Kitchen Design
Kitchen Design
Kitchen Design
VENTILATION SYSTEMS
BY
THOMAS E CARTER
KITCHEN
VENTILATION SYSTEMS
by
Thomas E. Carter
Thomas E. Carter
A. W. Cockerill
Charlotte Brewer, M.A. (Oxon.)
Vent Master
1021 Brevik Place
Mississauga, ON L4W 3R7
Canada
Tel:
Fax:
U.S.A. to Canada:
Fax: U.S.A. to Canada:
Publishing history
First printed September 1995
Reprinted January 1996
Revised and reprinted 1997
905-624-0301
905-624-5547
1-800-565-2981
1-800-665-2438
Contents
Page
Foreword
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Hoods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
11
23
Ducts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
29
Air Flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
35
Auxiliary Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . .
45
55
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
61
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
75
Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
79
105
Trouble Shooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
133
Engineered Features . . . . . . . . . . . . . . . . . . . . . . . . . . . .
141
149
Abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
151
Bibliography . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
153
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
155
Foreward
This book is for architects, engineers, kitchen designers, contractors, inspectors and others who install,
inspect, operate, maintain or service commercial kitchen ventilation systems. Its purpose is to explain
the elements of cooking equipment ventilation in plain English. It discusses four main topics:
C
The factors that shape and define a ventilation system specified by the kitchen designer;
Building codes, fire and environmental regulations that govern ventilation systems.
Contractors and service personnel will find here a concise summary of installation requirements,
operating, cleaning and maintenance procedure. The book makes frequent reference to the National
Fire Prevention Association 96 (commonly known as NFPA96) Standard, which many jurisdictions use
as a basis on which to inspect and approve kitchen installations. The influence of the NFPA 96
Standard on the layout and content of the book is readily acknowledged. Without the clear and concise
treatment the Standard gives to kitchen ventilation technology, the task of writing the book would have
been considerably more difficult than in fact it proved to be.
The book will help users avoid the costly mistakes sometimes made in choosing a ventilation system.
It should also answer many of the questions clients frequently ask architects and designers, including:
C
How can I get the most efficient system at the least cost?
What does labelled product mean and whats important about it?
I sincerely hope that those who use the book will find sound, useful and practical advice in it to apply
to their work in kitchen ventilation technology. I purposely intended to discuss ventilation technology
in a generic sense although, admittedly with without apology, there is frequent reference to the products
of Vent Master, one of the foremost leaders in the kitchen ventilation equipment field.
Thomas E. Carter
Maplewood, NJ
Introduction
More than 5000 years ago, the Egyptians built ventilation shafts into the
pyramids to provide artisans working in the vaults and passageways with a
constant supply of cool, fresh air. Visitors to the pyramids at Giza still benefit
from the built-in ventilation system of the ancient builders when they are inside
the massive structures. Without that cooling ventilation, the atmosphere in the
dimly lit passageways and tunnels would soon become exceedingly stale and
stifling.
Good ventilation is important for the comfort of occupants in any
enclosed space. In commercial kitchens with banks of ovens, grills and fryers,
adequate ventilation is essential to deal with the effects of heat, smoke, odors,
pollutants and numerous airborne contaminants. Without adequate ventilation,
cooking operations in confined spaces would be impossible. The degree of
ventilation a given kitchen space requires depends on various factors: the type
of operation being conducted; the structure in which the kitchen operates; the
type of equipment in use; the heating source; applicable regulations and ecology
requirements.
About this book
A number of factors govern the efficiency and reliability of kitchen ventilation
systems. They include installing the right equipment for the job, good operating
practices and regular maintenance. Users will find this practical illustrated guide
helpful whether they are dealing with kitchen design, the selection of equipment, its installation, operation or servicing. It tells you the `what' and the `why'
of Vent Master equipment. Its primary purpose is to serve users as a source of
reference that neither product literature nor codes can provide.
10
Hoods
Hoods
A hood is the primary device used to collect vapors, pollutants and airborne
residues from cooking operations to funnel them into the ventilation system. The
closer the hood is to the cooking surface, the griddle plate, oven top and broiler,
the more efficiently it will collect the generated heat and particulate matter to
channel into the ventilation system. From a practical viewpoint, however, a hood
cannot be so close to the cooking surface that it hinders the kitchen staff in doing
their work.
Hood nomenclature
Over the years, a common terminology has evolved in hood types and
nomenclature. Common terms include the backshelf hood, the canopy hood,
make-up air and the abbreviations CFM, SP and FPM, as shown in Figure 7..
Make-up air means the supply of air from an exterior source to replace the air
ventilated from the kitchen.
The hood is only one component of a kitchen ventilation system, but
an important one whose size is determined by the size and capacity of the
cooking equipment being used. The capacity of the system is expressed in cubic
feet per minute (cfm). Three factors determine capacity:
1. The type of cooking appliances in use: fryers, ovens, broilers, steam
kettles, etc.
2. The type of heating source: gas, steam, electricity, or a combination of
these.
3. The barriers to air flow: building walls, fabricated enclosures.
These factors define the velocity and rate of expansion of the air in the
generated up-draft. For example, cooking appliances with large, open heated
surfaces, such as grills and broilers, create stronger up-drafts than an
11
Ventilation Systems
oven, which is built to contain the heat it uses.
Gas and solid fuel-burning appliances lose most of the energy they
produce. This waste heat generates stronger thermal currents than equipment
heated electrically or with steam.
Walls, fabricated enclosures and the type of hood used affects the volume
of exhaust air needed. Hot air rising from the cooking equipment induces the
surrounding air; i.e., the faster the hot air rises the more the surrounding air is
drawn in to replace it. Therefore the more air is required on all open or exposed
sides of the hood. Another feature of ventilation systems is that the more
enclosed the cooking operation, the less the exhaust air needed to ventilate it.
An appliance open on all sides requires a larger volume of exhaust air than
when only one side is open.
Although there are many variants of the backshelf and the canopy-type
hoods, it is the cooking equipment that determines which type of hood best suits
the application.
Figure 8 shows a low cooking surface appliance for which the backshelf
hood is well suited. The backshelf hood is sometimes called a low-profile
wall or up-draft hood.
A backshelf hood in close proximity to the cooking surface requires less
exhaust air than is required by a canopy hood for the same application. This
makes the backshelf hood an efficient choice for this service. The range of
clearances from the cooking surface to the top of the hood and from the floor
to the hood ducting is fairly restricted. The backshelf hood is not suitable for
tall appliances or operations that produce large volumes of smoke or steam. For
such applications a canopy hood (see Figure 9) is essential.
A canopy hood requires a larger volume of exhaust air than a backshelf
hood. Conversely, a canopy is suitable for ventilating any type of cooking
operation, its main advantage being its flexibility. By flexibility is meant that,
being open on all sides, the hood can be positioned anywhere in the cooking
space that is not adjacent to a wall. The construction of a backshelf hood
requires it to be positioned and fitted where it was designed to go. It cannot be
repositioned without modification.
12
Hoods
Exhaust air velocity
An air velocity of 50 fpm is the minimum required to contain a rising thermal
column and capture suspended particulate matter released by cooking
operations. This minimum velocity is called the capture velocity.
The capture velocity does more than arrest released cooking particulates.
It provides a minimum flow of air across the cooking surface to ventilate the
appliance. A velocity less than the capture velocity results in appliance
overheating problems. Higher levels can remove too much heat and cause the
cooking temperature of the appliance to fluctuate.
Calculating exhaust volumes
Once the cooking equipment layout, hood type, size and number of exposed
sides of the hood are known, calculate the required exhaust volume by adding
the lengths of the open sides, as shown in Figure 10.
The three figures combined in Figure 11 overleaf show possible
combinations of open and closed sides found in kitchen designs.
Multiply the total length of the open sides by the distance from the
cooking surface to the bottom of the hood (see Figure 12). The product in
square feet is the captive area.
Next, multiply the captive area in sq. ft. by 50 to get the captive velocity.
Finally, referring to Table 1, shown overleaf, add or subtract the cfm
correction factors according to the actual appliances in the cooking configuration.
Sizing a hood
There are three areas to consider when sizing a hood.
C
13
Ventilation Systems
W1
W2
L
Length of open sides (LT)
=L+W
+225
Fryers
+75
+50
Tilting skillets
+150
+150
+150
+150
Conv. broilers
+150
+350
Mesquite broiles
+350
Salamanders
Ovens
Elect.
Equip.
Broilers
Griddles
L
Length of open side (LT) = L
Gas
Equip.
+150
+50
+300
-300
+300
-200
The wall locations. Determine the wall locations around the hood
perimeter. For example, if the cooking equipment is against the back wall
and in a corner, the hood would require a 6 overhang on the front of the
cooking bank and a 6 overhang on one end of the bank only.
dimension.
Hoods with odd dimensions can be and often are produced. For example,
14
Hoods
end walls on both sides of a hood may give a dimension of 8'5. A
clearance of 1 should be allowed on either side to make sure the hood will
3.
fit into the space with ease. This would make the hood length 8'3.
The standard depth of a VM hood is 4'. The smallest available depth is 3'.
If the cooking bank requires a 3'6 deep hood it is better to use a 4' deep
hood as this will increase the capture area, give improved smoke control
5.
and will not change the cfm requirements for the cooking bank.
All exhaust hoods can be tapered, but VM does not recommend a taper in
excess of 12. Always consult the factory if special tapers are required.
When tapering an exhaust canopy, remember that it is usually mounted
6.
with the front lip 6'6 above the finished floor. There is no minimum
height code requirement, although VM recommends a minimum height of
6'3 to provide adequate working clearance and head room.
Always check the height of the cooking equipment below the hood when
4.
tapering any hood section. If a hood is tapered 12 and the hood front
mounted 6'6 above the finished floor, the back of the hood will be 5'6
above the floor. This means that, as salamanders and cheese melters
typically stand at a height of 5'10, they cannot be accommodated under
7.
8.
Ventilation Systems
9.
The cooking equipment determines the dimensions of the hood. Once this
is known, the hood can be banked, tapered or custom-built to suit the
space.
16
Hoods
17
Ventilation Systems
The large circle of this illustration represents about 1 per cent of the air we
breathe. Three constituents make up this 1 per cent: trace gases, variable gases,
and atmospheric impurities
For striking comparison, Figure 17 shows various sizes of
aerosols in relation to a strand of human hair, which is
about 150 microns in size. Aerosols of the smallest size
(0.3 to 1 micron) such as tobacco smoke, cooking oil, and
perfumes are easily detected by one's sense of smell. The
smaller the size the higher the degree of filter or ventilation
equipment efficiency needed to deal with the aerosol.
An aerosol is a suspension of microscopic liquid or
solid particles in the air. It is the function of any kitchen
ventilation system to reduce the aerosols in a kitchen
atmosphere to a minimum.
Aerosols (or particles) are measured in microns. A
micron is one millionth of a meter (1/25,400 inch). Under SI (System
International) units of measure, micrometre is beginning to replace the word
micron. In the U.S. filter industry, micron (abbreviated Fm) is the term in
common usage.
Figure 18 is a tabulation of particle size distribution in the atmosphere.
Architects and kitchen designers will find the particulate size and element
comparison chart shown in Figure 19 a useful source of reference for a variety
of particulates. Some clients require technical specifications to cover various
types and sizes of particulates.
18
Hoods
Average particle
size (microns)
Per cent
by weight
Per cent by
particle count
Particle size
(microns)
30
20
0.005
28
10
7.5
0.175
52
5
4
0.25
11
1.07
0.5
98.5
3
1
0.0
Source: NAFA
"Guide to Air Filtration"
0.01
0.1
2
5 6 7 89
1.0
2
5 6 7 89
10
2
5 6 7 89
100
2
Plant
1000
5 6 7 89
5 6 7 89
5 6 7 89
5 6 7 89
Pollen
Mold
Carbon black
Bacteria
Animal
Asbestos
Mineral
Coal dust
Textiles
Cement dust
Smoldering or flaming cooking oil
Combustion
Burning wood
Auto emissions
Air freshener
Home care
Humidifier
Insecticide dusts
Face powder
Copier toner
0.01
5 6 7 89
0.1
5 6 7 89
1.0
5 6 7 89
10
100
1000
Source: ASHREA
19
Ventilation Systems
Some technical specifications specify a media velocity of something
less than the face velocity. Figure 20 shows how a pleated panel filter
achieves this reduced media velocity. Although more expensive, the
pleated panel filter is more efficient and has a longer life than an
equivalent panel filter because the media velocity can be reduced by as
much as 50% of the face velocity.
The four diagrams shown in Figure 21 illustrate various ways in
which the filter media captures particles. They show the difference
between impingement, interception, straining and diffusional effect.
20
Hoods
Terms and Definitions
Dust is dry particles of matter predominantly larger than colloidal size and
capable of temporary gas suspension. Dust is generated from the reduction of
larger, solid materials. The action of a jackhammer drilling rock creates dust;
volcanic eruptions discharge lava dust (also called ash) into the air.
Dust varies in size from <0.1 to >25 microns. Larger dust particles
settle rapidly. Smaller particles stay in suspension longer and settle more
slowly. Airborne dust under <0.1 behaves like a gas and has no rate of fall, but
is affected by Brownian movement*. This is the random movement of particles
caused by statistical pressure fluctuations over them.
Particles in the range of 0.1 to 1 micron have negligible settling
velocities. Particles in the 1 to 10 micron range have a constant and appreciable
settling rate, but are kept in suspension by air currents. Particles in excess of 10
microns settle out of the atmosphere.
Fumes are particulate matter consisting of the solid particles generated by
condensation from the gaseous state. Generally, this occurs after the volatization
from melted substances, often accompanied by a chemical reaction such as
oxidization. Arc welding fumes are typical of this chemical action. Heat from
the electric arc vaporizes some of the rod and its coating.
Fog is the condensation of water vapor in the air in sufficient concentration
to reduce visibility. This is the same phenomenon that causes clouds to form.
Mist is similar to fog except that it is the formation of liquid droplets
suspended in or falling through a moving or stationary atmosphere.
Smoke is dispersion of liquid aerosols formed by the incomplete
combustion of organic material in a gaseous atmosphere.
Gas is a phase of matter in molecular form, characterized by relatively low
density, which expands readily to fill any containing vessel.
Vapor is a gas formed by the evaporation of a material in liquid or solid
form. It is a gas at a temperature below critical temperature, so that it can be
liquified under pressure without lowering the temperature.
