Table of Contents
SECTION PAGE NUMBER
Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
5: Grease Extraction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
8: Unit Selection
12: Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Greenheck Method. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Our Warranty. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
INTRODUCTION
A kitchen hood is not just a box. Every commercial kitchen requires ventilation, and in the past, the importance
of a proper ventilating system has been overlooked. Today, designers, installers, and operators are recognizing
the value in well-designed commercial kitchen ventilation (CKV) systems. Emphasizing system because it is
not just a box, it is an engineered system of exhaust hoods, ventilators, make-up air ventilators, grease removal
apparatuses and more. Taking time to properly design a CKV system will increase the health and safety of the
kitchen operators and increase the efficiency and energy savings for the owner.
This guide discusses many of the factors that must be analyzed when designing an efficient kitchen ventilation
system. It offers a background in the basic theories of CKV design, product types with their application,
necessary calculations with examples, troubleshooting, and more. This guide will assist in the development of a
well-balanced and functional system.
Although this guide will aid in a successful design, it is important to keep in mind the variation in standards
and codes which have been adopted. Each county may have slightly different requirements for the designer
to meet. The local authority having jurisdiction (AHJ) should be consulted to ensure the final design meets the
requirements set forth. See the design and code reference section on pages 52 and 53 of the guide for a listing
of common codes. If you would like to discuss any of the topics to further detail please contact Greenheck.
Filter Bank
1
TYPES OF COMMERCIAL KITCHEN VENTILATION HOODS
Wall Canopy
1
Single Island Hoods
A single island hood is used over one row of cooking
equipment placed where no walls exist. Single island
hoods can be seen from all directions, therefore, have
four finished sides. With four exposed sides, this type of
hood is more susceptible to cross drafts, spillage, and is
dependent only on the thermal updraft of heat from the
cooking equipment and how quickly the exhaust fan can
rid the hood of contaminated air. These hoods should be
sized larger and use more airflow than a wall canopy hood
with the same cooking battery. The single island hood must
overhang the cooking equipment by a minimum of 6 inches
on all four sides of the hood. However, it is recommended
that the overhang be extended to 12 inches on all sides
of the hood. Extending hood overhangs increases capture
volume which aids capture and containment. To eliminate
the front to back airflow on a single island, a V-bank of Single Island Canopy
filters improves capture and containment by directing the
contaminated air to the center of the hood.
A wall canopy can be installed as an island hood with
a finished back enhancing its aesthetic appearance.
However, it is not recommended because the front to
back airflow pattern of a wall canopy will cause capture
problems when being utilized as a single island canopy.
1
Short Circuit Hoods *Warning: NOT RECOMMENDED*
Short circuit canopy hoods were once thought of as an energy saving device. The theory, by introducing
untempered make-up air inside the hood reservoir it would reduce the amount of tempered air being exhausted
from the kitchen, minimizing heating and cooling loads. This was done to get around old codes which set a
minimum exhaust rate that was much higher than needed to achieve capture and containment. Make-up air
was short-circuited by as much as 80-90% of the exhaust rate resulting in spillage of the contaminated air.
*Schlieren Imaging (see Schlieren Imaging on page 8) confirms that
only 15% of the minimum capture and containment airflow can be
brought through the hood without causing spillage.
Short circuit hoods are ineffective because they do not discharge the
make-up air in the correct location. Think of the cooking equipment
as a generator of contaminated air. The purpose of make-up air is to
replace the air that is being generated at the cooking surface. Both
the hood and exhaust system are designed to capture and contain the
airflow generated by the cooking equipment. Short circuit hoods dump
make-up air into the capture and containment area, thus overfilling the
Short-Circuit Hood - End View
hood and releasing a mix of make-up and contaminated air into the
room causing greasy surfaces and increased heat loads. For these
reasons, short circuit hoods are not recommended.
Proximity hoods are TYPE I hoods that are shorter in 1.5 INCH OPTIONAL SHELF
of contaminated air may escape from the hood, therefore proximity hoods
are best suited for light and medium duty cooking applications such as
COOK SURFACE
griddles. The major benefit is reduced airflow required to obtain capture and
containment compared to a canopy hood with the same cooking lineup. The
savings are realized through reduced heating and cooling loads.
Proximity hoods are mounted closer to the cooking equipment subjecting the grease filters to
abnormal heating loads from appliance flues. When gas-fired cooking equipment with flues
are used, flue bypass proximity hoods offer another advantage. Instead of allowing the heat
from the flues to pass-thru the face of the filters, the flues are ducted to discharge the hot air
directly to the back of the exhaust plenum, bypassing the grease filters. Normally, this heat
would hit the filters, causing them to radiate heat onto the cooking personnel. Radiant heat
loads are greatly reduced with the absence of the hot flue gases and grease is less likely to
bake to the filter face which enables the filters to be cleaned more easily. Airflow requirements
are lowered because the hood does not have to capture the excess heat, only the heat and
grease from the cooking surface must be contained.
The flues on the equipment must be sized correctly to the bypass chamber to ensure grease
is not pulled into the flue. Dampers control the amount of hot flue gases that exit through
the exhaust plenum. This airflow is critical to cooking equipment performance, therefore,
the dampers must be set according to the cooking equipment beneath the particular hood.
Greenheck should be consulted prior to ordering flue bypass proximity hoods to ensure a
proper hood-to-equipment fit. Flue bypass is recommended for fryers and griddles. Flue Bypass
6
TYPE II Hoods 1
TYPE II hoods are commonly referred to as oven or condensate hoods. In essence, these are stripped down
exhaust only canopy hoods. The purpose of the TYPE II hood is to remove heat, moisture, and odor-ridden air
from non-grease producing appliances. The hoods do not contain grease filter banks but rather a duct collar
to exhaust the contaminated air. A TYPE II hood duct does not
need to be fully-welded, instead it can be a standard galvanized
duct because there is no grease loading. Flex-duct is not
allowed for TYPE II hoods.
Oven Hood
The oven hood is an exhaust only canopy hood with an exhaust
duct collar for the removal of heat and vapor. These hoods are
the simplest of all hoods and are usually placed over ovens or
small appliances only producing heat and odor. For complete
capture and containment, overhangs should be measured with Oven Hood - End View
the oven door open.
Condensate Hood
The condensate hood is an exhaust only canopy hood with
U-shaped gutters to capture and direct condensate to a drain.
It also has an exhaust duct collar for heat, moisture, and
odor-ridden air to exit. Many manufacturers have options for
condensate baffles in the hood to help condense the moisture
laden air, one or two baffle configurations are typical, depending
on the moisture content of the contaminated airstream.
Condensate hoods are usually found mounted over dishwashers.
For complete capture and containment of large plumes of heat
and steam, 18-36 inches of overhang are recommended. Condensate Hood - End View
HOOD CERTIFICATION
Most jurisdictions require TYPE I exhaust hoods to bear the Underwriters Laboratory (UL) label. UL 710 is
the test criteria in which UL listed exhaust hoods are tested. Tests include temperature, cooking, flare-up,
fan failure, fire, and burnout testing. In order to complete the analysis, these hoods have to be operating at a
minimum exhaust airflow rate to obtain capture and containment determined under laboratory conditions.
This is where the misconception of the UL listing becomes apparent. The minimum airflow that UL uses to
test hoods is obtained by first adjusting airflow to the manufacturers recommendation, then fine tuning it to
ensure complete capture and containment of the effluent generated by cooking hamburgers. This airflow is
then assumed to be the minimum capture and containment value for the UL testing of a particular hood in
a controlled laboratory environment. This airflow is then considered safe for the flare-up and burn tests that
follow. The temperature of the hood shall remain in a range that does not compromise the structural integrity
of the hood at the listed airflow. The airflow does not guarantee capture and containment.
UL minimum airflow ratings in the hoods exist only as a safety rating. It does not guarantee capture and
containment and therefore, should rarely be used as design criteria. It is important to realize that UL
established airflow rates are determined and utilized under laboratory conditions. More exhaust and/or
lesser supply rates may be required in real environments. There are situations where extremely light cooking
applications exist where the exhaust rate may be at or near the UL listings, but only in these light, low
volume, and light cooking battery situations.
Figure 1
The Cooking Equipment
When using the Greenheck Method the cooking equipment can
be thought of as a generator of contaminated air. The quantity
of such air generated by each appliance is ultimately dependent
upon the temperature and size of the physical cooking surface.
Gas flues on gas equipment are also considered generators. Hood
Heat from appliance surfaces cause a change in the density of
surrounding air creating a thermal updraft. While hot air rises, it is Updraft
replaced by air in the immediate vicinity as shown in Figure 2. The
replacement air assists in establishing minimal capture velocity at
the cooking surface and contains the contaminated air generated
by the cooking equipment. There are many factors that can alter
the direction and velocity of this air which are discussed in the
design consideration (pages 42-45) section of this guide.
Heated Surface
Figure 2
Schlieren Imaging
Schlieren Imaging is a powerful tool now being used for research in the commercial kitchen ventilation industry.
Schlieren Imaging enables people to see the heat given off by appliances and watch its flow pattern in the
hood. It is an excellent way to test for capture and containment due to the ability to zoom in closely along
edges of the hood and observe any escaping effluent. Schlieren images are made visible by taking advantage
of the different air densities
yielding a high contrast
optical image.
Figure 3A & 3B are an example of
the heat load seen in a common
kitchen application. Both hoods
use the same exhaust rate,
however, the hood in Figure 3A is
spilling heat into the space.
Figure 3A Figure 3B
8
Previously undetectable to the eye, it is apparent that the heat gain to the space can be quite significant. Figure
3B demonstrates Greenhecks PEL lip technology, which is a 1.5 inch return lip along the bottom edge of the
hood. This lip directs airflow back into the hood allowing cfm requirements to be reduced without spillage. A
properly designed system should look like the image on the right.
Utilizing Exhaust Flow Definitions 2
Using any of the concepts, every piece of cooking equipment can be placed into a category which assigns
a value to the actual updraft velocity or airflow volume per foot. These values can be used for CFM hood
calculations. Figure 4 categorizes common kitchen appliances and provides the updraft velocity factors and
International Mechanical Codes airflow volume per linear foot necessary to complete the calculations.
Recognize that the extra-heavy category contains nearly all solid fuel cooking appliances. Solid fuel is the most
volatile and uncontrollable fuel source in a commercial cooking operation. There is no on/off switch like most
appliances, but rather one can add fuel or let the fuel burn out. Thus, the load is extremely variable and may
exceed projected exhaust requirements. In these situations it is important to have additional airflow up front and
size exhaust and supply fans so their airflow can be increased if needed. Lastly, look into standards and code
requirements such as: Local Codes, State Codes, NFPA 96, IMC, or any other required agencies in the area to
ensure proper installation.
Greenheck Method
(updraft velocity in feet 50 85 150 185
per minute)
International Mechanical
Code
200 300 400 550
2003 Edition
(cfm per linear foot)
Figure 4
A typical cooking battery has been created and will be used to illustrate the IMC code method, Greenheck
Method, Free Foot Consideration, and Greenhecks Airflow Volume per linear foot method. Figure 5 illustrates
the typical cooking battery.
ASSUMPTIONS
Fryers Griddle Oven
36 in. x 30 in. 24 in. x 30 in. 36 in. x 36 in. 3 inch spacing behind hood
Typical 6 inch overhang required on sides and front
Hood Dimensions: 9 ft. 0 in. long x 4 ft. 0 in. wide
Greenheck Method uses actual containment area of
45 in. because of 3 in. integral air space
Figure 5
IMC EXAMPLE
IMC requires that when calculating the exhaust rate for a combination of appliances, the highest exhaust rate
be applied over the entire length of the hood. Therefore, in the case of the hood above, IMC requires 300 cfm/
ft. for the 9 feet of hood yielding a total of 2700 cfm. Furthermore, it is recommended by IMC and NFPA that any
hood over a solid fuel cooking battery shall have a separate hood, duct, and exhaust system.
9
Greenheck Method
QE
QF
QC
10
EXAMPLE CALCULATION
cfm
Airflow (cfm) = Length (feet) Airflow Volume
Limits and Assumptions linear foot
(for cfm per lineal foot calculations)
cfm
1. Used for hoods 54 in. or less in width Left Overhang Airflow = 0.5 feet 200 = 100 cfm
linear foot
2. Cannot be used for pizza ovens
3. Cannot be used for cook chill cfm
Fryer Airflow = 3 feet 250 = 750 cfm
linear foot
4. 6 ft. 6 in. hanging height
5. Vertical updrafts cfm
Griddle Airflow = 2 feet 250 = 500 cfm
6. Proper room ventilation linear foot
7. Proper overhangs
cfm
Oven Airflow = 3 feet 200 = 600 cfm
linear foot
cfm
Right Overhang Airflow = 0.5 feet 200 = 100 cfm
linear foot
Figure 7
11
12
144 in.
