Havels Cable Catalogue
Havels Cable Catalogue
Havels Cable Catalogue
Control Cables
Catalogue 2011
n
HT Power
Cables upto 66 kV
Power Cables
n
1.1 kV Copper Control Cables
n
1.1 kV
Index
Introduction
Manufacturing Process ..............................................................................................................
Manufacturing of Cables.............................................................................................................
Advantages................................................................................................................................
Cable ranges at a glance............................................................................................................
1
2
3
4,5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
Basic assumption for current ratings & rating factors .................................................................. 40,41
Selection criteria of M/VHV cable size for primary distribution .....................................................
42
Standard Drum lengths of Cables ...............................................................................................
43
Quality Control & Test ................................................................................................................
44
Selection Guide .........................................................................................................................
45
Handling & Storage ....................................................................................................................
46
Introduction
Havells India Ltd., a billion-dollar-plus organization and one of the largest & India's fastest growing electrical and
power distribution equipment manufacturer with products ranging from Industrial & Domestic Circuit Protection
Switchgear, Cables & Wires, Motors, Fans, Power Capacitors, CFL Lamps, Luminaires for Domestic, Commercial &
Industrial applications, Modular Switches & Bathfittings covering the entire gamut of household, commercial and
industrial electrical needs.
Havells owns some of the prestigious global brands like Crabtree, Sylvania, Concord, Luminance, Linolite & SLI
Lighting.
With 91 branches / representative offices and over 8000 professionals in over 50 countries across the globe, the
group has achieved rapid success in the past few years. Its 7 state-of-the-art manufacturing plants in India located at
Haridwar, Baddi, Noida, Faridabad, Bhiwadi, Alwar, Neemrana, and 9 state-of-the-art manufacturing plants located
across Europe, Latin America & Africa churn out globally acclaimed products. Havells is a name synonymous with
excellence and expertise in the electrical industry. Its 20000 strong global distribution network is prompt to service
customers.
The company has acquired a number of International certifications, like BASEC, CSA, KEMA, CB, CE, ASTA, CPA,
SEMKO, SIRIUM (Malaysia), SPRING (Singapore), TSE (Turkey), SNI (Indonesia) and EDD (Bahrain) for various
products. Today, Havells and its brands have emerged as the preferred choice of electrical products for discerning
individuals and industrial consumers both in India and abroad.
The essence of Havells success lies in the expertise of its fine team of professionals, strong relationships with
associates and the ability to adapt quickly and efficiently, with the vision to always think ahead.
Manufacturing Process
Copper or
Aluminium Rods
Annealing
Stranding
Conductor Screening
Insulation
Insulation Screening
Insulation Screening
(Metallic Part)
Wire Drawing
Laying Up
Inner Sheathing
Armouring
Outer Sheath
All cables are rewound on wooden Drums & tests Carriedout as per required specification
Packing
Manufacturing of Cables
Cables with Aluminium and Copper conductor and polymer insulation are manufactured at Havells India Ltd. (Cable Works) Alwar. Essentially
cables comprise of conductors, insulation, inner-sheath, armour and outersheath. The brief description of the process is mentioned as under:
CONDUCTOR
strength of insulation.
circuit conditions.
as under:
1.
3.
compaction.
2.
IS:5831/IS:7098
International Specifications
BS:6746/BS:5467/IEC:60502
SCREENING
XLPE Cables with rated voltage over 3300V shall be provided with
large sized conductor, which are due to skin and proximity effects.
Conductor
Screen
Insulation
Screen
part 2.
IS:8130
International specification
IEC:60228 / BS:6360
DIELECTRIC INSULATION
International specifications.
LAYING UP
Cores are tested on line during production both for physical and
setting insulations.
- PVC Cables
Thermoplastic dielectric
- XLPE Cables
Havells PVC cables use PVC compounds that take care of over
INNERSHEATH
load and short circuit current with both coarse & fine protection
Laid up cables are provided with inner sheath with high quality of
systems.
oxidant
Advantage
In Havells Cable-polymers used for inner sheath are softer than
FINAL TESTING
From a lot of Cable one cable of each type is tested for Type tests,
as per relevant specifications.
component of cable.
Inner sheath is applied either with extrusion or by wrapping. In
Havells Cables though the inner sheath is closely applied on the
insulation.
The inner sheath dimensions are maintained strictly in accordance
1.
2.
3.
4.
losses on A. C. System.
5.
6.
Specification
ARMOURING
Mechanical protection to the cable is provided with armouring.
Havells single core cables are armoured with Aluminium or
Aluminium alloy wire/strips, thus avoiding magnetic hysteresis
1.
2.
3.
4.
5.
6.
7.
8.
ST1
Smoke Compound
9.
(FRLS)
IEEE-383
ASTM-2843
ASTM-2863
Flame Retartant Compound (FR)
to EIL Specn.
Arial Bunched /
Bundled required
for over head power
distribution
Copper Control
Cables for Power
Switch yard Control /
Relay Equipment
Railway Signaling
Cables
Telecom / Switch
board cables for
Indoor Telephones
Options
Conductor - Stranded / Solid, Circular /
Shaped Aluminium / Copper
Insulation - PVC / HR PVC
Inner Sheath - PVC / HR PVC / FRLS / PVC
Unarmoured / Armoured - G.S. Round Wire/
Flat Strip or Aluminum Wire / Flat Strip
Outer Sheath - PVC/ HR PVC/ FRLS PVC
Available in specified RG
& UR Series as per MIL-C-17 /
BS: 2316 / IS: 5608 / IS: 11967
Sizes :
Suitable for Impedance
of 50 / 75 / 100 / 125 ohms
Outer-Sheath
Armouring
Inner-Sheath
Insulation
Aluminium /
Copper Conductor
PVC Outer-Sheath
Armouring
PVC Inner-Sheath
Filler
Stranded Conductor
Conductor Screening
XLPE Insulation
Insulation Screening
Metallic Screening
Outer-sheath
Armour (outer layer)
Seprator (PVC tape)
Armour (inner layer)
Inner-Sheath
Insulation
Conductor
Outer Sheath
Cu Tape Screening
Insulation Screening
XLPE Insulation
Conductor Screening
Conductor
AAA
Messenger
Conductor
Outer Sheath
Armour
Inner Sheath
Conductor
Insulation
Outer Sheath
Armour
Inner Sheath
Conductor
Insulation
Outer Sheath
Armour
Inner Sheath
Bedding Tape
Conductor
Insulation
Twisted Pair
Filler
P.E. Insulation
Sheath
Braid
Insulation
Conductor
Sheath
Options
Energy Cables
for Power Supply to
Telephone
Exchanges / UPS /
Battery Backup /
Equipments
Conductor
Insulation
Filler
Sheath
Insulation
Conductor
Color Skin
Natural PVC
Multistrand Flexible
Copper Conductor
Insulation
Conductor
Sheath
Table -1
Physical Parameters
SIZE
cross-sectional
area ( Sq MM)
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
Minimum
No of Strand in
Conductor
Al
Cu
1
1
6
6
6
6
12
15
15
15
30
30
30
53
53
53
53
53
Nominal
Thickness of
Insulation)
(mm)
Nominal
Thickness of
outer sheath
(mm)
Approx.
Overal
Diameter
(mm)
1.0
1.0
1.0
1.0
1.2
1.2
1.4
1.4
1.6
1.6
1.8
2.0
2.2
2.4
2.6
3.0
3.4
3.4
3.4
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
2.0
2.0
2.0
2.0
2.0
2.2
2.2
2.4
2.4
2.6
8
9
10
11
13
14
16
17
19
21
23
25
28
30
35
38
43
48
52
1/7
1/7
6
6
6
6
6
12
15
18
18
30
34
34
53
53
53
53
53
80
100
120
160
210
250
300
400
500
600
750
900
1100
1350
1700
2150
2750
3300
4100
105
135
180
260
365
460
610
830
1100
1350
1680
2050
2600
3200
4200
5250
6650
8250
10300
Cross-sectional view
1
INSULATION : PVC Type A of IS:5831 / OPTION: HR PVC (Type-C of IS-5831), Colour : Black
OUTER SHEATH : PVC TYPE ST-1 OF IS : 5831 OPTIONS : PVC Type ST-2 of IS:5831/ FR TYPE/FRLS TYPE
COLOUR OF OUTER SHEATH : BLACK . OPTIONS : any other colour as per requirement.
- Tabulated approx. net wt. of cables are only guidelines for transportation, loading & unloading purpose..
- Please ref page no 43 for normal delivery lengths & packing details.
Electrical Parameters
SIZE
cross-sectional
area (Sq MM)
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
Max. Cond. D.C. Approx. Cond. A.C. App. Reactance App. Capecitance
Resistance at
Resistance at
at 50HZ
of cable
20oCin Ohm/km 70oC in Ohm/km
in ohms/km
in microF/KM
Al
Cu
Al
Cu
4.61
3.08
1.91
1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778
0.0605
0.0469
0.0367
0.0291
4.61
3.08
1.83
1.15
0.727
0.524
0.387
0.268
0.193
0.153
0.1240
0.0991
0.0754
0.0601
0.0470
0.0366
0.0283
0.0221
0.0176
5.53
3.70
2.29
1.44
1.04
0.769
0.532
0.384
0.304
0.247
0.197
0.151
0.122
0.0961
0.0759
0.0610
0.0503
0.0422
5.53
3.70
2.20
1.38
0.87
0.63
0.464
0.322
0.232
0.184
0.1488
0.1189
0.0912
0.0733
0.0580
0.0459
0.0368
0.0303
0.0255
0.140
0.127
0.118
0.110
0.105
0.100
0.098
0.091
0.088
0.086
0.085
0.084
0.082
0.080
0.080
0.079
0.077
0.077
0.076
0.58
0.68
0.83
1.01
1.05
1.22
1.22
1.43
1.47
1.62
1.62
1.62
1.72
1.74
1.81
1.86
1.87
1.98
2.20
39
51
66
86
100
120
140
175
195
220
240
270
295
325
345
390
450
500
37
51
65
84
100
115
135
155
170
190
210
225
245
275
295
320
380
415
35
47
64
84
105
130
155
190
220
250
290
335
380
435
480
550
610
680
39
49
65
85
110
130
155
190
220
250
280
305
345
375
400
425
470
530
590
38
48
64
83
110
125
150
175
200
220
245
260
285
310
335
355
375
425
740
35
44
60
82
110
130
165
205
245
280
320
370
425
475
550
590
660
725
870
in K. Amps
Al
Cu
0.304
0.456
0.760
1.220
1.900
2.660
3.800
5.320
7.220
9.120
11.40
14.10
18.20
22.80
30.40
38.00
47.90
60.80
76.00
0.460
0.690
1.150
1.84
2.88
4.03
5.75
8.05
10.90
13.80
17.30
21.30
27.30
34.50
46.00
57.50
72.50
92.00
115.00
Note : Normal current ratings are given in standard conditions (as given in page no 40,41), if site conditions are different, current rating should be multiplied by
rating factor as given in page no. 42
Table -2
Physical Parameters
SIZE Cross-sectional
Minimum No of
Strands in
Nominal
Thickness of
Minimum
thickness of
Nominal thick.
of OUTER
Approx.
Overall
area
( sqmm)
Conductor
Al
Cu
Insulation)
(mm)
inner Sh.
(mm)
Sheath
(mm)
Diameter
(mm)
Approx. Net Wt
of cable ( Kg/KM)
With Al cond
AYY
With Cu Cond.
YY
1/7
1.0
0.30
1.80
14
240
290
1/7
1.0
0.30
1.80
17
300
370
10
1.0
0.30
1.80
18
400
520
16
1.0
0.30
1.80
17
430
630
25
1.2
0.30
2.00
19
450
750
35
1.2
0.30
2.00
21
550
980
50
1.4
0.30
2.00
24
700
1300
70
12
12
1.4
0.30
2.00
26
850
1700
95
15
15
1.6
0.40
2.20
30
1150
2300
120
15
18
1.6
0.40
2.20
32
1300
2800
150
15
18
1.8
0.40
2.40
34
1600
3450
185
30
30
2.0
0.50
2.40
38
2000
4300
240
30
34
2.2
0.50
2.60
42
2500
5500
300
30
34
2.4
0.60
2.80
46
3000
6700
8750
400
53
53
2.6
0.70
3.20
52
3800
500
53
53
3.0
0.70
3.40
54
4800
11000
630
53
53
3.4
0.70
3.80
65
6000
13800
2
3
4
INSULATION : PVC Type A of IS :5831/ OPTION : HR PVC ( Type -C of IS -5831), Colour : Red & Black
INNER SHEATH : PVC as per IS :1554PT-1
OUTER SHEATH : PVC TYPE ST-1 OF IS : 5831 OPTIONS : PVC TYPE ST-2 OF IS : 5831/ FR TYPE/ FRLS TYPE
COLOUR OF OUTER SHEATH : BLACK . OPTIONS : any other colour as per requirement.
~ Tabulated approx. net wt. of cables are only guidelines for transportation, loading &unloading purpose.
~ Please ref page no 43 for normal delivery lengths & packing details.
Electrical Parameters
SIZE
cross-sectional
area (Sq MM)
in K. Amps
Al
Cu
4.61
5.53
0.098
0.23
32
27
27
41
35
35
0.304
0.460
4.61
3.08
5.53
3.70
0.096
0.28
40
34
35
50
44
45
0.456
0.690
10
3.08
1.83
3.70
2.20
0.091
0.34
55
45
47
70
58
60
0.760
1.150
16
1.91
1.15
2.29
1.38
0.085
0.40
70
58
59
90
75
78
1.220
1.840
25
1.20
0.727
1.44
0.87
0.083
0.42
90
76
78
115
97
105
1.900
2.880
35
0.868
0.524
1.04
0.63
0.082
0.48
110
92
99
140
120
125
2.660
4.030
5.750
50
0.641
0.387
0.769
0.464
0.082
0.49
135
115
125
165
145
155
3.800
70
0.443
0.268
0.532
0.322
0.076
0.56
160
140
150
205
180
195
5.320
95
0.320
0.193
0.384
0.232
0.076
0.58
190
170
185
240
215
230
7.220
0.304
120
0.253
0.153
150
0.206
0.1240 0.247
8.050
10.90
0.184
0.075
0.63
210
190
210
275
235
265
9.120
13.80
0.1488
0.074
0.63
240
210
240
310
270
305
11.40
17.300
185
0.164
0.0991 0.197
0.1189
0.074
0.64
275
240
275
350
300
350
14.10
21.280
240
0.125
0.0754 0.151
0.0912
0.073
0.67
320
275
325
405
345
410
18.20
27.600
300
0.100
0.0601 0.122
0.0733
0.073
0.68
355
305
365
450
385
465
22.80
34.500
400
0.072
0.70
385
345
420
490
485
530
30.40
46.000
500
0.072
0.70
425
380
475
540
460
605
38.00
57.500
630
0.072
0.70
465
415
540
640
550
785
47.90
72.550
Note : Normal current ratings are given in standard conditions (as given in page no 40,41) , if site conditions are different, current rating should be multiplied by
rating factor as given in page no. 42
Table -3
Physical Parameters
SIZE Cross-sectional
Minimum No of
Strands in
Nominal thick.
Thickness of
Minimum
thickness of
Nominal thick.
of outer
Approx.
Overall
area
( sqmm)
Conductor
Al
Cu
Insulation)
(mm)
inner Sh.
(mm)
Sheath
(mm)
Diameter
(mm)
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
1
1
6
6
6
6
12
15
15
15
30
30
30
53
53
53
1/7
1/7
6
6
6
6
6
12
15
18
18
30
34
34
53
53
53
1.0
1.0
1.0
1.0
1.2
1.2
1.4
1.4
1.6
1.6
1.8
2.0
2.2
2.4
2.6
3.0
3.4
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.40
0.40
0.40
0.50
0.50
0.60
0.60
0.70
0.70
0.70
1.80
1.80
1.80
1.80
2.00
2.00
2.00
2.20
2.20
2.20
2.40
2.60
2.80
3.00
3.40
3.60
4.00
Approx. Net Wt
of cable ( Kg/KM)
With Al cond
AYY
16
18
19
19
22
24
27
30
34
37
40
44
50
55
62
69
77
With Cu Cond.
YY
270
360
440
460
620
740
940
1200
1600
1900
2300
2750
3500
4300
5450
6900
8700
340
470
650
730
1080
1400
1870
2500
3350
4100
5100
6200
7950
9900
12800
16200
20400
Cross-sectional View
1
INSULATION : PVC Type A of IS :5831/ OPTION : HR PVC ( Type -C of IS -5831), Colour : Red, Yellow & Blue
INNER SHEATH : PVC as per IS :1554PT-1
OUTER SHEATH : PVC TYPE ST-1 OF IS : 5831 OPTIONS : PVC TYPE ST-2 OF IS : 5831/ FR TYPE/ FRLS TYPE
COLOUR OF OUTER SHEATH : BLACK. OPTIONS : any other colour as per requirement.