21
Ventilation Systems
* Brownian movement is the continuous zig-zag motion of particles (aerosols) in
suspension. The motion is caused by the impact of the molecules of the fluid (air) upon the
particles.
22
The control and removal of grease from hoods by means of grease filters, baffles
and similar devices is a subject of sufficient concern to warrant a separate
chapter in NFPA 96. The standard specifies the conditions of installation and
minimum distances between the cooking surface and the grease removal device.
Grease Extraction Rates
The National Bureau of Standards is not equipped to test ventilators.
Manufacturers test their own units according to NBS test procedure IR74-505.
This is therefore the procedure VM uses to test its Cyclo-Wash 3, Cyclo-Maze
and Cyclo-Vent units.
Although VM tested its own units to the specified NBS test procedure, it
used the services of the Institute for Storm Research to verify the tests. Dr. J.
C. Freeman, President of the Institute, has expertise in air movement,
temperature, point and factors related to condensation extraction.
The grease extraction rates of VM units, expressed as a percentage by
weight of grease removed, are on the basis of averages of a series of tests.
Filters (stainless steel baffle type GF Series)
Of the various devices available to collect and remove grease from hoods, steel
filters were for many years the most common means. The main requirements
for a filter are that it must be:
C of steel construction, tight fitting and firmly held in position;
C easily accessible and easy to remove for cleaning;
C installed at an angle not less than 45o from the horizontal;
C equipped with a drip tray pitched to drain into a container having a
minimum capacity of 0.13 gallon (0.5L).
23
Ventilation Systems
Some devices for removing grease also serve other functions, such as removal
of combustion gases, heat and cooking odors. VM has pioneered a number of
combination units, which this Section explains. For installation, operating and
maintenance procedures, refer to the relevant sections and the appendices.
Filter Grease extractor chambers (Cyclo Maze series)
There are two types of Cyclo Maze ventilators. One is a dry type; the other is
a water mist unit that uses a cold water mist to extract grease and airborne
solids, and a hot water wash for cleaning. The principle of operation for both
types is the same.
Baffles cause grease-laden air entering the plenum to move in a spinning
motion. With cold water mist nozzles, the air passes through a curtain of cold
water mist, which causes grease particles in suspension to solidify and fall into
7
6
The unit operates on the principle of high capture velocities and low
5
4
1
3
2
24
Note
5
4
1
3
9
2
C
C
C
Air velocity
Change of direction and spinning thin air
Lower exhaust air temperatures
Ventilation Systems
Exhaust hoods come in various shapes, capacities and styles. The grease
extractor is the engine of the hood and the main feature on which the efficiency
of the hood depends. This report is a summary of the characteristics and
specifications of hoods and their grease extraction engines.
What makes a hood engine efficient?
C Changing the direction of air to spin out grease.
C Changing the air velocity to drop out grease.
C Changing the air temperature with cold water mist to scrub and condense
out grease.
What types of engines are there?
Automobiles with which engines are most frequently associated are equipped
with four, six and eight cylinder engines, together with many features that make
them different. The same is true of exhaust hood engines.
The power of the engine lies in its capacity to remove grease. The 4
cylinder engine (2 deep) is the smallest in the range and removes the least
amount of grease. The 6 cylinder engine is larger (12 deep) and can be
manually cleaned or self cleaning using a hot water wash. The 8 cylinder engine
has a cold water mist scrubber added and, using the third grease removal
principle, removes a lot more grease. The 12 cylinder unit is the largest engine
(18 deep). It has 200% more cold water.
HOOD SECTION
"Engine"
area
The exhaust hood body is
the same as a car body.
Vent Master hoods
accommodate all engines
4 Cylinder
S/S filter
6 Cylinder
Dry extractor
with hot water
wash
6 Cylinder
Dry extractor
or removable
cartridge
8 Cylinder
cold water mist
extractor with
hot water wash
26
27
Ventilation Systems
28
Ducts
Ducts
Ventilation Systems
ventilation ducts, which make the ducting an important part of any system. The
applicable codes (see the Codes and Equipment Specifications Section),
provide specific detail and consultation of those considerations that apply. Here
are other important topics worth noting.
Ducts & ventilation rates
To give some idea of the cfm capacity requirements of exhaust systems, Table
3 lists cfm values used for various typical kiosk food court installations and the
hood sizes installed for food court applications.
Using the values tabulated in Table 3 for the eight kiosks, there is an average
cfm value of 17,800/8 = 2,225. It is therefore safe to work on an average value
of 2,500 cfm per kiosk, but allow for individual kiosk sizing for cfm. (See also
the Auxiliary Equipment Section.)
Openings
Access openings are required either at the sides or on the top of duct runs at
every change in direction. Hoods with dampers in the exhaust or supply collar
require an access opening for cleaning and inspection purposes. Similarly,
cleaning and inspection openings are needed for exhaust fans having duct work
connected to both sides, the opening or openings to be within 3 ft. of the fan.
30
Ducts
Duct cleaning is such an important part of maintenance that openings must
allow for cleaning the duct work along its entire length. This, in turn, means
that the system designer must make sure inspection and cleaning openings
satisfy this cleaning requirement. Kitchen ventilation is not the same as ordinary
building air conditioning ducting. Venting odors and grease vapor material can
pose fire hazards about which local and jurisdictional authority inspectors can
be and are particular.
Ducting installation
The emphasis placed on fire safety and protection by all authorities with regard
to ducting is reflected in the installation requirements of ducting seams,
penetrations and connections.
Many codes specify that duct-to-hood collar connections must have a
liquid-tight continuous external weld. NFPA 96 from which
Figure 27 is taken is specific in its requirements for connections at the hood
collar that are not continuously welded.
Ventilation Systems
potential of cooking operations. Figure 28, taken from NFPA 96 Appendix A,
shows detail to cover various types of installation requirements for a typical
commercial cooking exhaust system. Figure 28 is followed by Table 4 (also
courtesy NFPA 96 Standard) giving examples of types of construction
assemblies containing noncombustible, limited combustible and combustible
materials.
Discharge
10' 0"
Exhaust fan
Access panel
Access panel
40"
Weather-protected
opening
Roof
Not less than 1-hr fire resistance for
building less than 4 stories in height
Not less than 2-hr fire resistance for
building 4 stories or more in height
Fire-rated
floor
Access panel
Opening in enclosure
Second
story
Grease duct
Non-fire-rated ceiling
Sealed around the duct at
this point since fire-rated
floor
Exhaust hood
Figure 28 - Typical section view for building with two stories or more
with non-fire-rated ceiling and fire-rated floor
Exterior installation
Many codes, and NFPA 96 in particular, recommend that duct work be installed
vertically and adequately secured to the building exterior. The fasteners - bolts,
screws or rivets - used to secure the duct must not penetrate the duct walls.
Interior installation
As specified in NFPA 96, in buildings having more than one floor, but also in
single-story buildings with a specified fire-rated roof-ceiling assembly, ducts
have to be enclosed in a continuous enclosure to maintain the integrity of fire
separations required by the applicable building codes. The enclosure must
extend from the lowest fire-rated ceiling or floor above the hood through
32
Ducts
any concealed spaces to or through the roof.
Further, if the building is less than four stories, the enclosure wall has to have
a fire rating of not less than one hour. In buildings of more than four stories, the
enclosure fire rating has to be two hours or more.
If fire does occur in a ducting system, inspection by a qualified inspector
is necessary before further use to determine if the structural integrity of the duct
and enclosure still meets requirements for fire protection purposes.
The whole point of duct design and installation for ventilation systems is
the need to consult, and comply with, applicable code requirements.
33
Ventilation Systems
Exhaust terminations
Codes are specific for exhaust system terminations for both rooftops and walls.
For example, for rooftop terminations, NFPA 96 specifies minimum clearances
between the exhaust outlet and property lines, adjacent buildings and air
intakes as well as minimum height levels of the outlet above adjacent air intake
devices.
The requirements for wall terminations are equally specific, particularly
with respect to clearances from the outlet to adjacent buildings, power lines, air
intakes, doors and windows, etc. At no time should grease from a commercial
kitchen cooking exhaust be allowed to run down the wall of a building.
Note: Exhaust termination requirements are shown in codes as minimum
requirements. Consideration must still be given to make sure that grease build
up will not occur through roof top air intakes or in surrounding structures.
34
Air Flow
Air Flow
Every commercial kitchen requires make-up air to compensate for the air
ventilated from the kitchen space to remove heat, cooking odors and grease
created by cooking operations. Ventilation is also essential to maintain a
comfortable work environment. Make-up air can be taken from the building
HVAC system of which the kitchen area is usually a part, as illustrated in Figure
29. While this is frequently done, it is an expensive and inefficient method of
replacing exhausted air.
Quite apart from the obvious need to replace air removed from a kitchen,
inadequate make-up air will prevent the kitchen operating the way it should. Air
will be drawn in from other areas through doors and passageways.
In keeping with new requirements in kitchen ventilation, VM has introduced
a number of devices for ventilating kitchens, which include kiosk ventilation
units, air cleaning systems, water wash filter hoods with make-up air packages,
dampers for adjustable volume control and fire dampers.
The easiest situation in which to provide make-up air is in a free-standing
building of one level construction, such as found in food courts or restaurants.
The complexities of providing make-up air increase as the building in which the
kitchen operates changes from the detached, single-purpose building to the
multi-story tower structure (see the Design Section for further discussion of this
subject).
Make-up air can come from the room HVAC system, either from outlets
near to the hood or integrated into the hood. The use of cooled and heated
make-up air is expensive. For example, utility bills can double and triple. (Every
200-400 cfm of air requires one ton of A-C system capacity, which is expensive.)
Following is a summary of the devices and systems available to solve the
35
Ventilation Systems
problem of providing make-up air.
Distributing air from the ceiling near the hood with low air velocity provides
local cooling that is a necessity because of the strong radiant heat created by
cooking appliances. Increased airflows did not raise metered indicators at the
same ratio, which proves that good results in kitchen ventilation can be achieved
with careful design and efficient equipment without excessive airflows.
The following are some basic principles of commercial kitchen ventilation:
1.
2.
3.
2.
3.
than that of heated air rising from the cooking surface, which
results in spillage of contaminated air held within the hood.
The lower temperature of the make-up air combined with the
greater velocity causes the air to drop rapidly, pulling
contaminant into the operator's face.
The direct down discharge can make it uncomfortable for
kitchen staff, especially in cold climates. As a consequence,
operators often shut off the make-up air system, thereby
Air Flow
untempered outdoor air within the hood enclosure to reduce the amount of air
the HVAC system must supply. This may seem to reduce the cost of using the
HVAC system, but unless the velocity of the supply air is strictly controlled
its velocity can exceed the velocity of the exhaust air and cause smoke
emission from the hood cavity.
The difference between discharging make-up air into the kitchen space
from the hood bottom front lip (Figure 30) and the short cycle method
(Figure 31) lies in the air discharge exits of the two arrangements.
In addition to the chance of emitting smoke, safety problems can arise
with short cycle hoods. In northern regions, for example, cold air can cause
frost build-up on fire protection fusible links, which effectively prevents the
links from detecting fire.
Front panel make-up air
The front panel type of make-up air (see Figure 32) is effective for virtually
all applications and climates. A perforated stainless steel plate keeps the air
flow velocity between 300 and 500 fpm. This permits the supply of a large
volume of air at the hood, with little or no effect on the kitchen environment.
The low velocity of make-up air means that it is felt only 3 to 4 feet from the
hood face.
During winter months, it may be necessary to heat the air of front panel
type make-up air (50o - 60oF is recommended). The need to cool the air during
the summer period is, however, negligible because the incoming air provides
evaporative cooling to kitchen staff working under the effect of radiant heat
generated by the cooking operation. Special consideration for some cooling may
be required in hot, humid climates.
Exhaust and make-up air limitations
If one site provides ample access for duct shafts to exhaust to the roof and
provide outdoor make-up air back to the kitchen, there are others with restricted
access. This poses problems. With no obvious solution to providing the required
air changes or to providing exhaust to the roof, and with space limitations that
make the installation of equipment difficult, the designer has many problems to
37
Ventilation Systems
overcome. A number of options are, however, available.
These are by no means the only options available for situations in which a
38
Air Flow
Why ventilation systems are essential
Cooking produces heat, odors, smoke, vapors, airborne grease and other
pollutants, which is true of all cooking operations regardless of the type of food
preparation being done. When a ventilation system breaks down, the kitchen
atmosphere soon becomes stifling and impossible to work in. Hence, a constant
supply of fresh, clean air is essential.
The ventilation system must exhaust the heat produced and remove the
odors and pollutants. A kitchen which specializes in producing light snacks,
sandwiches and salads generates less heat and odors than kitchens producing
heavier fare: steaks, hamburgers, and French fries.
Venting cooking equipment
Gas, electric and steam cooking equipment must be allowed to breathe. Proper
air flow is required for combustion, to exhaust fumes and odors, and to prevent
moisture and heat build-up in control cabinets. Too much exhaust can suck the
heat out of an oven, preventing it from properly baking or roasting the product;
too little exhaust can cause a control cabinet to overheat and burn out expensive
equipment. Knowing what the cooking equipment requires for ventilation is
critical to its performance and operating life. If the cooking equipment does not
work properly, the kitchen will not remain in business long.
Maintaining negative pressure
The final reason why efficient ventilation is necessary is the need to maintain
negative pressure in any kitchen area. Negative pressure means drawing air into
the kitchen space atmosphere to contain the odors and pollutants that cooking
operations generate.
Kitchens operating under positive pressure force cooking odors into spaces
outside the kitchen envelope. This is unacceptable in most instances and
certainly in places of shared space: food courts, hotels, office buildings, and
even in large, stand-alone structures where the owner-operator wishes to
maintain fresh air free from excessive cooking odors in large dining
39
Ventilation Systems
areas.
Combination of equipment
The type and combination of kitchen equipment used affects the design and
capacity of the ventilation system. Deep-fryers and open ranges produce more
pollutants and continuous heat than closed ovens. When opened to remove
roasts, pizzas and baked products, ovens release waves of intense heat with
which the ventilation system must cope to maintain a stable atmosphere in the
kitchen space. The type of equipment required is one factor; the use of kitchen
space is another.
Regardless of the source of make-up air, it is necessary to calculate the
make-up air required for a given kitchen operation. This will depend on the type
of cooking being done, the equipment installed, and restrictions of the building
configuration. Some considerations to take into account when calculating the
make-up air and equipment required are:
C
C
The cooking equipment being used, to determine where the most smoke,
grease and heat will be produced along the cooking bank.
