Cable Catalogue

Download as pdf or txt
Download as pdf or txt
You are on page 1of 50

LT/HT Power &

Control Cables

Catalogue 2009
HT Power
n Cables upto 33 kV
1.1 kV
n Power Cables
1.1 kV Copper Control Cables
n
Certification

ISO-9001
Cer tified

"Building customer confidence by providing a wide range


of quality products and services through team work".
Index

Introduction
Manufacturing Process .............................................................................................................. 1
Manufacturing of Cables............................................................................................................. 2
Advantages................................................................................................................................ 3
Cable ranges at a glance............................................................................................................ 4,5

Technical detail for


1.1 kV Single Core, PVC Insulated, Un-armoured Cables........................................................... 6
1.1 kV Two Core, PVC Insulated, Un-armoured Cables.............................................................. 7
1.1 kV Three Core, PVC Insulated, Un-armoured Cables............................................................ 8
1.1 kV Three & Half Core, PVC Insulated, Un-armoured Cables.................................................. 9
1.1 kV Four Core, PVC Insulated, Un-armoured Cables............................................................. 10

Technical detail for


1.1 kV Single Core, PVC Insulated, Armoured Cables................................................................ 11
1.1 kV Two Core, PVC Insulated, Armoured Cables.................................................................... 12
1.1 kV Three Core, PVC Insulated, Armoured Cables................................................................. 13
1.1 kV Three & Half Core, PVC Insulated, Armoured Cables....................................................... 14
1.1 kV Four Core, PVC Insulated, Armoured Cables................................................................... 15

Technical detail for


1.1 kV 1.5 sq. mm Copper Cond. PVC Insulated, Armoured Cables........................................... 16
1.1 kV 2.5 sq. mm Copper Cond. PVC Insulated, Armoured Cables........................................... 17

Technical detail for


1.1 kV Single Core, XLPE Insulated, Un-armoured Cables ........................................................ 18
1.1 kV Two Core, XLPE Insulated, Un-armoured Cables ............................................................ 19
1.1 kV Three Core, XLPE Insulated, Un-armoured Cables ......................................................... 20
1.1 kV Three & Half Core, XLPE Insulated, Un-armoured Cables ............................................... 21
1.1 kV Four Core, XLPE Insulated, Un-armoured Cables ........................................................... 22

Technical detail for


1.1 kV Single Core, XLPE Insulated, Armoured Cables .............................................................. 23
1.1 kV Two Core, XLPE Insulated, Armoured Cables ................................................................. 24
1.1 kV Three Core, XLPE Insulated,Armoured Cables................................................................ 25
1.1 kV Three & Half Core, XLPE Insulated,Armoured Cables...................................................... 26
1.1 kV Four Core, XLPE Insulated, Armoured Cables ................................................................. 27

Technical detail for


3.3 kV Single Core, XLPE Insulated, Armoured Cables .............................................................. 28
3.3 kV Three Core, XLPE Insulated, Armoured Cables ............................................................... 29

Technical detail for


3.8/6.6 kV Single Core, XLPE Insulated, Armoured Cables ........................................................ 30
3.8/6.6 kV Three Core, XLPE Insulated, Armoured Cables ......................................................... 31

Technical detail for


6.6/6.6 kV& 6.35/11Kv Single Core, XLPE Insulated, Armoured Cables ..................................... 32
6.6/6.6 kV& 6.35/11Kv Three Core, XLPE Insulated, Armoured Cables ...................................... 33

Technical detail for


11/11kV Single Core, XLPE Insulated, Armoured Cables ........................................................... 34
11/11kV Three Core, XLPE Insulated, Armoured Cables ............................................................ 35

Technical detail for


12.7/22 kV Single Core, XLPE Insulated, Armoured Cables ....................................................... 36 ISI & CM/L Nos.
12.7/22 kV Three Core, XLPE Insulated, Armoured Cables ........................................................ 37
IS:1554 (Part-1), 1988
Technical detail for CM/L No.: 81579 82
19/33 kV Single Core, XLPE Insulated, Armoured Cables .......................................................... 38
19/33 kV Three Core, XLPE Insulated, Armoured Cables ........................................................... 39 IS:1554 (Part-2), 1988
CM/L No.: 82594 85
Basic assumption for current ratings & rating factors .................................................................. 40,41
Selection criteria of M/VHV cable size for primary distribution ..................................................... 42 IS:7098 (Part-1), 1988
Standard Drum lengths of Cables ............................................................................................... 43 CM/L No.: 81896 92
Quality Control & Test ................................................................................................................ 44
Selection Guide ......................................................................................................................... 45 IS:7098 (Part-2), 1985
Handling & Storage .................................................................................................................... 46 CM/L No.: 83683 89
Introduction

Havells India Ltd., a billion-dollar-plus organization and one of the largest & India's fastest growing electrical and
power distribution equipment manufacturer with products ranging from Industrial & Domestic Circuit Protection
Switchgear, Cables & Wires, Motors, Fans, Power Capacitors, CFL Lamps, Luminaires for Domestic, Commercial &
Industrial applications, Modular Switches & Bathfittings covering the entire gamut of household, commercial and
industrial electrical needs.

Havells owns some of the prestigious global brands like Crabtree, Sylvania, Concord, Luminance, Linolite & SLI
Lighting.

With 91 branches / representative offices and over 8000 professionals in over 50 countries across the globe, the
group has achieved rapid success in the past few years. Its 7 state-of-the-art manufacturing plants in India located at
Haridwar, Baddi, Noida, Faridabad, Bhiwadi, Alwar, Neemrana, and 9 state-of-the-art manufacturing plants located
across Europe, Latin America & Africa churn out globally acclaimed products. Havells is a name synonymous with
excellence and expertise in the electrical industry. Its 20000 strong global distribution network is prompt to service
customers.

The company has acquired a number of International certifications, like BASEC, CSA, KEMA, CB, CE, ASTA, CPA,
SEMKO, SIRIUM (Malaysia), SPRING (Singapore), TSE (Turkey), SNI (Indonesia) and EDD (Bahrain) for various
products. Today, Havells and its brands have emerged as the preferred choice of electrical products for discerning
individuals and industrial consumers both in India and abroad.

The essence of Havells success lies in the expertise of its fine team of professionals, strong relationships with
associates and the ability to adapt quickly and efficiently, with the vision to always think ahead.

Inner view - Cable Factory Pay-off CCV Line

Testing Laboratory

16 Drawing Wire Machine Triple Head Extrusion Line


Manufacturing Process

Copper or
Aluminium Rods

Wire Drawing Wire to be drawn for required size

Annealing Drawn Copper wires are annealed

Required conductor size to be


Stranding
manufactured with specified design

Stranded conductors are screened with extruded


Conductor Screening semiconducting compound (Applicable for H.T.
Screened cable only)

Conductor to be Insulated with PVC /


Insulation XLPE as per required specification.

Insulated cores are screened with extruded


Insulation Screening semiconducting compound (Applicable for H.T.
(Non metallic part)
Screened cables only)
L.T. Unscreened Cables
H.T. Screened Cables

Cores to be rewound & cured with specified requirement


Core Rewinding & Curing
(for P.V.C. Cables curing not required).

Copper tape shall be applied hellically with 100%


Insulation Screening coverage over screened cores ( Applicable for H.T.
(Metallic Part)
Screend core only)

Laying Up All rewound cores to be arranged together to from a Cable


with Specified design.

Inner Sheathing To be done with required specification

Armouring To be done with required specification.

Outer Sheath To be done with required specification.

All cables are rewound on wooden Drums & tests Carried-


Rewinding & Testing
out as per required specification

Packing All tested and passed cables are packed in required sized
drums prior to despatch.

1
Manufacturing of Cables
Cables with Aluminium and Copper conductor and polymer insulation are manufactured at Havells India Ltd. (Cable Works) Alwar. Essentially
cables comprise of conductors, insulation, inner-sheath, armour and outersheath. The brief description of the process is mentioned as under:

CONDUCTOR improving electrical treeing characteristics and mechanical


Havells Cables are available with both aluminum and copper strength of insulation.
conductors. It is manufactured with solid/Stranded Circular/ Havells cables are friendly during continuous, emergency and short
Shaped Aluminium / Copper Conductor. Stranding makes Cables circuit conditions.
flexible and easy to handle while shaping makes them compact. Though there is no change in basic design of Havells cables yet the
Compaction is provided to all stranded conductor constructions latest manufacturing process gives improved reliability and
as under: compactness to cables. The relative thermal expansion during

1. Circular Conductor With one wire in the centre conductor short circuit between dielectric and conductor is therefore limited to
minimum both in PVC & XLPE, thus limiting displacement of cores
contains 6, 12, 18, 24, 30... wire layers in either unilay or
in cables during short circuit.
opposite helical directions. The conductor is sized upto 92%
Insulation for Havells Cables are strictly manufactured and applied
compaction.
over conductor in accordance with National and International
2. Shaped Conductors In all multicore cables from
specifications:
16 Sq. mm size, conductors are “shaped”. Compaction
National Specification IS:5831/IS:7098
degree in multicore power cables is upto 92%.
International Specifications BS:6746/BS:5467/IEC:60502
3. Segmental Conductor As a special case Havells cables of
1600 sq. mm are made up of segmental conductors. SCREENING
The conductor is manufactured in equal segments and XLPE Cables with rated voltage over 3300V shall be provided with
compacted, then laid together. This reduces A.C. losses in the conductor and insulation screening as follows:
large sized conductor, which are due to skin and proximity effects. Conductor Conductor shall be screened with extruded
Havells has special construction of conductor to suggest to its Screen Semiconducting compound as per is:7098 part 2.
customer for meeting their specific need. Insulation Insulation screening shall consist of non-metalic
Havells copper conductor cables are of the same construction Screen Part in combination with metalic part. Non metalic
that of cables with Aluminium conductor except for high tensile part shall consist of either semi conducting
strength, superior conductivity, better flexibility and ease of compound tape applied hellically or extruded layer of
jointing, copper cables are used in control, instrumentation, semi conducting compound, applied directly over
winding, submarine, mining and ship wiring etc. etc applications. insulation. Over this, metalic part (copper tape)
shall be applied hellically with overlap as per IS:7098
All conductors for Havells cables are manufactured strictly in
part 2.
accordance with National and International specifications.
To avoid the cavities and voids formation in dielectric particularly on
National specifications IS:8130
bending operation of cable, perfect bonding of insulation and
International specification IEC:60228 / BS:6360
screening is required. To ensure this Havells applying conductor
DIELECTRIC INSULATION screen, insulation and insulation screen (non-metalic part) in one
Insulation for Havells cables is strictly as per National and operation through tripple extrusion.

International specifications. LAYING UP


Havells cables are designed and manufactured with polymer Cores are tested on line during production both for physical and
dielectrics to bear thermal and thermomechanical stresses safely electrical characteristics. Control is observed within tight tolerance
at continuous normal and short circuit temperature conditions. limits for dimensions in case pf PVC/XLPE insulation. For multicore
Havells cables are available with both thermoplastic & thermo cables cores are laid up on our latest laying up machine equipped
setting insulations. with sector correction equipment. In case of XLPE insulated cores
- PVC Cables Thermoplastic dielectric the same are cured so as to impart the requisite characteristics

- XLPE Cables Thermo setting dielectric both electrical and mechanical and then are laid up.

Havells PVC cables use PVC compounds that take care of over INNERSHEATH
load and short circuit current with both coarse & fine protection Laid up cables are provided with inner sheath with high quality of
systems. PVC which acts as bedding for steel wire / strip armouring.
Havells XLPE cables use XLPE compound with anti oxidant Wherever required, filler cords are provided to maintain the
stabilizers and traces of aromatic polynuclear hydrocarbon. Thus circularity to laid up cables.

2
Advantage
In Havells Cable-polymers used for inner sheath are softer than FINAL TESTING
insulation or outer sheath & are compatible with temperature Each Havells Cable is tested for all applicable Routine Tests.
ratings of cables & do not have deleteriocus effect on any other From a lot of Cable one cable of each type is tested for Type tests,
component of cable. as per relevant specifications.
Inner sheath is applied either with extrusion or by wrapping. In Havells conduct its testing at Havell’s India Ltd. cable plant at
Havells Cables though the inner sheath is closely applied on the Alwar for acceptance test as per specification.
laid up cores, same can be stripped with ease without damaging
Testing of Havells Cables are carried out as per Havells Work
insulation.
Standards for testing, besides applicable standards.
The inner sheath dimensions are maintained strictly in accordance
with laid down specification . ADVANTAGES OF PVC CABLES
Specification For PVC Cables IS:1554 (Part-I & II) 1. A non-hygroscopic insulation almost unaffected by moisture.
For XLPE Cables IS:7098 (Part-I & II) 2. Non-migration of compound permitting vertical installation.

ARMOURING 3. Complete protection against most forms of electrolytic and


chemical corrosion.
Mechanical protection to the cable is provided with armouring.
4. A tough and resilient sheath with excellent fire - resisting
Havells single core cables are armoured with Aluminium or
qualities.
Aluminium alloy wire/strips, thus avoiding magnetic hysteresis
losses on A. C. System. 5. Good ageing characterstics.

Multicore cables are provided with galvanised steel wire/strips. 6. Not affected by vibration.
Havells cables are provided with galvanised wire armouring, where ADVANTAGES OF XLPE CABLES
cables are to run vertically and are subjected to stresses.
1. Higher Current Rating.
Havells Mining cables are armoured with steel wire and tinned
2. Higher Short Circuit Rating.
copper wires, so as to provide conductivity of armour more than
3. Longer Service Life.
75% of main conductor of cable.
Havells cables armour wires/strips are of low resistivity material 4. For a short time it can withstand maximum 130oC and is
favourable to endure short circuit stresses.
and meet the requirements of IS:3975.
Havells armoured cables are with almost 95% armour coverage. 5. It is less sensitive to the setting of the network protection.
6. Because of the thermosetting process taking place due the
OUTER SHEATH
effect of cross linking, the crack resistance is increased.
All Havells Cables are provided with PVC/polymer outer sheath.
7. Due to the chemical cross-linking internal stresses are
Havells Cables are manufactured with various characteristics of reduced. Consequently the material is less sensitive
sheathing compounds. during manufacturing process to the setting of the cooling
General purpose sheathing Compound ST1 gradient.
Heat resistant Compound for sheath (H.R.) ST2 8. The thermal resistivity of cross-linked material is favourably
Fire Retardant Low IEC 754 Part I low, compared to thermoplastic material.

Smoke Compound IEC 60332 Part I& III 9. The low dielectric loss is a significant advantage.

(FRLS) IEEE-383 10. The excellent mechanical features of the insulation improves
ASTM-2843 the protection against external effects.

ASTM-2863 11. The resistance of the XLPE to acids, alkalies is outstanding


and is often compensating the adverse environmental
Flame Retartant Compound (FR) to EIL Specn.
influences.
Ultra Voilet Radiations Resistance Compound to ASTM G-53.
Anti Rodent and Anti Termite Compound.
PVC compounds used for Havells Cables are of various grades to
meet specifications IS: 5831.
In order to be identified, Havells Cables have their name
embossed/printed/indented on outersheath at regular intervals on
the outer sheath of Havells Cables, Voltage Grade, cable size,
trade name & year of manufacture are embossed, as desired.
Cables are sequentially marked for length at every metre
throughout its length.

3
Cable range at a glance
Application Type & Size Options Cross Sectional View

Cables for Power PVC/XLPE Power cables for 1.1 Conductor - Stranded / Solid, Circular /
Supply to Residential, & 3.3 kv for Electrical Substations Shaped Aluminium / Copper Outer-Sheath

Commercial & as per IS:1554 - I & 2 Insulation - PVC / HR PVC Armouring

Industrial units Sizes: Inner Sheath - PVC / HR PVC / FRLS / PVC Inner-Sheath
Single Core 10-1000 sq. mm Insulation
Multicore 6-630 sq. mm Unarmoured / Armoured - G.S. Round Wire/ Aluminium /
Flat Strip or Aluminum Wire / Flat Strip Copper Conductor

Outer Sheath - PVC/ HR PVC/ FRLS PVC

PVC Outer-Sheath
Heavy Duty XLPE XLPE Power cables Conductor - Circular/Shaped - Aluminum/Copper Armouring
Power cables for upto 19/33 kv grade 33 kv (E) Insulation - XLPE PVC Inner-Sheath
Filler
Power Generation as per IS:7098 - I & II Innersheath - PVC / HR PVC / FRLS
Stranded Conductor
Distribution Sizes : Unarmoured / Armoured - G.S Round Wire / Conductor Screening

Single Core : 25 - 1000 sq. mm Flat Strip or Aluminum Wire / Flat Strip XLPE Insulation
Insulation Screening
Multicore : 25 - 400 sq. mm Outersheath - PVC / HR PVC / FRLS Metallic Screening

Heavy Duty copper Stranded bright annnealed Conductor - Circular / Shaped Outer-sheath

cables for Coal Mines electrolytic copper conductor, PVC/ Insulaton - PVC / XLPE Armour (outer layer)
Seprator (PVC tape)
XLPE insulated / PVC sheathed Innersheath- PVC / HR PVC / FRLS Armour (inner layer)
upto and including 3.3 kv as per Unarmoured/Armoured- Round Wire/Flat Strip Inner-Sheath
IS: 1554 - I&II / IS: 7098 - I & II with conductivity not less than 75% of the phase Insulation

Sizes : Conductor Conductor

Multicore 25 to 400 sq. mm Outer Sheath - PVC/ HR PVC / FRLS

Arial Bunched / PE/XLPE insulated 1.1 kv to 33 kv Conductor - Stranded Circular compacted


Bundled required as per IS:14255 & IS:7098-II Aluminium Outer Sheath
for over head power Insulation - PE/XLPE Cu Tape Screening

distribution Messenger conductor - All Aluminium Alloy-Bare/ Insulation Screening


XLPE Insulation
Insulated Conductor Screening

Street Light Cond. - Stranded Circular Conductor

Compacted Aluminium, Bare/Insulated AAA


Messenger
Conductor

Copper Control Annealed electrolytic copper Conductor - Solid/Stranded, Plain /Tinned


Cables for Power conductor, PVC/XLPE insulated, Insulation - PVC/HR PVC/XLPE
Outer Sheath
Switch yard Control / PVC sheathed 650/ 1100V Innersheath - PVC/HR PVC/FRLS/Zero Halogen Armour
Relay Equipment grade as per IS: 1554-I & IS: 7098-I Unarmoured / Armoured - G.S. Round Wire/ Inner Sheath
Sizes : Flat Strip Conductor

1.5 / 2.5 sq. mm upto 61 core Outersheath - PVC/HR PVC/FRLS/Zero Halogen Insulation

4 & 6 Sq. mm upto 4 core Additional Option : Overall shielding with


Aluminum mylar tape with 100% coverage & 25%
overlap on laid up cores for static noise rejection.

Railway Signaling Annealed Bare Copper conductor, Screened/Unscreened - Aluminum mylar tape Outer Sheath
Cables PVC insulated cores laid up PVC Unarmoured/Armoured - G.S. Round Wire / Armour
sheath as per IRS-S-63/89 RDSO Flat Strip/Galvanised Tape Inner Sheath

& related specifications Additional Option : Conductor

Sizes : Insulation/Inner/Outer Sheath - PVC Insulation

1.5 & 2.5 sq. mm upto 61 core Inner/Outer sheath - PVC


4 & 6 sq. mm upto 4 core

Telecom / Switch Annealed Copper conductor, Conductor - Tinned / Plain


board cables for PVC Insulated as per DOT TEC Insulation - PVC / HR PVC / Nylon Outer Sheath
Indoor Telephones Spec No: G/WIR-06/02 Innersheath - PVC/ HR PVC/ FRLS Zero Halogen Armour

Sizes : Unarmoured / Armoured - G.S. round wire / Inner Sheath


Bedding Tape
0.4 / 0.5 / 0.6 / 0.7 / 0.9 mm Flat Strip Conductor
Outer sheath - PVC/HR PVC/FRLS Insulation
AdditIonal Option - Individual / Overall pair/ Twisted Pair

Shielding / Screening Filler

Coaxial cables for Available in specified RG Conductor - Plain / Tinned / Copper Clad Steel /
Telcom / Microwave / & UR Series as per MIL-C-17 / Silver Plated P.E. Insulation

CATV / MATV BS: 2316 / IS: 5608 / IS: 11967 Insulation - Solid / Foam / Semi air spaced
Sheath
industry Sizes : Screen - Single / Double braid
Suitable for Impedance Sheath - PVC / HR PVC / FRLS / P.E
of 50 / 75 / 100 / 125 ohms Braid

Flat cables for Stranded Plain copper, PVC Insulation - PVC / HR PVC
Submersible insulated & PVC sheathed of Sheathing - PVC / HR PVC Insulation

Pumps & Motors 1.1kV grade as per IS: 694 Conductor

Sizes :
Sheath
3 core - 1.5 to 50 sq. mm

4
Cable range at a glance
Application Type & Size Options Cross Sectional View

Instrumentation PVC Sheathed 225/650/ Conductor - Standed / Solid, plain / tinned Drain Wire
Signal Cables for 1100 V grade cables as per Insulation - PVC / HR PVC / P.E / Zero Halogen Outer Sheath
Armour
Process control & BS: 5308 / DIN VDE 0815 & Shielding - Individual Pair / over all pairs Inner Sheath
Instrumentation 816 / IS: 1554 / IEC: 189 Drain wire - Solid Stranded Drain Wire

Sizes : Innersheath - PVC / HR PVC Individual Pair Shield

Conductor
0.5/0.75/1.0/1.5 sq. mm Zero Halogen Insulation
Unarmoured/Armoured-G.S. Round Wire, Flat
Strip Outersheath - PVC / HR PVC/ FRLS /
Zero Halogen

Flexible & Cord Multistrand, flexible, bright Insulation - PVC / HR PVC / FRLS /
Cables for annealed electrolytic copper Zero Halogen Conductor

appliances, Machine conductor, PVC insulated and Unsheathed /Sheathed - PVC / HR PVC / Insulation

Tools & Equipment sheathed upto 1100V as per IS:694 FRLS / Zero Halogen Filler

Wiring Sizes : Sheath

Single, Two, Three or


Four core upto 25 sq. mm

Wiring Cables for Multistrand Flexible, upto 1100V Conductor - Bright Annealed Copper Insulation
electrical industry grade PVC Cables as per IS: 694 Insulation - PVC/ HR PVC/ FRLS PVC /
Sizes : Zero Halogen
Conductor
Single core 1.0 - 630 sq. mm

Energy Cables PVC Flexible Cables upto 1.1kv Conductor - Stranded / Solid bright
for Power Supply to grade as per IS:694 annealed Copper
Color Skin
Telephone Sizes : Insulation - PVC / HR PVC / FRLS /
Exchanges / UPS / 1.0 upto 240 sq. mm Zero Halogen Natural PVC

Battery Backup / Single / Multi Core Multistrand Flexible


Equipments Copper Conductor

Air Field Lighting Stranded plain annealed copper, Insulation - PVC / XLPE
Cables PVC insulated & PVC
Insulation
sheathed of 5 kV grade
Sizes : Conductor

Single core 6 /16 sq.mm Sheath


and 2 x 6, 16 & 25

Inside View - Cable Factory

5
Table -1 TECHNICAL DETAIL FOR HAVELLS 1.1 KV SINGLE CORE,
AL/COPPER COND., PVC INSULATED, UN-ARMOURED CABLES
Cable Code : AYY/YY Ref. Spec. : IS :1554Part-1
Physical Parameters
SIZE Minimum Nominal Nominal Approx. Approx. Weight of cable in kg /km
cross-sectional No of Strand in Thickness of Thickness of Overal
area ( Sq MM) Conductor Insulation) outer sheath Diameter With Al Conductor With Cooper conductor
Al Cu (mm) (mm) (mm) AYY YY
4 — 1/7 1.0 1.8 8 80 105
6 1 1/7 1.0 1.8 9 100 135
10 1 6 1.0 1.8 10 120 180
16 6 6 1.0 1.8 11 160 260
25 6 6 1.2 1.8 13 210 365
35 6 6 1.2 1.8 14 250 460
50 6 6 1.4 1.8 16 300 610
70 12 12 1.4 1.8 17 400 830
95 15 15 1.6 1.8 19 500 1100
120 15 18 1.6 2.0 21 600 1350
150 15 18 1.8 2.0 23 750 1680
185 30 30 2.0 2.0 25 900 2050
240 30 34 2.2 2.0 28 1100 2600
300 30 34 2.4 2.0 30 1350 3200
400 53 53 2.6 2.2 35 1700 4200
500 53 53 3.0 2.2 38 2150 5250
630 53 53 3.4 2.4 43 2750 6650
800 53 53 3.4 2.4 48 3300 8250
1000 53 53 3.4 2.6 52 4100 10300

Cross-sectional view
1 CONDUCTOR : Material - Aluminium /Copper
*Shape : ~AL . Cond :- 6 & 10 SQMM -Solid circular, 16 sq.mm & above : Stranded compacted circular
~Copper. Cond :- 4 & 6 sq. mm-solid/ stranded non compacted circular, 10 sq. mm & above : Stranded compacted circular
2
INSULATION : PVC Type A of IS:5831 / OPTION: HR PVC (Type-C of IS-5831), Colour : Black
3 OUTER SHEATH : PVC TYPE ST-1 OF IS : 5831 ‘— OPTIONS : PVC Type ST-2 of IS:5831/ FR TYPE/FRLS TYPE
COLOUR OF OUTER SHEATH : BLACK . OPTIONS : any other colour as per requirement.
- Tabulated approx. net wt. of cables are only guidelines for transportation, loading & unloading purpose..
- Please ref page no 43 for normal delivery lengths & packing details.

Electrical Parameters
SIZE Max. Cond. D.C. Approx. Cond. A.C. App. Reactance App. Capecitance Normal* Current Rating in Amps Short Circuit Current
cross-sectional Resistance at Resistance at at 50HZ of cable With Aluminium cond. With Copper cond. Rating for 1Sec.duration
area (Sq MM) 20oCin Ohm/km 70oC in Ohm/km in ohms/km in microF/KM Ground Duct Air Ground Duct Air in K. Amps
Al Cu Al Cu Al Cu
4 — 4.61 — 5.53 0.140 0.58 — — — 39 38 35 0.304 0.460
6 4.61 3.08 5.53 3.70 0.127 0.68 39 37 35 49 48 44 0.456 0.690
10 3.08 1.83 3.70 2.20 0.118 0.83 51 51 47 65 64 60 0.760 1.150
16 1.91 1.15 2.29 1.38 0.110 1.01 66 65 64 85 83 82 1.220 1.84
25 1.20 0.727 1.44 0.87 0.105 1.05 86 84 84 110 110 110 1.900 2.88
35 0.868 0.524 1.04 0.63 0.100 1.22 100 100 105 130 125 130 2.660 4.03
50 0.641 0.387 0.769 0.464 0.098 1.22 120 115 130 155 150 165 3.800 5.75
70 0.443 0.268 0.532 0.322 0.091 1.43 140 135 155 190 175 205 5.320 8.05
95 0.320 0.193 0.384 0.232 0.088 1.47 175 155 190 220 200 245 7.220 10.90
120 0.253 0.153 0.304 0.184 0.086 1.62 195 170 220 250 220 280 9.120 13.80
150 0.206 0.1240 0.247 0.1488 0.085 1.62 220 190 250 280 245 320 11.40 17.30
185 0.164 0.0991 0.197 0.1189 0.084 1.62 240 210 290 305 260 370 14.10 21.30
240 0.125 0.0754 0.151 0.0912 0.082 1.72 270 225 335 345 285 425 18.20 27.30
300 0.100 0.0601 0.122 0.0733 0.080 1.74 295 245 380 375 310 475 22.80 34.50
400 0.0778 0.0470 0.0961 0.0580 0.080 1.81 325 275 435 400 335 550 30.40 46.00
500 0.0605 0.0366 0.0759 0.0459 0.079 1.86 345 295 480 425 355 590 38.00 57.50
630 0.0469 0.0283 0.0610 0.0368 0.077 1.87 390 320 550 470 375 660 47.90 72.50
800 0.0367 0.0221 0.0503 0.0303 0.077 1.98 450 380 610 530 425 725 60.80 92.00
1000 0.0291 0.0176 0.0422 0.0255 0.076 2.20 500 415 680 590 740 870 76.00 115.00
Note : Normal current ratings are given in standard conditions (as given in page no 40,41), if site conditions are different, current rating should be multiplied by
rating factor as given in page no. 42

6
Table -2 TECHNICAL DETAIL FOR HAVELLS 1.1 KV TWO CORES,
AL/ COPPER COND., PVC INSULATED, UN-ARMOURED CABLES
Cable Code : AYY/ YY Ref. Spec. : IS:1554 Part -1
Physical Parameters
SIZE Cross- Minimum No of Nominal Minimum Nominal thick. Approx. Approx. Net Wt
-sectional Strands in Thickness of thickness of of OUTER Overall of cable ( Kg/KM)
area Conductor Insulation) inner Sh. Sheath Diameter With Al cond With Cu Cond.
( sqmm) Al Cu (mm) (mm) (mm) (mm) AYY YY
4 — 1/7 1.0 0.30 1.80 14 240 290
6 1 1/7 1.0 0.30 1.80 17 300 370
10 1 6 1.0 0.30 1.80 18 400 520
16 6 6 1.0 0.30 1.80 17 430 630
25 6 6 1.2 0.30 2.00 19 450 750
35 6 6 1.2 0.30 2.00 21 550 980
50 6 6 1.4 0.30 2.00 24 700 1300
70 12 12 1.4 0.30 2.00 26 850 1700
95 15 15 1.6 0.40 2.20 30 1150 2300
120 15 18 1.6 0.40 2.20 32 1300 2800
150 15 18 1.8 0.40 2.40 34 1600 3450
185 30 30 2.0 0.50 2.40 38 2000 4300
240 30 34 2.2 0.50 2.60 42 2500 5500
300 30 34 2.4 0.60 2.80 46 3000 6700
400 53 53 2.6 0.70 3.20 52 3800 8750
500 53 53 3.0 0.70 3.40 54 4800 11000
630 53 53 3.4 0.70 3.80 65 6000 13800

Cross- Sectional View


1 CONDUCTOR : Material - Aluminium /Copper
*Shape : ~AL . Cond :- 6 & 10 SQMM -Solid circular, 16 sqmm & above : Stranded compacted shaped
~ Copper. Cond :- 4 & 6sqmm -solid/ stranded non compacted circular, 10sqmm : Stranded compacted circular,16sqmm & above : Stranded compacted shaped
2 INSULATION : PVC Type A of IS :5831/ OPTION : HR PVC ( Type -C of IS -5831), Colour : Red & Black
3 INNER SHEATH : PVC as per IS :1554PT-1
4 OUTER SHEATH : PVC TYPE ST-1 OF IS : 5831 ‘— OPTIONS : PVC TYPE ST-2 OF IS : 5831/ FR TYPE/ FRLS TYPE
COLOUR OF OUTER SHEATH : BLACK . OPTIONS : any other colour as per requirement.
~ Tabulated approx. net wt. of cables are only guidelines for transportation, loading &unloading purpose.
~ Please ref page no 43 for normal delivery lengths & packing details.

