Presentation outline
Introduction on proposed research topic
Progress in the current semester
Overview
Types of earthing system;
functional earthing system, specific to sensitive
ground.
protective earthing refers to bonding of all
Introduction contd.
Substation Earthing;
The substation earthing system is necessary for
connecting neutral points of transformers and
generators to ground.
For connecting the non-current carrying metal parts
such as structures, overhead shielding wires, tanks,
frames, etc. to ground.
Introduction contd.
The substation earthing system provides a
grounding mat below the earth surface in and
around the substation.
Provides uniform zero potential with respect to
ground and lower earth resistance.
Introduction contd.
Substations are basically classified based on,
1. Voltage level, e.g. A.C Substation: EHV, HV, MV, LV or,
HVDC Substation
2. Indoor or Outdoor, Indoor substations are sited within
buildings, while Outdoor Substations are under the
open
sky.
3. Configuration, conventional air insulated out door,
SF6 Gas
4. Application,
Step Up Substation; associated with generating stations.
step up voltages from 16-25kV to EHV or HV.
Primary grid Substation; installed at suitable load centre
along the primary transmission line. Receive power from
EHV lines at 400kV, 220kV, 132kV and transform to
66kV, 33kV or 22kV.
Secondary Substation; installed along secondary
transmission line, working voltages 66/33kV further
stepped down to 11kV.
Separated/isolated earthing
It is reported in IEEE Std. 142:2007 that,
The power earthing system has been found to cause
malfunctions and failures of electronic equipment.
A logical solution was not to use the equipment
earthing system for grounding electronic equipments.
The chosen alternative was to earth electronic
equipment through an isolated earthing electrode
consisting of one or more driven rods separate from
the power system earthing electrode system.
Separated/isolated contd.
Separated/isolated contd.
Analysis indicated that, separation of earthing was
responsible for very large voltages being impressed
on
electronic
equipment
components
under
thunderstorm conditions.
These voltages occurred whether or not electronic
equipment were in operation.
The large voltages were due to lightning striking
either the building housing the electronic equipment
or the power system serving the building.
Integration contd.
A serious hazard that may result from an integrated
earthing system is the transfer of potential between
the substation ground grid area and outside locations
during a ground fault.
This transferred potential may be transmitted by
communication circuits, conduit, pipes, metallic
fences, low-voltage neutral wires, etc.
Potentials may also be transferred by coupling.
Proposed Study
Response of Separated Grounding Systems Under Low
Frequency and Transient Conditions
To be studied under,
Different soil conditions
Different equipment conditions,
Power system substation
Communication tower
Study contd.
Methodology of study
Simulation using ATP-EMTP software
CDEGS software/resistivity measurement
Experiment using scale model
A formal proposal is in writing process and would be
presented to my supervisory committee soon.