To put all of the information 2
from this section together, the
following is a full example from
start to finish. Examine first the
cooking battery and hood to Fryer Griddle Char-broiler Range
the right and follow through the 30 in. x 30 in. 36 in. x 30 in. 36 in. x 30 in. 30 in. x 30 in.
39 in.
calculations illustrated below.
48 in.
13
2
QF - Quantity of air required to
contain surges and drafts. Use
the minimum updraft velocity
of 50 fpm and multiply it by the
difference in area between the
hood containment area and the
appliance area.
All calculations shown in this example have been built into Greenhecks
Computer Aided Product Selection (CAPS) program. These examples
illustrate the logic used to properly determine exhaust rates. To obtain
CAPS, request online at www.greenheck.com or consult your local
Greenheck representative.
14
Supply Options
Make-up air can be introduced through the hood with an
integrated supply plenum or an external supply plenum.
The advantages of using an external supply plenum verses Integrated Supply Exhaust Only
an integrated supply plenum can be seen in Figure 11. Figure 11
The shaded region represents the volume of the hood. Increasing the volume allows more smoke and
heat to be held in the hood until it can be exhausted. This is important over cooking equipment that
produces a great deal of heat and smoke, such as a char-broiler. External supply plenums are usually less
expensive and can be retrofitted to most exhaust only hoods.
15
150 cfm/ft.
Face Supply
Located on the front of the hood (Figure 13), face discharge
is designed to throw make-up air across the room. Use
face supply when tempered air is brought in through MUA
into a tempered kitchen or when the MUA and kitchen Figure 13
Integrated Face Supply Plenum
are untempered because mixing will occur with the air
in the space. Registers can be used for larger kitchens with longer throws, but perforated face panels
are recommended for lower air velocities, which will minimize drafts in the kitchen. The maximum supply
Hot rate is 250 cfm/ft. through perforated panels under
Air
ideal conditions. For optimum performance design to
Ceiling
recommended values of 150 cfm/ft. Face supply should
not be used when a wall, another hood, menu board,
or other object is less than 6feet from the face.
Figure 14
The problem with bringing hot untempered air into an air-conditioned room can be seen in Figure 14. Hot air will
not fall into the room and cycle back out through the hood, rather the hot air will hug the ceiling because it is
more buoyant. If humidity is present in the hot make-up air, it will condense on the metal ceiling diffuser when
it mixes with the air-conditioned air brought through it. Most of the hot air along the ceiling will be taken in at
a return grill by the roof top unit (RTU) and conditioned before it is introduced back into the room, thus totally
defeating the purpose of bringing in untempered make-up air.
16
>180 cfm/ft.
Combination Hood Low
Combination hoods (Figure 18) are a combination of face supply and air Pressure
curtain supply and are better suited for cooler climates where outside air Pocket
Figure 17
can be used to cool the kitchen. See Face Supply (pg. 16) and Integrated
Air Curtain (pg. 16) for design considerations for the different parts of
the combination hood. More make-up air can be brought through a
combination hood than a face or air curtain alone, but the same limits
exist for each part of the plenum, maximum 250 cfm/ft. from the face
150
and maximum 125 cfm/ft. from the air curtain. Perforated panels should
cfm/ft.
always be used to reduce air velocities and eliminate spillage from the
hood. Supply rates should be designed to recommended values of 150
cfm/ft. through the face and 65 cfm/ft. through the curtain for optimum
performance. An exhaust
only hood with a variable
80-160 65 cfm/ft.
supply plenum (Figure 19)
cfm/ft.
can be used instead of a Combination Hood Figure 18
combination hood which
will increase maximum
supply rates (see external adjustable
air curtain, face supply) and damper
not take up valuable capture
and containment volume. 0-80 cfm/ft.
Multiple Sources
Figure 21 depicts
two scenarios. The
picture on the left
shows air brought in
through one side of
the room while the
picture on the right
shows air brought Figure 21
3 in evenly throughout Figure 22
the room. To accomplish even airflow, use any one of the hood supply types along with multiple
non-directional ceiling diffusers, or transfer air from another room. The amount of air to each diffuser decreases
with an increase in number of diffusers, thus lowering air velocities. Various types of diffusers can be used,
but non-directional perforated panel diffusers work best. Transfer air can be brought into the kitchen through
non-directional ceiling diffusers from the building HVAC as long as air velocities are kept below 50 ft./min at the
hood. Figure 22 illustrates the spilling of effluent when using a 4-way diffuser within 10 feet of the hood. See the
room balance section of this guide for an example of multiple sources.
These units condition the space while only taking in some 800 1000 800 1000 800 1000
Cross Drafts
Another way to reduce spillage is to reduce cross drafts present in the kitchen. Cross drafts are created from
an unbalanced room, unequal air distribution, too much airflow from one source, or a separate air movement
source such as a fan. An unbalanced kitchen will become hot due to escaping heat. In an effort to cool the 4
kitchen, employees will open doors and run fans to cool themselves, which is a mistake. These two things will
create cross drafts and further disrupt capture & containment, making the situation worse. If cross drafts are
unavoidable, end skirts on both sides of the hood are the easiest and most inexpensive aid in reducing cross
draft effects. Figure25 illustrates the effects of an unbalanced room condition creating air currents. Figure26
shows the effects of having a fan in the space at or near the hood. Avoid both of the situations depicted in
Figures 25 and 26.
Figure 25 Figure 26
Room Pressure
Kitchen room pressure should be kept
at a slight positive to the outside at RTU
HVAC MUA
all times. This can be accomplished Exhaust
19
Illustrated below in Figure 28 is a typical supply air diagram for a kitchen and dining room arrangement with
the accompanying air balance tables. The hood has a dedicated exhaust fan and make-up air unit. The kitchen
also has a dedicated HVAC supply (RTU) unit to help take some of the conditioning load. In the dining area
another dedicated HVAC unit is used to supply the air and make up any losses from rest rooms or other small
exhausted areas. Notice, there is transfer air going into the kitchen from the dining area, thus the kitchen
is slightly negative to the dining area containing odors although the balance of the dining area of 200 cfm
exfiltration (EXF) shows that the building as a whole is at a slight positive to the outdoors as desired.
KX-4000
OSA-1100
MUA-3100 OSA-200
TX-200
MUA-1600 SUP-800
600 3900 SUP-2500 SUP-2500
EXF-200
MUA-1500 TRA-700
KX-4000
Water
Kitchen Dining Closet
Figure 28
20
AIRDATA Multimeter by
Shortridge Industries
The Shortridge multimeter is a new
alternative to the rotating vane anemometer.
This meter can measure airflow, velocity,
pressure, and temperature quite easily.
It consists of two main components,
the velgrid to sense the airflow and the 4
meter itself. Additionally, it can store up
to 200 readings and automatically senses
the temperature of the air so that it can
account for the local air density when taking Figure 29
readings. Different conversions for different
types of filters are required in order to
convert the reading from feet per minute to cubic feet per minute. Greenheck has charts with instructions to do
so for its filters. Figure29 is an illustration of the Shortridge setup and operation.
21
3.5
balanced.
3
Note 1: For many systems, an
EABB may not be needed on the 2.5
hood that has the highest static
pressure. The exception to this 2
is if the individual ductwork has
1.5
uneven static pressures.
1
Note 2: When sizing the fan,
use the static pressure from the 0.5
highest hood and sum the cfm
from all the hoods. 0
500 1000 1500 2000 2500 3000 3500
Duct Velocity FPM
Figure 32
22
GREASE EXTRACTION
The removal of grease from the exhaust airflow is a very important part of commercial kitchen operation.
Without proper filtration, grease will:
Collect in the exhaust plenum and ducts creating:
- A fire hazard
- An increase in the frequency of costly duct cleaning
Collect on the fan causing it to become unbalanced and lead to premature failure
Create odor in or near the restaurant
Collect on the rooftop causing deterioration of roof materials
Collect on the rooftop equipment and cooling coils
These problems can be greatly reduced through the use of proper grease filtration devices.
History
For years, the commercial kitchen industry has been without a standard for rating filtration devices. This has
led to many manufacturers listing efficiency ratings of 90% on their filters. These claims are made from the old
Navy test, ULC 710, and UL 1046 grease loading safety tests required for all filters in TYPE I hoods which are 5
inaccurate because grease particle size is not taken into account. Research started in the mid 1990s to develop
a standard test that would account for particle size with filter efficiency. With this standard, grease filters will be
directly comparable.
Total Emissions - Vapor & Particulate
Particulate Vapor
Grease Emissions 35
Mass of Emissions (lb/1000 lb food)
tti
t
tti
t
s
s
er
er
er
r
as
as
toe
oe
izz
izz
he
he
urg
urg
urg
Bre
Bre
tat
eP
eP
bu
ag
ag
ta
mb
mb
mb
and roofs.
Po
Po
am
Sp
Sp
n
en
ag
g
ke
Ha
Ha
Ha
sa
r
er
ick
H
us
ge
ge
rye
hic
au
Fry
er
dle
ler
le
Sa
Ch
an
an
sF
nS
rC
idd
oil
roi
ic R
sR
ic
en
ler
Br
Ga
ile
Gr
ve
sB
ctr
sG
Ov
roi
Ga
Bro
ctr
ic
sO
Ele
ic
Ga
sB
Ga
ctr
Ele
ic
Ga
tric
Ele
ctr
Ele
Ga
Figure 33
can range in size from .01 to 100
( = microns). A human hair = 100 microns. Grease vapor refers to grease in the gaseous state that is much
smaller than grease particulate. Vapor is condensable and may condense into grease particulate or remain in a
vapor state while being exhausted into the atmosphere. Figure 33 shows the amount of grease particulate and
vapor produced when cooking 1000 lbs. of different foods on different types of cooking equipment.
Theoretically, emissions down to 0.01 can be filtered out of the airstream, however, vapors cannot be filtered
using traditional filters. Grease particulate larger than 10 - 20 is too heavy to remain airborne and will drop out
of the airstream. Most grease filters operate between 1 - 10 .
Cooking Equipment
Another important concept to understand is the variation of emissions given off by different cooking equipment.
A study was done in 1998 by the University of Minnesota for ASHRAE, report 745-RP, which identified the type
and size of grease emitted from various cooking equipment. Different amounts of various sized particles are
emitted from the cooking equipment depending of the type of equipment being used and type of food being
cooked. Appliances that produce a large heat load typically produce a larger amount of emissions. The total
shaded region in Figure 35 shows the mass of emissions vs. particle size for a griddle.
23
Filter Efficiency
Filters can seldomly be given a single meaningful efficiency number. This is because a filter has a different
efficiency for different size particles, different flow rates, and different phase of particles. A filter that is 90%
efficient at removing 5 particles
may only be 75% efficient at Efficiency vs. Particle Size
removing 1 particles. 600 cfm per filter
100
GG
A fractional efficiency curve is a 90
graph that gives the efficiency 80
of a filter over a range of particle GX
Particulate Efficiency
70
sizes. Fractional efficiency curves
60 Water Wash
are created by subjecting a test
filter to a controlled distribution 50
of particles and measuring the 40 Dry Cartridge Filter
quantity of particles at each given 30
size before and after the filter. The 20
Baffle
60 120
represents the amount of grease taken out of Grease Removed
the airstream by the filter. The lightly shaded 50 100
area represents the grease particulate that
40 80
escaped past the filter. The ratio of dark shading System Efficiency = 68%
to light shading at a particular particle size is 30 60
represented by the fractional efficiency curve.
20 40
Filters with higher efficiencies will have more
of the total shaded area darkened. This can be 10 20
seen in Figures 35-38. Grease not Removed
0 0
0.1 1 10 100
Particle Size m
Gas Griddle Hamburger Emissions Grease not Removed Efficiency Water Wash Hood
Figure 35
24
Particulate Efficiency
Mass (mg/m3)
ability to remove particulate is 60 120
50 100
30%. Baffle filters use inertial
40 80
impaction, which is the System Efficiency = 31%
30 60
principle of the particles
20 40
momentum throwing the
10 20
particle out of the airflow
0 0
as it changes direction, to 0.1 1 10 100
remove grease from the airflow. Typical pressure drops Particle Size m
for a 9 ft. x 4 ft. hood at 2050 cfm will be 0.5-0.6 in. wg. Gas Griddle Hamburger Emissions Grease not Removed Efficiency Baffle Filter 600 cfm 5
See Figure 36. Figure 36
Mass & Efficiency vs. Particle Size
Grease-X-TractorTM Filter Over Griddle with Hamburger
Centrifugal Filter
100 200
The Grease-X-Tractor is 50%
90 180
efficient at 5 . A cut point of 5 80 160
is typical of a centrifugal filter.
