
End
4 --- 53
Operation
-
Enter password
Press the arrow up key () until password appears in the third line of the display.
EDU
& 5
SDVVZRUG
;;;;; /
;;;;; / C
By pressing the return key () a flashing cursor appears below the first X of the password
(XXXXX).
Change the first character with the arrow keys (). Keep pressing the arrow keys until the
first X is replaced by the character required.
Press the return key (), the cursor now jumps to the next character in the password.
EDU
& 5
SDVVZRUG
;;; /
;;;;; / C
Press the return key (), the cursor now jumps to the next character in the password.
Using this method, enter the remaining characters of the password for level 4 (12EXP). When the
last character of the password is entered with the return key (), the activated password level is
displayed.
EDU
& 5
SDVVZRUG
;;;;; /
;;;;; / C
4 --- 54
In the main menu, press and hold the arrow up key (D) until configuration appears in the
third line of the display.
Press the return key ().
Operation
The following display appears:
EDU
& 5
JHQHUDO
SUHVVXUH VHWWLQJV
FRQWURO PRGH
E
Press the return key () when pressure settings appears in the third line of the display;
compressor now appears in the third line.
Press the return key () to display setpoint pressure in the third line of the display.
Press the return key () again and the following display appears.
EDU
& 5
VHWSRLQW SUHVV
S 63 EDU
6' EDU E
Press the arrow down key () twice, the following display appears.
EDU
& 5
6' EDU
S 63 EDU
6' EDU E
Press the return key () and a flashing cursor appears below value p2.
Increase the setpoint pressure p2 with the arrow up key () and decrease it with the arrow
down key ().
Enter the new setpoint pressure with the return key ().
Press the arrow down key once (), so that the switching differential ---SD appears in the
third line of the display.
Press the return key () and a flashing cursor appears below the switching differential ---SD.
Increase the switching differential ---SD with the arrow up key () and decrease it with the
arrow down key ().
4 --- 55
Operation
In the main menu, press and hold the arrow up key (D) until configuration appears in the
third line of the display.
EDU
& 5
JHQHUDO
SUHVVXUH VHWWLQJV
FRQWURO PRGH
E
Press the return key () when pressure settings appears in the third line of the display.
Press the arrow down key () four times, until load control appears in the third line of the
display.
EDU
VHOHFWLRQ
& 5
ORDG FRQWURO
E
Press the arrow down key () three times and the following appears in the display.
EDU
& 5
ORFDO PRGH
S
Press the arrow keys () until p2 appears in the third line of the display.
4 --- 56
Press the return key () when local mode appears in the second line of the display. A flashing cursor appears in the third line.
Enter the new value with the return key ().
Operation
-
Having set p2 for the internal pressure control, press the arrow down key () four times and
the following appears in the display.
EDU
& 5
UHPRWH PRGH
S
UHPRWH NH\
Q E
Press the return key (), a flashing cursor appears in the third line of the display.
Press the arrow keys () until loc. ---loadRC appears in the third line of the display.
Press the arrow down key () once until remote key: n appears in the third line of the display.
Press the return key (), a flashing cursor appears below the n.
Confirm activation of the remote key with the return ) key. The following display appears:
EDU
& 5
ORFORDG5&
UHPRWH NH\ M
(see also chapter 7.3.2.3).
The following status is displayed in automatic mode:
4 --- 57
Operation
4.8.5.3
VESIS as an example
Wiring of the process field bus with the help of the above circuit diagram
Vesis
Pin
comp.4
Pin
comp.5
Pin
comp.1
Pin
comp.2
Pin
comp.3
Pin
8
9
8
9
8
9
8
9
8
9
8
9
The terminating resistor must be connected in the plugs of the first and last subscribers of a
Profibus link.
4 --- 58
Operation
Start
Make
electrical
connections
Menu:
configuration
password
Activate
password level 4
see chapter 7.1.1
Menu:
configuration
pressure settings
compressor
system pressure
Set
parameter for p2
for manual mode
setpoint pressure
p2
Menu:
configuration
pressure settings
load control
Note:
The setpoint for p2 must result in a reasonable switching combination if all compressor packages are to be controlled in
manual mode, i.e. by their own default
pressure settings.
Set p2
for internal
control
local mode
> p2
L2DP bus
communication:
> send + receive
> slave number
> Software
monitoring: y
Activate
remote control
from bus
4 --- 59
Operation
Menu:
communication
data
EEPROM: y
Save
settings
Attention!
An error message appearing after activation
is normal. This can be finally reset in active
bus mode after all items have been processed.
Switch off
control voltage
Attention!
Switch off
control voltage
Press
remote
key
End
4 --- 60
Operation
-
Enter password
Press the arrow up key () until password appears in the third line of the display.
EDU
& 5
SDVVZRUG
;;;;; /
;;;;; / C
By pressing the return key () a flashing cursor appears below the first X of the password
(XXXXX).
Change the first character with the arrow keys (). Keep pressing the arrow keys until the
first X is replaced by the character required.
Press the return key (), the cursor now jumps to the next character in the password.
EDU
& 5
SDVVZRUG
;;; /
;;;;; / C
Press the return key (), the cursor now jumps to the next character in the password.
Using this method, enter the remaining characters of the password for level 4 (12EXP). When the
last character of the password is entered with the return key (), the activated password level is
displayed.
EDU
& 5
SDVVZRUG
;;;;; /
;;;;; / C
4 --- 61
Operation
-
In the main menu, press and hold the arrow up key (D) until configuration appears in the
third line of the display.
EDU
& 5
JHQHUDO
SUHVVXUH VHWWLQJV
FRQWURO PRGH
E
Press the return key () when pressure settings appears in the third line of the display;
compressor now appears in the third line.
Press the return key () to display setpoint pressure in the third line of the display.
Press the return key () again and the following display appears.
EDU
& 5
VHWSRLQW SUHVV
S 63 EDU
6' EDU E
EDU
& 5
6' EDU
S 63 EDU
6' EDU E
Increase the setpoint pressure p2 with the arrow up key () and decrease it with the arrow
down key ().
Enter the new setpoint pressure with the return key ().
Press the arrow down key once (), so that the switching differential ---SD appears in the
third line of the display.
4 --- 62
Press the return key () and a flashing cursor appears below value p2.
Press the return key () and a flashing cursor appears below the switching differential ---SD.
Operation
Increase the switching differential ---SD with the arrow up key () and decrease it with the
arrow down key ().
In the main menu, press and hold the arrow up key (D) until configuration appears in the
third line of the display.
EDU
& 5
JHQHUDO
SUHVVXUH VHWWLQJV
FRQWURO PRGH
E
Press the return key () when pressure settings appears in the third line of the display.
Press the arrow down key () four times, until load control appears in the third line of the
display.
EDU
VHOHFWLRQ
& 5
ORDG FRQWURO
E
Press the arrow down key () three times and the following appears in the display.
EDU
& 5
ORFDO PRGH
S
Press the return key () when local mode appears in the second line of the display. A flashing cursor appears in the third line.
Press the arrow keys () until p2 appears in the third line of the display.
4 --- 63
Operation
-
In the main menu, press and hold the arrow up key (D) until communication appears in the
third line of the display.
EDU
56
56
& 5
[
[ 8
Press the arrow down key () twice until L2DP bus appears in the third line of the display.
Press the return key () when L2DP bus appears in the third line of the display. The following display appears:
EDU
& 5
QD
Press the arrow up key () until send+ receive appears in the third line of the display.
Press the arrow down key () twice until slave no.: 2 appears in the third line of the display.
Press the return key (), a flashing cursor appears below the number.
Set the correct slave number with the arrow keys ().
