Process Control Systems
Process Control Systems
Workbook
171 149
Order No.: 171 149
Description: WORKBOOK
Designation: D.MP-C-PCS-1-GB
Status: 10/1997
Layout: 1.10.97, M. Schwarz
Graphics: D. Schwarzenberger
Authors: H. Bischoff*, D. Hofmann*, E. v. Terzi
Editor: F. Ebel
Preface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Part A
Exercises and Worksheets
Part B
Fundamentals
Chapter 1 Fundamentals of closed-loop control technology
1.1 What is closed-loop control technology? . . . . . . . . . B1-2
1.2 What is a system? . . . . . . . . . . . . . . . . . . . . . B1-4
1.3 Open-loop and closed-loop control . . . . . . . . . . . . B1-6
1.4 Basic terminology . . . . . . . . . . . . . . . . . . . . . B1-9
1.5 Controlled system . . . . . . . . . . . . . . . . . . . . B1-12
1.5.1 Description of the dynamic response
of a controlled system . . . . . . . . . . . . . . . . . . B1-14
1.6 Controllers . . . . . . . . . . . . . . . . . . . . . . . . B1-16
1.6.1 Control response . . . . . . . . . . . . . . . . . . . . . B1-17
1.6.2 Time response of a controller . . . . . . . . . . . . . . B1-18
1.6.3 Technical details of controllers . . . . . . . . . . . . . B1-20
Part C
Solutions
Solution 1 Overview of project design process . . . . . . . . . C1-1
Part D
Appendix
Preface
The authors have produced this book in order to present to you the
main training contents relating to the automation of continuous proces-
ses in a practice-related form intended for vocational and further train-
ing. To this end, the extensive experience available at Festo Didactic
and at the Department of Automation Technology at the Dresden Uni-
versity of Technology has been gathered and combined in the form of
this workbook.
The authors, Dr. Eng. H. Bischoff and Dr. Eng. D. Hofmann, both hold
posts at the Department of Automation Technology at the Dresden Uni-
versity of Technology and are responsible for student training in the
areas of project designing of automation systems, comprehensive prac-
tical training in process automation and the design of closed control
loops and binary control systems.
The authors feel that this workbook will provide a meaningful contribu-
tion towards application-related vocational and further training, and
hope that those who have studied the book will have gained some use-
ful knowledge.
All readers are invited to contribute with tips, criticisms and suggestions
for the further improvement of this book.
General
Trainees must not work on the station unless supervised by a qualified
instructor.
Please observe the specifications given in the data sheets for the
individual components, and in particular all advice regarding safety!
Electrics
Electrical connections are to be wired up or disconnected only when
power is disconnected!
The heater is operated using 230 V AC. Please observe the current
safety regulations during commissioning!
(DIN VDE 0113 [EN 60204])
Mechanics
Mount all components on the plate.
The maximum operating temperature of the containers of + 65 °C
must not be exceeded.
Do not operate the heater, unless the heating element is fully immer-
sed in the fluid.
Part A
Title
Name (in brief) the key areas involved in core project design!
Explain in principle, the procedure for the linking of the core, electrical
and pneumatic projects.
Title
One important part exercise of the project design work is the develop-
ment of the piping and installation (PI) flow diagram. As a rule, this is
based on a process flow diagram, also taking into consideration any
relevant comments.
Draft the PI flow diagram for the specified process flow diagram (Requi-
rements: Control of filling level in container 2 [B2]; monitoring of filling
levels in containers B2 and B1).
B2 L = 0.2 m
B1
Draft the PI flow diagram for the specified process flow diagram (Requi-
rements: Control of temperature in container B1; monitoring of filling
level and temperature in container B1).
Temperature
control system –
Process flow diagram
M
Field level
Draft the preliminary EMCS block diagrams for the EMCS points of the
PI flow diagram created in part exercise 2-2 (see solution, part exercise
2-2).
PLC
Process control
console (PCC)
(Terminal
X100.01 1 2 3 4 5 6 7 8
distributor)
1 2 3 4
Measuring Measuring (Assembly position 3) (Assembly position 4) (Assembly
transducer transducer level A)
E1 E2 A1 A2 E1 E2 A1 A2 A
(Assembly
Switchroom
level B)
(SR)
B
Switchroom rack
(Terminal
X200.01 1 2 3 4 5 6 7 8 X200.02 1 2 3 4 5 6 7 8 distributor)
Terminal box
Field level
X300.01 1 2 3 4 5 6 7 8 X300.02 1 2 3 4 5 6 7 8
(process)
(field level)
Process
X200.01
X300.01-1 A / 1 / E1
1
X300.01-2 A / 1 / E2
2
X100.01-7 A / 2 / E1
3
X100.01-8 A / 2 / E2
4
Title
Title
Draft the PI flow diagram for the process flow diagram provided (fig. 4-1
Flow method A / Flow method B), integrating the EMCS functions for
control, monitoring, structure variation and process protection into the
process flow diagram in an adequate form.
Type of operation A
B32
0.2m LC
B31 L<0.35m
L>0.05m
Outflow
P31
Inflow
Type of operation B
B32
0.2m LC
B31 L<0.35m
L>0.05m
Outflow
P31
Fig. 4-1:
Process flow diagram for Inflow
filling level control
Fig. 4-2:
PI flow diagram for filling level control (Open and closed loop control and process protection)
EMCS point Function Closed loop Open loop control Process protection
control
Table: For functioning of EMCS points of PI flow diagram – Filling level control
Title
Temperature
°C °C °C °C °C
displayed
Note
Conduct the measurements in quick succession at a constant water
temperature.
– if Rl1 = Rl2, or
– with different Rl’s.
Temperature
°C °C °C °C
displayed
Note
Conduct the measurements in quick succession at a constant water
temperature.
Title
Y = 0% X1 =
Y = 100% X2 =
10 Lower Kp Increase Kp
– Note:
The flow and filling level control systems have been selected in such
a way that the oscillating process can be observed without any auxi-
liary equipment (just eyes and ears).
KKR
TK
Controller type Kp Tn Tv
P 0.5 KKR – –
Selected parameters:
Controller type Kp Tn Tv
PI
PID
Part B
Fundamentals
Chapter 1
Fundamentals of closed-loop
control technology
Reference variable
Controlled variable
Manipulated variable
Controlled system
The controlled system has an input variable and an output variable. Its
response is described in terms of dependence of the output variable on
the input variable. These responses between one or several variables
can normally be described using mathematical equations based on phy-
sical laws. Such physical relationships can be determined by experi-
mentation.
Controlled systems are shown as a block with the appropriate input and
output variables (see Fig. B1-1).
Fig. B1-1:
Block diagram of a
controlled system
Example
A water bath is to be maintained at a constant temperature. The water
bath is heated by a helical pipe through which steam flows. The flow
rate of steam can be set by means of a control valve. Here the control
system consists of positioning of the control valve and the temperature
of the water bath. This result in a controlled system with the input vari-
able "temperature of water bath" and the output variable "position of
control valve" (see Fig. B1-2).
Water
Steam
Control valve
Fig. B1-2:
Water bath Helical heating pipe
controlled system
The advantage of creating a system with input and output variables and
representing the system as a block is that this representation separates
the problem from the specific equipment used and allows a generic
view. You will soon see that all sorts of controlled systems demonstrate
the same response and can therefore be treated in the same way.
Section B 1.4 contains more information on the behaviour of controlled
systems and their description.
Having defined the term "controlled system" it only remains to give defi-
nitions of closed-loop control as contained in standards. First it is useful
to fully understand the difference between open-loop control and
closed-loop control.
Open-loop control
Example
Volumetric flow is set by adjusting a control valve. At constant applied
pressure, the volumetric flow is directly influenced by the position of the
control valve. This relationship between control valve setting and volu-
metric flow can be determined either by means of physical equation or
by experiment. This results in the definition of a system consisting of
the "valve" with the output variable "volumetric flow" and the input vari-
able "control valve setting" (see Fig. B1.3).
l/h
Applied pressure
p [bar]
Measuring
device
Control valve
This system can be controlled by adjusting the control valve. This al-
lows the desired volumetric flow to be set.
However, if the applied pressure fluctuates, the volumetric flow will also
fluctuate. In this open system, adjustment must be made manually. If
this adjustment is to take place automatically, the system must have
closed-loop control.
