Instrument & Control
Instrument & Control
Instrument & Control
SNERDI, Shanghai
TABLE OF CONTENTS
1.1
1.2
1.3
1.4
1.5
1.6
1.7
page 1 - 0 - 1
MODULE OBJECTIVES:
At the end of this module, you will be able to:
1.
Explain briefly, in your own words, the need for signal transmission.
2.
3.
4.
5.
6.
7.
8.
9.
10.
page 1 - 1 - 1
Introduction
Before
any processElectric
can be controlled,
its current
Figure
1. Simplified
Generating
Station status must be known.
Local indication is useful in many applications, but has the disadvantage that
someone must travel throughout the plant in order to determine the system
status.
page 1 - 1 - 2
To bring all of these indicators into one single location (i.e. the central control
room), would mean transporting the actual process quantity to that location.
This would result in hazardous conditions due to the presence of high
pressure steam, high voltage, toxic gases, corrosive liquids, etc., in the control
room.
Instead of simply indicating the process status locally, or transporting the actual
process to the control room, it would be desirable to be able to transmit a
representative signal corresponding to the process status, to the central
control room.
By measuring and displaying this signal in the control room, the field process
state can be determined. The read-out device mounted in the control room
panel can be adjusted or calibrated to indicate the process value directly.
Another advantage of being able to transmit a signal is that some signals may
be analyzed by controllers or computers so that an automatic corrective
action will be initiated if the process deviates from the desired operating point,
called the setpoint.
Also, if abnormal conditions arise, alarm units which are activated by these
signals can be used to trigger annunciations in the control room or to cause a
process to shut down safely.
Pneumatic
Electronic
page 1 - 1 - 3
Pneumatic Signals
The output signal of the pneumatic transmitter is air pressure, the magnitude of
which is directly proportional to the process variable being monitored.
page 1 - 1 - 4
Note that the transmitter signal output starts at 20 kPa(g) not 0 kPa(g).
A live zero allows control room staff to distinguish between a valid process
condition of 0% (a 20 kpa(g) reading) and a disabled transmitter or interrupted
pressure line (a 0 kpa(g) reading) providing a coarse rationality check
means.
Example
A 20 - 100 kPa(g) output pneumatic transmitter is used to the monitor water level
inside a tank. The calibrated range is 100 to 200 cm. of water above the base of
the tank. Calculate the output of the transmitter when the water level is at 175 cm.
above the base of the tank.
Solution
Span (difference between the upper and lower limit) of the transmitter output
= 100 kPa - 20 kPa
= 80 kPa(g)
Fraction of measurement
Output Signal
=
175 - 100 = 0.75
200 - 100
= (Fraction of Measurement) x (Signal Span) + Live Zero
= 0.75 x 80 + 20
= 80 kPa(g)
The biggest problem with pneumatic systems is that air is compressible. This
means that a pressure transient representing a process change will only travel
in the air line at sonic velocity (approximately 300 m/sec.). Long signal lines
must therefore be avoided to prevent substantial time delays a serious
drawback when you consider the size of our nuclear generating stations.
page 1 - 1 - 5
Electronic Signals
The relationship between the process condition and electronic transmitter signal
output is shown in Figure 3.
page 1 - 1 - 6
Solution
Span of transmitter 20 mA - 4 mA = 16 mA
Fraction of Measurement Change = Output Signal - Live Zero
Signal Span
= 12 - 4
16
= 0.5
Actual Process Change
The electronic current signals travel at speeds which approach the speed of
light.
These current signals can be transmitted over long distances without the
introduction of unnecessary time delays.
In this course, it is intended that all transmitted signals will be electronic with
the only use of other signals for the necessary final device operations.
page 1 - 1 - 7
By varying the resistance while the power supply voltage is kept at a constant
value, the amount of current in a loop can be proportionally manipulated.
The same two wires that power the transmitter also carry the signal. Using a
current signal minimizes the number of wires needed and the effect of
background noise, which is essentially induced voltage.
Readout devices which can either be current or voltage sensitive can be used
to provide a signal indication. To get a direct indication of the current signal, a
milli-ammeter can be connected in series in the loop. Alternatively, a voltage
sensitive device such as a voltmeter can be connected in parallel with a
dropping resistor to sense the potential developed across the resistor by the
current flow. (Figure 4).
page 1 - 1 - 8
Voltage sensitive instruments can respond to a voltage range of say 0.25 1.25V or 1 - 5V. To calculate the value of dropping resistor required, Ohm's
Law can be used.
Ohm's Law: V = IR
or
R = V/1
where
V = voltage across the resistor (Volt)
I = current (Amp)
R = resistance ()
Example
A dropping resistor is required to generate:
(a) a 0.25 - 1.25 V signal
(b) a
1 - 5 V signal
from a 4 - 20 mA current signal. Calculate the resistance value.
Solution
(a) When current = 20 mA, voltage = 1.25 V
By Ohm's Law,
R = V / I = 1.25V / (20x10-3)A
= 62.5
R = V / I = 5 V/ (20x10-3)A
= 250
page 1 - 1 - 9
Trend Recording
Inevitably, recorders can only carry a limited amount of chart paper and ink.
Periodic changing of chart paper and inking problems had made the recorder
one of the most troublesome instruments to service.
The jack will be wired across this dropping resistor so that the recorder will
respond to that loop signal when the lead connector is plugged in (Figure 5).
Of course, the concept of Trend Recording has been adopted into computerized
display systems and in these, selected variables can be chosen from a menu
for display purposes. However, automatic archiving of data can also be
implemented, even though that parameter has not been selected for display.
page 1 - 1 - 10
page 1 - 1 - 11
ASSIGNMENT: Lesson 1
1) Why is signal transmission vital in the operation of large industrial process
systems?
2) What is the accepted standard industrial range for pneumatic signals?
3) List two advantages and two disadvantages of a pneumatic system.
4) What is the standard instrument range for electronic signals?
5) Why are electronic signals used almost exclusively in industrial process
systems, particularly electrical generating stations?
6) Both pneumatic and electronic signals employ a "live zero". Explain the
purpose of this live zero.