Particulate Efficiency
70 140
Its efficiency improves rapidly
Mass (mg/m3)
60 120
above 5 and drops below 50 100
5 . The use of centrifugal 40 80
force rather than two- 30
System Efficiency = 73%
60
dimensional impaction allows 20 40
the efficiency to be improved 10 20
without a high penalty in 0 0
60 120
works by adsorption of 30 60
increases to near 100% at 7 and drops for particles Gas Griddle Hamburger Emissions Grease not Removed 600 cfm Efficiency Grease Grabber
Wet Chemical
Wet chemical fire suppression systems use a potassium based chemical extinguishing agent. The agent is
discharged over the entire cooking battery and reacts with hot grease to form a blanket of foam in a process
called saponification that seals the hazard depriving the fire of oxygen. The wet chemical system is available in
two types:
Appliance Specific
These systems are designed specifically for appliances and require knowledge of the cooking battery under
the hood. Specific nozzles and fusible links are chosen based on the type of appliance. The systems use
a temperature rated fusible link to hold a scissors link together (Figure 40). When the fusible link melts,
the scissors opens activating the system. This is a dedicated detection system that requires permanent
equipment placement if the equipment is moved or changed, re-piping is necessary.
6
Full Flood
Full flood systems require no prior knowledge of the cooking battery
with the exception of shelves, salamanders, and upright broilers. Full
flood systems have drops evenly spaced across the length, the spacing
is dependent on the manufacturers UL listing. The detection system is
either a pneumatic tube (Figure 41) that runs the full length of the hood,
or fusible link detection with the links evenly spaced along the length
of the hood. The advantage of the full flood system is that cooking
equipment can be moved and changed without having to alter the fire
suppression piping. See Figure 39 for an example of full flood coverage.
Length of Hood
Dual agent fire suppression systems uses both wet chemical and water to suppress the fire. Similar to the other
systems, a wet chemical agent is used to blanket the fire with foam followed by water to cool the hazard. By
cooling the area the chance of a flare-up is reduced. Dual agent fire suppression systems are available both as
appliance specific and full flood, and utilize a fusible link detection system.
Before choosing a type of dual agent fire suppression it is imperative that the water pressure at the jobsite be
verified. The dual agent system requires 33 psi for large systems and continuous piping systems. For branch
piping and average size systems, 22 psi of water pressure will be sufficient. Check with the fire system supplier
to determine the required water pressure for the application.
Water Spray
The Water Spray fire suppression system is an automatic system, designed to protect the cooking equipment,
hoods, ducts, plenums, and filters in facilities designed with wet-pipe sprinkler systems. Once activated, the
system provides a focused continuous water mist until it is manually turned off. Water spray fire suppression
only discharges onto the fire area, not over the entire cooking battery. In 1997, UL removed the listing from the
EA-1 fryer nozzles. Greenheck, with several other manufacturers, has developed the Dual Tech nozzle for use
over fryers. The nozzle has self-contained chemical canisters that discharge on the fryer first, followed by water.
Due to the poor performance of water spray fire protection, many local and state codes prohibit the use of
these types of systems. Thus, check with the local code authority on the job to get approval in writing before
specifying and purchasing a water spray fire suppression system.
26
Figure 41
Figure 40
27
28
Control System for 3-phase motors with variable speed (temperature sensors)
Temperature sensor in the duct collar as input device
Exhaust and supply speeds vary with the temperature
Fire system warning alarm tripped at a set temperature
Fire system activated which also turns off supply fan
100% override to high speed
Variable frequency drives (exhaust and supply)
The control system varies the frequency of the motor drives according to the temperature seen in the duct
collar. Instead of high or low, this system will run at the optimum performance. This option will include a duct
mounted temperature sensor, I/O processor, frequency motor drives, and a keypad.
29
30
TYPES OF FANS
Upblast
Upblast fans are the most common type of kitchen exhaust fan. They use a centrifugal
backward inclined fan wheel, are either direct drive or belt driven with an isolated
motor, and can be roof or sidewall mounted. The belt driven units have adjustable
pulleys for final system balancing. Be sure to check the current load (amps) on the
fan motor after a change has been made. Small increases in fan speed results in large
power increases required by the motor. Grease drains/traps should be used on the
fan to collect grease that has passed through the filtration system and may cause
roof damage. A vented curb may be required in heat applications such as kitchen
ventilation. Hinged curb cap and cleanout ports allow easy access to the inside of the fan and duct.
Inline
Inline exhaust fans use a centrifugal backward inclined fan wheel and are mounted
as part of the ductwork, usually inside the building. Access panels are located on
the housing allowing disassembly of the fan without removal from the ductwork.
These fans are best suited for applications where mounting a fan on the exterior
of the building is not possible. Examples would be a high-rise building where
penetrating multiple floors with ductwork would not be feasible or a building where
a fan would detract from its visual appearance. Inline grease fans have an isolated
motor, adjustable pulleys, and two grease drain plugs with the capability of being
mounted horizontally or vertically. 8
Utility
Utility fans offer a variety of discharge positions and can be mounted inside or
outside of the building, offering flexibility with respect to duct design. Although utility
fans use a centrifugal backward inclined type wheel, the airflow pattern is changed
such that the air is turned 90 as it passes through the fan. This must be considered
when designing the ductwork layout. An isolated motor compartment and adjustable
pulleys offer flexible speed adjustment for final system balancing, but check the
current load (amps) on the motor after each adjustment.
Fan Selection
A fan should be selected based upon a variety of criteria. First, decide which type of fan is best suited for the
application. Next, determine airflow requirements (see determining exhaust rate) and system static pressure
(see ductwork and pressure loss). Third, consider the fan sound level. For example, for two fans that produce
the same airflow rate, the fan with the larger fan wheel will be running at a lower RPM, thus producing less
sound. A fans sound level at various operating points can be obtained from the fan manufacturer and are given
in either decibels or sones. Choose the appropriate voltage and phase for the power going to the motor.
Each fan has a set of fan curves based on airflow, system resistance, motor power, and fan speed. It is crucial
to choose a fan within the limits given by the fan manufacturer on the fan curves. The curve that represents
system resistance begins at the origin and has an increasing slope on the fan performance graph. The curve
that begins at a higher static pressure at zero airflow and tapers to zero pressure with increasing airflow is the
fan performance curve. This is a line of constant fan RPM. To find the correct fan, operating points must fall on
the fan performance curve to the right of the system resistance curve.
31
2.5 1.0
2.0 0.8
Curve A
2.0 Curve A 0.8
Static Pressure (in. wg)
1.5 0.6
Curve B
Power (hp)
Power (hp)
1.0 0.4
1.0 0.4
Curve C Curve C
0.5 0.2
0.5 0.2
Model 1 Model 2
32
Heating
Direct Gas The most common units, especially in the northern half of the United States, are the direct gas-
fired units. These units provide outside air that is usually untempered in the summer months and heated in the
fall, winter, and spring months. They have an operating efficiency of nearly 100% because the flame is directly
in the airstream. Some efficiency is lost in the combustion process. A temperature sensor is set in the unit to
regulate the heating cycle. Direct gas-fired units move the air directly over a burner to obtain the desired leaving
air temperature. A unit that is running too slowly is likely to introduce unwanted by-products into the building
airstream.
Fortunately, many manufacturers have the ability to operate their units at 70-50% of the total airflow. A
modulating damper at the inlet maintains a minimum airflow velocity of 3000 fpm across the burner. It is
important to verify the heat and airflow turndown with the manufacturer to prevent costly redesigns.
Indirect Gas Similar to direct gas-fired, indirect gas-fired units also heat the air when needed or otherwise
bring in untempered outdoor air during warm months. This process uses a heat exchanger which is 80%
efficient. Gas is fired through a clamshell or S-tube heat exchanger. Heat is then transferred to the air as it
passes over the clamshell or tubes while combustion by-products are vented to the outdoors.
Steam Coil Air reaches its leaving temperature by flowing over steam-heated radiator coils. Steam from a
boiler system can be tied into a series of coils in a make-up air unit. This allows the use of steam in heating air
during cold periods.
8
Hot Water Hot water can be used similar to a steam coil but is uncommon in kitchen applications.
Electric Heating Electric-heating coils can be placed in a heater control cabinet on a make-up air unit to
provide heat during cooler periods of the year. However, electric heat can be costly.
Cooling
Direct Expansion This method of cooling utilizes refrigerant gas in a cooling coil. Air is cooled as it travels
across the coil. This method is commonly used with direct gas-fired and indirect gas-fired units when both
heating and cooling is desired.
Evaporative Cooling Evaporative cooling is inexpensive and works well in areas that are hot and dry. The
hot, dry air is passed through a moistened media and cooled using the principle of evaporation. Heat is needed
to cause evaporation, thus heat is pulled from the hot air passing over the media. This is an easy addition to
any make-up air unit to provide inexpensive and efficient cooling.
Chilled Water Coil Just the opposite of the hot water coil, chilled water runs through a set of coils cooling
the air as it passes over them. An easy and relatively inexpensive option if already using chilled water cooling to
condition a building.
In many cases, heating is required more often than both heating and cooling. Additionally, a building may have
an air conditioning system already in place that can supply enough cool air to the kitchen during warm days
eliminating the need for cooling. However, heating and cooling options can be combined into one make-up air
unit. It is best to consult the manufacturer for a full list of heating and cooling options.
33
Curve A
1.4 3.5
1.2 3.0
Static Pressure (in. wg.)
Power (hp)
0.6 1.5
0.4 1.0
34
Design
A consideration when designing ductwork is finding the optimum flow rate through the duct. This is done to
reduce grease particles from settling in the ductwork. Hood exhaust flow rate (cfm) should be known from
the hood selection process, therefore duct size can be calculated. Choose a duct velocity between 1000
and 2000fpm and use Eq. 1-3 to determine duct areas and velocities. Duct velocities above 2000 fpm create
unwanted noise and duct sizes are too large for velocities below 1000 fpm.
Eq. 1
Eq. 2
Eq. 3
System Effects
System effects are losses that occur due to the design of duct
systems. There is no good way to calculate the pressure loss
associated with this phenomenon, but there are ways to prevent
it. One of the largest contributors to system effects is an elbow
just before termination into the exhaust fan. This elbow creates Avoid direction
turbulence at the fan, causing fan performance to suffer. See changes like this Figure 49
near inlets and
Figure 49. A minimum distance of three fan wheel diameters outlets.
must be between the bend and the fan inlet.
35
Eq. 4
Expansion and Contraction joints are used to change the duct velocity by increasing or decreasing the duct
size. To determine pressure loss, find the area of the duct on both sides of the joint, then find the ratio of the
areas. Determine the angle of the transition, then use the table to find the pressure loss.
A2
Expansion Loss (in. wg) @ 1500 feet per min
A1
Duct Expansions
180 Expansion
Figure 50
9
Contraction Loss (in. wg) @ 1500 feet per min A1
A2/A1 10 15-40 50-60 90 120 150 180
2 0.0070 0.0070 0.0600 0.0168 0.0253 0.0337 0.0365
A2
4 0.0070 0.0056 0.0700 0.0239 0.0379 0.0491 0.0575
Gradual Contraction
6 0.0070 0.0056 0.0700 0.0253 0.0393 0.0505 0.0589
10 0.0070 0.0070 0.0800 0.0267 0.0407 0.0519 0.0603 A1
Duct Contractions A2
180 Contraction
Figure 51
36
Ac
A tee-type connection is for ducts running into other Qc
37
F = 180o
C Y-Type Connection
C D 90 Elbow (Miter)
E 180 Expansion
A B
= 45
o
F 90 Elbow
G Fan Inlet
38
Reference Figure 53
Reference Figure 52
Reference Figure 50
Reference Figure 52
39
5 UDS FEATURES
1. Utility Chase
Gas Drop 2. Utility Riser
3. Removable Panels
Hot or Cold Water Drop
4. Bumper Guards
10 5. Riser Collar
1 6. Support Pedestal
7. Pipe Manifolds
9 2 3
8. Pipe Stub Outs
7 9. Hood Light/Fan
Switches
8 10. Covered
4 Convenience Outlet
11
11. Receptacle
6
Figure 55 Mounting Plate
(Underneath)
10
40
Greenhecks FlexConnect UDS is available in four different options; base unit, receptacle only (Electrical
option 1), a complete wiring (Electrical option 2), and custom units. FlexConnect base and optional equipment
packages allow for fast lead times and lower prices while custom units can be designed to meet any need.