Closed-loop control
Example
The volumetric flow (the output variable) is to be maintained at the pre-
determined value of the reference variable. First a measurement is
made and this measurement is converted into an electrical signal. This
signal is passed to the controller and compared with the desired value.
Comparison takes place by subtracting the measured value from the
desired value. The result is the deviation.
Manipulating element
In order to automatically control the control valve with the aid of the
deviation, an electrical actuating motor or proportional solenoid is requi-
red. This allows adjustment of the controlled variable. This part is called
the manipulating element (see Fig. B1-4).
Measuring element
Applied pressure Control valve Volumetric flow
3
p [bar] V [m /s]
Manipulated variable
Fig. B1-4: Reference variable
Closed-loop control
of volumetric flow
Controlled variable x
Manipulated variable y
Disturbance variable z
Reference variable w
The reference variable is also known as the set point. It represents the
desired value of the controlled variable. The reference variable can be
constant or may vary with time. The instantaneous real value of the
controlled variable is called the actual value w.
Deviation xd
Control response
Controller
The controller has the task of holding the controlled variable as near as
possible to the reference variable. The controller constantly compares
the value of the controlled variable with the value of the reference vari-
able. From this comparison and the control response, the controller de-
termines and changes the value of the manipulating variable (see Fig.
B1-5).
Manipulated
Controlled variable x - Deviation xd Control variable y
response
(actual value) (algorithm)
+
Measuring element
Closed loop
The closed loop contains all components necessary for automatic clo-
sed-loop control (see Fig. B1-6).
Manipulated
variable y
Valve Temperature
setting water bath
Water bath
Valve
setting [%]
100
50
Time t
Temperature
water bath [°C]
80
70
60
Fig. B1-7: 50
Time response of 40
the controlled system Time t
"water bath"
Example
In the example of a valve for volumetric flow control, the dynamic re-
sponse is rapid. Here, a change in the valve setting has an immediate
effect on flow rate so that the change in the volumetric flow rate output
signal almost immediately follows the input signal for the change of the
valve setting (see B1-8).
Valve Volumetric
Valve
setting flow
Valve
setting [%]
100
50
Time t
Volumetric
3
flow [m /s]
80
70
60
50
40
Fig. B1-8:
Time t
Time response of the
controlled system "valve"
Step response
Dynamic response
y x
t t
Equilibrium
Static behaviour
Example
The characteristic of the "valve" system from our water bath example
shows the relationship between volumetric flow and valve position (see
Fig. B1-10).
3
Volumetric flow [m /s]
3
at applied pressure p
Fig. B1-10:
1 2 Valve setting y [mm] Characteristic curve of
the "valve" system
1.6 Controllers
The previous section dealt with the controlled system - the part of the
system which is controlled by a controller. This section looks at the
controller.
The controller is the device in a closed-loop control that compares the
measured value (actual value) with the desired value, and then calcu-
lates and outputs the manipulated variable. The above section showed
that controlled systems can have very different responses. There are
systems which respond quickly, systems that respond very slowly and
systems with storage property.
For each of these controlled systems, changes to the manipulated
variable y must take place in a different way. For this reason there are
various types of controller each with its own control response. The con-
trol engineer has the task of selecting the controller with the most suit-
able control response for the controlled system.
Continous-action controller
Non-continous-action controller
Temperature
Bi-metallic switch
Heating
element
Proportional controller
Integral-action controller
Differential-action controller
Electrical and electronic controllers work with electrical input and output
signals. The transducers are sensors which convert physical variables
into voltage or current. The manipulating elements and servo drives are
operated by current or voltage outputs. Theoretically, there is no limit to
the range of these signals. In practice, however, standard ranges have
become established for controllers:
Internal processing of signals in the controller is either analog with ope-
rational amplifier circuits or digital with microprocessor systems
In circuits with operational amplifiers, voltages and currents are pro-
cessed directly in the appropriate modules.
In digital processing, analog signals are first converted into digital
signals. After calculation of the manipulated variable in the micropro-
cessor, the digital value is converted back into an analog value.
Although theoretically these two types of processing have to be dealt
with very differently, there is no difference in the practical application of
classical controllers.
xd y
y0
x0
t t
If the proportional gain is too high, the controller will undertake large
changes of the manipulating element for slight deviations of the control-
led variable. If the proportional gain is too small, the response of the
controller will be too weak resulting in unsatisfactory control.
A step in the system deviation will also result in a step in the output
variable. The size of this step is dependent on the proportional gain. In
practice, controllers often have a delay time, that is a change in the
manipulated variable is not undertaken until a certain time has elapsed
after a change in the system deviation. On electrical controllers, this
delay time can normally be set.
An important property of the P controller is that as a result of the rigid
relationship between system deviation and manipulated variable, some
system deviation always remains. The P controller cannot compensate
this remaining system deviation.
The I controller adds the system deviation over time. It integrates the
system deviation. As a result, the rate of change (and not the value) of
the manipulated variable is proportional to the system deviation. This is
demonstrated by the step response of the I controller: if the system
deviation suddenly increases, the manipulated variable increases conti-
nuously. The greater the system deviation, the steeper the increase in
the manipulated variable (see Fig. B1-12).
xd y
t t
For this reason the I controller is not suitable for totally compensating
remaining system deviation. If the system deviation is large, the mani-
pulated variable changes quickly. As a result, the system deviation be-
comes smaller and the manipulated variable changes more slowly until
equilibrium is reached.
Nonetheless, a pure I controller is unsuitable for most controlled
systems, as it either causes oscillation of the closed loop or it responds
too slowly to system deviation in systems with a long time response. In
practice there are hardly any pure I controllers.
Reset time
The reset time is a measure for how fast the controller resets the mani-
pulated variable (in addition to the manipulated variable generated by
the P component) to compensate for a remaining system deviation. In
other words: the reset time is the period by which the PI controller is
faster than the pure I controller. Behaviour is shown by the time re-
sponse curve of the PI controller (see Fig. B1-13).
xd y
t t
Tr
Tr = reset time
Derivative-action time
xd y
t t
Td
Td = derivative-action time
xd y
t t
Tr Td Tr = reset time
Td = derivative-action time
Derivative-action time
1.8 Summary
Chapter 2
Project design of
automation systems
2.1 Introduction
2.1.1 Motivation
Based on the fact that currently engineering training in the field of auto-
mation technology is principally dominated by the theory of open and
closed loop control, the main purpose of this training concept is to pro-
vide would-be practical automation specialists with a sound knowledge
of automation methods and project design methods for automation
systems. In the sense of holistic training this means that training mat-
ters such as the selection and sizing of automation equipment, project
design methods, information, electrotechnology, as well as open and
closed loop theory must always be taught within a joint context, demon-
strated through relevant, practical examples and consolidated by means
of practical exercises (learning by doing).
With this type of vocational and further training of engineers and other
specialists in mind, many years’ experience has been gathered by both
Festo Didactic (e. g. Modular Production System / MPS), and the De-
partment of Automation of the Technical University of Dresden, and, as
part of a joint project, used to design and develop a small-scale trial
station for the automation of continuous processes as in process tech-
nology.
Module
Base plate
(for module configuration) Display/operating module – local (optional)
Supply of electrical auxiliary energy
Fig. B2-1:
Design of a
* currently being developed at the Department of Automation
process technology module
Open and
Automation Electrical Pneumatics/ Information
closed-loop
tools technology Hydraulics technology
control technology
Use of CAE
Determining
Determining resources Design and
Selecting the
the for commissioning
and auxiliary
required project design of closed control
sizing of energy
power; and the loops and binary
sensors/ requirements,
distribution of design of control systems;
actuators distribution
electrical closed-loop integration into
and of this
auxiliary control systems automation
processors auxiliary
energy and binary concepts
energy
control systems
Fig. B2-3:
Overview of extent
and technical diversity of
of the basic knowledge
involved in the
project design of Project design of automation systems
automation systems
The broad knowledge base required for this can only be mastered and
put to effective use for project design work by means of a systematic
approach (project design know-how). From this viewpoint alone, the
small-scale trial station represents an important auxiliary means for the
tuition of the necessary training contents and for the development of the
required technical and practical competence by means of systematically
applying the "learning by doing" concept.