7) A standard electronic transmitter is used to monitor the water temperature in a
vessel. The transmitter is calibrated such that it responds to the temperature
range of 50C - 100C. What is the transmitter output when the water
temperature is 85C? (Answer: 15.2 mA)
8) Explain briefly what a trend recorder is, and why one would be utilized.
page 1 - 1 - 12
2.
State the instrument which a given standard ISA symbol represents, with
respect to its function and mounting location.
3.
Sketch a simple flowsheet using standard ISA symbols, given the function
and location of different instruments and the type of transmission line
connecting them.
page 1 - 2 - 1
ISA Symbols
Line Symbols
Transmission lines which link different instruments are shown in Figure 1.
Instruments are identified by circles with lettered codes (two or three letters)
inserted. This lettered code shows the instrument type and function.
F=
L=
P=
T=
Flow
Level
Pressure
Temperature
The second letter in the coding indicates the function of the instrument, for
example:
FI =
FC =
LA =
LR =
PT =
TE =
Flow Indicator
Flow Controller
Level Alarm
Level Recorder
Pressure Transmitter
Temperature EIement
page 1 - 2 - 2
In some cases, when the instrument is used for two purposes or when the
function of the instrument has to be more clearly specified, a third letter is used,
for example:
page 1 - 2 - 3
Symbol Example
A level loop consists of:
Level transmitter
Level indicator
Field Mounted
Level controller
Level recorder
The level transmitter is connected directly to the tank and the rest of the
instruments are driven by the level transmitter and used to monitor and indicate the
level in a tank.
Assuming that the signal transmitted is electronic, draw a representative flow
sheet using ISA symbols.
Solution
The loop can be represented by ISA symbols as shown in Figure 3.
SUCCEEDING LETTERS
Measured Variable
Read-out or
Passive Function
CURRENT
ALARM
Output Function
Modifier
CONTROL
AVERAGE
CONTACT
ELEMENT
FLOW RATE
GLASS
HAND (MANUAL)
HIGH
INDICATE
LEVEL
MOTORIZED
PRESSURE
NEUTRON FLUX
RECORD
SOLENOID
TEMPERATURE
MEDIAN
RELAY
SWITCH
TRANSMIT
VALVE
WELL
TRANSDUCER
COMPUTE
POSITION
page 1 - 2 - 5
ASSIGNMENT: Lesson 1
1) State the functions and locations of the instruments represented by the
following ISA symbols:
page 1 - 2 - 6
MODULE OBJECTIVES:
At the end of this module, you will be able to:
1.
Pressure Unit
Pressure is defined as force exerted on a unit surface area. Mathematically, we
have:
P = F/A
where
P = Pressure (Pa)
F = Force (N)
A = Area (m2)
Since the Pascal (Pa) is a very small unit (1 Pa = 1.45 x 10-4 PSI), it is more
common to use units of kPa (1 kPa = 1000 Pa) and MPa (1 MPa = 1000 kPa or
1 x 106 Pa) when we deal with the pressures we encounter in in typical
industrial process applications.
page 1 - 3 - 1
Gauge pressure is the unit we encounter in everyday work (e.g. tire ratings are
in gauge pressure).
A gauge pressure device will indicate zero pressure when bled down to
atmospheric pressure (i.e. gauge pressure is in reference to atmospheric
pressure that pressure above atmospheric pressure).
Gauge pressure is denoted by a (g) at the end of the pressure unit (e.g. kPa(g)).
Absolute pressure includes the effect of atmospheric pressure with the gauge
pressure. It is denoted by an (a) at the end of the pressure unit (e.g. kPa(a).)
Note a reading of less than 101.3 kPa(a) indicates a vacuum condition. For
example, a typical condenser pressure is 5 kPa(a) or a vacuum of 96.3 kPa.
Example
The pressure of the gas in a tank is 1000 kPa(a). What is the pressure in gauge
units?
Solution
Gauge Pressure = Absolute Pressure - Atmospheric Pressure
Therefore, Gauge Pressure
Figure 1 illustrates the relationship between absolute and gauge, note that the
base point for gauge scale (0 kPa(g)) is taken as 101.3 kPa(a) atmospheric
pressure
page 1 - 3 - 2
Pressure Measurement
page 1 - 3 - 3
Figure 2. Primary Pressure Elements Capsule, Bellows & Spring Opposed Diaphragm
page 1 - 3 - 4
They are usually capable of measuring Differential Pressure (that is, the
difference between a high pressure input and a low pressure input) and hence
they are usually called DP transmitters or DP cells.
page 1 - 3 - 5
page 1 - 3 - 6
Silicone oil is used to fill the cavity between the diaphragm for even pressure
transmission. Most DP capsules can withstand static pressure of up to 14 MPa
(2000 psi) on both sides of the capsule without any damaging effect.
However, the sensitive range for most DP capsules is quite low. Typically they
are sensitive up to only a few hundred kPa of differential pressure.
Differential pressure that is significantly higher than the capsule range may
damage the capsule permanently. When choosing a capsule for pressure
measurement, it is important to match the capsule range with the anticipated
differential pressure.
page 1 - 3 - 7
DP Transmitter Installation
A DP transmitter is used to measure the gas pressure (in gauge scale) inside
a vessel.
In this case, the low pressure side of the transmitter is vented to atmosphere,
and the high pressure side is connected to the vessel through an isolating
valve.
page 1 - 3 - 8
ASSIGNMENT: Lesson 1
1) Sketch a bar chart and state the relationship between absolute pressure and
gauge pressure. Clearly indicate a vacuum scale on this bar chart.
2) Sketch a typical DP transmitter device and explain the principle of operation.
3) Sketch and describe a DP transmitter low pressure installation used to
measure the gauge pressure in a closed tank.
4) If a transmitter is calibrated to measure a pressure of 0-80 KpaG in order to
develop a 4-20 mA current signal; what pressure will correspond to a signal of
13.5 mA? (answer: 47.5 kPaG)
page 1 - 3 - 9
2.
3.
4.
5.
Briefly explain the principle of operation of a closed tank, wet leg, level
measurement installation.
6.
7.
8.
page 1 - 4 - 1
The level of liquid inside a tank can be determined from the pressure reading
at the base of the tank, if the specific gravity of the liquid is constant.
page 1 - 4 - 2
If the tank is open to atmosphere, the high pressure side of the D/P level
transmitter will be connected to the base of the tank.