4 --- 64
Operation
-
Press the arrow down key () seven times until act.: n appears below software mon. in
the third line of the display. The following display appears:
EDU
& 5
VRIWZDUH PRQ
WLPHRXW V
DFWQ
8
EDU
& 5
WLPHRXW V
DFWQ
8
Press the return key (), a flashing cursor appears below the n.
Press the arrow down key () twice until remote key: n appears in the third line of the display. The following display appears:
EDU
& 5
UHPRWH NH\ Q
Press the return key (), a flashing cursor appears below the n.
4 --- 65
Operation
-
Saving settings
4 --- 66
Press and hold the arrow keys (D9) until data @EEPROM appears in the third line of the
display. Press the return key () .
When the display returns to n exit the submenu with the esc key.
Operation
4.8.6
Attention!
4.8.6.1
Sigma Control 1
Sigma Control 2
Pin
Pin
1
2
2
3
6
7
7
8
9
8
9
4 --- 67
Operation
Package 1
(controlling package)
Master
Package 2
(controlled package)
Slave
Start
Activate password
level 4
see chapter
7.1.1
Menu:
configuration
password
Menu:
configuration
password
Menu:
Menu:
configuration
configuration
Set pressure
parameter
for system
pressures
p1 and p2
pressure settings
compressor
system pressure
pressure settings
compressor
system pressure
setpoint pressure
p1
setpoint pressure
p1
setpoint pressure
p2
setpoint pressure
p2
Menu:
pressure settings
load control
settings
Change
default times
for p1 and p2
p1/p2 clock
or
p1/p2 cycle
Menu:
Menu:
configuration
pressure settings
load control
configuration
Activation of
p1/p2
changeover
from clock or
cycle
pressure settings
load control
remote mode
> p1/p2 RS 485
Activate
remote mode
via remote key
4 --- 68
Activation of
p2 from RS
485
remote key: y
Operation
2
Note:
The bitrate settings and the data
format must be identical for both
packages (communication menu).
Menu:
Menu:
communication
Activation
master
RS 485
communication
Activation
slave
RS 485
> master
> slave
Menu:
communication
data
EEPROM: y
Menu:
Save new
interface
settings
data
EEPROM: y
Attention!
Attention!
An error message appearing
after activation is normal. This
can be finally reset in active bus
mode after all items have been
processed.
communication
Switch off
control voltage
Switch on
control voltage
End
4 --- 69
Operation
4.8.6.1.1 Settings on both SIGMA CONTROLs
Carry out the following settings on both SIGMA CONTROLs.
-
Enter password
Press the arrow key () until password appears in the third line of the display.
EDU
& 5
SDVVZRUG
;;;;; /
;;;;; / C
By pressing the return key () a flashing cursor appears below the first X of the password
(XXXXX).
Change the first character with the arrow keys (). Keep pressing the arrow keys until the
first X is replaced by the character required.
Press the return key (), the cursor now jumps to the next character in the password.
EDU
& 5
SDVVZRUG
;;; /
;;;;; / C
Press the return key (), the cursor now jumps to the next character in the password.
Using this method, enter the remaining characters of the password for level 4 (12EXP). When the
last character of the password is entered with the return key (), the activated password level is
displayed.
EDU
& 5
SDVVZRUG
;;;;; /
;;;;; / C
4 --- 70
Operation
-
In the main menu, press and hold the arrow key (D) until configuration appears in the third
line of the display.
EDU
& 5
JHQHUDO
SUHVVXUH VHWWLQJV
FRQWURO PRGH
E
Press the return key () when the pressure settings appear in the third line of the display;
compressor now appears in the third line.
Press the return key () to display system pressure in the third line of the display.
Press the return key () again and the following display appears.
EDU
& 5
VHWSRLQW SUHVVXUH
S 63 EDU
6' EDU
Press the return key () and a flashing cursor appears below value p1.
Increase the setpoint pressure p1 with the arrow up key () and decrease it with the arrow
down key().
Enter the changed setpoint pressure with the return key ().
Press the arrow down key once (), so that the switching differential ---SD appears in the
third line of the display.
Press the return key and a flashing cursor appears below the switching differential ---SD.
Increase the switching differential ---SD with the arrow up key () and decrease it with the
arrow down key ().
4 --- 71
Operation
-
When the switching differential ---SD for setpoint pressure p1 has been set, press the arrow
down key () once. The following display appears:
EDU
& 5
6' EDU
S 63 EDU
6' EDU E
Press the return key () and a flashing cursor appears below value p2.
Increase the setpoint pressure p2 with the arrow up key () and decrease it with the arrow
down key ().
Enter the changed setpoint pressure with the return key ().
Press the arrow down key once (), so that the switching difference ---SD appears in the
third line of the display.
Press the return key () and a flashing cursor appears below the switching differential ---SD.
Increase the switching differential ---SD with the arrow up key () and decrease it with the
arrow down key ().
In the main menu, press and hold the arrow up key (D) until configuration appears in the
third line of the display.
EDU
JHQHUDO
& 5
SUHVVXUH VHWWLQJV
FRQWURO PRGH
E
4 --- 72
Press the return key () when the pressure settings appear in the third line of the display;
compressor now appears in the third line.
Press the arrow down key () until load control appears in the third line of the display.
Operation
a) Clock control
Press the arrow down key () until clock appears below settings in the third line of the display. Here the pressure change between p1 and p2 from the internal clock can be entered
(see also chapter 7.1.1 and 7.2.1).
EDU
& 5
SS FORFN
FORFN
E
b) Internal timer control
Press the arrow down key () until p1/p2 cycle appears below settings in the third line of
the display. Here the pressure change between p1 and p2 from the timer can be entered
(see also chapter 7.3.2.3).
EDU
& 5
SS F\FOH
S
K
S
K E
When all settings for the load changeover have been entered; the type of load changeover required can be selected.
Press the arrow up key () until local mode appears below load control in the second line of
the display.
Confirm the selected load changeover with the return key (). The following display appears:
a)
EDU
& 5
ORFDO PRGH
SS FORFN
b)
EDU
& 5
ORFDO PRGH
SS F\FOH
4 --- 73
Operation
-
Activate master
In the main menu, press and hold the arrow up key (D) until communication appears in the
third line of the display.
EDU
56
56
& 5
[
[ 8
Press the arrow down key () once, until RS485 appears in the third line of the display.
Press the return key () when RS485 appears in the third line of the display. The following
display appears:
56
;
QD
Press the arrow up key () until master appears in the third line of the display.
4 --- 74
Operation
4.8.6.1.3 Settings on the slave Sigma Control
Enter the following settings on the slave Sigma Control.
-
In the main menu, press and hold the arrow up key (D) until configuration appears in the
third line of the display.
EDU
& 5
JHQHUDO
SUHVVXUH VHWWLQJV
FRQWURO PRGH
E
Press the return key () when the pressure settings appear in the third line of the display;
compressor now appears in the third line.
Press the arrow down key () until load control appears in the third line of the display.
Press the return key (), a flashing cursor appears below the value to be changed.
UHPRWH NH\ Q E
Select control mode p1/p2 RS485 with the arrow keys (D9).
Press the arrow down key () once, so that remote key: n appears in the third line of the
display.
Press the return key (), a flashing cursor appears below the value to be changed.
4 --- 75
Operation
In the main menu, press and hold the arrow up key (D) until communication appears in the
third line of the display.
EDU
56
56
& 5
[
[ 8
Press the arrow down key () once, until RS485 appears in the third line of the display.
Press the return key () when RS485 appears in the third line of the display. The following
display appears:
56
;
QD
Press the arrow up key () until slave appears in the third line of the display.
4 --- 76
Operation
4.8.6.1.4 Settings on both SIGMA CONTROLs
Carry out the following settings on both SIGMA CONTROLs.
All important data are stored in an EEPROM that is no ---volt safe.
Data are retained even if the buffer battery discharges completely.
If the procedure is activated it takes approximately 30 seconds for the display to change back
from y to n.