If you now set the task of working through a project design task using
the example of this small-scale trial station or an industrial installation in
process technology, the project design know-how forms the crucial
basis for this. Fig. B2-4 therefore provides an initial introduction of the
scope and sequence of the actual project design work in the form of an
overview.
The starting point of every automation project are the project require-
ments, which are placed on the automation system. Generally, an invi-
tation to tender is drawn up by the customer for this which, in the sense
of the traditional DIN interpretation is characterised by the specification
and process flow diagram. The contractor, as a rule the project design
company, draws up a proposal (including quotation) and documents the
project design work (specification) to be completed via a so-called con-
figurational draft in the form of the PI flow diagram (piping and installa-
tion flow diagram).
Core project –
Project requirements
• Tender specification/
Problem definition
• Process flow diagram
Core project –
Final draft
• Assembly project
• Commissioning
specifications Fig. B2-4:
Sequence and content of
project design work
Components –
switchroom (SR)
Automation equipment
Measuring transducers
Components –
Process/field level (local)
PI LI+
305
Automation equipment LI-
Fig. B2-5:
Basic structure of an
automation system
Interference Process
Z xe (controlled xa
system/
Utilisation of information contol circuit) Processing acquisition
via via
Fig. B2-6:
Automation equipment of a single-loop closed control loop and the binary control system
and
Round
and
Oblong
Square with
inscribed circle
and
Rectangle with
inscribed oblong
Hexagon
and
extended hexagon
and
EMCS point local control console.
The project designer also defines what the EMCS point will be or
which components of the basic structure of the automation system it
will cover.
In accordance with DIN 19227 (Part 1/Sheet 6), the use of the letter
code and the design of the PI flow diagram (interpretation of the EMCS
point) are explained with the help of the introductory example (fig. B2-7).
Initial letter
T Temperature
Second letter
I Display
1st subsequent letter
A Alarm devices
TIAH
2nd subsequent letter
117 H High/upper limit value
Container
Fig. B2-7:
Introductory example
EMCS point number demonstrating the
letter code in the
PI flow diagram
(using the example of a
temperature measuring
point)
Selected examples
EMCS point 1
(Pressure measurement with display at process control console)
PI PDI
305 707
To begin with, the type of each of the EMCS points in the example
shown in fig. B2-8 is used to demonstrate how the different measuring
points on containers or the piping system are represented in a form
which conforms to DIN.
Based on this form, the entering of closed control loops also becomes
clear. Fig. B2-9 illustrates that, apart from the letter code for the
functions of the closed control loop, this symbolic representation also
defines the measuring place (the measuring signal) and the actuator
with manipulation point (actuating signal).
Finally, the binary control systems also have an important part within
the framework of the extent of EMCS points. Fig. B2-10 also shows an
example of how the binary control system fit into the PI flow diagram.
Again, the measuring place (measuring signal) and actuator with mani-
pulation point (control signal) have been entered for the EMCS points.
a)
EMCS point 1 (flow control at
process control console)
FIC
315 Measuring signal
Control signal (controlled variable x)
y
Container
Outflow
(to consuming device)
Pump
b)
EMCS point 2 (filling level control at
process control console)
LIC
320
Control signal Measuring signal
y (controlled variable x)
Pump
Container
Outflow
(to consuming device) Fig. B2-9:
Representation of
closed control loops
(in PI flow diagram)
Inflow
Outflow
Fig. B2-10: (towards
Representation of On/off
valve consuming
binary control systems device)
(in PI flow diagram)
In contrast with this, the actuator is already easy to classify from the PI
flow diagram. Hence, actuators (actuating devices) using pneumatic
auxiliary energy are often used which, apart from the advantages of–
high correcting speed/ruggedness – assume the preferred state "on" or
"off" in the event of failure of the air supply, depending on the construc-
tional arrangement of the spring (see fig. B2-11). The majority of electri-
cal actuators, for instance, do not have this characteristic and remain in
the position assumed at the time of failure of the electrical auxiliary
energy.
The PI flow diagram therefore forms the definitive basis for further reali-
sation of the automation system project with regard to technical en-
gineering. This requires a corresponding project classification, e. g. for
the selection of sensors, actuators and processors. Within this context,
the selection of sensors and actuators is also designated in the form of
field instrumentation and the additionally required second task of confi-
guration in the form of – selection of the process control technology –.
This enables the task to be subdivided and very often translated into
practical team work. This means that, one section of the team prepares
the field level instrumentation, and the other section the selection and
commissioning of the process control system.
To provide a better understanding, the small-scale trial system is used
as an example to introduce the official PI flow diagram in accordance
with DIN, followed by the PI flow diagram variant favoured by the De-
partment of Automation. The latter is also within the framework of DIN
19227, but specifies the allocated sensors as additional EMCS point for
each closed loop control and binary control system. This creates a
central interface, the EMCS points terminal, which provides the field
signals for the connection of the process control technology (figs. B2-12
and B2-13).
HSO
LIC
30
B2 20
B4 B5
V7 B1
V12 LS
V11 B3 M M Vr7 10
V9
V8
P3 P2 Vout1
V10
Outflow
V6 V4 V2
Vout3 Vout2 V5 V3 V1
a a
Outflow Outflow
P1
M
Fig. B2-12:
PI flow diagram conforming to DIN
Within the framework of the core project design, the PI flow diagrams
are followed by the so-called EMCS block diagrams. In the sense of a
level-graded project specification, a preliminary EMCS block diagram
and a final EMCS diagram are prepared for each EMCS point, where-
by the preliminary EMCS block diagram defines the connection of the
automation equipment involved in the configuration of an EMCS point
and the final EMCS block diagram documents the detailed wiring based
on this.
FIC
LI 20
30 TIC
1 2 10
HSO
FI
LI B2 20
20
31
B4 B5
LIC
30
V7 B1
V12 LIA-
TI
10
V11 B3 M M Vr7 10 LS
10
V9
V8
P3 P2 Vout1
V10
Outflow
V6 V4 V2
Vout3 Vout2 V5 V3 V1
a a
Outflow Outflow
P1
M
Fig. B2-13:
PI flow diagram – modified
Again, suitable symbols are used when drawing up these EMCS block
diagrams to indicate how the so-called standardised signals are used to
connect the automation devices deployed.
To provide a better understanding, this standardised signal concept is
therefore described in greater detail first.
Components –
Process control
console (PCC)
Process control system
Components –
Switchroom
(SR)
Power
Measuring transducers/
current
signal converters
supply
Components –
process/field Terminal box-field level
level (local) (TBF)
Components –
process control
console (PCC)
Process control system
Components –
switchroom (SR)
Power
Control console racks
current
for wiring block
supply
Electrical
standardised
signals
Components –
process/field
level (local)
Terminal box-field level
(TBF)
Symbols
Thermo element
(for temperature measurement)
DIN 19227 also provides a series of symbols for the measuring trans-
ducers / signal converters (adapters / safeguarding of standardised
signal concept) installed in the switchroom.
Display – analogue
Display – digital
Printer
The following symbols are used to represent the binary control systems,
which are also required to automate process technology operations.
Fibre-optic cable
Analogue Field
LIC30 1 0 to 20 mA 24 V DC 1
ultrasonic sensor level
E
H / A-
conversion 5
Switchroom
W PID
H
X
2
0 to 10V
E 3
0 to 20mA
0 to 24V
Field level
L
4
This list is drawn up for each EMCS point and in that order contains the
automation equipment for sensor, actuator, transducer and processor
technologies with precise designation so that, apart from the purpose of
documentation, it also contains the necessary ordering information.
In addition, the so-called allocation lists are also prepared on the basis
of the preliminary EMCS block diagrams.
The allocation lists are geared to the container systems used in the
automation system and as such provide the assembly specification for
the attachment of the automation equipment deployed (fig. B2-17). In
this context it should be noted that the container systems used are
subdivided into assembly levels and these again into assembly posi-
tions.
The allocation list is therefore a clearly arranged document used direct-
ly for the assembly of the automation equipment.
Assembly levels
1 2 3 4 1 2 3 4 1 2 3 4
A A A
1 2 3 4 1 2 3 4 1 2 3 4
B B B
1 2 3 4 1 2 3 4 1 2 3 4
C C C
1 2 3 4 1 2 3 4 1 2 3 4
D D D
Fig. B2-17:
Terminal distributors Allocation list –
basic configuration
Based on the preliminary EMCS block diagram, the final EMCS block
diagram documents the detailed wiring of the automation equipment
and thus represents the basis for the creation of the wiring documenta-
tion. To provide a better understanding, reference is again made to the
structure of an automation system defined in fig. B2-5, which now po-
ses the task of interconnecting the components process control conso-
le, switchroom and field by means of wiring.
