Power System Stability
Power System Stability
Electrical power oscillations can occur on power systems that contain generation
equipped with fast acting excitation systems. These oscillations occur when a large
amount of power is transmitted over long transmission lines. Power oscillations of small
magnitude and low frequency (<10Hz) often persist for long periods of time. In some
cases, this presents a limitation on the amount of power able to be transmitted within the
system. Power system stabilizers have been developed to aid in the damping of these
power oscillations by modulating the excitation supplied to the synchronous machine.
This paper will discuss the various types of power system instability. It will cover the effects
of system impedance and excitation on stability. Synchronizing torque and damping
torque will be discussed and a justification will be made for the addition of supplemental
stabilization. A review of various types of Power System Stabilizers is presented, with a
concentration on the dual input, integral-of-accelerating-power style of stabilizer.
BASIS FOR STEADY-STATE STABILITY
In an interconnected power system, the rotors of each synchronous machine in the system
rotate at the same average electrical speed. The power delivered by the generator to the
power system is equal to the mechanical power applied by the prime mover, neglecting
losses. During steady state operation, the electrical power out balances the mechanical
power in. The mechanical power input to the shaft from the prime mover is the product of
torque and speed, PM = TM . The mechanical torque is in the direction of rotation. An
electrical torque is applied to the shaft by the generator and is in a direction opposite of
rotation as seen in Figure 1 below.
rotor MMF, F2, and the resultant of the vector addition of the rotor and stator MMFs, R, as
seen in Figure 2 below.
Pe = E g E T sin
Xg
Equation 1: Steady State Electrical Power Output
where is the angle between the generator terminal voltage and the internal voltage of the
machine. As the power transfer increases, the angle increases. A disturbance in the
system can result in a change in electrical power flow, resulting in a change in the power
angle, . This can be seen graphically in Figure 4.
Eg
j IX g
ET
E0 jIXE
inability of the mechanical torque to instantaneously balance out the transient variation in
electrical torque.
exciter system must decrease excitation by applying a high negative voltage to the alternator field as quickly as possible.
system has the potential to contribute to small signal instability of power systems. With
very old electromechanical excitation systems, the transient response was relatively slow
compared to systems introduced today. This slow response has minimal effect in reducing
the damping torque.
SMALL SIGNAL STABILITY
Small signal stability is defined as the ability of the power system to remain stable in the
presence of small disturbances. These disturbances could be minor variations in load or
generation on the system. If sufficient damping torque doesnt exist, the result can be rotor
angle oscillations of increasing amplitude. Generators connected to the grid utilizing high
gain automatic voltage regulators can experience insufficient damping to system oscillations.
To further understand the difference between the good effect of high performance excitation systems and the side effect of reduced damping torque, remember the equation
Positive synchronizing torque can be provided to restore the rotor back to the steady state
operating point if the excitation system can be made to appropriately accelerate or decelerate the rotor. Positive damping torque damps out the rotor oscillations of the torque
angle loop to return the system back to normal. For most power systems, the configuration
of the network and the generator control systems maintains stable damping forces that
restore equilibrium to the power system. In some system configurations, however, unstable
oscillations can result from the introduction of negative damping torques caused by a fast
responding excitation system. This can occur when the system is connected to a high
impedance transmission system as compared to one connected to a low impedance
transmission system.
electrical power will vary around their steady-state operating points. The relationship between these quantities can be expressed in a simplified form of the swing equation:
r
Tm
Te
H
KD
For small deviations in rotor speed, the mechanical and electrical torques are approximately equal to the respective per unit power values. The base value of power is selected
to be equal to the generator nameplate MVA. The swing equation dictates that, when
disturbed from equilibrium, the rotor accelerates at a rate that is proportional to the net
torque acting on the rotor divided by the machines inertia constant.
Equation 3 can be rewritten in terms of small changes about an operating point:
10
12
Convert the measured speed signal into a dc voltage proportional to the speed.
