Omron JX Quick Start Guide
Omron JX Quick Start Guide
Omron JX Quick Start Guide
I128E-EN-01
JX
Notice:
OMRON products are manufactured for use according to proper procedures
by a qualified operator and only for the purposes described in this manual.
The following conventions are used to indicate and classify precautions in this
manual. Always heed the information provided with them. Failure to heed precautions can result in injury to people or damage to property.
OMRON, 2012
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form, or
by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permission of
OMRON.
No patent liability is assumed with respect to the use of the information contained herein. Moreover, because OMRON is constantly striving to improve its high-quality products, the information contained in this manual is subject to change without
notice. Every precaution has been taken in the preparation of this manual. Nevertheless, OMRON assumes no responsibility
for errors or omissions. Neither is any liability assumed for damages resulting from the use of the information contained in
this publication.
2 INSTALLATION..................................................................................... 5
2.1
2.2
2.3
2.4
2.5
2.6
2.7
5
5
6
7
7
8
9
3 PROGRAMMING JX ........................................................................... 10
3.1 Digital operator..................................................................................................................
3.2 Keypad navigation .............................................................................................................
3.3 Parameter initialization.....................................................................................................
3.4 Basic settings ......................................................................................................................
3.5 Ramps adjustment .............................................................................................................
3.6 DC injection braking..........................................................................................................
3.7 V/F curve............................................................................................................................
3.8 Torque boost function ........................................................................................................
3.9 Digital inputs......................................................................................................................
3.10 Digital outputs .................................................................................................................
3.11 Analog inputs ...................................................................................................................
3.12 Analog output AM terminal............................................................................................
3.13 Electronic thermal function.............................................................................................
3.14 Carrier frequency.............................................................................................................
3.15 PID function.....................................................................................................................
3.16 Overload limit/warning ...................................................................................................
3.17 Overvoltage control function ...........................................................................................
3.18 Controlled stop at power loss...........................................................................................
10
11
12
12
13
14
15
16
17
19
19
20
21
22
22
23
23
24
25
25
27
29
30
30
Inspect the driver for damage. If the drive appear damage upon receipt, contact your supplier.
Verify the receipt of the correct model by checking the information on the nameplate. If you have received the wrong model contact your
supplier.
Refer to the Users Manual for detailed information about the product and functions.
1 x 200 V
3 x 200 V
3 x 400 V
Type
3G3JX-
AB002
0.2
1.4
AB004
0.4
2.6
AB007
0.75
4.0
AB015
1.5
7.1
AB022
2.2
10.0
A2002
0.2
1.4
A2004
0.4
2.6
A2007
0.75
4.0
A2015
1.5
7.1
A2022
2.2
10.0
A2037
3.7
15.9
A2055
5.5
24.0
A2075
7.5
32.0
A4004
0.4
1.5
A4007
0.75
2.5
A4015
1.5
3.8
A4022
2.2
5.5
A4040
4.0
8.6
A4055
5.5
13.0
A4075
7.5
16.0
EMC filter
AX-FIJ1006-RE
AX-FIJ1010-RE
AX-FIJ1026-RE
AX-FIJ2006-RE
AX-FIJ2020-RE
AX-FIJ2040-RE
AX-FIJ3005-RE
AX-FIJ3011-RE
AX-FIJ3020-RE
Output
characteristics
200 V
240 V
AB002
A2002
0.2
0.4
0.5
1.4
AB004
A2004
0.4
0.9
1.0
2.6
3.1
1.8
5.8
3.4
Built-in filter
Braking torque
At short-time deceleration
At capacitor feedback
Cooling method
Approx. 50%
AB007
AB015
AB022
A2007
A2015
A2022
A2037
0.75
1.5
2.2
3.7
1.3
2.4
3.4
5.5
1.6
2.9
4.1
6.6
4.0
7.1
10.0
15.9
Proportional to input voltage: 0 to 240 V
400 Hz
Single-phase 200 to 240 V 50/60 Hz
Three-phase 200 to 240 V 50/60 Hz
9.0
16.0
22.5
5.2
9.3
13.0
20.0
-15% to +10%
+5%
EMC filter (C1 single phase)
50% for
3-phase
Approx. 20% to 40%
20 to 40% for
A2055
5.5
8.3
9.9
24.0
A2075
7.5
11.0
13.3
32.0
30.0
40.0
Approx. 20%
1-phase
Self cooling
Forced-air-cooling
SPECIFICATIONS
Motor (kW)
Power supply
A4004
0.4
0.9
1.2
1.5
A4007
0.75
1.6
2.0
2.5
2.0
3.3
Built-in filter
Braking torque
At short-time deceleration
At capacitor feedback
Cooling method
Approx. 50%
Self cooling
A4015
A4022
A4040
1.5
2.2
4.0
2.5
3.6
5.6
3.1
4.5
7.1
3.8
5.5
8.6
Proportional to input voltage: 0 to 480 V
400 Hz
3-phase 380 to 480 V 50/60 Hz
5.0
7.0
11.0
-15% to +10%
+5%
EMC filter C2 class
Approx. 20% to 40%
A4055
5.5
8.5
10.8
13.0
A4075
7.5
10.5
13.3
16.0
16.5
20.0
Approx. 20%
Forced-air-cooling
Control functions
Functionality
Input signals
Output signals
Standard functions
Analogue inputs
Accel/Decel times
Ambient conditions
Protection functions
Display
Specifications
Phase-to-phase sinusoidal modulation PWM (V/F)
0.5 to 400 Hz
Digital set value: 0.01% of the max. frequency
Analogue set value: 0.4% of the max. frequency (25 10 C)
Digital set value: 0.1 Hz
Analogue set value: 1/1000 of maximum frequency
0.1Hz
150% rated output current for one minute
0 to 10 VDC (10 k), 4 to 20 mA (250 ), frequency setting volume (selectable), RS485 Modbus
Constant/reduced torque
FW (forward), RW (reverse), CF1 to CF4 (multi-step speed), JG (jogging), DB (external DC injection braking), SET (2nd function), 2CH
(2-step acceleration/deceleration), FRS (free run), EXT (external trip), USP (USP function), SFT (soft lock), AT (analog current input
function selection), RS (reset), PTC (thermistor input), STA (3-wire startup), STP (3-wire stop), F/R (3-wire forward/reverse), PID (PID
selection), PIDC (PID integral reset), UP (UP of UP/DWN function), DWN (DWN of UP/DWN function), UDC (data clear of UP/DWN
function), OPE (forced OPE mode), ADD (frequency addition), F-TM (forced terminal block), RDY (operation ready), SP-SET (special
setting), EMR (emergency shutoff)
RUN (signal during operation), FA1 (frequency arrival signal 1), FA2 (frequency arrival signal 2), OL (overload warning signal), OD (PID
excess deviation signal), AL (alarm signal), DC (analog input disconnection detection signal), FBV (PID FB status output), NDc (network
error), LOG (logical operation result), ODc (communication option disconnected), LOC (light load signal)
AVR function, V/F characteristics selection, upper/lower limit, 16-step speeds, starting frequency adjustment, jogging operation, carrier
frequency adjustment, PID control, frequency jump, analog gain/bias adjustment, S-shape acceleration/deceleration, electronic thermal
characteristics/level adjustment, retry function, simplified torque boost, trip monitor, soft lock function, frequency conversion display,
USP function, 2nd control function, motor rotation speed UP/DWN, overcurrent suppression function.