Air Flow
C
The hood arrangement and wall locations around the cooking equipment,
island operation, or a combination of island and wall locations.
For light duty equipment such as steam and ovens, use 250 CFM per
linear foot.
In the majority of instances, the CFM estimates given in the guide will provide
ample air for the exhaust requirements. The guide serves for wall-mounted
canopies only. It does not serve for island applications, single cooking bank
arrangements or in cases where, say, the designer wants to know the absolute
minimum requirements.
CFM calculations for hoods
The terms used to calculate CFM values are:
Minimum exhaust cfm = Capture area x capture velocity + equipment cfm
correction factors.
Capture area = all open sides of the hood x the height above the cooking
equipment (in feet).
Capture velocity = 50 fpm (minimum.)
Equipment cfm correction factors = see Table 5 in left hand column of this
page.
A sample CFM calculation based on the elements discussed in this section is
shown in Figure 34.
41
Ventilation Systems
18'
3.5'
Broiler
Kettle
3.5'
3.5'
Range
Fryer
Fryer
Griddle
Note:
Using a rule of thumb for medium
duty cooking of 300 cfm/linear foot
of hood, the total cfm is
= 300 x 18 = 5400 cfm
16.5'
Min. exhaust cfm = (W1 + W2 + L) x H x 50 broiler + fryer + griddle
= (3.5 + 3.5 + 18) x 3.5 x 50 + (225 + 75 + 75 + 150)
= 4375 + 525
= 4900 cfm (min.)
Figure 34 - Sample cfm calculation
2.
3.
Air Flow
Example
The specification is for 2250 CFM on a 9' ventilator.
OPN
VEL
2.6
For quick reference, use Table 7.
Measuring intake velocity
VM recommends the use of either an Alnor 6000 or Alnor Jr. to measure the air
velocity through the slot of Cyclo Wash and Cyclo Maze ventilators.
To measure velocity at the throat using the Alnor 6000 (see Figure 35)
position the tip of the velometer probe halfway between the inside rim and the
face of the access panel at a plane perpendicular to the air stream. Do not put
the probe too deeply into the intake throat or you will get erroneous readings.
Make sure that the hoses are of reversed polarity (+ to - and - to +) when
measuring the exhaust. Take a minimum of three readings, evenly spaced, at
each access door, then average the readings to calculate the exhaust rate.
The Alnor Jr. (see Figure 36) has a dual scale range to 1600 FPM and is
another convenient way of measuring the intake velocity. Position the velometer
as shown in the figure and take multiple readings at various points across the
length of the intake throat. Because the instrument is calibrated for use in an
upright position, expect a slight error (to 5%) on the high side. If accurate
readings are needed, use an Alnor 6000 velometer.
43
Ventilation Systems
44
Auxillary Equipment
Auxiliary Equipment
Ventilation Systems
path of exhaust air except where specifically approved for that use in
grease ducts. For example, they are essential in fire control and protection
devices such as fire doors.
C
Fans
The selection of fans for ventilation systems, either to exhaust or to provide
make-up air, is an important consideration. Many types and arrangements are
available.
For typical roof top exhaust equipment and fan design improvement:
1.
Check the location and setting of the exhaust air discharge in relation
2.
3.
4.
5.
Auxillary Equipment
6.
Stop the build-up of water in fans during heavy rain storms and when
7.
8.
9.
10.
11.
12.
Fan location
Light, aluminum construction
& access area
Wiring to run
outdoors to fan
VMs grease exhaust roof fans are heavy duty UL\ULC units listed for 3
clearance from combustible material. A discharge clearance of 40 above the
roof line as required by NFPA 96 eliminates discharge duct work above the
roof. This unit, shown front view in Figure 41, has removable access doors for
servicing, a pivoted fan drive section to give access to the exhaust duct, and an
average discharge velocity of 3,000 fpm as recommended by
47
Ventilation Systems
environmental authorities.
Filtration systems
The ecology filtration system of an Ecoloair unit removes 95 per cent (and 99%
as measured by ASHRAE Standard 52-68) of particulates over 0.03 microns.
This virtually means the removal by filtering of all smoke and grease, which
means that part of the odor-carrying material is removed from the exhaust.
Molecules too small to be filtered out, however, convey most of the odor. This
material is chemically treated by VM's Scentry liquid odor control solution,
which reduces cooking odors to innocuous levels.
VM rates odors for cooking operations in three categories:
C
High: This category covers large volume restaurants, hotels and 24-hour
food preparation operations using large broilers and preparing fragrant
foods for 16 hours a day or more.
Heat exchangers
Relative to make-up air systems, cooking operations require large amounts of
energy. Up to 70 per cent of the heat energy needed for cooking is exhausted to
atmosphere when drawing in make-up air and exhausting the used air.
Recovering this otherwise lost energy by means of an air-to-air heat exchanger
is possible and has obvious economical advantages in the right circumstances.
It is part of the kitchen consultant's job to include this in any kitchen planning
48
Auxillary Equipment
study. This section will help clarify the main points.
Exhaust air temperatures in the order of 85oF to 95oF at 50% RH make the
heat recovery option economic, when the air volume being considered is in
excess of 5,000 cfm. For air volumes less than this level, the energy cost saving
may not cover the cost of the equipment. These are general statements, but give
some idea of the point at which heat recovery is worth considering.
Nevertheless, since the make-up air is about 80% of the exhaust air there is
more heat in the exhaust air stream to recover, which allows a higher
temperature rise in the fresh supply air stream.
Kitchen heat recovery equipment usually handles exhaust air laden with
airborne greases given off by the cooking equipment. As this can easily plug up
the heat exchanger it is necessary to wash and clean the coil frequently.
Depending on the application, a detergent spray wash system is fitted on the
exhaust side of the unit. The frequency and duration of the spray is adjustable
to suit the particular operation.
Note: Heat pipe systems are normally used for this application as air-to-air
plate type heat exchangers are difficult to clean and maintain in greasy cooking
applications.
Another way of dealing with grease-laden air when using heat recovery
equipment is to filter the exhaust air before it enters the heat exchanger. Again,
the relative cost of this method as compared with a wash feature on the heat
exchanger requires study.
A rule of thumb to calculate savings from the installation of a heat
recovery system is $1 per cfm per year. A pay-back period of two to four years
would be the second criterion to use. To use an example, if the supply air
volume being handled is, say, 10,000 cfm, the saving in fuel costs would
amount to $10,000 per year. Applying the pay back period of three years, a
capital cost estimate of $30,000 for energy recovery equipment is an economic
investment.
49
Ventilation Systems
Access panel
Isolated electrical
chase
Example
Location of branch
circuit breaker
Bus bars or
panel box
Isolated
plumbing chase
Equipment
bumper rail
Cords and plugs
or sealtite conduit
available
50
Mechanical
services available
Gas
Hot water
Cold water
Steam supply
Steam return
Chilled water
Compressed air
Auxillary Equipment
Features of the MDS
Features of the modular distribution system (see also the Engineered Features
Section) are:
C
Full function capabilities are available for gas, electric, hot water, cold
water, steam, chilled water, and compressed air services.
Flexibility is built into the system allowing for additions and changes.
51
Ventilation Systems
Raceway Options
24"
(Typ)
Typical electrical
plates configuration
12"
(Typ)
72"
Space between
electrical plates
31"
MDS-GW Unit
Note: Raceways can be wall mounted
2" Gas
Breaker
6"
3/4" C.W.
Insulated
1.5"
Receptacle
28.5"
21.5"
3/4" H.W.
Insulated
6"
3/4" H.W.
Insulated
Bumper strip
8"
3/4" C.W.
Insulated
1.5" Steam
insulated
MDS-GW Unit
View A-A
1.5" Gas
1" Condensate
return insulated
12"
MDS-GWS Unit
View B-B
24"
(Typ)
12"
(Typ)
12"
Typical electrical
plates configuration
72"
B
MDS-GWS Unit
24"
Figure 43
52
Auxillary Equipment
Riser Options
for MDS-GW & MDS-GWS Units
72"
72"
(Recommended)
(Recommended)
Electrical
Electrical
& plumbing
Pedestal
Plumbing
MDS-GW-EL/PR
MDS-GW-EPR
72"
72"
(Typical)
Electrical
& plumbing
(Special)
Plumbing
MDS-GWS-EPL/PR
Electrical
& plumbing
MDS-GWS-EPL/EPR
53
Electrical
& plumbing
Ventilation Systems
Note 1: There are three VM KVS models available. These are the KVS-5,
the KVS-6 and KVS-8. Referring to the table of cooking equipment, a KVS-5
can satisfy a cooking load for a maximum of 2 appliance; a KVS-6 for 3
appliances; and a KVS-8 for 4 appliances. See also the Codes and Specifications
Section.
Note 2: A recirculating hood system must meet the requirements of NFPA
96, Chapter 10 and be tested and listed as per U.L. 197-1994 for integral
recirculating systems for commercial electric cooking appliances. A clean air
EPA 202 test must also be passed using the specific cooking equipment being
used with the system.
54
Fire protection and control is an integral part of any kitchen ventilation system.
The subject is specifically addressed in the NFPA Standard, which requires fire
extinguishing equipment for the protection of grease extraction devices and
cooking equipment. NFPA 96, however, is not the only standard local regulatory
authorities apply to commercial kitchen systems.
Automatic fire extinguishing systems are an increasingly common feature
of modern kitchen ventilation systems. Indeed, most codes require that automatic
fire protection systems form part of the ventilation system. This system must not
only provide fire protection, but also automatic disconnection of the fuel supply
to the cooking equipment if a fire occurs.
The three primary types of fire protection systems are dry chemical, wet
chemical and water sprinkler, which are summarized here.
Dry chemical systems
The chemical most often used in a dry system is a sodium bicarbonate based
material. In this type of system, the chemical suppresses the flame and reacts
with the grease to form a foam, which prevents the grease and vapors from
escaping to the atmosphere. The dry chemical system is being replaced by the
more efficient and cost effective wet chemical system and will soon be removed
from the field for new installations.
Wet chemical systems
In contrast, wet chemical systems most commonly use a potassium carbonate,
potassium acetate, or CO2 based formulation. The wet chemical is similar to the
action of dry chemical in suppressing the flame and preventing or retarding the
escape of grease vapors to the atmosphere.
Both wet and dry chemicals are effective fire extinguishing agents, but
both have several disadvantages. The most obvious is that, following
55
Ventilation Systems
activation and suppression of the fire, the cooking line requires thorough
cleaning to restore it to an operating condition. As a result, the down time can
be lengthy. Also, to conform to fire regulations, the chemical agent must be
replaced before a resumption of cooking. If a reflash occurs, there is no agent
left to discharge a second time. Also the system discharges all at once over the
entire cooking bank.
Water sprinkler systems
A water mist sprinkler installation is a preferred means of providing fire
protection in a kitchen. Water mist sprinkler systems are easily interconnected
to a building's sprinkler system. A fire detecting element fitted in each of the
system's nozzles guarantees that water comes from an activated nozzle only.
Once the fire is extinguished, the water supply is easily shut off by means of the
hand operated valve in the control cabinet.
Once activated and the fire suppressed, clean-up is quick, easy and
simple with, as a consequence, a minimum down time of the cooking line.
The general requirements for fire suppression systems are:
C
The minimum water pressure at the control cabinet must not be less than
40 psi.
C
C
The maximum pressure at the cabinet must not exceed 175 psi.
If the authority having jurisdiction accepts a water pressure greater than
175 psi, the contractor responsible for the sprinkler installation must
supply and install an approved pressure reducing valve.
The minimum water flow required in gpm will depend on the pipe size of
the system. Refer to the pipe size chart -
C
C
Table 9.
The size of pipe required is determined by the number of nozzles (see
Table 10 in the Installation Section).
56
Nozzles Min
Max.
Nozzles Disch. GPM
8
12
20
30
2
4
6
8
15
30
45
75
Model
No.
SU3-100
SU3-125
SU3-150
SU3-200
No. of
nozzles on
system
57
Space occupied by
cooking equipment
per project specifications
(supplied by others)
Ventilation Systems
Surface fire protection
The number of nozzles required in a fire suppressor system depends, of course,
on the variety and number of items of cooking equipment.
VM calculates the number of nozzles required and designs each system to
meet the cooking bank lay-out requirements.
Nozzles
The sprinkler nozzle is an important part of any fire protection system. Table
10 (see the Installation Section) gives hydraulic data based on the size of
piping and number of nozzles in a system.
For installation, nozzle settings and related information, refer to Figure 47
in the next section, Installation.
Fire dampers
There is considerable divergence of opinion among various code authorities,
inspectors, engineers, consultants and manufacturers on the need for and
effectiveness of fire dampers in commercial cooking exhaust hoods.
There are two bodies of opinion on the use of dampers. The first is that
U.L. listed and properly installed dampers can contain a fire and that the
mechanism will not permit the ambient air temperature in the exhaust duct work
to rise above 365oF. This parameter is established under U.L. Standard 710 and
VM products listed under this evaluation have passed this requirement. Here the
intent is to contain a fire within the hood or a portion of the exhaust duct work
to avoid transfer of the fire into adjoining areas of the building. This minimizes
fire damage and is some insurance against loss of life, particularly in
multi-story buildings.
The second body of opinion is to install exhaust systems and not to permit
a damper of any kind, so as to allow the fire and smoke to escape through the
exhaust duct to give building occupants more time to leave the building. This
approach relies strictly on the construction of the duct, the rated duct shaft
enclosure, and the ability of the building to contain the fire until it is
extinguished. The principle behind this approach is that loss of life occurs
through smoke inhalation much sooner than by any fire in a building.
58
Ventilation Systems
the test there may be no separation of seams or undue buckling of the unit. No
flames or temperatures in excess of 375oF may enter the exhaust duct at any
time.
The U.L. test is conducted without the use of water, the assumption being
that a fire could render the water wash function inoperable. For this reason, the
U.L. listing does not require the grease extractor to go into a wash down
mode during a surface fire.
Fire marshals, building inspectors and specifiers in some areas do require
that the wash function be energized simultaneously with the fire protection
system. There are several ways of achieving this function. They are:
1 Specify a control panel that interconnects to the fire protection panel. When
it is specified, VM adds a firestat relay to the control panel. Wired in the
field, the relay allows an external control circuit to energize the wash timer.