High-pass filter the resulting signal to remove the average speed level, producing a change-in-speed signal. This ensures that the stabilizer reacts only to
changes in speed and does not permanently alter the generator terminal voltage
reference.
Apply phase lead to the resulting signal to compensate for the phase lag in the
closed-loop voltage regulator.
Adjust the gain of the final signal applied to the AVR input.
With some minor variations, many of the early power system stabilizers were constructed
using this basic structure.
DUAL INPUT STABILIZERS
While speed-based stabilizers have proven to be extremely effective, it is frequently difficult
to produce a noise-free speed signal that does not contain other components of shaft
motion such as lateral shaft run-out (hydroelectric units) or torsional oscillations (steamdriven turbogenerators). The presence of these components in the input of a speed-based
stabilizer can result in excessive modulation of the generators excitation and, for the case
of torsional components, in the production of potentially damaging electrical torque variations. These electrical torque variations led to the investigation of stabilizer designs based
upon measured power.
signal can be derived from the net accelerating power acting on the rotor; i.e., the difference between applied mechanical power and generated electrical power. Early attempts at
constructing power-based stabilizers used the above relationship to substitute measured
electrical and mechanical power signals for the input speed. The electrical power signal
was measured directly using an instantaneous watt transducer. The mechanical power
could not be measured directly and instead was estimated, based on the measurement of
valve or gate positions. The relationship between these physical measurements and the
actual mechanical power varies based on the turbine design and other factors, resulting in
a high degree of customization and complexity.
This approach was abandoned in favor of an indirect method that employed the two available signals, namely electrical power and speed. The goal was to eliminate the undesirable components from the speed signal while avoiding a reliance on the difficult-to-measure mechanical power signal. To accomplish this, the relationship of Equation 5 was
rearranged to obtain a derived integral-of-mechanical power signal from electrical power
and speed:
14
The derivation of shaft speed from the frequency of a voltage phasor and a current phasor
is depicted graphically in Figure 17. The internal voltage phasor is obtained by adding the
voltage drop associated with a q-axis impedance (Note: For salient pole machines, the
synchronous impedance provides the required compensation.) to the generator terminal
voltage phasor. The magnitude of the internal phasor is proportional to field excitation and
its position is tied to the quadrature axis. Therefore, shifts in the internal voltage phasor
position correspond with shifts in the generator rotor position. The frequency derived from
the compensated phasor corresponds to shaft speed and can be used in place of a physical measurement. On round-rotor machines, the selection of the correct compensating
impedance is somewhat more complicated; simulations and site tests are normally performed to confirm this setting.
In either case, the resulting signal must be converted to a constant level, proportional to
speed (frequency). Two high-pass filter stages are applied to the resulting signal to remove
the average speed level, producing a speed deviation signal. This ensures that the stabilizer reacts only to changes in speed and does not permanently alter the generator terminal voltage reference. Each high-pass filter is implemented with the following transfer
function where the range of adjustment of the time constant is:
Figure 18 shows the high-pass filter transfer function blocks in frequency domain form (the
letter s is used to represent the complex frequency or Laplace operator).
The first filter, a simple four-pole low-pass filter, was used to provide attenuation
of torsional components appearing in the speed. For thermal units, a time constant can be selected to provide attenuation at the lowest torsional frequency of
the turbogenerator set. Unfortunately, this design requirement conflicts with the
production of a reasonable derived mechanical power signal, which can follow
changes in the actual prime mover output. This is particularly problematic on
hydroelectric units where rates of mechanical power change can easily exceed
10 percent per second. Excessive band-limiting of the mechanical power signal
can lead to excessive stabilizer output signal variations during loading and
unloading of the unit.