The basis of this wiring are the respective wiring harnesses and the
corresponding terminal distributors. Fig. B2-18 illustrates the structure
of the wiring paths and the assembly points of these terminal distribu-
tors defined in the container units of process control console, switch-
room and as such in the terminal boxes at field level. This illustrates
that the terminal distributors are the major support points for the wiring
paths, since they accommodate the incoming cables and route them via
corresponding wiring blocks to the assembly levels of the control cabi-
nets or other container units.
Path 5
PLC technology
(built-in)
Path 4
Terminal distributor
(process control console)
X100.01
Path 6 Switchroom
1 2 racks
A
Switchroom 3 4
B Assembly
(SR) Path 3 Path 8 levels
C (A, B, C, D)
Path 2/7
Path 3/8
D X200.02
Terminal
distributor
(switchroom)
Path 8 X200.01
Path 1
X300.01 . . . X300.12
PROCESS
Fig. B2-18:
Structure of wiring path
X300.01
Terminal distributor Consecutive number
Ordinal number
Fig. B2-19:
Project-specific definition
Basic designation of a
terminal distributor
Ordinal number
general identification symbol consecutive number
Path 2
From terminal strip-switchroom to assembly area switchroom
racks
e. g.: X200.01 ⇒ Level A/Area 1
Path 3
From assembly area switchroom racks via terminal distributor
switchroom to terminal distributor process control console
e. g.: Level A/Area 1 ⇒ X200.02 ⇒ X100.01
Path 4
From terminal distributor-process control console to PLC
e. g.: X100.01 ⇒ P-I/O card of PLC (DE 1)
Path 5
From PLC to terminal distributor-process control console
e. g.: P-I/O card of PLC (DA 11) ⇒ X100.01
Path 6
Terminal distributor-process control console to terminal distributor-
switchroom e. g.: X100.01 ⇒ X200.01
Path 7
Terminal distributor-switchroom to assembly area-switchroom racks
e. g.: X200.01 ⇒ Level A/Area 2
Path 8
Assembly area-switchroom racks via terminal distributor switchroom
to terminal box field level
e. g.: Level A/Area 2 ⇒ X200.02 ⇒ X300.01
The wiring lists are then set out in accordance with these wiring paths
and, as such, the connections documented in the final EMCS block
diagram of the automation equipment involved in the configuration of
the EMCS points, are put into an easily manageable form for the pro-
cess control engineer.
Fig. B2-21 also uses the example of the filling level control (LIC30
small-scale experimental modules) to introduce the final EMCS block
diagram and to give a partial representation of a wiring list (table 2).
The wiring list is partially represented in table 2, and set out in accord-
ance with the configuration already described in section B.3.3.
Section 1
to controller in switchroom
24V 24V
0V 0V
I 0.0
I 0.1
Wiring terminal (filling level module)
I 0.2
I 0.3
I 0.4
I 0.5 21 11
I 0.6 22 12
I 0.7 23 13
0V 24 14
25 15
O 0.0 41 31 -
O 0.1 42 32
+
O 0.2 43 33 M
O 0.3 44 34
Field level
O 0.4 45 35 M3
O 0.5
O 0.6
O 0.7 X3.2
0V
24V
24V
X3 24V 24V
0V 0V
-R3 1
200 Ω 2
Section 2
Master computer
PCC
PROFIBUS
L1 L1
N N
PE PE
X3.3 Rear side of terminals/controller
Switchroom
1 2 3 4 5 6 7 8 9 10 11 12 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 13 14 15
Field level
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Fig. B2-21:
Final EMCS block diagram – Filling level closed control loop (LIC 30) (Part 1 and 2)
from X3.3 to
Field level/X3 3 33
Profibus cable to master
Field level/X3 4 34 computer
Field level/X3 18 29
Table 2:
Wiring list (excerpt A)
using the example of the
13 Protective
filling level closed control
loop (LIC30/Part 2) earth PE
Introductory comments
As already shown in figure B2-6, the project design work also includes
the appropriate project documentation for the provision of the electrical,
pneumatic and hydraulic auxiliary energy, apart from the core project.
Due to the technical specifics and considerable amount of work invol-
ved, the electrical project accounts for the greater part except for the
core project. The principal outlines of the electrical project design are
therefore introduced in shortened form.
The EMCS block diagram based on the preliminary EMCS block dia-
gram also defines the detailed cabling for the required voltage supplies.
This highlights the relevance of the question for an interface for the
respective reduction of the required voltages. Fig. B2-22 illustrates a
structure, which provides a solution to this problem.
Requirements
regarding explosion Fig. B2-22:
Combination of
and lightning protection
core project with
and EMC electrical and pneumatic
project
Industrial installation
System components – Office and staff
Automation system
process technology facilities complex
L1 50Hz 230VAC
N
-X-S1A2-1
-X-S1A2-1
1 ON 1
EMERGENCY-
OFF 1 STOP 2 2
-S2
2 Process
control
-X-S1A2-1 console
1 3
EMERGENCY- -K3
STOP 2 4
ON 1 3
-K1 Switchroom
2 4 -X-S1D1-1 3 -X-S1C1-1
3 1
-K4
4
-K2 EMERGENCY-
4 STOP 2
A1 A1 Field level A1 A1
-K1 -K2 -K3 -K4
-X-S1A2-1 A2 A2 A2 A2
1
3 4 3 4
OFF 3 4 3 4
2
...
...
...
...
Latching – Latching –
Processors/PLC technology Three-phase consuming devices
Fig. B2-24:
Circuit diagrams for electrical auxiliary energy (self-latching)
for processors/PLC technology and three-phase consuming devices
Behavioural models
Model configuration
Theoretical Experimental
process analysis process analysis
Fig. B2-25:
Fundamentals
of model configuration
Model configuration
Fig. B2-26:
Basic structure of
calculation models,
y – correcting variable,
z – main disturbance
variable,
v – negligible
disturbance variable,
x – output variable
The relationship between the input and the output variables of a techni-
cal system in its steady-state condition is known as the static behaviour.
A simple example of this is shown in fig. B2-27, in the form of a so-
called correcting characteristic of a controlled system, i.e. the relations-
hip between, for example, the valve position y as a process input varia-
ble and the temperature x as a process output variable with the main
interference z (e. g. pressure) as a performance data parameter.
Fig. B2-27:
Control characteristic curve
in the form of
steady-state model
The index zero designates the working point values (process signal
values during nominal operation).
However, input and output signals change from time to time during the
operation of technical equipment, due to starting and shut down proce-
dures and varying, unforeseeable disturbances. This is why it is often
essential for the process model to include the description of the rela-
tionship between these time-related signal changes, which is also
known as dynamic behaviour. Dynamic models in the form of linear
models are often adequate, even for example for the important task of
process stabilisation with the help of a closed control loop. This is pos-
sible in cases where the process signals operate sufficiently closely to
the working point during the execution of technical processes, so that
the process behaviour does not perceptibly change even during transi-
tional phases. In the case of practical operation of automation equip-
ment, it then becomes necessary to consider the limits of the linear
operating range. If these are exceeded, then the results achievable in
the course of the system design using the linear models are put into
question.
y1
Controlled system
x
yn (process)
Fig. B2-28:
Basic structure
for experimental Input signals Output signals
process analysis
1.2
0.8
0.6
AN
0.4
0.2
Fig. B2-29:
Illustration of
0 disturbance/useful signal
0 5 10 15 Time t 20 ratio using the example
of a faulty step response
At least with regard to practical matters, the step response, i.e. the
transient function represents the most important form of a linear dyna-
mic system model.
h
Transient phase Behaviour for t → ∞
I – action
P – action
Fig. B2-31:
Qualitative depiction of D – action
transient behaviour t
with the help of
transient function
h
K
Inflectional tangent
Experimentally
recorded
step response
Smoothed curve
(standardised) Fig. B2-32:
∆h Frequently used transient
function model (inflectional
∆t tangent model)
K – proportional coefficient
Tu – time delay
t Tg – transient time
∆h K
Tu Tg KIS = = – Integral
∆t T g
coefficient
Tg
From the quotient , it is incidentally already possible to estimate the
Tu
degree of difficulty to be expected in the control of a system:
Tg
Ratio Degree of complexity
Tu
h
K
0.8 K
0.2 K
Fig. B2-33:
t20 t80 t Controlled system transient
function
Time constant T and dead time Tt are calculated from the time values
t20 and t80 in accordance with the following formulae:
Container
Water
Flow sensor
Flow Q
Hand valve
Control valve
Pump
Fig. B2-34:
Schematic representation Exhaust valve towards container
of flow control system
Fig. B2-35:
Physical model of
flow process in
flow control system
Q2
∆pV = KS 2 – Pressure drop through the control valve
Kv (Y)
Y – Valve travel.
