Synchronous Machines Tests
Synchronous Machines Tests
Synchronous Machines
OBJECTIVE
Three-phase synchronous machines account for a high percentage of this country’s power
generation. Understanding the machine’s behavior and determining its equivalent network and
performance characteristics are of prime importance to a power engineer. This experiment
studies the characteristics of doubly-excited synchronous motors and generators. Specific tests
are run to determine equivalent circuit parameters, torque, and power factor control. This lab
shows that system design considerations must include frequency, speed, power factor, and
voltage. Also illustrated are important machine design parameters including linear versus non-
linear magnetic characteristics and efficiency.
REFERENCES
4. “Electric Machinery and Transformers”, Kosow, Irving L., Prentice-Hall, Inc., 1972.
BACKBROUND INFORMATION
transferred to the rotor through stator mounted brushes that make contact with rotor mounted slip
rings. The rotating field that is necessary for continuous torque development is accomplished by
the AC utility supply.
As shown in Figure 1, the rotor can be of either the salient-pole type or the cylindrical
(non-salient-pole) type. The machine used for this experiment is somewhat salient, but the
impact of the salient is negligible. In either case, the flux of the field is fairly uniformly
distributed throughout the stator, as shown in Figure 2.
Figure 2 shows the assumed current direction for phase a of the stator winding. The flux
produced by the stator (armature) current combines with the flux produced by the rotor (field)
circuit to create the mutual flux. Any flux produced that does not link another winding in the
machine is called leakage flux.
We shall now explore how torque is produced in the cylindrical rotor synchronous
machine. We first assume that a direct current has been applied to the field circuit. Thus, the
rotor contains alternate North and South magnetic poles. The next step is to apply a symmetrical
three-phase current to the armature winding. Such a current waveform is shown in Figure 3. If
the armature windings are properly distributed, each phase of the input current produces a
sinusoidal distributed MMF, or magnetic field, centered on each winding axis. The three MMF
distributions are:
F a
= F max cosωt cosθ A–T Eq,. 1
F b
= F max cos(ωt - 120º) cos(θ - 120º) A–T Eq. 2
F =F c max
cos(ωt + 120º) cos(θ + 120º) A–T Eq. 3
and
F max
= I max k w N phase A–T Eq. 4
where
F max
= peak MMF
I max
= peak current
k w
= winding factor
N phase
= series connected turns per phase
k N w phase
= effective turns
The total MMF due to the armature currents is the sum of the individual MMF’s. Thus,
F total
= Fa + Fb + Fc A–T Eq.5
3
F = cos(ωt - θ )
2 F max
total
A–T Eq. 6
Eq. 6 describes a traveling wave which moves around the stator at a velocity
As long as the applied frequency is constant, Eq. 7 tells us that the speed of a
synchronous motor will be constant. Therefore, the only way to change the speed of a
synchronous motor is to change the applied frequency. However, if the frequency is decreased
to slow the motor and the field current is held constant, the back EMF and the synchronous
impedance also decrease. Thus, if the applied voltage V t is held constant, the armature current
will increase until it burns the armature windings. Therefore, to control the speed of a
synchronous motor, the terminal voltage must be adjusted roughly proportionally to the
frequency.
120 f
N sync
= RPM Eq. 7
P
where N sync
= synchronous speed
f = applied frequency, Hz
Figure 4: Representation of the rotating magnetic field for three time increments from Figure 3.
Having previously established the rotor magnetic field and having now established the stator
magnetic field, the machine will attempt to align the two fields. This attempt at alignment produces
torque at the rotor shaft. However, since the stator field is rotating at synchronous speed, the rotor is
dragged right along with the stator field, thus producing a continuous torque.
The two fields can only completely align themselves if there is no load torque attempting to turn
the rotor in the opposite direction. If a load torque exists, the fields must separate enough to produce the
required torque. The concept is described by Eq. 8 and illustrated by Figure 4.
Pu πDl
T dev = − 2og FF
s R
sin δ Eq. 8
where T dev
= developed torque
P = number of poles
D = rotor diameter
g = length of gap
Eq. 8 indicates that the torque is proportional to the peak values of the stator and rotor
MMF’s and the sine of the electrical space angle between them. The negative sign indicates that
the fields are attempting to align themselves. Of course, an equal and opposite torque is
established within the stator.
As the rotor moves within the stator, the field induces voltage in the armature winding of
the machine. This voltage is called the generated voltage in a generator and the back EMF in a
motor. Its magnitude is directly proportional to the speed of the rotor, the strength of the field,
and the effective turns of the armature. If the field poles are properly shaped and the armature
winding properly distributed, the induced voltage is sinusoidal. Figures 7 and 8 illustrate the
phenomenon.
Figure 7: Induced voltages at two different times in the armature of a synchronous machine.
If the machine is supporting a load (armature current not equal to zero), then there is a
rotating magnetic field created by the armature. The armature field tends to reduce the net flux
in the machine air gap, which in turn causes a reduced voltage. This process is called armature
reaction.
We now have enough information to develop equivalent circuit models for the
synchronous machine. The models are shown in Figure 9 and 10 where
E f
= no-load generated voltage
E r
= generated voltage including armature reaction
I a
= armature current
X l
= armature leakage inductance
X s
= synchronous reactance
R a
= per-phase armature resistance
V t
= per-phase terminal voltage
Figure 10: Phasor diagrams for a cylindrical-rotor synchronous machine, for the case of a lagging power
factor (armature current lagging behind the terminal voltage). a) Generator, b) Motor.
producing more magnetic energy than the machine needs for the required output real power. The
excess reactive energy is used to charge the inductances of the external system. The motor
shown in Figure 10 is under excited ( E f > V t
) indicating that the external system must
provide reactive energy to the motor to supplement the weak strength of the field. The
magnitude of the armature current reflects the transfer of reactive energy into or out of the
machine. If the field is providing just the right amount of flux to produce the torque, the
armature current will transmit only real power. At this condition, the armature current
magnitude is minimized for this particular load and the terminal power factor is unity. Figure 11
shows the armature current versus field current curves for different real power conditions. These
are called the V-curves.