FlexConnect Design Options
1. Base Unit This unit includes plumbing for gas and water service. No electrical package, but unit can be
field wired by the electrical contractor. To design this system the following must be provided: Desired UDS
length, hood hanging height, and if plumbing accessories are required, provide appliance requirements (gas
and water ball valve sizes).
2. Electrical Option 1 Base unit with receptacles every 12 inches along the bottom of chase. They are
sized to the cooking equipment but are not wired. Field wiring is required by electrical contractor. To
design this system the following must be provided: Desired UDS length, hood hanging height, appliance
requirements (gas and water ball valve sizes, voltage, amps, phase).
3. Electrical Option 2 Base unit with receptacles fully wired to either a panelboard or point of use electrical
system. To design this system the following must be provided: Desired UDS length, hood hanging height,
appliance requirements and location (gas and water ball valve sizes, voltage, amps, phase).
Main Service
Disconnect Switch
ACCESS PANEL(S) 1
FIRE SYSTEM 2.
3.
4.
6 6 7
DISCONNECT SWITCH 5.
6.
7.
8.
9.
10.
11.
VERTICAL 12.
13.
14.
VENTILATOR
FAN/LIGHT SWITCHES
BLANK PLATE(S)
FOR OTHER CONTROLS
20 AMP 120V
RECEPTACLE
BOTH ENDS
UNDERSIDE OF CHASE
RECEPTACLE PLATES
120/1ph 20 AMP.
LABELED
BREAKER PLATE
4 5
120/1ph 20 AMP.
6 7
120/1ph 20 AMP.
10
UNDERSIDE OF CHASE
RECEPTACLE PLATES
41
DESIGN CONSIDERATIONS
When designing a kitchen ventilation system, there are a number of ways to enhance hood performance. Even
though many of these considerations are not required, it is still a good idea to make sure the system being
designed meets these considerations.
Recommended Overhang
(Units in Inches)
Front Sides Back
Combi Oven 18 6 -
Overhang
Dishwasher 18-24 6 18
Equipment Under
12 6 -
Wall Canopy
Equipment Under
12 12 12
3. Dishwasher Overhang Single Island
12 inches minimum overhang on sides with doors Equipment Under
12 12 -
Spilling may occur when dishwasher door is opened Double Island
18 inches is recommended to minimize spillage
11
4. Hood Hanging Height Affects Capture 5. Extraneous Air Currents can have enough force
and Containment: and velocity to push the contaminated air out
6 ft. 6 in. (78 inches) recommended from under the hood:
7 ft. 0 in. (84 inches) allowed but requires more Keep air currents to a minimum. NO fans for
overhang or more exhaust airflow spot cooling.
Higher hanging heights may create problems
42
30
24
11
10. Hood Volume: 24 inches vs. 30 inches 11. Internal Supply Plenum vs. Exhaust Only
30 inches provides a larger capture tank Exhaust only has a larger capture tank for
for surges surges
Most important over char-broilers Use exhaust only with external supply plenums
Most important over char-broilers
43
Transfer
Fan
11
16. Even Supply Air Distribution 17. Uneven Supply Air Distribution
Supplying air equally from all sides of the As illustrated, uneven supply air will induce
hood will enable efficient capture and spilling
containment
44
B B
A A
C C
18. Even Supply Air 19. Hoods Facing Each Other (avoid if possible)
Bringing in supply air evenly on all sides If situation A occurs, use perforation in face
of the hoods will enable capture and Use B with perforation, no 4-way diffusers
containment at lower airflow Along with B, use C (back supply plenum)
11
Hood Perforated
Ceiling Diffuser
22. 4-Way and Throw Distance 23. Japanese Steak House (Show Cooking)
Keep the airflow below 75 fpm at the hood, Hoods located in dining room, not in kitchen
although recommended to be at 50 fpm Use perforated ceiling diffusers throughout the
maximum entire dining area to reduce cross drafts
45
APPENDIX: TROUBLESHOOTING
Problem: Pilot lights are blown out or cooking equipment is cooled by make-up air
Try turning off or reducing the amount of make-up air;
Block off portions of the supply to direct air away from
Are there drafts from make-up air? the problem area (test with cardboard first); remove any
obstructions in front of supply that directs air toward the
cooking equipment
46
Problem: Hood is full of smoke. There is smoke spilling out of the edges of the hood.
See determining exhaust rate and exhaust fan
Is the fan operating at design levels?
selection (pages 31 to 32)
Refer to test and balance report and compare with
Is the fan correctly sized?
findings from the exhaust rate calculations
Clean filters, replace damaged filters, and properly
Are the filters in good condition?
position them
Is there sufficient make-up air?
Check make-up air unit, increase make-up air, ensure
(Kitchen should be a slight negative but not
that make-up air is evenly distributed through the
excessive; check to see if there is a strong draft
kitchen
through an open door)
Does the current cooking equipment battery match
Adjust or replace fan to match the cooking load
the original design?
One hood may be over exhausting and the other
Are there multiple hoods on one fan? not drawing enough; restrict second hood using a
balancing baffle to balance the airflow
Are there closed fire dampers in the duct? Open fire dampers
Replace fan that can handle higher static loads or
Is the ductwork too complex or too small?
modify the ductwork
Is the ductwork obstructed? Clear obstruction
Turn off or reduce the amount of air supplied to short
Is this a short-circuit hood?
circuit
Problem: Smoke blows away before reaching the bottom of the hood
Adjust the amount and locations of make-up air to
Are there pass-thru windows near the hood?
eliminate drafts through the pass-thru windows
Is this an air curtain hood? Turn off or reduce the amount of make-up air
Try turning off or reducing the amount of make-up air;
Is the make-up air part of the hood or an attached
block off portions of the supply to direct the air away
plenum?
from the problem area. (test with cardboard)
Are there cooling fans directed at the hood or cooking
Turn off fans
equipment?
Move diffusers to a more neutral area or replace with
Are there ceiling diffusers directing air at the hood?
a diffuser that directs air away from the hood
Are there open windows or doors? Close windows and doors
Find the source of the draft and eliminate it; consider 12
Are there cross drafts or other side drafts? adding end skirts to the hood (test with cardboard);
increase overhang
Add end skirts to the hood (test with cardboard first);
Is the hood near a main walkway?
increase overhang on spilling edges
47
GLOSSARY
Authority Having Jurisdiction (AHJ): The organization, office, or individual responsible for approving equipment,
installation, or a procedure in local jurisdictions.
Backward Inclined: A fan wheel with blades that lay back in the direction of rotation. That is, the edge of the blade
closest to the center axis of rotation will pass a given point before the rest of the blade.
Centrifugal Fan: Fan which moves air away from the center of the wheel to the outer edge in a radial orientation.
CFM: A volume flow rate, cubic feet per minute.
Char-Broiler: An open grill with gas heated briquettes or electric strip heaters. Temperature rating 600F.
Clearance to Combustibles: The airspace required between any hood surface and adjacent surfaces (walls,
ceilings, etc.) See NFPA 96, IMC, and local codes for airspace requirements.
Contaminated Air: The unwanted by-products of cooking such as heated air, grease vapors, water vapor, smoke,
gas combustion by-products and the air affected by these items.
Centrifugal Action: The act of using centrifugal force while spinning the air in a helical or corkscrew to separate
solid particles from contaminated air.
Exfiltration: Air exiting a space due to positive pressure.
FPM: Feet per minute, defines the speed of the air.
Fryer: Kettles mounted in a floor or bench mounted unit heated by gas or electricity. Food is cooked by being
immersed in a kettle full of heated oil. Temperature rating 400F.
Griddle: A unit with a thick, flat, steel plate heated by gas or electricity for cooking by dry heat. Temperature rating 400F.
Hood Face Area: The area of the hood, measured at the inside, lower canopy entrance, expressed in square feet.
Inertial Impaction: As grease laden air passes through a filter that causes a change in direction of the air, the
grease is thrown out of the airstream and sticks to the filter upon impact.
Interception: As grease laden air passes through a bead bed filter, the particle contacts the filter media where
upon impact the grease is collected while the rest of the air continues its path of travel.
K-Class Fire Extinguisher: Portable wet chemical fire extinguisher designed to suppress grease fires found in
kitchens. It utilizes the same chemicals found in the fire suppression systems.
Kitchen Ventilation System: Hoods, fans, make-up air units, and other accessories that comprise the system for
ventilating a kitchen.
Minimum Capture Velocity: The velocity of air in feet per minute required to contain smoke, grease vapors, steam,
or heat.
Minimum Face Capture Velocity: The velocity of air in feet per minute required across the face of the hood to
contain smoke, grease vapors, steam, or heat in the regions outside the updrafts.
Oven: A chamber used for baking, heating or drying foods. Temperature rating 400F.
Overhang: The areas of the hood that project beyond the cooking equipment, measured from the internal
perimeter of the hood.
Payback Period: The time for the annual savings to equal the initial cost of an investment.
Proximity Hood: Also referred to as a low wall or backshelf hood. Typically used for low to moderate temperature
counter-height equipment.
Qc: Amount of contaminated air generated by a heated cooking appliance.
Qf: Amount of air required to contain sudden surges, cross drafts, and turbulence above and beyond Qc.
Range: A stove with spaces to cook several things at the same time. Temperature rating 400F.
Rate of Return: The rate of earnings received above the initial cost of an investment compounding annually.
(Usually expressed as a percentage)
Schlieren Imaging: An advanced visualization tool that allows the eye to see changes in air density such as the
heat rising off of appliances.
Solid Fuel: Charcoal, wood, or other natural burning cooking sources. Temperature rating 700F.
Spilling: The act of contaminated air escaping from a kitchen hood.
Surges: Large quantities of contaminated air generated by abnormal conditions.
12 Thermal Updraft: The upward movement of air due to a change in density. (Temperature drives density changes).
Variable Volume: A control system that varies the amount of airflow a kitchen ventilation system exhausts and
makes up based on the cooking load.
Wet Chemical Agent: The suppression agent for wet chemical fire suppression system that suppresses fire by
asphyxiating the fire. Usually made up of a solution of water and potassium carbonate-based chemical, potassium
acetate-based chemical, potassium citrate-based chemical or a combination thereof that forms the extinguishing agent.
48
GREENHECK METHOD
Steps 1 through 4 are the steps required to obtain the total exhaust rate using the Greenheck Method.
QE
See page 14 for an example calculation.
QF
QC
HOOD FACTORS
50
Recommended
Dimensions Supply Rate
Supply Type
(inches)
cfm/linear ft. fpm
The table to the right lists the various methods Back Supply 6 wide 145 290
of supplying air to the space. The recommended Air Supply 12 wide 110 150
External
13
51
13
52
13
53
Underwriters Laboratory
http://www.ul.com
13
54
NOTES:
13
55
Our Warranty
Greenheck warrants this equipment to be free from defects in material and workmanship for a period of
one year from the shipment date. Any units or parts which prove defective during the warranty period will
be replaced at our option when returned to our factory, transportation prepaid. Motors are warranted by the
motor manufacturer for a period of one year. Should motors furnished by Greenheck prove defective during
this period, they should be returned to the nearest authorized motor service station. Greenheck will not be
responsible for any removal or installation costs.
As a result of our commitment to continuous improvement, Greenheck reserves the right to change Prepared to Support
specifications without notice. Green Building Efforts
January
2014
Table of Contents
Greenhecks comprehensive line of kitchen ventilation products are designed to meet the varying needs of
food service establishments. Whether you are working on a school cafeteria, restaurant, industrial cooking
process, or otherwise, Greenheck has the products and resources to meet your ventilation requirements.
Additionally, Greenheck offers exhaust fans, make-up air units and more to create a complete, quality kitchen
ventilationsystem.
To learn about our controls, utility distribution systems and other products, see the kitchen ventilation catalogs
identified on the back cover and visit www.greenheck.com.
Grease Extraction
2
2-Step Decision Guide
3
2-Step Decision Guide
Single-Island Hood
Double-island hoods:
Used when the cooking battery is in two back-to-back rows, not
against a wall.
Double-Island Hood
Type II Hoods: What hood style do I need?
Heat and fume:
Heat-only hoods are typically used for oven applications.
