Wind Load and Roof Load Calculation
Wind Load and Roof Load Calculation
Wind Load and Roof Load Calculation
Example Calculations
Design a CMU pier and ground anchor foundation for a manufactured home to be placed in
an SFHA Zone AE having a ood velocity of 2 fps. The BFE is 9 feet and existing ground eleva-
tion is approximately 7 feet. The ood depth is 2 feet and the freeboard is 1 foot, which yields
a DFE depth of 3 feet. The manufactured home dimensions for these example calculations are
shown in Figure F-1. The manufactured home is a single unit, 16 feet wide and 60 feet long
with a 30-degree gable roof with a 1-foot overhang. Roong members are spaced 16 inches on
center (o.c.). The manufactured home weighs 20 psf. Assume an NFPA 5000 soil classication
of soft, sandy clay, or clay (allowable bearing pressure q
a
=1,000 psf ; ultimate bearing pressure
q
u
= 2,000 psf). Use ASCE 7 to calculate loads.
Foundation loads selected for this example of a manufactured home in an SFHA differ from
those that may be found in HUD standard 24 CFR 3280. Design loads in this example are in ac-
cordance with ASCE 7-05 and other standards.
These example calculations assume transverse wind loads produce the controlling loading.
Wind in the direction parallel to the roof ridge may produce greater loads for certain cases and
must be evaluated during nal design.
Figure F-1. Manufactured
home dimensions.
ASCE 7-05
PROTECTING MANUFACTURED HOMES FROM FLOODS AND OTHER HAZARDS
A Mul ti - Hazard Foundati on and I nstal l ati on Gui de
F-1
F EXAMPLE CALCULATIONS
Step 1: Determine Design Criteria
NORMAL LOADS
Dead Load (D)
D = 20 psf Given in the example statement
Live Load (L)
L is based on one- and two-family dwellings
L = 40 psf
Roof Live Load (L
r
)
L
r
= 20R
1
R
2
=20(1)(0.85)=17 psf
R
1
= 1 for A
t
200 ft
2
A
t
= 2(9.2 ft)(16 in) =24.5 ft
2
F = number of inches of rise per foot
F = 1ft tan 30 = 7 in
Note that the roof live load falls between the limits giv-
en:
12 L
r
20
ENVIRONMENTAL LOADS
Wind Loading
Structure is a regular shape, located in a windborne debris region with
terrain classication of Exposure C and surrounded by at terrain.
Mean roof height (h)
h = 3 ft + 10 ft + 0.5(4 ft)
= 15 ft
h < 16 ft (least horizontal dimension)
Calculations are for a foundation system, which is a main wind force re-
sisting system (MWFRS).
Velocity Pressures
Velocity pressures are determined using
Method 2: Analytical Procedure
ASCE 7-05
Table 4-1
ASCE 7-05
Section 6.2
Section 6.5
1 ft
12 in
( )
12 in
1 ft
( )
F-2 PROTECTING MANUFACTURED HOMES FROM FLOODS AND OTHER HAZARDS
A Mul ti - Hazard Foundati on and I nstal l ati on Gui de
EXAMPLE CALCULATIONS F
(A simplied alternative is to use ASCE 7, Section 6.4, Method 1. Wind
pressures are tabulated for basic conditions. The wind pressure must be
adjusted for mean roof height and exposure category.)
Velocity Pressure Coefcient (q
z
)
q
z
= 0.00256K
z
K
zt
K
d
V
2
I
Velocity pressure exposure coefcient evaluated at height z (the
height above ground level in feet) (K
z
)
K
z
= 0.85
Topographical factor (K
zt
)
K
zt
=1 (assume a at surface)
Wind directionality factor (K
d
)
K
d
= 0.85
Basic Wind Speed (V)
V = 110 mph (3-second gust)
I = 1 (Category II building: Table 1-1 (ASCE 7))
Therefore, q
z
= 0.00256(0.85)(1)(0.85)(110)
2
(1)
= 23 psf
Design Pressures for MWFRS
Internal Pressure Coefcient (GC
pi
)
GC
pi
= 0.18
External Pressure Coefcient (C
p
)
h = Mean roof height, in feet
L = Horizontal dimension of building, in feet, measured par-
allel to wind direction
B = Horizontal dimension of building, in feet, measured nor-
mal to wind direction
Table F-1 shows the External Pressure Coefcients calculated for the
windward, leeward and side walls. Computations of the External Pres-
sure Coefcients for the windward and leeward roof are shown Table
F-2.