~Copper . Cond :- 4 & 6 sqmm-solid/ stranded non compacted circular, 10 sqmm : Stranded compacted circular,16sqmm & above : Stranded compacted shaped
3
4
~ Tabulated approx. net wt. of cables are only guidelines for transportation, loading &unloading purpose.
~ Please ref page no 43 for normal delivery lengths & packing details.
Electrical Parameter
SIZE
cross-sectional
area (Sq MM)
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
Max. Cond. D.C. Approx. Cond. A.C. pp.. Reactance App. Capecitance
Resistance at
Resistance at
at 50HZ
of cable
20oC in Ohm/km 70oC in Ohm/km
in ohms/km
in microF/KM
Al
Cu
Al
Cu
4.61
3.08
1.91
1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778
0.0605
0.0469
4.61
3.08
1.83
1.15
0.727
0.524
0.387
0.268
0.193
0.153
0.1240
0.0991
0.0754
0.0601
0.0470
0.0366
0.0283
5.53
3.70
2.29
1.44
1.04
0.769
0.532
0.384
0.304
0.247
0.197
0.151
0.122
0.0961
0.759
0.0610
5.53
3.70
2.20
1.38
0.87
0.63
0.464
0.322
0.232
0.184
0.1488
0.1189
0.0912
0.0733
0.0580
0.0459
0.0368
0.098
0.096
0.091
0.085
0.083
0.082
0.082
0.076
0.076
0.075
0.074
0.074
0.073
0.073
0.072
0.072
0.072
0.23
0.28
0.34
0.40
0.42
0.48
0.49
0.56
0.58
0.63
0.63
0.64
0.67
0.68
0.70
0.70
0.70
28
35
46
60
76
92
110
135
165
185
210
235
275
305
335
370
405
23
30
39
50
63
77
95
115
140
155
175
200
235
260
290
320
350
23
30
40
51
70
86
105
130
155
180
205
240
280
315
375
425
480
36
45
60
77
99
120
145
175
210
240
270
300
345
385
425
470
555
30
38
50
64
81
99
125
150
175
195
225
255
295
335
360
390
470
30
39
52
66
90
110
135
165
200
230
265
305
355
400
435
520
675
in K. Amps
Al
Cu
0.304
0.456
0.760
1.220
1.900
2.660
3.800
5.320
7.220
9.120
11.40
14.10
18.20
22.80
30.40
38.00
47.90
0.460
0.690
1.150
1.840
2.880
4.030
5.750
8.050
10.900
13.800
17.300
21.300
27.600
34.500
46.000
57.500
72.500
Note : Normal current ratings are given in standard conditions( as given in page no- 40,41) , if site conditions are different, current rating should be multiplied
by rating factor as given in page no. 42
Table -4
Physical Parameters
SIZE
cross-sectional
area ( Sq MM)
Minimum nos of
Strands in conductor
Phase
Neutral
Al
Cu
Nominal
Thickness of
Insulation) (mm)
Phase / Neutral
Minimum
Thickness of
inner sheath
(mm)
Nominal
thickness of
outer sheath
(mm)
Approx.
Overal
Diameter
(mm)
3X25+16
6/6
6/6
1.20/1.00
0.30
2.00
24
700
1264
3X35+16
6/6
6/6
1.20/1.00
0.30
2.00
26
850
1600
3X50+25
6/6
6/6
1.40/1.20
0.30
2.00
29
1050
2100
3X70+35
12/6
12/6
1.40/1.20
0.40
2.20
32
1400
2900
3X95+50
15/6
15/6
1.60/1.40
0.40
2.20
36
1800
3900
3X120+70
15/12
18/12
1.60/1.40
0.50
2.40
40
2200
4850
3X150+70
15/12
18/12
1.80/1.40
0.50
2.40
44
2600
5800
3X185+95
30/15
30/15
2.00/1.60
0.50
2.60
48
3200
7200
3X240+120
30/15
34/18
2.20/1.60
0.60
3.00
54
4100
9300
3X300+150
30/15
34/18
2.40/1.80
0.60
3.20
62
5000
11500
3X400+185
53/30
53/30
2.60/2.00
0.70
3.40
68
6300
15000
3X500+240
53/30
53/34
3.00/2.20
0.70
3.80
77
8000
18500
3X630+300
53/30
53/34
3.40/2.40
0.70
4.00
87
10000
23500
Cross-sectional View
1
2
3
4
INSULATION : PVC Type A of IS :5831/ OPTION : HR PVC ( Type -C of IS -5831), Colour : Red, Yellow, Blue, Black
INNER SHEATH : PVC as per IS :1554PT-1
OUTER SHEATH : PVC TYPE ST-1 OF IS : 5831 OPTIONS : PVC TYPE ST-2 OF IS : 5831/ FR TYPE/ FRLS TYPE
COLOUR OF OUTER SHEATH : BLACK . OPTIONS : any other colour as per requirement.
~ Tabulated approx. net wt. of cables are only guidelines for transportation, loading &unloading purpose ..
~ Please ref page no 43 for normal delivery lengths & packing details.
Electrical Parameters
SIZE
cross-sectional
area (Sq MM)
in K. Amps
Al
Cu
3X25+16
1.20
0.727 1.44
0.87
0.083
0.42
76
63
70
99
81
90
1.90
2.88
3X35+16
0.868
0.524 1.04
0.63
0.082
0.48
92
77
86
120
99
110
2.66
4.03
3X50+25
0.641
0.387 0.769
0.464
0.082
0.49
110
95
105
145
125
135
3.80
5.75
3X70+35
0.443
0.268 0.532
0.322
0.076
0.56
135
115
130
175
150
165
5.32
8.05
3X95+50
0.320
0.193 0.384
0.232
0.076
0.58
165
140
155
210
175
200
7.22
10.90
3X120+70
0.253
0.153 0.304
0.184
0.075
0.63
185
155
180
240
195
230
9.12
13.80
3X150+70
0.206
0.1240 0.247
0.1488
0.074
0.63
210
175
205
270
225
265
11.40
17.30
3X185+95
0.164
0.0991 0.197
0.1189
0.074
0.64
235
200
240
300
255
305
14.10
21.30
3X240+120
0.125
0.0754 0.151
0.0912
0.073
0.67
275
235
280
345
295
355
18.20
27.60
3X300+150
0.100
0.0601 0.122
0.0733
0.073
0.68
305
260
315
385
335
400
22.80
34.50
3X400+185
0.0580
0.072
0.70
335
290
375
425
360
435
30.40
46.00
3X500+240
0.0459
0.072
0.70
370
320
425
470
390
520
38.00
57.50
3X630+300
0.0368
0.072
0.70
405
350
480
555
470
675
47.90
72.50
Note : Normal current ratings are given in standard conditions (as given in page no- 40,41) , if site conditions are different, current rating should be multiplied
by rating factor as given in page no. 42
Table -5
Physical Parameters
SIZE
cross-sectional
area
(sq mm)
Minimum
No of Strand in
Conductor
Al
Cu
Nominal
Thickness of
Insulation)
(mm)
Minimum
Thickness of
inner sheath
(mm)
Nominal
thickness of
outer sheath
(mm)
Approx.
Overal
Diameter
(mm)
1/7
1.0
0.30
1.80
16
300
400
1/7
1.0
0.30
1.80
18
390
540
10
1.0
0.30
1.80
20
540
788
16
1.0
0.30
2.00
23
560
950
25
1.2
0.30
2.00
26
750
1370
35
1.2
0.30
2.00
30
940
1800
50
1.4
0.40
2.20
34
1250
2500
70
12
12
1.4
0.40
2.20
38
1550
3300
95
15
15
1.6
0.40
2.40
43
2050
4400
120
15
18
1.6
0.50
2.40
46
2400
5380
150
15
18
1.8
0.50
2.60
51
2950
6670
185
30
30
2.0
0.60
2.80
55
3650
8250
240
30
34
2.2
0.60
3.00
60
4600
10550
300
30
34
2.4
0.70
3.40
66
5500
12950
400
53
53
2.6
0.70
3.60
73
6800
16720
500
53
53
3.0
0.70
4.00
82
8600
21000
630
53
53
3.4
0.70
4.00
92
11000
26000
2
3
4
INSULATION : PVC Type A of IS :5831/ OPTION : HR PVC ( Type -C of IS -5831), Colour : Red, Yellow, Blue, Black
INNER SHEATH : PVC as per IS :1554PT-1
OUTER SHEATH : PVC TYPE ST-1 OF IS : 5831 OPTIONS : PVC TYPE ST-2 OF IS : 5831/ FR TYPE/ FRLS TYPE
COLOUR OF OUTER SHEATH : BLACK . OPTIONS : any other colour as per requirement.
~ Tabulated approx. net wt. of cables are only guidelines for transportation, loading &unloading purpose ..
~ Please ref page no 43 for normal delivery lengths & packing details.
Electrical Parameters
SIZE
cross-sectional
area (Sq MM)
4.61
5.53
0.098
0.23
28
23
23
36
30
30
in K. Amps
Al
Cu
0.304
0.460
4.61
3.08
5.53
3.70
0.096
0.28
35
30
30
45
38
39
0.456
0.690
10
3.08
1.83
3.70
2.20
0.091
0.34
46
39
40
60
50
52
0.760
1.150
16
1.91
1.15
2.29
1.38
0.085
0.40
60
50
51
77
64
66
1.220
1.840
25
1.20
0.727
1.44
0.87
0.083
0.42
76
63
70
99
81
90
1.900
2.880
35
0.868
0.524
1.04
0.63
0.082
0.48
92
77
86
120
99
110
2.660
4.030
50
0.641
0.387
0.769
0.464
0.082
0.49
110
95
105
145
125
135
3.800
5.750
70
0.443
0.268
0.532
0.322
0.076
0.56
135
115
130
175
150
165
5.320
8.050
95
0.320
0.193
0.384
0.232
0.076
0.58
165
140
155
210
175
200
7.220
10.900
0.304
120
0.253
0.153
150
0.206
0.1240 0.247
0.184
0.075
0.63
185
155
180
240
195
230
9.120
13.800
0.1488
0.074
0.63
210
175
205
270
225
265
11.400
17.300
185
0.164
0.0991 0.197
0.1189
0.074
0.64
235
200
240
300
255
305
14.100
21.300
240
0.125
0.0754 0.151
0.0912
0.073
0.67
275
235
280
345
295
355
18.200
27.600
300
0.100
0.0601 0.122
0.0733
0.073
0.68
305
260
315
385
335
400
22.800
34.500
400
0.072
0.70
335
290
375
425
360
435
30.400
46.000
500
0.072
0.70
370
320
425
470
390
520
38.000
57.500
630
0.072
0.70
405
350
480
555
470
675
47.900
72.500
Note : Normal current ratings are given in standard conditions (as given in page no 40,41) , if site conditions are different, current rating should be multiplied by
rating factor as given in page no. 42
10
Table -6
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
Minimum
No of
Strands in
Conductor
Al
Cu
1
1
6
6
6
6
12
15
15
15
30
30
30
53
53
53
53
53
Nominal
Thickness of
Insulation)
(mm)
1/7
1/7
6
6
6
6
6
12
15
18
18
30
34
34
53
53
53
53
53
1.3
1.3
1.3
1.3
1.5
1.5
1.7
1.7
1.9
1.9
2.1
2.3
2.5
2.7
3.0
3.4
3.9
3.9
3.9
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
1.40
1.40
1.40
1.40
1.40
1.56
1.56
1.56
1.72
1.88
2.04
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
21
23
24
27
30
32
37
40
45
49
55
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
650
750
900
1050
1300
1600
1950
2400
3100
3700
4600
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
1230
1500
1830
2200
2800
3450
4400
5500
7000
8650
10800
1.40
1.40
1.40
1.40
1.40
1.40
1.40
1.40
1.60
1.60
1.60
1.60
1.60
1.60
2.00
2.00
2.00
2.00
2.50
1.24
1.24
1.24
1.24
1.24
1.24
1.24
1.40
1.40
1.40
1.40
1.40
1.56
1.56
1.56
1.72
1.88
1.88
2.04
11
12
13
14
15
16
18
20
22
24
26
29
32
33
39
42
48
52
59
150
180
200
250
300
350
450
550
700
800
950
1100
1400
1650
2100
2700
3300
4000
4900
180
210
260
350
450
560
750
980
1300
1550
1880
2250
2900
3500
4580
5800
7200
8950
11000
INSULATION : PVC Type A of IS :5831/ OPTION : HR PVC (Type -C of IS -5831), Colour : Black
INNER SHEATH : PVC as per IS :1554PT-1
ARMOURING : Single layer of Aluminium Round wires / Flat Strips
OUTER SHEATH : PVC TYPE ST-1 OF IS : 5831 OPTIONS : PVC TYPE ST-2 OF IS : 5831/ FR TYPE/ FRLS TYPE
COLOUR OF OUTER SHEATH : BLACK. OPTIONS : any other colour as per requirement.
~Copper . Cond :- 4 & 6sqmm -solid/ stranded non compacted circular, 10sqmm : Stranded compacted circular,16sqmm & above : Stranded compacted shaped
3
4
5
~ Tabulated approx. net wt. of cables are only guidelines for transportation, loading &unloading purpose.
~ Please ref page no 43 for normal delivery lengths & packing details.
Electrical Parameters
SIZE
cross-sectional
area (Sq MM)
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
7.41
4.61
3.08
1.91
1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778
0.0605
0.0469
0.0367
0.0291
4.61
3.08
1.83
1.15
0.727
0.524
0.387
0.268
0.193
0.153
0.1240
0.0991
0.0754
0.0601
0.0470
0.0366
0.0283
0.0221
0.0176
8.89
5.53
3.70
2.29
1.44
1.04
0.769
0.532
0.384
0.304
0.247
0.197
0.151
0.122
0.0961
0.076
0.0610
0.0503
0.0422
5.53
3.70
2.20
1.38
0.87
0.63
0.464
0.322
0.232
0.184
0.1488
0.1189
0.0912
0.0733
0.0580
0.0459
0.0368
0.0303
0.0255
0.157
0.148
0.138
0.128
0.120
0.114
0.110
0.103
0.101
0.096
0.094
0.092
0.090
0.088
0.088
0.087
0.086
0.083
0.082
0.48
0.56
0.67
0.81
0.87
1.00
1.03
1.21
1.27
1.42
1.42
1.44
1.53
1.56
1.59
1.67
1.67
1.75
1.94
31
39
51
66
86
100
120
140
175
195
220
240
270
295
325
345
390
450
500
30
37
51
65
84
100
115
135
155
170
190
210
225
245
275
295
320
380
414
27
35
47
64
84
105
130
155
190
220
250
290
335
380
435
480
550
610
680
39
49
65
85
110
130
155
190
220
250
280
305
345
375
400
425
470
530
590
38
48
64
83
110
125
150
175
200
220
245
260
285
310
335
355
375
423
471
35
44
60
82
110
130
165
205
245
280
320
370
425
475
550
590
660
725
870
in K. Amps
Al
Cu
0.304
0.460
0.456
0.690
0.760
1.150
1.220
1.840
1.900
2.880
2.660
4.030
3.800
5.750
5.320
8.050
7.220 10.90
9.120 13.80
11.400 17.30
14.100 21.30
18.200 27.60
22.800 34.50
30.400 46.00
38.000 57.50
47.880 72.50
60.800 92.00
76.000 115.00
Note : Normal current ratings are given in standard conditions (as given in page no - 40,41) , if site conditions are different, current rating should be multiplied by
rating factor as given in page no. 42
11
Table -7
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
Minimum
No of
Strands in
Conductor
Al
Cu
1
1
6
6
6
6
12
15
15
15
30
30
30
53
53
53
Nominal Minimum
ARMOURING WITH FLAT STRIP ( AYFY/ YFY)
ARMOURING WITH
Thickness Thickness Nominal
Minimum
Approx.
Approx. Net Wt
Nominal
Minimum
of
Thickness Thickness of
Overall
of cable (Kg/KM)
Diameter Thickness of
of
Insulation) inner Sh. of armour outer sheath Diameter With Al cond With Cu Cond. of armour outer sheath
(mm)
(mm)
(mm)
(mm)
AYFY
YFY
(mm)
(mm)
(mm)
1/7
1/7
6
6
6
6
6
12
15
18
18
30
34
34
53
53
53
1.0
1.0
1.0
1.0
1.2
1.2
1.4
1.4
1.6
1.6
1.8
2.0
2.2
2.4
2.6
3.0
3.4
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.40
0.40
0.40
0.50
0.50
0.60
0.70
0.70
0.70
N/A
N/A
N/A
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
N/A
N/A
N/A
1.40
1.40
1.40
1.40
1.56
1.56
1.56
1.72
1.88
2.04
2.20
2.36
2.68
2.84
N/A
N/A
N/A
18
20
22
25
27
30
32
35
38
43
48
53
56
66
N/A
N/A
N/A
580
700
800
1000
1200
1550
1800
2100
2500
3100
3700
4500
5600
6900
N/A
N/A
N/A
780
1000
1230
1620
2050
2720
3290
3970
4800
6080
7400
9450
11800
14700
1.40
1.40
1.40
1.60
1.60
1.60
1.60
1.60
2.00
2.00
2.00
2.00
2.50
2.50
3.15
3.15
4.00
1.24
1.24
1.24
1.40
1.40
1.40
1.56
1.56
1.56
1.72
1.72
1.88
2.04
2.20
2.52
2.84
3.00
18
19
20
20
22
23
26
29
33
35
37
41
47
50
58
64
72
600
660
750
750
900
1030
1300
1500
2050
2400
2760
3200
4200
5000
6600
8000
11000
650
730
870
950
1200
1450
1900
2350
3200
3900
4600
5500
7200
8700
11500
14000
18800
2
3
4
5
INSULATION : PVC Type A of IS :5831/ OPTION : HR PVC ( Type -C of IS -5831), Colour : Red & Black
INNER SHEATH : PVC as per IS :1554PT-1
ARMOURING : Single layer of Galvanized steel Round wires / Flat Strips
OUTER SHEATH : PVC TYPE ST-1 OF IS : 5831 OPTIONS : PVC TYPE ST-2 OF IS : 5831/ FR TYPE/ FRLS TYPE
COLOUR OF OUTER SHEATH : BLACK . OPTIONS : any other colour as per requirement.