Electrical Parameters
SIZE Max. Cond. D.C. Approx. Cond. A.C. App.Reactance App.Capecitance Normal* Current Rating in Amps Short Circuit Current
cross-sectional Resistance at Resistance at of cable at 50HZ of cable With Aluminium cond. With Copper cond. Rating for 1Sec.duration
area (Sq MM) 20oC in Ohm/km 70oC in Ohm/km in ohms/km in microF/KM Ground Duct Air Ground Duct Air in K. Amps
Al Cu Al Cu Al Cu
4 — 4.61 — 5.53 0.098 0.23 32 27 27 41 35 35 0.304 0.460
6 4.61 3.08 5.53 3.70 0.096 0.28 40 34 35 50 44 45 0.456 0.690
10 3.08 1.83 3.70 2.20 0.091 0.34 55 45 47 70 58 60 0.760 1.150
16 1.91 1.15 2.29 1.38 0.085 0.40 70 58 59 90 75 78 1.220 1.840
25 1.20 0.727 1.44 0.87 0.083 0.42 90 76 78 115 97 105 1.900 2.880
35 0.868 0.524 1.04 0.63 0.082 0.48 110 92 99 140 120 125 2.660 4.030
50 0.641 0.387 0.769 0.464 0.082 0.49 135 115 125 165 145 155 3.800 5.750
70 0.443 0.268 0.532 0.322 0.076 0.56 160 140 150 205 180 195 5.320 8.050
95 0.320 0.193 0.384 0.232 0.076 0.58 190 170 185 240 215 230 7.220 10.90
120 0.253 0.153 0.304 0.184 0.075 0.63 210 190 210 275 235 265 9.120 13.80
150 0.206 0.1240 0.247 0.1488 0.074 0.63 240 210 240 310 270 305 11.40 17.300
185 0.164 0.0991 0.197 0.1189 0.074 0.64 275 240 275 350 300 350 14.10 21.280
240 0.125 0.0754 0.151 0.0912 0.073 0.67 320 275 325 405 345 410 18.20 27.600
300 0.100 0.0601 0.122 0.0733 0.073 0.68 355 305 365 450 385 465 22.80 34.500
400 0.0778 0.0470 0.0961 0.0580 0.072 0.70 385 345 420 490 485 530 30.40 46.000
500 0.0605 0.0366 0.0759 0.0459 0.072 0.70 425 380 475 540 460 605 38.00 57.500
630 0.0469 0.0283 0.0610 0.0368 0.072 0.70 465 415 540 640 550 785 47.90 72.550
Note : Normal current ratings are given in standard conditions (as given in page no 40,41) , if site conditions are different, current rating should be multiplied by
rating factor as given in page no. 42

7
Table -3 TECHNICAL DETAIL FOR HAVELLS 1.1 KV
THREE CORES, AL/COPPER COND., PVC INSULATED, UN-ARMOURED CABLES
Cable Code : AYY/ YY Ref. Spec. : IS :1554PART -1
Physical Parameters
SIZE Cross- Minimum No of Nominal thick. Minimum Nominal thick. Approx. Approx. Net Wt
-sectional Strands in Thickness of thickness of of outer Overall of cable ( Kg/KM)
area Conductor Insulation) inner Sh. Sheath Diameter With Al cond With Cu Cond.
( sqmm) Al Cu (mm) (mm) (mm) (mm) AYY YY
4 — 1/7 1.0 0.30 1.80 16 270 340
6 1 1/7 1.0 0.30 1.80 18 360 470
10 1 6 1.0 0.30 1.80 19 440 650
16 6 6 1.0 0.30 1.80 19 460 730
25 6 6 1.2 0.30 2.00 22 620 1080
35 6 6 1.2 0.30 2.00 24 740 1400
50 6 6 1.4 0.30 2.00 27 940 1870
70 12 12 1.4 0.40 2.20 30 1200 2500
95 15 15 1.6 0.40 2.20 34 1600 3350
120 15 18 1.6 0.40 2.20 37 1900 4100
150 15 18 1.8 0.50 2.40 40 2300 5100
185 30 30 2.0 0.50 2.60 44 2750 6200
240 30 34 2.2 0.60 2.80 50 3500 7950
300 30 34 2.4 0.60 3.00 55 4300 9900
400 53 53 2.6 0.70 3.40 62 5450 12800
500 53 53 3.0 0.70 3.60 69 6900 16200
630 53 53 3.4 0.70 4.00 77 8700 20400

Cross-sectional View
1 CONDUCTOR : Material - Aluminium /Copper
*Shape : ~AL . Cond :- 6 & 10 sqmm - Solid circular, 16 sqmm & above : Stranded compacted shaped
~Copper . Cond :- 4 & 6 sqmm-solid/ stranded non compacted circular, 10 sqmm : Stranded compacted circular,16sqmm & above : Stranded compacted shaped
2 INSULATION : PVC Type A of IS :5831/ OPTION : HR PVC ( Type -C of IS -5831), Colour : Red, Yellow & Blue
3 INNER SHEATH : PVC as per IS :1554PT-1
4 OUTER SHEATH : PVC TYPE ST-1 OF IS : 5831 ‘— OPTIONS : PVC TYPE ST-2 OF IS : 5831/ FR TYPE/ FRLS TYPE
COLOUR OF OUTER SHEATH : BLACK. OPTIONS : any other colour as per requirement.
~ Tabulated approx. net wt. of cables are only guidelines for transportation, loading &unloading purpose.
~ Please ref page no 43 for normal delivery lengths & packing details.

Electrical Parameter
SIZE Max. Cond. D.C. Approx. Cond. A.C. pp.. Reactance App. Capecitance Normal* Current Rating in Amps Short Circuit Current
cross-sectional Resistance at Resistance at at 50HZ of cable With Aluminium cond. With Copper cond. Rating for 1Sec.duration
o o
area (Sq MM) 20 C in Ohm/km 70 C in Ohm/km in ohms/km in microF/KM Ground Duct Air Ground Duct Air in K. Amps
Al Cu Al Cu Al Cu
4 —— 4.61 —— 5.53 0.098 0.23 28 23 23 36 30 30 0.304 0.460
6 4.61 3.08 5.53 3.70 0.096 0.28 35 30 30 45 38 39 0.456 0.690
10 3.08 1.83 3.70 2.20 0.091 0.34 46 39 40 60 50 52 0.760 1.150
16 1.91 1.15 2.29 1.38 0.085 0.40 60 50 51 77 64 66 1.220 1.840
25 1.20 0.727 1.44 0.87 0.083 0.42 76 63 70 99 81 90 1.900 2.880
35 0.868 0.524 1.04 0.63 0.082 0.48 92 77 86 120 99 110 2.660 4.030
50 0.641 0.387 0.769 0.464 0.082 0.49 110 95 105 145 125 135 3.800 5.750
70 0.443 0.268 0.532 0.322 0.076 0.56 135 115 130 175 150 165 5.320 8.050
95 0.320 0.193 0.384 0.232 0.076 0.58 165 140 155 210 175 200 7.220 10.900
120 0.253 0.153 0.304 0.184 0.075 0.63 185 155 180 240 195 230 9.120 13.800
150 0.206 0.1240 0.247 0.1488 0.074 0.63 210 175 205 270 225 265 11.40 17.300
185 0.164 0.0991 0.197 0.1189 0.074 0.64 235 200 240 300 255 305 14.10 21.300
240 0.125 0.0754 0.151 0.0912 0.073 0.67 275 235 280 345 295 355 18.20 27.600
300 0.100 0.0601 0.122 0.0733 0.073 0.68 305 260 315 385 335 400 22.80 34.500
400 0.0778 0.0470 0.0961 0.0580 0.072 0.70 335 290 375 425 360 435 30.40 46.000
500 0.0605 0.0366 0.759 0.0459 0.072 0.70 370 320 425 470 390 520 38.00 57.500
630 0.0469 0.0283 0.0610 0.0368 0.072 0.70 405 350 480 555 470 675 47.90 72.500
Note : Normal current ratings are given in standard conditions( as given in page no- 40,41) , if site conditions are different, current rating should be multiplied
by rating factor as given in page no. 42

8
Table -4 TECHNICAL DETAIL FOR HAVELLS 1.1 KV
THREE & HALF CORES, AL/COPPER COND., PVC INSULATED, UN-ARMOURED CABLES
Cable Code : AYY/ YY Ref. Spec. : IS :1554PART -1
Physical Parameters
SIZE Minimum nos of Nominal Minimum Nominal Approx. Approx. Net Wt.
cross-sectional Strands in conductor Thickness of Thickness of thickness of Overal of cable (Kg/KM)
area ( Sq MM) Phase Neutral Insulation) (mm) inner sheath outer sheath Diameter With Al Conductor With Cu conductor
Al Cu Phase / Neutral (mm) (mm) (mm) AYY YY

3X25+16 6/6 6/6 1.20/1.00 0.30 2.00 24 700 1264


3X35+16 6/6 6/6 1.20/1.00 0.30 2.00 26 850 1600
3X50+25 6/6 6/6 1.40/1.20 0.30 2.00 29 1050 2100
3X70+35 12/6 12/6 1.40/1.20 0.40 2.20 32 1400 2900
3X95+50 15/6 15/6 1.60/1.40 0.40 2.20 36 1800 3900
3X120+70 15/12 18/12 1.60/1.40 0.50 2.40 40 2200 4850
3X150+70 15/12 18/12 1.80/1.40 0.50 2.40 44 2600 5800
3X185+95 30/15 30/15 2.00/1.60 0.50 2.60 48 3200 7200
3X240+120 30/15 34/18 2.20/1.60 0.60 3.00 54 4100 9300
3X300+150 30/15 34/18 2.40/1.80 0.60 3.20 62 5000 11500
3X400+185 53/30 53/30 2.60/2.00 0.70 3.40 68 6300 15000
3X500+240 53/30 53/34 3.00/2.20 0.70 3.80 77 8000 18500
3X630+300 53/30 53/34 3.40/2.40 0.70 4.00 87 10000 23500

Cross-sectional View
1 CONDUCTOR : Material - Aluminium /Copper
*Shape : ~AL . Cond :- 6 & 10 sq mm -Solid circular, 16sqmm & above : Stranded compacted shaped
~Copper . Cond :- 4 & 6sqmm -solid/ stranded non compacted circular , 10sqmm : Stranded compacted circular,16sqmm & above : Stranded compacted
shaped
2
INSULATION : PVC Type A of IS :5831/ OPTION : HR PVC ( Type -C of IS -5831), Colour : Red, Yellow, Blue, Black
3
INNER SHEATH : PVC as per IS :1554PT-1
4 OUTER SHEATH : PVC TYPE ST-1 OF IS : 5831 ‘— OPTIONS : PVC TYPE ST-2 OF IS : 5831/ FR TYPE/ FRLS TYPE
COLOUR OF OUTER SHEATH : BLACK . OPTIONS : any other colour as per requirement.
~ Tabulated approx. net wt. of cables are only guidelines for transportation, loading &unloading purpose ..
~ Please ref page no 43 for normal delivery lengths & packing details.

Electrical Parameters
SIZE Max. Cond. D.C. Approx. Cond. A.C. App.Reactance App. Capecitance Normal* Current Rating in Amps Short Circuit Current
cross-sectional Resistance at Resistance at of cable at 50HZ of cable With Aluminium cond. With Copper cond. Rating for 1Sec.duration
area (Sq MM) 20oC in Ohm/km 70oC in Ohm/km in ohms/km in microF/KM Ground Duct Air Ground Duct Air in K. Amps
Al Cu Al Cu Al Cu

3X25+16 1.20 0.727 1.44 0.87 0.083 0.42 76 63 70 99 81 90 1.90 2.88


3X35+16 0.868 0.524 1.04 0.63 0.082 0.48 92 77 86 120 99 110 2.66 4.03
3X50+25 0.641 0.387 0.769 0.464 0.082 0.49 110 95 105 145 125 135 3.80 5.75
3X70+35 0.443 0.268 0.532 0.322 0.076 0.56 135 115 130 175 150 165 5.32 8.05
3X95+50 0.320 0.193 0.384 0.232 0.076 0.58 165 140 155 210 175 200 7.22 10.90
3X120+70 0.253 0.153 0.304 0.184 0.075 0.63 185 155 180 240 195 230 9.12 13.80
3X150+70 0.206 0.1240 0.247 0.1488 0.074 0.63 210 175 205 270 225 265 11.40 17.30
3X185+95 0.164 0.0991 0.197 0.1189 0.074 0.64 235 200 240 300 255 305 14.10 21.30
3X240+120 0.125 0.0754 0.151 0.0912 0.073 0.67 275 235 280 345 295 355 18.20 27.60
3X300+150 0.100 0.0601 0.122 0.0733 0.073 0.68 305 260 315 385 335 400 22.80 34.50
3X400+185 0.0778 0.0470 0.0961 0.0580 0.072 0.70 335 290 375 425 360 435 30.40 46.00
3X500+240 0.0605 0.0366 0.0759 0.0459 0.072 0.70 370 320 425 470 390 520 38.00 57.50
3X630+300 0.0469 0.0283 0.0610 0.0368 0.072 0.70 405 350 480 555 470 675 47.90 72.50
Note : Normal current ratings are given in standard conditions (as given in page no- 40,41) , if site conditions are different, current rating should be multiplied
by rating factor as given in page no. 42

9
Table -5 TECHNICAL DETAIL FOR HAVELLS 1.1 KV
FOUR CORES, AL/COPPER COND., PVC INSULATED, UN-ARMOURED CABLES
Cable Code : AYY/ YY Ref. Spec. : IS :1554PART -1
Physical Parameters
SIZE Minimum Nominal Minimum Nominal Approx. Approx. Net Wt.
cross-sectional No of Strand in Thickness of Thickness of thickness of Overal of cable (Kg/KM)
area Conductor Insulation) inner sheath outer sheath Diameter With Al Conductor With Cu
(sq mm) Al Cu (mm) (mm) (mm) (mm) AYY YY
4 — 1/7 1.0 0.30 1.80 16 300 400
6 1 1/7 1.0 0.30 1.80 18 390 540
10 1 6 1.0 0.30 1.80 20 540 788
16 6 6 1.0 0.30 2.00 23 560 950
25 6 6 1.2 0.30 2.00 26 750 1370
35 6 6 1.2 0.30 2.00 30 940 1800
50 6 6 1.4 0.40 2.20 34 1250 2500
70 12 12 1.4 0.40 2.20 38 1550 3300
95 15 15 1.6 0.40 2.40 43 2050 4400
120 15 18 1.6 0.50 2.40 46 2400 5380
150 15 18 1.8 0.50 2.60 51 2950 6670
185 30 30 2.0 0.60 2.80 55 3650 8250
240 30 34 2.2 0.60 3.00 60 4600 10550
300 30 34 2.4 0.70 3.40 66 5500 12950
400 53 53 2.6 0.70 3.60 73 6800 16720
500 53 53 3.0 0.70 4.00 82 8600 21000
630 53 53 3.4 0.70 4.00 92 11000 26000

Cross- Sectional View


1
CONDUCTOR : Material - Aluminium /Copper
*Shape : ~AL . Cond :- 6 & 10SQMM -Solid circular, 16sqmm & above : Stranded compacted shaped
~Copper . Cond :- 4 & 6sqmm -solid/ stranded non compacted circular, 10sqmm : Stranded compacted circular,16sqmm & above : Stranded compacted shaped
2 INSULATION : PVC Type A of IS :5831/ OPTION : HR PVC ( Type -C of IS -5831), Colour : Red, Yellow, Blue, Black
3 INNER SHEATH : PVC as per IS :1554PT-1
4 OUTER SHEATH : PVC TYPE ST-1 OF IS : 5831 ‘— OPTIONS : PVC TYPE ST-2 OF IS : 5831/ FR TYPE/ FRLS TYPE
COLOUR OF OUTER SHEATH : BLACK . OPTIONS : any other colour as per requirement.
~ Tabulated approx. net wt. of cables are only guidelines for transportation, loading &unloading purpose ..
~ Please ref page no 43 for normal delivery lengths & packing details.

Electrical Parameters
SIZE Max. Cond. D.C. Approx. Cond. A.C. App.Reactance App. Capecitance Normal* Current Rating in Amps Short Circuit Current
cross-sectional Resistance at Resistance at of cable at 50HZ of cable With Aluminium cond. With Copper cond. Rating for 1Sec.duration
area (Sq MM) 20oC in Ohm/km 70oC in Ohm/km in ohms/km in microF/KM Ground Duct Air Ground Duct Air in K. Amps
Al Cu Al Cu Al Cu
4 —— 4.61 —— 5.53 0.098 0.23 28 23 23 36 30 30 0.304 0.460
6 4.61 3.08 5.53 3.70 0.096 0.28 35 30 30 45 38 39 0.456 0.690
10 3.08 1.83 3.70 2.20 0.091 0.34 46 39 40 60 50 52 0.760 1.150
16 1.91 1.15 2.29 1.38 0.085 0.40 60 50 51 77 64 66 1.220 1.840
25 1.20 0.727 1.44 0.87 0.083 0.42 76 63 70 99 81 90 1.900 2.880
35 0.868 0.524 1.04 0.63 0.082 0.48 92 77 86 120 99 110 2.660 4.030
50 0.641 0.387 0.769 0.464 0.082 0.49 110 95 105 145 125 135 3.800 5.750
70 0.443 0.268 0.532 0.322 0.076 0.56 135 115 130 175 150 165 5.320 8.050
95 0.320 0.193 0.384 0.232 0.076 0.58 165 140 155 210 175 200 7.220 10.900
120 0.253 0.153 0.304 0.184 0.075 0.63 185 155 180 240 195 230 9.120 13.800
150 0.206 0.1240 0.247 0.1488 0.074 0.63 210 175 205 270 225 265 11.400 17.300
185 0.164 0.0991 0.197 0.1189 0.074 0.64 235 200 240 300 255 305 14.100 21.300
240 0.125 0.0754 0.151 0.0912 0.073 0.67 275 235 280 345 295 355 18.200 27.600
300 0.100 0.0601 0.122 0.0733 0.073 0.68 305 260 315 385 335 400 22.800 34.500
400 0.0778 0.0470 0.0961 0.0580 0.072 0.70 335 290 375 425 360 435 30.400 46.000
500 0.0605 0.0366 0.0759 0.0459 0.072 0.70 370 320 425 470 390 520 38.000 57.500
630 0.0469 0.0283 0.0610 0.0368 0.072 0.70 405 350 480 555 470 675 47.900 72.500
Note : Normal current ratings are given in standard conditions (as given in page no 40,41) , if site conditions are different, current rating should be multiplied by
rating factor as given in page no. 42
10
Table -6 TECHNICAL DETAIL FOR HAVELLS 1.1 KV
SINGLE CORE, AL/COPPER COND., PVC INSULATED, AL WIRE/STRIP ARMOURED CABLES
Cable Code : AYFaY/ YFaY, AYWaY/ YWaY Ref. Spec. : IS :1554PART -1
Physical Parameters

SIZE Minimum Nominal ARMOURING WITH FLAT STRIP ( AYFaY/ YFaY) ARMOURING WITH ROUND WIRES ( AYWaY/ YWaY)
Cross- No of Nominal Minimum Approx. Approx. Net Wt Nominal Minimum Approx. Approx. Net Wt
-sectional Strands in Thickness of Thickness Thickness of Overall of cable ( Kg/KM) Diameter Thickness of Overall of cable ( Kg/KM)
area Conductor Insulation) of armour outer sheath Diameter With Al cond With Cu Cond. of wire outer sheath Diameter With Al cond With Cu Cond.
( sqmm) Al Cu (mm) (mm) (mm) (mm) AYFaY YFaY (mm) (mm) (mm) AYWaY YWaY
4 — 1/7 1.3 N/A N/A N/A N/A N/A 1.40 1.24 11 150 180
6 1 1/7 1.3 N/A N/A N/A N/A N/A 1.40 1.24 12 180 210
10 1 6 1.3 N/A N/A N/A N/A N/A 1.40 1.24 13 200 260
16 6 6 1.3 N/A N/A N/A N/A N/A 1.40 1.24 14 250 350
25 6 6 1.5 N/A N/A N/A N/A N/A 1.40 1.24 15 300 450
35 6 6 1.5 N/A N/A N/A N/A N/A 1.40 1.24 16 350 560
50 6 6 1.7 N/A N/A N/A N/A N/A 1.40 1.24 18 450 750
70 12 12 1.7 N/A N/A N/A N/A N/A 1.40 1.40 20 550 980
95 15 15 1.9 0.80 1.40 21 650 1230 1.60 1.40 22 700 1300
120 15 18 1.9 0.80 1.40 23 750 1500 1.60 1.40 24 800 1550
150 15 18 2.1 0.80 1.40 24 900 1830 1.60 1.40 26 950 1880
185 30 30 2.3 0.80 1.40 27 1050 2200 1.60 1.40 29 1100 2250
240 30 34 2.5 0.80 1.40 30 1300 2800 1.60 1.56 32 1400 2900
300 30 34 2.7 0.80 1.56 32 1600 3450 1.60 1.56 33 1650 3500
400 53 53 3.0 0.80 1.56 37 1950 4400 2.00 1.56 39 2100 4580
500 53 53 3.4 0.80 1.56 40 2400 5500 2.00 1.72 42 2700 5800
630 53 53 3.9 0.80 1.72 45 3100 7000 2.00 1.88 48 3300 7200
800 53 53 3.9 0.80 1.88 49 3700 8650 2.00 1.88 52 4000 8950
1000 53 53 3.9 0.80 2.04 55 4600 10800 2.50 2.04 59 4900 11000

Cross- Sectional View


1 CONDUCTOR : Material - Aluminium /Copper
*Shape : ~AL . Cond :- 6 & 10 sqmm - Solid circular, 16 sqmm & above : Stranded compacted shaped
~Copper . Cond :- 4 & 6sqmm -solid/ stranded non compacted circular, 10sqmm : Stranded compacted circular,16sqmm & above : Stranded compacted shaped
2 INSULATION : PVC Type A of IS :5831/ OPTION : HR PVC (Type -C of IS -5831), Colour : Black
3 INNER SHEATH : PVC as per IS :1554PT-1
4 ARMOURING : Single layer of Aluminium Round wires / Flat Strips
5 OUTER SHEATH : PVC TYPE ST-1 OF IS : 5831 ‘— OPTIONS : PVC TYPE ST-2 OF IS : 5831/ FR TYPE/ FRLS TYPE
COLOUR OF OUTER SHEATH : BLACK. OPTIONS : any other colour as per requirement.
~ Tabulated approx. net wt. of cables are only guidelines for transportation, loading &unloading purpose.
~ Please ref page no 43 for normal delivery lengths & packing details.

Electrical Parameters
SIZE Max. Cond. D.C. Approx. Cond. A.C. App.Reactance App. Capecitance Normal* Current Rating in Amps Short Circuit Current
cross-sectional Resistance at Resistance at of cable of cable With Aluminium cond. With Copper cond. Rating for 1Sec.duration
o o
area (Sq MM) 20 C in Ohm/km 70 C in Ohm/km in at 50HZ in microF/KM Ground Duct Air Ground Duct Air in K. Amps
Al Cu Al Cu ohms/km Al Cu
4 7.41 4.61 8.89 5.53 0.157 0.48 31 30 27 39 38 35 0.304 0.460
6 4.61 3.08 5.53 3.70 0.148 0.56 39 37 35 49 48 44 0.456 0.690
10 3.08 1.83 3.70 2.20 0.138 0.67 51 51 47 65 64 60 0.760 1.150
16 1.91 1.15 2.29 1.38 0.128 0.81 66 65 64 85 83 82 1.220 1.840
25 1.20 0.727 1.44 0.87 0.120 0.87 86 84 84 110 110 110 1.900 2.880
35 0.868 0.524 1.04 0.63 0.114 1.00 100 100 105 130 125 130 2.660 4.030
50 0.641 0.387 0.769 0.464 0.110 1.03 120 115 130 155 150 165 3.800 5.750
70 0.443 0.268 0.532 0.322 0.103 1.21 140 135 155 190 175 205 5.320 8.050
95 0.320 0.193 0.384 0.232 0.101 1.27 175 155 190 220 200 245 7.220 10.90
120 0.253 0.153 0.304 0.184 0.096 1.42 195 170 220 250 220 280 9.120 13.80
150 0.206 0.1240 0.247 0.1488 0.094 1.42 220 190 250 280 245 320 11.400 17.30
185 0.164 0.0991 0.197 0.1189 0.092 1.44 240 210 290 305 260 370 14.100 21.30
240 0.125 0.0754 0.151 0.0912 0.090 1.53 270 225 335 345 285 425 18.200 27.60
300 0.100 0.0601 0.122 0.0733 0.088 1.56 295 245 380 375 310 475 22.800 34.50
400 0.0778 0.0470 0.0961 0.0580 0.088 1.59 325 275 435 400 335 550 30.400 46.00
500 0.0605 0.0366 0.076 0.0459 0.087 1.67 345 295 480 425 355 590 38.000 57.50
630 0.0469 0.0283 0.0610 0.0368 0.086 1.67 390 320 550 470 375 660 47.880 72.50
800 0.0367 0.0221 0.0503 0.0303 0.083 1.75 450 380 610 530 423 725 60.800 92.00
1000 0.0291 0.0176 0.0422 0.0255 0.082 1.94 500 414 680 590 471 870 76.000 115.00
Note : Normal current ratings are given in standard conditions (as given in page no - 40,41) , if site conditions are different, current rating should be multiplied by
rating factor as given in page no. 42

11
Table -7 TECHNICAL DETAIL FOR HAVELLS 1.1 KV
TWO CORES, AL/COPPER COND., PVC INSULATED,
GALVANIZED STEEL WIRE/STRIP ARMOURED CABLES
Cable Code : AYFY/ YFY, AYWY/ YWY Ref. Spec. : IS :1554 PART -1
Physical Parameters
SIZE Minimum Nominal Minimum ARMOURING WITH FLAT STRIP ( AYFY/ YFY) ARMOURING WITH ROUND WIRES ( AYWY/ YWY)
Cross- No of Thickness Thickness Nominal Minimum Approx. Approx. Net Wt Nominal Minimum Approx. Approx. Net Wt
-sectional Strands in of of Thickness Thickness of Overall of cable (Kg/KM) Diameter Thickness of Overall of cable ( Kg/KM)
area Conductor Insulation) inner Sh. of armour outer sheath Diameter With Al cond With Cu Cond. of armour outer sheath Diameter With Al cond With Cu Cond.
(sqmm) Al Cu (mm) (mm) (mm) (mm) (mm) AYFY YFY (mm) (mm) (mm) AYWY YWY
4 — 1/7 1.0 0.30 N/A N/A N/A N/A N/A 1.40 1.24 18 600 650
6 1 1/7 1.0 0.30 N/A N/A N/A N/A N/A 1.40 1.24 19 660 730
10 1 6 1.0 0.30 N/A N/A N/A N/A N/A 1.40 1.24 20 750 870
16 6 6 1.0 0.30 0.80 1.40 18 580 780 1.60 1.40 20 750 950
25 6 6 1.2 0.30 0.80 1.40 20 700 1000 1.60 1.40 22 900 1200
35 6 6 1.2 0.30 0.80 1.40 22 800 1230 1.60 1.40 23 1030 1450
50 6 6 1.4 0.30 0.80 1.40 25 1000 1620 1.60 1.56 26 1300 1900
70 12 12 1.4 0.30 0.80 1.56 27 1200 2050 1.60 1.56 29 1500 2350
95 15 15 1.6 0.40 0.80 1.56 30 1550 2720 2.00 1.56 33 2050 3200
120 15 18 1.6 0.40 0.80 1.56 32 1800 3290 2.00 1.72 35 2400 3900
150 15 18 1.8 0.40 0.80 1.72 35 2100 3970 2.00 1.72 37 2760 4600
185 30 30 2.0 0.50 0.80 1.88 38 2500 4800 2.00 1.88 41 3200 5500
240 30 34 2.2 0.50 0.80 2.04 43 3100 6080 2.50 2.04 47 4200 7200
300 30 34 2.4 0.60 0.80 2.20 48 3700 7400 2.50 2.20 50 5000 8700
400 53 53 2.6 0.70 0.80 2.36 53 4500 9450 3.15 2.52 58 6600 11500
500 53 53 3.0 0.70 0.80 2.68 56 5600 11800 3.15 2.84 64 8000 14000
630 53 53 3.4 0.70 0.80 2.84 66 6900 14700 4.00 3.00 72 11000 18800

Cross- Sectional View


1
CONDUCTOR : Material - Aluminium /Copper
*Shape : ~AL . Cond :- 6 & 10SQMM -Solid circular, 16sqmm & above : Stranded compacted shaped
~Copper. Cond :- 4 & 6 sqmm-solid/ stranded non compacted circular, 10sqmm : Stranded compacted circular,16sqmm & above : Stranded compacted shaped
2 INSULATION : PVC Type A of IS :5831/ OPTION : HR PVC ( Type -C of IS -5831), Colour : Red & Black
3 INNER SHEATH : PVC as per IS :1554PT-1
4 ARMOURING : Single layer of Galvanized steel Round wires / Flat Strips
5 OUTER SHEATH : PVC TYPE ST-1 OF IS : 5831 ‘— OPTIONS : PVC TYPE ST-2 OF IS : 5831/ FR TYPE/ FRLS TYPE
COLOUR OF OUTER SHEATH : BLACK . OPTIONS : any other colour as per requirement.
~ Tabulated approx. net wt. of cables are only guidelines for transportation, loading &unloading purpose.
~ Please ref page no 43 for normal delivery lengths & packing details.

