EE454 HW 6
EE454 HW 6
EE454 HW 6
The secondary is
terminated in a load impedance of ZL=30+j40ohms.
a. find the primary driving point impedance, i.e., the input impedance of the transformer-load pair as
seen from the source terminals.
b. If the primary voltage is 120V, find the primary current, secondary current, complex power into
the load, and complex power into the transformer primary.
j :=
ZL := ( 30 + j 40) ohm
Because the transformer is ideal, the driving point impedance is the load impedance reflected to
the primary. Reflecting the load impedance across the transformer means multiplying it by the
square of the turns ratio of the transformer. The wording of the problem infers that the turns ratio
is the reciprocal of the gain.
N := gain
ZLp :=
N = 10
ZL
( N N)
Vin = 120 V
Find the secondary voltage first. It is the primary voltage multiplied by the turns ratio.
Vout := Vin N
Vout = 1.2 kV
Iout = 24 A
( )
Iin = 240 A
( )
Complex power in
( )
Problem 2. Problem 5.4 A single phase transformer has the following ratings: 10kVA, 240/2400V. IN the
open circuit test with rated primary voltage, the primary current is 0.85A and the secondary voltage
is 2400V. A short circuit test is performed as follows: The primary is short circuited and a reduced
secondary voltage is applied. Rated secondary circuit is achieved with a secondary voltage of
121V. Neglect resistance and find Xl, Xm, and n=N2/N1.
Writing down the test data,
V1oc := 240 V
V2oc := 2400 V
Srated
I2sc :=
V2oc
V2sc := 121 V
I1oc := 0.85 A
Srated := 10 kV A
I2sc = 4.167 A
A first set of calculations gives us reasonable estimates of the items that we seek. The ratio of the
open circuit voltages is a good approximation of the turns ratio.
n :=
V2oc
n = 10
V1oc
The leakage reactance is approximately the ratio between short circuit voltage and short circuit
current, assuming that the magnetizing reactance is large enough to be insignificant in the
calculations.
Z2sc :=
V2sc
Z2sc = 29.04
I2sc
The magnetizing reactance is approximately the ratio between open circuit voltage and open circuit
current. This measurement is taken on the low voltage side, according to the problem statement.
V1oc
Xl :=
I1oc
Xl = 282.353
These give reasonable approximations of the items that we seek. A more detailed solution follows:
Using the equivalent circuit model of Figure 5.4,
V1oc
Xl + Xm =
I1oc
V1oc
Xl + Xm
V2sc
V2oc
n Xm
The sum of the leakage and magnetizing reactance is the ratio of the input
voltage to input current under open circuit conditions.
The input voltage divides across the leakage and magnetizing reactances;
the portion reflected from the magnetizing reactance is the output voltage.
n X1 Xm
Xsc =
=
Xl + Xm
I2sc
Looking back into the circuit from the output terminals, the impedance
that appears from the output terminals is reflected parallel combination
of the leakage and magnetizing reactances.
Three equations...let's solve. There are a host of ways to solve. One of the better ones is to
assume one value, work our way through the equations in sequence, and then compare the
result by recalculating the first equation in the sequence. We use new values of the unknowns
as we calculate them. This method is known as Gauss-Seidel iteration. We will take the
equations in inverse order...
Assume n=2400V/240V=10
n := 10
V2sc
Xsc :=
I2sc
Xm
Xsc = 29.04
X1 + Xm
or rearranging,
V2oc
n V1oc
n X1
V2oc
n V1oc
n V2oc
X1 = 0.29 ohm
Xm = 282.063
n :=
V2sc X1 + Xm
I2sc X1 Xm
n = 10.005
n V2oc
V1oc
Xm :=
X1
I1oc
n X1
Substituting,
29.04 ohm
29.04 ohm
X1 = 0.2903 ohm
Xm = 282.06
Xm
X1 + Xm
n :=
V2sc X1 + Xm
n = 10.008
I2sc X1 Xm
We have our answers correct to 4 significant figures. Another iteration doesn't change much,
so we can say that we have converged.