Attention!
Press and hold the arrow keys (D9) until data @EEPROM appears in the third line of the
display. Press the return key () .
When the display returns to n exit the submenu with the esc key.
4 --- 77
Operation
4.8.6.2
Example 1
A BS 51 with Sigma Control and an existing SK 26 are to supply the demand at weekends
and during the night.
Recommendation:
The pressure switch settings of the SK 26 should lie exactly between the programmed pressures of the BS 51.
7.5 bar
7.0 bar
p1/BS
p2/BS
SK
6.0 bar
-
Example 2
Two machines of the same capacity, one with Sigma Control and the other with conventional
control, are to be sequenced as base and peak load machines.
Program the submenu p1/p2 on the Sigma Control machine according to the base load
sequence requirements.
Enter the required values (SP and SD) for p1 and p2.
Enter the changeover delays and/or periods in the load control menu.
One of the volt ---free contacts O0.3, O0.4 or O0.5 must be functionally allocated to the
p1/p2 submenu.
This contact is then used for the changeover between two pressure switches in the existing
old compressor package (see example circuit diagram).
4 --- 78
Operation
21
K3
22
K3
K3
A open:
A closed:
4 --- 79
Operation
-
1.
1.1
Daily changeover between p1 and p2 after 24 hours. The compressor package starts with
setpoint pressure p2 at 0.00 hours.
Start
Menu:
configuration
pressure settings
load control
p1/p2 changeover
from timer
local mode
> p1/p2 cycle
Menu:
configuration
pressure settings
load control
settings
> p1/p2 cycle
Duration
p1:
24h
p2:
24h
1st p2 start at:
00:00
End
1.2
Menu:
Start
load control
p1/p2 clock
p1/p2 day
1 p1/p2 day
p2:
00:00
p1:
06:00
2 p1/p2 day
p2:
12:00
p1:
18:00
End
4 --- 80
Operation
1.3
Start
Menu:
load control
p1/p2 clock
p1/p2 week
1>
1>
1<
1<
2>
2>
2<
2<
3>
3>
3<
3<
4>
4>
4<
4<
Monday
00:00
Monday
21:00
Tuesday
18:00
Wednesday
15:00
Thursday
12:00
Friday
09:00
Saturday
09:00
Sunday
03:00
End
4 --- 81
Operation
1.4
Start
Menu:
load control
p1/p2 clock
p1/p2 day
1 p1/p2 day
p2:
00:00
p1:
06:00
2 p1/p2 day
p2:
17:00
p1:
23:59
Menu:
load control
p1/p2 clock
p1/p2 week
1>
1>
1<
1<
Friday
17:00
Sunday
23:59
End
4 --- 82
31
61
6<6
6
+:
PN:
SN:
serial number
SYS:
system version
S5:
HW:
5.1
part number
hardware version
Main Menu
The main menu shows the current system pressure, the airend discharge temperature and the
mode of operation.
Example:
1
2
EDU
& 5
RII
E
Current system pressure and airend discharge temperature
Operational mode (current state)
If the arrow down key () key is pressed three times a further display level is accessed in which
the total operating hours and hours on load are additionally displayed.
5 --- 83
2
3
4
EDU
& 5
NH\2)) SLGOH
WRWDO K
ORDG
K
Hours on load
The following information can be displayed in the second line (operational messages):
e.g. key---ON p1---idle
load control status:
idle
in idle mode
off
p2
pE
RC
RB
compressor status
ON
compressor running
clk
Internal clock
RC
RB
5 --- 84
Return to the main menu from all other menus with the esc key.
Password Protection
When the controller is switched on, the lowest level of access (level 0) is started. An access level
(level 4) is available to the customers user. Changes to the settings in Sigma Control are allowed
in level 4.
See chapter 7.1.1 for entry of the password.
Attention!
5 --- 85
clock
configuration
components
package test
communication
5.4
password
language
Display Level
If the main menu is scrolled downwards with the arrow down key (), the menus in the Display
Level in which values can only be read are shown. These are:
-
status
analog data
operating data
maintenance
See following pages for an overall list of menus and submenus in the Display and Setup Level.
For an explanation of the abbreviated messages in the Display, see list of abbreviations in
chapter 7.8.
5 --- 86
Password Level 0
language
communication
esc
esc
--- general
---version no.
---model:
---P number:
---S number:
---weekday
---date
---time
---date format
---time format
---unit of pressure
---unit of temperature
(1X9)
---> (n.a./send/
send
receive)
---slave no.: ...
---hardware monitoring
start: ... s
---software monitoring
timeout: ... s
---active: y/n
---remote key y/n
configuration
clock
esc
password
---ON/OFF day
---ON/OFF week
---ON/OFF year
-- clock key y/n
esc
--- password
---password:
XXXXX L0
XXXXX L0
--- SMS
---SMS status
---active: y/n
---buffer empty
---channel 1
---error: 0
---modem
---location
---channel 1
---channel 2
Test menu
Version menu
System test
PN:
SN: 00000000
SYS: S5: HW:
2.14 0.60 0.5
Power in
automatic
Main Menu
5 sec.
PN:
= Part number
SN:
= Serial number
SYS: = System version
S5:
= Operating system version
HW: = Hardware version
Display Level
Normal text:
can be read
Bold text:
status
can be changed
analog data
operating data
maintenance
esc
---------------
oil filter
oil separator
oil change
air filter
V---belts change
V---belt tension
bearing change
--- bearing maint.
--- elect. equip.
esc
esc
--- operating hours
---total hours
---load hours
---compressor motor
---airend
---Sigma Control
---modulating valve
--- load valve ON
Escape key
returns to next higher level or to the main menu
-------------------------------
esc
display 1---6
system pressure
internal pressure
cut ---out pressure
differential pressure
oil separator
ADT temperature
ADT before start
ADT-rise dT/dt
PD temperature
VFD frequency
analog output
differential pressure
air filter
coolwater temperature
motor temp.
oil filter dp
statistics
Info key
calls up current
messages
esc
esc
messages
esc
---------
event info
last alarm:
last warning
current number
alarms:
Warnings:
--- current messages
Return key
initiates move to the next submenu, enters
parameters and passwords
5 --- 87
Password Level 4
Test menu
Version menu
System test
PN:
SN: 00000000
SYS: S5: HW:
2.14 0.60 0.5
Power in
automatic
5 sec.
PN:
= Part number
SN:
= Serial number
SYS: = System version
S5:
= Operating system version
HW: = Hardware version
status
Main Menu
esc
messages
analog data
operating data
maintenance
esc
esc
-------------------------------
statistics
esc
display 1---6
system pressure
internal pressure
cut ---out pressure
differential pressure
oil separator
ADT temperature
ADT before start
ADT rise dT/dt
PD temperature
VFD speed
analog output
differential pressure
air filter
coolwater temperature
motor temp.
oil filter dp
esc
5 --- 88
esc
Info key
calls up current messages
Escape key
returns to next higher level or to the main menu
esc
esc
event info
last alarm:
last warning:
current number
alarms:
warnings:
--- current messages
---------
Return key
initiates move to the next submenu, enters
parameters and passwords
Normal text:
Bold text:
can be read
can be changed
language
Password Level 4
communication
esc
package test
components
configuration
esc
--- general
clock
password
esc
esc
-- ON/OFF day
-- ON/OFF week
--- password
---password:
XXXXX L4
XXXXX L4
-- ON/OFF year
-- clock key y/n
--- reset
---remote reset
inputs: n.a. ; I..
---remote key: active y/n
---version no.
---model
---P number:
---S number:
---weekday
---date
---time
---summer/winter t
---date format
---time format
---unit of pressure
---unit of temperature
esc
--- motor
---power switching
---selection
---settings:
* star---delta
---star period
T : t: ...s
T : t: ...s
---c/o delay t: ...s
C
8
-- function
-- bitrate: ....
esc
-- format: ....