2 analogue inputs 0 to 10 V (20 k), 4 to 20 mA (250 )
0.01 to 3600.0 s (line/curve selection), 2nd accel/decel setting available
Status indicator LEDs Run, Program, Power, Alarm, Hz, Amps, Volume Led indicator
Digital operator: Available to monitor frequency reference, output current, output frequency
Electronic Thermal overload relay and PTC thermistor input
180% of rated current
150% for 1 minute
790 V for 400 V type and 395 V for 200 V type
Following items are selectable: alarm, 0 Hz start, frequency output at interruption, maximum frequency
Temperature monitor and error detection
Selectable level applicable only at constant speed or during acceleration and constant speed
Detected at power-on
On when power is supplied to the control part
IP20
90% RH or less (without condensation)
-20C to +65C (short-term temperature during transportation)
-10C to 50C (both the carrier frequency and output current need to be reduced at over 40C)
Indoor (no corrosive gas, dust, etc.)
Max. 1000 m
5.9 m/s2 (0.6 G), 10 to 55 Hz (complies with the test method specified in JIS C0040 (1999).)
INSTALLATION
2 INSTALLATION
2.1 Wiring sizes and protection
Motor output (kW)
0.2
A2002
Wiring
Power cable (mm )
1.25
5A
A2004
0.4
Applicable device
2
1.25
5A
A2007
2.0
10 A
A4007
1.25
5A
6A
A2015
2.0
15 A
15 A
A4015
2.0
10 A
10 A
A2022
2.0
20 A
20 A
A4022
2.0
10 A
10 A
A2037
3.5
30 A
30 A
A4040
2.0
15 A
15 A
A2055
5.5
50 A
40 A
A4055
3.5
30 A
20 A
A2075
8.0
60 A
50 A
A4075
3.5
30 A
25 A
0.2
AB002
2.0
5A
14 A
0.4
AB004
2.0
5A
0.75
AB007
2.0
10 A
1.5
AB015
5.5
15 A
2.2
AB022
5.5
20 A
A4004
0.75
1.5
2.2
3.7
5.5
7.5
3A
15 A
Fig ure 2
W
W1
5
6
W
W1
5
6
H1
H
H1
H
t1
5
Voltage class
Single-phase
200 V
Three-phase
200 V
Max. applicable
motor output kW
0.2
0.4
0.75
1.5
2.2
0.2
0.4
0.75
1.5
2.2
3.7
5.5
7.5
D1
1.9
t1
D1
1.9
Figure
W1
H1
67
143
80
98
176
110
Dimensions in mm
H
D
95.5
155
109.5
130.5
189
157.5
t1
2.6
D1
13
27
28
55
2.6
13
27
50
67
143
80
155
95.5
109.5
132.5
98
176
110
189
157.5
55
164
235
180
250
167.5
1.6
77.5
Weight (kg)
0.8
0.9
1.5
2.3
2.4
0.8
0.9
1.1
2.2
2.4
4.2
INSTALLATION
Voltage class
Three-phase
400 V
Max. applicable
motor output kW
0.4
0.75
1.5
2.2
4.0
5.5
7.5
Figure
A4004
A4007
A4015
A4022
A4040
A4055
A4075
W1
H1
Dimensions in mm
H
D
130.5
98
176
110
189
164
235
180
250
t1
2.6
D1
28
157.5
55
167.5
1.6
77.5
Weight (kg)
1.5
2.3
2.4
4.2
INSTALLATION
10 cm min.
Airflow
Wall
5 cm min.
5 cm min.
10 cm min.
You can install multiple 3G3JX inverters side by side in the control panel (side-by-side installation). Again, keep the ambient
temperature within the specified range (40C or below).
If the ambient temperature is from 40C through to 50C, the carrier frequency should be reduced and the inverter capacity
should be increased.
INSTALLATION
Inverter
R (L1)
U/T1
S (L2)
V/T2
T/N (L3)
W/T3
Note:
To connect the DC reactor,
remove the short-circuit bar.
P24
4.7 k
Motor
PD/+1
DC reactor
4
P/+
3
2
1
N/PCS
AL1
L
AL2
AL0
Frequency
meter
Relay output
Common
AM
11
10 VDC
H
Frequency
setting unit
1 to 2 k
RY
O
10 k
OI
L
250
24 VDC
CM2
Inverter output
PD/+1, P/+
P/+, N/-
Purpose
Details
Used to connect line power to the drive
Drives with single-phase 200 V input power use only terminals R/L1 and N (T/L3), terminal S/L2 is not
available for these units
Used to connect the motor
Normally connected by the short-circuit bar. Remove the short-circuit bar between +1 and P/+2 when a
DC reactor is connected
Grounding
INSTALLATION
Model (3G3JX-)
Screw size
W (mm)
S/L2
7.1
T/L3
AB002 to AB004
A2002 to A2007 *1
M3.5
7.1
P/+ PD+1
Main Circuit
Terminal Block
A2015 to A2037
A4004 to A4040
AB007 to AB022 *1
M4
9.2
A2055 to A2075
A4055 to A4075
M5
13
9.2 or 13
N/-
P/+
PD+1
Main Circuit
Terminal Block
*1. For 3G3JX-AB, R/L1 corresponds to L1 and T/L3 to N, terminal S/L2 is not available. Connect a single-phase 200 VAC input to terminals L1 and N.