(Specify 120V AC, 24V AC, or 24V DC.)
2 Specify a microswitch option with the fire protection system. This will be
supplied with the unit for installation by the fire protection or electrical
contractor.
3 Specify that the electrical contractor provides a separate control circuit
(120V AC unless otherwise specified) to the fire protection panel. From
there the contractor should provide a 2-wire service to the ventilator control
panel and the cooking equipment disconnect.
For detail regarding the inter-connections between the ventilator control panel
and the fire protection panel refer to the Installation Section under Listed
grease extractors, electrical controls.
Automatic duct protection
Fire protection of ducts equipped with dampers is by means of fusible links that
monitor the exhaust temperature at the duct collar. Rated to activate at 280oF,
the fusible link will cause the damper to close.
60
Installation
Installation
ECOLOAIR INSTALLATION INSTRUCTIONS
AND DESIGN REQUIREMENTS
All duct connections to the unit must be transitioned to the full opening at
the unit inlet and outlet openings.
All duct work between the ventilator, the Ecoloair unit, and downstream
of the unit is by others.
Maintain a minimum 30 clearance on the access panel side of the unit for
servicing and replacement of the filter.
Install the filters in the correct sequence (see the Section on Grease
Removal Devices) and make sure the panels are properly seated against
the filter support frame.
Remove the fan spring isolator hold-down brackets before starting the
exhaust fan. The brackets are used for shipping purposes only. When the
brackets are removed, the exhaust fan should float freely on the spring
isolators. Make sure the fan does float freely.
61
Ventilation Systems
C
A qualified structural engineer should verify that the structure will support
the additional load and provide the qualification details. This applies to all
applications: roof mounted, ceiling suspended or any other form of
mechanical structural support.
Provide suspended units with a service platform along the entire length of
the unit. Service platforms supplied by others should provide a minimum
clearance of 30 for servicing access as specified for replacing the filter.
Electrical
Connect the incoming 3-phase, 60 cycle power supply to the main disconnect
of the fan starter of the exhaust fan section.
Caution
The electrical power rating shown on the control panel will determine the size
of the power cable, which must conform to the applicable electrical codes.
C
package of shop drawings shipped with the unit and make the following
electrical connections. (Additional copies of shop drawings are usually
available on request.)
Note
Use 120V 14 gauge (min.) AWG wire for control wiring connections between
panels. It is, however, necessary to check that wiring used for field connections
conforms to the applicable local electrical codes.
C
Through conduit run between the exhaust fan cabinet panel and the
pressure sensor enclosure on the filter section, make the control wire
connections as shown on the wiring diagram supplied.
Connect the field wiring from the Ecoloair control panel to the ventilator
control panel or disconnect switch, whichever is applicable as shown
62
Installation
on the wiring diagram.
C
Sound levels
Workers and the general public are becoming increasingly concerned with noise
pollution in all its forms: blaring radios, Musak systems, loud machinery,
engine noises, aircraft near airports. Conscious of the need to eliminate
unnecessary noise in its equipment, VM has designed its Ecoloair system for a
smooth-running minimum noise operation and has available acoustic insulation
options; (consult the factory if required).
FIRE SUPPRESSOR SYSTEMS INSTALLATION
INSTRUCTIONS AND DESIGN REQUIREMENTS
Some local codes and regulations may not permit connection to the building
domestic water system. This needs investigating. If the connection is not
approved, operation of the fire suppressor system might trip the low water
pressure switch, shut down the equipment, and register an alarm. The water
pressure must be constant and uninterrupted.
Sprinkler nozzles
The positioning and setting of sprinkler nozzles varies from one type of cooking
equipment to another. Particular features follow for each type of ventilator or
item of cooking equipment. Table 10 is a nozzle temperature rating chart.
Canopy ventilator
Figure 47 illustrates the important setting and positioning features of sprinkler
nozzles in the canopy drop ventilator. Accurate leveling and positioning of the
nozzle frame below the lower edge of the ventilator face is essential.
63
Ventilation Systems
64
Installation
Plumbing
Piping for the suppressor manifold is sized according to the number of nozzles
required. The suppressor system, complying with the requirements of NFPA 13,
is for incorporation in the building sprinkler system. For this reason, the
sprinkler contractor will need to review the water requirements and number of
nozzles.
Note: VM duct and plenum nozzles are rated at 325EF. For special
applications or for equipment not shown in this chart, consult the factory.
Nozzles have a 1/4" orifice.
Backshelf ventilator
Duct and plenum protection is required for dry-type hoods only when surface
protection is needed or when local codes and regulations specify it. (See
Figure 48.)
65
Ventilation Systems
Fryers
Installation
max. as measured from the cooking surface to the nozzle deflector (see Figure
51). For the head temperature range, refer to Table 11.
Salamander broiler
Each salamander broiler requires a nozzle. This must be positioned within the
nozzle plane area 1 to 3 below the broiler compartment opening and between
0 to 3 in front of the opening. See Figure 52, which includes the applicable
head temperature information.
67
Ventilation Systems
Upright broiler
One nozzle is required for each compartment of an upright broiler, each nozzle
being positioned in the same place specified for the salamander broiler (see
Figure 53).
A tilt fry pan up to 48 wide requires one nozzle positioned within the nozzle
plane 6 square area, starting 1 in front of the fry pan center and centered
left to right. The head temperature is 175oF.
A fry pan cover in the upright position may require a different
nozzle location. This is best determined by checking the clearance when the
cover is moved from the closed to the open position (see Figure 54).
68
Installation
Conveyor broiler
Conveyor broilers require three nozzles, one for each conveyor opening
positioned within a 6 square area nozzle plane and the third for the exhaust
opening. The plane is 1 to 2 below the bonnet or opening flush with the end
of the bonnet and centered left to right on the end of the broiler (see Figure 55).
Plenum protection for hoods
One nozzle protects up to 10 ft. of plenum length, the nozzle to be positioned
in the center of the plenum, left to right, and 2 1/2 away from the back of the
plenum. Two nozzles are required for a plenum of between 10 ft. and 20 ft in
length. The nozzles are to be positioned 1/4 of the total length from each end of
the plenum and 2 1/2 from the back of the plenum. See the threeviews shown
in Figure 56.
1" pipe
1" pipe
Duct collar
1" pipe
A'
2xA
10' 0" to 20' 0"
Front elevation
Front elevation
2 1/2" +/- 1/2"
1 1/2" to 2 1/2"
Top of pipe
Make sure top of
pipe clears swing
of damper
Section at pod
69
A'
Ventilation Systems
Duct protection for hoods
Duct protection is required only when it is specified or required by local
codes.
One nozzle will protect a duct with a maximum dimension of any side
not exceeding 30. The nozzle should be positioned in the center of the duct
within 1 min. to 12 max. from the top of the damper blade.
Ducts 31 and larger on any side require two nozzles positioned at
quarter points from sides not equipped with a damper and from the top of the
plenum. Ducts fitted with nozzles require service access doors of adequate
size, grease and water tight, and of approved construction (see Figure 57).
Test valve arrangement
Each suppressor control cabinet requires one test nozzle positioned at the most
remote ventilator after the last sprinkler head of the system. In Figure 58, the
water-wash hood is shown in solid lines, the filter hood arrangement in broken
lines.
Fire system certification
The sprinkler contractor or an agent of the local fire authority is responsible for
certifying the fire system. A manufacturer is not responsible for testing or
certifying the system. Most codes require that fire systems be tested and
recertified annually. A manufacturer is not liable for problems attributable to
water pressure, installation, testing or certification.
Listed grease extractors, electrical controls
The Fire Protection Equipment section deals with specified requirements of
control systems concerning the control circuit to simultaneously energize wash
function of listed grease extractors with the fire protection system. Figure 59
and Figure 60 outline typical wiring interlocks with exhaust hood water wash
panels and cooking equipment shutdown interlocks.
70
Installation
71
Ventilation Systems
72
Installation
73
Ventilation Systems
74
Maintenance
Maintenance
75
Ventilation Systems
Monthly
C Clean the water line strainers: on both hot and cold water models, if water nozzles
become clogged with scale, remove and immerse them in vinegar for half an hour.
C Check that the solenoids and relay click when the START and STOP pushbuttons
are energized.
C Pour a pint of full strength detergent in the bottom of each ventilator section and
let it sit overnight.
C Check the duct work.
Twice a year
C Thoroughly clean the unit and related duct work to remove grease. A commercial
cleaning service is recommended for this work. The frequency of cleaning will
depend on the type of operation being used.
Non-water wash hoods
Daily/weekly as required
C Use hot water and detergent to clean the ventilator and remove any surface grease.
C Remove and clean the access panels to inspect and clean the interior of the unit.
C Clean the grease collection pans.
Twice a year
C Thoroughly clean the unit and related duct work to remove grease. A commercial
cleaning service is recommended for this work. The frequency of cleaning will
depend on the type of operation being used
General requirements for start-up
C To help maintain the equipment warranty, obtain an authorization number from the
Service Department before starting up the equipment following installation.
C To make sure the service technician is on site at the right time, contact the job site
manager and the dealer for coordination.
C Have the correct drawings available for the equipment start-up.
C The system cannot be fully checked if the kitchen is already in operation. If this
is the case, contact the Service Department for instructions.
C Thoroughly check the system, the ventilators, ducts, air passages, water strainers
and control panel for foreign material: dirt, tape, fabric, tools.
76
Maintenance
Control panel
1.
The control panel is wired with 18-gauge wire and has a 3AG 8
amp fuse. The incoming power line is a field connection at
terminals 1 & 2. Check that there is 120V AC between terminals 1
& 2.
2.
3.
Control panels are for cold water mist and hot wash as well as for
hot water only.
4.
5.
6.
Check that the cold water pressure at the panel is at 20 psi. of the air
column.
7.
8.
9.
Cold water mist in the hood [distributed from the lower row of
nozzles] greatly improves grease removal.
10.
The RUN switch and the momentary switch will open the cold
water solenoid, and start the fan and mist.
When the switch is in the wash position, the momentary switch
drops out the cold water solenoid and stops the fan. The hot water
and detergent pump are activated.
11.
77
Ventilation Systems
12.
13.
14.
15.
78
Design
Design
Ventilation Systems
and vapor state, other solids, and volatile organic compounds (cooking odors).
Failure to remove the grease first will result in the fouling of the odor control
system.
Grease removal starts in the hood with the grease removal devices such as
baffle filters. The more effective these are, the less necessary it is to install
additional equipment downstream of the hood. The next device is almost always
another grease removal device to capture the remaining grease. The odor
removal device follows.
Grease extraction filters are tested and listed for their ability to limit, but
not totally prevent, flame penetration into the hood plenum and duct, not for
their ability to extract grease. Research shows that grease particles are so small
(less than 20 m diameter) that they are aerodynamic and not easily removed
by the centrifugal impingement principle usually used in grease extraction
devices.
The following summarizes the filtration technologies available today and
applied to varying degrees for control of cooking effluent. Quoted from the
earlier referenced 1995 ASHRAE Handbook, they are listed in common order
of use with particulate control upstream of the VOC
compounds) controls.
(volatile organic
Water mist, waterfall, and water bath: The water forms a barrier that
mechanically entraps the particulates as the effluent stream passes by.
C
Bath types have a high static pressure loss.
C
Spray nozzles need attention to deal with the build-up of scale.
Watermay need to be softened to minimize clogging.
C
Drains can become blocked if the system is not maintained.
Electrostatic precipitators (ESPs): Particulate removal is by high-voltage
ionization, then by collection on flat plates.
C
Design
Pleated or bag filters of natural and synthetic fibers: Very fine particulate
removal is by mechanical filtration. Some types have an activated carbon face
coating for odor control.
C
C
C
Oxidizing pellet bed filters: VOC and odor control is by oxidation of gaseous
effluent into solid compounds.
C
C
C
C
In addition, for fire safety, grease should be eliminated entirely or drained from
the duct to a safe container.
Liquid odor control systems: Dispense a powerful odor eradicator into the
81
Ventilation Systems
cooking exhaust air on a continuous programmed cycle. This mist spray of
atomized particles permeates the exhaust air, attacks and neutralizes airborne
odors and the bacteria that cause odors. The odor control system works
continuously while the exhaust fan is operating.
C
C
If a fire occurs, neither the flames, nor the radiant heat, nor the dripping
grease should be able to ignite the roof or nearby structures.
All grease from the fan or the duct termination should be collected and
drained to a remote closed container to preclude ignition.
Rain water should be kept out of the exhaust system and especially the
grease container. If this is not possible, then the grease container should
have a design that separates the water and grease and drains the water
back onto the roof. Figure 63 shows a roofing upblast utility set with
a stackhead fitting, which directs the exhaust away from the roof and
minimizes rain penetration. Discharge caps should not be used because
they direct the exhaust back toward the roof and can become fouled with
grease.
Outside wall: The fan of a wall termination may or may not be the terminus of
the system, located on the outside of the wall. The common concerns with wall
terminations are:
C
Discharge from the exhaust system should not be able to enter any fresh
Design
Upper stack held off from
lower stack 10 mm ON ALL
SIDES. Bracket upper
stack to lower stack.
4 Dh
150 mm min.
For round duct, Dh = D.
For rectangular duct,
Dh = (H + W/2)
Reducer if necessary to
increase stack velocity
to disperse effluent
C
C
C
Duct sections should pitch back to the hood inside, or a grease drain should
be provided to drain the grease back into a safe container inside the
building to prevent grease from draining down the side of the building.
The discharge must not be directed downward or toward any pedestrian
areas.
Louvers should be designed to minimize grease extraction effects and to
prevent staining the building facade.
To ensure clean, safe exhaust discharge, an approved air filtration device
should be added in the duct system.
Figure 63
Types of installations
In the introductory chapter to this manual we touched on the types of buildings
in which commercial kitchen operations are conducted. These include high-rise
buildings of various architectural designs, some suited for venting to the roof
and some not. Historical sites, food courts, existing buildings such as hospitals,
schools and penitentiaries all present the designer with features and factors not
found elsewhere.
Although each site requires separate assessment, study and treatment the
following illustrates some of the problems encountered and factors to take into
account.
In general, considering both traditional and non- traditional sites, a number
of options are available to the designer. Options 1, 2 and 3 following illustrate
three of these.
An existing installation
Roof-mounted exhaust and make-up air systems are installed to meet the
applicable codes. The design shown in Figure 64 exhausts 100 per cent of the
required air volume and replaces 80 per cent of the make-up air directly back
into the kitchen using outdoor air through some type of ventilation unit, which
possibly provides heat, air conditioning and free cooling.