TV check
(master/slave)
--- TV check
relief valve: y / n
pi= ...
--- TV check
ADT alarm: y / n
offset: = ... C
ADT = ... C
---bitrate: ....
-- format: ....
---remote key y/n
(1X9)
---> (n.a./send /
send+ receive)
--- ...
---hardware monitoring
--- ...
--- set: y / n
start: ... s
---software monitoring
timeout: ... s
-- active:y / n
--- booster
---booster on
SP: ... bar
---SD: ... bar
output: n.a.; O...
---remote key y / n
--- SMS
---SMS status
--- AM charging
-- active: y/n
---valve open
SP: ... bar
---SD: ... bar
output: n.a.; O...
---buffer: empty
---channel 1
---error: 0
--- PD temperature
-- modem
-- location
-- channel 1
-- channel 2
Normal text:
Bold text:
can be read
can be changed
--- timer
---OFF: ... s
--- ON: ... s
output: n.a.; O ...
5 --- 89
Display Level
6
6.1
Status Data
status
statistics
print
6 --- 90
esc
esc
esc
--- total duty cycle
--- duty cycle from
--- reset
--- syspress. max
--- reset
--- syspress. min
--- reset
--- internal press. max
--- reset
--- motor starts from
--- reset
--- motor starts/day
--- max
--- motor starts/h
--- max
--- last load run
--- last idle run
--- motor OFF
messages
esc
event info
last alarm
last warning
current number
alarms:
warnings:
--- current messages
---------
Display Level
Display of status data
Press the arrow key ) until status appears in the third line of the display and then press
the enter key ).
Three further options are displayed:
- messages
- statistics
- print
6.1.1
Messages
Activate the messages menu option by pressing the return key () when messages appears in the third line of the display.
The submenu is divided into the following options:
- event information
The last 100 messages can be displayed. These include alarm messages and warning
messages.
- last alarm
The time at which the last alarm occurred and the corresponding alarm number.
- last warning
The time at which the last warning message occurred and the corresponding message
number.
- number of current alarm and warning messages.
- call---up of all current messages
Note
This menu option shows all current alarms and warnings and is especially
useful for faultfinding.
It can also be called up directly with the i key.
2
3
ODVW ZDUQLQJ
: F
EORZRII SURW
Type of message
5
6
Alarm
Message status
Warning
A
3
6 --- 91
Display Level
6.1.2
Statistics
Motor starts
The total number of motor starts is displayed and can be changed, if required. This could be
the case if another drive motor is fitted.
6 --- 92
Display Level
-
EDU
& 5
V\VSUHVV PD[
EDU E
2
3
Print
new messages
parameters
parameters file
2
3
EDU
& 5
SULQWHU RXWSXW
!QHZ PHVVDJH
6 --- 93
Display Level
6.1.3.1
Printer clock
The printer can also be controlled with the internal clock.
EDU
FORFN
& 5
Press the return key () to set the clock for the printer in the following submenu.
The clock for the printer can be set up exactly the same as for the clock for compressor (see
chapter 7.2).
6 --- 94
Display Level
6 --- 95
Display Level
6.2
Analog data
analog data
-------------------------------
6 --- 96
esc
available displays 1---6
system pressure
internal pressure
cut ---out pressure
differential pressure
oil separator
airend discharge
temperature
airend discharge
temperature before start
airend discharge
temperature-rise
package dischargetemperature
VFD speed
analog output
differential pressure
cooling water
temperature
motor temperature
oil filter dp
Display Level
Display of analog data
Press and hold the arrow key () until analog data appears in the third line of the display.
analog output*
motor temperature*
2
3
EDU
& 5
V\VWHP SUHVVXUH
S1
EDU
E
6 --- 97
Display Level
6.3
Operating data
operating data
esc
--- operating hours
--- total hours
--- load hours
--- compressor motor
--- airend
--- Sigma Control
--- modulating valve
--- load valve ON
6 --- 98
Display Level
Display of operating data
Press and hold the arrow down key () until operating data appears in the third line of the
display.
Press the return key () to display operating hours, total hours, number of motor starts and
the number of operations of the load valve.
Move from one display to the next with the arrow keys ().
Press the return key () until operating hours appears in the third line of the display.
Move between the different displays with the arrow keys ().
total hours
load hours
* If the hours shown in the third line of the display their value can be selected with the return key
() and changed with the arrow keys (). Change the hours if the corresponding component
has been replaced.
The following display options are possible:
Example:
2
3
EDU
& 5
WRWDO KRXUV
K
E
6 --- 99
Display Level
6.4
Maintenance
maintenance
6 --- 100
esc
Display Level
Display of maintenance hours
Press and hold the arrow down key () until maintenance appears in the third line of the
display.
All maintenance hours remaining until the next maintenance are displayed.
Example:
-
oil filter
oil separator
oil change
air filter
V---belts change
V---belt tension
bearing change
bearing maintenance
elect. equip.
2
4
EDU
& 5
RLO ILOWHU
K
UHVHW Q E
3
6 --- 101
Display Level
6.4.1
When the maintenance is complete the remaining interval (3) must be reset
to the default interval (4).
Password level 4 access is required to carry out changes to the maintenance
interval counters.
Note
The remaining hours in the corresponding maintenance interval counter can be individually reset.
Press and hold the arrow down key () until reset appears in the third line of the display.
Example:
EDU
& 5
K
K
UHVHW Q
Press the return key (), a flashing cursor appears below the n.
Change the reset display from n to y with the arrow up key ().
Confirm with the return key (). The counter resets to the default maintenance interval.
At the same time the reset display changes from y to n.
Press and hold the arrow down key () until the hours display for the required maintenance
interval appears in the third line of the display.
Example:
EDU
& 5
RLO ILOWHU
K
K
5HVHW Q E
The maintenance interval can be increased with the arrow up key () and reduced with
the arrow down key ().
Enter the maintenance interval setting with the return key ().
6 --- 102
Press the return key (), a flashing cursor appears below the maintenance interval.
Display Level
6 --- 103
7.1
Password
--- password
---password:
XXXXX L0
XXXXX L0
7 --- 104
password
esc
Enter password
(main menu password)
In the main menu, press and hold the arrow down key (D) until password appears in the
third line of the display.
EDU
& 5
SDVVZRUG
;;;;; /
;;;;; / E
Scroll through the character set with the arrow keys (D9) until the desired character appears.
Press the return key () to confirm the selection and the cursor moves to the next character
in the password.
Level
Password
00000
12EXP
7 --- 105
Clock
clock
esc
7 --- 106
In the main menu, press and hold the arrow up key (D) until clock appears in the third line
of the display.
compressor ON/OFF
EDU
2
& 5
FRPS212))
2
3
4
1
2
3
4
EDU
& 5
212)) GD\
212)) ZHHN
212)) \HDU
E
Current system pressure and airend discharge temperature
Daily schedule
Weekly schedule
Yearly schedule
Scroll the menu options up and down with the arrow keys ().
Scroll the schedule to be changed to the third line and activate with the return key ().
7 --- 107
2
3
4
1
2
3
4
7.2.1
EDU
& 5
212)) GD\
21
2))
E
Current system pressure and airend discharge temperature
First ON/OFF schedule (period)
Cut ---in time (ON switching point) of the compressor package in hours and minutes
Cut ---out time (OFF switching point) of the compressor package in hours and minutes
The cut ---in and cut ---out times of the compressor package can be changed by pressing the
return key ().
7.2.1.1
The daily schedule has the lowest and the yearly schedule the highest
priority.
Switching points in the weekly schedule have priority over switching points
in the daily schedule.
Daily switching point restrictions, such as are necessary for the weekend, are entered in the
weekly schedule.