Relay
output
AL2 AL1 AL0
Analog Frequency
monitor reference
output
input
AM H
OI
Multi-function input
5
2 1
Multi-function
output
L PCS P24
CM2
11
Short-circuit bar
Type
Digital
input
signals
Analog
input
signals
No.
Signal name
Function
PCS
P24
Internal 24 VDC
10 VDC 10 mA max
0 to 10 VDC (10 k)
OI
4 to 20 mA (250 )
Signal level
24 VDC 10%
27 VAC max
ON voltage: 18 V min
OFF voltage: 3 V max
Load current: 5 mA
Min ON time: 12 ms
INSTALLATION
AL2
Digital
output
signals
AL1
NO output
AL0
250 VAC 1 A
30 VDC 1 A
5 V, 100 mA min
CM2
AM
11
Monitor
signal
NC output
27 VDC
50 mA max
0 to 10 VDC, 1 mA
+V
+V
P24
Short-circuit
bar
PCS
L
P24
PCS
24 V DC
24 V DC
1
5
5
COM
COM
Inverter
COM
10
COM
24 V DC
24 V DC
P24
PCS
L
0V
Output unit etc.
Inverter
P24
Short-circuit PCS
bar
L
DC24V
24 V DC
0V
Inverter
Inverter
PROGRAMMING JX
3 PROGRAMMING JX
3.1 Digital operator
Data display
RUN command LED indicator
FREQ adjuster
Operation keys
Item
8888
Name
POWER LED indicator
Description
Lit when the power is supplied to the control circuit.
Lit when the set value of each function is indicated on the data display.
Blinks during warning (when the set value is incorrect).
Displays relevant data, such as frequency reference, output current and set values.
Data display
FREQ adjuster
Sets a frequency. Available only when the frequency reference source is set to the
FREQ adjuster. (Check that the Volume LED indicator is lit.)
Lit when the RUN command is set to the Digital operator. (The RUN key on the
Digital operator is available for operation.)
Activates the inverter. Available only when operation via the Digital operator is
selected. (Check that the RUN command LED indicator is lit.)
Forward/Reverse rotation depends on F004 setting.
RUN key
STOP/RESET key
Decelerates and stops the inverter. Functions as a reset key if an inverter error
occurs.
Mode key
Switches between: the monitor mode (d@@@), the basic function mode (F@@@),
and the extended function mode (A@@@, b@@@, C@@@, H@@@).
With this key, you can always change the display as follows.
[Supplemental information]
To jump to d001 from any function mode, hold down the Mode key for 3
seconds.
58.1
or
f001
58.0
f001
57.9
Enter key
Increment key
Decrement key
Note: Always press the Enter key to store any changed data.
Enters and stores changed data.
(To change the set value, be sure to press the Enter key.)
Do not press the Enter key if you dont want to store any changes, for example, if
you have changed the data inadvertently.
Changes the mode.
Also, increases the set value of each function.
11
PROGRAMMING JX
d001
*4
0.0
*4
d083
*4
f001
*5
f004
*3
a001
*1
*5
a---
0000
a001
*2
0001 9999
*5
b---
a002
c---
*1
*2
0000
0001 9999
*5
h---
a003
12
PROGRAMMING JX
Display example
0.0
b--b001
b084
00
02
b084
Description
Power On
Press the Mode key once, and then press the Decrement key three times to
display b---.
Press the Enter key. The set value is entered and b084 is displayed.
Press the STOP/RESET key while holding down the Mode and Decrement
keys simultaneously.
When the display blinks, release the STOP/RESET key first, and then the
Mode and Decrement keys.
-. 00
(In 1 s)
d001
Displays initialization.
Parameter name
Frequency reference selection
Details
00: Digital operator (FREQ adjuster)
01: Terminal
2nd frequency reference selection 02: Digital operator (F001)
03: ModBus communication
10: Frequency operation result
13
PROGRAMMING JX
Parameter name
RUN command selection
2nd RUN command selection
A202
Details
01: Terminal
02: Digital operator
03: ModBus communication
Adjust the stopping method by b091 and the acceleration/deceleration ramps on parameters F002 and F003
Parameter
b091
Parameter name
Stop selection
F002
F202
F003
F203
Details
00: Deceleration to stop
01: Free-run stop
0.01 to 3000. s
Acceleration time 1
2nd acceleration time 1
Deceleration time 1
2nd deceleration time 1
0.01 to 3000. s
Set the motor base frequency and AVR voltage of the motors in parameters A003 and A082
Parameter
A003
A203
A082
Parameter name
Base frequency
2nd base frequency
AVR voltage selection
Details
30. to Max. frequency [A004]
30. to Max. frequency [A204]
200-V class: 200/215/220/230/240 V
400-V class: 380/400/415/440/460/480 V
Set the motor data: rated current (b012), rated power (H003) and number of poles (H004)
Parameter
b012
b212
H003
H203
H004
H204
Parameter name
Electronic thermal level
2nd electronic thermal level
Motor capacity selection
2nd motor capacity selection
Motor pole number selection
2nd motor pole number selection
Details
0.2 x Rated current to 1.0 x Rated current
200-V class: 0.2/0.4/0.75/1.5/2.2/3.7/5.5/7.5 kW
400-V class: 0.4/0.75/1.5/2.2/3.7/5.5/7.5 kW
2/4/6/8 poles
At this point the inverter is ready to run the motor for the first time, but first review this check-list:
Verify the power LED is ON. If not, check the power connections.
Make sure the motor is disconnected from any mechanical load.
Make sure that you have a frequency reference checking the content of F001.
Now give the RUN command from the selected source. The RUN LED will turn ON.
The motor should start turning.
Remove the RUN command or press the STOP key to stop the motor rotation.
