Basics of Process Control
Basics of Process Control
Fundamentals
Part B
Fundamentals
Chapter 1
Fundamentals of closed-loop
control technology
Reference variable
Controlled variable
Manipulated variable
Controlled system
The controlled system has an input variable and an output variable. Its
response is described in terms of dependence of the output variable on
the input variable. These responses between one or several variables
can normally be described using mathematical equations based on phy-
sical laws. Such physical relationships can be determined by experi-
mentation.
Controlled systems are shown as a block with the appropriate input and
output variables (see Fig. B1-1).
Fig. B1-1:
Block diagram of a
controlled system
Example
A water bath is to be maintained at a constant temperature. The water
bath is heated by a helical pipe through which steam flows. The flow
rate of steam can be set by means of a control valve. Here the control
system consists of positioning of the control valve and the temperature
of the water bath. This result in a controlled system with the input vari-
able "temperature of water bath" and the output variable "position of
control valve" (see Fig. B1-2).
Water
Steam
Control valve
Fig. B1-2:
Water bath Helical heating pipe
controlled system
The advantage of creating a system with input and output variables and
representing the system as a block is that this representation separates
the problem from the specific equipment used and allows a generic
view. You will soon see that all sorts of controlled systems demonstrate
the same response and can therefore be treated in the same way.
Section B 1.4 contains more information on the behaviour of controlled
systems and their description.
Having defined the term "controlled system" it only remains to give defi-
nitions of closed-loop control as contained in standards. First it is useful
to fully understand the difference between open-loop control and
closed-loop control.
Open-loop control
Example
Volumetric flow is set by adjusting a control valve. At constant applied
pressure, the volumetric flow is directly influenced by the position of the
control valve. This relationship between control valve setting and volu-
metric flow can be determined either by means of physical equation or
by experiment. This results in the definition of a system consisting of
the "valve" with the output variable "volumetric flow" and the input vari-
able "control valve setting" (see Fig. B1.3).
l/h
Applied pressure
p [bar]
Measuring
device
Control valve
This system can be controlled by adjusting the control valve. This al-
lows the desired volumetric flow to be set.
However, if the applied pressure fluctuates, the volumetric flow will also
fluctuate. In this open system, adjustment must be made manually. If
this adjustment is to take place automatically, the system must have
closed-loop control.
Closed-loop control
Example
The volumetric flow (the output variable) is to be maintained at the pre-
determined value of the reference variable. First a measurement is
made and this measurement is converted into an electrical signal. This
signal is passed to the controller and compared with the desired value.
Comparison takes place by subtracting the measured value from the
desired value. The result is the deviation.
Manipulating element
In order to automatically control the control valve with the aid of the
deviation, an electrical actuating motor or proportional solenoid is requi-
red. This allows adjustment of the controlled variable. This part is called
the manipulating element (see Fig. B1-4).
Closed-loop control
Measuring element
Applied pressure Control valve Volumetric flow
3
p [bar] V [m /s]
Manipulated variable
Fig. B1-4: Reference variable
Closed-loop control
of volumetric flow
Controlled variable x
The aim of any closed-loop control is to maintain a variable at a desired volumetric flow
value or on a desired-value curve. The variable to be controlled is
known as the controlled variable x. In our example it is the volumetric
flow.
Manipulated variable y
Disturbance variable z
Disturbances occur in any controlled system. Indeed, disturbances are applied pressure
often the reason why a closed-loop control is required. In our example, changes
volumetric flow
the applied pressure changes the volumetric flow and thus requires a
which in turn
change in the control valve setting. Such influences are called distur- changes
bance variables z. valve setting
The controlled system is the part of a controlled machine or plant in control
which the controlled variable is to be maintained at the value of the
reference variable. The controlled system can be represented as a
system with the controlled variable as the output variable and the mani-
pulated variable as the input variable. In the example of the volumetric
flow control, the pipe system through which gas flows and the control
valve formed the control system.
Reference variable w
The reference variable is also known as the set point. It represents the
desired value of the controlled variable. The reference variable can be
constant or may vary with time. The instantaneous real value of the
controlled variable is called the actual value w.
Deviation xd
Control response
Controller
What are the main The controller has the task of holding the controlled variable as near as
functions of a controller in possible to the reference variable. The controller constantly compares
a controlled system? the value of the controlled variable with the value of the reference vari-
able. From this comparison and the control response, the controller de-
termines and changes the value of the manipulating variable (see Fig.
B1-5).
Manipulated
Controlled variable x - Deviation xd Control variable y
response
(actual value) (algorithm)
+
Measuring element
Closed loop
The closed loop contains all components necessary for automatic clo-
sed-loop control (see Fig. B1-6).