83
Ventilation Systems
Cooking
Serving
20%
transfer
Preparations
Exhaust air of
general building
system
Inlet air
Clean, recirculated
air
Cooking
Return air
Serving Preparations
operations, cleaned exhaust air can be vented through an exterior wall for low level exhaust asFigure 66
illustrates.
Transfer air
Cooking
Serving
Preparations
84
Design
Filter
Clean exhaust air
Low level exhaust
Fan
Odors
Cooking
Transfer
air
Serving Preparations
Fan
Odor
Filter
85
Ventilation Systems
Odor control
Factors that affect cooking exhaust odors are:
1 Food being cooked. Fish, chicken, sauces and marinades, garlic, etc.,
produce noticeable cooking odors.
2 How food is cooked. Broiling, frying, wok and saut produce smoke, steam
and vapors that carry odors. High heat, charring or burning may increase
odor production.
86
Design
3 The number of meals cooked per day and actual cooking hours.
4 The volume of air in CFM exhausted from the kitchen.
5 The state of cleanliness of the ducts, hoods, cooking equipment and the
presence of rancid grease and garbage odors.
Liquid odor solution
The use of non-approved products in Ecoloair and Ecolo-spray odor-reducing
units voids the warranty on odor control and other components that may be
affected, including the fan and motor. The liquid solution works. It does not
clog the nozzle nor does it leave oil or harmful residue downstream of the odor
cabinet.
Special odor problems
The sense of smell is subjective. What one person finds pleasant another might
find unpleasant. When cooking odors collect in confined areas of buildings, in
cul-de-sac areas, courtyards and similar places one's sense of smell is
heightened. Otherwise pleasant cooking odors become offensive and present a
problem. This may have nothing to do with how good or bad the odor is as
much as the fact that the smell is inappropriate because it is retail space or
office or residential territory. The restaurant operator may wish to select
continuous spray settings on the odor control equipment as the preferred
option to handle tenant complaints or, even worse, health department citations
and law suits. In these circumstances, the use of filtration and odor-reducing
equipment may make the difference between being permitted to operate a
restaurant or not. In such cases, cost is of secondary importance.
Elements of ventilation design
Many factors affect the choice of a ventilation system that is right for a given
operation. Some are obvious from the options discussed for new and
non-traditional site problems encountered. One of the most important, however,
is cost. When cost is examined in terms of capital outlay and operating costs,
the whole concept of life cycle costing can be assessed in its proper perspective.
That is, a choice between high and low capital cost must be analyzed in
87
Ventilation Systems
relation to the life cycle cost to have meaning in terms of the whole economic
investment. For example, the cost of a conventional hood as compared with
an engineered ventilation system (EVS) pales into insignificance when the
initial savings are quickly lost in increased operating expenses. The same
reasoning can hold true for other major items of a system: the ducting,
extraction fans, grease extraction and controls.
Use of the available space for designing and installing an economic kitchen
ventilation system to manage the by-products of a cooking operation also
centers on basic elements. These are factors that affect the containment of
odors, equipment sizing and, by extension, the overall efficiency of the
operation. The elements are:
C
C
C
C
Design
Third
Calculate the make-up air required. This is where knowledge of the installed
HVAC system on an existing site is important. It is necessary to know the
volume of air delivered to the kitchen area by the HVAC system to calculate the
make-up air needed to offset the air exhausted from the kitchen.
Fourth
The NFPA 96 Standard is an excellent source of reference for making sure the
ventilation equipment complies with national requirements.
All the factors so far discussed can and do present problems in applying
ventilation principles. Frequently, problems stem from inadequate assessment
of the proposed cooking operation and the majority arise from ignoring factors
that affect the ventilation equation in some way. Conditions vary from site to
site, so it is necessary to assess everything that can change them.
Fifth
Odors are contained in the kitchen area by keeping the atmosphere under
negative pressure and then removing them through an exhaust hood using a
ventilation system of adequate capacity.
In energy management, it is necessary to calculate the minimum exhaust
required to permit efficient operation at the least cost. Energy costs money. The
less energy used to exhaust cooking vapors and provide make-up air, the lower
the operating cost. Efficient ventilation reduces operating costs and extends the
equipment's operating life. If, however, there is not enough exhaust air then the
kitchen space cannot operate efficiently and the cooking equipment will not
perform properly.
Sixth
Many problems occur in renovations or the conversion of space to a kitchen
operation through insufficient attention to detail.
In a traditional site application a separate, kitchen roof-mounted exhaust
and make-up air system is fairly common. The design shown in Figure 64
exhausts 100 per cent of the required air volume for cooking exhaust and
replaces 80 per cent of the make-up air directly back into the kitchen, using
outdoor air. This is done through some type of ventilation unit that may provide
heat and cooling.
An installation of this kind does all the things a good design requires:
89
Ventilation Systems
It removes grease vapor, heat and odors produced from the cooking
areas of the kitchen.
90
Design
Efficiency and costs
The life cycle cost of any electro-mechanical equipment has two main
components: the capital cost of the installation and its maintenance and
operating cost. Owners are concerned with the capital cost of the ventilation
system; the operator, however, in addition to paying for the installation, must
also consider the cost of upkeep and maintenance. Large chains that own and
operate commercial cooking operations concern themselves with the life cycle
cost of the installation.
Designers need to choose equipment based on a knowledgeable
understanding of the life cycle equation; will the client opt for a top-of-the-line
installation for the highest efficiency or be reconciled to something less? This
and similar questions are important and require answering. This is where
ventilation experts can help.
The efficiency of the system, its capital cost, and estimated operating cost
are important factors to consider when choosing equipment.
Factors that govern choice
Discussing the need for kitchen ventilation, we have dealt with the main
principles that affect ventilation. More particularly, what factors govern the
choice of a system? There are four main categories: structure and ecology; type
of cooking equipment; kitchen lay-out and equipment placement; and the type
of heating source used (gas, electricity or steam).
Placement of equipment
The placement of cooking equipment in the kitchen area dictates the type of
ventilation hood required to capture and contain the exhaust stream. The
combination of hood and equipment placement also influences the type and
capacity of the HVAC (heating, ventilation and air-conditioning) system.
Is the kitchen equipment in an island configuration? Is it placed against a
wall? In a corner? How does placement affect cfm calculations for ventilating
the space?
91
Ventilation Systems
Sound levels
The subject of equipment noise was discussed in the Installation Section, under
the subheading Sound Levels. It is worth repeating here. Noise is an especially
important consideration of ventilation systems about which kitchen designers
should be aware. Sources of noise in ventilation systems include:
C
Inadequately-sized air inlet and exhaust ducting for type and size of fan
or fans installed.
92
Design
Surrounding
commercial and/or residential area
Street front
Optional outdoor
playground
Entrance
Entrance
Exit
Serving area
General
seating
Drive through
pick up
Kitchen area
Entrance
Delivery and
Washrooms services
Parking varies
Figure 71 - Layout of typical
drive-through restaurant
1
Surrounding
commercial and residential areas
Playground &
2 pedestrians
Entrance
Exit
Building
3 entrances
Possible problems
Area
1
2
3
4
5
6
7
Smoke
x
x
x
x
x
x
-
Odor
x
x
x
x
x
x
-
Grease
x
x
x
x
5
Roof
7 area
Climate and
prevailing winds 6
Table 17
93
Kitchen exhaust
discharge
Ventilation Systems
94
Design
Type of fuel
[
[
[
[
]
]
]
]
Gas
Electric
Steam
Solid fuel (charcoal,
mesquite)
TM
EcoloAir Checklist
What codes & standards
apply?
[
[
[
[
[
[
[
[
[
]
]
]
]
]
]
]
]
]
U.L.
BOCA
NFPA 96
NSF
UL/ULC
UMC
SBCC
AGA/CGA
Local codes ---------
Optional equipment
95
[ ] Temperature sensor in
the Energy Reclaim
Module?
Note
This is a checklist reminder of the
applicable codes and standards, the
main features needed to meet a
particular client's needs. A detailed
specification for an Ecoloair assembly is provided in the Codes and
Equipment Specifications
Section following.
Ventilation Systems
96
Design
Option A
System diagram and budget pricing
GEF exhaust
fans - ULC
listed
Note:
The installation may require two or more shafts to balance the air flow
if the duct runs are too long or too difficult to size properly.
Budget Pricing:
Kiosk-mounted
exhaust hoods
$?
?
?
?
?
.
?
____
$
Figure 74
Option A
Central fan for all kiosks
Under this option, a single, roof-mounted fan connected to a main exhaust
duct serves each kiosk area via the branch ducts.
Advantages
C
It is the least expensive option.
C
It saves space because a single duct requires less floor and ceiling space
for exhaust shafts and fire-rated enclosures as required by codes.
Disadvantages
C
Difficult to balance exhaust cfm of each kiosk, as balancing dampers are
not per- mitted in ducts.
C
Difficult to change once installed: duct runs sized for originally
designed cfm and ducts welded.
C
If one kiosk shuts down due to fire, the exhaust velocity may fall below
the minimum of 1,500 fpm allowed by code and require a shutdown of
C
C
Ventilation Systems
Option B
System diagram and budget pricing
GEF exhaust
fans - ULC
listed
NFPA 96 welded
& fire-rated
enclosed duct
Kiosk-mounted
exhaust hoods
Budget Pricing:
Exhaust fan complete with roof curb
Welded duct work and fire-rated enclosures
Indirect gas fired make-up air heater
16,000 cfm rooftop unit (central)
Installation cost for above equipment
Shaft requirements
Loss of rentable floor space
Future relocation costs for fans if required
Interlocking of exhaust fans
Figure 75
$?
?
?
?
?
?
?
____
?
$
Option B
Separate exhaust for each kiosk
Under this option, each kiosk has a separate exhaust hood and roof-mounted fan.
Advantages
C
C
fixed range.
As each kiosk operates independently, it does not need to be shut down for fire in
another unit.
Disadvantages
C
C
C
C
Supply and installation of multiple exhaust shafts and fans is expensive, although
its flexibility makes this the most commonly used system.
Fans occupy a large roof area.
Separate systems are too small to justify the cost of a future heat recovery
installation.
The relocation of fans to accommodate changes in equipment lay-out is
98
Design
required.
C
If a central make-up air system is used, exhausts should be interlocked to a timer
system. Alternatively, separate make-up air systems are needed for independent
operation. Independent operation requiring increased roof area is common, but
code exhaust outlets and make-up air inlets must be 10ft. apart.
Option C
System diagram and budget pricing
Roof-mounted ecology
exhaust unit (mount fan
indoors if possible)
Kiosk-mounted
exhaust hoods
Budget Pricing:
VM Ecology B-20 exhaust fan, 20,000 cfm roof mounted
VM Ecology EF-20 filter box, indoor mounted
VM odor control
Duct work - NFPA welded and standard
Indirect gas fired make-up air heater, 20,000 cfm rooftop unit
Installation costs of this equipment
Extra cost to add heat recovery section (optional)
Benefits to add odor control
Savings to add future kiosks without relocating fans
Savings for duct cleaning and roof replacement
Figure 76
$?
?
?
?
?
?
?
?
?
___
?
$?
Option C
Central ecology system
The central ecology system option serves all kiosks in much the same manner
as the common fan of Option A. The difference is the addition of the
99
Ventilation Systems
filter unit, which can be located indoors if need be.
The ULC listed ecology system eliminates grease and smoke from exhaust
air. Odor control is an optional addition. The use of an ecology unit eliminates
the need for roof top discharge of exhaust air as well as welded duct work on
the secondary side of the filter box. (In the U.S.A., check local codes for
approval.)
Advantages
C
The exhaust air and ducts on the secondary side of the filter unit are
clean.
The equipment is less expensive than separate filters (see Option D).
A single shaft occupies less space than multiple shafts required for
Option B.
Standard duct work between the filter box and building exit does not
require welding nor a fire-rated enclosure. (In the U.S.A., check local
codes for approval.)
Heat recovery equipment can be added without the wash down feature.
C
C
If a kiosk is added, additional filter boxes can be tied into the existing
system.
If a new level is added to the building, the ecology unit need not be
relocated. A duct extension will accomplish the change or be redirected
through a side wall.
C
C
Disadvantages
C
C
100
Design
Option D
System diagram and budget pricing
Roof-mounted ecology
exhaust unit (mount fan
indoors if possible)
Future
systems
EF-4 ecology
filter boxes
Kiosk-mounted
exhaust hoods
NFPA welded
duct work
Budget Pricing:
VM Ecology B-30 exhaust fan (total 8 units x unit price)
VM EF-4 Ecology filter boxes (total 8 units x unit price)
VM odor control mounted on roof
Duct work - NFPA welded and standard
Indirect gas fired make-up air heater Temprite TDM-20,
20,000 cfm rooftop unit
Installation costs of this equipment
Extra cost to add heat recovery section (optional)
Benefits to add odor control
Savings to add future kiosk
Savings for duct cleaning and roof replacement
Benefits to balance system easily
$?
?
?
?
?
?
?
?
?
?
___
?
$?
Figure 77
Option D
Central fan and separate filters
This option consists of a single roof-mounted exhaust unit and a separate
filter unit for each kiosk.
Advantages
C
C
With a 4,000 cfm filter box per kiosk, there is room for future
expansion. (The cost difference between 2,000 cfm and 4,000 cfm
filters is minimal, whereas the doubled capacity accommodates any type
of kiosk size.)
A single main exhaust shaft occupying less space than multiple shafts
reduces costs.
101
Ventilation Systems
C
Disadvantages
C
It is not possible to recommend one of these options over another. The choice
made will depend on the particular circumstances of each application. Life
cycle cost analysis is an important part of any commercial kitchen plan
regardless of the size of the investment. The importance of cost analysis to the
project, however, increases with the level of the capital investment.
For example, Option C discusses the application of central ecology
systems. Their use may or may not be cost effective in single-story structures,
but have a clear advantage in multi-story structures with, perhaps, cooking
operations being conducted at the ground floor or mid-way up the building. In
this case, the expense of an ecology unit will compare favorably with fire-rated
shafts and ducting through many floors to the rooftop.
Filtration System
Ecoloair is the name VM has given to the modular air filtration system for use
in kitchens in which grease and smoke removal, environmental and odor
considerations are of paramount importance. The system contains three
sections: a filter section, an odor-reducing section, and an exhaust section. An
optional section for the Ecoloair filtration system, however, is an energy
reclaim section.
