Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Guide To Air Change Effectiveness

Download as pdf or txt
Download as pdf or txt
You are on page 1of 7

FORUM

Guide to air change effectiveness


Kemal Gungor, M.AIRAH, of Norman Disney & Young

Abstract
Green Star rating under the Green Building Council of Australia is increasingly considered and demanded by the building developers.
One of the Green Star rating categories is air change effectiveness (ACE). Two points are awarded if ventilation systems are designed
to achieve ACE of at least 95 % of the net lettable area (NLA) when measured in accordance with ASHRAE 129-1997. During the design
stage this can only be demonstrated through computational fluid dynamics (CFD) modelling of the air conditioning system other
than the nominated DTS criteria. This study summaries the factors affecting ACE and provides design guidelines to assist in achieving
compliance with the GBCA ACE requirements. The effect of return air plenum on ACE is discussed.
Keywords:Air change effectiveness (ACE), Green Building Council of Australia (GBCA),
computational fluid Dynamics (CFD), effect of return air plenum

Introduction
Air change effectiveness (ACE) is a description of an air
distribution systems ability to deliver ventilation air to a
building, zone or space. One common definition of ACE is
the ratio of a nominal time constant to a mean age of air. The
nominal time constant is calculated as a ratio of the domain
volume (m3) to the supply air volume to that domain (m3/s).
ACE can sometimes be confused with ventilation effectiveness.
Ventilation effectiveness is a description of an air distribution
systems ability to remove internally generated pollutants from
a zone.
ACE simply indicates how well the air is distributed within
the breathing height. ACE = 1 indicates that the air distribution
system delivers air equivalent to that of a system with perfectly
mixed air in the space. An ACE value less than 1 indicates that
the air distribution within the zone is less than perfect mixing.
A short-circuiting flow pattern between the air-supply diffusers
and return grilles increases the room-air age and causes ACE
to be less than unity. Preferentially supplying the air to the
breathing zone will cause the ACE to be greater than unity.

Figure 2: Entrainment flow within a room (ASHRAE)

Figure 3: Section of the room lay-out for the flow pattern study [2].

Providing more fresh air than required by AS 1668.2


does not guarantee GBCA [1], Green Star ACE compliance.
In order to achieve better ACE and comply with GBCA
requirements, air distribution systems need to deliver the
supply air to the breathing zone. Air movement within the
space directly affects the occupant comfort, indoor air quality
and ACE. Displacement flow and entrainment flow are the
two distinct flow patterns commonly used to characterise air
movements in buildings.
Figure 1: Displacement flow within a space

32

Eco l i b r i u m M A R C H 2 0 1 3

Displacement flow is characterised with the movement


of air within a space like a piston motion. (Figure 1). In an

FORUM

flow pattern and ACE are dependent on a large number


of variables. Some of the variables are listed below:
Room geometry;
Location of supply-air terminals within the room;
Flow rates and flow characteristics of supply-air terminals;
Temperature of supply air;
Location of return-air terminals or other pathways within the
room;
Figure 4: Flow pattern of the room shown in Figure 3
when air change rate is 19.5 ACH [2].

ideal displacement flow, the room air does not mix. A typical
entrainment flow is shown in Figure 2. Ceiling-based air supply
and return air grilles generally exhibit an entrainment flow.
Displacement flow has a higher potential to achieve a better
ACE value than the entrainment flow.
Air distribution systems that show entrainment flow
pattern might cause short circuiting. Lingying Zhao et al [2]
conducted an experimental study to determine the flow pattern
in a room. Figures 3 and 4 show the experimental room lay-out
and one of the flow patterns (velocity vector map).
Lingying Zhao et al concluded that The different ventilation
modes [different inlet velocity, KG] do create quite different airflow
patterns. Some parts of the patterns have conflicts with previous
measurements, and some parts agree very well with flow principles
revealed by previous researchers. Airflow velocities in the occupant
zones vary a lot for the tested four ventilation modes.

