Proposed Addendum h to
Standard 62.1-2010, Ventilation for
Acceptable Indoor Air Quality
Second Public Review (February 2012)
(Draft shows Proposed Changes to Current Standard)
This draft has been recommended for public review by the responsible project committee. To submit a comment on this
proposed standard, go to the ASHRAE website at www.ashrae.org/standards-research--technology/public-review-drafts and
access the online comment database. The draft is subject to modification until it is approved for publication by the Board of
Directors and ANSI. Until this time, the current edition of the standard (as modified by any published addenda on the ASHRAE
website) remains in effect. The current edition of any standard may be purchased from the ASHRAE Online Store at
www.ashrae.org/bookstore or by calling 404-636-8400 or 1-800-727-4723 (for orders in the U.S. or Canada).
This standard is under continuous maintenance. To propose a change to the current standard, use the change submittal form
available on the ASHRAE website, www.ashrae.org.
The appearance of any technical data or editorial material in this public review document does not constitute endorsement,
warranty, or guaranty by ASHRAE of any product, service, process, procedure, or design, and ASHRAE expressly disclaims
such.
© 2012 ASHRAE. This draft is covered under ASHRAE copyright. Permission to reproduce or redistribute all or any part of this
document must be obtained from the ASHRAE Manager of Standards, 1791 Tullie Circle, NE, Atlanta, GA 30329. Phone: 404-
636-8400, Ext. 1125. Fax: 404-321-5478. E-mail: standards.section@ashrae.org.
(This foreword is not part of this standard. It is merely informative and does not contain requirements
necessary for conformance to the standard. It has not been processed according to the ANSI requirements
for a standard and may contain material that has not been subject to public review or a consensus process.
Unresolved objectors on informative material are not offered the right to appeal at ASHRAE or ANSI.)
FOREWORD
Standard 62.1-2010, Table 6-1, includes ventilation rates for “Sports arena (play area)” and “Gym, stadium
(play area).” Both space types have ventilation rates based on floor area only, the per person rate is zero. Users
of the standard have expressed interest in applying demand controlled ventilation to these space types, which is
effectively prohibited by the lack of a per person component to the ventilation rate. This proposed addendum
replaces both of these space types with “Gym, Sports Arena (play area)”, with Rp = 20 cfm/person and Ra = 0.18
cfm/ft².
The second public review version of the addendum assigns this new space type with an air class of 2 rather than
class 1 from the first publication public review version, and increased Ra from 0.06 cfm/ft² to 0.18 cfm/ft².
One concern about allowing CO2-based demand controlled ventilation in these spaces is that the volume per
person in these spaces is typically large, which means that CO2 concentration changes will have longer than
usual lag times behind occupancy changes.
[Note to Reviewers: This addendum makes proposed changes to the current standard. These changes are
indicated in the text by underlining (for additions) and strikethrough (for deletions) except where the reviewer
instructions specifically describe some other means of showing the changes. Only these changes to the current
standard are open for review and comment at this time. Additional material is provided for context only and is
not open for comment except as it relates to the proposed changes.]
Addendum h to 62.1-2010
Revise Table 6-1 as follows: (The rest of Table 6-1 remains unchanged.)
Default Values
People Outdoor Area Outdoor
Air Rate Air Rate Occupant
Combined Outdoor Air
Rp Ra Density Air
Occupancy Category Notes Rate (see Note 5)
(see Note 4) Class
cfm/pers #/1000 ft2 or
L/s•person cfm/ft2 L/s•m2 cfm/person L/s·person
on #/100 m2