Q (Y) =
√kpN2 − ρg (hA − hw)
1
ki + kR + KS 2 2
k Y
Linearised
Q
characteristic curve
q
Q0 y
A
Fig. B2-36:
Steady-state y0
characteristic curve of
controlled system if 0 Operating range 100% Y
control valve is used to of valve
control the flow rate
In the area of the operating point A (Q=Q0 + q, Y=Y0 + y), the following
linear correlation then applies
q = Ky (linearised model).
If the flow is regulated above the pump speed N, then the following
linear relationship can be assumed in the operating range of the pump
Q(N) = k1 + k2N
between the correcting variable Pump Speed N and controlled variable
Flow Q (see also fig. B2-37).
Fig. B2-37:
Steady-state
characteristic curve of
0 Operating range 100% N controlled system if
of pump pump is used to
control the flow rate
Fig. B2-38:
Qualitative process
of system step response
However, due to the arrangement of the piping system and the measu-
ring technology and measured-value processing used, a (minor) system
delay dead time Tt still has to be expected when the system is operated
in practice, which will then have to be experimentally determined in the
same way as the controlled system values K andT.
The same deliberations apply with regard to the transient phenomena
relating to the use of the centrifugal pump. Here it must be assumed
that the pump speed variation does not immediately affect the flow but
that, due to the pump design, acceleration processes in the moving
volume of water will lead to delays in the process. The same delibera-
tions as above apply with regard to the dead time Tt.
All in all, these deliberations in the area of the operating point provide a
qualitative dynamic system model (configuration model), which contains
three parameters (Ks, Tt, T) still to be determined by experiment.
Fig. B2-39:
Schematic representation of
level control system
P0
HH
Qout
PB P0
Fig. B2-40: ∆p
Physical model of
outflow process
and ∆p = pB - p0 = ρgHh
∆pR = kR1Q2in
∆pi = kiQ2in
Here it should be noted that if the containers are identical in design, the
total of the filling levels
HW = HU + HH
remains constant.
Qin =
√kpN2 − ρg [HA + 2HH − HW]
k +k i R
between the pump speed N, level HH in the upper container and inflow
Qin in the upper container.
The filling level HH only changes if a difference ∆Q between inflow Qin
and outflow Qout,
∆Q = Qin − Qout’
occurs.
Per time interval ∆t, the volume of water V in the upper container would
then change by
∆V = A ⋅ ∆HH = ∆Q ⋅ ∆t
If we use the inflow and outflow rates according to the equations quo-
ted above are used here, this results in the following correlation in re-
spect of the level change ∆HH per time interval ∆t
1
√ − k √
∆HH 2
k N − ρg (H − H + 2H )
= p A
ρgH
W H
∆t A k +k i R H
Qin = Qout
√ k +k
kpN2 − ρg (HA − HW + 2HH)
i R
=k√
ρgHH
HH
Operating point
of pump
A
HH0
N0 N Fig. B2-41:
0 100% Qualitative process
Operating range of steady-state
of pump characteristic curve
of controlled system
HH = HHO + hH N = N0 + n
∆hH
= −a ⋅ hH + b∆n
∆t
with the two controlled system parameters a and b, which are system
and operating point dependent.
Fig. B2-42:
Step response of
level control system
Fig. B2-43:
Schematic representation
of temperature
control system
Fig. B2-44:
Simplified representation of
temperature control system
The quantity of heat supplied and removed during time interval ∆t, can
be noted as follows
∆ Qin = Pel ⋅ ∆ t or
∆ Qout = ∆ QW + ∆ QL
and hence
Pel = α ⋅ AL ⋅ (T − Tu) + k ⋅ AW ⋅ (T − Tu)
must apply. With an assumed constant ambient temperature, this equa-
tion results in the correlation
Pel
T (Pel) = + Tu
α ⋅ AL + k ⋅ Aw
which indicates the dependence between heating capacity output and
water temperature in the stationary state. Fig. B2-45 shows the steady-
state characteristic curve of the temperature control system.
An assumed constant ambient temperature becomes less and less valid
with increased heat dissipation. With increasing ambient temperature,
the lost heat flow decreases, (∆Qab ~ T-Tu), whereby the water tempe-
rature becomes higher than in the ideal case.
Fig. B2-45:
Qualitative process of
steady-state
characteristic curve of
temperature control system
(ideal case)
To
Tm
Tu
Pelmax
Pel
Fig. B2-46:
Temperature and
t performance pattern
during on/off
ttot ton toff switching of heater module
(two-point element)
∆T 1
= ⋅ [Pel − (α ⋅ AL + k ⋅ AW) ⋅ (T − Tu)]
∆t c⋅m
T T
Tend Tt=0
K
Tt=0 Tend
Fig. B2-47:
Qualitative representation
of system step response
t t
a) Heating THeating TCooling
b) Cooling
Fig. B2-48 shows the basic structure of a closed control loop; its mode
of operation can be described as follows:
However, if the controller is active then, on the basis of the same consi-
derations which apply to the interface A0, the operating point A2occurs,
since the now operative characteristic curves of the controlled system
for Z= Z1 and of the controlling device for W = W0 (with unchanged
setpoint value) now need to be intersected. The operating point in this
case therefore drifts from A0 to A2. The corresponding operating point
values are Y2 and X2. In order to prevent the unwanted increase of the
controlled variable from X0 to X1 at least to some extent, the setpoint
value is reset via the controller from Y0 to Y2 and the steady-state
controlled variable value X2 set.
The flatter the form of the characteristic curve of the controller in fig.
B2-50, the more effective the controller probably is with regard to the
steady-state behaviour of the closed control loop. In the borderline case
of a horizontally running controller characteristic curve, the control ob-
jective of complete diminution of the stationary system deviation es =
W0 - X2, could even be completely achieved. However, a horizontally
running controller characteristic curve as shown in fig. B2-50 means a
vertical pattern in fig. B2-49b, and as such an infinitely high proportional
coefficient of the controller assumed to be of proportional action. That
this optimum steady-state closed control loop behaviour can actually be
realised, can only be seen by further pursuing deliberation regarding
information processing in technical controllers.
Fig. B2-50:
Steady-state performance
characteristics
of closed control loop, 1. Working point variation with fixed setpoint value Y0
Interference changes from 2. Working point variation with active closed-loop control
Z0 to Z1
a) b)
P-action
YP
Fig. B2-51:
Signal flow diagram of I-action
PID-controller
W e YI Y W e Y
a) with individual - -
representation of controller x x
actions P, I and D
D-action
b) with overall
representation YD
(Addition of
individual representations)
of controller transient
function hR(t)
Fig. B2-52:
Favourable behaviour of
control step response
of a closed control loop
Fig. B2-53:
Favourable behaviour of
interference step response
of a closed control loop
Here too, the process can be described roughly by means of two char-
acteristic values (Tm and ∆h* or xm).
KR Tn Tv
Con-
Overshoot amplitude 20 % no overshoot (0%)
troller
after step-change after step-change
Type
of disturbance of disturbance
of setpoint value of setpoint value
variable variable
w w
z z
1
For I-controlled systems the expression is to be used instead
KIS ⋅ Tu
Tg
of .
KS ⋅ Tu
These rules can also be applied to a total time constant model, provi-
ded
Tu = Tt and Tg = T
are set.
Miscellaneous
The aspects to be considered under this heading are, for instance,
size, weight, possible installation of automation equipment, customer
service, etc.
Moreover, the importance of the various evaluations of these require-
ments should be considered in this context whereby, for instance, the
guarantee of process reliability is always of greater importance than a
reduction of costs.