Section 6.5.10
Eq. 6-15
Section 6.5.6
Table 6-3
Section 6.5.6
Section 6.5.4.4
Section 6.5.5
Table 6-1
Section 6.5.4
Section 6.5.11.1
Figure 6-5
Section 6.5.11.2.1
Figure 6-6
Figure 6-6
PROTECTING MANUFACTURED HOMES FROM FLOODS AND OTHER HAZARDS
A Mul ti - Hazard Foundati on and I nstal l ati on Gui de
F-3
F EXAMPLE CALCULATIONS
Table F-1. External Wall Pressure Coefcients
Surface Wind Direction L/B C
p
Windward Wall n/a n/a 0.8
Leeward Wall
Perpendicular to
roof ridge
-0.5
Side Wall n/a n/a -0.7
Table F-2. External Roof Pressure Coefcients
Surface Wind Direction h/L C
p
Windward Roof
Perpendicular to
roof ridge
-0.3
0.2
Leeward Roof -0.6
Foundation systems are considered rigid, therefore, G = 0.85.
Design Pressure (p)
The basic pressure equation (ASCE 7 6-17), which includes the internal
pressure coefcient is as follows:
p = qGC
p
q
i
(GC
pi
)
However, this would only be used if designing individual components
whose effective tributary area is equal to or greater than 700 sf (ASCE
7-05 6.5.12.1.3 and IBC 2006 1607.11.2.1). When determining loads on
the global structure (i.e., shear walls or foundation design), the inter-
nal pressure components will act in equal and opposite directions on
the roof/oor and the leeward/windward walls, thereby algebraical-
ly canceling each other. The resulting simplied form of the pressure
equation is:
p = q x GC
p
Table F-3 summarizes the design pressures calculated using this simpli-
ed wind design pressure equation. Figure F-2 shows the application of
these design pressures on the structure. For foundation design, internal
pressures need not be considered since internal pressure on windward
walls, leeward walls, oors, and roofs cancel each other. For example,
internal pressures acting on a windward wall are equal and opposite to
those acting on a leeward wall and the net force on the foundation from
internal pressures is zero.
15 ft
16 ft
= 0.94
16 ft
60 ft
= 0.27
Figure 6-6
Figure 6-6
Section 6.5.8
Eq. 6-17
F-4 PROTECTING MANUFACTURED HOMES FROM FLOODS AND OTHER HAZARDS
A Mul ti - Hazard Foundati on and I nstal l ati on Gui de
EXAMPLE CALCULATIONS F
While internal pressures cancel, internal pressures for a partially en-
closed building have been included in the example. This is to provide
an example of more general wind load calculations.
Table F-3. Design Pressures for Wind Perpendicular to the Roof Ridge
Surface
Design Wind Pressure
Calculations
pressure
(psf)
Windward Wall p = 23 psf(0.85)(0.8) 15.7
Leeward Wall p = 23 psf(0.85)(-0.5) -9.8
Side Walls p = 23 psf(0.85)(-0.7) -13.7
Windward Roof
p = 23 psf(0.85)(-0.3) -5.9
p = 23 psf(0.85)(0.2) 4.0
Leeward Roof p = 23 psf(0.85)(-0.6) -11.8
MWFRS Roof Overhang Pressures
ASCE 7 only addresses the windward overhang, specifying the use of a
positive pressure coefcient of C
p
= 0.8. Acting on the bottom surface of
the overhang in combination with pressures acting on the top surface.
For the leeward overhang, the coefcient for the leeward wall (C
p
= -0.5)
could be used, but the coefcient has been conservatively taken as zero.
p = 23 psf(0.85)(0.8)
= 15.7 psf
p
OH
= -5.9 psf 15.7 psf = -21.6 psf
A conservative simplication is to use the wind pressure acting away from
the roof case for uplift roof pressure simultaneously with the wind pres-
sure toward the roof for the lateral roof pressure.
ASCE 7-05
Section 6.5.11.4.1
PROTECTING MANUFACTURED HOMES FROM FLOODS AND OTHER HAZARDS
A Mul ti - Hazard Foundati on and I nstal l ati on Gui de
F-5
F EXAMPLE CALCULATIONS
Figure F-2. Maximum
uplift and lateral wind
loads on roof.