For a given level of real power transmission, the position on the V-curve is controlled by
the magnitude of the field current. In fact, at very low power levels the synchronous motor can
be made to “look” capacitive and can be used as a continually adjustable power factor corrector.
The impedance parameters for the equivalent circuits can be found by testing the
machine. The armature resistance is found by placing a DC source across the appropriate
armature terminals and measuring the voltage and current. The resistance is the ratio of voltage
to current multiplied by an appropriate correction to account for skin effect (approximately 1.2 at
60 Hz).
The total impedance of the equivalent circuit is found from the ratio of no-load terminal
voltage to short-circuit current at a specified field current. Figure 12 shows the open-circuit
voltage curve (OCC) and the short-circuit current curve (SCC) for a typical machine. The
voltage curve slope begins to decrease as the field current increases due to saturation of the iron
in the machine.
Figure 12: Open-circuit and short-circuit characteristics of a synchronous machine at rated speed.
The impedance is
Z= R + jX
1
Ω/phase Eq. 9
s
be easily found.
The machines used for this experiment are four-poles, three-phase, wound-rotor induction
motors, but they work quite well as doubly-excited synchronous machines. The stators are rated
for 120V line-to-line and are wye-connected. Both the stator and the rotor windings are rated for
1.5 amperes, but they will handle 2.5 amperes for short periods of time. Note that the pulley
system ratio is 1:1. Therefore, the motor being tested operates at same the speed of
dynamometer.
SUGGESTED PROCEDURE
1. Connect the circuitry shown in Fig. 13. This set-up is used to test the synchronous
machine as a motor.
Remove lock from dynamometer. Place the DPDT switch in position 1 to convert the
rotor to an induction rotor. Increase the 3-φ AC SOURCE output to 120VL – L . Now,
place the switch in position 2 and apply 0.5 Adc to the rotor. This action brings the
machine into synchronism. Use the digital tachometer to verify synchronous speed.
During the next procedures, observe the field current magnitude, armature current
magnitude and phase, and the instantaneous line-to-neutral terminal voltage. The angle
between the phase voltage and phase current is the “power factor” angle. The motor
terminal voltage must be maintained at 120VL – L throughout these tests.
Set four load switches up with the field current still at 0.5 ADC. Slowly increase the
dynamometer field current (load switches “up”) until the synchronous motor stalls (loses
synchronism). Note the value of Iarm and Torque, reset to just below these values get a
maximum stable values for the table below at each value of Ifield. Complete Table 1 for
the given field current values. Note the impact of the field current on the torque capacity
of the motor.
Ifield ⏐Iarm⏐ Vphase to Iphase Phase angle Vt L-L PF Stall
Delay Calculated Calculated Torque
0.5A 120
1.0A 120
1.5A 120
2.0A 120
Table 1
V-curves
For the various dynamometer settings, (no load, half load, and full load) vary the DC
field current from 0.5 ADC to 2.0 ADC. Set four load switches up with the field current
at 0.5 ADC. Slowly increase the dynamometer field current (4 load switches “up”) until
the synchronous motor stalls (loses synchronism). Note the value of Iarm and Torque,
reset to just below these values get a maximum value before it stalls. Do not change the
dynamometer field settings for the rest of this part. For the table below at each value of
motor field current If settings, only change the load switches from full, to ½, and no-load.
For each setting, record the armature current in Table 2. These data points are required to
plot the V-curves of the motor.
Armature Current
If No-Load ½ Load Full Load
no switches 2 switches 4 switches
0.50A
0.75A
1.00A
1.25A
1.50A
1.75A
2.00A
Table 2
1.0A 1800
1.5A 1800
76.2V 1800
Table 3 Open Circuit Characteristic
REPORT
Power Factor
What did you observe in this part? Include any table, data and plots.
What does the Stall mean to a synchronous machine?
How is the phase angle and power factor calculated from the data collected?
Describe the capability of a synchronous motor to control the power factor seen by the
supplying power system. See Table 1. (Short answers, be brief and <5 lines)
(Refer to the textbook pp 240-243 and the experiment results, answer it in your own words)
Torque production.
Explain the impact of field excitation (If) on torque production. Relate it to the fundamentals.
See table 1.
(Examine equations listed on page 4-8 in the lab manual to figure out the answer. For more
information about these equations, please refer to the Reference Book -1 listed in the lab
manual. MMF is the abbreviation of MagnetoMotive Force)
V-Curves
What did you observe in this part? Include any table, data and plots.
Draw the motor V-curves from the data captured, and explain the system aspects of the
characteristic described by the curves. See Figure 11 and Table 2.
(refer to textbook pp 235-240 to organize your explanation. We did not get a whole V-curve in
our experiment, you need to give a general idea about the effect of field current on a
synchronous motor with different amounts of load applied)
Draw the Open-circuit and Short-circuit characteristic. Derive and draw the per-phase
equivalent of the synchronous machine. See Figures 9b and 12, also Tables 3, 4, and 5.
(Pay attention to the Skin effect, and how to find the AC resistance from the DC resistance
calculated)