The low pressure side will be vented to atmosphere.
In this manner, the level transmitter acts as a simple pressure transmitter. We
have:
Phigh = Patm + S H
Plow = Patm
page 1 - 4 - 3
If the tank is closed, and a gas phase exists on top of the liquid, this gas phase
pressure must be compensated for.
A change in the gas pressure will cause a change in the measured pressure
resulting in a corresponding transmitter output not related to level.
Moreover, the pressure exerted by the gas phase may be so high that the
hydrostatic pressure of the liquid level column becomes insignificant. For
example, the measured hydrostatic head in a steam generator may be only
three meters (30 kPa or so), whereas the steam pressure is typically 5MPa.
Phigh
= Pgas + S H
Plow
= Pgas
DP
= Phigh - Plow = S H
The effect of the gas pressure is canceled and only the pressure due to the
hydrostatic head of the liquid is sensed.
When the low pressure impulse line is connected directly to the gas phase
above the liquid level, it is called a dry leg.
page 1 - 4 - 4
However, as already mentioned, the gas pressure (Pgas.) is often much higher
than the hydrostatic pressure (i.e. level head) that is to be measured.
If the gas pressure is accidentally applied to only one side of the DP capsule
(say during installation or removal of the DP transmitter), overranging of the
capsule could occur and the capsule would be damaged.
A three valve manifold is a device that is used to ensure that the capsule will
not be over-ranged and allows isolation of the transmitter from the process
loop.
The three valve manifold consists of two block valves a high pressure and a
low pressure block valve - and an equalizing valve.
Figure 3:
During operation, the equalizing valve is closed and the two block valves are
open to connect the process pressure across the D/P cell.
When the transmitter is put into or removed from service, the valves must be
operated in such a manner that the high pressure gas phase is not applied to
only one side of the DP capsule.
page 1 - 4 - 5
1.
2.
3.
4.
5.
6.
page 1 - 4 - 6
Reversal of the previous steps allows the d/P transmitter to be removed from
service The starting operating state is with the equalizing valve closed and
both block valves open.
1.
Close the low pressure block valve to trap pressure in the low side
check for leaks and ensure the indicated d/P does not change.
2.
3.
4.
Bleed down (i.e. vent) the pressure trapped in the d/P cell body should
continue to read zero d/P
5.
page 1 - 4 - 7
If the gas phase is condensable, such as steam, condensate will form in the
low pressure impulse line resulting in a column of liquid which exerts extra
pressure on the low pressure side of the transmitter (i.e. transmitter will read in
error low).
A disadvantage of the dry leg that restricts its use is the frequent maintenance
that may be required. One example of a dry leg application is the measurement
of liquid level in a closed tank with a purge cover gas pressure.
page 1 - 4 - 8
In a wet leg system, the low pressure impulse line is completely filled with
liquid (usually the same liquid as the process), and hence the name "wet leg".
identical manner to the dry leg system. Figure 5 shows a typical wet leg
installation.
page 1 - 4 - 9
page 1 - 4 - 10
The vapour from the gas phase will condense in the wet leg and the catch tank.
The catch tank, with the sloped interconnecting line back to the tank, maintains
a constant hydrostatic pressure on the low pressure side of the level
transmitter.
This pressure error, being a constant low signal component, can easily be
corrected for by calibration.
If the tank is located outdoors, trace heating of the wet leg might be necessary
to prevent it from freezing. Steam lines or an electric heating element can be
wound around the wet leg to keep the temperature of the condensate above its
freezing point.
Note the two sets of drain valves. The transmitter drain valves would be used
to drain (bleed) the transmitter only. The two drain valves located immediately
above the three valve manifold are used for impulse and wet leg draining or
filling.
Isolate the d/P transmitter using the standard three valve isolating
procedure (described earlier in this module).
(b)
Close the HP and LP isolating valves (isolate process). This gives two point
isolation.
(c)
Open pressure relief valve (bleed system pressure from wet leg). Reclose
pressure relief valve and re-open after five minutes.
If there is a further release of pressure the upper isolation valve is passing.
If no further leakage then leave valve open.
(d)
Bleed system pressure from d/P cell using the transmitter drain valves.
page 1 - 4 - 11
Zero Suppression
In some cases, it is impossible to mount the level transmitter right at the base
level of the tank. Say for maintenance access purposes, the level transmitter
must be mounted X meters below the base of an open tank as shown in Figure 6.
DP = Phigh - Plow = S H + S X
page 1 - 4 - 12
Zero Suppressioncontinued
That is, the pressure on the high pressure side of the d/P cell is always higher
than the actual pressure exerted by the liquid column in the tank by (S X) so
the reading will be in error high.
This constant pressure would cause an output signal that is higher than 4 mA
when the tank is empty and above 20 mA when it is full (if the transmitter is
calibrated 4-20mA for the S H range.)
Zero Elevation
When a wet leg installation is used (see Figure 7), the low pressure side of the
level transmitter will always experience a higher hydrostatic pressure than the
high pressure side.
This is due to the fact that the height of the wet leg (X) is always just greater
than the maximum height of the liquid column (H) inside the tank.
Phigh = Pgas + S H
Plow = Pgas + S X
DP = Phigh - Plow = S H - S X = -S(X - H)
page 1 - 4 - 13
If the transmitter is not calibrated for this constant negative error (-S
transmitter output would read low at all times.
page 1 - 4 - 14
X), the
X) is needed to
A gas (called purge gas) is allowed to pass through the bubbler tube.
Consider that the tank is empty. In this case, the gas will escape freely at the
end of the tube and therefore the gas pressure inside the bubbler tube (called
back pressure) will be at atmospheric pressure.
However, as the liquid level inside.the tank increases, pressure exerted by the
liquid at base of the tank and at the opening of the bubbler tube increases.
The hydrostatic pressure of the liquid acts as a pressure seal which restricts
the escape of purge gas from the bubbler tube.
As a result, the gas pressure in the bubbler tube will continue to increase until it
At this point the back pressure in the bubbler tube is exactly the same as the
hydrostatic pressure of the liquid and it will remain constant until any change in
the liquid level occurs.