If we now revert back to the already mentioned small-scale experimen-
tal modules or other process technology systems, then the analysis of
the PI flow diagrams and the EMCS block diagrams clearly shows that
the selection of automation equipment mainly applies to actuators and
sensors.
The following lists the essential fundamentals for the selection of this
automation equipment, integrating it into a strategy for selection.
Using the example of flow and filling level control you are familiar with
from the small-scale experimental modules, there now follows an expla-
nation of the essential fundamentals of the theory of flow. Both closed
control loops start from the premise of one fluid flow (water throughput),
whereby flow q and pressure p represent the characteristic process pa-
rameters. Here, it should be noted that in the relevant literature on
pump function and pump design, the term ’output flow’ is often used
instead of flow rate.
The object of the exercise now is to realise a corresponding flow rate or
output flow for the respective specifications.
In process technology, centrifugal pumps (also adjustable) and control
valves are primarily used for this purpose.
Fig. B2-54 initially provides a more detailed account of the design and
configuration of the centrifugal pump.
Pressure side
Impeller vanes
Fig. B2-54:
Suction side Drive shaft Design of a centrifugal
pump (front and side view)
Very often the delivery pressure ∆p, the delivery head h in relation to a
specific fluid, is often specified as a typical pump parameter as an alter-
native to delivery pressure, e. g. example for water (density p = 1
g/cm3), the delivery head is calculated as
∆p
h=
ρ⋅g
Delivery
pressure ∆p
Efficiency η ∆p(n2) n1 < n2
A ∆p(n1)
∆p0(n1)
B η(n2)
η(n1)
Fig. B2-56: C n1 n2
Qualitative representation
of pump and efficiency Output flow
characteristic curves
With an output flow of zero (point A in fig. B2-56), i.e. the pump is
operated against a closed valve or the static differential pressure in a
pipeline is identical to the delivery pressure, this results in a situation
where, although the pump is working, no fluid is transported. This
means that efficiency is 0 and the energy consumed is converted into
heat in the pump housing. However, over an extended period and with
insufficient cooling, this may lead to pump damage, whereby this wor-
king point can no longer be maintained over an extended period.
Once the output flow has increased, the pump reaches its maximum
efficiency (point B) at a working point.
If the output flow further increases (point C), the recorded drive capacity
increases, which leads to a deterioration in efficiency in the case of a
squared degressive delivery pressure. The increase in power consump-
tion may lead to overloading of the drive motor. This is why a predeter-
mined output flow must not be exceeded.
If you now assume the task of selecting a centrifugal pump, this pro-
cess of selection can be conducted along the lines of a relatively simple
procedure.
First of all, differentation must be made between two types of pump
application. In the first case, the pump is used as a pressure increase
facility to maintain the flow (of the output flow) in a pipe, whereby the
pump operates at a constant speed. In the second case, the pump is
used as a throughput regulating element, whereby its speed is used as
a correcting variable.
Fig. B2-57 deals with the first case, i.e. the pump operates at a con-
stant speed. In addition, the steady-state characteristic curve of the
pump and system (system section) are entered in a diagram (fig. B2-
57) and the planned working point of the pump defined at the
point of intersection of the pump characteristic curve and system curve.
Furthermore, the efficiency of the pump is also used to determine the
working point (the nominal ratios) (fig. B2-58).
Working point
Fig. B2-57:
∆pPump = ∆pSystem Selection of a
centrifugal pump
System characteristic curve with the help of the
steady-state
characteristic curve of
system section and pump
q0 q (qo – delivery rate within
working point)
Fig. B2-58:
Efficiency of
centrifugal pump in relation
to delivey rate
(q0 – delivery rate within
working point)
This means that apart from defining the working point of the centrifugal
pump (output flow q0) at the intersection of the above characteristic
curves, it is also necessary to take into account the maximum efficiency
as a specification for the output flow q0. Depending on the pump selec-
tion available, it is often not possible to avoid a compromise in the
sense of deviations from ηmax.
In the case of the centrifugal pump with variable speed, the basic re-
quirement – definition of qmin and qmax – must be met to begin with (in
accordance with corresponding process technological specifications)
(fig. B2-59).
∆p n1 < n2 < n3
n3 Pump characteristic curves
Fig. B2-60:
Efficiency characteristics
of a centrifugal pump in
relation to the delivery rate
(q0 – Delivery rate within
working point)
Definition of
Control range q0 to
ηmax (n)
qmax and qmin ∆pPump = ηmax to q0
to q0 (n)
on the basis of ∆pSystem
process technology
considerations and
q0 to
∆pPump (n) = ∆pSystem
The final control element (regulating valve / control valve / valve actuator)
h h
Valve stem
Stroke y
Valve poppet Packing gland Valve closed
Faced with the task of selecting a final control element, the first step is
to examine the basic behaviour of the final control element in a system
section (pipe section). In this context, it should be noted that due to the
flow resistance of this final control element a dynamic pressure drop
occurs ∆p, which quadratically depends on the flow velocity or
throughput. This means that part of the overall pressure available at the
start of the pipe is reduced in the final control element (loss of energy).
Fig. B2-64:
Equivalent
electrical circuit diagram of
a control valve
100
80
kV / kVS in %
60 linear
40
equal-percentage
20
KVO
10 20 30 40 50 60 70 80 90 100
Fig. B2-65:
Stroke in % Basic characteristic curve
of control valves
kV(y)
kvs
without zero suppression
kv0
Fig. B2-66: with zero suppression
kvr
Linear basic characteristic
curves of control valves 0 Stroke y in % 100
with and without
zero suppression
The parameters kvs and kvo are used to form the so-called theoretical
control ratio kvs/kvo, which is generally specified as a typical parameter
by the valve manufacturer and, in practice is often also replaced by the
effective control ratio kvs/kvr. This takes into account the tolerance be-
tween the targeted and the actually measured basic characteristic curve
(see also fig. B2-66).
Kv
min
= 0.032 ⋅ qmin √∆ρp
q = kv ⋅ 31.62 √∆ρp
= g (y, ∆p)
However, in this case ∆p represents the actual pressure drop via the
control valve for the respective flow rate, which can only be recorded
metrologically, but in practice is not realised in the form of a measuring
point. The formula is therefore less relevant in practical terms and the
satisfactory (practically linear) operating characteristic can only be
achieved by means of the already mentioned superimposition of basic
characteristic curve and system characteristic curve.
In conclusion, a few comments should also be added with regard to the
classification /estimation of the steady-state characteristic curves of pro-
cess technology system groups.
As can be seen from fig. B2-69, differentiation is made between system
sections with dominant static pressure drop and dominant dynamic
pressure drop. However, in fig. B2-67, it can be clearly seen that in
systems with static pressure drop, this only marginally depends on the
flow rate, also known as output flow q.
Delivery
pressure
∆ptot Total pressure drop
∆p Piping characteristic
curve (without final
control element)
Pressure drop on
∆pSystem ∆p control valve
Fig. B2-67:
System with
steady-state pressure drop qmin qmax Output flow
(ideal case –
pump resistance neglected)
Delivery
pressure
∆ptot Total pressure drop
Piping characteristic
curve (without final
∆p control element)
Pressure drop on
Fig. B2-68:
∆pSystem control valve System section with
qmin qmax Output flow dynamic pressure drop
(ideal case – pump
resistance neglected)
Theoretical and
experimental system analysis
for
4.
Calculation of
Taking into account control ratio
the process conditions kVS / kV0
Selection of sensors
Process
parameters Sensors
Measuring range
Temperature 1 from ….to Resistance
Process technology system
thermometer
Measuring range
Temperature 2 from ….to Thermo- Company literature
Measuring range element
Pressure from ….to Semiconductor
Measuring range pressure sensor
Filling level from ….to Ultrasonic
Measuring range sensor
Flow from ….to Inductive
flow meter
Fig. B2-70:
Selection of sensors
Process variable
unacceptable
error range
Limit value of
permissible
error range
safety device
Limit value of
monitoring device
error range
Acceptable
Chapter 3
Commissioning and
maintenance
3.1 Commissioning of
process and automation systems
Establishing of Monitoring of
Level II. operating mode – steady-state
automatic mode initial start up
Fig. B3-1:
Main activities involved in the commissioning of technical process systems
Level I
Group 1 (step 1)
Connection of electrical (and pneumatic) auxiliary energy for proces-
sors and other automation equipment (with the exception of large
electrical consuming devices).