~ Tabulated approx. net wt. of cables are only guidelines for transportation, loading &unloading purpose.
~ Please ref page no 43 for normal delivery lengths & packing details.
Electrical Parameters
SIZE
cross-sectional
area (Sq MM)
in K. Amps
Al
Cu
4
--4.61
--5.53
0.098
0.23
32
27
27
41
35
35
0.304
0.460
6
4.61
3.08
5.53
3.70
0.096
0.28
40
34
35
50
44
45
0.456
0.690
10
3.08
1.83
3.70
2.20
0.091
0.34
55
45
47
70
58
60
0.760
1.150
16
1.91
1.15
2.29
1.38
0.085
0.40
70
58
59
90
75
78
1.220
1.840
25
1.20
0.727 1.44
0.87
0.083
0.42
90
76
78
115
97
105
1.90
2.880
35
0.868 0.524 1.04
0.63
0.082
0.48
110
92
99
140
120
125
2.66
4.030
50
0.641 0.387 0.769 0.464
0.082
0.49
135
115
125
165
145
155
3.80
5.750
70
0.443 0.268 0.532 0.322
0.076
0.56
160
140
150
205
180
195
5.32
8.050
95
0.320 0.193 0.384 0.232
0.076
0.58
190
170
185
240
215
230
7.22
10.90
120
0.253 0.153 0.304 0.184
0.075
0.63
210
190
210
275
235
265
9.12
13.80
150
0.206 0.1240 0.247 0.1488
0.074
0.63
240
210
240
310
270
305
11.40
17.30
185
0.164 0.0991 0.197 0.1189
0.074
0.64
275
240
275
350
300
350
14.10
21.30
240
0.125 0.0754 0.151 0.0912
0.073
0.67
320
275
325
405
345
410
18.20
27.60
300
0.100 0.0601 0.122 0.0733
0.073
0.68
355
305
365
450
385
465
22.80
34.50
400
0.0778 0.0470 0.0961 0.0580
0.072
0.70
385
345
420
490
485
530
30.40
46.00
500
0.0605 0.0366 0.0759 0.0459
0.072
0.70
425
380
475
540
460
605
38.00
57.50
630
0.0469 0.0283 0.0610 0.0368
0.072
0.70
465
415
540
640
550
785
47.90
72.50
Note : Normal current ratings are given in standard conditions (as given in page no - 40,41), if site conditions are different, current rating should be multiplied by
rating factor as given in page no. 42
12
Table -8
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
-1
1
6
6
6
6
12
15
15
15
30
30
30
53
53
53
Nominal Minimum
ARMOURING WITH FLAT STRIP ( AYFY/ YFY)
ARMOURING WITH
Thickness Thickness Nominal
Minimum
Approx.
Approx. Net Wt
Nominal
Minimum
of
Thick. of
Thick. of
Overall
of cable ( Kg/KM)
Diameter Thickness of
of
Insulation) inner Sh. armour strip outer sheath Diameter With Al cond With Cu Cond. of wire
outer sheath
(mm)
(mm)
(mm)
(mm)
AYFY
YFY
(mm)
(mm)
(mm)
1/7
1/7
6
6
6
6
6
12
15
18
18
30
34
34
53
53
53
1.0
1.0
1.0
1.0
1.2
1.2
1.4
1.4
1.6
1.6
1.8
2.0
2.2
2.4
2.6
3.0
3.4
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.40
040
0.40
0.50
0.50
0.60
0.60
0.70
0.70
0.70
N/A
N/A
N/A
0.80
080.
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
N/A
N/A
N/A
1.40
1.40
1.40
1.56
1.56
1.56
1.72
1.88
1.88
2.20
2.36
2.52
2.84
3.00
N/A
N/A
N/A
20
23
24
27
31
35
37
41
46
51
56
63
70
78
N/A
N/A
N/A
700
900
1000
1300
1600
2000
2400
2800
3400
4200
5050
6300
7800
9700
N/A
N/A
N/A
1000
1350
1650
2230
2900
3750
4630
5600
6840
8650
10630
13740
17100
21418
1.40
1.40
1.40
1.60
1.60
1.60
1.60
2.00
2.00
2.00
2.00
2.50
2.50
2.50
3.15
3.15
4.00
1.24
1.24
1.40
1.40
1.40
1.40
1.56
1.56
1.72
1.72
1.88
2.04
2.20
2.36
2.68
3.00
3.00
18
19
21
21
23
26
29
33
37
39
43
49
54
59
68
75
84
600
700
900
950
1100
1300
1600
2150
2650
3000
3550
4600
5600
6600
8700
11000
14000
650
810
1100
1250
1550
1950
2530
3450
4400
5200
6300
8000
10000
12000
16000
20000
25500
2
3
4
5
INSULATION : PVC Type A of IS :5831/ OPTION : HR PVC ( Type -C of IS -5831), Colour : Red, Yellow, Blue
INNER SHEATH : PVC as per IS :1554PT-1
ARMOURING : Single layer of Galvanized steel Round wires / Flat Strips
OUTER SHEATH : PVC TYPE ST-1 OF IS : 5831 OPTIONS : PVC TYPE ST-2 OF IS : 5831/ FR TYPE/ FRLS TYPE
COLOUR OF OUTER SHEATH : BLACK . OPTIONS : any other colour as per requirement.
~ Tabulated approx. net wt. of cables are only guidelines for transportation, loading &unloading purpose.
~Please ref page no 43 for normal delivery lengths & packing details.
Electrical Parameters
SIZE
cross-sectional
area (Sq MM)
in K. Amps
Al
Cu
4.61
5.53
0.098
0.23
28
23
23
36
30
30
0.304
0.460
6
4.61
3.08
5.53
3.70
0.096
0.28
35
30
30
45
38
39
0.456
0.690
10
3.08
1.83
3.70
2.20
0.091
0.34
46
39
40
60
50
52
0.760
1.150
16
1.91
1.15
2.29
1.38
0.085
0.40
60
50
51
77
64
66
1.220
1.840
25
1.20 0.727 1.44
0.87
0.083
0.42
76
63
70
99
81
90
1.900
2.880
35
0.868 0.524 1.04
0.63
0.082
0.48
92
77
86
120
99
110
2.660
4.030
50
0.641 0.387 0.769
0.464
0.082
0.49
110
95
105
145
125
135
3.800
5.750
70
0.443 0.268 0.532
0.322
0.076
0.56
135
115
130
175
150
165
5.320
8.050
95
0.320 0.193 0.384
0.232
0.076
0.58
165
140
155
210
175
200
7.220
10.900
120
0.253 0.153 0.304
0.184
0.075
0.63
185
155
180
240
195
230
9.120
13.800
150
0.206 0.1240 0.247 0.1488
0.074
0.63
210
175
205
270
225
265
11.400 17.300
185
0.164 0.0991 0.197 0.1189
0.074
0.64
235
200
240
300
255
305
14.100 21.300
240
0.125 0.0754 0.151 0.0912
0.073
0.67
275
235
280
345
295
355
18.200 27.600
300
0.100 0.0601 0.122 0.0733
0.073
0.68
305
260
315
385
335
400
22.800 34.500
400
0.0778 0.0470 0.0961 0.0580
0.072
0.70
335
290
375
425
360
435
30.400 46.000
500
0.0605 0.0366 0.0759 0.0459
0.072
0.70
370
320
425
470
390
520
38.000 57.500
630
0.0469 0.0283 0.0610 0.0368
0.072
0.70
405
350
480
555
470
675
47.900 72.500
Note : Normal current ratings are given in standard conditions (as given in page no - 40,41), if site conditions are different, current rating should be multiplied by
rating factor as given in page no. 42
13
Table -9
Minimum
Nominal
ARMOURING WITH FLAT STRIP ( AYFY/ YFY)
ARMOURING WITH
Minimum
Nos of
Thickness of Thickness Nominal
Minimum
Approx.
Approx. Net Wt
Nominal
Minimum
Strands in
Insulation)
Thickness Thickness of Overall
of cable ( Kg/KM) Diameter Thickness of
of
outer sheath
Conductor
(mm)
Strip
outer sheath Diameter With Al cond With Cu Cond. of wire
inner Sh.
Phase/Neutral Phase/Neutral (mm)
(mm)
(mm)
(mm)
AYFY
YFY
(mm)
(mm)
3X25+16
6/6
6/6
1.20/1.00
0.30
0.80
1.40
24
1000
1550
1.60
1.40
26
1300
1850
3X35+16
6/6
6/6
1.20/1.00
0.30
0.80
1.40
26
1200
1950
1.60
1.40
28
1450
2150
3X50+25
6/6
6/6
1.40/1.20
0.30
0.80
1.56
30
1500
2600
1.60
1.56
31
1800
2800
3X70+35
12/6
12/6
1.40/1.20
0.40
0.80
1.56
34
1800
3300
2.00
1.56
36
2400
3800
3X95+50
15/6
15/6
1.60/1.40
0.40
0.80
1.56
37
2300
4350
2.00
1.72
39
3000
5000
1.60/1.40
0.50
0.80
1.72
41
2800
5450
2.00
1.88
43
3500
6100
1.80/1.40
0.50
0.8
1.88
45
3200
6400
2.00
1.88
47
4000
7200
2.00/1.60
0.50
0.80
2.04
49
3900
7900
2.50
2.04
53
5200
9200
2.20/1.60
0.60
0.80
2.20
55
4800
10000
2.50
2.30
58
6400
11500
2.40/1.80
0.60
0.80
2.36
61
5800
12300
3.15
2.52
65
8200
14500
2.60/2.00
0.70
0.80
2.68
69
7300
15800
3.15
2.63
75
9900
18400
3.00/2.20
0.70
0.80
2.84
77
9000
19500
4.00
3.00
84
13500
24000
3.40/2.40
0.70
0.80
3.00
87
11500
25000
4.00
3.00
92
16000
28500
2
3
4
5
INSULATION : PVC Type A of IS :5831/ OPTION : HR PVC ( Type -C of IS -5831), Colour : Red, Yellow, Blue, Black
INNER SHEATH : PVC as per IS :1554PT-1
ARMOURING : Single layer of Galvanized steel Round wires / Flat Strips
OUTER SHEATH : PVC TYPE ST-1 OF IS : 5831 OPTIONS : PVC TYPE ST-2 OF IS : 5831/ FR TYPE/ FRLS TYPE
COLOUR OF OUTER SHEATH : BLACK . OPTIONS : any other colour as per requirement.
~ Tabulated approx. net wt. of cables are only guidelines for transportation, loading &unloading purpose.
~ Please ref page no 43 for normal delivery lengths & packing details.
Electrical Parameters
SIZE
cross-sectional
area (Sq MM)
3X25+16
1.20
0.727
1.44
0.87
0.083
0.42
76
63
70
99
81
90
1.90
2.88
3X35+16
0.868
0.524
1.04
0.63
0.082
0.48
92
77
86
120
99
110
2.66
4.03
in K. Amps
Al
Cu
3X50+25
0.641
0.387
0.769
0.464
0.082
0.49
110
95
105
145
125
135
3.80
5.75
3X70+35
0.443
0.268
0.532
0.322
0.076
0.56
135
115
130
175
150
165
5.32
8.05
3X95+50
0.320
0.193
0.384
0.232
0.076
0.58
165
140
155
210
175
200
7.22
10.90
3X120+70
0.253
0.153
0.304
0.184
0.075
0.63
185
155
180
240
195
230
9.12
13.80
3X150+70
0.206
0.1240 0.247
0.1488
0.074
0.63
210
175
205
270
225
265
11.40
17.30
3X185+95
0.164
0.0991 0.197
0.1189
0.074
0.64
235
200
240
300
255
305
14.10
21.30
3X240+120
0.125
0.0754 0.151
0.0912
0.073
0.67
275
235
280
345
295
355
18.20
27.60
0.0601 0.122
3X300+150
0.100
0.0733
0.073
0.68
305
260
315
385
335
400
22.80
34.50
3X400+185
0.072
0.70
335
290
375
425
360
435
30.40
46.00
3X500+240
0.072
0.70
370
320
425
470
390
520
38.00
57.50
3X630+300
0.072
0.70
405
350
480
555
470
675
47.90
72.50
Note : Normal current ratings are given in standard conditions (as given in page no - 40,41), if site conditions are different, current rating should be multiplied by
rating factor as given in page no. 42
14
Table -10
Physical Parameters
SIZE
Cross-sectional
area
( sqmm)
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
Minimum
No of
Strands in
Conductor
Al
Cu
1
1
6
6
6
6
12
15
15
15
30
30
30
53
53
53
Nominal Minimum
ARMOURING WITH FLAT STRIP ( AYFY/ YFY)
ARMOURING WITH ROUND WIRES ( AYWY/ YWY)
Thickness Thickness Nominal
Minimum
Approx.
Approx. Net Wt
Nominal Minimum
Approx.
Approx. Net Wt
of
Thickness Thickness of
Overall
of cable (Kg/KM)
Diameter Thickness of Overall
of cable ( Kg/KM)
of
Insulation) inner Sh. of armour outer sheath Diameter With Al cond With Cu Cond. of armour outer sheath Diameter With Al cond With Cu Cond.
(mm)
(mm)
(mm)
(mm)
AYFY
YFY
(mm)
(mm)
(mm)
AYWY
YWY
(mm)
1/7
1/7
6
6
6
6
6
12
15
18
18
30
34
34
53
53
53
1.0
1.0
1.0
1.0
1.2
1.2
1.4
1.4
1.6
1.6
1.8
2.0
2.2
2.4
2.6
3.0
3.4
0.30
0.30
0.30
0.30
0.30
0.30
0.40
0.40
0.40
0.50
0.50
0.60
0.60
0.70
0.70
0.70
0.70
N/A
N/A
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
N/A
N/A
1.40
1.40
1.40
1.40
1.56
1.56
1.72
1.88
1.88
2.04
2.36
2.52
2.84
3.00
3.00
N/A
N/A
21
22
25
28
32
35
40
43
48
52
59
67
74
80
90
N/A
N/A
750
860
1100
1300
1600
2000
2600
3050
3600
4300
5400
6600
8200
10500
13000
N/A
N/A
998
1260
1720
2170
2850
3740
5000
6030
7325
8890
11355
14050
18128
22900
28625
1.40
1.40
1.60
1.60
1.60
1.60
2.00
2.00
2.00
2.00
2.5
2.5
2.50
3.15
3.15
4.00
4.00
1.24
1.24
1.40
1.40
1.40
1.56
1.56
1.56
1.72
1.88
2.04
2.20
2.36
2.68
2.84
3.00
3.00
18
21
22
23
27
30
34
37
42
47
51
56
62
70
76
86
96
650
880
900
1120
1400
1600
2200
2650
3300
3850
4850
5800
7000
9200
11000
15000
18000
800
1030
1150
1520
2020
2470
3445
4390
5660
6830
8575
10390
12960
16650
20930
27400
33630
2
3
4
5
INSULATION : PVC Type A of IS :5831/ OPTION : HR PVC ( Type -C of IS -5831), Colour : Red, Yellow, Blue, Black
INNER SHEATH : PVC as per IS :1554PT-1
ARMOURING : Single layer of Galvanized steel Round wires / Flat Strips
OUTER SHEATH : PVC TYPE ST-1 OF IS : 5831 OPTIONS : PVC TYPE ST-2 OF IS : 5831/ FR TYPE/ FRLS TYPE
COLOUR OF OUTER SHEATH : BLACK . OPTIONS : any other colour as per requirement.
~ Tabulated approx. net wt. of cables are only guidelines for transportation, loading &unloading purpose ..
~ Please ref page no 43 for normal delivery lengths & packing details.