Any excess supply pressure will escape as bubbles through the liquid.
page 1 - 4 - 15
As the liquid level rises, the back-pressure in the bubbler tube increases
proportionally, since the density of the liquid is constant.
In an open tank installation, the bubbler tube pressure is connected to the high
pressure side of the transmitter, while the low pressure side is vented to
atmosphere. The output of the transmitter will be proportional to the tank level.
A constant differential pressure relay is often used in the purge gas supply
line to ensure that bubbling action occurs at all tank levels.
This ensures that bubbling will occur for the maximum tank level and the flow
rate does not increase at low tank levels in such a way as to cause excessive
disturbances at the surface of liquid.
Note that bubbling action has to be continuous, or the measurement signal will
not be accurate.
Otherwise, the gas bubbling through the liquid will pressurize the gas space to
a point where bubbler supply pressure cannot overcome the static pressure.
Also, as in the case of a closed tank inferential level measurement system, the
low pressure side of the level transmitter has to be connected to the gas space
in order to compensate for the effect of gas pressure.
In this way, the bubbler medium (say helium) back-pressures are applied
against both the high side and low sides of the d/P cell to provide a differential
pressure signal proportional to the level in the closed tank.
page 1 - 4 - 16
State the relationship between pressure at the base of the tank and liquid
column height.
2.
Sketch a level transmitter installation for a closed tank application. Show all
necessary pipe connections.
3.
4.
Describe an operating sequence for the three valve manifold when a d/P
transmitter has to be placed into service. Assume that the static pressure
could over-range the capsule if incorrectly applied.
5.
What is the difference between a "dry" leg and a "wet" leg in closed tank
application?
6.
In a wet leg installation, the low pressure side of the DP transmitter always
experiences a higher pressure than the high pressure side. What would be
the effect of reversing the connections such that the wet leg is connected to
the high pressure side of the transmitter.
7.
When a wet leg installation is used, the "zero" has to be elevated. Explain
the reason for this zero elevation.
8.
9.
List the two main advantages of the bubbler system in a nuclear system.
page 1 - 4 - 17
MODULE OBJECTIVES:
At the end of this module, you will be able to:
1.
2.
3.
Sketch a flow measurement installation including an orifice plate, threevalve manifold and flow d/P transmitter.
4.
5.
State an application for each of a venturi tube, flow nozzle and elbow taps
in an industrial process plant.
page 1 - 5 - 1
page 1 - 5 - 2
If the flow is steady, then the same quantity of fluid must pass through the two
different sections of the pipework in a given time. Section 2 has a smaller
cross-sectional area than Section 1, therefore, the fluid must travel faster in
Section 2 than in Section 1.
Q = AV = AK(h) _
Q = flow quantity
A= flow restriction area
K = flow constant
h= differential pressure measured across the restriction
The flow rate is proportional to the square root of the differential pressure
developed across a flow restriction.
This is the principle behind flow metering the flow can be calculated if we
measure the differential pressure across a defined flow restriction
In order to obtain a linear flow signal, we must always take the square root of
the measured differential pressure
page 1 - 5 - 3
Primary Devices
Orifice Plate
page 1 - 5 - 4
The orifice has a diameter that is between 30% to 75% of the inside diameter of
the pipe work in which it is installed.
The ratio of orifice bore diameter (d) to the pipe inside diameter (D) is called
the Beta Ratio (b ).
b = d/D
For example, a b ratio of 0.5 indicates that the orifice bore diameter is 50% of
the pipe inside diameter.
When an orifice plate is installed in a flow line (usually clamped between a pair
of flanges), the increase of fluid flow velocity through the reduced area at the
orifice develops a differential pressure across the orifice.
The differential pressure generated is related to the b value of the orifice plate.
The smaller the b ratio, the higher the differential pressure.
With an orifice plate in the pipe work, static pressure increases slightly
upstream of the orifice (due to back pressure effect) and then decreases
sharply as the flow passes through the orifice.
Flow downstream from an orifice reaches a minimum at a point called the vena
contracta where the velocity of the flow is at a maximum.
Beyond this point, static pressure starts to recover as the flow slows down.
In addition some pressure energy is converted to sound and heat at the orifice
plate.
page 1 - 5 - 5
Flange taps are the most widely used pressure tapping location.
They are holes bored through the flanges, located one inch upstream and one
inch downstream from the respective faces of the orifice plate.
The upstream (H) and downstream (L) sides of the orifice plate are connected
to the high pressure and low pressure sides of a d/P transmitter.
As in the case of level measurement, the flowing fluid static pressure in the
pipework could be many times higher than the differential pressure created by
the orifice plate.
In order to use a capsule that is sensitive to low differential pressure, a threevalve manifold has to be used to protect the d/P capsule from being overranged.
page 1 - 5 - 6
The same procedure for valving in and out the three valve manifold in a level
installation is applied to flow installation.
2.
Open the equalizing valve d/P cell should read zero differential.
3.
Open the high pressure block valve to apply high pressure to both sides of
the d/P cell d/P cell should read zero differential.
4.
Close the equalizing valve trap high pressure in both sides, check for
leaks d/P cell should still read zero differential.
5.
page 1 - 5 - 7
1.
Close the low pressure block valve this traps the low pressure in the d/P
cell and the differential reading should be unchanged.
2.
Open the equalizing valve to equalize the high pressure across the d/P cell.
Differential reading should now be zero. Note that no significant flow passes
through the equalizing valve as all three valves are not open at the same
time.
3.
Close the high pressure block valve. Transmitter is now out of service but
pressure trapped in the d/P cell body must be bled away.
Corner taps which are located right at the upstream and downstream faces of
the orifice plates (Figure 5).
page 1 - 5 - 8
Vena contracts taps, are located one pipe inner diameter upstream and at the
point of minimum pressure, usually one half pipe inner diameter downstream
Pipe taps, which are located two and a half pipe inner diameters upstream and
eight pipe inner diameters downstream.
When an orifice plate is used with one of the standardized pressure tap
locations, an on-location calibration of the flow transmitter is not necessary.
Once the ratio and the kind of pressure tap to be used are decided, there are
empirically derived charts and tables available to facilitate calibration.
page 1 - 5 - 9
2.
3.
4.
Easy replacement.
2.