Output frequency
Max. frequency
A004/A204
F002/F202
Parameter
A004
A204
b082
F001
F002
F202
14
Parameter name
Maximum frequency
2nd maximum frequency
Starting frequency
Output frequency setting/monitor
Acceleration time 1
2nd acceleration time 1
Actual
deceleration
time
F003/F203
Description
30. to 400. Hz
0.5 to 9.9 Hz
Starting frequency to 1st or 2nd max. frequency
0.01 to 3000. s
PROGRAMMING JX
F003
F203
Deceleration time 1
2nd deceleration time 1
0.01 to 3000. s
Standard acceleration and deceleration is linear. The inverter CPU can also calculate an S-curve acceleration or deceleration
curve as shown. Even if the shape of the ramps change the time keeps being the same one set in F002/F003.
Curve settings for acceleration and deceleration are independently selected. To enable the S-curve, use function A097 (acceleration) and A098 (deceleration).
Parameter
A097
A098
Parameter name
Acceleration pattern selection
Deceleration pattern selection
Description
00: Line
01: S-shape curve
00
01
Line
S-shape curve
Output frequency
Output frequency
A097
(Acceleration)
Time
Output frequency
A098
(Deceleration)
Output frequency
Time
Time
Description
Time
Normal DC injection braking is used when A051 is set to 01 (Enable during stop) and the RUN command (FW/RV) is
turned OFF, at the moment that deceleration stops the DC injection brake starts with a settable power (A054) and duration
(A055). Additionally is possible to specify a wait time between the end of the ramp and the DC injection braking on parame-
15
PROGRAMMING JX
ter A053, during which the motor will free run. If free-run is selected as stopping method the DC injection braking will start
just when the Run commands turns OFF.
DC Brake at stop
FW
ON
F-SET
A053
A055
F-OUT
DB
A053
DC injection braking by frequency detection can be selected setting A051 to 02 (Frequency control). In this case DC injection braking operates when the output frequency comes down to the one you specified in A052 while the RUN command is
still active. External DB and internal DC injection braking are invalid during the frequency detection mode.
FW
FW
ON
F-SET
F-SET
A052
A052
F-OUT
F-OUT
ON
DB
DB
DB
DB
Last option is to trigger the DC injection by a digital input when the terminal (DB) is turned ON. Set parameters A053 and
A054 to setup this function. There are several cases depending on the motor rotation and Run command status.
[FW,RV]
[DB]
FW or RV DI are ON
1
0
1
0
1
0
1
0
1
0
1
0
delay
A053
F-OUT
Parameter
16
Parameter name
Description
A051
00: Disabled
01: Enabled
02: Frequency control [A052 set value]
A052
0.0 to 60.0 Hz
PROGRAMMING JX
Parameter
Parameter name
Description
A053
A054
0. to 100.%
A055
A056
Be careful to avoid specifying too long braking time or too high carrier frequency that can cause motor overheating. If you use
DC injection braking is recommended to use motors with a built-in thermistor and wire it to inverters thermistor input.
Parameter name
Description
A044
A244
Constant torque characteristics (VC) - Output voltage is proportional to output frequency. While proportional from 0 Hz to
base frequency, the output voltage is constant from base to maximum frequencies regardless of the frequency.
Output
voltage
(100%)
Output
frequency (Hz)
0
Reduced torque characteristics (VP 1.7th power) - Suitable for a fan or pump that does not require large torque in a low
speed range. These provide high efficiency, reduced noise and vibration, owing to reduced output voltage in a low speed
range.
Output
voltage
(100%)
VP (1.7th
power of VP)
Output
frequency (Hz)
0
Base frequency Max. frequency
(A004/A204)
(A003/A203)
Special reduced torque characteristics (Special VP) - Suitable for a fan or pump that requires torque in a low speed range
using VC characteristics at this area.
Output
voltage
(100%)
VP
(1.7th power)
VC
Output
frequency (Hz)
0
10% of base
frequency
a
Period a: Provides constant torque characteristics (VC) within a range from 0 Hz to 10% of base frequency. (Example) If the
base frequency is 50 Hz, the inverter provides constant torque characteristics within a range from 0 to 5 Hz.
Period b: Provides reduced torque characteristics within a range from 10% to 100% of the base frequency. The inverter outputs voltage based on a curve of the 1.7th power of the frequency.
17
PROGRAMMING JX
Period c: Provides constant voltage within a range from the base frequency to the maximum frequency.
Compensates the voltage drop caused by the primary resistance of the motor or wiring increasing the torque in a low speed
range.
To select the simple torque boost in the torque boost selection (A041/A241), set the motor capacity selection (H003/H203)
and motor pole number selection (H004/H204) according to your motor.
18
PROGRAMMING JX
Output
voltage (100%)
Manual torque
boost voltage
(A042/A242)
V/f characteristics
(Example: VC)
If you raise the set value of the manual torque boost (A042/
A242) be careful about motor overexcitation. Otherwise the
motor may burn out.
If simple torque boost is selected in the torque boost selection (A041/A241: 01), it operates to adjust the output voltage
depending on the load level.
To select simple torque boost in the torque boost selection (A041/A241), set the motor capacity selection (H003/H203) and
motor pole number selection (H004/H204) according to your motor.
You may avoid a possible overcurrent trip during deceleration by always setting the AVR selection to ON (A081: 00).
Sufficient characteristics may not be obtained if you select two or more lower rank motor size than specified.
Parameter
Parameter name
A041
Description
A241
A042
A242
A043
A243
Can boost starting torque between 0 and 20% above normal V/f
curve
0.0 to 20.0%
Sets the frequency of the V/f breakpoint for torque boost
0.0 to 50.0%
Terminal
symbol
00
FW
01
RV
Function name
Forward command
Reverse command
02
CF1
03
CF2
04
CF3
05
CF4
Description
ON
OFF
ON
OFF
ON
OFF
06
JG
Jogging
ON
07
DB
ON
08
SET
ON
The inverter uses 2nd motor parameters for generating frequency output to motor
09
2CH
2-step acceleration/deceleration
11
FRS
Free-run stop
12
EXT
External trip
13
15
16
USP
SFT
AT
OFF
The inverter uses 1st (main) motor parameters for generating frequency output to motor
ON
OFF
ON
Causes output to turn OFF, allowing motor to free run (coast) to stop
ON
When assigned input transitions OFF to ON, inverter latches trip event and displays E 12
OFF
No trip event for ON to OFF, any recorded trip events remain in history until reset
ON
OFF
The inverter will resume a Run command that was active before power loss
ON
The keypad and remote programming devices are prevented from changing parameters
OFF
ON
OFF
19
PROGRAMMING JX
Terminal
symbol
18
RS
Function name
Reset
Description
ON
The trip condition is reset, the motor output is turned OFF, and powerup reset is asserted
OFF
ON
The inverter can detect motor temperature and, if the temperature exceeds the specified level, trips
to shut off the output (E35). The level is fixed.