Checking the operating mode – manual mode – for the existing
closed control loops and binary control systems on the technical pro-
cess system.
Basic test of binary control systems, e. g. for the switching on and off
of pumps, open/closed valves, etc., structure variations of the system
and the testing of monitoring equipment.
Group 2 (step 2)
Establishing the operational readiness of the process, e. g. availabil-
ity of required media (basic materials) in the appropriate output con-
tainers, necessary filling of piping systems, etc., (all operating steps
in manual operation).
Group 3 (step 3)
Testing of safety devices (as specified in VDI/VDE 2180), whereby
safety device 1 (sensors, actuators and processor algorithms are to
be tested first, followed by safety device 2.
Connection of electrical auxiliary energy for large consuming devi-
ces.
Approaching of the working points of the process technological
system, i.e. the closed control loops are moved into the required
working points in manual mode, whereby the controller structure and
the controller parameters are programmed for each closed control
loop.
Level II
Group 1
Establishing of operating mode – automatic mode – by means of a
smooth transition, manual/automatic changeover (control signal-
manual and control signal-automatic coincide).
Monitoring of steady-state initial start-up and testing of control and
disturbance behaviour.
1. 2. 3.
Step 1:
Connection of electrical auxiliary energy for processors (process control
system, compact controller, PLC technology and PC’s)
Typical voltage levels
230 V AC and
24 V DC (made available via power supply units)
Step 2:
Connection of electrical auxiliary energy for automation equipment –
standard consuming devices (such as sensors, actuators, measuring
transducers and safety devices)
Typical voltage levels
230 V AC (main supply)
24 V DC (made available via power supply units)
Step 3:
Connection of electrical auxiliary energy for automation equipment –
Large consuming devices (such as pumps and heaters)
Typical voltage levels
400 V AC (main supply)
230 V AC.
Small-scale experimental
modules
230 V AC 1.
Compact controller, PC
230 V AC 2. 24 V DC
Sensors, actuators, pumps
230 V AC 3. 24 V DC
Safety device
230 V AC 4.
230 V AC 5.
Fig. B3-3: Heater
Connection of
electrical auxiliary energy
using the example
of a small-scale
experimental module
L1 50Hz 230V AC
AUS 1
-S2
2 Terminals Terminals
-X-S1A2-1 2 3
EIN 1 13
-K1 -X-S1D1-1 1 2 3 4
-S1
2 14
13
-K2 A1 A1
14
-K1 -K2
A2 A2
-X-S1A2-1 4 5
1 2 1 2
3 4 3 4
5 6 5 6
13 14 13 14
Key: 15 16 15 16
-X-S1A2 / D1
Assembly levels in control cabinet 17 18 17 18
Fig. B3-4:
Connection of auxiliary
energy for processors
L1 50Hz 230VAC
EMERGENCY-
12
STOP 1 1
-S4 Terminals
1 2
ON 1
9
-S3
2
EMERGENCY- 13 14
STOP 2 1
-S5
2 13
-K3
10 14
Terminals -X-S1C1-1
13
1 2 3 4 5 6 7 8
EMERGENCY- -K4
14
STOP 3 1
13
-S6 -K6
2 14
A1 A1 A1 A1
13
11 -K3 -K4 -K5 -K6
-K5 A2 A2 A2 A2
14
OUT 1
-S7
13 14 13 14 13 14 13 14
2
Key:
-X-S1A2 / C1
Assembly levels in control cabinet
Fig. B3-5:
Connection of electrical auxiliary energy for heavy consuming devices
24VDC
1 -X-S4E0-1 -H21
-X-S1E0-1 3
Terminals
2 -X-S1E0-1 -X-S4E0-1 2 -X-S4A2-1 1 -X-S4A2-1 2
17
-K1 -X-S4E0-1 3 4
18
17
-K2
18
towards main valve
1
for connection of pneumatic
-YS1 auxiliary energy
Festo
2
from compressor station
-X-S4E0-2 9
Key:
-X-S4A2 / C1 / E0
Assembly levels in control cabinet
Fig. B3-6:
Connection of
pneumatic auxiliary energy
Step 1
Step 2
With step 1, the binary control systems are tested as a first measure.
This involves, for example, the testing of the on/off valves provided for
configurational changes and their interaction with the corresponding bi-
nary controllers. In this connection, the signals resulting from the so-
called final control element feedback in particular (see also section
B.2.2.4) are to be evaluated visually or by means of binary monitoring
(binary control systems). Similarly, the allocated binary control systems
for the switching on and off of corresponding pumps and heaters are to
be tested. Here again, the allocated binary control systems are to be
tested via the manual control elements and corresponding feedback
sensors.
Classification of malfunctions in
automation systems in process technology
Category 1
Sensor faults
Metrological checking immediately at the sensor terminals themsel-
ves or on the EMCS field terminal points.
Actuator faults
Testing of the incoming control signal on the actuator
Testing directly on the actuator – signal path from the positioning to
the servo drive (checking of calibrating accuracy)
Testing directly on the actuator – mobility of the valve poppet and
spindle (error – e. g. as a result of jamming or rusting of valve pop-
pet or spindle).
Category 2
Category 3
Category 4
Errors on processors
Checking of supply voltages
Checking of input/output signals according to allocations resulting
from algorithm processing (e. g. off-line testing of PLC or compact
controller).
Chapter 4
Fault finding
Fig. B4-1:
Areas of maintenance
4.1.1 Service
The term Service refers to preventive measures to prolong operating
times. Servicing of technical installations covers:
Fig. B4-2:
Service
4.1.2 Inspection
Fig. B4-3:
Inspection
4.1.3 Repairs
Fig. B4-4:
Repairs
Fig. B4-5:
Systematic repairs
2. Mechanical design
Structure and support unit
Function units
Adjustment
3. Drive technology
Electrical system
Hydraulics
Pneumatics
Mechanical system
5. Control system
Electrical relay control
Programmable logic controller
6. Signal generator
Binary sensors
Analogue sensors
Digital sensors
7. Power supply
Electrical
Hydraulic
Pneumatic
4.2.2 Procedure
The first thing that must be done in the event of an error signal is to
establish the actual status. The following options are available for this:
Discussing the fault with the user
(Does the system operate incorrectly?)
Start failure
Stopping during process step
Faulty process
Incorrect working practice
Fig. B4-6:
Acquisition of actual status
Fig. B4-7:
Systematic fault finding
This list can be useful in detecting frequently recurring faults and their
causes. The fault index makes it easier to establish the nature of the
error.
A= Incorrect working practice
(e.g. a retaining screw is not properly tightened on an
assembly part)
M= Mechanical fault
(e.g. sensors are maladjusted)
E= Electrical fault
(e.g. relay is not energised or solenoid does not switch)
S= Controller error
(e.g. program or program part is not activated)
L= Leakage fault
(e.g. water escaping from threaded connection)
B= Operator error
(e.g. shut-off valve not closed)
W= Service error
(e.g. filter not cleaned)
Example
1303 04.01.95 / Part system Filling level, Filling level sensor M TZI
11.00 Controller does not operate maladjusted
correctly
Fig. B4-8:
Fault analysis
Fault finding and elimination means not just to render the system ope-
rational again, but also to identify and improve weak areas in the
system.
The basic prerequisite for this is a knowledge of all control technology
aspects and understanding of the function and interaction of hybrid
systems.
Index
A
D-action . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B2-77
Damage prevention training . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B3-13
Degree of complexity of closed loop control . . . . . . . . . . . . . . . . . . B2-54
Delay of first order . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B2-71
Delivery head . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B2-88
Derivative-action time. . . . . . . . . . . . . . . . . . . . . . . B1-25 - B1-26, B2-77
Disturbance variable z . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B1-9, B2-73
Dynamic behaviour . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B1-14
Dynamic closed control loop behaviour . . . . . . . . . . . . . . . . . . . . . B2-78
I-action . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B2-77
I-controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B1-23
Inflectional tangent model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B2-53
Initial letter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B2-13
Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B4-3
Intermittent controllers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B1-17
I/O model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B2-45
L
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B4-3
Manipulation point . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B2-15
Measuring element . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B1-11
Measuring point. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B2-15
Model configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B2-43, B2-56
Model configuration strategies . . . . . . . . . . . . . . . . . . . . . . . . . . . . B2-45
Model configuration through experimental process analysis. . . . . B2-48
Model forms. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B2-46
Monitoring device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B2-104
O
P-action . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B2-77
P-controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B1-21
PD-controller. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B1-25
Performance specification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B2-9
Permissible error range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B2-104
PI-controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B1-24
PID-controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B1-26
PI flow diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . B2-5, B2-11, B2-40
Preliminary EMCS block diagram . . . . . . . . . . . . . . . . . . . . . . . . . . B2-29
Process analysis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B2-43
Process control console. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B2-7
Process flow diagram. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B2-5, B2-10
Process model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B2-44
Process protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B2-102
Proportional coefficient. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B2-77
Pump characteristic curve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B2-89
R
Part C
Solutions
Title
Name (in brief) the main areas involved in core project design!