Electrical Parameters
SIZE
cross-sectional
area (Sq MM)
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
4.61
3.08
1.91
1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778
0.0605
0.0469
4.61
3.08
1.83
1.15
0.727
0.524
0.387
0.268
0.193
0.153
0.1240
0.0991
0.0754
0.0601
0.0470
0.0366
0.0283
5.53
3.70
2.29
1.44
1.04
0.769
0.532
0.384
0.304
0.247
0.197
0.151
0.122
0.0961
0.0759
0.0610
5.53
3.70
2.20
1.38
0.87
0.63
0.464
0.322
0.232
0.184
0.1488
0.1189
0.0912
0.0733
0.0580
0.0459
0.0368
0.098
0.096
0.091
0.085
0.083
0.082
0.082
0.076
0.076
0.075
0.074
0.074
0.073
0.073
0.072
0.072
0.072
0.23
0.28
0.34
0.40
0.42
0.48
0.49
0.56
0.58
0.63
0.63
0.64
0.67
0.68
0.70
0.70
0.70
28
35
46
60
76
92
110
135
165
185
210
235
275
305
335
370
405
23
30
39
50
63
77
95
115
140
155
175
200
235
260
290
320
350
23
30
40
51
70
86
105
130
155
180
205
240
280
315
375
425
480
36
45
60
77
99
120
145
175
210
240
270
300
345
385
425
470
555
30
38
50
64
81
99
125
150
175
195
225
255
295
335
360
390
470
30
39
52
66
90
110
135
165
200
230
265
305
355
400
435
520
675
in K. Amps
Al
Cu
0.304
0.456
0.760
1.220
1.900
2.660
3.800
5.320
7.220
9.120
11.40
14.10
18.20
22.80
30.40
38.00
47.90
0.460
0.690
1.150
1.840
2.880
4.030
5.750
8.050
10.900
13.800
17.300
21.300
27.600
34.500
46.000
57.500
72.500
Note : Normal current ratings are given in standard conditions (as given in page no - 40,41), if site conditions are different, current rating should be multiplied by
rating factor as given in page no. 42
15
Table -11
Physical Parameters
No
of
Cores
2
3
4
5
6
7
10
12
14
16
19
24
27
30
37
40
44
52
61
Minimum
UNARMOURED ( YY)
Approx.
Overall
Diameter (mm)
Approx. Net Wt
of cable ( Kg/KM)
Nominal Minimum
Thickness Thickness
of Armour of outr sh.
Approx.
Overall
Diameter (mm)
( mm)
mm
Solid cond
Std. Cond.
Solid cond
Std. Cond.
strip( mm)
(mm)
Solid cond
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.40
0.40
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.2
12
12.5
13
14
15
15
18
19
20
21
22
25
26
27
28
29
31
33
35
12
13
14
14
15
15
19
20
20
21
23
26
27
28
29
30
33
35
37
180
200
230
250
290
310
420
470
530
600
700
850
920
1000
1200
1270
1400
1650
1850
180
210
250
250
300
320
450
500
550
600
720
900
995
1050
1240
1300
1450
1700
1950
N/A
N/A
N/A
N/A
N/A
N/A
N/A
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
N/A
N/A
N/A
N/A
N/A
N/A
N/A
1.24
1.40
1.40
1.40
1.40
1.40
1.40
1.40
1.40
1.56
1.56
1.56
N/A
N/A
N/A
N/A
N/A
N/A
N/A
19
20
21
22
25
26
27
29
30
32
34
35
Std. Cond.
N/A
N/A
N/A
N/A
N/A
N/A
N/A
20
21
22
23
27
27
28
30
31
34
35
37
Approx. Net Wt
of cable ( Kg/KM)
Nominal Minimum
Approx.
Dia of Thickness
Overall
Armour of outr sh. Diameter (mm)
Solid cond
Std. Cond.
wire ( mm)
(mm)
N/A
N/A
N/A
N/A
N/A
N/A
N/A
700
800
850
950
1150
1250
1330
1530
1650
1850
2050
2300
N/A
N/A
N/A
N/A
N/A
N/A
N/A
745
820
900
1000
1200
1300
1400
1600
1750
1950
2150
2450
1.40
1.40
1.40
1.40
1.40
1.40
1.40
1.60
1.60
1.60
1.60
1.60
1.60
1.60
1.60
1.60
1.60
2.00
2.00
1.24
1.24
1.24
1.24
1.24
1.24
1.40
1.40
1.40
1.40
1.40
1.40
1.40
1.40
1.40
1.56
1.56
1.56
1.56
Approx. Net Wt
of cable ( Kg/KM)
with
with
13
14
15
16
17
17
20
21
22
23
24
27
28
29
30
32
34
36
38
14
14
15
16
17
17
21
22
23
24
25
28
29
30
32
35
36
38
40
400
450
500
520
580
650
800
940
1000
1100
1200
1450
1500
1650
1850
2000
2200
2700
3000
420
450
500
550
600
680
840
970
1050
1100
1250
1500
1550
1700
1950
2100
2300
2800
3100
INSULATION MATERIAL : PVC Type A of IS :5831/ OPTION : HR PVC ( Type -C of IS -5831) Nominal insulation thickness - 0.80mm
Cores identification : Up to 5Cores by colour coding & more than 5 cores 5cores : By colour coding / Nos. printing on cores as per IS :1554pt-1
3
ARMOURING : Single layer of Galvanized steel Round wires / Flat Strips as applicable
OUTER SHEATH : PVC TYPE ST-1 OF IS : 5831 OPTIONS : PVC TYPE ST-2 OF IS : 5831/ FR TYPE/ FRLS TYPE
COLOUR OF OUTER SHEATH : BLACK . OPTIONS : any other colour as per requirement
~ Tabulated approx. net wt. of cables are only guidelines for transportation, loading &unloading purpose .
~ Please ref page no 43 for normal delivery lengths & packing details.
Electrical Parameters
Max. Cond. D.C.
Resistance at
20oC in Ohm/km
2
3
4
5
6
7
10
12
14
16
19
24
27
30
37
40
44
52
61
12.10
12.10
12.10
12.10
12.10
12.10
12.10
12.10
12.10
12.10
12.10
12.10
12.10
12.10
12.10
12.10
12.10
12.10
12.10
14.52
14.52
14.52
14.52
14.52
14.52
14.52
14.52
14.52
14.52
14.52
14.52
14.52
14.52
14.52
14.52
14.52
14.52
14.52
15.2
15.2
15.2
15.2
15.2
15.2
15.2
15.2
15.2
15.2
15.2
15.2
15.2
15.2
15.2
15.2
15.2
15.2
15.2
Reactance
of cable
Appro
Capecitance
at 50HZ
of cable
Duct
Air
With H. R. insulation
Ground
Duct
Air
in ohms/km in microF/KM
0.112
0.112
0.112
0.112
0.112
0.112
0.112
0.112
0.112
0.112
0.112
0.112
0.112
0.112
0.112
0.112
0.112
0.112
0.112
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20
Insulation
23
21
21
21
15
14
13
12
11
11
10
9
9
9
8
8
7
6
6
20
17
17
17
13
13
11
10
10
9
9
8
8
7
7
7
7
6
6
20
17
17
17
13
13
11
10
10
9
9
8
8
7
7
7
7
6
6
26
24
24
24
17
16
15
14
13
13
11
10
10
10
9
9
8
7
7
24
21
21
21
16
15
13
12
12
11
11
10
10
8
8
8
7
7
7
24
21
21
21
16
15
13
12
12
11
11
10
10
8
8
8
7
7
7
0.173
0.173
0.173
0.173
0.173
0.173
0.173
0.173
0.173
0.173
0.173
0.173
0.173
0.173
0.173
0.173
0.173
0.173
0.173
Insulation
0.156
0.156
0.156
0.156
0.156
0.156
0.156
0.156
0.156
0.156
0.156
0.156
0.156
0.156
0.156
0.156
0.156
0.156
0.156
Note : Normal current ratings are given in standard conditions (as given in page no -40,41), if site conditions are different, current rating should be multiplied by
rating factor as given in page no. 42
16
Table -12
Physical Parameters
No
of
Cores
Minimum
Thick. Nom thick.
of inner of outer
Sheath
Sheath
UNARMOURED ( YY)
Approx.
Approx. Net Wt
Overall
of cable ( Kg/KM)
Diameter (mm)
Armour outer
wire ( mm)
(mm)
Approx. Net Wt
of cable ( Kg/KM)
Diameter (mm)
( mm)
mm
Solid cond
Std. Cond.
Solid cond
Std. Cond.
strip( mm)
(mm)
Solid cond
Std. Cond.
0.30
1.8
13
13
220
240
N/A
N/A
N/A
N/A
N/A
N/A
1.40
1.24
14
15
480
500
3
4
5
6
7
10
12
14
16
19
24
27
30
37
40
44
52
61
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.40
0.40
0.40
0.40
0.40
1.8
1.8
1.8
1.8
1.8
1.8
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.2
2.2
2.2
2.2
2.2
14
15
16
17
17
20
21
22
24
25
28
29
30
33
34
36
38
40
14
15
16
17
17
21
22
24
25
26
30
31
32
34
36
38
40
43
260
310
340
390
424
570
670
750
840
950
1200
1300
1400
1700
1850
2000
2350
2700
270
320
350
420
440
600
700
800
900
1000
1260
1350
1500
1800
1900
2100
2450
2800
N/A
N/A
N/A
N/A
N/A
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
N/A
N/A
N/A
N/A
N/A
1.40
1.40
1.40
1.40
1.40
1.40
1.40
1.56
1.56
1.56
1.56
1.56
1.56
N/A
N/A
N/A
N/A
N/A
21
22
23
24
25
29
30
31
34
35
37
39
41
N/A
N/A
N/A
N/A
N/A
22
23
24
25
26
30
31
32
35
36
37
41
43
N/A
N/A
N/A
N/A
N/A
850
950
1050
1120
1250
1550
1650
1800
2100
2300
2500
2850
3250
N/A
N/A
N/A
N/A
N/A
900
1000
1035
1150
1330
1630
1750
1920
2225
2400
2600
2950
3350
1.40
1.40
1.40
1.40
1.40
1.60
1.60
1.60
1.60
1.60
1.60
1.60
1.60
2.00
2.00
2.00
2.00
2.00
1.24
1.24
1.24
1.24
1.24
1.40
1.40
1.40
1.40
1.40
1.56
1.56
1.56
1.56
1.56
1.56
1.72
1.72
15
16
17
19
19
23
24
25
26
27
31
32
33
36
37
40
42
44
16
17
18
20
20
24
25
26
27
28
32
33
34
37
39
41
43
46
530
600
640
730
760
1100
1180
1300
1400
1550
1900
2050
2200
2800
2950
3200
3600
4000
550
620
680
750
790
1150
1250
1350
1450
1620
2000
2100
2250
2900
3100
3350
3700
4200
CONDUCTOR : MATERIAL : Annealed bare copper / option :Tinned Construction : SOLID / STRANDED
INSULATION MATERIAL : PVC Type A of IS :5831/ OPTION : HR PVC (Type -C of IS -5831) Nominal insulation thickness 0.90mm Cores identification : Up to 5Cores by colour coding & more than 5 cores 5cores : By colour coding / Nos. printing on
cores as per IS :1554pt-1
INNER SHEATH : Extruded PVC as per IS :1554PT-1
ARMOURING : Single layer of Galvanized steel Round wires / Flat Strips as applicable
OUTER SHEATH : PVC TYPE ST-1 OF IS : 5831 OPTIONS : PVC TYPE ST-2 OF IS : 5831/ FR TYPE/ FRLS TYPE
COLOUR OF OUTER SHEATH : BLACK . OPTIONS : any other colour as per requirement.
~ Tabulated approx. net wt. of cables are only guidelines for transportation, loading &unloading purpose .
~ Please ref page no 43 for normal delivery lengths & packing details.
Electrical Parameters
Max. Cond. D.C.
Resistance at
20oC in Ohm/km
2
3
4
5
6
7
10
12
14
16
19
24
27
30
37
40
44
52
61
7.41
7.41
7.41
7.41
7.41
7.41
7.41
7.41
7.41
7.41
7.41
7.41
7.41
7.41
7.41
7.41
7.41
7.41
7.41
8.89
8.89
8.89
8.89
8.89
8.89
8.89
8.89
8.89
8.89
8.89
8.89
8.89
8.89
8.89
8.89
8.89
8.89
8.89
9.34
9.34
9.34
9.34
9.34
9.34
9.34
9.34
9.34
9.34
9.34
9.34
9.34
9.34
9.34
9.34
9.34
9.34
9.34
Reactance
of cable
at 50HZ
in ohms/km
0.107
0.107
0.107
0.107
0.107
0.107
0.107
0.107
0.107
0.107
0.107
0.107
0.107
0.107
0.107
0.107
0.107
0.107
0.107
Appro
Normal* Current Rating in Amps
Capecitance
With general insulation
With H. R. insulation
of cable
Ground Duct
Air
Ground Duct
Air
in microF/KM
0.22
0.22
0.22
0.22
0.22
0.22
0.22
0.22
0.22
0.22
0.22
0.22
0.22
0.22
0.22
0.22
0.22
0.22
0.22
32
27
27
27
21
20
18
17
16
15
14
13
12
12
11
11
10
9
8
27
24
24
24
18
17
15
14
13
13
12
11
10
10
9
9
9
8
8
27
24
24
24
18
17
15
14
13
13
12
11
10
10
9
9
9
8
8
38
30
30
30
24
22
20
19
18
17
16
14
13
13
12
12
11
10
9
32
28
28
28
21
20
16
16
15
15
14
13
12
12
10
10
10
10
9
32
28
28
28
21
20
16
16
15
15
14
13
12
12
10
10
10
10
9
General
Insulation
Heat
Insulation
0.288
0.288
0.288
0.288
0.288
0.288
0.288
0.288
0.288
0.288
0.288
0.288
0.288
0.288
0.288
0.288
0.288
0.288
0.288
0.260
0.260
0.260
0.260
0.260
0.260
0.260
0.260
0.260
0.260
0.260
0.260
0.260
0.260
0.260
0.260
0.260
0.260
0.260
Note : Normal current ratings are given in standard conditions (as given in page no -40,41), if site conditions are different, current rating should be multiplied by
rating factor as given in page no. 42
17
Table -13
Physical Parameters
SIZE
cross-sectional
area ( Sq MM)
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
Minimum
No of Strand in
Conductor
Al
Cu
1
1
6
6
6
6
12
15
15
15
30
30
30
53
53
53
53
53
Nominal
Thickness of
Insulation)
(mm)
Nominal
Thickness of
outer sheath
(mm)
Approx.
Overal
Diameter
(mm)
With Al Conductor
A2XY
0.7
0.7
0.7
0.7
0.9
0.9
1.0
1.1
1.1
1.2
1.4
1.6
1.7
1.8
2.0
2.2
2.4
2.6
2.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
1.8
2.0
2.0
2.0
2.0
2.2
2.2
2.2
2.4
2.6
8
9
10
11
12
13
15
16
18
20
22
24
27
30
33
36
40
47
51
70
80
100
130
180
230
300
370
460
550
620
820
1000
1200
1550
1900
2400
3000
3750
1/7
1/7
6
6
6
6
6
12
15
18
18
30
34
34
53
53
53
53
53
95
120
160
230
335
450
610
800
1050
1300
1550
1950
2500
3050
4000
5000
6300
7950
9950
~Copper. Cond :- 4 & 6 sq. mm-solid/ stranded non compacted circular, 10 sq. mm & above : Stranded compacted circular
3
- Tabulated approx. net wt. of cables are only guidelines for transportation, loading & unloading purpose..
- Please ref page no 43 for normal delivery lengths & packing details.
Electrical Parameters
SIZE
cross-sectional
area (Sq MM)
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
Max. Cond. D.C. Approx. Cond. A.C. App. Reactance App. Capecitance
Normal* Current Rating in Amps
Resistance at
Resistance at
at 50HZ
of cable
With Aluminium cond.
With Copper cond.
20oC in Ohm/km 90oC in Ohm/km
in ohms/km
in microF/KM
Ground Duct
Air
Ground Duct
Air
Al
Cu
Al
Cu
4.61
3.08
1.91
1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778
0.0605
0.0469
0.0367
0.0291
4.61
3.08
1.83
1.15
0.727
0.524
0.387
0.268
0.193
0.153
0.1240
0.0991
0.0754
0.0601
0.0470
0.0366
0.0283
0.0221
0.0176
5.90
3.94
2.44
1.54
1.11
0.820
0.567
0.411
0.325
0.265
0.211
0.162
0.130
0.1023
0.0808
0.0648
0.0530
0.0444
5.90
3.94
2.34
1.47
0.931
0.671
0.495
0.343
0.248
0.197
0.159
0.127
0.0976
0.0778
0.0618
0.0489
0.0391
0.0319
0.0268
0.136
0.128
0.118
0.108
0.102
0.097
0.092
0.088
0.085
0.082
0.082
0.082
0.079
0.078
0.077
0.076
0.075
0.075
0.068
0.29
0.34
0.42
0.50
0.52
0.60
0.63
0.68
0.79
0.79
0.79
0.79
0.84
0.86
0.88
0.90
0.94
0.97
1.01
48
62
81
99
117
138
168
204
230
265
295
340
390
450
500
555
625
690
45
62
80
90
110
125
155
185
210
230
260
300
335
380
430
485
530
570
45
61
83
115
135
170
210
255
300
342
385
450
519
605
700
809
935
1065
48
60
80
104
130
155
185
225
265
300
335
380
435
490
550
610
680
740
780
47
59
78
102
115
140
165
200
235
265
300
335
385
430
480
530
590
630
660
45
57
77
106
145
175
215
270
330
380
430
495
590
670
780
900
1020
1140
1250
in K. Amps
Al
Cu
0.376
0.564
0.940
1.504
2.350
3.290
4.700
6.580
8.930
11.28
14.10
17.39
22.56
28.20
37.60
47.00
59.22
75.20
94.00
0.572
0.858
1.430
2.288
3.575
5.005
7.150
10.01
13.59
17.16
21.45
26.46
34.32
42.90
57.20
71.50
90.09
114.40
143.00
Note : Normal current ratings are given in standard conditions (as given in page no -40,41), if site conditions are different, current rating should be multiplied by
rating factor as given in page no. 42
18
Table -14
Physical Parameters
SIZE
Cross-sectional
area
Minimum
No of
Strands in
Nominal
Thickness of
Insulation)
Minimum
Thickness of
inner sheath
Nominal
Thickness of
OUTER sheath
Diameter
With Al Cond
With Cu Cond.
