Cooling Load Calculation Sheet: X X X X X X X X X X X X X X X X Cfm/Person Cfm/Door
Cooling Load Calculation Sheet: X X X X X X X X X X X X X X X X Cfm/Person Cfm/Door
CHAP CHAP
TABLE REFERENCE TABLE REFERENCES
REF REF
AREA OR SUNGAI LOCAL LOCAL
ITEM FACTOR ESTIMATE FOR 15.00 PM PEAK 12.00 AM
QUANTITY N OR TIME TIME
LOAD
TEMP. SUN SUN
SOLAR GAIN-GLASS (Btu/hr) 25,436 HOUR OF OPERATION 16
DIFF TIME TIME
GLASS 50 SQ FT X 108.24 X 0.94 CONDITIONS DB WB % RH DP GR/LB
3&4
2
GLASS 50 SQ FT X 108.24 X 0.94 ROOM (RM) 76 50 0 0 0
GLASS 50 SQ FT X 108.24 X 0.94 DIFFERENCE 19 XXX XXX XXX 0
SKYLIGHT 50 SQ FT X 108.24 X 0.94 OUTDOOR AIR
SOLAR & TRANS. GAIN-WALLS & ROOF (Btu/hr) 9,956 VEN 40 PEOPLE X 50 CFM/PERSON = 2000
WALL 200 SQ FT X 19 X 0.32 TI- 1000 SQ FT X 5 CFM/SQ FT = 5000
LATI
WALL 200 SQ FT X 19 X 0.32 ON CFM VENTILATION = 5000
WALL 200 SQ FT X 19 X 0.32 SWING
WALL 200 SQ FT X 19 X 0.32 REVOLVING
ING 50 PEOPL 12 CFM/PERSON = 600
6
DOORS E X
ROOF-SUN 200 SQ FT X 19 X 0.67 INFIL- OPEN 3 DOOR 100 CFM/DOOR = 300
5
STORAGE 25 SQ FT X 2 X 0.4 X
F. DA SUPPLY AIR QUANTITY
8
SUPPLY DUCT + SUPPLY DUCT + FAN 6058 CFM SA - 6,058 CFMDA = - CFMBA
HEAT GAIN % 15 LEAK LOSS % 10 H. 10 % BYPA
CF
P. SSM
OUTDOOR AIR 15 CFM X 19 F X 0.5 BF X RESULTING ENT & LVG CONDITIONS AT APPARATUS
8
100X
SUB TOTAL 3 (Btu/hr) bX 7,560
SAFETY FACTOR 10 % 1. USE DRY-BULB (DB) TEMPERATURE DIFFERENCE FROM TOP OF ESTIMATE FORM.
ROOM LATENT HEAT (Btu/hr) 8,316 2. USE MOISTURE CONTENT (GR/LB) DIFFERENCE FROM TOP OF ESTIMATE FORM.
7
SUPPLY AIR DUCT LEAK LOSS 10 % 3. NORMALLY. USE "CFM VENTILATION" FOR "CFM OUTDOOR AIR" HOWEVER
OUTDOOR AIR 0 CFM X 0 GR/L 0.5 BF X WHEN INFILTRATION IS TO BE OFFSET, REFER TO PAGE 92 TO DETERMINE
EFFECTIVE ROOM LATENT HEAT (Btu/hr) bX 0.68 8,316 "CFM OUTDOOR AIR."
EFFECTIVE ROOM TOTAL HEAT (Btu/hr) 83,552 4. WHEN INFILTRATION IS NOT TO BE OFFSET, AND "CFM VENTILATION IS LESS THAN
8
OUTDOOR AIR HEAT 1,635 "CFM INFILTRATION," THEN THE EXCESS INFILTRAITON IS ACCOUNTED FORHERE.
SENSIBLE : 450 CFM X 5 FX (1 - 0.5 BF)X1
LATENT : 510 CFM X 2 GR/Lb X 0.5 .08
BF)X0.
RETURN DUCT BX(1-
(1 - DUCT
RETURN 68
10 10
HEAT GAIN % + LEAK GAIN %
HP DEHUM. &
7
5 5
PUMP % + PIPE LOSS % * IF THIS DIFF TEMP IS TOO HIGH, DETERMINE SUPPLY CFM FOR DESIRED DIFFERENCE BY SUPPLY
SUB TOTAL 4 (Btu/hr) 2,126 AIR QUANTITY FORMLA.
#
WHEN BYPASSING MIXTURE OF OUTDOOR AND RETURN AIR, USE SUPPLY CFM WHEN BYPASSING
GRAND TOTAL HEAT (Btu/hr) 85,677
RETURN AIR ONLY, USE DEHUMIFIED CFM.
Windows area , sq ft
C12: Area of glassed structure that solar haet gain get thru at varies exposure. ( N,E,S,W,NE,SE
,SW,NW) , Chapter 3
Wall area , sq ft
C20: Area of wall or roof that conducted heat gain get thru at each exposure. ( ,E,S,W,NE,
SE,SW,NW)
C32: Power, kw
Grossory of power of operating motor in the A/C area. It can generate heat to be the cooling load.
C33: Power, kw
Grossory of power of lighting in the A/C area. It can generate heat to be the cooling load.
Outdoor air,CFM
C44: Quantity of outdoor air make up to the A/C system. See note 3 on the bottom of this calculation sheet (Table45,Page97 and Table 43, Page92)
Steam , Lb/Hr
C49: Amount of steam escape to conditioned space
Storage Factor
G37: Factor of storage heat gain depend on the load pattern, weight of material surrounding the space and hour of operation.(Table 13,Page 37)
People, Person
K16: Amount of people in the A/C area.
L21: Door,
The numbe of open door of the A/C area.