Internal heat gains and their distribution within the room;


Physical obstructions to air movement, including walls,
columns, and workstation surfaces;
Boundary surface temperatures and heat fluxes;
Stack effect; and
Wind pressure/infiltration air.
Small changes in these parameters can have a pronounced
effect on the assessment outcome, as they can result in significant
variations to the room air flow patterns around the measurement
plane or the room as a whole. Figures 5a and 5b demonstrate the
effect of changing supply-air flow direction of a single air-supply
terminal. Figure 5a shows the original design. Air is directed
towards the facade, and about 4% of NLA fails to comply with
GBCA ACE requirements. Figure 5b shows that all the floor
area complies after only one diffuser flow direction is reversed
(i.e. flow direction is from perimeter zone to centre zone).

William J. Fisk et al [3] measured the ACE in 26 laboratory


experiments. Ceiling-mounted induction-type supply-air
diffusers and return grilles were used with a VAV ventilation
system. They stated that In 15 tests with heated supply air
supplied at relatively low volumetric flow rates, 100% outside air,
and three typical supply diffusers (including a very basic unit),
the ACE ranged from 0.69 to 0.89. In four previous laboratory
tests with heating and 100% outside air, the ACE ranged from
approximately 0.7 to 0.9 (Fisk and Faulkner 1992). Two prior
ACE measurements by Offermann (1988) with heating and 33%
outside air yielded values of 0.66 and 0.73.
Poorly designed, installed, or operated systems in particular,
ceiling based systems in heating mode can exhibit shortcircuiting. The studies cited show the need for properly designed,
installed and operated air-distribution systems.
Accurate prediction of air-flow patterns within rooms and through
buildings becomes more and more important for the HVAC system
designs. For maximum energy efficiency, high thermal comfort,
and optimum indoor air quality and ACE, the details of the flow
pattern must be known during the design phase of a building.
CFD simulation is the only way to determine the flow pattern
and demonstrate the GBCAs Green Star compliance during the
design phase.

Variables that can


affect the flow patterns
The bases for air movement, both inside and outside of
buildings, are temperature and pressure differences. ACE is
dependent on the air-flow pattern. In a building environment,

Figure 5a: Original design

Figure 5b: One diffuser flow


direction was reversed.

Anticipating the impact of any change is not always possible.


Field measurement is the only objective method to determine
the effect of change on the flow pattern and ACE in built
environments. During the design stage, a CFD simulation
can be successfully used to identify and establish the flow
pattern for a building.

CFD simulation
When a CFD simulation is used to determine the flow pattern,
new parameters in addition to the ones listed above can affect
the results.
First and most important of the new parameters is the CFD
software package chosen for the job. Not every CFD software
package is suitable for GBCA Green Star ACE simulation. A CFD
package should be capable of modelling from momentum source
scale to at least building scale, if it is used for the ACE simulation.
ma r ch 2 0 1 3 Eco l i b r i u m

33

FORUM

Meshing size and quality is another parameter that has an


impact on the results. The primary role of a mesh is to enable an
accurate simulation to be performed on a computer. As such, it is
appropriate to consider mesh quality in terms of error analyses,
which is not examined in this study. A description of meshquality metrics can be found in Knupp [7] and Kwok and Chen
[8]. A comprehensive background could be found in Perez [9]
Supply-air terminal flow characteristics need to be known for
a successful simulation. Figure 6 shows typical information
provided by the supply-air terminal manufacturer.

Design issues influencing air


change effectiveness outcomes
As mentioned, there are many parameters affecting ACE, and
any small variation of these parameters can potentially alter the
flow pattern, resulting in significant change to the assessment
results. (Figure 5). In a typical ACE simulation, the CFD model
would have up to six to seven million, if not more, meshing
nodes; the results of one meshing node calculation would be the
input of adjoining nodes.
Due to this large number of interactions, anticipating the impact
of any change to boundary conditions is not always possible.
Therefore the discussion presented here should be considered as
guidance only. Since all the designs are unique to each project,
a CFD analysis is the only objective method to determine if a
design can achieve a GBCA ACE compliance other than the
nominated DTS criteria.

Which ventilation
system achieves better ACE?
Selection of the ventilation/AC system can have a profound effect
on ACE results. Brief information about the ACE performance
potential of ventilation and air conditioning systems is below.
Simulations presented in this study have been carried out with
the ANSYS Airpak software package using the mechanical design
specifications and drawings for that project in cooling mode.
Figure 6: Supply-air terminal flow characteristics needed
for the CFD model calibration.