Handling capacities range from 1,000 cfm to 40,000 cfm, although larger
units are available. An Ecoloair unit is applicable:
C
C
Design
if costly fire-rated shaft and duct connections to the roof of the building are
eliminated. The Ecoloair system allows the discharge of cleaned exhaust
through the ventilation shaft or via a side wall;
C
where recycling cleaned exhaust air (maximum 80%) into the kitchen
area or ventilator is desired, thus creating savings in the reduction of the
amount of required conditioned make-up air and related equipment.
when recycling cleaned exhaust air (80%) into the kitchen area or
ventilator, check local codes for approval.
The system can be installed in the mechanical room, on the roof of the
building, or in ceiling space.
C
C
C
To hang the filter and odor sections in the ceiling space and install the
fan section in a mechanical room.
To connect two or more filter sections into one exhaust fan section.
Control panels coordinate the operation of the ventilator and the Ecoloair
system. Turning the main switch on the Ecoloair control panel to the ON
position activates a separate control circuit in the ventilator wash control panel
or a regular motor starter when a dry ventilator is employed. Turning the wash
control panel switch to the RUN or ON position starts the exhaust fan.
Heated, grease-laden air is pulled through the ventilator and a high
percentage of grease is removed from the air stream through the baffled
103
Ventilation Systems
grease extraction system. The exhaust air is then ducted to the filter section
where it passes through a three-stage series of filters, with a final efficiency
rating of 99% as defined in ASHRAE Standard 52-76.
The air is then drawn through the odor-reducing section and sprayed with
an odor eradicator, then through the exhaust fan section and discharged through
the duct work system.
When the system includes the optional energy reclaim section, the heated,
cleaned exhaust air is mixed with untempered outdoor air through a series of
modulating dampers. A temperature-controlling sensor determines the mix for
the correct temperatures of return air to the kitchen area as make-up air. All the
heat needed to return comfort-controlled air back to the kitchen is reclaimed
from the exhaust air, leaving the customer with no additional fuel cost to heat
the kitchen supply air in winter. No supplementary heat is required, as a
temperature controller dictates the amount of heat desired for reclaim. In
summer, the mixing dampers automatically adjust to discharge all of the
cleaned exhaust air to the outside and bring in the required amount of fresh
outdoor air required for the kitchen.
Make-up air supply in a kitchen is normally based on a volume of 80% of
the exhaust volume. This leaves a negative pressure of 20% in the kitchen area,
containing cooking odors in the kitchen.
All fans, exhaust and supply, are sized to suit air capacity of the system,
including an appropriate allowance for external static pressure. In arriving at the
external static pressure for fan sizing, a dirty filter factor of 0.5 is added. This
will account for an average rating of the pressure increase over the three stages
of filters.
A modulating volume control is an available option in lieu of employing
an average dirty filter factor (see Typical Ecoloair Unit Selection).
104
Ventilation Systems
(ICBO) are used as a basis for most codes west of the Mississippi River and
the state of Indiana.
2. National codes of the Building Officials and Code Administrators
International, Inc. (BOCA) are used as a basis for most codes east of the
Mississippi River, north of North Carolina and Tennessee, and in parts of
Oklahoma and Texas.
3. Standard codes of the Southern Building Code Congress International, Inc.
(SBCCI) are used as a basis for most codes east of the Mississippi River,
south of Kentucky and Virginia, and in parts of Texas.
4. State-developed codes apply in Wisconsin, New York, and Michigan.
5. The cities of New York, Chicago, Phoenix and Los Angeles apply their own
codes.
6. NFPA standards referenced in the preceding documents apply, as well as
being adopted directly by many state and local regulatory agencies.
7. Similarly, applicable national product standards referenced in the preceding
documents also apply.
Definition of cooking equipment as commercial cooking in applying these
regulatory codes and standards to commercial cooking ventilation will
determine the need for an exhaust hood and duct system. If none is required,
any by-products of the cooking will become an internal load of the building. If
a hood is required, the code may dictate the minimum exhaust, which will, in
turn, affect the amount of make-up air required or a listed hood assembly and
its exhaust requirements may be used.
The need for exhaust
Three questions are asked:
Under what conditions are commercial cooking exhaust systems and hoods
required by codes?
Is there a logical matching of effluent quantity or quality or both to the
required exhaust?
Can the exhaust be segregated to match different loads, or must the exhaust
be based on the worst case in the cooking facility?
106
Ventilation Systems
number are listed and a copy is given to the product manufacturer. New
products installed in the City of New York require stickers bearing the MEA
number and a statement of compliance. Vent Master's MEA number is available
on request.
Baltimore, Maryland
Ventilators installed in Maryland must meet the Maryland Department of
Public Health Requirements for design of kitchen ventilation systems. Some of
its specific requirements are:
1. Capture velocity at the perimeter of the cooking equipment must be 50
fpm.
2. The minimum distance for a canopy above the floor is 6.25 feet.
3. The minimum overhang is 12 inches.
4. Grease filters must be installed in T-bar mullions with spring clips.
This guideline also states air quantity requirements for wall and island hoods:
back shelf ventilators will use 250 cfm per linear foot. They require the total
make-up air to be 90% of exhaust quantity. The authority grants no prior
approvals; this is done on a per job basis. Recently, some areas of Maryland
have begun recognizing UL listed products. In these instances, however, the
jurisdictional authority requires a letter of guarantee to confirm compliance with
COMAR 10.15.03.08.C.
State of Michigan
The State of Michigan requires contractors and suppliers to comply with the
Michigan Food Service Establishment Guidelines for Ventilation Systems. The
Department of Public Health requires that contractors submit plans and
technical data for approval before installing commercial kitchen ventilation
systems. The guidelines for ventilation systems cover materials, installation,
hood overhang, filters, grease extractors, and air exhausts.
The formula to determine the requirement for an air exhaust is Q = V x P x D
where:
Q is the quantity in cubic feet per minute;
V is the velocity as derived from a table given in the guidelines;
108
Ventilation Systems
approval. Along with the RR Number, the City issues the manufacturer with a
set of conditions with which they must abide. This includes a requirement for
annual renewal of the manufacturer's products and an explanation of any
product changes made. Vent Master's Research Report Number is RR8115.
Nevada
With the recent revision of the categories of UL710 from Grease Extractors
to Listed Exhaust Hoods with Exhaust Dampers, some local authorities have
adopted a stricter interpretation of the UMC Code where air volumes are
concerned. We advise consultation with the local authorities.
Florida
Most of Florida, with the exception of the :Reedy Creek District, requires the
exhaust fan to activate or remain active with the supply fan shutting down when
the fire system is activated. If a ventilation system includes a damper, the
system exhaust fan must be shut down when the damper closes.
NFPA 96
The NFPA (National Fire Prevention Association) Standard for Ventilation
Control and Fire Protection of Commercial Cooking Operations is the almost
universally accepted standard for the industry. The actual standard is known as
NFPA 96. Some authorities and inspection departments impose supplementary
standards and conditions on the design and installation of ventilation systems,
so it is necessary to make sure that the design and installation package meets
with local approval. NFPA 96 emphasizes these areas of ventilation equipment:
Grease tight construction
Location of hoods in relation to the cooking equipment
Structural integrity of the hood
Placement and types of accepted fire prevention equipment
Duct work design and specifications
Recirculating hood system requirements
BOCA
The Building Officials and Code Administration (BOCA) publish guidelines
for:
Hood design
110
Ventilation Systems
requirements found throughout North America. This code may be one of the
most helpful in providing the designer with a good understanding of what is
required for commercial cooking ventilation.
Auxiliary clean air filtration
The use of filters is an essential part of the Ecoloair Filtration System. Without
a filter section the unit would be little more than a forced air exhaust or
recirculation system. As the word implies, a filter removes dust, grease and
airborne particles from the air. Air washers and electrostatic precipitators do
much the same thing with varying degrees of efficiency.
Airborne particles range in size from less than 0.1 microns. Although it is
impossible to design a filter that suits every application, it is possible from
experience and empirical tests to choose one suitable for most kitchen
applications. This is one of the reasons why VM needs to know the type of
application for which an Ecoloair system is required.
Filter ratings
Three characteristics distinguish the various types of filter available. These are
the efficiency, its resistance to air flow, and its cleaning cycle. By `cleaning
cycle' is meant the filter's dust-holding capacity. These characteristics are:
Filter efficiency is a measure of the filter's ability to remove pollutants from
the air.
Resistance is the static pressure drop across the filter at a given rate of air
flow.
Capacity is the amount of dust or pollutant a filter can hold. The capacity is
also a measure of the operating life of the filter before it requires cleaning or,
more likely, replacing.
VM filter specifications following are based on various applications in which
VM air filters are installed. The listing is a guide and no more to the
replacement of filters in various applications. Experience will dictate when a
particular filter requires replacing.
112
Filter specifications
Although VM specifies that all filters used in Ecoloair systems be rated Class
II (as a minimum), ASHRAE specifies these types of filters:
1. Pre-filter: Class II UL; 40% ASHRAE. Non-flammable board or metal
frame. Media - non-woven, reinforced cotton and synthetic fabric, 0.15
thick with 96% open-area grid. Capacity - 2000 cfm @ 24 x 24 or 1000
cfm @ 12 x 24 at 500 fpm, 0.1 initial static pressure; 0.75 final static
pressure.
2. Bag filter: Class II UL; 90-95% ASHRAE. Galvanized steel retainer and
header; media - spun glass, fire-retardant sealer. Capacity - 2000 cfm @
24 x 24 or 1000 cfm @ 12 x 24 at 500 fpm; 0.7 initial static pressure;
1.25 final static pressure.
3. HEPA filter: Class I UL; 95% DOP; 99% average ASHRAE. Separators;
16 ga. galvanized casing; neoprene gasket downstream; Media - glass,
urethane sealer, fire resistant rating; Capacity - 2000 cfm @ 24 x 24 or
1000 cfm @ 12 x 24 at 500 cfm. 1.0 initial static pressure; 2.0 final
static pressure.
The Ecoloair filter chart shown in Table 20 gives the pre-filter, bag filter and
HEPA filter distribution for the unit sizes shown. VM is approved for filters of
all manufacturers meeting the above filter specifications.
113
Ventilation Systems
Odor control
The liquid deodorizer used in the Ecoloair Filtration System is a blend of many
ingredients. Because the dispensing system is non-aerosol, the deodorizer is
non-toxic and completely free of CFCs. For this reason, the solution is
environmentally and ozone safe, and non-hazardous when inhaled.
Ecoloair/Ecology filter replacement guide
This filter replacement guide is compiled from some projects in which VM has
been involved. Depending on the conditions prevailing at a particular site, it
may be necessary to increase or decrease the frequency for filter changes. In
short, this is a guide, not a specification.
114
Equipment specifications
The specifications following will interest architects, engineers and kitchen
consultants who need a check list of options. They are also a reliable source of
reference in the compilation of contract bid packages for kitchen construction
and renovation projects. They are based on specified VM products with options
for various combinations of electrical and mechanical services. To prepare a
specification that meets the client's needs, check the appropriate boxes of the
required equipment. These specifications have provision for item numbering
for inclusion in larger specification packages.
115
Ventilation Systems
Filter Hoods
This generic specification is based on VM's Cyclovent range of canopy style ventilators, suitable for all types
of cooking equipment. All Cyclovent ventilators are of the canopy style and the common alpha designation
in the GFIII series of UL/ULC listed filters is GLD for hoods with a damper assembly and GL for hoods
without a damper assembly. Refer to the explanatory listing of models in the Cyclovent range.
Model
-B
Description
Box style hood for ceiling or wall and ceiling mounting (full designation therefore GLD-B for a unit
with damper assembly and GL-B for a unit with out a damper assembly).
-D
-T
-MA
-DMA
Hood with integral, internal make-up air c/w insulated plenum, interior access door to fire dampers,
air diffuser plate, and adjustable supply air slot.
Low profile style ventilator, wall or equipment mounted for counter top cooking equipment.
-L
ITEM #
Provide a ventilator constructed of stainless steel with all welded exhaust duct collar with a 1 (25 mm)
connection flange; all joints and seams welded and/or liquid tight; all exposed welds ground and
polished to the original finish of the metal. Provide hanging brackets on each unit for mounting as
required by the model designated.
[ ]
Provide each ventilator with a UL/ULC listed self-closing, spring loaded fire damper assembly activated
by a listed fusible link rated at 286oF (141oC).
[ ] Provide a UL/ULC listed exhaust air volume control damper for optimum balancing of single and
multiple ventilator systems accessible through the ventilator plenum c/w fire damper assembly.
[ ]
Supply all stainless steel UL/ULC listed filters deburred and reversible with grease drain holes top and
bottom.
116
Services
[ ] Exhaust air ______________
[ ] Static pressure ___________
[ ] Collar size ______________
[ ] Supply air ______________
[ ] Static pressure ___________
[ ] Collar size ______________
[ ] Electrical: 120/1/60_______ watt
[ ] Direct connect to _______ junction box for lights (by electrical contractor)
Modifications and options
[ ] Lights - the ventilator shall contain - quantity _______
[ ] Flush mount fluorescent light fixtures 36 (914 mm) or 48 (1219 mm) long (2 x 40 watts).
[ ] Flush mount vapor proof incandescent light fixture (2 x 75 watts).
[ ]
Surface mount globe-type light fixtures complete with clear thermal shock proof glass with plated steel
wire guard (1 x 100 watts).
[ ] Offset collar - (specify left or right of center line) duct collars __________
[ ] Rear duct collar take-off.
[ ]
Taper - (on T models) specify taper required __________ to suit low ceiling. Standard is 12(305 mm).
[ ] Make-up air grilles - double deflection grilles with opposed blade balancing dampers in lieu of
perforated panels.
[ ] Stainless steel main back - where exposed, for island applications.
117
Ventilation Systems
-D
-D-MA
-D-DMA
Description
Box type canopy style ventilator for ceiling or wall and ceiling mounting.
Canopy style hood with tapered sides for low ceiling or wall and ceiling mouting.
Hood with integral, front discharge make-up air, c/w 60% perf s/s panels, air diffuser plate.
Hood with integral, internal make-up air c/w insulated plenum, interior access door to fire
dampers, air diffuser plate, and UL/ULC collar.
Low profile style ventilator for wall or equipment mouting for counter top type cooking
equipment.