Condensate:
Condensate hoods are typically used above dishwashers. Heat and Fume
Condensate
C d t
4
Grease Hoods Type I
NSF
5
Grease Hoods Type I
Type I Overview
GH - E - W
Filter Configuration
GH - Baffle Filter Make-Up Air Style W - Wall Style Canopy
GX - Grease-X-Tractor E - Exhaust Only V - Single-Island Style (V-Bank) Canopy
GG - Grease Grabber D - Exhaust Only - Double-Wall Front P - Proximity (Backshelf)
GK - High Velocity Cartridge Filter F - Face Supply
GW - Water Wash C - Face and Air Curtain Supply
PH - Pizza (PHEV) Only
GG H2O
6
Grease Hoods Type I
Exhaust Only
Supply air is introduced through ceiling diffusers or external
supply plenums (shown on page 26-28)
More dimensional flexibility than other manufacturers
Single-Wall Front
Double-Shell Front (Optional)
- One-inch of insulation between stainless steel panels
provides additional strength and rigidity
Face Supply
Supply air is introduced horizontally through the face via
perforated panels in a manner that does not interfere with the
cooking operation beneath the hood(s)
Perforated panels are located on the face to ensure uniform
distribution and will limit the throw to within several feet of the
hood(s)
Higher level of dimensional flexibility than other manufacturers
7
Grease Hoods Type I
Auto-Cleaning Hood
Typical grease hoods, though low-cost up front, carry many overlooked and expensive maintenance issues
that can lead to high costs over their lifespan. Capturing the grease generated by cooking processes is a
challenge and the clean-up of grease is both costly and time consuming.
8
Grease Hoods Type I
Face Supply
Make-up air is supplied horizontally through the face via
perforated panels in a manner that does not interfere with the
cooking operation beneath the hood(s)
Perforated panels are located on the face to ensure uniform
distribution and will limit the throw to within several feet of the
hood
Specialty Hoods
Greenheck offers many specialty hoods such as radius corners,
heavier gauges and hoods with cladding. Contact your Greenheck
representative to discuss your specic requirements.
9
Grease Hoods Type I
Filtration Options A variety of filtration options Tapered Hood* Tapered fronts are available for low
are available with increasing grease extraction ceiling applications.
efficiencies to suit specific needs. See our Grease Tapered Required
Extraction section on page 17-25 for more detail. Fronts Overhang
(inches) (inches)
12 12
External Supply Plenums* Several supply plenum 15 12
options are available to supply air back to the 18 6
spaceevenly. See External Supply Plenums section
on page 26-28 for moredetail. Exhaust Collars
Factory-Mounted Collars are fully welded to the
Continuous Capture* exhaust plenum and include a 1 inch flange.
Provides a UL Listed Ship Loose Exhaust collars are included, but not
bolted connection mounted to the hood. This enables the contractor
allowing end-to-end to locate and cut the exhaust opening, where
hoods to be connected desired, without knowing ahead of time.
and appear as Shape To accommodate various ductwork,
onehood. several sizes of rectangular and round collars are
available.
Material Options* Standard construction is
Location* Top or back placement for mounted
stainless steel where exposed and galvanized steel
exhaust collars.
in the unexposed plenum. 100% stainless steel
construction is available. Either option is available in Supply Collars
300 series stainless steel or 430 stainlesssteel. Additional Collars* To maintain lower supply
airflow velocities around the hood, additional
Lighting Options* Multiple supply collars can be added.
lighting options are available.
Shape (Round or Rectangle) To accommodate
Screw in for incandescent or CFL
various ductwork, different sized collars are
fixtures are standard. Recessed
available on most supply plenums in both round
incandescent and 2-, 3-, or 4-foot
and rectangular shapes.
recessed fluorescent fixtures are
also available. All fixtures are Ceiling Enclosure When the top of the hood is
vapor proof and UL Approved. mounted lower than the
finished ceiling height,
LED lighting provides a bright,
enclosure panels can
warm light for cooking and a
be provided to match
significantly longer operating
your hood. Enclosure
life. LED lights save up to 95% in
panels are easy to install
electrical costs when compared
with factory-provided
to using standard
hardware.
incandescent lights in
a kitchen hood. Backsplash Panels/Side Splash Panels Provide an
aesthetically desirable and easily
cleanable stainless steel surface
behind or on adjacent walls
near the hood. Constructed of
300 series stainless steel or
430 stainlesssteel to match the
hood. Optional insulated panels
are available.
*See Options & Accessories chart on page 12 for specic options for Grease Hoods Type I
10
Grease Hoods Type I
*See Options & Accessories chart on page 12 for specic options for Grease Hoods Type I
11
Grease Hoods Type I
Single-Island Proximity
Wall Canopy
(V-Bank) (Backshelf)
Options Make-Up
Air Style Exhaust Only Face and
Guide Face Exhaust Face Exhaust
Single- Double- Supply Air Curtain Only Supply Only
Wall Wall Supply
Options and Accessories Model --EW --DW --FW --CW --EV --FV --EP
Grease-X-Tractor
GX-- Optional Optional Optional Optional Optional Optional Optional
Centrifugal Filtration
Baffle Filter GH-- Optional Optional Optional Optional Optional Optional Optional
High Velocity Cartridge Filter GK-- Optional Optional Optional Optional Optional Optional Optional
Exhaust Collar (Ship Loose) - Optional Optional Optional Optional Optional Optional Optional
Exhaust Collar Shape - Optional Optional Optional Optional Optional Optional Optional
Exhaust Air Balancing Baffles - Optional Optional Optional Optional Optional Optional Optional
Automatic Fire Damper - Optional Optional Optional Optional Optional Optional Optional
Filter Removal Tool - Optional Optional Optional Optional Optional Optional Optional
12
Heat & Condensate Hoods
Type II
NSF
13
Heat & Condensate Hoods
Type II
Overview & Typical Applications
Type II hoods are designed to capture heat and/or condensate from non-grease producing appliances such
as ovens and dishwashers.
Greenheck heat and condensate hoods offer the following benefits:
The National Sanitation Foundation (NSF) Seal of Approval Model Number Code
(Standard 2)
Standard construction is a minimum of 18 gauge GO
430 stainless steel
Flexible lengths, widths and heights
Greenheck Hood Type II
Hood lengths: Available in 1-inch (25 mm) increments
GO - Oven, General Ventilation
Hood widths: Available in 3-inch (76 mm) increments
GD1 - Condensate - No Baffle
Hood heights: Available in 12-30 (350-762 mm) inches GD2 - Condensate - Single-Baffle
and 3-inch (76 mm) increments
GD3 - Condensate - Double-Baffle
Standing seam construction for superior strength
Excellent dimensional tolerances due to highly tooled
manufacturing
Condensate Hoods
Models GD1, GD2 & GD3
Primarily used for dishwasher or condensate applications
to capture heat and vapor, creating a more comfortable
environment for the cooking staff
These hoods are constructed with a gutter and drain
The condensate hoods are available in three styles:
No Baffles (model GD1) - Most economical and flexible
in condensate applications
14
Heat & Condensate Hoods
Type II
Options & Accessories
Material Options Standard construction is in Utility Cabinets Hood Mount/
300 series stainless steel or 430 stainlesssteel. Wall Mount Utility cabinets
for control mounting can be
Incandescent Lighting* UL Listed attached to the left or right
vapor proof incandescent light side of the hood. All hoods
fixtures are available. can be supplied with a cabinet
to be remote mounted in the
External Supply Plenums* Several supply l plenum
l space.
options are available to supply air evenly back to
the space. See External Supply Plenums section on Backsplash Panels/Side
pages 26-28 for more detail. Splash Panels Provide an
aesthetically desirable and
Mesh Filter* With most Type II easily cleanable stainless
hoods, the exhaust opening is steel surface behind or on
exposed. Adding a mesh filter in the adjacent walls near the
exhaust collar helps prevent anything hood. Constructed of 300
other than heat and moisture from series stainless steel or 430
passing through the duct opening. stainless steel to match the
hood. Optional insulated
panels are available.
Exhaust Collars
Factory-Mounted Collars are fully-welded to the
exhaust plenum and include a 1 inch flange. End Skirts* Available
in both full and mini
Ship Loose Exhaust collars are included but not configurations, end skirts
mounted to the hood. This enables the contractor lower required exhaust rates
to locate and cut the exhaust opening, where as they improve capture.
desired, without knowing ahead of time.
Shape To accommodate various ductwork, Airspace/Filler
several sizes of rectangular and round collars are Panels These
available. panels are used to
fill in open spaces
Switches* Greenheck Type II hoods allow for
and improve
switch mounting in a cabinet attached to the hood
aesthetics.
or as a remote option.
*See Options & Accessories chart on page 16 for specic options for Heat and Condensate Hoods Type II
15
Heat & Condensate Hoods
Type II
Options & Accessories
Condensate
Options
Heat/Oven
Guide No Bafe Single Bafe Double Bafe
Options and Accessories Model GO Model GD1 Model GD2 Model GD3
Incandescent Lighting Optional Optional Optional
16
Grease Extraction
NSF
17
Grease Extraction
Filtration Options
Greenheck is the industry leader in grease ltration as veried by testing to ASTM F2519-2005 standards.
This is crucial to the restaurant owner/operator because the grease generated by restaurant kitchens pose
many problems: frequent duct cleaning, rooftop grease problems and compliance with tougher air emissions
standards. Greenhecks offering of innovative lter designs attack the problem at the source for a fraction of
the cost of other grease removal devices or electrostatic precipitators.
Combination Ovens
Gas & Electric Fryers
Grease-X-Tractor Medium to
Griddles 0.7 to 0.8
Centrifugal Heavy Duty 69% 51%
Grill in.wg
Filtration Grease
Up-right Broiler
Electric Char-Broiler
18
Grease Extraction
Spatter
6.2 to 150 microns
Steam
0.55 to 6.2 microns
Submicron
.03 to 0.55 microns
19
Grease Extraction
90
Grease Extraction Efciency
80
70
60
50
40
30
20
10
0
0.1 1 10 100
Particle Size Em
Bafe Filter Grease-X-Tractor Grease Grabber Water Wash Hood Cartridge Filter
20
Grease Extraction
100 200
90 System Efciency = 99% 180
Grease Extraction Efciency
60 120
50 100
40 80
30 60
20 40
10 20
0 0
0.1 1 10
Particle Size Em
Gas Griddle Hamburger Emissions Griddle after Grease Grabber Efciency Grease Grabber 600 cfm
See Third-Party Grease Extraction Efciency Verication on page 25
21
Grease Extraction
100 200
90 System Efciency = 73% 180
Grease Extraction Efciency
60 120
50 100
40 80
30 60
20 40
10 20
0 0
0.1 1 10
Particle Size Em
Gas Griddle Hamburger Emissions Griddle after GX Efciency Grease-X-Tractor 600 cfm
22
Grease Extraction
High-Velocity Cartridge
The high velocity cartridge is designed for light duty grease applications.
How it works:
Exhaust or contaminated air passes through the high velocity stainless
steel cartridge.
As the air turns, the particles momentum forces itself out of the airstream
as it changes direction, causing the particulates to impact upon the
cartridge.
The grease then runs down the cartridge into the grease trough, which
then drains into a removable grease container.
100 200
90 System Efciency = 55% 180
Grease Extraction Efciency
60 120
50 100
40 80
30 60
20 40
10 20
0 0
0.1 1 10
Particle Size Em
Gas Griddle Hamburger Emissions Griddle after Cartridge Efciency Cartridge Filter 600 cfm
23
Grease Extraction
Standard Baffle
The industry standard bafe lter is designed for light-duty grease applications.
How it works:
Exhaust air passes through the aluminum/stainless steel baffles.
As the air turns, the particles momentum throws the particle out of the
airstream as it changes direction, causing the particulates to impact upon
the baffles.
The grease then runs down the baffle into the grease trough, which then
drains into a removable grease container.
100 200
90 System Efciency = 31% 180
Grease Extraction Efciency
60 120
50 100
40 80
30 60
20 40
10 20
0 0
0.1 1 10
Particle Size Em
Gas Griddle Hamburger Emissions Griddle after Bafe Efciency Bafe Filter 600 cfm
50
40
30
20
10
0
Gas Electric Gas Electric Gas Electric Gas Electric Gas Electric Gas Electric
Griddle Griddle Fryer Fryer Broiler Broiler Broiler Broiler Oven Oven Range Range
Hamburger French Fries Hamburger Chicken Pizza Spaghetti
Type of Appliance
= Grease Grabber
= Grease-X-Tractor Reference - ASHRAE 745-RP
The charts on pages 21-24 show the amount of grease that is extracted by a typical bafe lter, cartridge
lter, Greenhecks Grease-X-Tractor and Grease Grabber ltration system. The charts also show the
amount of grease that pass through the lter and into your exhaust duct, through your exhaust fan and
onto your roof.