The following conditions must be fulfilled:
-
7 --- 108
7.2.1.3
The periods entered must contain all information required (start weekday, start time, end
weekday, end time, required operational state).
Attention!
When the clock key is pressed (3, see chapter 4.3.1) only the channel
command (compressor channel) from the clock is used to control the compressor package.
The clock function itself is not influenced, that is, the clock runs continuously in the background.
7 --- 109
1 ON/OFF day
2 ON/OFF day
ON:
05:30
ON:
13:00
OFF:
12:00
OFF:
21:10
1 ON/OFF week
1 Friday
1 14:00
1 Sunday
1 23:59
1: comp. OFF
1 ON/OFF year
2 ON/OFF year
1 11.07.
2 24.12.
1 00:00
2 12:00
26.07.
31.12.
23:59
23:59
1: comp. OFF
-
3 ON/OFF year
3 01.01.
3 00:00
3
02.01.
05:30
3: comp. OFF
7 --- 110
2: comp. OFF
Enter 0 for year switching point 4.
1 Monday
1 06:00
1
Saturday
22:00
1: comp. ON
Note
Note
All settings in the ON/OFF compressor menu are active only after the clock
key has been pressed.
Note
7.2.1.4
Clock key:
Menu: clock -- compressor ON/OFF -- clock key
The clock key (
switched off.
Press the arrow keys (D9) until the following display appears:
EDU
& 5
FORFN NH\ Q
212)) GD\
C
Change the entry from act.: y to act.: n with the arrow keys (D9).
Confirm with the return key ().
7 --- 111
Configuration
---------------
7 --- 112
general
pressure settings
control mode
acknowledgement
compressor start
I/O periphery
timer
configuration
esc
In the main menu, press and hold the arrow up key (D) until configuration appears in the
third line of the display.
All settings affecting the configuration can be displayed and changed in password level 4.
The following display options are possible:
-
general
pressure settings
control mode
acknowledgement (reset) -
compressor start
I/O periphery
timer
Example:
EDU
& 5
JHQHUDO
SUHVVXUH VHWWLQJV
FRQWURO PRGH
E
7.3.1
Scroll between the individual entries with the arrow keys (D9).
Scroll the desired menu option to the third line and activate with the return key ().
General
(main menu configuration general)
Press and hold the arrow keys (D9) until general appears in the third line of the display.
version no.
model
PN:
(part number)
SN:
(serial number)
weekday
Press and hold the arrow keys (D9) until weekday appears in the second line of the
display. The default weekday is displayed.
Use the arrow keys (D9) to select the current day of the week.
7 --- 113
date
Press and hold the arrow keys (D9) until date appears in the second line of the display.
time setting
Press and hold the arrow keys (D9) until time appears in the second line of the display.
summer/winter time
Press and hold the arrow keys (D9) until summertime appears in the second line of the
display.
Press the return key (). A flashing cursor appears below the day value.
Select the date and month with the arrow keys (D9) and confirm each setting with the
return key ().
Press the arrow down key () until the time appears in the third line of the display. Press
the return key ().
Select the hours and minutes with the arrow keys (D9) and confirm each setting with the
return key ().
Press and hold the arrow keys (D9) until wintertime appears in the second line of the
display.
Press the return key (). A flashing cursor appears below the day value.
Select the date and month with the arrow keys (D9) and confirm each setting with the
return key ().
Press the arrow down key () until the time appears in the third line of the display. Press
the return key ().
7 --- 114
Press and hold the arrow keys (D9) until summer/winter t appears in the second line of
the display.
Select the hours and minutes with the arrow keys (D9) and confirm each setting with the
return key ().
Press and hold the arrow keys (D9) until time changeover appears in the second line of
the display.
-
Change the entry from n to y with the arrow keys (D9) and activate with the return
key ().
Press and hold the arrow keys (D9) until date format appears in the second line of the
display.
The currently set date format is shown in the third line of the display.
Use the arrow keys (D9) to select the required date format.
Example:
DD.MM.YY
30.08.98
YY---MM---DD
98---08---30
MM/DD/YY
08/30/98
Press and hold the arrow keys (D9) until time format appears in the second line of the
display.
Use the arrow keys (D9) to select the required time format.
Example:
hh:mm:ss
08:29:43
hh:mm
08:29
hh:mm:ss AM/PM
08:29:43 AM
hh:mm AM/PM
08:29 AM
h stands for hours, m for minutes, s for seconds, AM for forenoon and PM for afternoon.
-
Press and hold the arrow keys (D9) until unit of press. appears in the second line of the
display.
Use the arrow keys (D9) to select the required unit of pressure.
7 --- 115
at
Hg
megapascal
psi
hectopascal
unit of temperature
Press and hold the arrow keys (D9) until unit of temp. appears in the second line of the
display.
Press the return key () and a flashing cursor appears below the unit of temperature.
Use the arrow keys (D9) to select the required unit of temperature.
Example:
20 C
68 F
7.3.2
degrees Fahrenheit
293 K
degrees Celsius
degrees Kelvin
Pressure settings
(main menu configuration pressure settings)
Press and hold the arrow keys (D9) until pressure settings appears in the third line of the
display.
vacuum package
7.3.2.1
compressor
load control
Compressor configuration
(main menu configuration pressure settings compressor)
Pressure parameters important for the compressor are displayed and set in the following submenus.
7 --- 116
Press and hold the arrow keys (D9) until system pressure appears in the third line of the
display.
blowoff prot.
Two switching points (SP) are displayed:
These values are installed at the factory and can only be changed by an authorised KAESER
agent.
-
nominal pressure
The compressor is designed for this end pressure. It also represents the maximum possible
system setpoint pressure.
This value is installed at the factory and can only be changed by an authorised KAESER
agent.
setpoint pressure
The two pressure parameters p1 and p2 at which the compressor package can be run, i.e.
the upper cut ---out point together with its switching differential (SD) in each case are displayed and can be changed here.
Setting up a parameter:
-
Scroll the required parameter into the third line of the display with the arrow keys (D9).
Set the required value with the arrow keys (D9) and confirm with the return key ().
-
Scroll the required parameter into the third line of the display with the arrow keys (D9).
Set the required value with the arrow keys (D9) and confirm with the return key ().
It is regarded as the system pressure lower limit minus the system pressure switching differential.
Scroll the parameter to be set into the third line of the display.
7 --- 117
Set the required value with the arrow keys (D9) and confirm with the return key ().
This value is installed at the factory and can only be changed by an authorised KAESER
agent.
-
pressure increase
Press and hold the arrow keys (D9) until press. increase appears in the third line of the
display.
The currently set value for the pressure increase pE appears in the third line of the display.
Set the required value with the arrow keys (D9) and confirm with the return key ().
7 --- 118
Vacuum package
(main menu configuration pressure settings vacuum package)
Keep pressing the arrow keys (D9) in the pressure settings submenu option until vacuum
package appears in the third line of the display and then press the return key ().
Pressure parameters important for the vacuum package are displayed and set in the following
submenus.
Press and hold the arrow keys (D9) until vacuum package appears in the third line of the
display.
nominal pressure
Scroll the parameter to be set into the third line of the display with the arrow keys (D9).
Set the required value with the arrow keys (D9) and confirm with the return key ().
-
Scroll the parameter to be set into the third line of the display with the arrow keys (D9).
Set the required value with the arrow keys (D9) and confirm with the return key ().
setpoint pressure
The two pressure parameters p1 and p2, i.e., the lower cut ---out point together with its
switching differential (SD) in each case, are displayed here.
Setting a parameter:
-
Scroll the parameter to be set into the third line of the display with the arrow keys (D9).
Set the required value with the arrow keys (D9) and confirm with the return key ().
nominal pressure
The vacuum package is designed for this end pressure. It also represents the minimum
possible system setpoint pressure.