19
PTC
Thermistor input
20
STA
3-wire start
21
STP
3-wire stop
ON
22
F/R
3-wire forward/reverse
ON
Selects the direction of motor rotation: ON = FWD. While the motor is rotating, a change of F/R
will start a deceleration, followed by a change in direction
OFF
Selects the direction of motor rotation: OFF = REV. While the motor is rotating, a change of F/R
will start a deceleration, followed by a change in direction
ON
Temporarily disables PID loop control. Inverter output turns OFF as long as PID Enable is active
(A071=01)
23
PID
24
PIDC
PID enabled/disabled
OFF
If the thermistor is not connected, the inverter trips (E35) to shut off the output
ON
OFF
Has no effect on PID loop operation, operates normally if PID Enable is active (A071=01)
ON
Resets the PID loop controller. Main consequence is that integrator sum is forced to zero
Accelerates (increases output frequency) motor from current frequency
27
UP
ON
28
DWN
ON
29
UDC
ON
Clears the UP/DWN frequency memory by forcing it to equal the set frequency parameter F001.
31
OPE
Forced operator
ON
Forces the source of the output frequency setting A001 and the source of the Run command A002
to be from the digital operator
50
ADD
Frequency addition
51
F-TM
52
RDY
Ready function
53
SP-SET
64
EMR
255
no
OFF
Source of output frequency set by A001 and source of Run command set by A002 is used
ON
OFF
ON
Force inverter to use input terminals for output frequency and Run command sources
OFF
Source of output frequency set by A001 and source of Run command set by A002 is used
ON
OFF
ON
OFF
ON
Emergency shutoff is ON
All this functions could be assigned to any of the multi-function inputs on parameters C001 to C005, select if the input will be
normally open or normally close and the response time of the input.
Parameter
C001
Parameter name
Multi-function input 1 selection
C201
C002
C202
C003
C203
C004
C204
C005
C205
C011
C012
C013
C014
C015
Description
Refer to upper table for available settings
An input terminal configured for option code 18 ([RS] Reset command) cannot be configured for normally closed operation.
20
PROGRAMMING JX
Terminal
symbol
00
RUN
01
FA1
Function name
Description
ON
ON
OFF
ON
When output to motor is at or above the set frequency, even if in acceleration (C042) or
deceleration (C043) ramps
02
FA2
OFF
03
OL
Overload warning
ON
When output current is more than the set threshold (C041) for the overload signal
04
OD
ON
When PID error is more than the set threshold for the deviation signal
05
AL
Alarm output
ON
When an alarm signal has occurred and has not been cleared
06
Dc
07
FBV
Disconnection detection
ON
ON
Shifts output when exceeding the upper limit or falling below the lower limit
08
NDc
Network error
ON
09
LOG
ON
10
ODc
Not used
43
LOC
ON
In the same way of that the digital inputs is possible to choose between normally close and normally open and even is possible to
use some On and Off delay for each of the outputs.
Parameter
Parameter name
C021
Description
C026
C031
C036
OI
A001
[AT]
Frequency setting
Inverter VR
Voltage input
Current input
Analog ground
OI
Switching between the inputs could be done by a digital input setting parameter A005.
Parameter
A005
Parameter name
O/OI selection
Related parameters
Required settings
Data
00: Switches between O/OI via terminal AT
02: Switches between O/FREQ adjuster via terminal AT
03: Switches between OI/FREQ adjuster via terminal AT
04: O input only
05: OI input only
Default setting
Unit
02
A011 to A016, A101 to A105, A151 to A155, C001 to C005. C081, C082
A001= 01
Allocate AT (16) to any of the multi-function inputs with the frequency reference set to the terminal block (A001 or A201 = 01).
Data
Symbol
16
AT
Related parameters
Function name
Analog input switching
Status
Description
ON
OFF
Same as above
C001 to C005
21
PROGRAMMING JX
The settings are as follows. (VR: FREQ adjuster). If AT is not allocated to any of the multi-function input, this means the AT
input = OFF in the above table.
A005 set value
00
02
03
04
OFF
ON
OFF
ON
OFF
ON
O-L
OI-L
O-L
VR
OI-L
VR
OFF
05
ON
OFF
O-L
ON
OI-L
Parameter name
AM selection
Description
00: Output frequency
01: Output current
Output frequency - Outputs the voltage according to the output frequency, with the maximum frequency being full scale.
This is intended for display indication and cannot be used as a line speed signal. Through the accuracy is 5%, this could be
exceeded depending on your meter. Outputs a frequency obtained by multiplying the output frequency by the conversion
coefficient [b086], with the maximum frequency being full scale.
AM H
OI
Meter
10V, 1mA
Output current - Outputs a current value with 200% of the inverter rated voltage being full scale. The output method is the
same as the output frequency. Monitor accuracy is 10% at the halfway point of base frequency.
AM adjustment
You can adjust the calibration of the analog voltage (0 to 10 VDC) from the AM terminal on the control terminal block by using
the inverter setting.
Parameter
Parameter name
Data
Default setting
Unit
b080
AM adjustment
100.
C086
AM offset adjustment
0.0
Related parameters
Note: If the offset (C086) is changed, the point to reach 10 V changes accordingly because of parallel movement. To avoid this,
adjust the offset (C086) before the gain (b080).
When b080 = 100
AM output
10V
b080=0 to 255
10V
C086=0 to 10
Parallel shift
5V
5V
0
1/2 FS
22
1/2 FS
PROGRAMMING JX
Causes an overload trip (E05) to protect the motor from overheating by setting according to the motor rated current.
Provides the most appropriate protection characteristics, taking into account the decline of a standard motor cooling capability at a low speed.
To set a value over the rated current of the motor, be careful of any temperature rise of the motor.
