DRP 240 Spec
DRP 240 Spec
DRP 240 Spec
DRP-240
series
Features :
Universal AC input / Full range
Built in active PFC function
Protections: Short circuit / Overload / Over voltage / Over temperature
Cooling by free air convection
Can be installed on DIN rail TS-35/7.5 or 15
UL 508(industrial control equipment)approved
LED indicator for power on
100% full load burn-in test
Fixed switching frequency at 100KHz
3 years warranty
SPECIFICATION
MODEL
OUTPUT
DRP-240-24
DRP-240-48
DC VOLTAGE
24V
48V
RATED CURRENT
10A
5A
CURRENT RANGE
0 ~ 10A
0 ~ 5A
RATED POWER
240W
240W
150mVp-p
48 ~ 53V
1.0%
24 ~ 28V
VOLTAGE TOLERANCE Note.3 1.0%
LINE REGULATION
0.5%
LOAD REGULATION
1.0%
24ms/230VAC
INPUT
Note.5 85 ~ 264VAC
FREQUENCY RANGE
47 ~ 63Hz
0.96/230VAC
84%
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
2.8A/115VAC
1.4A/230VAC
OVERLOAD
PROTECTION OVER VOLTAGE
OVER TEMPERATURE
WORKING TEMP.
WORKING HUMIDITY
ENVIRONMENT STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
SAFETY STANDARDS
SAFETY & WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMC
(Note 4)
EMC EMISSION
85%
30 ~ 36V
Protection type : Shut down o/p voltage, re-power on to recover
100
5 (TSW1)detect on heat sink of power transistor
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
-10 ~ +70
20 ~ 90% RH non-condensing
-20 ~ +85
, 10 ~ 95% RH
0.03%/ (0 ~ 50
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
UL508, UL60950-1, TUV EN60950-1 approved
I/P-O/P:3KVAC
I/P-FG:1.5KVAC
O/P-FG:0.5KVAC
EMC IMMUNITY
MTBF
DIMENSION
PACKING
NOTE
LEAKAGE CURRENT
OTHERS
1.0%
800ms, 40ms/230VAC
0.5%
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
5. Derating may be needed under low input voltages. Please check the derating curve for more details.
DRP-240
series
Unit:mm
125.5
100
125.2
TB1
LED
3 2 1
TB2
4 3 2 1
+V ADJ.
Pin No.
1
2
3
35
Assignment
FG
AC/N
AC/L
Assignment
DC OUTPUT +V
DC OUTPUT -V
Block Diagram
fosc : 100KHz
EMI FILTER
&
RECTIFIERS
I/P
PFC
CIRCUIT
RECTIFIERS
&
FILTER
POWER
SWITCHING
FG
O.L.P.
+V
-V
CONSTANT
CURRENT
LIMITING &
DETECTION
CIRCUIT
O.V.P.
O.T.P.
Derating Curve
100
100
230VAC
90
80
80
70
110VAC
LOAD (%)
LOAD (%)
60
40
20
60
50
40
-10
10
20
30
40
50 55 60
AMBIENT TEMPERATURE ( )
70 (VERTICAL)
Vin: -- 230VAC
110VAC
85
100
110
135
155
230
264