This value is installed at the factory and can only be changed by an authorised KAESER
agent.
7 --- 119
pressure fall pE
Keep pressing the arrow keys (D9) until pressure fall appears in the third line of the display and then confirm with the return key ().
Set the required value with the arrow keys (D9) and confirm with the return key ().
Load control
(main menu configuration pressure settings load control)
Keep pressing the arrow keys (D9) in the pressure settings submenu option until load control appears in the third line of the display and then press the return key ().
a)
If the compressor is not controlled externally it defaults to the internal controller, Sigma Control.
Here, it is possible to keep to p1 or p2 permanently, to switch them with the clock or to cycle
them periodically.
Scroll with the arrow keys (D9) until local mode appears in the second line of the display.
Press the return key (). A flashing cursor appears below the operating mode.
Set the required mode with the arrow keys (D9) and confirm with the return key ().
b)
Scroll with the arrow keys (D9) until remote mode appears in the second line of the display.
7 --- 120
: setpoint pressure p1
: setpoint pressure p2
Example:
: p1/p2 RS485
Scroll with the arrow keys (D9) until remote key y/n appears in the third line of the display.
Press and hold the arrow keys (D9) until settings appears.
If the compressor package is switched between p1 and p2 setpoint pressures from a remote
contact the input address is shown here.
Changeover between p1 and p2 from the internal clock:
If the compressor package is to be run using two different pressures (p1 and p2), the switching
points for both pressures can be set in this menu option.
This is required for shift working, for example.
Press the return key () when p1/p2 appears in the third line of the display.
EDU
SS
SS
& 5
GD\
ZHHN
The procedure for setting up the day, week and year schedules is exactly the same as for the
clock.
Press the return key () when the parameter to be set appears in the third line of the display.
A flashing cursor appears below the time.
Press the return key () when p1/p2 day appears in the third line of the display.
Note
EDU
& 5
h SS GD\
S
S
C
7 --- 121
Press the return key () when the parameter to be set appears in the third line of the display.
A flashing cursor appears below the time.
Press the return key (), the cursor jumps to the minutes display.
The cycle periods can be preset if the compressor package is switched by a timer between setpoint pressures p1 and p2.
Press the arrow down key ) until p1: ..h appears in the third line of the display.
Press the arrow down key ) until p2: ..h appears in the third line of the display.
Press the arrow down key () until 1.Start p1 at: ..h appears in the third line of the display.
Press the arrow keys (D9) until the time below 1.Start p1 at: ..h appears in the third line of
the display.
Press the return key (), the cursor jumps to the minutes display.
The input address for the remote contact can be set in various control modes.
Idle key
The idle key on the control panel can be deactivated to prevent unauthorised use.
7 --- 122
Press the arrow keys () until idle key: y/n appears in the third line of the display.
Select idle key active y or inactive n with the arrow keys ().
7 --- 123
Control mode
(main menu configuration control mode)
Keep pressing the arrow keys (D9) in the control mode menu option until local mode
appears in the second line of the display and then press the return key ().
Press and hold the arrow keys (D9) in local mode until the control mode appears in the third
line of the display.
Select the required control mode with the arrow keys (D9).
The following control modes can be selected:
DUAL
VARIO
QUADRO
Continuous
Keep pressing the arrow keys (D9) in the control mode menu option until * Dual appears
in the third line of the display below the option settings and then press the return key ().
Keep pressing the arrow keys (D9) until t = ...s appears in the third line of the display
and then press the return key ().
Set the required idle period with the arrow keys (D9), taking the minimum period allowed
into account, and confirm with the return key ().
Press the arrow keys (D9) until * Quadro appears in the third line of the display and then
press the return key ().
Set the required unloaded period with the arrow keys (D9), taking the minimum period
allowed into account, and confirm with the return key ().
7 --- 124
Press and hold the arrow keys (D9) until unloaded period appears in the second and
t= ... s in the third line of the display. Press the return key ().
Scroll with the arrow up key (D) until unloaded period appears in the third line of the
display and then press the return key () to display the minimum unloaded period.
Press and hold the arrow keys (D9) until running period appears in the second and t=
... s in the third line of the display. Press the return key ().
Set the required running period with the arrow keys (D9), taking the minimum period allowed into account, and confirm with the return key ().
7.3.3.3
Scroll with the arrow up key (D) until running period appears in the third line of the display and then press the return key () to display the minimum running period.
Modulating control
(main menu configuration control mode modulating valve)
Keep pressing the arrow keys (D9) in the control mode menu option until mod. valve appears in the third line of the display and then press the return key ().
Keep pressing the arrow keys (D9) until pN SP: ...bar appears in the third line of the
display and then press the return key ().
Set the required cut ---out pressure with the arrow keys (D9) and confirm with the return
key ().
Note
Switching differential
Keep pressing the arrow keys (D9) until ---SD: ...bar appears in the third line of the
display and then press the return key ().
Set the required switching differential with the arrow keys (D9) and confirm with the
return key ().
The current output address of the modulating valve is shown in the third line of the display.
7 --- 125
Acknowledgement (reset)
(main menu configuration acknowledgement)
Keep pressing the arrow keys (D9) in the configuration menu option until acknowledgement appears in the third line of the display and then press the return key ().
In this menu option the settings for remote acknowledgement of a message are found.
-
Scroll the option remote ackn. into the second line of the display with the arrow
keys (D9).
C
Select act.: y (yes) or act.: n (no) with the arrow keys (D9).
7.3.5
Scroll the option remote key into the third line of the display with the arrow keys (D9)
and then press the return key ().
Compressor start
(main menu configuration compressor start)
Keep pressing the arrow keys (D9) in the configuration menu option until compressor
start appears in the third line of the display and then press the return key ().
7 --- 126
compressor ON
-
If several compressors start together there is danger of overloading the power supply.
To prevent this, each compressor package can be allocated a start delay time. This allows
the compressor packages to start at staggered intervals.
Keep pressing the arrow keys (D9) until td: ....s appears in the third line of the display
below compressor ONand then press the return key ().
Set the required delay time with the arrow keys (D9) and confirm with the return key ().
Press the return key () when compressor ON appears in the third line of the display.
The time at which the compressor packages are started can be set in this menu option. Also,
it can be differentiated between local and remote, i.e., direct control
-
local mode:
Press and hold the arrow keys (D9) in the compressor start menu option until compressor ON appears in the third line of the display.
Scroll with the arrow keys (D9) until local mode appears in the second line of the display.
In the key mode the compressor package is started with the ON key ( ). In the
key + clock mode the compressor package is additionally started by the internal clock.
Press the arrow down key () until clock key appears in the third line of the display.
Select clock key active y or inactive n with the arrow keys (D9).
remote mode:
Note
Press the arrow down key () until * comp. ON appears in the second line and
RC I.... appears in the third line of the display.
7 --- 127
Select a suitable input for the remote contact with the arrow keys (D9).
Enter the selection with the return key ().
compressor OFF
Venting: y/n
The compressor shutdown venting function (unloaded start) is activated in this menu.
-
Press the return key () when venting appears in the third line of the display.
Confirm the selection with the return key ().
Note
-
Press the return key () when restart appears in the third line of the display.
Confirm the selection with the return key ().
starting temp.
To prevent damage to the compressor package caused by starting at a temperature that is
too low, a minimum starting temperature of 2 C is set and the function activated in this
menu option.
7.3.6
I/O periphery
(main menu onfiguration I/O periphery)
Keep pressing the arrow keys (D9) in the configuration menu option until I/O periphery
appears in the third line of the display.
clock contact
Press the return key () when clock contact appears in the third line of the display.
EDU
& 5
FRQWDFW GD\
FRQWDFW ZHHN
The procedure for setting up the day, week and year schedules is exactly the same as for the
clock (see chapter 7.2.1).
