SP12-120 12V120Ah
Features and benefits:
Working features:
z
Rated voltage:12V
Number of cells: 6
z
z
120.0Ah
z
10 hours rate (11.16A, 10.50V) 111.6Ah
5 hours rate (20.4A, 10.50V) 102.0Ah
1 hours rate (72.0A, 10.20V) 72.0Ah
Internal resistance3.8 m for fully charged battery
at 77F (25)
Complied standard
z
GB/T 19639.1-2005
over-discharge
IEC 61056-1/22002
JIS C8702-1/22009
British unit
Length
407mm
16.02inch
Width
173mm
6.81inch
Height
222mm
8.74inch
TH
231mm
9.10inch
Weight
36.0kg
79.38lbs
Specifications
Discharge parameter
(V/cell)
10
15
20
30
45
60
90
120
180
300
600
1200
1.60
372.0
280.0
217.0
174.5
132.0
97.50
75.60
56.52
44.50
32.20
21.73
11.40
6.250
1.65
366.0
275.0
213.0
170.0
128.9
95.90
73.80
55.75
43.64
31.79
21.25
11.32
6.150
1.70
351.0
264.0
205.0
163.9
126.0
93.50
72.00
54.72
42.74
31.24
20.75
11.24
6.070
1.75
317.0
243.0
193.0
157.4
122.0
90.00
70.00
53.45
42.00
30.60
20.40
11.16
6.000
1.80
268.0
219.6
179.0
146.8
114.0
85.00
67.00
51.00
40.50
29.50
19.70
10.80
5.860
Cut-off Voltage
(V/cell)
10
15
20
30
45
60
90
120
180
300
600
1200
1.60
615.0
470.0
370.0
301.8
237.0
177.0
142.0
105.0
82.79
60.49
40.31
22.87
12.54
1.65
610.0
465.0
365.0
296.7
232.4
174.9
139.3
104.0
81.86
59.82
39.79
22.65
12.34
1.70
590.4
455.0
357.0
290.5
227.3
171.5
136.5
103.0
80.93
59.20
39.48
22.49
12.23
1.75
540.0
425.0
342.0
282.6
221.7
168.1
134.2
101.4
80.15
58.63
39.02
22.33
12.06
1.80
460.0
387.0
320.0
269.1
215.0
163.0
131.0
99.00
78.70
57.50
38.50
22.07
11.87
Specifications
Performance curve
Add: No.1, Shengyang Road, Qufu City, Shandong Province, 273100 P.R.China
Tel: 0537-4438666
Fax: 0537-4411936
E-mail: sales@sacredsun.cn
Website: http://www.sacredsun.com