Electrical Parameters
SIZE Max. Cond. D.C. Approx. Cond. A.C. App.Reactance App. Capecitance Normal* Current Rating in Amps Short Circuit Current
cross-sectional Resistance at Resistance at of cable at 50HZ of cable With Aluminium cond. With Copper cond. Rating for 1Sec. duration
area (Sq MM) 20oC in Ohm/km 70oC in Ohm/km in ohms/km in microF/KM Ground Duct Air Ground Duct Air in K. Amps
Al Cu Al Cu Al Cu
4 --- 4.61 --- 5.53 0.098 0.23 32 27 27 41 35 35 0.304 0.460
6 4.61 3.08 5.53 3.70 0.096 0.28 40 34 35 50 44 45 0.456 0.690
10 3.08 1.83 3.70 2.20 0.091 0.34 55 45 47 70 58 60 0.760 1.150
16 1.91 1.15 2.29 1.38 0.085 0.40 70 58 59 90 75 78 1.220 1.840
25 1.20 0.727 1.44 0.87 0.083 0.42 90 76 78 115 97 105 1.90 2.880
35 0.868 0.524 1.04 0.63 0.082 0.48 110 92 99 140 120 125 2.66 4.030
50 0.641 0.387 0.769 0.464 0.082 0.49 135 115 125 165 145 155 3.80 5.750
70 0.443 0.268 0.532 0.322 0.076 0.56 160 140 150 205 180 195 5.32 8.050
95 0.320 0.193 0.384 0.232 0.076 0.58 190 170 185 240 215 230 7.22 10.90
120 0.253 0.153 0.304 0.184 0.075 0.63 210 190 210 275 235 265 9.12 13.80
150 0.206 0.1240 0.247 0.1488 0.074 0.63 240 210 240 310 270 305 11.40 17.30
185 0.164 0.0991 0.197 0.1189 0.074 0.64 275 240 275 350 300 350 14.10 21.30
240 0.125 0.0754 0.151 0.0912 0.073 0.67 320 275 325 405 345 410 18.20 27.60
300 0.100 0.0601 0.122 0.0733 0.073 0.68 355 305 365 450 385 465 22.80 34.50
400 0.0778 0.0470 0.0961 0.0580 0.072 0.70 385 345 420 490 485 530 30.40 46.00
500 0.0605 0.0366 0.0759 0.0459 0.072 0.70 425 380 475 540 460 605 38.00 57.50
630 0.0469 0.0283 0.0610 0.0368 0.072 0.70 465 415 540 640 550 785 47.90 72.50
Note : Normal current ratings are given in standard conditions (as given in page no - 40,41), if site conditions are different, current rating should be multiplied by
rating factor as given in page no. 42

12
Table -8 TECHNICAL DETAIL FOR HAVELLS 1.1 KV
THREE CORES, AL/COPPER COND., PVC INSULATED,
GALVANIZED STEEL WIRE/STRIP ARMOURED CABLES
Cable Code : AYFY/ YFY, AYWY/ YWY Ref. Spec. : IS :1554 PART -1
Physical Parameters
SIZE Minimum Nominal Minimum ARMOURING WITH FLAT STRIP ( AYFY/ YFY) ARMOURING WITH ROUND WIRES ( AYWY/ YWY)
Cross- No of Thickness Thickness Nominal Minimum Approx. Approx. Net Wt Nominal Minimum Approx. Approx. Net Wt
-sectional Strands in of of Thick. of Thick. of Overall of cable ( Kg/KM) Diameter Thickness of Overall of cable ( Kg/KM)
area Conductor Insulation) inner Sh. armour strip outer sheath Diameter With Al cond With Cu Cond. of wire outer sheath Diameter With Al cond With Cu Cond.
(sq mm) Al Cu (mm) (mm) (mm) (mm) (mm) AYFY YFY (mm) (mm) (mm) AYWY YWY
4 -- 1/7 1.0 0.30 N/A N/A N/A N/A N/A 1.40 1.24 18 600 650
6 1 1/7 1.0 0.30 N/A N/A N/A N/A N/A 1.40 1.24 19 700 810
10 1 6 1.0 0.30 N/A N/A N/A N/A N/A 1.40 1.40 21 900 1100
16 6 6 1.0 0.30 0.80 1.40 20 700 1000 1.60 1.40 21 950 1250
25 6 6 1.2 0.30 080. 1.40 23 900 1350 1.60 1.40 23 1100 1550
35 6 6 1.2 0.30 0.80 1.40 24 1000 1650 1.60 1.40 26 1300 1950
50 6 6 1.4 0.30 0.80 1.56 27 1300 2230 1.60 1.56 29 1600 2530
70 12 12 1.4 0.40 0.80 1.56 31 1600 2900 2.00 1.56 33 2150 3450
95 15 15 1.6 040 0.80 1.56 35 2000 3750 2.00 1.72 37 2650 4400
120 15 18 1.6 0.40 0.80 1.72 37 2400 4630 2.00 1.72 39 3000 5200
150 15 18 1.8 0.50 0.80 1.88 41 2800 5600 2.00 1.88 43 3550 6300
185 30 30 2.0 0.50 0.80 1.88 46 3400 6840 2.50 2.04 49 4600 8000
240 30 34 2.2 0.60 0.80 2.20 51 4200 8650 2.50 2.20 54 5600 10000
300 30 34 2.4 0.60 0.80 2.36 56 5050 10630 2.50 2.36 59 6600 12000
400 53 53 2.6 0.70 0.80 2.52 63 6300 13740 3.15 2.68 68 8700 16000
500 53 53 3.0 0.70 0.80 2.84 70 7800 17100 3.15 3.00 75 11000 20000
630 53 53 3.4 0.70 0.80 3.00 78 9700 21418 4.00 3.00 84 14000 25500

Cross- Sectional View


1 CONDUCTOR : Material - Aluminium /Copper
*Shape : ~AL . Cond :- 6 & 10SQMM -Solid circular, 16sqmm & above : Stranded compacted shaped
~Copper . Cond :- 4 & 6sqmm -solid/ stranded non compacted circular, 10sqmm : Stranded compacted circular,16sqmm & above : Stranded compacted shaped
2 INSULATION : PVC Type A of IS :5831/ OPTION : HR PVC ( Type -C of IS -5831), Colour : Red, Yellow, Blue
3 INNER SHEATH : PVC as per IS :1554PT-1
4 ARMOURING : Single layer of Galvanized steel Round wires / Flat Strips
5 OUTER SHEATH : PVC TYPE ST-1 OF IS : 5831 ‘— OPTIONS : PVC TYPE ST-2 OF IS : 5831/ FR TYPE/ FRLS TYPE
COLOUR OF OUTER SHEATH : BLACK . OPTIONS : any other colour as per requirement.
~ Tabulated approx. net wt. of cables are only guidelines for transportation, loading &unloading purpose.
~Please ref page no 43 for normal delivery lengths & packing details.

Electrical Parameters
SIZE Max. Cond. D.C. Approx. Cond. A.C. App.Reactance App. Capecitance Normal* Current Rating in Amps Short Circuit Current
cross-sectional Resistance at Resistance at at 50HZ of cable With Aluminium cond. With Copper cond. Rating for 1Sec.duration
area (Sq MM) 20oC in Ohm/km 70oC in Ohm/km in ohms/km in microF/KM Ground Duct Air Ground Duct Air in K. Amps
Al Cu Al Cu Al Cu
4 — 4.61 — 5.53 0.098 0.23 28 23 23 36 30 30 0.304 0.460
6 4.61 3.08 5.53 3.70 0.096 0.28 35 30 30 45 38 39 0.456 0.690
10 3.08 1.83 3.70 2.20 0.091 0.34 46 39 40 60 50 52 0.760 1.150
16 1.91 1.15 2.29 1.38 0.085 0.40 60 50 51 77 64 66 1.220 1.840
25 1.20 0.727 1.44 0.87 0.083 0.42 76 63 70 99 81 90 1.900 2.880
35 0.868 0.524 1.04 0.63 0.082 0.48 92 77 86 120 99 110 2.660 4.030
50 0.641 0.387 0.769 0.464 0.082 0.49 110 95 105 145 125 135 3.800 5.750
70 0.443 0.268 0.532 0.322 0.076 0.56 135 115 130 175 150 165 5.320 8.050
95 0.320 0.193 0.384 0.232 0.076 0.58 165 140 155 210 175 200 7.220 10.900
120 0.253 0.153 0.304 0.184 0.075 0.63 185 155 180 240 195 230 9.120 13.800
150 0.206 0.1240 0.247 0.1488 0.074 0.63 210 175 205 270 225 265 11.400 17.300
185 0.164 0.0991 0.197 0.1189 0.074 0.64 235 200 240 300 255 305 14.100 21.300
240 0.125 0.0754 0.151 0.0912 0.073 0.67 275 235 280 345 295 355 18.200 27.600
300 0.100 0.0601 0.122 0.0733 0.073 0.68 305 260 315 385 335 400 22.800 34.500
400 0.0778 0.0470 0.0961 0.0580 0.072 0.70 335 290 375 425 360 435 30.400 46.000
500 0.0605 0.0366 0.0759 0.0459 0.072 0.70 370 320 425 470 390 520 38.000 57.500
630 0.0469 0.0283 0.0610 0.0368 0.072 0.70 405 350 480 555 470 675 47.900 72.500
Note : Normal current ratings are given in standard conditions (as given in page no - 40,41), if site conditions are different, current rating should be multiplied by
rating factor as given in page no. 42

13
Table -9 TECHNICAL DETAIL FOR HAVELLS 1.1 KV
THREE AND HALF CORES, AL/CUCOPPER COND.,
PVC INSULATED, GALVANIZED STEEL WIRE/STRIP ARMOURED CABLES
Cable Code : 3.5 Core - AYFY / YFY, AYWY / YWY Ref. Spec. : IS :1554PART -1
Physical Parameters
SIZE Minimum Nominal Minimum ARMOURING WITH FLAT STRIP ( AYFY/ YFY) ARMOURING WITH ROUND WIRES ( AYWY/ YWY)
Cross- Nos of Thickness of Thickness Nominal Minimum Approx. Approx. Net Wt Nominal Minimum Approx. Approx. Net Wt
-sectional Strands in Insulation) of Thickness Thickness of Overall of cable ( Kg/KM) Diameter Thickness of Overall of cable ( Kg/KM)
area Conductor (mm) inner Sh. Strip outer sheath Diameter With Al cond With Cu Cond. of wire outer sheath Diameter With Al cond With Cu Cond.
(sqmm) Phase/Neutral Phase/Neutral (mm) (mm) (mm) (mm) AYFY YFY (mm) (mm) (mm) AYWY YWY

3X25+16 6/6 6/6 1.20/1.00 0.30 0.80 1.40 24 1000 1550 1.60 1.40 26 1300 1850
3X35+16 6/6 6/6 1.20/1.00 0.30 0.80 1.40 26 1200 1950 1.60 1.40 28 1450 2150
3X50+25 6/6 6/6 1.40/1.20 0.30 0.80 1.56 30 1500 2600 1.60 1.56 31 1800 2800
3X70+35 12/6 12/6 1.40/1.20 0.40 0.80 1.56 34 1800 3300 2.00 1.56 36 2400 3800
3X95+50 15/6 15/6 1.60/1.40 0.40 0.80 1.56 37 2300 4350 2.00 1.72 39 3000 5000
3X120+70 15/12 18/12 1.60/1.40 0.50 0.80 1.72 41 2800 5450 2.00 1.88 43 3500 6100
3X150+70 15/12 18/12 1.80/1.40 0.50 0.8 1.88 45 3200 6400 2.00 1.88 47 4000 7200
3X185+95 30/15 30/15 2.00/1.60 0.50 0.80 2.04 49 3900 7900 2.50 2.04 53 5200 9200
3X240+120 30/15 34/18 2.20/1.60 0.60 0.80 2.20 55 4800 10000 2.50 2.30 58 6400 11500
3X300+150 30/15 34/18 2.40/1.80 0.60 0.80 2.36 61 5800 12300 3.15 2.52 65 8200 14500
3X400+185 53/30 53/30 2.60/2.00 0.70 0.80 2.68 69 7300 15800 3.15 2.63 75 9900 18400
3X500+240 53/30 53/34 3.00/2.20 0.70 0.80 2.84 77 9000 19500 4.00 3.00 84 13500 24000
3X630+300 53/30 53/34 3.40/2.40 0.70 0.80 3.00 87 11500 25000 4.00 3.00 92 16000 28500

Cross- Sectional View


1
CONDUCTOR : Material - Aluminium /Copper
*Shape : ~AL . Cond :- 6 & 10SQMM -Solid circular, 16sqmm & above : Stranded compacted shaped
~Copper. Cond :- 4 & 6sqmm -solid/ stranded non compacted circular, 10sqmm : Stranded compacted circular,16sqmm & above : Stranded compacted shaped
2 INSULATION : PVC Type A of IS :5831/ OPTION : HR PVC ( Type -C of IS -5831), Colour : Red, Yellow, Blue, Black
3 INNER SHEATH : PVC as per IS :1554PT-1
4 ARMOURING : Single layer of Galvanized steel Round wires / Flat Strips
5 OUTER SHEATH : PVC TYPE ST-1 OF IS : 5831 ‘— OPTIONS : PVC TYPE ST-2 OF IS : 5831/ FR TYPE/ FRLS TYPE
COLOUR OF OUTER SHEATH : BLACK . OPTIONS : any other colour as per requirement.
~ Tabulated approx. net wt. of cables are only guidelines for transportation, loading &unloading purpose.
~ Please ref page no 43 for normal delivery lengths & packing details.

Electrical Parameters
SIZE Max. Cond. D.C. Approx. Cond. A.C. App..Reactance App. Capecitance Normal* Current Rating in Amps Short Circuit Current
cross-sectional Resistance at Resistance at at 50HZ of cable With Aluminium cond. With Copper cond. Rating for 1Sec.duration
area (Sq MM) 20oC in Ohm/km 70oC in Ohm/km in ohms/km in microF/KM Ground Duct Air Ground Duct Air in K. Amps
Al Cu Al Cu Al Cu

3X25+16 1.20 0.727 1.44 0.87 0.083 0.42 76 63 70 99 81 90 1.90 2.88


3X35+16 0.868 0.524 1.04 0.63 0.082 0.48 92 77 86 120 99 110 2.66 4.03
3X50+25 0.641 0.387 0.769 0.464 0.082 0.49 110 95 105 145 125 135 3.80 5.75
3X70+35 0.443 0.268 0.532 0.322 0.076 0.56 135 115 130 175 150 165 5.32 8.05
3X95+50 0.320 0.193 0.384 0.232 0.076 0.58 165 140 155 210 175 200 7.22 10.90
3X120+70 0.253 0.153 0.304 0.184 0.075 0.63 185 155 180 240 195 230 9.12 13.80
3X150+70 0.206 0.1240 0.247 0.1488 0.074 0.63 210 175 205 270 225 265 11.40 17.30
3X185+95 0.164 0.0991 0.197 0.1189 0.074 0.64 235 200 240 300 255 305 14.10 21.30
3X240+120 0.125 0.0754 0.151 0.0912 0.073 0.67 275 235 280 345 295 355 18.20 27.60
3X300+150 0.100 0.0601 0.122 0.0733 0.073 0.68 305 260 315 385 335 400 22.80 34.50
3X400+185 0.0778 0.0470 0.0961 0.0580 0.072 0.70 335 290 375 425 360 435 30.40 46.00
3X500+240 0.0605 0.0366 0.0759 0.0459 0.072 0.70 370 320 425 470 390 520 38.00 57.50
3X630+300 0.0469 0.0283 0.0610 0.0368 0.072 0.70 405 350 480 555 470 675 47.90 72.50
Note : Normal current ratings are given in standard conditions (as given in page no - 40,41), if site conditions are different, current rating should be multiplied by
rating factor as given in page no. 42

14
Table -10 TECHNICAL DETAIL FOR HAVELLS 1.1 KV FOUR CORE, AL/CUCOPPER COND.,
PVC INSULATED, GALVANIZED STEEL WIRE/STRIP ARMOURED CABLES
Cable Code : AYFY/ YFY, AYWY/ YWY Ref. Spec. : IS :1554PT -1
Physical Parameters
SIZE Minimum Nominal Minimum ARMOURING WITH FLAT STRIP ( AYFY/ YFY) ARMOURING WITH ROUND WIRES ( AYWY/ YWY)
Cross- No of Thickness Thickness Nominal Minimum Approx. Approx. Net Wt Nominal Minimum Approx. Approx. Net Wt
-sectional Strands in of of Thickness Thickness of Overall of cable (Kg/KM) Diameter Thickness of Overall of cable ( Kg/KM)
area Conductor Insulation) inner Sh. of armour outer sheath Diameter With Al cond With Cu Cond. of armour outer sheath Diameter With Al cond With Cu Cond.
( sqmm) Al Cu (mm) (mm) (mm) (mm) (mm) AYFY YFY (mm) (mm) (mm) AYWY YWY
4 — 1/7 1.0 0.30 N/A N/A N/A N/A N/A 1.40 1.24 18 650 800
6 1 1/7 1.0 0.30 N/A N/A N/A N/A N/A 1.40 1.24 21 880 1030
10 1 6 1.0 0.30 0.8 1.40 21 750 998 1.60 1.40 22 900 1150
16 6 6 1.0 0.30 0.8 1.40 22 860 1260 1.60 1.40 23 1120 1520
25 6 6 1.2 0.30 0.8 1.40 25 1100 1720 1.60 1.40 27 1400 2020
35 6 6 1.2 0.30 0.8 1.40 28 1300 2170 1.60 1.56 30 1600 2470
50 6 6 1.4 0.40 0.8 1.56 32 1600 2850 2.00 1.56 34 2200 3445
70 12 12 1.4 0.40 0.8 1.56 35 2000 3740 2.00 1.56 37 2650 4390
95 15 15 1.6 0.40 0.8 1.72 40 2600 5000 2.00 1.72 42 3300 5660
120 15 18 1.6 0.50 0.8 1.88 43 3050 6030 2.00 1.88 47 3850 6830
150 15 18 1.8 0.50 0.8 1.88 48 3600 7325 2.5 2.04 51 4850 8575
185 30 30 2.0 0.60 0.8 2.04 52 4300 8890 2.5 2.20 56 5800 10390
240 30 34 2.2 0.60 0.8 2.36 59 5400 11355 2.50 2.36 62 7000 12960
300 30 34 2.4 0.70 0.8 2.52 67 6600 14050 3.15 2.68 70 9200 16650
400 53 53 2.6 0.70 0.8 2.84 74 8200 18128 3.15 2.84 76 11000 20930
500 53 53 3.0 0.70 0.8 3.00 80 10500 22900 4.00 3.00 86 15000 27400
630 53 53 3.4 0.70 0.8 3.00 90 13000 28625 4.00 3.00 96 18000 33630

Cross- Sectional View


1 CONDUCTOR : Material - Aluminium /Copper
*Shape : ~AL . Cond :- 6 & 10SQMM -Solid circular, 16sqmm & above : Stranded compacted shaped
~Copper . Cond :- 4 & 6sqmm -solid/ stranded non compacted circular , 10sqmm : Stranded compacted circular,16sqmm & above : Stranded
compacted shaped
2
INSULATION : PVC Type A of IS :5831/ OPTION : HR PVC ( Type -C of IS -5831), Colour : Red, Yellow, Blue, Black
3
INNER SHEATH : PVC as per IS :1554PT-1
4
ARMOURING : Single layer of Galvanized steel Round wires / Flat Strips
5
OUTER SHEATH : PVC TYPE ST-1 OF IS : 5831 ‘— OPTIONS : PVC TYPE ST-2 OF IS : 5831/ FR TYPE/ FRLS TYPE
COLOUR OF OUTER SHEATH : BLACK . OPTIONS : any other colour as per requirement.
~ Tabulated approx. net wt. of cables are only guidelines for transportation, loading &unloading purpose ..
~ Please ref page no 43 for normal delivery lengths & packing details.
Electrical Parameters
SIZE Max. Cond. D.C. Approx. Cond. A.C. App.Reactance App. Capecitance Normal* Current Rating in Amps Short Circuit Current
cross-sectional Resistance at Resistance at of cable at 50HZ of cable With Aluminium cond. With Copper cond. Rating for 1Sec.duration
area (Sq MM) 20oC in Ohm/km 70oC in Ohm/km in ohms/km in micro F/KM Ground Duct Air Ground Duct Air in K. Amps
Al Cu Al Cu Al Cu
4 —— 4.61 —— 5.53 0.098 0.23 28 23 23 36 30 30 0.304 0.460
6 4.61 3.08 5.53 3.70 0.096 0.28 35 30 30 45 38 39 0.456 0.690
10 3.08 1.83 3.70 2.20 0.091 0.34 46 39 40 60 50 52 0.760 1.150
16 1.91 1.15 2.29 1.38 0.085 0.40 60 50 51 77 64 66 1.220 1.840
25 1.20 0.727 1.44 0.87 0.083 0.42 76 63 70 99 81 90 1.900 2.880
35 0.868 0.524 1.04 0.63 0.082 0.48 92 77 86 120 99 110 2.660 4.030
50 0.641 0.387 0.769 0.464 0.082 0.49 110 95 105 145 125 135 3.800 5.750
70 0.443 0.268 0.532 0.322 0.076 0.56 135 115 130 175 150 165 5.320 8.050
95 0.320 0.193 0.384 0.232 0.076 0.58 165 140 155 210 175 200 7.220 10.900
120 0.253 0.153 0.304 0.184 0.075 0.63 185 155 180 240 195 230 9.120 13.800
150 0.206 0.1240 0.247 0.1488 0.074 0.63 210 175 205 270 225 265 11.40 17.300
185 0.164 0.0991 0.197 0.1189 0.074 0.64 235 200 240 300 255 305 14.10 21.300
240 0.125 0.0754 0.151 0.0912 0.073 0.67 275 235 280 345 295 355 18.20 27.600
300 0.100 0.0601 0.122 0.0733 0.073 0.68 305 260 315 385 335 400 22.80 34.500
400 0.0778 0.0470 0.0961 0.0580 0.072 0.70 335 290 375 425 360 435 30.40 46.000
500 0.0605 0.0366 0.0759 0.0459 0.072 0.70 370 320 425 470 390 520 38.00 57.500
630 0.0469 0.0283 0.0610 0.0368 0.072 0.70 405 350 480 555 470 675 47.90 72.500
Note : Normal current ratings are given in standard conditions (as given in page no - 40,41), if site conditions are different, current rating should be multiplied by
rating factor as given in page no. 42

15
Table -11 TECHNICAL DETAIL FOR HAVELLS 1.1 KV 1.5 SQ MM COPPER COND.,
PVC INSULATED, GALVANIZED STEEL WIRE/STRIP ARMOURED CONTROL CABLES
Cable Code : YY/YFY/ YWY Ref. Spec. : IS :1554PART -1
Physical Parameters
No Minimum UNARMOURED ( YY) ARMOURED WITH FLAT STRIPS ( YFY) ARMOURED WITH ROUND WIRES ( YWY)
of Thick. Nom thick. Approx. Approx. Net Wt Nominal Minimum Approx. Approx. Net Wt Nominal Minimum Approx. Approx. Net Wt
Cores of inner of outer Overall of cable ( Kg/KM) Thickness Thickness Overall of cable ( Kg/KM) Dia of Thickness Overall of cable ( Kg/KM)
Sheath Sheath Diameter (mm) of Armour of outr sh. Diameter (mm) Armour of outr sh. Diameter (mm) with with
( mm) mm Solid cond Std. Cond. Solid cond Std. Cond. strip( mm) (mm) Solid cond Std. Cond. Solid cond Std. Cond. wire ( mm) (mm) Solid cond Std. Cond. Solid cond Std. Cond.

2 0.30 1.8 12 12 180 180 N/A N/A N/A N/A N/A N/A 1.40 1.24 13 14 400 420
3 0.30 1.8 12.5 13 200 210 N/A N/A N/A N/A N/A N/A 1.40 1.24 14 14 450 450
4 0.30 1.8 13 14 230 250 N/A N/A N/A N/A N/A N/A 1.40 1.24 15 15 500 500
5 0.30 1.8 14 14 250 250 N/A N/A N/A N/A N/A N/A 1.40 1.24 16 16 520 550
6 0.30 1.8 15 15 290 300 N/A N/A N/A N/A N/A N/A 1.40 1.24 17 17 580 600
7 0.30 1.8 15 15 310 320 N/A N/A N/A N/A N/A N/A 1.40 1.24 17 17 650 680
10 0.30 1.8 18 19 420 450 N/A N/A N/A N/A N/A N/A 1.40 1.40 20 21 800 840
12 0.30 1.8 19 20 470 500 0.80 1.24 19 20 700 745 1.60 1.40 21 22 940 970
14 0.30 1.8 20 20 530 550 0.80 1.40 20 21 800 820 1.60 1.40 22 23 1000 1050
16 0.30 1.8 21 21 600 600 0.80 1.40 21 22 850 900 1.60 1.40 23 24 1100 1100
19 0.30 2.0 22 23 700 720 0.80 1.40 22 23 950 1000 1.60 1.40 24 25 1200 1250
24 0.30 2.0 25 26 850 900 0.80 1.40 25 27 1150 1200 1.60 1.40 27 28 1450 1500
27 0.30 2.0 26 27 920 995 0.80 1.40 26 27 1250 1300 1.60 1.40 28 29 1500 1550
30 0.30 2.0 27 28 1000 1050 0.80 1.40 27 28 1330 1400 1.60 1.40 29 30 1650 1700
37 0.30 2.0 28 29 1200 1240 0.80 1.40 29 30 1530 1600 1.60 1.40 30 32 1850 1950
40 0.30 2.0 29 30 1270 1300 0.80 1.40 30 31 1650 1750 1.60 1.56 32 35 2000 2100
44 0.30 2.0 31 33 1400 1450 0.80 1.56 32 34 1850 1950 1.60 1.56 34 36 2200 2300
52 0.40 2.0 33 35 1650 1700 0.80 1.56 34 35 2050 2150 2.00 1.56 36 38 2700 2800
61 0.40 2.2 35 37 1850 1950 0.80 1.56 35 37 2300 2450 2.00 1.56 38 40 3000 3100

Cross- Sectional View


1 CONDUCTOR : MATERIAL : Annealed bare copper / option - Tinned Construction : SOLID / STRANDED
2 INSULATION MATERIAL : PVC Type A of IS :5831/ OPTION : HR PVC ( Type -C of IS -5831) Nominal insulation thickness - 0.80mm
Cores identification : Up to 5Cores by colour coding & more than 5 cores 5cores : By colour coding / Nos. printing on cores as per IS :1554pt-1
3
INNER SHEATH : Extruded PVC as per IS :1554PT-1
4 ARMOURING : Single layer of Galvanized steel Round wires / Flat Strips as applicable
5 OUTER SHEATH : PVC TYPE ST-1 OF IS : 5831‘— OPTIONS : PVC TYPE ST-2 OF IS : 5831/ FR TYPE/ FRLS TYPE
COLOUR OF OUTER SHEATH : BLACK . OPTIONS : any other colour as per requirement
~ Tabulated approx. net wt. of cables are only guidelines for transportation, loading &unloading purpose .
~ Please ref page no 43 for normal delivery lengths & packing details.

Electrical Parameters
Max. Cond. D.C. App. Cond. A.C. Reactance Appro Normal* Current Rating in Amps Short Circuit Current
Resistance at Resistance at of cable Capecitance With general insulation With H. R. insulation Rating for 1Sec.duration
20oC in Ohm/km in Ohm/km at 50HZ of cable Ground Duct Air Ground Duct Air With Gen. Purpose With Heat Resis.
at 70oC at 85oC in ohms/km in microF/KM Insulation Insulation
2 12.10 14.52 15.2 0.112 0.20 23 20 20 26 24 24 0.173 0.156
3 12.10 14.52 15.2 0.112 0.20 21 17 17 24 21 21 0.173 0.156
4 12.10 14.52 15.2 0.112 0.20 21 17 17 24 21 21 0.173 0.156
5 12.10 14.52 15.2 0.112 0.20 21 17 17 24 21 21 0.173 0.156
6 12.10 14.52 15.2 0.112 0.20 15 13 13 17 16 16 0.173 0.156
7 12.10 14.52 15.2 0.112 0.20 14 13 13 16 15 15 0.173 0.156
10 12.10 14.52 15.2 0.112 0.20 13 11 11 15 13 13 0.173 0.156
12 12.10 14.52 15.2 0.112 0.20 12 10 10 14 12 12 0.173 0.156
14 12.10 14.52 15.2 0.112 0.20 11 10 10 13 12 12 0.173 0.156
16 12.10 14.52 15.2 0.112 0.20 11 9 9 13 11 11 0.173 0.156
19 12.10 14.52 15.2 0.112 0.20 10 9 9 11 11 11 0.173 0.156
24 12.10 14.52 15.2 0.112 0.20 9 8 8 10 10 10 0.173 0.156
27 12.10 14.52 15.2 0.112 0.20 9 8 8 10 10 10 0.173 0.156
30 12.10 14.52 15.2 0.112 0.20 9 7 7 10 8 8 0.173 0.156
37 12.10 14.52 15.2 0.112 0.20 8 7 7 9 8 8 0.173 0.156
40 12.10 14.52 15.2 0.112 0.20 8 7 7 9 8 8 0.173 0.156
44 12.10 14.52 15.2 0.112 0.20 7 7 7 8 7 7 0.173 0.156
52 12.10 14.52 15.2 0.112 0.20 6 6 6 7 7 7 0.173 0.156
61 12.10 14.52 15.2 0.112 0.20 6 6 6 7 7 7 0.173 0.156
Note : Normal current ratings are given in standard conditions (as given in page no -40,41), if site conditions are different, current rating should be multiplied by
rating factor as given in page no. 42

16
Table -12 TECHNICAL DETAIL FOR HAVELLS 1.1 KV 2.5 SQ MM COPPER COND.,
PVC INSULATED, |GALVANIZED STEEL WIRE/STRIP ARMOURED CONTROL CABLES
Cable Code : YY/YFY/ YWY Ref. Spec. : IS :1554PART -1
Physical Parameters
No Minimum UNARMOURED ( YY) ARMOURED WITH FLAT STRIPS ( YFY) (ARMOURED WITH ROUND WIRES ( YWY)
of Thick. Nom thick. Approx. Approx. Net Wt Nominal Minimum Approx. Approx. Net Wt Minimum Minimum Approx. Approx. Net Wt
Cores of inner of outer Overall of cable ( Kg/KM) Thickness Thickness Overall of cable ( Kg/KM) Dia of Thickness Overall of cable ( Kg/KM)
Sheath Sheath Diameter (mm) Armour outer of armour of outr. sth. Diameter (mm) Armour outer sheath Diameter (mm)
( mm) mm Solid cond Std. Cond. Solid cond Std. Cond. strip( mm) (mm) Solid cond Std. Cond. Solid cond Std. Cond. wire ( mm) (mm) Solid cond Std. Cond. Solid cond Std. Cond.