This type of information is the least amount of information


required for a CFD supply air terminal calibration. Calibration
of the supply air terminals is imperative for a realistic CFD
simulation. Figure 7 shows the velocity contours after the CFD
calibration process of the described supply-air terminal.

CAV+ chilled beam


Chilled beam systems (active and passive) offer some energysaving advantages, and could be an attractive solution when ESD
is considered. There are many shapes and sizes of both types
of chilled beams, from rectilinear slots to 600mm squares and
rectangles. There are also varieties of both passive and active
chilled beams that incorporate other elements for example,
lights, sprinklers, speakers, space-occupancy sensors and smoke
detectors in a multi-service beam configuration. These can be
surface-mounted, suspended or recessed in a lay-in ceiling.
All of the chilled-beam arrangements have a common feature:
they all create additional vertical air movements within the space
they are installed. A typical air-flow pattern created by an active
chilled bean is shown in Figure 8.
This additional vertical air movements will provide better air
mixtures within the space compared to a VAV system. CAV+
chilled beam systems usually achieve compliance

Figure 7:Calibrated supply-air terminals velocity contours.


(Only scales are different)

34

Eco l i b r i u m M A R C H 2 0 1 3

Figure 8: Typical air movements caused by a chilled bean system.

FORUM

Figure 9: Compliance area of passive chilled beam system


(NDY Melbourne office first floor)

with the GBCA ACE requirements. The NDY Melbourne


headquarters has a passive chilled beam system. Figure 9 shows
the mean age of air contours for the office first floor. The blue
area indicates compliance. Images given in Figure 5 also have
passive chilled beams.

Figure 11: Mean age of air contours for the ANZ project
CFD model 4. (Compliance achieved)

flow pattern within a room. GBCA ACE assessment requires that


all the simulation be performed at the lowest turn-down ratios.
A typical office VAV system would have supply and return-air
terminals located on the ceiling, and there is a wide variety of air
terminals that could be considered. Figure 12 to 16 shows flow
characteristics of some supply-air terminals.

Displacement ventilation (UFAD)


The principle of displacement ventilation is that cooled air is
supplied with low momentum in the lower part of a room. The
cold air displaces the contaminated air from the occupied zone
upwards in a room. Buoyancy forces (temperature differences)
control the air movement in the room, as the free convection
around heat sources (occupants, equipments and lightning)
creates vertical air movements. In the same way, a cold window
or a cold wall will result in a downward convective flow.

Figure 12: Swirl diffuser flow pattern [4].

Figure 10: Typical air movements caused


by displacement ventilation system.

A very important characteristic of displacement ventilation


is the formation of stratified layers of air. This characteristic
provides a substantial advantage in order to achieve GBCA
ACE compliance. It is expected that many of the underfloor
distribution systems would achieve compliance with GBCA
ACE requirements by CFD simulation.

Variable air volume (VAV) systems


In variable air volume (VAV) systems, changes in the room heatload are met by controlling the volume of air supply to the room
without changing the supply temperature until the minimum
permissible air supply is reached. On the other hand, seasonal
control of the supply-air temperature takes place as a function of
the outdoor temperature. A VAV system can operate over a wide
range of air-flow rates, and this will have a flow-on effect on the
36

Eco l i b r i u m M A R C H 2 0 1 3

Figure 13: Circular, horizontal and cross-flow pattern [4].

ACE assessment results are dependent on the selection and


location of supply and return-air terminals. Due to the high
induction air motion and strong mixing characteristics, swirl
diffusers are an attractive option for many designers and
architects. Swirl diffusers produce relatively poor ACE results
when used with perforated ceilings or light troffers/return
plenum slot diffusers. Figure 17 and 18 show open-plan office
ACE simulation results. The building has a VAV system with
swirl diffuser and light troffers RA arrangements, and also some
perforated ceiling at the buildings break-up area.

FORUM

Figure 17: Mean age of air contours of an open-plan office.

Figure 14: Downward projection characteristics


from ceiling diffusers [4].

Figure 15: Downward laminar flow diffusion pattern


and hemispherical flow diffusion pattern [4].