This data was gathered by a third-party testing agency while cooking beef patties on a griddle. The
cooking of beef patties on a griddle yielded the largest mass of grease particles at ~18 microns in size
and the smallest at ~0.2 microns in size (human hair ~100 microns).
The blue area represents the amount of grease that passed through the lter. The green area represents
the amount of grease extracted by the lter. The more green area there was, the more grease that
was extracted in the lter. The orange efciency line shows the efciency of the lter for a specic
particlesize.
25
External Supply Plenums
Make-up air can be introduced several ways, including ceiling diffusers, through-the-hood with an integrated
supply plenum or an external supply plenum. External supply plenums positioned around the perimeter
of exhaust only hoods are a great alternative to integral supply plenums. Unlike integral supply plenums,
they do not sacrice valuable hood containment area. They can be retrotted to almost any hood and are
generally less expensive than integral plenums. Greenheck offers four external supply choices: Air Curtain
Supply Plenum (ASP), Horizontal Supply Plenum (HSP), Variable Supply Plenum (VSP), and the Back Supply
Plenum (BSP).
Standard construction features:
18 gauge 430 stainless steel
Easily removable perforated discharge panels (23% open area)
Supply plenums are available in lengths from 3 to 16 feet where longer lengths require multipleplenums
Discharge Recommended
Recommended
Plenum Type Opening Supply Rate
Application
(Inches) (cfm/ft)
Tempered Air
Horizontal Supply (Heated and Cooling)*
15 Up to 150
(HSP) Provides supply air to mix with
room air.
Non-Tempered or
Back Supply MarginallyTempered Air
6 Up to 145
(BSP) Air is kept near hood to minimize
mixing with air in thespace.
Non-Tempered or
Variable Supply Face 8 Face Up to 160 Marginally Tempered Air
(VSP) Curtain 8 Curtain Up to 80 Air is kept near hood to minimize
mixing with air in the space.
26
External Supply Plenums
27
External Supply Plenums
28
Fire Suppression Systems
Code Information
The Restaurant Fire Suppression System is constructed in compliance with the following:
National Fire Protection Association (NFPA) Bulletin #96 and #17A
UL Standard 300 Listed
UL Standard 2092 Listed (Piranha )
NSF
International Association of Plumbing and Mechanical Officials (IAPMO)
Interim Guide IGC 113-07
ISO 9001-2000
29
Page
Fire Header
Suppression
Amerex
Restaurant res can be devastating. A re can begin on an appliance,
in the hood or ductwork, and quickly spread to the building. A pre-
engineered re suppression system is the rst line of defense against
a restaurant kitchen re. Amerex has been in the re protection
industry since 1971 and has a reputation for excellence, customer
service and innovation unsurpassed in the industry.
Amerex KP Fire Suppression Systems Amerex Zone Defense Fire Suppression Systems
Appliance specic re suppression is a wet The full ood/overlapping restaurant re suppression
chemical system to be used when the equipment systems were developed to solve the real world
placement is known and expect few, if any, problem of how to protect a kitchen where the
changes. Nozzles are selected and aimed at appliances are moved around, rolled in and out for
specic hazards on each appliance. The chemical cleaning, or replaced with different appliances to
agent itself a low pH thats non-corrosive to accommodate changing menus. These systems
stainless steel which can be safely cleaned up are also cost effective with medium and heavy duty
with water and a sponge. cooking lines requiring greater protection.
The Restaurant Fire Suppression System is constructed in compliance with the following:
UL/cUL Listed per UL 300 re test specications
New York City Department of Buildings (MEA)
Meets requirements of NFPA 96 (Standard for the Installation of Equipment for the Removal of Smoke
and Grease-Laden Vapors from Commercial Cooking Equipment)
Meets requirements of NFPA 17A (Standard on Wet Chemical Extinguishing Systems)
ISO 9001:2000 and ISO 14001:2004 certied
30
Page
Fire Header
Suppression
Ansul
Ansul has been protecting restaurants since 1962 and is one of
the industry leaders in re suppression systems,
Ansul led the industry at a time when kitchen res were a leading
cause of restaurant loss, and their continued advancements
in technology and design have made Ansul the number one
foodservice re protection solution in the world.
Ansul R-102 Fire Suppression System Ansul Piranha Fire Suppression System
In an appliance specic re Dual agent re suppression
system, the nozzles and systems combine water and
placement are chosen for the chemical agent to suppress
type of cooking equipment it the re. The agent is
needs to protect. This is the discharged rst, suppressing
most cost-effective system, the re, and water follows to
as only the appliances that cool the hazard and prevent
need protection are covered. reash. Dual agent systems
can be either
appliance
specic or
full ood.
The Restaurant Fire Suppression System is constructed in compliance with the following:
UL/cUL Listed per UL 300 re test specications
New York City Department of Buildings (MEA)
Meets requirements of NFPA 96 (Standard for the Installation of Equipment for the Removal of Smoke
and Grease-Laden Vapors from Commercial Cooking Equipment)
Meets requirements of NFPA 17A (Standard on Wet Chemical Extinguishing Systems)
ABS - American Bureau of Shipping
31
Kitchen Ventilation Systems
Kitc
hen V
Contr entila
m ols tion S
Syste and En yste
ution ms
t3FMB
Z#PY ergy M
Distrib
anagem
t'BO$
Utility M omical
POUSPM$
FOUFS
t5FN
QFSBUVSF
ent
odel Econ
UDS M Convenien
t t7BSJBC *OUFSMPD
MF7PMVN L
xible F4ZTUFN
Fle T
En
O gin
ms DUJP Gr ee
ste USB ea red
Sy F&Y
se
Gr Kit
ion FBT
ab ch
be
lat (S UFNT r en
nti T Po Ve
Ve PET 4Z llu
tio
ntil
atio
h en TU)P TTJPO nC
on nS
c V F
Kit &YIB VQQS T
tro yst
lU em
4 nit
t 'JSF TPSJF s s
T
t "DDF
t
cto
c
Oc
Oct be
ber
ob
ob
obe
cttto
tob err
e
20
2 12
012
01
012
201
ber
tem 9
200
p
Se Sep
epttem
embe
bber
err
20
200
009
9
Au
gu
201 st
1
Our Commitment
As a result of our commitment to continuous improvement, Greenheck reserves the right to change
specifications without notice.
Specific Greenheck product warranties are located on greenheck.com within the product
area tabs and in the Library under Warranties. Prepared to Support
Green Building Efforts
00.KIT.1013 R3 1-2014 IW
P.O. Box 410 Schofield, WI 54476-0410 Phone (715) 359-6171 greenheck.com Copyright 2014 Greenheck Fan Corp.
Kitchen Ventilation Systems
Controls and Energy Management
Relay Box Temperature Interlock
Fan Control Center Variable Volume Systems
February
2012
Control Decision Guide
No No No
No No
No No
Do you have:
More than two fans?
Kitchen Fan Control Center
3-phase motors?
Yes Yes
(KFCC)
The need for thermal
overloads?
No
Yes
Relay Box
2
Greenheck Controls
Relay Box
Greenhecks relay box is compact, prewired and offers a low-cost
method of starting one or several single-phase fan motors. The
relay box can be used in place of larger, more expensive starters.
Standard Construction Features
Prewired from factory
Wiring diagram included in control box
Interface to shut off supply fan in fire mode is included
Requirements:
All motors must have thermal overloads
Two fans maximum, both operating from one switch
(For more than two fans, use model KFCC)
Each fan must have its own power source
Limitations:
No additional options When switches are moved to the on position,
lights turn on and relays close to start fans.
Single phase power only (120, 208 or 230 volt)
Temperature Interlock
International Mechanical Code (IMC 507.2.1.1) requires the kitchen
ventilation system to automatically start when cooking operations
occur in the case where they have not been started manually.
Greenheck satisfies this requirement through their temperature
interlock as illustrated below. This solution is also available on
Greenhecks kitchen fan control center (KFCC) and is part of the
variable volume systems discussed on pages 4-7.
Standard Construction Features
Temperature sensor to detect heat from the cooking operations
is used to signal the control to start the fans.
Automatically turns off fans when heat is no longer present
and prevents fan cycling by means of set point temperature
differential (digital temperature interlock) or 1-100 minute time
delay relay (thermostat control option).
Meets IMC code 507.2.1.1
Heat from the equipment is sensed by the
UL Listed temperature probe. Control automatically
starts fans if not already started manually.
Temperature Control Options
Digital temperature interlock includes a micro controller with
LED display that can be remote mounted. This option provides
easy access and accurate control when making seasonal
adjustments to the temperature setting, eliminating the need to
access the hood top.
Thermostat control utilizes a sensor with set dial screw on the
back to adjust the temperature. This can be advantageous when
trying to control several sensors, as they can be connected in
parallel back to one small control. Digital Temperature Interlock
3
Greenheck Controls
4
Greenheck Controls
Variable Volume
Greenheck offers variable volume ventilation systems that track the cooking load and vary the exhaust
and supply ventilation based on demand. Since the cooking load varies throughout the day, your exhaust
system doesnt need to run at the maximum exhaust air volume all day. Greenheck understands that by
varying the speed of the fans based on the cooking load, you will save money by reducing power and
heating and cooling costs. See figures 1 and 2 below.
Standard Construction Features
The system monitors the cooking operation and adjusts the exhaust and supply unit fans so that when the
cooking load is reduced, the fans operate at a reduced level providing energy savings
Satisfies International Mechanical Code 507.2.1.1 requirement to start fans when cooking operationsoccur
System is prewired, UL Listed and includes wiring diagrams
Payback:
Typical payback of 1 to 3 years
Improved efficiency by reducing fan speed
Additional Benefits:
Ventilation equipment life is extended by soft-starting starting fans, therefore reducing stress on belts and
bearings
Reduced sound levels to improve customer and employee comfort
The charts below are an example of how the cooking load in a typical restaurant varies
throughout the day and how the variable volume system can generate money savings.
Constant Volume Design Airflow Variable Volume Matches Airflow to Cooking Load
100% 100%
$$$$$$$$$$$$$$$$$$$$
$$$$$$$$$$$$$$$$$$$$
80% 80%
$$$$$$$$$$$$$$$$$$$$
$$$$$$$$$$$$$$$$$$$$
$$$$$$$$$$ $$$$$$$ $
$ $ $ $$ $
60% 60% $ $$ $ $
CFM
CFM
Breakfast
Breakfast
40% 40%
Dinner
Dinner
Lunch
Lunch
20% 20%
0% 0%
6 7 8 9 10 11 12 1 2 3 4 5 6 7 8 9 10 11 6 7 8 9 10 11 12 1 2 3 4 5 6 7 8 9 10 11
Operating Hours Operating Hours
= Constant Volume = Variable Volume
Figure 1 The cooking load throughout the day varies Figure 2 A variable volume system will track the
significantly. However, the kitchen only requires maximum cooking load (dashed red line) and vary the exhaust and
ventilation for a small percentage of the day. The shaded supply ventilation. The area above the red line represents
area represents the savings potential for a variable energy savings.
volume system. The dashed red line is showing fan
operation at 100% regardless of cooking load.
5
Greenheck Controls
make-up air unit by sensing static pressure in the space, independent of the
exhaust fan speed, to ensure proper room pressurization at all times. Other SYSTEM
similar systems control the make-up air unit proportionally with the exhaust.
FAULT
However, when direct-fired gas make-up air units are requiring a constant 472621
pressure drop across the burner, this tracking will not follow the blower
curve, resulting in periods of imbalance.
5 Times Quicker Response Maintaining capture and containment of cooking effluent and heat is
important, so it is critical for the variable volume system to respond quickly. The Vari-Flow system is
designed with the temperature sensor in the capture tank versus in the duct collar where many other
systems detect heat. Greenhecks placement provides a response that is ready 5 times faster than a duct
mounted sensor for superior performance.
Fully Modulating Turndown up to 50% Idle cooking periods can realize up to 50 percent turndown
with the Vari-Flow Air Management System.
6
Greenheck Controls
Greenheck Melink
System Decision Matrix Vari-Flow Intelli-Hood
System System
7
Kitchen Ventilation Systems
August
ber
Octo 2011
2011
Febr
uary
2012
Our Warranty
Greenheck warrants this equipment to be free from defects in material and workmanship for a period
of one year from the shipment date. Any units or parts which prove defective during the warranty
period will be replaced at our option when returned to our factory, transportation prepaid. Motors are
warranted by the motor manufacturer for a period of one year. Should motors furnished by Greenheck
prove defective during this period, they should be returned to the nearest authorized motor service
station. Greenheck will not be responsible for any removal or installation costs.