(mm)
(mm)
(mm)
(mm)
A2XY
2XY
0.7
0.7
0.7
0.7
0.9
0.9
1.0
1.1
1.1
1.2
1.4
1.6
1.7
1.8
2.0
2.2
2.4
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.40
0.40
0.40
0.50
0.50
0.60
0.60
0.70
0.70
1.80
1.80
1.80
1.80
2.00
2.00
2.00
2.00
2.20
2.20
2.20
2.40
2.60
2.80
3.00
3.40
3.60
13
14
17
17
19
20
22
25
28
31
33
37
41
44
48
54
62
200
330
350
310
400
480
590
760
1000
1200
1400
1750
2000
2700
3350
4200
5300
Conductor
( sqmm)
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
Al
Cu
1
1
6
6
6
6
12
15
15
15
30
30
30
53
53
53
1/7
1/7
6
6
6
6
6
12
15
18
18
30
34
34
53
53
53
Approx. Net Wt
of cable (Kg/KM)
Approx.
overall
250
400
470
500
700
900
1200
1630
2200
2700
3300
4000
5000
6400
8300
10400
13000
2
3
4
~ Tabulated approx. net wt. of cables are only guidelines for transportation, loading &unloading purpose.
~ Please ref page no 43 for normal delivery lengths & packing details.
Electrical Parameters
SIZE
cross-sectional
area (Sq MM)
in K. Amps
Al
Cu
4.61
5.90
0.098
0.11
34
28
30
44
37
39
0.376
0.572
4.61
3.08
5.90
3.94
0.090
0.13
43
37
40
55
47
50
0.564
0.858
10
3.08
1.83
3.94
2.34
0.084
0.16
57
48
53
74
61
67
0.940
1.430
16
1.91
1.15
2.44
1.47
0.080
0.18
78
61
70
94
78
85
1.50
2.29
25
1.20
0.727
1.54
0.931
0.080
0.20
95
80
99
120
100
125
2.35
3.58
35
0.868
0.524
1.11
0.671
0.080
0.23
116
94
117
145
120
155
3.29
5.01
50
0.641
0.387
0.820
0.495
0.078
0.24
140
110
140
170
145
190
4.70
7.15
70
0.443
0.268
0.567
0.343
0.077
0.26
170
140
176
210
175
235
6.58
10.01
95
0.320
0.193
0.411
0.248
0.084
0.29
200
165
221
250
210
290
8.93
13.59
120
0.253
0.153
0.325
0.197
0.072
0.29
225
185
258
285
240
330
11.28
17.16
150
0.206
0.1240 0.265
0.159
0.072
0.29
255
210
294
315
270
375
14.10
21.45
185
0.164
0.0991 0.211
0.127
0.072
0.29
285
235
339
355
300
435
17.39
26.46
240
0.125
0.0754 0.162
0.098
0.072
0.31
325
270
402
410
350
510
22.56
34.32
300
0.100
0.0601 0.130
0.078
0.071
0.33
370
305
461
460
390
590
28.20
42.90
400
0.070
0.33
435
350
542
520
440
670
37.60
57.20
500
0.070
0.34
481
405
624
580
480
750
47.00
71.50
630
0.069
0.36
537
470
723
680
575
875
59.22
90.09
Note : Normal current ratings are given in standard conditions (as given in page no -40,41), if site conditions are different, current rating should be multiplied by
rating factor as given in page no. 42
19
Table -15
Physical Parameters
SIZE Cross-sectional
Minimum No of
Strands in
Nominal
thickness of
Minimum
thickness of
Nominal thick.
of outer
Approx.
Overall
area
( sqmm)
Conductor
Al
Cu
Insulation)
(mm)
inner Sh.
(mm)
Sheath
(mm)
Diameter
(mm)
0.7
0.7
0.7
0.7
0.9
0.9
1.0
1.1
1.1
1.2
1.4
1.6
1.7
1.8
2.0
2.2
2.4
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.40
0.40
0.40
0.50
0.50
0.60
0.60
0.70
0.70
0.70
1.80
1.80
1.80
1.80
2.00
2.00
2.00
2.20
2.20
2.20
2.40
2.60
2.80
3.00
3.20
3.60
3.80
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
1
1
6
6
6
6
12
15
15
15
30
30
30
53
53
53
1/7
1/7
6
6
6
6
6
12
15
18
18
30
34
34
53
53
53
14
16
18
18
21
22
25
30
32
35
39
43
49
53
59
66
73
Approx. Net Wt
of cable ( Kg/KM)
With Al cond
A2XY
225
330
400
400
530
640
800
1100
1350
1650
2050
2500
3150
3850
4850
6100
7650
With Cu Cond.
2XY
300
440
580
700
1000
1300
1700
2400
3100
3800
4800
5950
7600
9400
12000
15000
19000
2
3
4
COLOUR OF OUTER SHEATH : BLACK . OPTIONS : any other colour as per requirement.
~ Tabulated approx. net wt. of cables are only guidelines for transportation, loading &unloading purpose.
~ Please ref page no 43 for normal delivery lengths & packing details.
Electrical Parameters
SIZE
cross-sectional
area (Sq MM)
App.
App. Capecitance
Normal* Current Rating in Amps
Reactance of
of cable
With Aluminium cond.
With Copper cond.
cable at 50HZ
in microF/KM
Ground Duct
Air
Ground Duct
Air
in ohms/km
in K. Amps
Al
Cu
4.61
5.90
0.098
0.11
34
28
30
44
37
39
0.376 0.572
6
4.61
3.08
5.90
3.94
0.090
0.13
43
37
40
55
47
50
0.564 0.858
10
3.08
1.83
3.94
2.34
0.084
0.16
57
48
53
74
61
67
0.940 1.430
16
1.91
1.15
2.44
1.47
0.080
0.18
78
61
70
94
78
85
1.50
2.29
25
1.20
0.727 1.54
0.931
0.080
0.20
95
80
99
120
100 125
2.35
3.58
35
0.868 0.524 1.11
0.671
0.080
0.23
116
94
117
145
120 155
3.29
5.01
50
0.641 0.387 0.820
0.495
0.078
0.24
140
110
140
170
145 190
4.70
7.15
70
0.443 0.268 0.567
0.343
0.077
0.26
170
140
176
210
175 235
6.58 10.01
95
0.320 0.193 0.411
0.248
0.074
0.29
200
165
221
250
210 290
8.93 13.59
120
0.253 0.153 0.325
0.197
0.072
0.29
225
185
258
285
240 330
11.28 17.16
150
0.206 0.1240 0.265
0.159
0.072
0.29
255
210
294
315
270 375
14.10 21.45
185
0.164 0.0991 0.211
0.127
0.072
0.29
285
235
339
355
300 435
17.39 26.46
240
0.125 0.0754 0.162
0.098
0.072
0.31
325
270
402
410
350 510
22.56 34.32
300
0.100 0.0601 0.130
0.078
0.071
0.33
370
305
461
460
390 590
28.20 42.90
400
0.0778 0.0470 0.1023 0.0618
0.070
0.33
435
350
542
520
440 670
37.60 57.20
500
0.0605 0.0366 0.0808 0.0489
0.070
0.34
481
405
624
580
480 750
47.00 71.50
630
0.0469 0.0283 0.0648 0.0391
0.069
0.36
537
470
723
680
575 875
59.22 90.09
Note : Normal current ratings are given in standard conditions (as given in page no - 40,41), if site conditions are different, current rating should be multiplied by
rating factor as given in page no. 42
20
Table -16
Physical Parameters
SIZE
Cross-sectional
area
Minimum No of
strands
in conductor
Phase / Neutral
Nominal
Thickness of
Insulation)
Phase / Neutral
Minimum
Thickness of
inner sheath
Nominal
thickness of
OUTER
Sheath
Approx.
overall
Diameter
Approx. Net Wt
of cable ( Kg/KM)
With Al cond
With Cu Cond.
( sqmm)
Al
Cu
(mm)
(mm)
(mm)
(mm)
A2XY
2XY
3X25+16
6/6
6/6
0.90/0.70
0.30
2.00
22
600
1150
3X35+16
6/6
6/6
0.90/0.70
0.30
2.00
24
700
1450
3X50+25
6/6
6/6
1.00/0.90
0.30
2.00
27
900
2000
3X70+35
12/6
12/6
1.10/0.90
0.40
2.20
31
1200
2700
3X95+50
15/6
15/6
1.10/1.00
0.40
2.20
34
1500
3600
3X120+70
15/12
18/12
1.20/1.10
0.40
2.20
38
1900
4500
3X150+70
15/12
18/12
1.40/1.10
0.50
2.40
43
2300
5500
3X185+95
30/15
30/15
1.60/1.10
0.50
2.60
46
2800
6800
3X240+120 30/15
34/18
1.70/1.20
0.60
2.80
52
3600
8700
3X300+150 30/15
34/18
1.80/1.40
0.60
3.00
57
4400
10800
3X400+185 53/30
53/30
2.00/1.60
0.70
3.40
65
5600
14000
3X500+240 53/30
53/34
2.20/1.70
0.70
3.60
73
7000
17500
3X630+300 53/30
53/34
2.40/1.80
0.70
4.00
82
8900
22000
2
3
4
INSULATION : Crosslinked Polyethylene (XLPE) (Phase - Red, Yellow, Blue & neutral - Black colour)
INNER SHEATH : PVC as per IS :7098PT-1
OUTER SHEATH : PVC TYPE ST-2 OF IS : 5831 OPTIONS : FR TYPE FRLS TYPE
COLOUR OF OUTER SHEATH : BLACK . OPTIONS : any other colour as per requirement.
~ Tabulated approx. net wt. of cables are only guidelines for transportation, loading & unloading purpose.
~ Please ref page no 43 for normal delivery lengths & packing details.
Electrical Parameters
SIZE
cross-sectional
area (Sq MM)
3X25+16
Max. Cond. D.C. Approx. Cond. A.C. App. Reactance App. Capecitance
Resistance at
Resistance at
of cable at 50HZ
of cable
o
20 C in Ohm/km
Al
Cu
1.20
0.727
90 C in Ohm/km
Al
Cu
1.54
0.931
in ohms/km
in microF/KM
Ground
0.080
0.20
95
Duct
Air
Ground
Duct
Air
80
99
120
100
125
in K. Amps
Al
Cu
2.35
3.58
3X35+16
0.868
0.524
1.11
0.671
0.080
0.23
116
94
117
145
120
155
3.29
5.01
3X50+25
0.641
0.387
0.820
0.495
0.078
0.24
140
110
140
170
145
190
4.70
7.15
3X70+35
0.443
0.268
0.567
0.343
0.077
0.26
170
140
176
210
175
235
6.58
10.01
3X95+50
0.320
0.193
0.411
0.248
0.074
0.29
200
165
221
250
210
290
8.93
13.59
3X120+70
0.253
0.153
0.325
0.197
0.072
0.29
225
185
258
285
240
330
11.28
17.16
3X150+70
0.206
0.1240 0.265
0.159
0.072
0.29
255
210
294
315
270
375
14.10
21.45
3X185+95
0.164
0.0991 0.211
0.127
0.072
0.29
285
235
339
355
300
435
17.39
26.46
3X240+120
0.125
0.0754 0.162
0.098
0.072
0.31
325
270
402
410
350
510
22.56
34.32
3X300+150
0.100
0.0601 0.130
0.078
0.071
0.33
370
305
461
460
390
590
28.20
42.90
3X400+185
0.070
0.33
435
350
542
520
440
670
37.60
57.20
3X500+240
0.070
0.34
481
405
624
580
480
750
47.00
71.50
3X630+300
0.069
0.36
537
470
723
680
575
875
59.22
90.09
Note : Normal current ratings are given in standard conditions (as given in page no - 40,41), if site conditions are different, current rating should be multiplied by
rating factor as given in page no. 42
21
Table -17
Physical Parameters
SIZE
Minimum
Nominal
Minimum
Minimum
Cross-
No of
Thickness
Thickness
Thickness of
Approx.
of
outer sheath
over all
of cable ( Kg/KM)
-sectional
area
Strands in of
Conductor
Approx. Net Wt
(Insulation)
inner sheath
Diameter
With Al cond
( sqmm)
Al
Cu
(mm)
(mm)
(mm)
(mm)
A2XY
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
1
1
6
6
6
6
12
15
15
15
30
30
30
53
53
53
1/7
1/7
6
6
6
6
6
12
15
18
18
30
34
34
53
53
53
0.7
0.7
0.7
0.7
0.9
0.9
1.0
1.1
1.1
1.2
1.4
1.6
1.7
1.8
2.0
2.2
2.4
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.40
0.40
0.50
0.50
0.50
0.60
0.70
0.70
0.70
0.70
1.80
1.80
1.80
1.80
2.00
2.00
2.00
2.20
2.20
2.40
2.60
2.80
3.00
3.20
3.60
3.80
4.00
17
18
20
20
24
26
29
34
37
41
45
50
56
63
70
79
88
250
350
400
450
660
800
1000
1400
1700
2150
2650
3250
4100
5050
6400
8000
10000
With Cu Cond.
2XY
350
500
650
850
1300
1700
2200
3100
4000
5150
6350
7850
10000
12050
16000
20000
26000
INSULATION : Crosslinked Polyethylene (XLPE) (Red, Yellow, Blue & Black colour)
INNER SHEATH : PVC as per IS :7098PT-1
OUTER SHEATH : PVC TYPE ST-2 OF IS : 5831 OPTIONS : FR TYPE/ FRLS TYPE
COLOUR OF OUTER SHEATH : BLACK . OPTIONS : any other colour as per requirement.
~Copper . Cond :- 4 & 6sqmm -solid/ stranded non compacted circular , 10sqmm : Stranded compacted circular,16sqmm & above : Stranded compacted shaped
3
4
~ Tabulated approx. net wt. of cables are only guidelines for transportation, loading & unloading purpose.
~ Please ref page no 43 for normal delivery lengths & packing details.
Electrical Parameters
SIZE
cross-sectional
area (Sq MM)
Max. Cond. D.C. Approx. Cond. A.C. App. Reactance App. Capecitance
Normal* Current Rating in Amps
Resistance at
Resistance at
of cable at
of cable
With Aluminium cond.
With Copper cond.