Figure 18: Open-plan complied area indicated with blue;


velocity contours at plenum level.

Figure 19 shows the ACE assessment results of another


open-plan office. This building also has a VAV system. Supply
air, again, delivered to the zone via swirl diffusers, and light
troffers and plenum used as the return air path. Most of the
office area failed to achieve 0.95 ACE.
As figures 1719 indicate, swirl diffuser air supply and perforated
ceiling or light troffers/plenum slot return-air arrangements is likely
to fail to comply with GBCA ACE requirements when the ACE is
calculated in accordance with the ASHRAE F27-2005 methodology.
Use of return-air grilles achieves a better ACE then perforated
ceiling or light troffers return-air arrangement, but in many cases it
would still fail to comply with Green Star requirements.

Figure 16: An image from a round adjustable diffuser smoke test.

The design, shown in Figure 19, is modified. When the light


troffers were replaced with regulated return-air grilles and some
of the supply-air flow rates are finetuned (~1.5% increased)
then compliance is achieved. Figure 20 shows the final ACE
simulation results based on ASHRAE F27-2005 methodology.

ma r ch 2 0 1 3 Eco l i b r i u m

37

FORUM

is the inverse of the space air exchange rate. Definition of air


exchange rate is given by below equation (ASHRAE, F27-2005, Eq.2)
V
I = 
(3)
Q
Where
Q = volumetric flow rate of air into space, m3/s
V = interior volume of space, m3
So the time constant can be written as follows
(4)
= V
Q
Based on these definitions, return-air plenum volume should not
be taken in to account when the ACE is calculated.

Figure 19: Open-plan office ACE assessment.


Blue indicates ACE0.95. (Original design)

GBCA [6] ACE compliance criteria refers to ASHRAE Standard


129. This standard describes a method for measuring ACE of
mechanically ventilated spaces and buildings. The standard gives
the below equation for the time constant.
m (Qex,mAex,m)
N
=
(4)
m Qex,m
Where
N

is the nominal time constant

m is an identification number unique for each exhaust


airstream
N
is the rate of airflow in exhaust airstream m
Aex,m is the age air in exhaust airstream m
The symbol m indicates a summation for all m exhaust
airstreams.

Figure 20: Modified design achieves GBCA ACE compliance.


(East Bld Lev 4).

Use of balancing damper with strategically located return air


grilles further improves the ACE and compliance with green star
is achievable.
In many cases, this compliance comes at a significant modelling
effort which requires trial and error with the adjustment of flow
rates and location of diffusers/grilles.

Effect of return-air plenum


Does the return-air plenum affect the ACE or should the return-air
plenum be included in the ACE calculations? The answer depends
on the interpretation of the terminology. ASHRAE [5] states that
One common definition of air change effectiveness is the ratio
of a time constant to an age of air, and below equations are given:

I = Q
(1)
age
and local air change effectiveness ,I,L,
N
(2)
I,N =
Qage
where is time constant and Qage is age of air. In AHRAE[5],
the time constant was defined as follows The space time constant
38

Eco l i b r i u m M A R C H 2 0 1 3

Since the standard is about measuring the ACE, and some


of the flow-rate and age-of-air measurements need to be taken
at the exhaust location, its important to consider the time taken
air leaving a room to reaching the exhaust point.
In the standard, indoor air volume is defined as, indoor air
volume: the entire air volume of space or building in which the
ventilation air is distributed including ductwork and plenums.
The volume of indoor furnishings, equipment, and occupants must
be subtracted from the gross indoor volume that is based on interior
dimensions of the space or building.
This definition provides a base to take in the plenums volume
in ACE calculations. Using the volume of the plenum in ACE
calculations will increase the time constant and improve the
ACE results.
If a typical office is assumed to have 2700mm floor-to-falseceiling height and 900 mm plenum height, then the time
constant would increase by 20% when the plenum volume is
taken in to calculations of the volume (10% allowance made for
ductwork, etc). This is a significant increase and may change the
GBCA ACE assessment outcomes.
ACE calculations were repeated for the same building featured
in Figures 17 and 18 but this time the volume of the returnair plenum was taken into consideration in the time constant
calculations. Figure 21 shows the compliance area when plenum
volume is included in the calculations.

