Design Calculation Sheet: PEARL QATAR Facility MGT (Q07048) A.B N.E

Download as xls, pdf, or txt
Download as xls, pdf, or txt
You are on page 1of 1

Design calculation sheet

Project no: Date:27/12/2007 Sheet no.: 1 1 Computed by:


Subject: AIR HANDLING UNIT - PRESSURE DROP Checked by:
Approved by:
1 2
WH-AHU-02 WH-AHU-01
Ware House Ware House
Ware House Ware House
First Ground
Accessories Static 50.000 1.432
Cooling Coil 50.000 1.036
Sub total ( Internal) 100.000 2.468
Supply Duct work
Duct Run (m) 44.000 80
Friction Pa\m 20.000 0.065
Return Duct work
Duct Run (m) 25.000 65
Friction Pa\m 20.000 0.099
Duct Work 1380.000 0.171
Fittings 15% 207.000 0.026
Volume Damper 25.000 0.100
Duct Heater (if any) 0.000 0.000
Fire Damper 25.000 0.100
Terminal Box (if any) 75.000 0.000
Air Outlet 25.000 0.100
Fresh Air Louver (if any) 0.000 0.000
30% Safety 483.600 0.089
Sub total ( External) 2220.600 0.585
TOTAL AIR SIDE TOTAL +10%safety 2552.660 3.358
EXTERNAL (pa) 2220.600 146
TOTAL (pa) 2553 836
System served
PEARL QATAR Facility Mgt(Q07048)
INTERNAL STATIC
PRESSURE. AIR
SIDE (in Pa)
EXTERNAL STATIC
PRESSURE. AIR
SIDE (in Pa)
Column number
Location
Floor Served
NOTE:
Accessories Static consists of:1-Flat filter
2-Bag filter 3-Mixing Box Section 4-Fan
Section
A.B
N.E
Summary
Tag number
3.5KW-94% 11.6KW-77.4%