Manipulated
variable y
Valve Temperature
setting water bath
Water bath
Valve
setting [%]
100
50
Time t
Temperature
water bath [°C] dynamic response===time response
80
70
60
Fig. B1-7: 50
Time response of 40
the controlled system Time t
"water bath"
Example
In the example of a valve for volumetric flow control, the dynamic re-
sponse is rapid. Here, a change in the valve setting has an immediate
effect on flow rate so that the change in the volumetric flow rate output
signal almost immediately follows the input signal for the change of the
valve setting (see B1-8).
Valve Volumetric
Valve
setting flow
Valve
setting [%]
100
50
Time t
Volumetric
3
flow [m /s] dynamic response===time response
80
70
60
50
40
Fig. B1-8:
Time t
Time response of the
controlled system "valve"
Step response
Dynamic response
y x
t t
Equilibrium
Static behaviour
Example
The characteristic of the "valve" system from our water bath example
shows the relationship between volumetric flow and valve position (see
Fig. B1-10).
3
Volumetric flow [m /s]
3
at applied pressure p
Fig. B1-10:
1 2 Valve setting y [mm] Characteristic curve of
the "valve" system
1.6 Controllers
The previous section dealt with the controlled system - the part of the
system which is controlled by a controller. This section looks at the
controller.
The controller is the device in a closed-loop control that compares the
measured value (actual value) with the desired value, and then calcu-
lates and outputs the manipulated variable. The above section showed
that controlled systems can have very different responses. There are
systems which respond quickly, systems that respond very slowly and
systems with storage property.
For each of these controlled systems, changes to the manipulated
variable y must take place in a different way. For this reason there are
various types of controller each with its own control response. The con-
trol engineer has the task of selecting the controller with the most suit-
able control response for the controlled system.
Continous-action controller
Non-continous-action controller
Temperature
Bi-metallic switch
Heating
element
Proportional controller
Integral-action controller
Differential-action controller
Electrical and electronic controllers work with electrical input and output
signals. The transducers are sensors which convert physical variables
into voltage or current. The manipulating elements and servo drives are
operated by current or voltage outputs. Theoretically, there is no limit to
the range of these signals. In practice, however, standard ranges have
become established for controllers:
Internal processing of signals in the controller is either analog with ope-
rational amplifier circuits or digital with microprocessor systems
In circuits with operational amplifiers, voltages and currents are pro-
cessed directly in the appropriate modules.
In digital processing, analog signals are first converted into digital
signals. After calculation of the manipulated variable in the micropro-
cessor, the digital value is converted back into an analog value.
Although theoretically these two types of processing have to be dealt
with very differently, there is no difference in the practical application of
classical controllers.
xd y
y0
x0
t t
If the proportional gain is too high, the controller will undertake large
changes of the manipulating element for slight deviations of the control-
led variable. If the proportional gain is too small, the response of the
controller will be too weak resulting in unsatisfactory control.
A step in the system deviation will also result in a step in the output
variable. The size of this step is dependent on the proportional gain. In
practice, controllers often have a delay time, that is a change in the
manipulated variable is not undertaken until a certain time has elapsed
after a change in the system deviation. On electrical controllers, this
delay time can normally be set.
An important property of the P controller is that as a result of the rigid
relationship between system deviation and manipulated variable, some
system deviation always remains. The P controller cannot compensate
this remaining system deviation.
The I controller adds the system deviation over time. It integrates the
system deviation. As a result, the rate of change (and not the value) of
the manipulated variable is proportional to the system deviation. This is
demonstrated by the step response of the I controller: if the system
deviation suddenly increases, the manipulated variable increases conti-
nuously. The greater the system deviation, the steeper the increase in
the manipulated variable (see Fig. B1-12).
xd y
t t
For this reason the I controller is not suitable for totally compensating
remaining system deviation. If the system deviation is large, the mani-
pulated variable changes quickly. As a result, the system deviation be-
comes smaller and the manipulated variable changes more slowly until
equilibrium is reached.
Nonetheless, a pure I controller is unsuitable for most controlled
systems, as it either causes oscillation of the closed loop or it responds
too slowly to system deviation in systems with a long time response. In
practice there are hardly any pure I controllers.
Reset time
The reset time is a measure for how fast the controller resets the mani-
pulated variable (in addition to the manipulated variable generated by
the P component) to compensate for a remaining system deviation. In
other words: the reset time is the period by which the PI controller is
faster than the pure I controller. Behaviour is shown by the time re-
sponse curve of the PI controller (see Fig. B1-13).
xd y
t t
Tr
Tr = reset time
Derivative-action time
xd y
t t
Td
Td = derivative-action time
xd y
t t
Tr Td Tr = reset time
Td = derivative-action time
Derivative-action time
1.8 Summary