Cannot be used on dirty fluids, slurries or wet steam as erosion will alter the
differential pressure generated by the orifice plate.
Venturi Tubes
For applications where high permanent pressure loss is not tolerable, a venturi
tube (Figure 7) can be used.
Because of its gradually curved inlet and outlet cones, almost no permanent
pressure drop occurs.
This design also minimizes wear and plugging by allowing the fluid flow to
sweep suspended solids through without obstruction.
page 1 - 5 - 10
Flow Nozzle
A flow nozzle is also called a half venturi with flow characteristics between an
orifice plate and a venturi tube. Figure 8 shows a typical flow nozzle installation.
Because of its streamlined contour, the flow nozzle has a lower permanent
pressure loss than an orifice plate (but higher than a venturi).
The differential the flow nozzle generates is also lower than an orifice plate
(but again higher than the venturi tube).
Flow nozzles are widely used for flow measurements at high velocities.
They are more rugged and more resistant to erosion than the sharp-edged
orifice plate, and therefore are typically used in cases where the flow rate is
high and the flow has a high gas content.
page 1 - 5 - 11
Elbow Taps
page 1 - 5 - 12
State the relationship which exists between flow and differential pressure.
2.
What is a primary flow device? What are four commonly used primary
devices in process plant flow measurement applications?
3.
4.
Why is the selection of the type of pressure tap important to the final flow
metering installation performance (i.e. differential pressure range, etc).
5.
What is the major advantage and application of the following primary
devices:
a)
venturi tubes
b)
c)
elbow taps?
page 1 - 5 - 13
MODULE OBJECTIVES:
At the end of this module, you will be able to:
1.
2.
3.
4.
5.
6.
7.
8.
page 1 - 6 - 1
Temperature Instrumentation
Temperature measurement is divided into two different types - local and control
room (remote) measurement.
Often local measurement is used when no control function is required and i s
usually for indication purposes only.
If heat is applied to the strip, the metal with the higher coefficient of expansion
will expand more than the other.
page 1 - 6 - 2
Bimetallic Thermometer
If a pointer is attached
to the end of the
bimetallic strip,
indication of the
temperature sensed by
the strip can be
obtained.
page 1 - 6 - 3
When heat is applied to the junction, a voltage, in the range of millivolts (mV), is
generated. A thermocouple is therefore said to be self-powered.
If temperature T1 is higher than T2, then the voltage generated at Junction 1 will
be higher than that at Junction 2.
In the above circuit, the polarity of the voltage generated at the two junctions
oppose each other.
The net voltage (circuit emf) shown on the galvanometer depends on the
relative magnitude of the voltages at the two junctions.
The relationship between circuit emf and the junctions emf is:
Circuit emf = Measurement emf - Reference emf
If circuit emf and reference emf are known, measurement emf can be
calculated.
page 1 - 6 - 4
However, upon closer examination, there are actually more than two junctions
in existence.
There are two additional junctions formed by the metal C, which is the metal
used inside the transmitter, and the metal A.
page 1 - 6 - 5
From Figure 5 it can be seen that the emf generated by the metal A and C
junctions are equal and opposite to each other in polarity.
It has been proved that for thermocouple circuits where a carefully selected
third metal has been added, the reference junction itself can actually be
eliminated.
The emf generated by the junctions of the third metal is equivalent to the emf
that would be generated by the reference junction at the same temperature.
page 1 - 6 - 6
Since we know the total circuit emf and the reference junction emf, the
measurement junction emf can easily be obtained by the relationship:
Measurement emf = Total Circuit emf + Reference emf
The transmitter, when properly calibrated, will produce a 4-20 mA signal that is
directly proportional to the measurement emf and hence the process
temperature.
page 1 - 6 - 7
Thermocouple Construction
Several combinations
thermocouples.
A popular type of thermocouple is the "J" type which consists of iron and
constantan (a nickel-copper alloy) wires with very high purity.
The "J" type thermocouple has a fairly linear relationship between temperature
and millivolt output in the range of 0 to 300C, which suits many industrial
applications.
of
metals
are
used
for
the
construction
of
Extension grade wires are made of the same, or with the same characteristic,
materials as the thermocouple wires they are connected to.
Extension grade wires can be of lower purity than the thermocouple wires or be
of a cheaper material. (Important since some thermocouples use platinum a s
one of the metals).
Thermocouples are not used in areas where high radiation fields are present
(for example, in the reactor vault).
Since the signal from thermocouple is also a voltage, the induced voltage will
cause an error related to radiation fields sensed in the temperature transmitter
output.
page 1 - 6 - 8
grade
thermocouple
wires
or
R = resistance (W)
P = resistivity (W-M)
l = length (m)
A = cross-sectional area (m2)
By measuring the resistance change of the metal, the temperature of the metal
can be determined.
Several different pure metals (such as platinum, nickel and copper) can be
used in the manufacture of RTDs.
A typical RTD probe contains a coil of very fine metal wire, allowing for a
relatively large resistance change without a great space requirement.
In applications that require high accuracy and linearity, platinum RTDs are used
as process temperature monitors.
page 1 - 6 - 9
It can be shown that the galvanometer in the Wheatstone bridge detector reads
null, when
R1
R3
=
R 2 RTD
By keeping the resistance values for R1, R2 and R3 constant, the resistance of
the RTD can be determined by the reading the galvanometer.
A problem can exist when the RTD is installed some distance away from the
transmitter.
Since the connecting wires are long, the resistance of the wires changes a s
ambient temperature fluctuates. The variations in wire resistance could
introduce an error in the transmitter.
page 1 - 6 - 10
From Figure 8, it can be seen that the resistance of the right branch of the
Wheatstone bridge is R1 + R2 + RW2.
Since RW1 = RW2, the result is that the resistances of the lead wires cancel and
therefore the effect of the connecting wires is eliminated.
page 1 - 6 - 11
Thermal Wells
page 1 - 6 - 12
A thermal well is basically a hollow metal tube with one end sealed that is
usually mounted permanently in the pipe work.
The sensor is inserted into the well and makes contact with the sealed end.
An example of the temperature response for bare and thermal well installed
sensors is shown in Figure 10.
This thermal lag, however, can be decreased by minimizing the air space
between the sensor and the well.