Prepared to Support
As a result of our commitment to continuous improvement, Greenheck reserves the right to change Green Building Efforts
specifications without notice.
00.KIT.1001 R2 2-2012 IP
P.O. Box 410 Schofield, WI 54476-0410 Phone (715) 359-6171 greenheck.com Copyright 2012 Greenheck Fan Corp.
Engineered Kitchen Ventilation Systems
Grease Grabber Pollution Control Units
August
2011
Kitchen Ventilation Systems
We are your single source
for efficient, well-integrated
kitchen ventilation systems.
Kitchen Hoods
Industry-Leading Grease
Filtration
Exhaust Fans
2
Pollution Control
Even the best kitchen hood grease filters may need a little backup as no mechanical hood filter is 100% efficient
at removing all forms of grease.
Grease vapor and odors are not removed
Odors may cause neighbor complaints
Local ordinances/codes may require additional filtration and/or odor control
High efficiency filtration at the hood, like the Grease Grabber dual stage filtration system, is important. Capturing
a greater percentage of grease at the hood will significantly reduce pollution control unit maintenance costs. For
more information on Greenhecks hood filtration options, please refer to www.greenheck.com.
Feature Benefit
3
Grease Grabber Triple Play
The Grease Grabber Triple Play uses a 3-stage mechanical filter arrangement to clean grease
and smoke particles from the exhaust air at a low up front cost. Independent pressure switches
signal when any of the 3 filter stages need replacing, taking the guess work out of maintaining the
equipment. The Grease Grabber Triple Play incorporates activated carbon panels to remove odor
molecules prior to discharging the air, reducing the impact of kitchen exhaust to the surroundings.
4
Built in accordance with NFPA 96
B C D E
Dimensional Information
Max Air Inlet Unit Outlet
Model Height Width2 Unit Weight
Volume1 Transition3 Length Trans/Fan
GPBRC (inches) (inches) (pounds)
(cfm) (inches) (inches) (inches)
A B C D E
-10-10 2,000 34 26.3 18-26 98 52.3 1100
-10-20 4,000 34 50.0 18-26 98 57.8 1600
-10-30 6,000 34 73.7 18-26 98 71.5 2150
-20-20 8,000 58 50.0 18-26 98 72.0 2600
-20-30 12,000 58 73.7 18-26 98 77.8 3500
-20-40 16,000 58 97.4 18-26 98 99.1 4200
-30-30 18,000 82 73.7 18-26 98 78.0 4700
-30-40 24,000 82 97.4 18-26 98 84.1 5700
-40-40 32,000 109 97.4 18-26 98 98.4 7300
-40-50 40,000 109 121.5 18-26 98 104.4 8000
1 Maximum air volume is based on 500 ft/min air velocity across the precipitator
2 Lifting lugs for the unit add a nominal 4 inches to each side of the unit width
3 Actual dimension based on incoming duct dimension to ensure expansion angles do not exceed 45
The Grease Grabber Power Play electrostatic precipitator is the best available technology when it
comes to kitchen pollution control. It provides optimum performance with low operating costs. The
permanent electrostatic collector section removes grease and smoke particles from the airstream.
Additionally, the integrated self cleaning sequence, initiated by the system controls, readies the
Power Play to go to work again without the time and expense of replacing filters. The Power Play
incorporates activated carbon panels to remove odor molecules prior to discharging the air, reducing
5
Aluminum mesh pre-filter
2 4
removes large particles from
the incoming airstream prior 3
to reaching the ionizer cell. 2
1
SYSTEM START SYSTEM STAND BY NORMAL OPERATION to sequence the wash for the electrostatic
MANUAL WASH WASH IN PROGRESS
DETERGENT LOW
LEVEL
6
XX
Optional Items
MERV 17 HEPA filters available for efficiencies greater than 95%.
Potassium permanganate and other impregnates available for code compliance and/or
deal with specific odors.
Greenheck inline fan options available to fit specific needs.
Unit can be constructed in multiple sections for field assembly if required.
B C D E
Dimensional Information
Max Air Inlet Outlet
Model Height Width2 Unit Length Unit Weight
Volume1 Transition3 Trans/Fan
GSA (inches) (inches) (inches) (pounds)
(cfm) (inches) (inches)
A B C D E
-02-03 2,000 41 42.625 18-26 106.125 58.313 3100
-02-04 2,500 41 54.625 18-26 106.125 65.313 3620
-02-05 3,500 41 65.375 18-26 106.125 65.313 4025
-02-06 4,000 41 77.375 18-26 106.125 67.313 4280
-04-04 5,500 65 54.625 18-26 106.125 76.188 4580
-04-05 6,500 65 65.375 18-26 106.125 78.313 5200
-04-06 8,000 65 77.375 18-26 106.125 83.313 5700
-04-07 9,000 65 89.063 18-26 106.125 83.313 6420
-04-08 10,500 65 101.063 18-26 106.125 96.876 7080
-04-09 12,000 65 112.750 18-26 106.125 101.375 7560
-06-08 16,000 88.875 101.063 18-26 106.125 103.313 8800
-06-09 18,000 88.875 112.750 18-26 106.125 103.313 9570
1 Maximum air volume is based on 350 ft/min air velocity across the precipitator
2 Lifting lugs for the unit add a nominal 4 inches to each side of the unit width
3 Actual dimension based on incoming duct dimension to ensure expansion angles do not exceed 45
En
s ion gin
em act Gr ee
yst xtr
ea red
se
n S se E Gr
ab Kit
ch
tio rea s be en
tila & G stem
r
n Po Ve
Ve ods Sy llu
tio
ntil
atio
en Ho ion nC
ch us t
es
s on nS
Kit xha uppr s
tro yst
lU em
E nit
Fire S sorie s s
s
Acce
ber
tem 09
Sep 0
2
Ju
201 ly
1
Our Warranty
Greenheck warrants this equipment to be free from defects in material and workmanship for a period
of one year from the shipment date. Any units or parts which prove defective during the warranty
period will be replaced at our option when returned to our factory, transportation prepaid. Motors are
warranted by the motor manufacturer for a period of one year. Should motors furnished by Greenheck
prove defective during this period, they should be returned to the nearest authorized motor service
station. Greenheck will not be responsible for any removal or installation costs.
Prepared to Support
As a result of our commitment to continuous improvement, Greenheck reserves the right to change Green Building Efforts
00.KIT.1012 R1 8-2011 SN
P.O. Box 410 Schofield, WI 54476-0410 Phone (715) 359-6171 greenheck.com Copyright 2011 Greenheck Fan Corp.
Utility Distribution System
UDS Model M
t'MFYJCMFt$POWFOJFOUt&DPOPNJDBM
October
2012
Why buy a Greenheck
FlexConnect UDS
FlexConnect Utility
Distribution System
A pre-engineered delivery system for the
cooking equipments utilities. It eliminates
custom designed contractor built walls to bring
the utilities to the cooking appliances. To build a
contractor wall:
t &OHJOFFSTBOEDPOTVMUBOUTIBWFUPXPSL
together to design the utilities into the wall,
dependent on the cooking line-up.
t 1MVNCJOH
FMFDUSJDBMBOEHFOFSBMDPOUSBDUPST
all have to work together to install the utility
wall.
Custom built utility walls are built for a
specific cooking line-up and require hours of
coordination to be built in the field. If that line-up
changes, the electrical and plumbing have to be
changed to accommodate for the new line-up.
With FlexConnect, just send Greenheck the
cooking equipment utility information and you
will receive the flexibility your kitchen deserves.
Flexibility - Plumbing
t 8JUI'MFY$POOFDU
(SFFOIFDLQSPWJEFTJODI
IPUBOEDPMEXBUFSESPQTFWFSZJODIFT
BOE
BMUFSOBUJOHBOEJODIHBTESPQTFWFSZ
JODIFT5IFPXOFSNJHIUOPUOFFEBMMPGUIFTF
ESPQTJNNFEJBUFMZ
CVUJGDIBOHFTUPUIFDPPLJOH
MJOFBSFNBEFEVFUPNFOVPSTUBGGQSFGFSFODFT
'MFY$POOFDUIBTUIFFYUSBVUJMJUZESPQTEFTJHOFE
JOUPUIFTZTUFN5IJTCVJMUJOGMFYJCJMJUZBMMPXTZPV
UPDIBOHFFRVJQNFOUBTOFFEFEUISPVHIPVUUIF (BT%SPQT
SFTUBVSBOUTMJGFXJUIPVUDPTUMZSFQJQJOHDIBSHFT
.PWFFRVJQNFOUBTOFFEFE
BOZUJNF
BOZXIFSF )PU$PME8BUFS
XJUIPVUUIFIFBEBDIF
%SPQT
4JODFQMVNCJOHJTEJGGJDVMUUPEPJOUIFGJFMEBOE
FMFDUSJDBMDPNQBSBUJWFMZFBTZ
UIF#BTF6%4PS
3FDFQUBDMF0OMZXJMMCFUIFNPTUFDPOPNJDBMBOE
GVODUJPOBM5IFNBKPSJUZPGUIFQMVNCJOHXJMMCF
GBDUPSZJOTUBMMFEBOEUIFSFJTBEFRVBUFSPPNGPSUIF
FMFDUSJDJBOUPSVOXJSJOHGSPNSFDFQUBDMFTUPSFNPUF
CSFBLFSTUPTJNQMJGZDPOUSPMDJSDVJUXJSJOH
With a contractor built wall, changes to the cooking
line become cost prohibitive and difficult with wall
penetrations and multiple trade involvement.
2
Convenience Clean
t8JUI'MFY$POOFDUEJTDPOOFDUTBOE t 'MFY$POOFDUJTNBOVGBDUVSFEPG
PVUMFUTBMMPXUIFDPPLJOHFRVJQNFOUUPCF HBVHF4FSJFTTUBJOMFTTTUFFMUP
FBTJMZNPWFEGPSDMFBOVQBOEJOTQFDUJPOT QSPWJEFZPVXJUITVQFSJPSTUSFOHUI
$POWFOJFODFEVQMFYPVUMFUTBSFQMBDFE With a contractor built wall typically
JOFWFSZSJTFS
QSPWJEJOHZPVXJUIUIF being built out of drywall and wood
GMFYJCJMJUZUPVTFPUIFSFMFDUSJDBMFRVJQNFOU studs, moisture can cause health risks
With a contractor built wall, outlets are in the kitchen.
often inaccessible, and utility outlets are
difficult to clean around, often trapping
dirt and grease.
Tax Benefit
t"6%4JTDMBTTJGJFEBTBLJUDIFO
BQQMJBODFXJUIBZFBSEFQSFDJBUJPOMJGF
A contractor built wall has a
depreciation life of 31 years.
Codes
t6%4TZTUFNTIBWFCFFOQSFUFTUFE
BOEBQQSPWFEBTBDPEFDPNQMJBOU
BQQMJBODF*OTUBMMBUJPOBOEJOTQFDUJPO
BSFRVJDLMZDPNQMFUFE
A contractor built wall must be
inspected and approved by the
appropriate code authorities, often
resulting in delays and changes.
Drop Quantity
(SFFOIFDLEFTJHOFEJUT'MFY$POOFDU6%4XJUIUPPNBOZESPQT5IFFYUSBESPQTBSFUIFSFJODBTFFRVJQNFOU
JTDIBOHFEPSNPWFEQSPWJEJOHZPVXJUINPSFUIBOFOPVHIXBUFSBOEPSHBTGPSBOZFRVJQNFOUMJOFVQ
5IFTFFYUSBESPQTSFEVDFUIFBNPVOUPGGBDUPSZMBCPSUIVTSFEVDJOHUIFFOEDPTUUPUIFDVTUPNFS
Relocation
t5IF6%4JTDPOTJEFSFEBQJFDFPGFRVJQNFOUUIFSFGPSFXIFOUIFDVTUPNFSTMFBTFIBT
FOEFE
UIF6%4DBOCFSFNPWFEGSPNUIFQSFNJTFTGPSVTFJOBOPUIFSMPDBUJPO
A contractor built wall is a leasehold improvement. If a move is made to another
location, another wall must be built.