20oC in Ohm/km 90oC in Ohm/km
50HZ
in microF/KM
Ground Duct
Air
Ground Duct
Air
Al
Cu
Al
Cu
in ohms/km
in K. Amps
Al
Cu
4.61
5.90
0.098
0.11
34
28
30
44
37
39
0.376
4.61
3.08
5.90
3.94
0.090
0.13
43
37
40
55
47
50
0.564
0.572
0.858
10
3.08
1.83
3.94
2.34
0.084
0.16
57
48
53
74
61
67
0.940
1.430
16
1.91
1.15
2.44
1.47
0.080
0.18
78
61
70
94
78
85
1.50
2.29
25
1.20
0.727
1.54
0.931
0.080
0.20
95
80
99
120
100
125
2.35
3.58
35
0.868
0.524
1.11
0.671
0.080
0.23
116
94
117
145
120
155
3.29
5.01
50
0.641
0.387
0.820
0.495
0.078
0.24
140
110
140
170
145
190
4.70
7.15
70
0.443
0.268
0.567
0.343
0.077
0.26
170
140
176
210
175
235
6.58
10.01
95
0.320
0.193
0.411
0.248
0.074
0.29
200
165
221
250
210
290
8.93
13.59
120
0.253
0.153
0.325
0.197
0.072
0.29
225
185
258
285
240
330
11.28
17.16
150
0.206
0.1240 0.265
0.159
0.072
0.29
255
210
294
315
270
375
14.10
21.45
185
0.164
0.0991 0.211
0.127
0.072
0.29
285
235
339
355
300
435
17.39
26.46
240
0.125
0.0754 0.162
0.098
0.072
0.31
325
270
402
410
350
510
22.56
34.32
300
0.100
0.0601 0.130
0.078
400
0.071
0.33
370
305
461
460
390
590
28.20
42.90
0.070
0.33
435
350
542
520
440
670
37.60
57.20
500
0.070
0.34
481
405
624
580
480
750
47.00
71.50
630
0.069
0.36
537
470
723
680
575
875
59.22
90.09
Note : Normal current ratings are given in standard conditions (as given in page no - 40,41), if site conditions are different, current rating should be multiplied by
rating factor as given in page no. 42
22
Table -18
Physical Parameters
SIZE
Cross-sectional
area
( sqmm)
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
Minimum
No of
Strands in
Conductor
Al
Cu
1
1
6
6
6
6
12
15
15
15
30
30
30
53
53
53
53
53
Nominal
Thickness of
Insulation)
(mm)
1/7
1/7
6
6
6
6
6
12
15
18
18
30
34
34
53
53
53
53
53
1.0
1.0
1.0
1.0
1.2
1.2
1.3
1.4
1.4
1.5
1.7
1.9
2.0
2.1
2.4
2.6
2.8
3.1
3.3
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
1.40
1.40
1.40
1.40
1.40
1.56
1.56
1.56
1.72
1.72
1.88
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
21
23
24
26
30
32
36
39
44
48
54
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
600
700
800
950
1200
1400
1750
2150
2700
3350
4100
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
1195
1450
1730
2100
2690
3270
4230
5250
6610
8320
10300
1.40
1.40
1.40
1.40
1.40
1.40
1.40
1.40
1.60
1.60
1.60
1.60
1.60
1.60
2.00
2.00
2.00
2.00
2.50
1.24
1.24
1.24
1.24
1.24
1.24
1.24
1.24
1.40
1.40
1.40
1.40
1.40
1.56
1.56
1.56
1.72
1.88
2.04
10
11
12
13
14
15
17
19
22
24
25
28
30
33
38
41
46
51
56
90
130
160
200
300
350
420
520
650
750
850
1000
1250
1500
1900
2350
2900
3600
4600
130
170
222
300
455
567
730
954
1235
1494
1780
2147
2738
3360
4380
5450
6806
8560
10800
~ Tabulated approx. net wt. of cables are only guidelines for transportation, loading &unloading purpose ..
~ Please ref page no 43 for normal delivery lengths & packing details.
Electrical Parameters
SIZE
cross-sectional
area (Sq MM)
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
Max. Cond. D.C. Approx. Cond. A.C. App. Reactance App. Capecitance
Normal* Current Rating in Amps
Resistance at
Resistance at
of cable at 50HZ
of cable
With Aluminium cond.
With Copper cond.
20oC in Ohm/km 90oC in Ohm/km
in ohms/km
in microF/KM
Ground Duct
Air
Ground Duct
Air
Al
Cu
Al
Cu
4.61
3.08
1.91
1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778
0.0605
0.0469
0.0367
0.0291
4.61
3.08
1.83
1.15
0.727
0.524
0.387
0.268
0.193
0.153
0.1240
0.0991
0.0754
0.0601
0.0470
0.0366
0.0283
0.0221
0.0176
5.90
3.94
2.44
1.54
1.11
0.820
0.567
0.411
0.325
0.265
0.211
0.162
0.130
0.1023
0.0808
0.0648
0.0530
0.0444
5.90
3.94
2.34
1.47
0.931
0.671
0.495
0.343
0.248
0.197
0.159
0.127
0.0976
0.0778
0.0618
0.0489
0.0391
0.0319
0.0268
0.152
0.144
0.133
0.122
0.116
0.110
0.103
0.099
0.097
0.093
0.091
0.090
0.086
0.085
0.085
0.083
0.082
0.081
0.081
0.22
0.26
0.31
0.40
0.40
0.47
0.50
0.55
0.64
0.67
0.67
0.67
0.72
0.75
0.75
0.77
0.81
0.88
0.88
45
59
76
99
117
138
168
204
230
265
295
340
390
450
500
555
625
690
45
62
80
90
110
125
155
185
210
230
260
300
335
380
430
485
530
570
40
53
73
115
140
170
210
255
300
342
385
450
519
605
700
809
935
1065
48
60
80
104
130
155
185
225
265
300
335
380
435
490
550
610
680
740
780
47
59
78
102
115
140
165
200
235
265
300
335
385
430
480
530
590
630
660
45
57
77
106
145
175
215
270
330
380
430
495
590
670
780
900
1020
1140
1250
in K. Amps
Al
Cu
0.376
0.572
0.56
0.858
0.94
1.43
1.50
2.29
2.35
3.58
3.29
5.01
4.70
7.15
6.58
10.01
8.93
13.59
11.28
17.16
14.10
21.45
17.39
26.46
22.56
34.32
28.20
42.90
37.60
57.20
47.00
71.50
59.22
90.09
75.20 114.40
94.00 143.00
Note : Normal current ratings are given in standard conditions (as given in page no - 40,41), if site conditions are different, current rating should be multiplied by
rating factor as given in page no. 42
23
Table -19
Physical Parameters
SIZE
Cross-sectional
area
Minimum
No of
Strands in
Conductor
Nominal Minimum
ARMOURING WITH FLAT STRIP ( A2XFY/ 2XFY)
ARMOURING WITH ROUND WIRES ( A2XWY/ 2XWY)
Thickness Thickness Nominal
Minimum
Approx.
Approx. Net Wt
Nominal
Minimum
Approx.
Approx. Net Wt
of
Thickness Thickness of
Overall
of cable (Kg/KM)
Diameter Thickness of Overall
of cable ( Kg/KM)
of
Insulation inner Sh. of armour outer sheath Diameter With Al cond With Cu Cond. of wire
outer sheath Diameter With Al cond With Cu Cond.
(mm)
(mm)
(mm)
(mm)
A2XFY
2XFY
(mm)
(mm)
(mm)
A2XWY
2XWY
(mm)
(sqmm)
Al
Cu
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
1
1
6
6
6
6
12
15
15
15
30
30
30
53
53
53
1/7
1/7
6
6
6
6
6
12
15
18
18
30
34
34
53
53
53
0.7
0.7
0.7
0.7
0.9
0.9
1.0
1.1
1.1
1.2
1.4
1.6
1.7
1.8
2.0
2.2
2.4
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.40
0.40
0.40
0.50
0.50
0.60
0.60
0.70
0.70
N/A
N/A
N/A
N/A
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
N/A
N/A
N/A
N/A
1.40
1.40
1.40
1.56
1.56
1.56
1.72
1.72
1.88
2.04
2.36
2.52
2.68
N/A
N/A
N/A
N/A
20
21
23
26
29
31
34
37
42
45
50
55
63
N/A
N/A
N/A
N/A
650
750
900
1100
1350
1600
1900
2250
2800
3300
4100
5000
6100
N/A
N/A
N/A
N/A
950
1200
1500
1950
2500
3100
3750
4500
5800
7000
9050
11000
14000
1.40
1.40
1.40
1.40
1.60
1.60
1.60
1.60
2.00
2.00
2.00
2.00
2.50
2.50
2.50
3.15
3.15
1.24
1.24
1.24
1.40
1.40
1.40
1.40
1.56
1.56
1.56
1.72
1.88
2.04
2.20
2.36
2.68
2.84
15
16
18
19
21
23
25
28
31
34
37
40
45
49
52
60
66
500
550
650
700
850
950
1100
1400
1850
2150
2450
2900
3850
4450
5350
7100
8500
550
600
770
900
1150
1400
1700
2250
3000
3600
4300
5200
6800
8200
10300
13300
16300
2
3
4
5
~ Tabulated approx. net wt. of cables are only guidelines for transportation, loading &unloading purpose.
~ Please ref page no 43 for normal delivery lengths & packing details.
Electrical Parameters
SIZE
cross-sectional
area (Sq MM)
in K. Amps
Al
Cu
4
--4.61
--5.90
0.098
0.11
34
28
30
44
37
39
0.376
0.572
6
4.61
3.08
5.90
3.94
0.090
0.13
43
37
40
55
47
50
0.564
0.858
10
3.08
1.83
3.94
2.34
0.084
0.16
57
48
53
74
61
67
0.940
1.430
16
1.91
1.15
2.44
1.47
0.080
0.18
78
61
70
94
78
85
1.50
2.29
25
1.20
0.727 1.54
0.931
0.080
0.20
95
80
99
120
100 125
2.35
3.58
35
0.868 0.524 1.11
0.671
0.080
0.23
116
94
117
145
120 155
3.29
5.01
50
0.641 0.387 0.820 0.495
0.078
0.24
140
110 140
170
145 190
4.70
7.15
70
0.443 0.268 0.567 0.343
0.077
0.26
170
140 176
210
175 235
6.58
10.1
95
0.320 0.193 0.411 0.248
0.074
0.29
200
165 221
250
210 290
8.93
13.59
120
0.253 0.153 0.325 0.197
0.072
0.29
225
185 258
285
240 330
11.28
17.16
150
0.206 0.1240 0.265 0.159
0.072
0.29
255
210 294
315
270 375
14.10
21.45
185
0.164 0.0991 0.211 0.127
0.072
0.29
285
235 339
355
300 435
17.39
26.46
240
0.125 0.0754 0.162 0.0976
0.072
0.31
325
270 402
410
350 510
22.56
34.32
300
0.100 0.0601 0.130 0.0778
0.071
0.33
370
305 461
460
390 590
28.20
42.90
400
0.0778 0.0470 0.1023 0.0618
0.070
0.33
435
350 542
520
440 670
37.60
57.20
500
0.0605 0.0366 0.0808 0.0489
0.070
0.34
481
405 624
580
480 750
47.00
71.50
630
0.0469 0.0283 0.0648 0.0391
0.069
0.36
537
470 723
680
575 875
59.22
90.09
Note : Normal current ratings are given in standard conditions (as given in page no - 40,41), if site conditions are different, current rating should be multiplied by
rating factor as given in page no. 42
24
Table -20
Physical Parameters
SIZE
Cross-sectional
area
Minimum
No of
Strands in
Conductor
(sqmm)
Al
Cu
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
1
1
6
6
6
6
12
15
15
15
30
30
30
53
53
53
1/7
1/7
6
6
6
6
6
12
15
18
18
30
34
34
53
53
53
Nominal Minimum
ARMOURING WITH FLAT STRIP ( A2XFY/ 2XFY)
ARMOURING WITH ROUND WIRES ( A2XWY/ 2XWY)
Thickness Thickness Nominal
Minimum
Approx.
Approx. Net Wt
Nominal
Minimum
Approx.
Approx. Net Wt
of
Thickness Thickness of
Overall
of cable (Kg/KM)
Diameter Thickness of Overall
of cable ( Kg/KM)
of
Insulation) inner Sh. of armour outer sheath Diameter With Al cond With Cu Cond. of wire
outer sheath Diameter With Al cond With Cu Cond.
(mm)
strip (mm)
(mm)
(mm)
A2XFY
2XFY
(mm)
(mm)
(mm)
A2XWY
2XWY
(mm)
0.7
0.7
0.7
0.7
0.9
0.9
1.0
1.1
1.1
1.2
1.4
1.6
1.7
1.8
2.0
2.2
2.4
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.40
0.40
0.40
0.50
0.50
0.60
0.60
0.70
0.70
0.70
N/A
N/A
N/A
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
N/A
N/A
N/A
1.24
1.40
1.40
1.40
1.56
1.56
1.56
1.72
1.88
2.04
2.20
2.52
2.68
2.84
N/A
N/A
N/A
19
21
23
26
29
32
35
42
44
49
54
60
66
74
N/A
N/A
N/A
600
800
950
1100
1450
1750
2100
2500
3000
3750
4500
5600
6900
8550
N/A
N/A
N/A
900
1200
1500
2000
2700
3500
4200
5200
6300
8200
10000
13000
16000
20000
1.40
1.40
1.40
1.60
1.60
1.60
1.60
2.00
2.00
2.00
2.00
2.50
2.50
2.50
3.15
3.15
4.00
1.24
1.24
1.24
1.40
1.40
1.40
1.56
1.56
1.56
1.72
1.88
2.04
2.20
2.36
2.68
2.84
3.00
18
19
20
20
23
25
29
32
35
39
43
48
53
58
65
72
81
600
650
750
800
1000
1200
1450
2000
2350
2750
3250
4200
5100
6000
7950
9500
12600
670
770
930
1100
1450
1850
2300
3300
4100
4900
6000
7500
9500
11300
15200
18500
23700
~Copper. Cond :- 4 & 6 sqmm -solid/ stranded non compacted circular, 10 sqmm : Stranded compacted circular,16 sqmm & above : Stranded compacted shaped
3
4
5
~ Tabulated approx. net wt. of cables are only guidelines for transportation, loading & unloading purpose.
~ Please ref page no 43 for normal delivery lengths & packing details.
Electrical Parameters
SIZE
cross-sectional
area (Sq MM)
in K. Amps
Al
Cu
4
--4.61
--5.90
0.098
0.11
34
28
30
44
37
39
0.376
0.572
6
4.61
3.08
5.90
3.94
0.090
0.13
43
37
40
55
47
50
0.564
0.858
10
3.08
1.83
3.94
2.34
0.084
0.16
57
48
53
74
61
67
0.940
1.430
16
1.91
1.15
2.44
1.47
0.080
0.18
78
61
70
94
78
85
1.50
2.29
25
1.20
0.727 1.54
0.931
0.080
0.20
95
80
99
120
100 125
2.35
3.58
35
0.868 0.524 1.11
0.671
0.080
0.23
116
94
117
145
120 155
3.29
5.01
50
0.641 0.387 0.820 0.495
0.078
0.24
140
110
140
170
145 190
4.70
7.15
70
0.443 0.268 0.567 0.343
0.077
0.26
170
140
176
210
175 235
6.58
10.01
95
0.320 0.193 0.411 0.248
0.074
0.29
200
165
221
250
210 290
8.93
13.59
120
0.253 0.153 0.325 0.197
0.072
0.29
225
185
258
285
240 330
11.28
17.16
150
0.206 0.1240 0.265 0.159
0.072
0.29
255
210
294
315
270 375
14.10
21.45
185
0.164 0.0991 0.211 0.127
0.072
0.29
285
235
339
355
300 435
17.39
26.46
240
0.125 0.0754 0.162 0.0976
0.072
0.31
325
270
402
410
350 510
22.56
34.32
300
0.100 0.0601 0.130 0.0778
0.071
0.33
370
305
460
460
390 590
28.20
42.90
400
0.0778 0.0470 0.1023 0.0618
0.070
0.33
435
350
542
520
440 670
37.60
57.20
500
0.0605 0.0366 0.0808 0.0489
0.070
0.34
481
405
624
580
480 750
47.00
71.50
630
0.0469 0.0283 0.0648 0.0391
0.069
0.36
537
470
723
680
575 875
59.22
90.09
Note : Normal current ratings are given in standard conditions (as given in page no - 40,41), if site conditions are different, current rating should be multiplied by
rating factor as given in page no. 42
25
Table -21
Minimum
No of
Strands in
Nominal
Thickness
of
Conductor
Insulation)
Al
Cu
(mm)
Minimum
ARMOURING WITH FLAT STRIP ( A2XFY/ 2XFY)ARMOURING WITH ROUND WIRES ( A2XWY/ 2XWY)
Thickness Nominal
Minimum
Approx.
Approx. Net Wt
Nominal
Minimum
Approx.
Approx. Net Wt
of
Thickness Thickness of Overall
of cable ( Kg/KM) Diameter Thickness of Overall
of cable (Kg/KM)
inner Sh. of Armr. outer sheath Diameter With Al cond With Cu Cond. of wire
outer sheath Diameter With Al cond With Cu Cond.
(mm)
Strip (mm)
(mm)
(mm)
A2XFY
2XFY
(mm)
(mm)
(mm)
A2XWY
2XWY
3X25+16
6/6
6/6
0.90/0.70
0.30
0.80
1.40
23
900
1400
1.60
1.40
25
1100
1700
3X35+16
6/6
6/6
0.90/0.70
0.30
0.80
1.40
25
1000
1800
1.60
1.40
27
1300
2000
3X50+25
6/6
6/6
1.00/0.90
0.30
0.80
1.40
28
1200
2300
1.60
1.56
30
1600
2700
3X70+35
12/6
12/6
1.10/0.90
0.40
0.80
1.56
32
1600
3200
2.00
1.56
35
2200
3700
3X95+50
15/6
15/6
1.10/1.00
0.40
0.80
1.56
35
2000
4100
2.00
1.56
38
2600
4600
3X120+70
15/12 18/12
1.20/1.10
0.40
0.80
1.72
39
2400
5100
2.00
1.72
42
3100
5700
3X150+70
15/12 18/12
1.40/1.10
0.50
0.80
1.72
43
2800
6000
2.00
1.88
46
3600
6800
3X185+95
30/15 30/15
1.60/1.10
0.50
0.80
1.88
47
3400
7400
2.50
2.04
51
4700
8700
1.70/1.20
0.60
0.80
2.04
53
4300
9500
2.50
2.20
56
5700
10500
1.80/1.40
0.60
0.80
2.20
57
5000
11500
2.50
2.36
60
6700
13000
2.00/1.60
0.70
0.80
2.52
66
6400
14500
3.15
2.68
71
9000
17000
2.20/1.70
0.70
0.80
2.68
74
7900
18000
3.15
2.84
79
11000
21500
2.40/1.80
0.70
0.80
3.00
82
9900
23000
4.00
3.00
88
14500
28000
2
3
4
5
INSULATION : Crosslinked Polyethylene (XLPE) (Phase, Red, Yellow, Blue & Neutral - Black Colour
INNER SHEATH : PVC as per IS :7098PT-1
ARMOURING : Single layer of Galvanized steel Round wires / Flat Strips
OUTER SHEATH : PVC TYPE ST-2 OF IS : 5831 OPTIONS : FR TYPE/ FRLS TYPE
COLOUR OF OUTER SHEATH : BLACK . OPTIONS : any other colour as per requirement.