Figure 10: Response Curves of Bare Detector and Thermal Well Installation.
page 1 - 6 - 13
mV
-7.89
-7.78
-7.66
-7.54
-7.54
-7.40
-7.27
-6.97
-6.82
-6.66
-6.50
-6.33
-6.16
-5.98
-5.80
-5.61
-5.42
-5.23
-5.03
-4.83
-4.63
-4.42
-4.21
-4.00
-3.78
-3.56
-3.34
-3.12
-2.89
-2.66
-2.43
-2.20
-1.96
-1.72
-1.48
-1.24
-1.00
-0.75
-0.50
-0.25
mV
mV
mV
mV
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
85
90
95
100
105
110
115
120
125
130
135
140
145
150
155
160
165
170
175
180
185
190
195
200
205
210
215
220
225
230
235
240
245
250
0.00
0.25
0.50
0.76
1.02
1.28
1.54
1.80
2.06
2.32
2.58
2.85
3.11
3.38
3.65
3.92
4.19
4.46
4.73
5.00
5.27
5.54
5.81
6.08
6.36
6.63
6.90
7.18
7.45
7.73
8.00
8.28
8.56
8.84
9.11
9.39
9.67
9.95
10.22
10.50
10.78
11.06
11.34
11.62
11.89
12.17
12.45
12.73
13.01
13.28
13.56
255
260
265
270
275
280
285
290
295
300
305
310
315
320
325
330
335
340
345
350
355
360
365
370
375
380
385
390
395
400
405
410
415
420
425
430
435
440
445
450
455
460
465
470
475
480
485
490
495
500
13.84
14.12
14.39
14.67
14.94
15.22
15.50
15.77
16.05
16.33
16.60
16.88
17.15
17.43
17.17
17.98
18.26
18.54
18.81
19.09
19.37
19.64
19.92
20.20
20.47
20.75
21.02
21.30
21.57
21.85
22.13
22.40
22.68
22.95
23.23
23.50
23.78
24.06
24.33
24.61
24.88
25.16
25.44
25.72
25.99
26.27
26.55
26.83
27.11
27.39
505
510
515
520
525
530
535
540
545
550
555
560
565
570
575
580
585
590
595
600
605
610
615
620
625
630
635
640
645
650
655
660
665
670
675
680
685
690
695
700
705
710
715
720
725
730
735
740
745
750
27.67
27.95
28.23
28.52
28.80
29.08
29.37
29.65
29.94
30.22
30.51
30.80
31.08
31.37
31.66
31.95
32.24
32.53
32.81
33.11
33.41
33.70
33.99
34.29
34.58
34.88
35.18
35.48
35.77
36.08
36.38
36.69
36.99
37.30
37.60
37.91
38.22
38.53
38.84
39.15
39.47
39.78
40.10
40.41
40.73
41.05
41.36
41.68
42.00
42.32
755
760
765
770
775
780
785
790
795
800
805
810
815
820
825
830
835
840
845
850
855
860
865
870
875
880
885
890
895
900
905
910
915
920
925
930
935
940
945
950
955
960
965
970
975
980
985
990
995
1000
42.64
42.96
43.28
43.60
43.92
44.25
44.57
44.89
45.21
45.53
45.85
46.18
46.50
46.82
47.14
47.46
47.78
48.09
48.41
48.73
49.04
49.36
49.67
49.98
50.27
50.57
50.87
51.16
51.46
51.76
52.05
52.35
52.64
52.94
53.24
53.53
53.83
54.12
54.44
54.72
55.02
55.32
55.61
55.91
56.20
56.61
56.80
57.10
57.39
57.69
page 1 - 6 - 14
2.
3.
Why are extension grade wires needed when connections have to be made
between the thermocouple and the temperature transmitter?
4.
What full scale mV range should be specified for a J-couple installation with
a constant cold junction of 30 C and a hot junction which ranges from 30 to
250 C?
5.
6.
7.
8.
9.
page 1 - 6 - 15
MODULE OBJECTIVES:
At the end of this module, you will be able to:
1.
2.
State and sketch the three flow characteristics for the most common
globe valves.
3.
State a typical application for each of the three flow characteristics and
explain why it is the most appropriate selection for that application.
4.
State the effect of unbalanced force on valve position and explain with
an example, how bench setting would correct this problem.
5.
6.
7.
Sketch and describe a system pump head vs flow curve set to define
installed valve differential conditions.
8.
Explain, with a diagram, how a three-way solenoid valve can be used for
ON/OFF control of a pneumatic valve.
9.
State the formula which describes a control valve Cv factor. What is the Cv
for a valve which will pass a water flow of 100 USGPM with a pressure
drop of 25 psi? What flow would this valve pass when the pressure drop
is 49 psi?
10.
State why it is often advisable to use different sized valves in parallel when
the process variable has a very large range.
page 1 - 7 - 1
The final control element in a system is used to vary the flow of a manipulated
variable in an attempt to maintain a process parameter at a desired setpoint.
Final control elements include control valves, metering pumps, dampers and
louvers, variable pitch fan blades, and electrically driven control devices.
The control valve is the most widely used type of final control element and it
must perform satisfactorily with a minimum amount of maintenance attention,
even in severe conditions of temperature, pressure, corrosion and
contamination.
page 1 - 7 - 2
Globe Valve
Globe valves are the most frequently encountered control valves in process
plants. Figure 1 shows the side view of a typical globe valve, which is named
after its globular shaped valve body.
1.
The valve actuator which converts electrical or pressure energy into valve
stem movement which creates the regulating effect of the valve body.
2.
The valve body which contains and regulates the fluid flow.
page 1 - 7 - 3
The globe valve body itself is made up of the components shown in Figure 2.
The bonnet assembly is the part of the valve body through which the valve plug
stem moves.
The valve stem extends through the bonnet to permit positioning of the valve
plug, and therefore provide a variable restriction to the fluid flow.
page 1 - 7 - 4
a) Direct Acting
In a direct acting valve body, a downward movement of the valve plug stem
results in the valve closing (Figure 3(a)).
In a reverse acting valve body, a downward movement of the valve plug stem
results in the valve opening (Figure 3(b)).
page 1 - 7 - 5
Valve Actuators
A control valve actuator is a device which is used to drive the valve plug stem
and therefore sets the position of the plug with respect to the valve seat.