The second low-pass filter configuration deals with this problem. This filter,
referred to as a ramp-tracking filter, produces a zero steady-state error to ramp
changes in the input integral-of-electrical power signal. This limits the stabilizer
output variation to very low levels for the rates-of-change of mechanical power
that are normally encountered during operation of utility-scale generators. The
range of adjustment of the filter time constant is:
17
19
20
less than 10MVA each with a combined plant output in excess of 100MVA. The PSS was
applied to the voltage regulator used with a brushless rotating exciter. The AVR in this case
was not a negative forcing type, which, in combination with the non-negative forcing
characteristics typical of brushless rotary exciters, limited the PSSs ability to provide
damping of power oscillations. Additionally, the pulsating nature of the prime mover torque
complicated the settings of the PSS in this application. Eventually the system was
successfully commissioned by using a single input PSS (IEEE model PSS1A) based on
terminal frequency. The before and after graphs shown in Figures 26 and 27 show the
large power variations associated with reciprocating prime movers. The phase
compensation requirements of 30 degrees phase difference between the required
compensation and the PSS phase lead could be met over most of the inter-area frequency
range.
damping of an already well-damped generator. The real test case as the new 600MW plant
became operational. Operational experience indicated that the new PSS performed well in
this application.
Figure 28: Baseline of 1165 MW Generator - 10 second step of 1.0% terminal voltage test
Figure 29: Final Settings of 1165 MW Generator 10 second step of 1.0% terminal voltage test
24
Case 5
Concerns about the phase characteristics of a magnetic amplifier based compound source
excitation system known as an SCT-PPT (Saturable Current Transformer Power Potential
Transformer) has limited the application of PSS to these types of systems. The PSS philosophy is to compensate for the phase lag in the excitation system and field circuit by
adding an equivalent phase lead in the PSS. It was theorized that the phase lag in the
subject excitation system changed with output power, and thus would limit the effectiveness of the PSS to a narrow range of machine loading. The graphs in Figure 30 indicate a
very predictable phase lag (the machines phase lag was plotted as a phase lead, indicating the required compensation).
Figure 30: SCT/PPT Phase Compensation Requirements and PSS Phase Characteristics
Figure 31: Baseline of an SCT/PPT equipped generator - 2% step in terminal voltage test
25
Figure 32: Final Settings of an SCT/PPT equipped generator 2% step in terminal voltage test
The results show a significant improvement in damping by adding a PSS to an SCT/PPT
equipped generator.
CONCLUSION
In this tutorial, we have demonstrated the effects that excitation systems can have on system stability. We discussed transient and steady state stability. A review of various types of
power system stabilizers was presented, and an example of a successful application of a
PSS to a hydro generator has demonstrated the value of modern excitation equipment on
the performance of todays network connected generator systems.
REFERENCES
1.
2.
3.
4.
E. L. Busby, J. D. Hurley, F. W. Keay, and C. Raczkowski, Dynamic Stability Improvement at Montecelllo Station-Analytical Study and Field Tests, IEEE Transaction on Power Apparatus and Systems, Vol.Pas-98, May/June 1979, pp. 889-897.
P. Bingen, G. L. Landgren, F. W. Keay, and C. Raczkowski, Dynamic Stability Test
on a 733 MVA Generator at Kincaid Station, IEEE Transaction on Power Apparatus and Systems, Vol. Pas-93 Sep/Oct 1974 pp. 1328-1334.
F. R. Scheif, R. K. Feeley, W. H. Philips, and R. W. Torluemke, A Power System
Stabilizer Application with Local Mode Oscillations, IEEE Transactions on Power
Apparatus and Systems, Vol. Pas-98, May/June 1979, pp. 1054-1059.
O. W. Hansen, C. J. Goodwin, and P. L. Dandeno, Influence of Excitation and
Speed Control Parameters in Stabilizing Intersystem Oscillations, IEEE Transactions on Power Apparatus and Systems, Vol.Pas-87, May 1968, pp. 1306-1313.
26
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
28
e-mail: info@basler.com
P.A.E. Les Pins, 67319 Wasselonne Cedex FRANCE
Tel +33 3.88.87.1010 Fax +33 3.88.87.0808
e-mail: beifrance@basler.com