SNOW LOADING
Ground Snow Load (p
g
)
p
g
= 20 psf
Flat Roof Snow Load (p
f
)
p
f
= 0.7C
e
C
t
Ip
g
p
f
= 0.7(1.0)(1.0)(1.0)(20)
= 14 psf
But not less than p
f
=(I)p
g
= 20 psf
ASCE 7-05
Section 7.2
Figure 7-1
Section 7.3
Eq. 7-1
F-6 PROTECTING MANUFACTURED HOMES FROM FLOODS AND OTHER HAZARDS
A Mul ti - Hazard Foundati on and I nstal l ati on Gui de
EXAMPLE CALCULATIONS F
Section 7.3.1
Table 7-2
Section 7.3.2
Table 7-3
Section 7.3.3
Table 7-4
Section 7.4
Eq. 7-2
Section 7.4.1
Figure 7-2
Section 7.6
Section 7.6.1
Figure 7-9
Eq. 7-3
PROTECTING MANUFACTURED HOMES FROM FLOODS AND OTHER HAZARDS
A Mul ti - Hazard Foundati on and I nstal l ati on Gui de
F-7
Exposure Coefcient (C
e
)
C
e
= 1.0 (partially exposed roof)
Thermal Factor (C
t
)
C
t
= 1.0
Importance Factor (I)
I = 1.0 (Category II building: Table 7-4 (ASCE 7))
Sloped Roof Snow Load (p
s
)
p
s
= C
s
p
f
= (1.0)(20 psf)
= 20 psf
Warm Roof Slope Factor (C
s
)
C
s
= 1.0 (asphalt shingle not slippery)
Unbalanced Roof Snow Load (p
u
)
Since the roofs eave to ridge distance 20 ft, unbalanced uniform snow
loads shall be applied as follows:
P
windward
= 0.3 p
s
= 6 psf
P
leeward.1
= p
s
= 20 psf
P
leeward.2
= (h
d
)()/(S)
= (1.44 ft)(16.6 pcf)/(1.73)
= 18.2 psf
From the ridge toward the leeward eave a distance of:
x = (8/3)(h
d
)(S)
= 5.1 ft
h
d
= 1.44 ft
= 0.13 p
g
+ 14 30 pcf
= 16.6 pcf
F EXAMPLE CALCULATIONS
FLOOD LOADING
Hydrostatic Load (F
h
)
If the manufactured home is elevated above the BFE on
an enclosed foundation, venting must be provided in all
manufactured homes placed in a SFHA; the hydrostatic
forces on either side of the foundation wall will cancel.
However, the hydrostatic load is calculated because it is
used in the hydrodynamic load calculation.
F
h
= P
h
H
Hydrostatic Pressure (P
h
)
P
h
= H
Specic Weight of Fresh Water ()
= 62.4 pcf
Floodproong Design Depth (H)
H = 2 ft (base ood depth) + 1 ft
Hydrodynamic Load
The hydrodynamic load is calculated by converting it to an equivalent
hydrostatic load by increasing the ood depth. The increase in ood
depth is referred to as d
h.
Drag Coefcient (C
d
)
In the above equation, a value of 2.0 was assumed
for C
d
. This is a conservative estimate; the actual
value for C
d
could be anywhere between 1.2 and
2.0.
Acceleration Due to Gravity (g)
g = 32.2 ft/s
2
with a hydrodynamic pressure of
P
hydr
= (d
h
) = 62.4 pcf (0.13 ft) = 8.2 psf
The equivalent hydrostatic load (F
h/ad
) taken into consid-
eration the hydrodynamic load is :
F
h/ad
= P
hydr
x H = 8.2 psf x3 ft = 24.6 plf
ASCE 7
Eq. 7-5
C
d
V
2
2g
d
h
= = = 0.13 ft
2.0(2
ft
/
s
)
2
2(32.2
ft
/
s
)
FEMAs Coastal Construction Man-
ual (FEMA 55) recommends a value
of 2.0 for square or rectangular piles
and 1.2 for round piles.
For additional guidance regarding
drag coefcients, refer to Volume II
of the U.S. Army Corps of Engineers
Shore Protection Manual (USACE
1984), FEMA 55, and the Engineering
Principles and Practices for Retro-
tting Flood-Prone Residential Struc-
tures (FEMA 259).
