Friction Losses Estimation For Level 1 Office Desmoke Fan
Friction Losses Estimation For Level 1 Office Desmoke Fan
Friction Losses Estimation For Level 1 Office Desmoke Fan
Path
Q(cfm)
A(inches) B(inches) DE(equilvalent diameter,inches)
a-b
3,820
24
14
19.86
b-c
7,640
28
18
24.39
c-d
15,280
30
28
31.68
d-e
22,920
38
30
36.85
e-f
30,560
40
36
41.47
f-g
38,200
44
40
45.85
g-h
19,100
42
24
34.37
DP(inches h20/100ft)
0.21
0.28
0.28
0.29
0.27
0.25
0.29
Duct Length(m)
5.70
10.20
12.60
7.80
10.20
21.00
19.20
VCD / Damper
Elbow / Fitting
Ducting Transformation
Intake / Suction Pressure
Total friction losses
Safety factor
Selected Fan Static Pressure
duct velocity(fpm)
1,637.14
2,182.86
2,619.43
2,895.16
3,056.00
3,125.45
2,728.57
0.04
0.09
0.12
0.07
0.09
0.17
0.18
0.500
0.100
0.500
0.500
25%
2.37
0.59
2.97
2 elbow
inches h20
inches h20
DP(inches h20/100ft)
0.00
0.17
0.16
0.28
0.24
0.24
0.01
Duct Length(m)
1.80
11.40
9.10
8.50
13.00
34.00
1.00
VCD / Damper
Elbow / Fitting
Ducting Transformation
Intake / Suction Pressure
Total friction losses
Safety factor
Selected Fan Static Pressure
duct velocity(fpm)
471.38
2,154.86
2,514.00
3,480.92
3,447.77
3,447.77
942.75
0.00
0.06
0.05
0.08
0.10
0.27
0.00
0.500
0.150
0.500
0.500
35%
2.21
0.77
2.99
(3 elbow)
inches h20
inches h20
DP(inches h20/100ft)
0.34
0.27
0.30
0.30
0.23
Duct Length(m)
35.90
15.60
14.40
13.20
15.80
VCD / Damper
Elbow / Fitting
Ducting Transformation
Intake / Suction Pressure
0.500
0.080
0.700
0.500
Elbow Losses
Qty
Q(cfm)
1
4,800
1
31,300
A(inches)
36
44
B(inches)
10
34
DE(equilvalent diameter,inches)
19.77
42.19
DP(inches h20/100ft)
0.34
0.26
duct velocity(fpm)
1,920.00
2,310.00
2,745.00
3,006.00
2,890.91
0.40
0.14
0.14
0.13
0.12
10%
Equivalen Length
4.50
4.50
2 elbow
5 transformation
2.71
inches h20
0.27
2.98
inches h20
24
29
24
30
34
DE(equilvalent diameter,inches)
25.84
43.26
33.60
37.77
42.19
DP(inches h20/100ft)
0.105596771651
0.207
0.74
0.60
0.26
Duct Length(m)
VCD / Damper
Elbow / Fitting
Ducting Transformation
Intake / Suction Pressure
0.500
0.080
0.700
0.500
Total friction losses
Safety factor
2.73
0.27
3.01
10%
Selected Fan Static Pressure
Elbow Losses
Path
Q(cfm)
a-b
e-f
A(inches)
4,800
31,300
Transformation losses
Path
angle(degree)
b-c
16
Q(CFM)
5,297
B(inches)
36
44
v2(fpm)
10
34
v1(fpm)
2,285
1,714
DP(in H20/100ft)
0.10000000
DE(equilvalent diameter,inches)
26.1236644
DE(equilvalent diameter,inches)
19.77
42.19
DP(inches h20/100ft)
0.34
0.26
1.00
A(inches)
Equivalen Length(ft)
7.00
24.00
2 elbow
5 transformation
inches h20
inches h20
0.14
B(inches)
2.00
4.00
6.00
8.00
10.00
12.00
14.00
16.00
18.00
20.00
22.00
24.00
26.00
28.00
30.00
32.00
34.00
duct velocity(fpm)
1,364.81
2,633.36
4,414.35
4,326.48
3,012.83
0.12
0.11
0.32
0.26
0.14
DE(equilvalent diameter,inches)
DP
19.70
A
0.412
18.02
area
304.86
324.72