Low profile style hood, for wall or equipment mounting with integral, front discharge make-up
air for counter top type cooking equipment c/w 60% perf. s/s panels, air diffuser plate, and
UL/ULC collar.
Canopy style, double sided island ventilator for ceiling mouting.
Canopy style for ceiling mounting with front discharge make-up air c/w 60% perf. s/s panels, air
diffuser plate, and adjustable supply air slot.
Canopy style hood for ceiling mounting with integral internal make-up air c/w insulated plenum,
interior access door to fire dampers, air diffuser plate, and adjustable supply air slot.
ITEM #
The kitchen exhaust ventilator shall be a Vent Master:
[ ] Model C-CM__________ hot water wash and cold water mist, UL/ULC listed grease extractor (add
designated abbreviation as required; e.g., C-CM-D-DMA for a canopy style, double sided ventilator for
ceiling mounting with integral internal make-up air).
[ ] Model H-CM__________ hot water wash, UL/ULC listed grease extractor.
Construction
[ ]
Provide a ventilator constructed of stainless steel with an all-welded stainless steel duct collar with a 1
(25 mm) connection flange; all joints and seams welded and/or liquid tight; all exposed welds ground
and polished to the original finish of the metal. Provide continuous full-length hanging brackets on each
unit for mounting as required by the model designated.
[ ]
Provide each ventilator with a UL/ULC listed self-closing, spring loaded fire damper assembly activated
by a listed fusible link rated at 286oF (141oC).
[ ] Provide a UL/ULC listed exhaust air volume control damper for optimum balancing of single and
118
Provide water manifolds constructed of square, stainless steel tubing, and looped to provide equal water
pressure to all nozzles.
[ ] For hot water wash models, provide spray nozzles of machined brass.
[ ] For cold water mist models, provide spray nozzles of stainless steel.
[ ] Integrated make-up air shall be accomplished through the top of the ventilator at designated collars.
[ ] Hood size: Length ________ width _______ height _______
Services
[ ] Exhaust air ___________[ ] Static pressure ___________[ ] Collar size __________
[ ] Supply air ____________[ ] Static pressure ___________[ ] Collar size __________
[ ] Electrical: 120/1/60_______ watt
[ ] Direct connect to _______ junction box for lights (by electrical contractor)
Modifications and options
[ ] Lights - the ventilator shall contain - quantity _______
[ ] Flush mount fluorescent light fixtures 36 (914 mm) or 48 (1219 mm) long (2 x 40 watts).
[ ] Flush mount vapor proof incandescent light fixture (2 x 75 watts).
[ ]
Surface mount globe-type light fixtures complete with clear thermal shock-proof glass with plated steel
wire guard (1 x 100 watts).
[ ]
Drain manifold - for multiple sections to one common connection, complete with removable lower drain
enclosure.
[ ] Offset collar - (specify left or right of center line) duct collars __________.
[ ]
Taper - (on T models) specify taper required __________ to suit low ceiling. Standard is 12(305 mm).
119
Ventilation Systems
Cold
water
spray
Hot
water
mist
H4-25
--
HC4-25
Cyclo wash
Feet
MM
Feet
MM
40
12192
25
7620
40
12192
Table 22
25
7620
ITEM #
For the ventilator specified, provide a VM wash control panel to provide:
[ ] Cold water supply to the ventilator
[ ] Auto wash down cycle with adjustable wash timer and low detergent alarm.
[ ] Include provision for electrical interlock with the fire alarm system and, in case of fire, to initiate the
wash cycle.
[ ] Automatic operation of the exhaust and supply fans in addition to the run and wash cycles of the
ventilator.
[ ] A selector switch with RUN and WASH indicator pilot lights and a low level detergent light.
[ ]
Hand shut-off valves on inlet and outlet, hot and cold water solenoid valves, detergent pump, wash time,
120
For the initial charge of the detergent container, provide a 4-liter container of detergent for each control
panel supplied.
Trade notes
[ ] MECHANICAL: Supply and install back flow preventers, anti-syphon valves or vacuum breakers as
required by local codes. It is recommended that the control panel be located within 35 pipe feet (10668
mm) of the ventilator.
[ ] ELECTRICAL: Supply and install control field wiring and electrical devices required outside the
control panel. VM supplies field wiring diagrams on request. Power supply to be 120/1 /60 cycles.
Maximum control panel amperage during the wash cycles is 1 amp.
121
Ventilation Systems
Exhaust Fans
ITEM #
Construction
[ ] Supply [ ] grease extraction fans Garland GEF-A Series Model ________ (Specify model by air
volume, cfm, motor HP and static pressure as noted below.) The entire fan housing, cowl and discharge
shall be 16 gauge cold rolled steel, continuously welded and liquid tight to NFPA 96 requirements. The
unit(s) shall be complete with a 16 gauge cold rolled steel roof curb shipped separately for installation
in the field. Provide an exhaust duct collar of 1 (25mm) insulated double skin (16 ga. inner skin, 20
ga. outer skin) of welded cold rolled steel. The unit(s) shall extend 12 (305 mm) below the roof line
and have a 1.5 (38 mm) flanged connection for welding or bolting to the duct system. The minimum
clearance from the duct collar to combustible roof opening shall be 3 (76 mm) as per UL/ULC
approvals.
The fan wheel shall be all welded, statically and dynamically balanced at the factory with single inlet
and backward inclined blades to provide non-overloading characteristics and minimum noise level.
Bearings shall be grease lubricated, heavy duty self-aligning flange type, mounted outside of the air
stream on an oversized, polished steel shaft.
The unit shall be complete with a smoothly curved inlet venturi to create a streamlined air flow into
the fan wheel. The complete unit shall be factory primed and painted, ready for outdoor installation.
Electrical
[ ]
Provide an electrical disconnect switch (wired to the fan motor) and an electrical conduit sleeve that runs
the complete length of the duct collar. Provide a high temperature wire in the conduit to a point about
6 (151 mm) below the duct collar for electrical junction box hook- up below the roof line, indoors.
[ ] Provide an adjustable pitch (1 or 2 groove) pulley factory set at the proper operating speed for motors
up to 5 HP or a fixed pulley for motors over 5 HP.
Standard components
[ ] Provide unit(s) complete with a gravity back draft damper located at the fan discharge.
Approvals
The fan shall be AMCA rated and listed by the UL/ULC as a power roof ventilator for restaurant exhaust
systems.
Services
[ ] Exhaust air ____________(specify cfm requirement)
[ ] Static pressure__________(specify water gauge in inches)
[ ] Motor HP______________and voltage ___________
122
EcoloAir/Ecology Systems
The VM EcoloAirTM Ecology system removes smoke, grease and odors. It is used in conjunction with water
wash or filter type hoods. It permits the use of duct work from the unit to a low level outdoor discharge. This
is an exception to the NFPA 96 Standard because of the high filtration efficiency of this continuously
self-monitoring system. The system is applicable to non-traditional sites to meet environmental requirements
where the use of an all-welded NFPA duct from the hood to the roof fan is not possible, when the cost of
all-welded ducting is prohibitive.
ITEM #
[ ] The EcoloAirTM Ecology shall be a Vent Master Model EF-___-A___-B UL/ULC Approved.
[ ] CFM capacity _________
[ ] CFM set for __________
[ ] Total static pressure ____________
[ ] External static pressure: filter inlet ________ fan discharge ____________
Construction
[ ] The unit casing shall be of double wall construction reinforced and braced for maximum rigidity. The
inner walls shall be 16 gauge liquid tight welded construction and the outer walls shall be of 20 gauge
steel minimum.
[ ] Provide a filter section insulated with 1.5 (38 mm) insulation to UL/ULC requirements.
[ ] Provide a unit with three stages of filtration. The first stage shall be a 4 (102 mm) pleated UL/ULC
bag filter rate at 40% ASHRAE 52-76. The second stage shall be a 22 (559 mm) UL/ULC bag filter
rated at 95% ASHRAE 52-76. The third stage shall be a 12 (305 mm) absolute filter UL/ULC rated
at 95% DOP to 0.3 microns. A UL/ULC listed fire damper actuated by a fusible link shall be located
at the outlet.
[ ]
Provide a unit complete with four pressure switches to monitor pre-filter, high efficiency filter, absolute
filter and overall filters.
Mechanical
[ ] Provide a fan housing constructed from heavy gauge cold rolled steel with all joints reinforced and
braced for rigidity. The fan shall have a DWDI backward inclined wheel with an AMCA rating mounted
on heavy duty ground and polished steel shaft. The bearings shall be pillow block units with lubrication
nipples.
[ ] Provide hinged access doors to permit easy access to the fan and motor.
[ ]
The entire system shall be UL/ULC listed and approved for clean air, low level exhaust for commercial
kitchen cooking.
[ ]
Provide a high temperature limit sensor for emergency unit shut down and provide interlock to control
panel alarms.
123
Ventilation Systems
[ ] Supply V-belt drives of a capacity 25% greater than the motor horsepower.
Electrical
[ ] Supply a control panel constructed of heavy gauge steel for remote mounting with front locking screws
complete with timers, relays and lamps to indicate system on, condition of pre-filter, bag filter and
absolute filter, filter missing, fire and odor reducing operation.
[ ] Supply control circuits to operate at 24V AC.
[ ]
[ ] Supply an EcoloAir automatic odor control system VM Model A1R UL/ULC listed and NSF
approved with a reverse spray nozzle. Cabinet sizes: 16 (406 mm) wide x 11 (279 mm) deep x 32
(813 mm) high, having a capacity of 5 imperial gallons (23 liters). The unit shall be constructed of 18
gauge satin coated steel, charcoal air dry enamel finish with a side hinged access door panel fitted with
a key lock and two security bolts; an air compressor that operates at 22 psi (152 Kpa) and having an
atomizing type spray nozzle. Provide a program control in the master control panel equipped with two
timers: a 0-20 minute cycle timer and a 0-20 second spray timer. Provide a poly plastic reservoir bottle
with a removable cap, transfer tubing and 5 gallons of liquid solution.
Options
[ ] Odor reducing system consisting of a liquid spray system with timers mounted in the remote control
panel to switch on, off and cycle control and provide for infinite adjustment.
[ ] Double odor reducing system.
[ ] Odor liquid low level alarm.
[ ] Split sections.
[ ] 24 hour timer for odor reducing sequence.
[ ] Access platform base.
[ ] Lift off panels (in lieu of hinges).
[ ] Fifth pressure switch for absolute filter monitoring (filter missing).
124
Pipe
Size
Max.
Nozzl
es
Designed
nozzels
discharged
Min. water
vol. required
U.S. Gal. Liters
SU3-100
1.00"
15
57
SU3-125
1.25"
12
30
114
SU3-150
1.50"
20
45
170
SU3-200
2.00"
30
8
Table 23
75
374
Legend
-EFO exhaust fan remains on
-FP fire pull
-FPR fire pull remote
-S Surface mounted on wall
-R Recessed in wall
The fire protection system shall be a VM water mist fire protection suppressor system Model:
[ ] Series SU3-100-____-____
[ ] Series SU3-120-____-____
[ ] Series SU3-150-____-____
[ ] Series SU3-200-____-____
[ ]
Provide mandatory trouble indicating lights and audio alarm to indicate that system shutdown is a result
of the hand water valve being closed, system low water pressure or a fire condition.
Construction
[ ] The panel housing and hinged doors shall be of 18 ga. (min.) stainless steel; a backing plate of 16 ga.
(min.) galvanized steel; the piping of the fire extinguishing system shall be schedule 40 black iron; and
a watertight partition shall be provided between the plumbing compartment and the electrical
compartment. In the panel, provide these components.
A keyed MAINTENANCE OVERRIDE SWITCH.
Supervised manual shut-off valve.
Pressure sensing switch to shut off fuel sources should sprinkler water pressure drop to
125
Ventilation Systems
unsafe levels.
Gas shut-off delay with battery back-up for momentary power outage.
Flow sensing switch for immediate fuel shut-off and alarm activation upon nozzle discharge.
Pushbutton gas valve reset.
Pressure gauge (sprinkler water line).
Status indicator lights for POWER ON and GAS ON with lights and audible alarm for FIRE
ALERT, LOW WATER PRESSURE and HAND VALVE CLOSED.
Factory pre-piped, pre-wired and tested.
126
CFM
Motor
HP
KW
Amps
DS
Switch
KVS-5-L, or -R
1100
24
70
100
KVS-5-B
1250 to 1800
24
70
100
KVS-5-REM
1250 to 1800
24
70
100
1500
36
105
175
KVS-6-B
1500 to 1950
36
105
175
KVS-6-REM
1500 to 1950
36
105
175
2000
48
140
175
2000 to 2250
48
140
175
KVS-8-REM
2000 to 2250
5
48
140
Legend
LLeft hand mount
RRight hand mount
BBack of hood mount
REM - Remote mounting of filter tower up to 30 feet away.
5S6S8 -5, 6 or 8 ft. long sections.
Table 24
175
KVS-6-L, or -R
KVS-8-L, or -R
KVS-8-B
ITEM #
The KVS shall be a Vent Master Model:
[ ] KVS-5 _______(specify -L, -R, -B or -REM)
[ ] KVS-6 ________(specify -L, -R, -B or -REM)
[ ] KVS-8________(specify -L, -R, -B or -REM)
[ ] The KVS shall be a UL/ULC listed system tested in accordance with NFPA 96, Chapter 10, and UL
197-1994 for integral recirculating systems for commercial electric cooking appliances.
127
Ventilation Systems
Construction
[ ] The system shall have a listed exhaust filter hood, complete with VM stainless steel GFIII UL listed
filters, mounted 6' 2 (1880 mm) from floor level. The filtration tower shall include a filter module, fan
and motor, fire protection, odor control system and electrical cabinet.
[ ] The assembly shall be stainless steel construction with all exposed welds ground and polished to the
original finish of metal. The system shall be fully self-supported, pre-piped and wired for a fully
automated operation, factory tested and balanced.
[ ]
The system shall be listed and approved for a total flood fire protection of the cooking equipment below
with a fixed nozzle distribution system.
[ ] The system shall provide the utility power distribution, interlocks and controls for the cooking
equipment.
Options
[ ] The filtered, clean air shall be discharged back into the cooking area through the air wall vents and/or
through the air register mounted on top of the unit.
[ ] The filtered clean air shall be discharged through a duct to outdoors.
[ ]
Lights - the hood section shall contain ______(specify the number) surface mount globe type fixtures.