Note: A 1-foot freeboard is added
to the BFE depth to provide a
protection above the BFE; 3 feet
becomes the design depth or the
DFE.
F-8 PROTECTING MANUFACTURED HOMES FROM FLOODS AND OTHER HAZARDS
A Mul ti - Hazard Foundati on and I nstal l ati on Gui de
EXAMPLE CALCULATIONS F
Since piers are 16 inches wide, the total hydrodynamic force on
the pier is
CHECK SCOUR
Reference: Publication No. FHWA NHI 00-001, Evaluating Scour at Bridges, 4th Edition, May 2001,
Hydraulic Engineering Circular No. 18.
Y
s
= 2.0 x (K
1
)x (K
2
) x(K
3
) x(K
4
) x (a/Y
1
)
0.65
x F
r1
0.43
Y
1
Where: Y
= Scour depth
Y
1
= Flow depth directly upstream of pier
a = Pier width (ft.)
L = Pier length (ft)
F
r1
= Froude number
F
r1
= V
1
/(gY
1
)
1/2
Where V
1
= Mean velocity of fow directly upstream of pier
g = acceleration due to gravity (32.2 feet/sec
2
)
lb
ft
= 24.6 16 in 32 lbs per pier
1 ft
12 in
L = 16"
a = 8"
L = 16"
PROTECTING MANUFACTURED HOMES FROM FLOODS AND OTHER HAZARDS
A Mul ti - Hazard Foundati on and I nstal l ati on Gui de
F-9
F EXAMPLE CALCULATIONS
K
1
= Factor for pier nose shape. For square nose
K
2
= Factor for Angle of attack . K
2
= (cosine + (L/a) x sine )
0.65
K
3
= Factor for bed condition/. K
3
= 1.1
K
4
= Factor for armoring by bed material size.
Project parameters:
Flood low = 2 fps
Flood depth = 3 ft
Assume food angle of attack = 0
So that:
K
1
= 1.1 (Table 6.1)
K
2
= [cosine 0
o
+(L/a)x sine 0
0
]
0.65
= [1.00 + (1.33/0.67) x 0]
0.65
= 1.00
K
3
= Factor for bed condition/. K
3
= 1.1 (Table 6.3)
K
4
= Factor for armoring by bed material size. K
4
= 1.0 unarmored
F
r1
= V
1
/(gY
1
)
1/2
= 2/[32.2 x 3]
1/2
=2/9.84 = 0.203
And
Y
s
= (2) x (1.1) x (1.0) x (1.1) x (1.0) x (0.67/2)
0.65
x (0.203)
0.43
Y
1
Y
s
= (2.42) x (0.491) x (.504) = 0.6
Y
1
Y
s
= (0.6) x (Y
1
) = (0.6)x(3) = 1.8 ft
Scour protection or increased footing embedment required.
F-10 PROTECTING MANUFACTURED HOMES FROM FLOODS AND OTHER HAZARDS
A Mul ti - Hazard Foundati on and I nstal l ati on Gui de
EXAMPLE CALCULATIONS F
Step 2: Select a Design Methodology and Assess Load
Combinations and Failure Modes
Figure F-3 illustrates the loads applied to the manufactured home. Table F-4 lists the nomencla-
ture of the applied loads shown in Figure F-3.
Table F-4. Load Nomenclature
Nomenclature Load Description
D dead load
L live load
L
R
roof live load
R
H
horizontal reaction
R
LV
leeward vertical reaction
R
WV
windward vertical reaction
S
B
balanced snow load
W
H
horizontal wall wind pressure
W
RH
roof horizontal wind pressure
Figure F-3. Loading on a
manufactured home.
PROTECTING MANUFACTURED HOMES FROM FLOODS AND OTHER HAZARDS
A Mul ti - Hazard Foundati on and I nstal l ati on Gui de
F-11
F EXAMPLE CALCULATIONS
Nomenclature Load Description
W
LRV
leeward roof vertical wind pressure
W
WRV
windward roof vertical wind pressure
Note that snow load governs over roof live load and wind downward load, and wind lateral
load governs over earthquake lateral load. Load combinations for non-governing cases are not
shown.