Parameter
b012
Parameter name
Description
b212*
b013
b213*
Related parameters
C021
* To switch to the 2nd control, allocate 08 (SET) to the multi-function input terminal and then turn it on.
Electronic thermal level (motor protection level)
(Example) 3G3JX-AB007, rated current: 4.0 A, setting range: 0.8 to 4.0 A.
Time before trip (s)
Example where electronic
thermal level is b012 = 5.0 A
60
4
0
Reduced torque characteristics 1 - Multiplied by the time limit characteristics set in b012/212 for each frequency.
Constant torque characteristics - Do not skip this setting when using a constant torque motor. Multiplied by the time limit
characteristics set in b012/212 for each frequency.
Reduced torque characteristics 2 - Multiplied by the limit characteristics set in b012/212 for each frequency.
Constant torque
characteristics
Reduced torque
characteristics 1
Reduced torque
characteristics 2
X1.0
X1.0
X0.8
X0.8
X0.667
X0.6
0
20
60
Inverter output
frequency (Hz)
60
Inverter output
frequency (Hz)
20
60
Inverter output
frequency (Hz)
23
PROGRAMMING JX
Parameter name
Data
Carrier frequency
Default setting
Unit
3.0
kHz
2.0 to 12.0
With the carrier frequency set high, you can reduce metallic noise from the motor. However, this may increase electrical noise
or leakage current from the inverter.
Parameter name
Data
Default setting
Unit
00
PID selection
00: Disabled
01: Enabled
A072
PID P gain
0.2 to 5.0
1.0
A073
PID I gain
0.0 to 150.0
1.0
A074
PID D gain
0.00 to 100.0
0.0
A075
PID scale
0.01 to 99.99
1.00
Time
A076
00: OI
01: O
02: RS485 communication
10: Operation function output
00
A077
00
A078
0.0 to 100.0
0.0
C044
0.0 to 100.0
3.0
C052
0.0 to 100.0
100.0
C053
0.0
d004, A001, A005, C001 to C005, C021, C026
Sensor
=
Transducer
s: Operator
: Deviation
PID enable/disable
Data
Symbol
23
PID
Related parameters
Function name
PID enabled/disabled
Status
Description
ON
OFF
C001 to C005
Excessive deviation/output
Data
Symbol
04
OD
Function name
Excessive PID deviation
Status
Description
ON
OFF
The PID deviation has not reached the C044 set value
24
PROGRAMMING JX
Symbol
07
FBV
Function name
PID FB status output
Status
ON
OFF
Description
Shifts output when exceeding the upper limit or falling
below the lower limit
Symbol
24
PIDC
Related parameters
Function name
PID integral reset
Status
Description
ON
OFF
C001 to C005
Parameter name
b021
b221*
b022
b222*
b023
b223*
b028
b228*
C041
C241*
Data
Default setting
Unit
01
1.5 x Rated
current
0.1 to 3000.0
1.0
00
Rated current
00: Disabled
01: Enabled in acceleration/constant speed operation
02: Enabled in constant speed operation
0.1 x Rated current to 1.5 x Rated current
* To switch to the 2nd control, allocate 08 (SET) to the multi-function input terminal and then turn it on.
The inverter monitors the motor current during acceleration or constant speed operation. If it reaches the overload limit
level, the output frequency is lowered automatically according to the overload limit parameter.
Overload limit level
b022
Deceleration set by the overload
limit parameter
Output current
Max. frequency
A004/A204
Inverter output
frequency
Target frequency
F001
b023
Default setting
Unit
b055
0.2 to 5.0
0.2
b056
0.0 to 150.0
0.2
Parameter name
Data
25
PROGRAMMING JX
Parameter
Parameter name
Data
b130
00: Disabled
01: Enabled
b131
b133
00: Disabled
01: Enabled
b134
Default setting
Unit
00
380/760
00
380/760
Internal DC
voltage
Set level (B134)
t
Output
frequency
t
Normal
Default setting
Unit
b050
Parameter name
00: Disabled
01: Enabled (stop)
02: Enabled (restart)
Data
00
b051
0.0 to 1000.
0.0
b052
0.0 to 1000.
0.0
b053
0.01 to 3000.
1.0
b054
0.0 to 10.0
0.0
Hz
OFF
Power supply
Internal DC
voltage
b052
b051
Undervoltage level
Output frequency
b054
b053
b053
b053
26
PARAMETER LIST
4 PARAMETER LIST
The PDU (Process Data Unit) register number are addressed starting at zero. Therefore register numbered 0012h addressed as
0011h. Register address value (transmitted on Modbus line) is 1 less than the Register number of the table
Function name
d001
d002
d003
d004
d005
d006
ON
OFF
AL2
d007
d013
d016
Changes
during
operation
-
1005 (high)
1006 (low)
1007
1008
1009 (high)
100A (low)
100C
100E (high)
100F (low)
1010 (high)
1011 (low)
116A
0011
0012 to 001B
Default
setting
Unit
Modbus
address (hex)
Hz
A
-
1002
1003
1004
Terminal
4, 2: ON
Terminal
5, 3, 1: OFF
Terminal 11: ON
Terminal AL2: OFF
11
0.00 to 39960
(Output frequency x Conversion factor of b086)
0. to 600.
0. to 99990 hours
V
h
d017
0. to 99990 hours
d018
d080
d081
C
-
d082
Fault monitor 2
d083
Fault monitor 3
d102
d104
DC voltage monitor
Electronic thermal monitor
0.0 to 200.0
0. to 9999.
Error code (condition of occurrence)
Output frequency [Hz]
Output current [A]
Internal DC voltage [V]
RUN time [h]
ON time [h]
0.0 to 999.9
0.0 to 100.0
001C to 0025
0026 to 002F
-
V
%
116C
116D
Function name
A001
A201
A002
A202
A003
A203
A004
A204
A005
Base frequency
2nd base frequency
Maximum frequency
2nd maximum frequency
O/OI selection
A011
A012
A013
A014
A015
O start frequency
O end frequency
O start ratio
O end ratio
O start selection
A016
A020
A220
O, OI sampling
Multi-step speed reference 0
2nd multi-step speed reference 0
Default
setting
00
Changes
during
operation
No
Unit
Modbus
address
(hex)
1019
02
No
101A
50
No
Hz
50
No
Hz
02
No
101B
150C
101C
150D
101D
0.0
No
Hz
0.