Note
7 --- 128
Press the return key () when contact day appears in the third line of the display.
EDU
& 5
h FRQWDFW GD\
21
2))
C
Press the return key () when the parameter to be set appears in the third line of the
display.
Press the return key (), the cursor moves to the minutes display.
-
show quantities
-
selecting quantities
Keep pressing the arrow keys (D9) in the I/O periphery menu option until show quantities appears in the third line of the display.
Enter the list of individual quantities with the return key ().
There are two displays each for pressure, temperature and other physical quantities available.
Press the return key () when the required quantity appears in the third line of the display.
message text
Scroll the message text into the third line of the display with the arrow down key ().
Press the return key (), a cursor appears below the first character of the message text.
Search through the character set with the arrow keys (D9) for another character. Confirm
this character with the return key () and the cursor will move to the next character in
the text.
When all characters have been selected, confirm with the return key ().
The sensor input for this message is determined by scrolling the required input into the
third line of the display.
Press the return key (), a cursor appears under the corresponding input or its non ---activation (n.a.) is displayed.
7 --- 129
Scroll in the quantity to be processed with the arrow keys (D9) until calibration appears
in the second line of the display.
Press the return key (), a cursor appears below the quantity.
A definite quantity can now be assigned to the signal input from the sensor.
The value of this quantity can be changed with the arrow keys (D9).
-
calibration
external messages
In this menu option the type of message (alarm, service or operational message), the allocation of an input and the delay period for display of the message can be set.
Press the return key (), as soon as ext. messages appears in the third line of the display, the individual messages are displayed and can be processed.
Scroll the parameter to be set into the third line of the display with the arrow keys (D9).
message text
Scroll the message text into the third line of the display with the arrow keys (D9).
Press the return key (), a cursor appears below the first character of the message text.
Search through the character set with the arrow keys (D9) for another character. Confirm
this character with the return key and the cursor will move to the next character in the
text.
type of message
Press the return key (), a cursor appears below the message type, which can be
changed with the arrow keys (D9).
Press the return key (), a cursor appears below the input designation.
delay period
Press the return key (), a cursor appears below the delay period.
A period between 0 and 600 seconds can be set with the arrow keys (D9).
7 --- 130
When all characters have been selected, confirm with the return key ().
timer
(main menu configuration timer)
A solenoid valve for the drainage of condensate can be activated at regular intervals.
Press the arrow keys (D9) until timer appears in the third line of the display and then press
the return key (). The timer output is located below.
OFF period
Press the arrow keys (D9) until OFF appears in the third line of the display and then
press the return key ().
Set the required time period with the arrow keys (D9) and confirm with the return key ().
ON period
Press the arrow keys (D9) until ON appears in the third line of the display and then
press the return key ().
Set the required time period with the arrow keys (D9) and confirm with the return key ().
7 --- 131
Components
components
esc
---motor
---oil circulation
---booster
---AM charging
---PD temperature
7 --- 132
In the main menu, press and hold the arrow up key (D) until components appears in the
third line of the display.
EDU & 5
PRWRU
DFFHVV GRRUV
7.4.1
Motor
(main menu components motor)
Keep pressing the arrow keys (D9) in the components menu option until motor appears in
the third line of the display.
7.4.1.1
Power switching
(main menu components motor power switching)
The type of motor start and the corresponding settings are entered in this menu option.
-
star---delta start
direct ---online---start
high tension
soft start
VFD compressor
Set the required type of motor start with the arrow keys (D9) and confirm with the return
key ().
The parameters for the respective type of motor start can be set in this menu option.
7.4.2
Oil circulation
Press the return key () when oil circulation appears in the third line of the display in the
components menu option.
A submenu with the following menu option opens:
oil separator
7 --- 133
Oil separator
Press the return key () when oil separator appears in the third line of the display in the
oil circulation menu.
The inputs for the temperature and differential pressure transducers on the oil separator together with the delay period for an excessive differential pressure alarm are displayed.
Press the return key () when diff. pressure appears in the third line of the display.
The input allocation for the oil separator pressure transducer is set in this menu option.
Press the arrow down key () until td: ....s appears in the third line of the display.
Press the return key (), a cursor appears below the delay period.
Set the required delay period with the arrow keys (D9).
Press the return key () when temperature appears in the third line of the display.
The input allocation for the oil separator temperature transducer is set in this menu option.
7.4.3
Booster
Press the return key () when booster appears in the third line of the display in the components menu.
The pressure switching point and the pressure switching differential for a booster can be set
in this menu option.
Because a booster only works efficiently above a certain minimum pressure it should be cut
in only after achieving this pressure.
The output controlling the booster is also displayed.
Press the return key (), a cursor appears below the pressure value.
Set the required pressure switching point with the arrow keys (D9).
Press the arrow down key () until ---SD: ....bar appears in the third line of the display.
Press the return key (), a cursor appears below the pressure value.
Set the required switching differential with the arrow keys (D9).
7 --- 134
Press the arrow down key () until SP: ....bar appears in the third line of the display.
Press the return key () when AM charging appears in the third line of the display in the
components menu.
The pressure switching point and the pressure switching differential for air main charging of
an empty air main can be set in this menu option.
A valve is located upstream of the empty air main that first opens when the working pressure
has been reached. The output controlling the valve is displayed.
Press the return key (), a cursor appears below the pressure value.
Set the required pressure switching point with the arrow keys (D9).
Press the arrow key () until ---SD: ....bar appears in the third line of the display.
Press the return key (), a cursor appears below the pressure value.
Set the required switching differential with the arrow keys ().
7.4.5
Press the arrow key () until SP: ....bar appears in the third line of the display.
Press the return key ( ) when PD temperature appears in the third line of the display in the
components menu.
The analog input for the transducer is set in this menu option.
Press the arrow down key () until PD temperature appears in the second line of the
display.
Press the return key (), a cursor appears below the displayed input.
The pressure switching points and switching differentials for the high or low package discharge temperature alarm and warning messages can be set in this menu option.
Press the arrow down key () until SP: ....bar appears in the third line of the display.
Press the return key (), a cursor appears below the pressure value.
Set the required pressure switching point with the arrow keys (D9).
Press the arrow down key () until ---SD: ....bar appears in the third line of the display.
7 --- 135
Package Test
esc
package test
---compressor test
---TV check
---binary inputs
---binary outputs
---lamps test
In the main menu, press and hold the arrow up key (D) until package test appears in the
third line of the display.
EDU
& 5
7h9 FKHFN
E
7 --- 136
Compressor test
(main menu package test compressor test)
Press and hold the arrow up key (D) until the following display appears.
EDU
& 5
FRPSU WHVW Q
E
This option shows whether compressor test is activated or not.
7.5.2
TV check
(main menu package test TV check)
Press and hold the arrow keys (D9) until TV check appears in the third line of the display.
Press and hold the arrow keys (D9) until relief valve: n appears in the third line of the display.
The pressure relief valve can be checked for correct function using the following procedure:
Press the arrow up key (D) until the display changes to relief valve: j.
Press and hold the ON (I) key until the pressure relief valve opens. As long as the
ON key is pressed the compressor remains on load and does not switch to idle mode
even if the nominal package pressure is exceeded. The internal pressure pi that is built
up when the pressure relief valve blows is shown in the fourth line of the display.
For safety reasons the function must be deactivated when this check is finished.
Release the ON key immediately after the pressure relief valve opens because of escaping oil mist.
7 --- 137
Press and hold the arrow keys (D9) until ADT alarm appears in the third line of the display.
Shut down the compressor package and wait until the airend temperature has fallen by
around 5 C. The offset value is determined by subtracting the actual airend temperature
from 110 C.