128
Except as noted for circuit breaker (CB) panels below, provide secure fasteners on panels that must be
removed to give access to electrical components and services.
[ ] Provide a hinged, latching sub-door for access to the CB panel housing ON/Off switches and re-set
devices.
[ ] The services and supply lay-out is to match the cooking bank line-up specified and shown on the
drawings.
Mechanical Services
[ ] Provide pipe manifold support brackets of corrosion-protected 12 gauge steel, formed to accept
cushioned clamps of the correct size for each manifold. Each manifold shall traverse the full length of
the mechanical raceway. Supply a main quarter-turn shut-off ball valve for each piping service where
it enters the MDS. Using permanent tags that are not easily removed, label every manifold as to its
service; for example, `Hot Water', `Cold Water', `Steam', `Condensate Return'. Insulate the steam
delivery and condensate return manifolds.
[ ] Provide a [natural or LP] gas supply. A minimum Schedule 40 black iron pipe to be painted and used
for the gas manifold.
[ ]
For connection to the fire suppression system during installation, provide a solenoid to shut off the gas
supply should a fire occur.
[ ] Provide a cold water service having a fully insulated manifold of Type L hard-drawn copper.
[ ] Provide a hot water service having a fully insulated manifold of Type L hard-drawn copper.
[ ]
Provide a steam line and condensate return line with insulated manifolds of minimum Schedule 40 black
iron pipe. Pitch the steam supply manifold not less than 1/4 per 5' of horizontal run and connect a steam
trap. Connect the secondary side of the steam trap to the condensate return line 1/4 per 5' of horizontal
run to the building return end of the manifold.
129
Ventilation Systems
[ ] Provide an AGA/CGA quick-disconnect, plastic-coated hose set for each item of equipment requiring
gas or water connections.
[ ] Use restraining devices where equipment is on casters.
[ ] Mount a FILL faucet [specify type] at the peak of the raceway to serve these items of equipment:
[ ] Each unit that is part of this item shall be furnished complete with a prison package that shall consist
of keyed latches and tamper proof screws.
Electrical Services
[ ] The common requirements for electrical services shall be a raceway of adequate cross section for the
services being provided; a CB panel that meets regulatory code requirements for water-tight
applications; a main circuit breaker with a shunt trip for connection during installation to the ventilation
fire suppression system.
[ ]
Provide ground fault interrupters for electrical circuits rated 120V AC, 20A single phase and 208/240V
AC, 20A and 30A single phase.
[ ] In the mechanical chase, install a ventilator wash control station having RUN/WASH selectors with
indicator lights, a LOW DETERGENT light, audible alarm, 1/4-turn main shut-off valves, Y-strainers,
solenoid valves, detergent pump with TEST switch, PRESSURE TEMPERATURE gauge and
ADJUSTABLE WASH timer.
[ ] Provide suppressor water mist fire protection controls for a main shut-off valve, LOW WATER
pressure switch; a pressure gauge WATER FLOW switch; and electronic controls to monitor system
operation and provide audible and visual indication of fire, low water pressure, and closed main shut-off
valve.
[ ]
Supply a battery back-up system to maintain the gas valve in the open position and maintain the exhaust
and supply latching circuit for five seconds during electrical power outages.
[ ] At each end of the MDS, provide EMERGENCY SHUT-OFF push buttons with red mushroom
head-type actuators to turn off the gas and electrical supplies.
[ ] Provide electrical cord sets or pre-wired seal-tight conduit as required.
130
250
400
500
BTUH input
125,000
250,000
400,000
500,000
96,250
192,500
308,500
385,000
1.9
1.9
1.9
1.9
115V
0.95
0.95
0.95
1.9
980 to
1960 to
3135 to
3500 to
1175
2350
3765
12,000
482
588
662
1104
622
817
930
1588
1/2"
1/2"
3/4"
1"
(2) 20 x 25
(1) 20 x 20
(2) 20 x 20
(1) 16 x 20
(3) 20 x 25
(1) 16 x 20
(1) 16 x 25
(1) 16 x 25
(4) 12 x 20
permanent or pleated)
(2) 20 x 25
(4) 12 x 25
Note:
AGA ratings for altitudes to 2000 feet. Above 2000 feet derated by orifice change, 4% for each 1000 feet above sea level. CGA
ratings for altitudes to 2000 feet. High altitude units (2001 to 4500 ft.) Are derated by 10% of maximum output.
Table 25
ITEM #
The heating/make-up air unit shall be a Vent Master
[ ] Model VMRIG 125.
[ ] Model VMRIG 250.
[ ] Model VMRIG 400.
[ ] Model VMRIG 500.
Construction and operation
[ ] The heater/make-up air unit shall have a weatherized, aluminized steel cabinet with a full curb cap for
mounting on a roof curb or supports.
131
Ventilation Systems
132
Trouble Shooting
Trouble Shooting
Cause
Off its set point position.
Response
Make sure set point is correct.
Do the controller and sensor set
points agree?
If this fails to correct the
condition, re-calibrate the
controller.
If the controller is correct, check
the actuator.
133
Ventilation Systems
Air-conditioning systems
Trouble
HP too high
(High amp readings).
Low CFM
Cause
Fan speed above design.
Correct rotation.
Correct.
High CFM.
Response
Bearings
Trouble
Running hot or noisy or both.
Cause
Response
Lubrication.
Poor alignment.
Correct alignment.
Distorted shaft.
Tighten.
Seals misaligned.
Correct or replace.
Dirty.
Bearing worn.
Replace.
134
Trouble Shooting
Couplings
Trouble
Running hot and noisily.
Cyclo-Wash Units
Trouble
Cause
Coupling unbalanced.
Cause
Response
Correct alignment.
Lubricate.
Response
Cause
Response
135
Ventilation Systems
Trouble
Insufficient water.
Cause
Low water pressure.
Response
Check supply pressures: 30 psi for
cold water and hot water.
Clean all strainers and nozzles.
Ditto - clean nozzles.
No power.
136
Trouble Shooting
Trouble
Cause
Response
Check and ensure main water
supply.
Open hand valve.
Clean strainer in panel.
Switch on WASH. If no click of
solenoid replace as needed.
Replace.
Set dial indicator for 2 1/2 min. for
CWCH; 5 min. for CWH.
Clean solenoid.
Clean solenoid.
Refill container.
Re-prime pump.
Adjust screw on switch.
Cracked tubing.
Replace tubing.
Tighten plug.
Fittings over-tightened.
137
Ventilation Systems
Trouble
Detergent pump will not prime.
(Consult the section on pump
priming.)
Cause
Back pressure in line.
Response
Check water pressure. If it exceeds
40 psi, add regulator.
Incorrect detergent.
Response
Electric motors
Trouble
Fails to start.
Cause
Response
Overloads trip.
Open circuit.
138
Trouble Shooting
Trouble
Motor stalls.
Cause
Response
Single phasing.
Mechanical overload.
Undervoltage.
Power failure.
Low voltage.
Wrong rotation.
Motor overheating.
Mechanical overload.
Inadequate ventilation.
Unit misaligned.
Re-align.
Mechanical fault.
Noisy operation.
Fans
Trouble
Impeller hitting inlet ring or
housing.
Cause
Impeller not centered in inlet ring.
Inlet ring damaged.
Crooked or damaged impeller.
Shaft loose in bearing.
Impeller loose on shaft.
Bearing loose in housing.
139
Response
Again, these faults listed are
possible causes of fan units that
run roughly and noisily. Check the
possible causes and correct these
mechanical faults accordingly.
Ventilation Systems
Trouble
Fan running noisily and
vibrating.
Cause
Response
Shafts
Trouble
Unstable performance.
Shaft squealing.
Shaft overheating.
Cause
Response
Shaft bent.
Defective bearings.
See Bearings.
Shaft misaligned.
Re-align.
Lubrication.
Lubricate.
Shaft misaligned.
Poor lubrication.
Lubricate.
Seal failure.
Replace.
140
Engineered Features
Engineered Features
Engineering designs and modular equipment packages are an important aid to the
architect and kitchen designer. The result of years of experience working in the
field of kitchen ventilation systems, modular kitchen equipment packages help
solve problems encountered both in new kitchen designs and renovations.
Ventilation problems are often found in dealing with non-traditional site exhaust
systems, in life cycle costing assessments, and when considering the economics
of recirculating clean air systems. The purpose of this section is to discuss the
key features that architects, engineers and designers should look for regarding
product design.
The best product and kitchen system design should:
Ventilation Systems
Control systems
Make-up air units
Utility distribution equipment
In the pages that follow, the key features of the equipment packages listed above
are shown and advantages highlighted.
Hoods
Key features to look for
Each hood type should provide the highest grease removal
efficiencies with the lowest operating static pressures
142
Engineered Features
143
Ventilation Systems
144
Engineered Features
145
Ventilation Systems
146
Engineered Features
147
Ventilation Systems
148
149
150
Abbreviations
ICBO
International Conference
Building Officials
KG or Kg
Kilograms
KPA
Kilopascals
KVS
Kitchen ventilation system
KW or kw
Kilowatts
LB or lb
Pound weight
M
Meter (unit of length)
Max.
Maximum
Min.
Minute or minimum
MDS
Modular distribution system
NFPA
National Fire Protection
Association
NSF
National Sanitation
Foundation
OPN
Open area of intake
PA
Pascal
PSI
Pounds per square inch
REM
Remote
RPM or rpm Revolutions per minute
SBCCI
Southern Building Code
Congress International, Inc.
SP
Static pressure
s/s
Stainless steel
Temp.
Temperature
TPG
Temperature/pressure
gauge
UL
Underwriters' Laboratory
ULC
Underwriters' Laboratory
Canada
UMC
Uniform Mechanical Code
Vol.
Volume
V
Volts or voltage
VM
Vent Master
WG
Water gauge
AC
AGA
AMCA
Alternating current
American Gas Association
Air Movement
and Control
Association, Inc.
Amp
Ampere
ASHRAE
American Society of
Heating, Refrigeration and
Air Conditioning Engineers
ASTM
American Society for
Testing and Materials
AWG
American wire gauge
BOCA
Building Officials and Code
Administrators International, Inc.
CFM or cfm Cubic feet per minute
CGA
Canadian Gas Association
CM or cm
Centimeter
C/W or c/w Complete with
CWCH
Cold wash, cold water mist and
hot water wash
CWH
Cyclo Wash, hot water only
DC
Direct current
DWDI
Double width double inlet
EPA
Environmental Protection
Agency
EVS
Engineered ventilation
system
Ft. or ft.
Feet
FPM or fpm Feet per minute
Ga or ga
Gauge
GPM or gpm Gallons per minute
HEPA
High efficiency particle
absorption
HP
Horse power
HVAC
Heating, ventilating and air
conditioning
151
of
of
152
Bibliography
ASHRAE
ASHRAE
AMCA
ASTM E-1993
BOCA
EPA
EPA
NFPA 10
NFPA 12
NFPA 13
NFPA 16
NFPA 17
NFPA 17A
NFPA 54
NFPA 58
NFPA 70
NFPA 80
NFPA 96
NFPA 211
UL 723
UMC
154
Index
INDEX
Air flow
available options, 38
calculations, 40
CFM calculations, 39
CFM requirements of hoods, 40
down discharge supply, 36
front panel make-up air, 37
limitations of exhaust and make-up air, 37
make-up air, 35
negative pressure, 39
short cycle supply, 36
Auxiliary Equipment
features of the MDS, 51
Kiosk ventilation systems, 54
Auxiliary equipment
air balancing, 45
dampers, 45
electrical equipment, 45
fans, 46
fans for multiple kiosks, 96
heat exchangers, 48
Modular Distribution Systems, 50
Backshelf hood, Clearances, 12
Calculating velocity, example, 43
Canopy hood, Clearances, 12
ASHRAE filter specifications, 113
BOCA, 111
Ecoloair/Ecology filter guide, 114
filter ratings, 112
NFPA 96, 105
odor control, 114
technical specifications, 111
UMC, 111
Codes and standards
auxiliary clean air filtration, 112
building regulatory provisions, 105
filter specifications, 113
155
Index
listed grease extractors, 59
nozzles, 58
pipe sizes, 56
surface fire protection, 58
water mist systems, 58
water sprinkler systems, 56
wet chemical systems, 55
Fire suppressor systems, Installation
& Design Requirements, 63
Food court applications
comparison chart cfm vs leased area, 96
exhausting multiple kiosks, 96
Greader removal devices, extraction rates, 23
Grease devices, extraction rates, 23
Grease extraction devices
air flow in Cyclo Maze cold water mist, 25
air flow in Cyclo Maze dry unit, 24
Cyclo Maze series, 24
hood engine specifications, 27
types of extraction engines, 26
unit as an engine, 25
what makes units efficient, 26
Grease extractors, 16
Grease removal devices, 23
Hoods
backshelf, 12
canopy, 12
CFM calculations, 41
CFM correction factors, 41
equipment lay-out, 13
filters, 16
height limitations, 14
incremental lengths, 14
nomenclature, 11
sizing, 13
wall locations, 13
Installation
listed grease extractors electrical controls, 70
ranges, griddles, hot tops and plates with
high shelves, 66
Intake velocity measurements, 43
Listed grease extractors, U. L. tests, 60
Maintenance, Cyclo-wash 3, 75
156
Index
actuators/damper motors, 133
air-conditioning systems, 134
couplings, 135
Cyclo-Wash units, 135
electric motors, 138
fan and motor drives, 138
fans, 139
shafts, 140
Types of filtration technologies
active carbon filters, 81
catalytic conversion, 81
electrostatic precipitators, 80
incineration, 81
liquid odor control, 82
oxidizing pellet bed filters, 81
pleated or bag filters, 81
water mist, waterfall, and water bath, 80
Velocity calculations, 42
Ventilation at different sites, 9
Venting cooking equipment, 39
Why ventilation is essential, 39
Work processes, 7, 8, 9, 10
Odor control, 86
categories of odor, 48
filtration systems, 48
liquid odor solution, 87
special odor problems, 87
Procedures, Warnings, cautions & notes, 9
Sprinkler nozzle
conveyor broiler, 69
duct protection, 70
plenum protection, 69
test valve, 70
tilt fry pan, 68
upright broiler, 68
Sprinkler nozzles, 63, 65
nozzle temperature rating chart, 63
ranges, griddles, hot tops and plates, 66
salamander broiler, 67
System capacity factors, 11
Terms and definitions, 21
Trouble Shooting, Bearings, 134
Trouble Shooting
157