The air pressure applied on the diaphragm develops a working force. This
force is transmitted to the actuator stem via the diaphragm plate, which is a
supportive metal disk attached to the diaphragm.
The actuator spring provides a restoring force which positions and returns the
actuator stem.
The travel indicator (a pointer attached near the stem connector) indicates the
valve travel on the indicator scale.
The actuator is supported rigidly on the valve bonnet assembly by the yoke.
The actuator stem is connected by the stem connector to the valve plug stem.
page 1 - 7 - 6
The diameter of the diaphragm plate determines the force that will be applied to
the actuator stem. For example, if the maximum input signal pressure is 100
kPa and the plate diameter is 30 cm, then:
Although the signal pressure of 100 kPa seems to be fairly low, a substantial
force can still be generated if the diaphragm diameter is large.
A direct acting actuator will cause the actuator stem to be pushed downwards
as a result of applying signal air to the top of the diaphragm (Figure 5(a)).
The reverse acting actuator will push the actuator stem upwards as signal air i s
applied to the bottom of the diaphragm (Figure 5(b)).
page 1 - 7 - 7
Valve Action
Figure 6(a)
Air to Close (A/C) Valve
Figure 6(b)
Air to Open (A/0) Valve
An air to close (A/C), and therefore fail open valve, can be obtained with the
combination of a reverse acting actuator and a reverse acting valve body or a
direct acting actuator and a direct acting valve body. (Figure 6(a)).
Similarly, an air to open (A/O), and therefore fail close valve, can be obtained
with a combination of direct actuator and reverse body or reverse actuator and
direct body (Figure 6(b)).
Note that often it is not possible to determine the over all action of a valve by
observation alone.
Reference to the valve nameplate or flowsheet
identification is usually necessary for positive identification of the valve action.
page 1 - 7 - 8
The flow characteristic of a valve is the relationship between the flow capacity of
the valve and the valve plug position.
Flow capacity of a valve is the flowrate of the fluid through the valve under
specified conditions.
A standard method of defining a valve's flow capacity is to use the valve flow
coefficient (CV).
The valve flow coefficient is a function of flowrate of a specified fluid through the
valve at a specified pressure drop across the valve (DP). (Usually expressed in
U.S. gallons per minute
at a DP of 1 psi, i.e., not
S.I.)
Mathematically, flowrate
is related to valve
coefficient (CV)
and
pressure drop across
the valve (DP) by the
equation:
Q = CV P / S
where
Q = flowrate of the fluid
S = fluid specific gravity
Therefore CV = Q S / P
CV's are often used to compare valves with each other. The valve with the
higher CV will have a higher flow capacity.
The most important valve trim component is the valve plug. The valve plug can
be shaped to throttle the fluid flow with different flow characteristics.
Valve flow characteristic curves are usually shown by plotting CV versus valve
stem travel. The CV at each increment of stem travel is determined by
measuring the fluid flowrate with a DP of 1 psi appearing across the valve.
Flow characteristics fall into three major categories: quick opening, linear and
equal percentage.
page 1 - 7 - 9
The plug is designed to provide full capacity with a very short stem travel.
Figure 8(b) illustrates the relationship between valve travel and Cv of the quick
opening valve.
As shown in Figure 8(b), quick opening valve plugs achieve 80% of maximum
Cv with only 50% valve travel.
Figure 8a
page 1 - 7 - 10
The triplicated poison injection valve arrangement increases the reliability of the
system.
When a trip signal is received by the valves, they open to admit high pressure
helium to the poison tank and therefore inject poison into the reactor.
Total response time for the poison injection system is typically under 1.5
seconds.
page 1 - 7 - 11
Figure 10(a)
A Typical Linear Valve Plug
Figure 10(b)
Flow Characteristic of Linear Valve
A typical linear valve plug is shown in Figure 10(a). Figure 10(b) shows the flow
characteristic of a linear valve plug.
If DP, which is the pressure drop across the valve, can be kept constant, the
flowrate will be linearly proportional to the valve travel.
page 1 - 7 - 12
One application of a linear globe valve is in the primary heat transport (PHT)
feed and bleed system for PHT pressure control.
Linear globe valves are used as feed valves to throttle the discharge of the
pressurizing pumps (Figure 11).
The pressures at the discharge of the pressurizing pumps and the PHT system
are fairly stable.
Therefore the pressure drop across each valve is essentially constant. In this
installation, the flow rate is linearly proportional to the valve travel.
page 1 - 7 - 13
An equal percentage valve gets its name because for equal increments in valve
plug travel, the valve coefficient will change by the same predetermined
percentage over its original value.
For example, (refer to Figure 12(b)) if the valve plug position increases from
50% to 60% (an increase of 10%) the Cv increases from 17.5% to 25% (a 43%
increase over 17.5%).
For the same percentage (10%) increase in valve travel, say from 60% to 70%,
the Cv increases from 25% to 36%, again a 43% increase when compared with
the then initial Cv of 25%.
Equal percentage valves are used in situations where there is a highly varying
pressure drop (DP) across the valve.
page 1 - 7 - 14
page 1 - 7 - 15
Recall that for a typical centrifugal pump, pump head diminishes as flowrate
increases. Also, as flowrate increases, system pressure, loss (static plus
dynamic) increases.
From Figure 13, it can be seen that the difference between the pump head
curve (line 1) and system pressure loss (line 2) curve is the pressure (DP) that
is allocated for the valve, (line 3).
An equal percentage valve with flow characteristic as shown in line 4 is used for
this purpose. The result is a Linear relationship between flowrate and valve Iift
as represented by line 5.
page 1 - 7 - 16
In this system, the light water flow to the liquid zone is varied by valve CV1. The
outflow from the liquid zone is kept constant.
In order to vary the water level in the zone, the inflow has to be increased or
decreased.
Valve CV1 has to control the inflow over the range 0.2 - 0.9 liters /sec. Because
of this relatively large flow change, the system frictional (piping) losses will vary
and be significant.
page 1 - 7 - 17
Bench Setting
The valve is usually calibrated (by adjusting the spring force) such that a 20 kPa
signal applied to the actuator will cause the valve to be fully closed whereas a
100 kPa signal will cause it to be fully open.