X1 :=
n V2oc
V1oc
Xm :=
X1
I1oc
n :=
X1 = 0.2902 ohm
Xm = 282.06
V2sc X1 + Xm
I2sc X1 Xm
n = 10.009
Problem 3. Prob 5.14 on page 183 of the text. A 1 phase generator is represented by a
Thevenin Equivalnet circuit: 1320V in series with Zs=2 / 84 degrees ohms. A load, ZL = 50 / 60
degrees ohms, is connected across the terminals. Draw per unit diagrams for the following
choice of bases.
a. VB = 1000V, SB = 100 kVA
b. VB = 1320V, SB = 50 kVA
Using the per unit diagrams, do circuit analysis to find the per unit load voltage, current, and
complex power in each case. Convert per unit quantities to actual quantities and show they are
the some in both cases.
part a: V B
1000 . volt
SB
100 . kV . A
VS
1320 . volt
ZS
2 . ( cos( 84 . deg )
ZL
50 . ( cos( 60 . deg )
+
-
V B .V B
2 3
Z B = 10 kg . m . s . A
SB
IB
SB
I B = 100 A
VB
VS
Z Spu
VB
V Spu = 1.32
ZS
Z Lpu
ZB
Z Spu = 0.021
0.199i
ZL
ZB
Z Lpu = 2.5
4.33i
I pu
V Spu
Z Spu
Z Lpu
I pu = 0.124
0.223i
Ipu
I pu = 0.255
angle Re I pu , Im I pu
360 . deg
V Lpu
V Lpu = 1.273
0.02i
VLpu
V Lpu = 1.273
360 . deg
S Spu
S Spu = 0.163
S Lpu
0.294i
V Lpu . I pu
S Lpu = 0.162
S linepu
V Spu
S linepu = 1.356 . 10
0.281i
V Lpu . I pu
3
0.013i
V Lpu . V B
V L = 1273.3 V
VL
I pu . I B
I = 25.5 A
360 . deg
angle Re V L , Im V L
VL = 0.9 deg
SS
S Spu . S B
S S = 16.3
part b: V B
SB
S Lpu . S B
S L = 16.2
S line
28.1i kV . A
S linepu . S B
S line = 0.14
1.29i kV . A
1320 . volt
50 . kV . A
V B .V B
SB
360 . deg
I = 60.9 deg
SL
29.4i kV . A
Z B = 34.85
IB
SB
VB
I B = 37.88 A
VS
Z Spu
VB
ZS
Z Lpu
ZB
Z Spu = 5.999 . 10
V Spu = 1
ZL
ZB
1.243i
I pu
V Spu
Z Spu
I pu = 0.327
Z Lpu
0.587i
Ipu
I pu = 0.672
360 . deg
angle Re I pu , Im I pu
I pu . Z Lpu
V Lpu = 0.965
0.015i
V Lpu = 0.965
VLpu
360 . deg
S Spu
V Spu . I pu
S Spu = 0.327
S Lpu
0.587i
V Lpu . I pu
S Lpu = 0.324
S linepu
V Spu
S linepu = 2.712 . 10
0.562i
V Lpu . I pu
3
0.026i
V Lpu . V B
V L = 1273.3 V
VL
I pu . I B
I = 25.5 A
angle Re V L , Im V L
360 . deg
VL = 0.9 deg
SS
S Spu . S B
S S = 16.3
29.4i kV . A
360 . deg
I = 60.9 deg
SL
S Lpu . S B
S L = 16.2
S line
28.1i kV . A
S linepu . S B
S line = 0.14
1.29i kV . A
Problem 4. Prob 5.15 on page 184 of the text. Draw an impedance diagram for the system whose
one-line diagram is shown in Figure P5.15. the 3 phase and line-line ratings are as follows:
Generator: 30 MVA, 138 kV, Xs=0.10 pu
Motor :
20 MVA, 13.8 kV, Xs=0.08 pu
T1:
20 MVA, 13.2-132 kV, Xl=0.10 pu
T2:
15 MVA, 13.8-13.8 kV, Xl=0.12 pu
Line:
20 + j 100 ohms
Pick the generator ratings for the bases in the generator section.
It doesnt take long to figure out that there is an error in the problem statement. The configuration is not
practical. We should see a step up in voltage from generator to line, transmission at high voltage, and a
step down in voltage to feed the load. Practical generators will normally generate in the 10kV-30kv range,
not 138kV. When we find that the line impedance is too large, this confirms our suspicions. Therefore, the
solution is based on a more practical problem statement. If you prefer the original numbers, please
change the bases in MATHCAD.