100.
01
No
No
8.
6.0
No
Yes
Hz
1020
1022
1023
1024
1025
1026
1029
150F
27
PARAMETER LIST
Parameter
No.
Function name
A021
A022
A023
A024
A025
A026
A027
A028
A029
A030
A031
A032
A033
A034
A035
A038
A039
A041
A241
A042
A242
A043
A243
A044
A244
A045
A245
A051
A052
A053
A054
A055
A056
A061
A261
A062
A262
A063
A064
A065
A066
A067
A068
A071
A072
A073
A074
A075
A076
PID P gain
PID I gain
PID D gain
PID scale
PID feedback selection
A077
A078
A081
A082
A085
A086
A092
A292
28
Modbus
address
(hex)
102B
102D
102F
1031
1033
1035
1037
1039
103B
103D
103F
1041
1043
1045
1047
1048
1049
0.0
Changes
during
operation
Yes
6.00
00
Yes
No
Hz
-
00
No
0.0 to 20.0
5.0
0.0
2.5
0.0
00
Yes
Yes
No
100.
Yes
00
No
104E
1514
1051
0.5
0.0
50
0.5
01
No
No
No
No
No
Hz
s
%
s
1052
1053
1054
1055
1056
0.0
No
Hz
0.0
No
Hz
0.0
0.5
0.0
0.5
0.0
0.5
00
No
Hz
No
105A
1517
105B
1518
105D
105E
1060
1061
1063
1064
1068
1.0
1.0
0.0
1.00
00
Yes
Yes
Yes
No
No
s
s
Time
1069
106A
106B
106C
106D
00
No
106E
0.0
02
No
No
106F
1070
200/400
No
1071
00
No
1072
50
15.00
No
Yes
%
s
1073
1074 (high)
1075 (low)
1519 (high)
151A (low)
0.0 to 50.0
00: Constant torque characteristics (VC)
01: Reduced torque characteristics (VP 1.7th power)
06: Special reduced torque characteristics (Special VP)
20. to 100.
00: Disabled
01: Enabled
02: Frequency control [A052 set value]
0.0 to 60.0
0.0 to 5.0
0. to 100.
0.0 to 60.0
00: Edge operation
01: Level operation
0.0/frequency lower limit to max frequency
0.0/2nd frequency lower limit to 2nd max frequency
0.0/starting frequency to frequency upper limit
0.0/starting frequency to 2nd frequency upper limit
Jump frequency: 0.0 to 400.0
Jump frequency width: 0.0 to 1.0
00: Disabled
01: Enabled
0.2 to 5.0
0.0 to 150.0
0.0 to 100.0
0.01 to 99.99
00: OI
01: O
02: RS485 communication
10: Operation function result
00: OFF (Deviation = Target value - Feedback value)
01: ON (Deviation = Feedback value - Target value)
0.0 to 100.0
00: Always ON
01: Always OFF
02: OFF during deceleration
200-V class: 200/215/220/230/240
400-V class: 380/400/415/440/460/480
00: Normal operation
01: Energy-saving operation
0 to 100
0.01 to 3000.
Default
setting
Unit
Hz
104A
1510
104B
1511
104C
1512
104D
1513
PARAMETER LIST
Parameter
No.
Function name
A093
Deceleration time 2
A293
A094
A294
A095
A295
A096
A296
A097
A098
A101
A102
A103
A104
A105
A141
A142
A143
Operator selection
A145
A146
A151
A152
A153
A154
A155
VR start frequency
VR end frequency
VR start ratio
VR end ratio
VR start selection
00
No
0.0
No
Hz
0.0 to 400.0
0.0
No
Hz
00: Line
01: S-shape curve
0.0 to 400.0
00
No
0.0
No
Hz
0.
100.
01
No
No
Modbus
address
(hex)
1076 (high)
1077 (low)
151B (high)
151C (low)
1078
151D
107A
151F
107C
1521
107D
107E
1080
1082
1083
1084
1085
01
No
108E
0. to 100.
00: Use OI start frequency [A101]
01: 0 Hz start
00: Digital operator (F001)
01: Digital operator (FREQ adjuster)
02: Input O
03: Input OI
04: RS485 communication
00: Addition (A + B)
01: Subtraction (A - B)
03: Multiplication (A x B)
0.0 to 400.0
00: Adds A145 value to output frequency
01: Subtract A145 value from output frequency
0.0 to 400.0
0. to 100.
00: Use VR start frequency [A151]
01: 0 Hz start
15.00
Changes
during
operation
Yes
Default
setting
Unit
s
02
108F
00
No
1090
0.0
00
Yes
No
Hz
1091
1093
0.0
No
Hz
0.
100.
01
No
No
1095
1097
1098
1099
109A
Default
setting
00
Changes
during
operation
No
1.0
1.0
00
Function name
b001
Retry selection
b002
b003
b004
b005
b011
b012
b212
b013
b213
b021
b221
b022
b222
b023
b223
b028
b228
b029
b030
Modbus
address
(hex)
10A5
No
No
No
s
s
10A6
10A7
10A8
00
No
10A9
00
No
1170
Rated
current
No
00
No
10AD
1527
10AE
1528
01
No
10B5
1529
1.5 x
Rated
current
1.0
No
10B6
152A
No
00
No
0.5
No
10B7
152B
10BB
152C
1171
Rated
current
No
1172
Unit
29
PARAMETER LIST
Parameter
No.
Function name
b031
b050
b051
b080
b082
b083
b084
Starting frequency
Carrier frequency
Initialization selection
b085
b086
b087
b088
b089
b091
Stop selection
b092
b130
b131
b133
b134
b140
b150
b151
b052
b053
b054
b055
b056
30
Modbus
address
(hex)
10BC
No
10C9
No
10CA
01
Changes
during
operation
No
00
0.0
Default
setting
Unit
10CB
0.01 to 3000
1.0
No
10CC
0.0 to 10.0
0.0
No
Hz
10CE
0.2 to 5.0
0.2
Yes
1173
0.0 to 150.0
0.2
Yes
1174
0. to 255.