2 0.30 1.8 13 13 220 240 N/A N/A N/A N/A N/A N/A 1.40 1.24 14 15 480 500
3 0.30 1.8 14 14 260 270 N/A N/A N/A N/A N/A N/A 1.40 1.24 15 16 530 550
4 0.30 1.8 15 15 310 320 N/A N/A N/A N/A N/A N/A 1.40 1.24 16 17 600 620
5 0.30 1.8 16 16 340 350 N/A N/A N/A N/A N/A N/A 1.40 1.24 17 18 640 680
6 0.30 1.8 17 17 390 420 N/A N/A N/A N/A N/A N/A 1.40 1.24 19 20 730 750
7 0.30 1.8 17 17 424 440 N/A N/A N/A N/A N/A N/A 1.40 1.24 19 20 760 790
10 0.30 1.8 20 21 570 600 0.80 1.40 21 22 850 900 1.60 1.40 23 24 1100 1150
12 0.30 2.0 21 22 670 700 0.80 1.40 22 23 950 1000 1.60 1.40 24 25 1180 1250
14 0.30 2.0 22 24 750 800 0.80 1.40 23 24 1050 1035 1.60 1.40 25 26 1300 1350
16 0.30 2.0 24 25 840 900 0.80 1.40 24 25 1120 1150 1.60 1.40 26 27 1400 1450
19 0.30 2.0 25 26 950 1000 0.80 1.40 25 26 1250 1330 1.60 1.40 27 28 1550 1620
24 0.30 2.0 28 30 1200 1260 0.80 1.40 29 30 1550 1630 1.60 1.56 31 32 1900 2000
27 0.30 2.0 29 31 1300 1350 0.80 1.40 30 31 1650 1750 1.60 1.56 32 33 2050 2100
30 0.30 2.0 30 32 1400 1500 0.80 1.56 31 32 1800 1920 1.60 1.56 33 34 2200 2250
37 0.40 2.2 33 34 1700 1800 0.80 1.56 34 35 2100 2225 2.00 1.56 36 37 2800 2900
40 0.40 2.2 34 36 1850 1900 0.80 1.56 35 36 2300 2400 2.00 1.56 37 39 2950 3100
44 0.40 2.2 36 38 2000 2100 0.80 1.56 37 37 2500 2600 2.00 1.56 40 41 3200 3350
52 0.40 2.2 38 40 2350 2450 0.80 1.56 39 41 2850 2950 2.00 1.72 42 43 3600 3700
61 0.40 2.2 40 43 2700 2800 0.80 1.56 41 43 3250 3350 2.00 1.72 44 46 4000 4200

Cross- Sectional View


1 CONDUCTOR : MATERIAL : Annealed bare copper / option :Tinned Construction : SOLID / STRANDED
2 INSULATION MATERIAL : PVC Type A of IS :5831/ OPTION : HR PVC (Type -C of IS -5831) Nominal insulation thickness -
0.90mm Cores identification : Up to 5Cores by colour coding & more than 5 cores 5cores : By colour coding / Nos. printing on
cores as per IS :1554pt-1
3
INNER SHEATH : Extruded PVC as per IS :1554PT-1
4 ARMOURING : Single layer of Galvanized steel Round wires / Flat Strips as applicable
5 OUTER SHEATH : PVC TYPE ST-1 OF IS : 5831 ‘— OPTIONS : PVC TYPE ST-2 OF IS : 5831/ FR TYPE/ FRLS TYPE
COLOUR OF OUTER SHEATH : BLACK . OPTIONS : any other colour as per requirement.
~ Tabulated approx. net wt. of cables are only guidelines for transportation, loading &unloading purpose .
~ Please ref page no 43 for normal delivery lengths & packing details.

Electrical Parameters
Max. Cond. D.C. App. Cond. A.C. Reactance Appro Normal* Current Rating in Amps Short Circuit Current
Resistance at Resistance at of cable Capecitance With general insulation With H. R. insulation Rating for 1Sec.duration
20oC in Ohm/km in Ohm/km at 50HZ of cable Ground Duct Air Ground Duct Air General Heat
at 70oC at 85oC in ohms/km in microF/KM Insulation Insulation
2 7.41 8.89 9.34 0.107 0.22 32 27 27 38 32 32 0.288 0.260
3 7.41 8.89 9.34 0.107 0.22 27 24 24 30 28 28 0.288 0.260
4 7.41 8.89 9.34 0.107 0.22 27 24 24 30 28 28 0.288 0.260
5 7.41 8.89 9.34 0.107 0.22 27 24 24 30 28 28 0.288 0.260
6 7.41 8.89 9.34 0.107 0.22 21 18 18 24 21 21 0.288 0.260
7 7.41 8.89 9.34 0.107 0.22 20 17 17 22 20 20 0.288 0.260
10 7.41 8.89 9.34 0.107 0.22 18 15 15 20 16 16 0.288 0.260
12 7.41 8.89 9.34 0.107 0.22 17 14 14 19 16 16 0.288 0.260
14 7.41 8.89 9.34 0.107 0.22 16 13 13 18 15 15 0.288 0.260
16 7.41 8.89 9.34 0.107 0.22 15 13 13 17 15 15 0.288 0.260
19 7.41 8.89 9.34 0.107 0.22 14 12 12 16 14 14 0.288 0.260
24 7.41 8.89 9.34 0.107 0.22 13 11 11 14 13 13 0.288 0.260
27 7.41 8.89 9.34 0.107 0.22 12 10 10 13 12 12 0.288 0.260
30 7.41 8.89 9.34 0.107 0.22 12 10 10 13 12 12 0.288 0.260
37 7.41 8.89 9.34 0.107 0.22 11 9 9 12 10 10 0.288 0.260
40 7.41 8.89 9.34 0.107 0.22 11 9 9 12 10 10 0.288 0.260
44 7.41 8.89 9.34 0.107 0.22 10 9 9 11 10 10 0.288 0.260
52 7.41 8.89 9.34 0.107 0.22 9 8 8 10 10 10 0.288 0.260
61 7.41 8.89 9.34 0.107 0.22 8 8 8 9 9 9 0.288 0.260
Note : Normal current ratings are given in standard conditions (as given in page no -40,41), if site conditions are different, current rating should be multiplied by
rating factor as given in page no. 42

17
Table -13 TECHNICAL DETAIL FOR HAVELLS 1.1 KV SINGLE CORE,
AL/COPPER COND., XLPE INSULATED, UN-ARMOURED CABLES
Cable Code : A2XY/2XY Ref. Spec. : IS :7098PT-1
Physical Parameters
SIZE Minimum Nominal Nominal Approx. Approx. Weight of cable in kg /km
cross-sectional No of Strand in Thickness of Thickness of Overal
area ( Sq MM) Conductor Insulation) outer sheath Diameter With Al Conductor With Cooper conductor
Al Cu (mm) (mm) (mm) A2XY 2XY
4 — 1/7 0.7 1.8 8 70 95
6 1 1/7 0.7 1.8 9 80 120
10 1 6 0.7 1.8 10 100 160
16 6 6 0.7 1.8 11 130 230
25 6 6 0.9 1.8 12 180 335
35 6 6 0.9 1.8 13 230 450
50 6 6 1.0 1.8 15 300 610
70 12 12 1.1 1.8 16 370 800
95 15 15 1.1 1.8 18 460 1050
120 15 18 1.2 1.8 20 550 1300
150 15 18 1.4 2.0 22 620 1550
185 30 30 1.6 2.0 24 820 1950
240 30 34 1.7 2.0 27 1000 2500
300 30 34 1.8 2.0 30 1200 3050
400 53 53 2.0 2.2 33 1550 4000
500 53 53 2.2 2.2 36 1900 5000
630 53 53 2.4 2.2 40 2400 6300
800 53 53 2.6 2.4 47 3000 7950
1000 53 53 2.8 2.6 51 3750 9950

Cross- Sectional View


1 CONDUCTOR : Material - Aluminium /Copper
*Shape : ~AL . Cond :- 6 & 10 SQMM -Solid circular, 16 sq.mm & above : Stranded compacted circular
~Copper. Cond :- 4 & 6 sq. mm-solid/ stranded non compacted circular, 10 sq. mm & above : Stranded compacted circular
2
INSULATION : Crosslinked Polyethylene ( XLPE) ( Natural colour)
3 OUTER SHEATH : PVC TYPE ST-2 OF IS : 5831 ‘— OPTIONS : FR TYPE/ FRLS TYPE
COLOUR OF OUTER SHEATH : BLACK . OPTIONS : any other colour as per requirement.

- Tabulated approx. net wt. of cables are only guidelines for transportation, loading & unloading purpose..
- Please ref page no 43 for normal delivery lengths & packing details.

Electrical Parameters
SIZE Max. Cond. D.C. Approx. Cond. A.C. App. Reactance App. Capecitance Normal* Current Rating in Amps Short Circuit Current
cross-sectional Resistance at Resistance at at 50HZ of cable With Aluminium cond. With Copper cond. Rating for 1Sec.duration
o o
area (Sq MM) 20 C in Ohm/km 90 C in Ohm/km in ohms/km in microF/KM Ground Duct Air Ground Duct Air in K. Amps
Al Cu Al Cu Al Cu
4 — 4.61 — 5.90 0.136 0.29 — — — 48 47 45 0.376 0.572
6 4.61 3.08 5.90 3.94 0.128 0.34 48 45 45 60 59 57 0.564 0.858
10 3.08 1.83 3.94 2.34 0.118 0.42 62 62 61 80 78 77 0.940 1.430
16 1.91 1.15 2.44 1.47 0.108 0.50 81 80 83 104 102 106 1.504 2.288
25 1.20 0.727 1.54 0.931 0.102 0.52 99 90 115 130 115 145 2.350 3.575
35 0.868 0.524 1.11 0.671 0.097 0.60 117 110 135 155 140 175 3.290 5.005
50 0.641 0.387 0.820 0.495 0.092 0.63 138 125 170 185 165 215 4.700 7.150
70 0.443 0.268 0.567 0.343 0.088 0.68 168 155 210 225 200 270 6.580 10.01
95 0.320 0.193 0.411 0.248 0.085 0.79 204 185 255 265 235 330 8.930 13.59
120 0.253 0.153 0.325 0.197 0.082 0.79 230 210 300 300 265 380 11.28 17.16
150 0.206 0.1240 0.265 0.159 0.082 0.79 265 230 342 335 300 430 14.10 21.45
185 0.164 0.0991 0.211 0.127 0.082 0.79 295 260 385 380 335 495 17.39 26.46
240 0.125 0.0754 0.162 0.0976 0.079 0.84 340 300 450 435 385 590 22.56 34.32
300 0.100 0.0601 0.130 0.0778 0.078 0.86 390 335 519 490 430 670 28.20 42.90
400 0.0778 0.0470 0.1023 0.0618 0.077 0.88 450 380 605 550 480 780 37.60 57.20
500 0.0605 0.0366 0.0808 0.0489 0.076 0.90 500 430 700 610 530 900 47.00 71.50
630 0.0469 0.0283 0.0648 0.0391 0.075 0.94 555 485 809 680 590 1020 59.22 90.09
800 0.0367 0.0221 0.0530 0.0319 0.075 0.97 625 530 935 740 630 1140 75.20 114.40
1000 0.0291 0.0176 0.0444 0.0268 0.068 1.01 690 570 1065 780 660 1250 94.00 143.00
Note : Normal current ratings are given in standard conditions (as given in page no -40,41), if site conditions are different, current rating should be multiplied by
rating factor as given in page no. 42

18
Table -14 TECHNICAL DETAIL FOR HAVELLS 1.1 KV TWO CORE, AL/COPPER COND.,
XLPE INSULATED, UN-ARMOURED CABLES
Cable Code : A2XY/ 2XY Ref. Spec. : IS :7098PART -1
Physical Parameters
SIZE Minimum Nominal Minimum Nominal
Approx. Net Wt
Cross- No of Thickness of Thickness of Thickness of Approx.
of cable (Kg/KM)
-sectional Strands in Insulation) inner sheath OUTER sheath overall
area Conductor Diameter With Al Cond With Cu Cond.
( sqmm) Al Cu (mm) (mm) (mm) (mm) A2XY 2XY
4 — 1/7 0.7 0.30 1.80 13 200 250
6 1 1/7 0.7 0.30 1.80 14 330 400
10 1 6 0.7 0.30 1.80 17 350 470
16 6 6 0.7 0.30 1.80 17 310 500
25 6 6 0.9 0.30 2.00 19 400 700
35 6 6 0.9 0.30 2.00 20 480 900
50 6 6 1.0 0.30 2.00 22 590 1200
70 12 12 1.1 0.30 2.00 25 760 1630
95 15 15 1.1 0.40 2.20 28 1000 2200
120 15 18 1.2 0.40 2.20 31 1200 2700
150 15 18 1.4 0.40 2.20 33 1400 3300
185 30 30 1.6 0.50 2.40 37 1750 4000
240 30 34 1.7 0.50 2.60 41 2000 5000
300 30 34 1.8 0.60 2.80 44 2700 6400
400 53 53 2.0 0.60 3.00 48 3350 8300
500 53 53 2.2 0.70 3.40 54 4200 10400
630 53 53 2.4 0.70 3.60 62 5300 13000

Cross- Sectional View


1 CONDUCTOR : Material - Aluminium /Copper
*Shape : ~AL . Cond :- 6 & 10 sqmm -Solid circular, 16sqmm & above : Stranded compacted shaped
~Copper . Cond :- 4 & 6 sqmm -solid/ stranded non compacted circular, 10 sqmm : Stranded compacted circular,16 sqmm & above : Stranded compacted shaped

2
INSULATION : Crosslinked Polyethylene (XLPE) (Red & Black colour)
INNER SHEATH : PVC as per IS :7098PT-1
3
OUTER SHEETH : PVC TYPE ST-2 OF IS:5831' -- OPTIONS: FR TYPE/FRLS TYPE
4
COLOUR OF OUTER SHEATH : BLACK, OPTIONS : any other colour as per requirement.
~ Tabulated approx. net wt. of cables are only guidelines for transportation, loading &unloading purpose.
~ Please ref page no 43 for normal delivery lengths & packing details.

Electrical Parameters
SIZE Max. Cond. D.C. Approx. Cond. A.C. App.Reactance App. Capecitance Normal* Current Rating in Amps Short Circuit Current
cross-sectional Resistance at Resistance at at 50HZ of cable With Aluminium cond. With Copper cond. Rating for 1Sec.duration
area (Sq MM) 20oC in Ohm/km 90oC in Ohm/km in ohms/km in microF/KM Ground Duct Air Ground Duct Air in K. Amps
Al Cu Al Cu Al Cu
4 — 4.61 — 5.90 0.098 0.11 34 28 30 44 37 39 0.376 0.572
6 4.61 3.08 5.90 3.94 0.090 0.13 43 37 40 55 47 50 0.564 0.858
10 3.08 1.83 3.94 2.34 0.084 0.16 57 48 53 74 61 67 0.940 1.430
16 1.91 1.15 2.44 1.47 0.080 0.18 78 61 70 94 78 85 1.50 2.29
25 1.20 0.727 1.54 0.931 0.080 0.20 95 80 99 120 100 125 2.35 3.58
35 0.868 0.524 1.11 0.671 0.080 0.23 116 94 117 145 120 155 3.29 5.01
50 0.641 0.387 0.820 0.495 0.078 0.24 140 110 140 170 145 190 4.70 7.15
70 0.443 0.268 0.567 0.343 0.077 0.26 170 140 176 210 175 235 6.58 10.01
95 0.320 0.193 0.411 0.248 0.084 0.29 200 165 221 250 210 290 8.93 13.59
120 0.253 0.153 0.325 0.197 0.072 0.29 225 185 258 285 240 330 11.28 17.16
150 0.206 0.1240 0.265 0.159 0.072 0.29 255 210 294 315 270 375 14.10 21.45
185 0.164 0.0991 0.211 0.127 0.072 0.29 285 235 339 355 300 435 17.39 26.46
240 0.125 0.0754 0.162 0.098 0.072 0.31 325 270 402 410 350 510 22.56 34.32
300 0.100 0.0601 0.130 0.078 0.071 0.33 370 305 461 460 390 590 28.20 42.90
400 0.0778 0.0470 0.1023 0.0618 0.070 0.33 435 350 542 520 440 670 37.60 57.20
500 0.0605 0.0366 0.0808 0.0489 0.070 0.34 481 405 624 580 480 750 47.00 71.50
630 0.0469 0.0283 0.0648 0.0391 0.069 0.36 537 470 723 680 575 875 59.22 90.09
Note : Normal current ratings are given in standard conditions (as given in page no -40,41), if site conditions are different, current rating should be multiplied by
rating factor as given in page no. 42

19
Table -15 TECHNICAL DETAIL FOR HAVELLS 1.1 KV THREE CORES,
AL/COPPER COND., XLPE INSULATED, UN-ARMOURED CABLES
Cable Code : A2XY/ 2XY Ref. Spec. : IS:7098 PART -1
Physical Parameters
SIZE Cross- Minimum No of Nominal Minimum Nominal thick. Approx. Approx. Net Wt
-sectional Strands in thickness of thickness of of outer Overall of cable ( Kg/KM)
area Conductor Insulation) inner Sh. Sheath Diameter With Al cond With Cu Cond.
( sqmm) Al Cu (mm) (mm) (mm) (mm) A2XY 2XY
4 — 1/7 0.7 0.30 1.80 14 225 300
6 1 1/7 0.7 0.30 1.80 16 330 440
10 1 6 0.7 0.30 1.80 18 400 580
16 6 6 0.7 0.30 1.80 18 400 700
25 6 6 0.9 0.30 2.00 21 530 1000
35 6 6 0.9 0.30 2.00 22 640 1300
50 6 6 1.0 0.30 2.00 25 800 1700
70 12 12 1.1 0.40 2.20 30 1100 2400
95 15 15 1.1 0.40 2.20 32 1350 3100
120 15 18 1.2 0.40 2.20 35 1650 3800
150 15 18 1.4 0.50 2.40 39 2050 4800
185 30 30 1.6 0.50 2.60 43 2500 5950
240 30 34 1.7 0.60 2.80 49 3150 7600
300 30 34 1.8 0.60 3.00 53 3850 9400
400 53 53 2.0 0.70 3.20 59 4850 12000
500 53 53 2.2 0.70 3.60 66 6100 15000
630 53 53 2.4 0.70 3.80 73 7650 19000

Cross- Sectional View


1 CONDUCTOR : Material - Aluminium /Copper
*Shape : ~AL . Cond :- 6 & 10 SQMM -Solid circular, 16sqmm & above : Stranded compacted shaped
~ Copper. Cond :- 4 & 6 sqmm -solid/ stranded non compacted circular, 10sqmm : Stranded compacted circular,16sqmm & above : Stranded compacted shaped
2 INSULATION : Crosslinked Polyethylene (XLPE) (Red, Yellow & Blue colour)
3 INNER SHEATH : PVC as per IS :7098PT-1
4 OUTER SHEATH : PVC TYPE ST-2 OF IS : 5831 ‘— OPTIONS : FR TYPE/FRLS TYPE
COLOUR OF OUTER SHEATH : BLACK . OPTIONS : any other colour as per requirement.

~ Tabulated approx. net wt. of cables are only guidelines for transportation, loading &unloading purpose.
~ Please ref page no 43 for normal delivery lengths & packing details.

Electrical Parameters
SIZE Max. Cond. D.C. Approx. Cond. A.C. App. App. Capecitance Normal* Current Rating in Amps Short Circuit Current
cross-sectional Resistance at Resistance at Reactance of of cable With Aluminium cond. With Copper cond. Rating for 1Sec.duration
area (Sq MM) 20oC in Ohm/km 90oC in Ohm/km cable at 50HZ in microF/KM Ground Duct Air Ground Duct Air in K. Amps
Al Cu Al Cu in ohms/km Al Cu
4 — 4.61 — 5.90 0.098 0.11 34 28 30 44 37 39 0.376 0.572
6 4.61 3.08 5.90 3.94 0.090 0.13 43 37 40 55 47 50 0.564 0.858
10 3.08 1.83 3.94 2.34 0.084 0.16 57 48 53 74 61 67 0.940 1.430
16 1.91 1.15 2.44 1.47 0.080 0.18 78 61 70 94 78 85 1.50 2.29
25 1.20 0.727 1.54 0.931 0.080 0.20 95 80 99 120 100 125 2.35 3.58
35 0.868 0.524 1.11 0.671 0.080 0.23 116 94 117 145 120 155 3.29 5.01
50 0.641 0.387 0.820 0.495 0.078 0.24 140 110 140 170 145 190 4.70 7.15
70 0.443 0.268 0.567 0.343 0.077 0.26 170 140 176 210 175 235 6.58 10.01
95 0.320 0.193 0.411 0.248 0.074 0.29 200 165 221 250 210 290 8.93 13.59
120 0.253 0.153 0.325 0.197 0.072 0.29 225 185 258 285 240 330 11.28 17.16
150 0.206 0.1240 0.265 0.159 0.072 0.29 255 210 294 315 270 375 14.10 21.45
185 0.164 0.0991 0.211 0.127 0.072 0.29 285 235 339 355 300 435 17.39 26.46
240 0.125 0.0754 0.162 0.098 0.072 0.31 325 270 402 410 350 510 22.56 34.32
300 0.100 0.0601 0.130 0.078 0.071 0.33 370 305 461 460 390 590 28.20 42.90
400 0.0778 0.0470 0.1023 0.0618 0.070 0.33 435 350 542 520 440 670 37.60 57.20
500 0.0605 0.0366 0.0808 0.0489 0.070 0.34 481 405 624 580 480 750 47.00 71.50
630 0.0469 0.0283 0.0648 0.0391 0.069 0.36 537 470 723 680 575 875 59.22 90.09
Note : Normal current ratings are given in standard conditions (as given in page no - 40,41), if site conditions are different, current rating should be multiplied by
rating factor as given in page no. 42

20
Table -16 TECHNICAL DETAIL FOR HAVELLS 1.1 KV
THREE & HALF CORE, AL/COPPER COND., XLPE INSULATED, UN-ARMOURED CABLES
Cable Code : A2XY/ 2XY Ref. Spec. : IS :7098PART -1
Physical Parameters
SIZE Minimum No of Nominal Minimum Nominal
Cross- strands Thickness of Thickness of thickness of Approx. Approx. Net Wt
-sectional in conductor Insulation) inner sheath OUTER overall of cable ( Kg/KM)
area Phase / Neutral Phase / Neutral Sheath Diameter With Al cond With Cu Cond.
( sqmm) Al Cu (mm) (mm) (mm) (mm) A2XY 2XY
3X25+16 6/6 6/6 0.90/0.70 0.30 2.00 22 600 1150
3X35+16 6/6 6/6 0.90/0.70 0.30 2.00 24 700 1450
3X50+25 6/6 6/6 1.00/0.90 0.30 2.00 27 900 2000
3X70+35 12/6 12/6 1.10/0.90 0.40 2.20 31 1200 2700
3X95+50 15/6 15/6 1.10/1.00 0.40 2.20 34 1500 3600
3X120+70 15/12 18/12 1.20/1.10 0.40 2.20 38 1900 4500
3X150+70 15/12 18/12 1.40/1.10 0.50 2.40 43 2300 5500
3X185+95 30/15 30/15 1.60/1.10 0.50 2.60 46 2800 6800
3X240+120 30/15 34/18 1.70/1.20 0.60 2.80 52 3600 8700
3X300+150 30/15 34/18 1.80/1.40 0.60 3.00 57 4400 10800
3X400+185 53/30 53/30 2.00/1.60 0.70 3.40 65 5600 14000
3X500+240 53/30 53/34 2.20/1.70 0.70 3.60 73 7000 17500
3X630+300 53/30 53/34 2.40/1.80 0.70 4.00 82 8900 22000

Cross- Sectional View


1 CONDUCTOR : Material - Aluminium /Copper
*Shape : Standed compacted shaped as per Calss - 2 of IS:8130
2
INSULATION : Crosslinked Polyethylene (XLPE) (Phase - Red, Yellow, Blue & neutral - Black colour)
3 INNER SHEATH : PVC as per IS :7098PT-1
4
OUTER SHEATH : PVC TYPE ST-2 OF IS : 5831 ‘— OPTIONS : FR TYPE FRLS TYPE
COLOUR OF OUTER SHEATH : BLACK . OPTIONS : any other colour as per requirement.

~ Tabulated approx. net wt. of cables are only guidelines for transportation, loading & unloading purpose.
~ Please ref page no 43 for normal delivery lengths & packing details.

Electrical Parameters
SIZE Max. Cond. D.C. Approx. Cond. A.C. App. Reactance App. Capecitance Normal* Current Rating in Amps Short Circuit Current
cross-sectional Resistance at Resistance at of cable at 50HZ of cable With Aluminium cond. With Copper cond. Rating for 1Sec.duration
o o
area (Sq MM) 20 C in Ohm/km 90 C in Ohm/km in ohms/km in microF/KM Ground Duct Air Ground Duct Air in K. Amps
Al Cu Al Cu Al Cu

3X25+16 1.20 0.727 1.54 0.931 0.080 0.20 95 80 99 120 100 125 2.35 3.58
3X35+16 0.868 0.524 1.11 0.671 0.080 0.23 116 94 117 145 120 155 3.29 5.01
3X50+25 0.641 0.387 0.820 0.495 0.078 0.24 140 110 140 170 145 190 4.70 7.15
3X70+35 0.443 0.268 0.567 0.343 0.077 0.26 170 140 176 210 175 235 6.58 10.01
3X95+50 0.320 0.193 0.411 0.248 0.074 0.29 200 165 221 250 210 290 8.93 13.59
3X120+70 0.253 0.153 0.325 0.197 0.072 0.29 225 185 258 285 240 330 11.28 17.16
3X150+70 0.206 0.1240 0.265 0.159 0.072 0.29 255 210 294 315 270 375 14.10 21.45
3X185+95 0.164 0.0991 0.211 0.127 0.072 0.29 285 235 339 355 300 435 17.39 26.46
3X240+120 0.125 0.0754 0.162 0.098 0.072 0.31 325 270 402 410 350 510 22.56 34.32
3X300+150 0.100 0.0601 0.130 0.078 0.071 0.33 370 305 461 460 390 590 28.20 42.90
3X400+185 0.0778 0.0470 0.1023 0.0618 0.070 0.33 435 350 542 520 440 670 37.60 57.20
3X500+240 0.0605 0.0366 0.0808 0.0489 0.070 0.34 481 405 624 580 480 750 47.00 71.50
3X630+300 0.0469 0.0283 0.0648 0.0391 0.069 0.36 537 470 723 680 575 875 59.22 90.09
Note : Normal current ratings are given in standard conditions (as given in page no - 40,41), if site conditions are different, current rating should be multiplied by
rating factor as given in page no. 42

21
Table -17 TECHNICAL DETAIL FOR HAVELLS 1.1 KV
FOUR CORE, AL/COPPER COND., XLPE INSULATED, UN-ARMOURED CABLES
Cable Code : A2XY/ 2XY Ref. Spec. : IS :7098PART -1
Physical Parameters

SIZE Minimum Nominal Minimum Minimum


Cross- No of Thickness Thickness Thickness of Approx. Approx. Net Wt
-sectional Strands in of of outer sheath over all of cable ( Kg/KM)
area Conductor (Insulation) inner sheath Diameter With Al cond With Cu Cond.
( sqmm) Al Cu (mm) (mm) (mm) (mm) A2XY 2XY
4 — 1/7 0.7 0.30 1.80 17 250 350
6 1 1/7 0.7 0.30 1.80 18 350 500
10 1 6 0.7 0.30 1.80 20 400 650
16 6 6 0.7 0.30 1.80 20 450 850
25 6 6 0.9 0.30 2.00 24 660 1300
35 6 6 0.9 0.30 2.00 26 800 1700
50 6 6 1.0 0.30 2.00 29 1000 2200
70 12 12 1.1 0.40 2.20 34 1400 3100
95 15 15 1.1 0.40 2.20 37 1700 4000
120 15 18 1.2 0.50 2.40 41 2150 5150
150 15 18 1.4 0.50 2.60 45 2650 6350
185 30 30 1.6 0.50 2.80 50 3250 7850
240 30 34 1.7 0.60 3.00 56 4100 10000
300 30 34 1.8 0.70 3.20 63 5050 12050
400 53 53 2.0 0.70 3.60 70 6400 16000
500 53 53 2.2 0.70 3.80 79 8000 20000
630 53 53 2.4 0.70 4.00 88 10000 26000

Cross- Sectional View


1 CONDUCTOR : Material - Aluminium /Copper
*Shape : ~AL . Cond :- 6 & 10SQMM -Solid circular, 16sqmm & above : Stranded compacted shaped
~Copper . Cond :- 4 & 6sqmm -solid/ stranded non compacted circular , 10sqmm : Stranded compacted circular,16sqmm & above : Stranded compacted shaped
2 INSULATION : Crosslinked Polyethylene (XLPE) (Red, Yellow, Blue & Black colour)
3 INNER SHEATH : PVC as per IS :7098PT-1
4
OUTER SHEATH : PVC TYPE ST-2 OF IS : 5831 ‘— OPTIONS : FR TYPE/ FRLS TYPE
COLOUR OF OUTER SHEATH : BLACK . OPTIONS : any other colour as per requirement.
~ Tabulated approx. net wt. of cables are only guidelines for transportation, loading & unloading purpose.
~ Please ref page no 43 for normal delivery lengths & packing details.