Generator: 30 MVA, 13.8 kV, Xs=0.10 pu
Motor :
20 MVA, 13.8 kV, Xs=0.08 pu
T1:
20 MVA, 13.2-132 kV, Xl=0.10 pu
T2:
15 MVA, 138-13.8 kV, Xl=0.12 pu
Line:
20 + j 100 ohms
MVA
6
10 .volt .amp
30 .MVA
V Bgen
13.8 .kV
V Bline
138 .kV
V Bmotor
13.8 .kV
X sg
0.10
13.2 .13.2
T1:
X l1
0.10 .
20
13.8 .13.8
X l1 = 0.137
30
13.8 .13.8
T2:
X l2
0.12 .
15
13.8 .13.8
X l2 = 0.24
30
13.8 .13.8
Motor:
X sm
0.08 .
20
13.8 .13.8
X sm = 0.12
30
Line:
Z line
j .100 ) .ohm
V Bline .V Bline
( 20
SB
Z line = 0.032
0.158i
X sg = 0.1
+
-
X l1 = 0.137
Z line = 0.032
0.158i
X l2 = 0.24
X sm = 0.12
Vgen
Vmotor
Gen
T1
line
T2
+
-
Motor
Problem 5. Prob 5.16 on page 184 of the text. Using the impedance diagram of Problem 5.15,
assume that the motor voltage is 13.2 kV when the motor draws 15 MW at a power of 0.85 leading.
a. find the following quantities in per unit: motor current, transmission line current, generator
current, generator terminal voltage, sending end transmission voltage, and complex power supplied
by the generator.
b. convert the quantities found in part a to actual units.
MW
Convert the motor voltage and kVA to per unit
V motor
13.2 .kV
V motor = 0.957
V Bmotor
15 .MW
j.
S motor
SB
0.31i
I pu
S motor
V motor
I pu = 0.523
I pu = 0.615
0.324i
I
angle Re I pu , Im I pu
I = 31.788 deg
6
10 .volt .amp
The transmission line current and generator current are the same series current...the same value in per
unit.
Find the generator voltage
V gen
I pu . j .X l1
V motor
V gen = 0.8
j .X l2
Z line
V gen = 0.851
0.29i
gen
I pu . j .X l2
V motor
V send = 0.844
0.218i
Z line
V send = 0.872
send
S gen
V gen .I pu
S gen = 0.512
0.108i
S gen = 0.523
S motor
V motor .I pu
S motor = 0.588
part b. Same quantities in actual units. First, calculate the base currents.
I Bgen
I Bline
I Bmotor
SB
V Bgen . 3
SB
V Bline . 3
SB
V Bmotor. 3
3
I Bgen = 1.255 .10 A
I Bline = 125.511 A
3
I Bmotor = 1.255 .10 A
I motor
I line
I motor = 656.08
I pu .I Bline
I gen
I pu .I Bgen
V send
S gen
S motor
I line = 65.608
40.66i A
I line = 77.2 A
I gen = 656.08
406.602i A
I gen = 771.9 A
V gen = 0.8
0.29i
I motor = 771.9 A
406.602i A
V gen .V Bgen
V gen
S gen .S B
S gen = 15.357
S motor .S B
V send = 120.3 kV
30.085i kV
S motor = 15
V gen = 11.7 kV
S gen = 15.7 MVA
3.229i MVA
9.296i MVA
Problem 6. Prob 5.17 on page 184 of the text. Assume that the motor is replaced by a Y-connected
load impedance woith ZL=20 / 45 degrees in each leg. the generator terminal voltage is 13.2 kV. find
the voltage and current at the load n per unit and actual units.
X l1 = 0.137
+
-
Gen
Z line = 0.032
0.158i
X l2 = 0.24
Vgen = 13.2 kV
Vmotor
T1
ZL
line
20 .( cos( 45 .deg )
T2
j .sin( 45 .deg ) ) .ohm
ZL
Motor
Z L = 14.1
14.1i ohm
ZL
Z L = 2.23
V Bmotor.V Bmotor
Z L = 3.15
2.23i
SB
Given the generator voltage, convert to per unit
13.2 .kV
V gen
V gen = 0.957
V Bgen
I pu
V gen
j .X l1
Z line
j .X l2
ZL
I pu = 0.268
I pu = 0.17
0.207i
angle Re I pu , Im I pu
360 .deg
I = 50.7 deg
360 .deg
I pu .Z L
V load = 0.844
V load = 0.84
Vload
0.084i
I pu .I Bmotor
I load = 212.965
260.403i A
The angles are the same in per unit and actual units.
I load = 336.398 A
V load = 11.653 kV