Example:
--- operational airend discharge temperature: 80 C
--- airend discharge temperature after cooling: 75 C
--- offset value: 110 C minus 80 C = 30 C
Press the arrow keys (D9) until offset= ...C appears in the third line of the display and
then press the return key ().
Enter the evaluated offset value with the arrow keys (D9) and confirm with the return key
() .
Press and hold the arrow up key (D) until ADT alarm:n appears in the third line of the
Press the arrow up key (D) until the display changes to ADT alarm: y.
Press and hold the ON (I) key and switch the compressor package to load. The ADT
display now shows the total temperature (airend discharge temperature + offset). If the
airend discharge temperature climbs to the previous temperature, the compressor package will shut down at 110 C because of the offset. The temperature prevailing at shutdown is displayed in the fourth line of the display by pressing the arrow down key (9)
(ADT).
Press and hold the arrow keys (D9) until offset= ... C appears in the third line of the
display and then press the return key ().
Reset the offset value to 40 C with the arrow keys (D9) and enter with the return key ()
.
For safety reasons the function must be deactivated when this check is finished.
7.5.3
Press and hold the arrow keys (D9) until binary inputs or binary outputs appear in the
third line of the display.
The current binary states of the digital inputs and outputs are shown.
Example:
7 --- 138
EDU
& 5
E
(
(
(
(
7.5.4
Lamps test
Press and hold the arrow keys (D9) until lamps test appears in the third line of the display.
EDU
& 5
/DPSV WHVW Q
E
The setting can be changed from n (no) to y (yes) by pressing the arrow key (D).
7 --- 139
Communication
7 --- 140
Communication
esc
Press and hold the arrow up key (D) until communication appears in the third line of the
display.
RS232:
Provides an interface to programming equipment (e.g. AS 511), a modem, a printer, etc.
RS485:
Allows two compressors to be sequenced (master---slave).
All the parameters entered are permanently stored in the EEPROM even if the power supply fails.
The following display options are possible:
EDU
2
56
56
& 5
[
[E
RS 232 interface
The RS 232 is a serial interface that is required for several functions.
Some examples are programming of the controller, an interface for the printer or modem.
Press the return key () when RS 232 is in the third line of the display, the RS 232 menu option opens.
Function
A function can be allocated to the RS 232 in this menu option or the allocated function is displayed.
Press the arrow keys (D9) until the function [printer, modem, programming unit (AS511)] appears in the third line of the display.
Press and hold the arrow keys (D9) until the required function for this interface is set.
7 --- 141
Press and hold the arrow down key () until the bitrate appears in the third line of the display.
Press and hold the arrow keys (D9) until the required bitrate appears in the third line of the
display.
Format
Press and hold the arrow keys (D9) until format appears in the third line of the display.
The current character frame is shown in the third line of the display.
Press and hold the arrow keys (D9) until the required format is set.
7 --- 142
RS 485 interface
The RS 485 interface is used for the master---slave function. The settings for bitrate and format
must be the same for both master and slave.
Function
A detailed description of this function is given in chapter 4.
Press and hold the arrow keys (D9) until either master or slave or n.a., as required, appears
in the third line of the display.
Select the required function with the arrow keys (D9) and confirm with the return key ().
Bitrate
Press and hold the arrow keys (D9) until the preset bitrate is displayed.
Format
Press and hold the arrow keys (D9) until format appears in the third line of the display.
The current character frame is shown in the third line of the display.
Press and hold the arrow keys (D9) until the required format appears in the third line of the
display.
Remote key
If the compressor package is to be controlled by a master controller via the RS 485 interface the
remote key must be set to y.
Press and hold the arrow keys (D9) until the remote key is set to yes or no, as required.
7.6.3
Press and hold the arrow keys (D9) until remote key appears in the third line of the display.
Keep pressing the arrow keys (D9) until L2DP bus appears in the third line of the display
and then confirm with the return key ().
Press the return key () when the first entry appears in the third line of the display.
7 --- 143
Select the options not active (n.a.) or send or send and receive (send+ receive) with
the arrow keys (D9) and then confirm with the return key ().
Slave number
If the compressor package is connected to a profibus system a clear allocation of the master
must be evident. This allocation is made with the slave number.
Press the arrow keys (D9) until slave no.: ... appears in the third line of the display and then
press the return key ().
Set the appropriate slave number (2...126) with the arrow keys (D9) and confirm with the return key ().
Hardware monitoring
The hardware monitoring function is shown in this menu.
The bus monitoring is deactivated for this period by the bus controller after the mains power supply is switched on.
Software monitoring
The software monitoring can be activated in this menu.
Timeout:
The bus---master must respond to a Sigma Control signal within this period otherwise an alarm is initiated.
Press and hold the arrow keys (D9) until active (act.:) y/n appears in the second line of the
display.
Press and hold the arrow keys (D9) until active is set toyes orno.
Remote key
If the compressor package is to be controlled by a master controller via the L2DP bus the remote
key must be set to y.
Press and hold the arrow keys (D9) until the remote key is set to yes or no, as
required.
7.6.4
Press and hold the arrow keys (D9) until remote key appears in the third line of the display.
SMS
Press the arrow keys (D9) until SMS appears in the third line of the display and then press
the return key ().
Settings defining transmission of an SMS to the customer service department are made in this
menu.
Press the arrow down key () once, until active (act.:) appears in the third line of the display.
Press the return key () and change the n to a y with the arrow up key ().
Further menu options can be accessed with the arrow down key ():
modem
The telephone number of the online modem is entered and the necessary initialisation is carried
out in this option.
7 --- 144
location
The responsible Kaeser subsidiary is shown. The customers name, telephone number and the
language in which the SMS is to be sent can be entered in this option.
-
channel 1
The telephone number of the responsible call centre, the number of automatic redials and the
duration of the pause between two calls is entered in this menu option.
Further, the telephone number of the customer service department responsible and the type of
protocol sent in the SMS is shown.
-
channel 2
Saving settings
All important data are stored in an EEPROM that is no ---volt safe.
Data are retained even if the buffer battery discharges completely.
If the procedure is activated it takes approximately 30 seconds for the display to change back
from y to n.
Attention!
Press and hold the arrow keys (D9) until data @EEPROM appears in the third line of the
display. Press the return key () .
When the display returns to n exit the submenu with the esc key.
7 --- 145
Languages
language
7 --- 146
Press and hold the arrow up key (D) until the language setting appears in the third line of the
display.
7 --- 147
List of Abbreviations
A
act
ADT
AI
alm
AM
an.
AO
avail
bin.
blowoff prot
C
clk
ch
c/o
comp
cont break
cont.
corr
cRC
D
DI
diff.
dir
DO
DOL
DoR
DOS
DP
dp
dT
tial)
elect.
equip
ext .
F
VFD
fil
Fr
G
h
hPA
HT
I
K
loc.
max
min.
min
Mo
MOPS
n
n.a.
7 --- 148
no.
O
OM
op
open cct.
os
P
p
para
param.
PD
pE
PDT
pd
PG
pi
PN
pN
press.
prot
profibus
PS
RAM
RB
RC
RD
S
s
SD
SN
Sa
sh.cct
SP
SSt
Su
t
T
TAP
temp
tens.
Th
tmr
UCP
W
We
VS
y
star---delta
number
operational message
output
operational message
operation
open circuit
oil separator
parity
pressure, usually airmain
pressure
parameter
parameter
package discharge
system pressure increase
package discharge
temperature
period
programming function
internal pressure
(in oil separator)
L2DP
system pressure
pressure
protection
process field bus
power switching
random access memory
remote bus
remote contact
refrigeration dryer
STOP or stop bit
second(s)
switching differential
serial number
Saturday
short circuit
switching point
soft start device
Sunday
time value
temperature
SMS protocol
temperature
tension
Thursday
timer
SMS protocol
warning, or maintenance
message
Wednesday
variable speed
yes
star---delta (wye---delta)