Electrical Parameters
SIZE Max. Cond. D.C. Approx. Cond. A.C. App. Reactance App. Capecitance Normal* Current Rating in Amps Short Circuit Current
cross-sectional Resistance at Resistance at of cable at of cable With Aluminium cond. With Copper cond. Rating for 1Sec.duration
area (Sq MM) 20oC in Ohm/km 90oC in Ohm/km 50HZ in microF/KM Ground Duct Air Ground Duct Air in K. Amps
Al Cu Al Cu in ohms/km Al Cu
4 — 4.61 — 5.90 0.098 0.11 34 28 30 44 37 39 0.376 0.572
6 4.61 3.08 5.90 3.94 0.090 0.13 43 37 40 55 47 50 0.564 0.858
10 3.08 1.83 3.94 2.34 0.084 0.16 57 48 53 74 61 67 0.940 1.430
16 1.91 1.15 2.44 1.47 0.080 0.18 78 61 70 94 78 85 1.50 2.29
25 1.20 0.727 1.54 0.931 0.080 0.20 95 80 99 120 100 125 2.35 3.58
35 0.868 0.524 1.11 0.671 0.080 0.23 116 94 117 145 120 155 3.29 5.01
50 0.641 0.387 0.820 0.495 0.078 0.24 140 110 140 170 145 190 4.70 7.15
70 0.443 0.268 0.567 0.343 0.077 0.26 170 140 176 210 175 235 6.58 10.01
95 0.320 0.193 0.411 0.248 0.074 0.29 200 165 221 250 210 290 8.93 13.59
120 0.253 0.153 0.325 0.197 0.072 0.29 225 185 258 285 240 330 11.28 17.16
150 0.206 0.1240 0.265 0.159 0.072 0.29 255 210 294 315 270 375 14.10 21.45
185 0.164 0.0991 0.211 0.127 0.072 0.29 285 235 339 355 300 435 17.39 26.46
240 0.125 0.0754 0.162 0.098 0.072 0.31 325 270 402 410 350 510 22.56 34.32
300 0.100 0.0601 0.130 0.078 0.071 0.33 370 305 461 460 390 590 28.20 42.90
400 0.0778 0.0470 0.1023 0.0618 0.070 0.33 435 350 542 520 440 670 37.60 57.20
500 0.0605 0.0366 0.0808 0.0489 0.070 0.34 481 405 624 580 480 750 47.00 71.50
630 0.0469 0.0283 0.0648 0.0391 0.069 0.36 537 470 723 680 575 875 59.22 90.09
Note : Normal current ratings are given in standard conditions (as given in page no - 40,41), if site conditions are different, current rating should be multiplied by
rating factor as given in page no. 42

22
Table -18 TECHNICAL DETAIL FOR HAVELLS 1.1 KV SINGLE CORE, AL/COPPER COND.,
XLPE INSULATED, AL WIRE/STRIP ARMOURED CABLES
Cable Code : A2XFaY/ 2XFaY, A2XWaY/ 2XWaY Ref. Spec. : IS :7098PART -1
Physical Parameters
SIZE Minimum Nominal ARMOURING WITH FLAT STRIP ( A2XFaY/2XFaY) ARMOURING WITH ROUND WIRES ( A2XWaY/ 2XWaY)
Cross- No of Nominal Minimum Approx. Approx. Net Wt Nominal Minimum Approx. Approx. Net Wt
-sectional Strands in Thickness of Thickness Thickness of Overall of cable ( Kg/KM) Diameter Thickness of Overall of cable ( Kg/KM)
area Conductor Insulation) Strip outer sheath Diameter With Al cond With Cu Cond. of wire outer sheath Diameter With Al cond With Cu Cond.
( sqmm) Al Cu (mm) (mm) (mm) (mm) A2XFaY 2XFaY (mm) (mm) (mm) A2XWaY 2XWaY
4 — 1/7 1.0 N/A N/A N/A N/A N/A 1.40 1.24 10 90 130
6 1 1/7 1.0 N/A N/A N/A N/A N/A 1.40 1.24 11 130 170
10 1 6 1.0 N/A N/A N/A N/A N/A 1.40 1.24 12 160 222
16 6 6 1.0 N/A N/A N/A N/A N/A 1.40 1.24 13 200 300
25 6 6 1.2 N/A N/A N/A N/A N/A 1.40 1.24 14 300 455
35 6 6 1.2 N/A N/A N/A N/A N/A 1.40 1.24 15 350 567
50 6 6 1.3 N/A N/A N/A N/A N/A 1.40 1.24 17 420 730
70 12 12 1.4 N/A N/A N/A N/A N/A 1.40 1.24 19 520 954
95 15 15 1.4 0.80 1.40 21 600 1195 1.60 1.40 22 650 1235
120 15 18 1.5 0.80 1.40 23 700 1450 1.60 1.40 24 750 1494
150 15 18 1.7 0.80 1.40 24 800 1730 1.60 1.40 25 850 1780
185 30 30 1.9 0.80 1.40 26 950 2100 1.60 1.40 28 1000 2147
240 30 34 2.0 0.80 1.40 30 1200 2690 1.60 1.40 30 1250 2738
300 30 34 2.1 0.80 1.56 32 1400 3270 1.60 1.56 33 1500 3360
400 53 53 2.4 0.80 1.56 36 1750 4230 2.00 1.56 38 1900 4380
500 53 53 2.6 0.80 1.56 39 2150 5250 2.00 1.56 41 2350 5450
630 53 53 2.8 0.80 1.72 44 2700 6610 2.00 1.72 46 2900 6806
800 53 53 3.1 0.80 1.72 48 3350 8320 2.00 1.88 51 3600 8560
1000 53 53 3.3 0.80 1.88 54 4100 10300 2.50 2.04 56 4600 10800

Cross- Sectional View


1 CONDUCTOR : Material - Aluminium /Copper
*Shape : ~AL . Cond :- 6 & 10SQMM -Solid circular, 16 sqmm & above : Stranded compacted shaped circular
2 ~Copper. Cond :- 4 & 6sqmm -solid/ stranded non compacted circular , 10sqmm : Stranded compacted circular
INSULATION : Crosslinked Polyethylene (XLPE) (Natural colour)
3
ARMOURING : Single layer of Aluminium Round wires / Flat Strips
4
OUTER SHEATH : PVC TYPE ST-2 OF IS : 5831 ‘— OPTIONS : PVC TYPE
COLOUR OF OUTER SHEATH : BLACK . OPTIONS : any other colour as per requirement.

~ Tabulated approx. net wt. of cables are only guidelines for transportation, loading &unloading purpose ..
~ Please ref page no 43 for normal delivery lengths & packing details.

Electrical Parameters
SIZE Max. Cond. D.C. Approx. Cond. A.C. App. Reactance App. Capecitance Normal* Current Rating in Amps Short Circuit Current
cross-sectional Resistance at Resistance at of cable at 50HZ of cable With Aluminium cond. With Copper cond. Rating for 1Sec.duration
o o
area (Sq MM) 20 C in Ohm/km 90 C in Ohm/km in ohms/km in microF/KM Ground Duct Air Ground Duct Air in K. Amps
Al Cu Al Cu Al Cu
4 — 4.61 — 5.90 0.152 0.22 — — — 48 47 45 0.376 0.572
6 4.61 3.08 5.90 3.94 0.144 0.26 45 45 40 60 59 57 0.56 0.858
10 3.08 1.83 3.94 2.34 0.133 0.31 59 62 53 80 78 77 0.94 1.43
16 1.91 1.15 2.44 1.47 0.122 0.40 76 80 73 104 102 106 1.50 2.29
25 1.20 0.727 1.54 0.931 0.116 0.40 99 90 115 130 115 145 2.35 3.58
35 0.868 0.524 1.11 0.671 0.110 0.47 117 110 140 155 140 175 3.29 5.01
50 0.641 0.387 0.820 0.495 0.103 0.50 138 125 170 185 165 215 4.70 7.15
70 0.443 0.268 0.567 0.343 0.099 0.55 168 155 210 225 200 270 6.58 10.01
95 0.320 0.193 0.411 0.248 0.097 0.64 204 185 255 265 235 330 8.93 13.59
120 0.253 0.153 0.325 0.197 0.093 0.67 230 210 300 300 265 380 11.28 17.16
150 0.206 0.1240 0.265 0.159 0.091 0.67 265 230 342 335 300 430 14.10 21.45
185 0.164 0.0991 0.211 0.127 0.090 0.67 295 260 385 380 335 495 17.39 26.46
240 0.125 0.0754 0.162 0.0976 0.086 0.72 340 300 450 435 385 590 22.56 34.32
300 0.100 0.0601 0.130 0.0778 0.085 0.75 390 335 519 490 430 670 28.20 42.90
400 0.0778 0.0470 0.1023 0.0618 0.085 0.75 450 380 605 550 480 780 37.60 57.20
500 0.0605 0.0366 0.0808 0.0489 0.083 0.77 500 430 700 610 530 900 47.00 71.50
630 0.0469 0.0283 0.0648 0.0391 0.082 0.81 555 485 809 680 590 1020 59.22 90.09
800 0.0367 0.0221 0.0530 0.0319 0.081 0.88 625 530 935 740 630 1140 75.20 114.40
1000 0.0291 0.0176 0.0444 0.0268 0.081 0.88 690 570 1065 780 660 1250 94.00 143.00
Note : Normal current ratings are given in standard conditions (as given in page no - 40,41), if site conditions are different, current rating should be multiplied by
rating factor as given in page no. 42

23
Table -19 TECHNICAL DETAIL FOR HAVELLS 1.1 KV TWO CORES, AL/COPPER COND.,
XLPE INSULATED, GALVANIZED STEEL WIRE/STRIP ARMOURED CABLES
Cable Code : A2xFY/2xFY, A2XWY/ 2XWY Ref. Spec. : IS :7098 PART -1
Physical Parameters
SIZE Minimum Nominal Minimum ARMOURING WITH FLAT STRIP ( A2XFY/ 2XFY) ARMOURING WITH ROUND WIRES ( A2XWY/ 2XWY)
Cross- No of Thickness Thickness Nominal Minimum Approx. Approx. Net Wt Nominal Minimum Approx. Approx. Net Wt
-sectional Strands in of of Thickness Thickness of Overall of cable (Kg/KM) Diameter Thickness of Overall of cable ( Kg/KM)
area Conductor Insulation) inner Sh. of armour outer sheath Diameter With Al cond With Cu Cond. of wire outer sheath Diameter With Al cond With Cu Cond.
(sqmm) Al Cu (mm) (mm) (mm) (mm) (mm) A2XFY 2XFY (mm) (mm) (mm) A2XWY 2XWY
4 — 1/7 0.7 0.30 N/A N/A N/A N/A N/A 1.40 1.24 15 500 550
6 1 1/7 0.7 0.30 N/A N/A N/A N/A N/A 1.40 1.24 16 550 600
10 1 6 0.7 0.30 N/A N/A N/A N/A N/A 1.40 1.24 18 650 770
16 6 6 0.7 0.30 N/A N/A N/A N/A N/A 1.40 1.40 19 700 900
25 6 6 0.9 0.30 0.80 1.40 20 650 950 1.60 1.40 21 850 1150
35 6 6 0.9 0.30 0.80 1.40 21 750 1200 1.60 1.40 23 950 1400
50 6 6 1.0 0.30 0.80 1.40 23 900 1500 1.60 1.40 25 1100 1700
70 12 12 1.1 0.30 0.80 1.56 26 1100 1950 1.60 1.56 28 1400 2250
95 15 15 1.1 0.40 0.80 1.56 29 1350 2500 2.00 1.56 31 1850 3000
120 15 18 1.2 0.40 0.80 1.56 31 1600 3100 2.00 1.56 34 2150 3600
150 15 18 1.4 0.40 0.80 1.72 34 1900 3750 2.00 1.72 37 2450 4300
185 30 30 1.6 0.50 0.80 1.72 37 2250 4500 2.00 1.88 40 2900 5200
240 30 34 1.7 0.50 0.80 1.88 42 2800 5800 2.50 2.04 45 3850 6800
300 30 34 1.8 0.60 0.80 2.04 45 3300 7000 2.50 2.20 49 4450 8200
400 53 53 2.0 0.60 0.80 2.36 50 4100 9050 2.50 2.36 52 5350 10300
500 53 53 2.2 0.70 0.80 2.52 55 5000 11000 3.15 2.68 60 7100 13300
630 53 53 2.4 0.70 0.80 2.68 63 6100 14000 3.15 2.84 66 8500 16300

Cross- Sectional View


1 CONDUCTOR : Material - Aluminium /Copper
*Shape : ~AL . Cond :- 6 & 10SQMM -Solid circular, 16sqmm & above : Stranded compacted shaped
~Copper. Cond :- 4 & 6 sqmm -solid/ stranded non compacted circular, 10 sqmm : Stranded compacted circular,16sqmm & above : Stranded compacted shaped
2 INSULATION : Crosslinked Polyethylene (XLPE) (Red & Black colour)
3 INNER SHEATH : PVC as per IS : 7098PT-1
4 ARMOURING : Single layer of galvanized steel round wires / flat strips
5 OUTER SHEATH : PVC TYPE ST-2 OF IS : 5831 ‘— OPTIONS : FR TYPE/ FRLS TYPE
COLOUR OF OUTER SHEATH : BLACK. OPTIONS : any other colour as per requirement.
~ Tabulated approx. net wt. of cables are only guidelines for transportation, loading &unloading purpose.
~ Please ref page no 43 for normal delivery lengths & packing details.

Electrical Parameters
SIZE Max. Cond. D.C. Approx. Cond. A.C. App.Reactance App. Capecitance Normal* Current Rating in Amps Short Circuit Current
cross-sectional Resistance at Resistance at at 50HZ of cable With Aluminium cond. With Copper cond. Rating for 1Sec. duration
area (Sq MM) 20oC in Ohm/km 90oC in Ohm/km in ohms/km in microF/KM Ground Duct Air Ground Duct Air in K. Amps
Al Cu Al Cu Al Cu
4 --- 4.61 --- 5.90 0.098 0.11 34 28 30 44 37 39 0.376 0.572
6 4.61 3.08 5.90 3.94 0.090 0.13 43 37 40 55 47 50 0.564 0.858
10 3.08 1.83 3.94 2.34 0.084 0.16 57 48 53 74 61 67 0.940 1.430
16 1.91 1.15 2.44 1.47 0.080 0.18 78 61 70 94 78 85 1.50 2.29
25 1.20 0.727 1.54 0.931 0.080 0.20 95 80 99 120 100 125 2.35 3.58
35 0.868 0.524 1.11 0.671 0.080 0.23 116 94 117 145 120 155 3.29 5.01
50 0.641 0.387 0.820 0.495 0.078 0.24 140 110 140 170 145 190 4.70 7.15
70 0.443 0.268 0.567 0.343 0.077 0.26 170 140 176 210 175 235 6.58 10.1
95 0.320 0.193 0.411 0.248 0.074 0.29 200 165 221 250 210 290 8.93 13.59
120 0.253 0.153 0.325 0.197 0.072 0.29 225 185 258 285 240 330 11.28 17.16
150 0.206 0.1240 0.265 0.159 0.072 0.29 255 210 294 315 270 375 14.10 21.45
185 0.164 0.0991 0.211 0.127 0.072 0.29 285 235 339 355 300 435 17.39 26.46
240 0.125 0.0754 0.162 0.0976 0.072 0.31 325 270 402 410 350 510 22.56 34.32
300 0.100 0.0601 0.130 0.0778 0.071 0.33 370 305 461 460 390 590 28.20 42.90
400 0.0778 0.0470 0.1023 0.0618 0.070 0.33 435 350 542 520 440 670 37.60 57.20
500 0.0605 0.0366 0.0808 0.0489 0.070 0.34 481 405 624 580 480 750 47.00 71.50
630 0.0469 0.0283 0.0648 0.0391 0.069 0.36 537 470 723 680 575 875 59.22 90.09
Note : Normal current ratings are given in standard conditions (as given in page no - 40,41), if site conditions are different, current rating should be multiplied by
rating factor as given in page no. 42

24
Table -20 TECHNICAL DETAIL FOR HAVELLS 1.1 KV THREE CORES, AL/COPPER COND.,
XLPE INSULATED, GALVANIZED STEEL WIRE/STRIP ARMOURED CABLES
Cable Code : A2XFY/2XFY, A2XWY/ 2XWY Ref. Spec. : IS :7098 PART -1
Physical Parameters
SIZE Minimum Nominal Minimum ARMOURING WITH FLAT STRIP ( A2XFY/ 2XFY) ARMOURING WITH ROUND WIRES ( A2XWY/ 2XWY)
Cross- No of Thickness Thickness Nominal Minimum Approx. Approx. Net Wt Nominal Minimum Approx. Approx. Net Wt
-sectional Strands in of of Thickness Thickness of Overall of cable (Kg/KM) Diameter Thickness of Overall of cable ( Kg/KM)
area Conductor Insulation) inner Sh. of armour outer sheath Diameter With Al cond With Cu Cond. of wire outer sheath Diameter With Al cond With Cu Cond.
(sqmm) Al Cu (mm) (mm) strip (mm) (mm) (mm) A2XFY 2XFY (mm) (mm) (mm) A2XWY 2XWY
4 — 1/7 0.7 0.30 N/A N/A N/A N/A N/A 1.40 1.24 18 600 670
6 1 1/7 0.7 0.30 N/A N/A N/A N/A N/A 1.40 1.24 19 650 770
10 1 6 0.7 0.30 N/A N/A N/A N/A N/A 1.40 1.24 20 750 930
16 6 6 0.7 0.30 0.8 1.24 19 600 900 1.60 1.40 20 800 1100
25 6 6 0.9 0.30 0.8 1.40 21 800 1200 1.60 1.40 23 1000 1450
35 6 6 0.9 0.30 0.8 1.40 23 950 1500 1.60 1.40 25 1200 1850
50 6 6 1.0 0.30 0.8 1.40 26 1100 2000 1.60 1.56 29 1450 2300
70 12 12 1.1 0.40 0.8 1.56 29 1450 2700 2.00 1.56 32 2000 3300
95 15 15 1.1 0.40 0.8 1.56 32 1750 3500 2.00 1.56 35 2350 4100
120 15 18 1.2 0.40 0.8 1.56 35 2100 4200 2.00 1.72 39 2750 4900
150 15 18 1.4 0.50 0.8 1.72 42 2500 5200 2.00 1.88 43 3250 6000
185 30 30 1.6 0.50 0.8 1.88 44 3000 6300 2.50 2.04 48 4200 7500
240 30 34 1.7 0.60 0.8 2.04 49 3750 8200 2.50 2.20 53 5100 9500
300 30 34 1.8 0.60 0.8 2.20 54 4500 10000 2.50 2.36 58 6000 11300
400 53 53 2.0 0.70 0.8 2.52 60 5600 13000 3.15 2.68 65 7950 15200
500 53 53 2.2 0.70 0.8 2.68 66 6900 16000 3.15 2.84 72 9500 18500
630 53 53 2.4 0.70 0.8 2.84 74 8550 20000 4.00 3.00 81 12600 23700

Cross- Sectional View


1 CONDUCTOR : Material - Aluminium /Copper
*Shape : ~AL . Cond :- 6 & 10 SQMM -Solid circular, 16 sqmm & above : Stranded compacted shaped
~Copper. Cond :- 4 & 6 sqmm -solid/ stranded non compacted circular, 10 sqmm : Stranded compacted circular,16 sqmm & above : Stranded compacted shaped
2 INSULATION : Crosslinked Polyethylene (XLPE) Red, Yellow, Blue)
3 INNER SHEATH : PVC as per IS :7098PT-1
4 ARMOURING : Single layer of Galvanized steel Round wires / Flat Strips
5 OUTER SHEATH : PVC TYPE ST-2 OF IS : 5831 ‘— OPTIONS : FR TYPE/ FRLS TYPE
COLOUR OF OUTER SHEATH : BLACK. OPTIONS : any other colour as per requirement.
~ Tabulated approx. net wt. of cables are only guidelines for transportation, loading & unloading purpose.
~ Please ref page no 43 for normal delivery lengths & packing details.

Electrical Parameters
SIZE Max. Cond. D.C. Approx. Cond. A.C. App.Reactance App. Capecitance Normal* Current Rating in Amps Short Circuit Current
cross-sectional Resistance at Resistance at at 50HZ of cable With Aluminium cond. With Copper cond. Rating for 1Sec. duration
area (Sq MM) 20oC in Ohm/km 90oC in Ohm/km in ohms/km in microF/KM Ground Duct Air Ground Duct Air in K. Amps
Al Cu Al Cu Al Cu
4 --- 4.61 --- 5.90 0.098 0.11 34 28 30 44 37 39 0.376 0.572
6 4.61 3.08 5.90 3.94 0.090 0.13 43 37 40 55 47 50 0.564 0.858
10 3.08 1.83 3.94 2.34 0.084 0.16 57 48 53 74 61 67 0.940 1.430
16 1.91 1.15 2.44 1.47 0.080 0.18 78 61 70 94 78 85 1.50 2.29
25 1.20 0.727 1.54 0.931 0.080 0.20 95 80 99 120 100 125 2.35 3.58
35 0.868 0.524 1.11 0.671 0.080 0.23 116 94 117 145 120 155 3.29 5.01
50 0.641 0.387 0.820 0.495 0.078 0.24 140 110 140 170 145 190 4.70 7.15
70 0.443 0.268 0.567 0.343 0.077 0.26 170 140 176 210 175 235 6.58 10.01
95 0.320 0.193 0.411 0.248 0.074 0.29 200 165 221 250 210 290 8.93 13.59
120 0.253 0.153 0.325 0.197 0.072 0.29 225 185 258 285 240 330 11.28 17.16
150 0.206 0.1240 0.265 0.159 0.072 0.29 255 210 294 315 270 375 14.10 21.45
185 0.164 0.0991 0.211 0.127 0.072 0.29 285 235 339 355 300 435 17.39 26.46
240 0.125 0.0754 0.162 0.0976 0.072 0.31 325 270 402 410 350 510 22.56 34.32
300 0.100 0.0601 0.130 0.0778 0.071 0.33 370 305 460 460 390 590 28.20 42.90
400 0.0778 0.0470 0.1023 0.0618 0.070 0.33 435 350 542 520 440 670 37.60 57.20
500 0.0605 0.0366 0.0808 0.0489 0.070 0.34 481 405 624 580 480 750 47.00 71.50
630 0.0469 0.0283 0.0648 0.0391 0.069 0.36 537 470 723 680 575 875 59.22 90.09
Note : Normal current ratings are given in standard conditions (as given in page no - 40,41), if site conditions are different, current rating should be multiplied by
rating factor as given in page no. 42

25
Table -21 TECHNICAL DETAIL FOR HAVELLS 1.1 KV THREE AND HALF CORES,
AL/CUCOPPER COND.,
XPLE INSULATED, GALVANIZED STEEL WIRE/STRIP ARMOURED CABLES
Cable Code : 3.5 Core - A2XFY / 2XFY, A2XWY / 2XWY Ref. Spec. : IS :7098PART -1
Physical Parameters
SIZE Minimum Nominal Minimum ARMOURING WITH FLAT STRIP ( A2XFY/ 2XFY)ARMOURING WITH ROUND WIRES ( A2XWY/ 2XWY)
Cross- No of Thickness Thickness Nominal Minimum Approx. Approx. Net Wt Nominal Minimum Approx. Approx. Net Wt
-sectional Strands in of of Thickness Thickness of Overall of cable ( Kg/KM) Diameter Thickness of Overall of cable (Kg/KM)
area Conductor Insulation) inner Sh. of Armr. outer sheath Diameter With Al cond With Cu Cond. of wire outer sheath Diameter With Al cond With Cu Cond.
(mm)
( sqmm) Al Cu (mm) Strip (mm) (mm) (mm) A2XFY 2XFY (mm) (mm) (mm) A2XWY 2XWY

3X25+16 6/6 6/6 0.90/0.70 0.30 0.80 1.40 23 900 1400 1.60 1.40 25 1100 1700
3X35+16 6/6 6/6 0.90/0.70 0.30 0.80 1.40 25 1000 1800 1.60 1.40 27 1300 2000
3X50+25 6/6 6/6 1.00/0.90 0.30 0.80 1.40 28 1200 2300 1.60 1.56 30 1600 2700
3X70+35 12/6 12/6 1.10/0.90 0.40 0.80 1.56 32 1600 3200 2.00 1.56 35 2200 3700
3X95+50 15/6 15/6 1.10/1.00 0.40 0.80 1.56 35 2000 4100 2.00 1.56 38 2600 4600
3X120+70 15/12 18/12 1.20/1.10 0.40 0.80 1.72 39 2400 5100 2.00 1.72 42 3100 5700
3X150+70 15/12 18/12 1.40/1.10 0.50 0.80 1.72 43 2800 6000 2.00 1.88 46 3600 6800
3X185+95 30/15 30/15 1.60/1.10 0.50 0.80 1.88 47 3400 7400 2.50 2.04 51 4700 8700
3X240+120 30/15 34/18 1.70/1.20 0.60 0.80 2.04 53 4300 9500 2.50 2.20 56 5700 10500
3X300+150 30/15 34/18 1.80/1.40 0.60 0.80 2.20 57 5000 11500 2.50 2.36 60 6700 13000
3X400+185 53/30 53/30 2.00/1.60 0.70 0.80 2.52 66 6400 14500 3.15 2.68 71 9000 17000
3X500+240 53/30 53/34 2.20/1.70 0.70 0.80 2.68 74 7900 18000 3.15 2.84 79 11000 21500
3X630+300 53/30 53/34 2.40/1.80 0.70 0.80 3.00 82 9900 23000 4.00 3.00 88 14500 28000

Cross- Sectional View


1 CONDUCTOR : Material - Aluminium /Copper
*Shape : Stranded compacted shaped as per class-2 of IS:8130
2
INSULATION : Crosslinked Polyethylene (XLPE) (Phase, Red, Yellow, Blue & Neutral - Black Colour
3
INNER SHEATH : PVC as per IS :7098PT-1
4
ARMOURING : Single layer of Galvanized steel Round wires / Flat Strips
5
OUTER SHEATH : PVC TYPE ST-2 OF IS : 5831 ‘— OPTIONS : FR TYPE/ FRLS TYPE
COLOUR OF OUTER SHEATH : BLACK . OPTIONS : any other colour as per requirement.
~ Tabulated approx. net wt. of cables are only guidelines for transportation, loading &unloading purpose.
~ Please ref page no 43 for normal delivery lengths & packing details.

Electrical Parameters
SIZE Max. Cond. D.C. Approx. Cond. A.C. App..Reactance App. Capecitance Normal* Current Rating in Amps Short Circuit Current
cross-sectional Resistance at Resistance at at 50HZ of cable With Aluminium cond. With Copper cond. Rating for 1Sec.duration
area (Sq MM) 20oC in Ohm/km 90oC in Ohm/km in ohms/km in microF/KM Ground Duct Air Ground Duct Air in K. Amps
Al Cu Al Cu Al Cu

3X25+16 1.20 0.727 1.54 0.931 0.080 0.20 95 80 99 120 100 125 2.35 3.58
3X35+16 0.868 0.524 1.11 0.671 0.080 0.23 116 94 117 145 120 155 3.29 5.01
3X50+25 0.641 0.387 0.820 0.495 0.078 0.24 140 110 140 170 145 190 4.70 7.15
3X70+35 0.443 0.268 0.567 0.343 0.077 0.26 170 140 176 210 175 235 6.58 10.01
3X95+50 0.320 0.193 0.411 0.248 0.074 0.29 200 165 221 250 210 290 8.93 13.59
3X120+70 0.253 0.153 0.325 0.197 0.072 0.29 225 185 258 285 240 330 11.28 17.16
3X150+70 0.206 0.1240 0.265 0.159 0.072 0.29 255 210 294 315 270 375 14.10 21.45
3X185+95 0.164 0.0991 0.211 0.127 0.072 0.29 285 235 339 355 300 435 17.39 26.46
3X240+120 0.125 0.0754 0.162 0.098 0.072 0.31 325 270 402 410 350 510 22.56 34.32
3X300+150 0.100 0.0601 0.130 0.078 0.071 0.33 370 305 461 460 390 590 28.20 42.90
3X400+185 0.0778 0.0470 0.1023 0.0618 0.070 0.33 435 350 542 520 440 670 37.60 57.20
3X500+240 0.0605 0.0366 0.0808 0.0489 0.070 0.34 481 405 624 580 480 750 47.00 71.50
3X630+300 0.0469 0.0283 0.0648 0.0391 0.069 0.36 537 470 723 680 575 875 59.22 90.09
Note : Normal current ratings are given in standard conditions (as given in page no -40,41), if site conditions are different, current rating should be multiplied by
rating factor as given in page no. 42

26
Table -22 TECHNICAL DETAIL FOR HAVELLS 1.1 KV FOUR CORES,
AL/COPPER COND.,
XLPE INSULATED, GALVANIZED STEEL WIRE/STRIP ARMOURED CABLES
Cable Code : A2XFY/2XFY, A2XWY/ 2XWY Ref. Spec. : IS :7098 PART -1
Physical Parameters
SIZE Minimum Nominal Minimum ARMOURING WITH FLAT STRIP ( A2XFY/2XFY) ARMOURING WITH ROUND WIRES ( A2XWY/ 2XWY)
Cross- No of Thickness Thickness Nominal Minimum Approx. Approx. Net Wt Nominal Minimum Approx. Approx. Net Wt
-sectional Strands in of of Thickness Thickness of Overall of cable (Kg/KM) Diameter Thickness of Overall of cable ( Kg/KM)
area Conductor Insulation) inner Sh. of armour outer sheath Diameter With Al cond With Cu Cond. of wire outer sheath Diameter With Al cond With Cu Cond.
(sqmm) Al Cu (mm) (mm) strip (mm) (mm) (mm) A2XFY 2XYF (mm) (mm) (mm) A2XWY 2XWY
4 — 1/7 0.7 0.30 N/A N/A N/A N/A N/A 1.40 1.24 18 550 650
6 1 1/7 0.7 0.30 N/A N/A N/A N/A N/A 1.40 1.24 19 600 750
10 1 6 0.7 0.30 N/A N/A N/A N/A N/A 1.40 1.40 21 670 950
16 6 6 0.7 0.30 0.80 1.40 20 700 1100 1.60 1.40 22 925 1300
25 6 6 0.9 0.30 0.80 1.40 24 900 1500 1.60 1.40 26 1200 1770
35 6 6 0.9 0.30 0.80 1.40 27 1100 2000 1.60 1.40 28 1450 2200
50 6 6 1.0 0.30 0.80 1.56 30 1400 2500 1.60 1.56 32 1750 2850
70 12 12 1.1 0.40 0.80 1.56 34 1800 3400 2.00 1.56 37 2400 4000
95 15 15 1.1 0.40 0.80 1.56 37 2200 4400 2.00 1.72 40 2900 5150
120 15 18 1.2 0.50 0.80 1.72 41 2700 5600 2.00 1.88 44 3500 6300
150 15 18 1.4 0.50 0.80 1.88 46 3200 6800 2.50 2.04 49 4500 8000
185 30 30 1.6 0.50 0.80 2.04 51 3900 8300 2.50 2.20 54 5200 9700
240 30 34 1.7 0.60 0.80 2.20 57 4850 10500 2.50 2.36 65 6400 12000
300 30 34 1.8 0.70 0.80 2.36 63 5850 13000 3.15 2.52 68 8300 15400
400 53 53 2.0 0.70 0.80 2.68 71 7320 17000 3.15 2.84 76 10000 19500
500 53 53 2.2 0.70 0.80 2.84 79 9000 21000 4.00 3.00 86 13500 25000
630 53 53 2.4 0.70 0.80 3.00 88 11000 27000 4.00 3.00 94 16000 30500

Cross- Sectional View


1
CONDUCTOR : Material - Aluminium /Copper
*Shape : ~AL . Cond :- 6 & 10 SQMM -Solid circular, 16 sqmm & above : Stranded compacted shaped
~Copper. Cond :- 4 & 6 sqmm -solid/ stranded non compacted circular, 10 sqmm : Stranded compacted circular,16 sqmm & above : Stranded compacted shaped
2 INSULATION : Crosslinked Polyethylene (XLPE) (Red, Yellow, Blue & Black)
3 INNER SHEATH : PVC as per IS :7098PT-1
4 ARMOURING : Single layer of Galvanized steel Round wires / Flat Strips
5 OUTER SHEATH : PVC TYPE ST-2 OF IS : 5831 ‘— OPTIONS : FR TYPE/ FRLS TYPE
COLOUR OF OUTER SHEATH : BLACK. OPTIONS : any other colour as per requirement.
~ Tabulated approx. net wt. of cables are only guidelines for transportation, loading &unloading purpose.
~ Please ref page no 43 for normal delivery lengths & packing details.

