FMDS0404N
FMDS0404N
FMDS0404N
4-4N
January 2001
Supersedes September 1998
Page 1 of 5
Table of Contents
Page
1.0 SCOPE ................................................................................................................................................... 2
1.1 Changes ............................................................................................................................................ 2
1.2 Superseded Information ................................................................................................................... 2
2.0 FM GLOBAL INTERPRETATION .......................................................................................................... 2
2.1 Introduction ...................................................................................................................................... 2
2.1.1 Shall versus Should .............................................................................................................. 2
2.1.2 Authority Having Jurisdiction ................................................................................................. 2
2.1.3 Listed or Approved ................................................................................................................ 2
2.1.4 Related NFPA Standards ...................................................................................................... 2
2.2 Protection ......................................................................................................................................... 2
2.3 Operation And Maintenance ............................................................................................................ 4
2.3.1 Tests and Inspection ............................................................................................................. 4
3.0 SUPPORT FOR RECOMMENDATIONS ............................................................................................... 4
4.0 REFERENCES ....................................................................................................................................... 5
4.1 FM Global ........................................................................................................................................ 5
4.2 NFPA Standards .............................................................................................................................. 5
APPENDIX A DOCUMENT REVISION HISTORY ....................................................................................... 5
List of Figures
Fig. FM1. Two zone system. ........................................................................................................................... 3
2000 Factory Mutual Insurance Company. All rights reserved. No part of this document may be reproduced,
stored in a retrieval system, or transmitted, in whole or in part, in any form or by any means, electronic, mechanical,
photocopying, recording, or otherwise, without written permission of Factory Mutual Insurance Company.
4-4N
Page 2
1.0 SCOPE
FM Global has accepted and adopted NFPA Standard 14, Standard for the Installation of Standpipe, Private
Hydrant and Hose Systems, 2000 Edition.
This data sheet addresses design and installation of Standpipe and Hose Systems as it pertains to the
conservation and protection of property.
1.1 Changes
This document establishes Data Sheet 4-4N as a new and independent document to NFPA 14.
1.2 Superseded Information
This new standard supersedes all previous information in Data Sheet 4-4N.
2.0 FM GLOBAL INTERPRETATION
2.1 Introduction
Design and install standpipe and hose system in accordance with NFPA 14, Standard for the Installation of
Standpipe, Private Hydrant and Hose Systems, 2000 Edition. In its application, use the following
interpretations.
4-4N
Page 3
2.2.6 Pump Arrangement. Design and install fire and booster pumps in accordance with Data Sheet 3-7N,
Stationary Pumps for Fire Protection (NFPA). (Paragraph 7-1.2)
2.2.7 Do not accept series staging of fire or booster pumps to supply water for sprinkler or standpipe systems
as indicated in paragraph 7-4 of NFPA 14 or shown in Figures A-5-1(b) and A-5-1(c) of NFPA 14. Install and
arrange fire and booster pumps in accordance with Data Sheet 3-7N. (Paragraph 7-4)
2.2.8 Arrange for automatic starting and manual stopping when fire or booster pump units supply water for
standpipes (see Data Sheet 3-7N). (Paragraph 7-1.1 and 7-1.2)
2.2.9 Figure 1 illustrates a two zone system for a building having a maximum height of 550 ft (168 m). It
differs from NFPA 14 Figure A-5-1(b) in that both fire pumps take their suction directly from the water supply.
If two water supplies are necessary, each zone should have the second pump in parallel or a gravity tank
at the top. The gravity tank may be refilled by the fire pump for that zone or by a separate tank-filling pump.
(Paragraph 5-1 and Fig. A-5-1(b))
2.2.10 Where gravity or water tanks are needed, design and install tanks in accordance with FM Global Data
Sheet 3-2, Water Tanks for Fire Protection. (Paragraph 7-1.2)
2.2.11 Avoid the use of Standpipe zones exceeding 275 ft. For Buildings having three or more zones of
275 feet (84 m) each should duplicate the high zone arrangement from Figure 1 for the third and higher zones.
(Paragraph 5-2)
2.2.12 Make small (hand) hose connections to sprinkler pipes preferably to sprinkler systems serving areas
other than those in which the hose would be used. Otherwise, if the sprinkler system is shut off, the hand
hose would be without water (see Data Sheet 2-8N). (Paragraph 5-3.3 [see also NFPA 13 paragraph
5-15.5.1.1])
2.2.13 Location of Standpipes in Unheated Areas.
Small hose protection is needed for storage areas. Many such areas are unheated, so that piping is subject
to freezing in the winter. Under such conditions, the best practice is to locate the hose connection in an
adjacent heated area such as an office, washroom, or dry pipe valve enclosure. If there are no heated areas
in the immediate vicinity, the best arrangement is an approved remote control hose valve station.
4-4N
Page 4
Another acceptable method is a small approved deluge valve actuated by push buttons at each hose station.
An emergency power supply should be provided for any deluge valve electrical circuitry. Drains are needed
at low points. If pressure is not maintained on piping, ordinary hose valves may be used.
A less effective method is hose stations in unheated areas supplied by a small dry pipe valve separate from
the dry pipe valves supplying sprinklers. Low points should have dual valves and drum drips. Hose control
valves should have an automatic air maintenance device. Employees should be given special instruction in the
use of these hose stations, in that they should expect air to discharge for several seconds until water reaches
the hose. A pressure surge may be expected when water starts to flow.
Existing hose stations supplied on a shut-in-winter system are acceptable providing the control valve in the
heated area is on the same floor. The valve should be no more than 150 ft (45.7 m) from the hose connection, well marked, and readily accessible. Employees should be thoroughly instructed and drilled in emergency
operating procedures. New indoor hose connections should not use this method because of complications
regarding valve arrangements and the continuing need for employee education. (Paragraph 4-1-2.3)
2.2.14 Standpipe Installations In Buildings Under Construction. Provide at least one hose valve at each floor
with a connection for attaching fire department hose and an additional 1-12 inch outlet and hose for use by
personnel on the site until the fire department arrives. (Paragraph 10-1)
2.3 Operation And Maintenance
4-4N
Page 5
4.0 REFERENCES
4.1 FM Global
Data Sheet 2-8N, Installation Of Sprinkler Systems (NFPA).
Data Sheet 2-8, Earthquake Protection for Water-Based Fire Protection Systems.
Data Sheet 3-2, Water Tanks for Fire Protection.
Data Sheet 3-7N/13-4N, Stationary Pumps for Fire Protection (NFPA).
4.2 NFPA Standards
NFPA 14, Standard for the Installation of Standpipe, Private Hydrant, and Hose Systems, 2000 Edition.
APPENDIX A DOCUMENT REVISION HISTORY
Data Sheet 4-4N was created in 1978. It included the exact text of NFPA 14, 1978 edition, including appendix
material, and the applicable FM Global comments in bold letters.
The 1978 version of Data Sheet 4-4N was revised in 1981 and restructured in 1998.