Flash Tanks
Flash Tanks
Flash Tanks
BULLETIN 161
Revised 4/13
FLASH TANKS
and
RECOVERY UNITS
TYPE VFT
Vertical Flash Tank
TYPE HFT
Horizontal Flash Tank
TYPE FRV
Flash Recovery Vessel
Advantages
Steam offers the following advantages:
Steam flows through the system unaided by external
energy sources such as pumps.
Because of its low density, steam can be used in
tall buildings where water systems create excessive
pressure.
Terminal units can be added or removed without
making basic changes to the design.
Steam components can be repaired or replaced by
closing the steam supply, without the difficulties associated with draining and refilling a water system.
Steam is pressure-temperature dependent; therefore, the system temperature can be controlled by
varying either steam pressure or temperature.
Steam can be distributed throughout a heating
system with little change in temperature.
In view of these advantages, steam is applicable to the
following facilities:
Where heat is required for process and comfort
heating, such as in industrial plants, hospitals,
restaurants, dry-cleaning plants, laundries, and
commercial buildings.
Where the heating medium must travel great distances, such as in facilities with scattered building
locations, or where the building height would result
in excessive pressure in a water system.
Where intermittent changes in heat load occur.
Fundamentals
Steam is the vapor phase of water and is generated by adding more heat than required to maintain its
liquid phase at a given pressure, causing the liquid to
change to vapor without any further increase in temperature. Equation 1 illustrates the pressure-temperature relationship and various other properties of steam.
Temperature is the thermal state of both liquid
and vapor at any given pressure. The values shown
2
in Table 1 are for dry saturated steam. The vapor temperature can be raised by adding more heat, resulting
in superheated steam, which is used (1) where higher
temperatures are required, (2) in large distribution systems to compensate for heat losses and to ensure that
steam is delivered at the desired saturated pressure
and temperature, and (3) to ensure that the steam is
dry and contains no entrained liquid that could damage
some turbine-driven equipment.
Enthalpy of the liquid hf (sensible heat) is the
amount of heat in Btu required to raise the temperature
of a pound of water from 32F to the boiling point at the
pressure indicated.
Enthalpy of evaporation hfg (latent heat of vaporization) is the amount of heat required to change a
pound of boiling water at a given pressure to a pound
of steam at the same pressure. This same amount of
heat is released when the vapor is condensed back to
a liquid.
Enthalpy of the steam hg (total heat) is the combined enthalpy of liquid and vapor and represents the
total heat above 32F in the steam.
Specific volume, the reciprocal of density, is the
volume of unit mass and indicates the volumetric space
that 1 lb of steam or water occupies.
An understanding of the above helps explain some
of the following unique properties and advantages of
steam:
Steam,
As
Heat Recovery
Two methods are generally employed to recover
heat from condensate: (1) the enthalpy of the liquid
condensate (sensible heat) can be used to vaporize or
flash some of the liquid to steam at a lower pressure,
or (2) it can be used directly in a heat exchanger to heat
air, fluid, or a process.
The particular methods used vary with the type of
system. Facilities that purchase steam from a utility generally do not have to return condensate and, therefore,
can recover heat to the maximum extent possible. On
the other hand, facilities with their own boiler generally
want the condensate to return to the boiler as hot as
possible, limiting heat recovery because any heat removed from condensate has to be returned to the boiler
to generate steam again.
Flash Steam
Flash steam is an effective use for the enthalpy
of the liquid condensate. It can be used in any facility
that has a requirement for steam at different pressures,
regardless of whether steam is purchased or generated
by a facilitys own boiler. Flash steam can be used in
any heat exchange device to heat air, water, or other liquids or directly in processes with lower pressure steam
requirements. Equation 1 may be used to calculate the
amount of flash steam generated, and Figure 1 provides
a graph for calculating the amount of flash steam as a
function of system pressures.
Although flash steam can be generated directly
by discharging high-pressure condensate to a lower
pressure system, most designers prefer a flash tank
Figure 1
to control flashing. Flash tanks can be mounted either
vertically or horizontally, but the vertical arrangement
shown in Figure 3 (on page 4) is preferred because it
provides better separation of steam and water, resulting
in the highest possible steam quality.
The most important dimension in the design of
vertical flash tanks is the internal diameter, which must
be large enough to ensure a low upward velocity of
flash to minimize water carryover. If this velocity is low
enough, the height of the tank is not important, but it
is good practice to use a height of at least 2 to 3 feet.
The graph in Figure 2 can be used to determine the
internal diameter and is based on a steam velocity of
10 ft/s, which is the maximum velocity in most systems.
Figure 2
3
Installation is important for proper flash tank operation. Condensate lines should pitch towards the flash
tank. If more than one condensate line discharges to
the tank, each line should be equipped with a swing
check valve to prevent backflow. Condensate lines and
the flash tank should be well insulated to prevent any
unnecessary heat loss. A thermostatic air vent should
be installed at the top of the tank to vent any air that
accumulates. The tank should be trapped at the bottom
with an inverted bucket or float and thermostatic trap
sized to triple the condensate load.
The demand load must always be greater than
the amount of flash steam available to prevent the
low-pressure system from becoming overpressurized.
A safety relief valve should always be installed at the
top of the flash tank to preclude such a condition.
Because the flash steam available is generally less
than the demand for low-pressure steam, a makeup
valve ensures that the low-pressure system maintains
design pressure.
Flash tanks are considered pressure vessels and
must be constructed in accordance with ASME and
local codes.
FIG 1 F
S
RELIEF DEVICE
PRESSURE GAUGE
SAFET RELEIF
VALVE
FLASH TANK
S ING CHECK VALVE
HIGH PRESSURE
CONDENSATE RETURN
F T OR IB TRAP
DRIP
POCKET
LO PRESSURE RETURN
FIG 2 VFigure 3 F T
Rules of thumb:
Horizontal flash tanks should be 2 times tank diameter or 24" minimum length.
Vertical flash tanks should be 3 times tank diameter
or 36" minimum length.
FT
BDS
BDT
SHIPPENSBURG PUMP COMPANY, INC., P.O. BOX 279, SHIPPENSBURG, PA 17257 PHONE 717-532-7321 FAX 717-532-7704 WWW.SHIPCOPUMPS.COM
PRINTED IN THE U.S.A. BEIDEL PRINTING HOUSE, INC., 717-532-5063