Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

TR2000 Ametek

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

F A U L T R E C O R D E R S

TR-2000 Multi-Function Recorder


FOR GENERATION, TRANSMISSION, AND DISTRIBUTION POWER SYSTEM MONITORING

MULTI-FUNCTION RECORDER
For all types of power system events,
the TR-2000 Multi-Function Recorder
provides all the information you need
to capture the complete picture.
With the true integrated functionality
of the TR-2000, you have one place
for all your answers. Simultaneously
perform: transient recording,
disturbance recording, phasor
measurements, power quality
analysis, and sequence of events
recording. The TR-2000 provides
answers when you need them with as
much information as you need to get results quick.
The system can operate automatically to retrieve
events and perform an expert analysis so you have FEATURES AND BENEFITS
the answers fast, saving time and money. The
Very high-speed transient recorderanalyze
TR-2000 Multi-Function Recorder takes the place
switching transients, lightning strikes
of several devices, integrating their functions into
one unit, saving you money on equipment and Transient fault recorderpost fault analysis
installation while providing all the answers in one to verify protection and circuit breaker
software platform. All of these functions are operations, fault clearance times
performed at the highest level so it will meet your Disturbance recorder/loggeranalyze power
needs of today and in the future. In a deregulated system stability by recording reclose
environment, the TR-2000 is the best tool to provide sequences, power swing, and frequency
the necessary data to increase revenues and retain oscillations
your customers.
Trend recordingverify voltage regulation
Optimize your power system to improve reliability, and balancing
shorten your fault clearance times, and verify correct Power quality monitorvoltage and
operation of your switchgear and protection equip- frequency profiles, voltage dips and surges,
ment. The TR-2000 is ideally suited for your genera- loss of supply, harmonic content, flicker,
tion, transmission, and distribution power system voltage and current imbalance
monitoring.
Phasor Measurement Unitsynchronized
The TR-2000 can be matched to any application phasor measurements, in accordance with
with models available for: IEEE STD 1344-1995
8 Analog/16 Digital Inputs
Fault locatorcalculates distance to fault
16 Analog/32 Digital Inputs based on configurable line model
24 Analog/48 Digital Inputs
32 Analog/64 Digital Inputs Real time monitorview analog, digital
inputs, and computed values in near real time
Sequence of events recorder1 msec or
better resolution on digital contacts

POWER INSTRUMENTS

Experience the Power


F A U L T R E C O R D E R S

SPECIFICATIONS
INPUTS distortion and frequency (x2), positive, Synchronization
negative and zero sequence, voltage 1 pulse per second on optical
Number of Channels imbalance port. Any number of systems can
8, 16, 24, or 32 Analog be linked together.
16, 32, 48, or 64 Digital (larger
systems available) RECORDING
Voltage Inputs (DISTURBANCE LOGGING) COMMUNICATIONS
63.5 or 110 V RMS nominal Serial Ports
OPTIONAL Up to 4 x RS232 type
Current Inputs
Sample Rate
1 A or 5 A RMS nominal (thru current Default Setting
shunts/CICTs) 1/2 x supply frequency (25/30 Hz)
57.6 kbaud, 8 bits, 1 stop, no
Frequency Response Recording Time parity. Rates can be set up to 115
DC 1/2 sampling rate 2 weeks (circulating buffer) kbaud.
Accuracy Modem
Better than 0.1% of full scale RECORDING (TREND) Hayes compatible type internal or
external, fax compatible
Digital Inputs Sampling Interval
Phone Line Sharing
24/48/125/250 VDC normally 1 minute, or 10 minutes data can
open or closed wetted contact be retrieved at up to a 60 minute External unit to share a single phone
interval line with a station phone
Record Length Network
RECORDING (TRANSIENT) 52 weeks (circulating buffer) 10Base2 (50 ohm coax and BNC),
Recording Resolution 10baseT, Fiber
Stored Parameters
16 bits, 65536 levels (15 plus sign) Network protocol: TCP/IP
Maximum, minimum, and average
Sample Rate voltage, current, frequency (2),
TR-2100 up to 384 samples power, flicker, harmonics, and DATA STORAGE
per cycle imbalance. Digital data in SER format
at user defined time resolution. Permanent Storage
TR-2200 up to 195 kHz 13 GB Hard Disk
Pre-fault Time
2 to 500 cycles TRIGGERING (TRANSIENT)
Post-fault Time Analog Channels
POWER SUPPLY
Fault length will extend as long as a Over/under RMS level, Rate-of- Input Voltage Options
trigger condition exists. Minimum is Change and THD. Positive, zero and 100 to 300 VDC, 85 to 264 VAC,
8 to 100 cycles negative sequence triggers, over, (optional 85 to 150 VDC, 85 to
Safety Window under and R-o-C frequency triggers, 264 VAC)
Recording time after active trigger: differential frequency Power Requirement
4 to 16 cycles Digital Channels 60VA (16 channel),
Maximum Record Length Normal to alarm state and return to 70VA (32 channel)
Maximum size 1 to 30 sec. (this normal state. Edge or level sensitive.
prevents memory filling with a VOLTAGE WITHSTAND
continuous trigger)
TRIGGERING Isolation, Impulse Voltage, RFI and
(DISTURBANCE) ESD per IEEE/IEC Standards
RECORDING Analog Channels
(DISTURBANCE) Under/over level of fundamental and ENCLOSURE
Sample Rate R-o-C, frequency and ROCOF, power
and frequency oscillation, imbalance Cabinet
2 x supply frequency (100/120 Hz) 8 and 16 channel 6U,
and impedance, cross trigger from
Pre-fault transient recorder 24 and 32 channel 8U
10 sec. to 10 min.
Post-fault Time ENVIRONMENT
Fault length will extend as long as a SYSTEM TIMING
trigger point condition exists. Time Source Operating Temperature
Minimum value is 30 sec. to 5 min. Internal GPS receiver with 1 PPS 14O to 131OF (-10O to 55OC)
Maximum Record output for phasor measurement Relative Humidity
Absolute maximum: 30 minutes Optional IRIG-B 0 to 97% non-condensing
Computed Values Accuracy
Voltage and current, real power, Normally better than +/- 60 ns CERTIFICATION
reactive power, apparent power,
power factor, total harmonic CE

POWER INSTRUMENTS

For customer support call:


POWER INSTRUMENTS HEADQUARTERS EUROPEAN HEADQUARTERS ASIA PACIFIC HEADQUARTERS
255 North Union Street AMETEK Power Instruments Unit 15, Lisburn Enterprise Centre 10 Ang Mo Kio Street 65
Rochester, NY 14605 50 Fordham Road Ballinderry Road #05-12 Techpoint
Tel: 585.263.7700 Wilmington, MA 01887 Lisburn, Co Antrim, UK BT282BP Singapore 569059
Fax: 585.454.7805 Tel: 978.988.4903 Tel: 44.28.9260.4100 Tel: 65.484.2388
power.sales@ametek.com Fax: 978.988.4990 Fax: 44.28.9260.4141 Fax: 65.481.6588
power.sales@ametek.com sales@ametekuk.com

ISO 9001 Certified


2007, by AMETEK, Inc. All rights reserved. 2.5M507A (210036)