~ Tabulated approx. net wt. of cables are only guidelines for transportation, loading &unloading purpose.
~ Please ref page no 43 for normal delivery lengths & packing details.
Electrical Parameters
SIZE
cross-sectional
area (Sq MM)
Al
in K. Amps
Cu
3X25+16
1.20
0.727
1.54
0.931
0.080
0.20
95
80
99
120
100
125
2.35
3.58
3X35+16
0.868
0.524
1.11
0.671
0.080
0.23
116
94
117
145
120
155
3.29
5.01
3X50+25
0.641
0.387
0.820
0.495
0.078
0.24
140
110
140
170
145
190
4.70
7.15
3X70+35
0.443
0.268
0.567
0.343
0.077
0.26
170
140
176
210
175
235
6.58
10.01
3X95+50
0.320
0.193
0.411
0.248
0.074
0.29
200
165
221
250
210
290
8.93
13.59
3X120+70
0.253
0.153
0.325
0.197
0.072
0.29
225
185
258
285
240
330
11.28
17.16
3X150+70
0.206
0.1240 0.265
0.159
0.072
0.29
255
210
294
315
270
375
14.10
21.45
3X185+95
0.164
0.0991 0.211
0.127
0.072
0.29
285
235
339
355
300
435
17.39
26.46
3X240+120
0.125
0.0754 0.162
0.098
0.072
0.31
325
270
402
410
350
510
22.56
34.32
0.0601 0.130
0.078
3X300+150
0.100
0.071
0.33
370
305
461
460
390
590
28.20
42.90
3X400+185
0.070
0.33
435
350
542
520
440
670
37.60
57.20
3X500+240
0.070
0.34
481
405
624
580
480
750
47.00
71.50
3X630+300
0.069
0.36
537
470
723
680
575
875
59.22
90.09
Note : Normal current ratings are given in standard conditions (as given in page no -40,41), if site conditions are different, current rating should be multiplied by
rating factor as given in page no. 42
26
Table -22
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
Minimum
No of
Strands in
Conductor
Al
Cu
1
1
6
6
6
6
12
15
15
15
30
30
30
53
53
53
Nominal Minimum
ARMOURING WITH FLAT STRIP ( A2XFY/2XFY)
Thickness Thickness Nominal
Minimum
Approx.
Approx. Net Wt
of
Thickness Thickness of
Overall
of cable (Kg/KM)
of
Insulation) inner Sh. of armour outer sheath Diameter With Al cond With Cu Cond.
(mm)
(mm)
(mm)
A2XFY
2XYF
(mm) strip (mm)
1/7
1/7
6
6
6
6
6
12
15
18
18
30
34
34
53
53
53
0.7
0.7
0.7
0.7
0.9
0.9
1.0
1.1
1.1
1.2
1.4
1.6
1.7
1.8
2.0
2.2
2.4
0.30
0.30
0.30
0.30
0.30
0.30
0.30
0.40
0.40
0.50
0.50
0.50
0.60
0.70
0.70
0.70
0.70
N/A
N/A
N/A
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
0.80
N/A
N/A
N/A
1.40
1.40
1.40
1.56
1.56
1.56
1.72
1.88
2.04
2.20
2.36
2.68
2.84
3.00
N/A
N/A
N/A
20
24
27
30
34
37
41
46
51
57
63
71
79
88
N/A
N/A
N/A
700
900
1100
1400
1800
2200
2700
3200
3900
4850
5850
7320
9000
11000
N/A
N/A
N/A
1100
1500
2000
2500
3400
4400
5600
6800
8300
10500
13000
17000
21000
27000
1.40
1.40
1.40
1.60
1.60
1.60
1.60
2.00
2.00
2.00
2.50
2.50
2.50
3.15
3.15
4.00
4.00
1.24
1.24
1.40
1.40
1.40
1.40
1.56
1.56
1.72
1.88
2.04
2.20
2.36
2.52
2.84
3.00
3.00
18
19
21
22
26
28
32
37
40
44
49
54
65
68
76
86
94
550
600
670
925
1200
1450
1750
2400
2900
3500
4500
5200
6400
8300
10000
13500
16000
650
750
950
1300
1770
2200
2850
4000
5150
6300
8000
9700
12000
15400
19500
25000
30500
2
3
4
5
~ Tabulated approx. net wt. of cables are only guidelines for transportation, loading &unloading purpose.
~ Please ref page no 43 for normal delivery lengths & packing details.
Electrical Parameters
SIZE
cross-sectional
area (Sq MM)
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
4.61
3.08
1.91
1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778
0.0605
0.0469
4.61
3.08
1.83
1.15
0.727
0.524
0.387
0.268
0.193
0.153
0.1240
0.0991
0.0754
0.0601
0.0470
0.0366
0.0283
5.90
3.94
2.44
1.54
1.11
0.820
0.567
0.411
0.325
0.265
0.211
0.162
0.130
0.1023
0.0808
0.0648
5.90
3.94
2.34
1.47
0.931
0.671
0.495
0.343
0.248
0.197
0.159
0.127
0.0976
0.0778
0.0618
0.0489
0.0391
0.098
0.090
0.084
0.080
0.080
0.080
0.078
0.077
0.074
0.072
0.072
0.072
0.072
0.071
0.070
0.070
0.069
0.11
0.13
0.16
0.18
0.20
0.23
0.24
0.26
0.29
0.29
0.29
0.29
0.31
0.33
0.33
0.34
0.36
34
43
57
78
95
116
140
170
200
225
255
285
325
370
435
481
537
28
37
48
61
80
94
110
140
165
185
210
235
270
305
350
405
470
30
40
53
70
99
117
140
176
221
258
294
339
402
460
542
624
723
44
55
74
94
120
145
170
210
250
285
315
355
410
460
520
580
680
37
47
61
78
100
120
145
175
210
240
270
300
350
390
440
480
575
39
50
67
85
125
155
190
235
290
330
375
435
510
590
670
750
875
in K. Amps
Al
Cu
0.376
0.564
0.940
1.50
2.35
3.29
4.70
6.58
8.93
11.28
14.10
17.39
22.56
28.20
37.60
47.00
59.22
0.572
0.858
1.430
2.29
3.58
5.01
7.15
10.01
13.59
17.16
21.45
26.46
34.32
42.90
57.20
71.50
90.09
Note : Normal current ratings are given in standard conditions (as given in page no - 40,41), if site conditions are different, current rating should be multiplied by
rating factor as given in page no. 42
27
Table -23
Nominal
Nominal Diameter
Minimum Thickness
Approx.
Approx.
cross- Sectional
Insulation
of Armour Wire
of Outer Sheath
Over all
cable wt ( kg /km)
area(Sqmm)
thickness
(mm)
(mm)
Diameter
( mm)
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.8
2.8
3.0
3.3
3.5
1.40
1.40
1.40
1.60
1.60
1.60
1.60
1.60
1.60
1.60
2.00
2.00
2.00
2.00
2.50
With Al.
With Cu
(mm)
Cond.
Cond.
18
19
21
23
25
26
28
29
32
34
39
42
47
52
56
350
400
500
650
750
850
950
1100
1350
1550
2000
2400
3000
3650
4500
500
600
800
1100
1350
1600
1900
2250
2850
3400
4500
5500
6900
8600
10700
1.24
1.24
1.40
1.40
1.40
1.40
1.40
1.40
1.56
1.56
1.56
1.56
1.72
1.88
2.04
OUTER SHEATH : PVC TYPE ST-2 OF IS : 5831 OPTIONS : PVC TYPE ST-2/ FR TYPE/ FRLS TYPE
COLOUR OF OUTER SHEATH : BLACK . OPTIONS : ANY OTHER COLOURS AS PER REQUIREMENT
~ Tabulated approx. net weights of cables are only for guidelines for transportation / loading/ unloading purpose.
Electrical Parameters
SIZE
cross-sectional
area (Sq MM)
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778
0.0605
0.0469
0.0367
0.0291
0.727
0.524
0.387
0.268
0.193
0.153
0.1240
0.0991
0.0754
0.0601
0.0470
0.0366
0.0283
0.0221
0.0176
1.54
1.11
0.820
0.567
0.410
0.325
0.265
0.211
0.162
0.130
0.1023
0.0808
0.0648
0.0530
0.0444
0.931
0.671
0.495
0.343
0.248
0.197
0.159
0.127
0.098
0.078
0.0618
0.0489
0.0391
0.0319
0.0268
0.133
0.126
0.122
0.116
0.111
0.106
0.103
0.100
0.097
0.095
0.093
0.091
0.090
0.088
0.086
Capecitance
of cable
in microF/KM
(Approx).
0.25
0.29
0.33
0.38
0.44
0.49
0.53
0.58
0.67
0.73
0.84
0.86
0.88
0.94
0.99
100
120
140
175
205
235
260
295
340
385
440
495
560
620
670
91
110
125
155
185
210
230
260
300
335
380
430
485
530
570
110
135
165
210
255
295
335
390
460
530
620
730
840
960
1070
130
155
185
225
265
300
335
380
435
490
550
610
680
740
780
115
140
165
200
235
265
300
335
385
430
480
530
590
630
660
145
175
215
270
330
380
430
495
590
670
780
900
1020
1140
1250
in K. Amps
Al
Cu
2.35
3.29
4.70
6.58
8.93
11.28
14.10
17.39
22.56
28.20
37.60
47.00
59.22
75.20
94.00
3.58
5.00
7.15
10.00
13.59
17.16
21.45
26.45
34.32
42.90
57.20
71.50
90.10
114.40
143.00
Note : Normal current ratings are given in standard conditions (as given in page no - 40,41), if site conditions are different, current rating should be multiplied by
rating factor as given in page no. 42
28
Table -24
Nominal
diameter
of armour
wire ( mm)
25
2.2
0.3
0.8
1.40
28
1100
1550
1.60
1.56
30
1450
1900
35
2.2
0.3
0.8
1.56
31
1300
1950
1.60
1.56
33
1600
2250
50
2.2
0.4
0.8
1.56
33
1500
2450
2.00
1.56
35
2100
3050
70
2.2
0.4
0.8
1.56
36
1800
3100
2.00
1.56
38
2400
3700
95
2.2
0.4
0.8
1.72
39
2150
3900
2.00
1.72
42
2850
4600
120
2.2
0.5
0.8
1.72
42
2500
4750
2.00
1.88
45
3300
5550
150
2.2
0.5
0.8
1.88
44
2850
5650
2.50
2.04
48
4100
6900
185
2.2
0.5
0.8
2.04
48
3350
6800
2.50
2.04
51
4650
8100
240
2.2
0.6
0.8
2.20
52
4100
8550
2.50
2.20
56
5450
9900
300
2.2
0.6
0.8
2.20
56
4750
10350
2.50
2.36
60
6300
11900
400
2.2
0.7
0.8
2.36
62
5750
13200
3.15
2.68
67
8350
15800
OUTER SHEATH : PVC TYPE ST-2 OF IS : 5831 OPTIONS : FR TYPE/ FRLS TYPE
COLOUR OF OUTER SHEATH : BLACK. OPTIONS : any other colour as per requirement.
~ Tabulated approx. net wt. of cables are only guidelines for transportation, loading &unloading purpose.
~ Please ref page no 43 for normal delivery lengths & packing details.
Electrical Parameters
SIZE
cross-sectional
area (Sq MM)
25
Max. Cond. D.C. Approx. Cond. A.C. pp.. Reactance App. Capecitance
Normal* Current Rating in Amps
Resistance at
Resistance at
at 50HZ
of cable
With Aluminium cond.
With Copper cond.
20oC in Ohm/km 90oC in Ohm/km
in ohms/km
in microF/KM
Ground Duct
Air
Ground Duct
Air
Al
Cu
Al
Cu
(APPROX.)
(APPROX.)
1.20
0.727
1.54
0.931
0.098
0.25
94
80
99
120
100
125
in K. Amps
Al
Cu
2.35
3.58
35
0.868
0.524
1.11
0.671
0.094
0.29
115
95
120
145
120
155
3.29
5.00
50
0.641
0.387
0.820
0.495
0.086
0.33
135
110
145
170
145
190
4.70
7.15
70
0.443
0.268
0.567
0.343
0.084
0.38
165
140
185
210
175
235
6.58
10.01
95
0.320
0.193
0.410
0.248
0.081
0.44
195
165
225
250
210
290
8.93
13.59
120
0.253
0.153
0.325
0.197
0.078
0.49
220
185
255
285
240
330
11.28
17.16
150
0.206
0.1240 0.265
0.159
0.076
0.53
245
210
295
315
270
375
14.10
21.45
185
0.164
0.0991 0.211
0.127
0.075
0.58
280
235
340
355
300
435
17.39
26.46
240
0.125
0.0754 0.162
0.098
0.073
0.67
320
270
400
410
350
510
22.56
34.32
300
0.100
0.0601 0.130
0.078
400
0.072
0.73
360
305
460
460
390
590
28.20
42.90
0.071
0.84
410
350
535
520
440
670
37.60
57.20
Note : Normal current ratings are given in standard conditions (as given in page no - 40,41), if site conditions are different, current rating should be multiplied by
rating factor as given in page no. 42
29
Table -25 TECHNICAL DETAIL FOR HAVELLS 3.8/6.6 KV SINGLE CORE, AL/COPPER COND.,
XLPE INSULATED, ARMOURED CABLES
Cable Code : A2XWaY/2XWaY ( 6.6KV-EARTHED GRADE)
Physical Parameters
SIZE
Nominal
Minimum
Nominal Diameter
Minimum Thickness
Approx.
Approx.
cross-Sectional
Insulation
Inner Sheath
of Armour Wire
of Outer Sheath
Over all
cable wt ( kg /km)
area(Sqmm)
thickness
thickness
( mm)
( mm)
Diameter
With Al.
With Cu
mm
mm
( mm)
Cond.
Cond.
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
2.8
3.0
3.3
3.5
3.5
3.5
3.6
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.4
0.4
0.4
0.5
0.5
0.5
0.5
23
24
25
27
28
30
32
34
37
39
44
47
51
57
61
600
650
700
800
950
1050
1200
1400
1700
2000
2450
2800
3400
4300
5100
750
850
1000
1250
1550
1800
2100
2550
3200
3850
4900
5900
7300
9200
11300
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
1.60
1.60
1.60
1.60
1.60
1.60
1.60
1.60
2.00
2.00
2.00
2.00
2.00
2.50
2.50
1.40
1.40
1.40
1.40
1.40
1.40
1.56
1.56
1.56
1.56
1.72
1.72
1.88
2.04
2.20
INSULATION SCREENING : Extruded semiconducting compound followed by helically wrapped 0.050mm thick copper tape.
OUTER SHEATH : PVC TYPE ST-2 OF IS : 5831 OPTIONS : PVC TYPE ST-2/ FR TYPE/ FRLS TYPE
COLOUR OF OUTER SHEATH : BLACK . OPTIONS : ANY OTHER COLOURS AS PER REQUIREMENT
~ Tabulated approx. net weights of cables are only for guidelines for transportation / Loading/ Unloading Purpose.
Electrical Parameters
SIZE
cross-sectional
area (Sq MM)
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778
0.0605
0.0469
0.0367
0.0291
0.727
0.524
0.387
0.268
0.193
0.153
0.1240
0.0991
0.0754
0.0601
0.0470
0.0366
0.0283
0.0221
0.0176
1.54
1.11
0.820
0.567
0.410
0.325
0.265
0.211
0.162
0.130
0.1023
0.0808
0.0648
0.0530
0.0444
0.931
0.671
0.495
0.343
0.248
0.197
0.159
0.127
0.098
0.078
0.0618
0.0489
0.0391
0.0319
0.0268
0.149
0.142
0.133
0.127
0.121
0.116
0.113
0.109
0.105
0.104
0.102
0.100
0.096
0.094
0.092
App. Capecitance
Normal* Current Rating in Amps
of cable
With Aluminium cond.
With Copper cond.
in microF/KM
Ground Duct
Air
Ground Duct
Air
(Approx).