(Shared with C086 for AM offset adjustment)
0.5 to 9.99
2.0 to 12.0
00: Clears the trip monitor
01: Initializes data
02: Clears the trip monitor and initializes data
00 (Do not change)
0.1 to 99.9
00: Enabled
01: Disabled
00: 0 Hz start
01: Active frequency matching restart
01: Output frequency monitor
02: Output current monitor
03: Rotation direction monitor
04: PID feedback value monitor
05: Multi-function input monitor
06: Multi-function output monitor
07: Frequency conversion monitor
00: Decel-Stop
01: Free-RUN
00: Always ON
01: ON during RUN
02: Depends on the fin temperature
00: Disabled
01: Enabled
200-V class: 330. to 395.
400-V class: 660. to 790.
00: Disabled
01: Enabled
200-V class: 330. to 395.
400-V class: 660. to 790.
00: Disabled
01: Enabled
00: Disabled
01: Enabled
00: Disabled
01: Enabled
100.
Yes
10CF
1.5
3.0
00
No
No
No
Hz
kHz
10D1
10D2
10D3
00
1.0
00
No
Yes
No
10D4
10D5
10D6
00
No
10D7
01
Yes
10D8
00
No
10DA
01
No
10DB
00
No
10F5
380/760
Yes
10F6
00
No
1176
380/760
No
1177
01
No
10F7
00
No
10F8
00
No
10F9
PARAMETER LIST
Function name
C001
C201
C002
C202
C003
C203
C004
C204
C005
C205
C011
C012
C013
C014
C015
C021
C026
C028
AM selection
C031
C036
C038
C039
C041
C241
C042
C043
C044
C052
C053
C070
C071
C072
Default
setting
00
Changes
during
operation
No
Unit
Modbus
address
(hex)
1103
00
1532
01
1104
01
1533
18
1105
18
1534
12
1106
12
1535
02
1107
02
1536
*1. The EMR is set forcibly with switch S8, not with parameters.
00: NO
01: NC
00
No
00
No
05
110B
110C
110D
110E
110F
1114
1119
00
No
111B
00
No
111D
01
01
No
1122
1178
Rated
current
Rated
current
No
1179
No
0.0
No
Hz
3.0
100.0
0.0
02
No
No
%
%
No
1124
153A
1126
1128
1129
112E
112F
1137
04
No
1137
1.
No
1139
31
PARAMETER LIST
Parameter
No.
Function name
C074
C075
C076
C077
C078
C081
C082
C086
C091
C101
C102
Reset selection
C141
C142
C143
C144
C145
C148
C149
Modbus
address
(hex)
113B
No
113C
02
No
113D
0.00
0.
100.0
No
No
Yes
s
ms
%
0.0 to 10.0
Use 00 (Do not change)
00: Do not store the frequency data
01: Store the frequency data
00: Trip reset at rising edge of RS input
01: Trip reset at falling edge of RS input
02: Enabled only during trip (Reset at rising edge of RS
input)
00: RUN (signal during RUN)
01: FA1 (constant speed arrival signal)
02: FA2 (over set frequency arrival signal)
03: OL (overload warning)
04: OD (excessive PID deviation)
05: AL (alarm output)
06: Dc (disconnection detected)
07: FBV (PID FB status output)
08: NDc (network error)
10: ODc (do not use)
43: LOC (light load detection signal)
00: AND
01: OR
02: XOR
0.0 to 100.0
0.0
00
00
Yes
No
113E
113F
1141
1142
1145
1149
00
No
114A
00
No
1150
0.0 to 100.0
00
Changes
during
operation
No
Default
setting
Unit
01
1151
00
No
1152
0.0
No
0.0
No
1153
1154
1157
1158
Default
setting
Changes
during
operation
Unit
Factory
default
No
kW
No
Function name
H003
H203
H004
2/4/6/8
H204
H006
Stabilization parameter
H206
Modbus
address
(hex)
1165
1541
Pole
1166
1542
0. to 255.
100
Yes
1168
1544
Function name
F001
F002
Acceleration time 1
0.01 to 3000.
F202
F003
Deceleration time 1
F203
F004
Changes
during
operation
Unit
Yes
Hz
10.0
Yes
1014 (high)
Default
setting
Modbus
address
(hex)
1015 (low)
1501 (high)
1502 (low)
0.01 to 3000.
10.0
Yes
1016 (high)
1017 (low)
1503 (high)
1504 (low)
32
00: Forward
01: Reverse
00
No
1018
OmRON EUROPE B.V. Wegalaan 67-69, NL-2132 JD, Hoofddorp, The Netherlands.
Tel: +31 (0) 23 568 13 00 Fax: +31 (0) 23 568 13 88 industrial.omron.eu
Austria
Tel: +43 (0) 2236 377 800
industrial.omron.at
France
Tel: +33 (0) 1 56 63 70 00
industrial.omron.fr
Netherlands
Tel: +31 (0) 23 568 11 00
industrial.omron.nl
Spain
Tel: +34 902 100 221
industrial.omron.es
Belgium
Tel: +32 (0) 2 466 24 80
industrial.omron.be
Germany
Tel: +49 (0) 2173 6800 0
industrial.omron.de
Norway
Tel: +47 (0) 22 65 75 00
industrial.omron.no
Sweden
Tel: +46 (0) 8 632 35 00
industrial.omron.se
Czech Republic
Tel: +420 234 602 602
industrial.omron.cz
Hungary
Tel: +36 (0) 1 399 30 50
industrial.omron.hu
Poland
Tel: +48 22 458 66 6
industrial.omron.com.pl
Switzerland
Tel: +41 41 748 13 13
industrial.omron.ch
Denmark
Tel: +45 43 44 00 11
industrial.omron.dk
Italy
Tel: +39 02 326 81
industrial.omron.it
Portugal
Tel: +351 21 942 94 00
industrial.omron.pt
Turkey
Tel: +90 212 467 30 00
industrial.omron.com.tr
Finland
Tel: +358 (0) 207 464 200
industrial.omron.fi
South Africa
Tel: +27 (0) 11 579 2600
industrial.omron.eu
Russia
Tel: +7 495 648 94 50
industrial.omron.ru
United Kingdom
Tel: +44 (0) 870 752 08 61
industrial.omron.co.uk