Construction
Features
BOEJODIFTBCPWFUIFGMPPS$IBTF
GAS
TFDUJPOTBSFBWBJMBCMFJOJODI EVE
JODSFNFOUTGUUISVGU DPNCJOF 3/4" & 1
UIFNUPNBLFMPOHFSMFOHUIT
Utility RiserGPSJODPNJOHGJFME
2
DPOOFDUJPOTUPQMVNCJOHBOE
FMFDUSJDBM3JTFSTBSFJODIFTXJEF
SJTFSIFJHIUJTGUJOUPGUUBMM 2
XJUIBEKVTUBCMFDPMMBS T
1
Removable PanelsBMMPXTBDDFTT
3 9
UPJOUFSOBM6%4DPNQPOFOUT
Bumper GuardsSVOOJOHUIFGVMM
4 MFOHUI
QSPUFDUUIF6%4BOE 7
BQQMJBODFTGSPNEBNBHFBT
BQQMJBODFTBSFNPWFEGPSDMFBOJOH
10
Code Information
(SFFOIFDL6UJMJUZ%JTUSJCVUJPO4ZTUFNUPCF6--JTUFE
BOECVJMUJODPNQMJBODFXJUIBMMBQQMJDBCMFDPEFTBOE
TUBOEBSET
JODMVEJOH/4'
/'1"
/&$
/&."
6OJGPSN1MVNCJOH$PEF
"4.&
VTJOHPOMZ6--JTUFE
PSSFDPHOJ[FEDPNQPOFOUT
Panel Board Breaker System
Electrical Option
Main Service
Disconnect Switch
MAIN 120/208/3ph.
H C H C H C
SINGLE LINE 17.
18.
19.
BLANK PLATE(S)
FOR OTHER CONTROLS
20 AMP 120V
RECEPTACLE
3
BOTH ENDS
7 Pipe ManifoldsUPEJTUSJCVUF
HBT
IPUBOEDPMEXBUFS(BT
QJQFJT
PSJODIFT
CBTFEPOTFSWJDFSFRVJSFNFOUT
8 IPUBOEDPMEXBUFSQJQFBSF
JODI
Greenhecks FlexConnect utility distribution systems (UDS) are available in four different options; base,
PQUJPOBMSFDFQUBDMFTPOMZ 3FNPUFCSFBLFS
PQUJPOBMDPNQMFUFXJSJOH 1PJOUPGVTFCSFBLFSTPS1BOFM#PBSE
and custom units. Our base and option packages allow for faster leadtimes and better pricing, while our custom
program still allows us to meet any customer demand.
Base 5IFBase'MFY$POOFDU6%4IBTUIFTIPSUFTUMFBEUJNFBOEJTUIFNPTUGMFYJCMF
FlexConnect UDS 1MVNCJOHTFSWJDFTBSFMPDBUFEJOUIFDIBTFBOEJODMVEFHBT
IPUBOEDPMEXBUFS
ESPQT8JUIUIFCBTFQBDLBHFBQQMJBODFJOGPSNBUJPOJTOPUOFFEFE
5IFTZTUFNIBTBNBJO
PSJODIHBTMJOFCBTFEPOTFSWJDFSFRVJSFNFOUT
XJUIBQQMJBODFESPQTMPDBUFEFWFSZJODIFT5IFTFESPQTBSFDBQQFEPOUIF
CPUUPN)PUBOEDPMEXBUFSQJQJOHJTPSJODIFTJOEJBNFUFSBOEIBTBQQMJBODF
ESPQTFWFSZJODIFTUIBUBSFDBQQFEPOUIFCPUUPN-JHIUBOEGBOTXJUDIFTBOE
('$*SFDFQUBDMFTJOCPUISJTFSTBSFBMTPQSPWJEFE
#MBOLSFDFQUBDMFQMBUFTBSFQSPWJEFEPOUIFSBDFXBZ3FDFQUBDMFTBOEXJSJOHNVTU
CFQSPWJEFECZPUIFST5IFTFQMBUFTDBOCFVTFEUPNPVOUUIFSFDFQUBDMFT
5IF#BTF'MFY$POOFDU6%4JTBHPPEVOJUGPSUIFPXOFSUIBUJTMPPLJOHGPSBDMFBO
GJOJTIFEMPPLJOHVUJMJUZ
DIBTF)PXFWFSUIF#BTFVOJUEPFTOPUIBWFUIFFMFDUSJDBMSFRVJSFNFOUTPGUIFLJUDIFO5IFFMFDUSJDBMDPOUSBDUPS
NVTUXJSFUIFVOJUBDDPSEJOHUPUIFFRVJQNFOUTFMFDUSJDBMOFFET
*GZPVDIPTFB#BTF6%4XFOFFEUPLOPXUIFGPMMPXJOHUPQSPQFSMZTJ[FUIFVOJUGPSZPVSBQQMJDBUJPOMFOHUIPG
UIFVOJU
IPPEIBOHJOHIFJHIU
BOEUIFUZQFPGVOJU XBMMPSJTMBOE
Optional Equipment
t 'MFYJCMFRVJDL t 1SFTTVSFHBVHFT
EJTDPOOFDUIPTFT GPSXBUFSMJOFT
FBTJMZDPOOFDUTBOE TIPX14*PGXBUFS
EJTDPOOFDUTUIF JOUIFNBJOMJOF
BQQMJBODFTUPUIF6%4
t 2VBSUFSUVSOCBMMWBMWFTBOE t$PSEBOEQMVH
GJUUJOHTTIVUPGGGPSHBTBOE BTTFNCMJFT
IPUBOEDPMEXBUFSUPFBDI FMFDUSJDBMPQUJPO
BQQMJBODF QPJOUPGVTF
"WBJMBCMF4J[FT QBOFMCPBSEPS
SFDFQUBDMFPOMZ
GPS
JO
JO
RVJDLEJTDPOOFDUPG
JO JO NBJOWBMWF
FMFDUSJDBQQMJBODFT
t 4XJWFMGJUUJOHTLFFQTUIF t $BCMFSFTUSBJOUT
IPTFGSPNLJOLJOHBOE PONPCJMFHBT
UXJTUJOH BQQMJBODFT
TBGFUZGFBUVSF
UIBUQSFWFOUT
UIFFRVJQNFOU
GSPNNPWJOHBOE
EJTDPOOFDUJOHUIF
HBTMJOF
t 'JMMGBVDFUNPVOUJOH
CSBDLFU T
GBVDFUQSPWJEFE
CZPUIFSTBMMPXTGPSQPU
GJMMFSUPCFNPVOUFEPOUIF
6%4
&NFSHFODZ4IVU0GG7BMWFT
t *OTUBMMFEWBMWFTBOEEJTDPOOFDUTPOQMVNCJOHESPQT
t 1SJTPOQBDLBHF
t %PPSMBUDIFTJOQMBDFPGTDSFXTPONBJOSJTFS T
Application and Specification
1SPWJEF(SFFOIFDL'MFY$POOFDU6%4.PEFM.BTTIPXOPOQMBOTBOEJOBDDPSEBODFXJUI
UIFGPMMPXJOHTQFDJmDBUJPO
5IF'MFY$POOFDU6UJMJUZ%JTUSJCVUJPO4ZTUFN 6%4
NPEFM.TIBMMCFFJUIFSJTMBOEPSXBMM
UZQF4FSWJDFSJTFSTBOEIPSJ[POUBMSBDFXBZXJUISFNPWBCMFBDDFTTQBOFMTUPCFDPOTUSVDUFE
PGHBVHFUZQF4FSJFTTUBJOMFTTTUFFM5IFTFSWJDFSJTFSTXJMMCFBCMFUPBDDPNNPEBUF
CPUIFMFDUSJDBMBOEPSQMVNCJOH5IFIPSJ[POUBMSBDFXBZXJMMCFEJWJEFEJOUPTFQBSBUF
DPNQBSUNFOUTGPSQMVNCJOHBOEFMFDUSJDBM'MBOHFEGPPUQFEFTUBMTBSFQSPWJEFEBUFBDImFME
KPJOUPOUIFIPSJ[POUBMDIBTFXIFOUIFVOJUJTGUJODIFTPSMPOHFS
Plumbing:5IFIPSJ[POUBMQMVNCJOHDPNQBSUNFOUJTUPJODMVEFNBOJGPMETGPSHBT
IPUXBUFS
BOE
DPMEXBUFS5IF
PSJODIHBTNBOJGPME TJOHMFPSMPPQFE
XJMMJODMVEFXFMEFEUISFBEPMFU
DPOOFDUJPOT 5IF HBT DPOOFDUJPOT BSF TQBDFE JODIFT BQBSU BOE BSF BMUFSOBUFMZ TJ[FE BT
BOEJODIFTFWFSZPUIFSDPOOFDUJPO5IFJODIIPUBOEDPMEXBUFSNBOJGPMETXJMMJODMVEF
JODIQMVNCJOHESPQTFWFSZJODIFTBMPOHUIFIPSJ[POUBMSBDFXBZ"MMQMVNCJOHESPQTBSF
DBQQFECFMPXUIFDIBTF
SFBEZGPSFBTZDPOOFDUJPOUPBOZDPPLJOHBQQMJBODF0QUJPOBMHBT
NBOJGPMEJTTVQQMJFEXJUI
JODINFDIBOJDBMFNFSHFODZTIVUPGGHBTWBMWF
TIJQQFEMPPTF
Electrical:5IFCBTFFMFDUSJDBMQBDLBHFTIBMMJODMVEFBDPWFSFEQIBNQDPOWFOJFODF
PVUMFUMPDBUFEPOUIFFOEPGFBDITFSWJDFSJTFS5IFVOJUXJMMIBWFMJHIUBOEGBOUPHHMFTXJUDIFT
MPDBUFEPOUIFFOEPGPOFTFSWJDFSJTFS5IFTUBOEBSEIPSJ[POUBMDIBTFFMFDUSJDBMDPNQBSUNFOU
JODMVEFTTQBDFGPSXJSJOHBOEFRVJQNFOUSFDFQUBDMFT"MMSFDFQUBDMFTBOEXJSJOHDPOEVJUJTQSPWJEFE
CZPUIFST
Optional Electrical Package Receptacles Only:3FNPUF.PVOUFE#SFBLFS1BOFMGPS"QQMJBODF
3FDFQUBDMFTTIBMMJODMVEFBDPWFSFEQIBNQDPOWFOJFODFPVUMFUMPDBUFEPOFBDITFSWJDF
SJTFS5IFVOJUXJMMIBWFMJHIUBOEGBOUPHHMFTXJUDIFTMPDBUFEPOPOFPGUIFTFSWJDFUPXFST5IF
IPSJ[POUBMDIBTFFMFDUSJDBMDPNQBSUNFOUJODMVEFTFRVJQNFOUSFDFQUBDMFT"MMXJSJOHDPOEVJUJT
QSPWJEFECZPUIFST&RVJQNFOUSFDFQUBDMFTUPCFQMBDFEJOUIFTQFDJmFEMPDBUJPOVOEFSUIFIPSJ[POUBM
DIBTFCZPUIFST
Optional Electrical Package - Point-of-use or Panelboard:*OUFSOBM4FSWJDF1BOFMGPS"QQMJBODF
3FDFQUBDMFTTIBMMJODMVEFBOJODPNJOHFMFDUSJDBMTFSWJDFSJTFSPOUIFSJHIUFOEXJUIBBNQNBJO
TIVOUUSJQCSFBLFS5IFVOJUXJMMIBWFJOEJWJEVBMCSBODICSFBLFS T
GPSFBDIFRVJQNFOUSFDFQUBDMF
MPDBUFEFJUIFSPOUIFTFSWJDFSJTFSPSIPSJ[POUBMDIBTFEJSFDUMZJOMJOFXJUIUIFFRVJQNFOUSFDFQUBDMF
5IFVOJUXJMMIBWFMJHIUBOEGBOUPHHMFDPOUSPMTXJUDIFTMPDBUFEPOUIFFOEPGUIFFMFDUSJDBMTFSWJDFSJTFS
BOEBDPWFSFEQIBNQDPOWFOJFODFPVUMFUPOCPUITFSWJDFSJTFSFOET&RVJQNFOUSFDFQUBDMFT
BSFGBTUFOFEJOUIFTQFDJmFEMPDBUJPOVOEFSUIFIPSJ[POUBMDIBTF
Our Commitment
As a result of our commitment to continuous improvement, Greenheck reserves the right to change
specifications without notice.
Specific Greenheck product warranties are located on greenheck.com within the
product area tabs and in the Library under Warranties.
1SFQBSFEUP4VQQPSU
(SFFO#VJMEJOH&GGPSUT
00.KIT.1009 R4 10-2012 RG
10#PYt4DIPGJFME
8*t1IPOF
tHSFFOIFDLDPN Copyright 2012 Greenheck Fan Corp.