However, these settings do not take into account the pressure that is exerted by
the process fluid on the valve plug when it is installed in a flow system.
If the fluid pressure is high, the resultant force acting up on the valve plug will
be able to offset part of the downward force exerted by the actuator.
Assume the upward force exerted on the valve plug by the fluid is equivalent to
the downward force generated by 10 kPa of the actuator pressure. When the
signal pressure is 20 kPa, the net pressure effect on the diaphragm is only (20
- 10 kPa) 10 kPa. This will cause the valve to not start to open when the signal
is 20 KPa - may have to go to 30 KPa to open
Bench setting is the calibrating technique used to take into account the
anticipated force exerted by the process fluid.
For the air to open valve described above, bench setting would result in the
valve spring being calibrated such that the valve is fully closed at 10 kPa and
fully open at 90 kPa actuator pressure (with no line pressure present - on the
bench, so it will be correct once installed).
page 1 - 7 - 18
A globe valve can contain either one or two plugs. When there is only one plug,
the valve is called single ported (refer to Figure 2 at the beginning of this
module).
When there are two plugs as shown in Figure 16, it is called a double-ported
globe valve.
The fluid flows through the valve ports in opposite directions and therefore
generates forces that offset each other.
As a result, only a relatively small actuator force is needed for positioning the
valve plugs.
This makes the double-ported globe valve suitable for high pressure
applications.
In some CANDU plants, for example, double-ported globe valves are used to
control feedwater flow to the boilers, where both pressure (7 MPa) and flowrate
(250 kg/sec) are high.
page 1 - 7 - 19
Valve Positioners
Pneumatic valve positioners are the most commonly used valve accessories.
A valve positioner is a device which will accurately position a control valve in
accordance with the pneumatic control signal.
The control signal is routed to the positioner where comparison of the valve
position (actual) to the control signal (desired) is used to develop an output
pneumatic signal which operates the valve actuator.
The positioner compares the control signal (the requested valve position) with
the actual valve position through the mechanical feedback linkage.
If the valve position is incorrect, the positioner will either load or exhaust air
from the valve actuator until the correct valve position is obtained.
A positioner requires both a control signal and an instrument supply air for
normal operation. Most positioners come equipped with three gauges to
indicate supply air pressure, control signal pressure and actuator diaphragm
signal (output) air pressure,.
page 1 - 7 - 20
2.
3.
4.
(b)
The positioner has a larger volumetric output capacity than other pneumatic
devices, say an I/P transducer (typically 40 - 50 cfm vs 4 - 5 cfm). With a
positioner, quicker fill of the actuator and therefore faster valve speed of
response can be achieved.
5.
6.
Allows split range operation. In a split range control loop, one controller i s
used to drive two control valves.
page 1 - 7 - 21
SPLIT-RANGE CONTROL
An example of a split-range control loop is the wide range heat transport (PHT)
pressure control loop as shown in Figure 18. In this system, both valves use
the same 4 - 20 mA signal from the controller.
The feed valve is A/C and the bleed valve is A/O. (Note the different range of
signal the feed and bleed valve responds to.)
Under normal conditions, i.e., PHT pressure constant, both valves are closed,
i.e., signal at 63% for both valves).
If the pressure in the PHT system starts to increase, the PT will send an
increasing signal to the controller. This results in an increasing control signal
applied to both the bleed and the feed valve. The bleed valve will open more
(with the feed valve closed), removing more D2O from the PHT system, while
the feed valve stays closed. The net result is the pressure in PHT system
remains constant.
The opposite occurs if the pressure decreases, i.e., decreasing signal to both
valves - feed increases while bleed decreases.
Figure 18: Split Range Control Loop for PHT Feed and Bleed Pressure Control.
page 1 - 7 - 22
Solenoid Valves
The energized solenoid coil acts as an electromagnet which pulls the plunger
and the valve disc upwards.
The closing action of the valve is achieved by the weight of the plunger, valve
stem and disc. Once the disc comes close to its seat, flow (from left hand side)
will snap the valve tightly shut.
page 1 - 7 - 23
This arrangement, depending on the valve size, may be much more reliable,
more powerful, less expensive and faster responding than using an all electric
control valve.
page 1 - 7 - 24
When the solenoid valve is energized, 100 kPa(g) is applied to the A/O valve,
keeping it fully open note that this could be a pneumatic control signal rather
than a fixed supply.
When the solenoid valve is de-energized, the air supply (100 kPa(g)) is cut off,
and simultaneously the pressure trapped in the control valve actuator is vented
to atmosphere.
page 1 - 7 - 25
Boiler level control is a typical example. The feed flow to the boiler must be
adjusted from 0-325 Kg/sec to maintain boiler level at the setpoint over the
entire range of possible steam flows i.e., feedwater and steam flows must
always be in mass balance.
If just one valve, capable of meeting the 100% requirement, was used, then
control at low power (low flow) levels would be imprecise the large valve
would likely over correct or under correct when just opened a small amount.
To overcome this disadvantage, two valves are provided, one with 100%
capability and another with approximately 20% capability, in parallel to the
larger valve.
The operation of this type of system requires the smaller valve to open toward
its maximum whilst the larger valve remains closed. As the small valve
reaches approximately 75% opening, the large valve opens to begin to take up
the flow.
page 1 - 7 - 26
State the combinations of pneumatic actuator and globe valve body required
to provide:
a) air to open action;
b) air to close action.
2.
State and sketch the three flow characteristics for the most common globe
valves.
3.
State a typical application for each of the three flow characteristics and
explain why it is the most appropriate selection for that application.
4.
State the effect of unbalanced force on valve position and explain with an
example, how bench setting would correct this problem.
5.
6.
7.
Sketch and describe a system pump head vs flow curve set to define
installed valve differential conditions.
8.
Explain, with a diagram, how a three-way solenoid valve can be used for
ON/OFF control of a pneumatic valve.
9.
State the formula which describes a control valve Cv factor. What is the Cv
for a valve which will pass a water flow of 100 USGPM with a pressure drop
of 25 psi? What flow would this valve pass when the pressure drop is 49
psi?
10.
State why it is often advisable to use different sized valves in parallel when
the process variable has a very large flow range.
page 1 - 7 - 27