Electrical Parameters
SIZE Max. Cond. D.C. Approx. Cond. A.C. App.Reactance App. Capecitance Normal* Current Rating in Amps Short Circuit Current
cross-sectional Resistance at Resistance at at 50HZ of cable With Aluminium cond. With Copper cond. Rating for 1Sec. duration
area (Sq MM) 20oC in Ohm/km 90oC in Ohm/km in ohms/km in microF/KM Ground Duct Air Ground Duct Air in K. Amps
Al Cu Al Cu Al Cu
4 — 4.61 — 5.90 0.098 0.11 34 28 30 44 37 39 0.376 0.572
6 4.61 3.08 5.90 3.94 0.090 0.13 43 37 40 55 47 50 0.564 0.858
10 3.08 1.83 3.94 2.34 0.084 0.16 57 48 53 74 61 67 0.940 1.430
16 1.91 1.15 2.44 1.47 0.080 0.18 78 61 70 94 78 85 1.50 2.29
25 1.20 0.727 1.54 0.931 0.080 0.20 95 80 99 120 100 125 2.35 3.58
35 0.868 0.524 1.11 0.671 0.080 0.23 116 94 117 145 120 155 3.29 5.01
50 0.641 0.387 0.820 0.495 0.078 0.24 140 110 140 170 145 190 4.70 7.15
70 0.443 0.268 0.567 0.343 0.077 0.26 170 140 176 210 175 235 6.58 10.01
95 0.320 0.193 0.411 0.248 0.074 0.29 200 165 221 250 210 290 8.93 13.59
120 0.253 0.153 0.325 0.197 0.072 0.29 225 185 258 285 240 330 11.28 17.16
150 0.206 0.1240 0.265 0.159 0.072 0.29 255 210 294 315 270 375 14.10 21.45
185 0.164 0.0991 0.211 0.127 0.072 0.29 285 235 339 355 300 435 17.39 26.46
240 0.125 0.0754 0.162 0.0976 0.072 0.31 325 270 402 410 350 510 22.56 34.32
300 0.100 0.0601 0.130 0.0778 0.071 0.33 370 305 460 460 390 590 28.20 42.90
400 0.0778 0.0470 0.1023 0.0618 0.070 0.33 435 350 542 520 440 670 37.60 57.20
500 0.0605 0.0366 0.0808 0.0489 0.070 0.34 481 405 624 580 480 750 47.00 71.50
630 0.0469 0.0283 0.0648 0.0391 0.069 0.36 537 470 723 680 575 875 59.22 90.09
Note : Normal current ratings are given in standard conditions (as given in page no - 40,41), if site conditions are different, current rating should be multiplied by
rating factor as given in page no. 42

27
Table -23 TECHNICAL DETAIL FOR HAVELLS 3.3 KV
SINGLE CORE, AL/COPPER COND., XLPE INSULATED, ARMOURED CABLES
Cable Code : A2XWaY/2XWaY ( 3.3KV-EARTHED/ UNEARTHED GRADE) Ref. Spec. : IS :7098PART -2
Physical Parameters
SIZE Nominal Nominal Diameter Minimum Thickness Approx. Approx.
cross- Sectional Insulation of Armour Wire of Outer Sheath Over all cable wt ( kg /km)
area(Sqmm) thickness (mm) (mm) Diameter With Al. With Cu
( mm) (mm) Cond. Cond.
25 2.5 1.40 1.24 18 350 500
35 2.5 1.40 1.24 19 400 600
50 2.5 1.40 1.40 21 500 800
70 2.5 1.60 1.40 23 650 1100
95 2.5 1.60 1.40 25 750 1350
120 2.5 1.60 1.40 26 850 1600
150 2.5 1.60 1.40 28 950 1900
185 2.5 1.60 1.40 29 1100 2250
240 2.5 1.60 1.56 32 1350 2850
300 2.5 1.60 1.56 34 1550 3400
400 2.8 2.00 1.56 39 2000 4500
500 2.8 2.00 1.56 42 2400 5500
630 3.0 2.00 1.72 47 3000 6900
800 3.3 2.00 1.88 52 3650 8600
1000 3.5 2.50 2.04 56 4500 10700

Cross- Sectional View


1 CONDUCTOR :Stranded Compacted Circular Aluminium / copper as per Class -2 of IS:8130
INSULATION MATERIAL : CROSSLINKED POLYETHYLENE ( XLPE)
2 ARMOURING : Single layer of Aluminium Round wires.
3 OUTER SHEATH : PVC TYPE ST-2 OF IS : 5831 ‘— OPTIONS : PVC TYPE ST-2/ FR TYPE/ FRLS TYPE
COLOUR OF OUTER SHEATH : BLACK . OPTIONS : ANY OTHER COLOURS AS PER REQUIREMENT

~ Tabulated approx. net weights of cables are only for guidelines for transportation / loading/ unloading purpose.

Electrical Parameters
SIZE Max. Cond. D.C. Approx. Cond. A.C. Reactance of Capecitance Normal* Current Rating in Amps Short Circuit Current
cross-sectional Resistance at Resistance at cable at 50HZ of cable With Aluminium cond. With Copper cond. Rating for 1Sec.duration
area (Sq MM) 20oC in Ohm/km 90oC in Ohm/km in ohms/km in microF/KM Ground Duct Air Ground Duct Air in K. Amps
Al Cu Al Cu (Approx). (Approx). Al Cu
25 1.20 0.727 1.54 0.931 0.133 0.25 100 91 110 130 115 145 2.35 3.58
35 0.868 0.524 1.11 0.671 0.126 0.29 120 110 135 155 140 175 3.29 5.00
50 0.641 0.387 0.820 0.495 0.122 0.33 140 125 165 185 165 215 4.70 7.15
70 0.443 0.268 0.567 0.343 0.116 0.38 175 155 210 225 200 270 6.58 10.00
95 0.320 0.193 0.410 0.248 0.111 0.44 205 185 255 265 235 330 8.93 13.59
120 0.253 0.153 0.325 0.197 0.106 0.49 235 210 295 300 265 380 11.28 17.16
150 0.206 0.1240 0.265 0.159 0.103 0.53 260 230 335 335 300 430 14.10 21.45
185 0.164 0.0991 0.211 0.127 0.100 0.58 295 260 390 380 335 495 17.39 26.45
240 0.125 0.0754 0.162 0.098 0.097 0.67 340 300 460 435 385 590 22.56 34.32
300 0.100 0.0601 0.130 0.078 0.095 0.73 385 335 530 490 430 670 28.20 42.90
400 0.0778 0.0470 0.1023 0.0618 0.093 0.84 440 380 620 550 480 780 37.60 57.20
500 0.0605 0.0366 0.0808 0.0489 0.091 0.86 495 430 730 610 530 900 47.00 71.50
630 0.0469 0.0283 0.0648 0.0391 0.090 0.88 560 485 840 680 590 1020 59.22 90.10
800 0.0367 0.0221 0.0530 0.0319 0.088 0.94 620 530 960 740 630 1140 75.20 114.40
1000 0.0291 0.0176 0.0444 0.0268 0.086 0.99 670 570 1070 780 660 1250 94.00 143.00
Note : Normal current ratings are given in standard conditions (as given in page no - 40,41), if site conditions are different, current rating should be multiplied by
rating factor as given in page no. 42

28
Table -24 TECHNICAL DETAIL FOR HAVELLS 3.3 KV THREE CORES, AL/COPPER COND.,
XLPE INSULATED, ARMOURED CABLES
Cable Code : A2XFY/ 2XFY, A2XWY/2XWY (3.3KV UE/E) Ref. Spec. : IS :7098PART -2
Physical Parameters
FLAT STRIP ARMOURED ROUND WIRES ARMOURED
SIZE Nominal Minimum Nominal Minimum Approx. Approx. Nominal Minimum Approx. Approx.
cross- Insulation Inner Sheath Armour strip outer Sheath Over all cable wt ( kg /km) diameter outer Sheath Over all cable wt ( kg /km)
sectional thickness thickness thickness thickness Diameter With Al. With Cu of armour thickness Diameter With Al. With Cu
area(Sqmm) mm mm mm mm ( mm) Cond. Cond. wire ( mm) mm ( mm) Cond. Cond.

25 2.2 0.3 0.8 1.40 28 1100 1550 1.60 1.56 30 1450 1900
35 2.2 0.3 0.8 1.56 31 1300 1950 1.60 1.56 33 1600 2250
50 2.2 0.4 0.8 1.56 33 1500 2450 2.00 1.56 35 2100 3050
70 2.2 0.4 0.8 1.56 36 1800 3100 2.00 1.56 38 2400 3700
95 2.2 0.4 0.8 1.72 39 2150 3900 2.00 1.72 42 2850 4600
120 2.2 0.5 0.8 1.72 42 2500 4750 2.00 1.88 45 3300 5550
150 2.2 0.5 0.8 1.88 44 2850 5650 2.50 2.04 48 4100 6900
185 2.2 0.5 0.8 2.04 48 3350 6800 2.50 2.04 51 4650 8100
240 2.2 0.6 0.8 2.20 52 4100 8550 2.50 2.20 56 5450 9900
300 2.2 0.6 0.8 2.20 56 4750 10350 2.50 2.36 60 6300 11900
400 2.2 0.7 0.8 2.36 62 5750 13200 3.15 2.68 67 8350 15800

Cross- Sectional View


1 CONDUCTOR : Material - Aluminium /Copper - Shape : stranded compacted shaped.
2 INSULATION : Crosslinked Polyethylene (XLPE) (Red, Yellow & Blue)
3 INNER SHEATH : PVC as per IS :7098PT-1
4
ARMOURING : Single layer of Galvanized steel Round wires / Flat Strips
5 OUTER SHEATH : PVC TYPE ST-2 OF IS : 5831 ‘— OPTIONS : FR TYPE/ FRLS TYPE
COLOUR OF OUTER SHEATH : BLACK. OPTIONS : any other colour as per requirement.
~ Tabulated approx. net wt. of cables are only guidelines for transportation, loading &unloading purpose.
~ Please ref page no 43 for normal delivery lengths & packing details.

Electrical Parameters
SIZE Max. Cond. D.C. Approx. Cond. A.C. pp.. Reactance App. Capecitance Normal* Current Rating in Amps Short Circuit Current
cross-sectional Resistance at Resistance at at 50HZ of cable With Aluminium cond. With Copper cond. Rating for 1Sec.duration
area (Sq MM) 20oC in Ohm/km 90oC in Ohm/km in ohms/km in microF/KM Ground Duct Air Ground Duct Air in K. Amps
Al Cu Al Cu (APPROX.) (APPROX.) Al Cu

25 1.20 0.727 1.54 0.931 0.098 0.25 94 80 99 120 100 125 2.35 3.58
35 0.868 0.524 1.11 0.671 0.094 0.29 115 95 120 145 120 155 3.29 5.00
50 0.641 0.387 0.820 0.495 0.086 0.33 135 110 145 170 145 190 4.70 7.15
70 0.443 0.268 0.567 0.343 0.084 0.38 165 140 185 210 175 235 6.58 10.01
95 0.320 0.193 0.410 0.248 0.081 0.44 195 165 225 250 210 290 8.93 13.59
120 0.253 0.153 0.325 0.197 0.078 0.49 220 185 255 285 240 330 11.28 17.16
150 0.206 0.1240 0.265 0.159 0.076 0.53 245 210 295 315 270 375 14.10 21.45
185 0.164 0.0991 0.211 0.127 0.075 0.58 280 235 340 355 300 435 17.39 26.46
240 0.125 0.0754 0.162 0.098 0.073 0.67 320 270 400 410 350 510 22.56 34.32
300 0.100 0.0601 0.130 0.078 0.072 0.73 360 305 460 460 390 590 28.20 42.90
400 0.0778 0.0470 0.1023 0.0618 0.071 0.84 410 350 535 520 440 670 37.60 57.20
Note : Normal current ratings are given in standard conditions (as given in page no - 40,41), if site conditions are different, current rating should be multiplied by
rating factor as given in page no. 42

29
Table -25 TECHNICAL DETAIL FOR HAVELLS 3.8/6.6 KV SINGLE CORE, AL/COPPER COND.,
XLPE INSULATED, ARMOURED CABLES
Cable Code : A2XWaY/2XWaY ( 6.6KV-EARTHED GRADE) Ref. Spec. : IS :7098PART -2
Physical Parameters
SIZE Nominal Minimum Nominal Diameter Minimum Thickness Approx. Approx.
cross-Sectional Insulation Inner Sheath of Armour Wire of Outer Sheath Over all cable wt ( kg /km)
area(Sqmm) thickness thickness ( mm) ( mm) Diameter With Al. With Cu
mm mm ( mm) Cond. Cond.
25 2.8 0.3 1.60 1.40 23 600 750
35 2.8 0.3 1.60 1.40 24 650 850
50 2.8 0.3 1.60 1.40 25 700 1000
70 2.8 0.3 1.60 1.40 27 800 1250
95 2.8 0.3 1.60 1.40 28 950 1550
120 2.8 0.3 1.60 1.40 30 1050 1800
150 2.8 0.3 1.60 1.56 32 1200 2100
185 2.8 0.3 1.60 1.56 34 1400 2550
240 2.8 0.4 2.00 1.56 37 1700 3200
300 3.0 0.4 2.00 1.56 39 2000 3850
400 3.3 0.4 2.00 1.72 44 2450 4900
500 3.5 0.5 2.00 1.72 47 2800 5900
630 3.5 0.5 2.00 1.88 51 3400 7300
800 3.5 0.5 2.50 2.04 57 4300 9200
1000 3.6 0.5 2.50 2.20 61 5100 11300

Cross- Sectional View


1 CONDUCTOR : Stranded Compacted Circular Aluminium / copper as per Class -2 of IS:8130
2 Conductor screening : Extruded Semiconducting Compound
3 INSULATION MATERIAL : CROSSLINKED POLYETHYLENE (XLPE)
4
INSULATION SCREENING : Extruded semiconducting compound followed by helically wrapped 0.050mm thick copper tape.
5
INNER SHEATH : Extruded PVC
6
ARMOURING : Single layer of Aluminium Round wires.
7
OUTER SHEATH : PVC TYPE ST-2 OF IS : 5831 ‘— OPTIONS : PVC TYPE ST-2/ FR TYPE/ FRLS TYPE
COLOUR OF OUTER SHEATH : BLACK . OPTIONS : ANY OTHER COLOURS AS PER REQUIREMENT
~ Tabulated approx. net weights of cables are only for guidelines for transportation / Loading/ Unloading Purpose.

Electrical Parameters
SIZE Max. Cond. D.C. Approx. Cond. A.C. Reactance of App. Capecitance Normal* Current Rating in Amps Short Circuit Current
cross-sectional Resistance at Resistance at cable at 50HZ of cable With Aluminium cond. With Copper cond. Rating for 1Sec.duration
area (Sq MM) 20oC in Ohm/km 90oC in Ohm/km in ohms/km in microF/KM Ground Duct Air Ground Duct Air in K. Amps
Al Cu Al Cu (Approc). (Approx). Al Cu
25 1.20 0.727 1.54 0.931 0.149 0.21 100 90 120 130 115 155 2.35 3.58
35 0.868 0.524 1.11 0.671 0.142 0.24 120 105 145 155 140 185 3.29 5.00
50 0.641 0.387 0.820 0.495 0.133 0.27 140 125 170 185 160 220 4.70 7.15
70 0.443 0.268 0.567 0.343 0.127 0.31 175 155 215 225 195 275 6.58 10.01
95 0.320 0.193 0.410 0.248 0.121 0.36 205 180 260 265 235 340 8.93 13.59
120 0.253 0.153 0.325 0.197 0.116 0.39 235 205 305 300 265 390 11.28 17.16
150 0.206 0.1240 0.265 0.159 0.113 0.43 260 230 345 335 295 440 14.10 21.45
185 0.164 0.0991 0.211 0.127 0.109 0.47 295 260 395 380 330 510 17.39 26.46
240 0.125 0.0754 0.162 0.098 0.105 0.53 340 300 470 435 380 600 22.56 34.32
300 0.100 0.0601 0.130 0.078 0.104 0.54 385 335 540 490 425 680 28.20 42.90
400 0.0778 0.0470 0.1023 0.0618 0.102 0.57 440 380 630 550 480 790 37.60 57.20
500 0.0605 0.0366 0.0808 0.0489 0.100 0.60 495 430 730 610 530 910 47.00 71.50
630 0.0469 0.0283 0.0648 0.0391 0.096 0.67 560 480 840 680 580 1030 59.22 90.10
800 0.0367 0.0221 0.0530 0.0319 0.094 0.76 620 530 960 740 630 1140 75.20 114.40
1000 0.0291 0.0176 0.0444 0.0268 0.092 0.82 680 580 1070 790 670 1250 94.00 143.00
Note : Normal current ratings are given in standard conditions (as given in page no - 40,41), if site conditions are different, current rating should be multiplied by
rating factor as given in page no.. 42

30
Table -26 TECHNICAL DETAIL FOR HAVELLS 3.8/6.6 KV THREE CORES, AL/COPPER COND.,
XLPE INSULATED, ARMOURED CABLES
Cable Code : A2XFY/ 2XFY, A2XWY/2XWY (6.6KVE) Ref. Spec. : IS :7098PART -2
Physical Parameters
FLAT STRIP ARMOURED ROUND WIRES ARMOURED
SIZE Nominal Minimum Nominal Minimum Approx. Approx. Nominal Minimum Approx. Approx.
cross- Insulation Inner Sheath Armour strip outer Sheath Over all cable wt ( kg /km) diameter outer Sheath Over all cable wt (kg /km)
sectional thickness thickness thickness thickness Diameter With Al. With Cu of armour thickness Diameter With Al. With Cu
area(Sqmm) mm mm mm mm ( mm) Cond. Cond. wire (mm) mm (mm) Cond. Cond.

25 2.8 0.4 0.8 1.56 37 1800 2250 2.00 1.72 40 2500 2950
35 2.8 0.4 0.8 1.72 39 2000 2650 2.00 1.72 42 2800 3450
50 2.8 0.5 0.8 1.72 42 2300 3250 2.00 1.88 45 3200 4150
70 2.8 0.5 0.8 1.88 46 2800 4100 2.00 1.88 49 3700 5000
95 2.8 0.5 0.8 1.88 50 3300 5050 2.50 2.04 54 4700 6450
120 2.8 0.6 0.8 2.04 54 3800 6050 2.50 2.20 58 5400 7650
150 2.8 0.6 0.8 2.20 58 4300 7100 2.50 2.20 61 5900 8700
185 2.8 0.6 0.8 2.20 61 4800 8250 2.50 2.36 65 6600 10050
240 2.8 0.7 0.8 2.36 67 5900 10350 3.15 2.52 72 8400 12850
300 3.0 0.7 0.8 2.52 72 6800 12400 3.15 2.68 77 9700 15300
400 3.3 0.7 0.8 2.84 82 8500 15950 4.00 3.00 88 13000 20450

Cross- Sectional View


1 CONDUCTOR : Stranded Compacted Circular Aluminium / copper as per Class -2 of IS:8130

2 Conductor screening : Extruded Semiconducting Compound


3 INSULATION MATERIAL : CROSSLINKED POLYETHYLENE (XLPE)

4 INSULATION SCREENING : Extruded semiconducting compound followed by helically wrapped 0.050mm thick copper tape.

5 PVC FILLERS
6 INNER SHEATH : Extruded PVC
7
ARMOURING : Single layer of Galvanized Flat strip/ Round wires.
8
OUTER SHEATH : PVC TYPE ST-2 OF IS : 5831 ‘— OPTIONS : PVC TYPE ST-2/ FR TYPE/ FRLS TYPE
COLOUR OF OUTER SHEATH : BLACK . OPTIONS : ANY OTHER COLOURS AS PER REQUIREMENT
~ Tabulated approx. net weights of cables are only for guidelines for transportation / Loading/ Unloading Purpose.

Electrical Parameters
SIZE Max. Cond. D.C. Approx. Cond. A.C. Reactance of Capecitance Normal* Current Rating in Amps Short Circuit Current
cross-sectional Resistance at Resistance at cable at 50HZ of cable With Aluminium cond. With Copper cond. Rating for 1Sec.duration
area (Sq MM) 20oC in Ohm/km 90oC in Ohm/km in ohms/km in microF/KM Ground Duct Air Ground Duct Air in K. Amps
Al Cu Al Cu (APPROX.) (APPROX.) Al Cu

25 1.20 0.727 1.54 0.931 0.126 0.21 95 82 105 120 105 135 2.35 3.58
35 0.868 0.524 1.11 0.671 0.120 0.24 115 97 125 145 125 165 3.29 5.01
50 0.641 0.387 0.820 0.495 0.114 0.27 130 115 150 170 150 195 4.70 7.15
70 0.443 0.268 0.567 0.343 0.107 0.31 160 140 190 210 180 240 6.58 10.01
95 0.320 0.193 0.410 0.248 0.102 0.36 190 165 230 250 215 295 8.93 13.59
120 0.253 0.153 0.325 0.197 0.098 0.39 220 190 260 280 240 335 11.28 17.16
150 0.206 0.1240 0.265 0.159 0.095 0.43 245 210 295 310 270 380 14.10 21.45
185 0.164 0.0991 0.211 0.127 0.093 0.47 275 240 335 350 305 430 17.39 26.46
240 0.125 0.0754 0.162 0.098 0.090 0.53 315 275 395 400 350 500 22.56 34.32
300 0.100 0.0601 0.130 0.078 0.090 0.54 355 310 450 445 390 570 28.20 42.90
400 0.0778 0.0470 0.1023 0.0618 0.087 0.57 400 350 520 500 440 650 37.60 57.20

Note : Normal current ratings are given in standard conditions (as given in page no - 40,41), if site conditions are different, current rating should be multiplied by
rating factor as given in page no. 42

31
Table -27 TECHNICAL DETAIL FOR HAVELLS 6.6/6.6KV & 6.35/11 KV SINGLE CORE,
AL/COPPER COND.,
XLPE INSULATED, ARMOURED CABLES
Cable Code : A2XWaY/2XWaY (6.6KV -UNEARTHED OR 11KV EARTHED GRADE) Ref. Spec. : IS :7098PART -2
Physical Parameters
SIZE Nominal Minimum Nominal Diameter Minimum Thickness Approx. Approx.
cross-Sectional Insulation Inner Sheath of Armour Wire of Outer Sheath Over all cable wt ( kg /km)
area (Sqmm) thickness thickness (mm) (mm) Diameter With Al. With Cu
mm mm ( mm) Cond. Cond.
25 3.6 0.3 1.60 1.40 24 650 800
35 3.6 0.3 1.60 1.40 25 700 900
50 3.6 0.3 1.60 1.40 26 800 1100
70 3.6 0.3 1.60 1.40 28 900 1300
95 3.6 0.3 1.60 1.40 30 1050 1650
120 3.6 0.3 1.60 1.56 32 1200 1950
150 3.6 0.3 1.60 1.56 33 1300 2200
185 3.6 0.4 2.00 1.56 36 1600 2750
240 3.6 0.4 2.00 1.56 39 1850 3350
300 3.6 0.4 2.00 1.56 41 2050 3900
400 3.6 0.5 2.00 1.72 44 2500 5000
500 3.6 0.5 2.00 1.72 47 2900 6000
630 3.6 0.5 2.00 1.88 51 3450 7350
800 3.6 0.5 2.50 2.04 57 4300 9250
1000 3.6 0.5 2.50 2.20 61 5100 11300

Cross- Sectional View


1 CONDUCTOR : Stranded Compacted Circular Aluminium / copper as per Class -2 of IS:8130

2 Conductor screening : Extruded Semiconducting Compound


3 INSULATION MATERIAL : CROSSLINKED POLYETHYLENE (XLPE)

4 INSULATION SCREENING : Extruded semiconducting compound followed by helically wrapped 0.050mm thick copper tape.

5 PVC FILLERS
6 INNER SHEATH : Extruded PVC
7
ARMOURING : Single layer of Galvanized Flat strip/ Round wires.
8
OUTER SHEATH : PVC TYPE ST-2 OF IS : 5831 ‘— OPTIONS : PVC TYPE ST-2/ FR TYPE/ FRLS TYPE
COLOUR OF OUTER SHEATH : BLACK . OPTIONS : ANY OTHER COLOURS AS PER REQUIREMENT
~ Tabulated approx. net weights of cables are only for guidelines for transportation / Loading/ Unloading Purpose.

Electrical Parameters
SIZE Max. Cond. D.C. Approx. Cond. A.C. Reactance of Capecitance Normal* Current Rating in Amps Short Circuit Current
cross-sectional Resistance at Resistance at cable at 50HZ of cable With Aluminium cond. With Copper cond. Rating for 1Sec.duration
o o
area (Sq MM) 20 C in Ohm/km 90 C in Ohm/km in ohms/km in microF/KM Ground Duct Air Ground Duct Air in K. Amps
Al Cu Al Cu (Approx) (Approx) Al Cu
25 1.20 0.727 1.54 0.931 0.164 0.18 100 90 120 130 115 155 2.35 3.58
35 0.868 0.524 1.11 0.671 0.156 0.20 120 105 145 155 140 185 3.29 5.00
50 0.641 0.387 0.820 0.495 0.147 0.22 140 125 170 185 160 220 4.70 7.15
70 0.443 0.268 0.567 0.343 0.139 0.26 175 155 215 225 195 275 6.58 10.01
95 0.320 0.193 0.410 0.248 0.133 0.29 205 180 260 265 235 340 8.93 13.59
120 0.253 0.153 0.325 0.197 0.127 0.32 235 205 305 300 265 390 11.28 17.16
150 0.206 0.1240 0.265 0.159 0.124 0.35 260 230 345 335 295 440 14.10 21.45
185 0.164 0.0991 0.211 0.127 0.120 0.38 295 260 395 380 330 510 17.39 26.46
240 0.125 0.0754 0.162 0.098 0.117 0.43 340 300 470 435 380 600 22.56 34.32
300 0.100 0.0601 0.130 0.078 0.113 0.46 385 335 540 490 425 680 28.20 42.90
400 0.0778 0.0470 0.1023 0.0618 0.110 0.53 440 380 630 550 480 790 37.60 57.20
500 0.0605 0.0366 0.0808 0.0489 0.107 0.59 495 430 730 610 530 910 47.00 71.50
630 0.0469 0.0283 0.0648 0.0391 0.104 0.66 560 480 840 680 580 1030 59.22 90.10
800 0.0367 0.0221 0.0530 0.0319 0.100 0.74 620 530 960 740 630 1140 75.20 114.40
1000 0.0291 0.0176 0.0444 0.0268 0.098 0.82 680 580 1070 790 670 1250 94.00 143.00
Note : Normal current ratings are given in standard conditions (as given in page no -40,41), if site conditions are different, current rating should be multiplied by
rating factor as given in page no. 42

32
Table -28 TECHNICAL DETAIL FOR HAVELLS 6.6/6.6KV & 6.35/11 KV THREE CORES,
AL/COPPER COND.,
XLPE INSULATED, ARMOURED CABLES
Cable Code : A2XFY/ 2XFY, A2XWY/2XWY (6.6KV UE / 11KV E) Ref. Spec. : IS :7098PART-2
Physical Parameters
FLAT STRIP ARMOURED ROUND WIRES ARMOURED
SIZE Nominal Minimum Nominal Minimum Approx. Approx. Nominal Minimum Approx. Approx.
cross- Insulation Inner Sheath Armour strip outer Sheath Over all cable wt ( kg /km) diameter outer Sheath Over all cable wt ( kg /km)
sectional thickness thickness thickness thickness Diameter With Al. With Cu of armour thickness Diameter With Al. With Cu
area(Sqmm) mm mm mm mm ( mm) Cond. Cond. wire ( mm) mm ( mm) Cond. Cond.