For the purposes of these calculations, the worst case wind load is taken to be perpendicular to
the roof ridge for all failure modes. Wind in the direction parallel to the roof ridge may pro-
duce greater loads for certain failure modes.
Uplift and Downward Failure Mode
Uplift failure is a vertical force phenomenon. The loads that act vertically are wind, snow, dead,
and live loads. Table F-5 summarizes the loads that inuence uplift and downward failure mode.
Table F-6 assesses uplift and downward failure load combinations. Note that uplift is based on
MWFRS pressures for the global foundation design. Design of the connections to the founda-
tion may require components and cladding (C&C) pressures to be used.
Table F-5. Vertical Load Values
Load
Type
Total load acting on the structure and, therefore, must be supported by the foundation
D D = [dead load per square foot][width of the manufactured home]
D = [20 psf][16 ft]
D = 320 lbs per linear ft of manufactured home length
L L = [live load per square foot][width of the manufactured home]
L = [40 psf][16 ft]
L = 640 lbs per linear ft of manufactured home length
L
r
L
r
= [roof live load per square foot][width of the manufactured home]
L
r
= [17 psf][18 ft]
L
r
= 306 lbs per linear ft of manufactured home length
Table F-4. Load Nomenclature (continued)
F-12 PROTECTING MANUFACTURED HOMES FROM FLOODS AND OTHER HAZARDS
A Mul ti - Hazard Foundati on and I nstal l ati on Gui de
EXAMPLE CALCULATIONS F
Load
Type
Total load acting on the structure and, therefore, must be supported by the foundation
W Maximum wind uplift loads occur for winds parallel to the roof ridge at the windward end.
W = W
WRV
+W
LRV
= [(vertical component roof wind pressures)(area roof)]/manufactured home length
W = [-17.6 psf][(9 ft)(15 ft)(2)] 0 ft to 15 ft +
[-9.8 psf][(9 ft)(15 ft)(2)] 15 ft to 30 ft +
[-5.9 psf][(9 ft)(30 ft)(2)] 30 ft to 60 ft
W = -10,584 lbs/60 ft = -176 lbs per linear foot of manufactured home length (average)
In this case, vertical uplift loads are low and so this simplication is acceptable. However, to
account for the unbalanced uplift if wind loads were higher, either overturning in this direction
would need to be considered, or the windward uplifts conservatively made symmetrical about the
middle.
Maximum wind downward loads occur for wind perpendicular to the roof ridge; however, they are
much less than, and do not govern over, roof live or snow loads.
S S = [snow pressure][horizontal projected roof area]
S = [20 psf][(9 ft)]SW + [20 psf][(9 ft)]SL
S = 360 lbs per linear ft of manufactured home length
Table F-6. Vertical Failure Mode ASD Load Combinations
Load Combinations
4
D + 0.75L + 0.75S
320 lbs + 0.75(640 lbs) + 0.75(360 lbs) = 1,070 lbs per linear ft of manufactured home length
7
0.6D + W
0.6(320 lbs) - 176 lbs = 16 lbs per linear ft of manufactured home length acting downward
Note that, for load combination 7, the 0.6 load factor should be applied to the dead load that
would actually be present over the whole structure. Additions to the dead load tabulation such
as mechanical and miscellaneous or shingles should not be included in this value as they may
not be present in all areas or during a high-wind event and their inclusion would not be con-
servative.
Sliding or Shearing Failure Mode
Sliding failure is a lateral force phenomenon. The loads that act laterally are wind and ood
loads. Table F-7 summarizes the lateral loads and their values. Maximum lateral wind loads oc-
cur when the wind is perpendicular to the roof ridge. Note that lateral wind loads act on the
overall structure (i.e., foundation), whereas ood loads act on the individual piers. Table F-8
gives the load combinations for sliding failure. Once the number of piers is dened, the hy-
drodynamic forces on these piers are to be added to load combination 4, and the foundation
design will have to be checked to make sure it can resist the added hydrodynamic loads.
Table F-5. Vertical Load Values (continued)
PROTECTING MANUFACTURED HOMES FROM FLOODS AND OTHER HAZARDS
A Mul ti - Hazard Foundati on and I nstal l ati on Gui de
F-13
F EXAMPLE CALCULATIONS
Table F-7. Lateral Load Values
Load
Type
Total load acting on the structure and, therefore, must be supported by the foundation
W Maximum lateral wind loads occur for winds