Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Bodrum

Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 8

Calculate And Selection Result

1.Project Parameter
Project Name: New Project
Nation: China
Location: GuangZhou
Address:
Name:
Job Title:
Outdoor barometric pressure in summer(Pa): 98503
Outdoor mean air velocity in summer(m/s): 0.7
Summer OutDoor Dry-bulb: 35
Summer OutDoor Wet-bulb: 24
Winter OutDoor Dry-bulb: 7
Winter OutDoor Wet-bulb: 6
2.Material List
Model Qty Description
YDS-900WC35C 1 Modular digital scroll
YDS-140KC15IA 6 Four-way Cassette
YDS-56HC15IA 1 Wall-mount (EXV Integrated)
YDSB/FQ04 1 Distributor
YDSB/FQ03 3 Distributor
YDSB/FQ02 2 Distributor
YDSB/FN02 1 Distributor
34.9 4.0m Copper Pipe
19.1 3.0m Copper Pipe
28.6 9.0m Copper Pipe
15.9 25.0m Copper Pipe
12.7 9.0m Copper Pipe
22.2 6.0m Copper Pipe
9.53 24.0m Copper Pipe
3.GROUP1
3.1 Material List
Model Qty Description
YDS-900WC35C 1 Modular digital scroll
YDS-140KC15IA 6 Four-way Cassette
YDS-56HC15IA 1 Wall-mount (EXV Integrated)
YDSB/FQ04 1 Distributor
YDSB/FQ03 3 Distributor
YDSB/FQ02 2 Distributor
YDSB/FN02 1 Distributor
34.9 4.00m Copper Pipe
19.1 3.00m Copper Pipe
28.6 9.00m Copper Pipe
15.9 25.00m Copper Pipe
12.7 9.00m Copper Pipe
22.2 6.00m Copper Pipe
9.53 24.00m Copper Pipe
3.2 Specifications
Room Description Model RTC kW ATC kW RTH kW ATH kW Rated Air
Flow m^3/h
Sound dBA Dimension
mm
Weight kg Static
Pressure Pa
IU-1 Indoor Unit YDS-140KC1
5IA
14 13.942 15 14.578 1802 44 840*310*8
40
36 N/A
IU-2 Indoor Unit YDS-140KC1
5IA
14 13.957 15 14.621 1802 44 840*310*8
40
36 N/A
IU-3 Indoor Unit YDS-140KC1
5IA
14 13.942 15 14.578 1802 44 840*310*8
40
36 N/A
IU-4 Indoor Unit YDS-140KC1
5IA
14 13.942 15 14.578 1802 44 840*310*8
40
36 N/A
IU-5 Indoor Unit YDS-140KC1
5IA
14 13.957 15 14.621 1802 44 840*310*8
40
36 N/A
IU-6 Indoor Unit YDS-140KC1
5IA
14 13.927 15 14.534 1802 44 840*310*8
40
36 N/A
IU-7 Indoor Unit YDS-56HC1
5IA
5.6 5.571 6.3 6.104 800 41 1080*315*
216
14 N/A
Outdoor Outdoor
Unit
YDS-900WC
35C
90 89.6 94 93.6 N/A 60 1380*1630
*830
1380*1630
*830

764 N/A
RTC: Required total cooling capacity
ATC: Available total cooling capacity
RTH: Required total heating capacity
ATH: Available total heating capacity
3.3 Pipe And Refrigerant Distributors
IU quantity 7/32
Combination Ratio 99.56%
Additional Refrigerant 3.860kg
Total pipe length 42m/500m
Furthest Actual 15m/150m
Furthest equivalent 17m/175m
Drop height between IU and IU 0m/15m
After first branch length 13.5m/40m
Drop height between IU and OU 0m/70m
Available Capacity Cooling 89.6 kW
Available Capacity Heating 93.6 kW


Currently our units that according to our literature are being shipped with a pre-charge of
refrigerant of 12kgs or above, are actually being shipped without refrigerant due to international
regulations in handling hazardous materials.So in order to calculate the quantity of refrigerant
needed you will need to add the pre-charge shown in the literature.

No Length Gas Pipe Liquid Pipe
(1) 3 34.9 19.1
(2) 3 28.6 15.9
(3) 3 28.6 12.7
(4) 3 28.6 12.7
(5) 3 22.2 12.7
(6) 3 15.9 9.53
(7) 3 15.9 9.53
(8) 3 15.9 9.53
(9) 3 15.9 9.53
(10) 3 15.9 9.53
(11) 3 22.2 9.53
(12) 3 15.9 9.53
(13) 3 15.9 9.53

No Load kW Model
(1) 89.6 YDSB/FQ04
(2) 47.6 YDSB/FQ03
(3) 33.6 YDSB/FQ03
(4) 42 YDSB/FQ03
(5) 28 YDSB/FQ02
(6) 19.6 YDSB/FQ02
3.4 Drawing

YDS-900WC35C
JCI Commercial A/C 50Hz R410A
(1)
YDSB/FQ04
(2)
YDSB/FQ03
(3)
YDSB/FQ03
(4)
YDSB/FQ03
(5)
YDSB/FQ02
IU-1
YDS-140KC15IA
13.942 kW
IU-2
YDS-140KC15IA
13.957 kW
IU-3
YDS-140KC15IA
13.942 kW
IU-4
YDS-140KC15IA
13.942 kW
IU-5
YDS-140KC15IA
13.957 kW
(6)
YDSB/FQ02
IU-6
YDS-140KC15IA
13.927 kW
IU-7
YDS-56HC15IA
5.571 kW
34.9,19.1 28.6,15.9
28.6,12.7
28.6,12.7
15.9,9.53
22.2,9.53
15.9,9.53
22.2,12.7
15.9,9.53
15.9,9.53
15.9,9.53
15.9,9.53
15.9,9.53
3.5 Optional controller


OU-1
P Q E H1 H2 E P Q E H1 H2 E
IU-1
P Q E
IU-2
P Q E
IU-3
P Q E
IU-4
P Q E
IU-5
P Q E
IU-6
P Q E
IU-7
P Q E
0.75mm2*3
0.75mm2*3 0.75mm2*3
0.75mm2*3
0.75mm2*3 0.75mm2*3
0.75mm2*3

You might also like