25 3.6 0.4 0.8 1.72 41 2100 2550 2.00 1.72 43 2800 3250
35 3.6 0.5 0.8 1.72 43 2350 2950 2.00 1.88 46 3200 3850
50 3.6 0.5 0.8 1.88 46 2700 3650 2.50 2.04 50 4000 4950
70 3.6 0.5 0.8 1.88 50 3100 4400 2.50 2.04 54 4500 5800
95 3.6 0.6 0.8 2.04 54 3700 5450 2.50 2.20 58 5200 6950
120 3.6 0.6 0.8 2.20 58 4200 6450 2.50 2.20 62 5800 8050
150 3.6 0.6 0.8 2.20 61 4700 7500 2.50 2.36 65 6400 9200
185 3.6 0.7 0.8 2.36 65 5300 8750 3.15 2.52 70 7900 11350
240 3.6 0.7 0.8 2.52 71 6300 10750 3.15 2.68 76 9000 13500
300 3.6 0.7 0.8 2.68 75 7200 12800 3.15 2.84 80 10000 15600
400 3.6 0.7 0.8 2.84 83 8700 16150 4.00 3.00 90 13500 20500

Cross- Sectional View


1 CONDUCTOR : Stranded Compacted Circular Aluminium / copper as per Class -2 of IS:8130
2 Conductor screening : Extruded Semiconducting Compound
3 INSULATION MATERIAL : CROSSLINKED POLYETHYLENE (XLPE)
4
INSULATION SCREENING : Extruded semiconducting compound followed by helically wrapped 0.050mm thick copper tape.
5
INNER SHEATH : Extruded PVC
6
ARMOURING : Single layer of Aluminium Round wires.
7
OUTER SHEATH : PVC TYPE ST-2 OF IS : 5831 ‘— OPTIONS : PVC TYPE ST-2/ FR TYPE/ FRLS TYPE
COLOUR OF OUTER SHEATH : BLACK . OPTIONS : ANY OTHER COLOURS AS PER REQUIREMENT
~ Tabulated approx. net weights of cables are only for guidelines for transportation / Loading/ Unloading Purpose.

Electrical Parameters
SIZE Max. Cond. D.C. Approx. Cond. A.C. Reactance App. Capecitance Normal* Current Rating in Amps Short Circuit Current
cross-sectional Resistance at Resistance at at 50HZ of cable With Aluminium cond. With Copper cond. Rating for 1Sec.duration
o o
area (Sq MM) 20 C in Ohm/km 90 C in Ohm/km in ohms/km in microF/KM Ground Duct Air Ground Duct Air in K. Amps
Al Cu Al Cu (APPROX.) (APPROX.) Al Cu

25 1.20 0.727 1.54 0.931 0.133 0.18 95 82 105 120 105 135 2.35 3.58
35 0.868 0.524 1.11 0.671 0.126 0.20 115 97 125 145 125 165 3.29 5.01
50 0.641 0.387 0.820 0.495 0.118 0.22 130 115 150 170 150 195 4.70 7.15
70 0.443 0.268 0.567 0.343 0.116 0.26 160 140 190 210 180 240 6.58 10.01
95 0.320 0.193 0.410 0.248 0.107 0.29 190 165 230 250 215 295 8.93 13.59
120 0.253 0.153 0.325 0.197 0.102 0.32 220 190 260 280 240 335 11.28 17.16
150 0.206 0.1240 0.265 0.159 0.099 0.35 245 210 295 310 270 380 14.10 21.45
185 0.164 0.0991 0.211 0.127 0.097 0.38 275 240 335 350 305 430 17.39 26.46
240 0.125 0.0754 0.162 0.098 0.084 0.43 315 275 395 400 350 500 22.56 34.32
300 0.100 0.0601 0.130 0.078 0.093 0.46 355 310 450 445 390 570 28.20 42.90
400 0.0778 0.0470 0.1023 0.0618 0.089 0.53 400 350 520 500 440 650 37.60 57.20
Note : Normal current ratings are given in standard conditions (as given in page no -40,41), if site conditions are different, current rating should be multiplied by
rating factor as given in page no. 42

33
Table -29 TECHNICAL DETAIL FOR HAVELLS 11/11 KV SINGLE CORE, AL/COPPER COND.,
XLPE INSULATED, ARMOURED CABLES
Cable Code : A2XWaY/2XWaY (11KV - UN-EARTHED GRADE) Ref. Spec. : IS :7098PART-2
Physical Parameters
SIZE Nominal Minimum Nominal Diameter Minimum Thickness Approx. Approx.
cross- Sectional Insulation Inner Sheath of Armour Wire of Outer Sheath Over all cable wt ( kg /km)
area(Sqmm) thickness thickness (mm) (mm) Diameter With Al. With Cu
mm mm ( mm) Cond. Cond.
25 5.5 0.3 1.60 1.40 28 900 1050
35 5.5 0.3 1.60 1.40 29 950 1150
50 5.5 0.3 1.60 1.56 31 1100 1400
70 5.5 0.3 1.60 1.56 33 1200 1650
95 5.5 0.3 1.60 1.56 34 1400 2000
120 5.5 0.4 2.00 1.56 37 1600 2350
150 5.5 0.4 2.00 1.56 38 1700 2600
185 5.5 0.4 2.00 1.56 40 1900 3050
240 5.5 0.4 2.00 1.72 43 2200 3700
300 5.5 0.4 2.00 1.72 44 2500 4350
400 5.5 0.5 2.00 1.88 48 2900 5400
500 5.5 0.5 2.50 1.88 53 3500 6600
630 5.5 0.5 2.50 2.04 56 4100 8000
800 5.5 0.6 2.50 2.20 61 4900 9900
1000 5.5 0.6 2.50 2.20 65 5700 11900

Cross- Sectional View


1 CONDUCTOR : Stranded Compacted Circular Aluminium / copper as per Class -2 of IS:8130
2 Conductor screening : Extruded Semiconducting Compound
3 INSULATION MATERIAL : CROSSLINKED POLYETHYLENE (XLPE)
4
INSULATION SCREENING : Extruded semiconducting compound followed by helically wrapped 0.050mm thick copper tape.
5
INNER SHEATH : Extruded PVC
6
ARMOURING : Single layer of Aluminium Round wires.
7
OUTER SHEATH : PVC TYPE ST-2 OF IS : 5831 ‘— OPTIONS : PVC TYPE ST-2/ FR TYPE/ FRLS TYPE
COLOUR OF OUTER SHEATH : BLACK . OPTIONS : ANY OTHER COLOURS AS PER REQUIREMENT
~ Tabulated approx. net weights of cables are only for guidelines for transportation / Loading/ Unloading Purpose.

Electrical Parameters
SIZE Max. Cond. D.C. Approx. Cond. A.C. Reactance of Capecitance Normal* Current Rating in Amps Short Circuit Current
cross-sectional Resistance at Resistance at cable at 50HZ of cable With Aluminium cond. With Copper cond. Rating for 1Sec.duration
area (Sq MM) 20oC in Ohm/km 90oC in Ohm/km in ohms/km in microF/KM Ground Duct Air Ground Duct Air in K. Amps
Al Cu Al Cu (Approx). (Approx). Al Cu
25 1.20 0.727 1.54 0.931 0.164 0.14 100 90 120 130 115 155 2.35 3.58
35 0.868 0.524 1.11 0.671 0.156 0.16 120 105 145 155 140 185 3.29 5.00
50 0.641 0.387 0.820 0.495 0.147 0.17 140 125 170 185 160 220 4.70 7.15
70 0.443 0.268 0.567 0.343 0.139 0.20 175 155 215 225 195 275 6.58 10.01
95 0.320 0.193 0.410 0.248 0.132 0.21 205 180 260 265 235 340 8.93 13.59
120 0.253 0.153 0.325 0.197 0.126 0.23 235 205 305 300 265 390 11.28 17.16
150 0.206 0.1240 0.265 0.159 0.124 0.25 260 230 345 335 295 440 14.10 21.45
185 0.164 0.0991 0.211 0.127 0.120 0.26 295 260 395 380 330 510 17.39 26.46
240 0.125 0.0754 0.162 0.098 0.116 0.29 340 300 470 435 380 600 22.56 34.32
300 0.100 0.0601 0.130 0.078 0.112 0.32 385 335 540 490 425 680 28.20 42.90
400 0.0778 0.0470 0.1023 0.0618 0.109 0.35 440 380 630 550 480 790 37.60 57.20
500 0.0605 0.0366 0.0808 0.0489 0.105 0.39 495 430 730 610 530 910 47.00 71.50
630 0.0469 0.0283 0.0648 0.0391 0.102 0.43 560 480 840 680 580 1030 59.22 90.10
800 0.0367 0.0221 0.0530 0.0319 0.097 0.50 620 530 960 740 630 1140 75.20 114.40
1000 0.0291 0.0176 0.0444 0.0268 0.096 0.56 680 580 1070 790 670 1250 94.00 143.00
Note : Normal current ratings are given in standard conditions (as given in page no - 40,41), if site conditions are different, current rating should be multiplied by
rating factor as given in page no. 42

34
Table -30 TECHNICAL DETAIL FOR HAVELLS 11/11KV THREE CORES, AL/COPPER COND.,
XLPE INSULATED, ARMOURED CABLES
Cable Code : A2XFY/ 2XFY, A2XWY/2XWY ( 11KVUE) Ref. Spec. : IS :7098PART -2
Physical Parameters
FLAT STRIP ARMOURED ROUND WIRES ARMOURED
SIZE Nominal Minimum Nominal Minimum Approx. Approx. Nominal Minimum Approx. Approx.
cross- Insulation Inner Sheath Armour strip outer Sheath Over all cable wt ( kg /km) diameter outer Sheath Over all cable wt ( kg /km)
sectional thickness thickness thickness thickness Diameter With Al. With Cu of armour thickness Diameter With Al. With Cu
area(Sqmm) mm mm mm mm (mm) Cond. Cond. wire (mm) mm (mm) Cond. Cond.

25 5.5 0.5 0.8 1.88 50 3000 3500 2.50 2.04 54 4300 4750
35 5.5 0.5 0.8 2.04 53 3200 3850 2.50 2.20 57 4700 5350
50 5.5 0.6 0.8 2.20 56 3700 4600 2.50 2.20 60 5100 6050
70 5.5 0.6 0.8 2.20 60 4100 5400 2.50 2.36 64 5800 7100
95 5.5 0.6 0.8 2.36 64 4800 6567 3.15 2.52 69 7300 9100
120 5.5 0.7 0.8 2.52 68 5400 7632 3.15 2.52 73 8000 10250
150 5.5 0.7 0.8 2.52 71 5900 8690 3.15 2.68 76 8600 11400
185 5.5 0.7 0.8 2.68 75 6500 9950 3.15 2.84 80 9400 12850
240 5.5 0.7 0.8 2.84 81 7600 12050 3.15 3.00 85 11000 15500
300 5.5 0.7 0.8 3.00 85 8600 14200 4.00 3.00 91 13000 18600
400 5.5 0.7 0.8 3.00 93 10000 17500 4.00 3.00 98 15000 22450

Cross- Sectional View


1 CONDUCTOR : Stranded Compacted Circular Aluminium / copper as per Class -2 of IS:8130

2 Conductor screening : Extruded Semiconducting Compound


3 INSULATION MATERIAL : CROSSLINKED POLYETHYLENE (XLPE)

4 INSULATION SCREENING : Extruded semiconducting compound followed by helically wrapped 0.050mm thick copper tape.

5 PVC FILLERS
6 INNER SHEATH : Extruded PVC
7
ARMOURING : Single layer of Galvanized Flat strip/ Round wires.
8
OUTER SHEATH : PVC TYPE ST-2 OF IS : 5831 ‘— OPTIONS : PVC TYPE ST-2/ FR TYPE/ FRLS TYPE

Electrical Parameters
SIZE Max. Cond. D.C. Approx. Cond. A.C. Reactance of App. Capecitance Normal* Current Rating in Amps Short Circuit Current
cross-sectional Resistance at Resistance at cabe at 50HZ of cable With Aluminium cond. With Copper cond. Rating for 1Sec.duration
area (Sq MM) 20oC in Ohm/km 90oC in Ohm/km in ohms/km in microF/KM Ground Duct Air Ground Duct Air in K. Amps
Al Cu Al Cu (APPROX.) (APPROX.) Al Cu

25 1.20 0.727 1.54 0.931 0.145 0.14 95 82 105 120 105 135 2.35 3.58
35 0.868 0.524 1.11 0.671 0.138 0.16 115 97 125 145 125 165 3.29 5.01
50 0.641 0.387 0.820 0.495 0.129 0.17 130 115 150 170 150 195 4.70 7.15
70 0.443 0.268 0.567 0.343 0.124 0.20 160 140 190 210 180 240 6.58 10.01
95 0.320 0.193 0.410 0.248 0.116 0.21 190 165 230 250 215 295 8.93 13.59
120 0.253 0.153 0.325 0.197 0.112 0.23 220 190 260 280 240 335 11.28 17.16
150 0.206 0.1240 0.265 0.159 0.108 0.25 245 210 295 310 270 380 14.10 21.45
185 0.164 0.0991 0.211 0.127 0.105 0.26 275 240 335 350 305 430 17.39 26.46
240 0.125 0.0754 0.162 0.0976 0.102 0.29 315 275 395 400 350 500 22.56 34.32
300 0.100 0.0601 0.130 0.0778 0.0999 0.32 355 310 450 445 390 570 28.20 42.90
400 0.0778 0.0470 0.1023 0.0618 0.0954 0.35 400 350 520 500 440 650 37.60 57.20
Note : Normal current ratings are given in standard conditions (as given in page no - 40,41), if site conditions are different, current rating should be multiplied by
rating factor as given in page no. 42

35
Table -31 TECHNICAL DETAIL FOR HAVELLS 12.7/22 KV SINGLE CORE, AL/COPPER COND.,
XLPE INSULATED, ARMOURED CABLES
Cable Code : A2XWaY/2XWaY (22KV - EARTHED GRADE) Ref. Spec. : IS :7098PART-2
Physical Parameters

SIZE Nominal Minimum Nominal Diameter Minimum Thickness Approx. Approx.


cross- Sectional Insulation Inner Sheath of Armour Wire of Outer Sheath Over all cable wt ( kg /km)
area(Sqmm) thickness thickness (mm) (mm) Diameter With Al. With Cu
mm mm ( mm) Cond. Cond.
25 6.0 0.3 1.60 1.40 29 950 1100
35 6.0 0.3 1.60 1.40 31 1050 1250
50 6.0 0.3 1.60 1.56 32 1150 1500
70 6.0 0.3 1.60 1.56 34 1300 1750
95 6.0 0.4 2.00 1.56 36 1600 2200
120 6.0 0.4 2.00 1.56 38 1700 2450
150 6.0 0.4 2.00 1.56 39 1800 2750
185 6.0 0.4 2.00 1.56 41 2000 3150
240 6.0 0.4 2.00 1.72 44 2300 3800
300 6.0 0.4 2.00 1.72 46 2600 4500
400 6.0 0.5 2.00 1.88 50 3000 5500
500 6.0 0.5 2.50 1.88 53 3600 6700
630 6.0 0.5 2.50 2.04 57 4300 8200
800 6.0 0.6 2.50 2.20 62 5000 9950
1000 6.0 0.6 2.50 2.36 66 5800 12000

Cross- Sectional View


1 CONDUCTOR : Stranded Compacted Circular Aluminium / copper as per Class -2 of IS:8130
2 Conductor screening : Extruded Semiconducting Compound
3 INSULATION MATERIAL : CROSSLINKED POLYETHYLENE (XLPE)
4
INSULATION SCREENING : Extruded semiconducting compound followed by helically wrapped 0.050mm thick copper tape.
5
INNER SHEATH : Extruded PVC
6
ARMOURING : Single layer of Aluminium Round wires.
7
OUTER SHEATH : PVC TYPE ST-2 OF IS : 5831 ‘— OPTIONS : PVC TYPE ST-2/ FR TYPE/ FRLS TYPE
COLOUR OF OUTER SHEATH : BLACK . OPTIONS : ANY OTHER COLOURS AS PER REQUIREMENT
~ Tabulated approx. net weights of cables are only for guidelines for transportation / Loading/ Unloading Purpose.

Electrical Parameters
SIZE Max. Cond. D.C. Approx. Cond. A.C. Reactance of App. Capecitance Normal* Current Rating in Amps Short Circuit Current
cross-sectional Resistance at Resistance at cable at 50HZ of cable With Aluminium cond. With Copper cond. Rating for 1Sec.duration
area (Sq MM) 20oC in Ohm/km 90oC in Ohm/km in ohms/km in microF/KM Ground Duct Air Ground Duct Air in K. Amps
Al Cu Al Cu (APPROX.) (APPROX). Al Cu
25 1.20 0.727 1.54 0.931 0.166 0.13 100 90 120 130 115 155 2.35 3.58
35 0.868 0.524 1.11 0.671 0.158 0.15 120 105 145 155 135 185 3.29 5.00
50 0.641 0.387 0.820 0.495 0.149 0.16 140 120 175 180 155 225 4.70 7.15
70 0.443 0.268 0.567 0.343 0.140 0.18 170 150 220 215 190 280 6.58 10.01
95 0.320 0.193 0.410 0.248 0.134 0.20 200 175 265 255 220 335 8.93 13.59
120 0.253 0.153 0.325 0.197 0.130 0.22 225 195 300 285 245 380 11.28 17.16
150 0.206 0.1240 0.265 0.159 0.126 0.23 250 215 340 310 270 430 14.10 21.45
185 0.164 0.0991 0.211 0.127 0.122 0.25 280 240 385 345 300 485 17.39 26.46
240 0.125 0.0754 0.162 0.098 0.118 0.27 315 275 450 390 335 560 22.56 34.32
300 0.100 0.0601 0.130 0.078 0.113 0.30 345 300 500 420 360 620 28.20 42.90
400 0.0778 0.0470 0.1023 0.0618 0.110 0.32 385 330 570 455 395 690 37.60 57.20
500 0.0605 0.0366 0.0808 0.0489 0.107 0.36 415 360 640 480 415 750 47.00 71.50
630 0.0469 0.0283 0.0648 0.0391 0.103 0.40 450 385 720 510 440 820 59.22 90.10
800 0.0367 0.0221 0.0530 0.0319 0.0997 0.46 485 415 790 540 460 840 75.20 114.40
1000 0.0291 0.0176 0.0444 0.0268 0.097 0.52 510 435 850 550 475 940 94.00 143.00
Note : Normal current ratings are given in standard conditions (as given in page no- 40,41), if site conditions are different, current rating should be multiplied by
rating factor as given in page no. 42

36
Table -32 TECHNICAL DETAIL FOR HAVELLS 12.7/22 KV THREE CORES, AL/COPPER COND.,
XLPE INSULATED, ARMOURED CABLES
Cable Code : A2XFY/ 2XFY, A2XWY/2XWY (22KV- E) Ref. Spec. : IS :7098PART -2
Physical Parameters

FLAT STRIP ARMOURED ROUND WIRES ARMOURED


SIZE Nominal Minimum Nominal Minimum Approx. Approx. Nominal Minimum Approx. Approx.
cross- Insulation Inner Sheath Armour strip outer Sheath Over all cable wt kg /km) diameter outer Sheath Over all cable wt ( kg /km)
sectional thickness thickness thickness thickness Diameter With Al. With Cu of armour thickness Diameter With Al. With Cu
area(Sqmm) mm mm mm mm ( mm) Cond. Cond. wire (mm) mm (mm) Cond. Cond.

25 6.0 0.5 0.8 2.04 53 3200 3650 2.50 2.20 56 4600 5050
35 6.0 0.6 0.8 2.04 56 3500 4150 2.50 2.20 59 5000 5650
50 6.0 0.6 0.8 2.20 59 3900 4850 2.50 2.36 61 5400 6350
70 6.0 0.6 0.8 2.36 63 4400 5700 2.50 2.36 65 6100 7400
95 6.0 0.7 0.8 2.36 67 5000 6800 3.15 2.52 72 7600 9350
120 6.0 0.7 0.8 2.52 70 5700 7950 3.15 2.68 75 8300 10550
150 6.0 0.7 0.8 2.68 74 6200 9000 3.15 2.68 78 9000 11800
185 6.0 0.7 0.8 2.68 77 6800 10250 3.15 2.84 83 9800 13250
240 6.0 0.7 0.8 2.84 83 7900 12350 4.00 3.00 90 12500 16950
300 6.0 0.7 0.8 3.00 88 8900 14500 4.00 3.00 93 13500 19100
400 6.0 0.7 0.8 3.00 95 10500 17950 4.00 3.00 102 15500 22950

Cross- Sectional View


CONDUCTOR : Stranded Compacted Circular Aluminium / copper as per Class -2 of IS:8130
1
Conductor screening : Extruded Semiconducting Compound
2
3
INSULATION MATERIAL : CROSSLINKED POLYETHYLENE (XLPE)
INSULATION SCREENING : Extruded semiconducting compound followed by helically wrapped 0.050mm thick copper tape.
4
PVC FILLERS
5
6 INNER SHEATH : Extruded PVC
7 ARMOURING : Single layer of Galvanized Flat strip/ Round wires.
8 OUTER SHEATH : PVC TYPE ST-2 OF IS : 5831 ‘— OPTIONS : PVC TYPE ST-2/ FR TYPE/ FRLS TYPE

COLOUR OF OUTER SHEATH : BLACK . OPTIONS : ANY OTHER COLOURS AS PER REQUIREMENT
~ Tabulated approx. net weights of cables are only for guidelines for transportation / Loading/ Unloading Purpose.

Electrical Parameters
SIZE Max. Cond. D.C. Approx. Cond. A.C. Reactance of Capecitance Normal* Current Rating in Amps Short Circuit Current
cross-sectional Resistance at Resistance at cable at 50HZ of cable With Aluminium cond. With Copper cond. Rating for 1Sec.duration
area (Sq MM) 20oC in Ohm/km 90oC in Ohm/km in ohms/km in microF/KM Ground Duct Air Ground Duct Air in K. Amps
Al Cu Al Cu (APPROX.) (APPROX.) Al Cu

25 1.20 0.727 1.54 0.931 0.148 0.13 90 85 110 120 100 135 2.35 3.58
35 0.868 0.524 1.11 0.671 0.141 0.15 110 100 130 145 120 165 3.29 5.01
50 0.641 0.387 0.820 0.495 0.132 0.16 130 115 155 170 150 200 4.70 7.15
70 0.443 0.268 0.567 0.343 0.125 0.18 160 140 190 205 180 245 6.58 10.01
95 0.320 0.193 0.410 0.248 0.119 0.20 190 170 230 245 215 300 8.93 13.59
120 0.253 0.153 0.325 0.197 0.114 0.22 215 190 265 275 245 340 11.28 17.16
150 0.206 0.1240 0.265 0.159 0.111 0.23 240 215 300 305 275 385 14.10 21.45
185 0.164 0.0991 0.211 0.127 0.107 0.25 270 240 340 345 305 435 17.39 26.46
240 0.125 0.0754 0.162 0.098 0.104 0.27 310 275 400 395 350 510 22.56 34.32
300 0.100 0.0601 0.130 0.078 0.102 0.30 350 310 455 440 390 580 28.20 42.90
400 0.0778 0.0470 0.1023 0.0618 0.097 0.32 395 355 530 495 440 660 37.60 57.20
Note : Normal current ratings are given in standard conditions (as given in page no - 40,41), if site conditions are different, current rating should be multiplied by
rating factor as given in page no. 42

37
Table -33 TECHNICAL DETAIL FOR HAVELLS 19/33 KV SINGLE CORE, AL/COPPER COND.,
XLPE INSULATED, ARMOURED CABLES
Cable Code : A2XWaY/2XWaY ( 33KV - EARTHED GRADE) Ref. Spec. : IS :7098PART -2
Physical Parameters

SIZE Nominal Minimum Nominal Diameter Minimum Thickness Approx. Approx.


cross- Sectional Insulation Inner Sheath of Armour Wire of Outer Sheath Over all cable wt ( kg /km)
area(Sqmm) thickness thickness (mm) (mm) Diameter With Al. With Cu
mm mm (mm) Cond. Cond.
25 8.80 0.40 2.00 1.56 36 1400 1450
35 8.80 0.40 2.00 1.56 38 1500 1600
50 8.80 0.40 2.00 1.56 39 1600 1800
70 8.80 0.40 2.00 1.56 40 1800 2100
95 8.80 0.40 2.00 1.72 43 2000 2500
120 8.80 0.40 2.00 1.72 44 2100 2700
150 8.80 0.40 2.00 1.72 46 2300 3130
185 8.80 0.50 2.00 1.72 47 2500 3550
240 8.80 0.50 2.00 1.88 50 2800 4200
300 8.80 0.50 2.50 2.04 53 3300 5050
400 8.80 0.50 2.50 2.04 57 3800 6200
500 8.80 0.60 2.50 2.20 60 4300 7300
630 8.80 0.60 2.50 2.20 64 4900 8800
800 8.80 0.60 3.15 2.36 70 6000 10500
1000 8.80 0.70 3.15 2.52 74 6900 13000

Cross- Sectional View


1 CONDUCTOR : Stranded Compacted Circular Aluminium / copper as per Class -2 of IS:8130
2 Conductor screening : Extruded Semiconducting Compound
3 INSULATION MATERIAL : CROSSLINKED POLYETHYLENE (XLPE)
4
INSULATION SCREENING : Extruded semiconducting compound followed by helically wrapped 0.050mm thick copper tape.
5
INNER SHEATH : Extruded PVC
6
ARMOURING : Single layer of Aluminium Round wires.
7
OUTER SHEATH : PVC TYPE ST-2 OF IS : 5831 ‘— OPTIONS : PVC TYPE ST-2/ FR TYPE/ FRLS TYPE
COLOUR OF OUTER SHEATH : BLACK . OPTIONS : ANY OTHER COLOURS AS PER REQUIREMENT
~ Tabulated approx. net weights of cables are only for guidelines for transportation / Loading/ Unloading Purpose.

Electrical Parameters
SIZE Max. Condt. D.C. Approx. Cond. A.C. Reactance of Capecitance Normal* Current Rating in Amps Short Circuit Current
cross-sectional Resistance at Resistance at cable at 50HZ of cable With Aluminium cond. With Copper cond. Rating for 1Sec.duration
o o
area (Sq MM) 20 C in Ohm/km 90 C in Ohm/km in ohms/km in microF/KM Ground Duct Air Ground Duct Air in K. Amps
Al Cu Al Cu (Approx). (Approx). Al Cu
25 1.20 0.727 1.54 0.931 0.175 0.10 100 90 120 130 115 155 2.35 3.58
35 0.868 0.524 1.11 0.671 0.169 0.11 120 105 145 155 135 185 3.29 5.00
50 0.641 0.387 0.820 0.495 0.161 0.12 140 120 175 180 155 225 4.70 7.15
70 0.443 0.268 0.567 0.343 0.152 0.14 170 150 220 215 190 280 6.58 10.00
95 0.320 0.193 0.410 0.248 0.145 0.15 200 175 265 255 220 335 8.93 13.59
120 0.253 0.153 0.325 0.197 0.140 0.16 225 195 300 285 245 380 11.28 17.16
150 0.206 0.1240 0.265 0.159 0.135 0.18 250 215 340 310 270 430 14.10 21.45
185 0.164 0.0991 0.211 0.127 0.130 0.19 280 240 385 345 300 485 17.39 26.46
240 0.125 0.0754 0.162 0.098 0.126 0.21 315 275 450 390 335 560 22.56 34.32
300 0.100 0.0601 0.130 0.078 0.122 0.23 345 300 500 420 360 620 28.20 42.90
400 0.0778 0.0470 0.1023 0.0618 0.117 0.25 385 330 570 455 395 690 37.60 57.20
500 0.0605 0.0366 0.0808 0.0489 0.113 0.27 415 360 640 480 415 750 47.00 71.50
630 0.0469 0.0283 0.0648 0.0391 0.111 0.29 450 385 720 510 440 820 59.22 90.10
800 0.0367 0.0221 0.0530 0.0319 0.105 0.34 485 415 790 540 460 840 75.20 114.40
1000 0.0291 0.0176 0.0444 0.0268 0.102 0.37 510 435 850 550 475 940 94.00 143.00

Note : Normal current ratings are given in standard conditions (as given in page no - 40,41), if site conditions are different, current rating should be multiplied by
rating factor as given in page no. 42

38
Table -34 TECHNICAL DETAIL FOR HAVELLS 19/33 KV THREE CORES, AL/COPPER COND.,
XLPE INSULATED, ARMOURED CABLES
Cable Code : A2XFY/ 2XFY, A2XWY/2XWY (33KV E) Ref. Spec. : IS :7098PART -2
Physical Parameters
FLAT STRIP ARMOURED ROUND WIRES ARMOURED
SIZE Nominal Minimum Nominal Minimum Approx. Approx. Nominal Minimum Approx. Approx.
cross- Insulation Inner Sheath Armour strip outer Sheath Over all cable wt ( kg /km) diameter outer Sheath Over all cable wt ( kg /km)
sectional thickness thickness thickness thickness Diameter With Al. With Cu of armour thickness Diameter With Al. With Cu
area(Sqmm) mm mm mm mm ( mm) Cond. Cond. wire (mm) mm ( mm) Cond. Cond.

25 8.80 0.70 0.8 2.36 67 4700 5150 3.15 2.68 72 7400 7850
35 8.80 0.70 0.8 2.52 70 5100 5750 3.15 2.68 75 7800 8450
50 8.80 0.70 0.8 2.52 72 5500 6450 3.15 2.68 77 8200 9150
70 8.80 0.70 0.8 2.68 76 6100 7400 3.15 2.84 81 9000 10300
95 8.80 0.70 0.8 2.84 80 6800 8550 3.15 3.00 86 10000 11750
120 8.80 0.70 0.8 2.84 84 7500 9750 4.00 3.00 90 12000 14250
150 8.80 0.70 0.8 3.00 87 8100 10900 4.00 3.00 94 12700 15500
185 8.80 0.70 0.8 3.00 90 8800 12250 4.00 3.00 97 13500 16950
240 8.80 0.70 0.8 3.00 95 9900 14350 4.00 3.00 103 15000 19450
300 8.80 0.70 0.8 3.00 100 11000 16600 4.00 3.00 106 16000 21600
400 8.80 0.70 0.8 3.00 108 12500 19950 4.00 3.00 114 18000 25450

Cross- Sectional View


1 CONDUCTOR : Stranded Compacted Circular Aluminium / copper as per Class -2 of IS:8130

2 Conductor screening : Extruded Semiconducting Compound


3 INSULATION MATERIAL : CROSSLINKED POLYETHYLENE (XLPE)

4 INSULATION SCREENING : Extruded semiconducting compound followed by helically wrapped 0.050mm thick copper tape.

5 PVC FILLERS
6 INNER SHEATH : Extruded PVC
7
ARMOURING : Single layer of Galvanized Flat strip/ Round wires.
8
OUTER SHEATH : PVC TYPE ST-2 OF IS : 5831 ‘— OPTIONS : PVC TYPE ST-2/ FR TYPE/ FRLS TYPE
COLOUR OF OUTER SHEATH : BLACK . OPTIONS : ANY OTHER COLOURS AS PER REQUIREMENT
~ Tabulated approx. net weights of cables are only for guidelines for transportation / Loading/ Unloading Purpose.