Project configuration
PI flow diagram
Wiring lists
Explain, in principle, the procedure for the combining of the core, elec-
trical and pneumatic projects!
Requirements
regarding explosion
and lightning protection
and EMC
Title
Develop the PI flow diagram for the specified process flow diagram (re-
quirements: control of filling level in container 2 [B2]; monitoring of filling
levels in containers B2 and B1).
Develop the PI flow diagram for the specified process flow diagram (re-
quirements: control of temperature in container B1; monitoring of filling
level and temperature in container B1).
Temperature control
system –
PI flow diagram
Draft the preliminary EMCS block diagram for the EMCS points of the
PI flow diagram created in part exercise 2-1 (see solution, part exercise
2-1).
PID
console
H L L
0 ... 10V
24VDC
Switchroom
0 ... 20mA E E
E
0 ... 24V 0/24V 0/10V 0/24V 0/10V
M
Field level
L G G
Vs1 Vs2
P1
Draft the preliminary EMCS block diagram for the EMCS points of the
PI flow diagram created in part exercise 2-2 (see solution, part exercise
2-2).
PID
console
L H 0/24V L
Switchroom
230VAC
E E
0/10V 0/10V
0/24V 0/24V
230VAC
Field level
G T G
Vs1 Vs2
Temperature P1
control system –
Preliminary LIA- 12 LIA+ 11
EMCS block diagram
With the help of the project configuration plan (process control console,
switchroom and field level), draw up two examples of wiring (e. g. simp-
le allocation of the switchroom terminal distributors X200.01 and
X200.02), whereby the terminal boxes/field level (X300.01 and
X300.02), the assembly levels A and B (switchroom rack) and the ter-
minal distributor X100.01 (process control console) are to be used as
additional components.
PLC
Process control
console (PCC)
(Terminal
X100.01 1 2 3 4 5 6 7 8
distributor))
1 2 3 4
Measuring Measuring
transducer transducer (Assembly position 3) (Assembly position 4) (Assembly
level A)
E1 E2 A1 A2 E1 E2 A1 A2
A
(Assembly
Switchroom
level B)
(SR)
B
Switchroom rackl
(Terminal
X200.01 1 2 3 4 5 6 7 8 X200.02 1 2 3 4 5 6 7 8 distributor)
Terminal box
Field level
X300.01 1 2 3 4 5 6 7 8 X300.02 1 2 3 4 5 6 7 8
(process)
(field level)
Process
X200.01
X300.01-1 A / 1 / E1
1
X300.01-2 A / 1 / E2
2
X100.01-7 A / 2 / E1
3
X100.01-8 A / 2 / E2
4
Title
a) b)
PC with PC with
multifunction card bus connection
Vmeaß
Bus
RL = 390Ω
Fig. C3-1:
Communication between Sensor Sensor Digital controller
Computer and process with
a) via PC card bus connection
b) via bus
Ultrasonic sensor
hB
h
Fig. C3-2:
Configuration of
ultrasonic sensor
310 9.98 35
290 10.48 55
270 11.15 75
250 11.73 95
150
100
50
0
10 11 12 13 14 15 mA 16
Signal
mm
150
Filling level
100
50
0
10 11 12 13 14 15 mA 16
Fig. C3-3: Signal
Representation of
sensor characteristic
Mathematical evaluation
Determine the static behaviour of the controlled system for the filling
level.
Note: Record the corresponding controlled variable for each correc-
ting variable in the steady-state condition.
Represent the results in a diagram in the form of a static charac-
teristic.
Evaluate the static characteristic determined (e. g. linear/non-linear)
and compare the results with those determined in the theoretical pro-
cess analysis.
Define the operating point for the dynamic analysis (identification) of
the controlled system.
35 Outflow open
Outflow closed
30
Filling level h in cm
25
20
15
10
5
Fig. C3-4:
Static characteristic curve 0
of filling level system 0 1 2 3 4 5 6 7 8 9 10
with open and
closed outflow Correcting variable in V
Comment
70
60
Pump delivery head in cm
50
40
30
20
10
0
0 1 2 3 4 5 6 7 8 Fig. C3-5:
Correcting variable in V Delivery head of
centrifugal pump
11.0
60%
Correcting variable
50%
6.0
0 Time in s 250
Fig. C3-6:
Step response
The filling level step response has been averaged out and evaluated by
computer. As a result of this evaluation, the following controlled system
parameters have been determined:
Proportional coefficient KS = 2.76 cm/V
Transient time Tg = 68.14 s
These two parameters can be derived from fig. C3-6 with the help of
the inflectional tangent method. It is however not possible to read a
time delay in this way.
It simply needs to be estimated in order to be able to apply the setting
rules in accordance with Chien, Hrones and Reswick, i. e. when estima-
ting Tu, a considerably reduced time delay is selected compared to the
transient time, e. g. Tu= 0.5 s.
Comments
Please note that the calculated value for KR ≈ 113 is obtained from
the estimated time delay Tu (see fig. C3-6) and therefore is to be
replaced by the practical setting value.
When setting the controller parameters in the digital controller the
existing scaling is to be observed (see page 54 of the operating
instructions of the digital industrial controller, type 1110 – Bürkert
open and closed loop control technology, 1994).
Examine the control behaviour of the closed control loop around the
operating point (triggering of setpoint step-changes).
Evaluate the results obtained in accordance with the following cri-
teria:
– How are the dynamics of the correcting variable to be evaluated?
– Does the controlled variable reach the new setpoint value after
a finite time?
– Is it necessary to correct the set controller parameters?
Controller test
The pre-configured controller is to be used to control the filling level
system using setpoint step-changes (control behaviour). The same
scaling is to be selected for the controlled variable acquisition and the
setpoint specification.
Fig. C3-7 illustrates the step-change from 6.5 V to 6 V.
6.8
6.5
Measuring signal in V
6.3
Controlled variable
6.0
Setpoint value
10.0
Controlled variable
Setpoint value
8.92
Filling level in cm
7.5
5.65
Fig. C3-8:
Setpoint step-change
(Filling level cm) 0 40 Time in s 80
Title
Draft the PI flow diagram, whereby the EMCS functions for process
protection are to be integrated into the process flow diagram in com-
plete form.
HSO
301
Close water outflow due
LIC HSO
301 to LIA+ in container of
302
next module
LIA+
302
B32
US US US
301 302 306
LIA+
303
Vh301 Vh302 B31 LIA-
M
Vs305 304
Outflow
Vs301 Vs302 Vs307
P31
Vs306
Vs303
Inflow
Vr301 Vh303
Vs304
US US
305 303
US
304
HSO
304
PI flow diagram for filling level control (open and closed loop control and process protection)
Limit-value monitoring in
LIA +- 302 – – –
B32
Limit-value monitoring in
LIA + 303 – – –
B31
Limit-value monitoring in
LIA - 304 – – –
B31
Table: Regarding function of the EMCS points of the PI flow diagram – Filling level control
Title
Title
Temperature control system Flow control system Filling level control system
Kp 4.00 Kp 3.50 Kp 28
Part D
Appendix
Chapter 1
ProVis – Software
for process visualisation
You have started Windows and are now in the Program Manager. In-
sert the ProVis diskette in your disc drive. Select File-Run in the Pull-
Down menu of the program manager. Enter the command line A:\
PCS_GB. ProVis is then installed.
Fig. D1-1:
Initial display of ProVis
Closed-loop
Provides information about methods of controller setting.
control technology
Configuration and
Information is given regarding configuration
commissioning