Test Report For Earthing System at 66/11Kv Substation at South West Wakrah
Test Report For Earthing System at 66/11Kv Substation at South West Wakrah
Test Report For Earthing System at 66/11Kv Substation at South West Wakrah
X(m) in metres
10 0.009262
20 0.009275
30 0.010065
40 0.01129
50 0.012531
60 0.008918
70 0.01326
80 0.01544
90 0.01108
100 0.01713
110 0.01766
120 0.01825
130 0.01907
140 0.01925
150 0.01949
160 0.01959
170 0.02012
180 0.01999
190 0.020948
200 0.021338
210 0.021687
220 0.021958
230 0.022238
240 0.02242
250 0.2252
260 0.02251
270 0.0225
280 0.02256
290 0.02267
300 0.02262
Measurement of Step voltage
Uev
Uev0 Uev (0°) Ustep= Location
SI..No Iv (A) (180°) Uev (mV) K
(mV) (mV) K*Uev(mV) Reference
(mV)
Main gate
Guard room
ladder
Lighting pole-8
Diesel tank
Pump controller
Main door
Delegue Support
Cooling fan
TCC box
OLTC
LV cable support
Link box(11KV)
Aux. Transformer
LV side
Aux. Transformer
HV side
main door
Delegue Support
Cooling fan
TCC box
OLTC
11kv cable
support
OGST tank
Link box(11KV)
lighting pole
RP 100
B11 RP2
RTCC-2
A190 RP
Telecome panel
LVAC q211
LVAC Q104
LVAC Q203
LVDC Q115
PDB-1
A130 SWGR
A18 SWGR
A200 SWGR
FM 200
C&R roo to Swgr
room door
Basement door
66kv cable support
basement
Basement door-2
Link box(11KV)b28
Battery room
LVAC/SWGR
double door
Store room
Uev
Uev0 Uev (180°) Utouch= Location
SI.No Iv (A) (0°) Uev (mV) K
(mV) (mV) K*Uev(mV) Reference
(mV)
Main gate
Lighting pole-8
Diesel tank
Pump controller
Main door
Delegue Support
Cooling fan
TCC box
OLTC
LV cable support
Link box(11KV)
Aux. Transformer
LV side
Aux. Transformer
HV side
main door
Cooling fan
TCC box
OLTC
OGST tank
Link box(11KV)
lighting pole
RP 100
B11 RP2
RTCC-2
A190 RP
Telecome panel
LVAC q211
LVAC Q104
LVAC Q203
LVDC Q115
110v B/C panel
PDB-1
A130 SWGR
A18 SWGR
A200 SWGR
FM 200
C&R roo to Swgr
room door
Basement door
Basement door-2
Link box(11KV)b28
Battery room
LVAC/SWGR
double door
Store room
1
1
MAX. STEP VOLTAGE
2.5
2 MAX STEP
VOLTAGE AT
1.5 DIFFERENT If
0.5
0
DIFFERENT FAULT CURRENT LEVELS
K
0.031746
0.15873
0.31746
0.47619
0.634921
0.793651
0.952381
1
1.111111
1.269841
MAX STEP
VOLTAGE AT
DIFFERENT If
MAX. TOUCH VOLTAGES AT DIFFERENT LEVELS OF FAULT CURRENT
70
60
50
40 MAX. TOUCH
30 VOLTAGE AT
20 DIFFERENT If
10
0 Column H
FAULT CURRENT IN kA