Electrical Parameters
SIZE Max. Cond. D.C. Approx. Cond. A.C. Reactance of Capecitance Normal* Current Rating in Amps Short Circuit Current
cross-sectional Resistance at Resistance at cable at 50HZ of cable With Aluminium cond. With Copper cond. Rating for 1Sec.duration
area (Sq MM) 20oC in Ohm/km 90oC in Ohm/km in ohms/km in microF/KM Ground Duct Air Ground Duct Air in K. Amps
Al Cu Al Cu (APPROX.) (APPROX.) Al Cu

25 1.20 0.727 1.54 0.931 0.160 0.10 90 85 110 120 100 135 2.35 3.58
35 0.868 0.524 1.11 0.671 0.153 0.11 110 100 130 145 120 165 3.29 5.01
50 0.641 0.387 0.820 0.495 0.146 0.12 130 115 155 170 150 200 4.70 7.15
70 0.443 0.268 0.567 0.343 0.138 0.14 160 140 190 205 180 245 6.58 10.01
95 0.320 0.193 0.410 0.248 0.130 0.15 190 170 230 245 215 300 8.93 13.59
120 0.253 0.153 0.325 0.197 0.125 0.16 215 190 265 275 245 340 11.28 17.16
150 0.206 0.1240 0.265 0.159 0.122 0.18 240 215 300 305 275 385 14.10 21.45
185 0.164 0.0991 0.211 0.127 0.118 0.19 270 240 340 345 305 435 17.39 26.46
240 0.125 0.0754 0.162 0.098 0.113 0.21 310 275 400 395 350 510 22.56 34.32
300 0.100 0.0601 0.130 0.078 0.111 0.23 350 310 455 440 390 580 28.20 42.90
400 0.0778 0.0470 0.1023 0.0618 0.106 0.25 395 355 530 495 440 660 37.60 57.20

Note : Normal current ratings are given in standard conditions (as given in page no - 40,41), if site conditions are different, current rating should be multiplied by
rating factor as given in page no. 42

39
Basic assumption for current ratings & rating factors
1. SCOPE
The current ratings of cables as indicated in various tables have been calculated on certain assumed conditions.
In actual practice these conditions may be different. Therefore to determine the actual current ratings as per installation conditions, the tabulated
ratings shall be multiplied with appropriate factors

a) Basic assumption for current ratings


i) Maximum permissible temperature - 90°C for XLPE insulation, 70°C for general purpose PVC, 85C for HR PVC
ii) Ground/Duct temperature - 30°C
iii) Ambient temperature - 40°C
iv) Thermal resistivity of soil - 150°C cm/W
v) Thermal resistivity of Dielectric 650°C cm/W for PVC, 350°C cm/W for XLPE
vi) Depth of laying - for 1.1KV cables - 750mm, 3.3KV to 11KV-900MM, Above 11KV-1050mm
vii) Single core cables installed in one circuit in following arrangement
OR
viii) Multicore cables installed in single circuit

b) RATING FACTORS
i) Rating factors related to variation in ambient air temperature
Air temperature in Deg. C20 25 30 35 40 45 50 55
Normal PVC 1.32 1.25 1.16 1.09 1.00 0.90 0.80 0.80
Rating factors HRPVC 1.22 1.17 1.12 1.06 1.00 0.94 0.87 0.80
XLPE 1.20 1.16 1.11 1.06 1.00 0.95 0.88 0.81

ii) Rating factors related to variation in ground temperature


Air temperature in Deg. C15 20 25 30 35 40 45 50
Normal PVC 1.17 1.12 1.06 1.00 0.94 0. 0.79 0.71
Rating factors HRPVC 1.13 1.09 1.04 1.00 0.95 0.90 0.85 0.80
XLPE 1.12 1.08 1.04 1.00 0.96 0.91 0..87 0.82

iii) Rating factors related to variation in ground thermal resistivity of soil for 3 single core cables laid direct in ground. (Average value)
Thermal Res. in oC.Cm/W 100 120 150 200 250 300
Rating factors 1.20 1.10 1.00 0.90 0.81 0.74

iv) Rating factors related to variation in ground thermal resistivity of soil for multi core cables laid direct in ground. (Average value)
Thermal Res. in oC.Cm/W 100 120 150 200 250 300
Rating factors 1.16 1.08 1.00 0.90 0.82 0.76

v) Rating factors related to variation in depth of laying for 1.1kv cables


For cross-sectional area of conductor < 25sqmm
Depth of laying (cm) > 75 90 105 120 150 180 & ABOVE
Rating factors 1.00 0.99 0.98 0.97 0.96 0.95

For cross-sectional area of conductor 25 to 300sqmm


Depth of laying (cm) > 75 90 105 120 150 180 & ABOVE
Rating factors 1.00 0.98 0.97 0.96 0.94 0.93

For cross-sectional area of conductor above 300sqmm


Depth of laying (cm) > 75 90 105 120 150 180 & ABOVE
Rating factors 1.00 0.97 0.96 0.95 0.92 0.91

vi) Rating factors related to variation in depth of laying for 3.3kv to 11kv cables
Depth of laying (cm) > 75 90 105 120 150 180 & ABOVE
Rating factors — 1.00 0.99 0.98 0.96 0.95

vii) Rating factors related to variation in depth of laying for above 11kv cables
Depth of laying (cm) > 75 90 105 120 150 180 & ABOVE
Rating factors — — 1.00 0.99 0.98 0.96

40
Basic assumption for current ratings & rating factors

GROUP RATING FACTORS


1. Cable laid direct in Ground
No of cables/
circuits in groups Multicore cables in horizontal formation Single cables in horizontal formation
Touching S=15CM S=30CM S=45CM S=60CM Touching S=15CM S=30CM S=45CM S=60CM
2 0.8 0.84 0.87 0.90 0.91 0.80 0.85 0.90 0.92 0.95
3 0.68 0.74 0.79 0.83 0.86 0.70 0.78 0.85 0.88 0.91
4 0.62 0.69 0.75 0.80 0.83 0.64 0.73 0.81 0.86 0.89
5 0.58 0.65 0.72 0.77 0.80 0.59 0.70 0.79 0.84 0.88
6 0.55 0.62 0.69 0.75 0.78 0.55 0.67 0.77 0.83 0.87
7 0.52 0.59 0.67 0.73 0.77 0.53 0.65 0.76 0.82 0.86
8 0.5 0.57 0.66 0.72 0.75 0.51 0.64 0.76 0.82 0.86
9 0.48 0.55 0.65 0.71 0.75 0.49 0.63 0.74 0.81 0.85
10 0.46 0.54 0.64 0.70 0.74 0.48 0.63 0.74 0.81 0.85
11 0.45 0.53 0.63 0.70 0.74 0.47 0.62 0.73 0.80 0.84
12 0.44 0.52 0.62 0.69 0.73 0.46 0.61 0.73 0.80 0.84
S = axial spacing of cable
No. of cables/ No. of Tier
Multicore cables in Tier formation
circuits in groups
Touching S=15CM S=30CM S=45CM S=60CM
2 1 0.80 0.84 0.87 0.90 0.91
3 1 0.68 0.74 0.79 0.83 0.86
4 2 0.6 0.66 0.73 0.77 0.79
5 2 0.55 0.61 0.68 0.71 0.73
6 2 0.51 0.57 0.63 0.67 0.69
7 3 0.48 0.54 0.59 0.63 0.64
8 3 0.46 0.51 0.56 0.6 0.61
9 3 0.44 0.48 0.53 0.57 0.58
10 4 0.42 0.47 0.52 0.55 0.56
11 4 0.41 0.46 0.50 0.54 0.55
12 4 0.4 0.45 0.49 0.53 0.54

1 Cable laid direct in open racks in air


MULTICORE CABLES IN OPEN RACKS IN AIR
25mm S 25mm

No.
of WALL
300mm
S = dia of cable WALL
300mm
t = touching
racks

No. of cables per rack No. of cables per rack


1 2 3 6 9 1 2 3 6 9
1 1.00 0.98 0.96 0.93 0.92 1.00 0.84 0.80 0.75 0.73
2 1.00 0.95 0.93 0.90 0.89 1.00 0.80 0.76 0.71 0.69
3 1.00 0.94 0.92 0.89 0.88 1.00 0.78 0.74 0.70 0.68
6 1.00 0.93 0.90 0.87 0.86 1.00 0.76 0.72 0.65 0.66

SINGLE CORE CABLES IN OPEN RACKS IN AIR


ARRANGEMENT
25MM

WALL
2d 300mm

No. of Racks No. of Circuit Racks (3 single cores) per rack


1 2 6
1 1.00 0.98 0.96
2 1.00 0.95 0.93
3 1.00 0.94 0.92
4 1.00 0.93 0.90

41
S = axial spacing of cable
No. of cables/ No. of
circuits in groups Tier Multicore cables in Tier formation
Touching S=15CM S=30CM S=45CM S=60CM
2 1 0.80 0.84 0.87 0.90 0.91
3 1 0.68 0.74 0.79 0.83 0.86
4 2 0.60 0.66 0.73 0.77 0.79
5 2 0.55 0.61 0.68 0.71 0.73
6 2 0.51 0.57 0.63 0.67 0.69
7 3 0.48 0.54 0.59 0.63 0.64
8 3 0.46 0.51 0.56 0.60 0.61
9 3 0.44 0.48 0.53 0.57 0.58
10 4 0.42 0.47 0.52 0.55 0.56
11 4 0.41 0.46 0.50 0.54 0.55
12 4 0.40 0.45 0.49 0.53 0.54
No. co cables/ Multicore cable (Touching) Multicore cables (spacing of cable S/core cables in trefoil touching formation
circuits in group No of cables in racks equal to dia meter of cable spacing between circuits equal to twice
No of cables in racks the diameter of cable) No of cables in racks
1 3 4 1 2 3 4 1 2 3 4
1 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
2 0.84 0.80 0.78 0.76 0.98 0.95 0.94 0.93 0.98 0.95 0.94 0.93
3 0.80 0.76 0.74 0.72 0.96 0.93 0.92 0.90 0.96 0.93 0.92 0.90
4 0.76 0.71 0.70 0.68 0.93 0.90 0.89 0.87 — — — —

Estimated Voltage Drops * Selection criteria of MV/HV


in PVC/XLPE Aluminium Cables cable size for primary distribution
For A.C. System 1 SCOPE
(Voltage drop - Volts/Km/Amps) The conductor size in the cables for any installation is also governed by its ability to carry short circuit current of
system. For L.V. distribution cable may be selected on the basis of continuous load current. But in case of MV/HV
Nominal
P.V.C. Cables XLPE Cables distribution it is always safer to select the cable on the basis of ability of conductor to carry expected short circuit
area of current. Short circuit current rating of cable should in line with short circuit capacity of damping apparatus such as
conductor Single Three Single Three circuit breakers, Transformers & reactor etc. beside its capacity to carry desired load current. Short circuit ratings
(sq. mm) Phase Phase Phase System of cables each size are given in relevant tables & have been calculated on the basis of IEC-949 & IEC-986 & on the
following assumption
1.5 43.44 37.62 46.34 40.13
a) Temperature of conductor just prior to short circuit
2.5 29.04 25.15 30.98 26.83
i) With XLPE insulation - 90 Deg. C ii) With PVC insulation - 70 Deg. C
4 17.78 15.40 18.98 16.44
b) Maximum permissible conductor temperature during short circuit
6 11.06 9.58 11.80 10.22 i) With XLPE insulation - 250 Deg. C ii) With PVC insulation - 160 Deg. C
10 7.40 6.41 7.88 6.82 c) Volumetric specific heat of the conductor
16 4.58 3.97 4.9 4.24 i) With Aluminium conductor - 2.5 x 10-3J/Deg. C/MM3 ii) With Copper conductor - 3.45 x 10-3J/Deg. C/MM3
25 2.89 2.50 3.08 2.67 d) Receprocal of temperature co-efficient of resistance at 9 Deg. C
35 2.10 1.80 2.23 1.94 i) With Aluminium conductor - 228 ii) With Copper conductor - 234.5
Short circuit current rating at different duration may be calculated as
50 1.55 1.30 1.65 1.44
70 1.10 0.94 1.15 1.00 Ish (for t duration) = Ish (for 1Sec.) Ish for 1 Sec. Duration is given in relevant tables in KA

95 0.79 0.68 0.83 0.70 t t = Time duration required tobe calculated of short circuit in Sec.
120 0.63 0.55 0.66 0.56 SELECTION CRITERIA OF H.V./MV CABLES FOR PRIMARY DISTRIBUTION
150 0.52 0.46 0.55 0.48 REQUIRED DATAS FOR EXAMPLE
185 0.42 0.37 0.44 0.40 1) Nominal System voltage at H.T. Side 11KV
240 0.34 0.30 0.35 0.30 2) Short circuit level for H.T. system 25KA
3) Fault withstand time for H.T. CBs 0.5 SEC
300 0.28 0.26 0.30 0.26
4) Formula for calculating H.T. cable size
400 0.24 0.22 0.24 0.22 With Aluiminium cond./XLPE insulated cable = Ish X√ t = 25 X√0.5
500 0.23 0.20 0.23 0.20 0.094 = 0.94
630 0.20 0.18 0.21 0.18 = 188
Hence nearest higher size 240sqmm is required
800 0.19 - 0.20 -
With Copper cond./XLPE insulated cable = Ish X√ t = 25 X √ 0.5
1000 0.18 - 0.18 - 0.143 0.143
**Above voltage drops (volts/km/amps) shall be multiplied = 124
with rated current & length of Cable in K.M. to calculate total Hence nearest higher size 150sqmm is required
voltage drop in particular length and size of cables.

ELECTRICAL FORMULAS FOR CALCULATING A.C. LOAD CURRENT


for Single phase (A.C.) for Three phase (A.C.)
Load current in Amps when KVA is given KVA X1000 KVA X1000
V 1.732 X V
for Single phase (A.C.) for Three phase (A.C.)
Load current in Amps when Kilo Watt is given KW X1000 KW X1000
VXpf 1.732 X V X pf
for Single phase (A.C.) for Three phase (A.C.)
Load current in Amps when H.P. is given H.P. X746 H.P. X746
V X %EFf X pf 1.732 X V X %Eff X pf
V = Nominal system voltage in Volts, pf = Power factor, KVA = Kilo Volts Ampere, H.P. = Horse Power
42
Standard drum lengths of cables
STANDARD LENGTH (MTS) WITH +5% TOLERANCE

DESCRIPTION OF CABLE UN-ARMOURED STRIP ARMOURED ROUND WIRE ARMOURED

1.1KV PVC/XLPE CABLES


WITH ALUMINIUM

~ SINGLE CORE UP TO 150SQMM-1000 UP TO 150SQMM-1000 UP TO 150SQMM-1000


185 TO 1000sqmm-500 185 to 1000sqmm-500 185 to 1000sqmm-500

~ TWO CORE UP TO 50SQMM-1000 UP TO 50SQMM-1000 UP TO 50SQMM-1000, 70 TO 500sqmm


70 to 630sqmm-500 70 to 630sqmm-500 500, 630sqmm-250

~ THREE CORE UP TO 50SQMM-1000 UP TO 50SQMM-1000 UP TO 50SQMM-1000, 70 TO 300sqmm


70 to 500sqmm-500
70 to 630sqmm-500 630sqmm-250 500, 500 to 630sqmm-250

~ THREE & HALF CORE UP TO 50SQMM-1000 UP TO 50SQMM-1000 UP TO 50SQMM-1000, 70 TO 300sqmm


70 to 400sqmm-500
70 to 630sqmm-500 500 to 630sqmm-250 500, 400-630sqmm-250

‘ FOUR CORE UP TO 50SQMM-1000 UP TO 50SQMM-1000 UP TO 50SQMM-1000, 70 to 240sqmm


70 to 500sqmm-500 70 to 400sqmm-500
630sqmm-250 500 to 630sqmm-250 500, 300 to 630sqmm-250

1.1KV PVC/XLPE CABLES

WITH COPPER CONDUCTOR

~ SINGLE CORE UP TO 150SQMM-1000 UP TO 150SQMM-1000 UP TO 150SQMM-1000


185 TO 630sqmm-500 185 to 630sqmm-500 185 to 630sqmm-500
800 to 1000sqmm-250 800 to 1000sqmm-250 800 to 1000sqmm-250

~ TWO CORE UP TO 10SQMM-1000 UP TO 10SQMM-1000 UP TO 10SQMM-1000, 70 TO 500sqmm


16 to 300sqmm-500 16 to 300sqmm-500 500
400 to 630sqmm-250 400 to 630sqmm-250 500, 300 to 630sqmm-250

~ THREE CORE UP TO 10SQMM-1000 UP TO 10SQMM-1000 UP TO 10SQMM-1000, 16 TO 185sqmm


16 to 240sqmm-500 16 to 185sqmm-500
300 to 400sqmm-250 240sqmm-400sqmm-250 500, 240 to 400sqmm-250

~ THREE & HALF CORE UP TO 10SQMM-1000 UP TO 10SQMM-1000 UP TO 10SQMM-1000, 16 TO 150sqmm


16 to 240sqmm-500 16 to 185sqmm-500
300 to 400sqmm-250 240 to 400sqmm-250 500, 185 to 400sqmm-250

‘ FOUR CORE UP TO 10SQMM-1000 UP TO 10SQMM-1000 UP TO 10SQMM-1000, 16 to 150sqmm


16 to 240sqmm-500 16 to 150sqmm-500
300 to 400sqmm-250 240 to 400sqmm-250 500, 185 to 400sqmm-250
~ Control cables more than FOUR CORES shall be supplied in 500 mts length
DESCRPITON OF CABLE 6.35/11KV GRADE 1/11KV GRADE 19/33KV GRADE
H.T. XLPE CABLES WITH
ALUMINIUM CONDUCTOR

~ SINGLE CORE-A2XWaY UP TO 150SQMM-1000 UP TO 150SQMM-1000 UP TO 150SQMM-1000


185 to 1000sqmm-500 185 to 1000sqmm-500 185 to 1000sqmm-500

~ THREE CORE-A2XFY 25 TO 300SQMM-500 25 TO 185SQMM-500 25 TO 95SQMM-500

400sqmm-250 240 to 400sqmm-250 120 to 400sqmm-250

~ THREE CORE-A2XWY 25 TO 150SQMM-500 25 TO 95SQMM-500 25 TO 50SQMM-250


185 to 300sqmm-250 120 to 240sqmm-250 70 to 120sqmm-250
400sqmm-200 300 to 400sqmm-200 185 to 400sqmm-200

43
Quality control Test
It has been rightly said that “Quality is never an accident, it is always the The tests on cables have been classified broadly in four categories as
result of intelligent efforts”. follows :

In the manufacture of cables, intelligent efforts are incorporated to Routine Tests :


achieve quality. For a quality end products, control starts from proper Tests carried out on each cable to check the requirements which are
design of the product. All raw materials are selected carefully and only
likely to vary during production.
materials of high quality are used in production. Having done this,
stage wise inspection is done to ensure conformity with the Type Tests :
requirements of relevant Indian Standards where these apply. Tests carried out to prove conformity with the specification. These are

Stage - Wise Inspection intended to prove the general qualities and design of a given type of

i) Wire-Drawing : Wire diameter cable.


Surface
Shape Acceptance Tests :
Quality of joints in the wire Tests carried out on samples taken from a lot for the purpose of

ii) Stranding of Wires: : Quality of joints in the wires acceptance of the lot.
Compaction of conductor
Shape of Conductor Optional Tests :
Dimensions Special tests to be carried out when required by agreement between
Resistance of Conductor
the purchaser and the manufacturer.
iii) Insulation : : Dimension over Insulation,
Thickness of Insulation, Special tests required for FRLS Cables can also be carried out at our
works i.e. Halogen gas generation test to IEC - 754 Part - I, Smoke
iv) Curing : Hot set test, Tensile strength &
(for XLPE Insulation) elongation test. generation test to ASTMD 2843, Oxygen index test and Temperature
index test to ASTMD - 2863, Flammability test to
v) Screening : Dimension over screen, thick of
(for H.T. Screened cables) screen visual examination of (1) IEC-332-1, (2) Swedish Chimney test to SS-4241475 Class F3
surface/defects. & (3) IEC-332-3, Flame resistance test to IEEE-383.

v) Laying Up : Sequence of Cores Together with the most advanced equipment available, we are able to
Direction of lay
Diameter over laid up cores offer to our valued customers assurances of highest quality and strict
Circularity adherence to the required specification. As a third party guarantee, our

vi) Inner Sheath : Thickness of Sheath cables have passed rigorous tests at various Government
Diameter over Sheath recogonized test laboratories such as CPRI, Shri
Surface Uniformity
Circularity Ram Test House, ERDA Baroda, National Test House, ERTL, RTC.
Porosity
Routine Tests, Type Tests, Acceptance Tests and Optional Tests as per
vii) Armouring : Diameter of Wires/ the Indian Standard Specification for Power and Control Cables with
Dimensions of Strips
Direction of lay PVC insulation, Cross linked Polyethylene insulation and Special Tests
Coverage are given in the Annexure.
Quality of Joints of Wires
Tensile Testing Machine
viii) Outer Sheath : Thickness of Sheath Diameter
over Sheath Tightness of Sheath
Eccentricity Porosity, Embossing

RM Testing Lab

44
Selection guide
List of Tests as per IS:1554(Part - I): 1988, IS:1554 (Part- II):1988, For selection of a cable, a first hand knowledge of the system in which
IS:7098 (Part - I):1988 and IS:7098 (Part-II) : 1985
the cable is to be used, and the installation conditions under which the
1. Routine Tests : cable has to operate, is necessary. A knowledge of statutory
a) Conductor Resistance Test restrictions and the manufacturing facilities available in the country will
b) High Voltage Test help in finding out as to what type of cable will be available for particular
c) Armour Resistance Test for mining Type Cables usage. The environmental conditions under which the cable has to
d) Partial Discharge test (for H.T. Screened cable)
operate will decide its protective covering. Thus once voltage grade of
2. Type Tests : the cable, number of cores, conductor material, type of insulation and
a) Tensile Test (for Aluminium Conductor) protective coverings are known, size of conductor remains to be
b) Wrapping Test (for Aluminium Conductor) decided. The first and foremost criteria for the size of conductor is
c) Annealing Test (for Copper Conductor) continuous current rating for the present load. There after the same
d) Conductor Resistance Test should be checked for short circuit, voltage drop, over load capacities
e) Test for Armour Wires/Strips
and future expansions. Once decided the selection of next higher size
f) Test for thickness of Insulation & Sheath
compared to what is essential for the requirement, will always be
g) Physical Test for Insulation & Outer Sheath
worthwhile.
h) Test for Bleeding & Blooming of Pigments
I) Insulation Resistance Test Economic considerations are also necessary.
j) High Voltage Test
INFORMATION REQUIRED WITH ENQUIRY & ORDER
k) Flammability Test
l) Hot Set Test - (For XLPE Insulation only) The following information should be included in an enquiry :
m) Partial Discharge test (for H.T. Screened cable)
i) Voltage Grade.
n) Bending test (for H.T. Screened cable)
o) Dielectric Power factor test (for H.T. Screened cable ii) Whether cable is to be used on Earthed or Unearthed system
with rated voltage 6.35/11KV & above) (for voltages above 3.3 KV).
p) Heating cycle test (for H.T. Screened cable)
q) Impulse withstand test (for H.T. Screened cable) iii) Type of installation whether in air or in ducts or in ground.

3 Acceptance Tests : iv) If cables are grouped together, then number of cables in group and

a) Tensile Test (For Aluminium Conductor) vertical and horizontal spacing between them.
b) Wrapping Test (For Aluminium Conductor) v) Required value and duration of short circuit current.
c) Annealing Test (For Copper Conductor)
Following further informations are also required for offering the exact
d) Conductor Resistance Test
e) Test for thickness of Insulation & Sheath type of cable for any specific purpose :

f) High Voltage Test a) The normal ambient or operating temperature.


g) Insulation Resistance Test
b) The maximum temperature to which the PVC will be exposed and
h) Tensile Strength & Elongation at break test for
Insulation and Sheath the duration and frequency of such exposures.
I) Hot Set Test - (for XLPE Insulation only)
c) The material with which the PVC will be in contact i.e. oil, gases,
j) Partial Discharge test (for H.T. Screened cable)
acids, alkalies etc. at normal and maximum temperature.
4. Optional Tests :
d) If special flame retardent property is required.
a) Cold Bend Test
b) Cold Impact Test e) If any special electrical characteristics needed.
c) Armour Resistance Test (for other than Mining Type
Cables)

5. Special Tests (As Applicable) :


a) Oxygen Index Test as per ASTMD - 2863-77
b) Temp. Index Test as per ASTMD - 2863-77
c) Smoke Generation Test as per ASTMD - 2843-77
d) Acid Gas Generation Test as per IEC - 754-1
e) Flammability Test as per IEC - 332-1, IEEE-383,
SS-4241475 Class F3 and IEC - 332-3
g) Water absorption test (by Electrical Method)
h) Ultra voilet resistance to ASTM-G-53
i) Die electric Strength retention test
j) Test for Antirodent & Antitermite property

45
Handling &&Storage
HANDLING STORAGE
Handling (Unloading at site) : On receipt of cable drums visual In case of multicore power cables, cables shall be laid side by side,
inspection of drums should be made ensuring drum packing is original. with spacings not less than one cable diameter. However derating
While unloading the cables certain precautions are to be taken to factors for cables laid on trenches are to be referred.
ensure the safety of the cables. Multicore power cables and single core D.C. circuits may be clamped
by means of galvanised mild steel saddles but 1.1 KV single core
1. The cable drums should not be dropped or thrown from railway
cables should be clamped by means of non-magnetic saddles. The
wagons or trucks during unloading operations as the shock may
saddles shall not be placed at intervals more than
cause serious damage to cable layers. A crane should be used 1500 mm. for horizontal and 1200 mm. for vertical runs.
for unloading cable drums. When lifting drums with the crane, it is 3. Multicore control cables can be laid touching each other on cable
recommended that the lagging should be kept in place to prevent racks and wherever required may be taken in two layers. They
the flanges from curshing on to the cable. If the crane is not should be clamped by means of PVC straps both for horizontal
available, a ramp should be prepared with approximate inclination and vertical runs (alternatively, fabricated aluminium clamps may
of 1:3 or 1:4. The cable drum should be rolled over the ramp by be used) at regular intervals.
means of ropes and winches. Additionally a sand bed at the foot 4. a) If the cables are buried directly in ground I.S. 1255 is to be
of the ramp may be prepared to brake the rolling the cable drum. followed for code of practice. However, generally cables are
laid 1000 mm. below finished ground level at any point of
2. Cable should not be dragged along the earth surface. cable run and 75 mm. of sand cushioning to be provided.
3. Cable ends should always be sealed by means of suitable end 4. b) In loose soil concrete pillar should be provided for as support
sealing materials to prevant moisturisation of cores and armour. and hence pipes are recommended to the used for cable
4. Drums should be rolled in direction of arrow marked on the drum. path.
5. If there is a possibility of mechanical damage, cables should be
Storage : protected by means of mild steel covers placed on racks.
Cables should be stored in a dry covered place to prevent exposure to 6. While laying cables, special care to be taken at bends. Followings
climatic conditions and wear and tear of wooden drums and it should are the recommended bending radius for power and control
cables.
preferably on a concrete surface/firm surface which will not cause the
drums to sink and thus lead to flange rot and extreme difficulty in Voltage Rating PVC and XLPE Cables
moving the drums. KV Single Core Multi Core
All drums should be stored in such a manner as to leave sufficient Upto 1.1 15 D 12 D
space between them for air circulation. It is desirable for drums to Above 1.1 but upto 11 K.V. 15 D 15 D
stand on battens placed directly under the flanges. Above 11 K.V. 20 D 15 D
In no case should the drums be stored, "On the Flat", i.e., with flange
horizontal. Where ‘D’ is overall R
diameter of cable.

7. Maximum safe pulling force (when pulled by pulling eye)


2
Laying : Aluminium Conductor Cables : 3.0 Kg/mm Copper Conductor
2
Cables : 5.0 Kg/mm Proper method of pulling of cable should be
For laying of cables special cares to be taken to prevent sharp bending, used.
kinking, twisting. Cable should be unwound from drum by proper
mounting the cable drum on a cable wheel making sure the spindle is TESTING
INSULATION RESISTANCE MEASUREMENT OF CABLE
strong enough to carry the weight without bending and that it is lying
The voltage rating of I.R. Tester (Megger) should be chosen as
horizontally in the bearings so as to prevent the drum creeping to one
following table :
side or the other while it is rotating.
Voltage grade Rating of IR Voltage grade Rating of IR
of cable Tester (Megger) of cable Tester (Magger)
Provision should be made to break the
drum to avoid further rolling & buckling 1.1 KV 500 V 11 KV 1000 V
of cable during sudden stop. A simple 3.3 KV 1000 V 22 KV 2500 V
wooden plank can server this purpose
6.6 KV 1000 V 33 KV 2500 V
Testing during laying :
All new cables shall be megger-tested before jointing. After jointing is
Cable must be puled completed all LV Cables shall be megger-tested.
This is incorrect way of pulling the cable & will cause
from the top
kinks & twist in cable. Shall be avoided at all End Terminations & Jointing :
Termination and jointing of Power & Control Cables shall be done by
means of compression methods using solderless tinned copper/
Aluminium terminal lugs. For control cables terminations, ring tongue
or reducer pin type terminal lug can also be used to suit the purpose.

Cable must be pulled accross hard & sharp


objects to avoid the damage to ve covering &
insulation
Cable must be laid in ducts or trenches as
shown in Fig.

However, following salient points are to be considered during laying


procedure of cables laid in racks and in built-in trenches.
1. For laying of cables power cables to be placed at the bottom most
layer and control cables at top most layer.
2. Single core power cable for use on A.C. system shall be laid in
delta formation supported by non-magnetic material. Trefoil
clamps of suitable size are to be placed at regular intervals but
preferably not more than 800 mm. Axial spacing of two circuits in A view of dispatch yard
delta formation shall not be less than 4 times the cable dia.
46