FORUM

REFERENCES
1 Green Building Council of Australia,
GBCA, www.gbca.org.au
2 Lingying Zhao, Yuanhui Zhang, Xinlei Wang, G. L.
Riskowski, L. L. Christianson, MEASUREMENT OF
AIRFLOW PATTERNS IN VENTILATED SPACES USING
PARTICLE IMAGE VELOCIMETRY, An ASAE Meeting
Presentation, Paper No. 994156

Figure 21: Compliance area for the same simulation shown in


Figure 18. (Time constant includes plenum volume)

As some experimental studies [2, 3] highlight, ACE values of


0.95 appear difficult to achieve when calculated in accordance
with ASHRAE F27-2005 methodology. However, if the return-air
plenum volume is considered then there is a potential risk of that
even a poorly design ventilations might comply with the GBCA.
This ambiguity needs to be clarified in order to achieve more
objective comparisons and assessments.

Summary and conclusion


CFD simulation is sensitive to a large number of input variables,
minor changes to which can significantly affect the airflow
pattern, the mean age of air and consequently ACE. VAV
systems have the highest risk factor when compared to the
other ventilation systems. In many cases it is possible, though
requiring significant trial and error with the adjustment of flow
rates, to achieve a Green Star-compliant solution or very close
to (in accordance with ASHRAE F27-2005 methodology).
The following are some general design considerations that are
generally expected to improve the ACE outcome for a project.

3 William J. Fisk, David Faulkner, Douglas Sullivan, and Fred


Bauman, Air Change Effectiveness and Pollutant Removal
Efficiency During Adverse Mixing Conditions Indoor Air 7:
55-63, 1997, also LBNL-40292
4 Titus, Engineering Guidelines B Grilles & Diffusers,
available at www.titus-hvac.com
5 ASHRAE Fundamentals F27 SI, 2005
6 GBCA, Technical Manual, Green Star Office Design
& as Built Version 3, 2008
7 Patrick M. Knupp, Remarks on Mesh Quality,
45th AIAA Aerospace Sciences Meeting and Exhibit, 7-10
January, 2007, Reno, NV
8 Wa Kwok1, Zhijian Chen, A simple and effective mesh
quality metric for hexahedral and wedge elements
Proceedings of the 9th International Meshing
Roundtable,New Orleans LA, pp.325-333, 2000
9 Rafael A. Perez, Uncertainty Analysis of Computational
Fluid Dynamics Via Polynomial Chaos Polynomial Chaos,
Dissertation submitted to the faculty of the Virginia
Polytechnic Institute and State University in partial
fulfillment of the requirements for the degree of Doctor
of Philosophy In Aerospace Engineering, September 2,
2008 Blacksburg, Virginia

Increasing the supply of fresh air may not necessarily


improve the ACE.
Ventilation systems that can preferentially deliver
the air to the breathing zone will achieve better ACE.
Personal ventilation systems, task-air ventilation,
displacement ventilation and under-floor ventilation
will generally provides best ACE results.
Chilled beam systems create additional vertical air
circulation, which improves ACE and in most cases
complies with GBCA ACE requirements.
The use of return-air light slots significantly impairs
the achievement of a good ACE outcome when the supply-air
terminals are also located at ceiling level.
The use of discrete return-air grilles provides a better
solution compared to perforated ceiling/air-handling
luminaries, and this can be further improved by regulating
the return-air flow through each with a balancing damper.
The location of return-air grilles has more impact
on ACE than the number of return-air grilles.
It is believed that the GBCA assessment would be performed
in accordance with ASHRAE F27-2005 methodology.

About the author


Kemal Gungor (PhD), M.AIRAH, is an ESD consultant
at Norman Disney & Youngs Melbourne office.
His expertise lies in heat transfer, thermodynamic
analysis, design and computer modelling of thermal
systems (i.e. energy modelling, facade analysis). He
is also a specialist in computational fluid dynamics
analysis. These skills are being utilised to search
for, develop and implement ecologically sustainable
design solutions within the building industry.

ma r ch 2 0 1 3 Eco l i b r i u m

39

You might also like