0.21
0.24
0.27
0.31
0.36
0.39
0.43
0.47
0.53
0.54
0.57
0.60
0.67
0.76
0.82
100
120
140
175
205
235
260
295
340
385
440
495
560
620
680
90
105
125
155
180
205
230
260
300
335
380
430
480
530
580
120
145
170
215
260
305
345
395
470
540
630
730
840
960
1070
130
155
185
225
265
300
335
380
435
490
550
610
680
740
790
115
140
160
195
235
265
295
330
380
425
480
530
580
630
670
155
185
220
275
340
390
440
510
600
680
790
910
1030
1140
1250
in K. Amps
Al
Cu
2.35
3.29
4.70
6.58
8.93
11.28
14.10
17.39
22.56
28.20
37.60
47.00
59.22
75.20
94.00
3.58
5.00
7.15
10.01
13.59
17.16
21.45
26.46
34.32
42.90
57.20
71.50
90.10
114.40
143.00
Note : Normal current ratings are given in standard conditions (as given in page no - 40,41), if site conditions are different, current rating should be multiplied by
rating factor as given in page no.. 42
30
Table -26 TECHNICAL DETAIL FOR HAVELLS 3.8/6.6 KV THREE CORES, AL/COPPER COND.,
XLPE INSULATED, ARMOURED CABLES
Cable Code : A2XFY/ 2XFY, A2XWY/2XWY (6.6KVE)
Physical Parameters
SIZE
cross-
sectional thickness
mm
area(Sqmm)
thickness
mm
thickness
mm
thickness
mm
Diameter
( mm)
Approx.
cable wt ( kg /km)
With Al.
Cond.
With Cu
Cond.
Nominal
diameter
Minimum
outer Sheath
of armour
wire (mm)
thickness
mm
With Al.
Cond.
With Cu
Cond.
25
2.8
0.4
0.8
1.56
37
1800
2250
2.00
1.72
40
2500
2950
35
2.8
0.4
0.8
1.72
39
2000
2650
2.00
1.72
42
2800
3450
50
2.8
0.5
0.8
1.72
42
2300
3250
2.00
1.88
45
3200
4150
70
2.8
0.5
0.8
1.88
46
2800
4100
2.00
1.88
49
3700
5000
95
2.8
0.5
0.8
1.88
50
3300
5050
2.50
2.04
54
4700
6450
120
2.8
0.6
0.8
2.04
54
3800
6050
2.50
2.20
58
5400
7650
150
2.8
0.6
0.8
2.20
58
4300
7100
2.50
2.20
61
5900
8700
185
2.8
0.6
0.8
2.20
61
4800
8250
2.50
2.36
65
6600
10050
240
2.8
0.7
0.8
2.36
67
5900
10350
3.15
2.52
72
8400
12850
300
3.0
0.7
0.8
2.52
72
6800
12400
3.15
2.68
77
9700
15300
400
3.3
0.7
0.8
2.84
82
8500
15950
4.00
3.00
88
13000
20450
OUTER SHEATH : PVC TYPE ST-2 OF IS : 5831 OPTIONS : PVC TYPE ST-2/ FR TYPE/ FRLS TYPE
COLOUR OF OUTER SHEATH : BLACK . OPTIONS : ANY OTHER COLOURS AS PER REQUIREMENT
~ Tabulated approx. net weights of cables are only for guidelines for transportation / Loading/ Unloading Purpose.
Electrical Parameters
SIZE
cross-sectional
area (Sq MM)
Reactance of
cable at 50HZ
in ohms/km
(APPROX.)
Capecitance
of cable
in microF/KM
(APPROX.)
in K. Amps
Al
Cu
25
1.20
0.727
1.54
0.931
0.126
0.21
95
82
105
120
105
135
2.35
3.58
35
0.868
0.524
1.11
0.671
0.120
0.24
115
97
125
145
125
165
3.29
5.01
50
0.641
0.387
0.820
0.495
0.114
0.27
130
115
150
170
150
195
4.70
7.15
70
0.443
0.268
0.567
0.343
0.107
0.31
160
140
190
210
180
240
6.58
10.01
95
0.320
0.193
0.410
0.248
0.102
0.36
190
165
230
250
215
295
8.93
13.59
120
0.253
0.153
0.325
0.197
0.098
0.39
220
190
260
280
240
335
11.28
17.16
150
0.206
0.1240 0.265
0.159
0.095
0.43
245
210
295
310
270
380
14.10
21.45
185
0.164
0.0991 0.211
0.127
0.093
0.47
275
240
335
350
305
430
17.39
26.46
240
0.125
0.0754 0.162
0.098
0.090
0.53
315
275
395
400
350
500
22.56
34.32
300
0.100
0.0601 0.130
0.078
0.090
0.54
355
310
450
445
390
570
28.20
42.90
400
0.087
0.57
400
350
520
500
440
650
37.60
57.20
Note : Normal current ratings are given in standard conditions (as given in page no - 40,41), if site conditions are different, current rating should be multiplied by
rating factor as given in page no. 42
31
Table -27
SINGLE CORE,
Physical Parameters
SIZE
Nominal
Minimum
Nominal Diameter
Minimum Thickness
Approx.
Approx.
cross-Sectional
Insulation
Inner Sheath
of Armour Wire
of Outer Sheath
Over all
cable wt ( kg /km)
area (Sqmm)
thickness
thickness
(mm)
(mm)
Diameter
With Al.
With Cu
mm
mm
( mm)
Cond.
Cond.
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
3.6
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.4
0.4
0.4
0.5
0.5
0.5
0.5
0.5
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
1.60
1.60
1.60
1.60
1.60
1.60
1.60
2.00
2.00
2.00
2.00
2.00
2.00
2.50
2.50
1.40
1.40
1.40
1.40
1.40
1.56
1.56
1.56
1.56
1.56
1.72
1.72
1.88
2.04
2.20
24
25
26
28
30
32
33
36
39
41
44
47
51
57
61
650
700
800
900
1050
1200
1300
1600
1850
2050
2500
2900
3450
4300
5100
800
900
1100
1300
1650
1950
2200
2750
3350
3900
5000
6000
7350
9250
11300
INSULATION SCREENING : Extruded semiconducting compound followed by helically wrapped 0.050mm thick copper tape.
OUTER SHEATH : PVC TYPE ST-2 OF IS : 5831 OPTIONS : PVC TYPE ST-2/ FR TYPE/ FRLS TYPE
COLOUR OF OUTER SHEATH : BLACK . OPTIONS : ANY OTHER COLOURS AS PER REQUIREMENT
~ Tabulated approx. net weights of cables are only for guidelines for transportation / Loading/ Unloading Purpose.
Electrical Parameters
SIZE
cross-sectional
area (Sq MM)
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778
0.0605
0.0469
0.0367
0.0291
0.727
0.524
0.387
0.268
0.193
0.153
0.1240
0.0991
0.0754
0.0601
0.0470
0.0366
0.0283
0.0221
0.0176
1.54
1.11
0.820
0.567
0.410
0.325
0.265
0.211
0.162
0.130
0.1023
0.0808
0.0648
0.0530
0.0444
0.931
0.671
0.495
0.343
0.248
0.197
0.159
0.127
0.098
0.078
0.0618
0.0489
0.0391
0.0319
0.0268
Reactance of
cable at 50HZ
in ohms/km
(Approx)
Capecitance
of cable
in microF/KM
(Approx)
0.164
0.156
0.147
0.139
0.133
0.127
0.124
0.120
0.117
0.113
0.110
0.107
0.104
0.100
0.098
0.18
0.20
0.22
0.26
0.29
0.32
0.35
0.38
0.43
0.46
0.53
0.59
0.66
0.74
0.82
100
120
140
175
205
235
260
295
340
385
440
495
560
620
680
90
105
125
155
180
205
230
260
300
335
380
430
480
530
580
120
145
170
215
260
305
345
395
470
540
630
730
840
960
1070
130
155
185
225
265
300
335
380
435
490
550
610
680
740
790
115
140
160
195
235
265
295
330
380
425
480
530
580
630
670
155
185
220
275
340
390
440
510
600
680
790
910
1030
1140
1250
in K. Amps
Al
Cu
2.35
3.29
4.70
6.58
8.93
11.28
14.10
17.39
22.56
28.20
37.60
47.00
59.22
75.20
94.00
3.58
5.00
7.15
10.01
13.59
17.16
21.45
26.46
34.32
42.90
57.20
71.50
90.10
114.40
143.00
Note : Normal current ratings are given in standard conditions (as given in page no -40,41), if site conditions are different, current rating should be multiplied by
rating factor as given in page no. 42
32
Table -28
THREE CORES,
sectional thickness
area(Sqmm)
mm
Approx.
cable wt ( kg /km)
thickness
mm
thickness
mm
thickness
mm
Diameter
( mm)
With Al.
Cond.
With Cu
Cond.
Nominal
diameter
of armour
wire ( mm)
thickness
mm
Diameter
( mm)
With Al.
Cond.
With Cu
Cond.
25
3.6
0.4
0.8
1.72
41
2100
2550
2.00
1.72
43
2800
3250
35
3.6
0.5
0.8
1.72
43
2350
2950
2.00
1.88
46
3200
3850
50
3.6
0.5
0.8
1.88
46
2700
3650
2.50
2.04
50
4000
4950
70
3.6
0.5
0.8
1.88
50
3100
4400
2.50
2.04
54
4500
5800
95
3.6
0.6
0.8
2.04
54
3700
5450
2.50
2.20
58
5200
6950
120
3.6
0.6
0.8
2.20
58
4200
6450
2.50
2.20
62
5800
8050
150
3.6
0.6
0.8
2.20
61
4700
7500
2.50
2.36
65
6400
9200
185
3.6
0.7
0.8
2.36
65
5300
8750
3.15
2.52
70
7900
11350
240
3.6
0.7
0.8
2.52
71
6300
10750
3.15
2.68
76
9000
13500
300
3.6
0.7
0.8
2.68
75
7200
12800
3.15
2.84
80
10000
15600
400
3.6
0.7
0.8
2.84
83
8700
16150
4.00
3.00
90
13500
20500
OUTER SHEATH : PVC TYPE ST-2 OF IS : 5831 OPTIONS : PVC TYPE ST-2/ FR TYPE/ FRLS TYPE
COLOUR OF OUTER SHEATH : BLACK . OPTIONS : ANY OTHER COLOURS AS PER REQUIREMENT
~ Tabulated approx. net weights of cables are only for guidelines for transportation / Loading/ Unloading Purpose.
Electrical Parameters
SIZE
cross-sectional
area (Sq MM)
Reactance
at 50HZ
in ohms/km
(APPROX.)
App. Capecitance
Normal* Current Rating in Amps
of cable
With Aluminium cond.
With Copper cond.
in microF/KM
Ground Duct
Air
Ground Duct
Air
(APPROX.)
in K. Amps
Al
Cu
25
1.20
0.727
1.54
0.931
0.133
0.18
95
82
105
120
105
135
2.35
3.58
35
0.868
0.524
1.11
0.671
0.126
0.20
115
97
125
145
125
165
3.29
5.01
50
0.641
0.387
0.820
0.495
0.118
0.22
130
115
150
170
150
195
4.70
7.15
70
0.443
0.268
0.567
0.343
0.116
0.26
160
140
190
210
180
240
6.58
10.01
95
0.320
0.193
0.410
0.248
0.107
0.29
190
165
230
250
215
295
8.93
13.59
120
0.253
0.153
0.325
0.197
0.102
0.32
220
190
260
280
240
335
11.28
17.16
150
0.206
0.1240 0.265
0.159
0.099
0.35
245
210
295
310
270
380
14.10
21.45
185
0.164
0.0991 0.211
0.127
0.097
0.38
275
240
335
350
305
430
17.39
26.46
240
0.125
0.0754 0.162
0.098
0.084
0.43
315
275
395
400
350
500
22.56
34.32
300
0.100
0.0601 0.130
0.078
0.093
0.46
355
310
450
445
390
570
28.20
42.90
400
0.089
0.53
400
350
520
500
440
650
37.60
57.20
Note : Normal current ratings are given in standard conditions (as given in page no -40,41), if site conditions are different, current rating should be multiplied by
rating factor as given in page no. 42
33
Table -29
Physical Parameters
SIZE
Nominal
Minimum
Nominal Diameter
Minimum Thickness
Approx.
Approx.
cross- Sectional
Insulation
Inner Sheath
of Armour Wire
of Outer Sheath
Over all
cable wt ( kg /km)
area(Sqmm)
thickness
thickness
(mm)
(mm)
Diameter
With Al.
With Cu
mm
mm
( mm)
Cond.
Cond.
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
5.5
0.3
0.3
0.3
0.3
0.3
0.4
0.4
0.4
0.4
0.4
0.5
0.5
0.5
0.6
0.6
28
29
31
33
34
37
38
40
43
44
48
53
56
61
65
900
950
1100
1200
1400
1600
1700
1900
2200
2500
2900
3500
4100
4900
5700
1050
1150
1400
1650
2000
2350
2600
3050
3700
4350
5400
6600
8000
9900
11900
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
1.60
1.60
1.60
1.60
1.60
2.00
2.00
2.00
2.00
2.00
2.00
2.50
2.50
2.50
2.50
1.40
1.40
1.56
1.56
1.56
1.56
1.56
1.56
1.72
1.72
1.88
1.88
2.04
2.20
2.20
INSULATION SCREENING : Extruded semiconducting compound followed by helically wrapped 0.050mm thick copper tape.
OUTER SHEATH : PVC TYPE ST-2 OF IS : 5831 OPTIONS : PVC TYPE ST-2/ FR TYPE/ FRLS TYPE
COLOUR OF OUTER SHEATH : BLACK . OPTIONS : ANY OTHER COLOURS AS PER REQUIREMENT
~ Tabulated approx. net weights of cables are only for guidelines for transportation / Loading/ Unloading Purpose.
Electrical Parameters
SIZE
cross-sectional
area (Sq MM)
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778
0.0605
0.0469
0.0367
0.0291
0.727
0.524
0.387
0.268
0.193
0.153
0.1240
0.0991
0.0754
0.0601
0.0470
0.0366
0.0283
0.0221
0.0176
1.54
1.11
0.820
0.567
0.410
0.325
0.265
0.211
0.162
0.130
0.1023
0.0808
0.0648
0.0530
0.0444
0.931
0.671
0.495
0.343
0.248
0.197
0.159
0.127
0.098
0.078
0.0618
0.0489
0.0391
0.0319
0.0268
Reactance of
cable at 50HZ
in ohms/km
(Approx).
Capecitance
of cable
in microF/KM
(Approx).
0.164
0.156
0.147
0.139
0.132
0.126
0.124
0.120
0.116
0.112
0.109
0.105
0.102
0.097
0.096
0.14
0.16
0.17
0.20
0.21
0.23
0.25
0.26
0.29
0.32
0.35
0.39
0.43
0.50
0.56
100
120
140
175
205
235
260
295
340
385
440
495
560
620
680
90
105
125
155
180
205
230
260
300
335
380
430
480
530
580
120
145
170
215
260
305
345
395
470
540
630
730
840
960
1070
130
155
185
225
265
300
335
380
435
490
550
610
680
740
790
115
140
160
195
235
265
295
330
380
425
480
530
580
630
670
155
185
220
275
340
390
440
510
600
680
790
910
1030
1140
1250
in K. Amps
Al
Cu
2.35
3.29
4.70
6.58
8.93
11.28
14.10
17.39
22.56
28.20
37.60
47.00
59.22
75.20
94.00
3.58
5.00
7.15
10.01
13.59
17.16
21.45
26.46
34.32
42.90
57.20
71.50
90.10
114.40
143.00
Note : Normal current ratings are given in standard conditions (as given in page no - 40,41), if site conditions are different, current rating should be multiplied by
rating factor as given in page no. 42
34
Table -30 TECHNICAL DETAIL FOR HAVELLS 11/11KV THREE CORES, AL/COPPER COND.,
XLPE INSULATED, ARMOURED CABLES
Ref. Spec. : IS :7098PART -2
mm
mm
mm
mm
(mm)
Cond.
Cond.
Nominal
diameter
of armour
wire (mm)
mm
(mm)
Cond.
Cond.
25
5.5
0.5
0.8
1.88
50
3000
3500
2.50
2.04
54
4300
4750
35
5.5
0.5
0.8
2.04
53
3200
3850
2.50
2.20
57
4700
5350
50
5.5
0.6
0.8
2.20
56
3700
4600
2.50
2.20
60
5100
6050
70
5.5
0.6
0.8
2.20
60
4100
5400
2.50
2.36
64
5800
7100
95
5.5
0.6
0.8
2.36
64
4800
6567
3.15
2.52
69
7300
9100
120
5.5
0.7
0.8
2.52
68
5400
7632
3.15
2.52
73
8000
10250
150
5.5
0.7
0.8
2.52
71
5900
8690
3.15
2.68
76
8600
11400
185
5.5
0.7
0.8
2.68
75
6500
9950
3.15
2.84
80
9400
12850
240
5.5
0.7
0.8
2.84
81
7600
12050
3.15
3.00
85
11000
15500
300
5.5
0.7
0.8
3.00
85
8600
14200
4.00
3.00
91
13000
18600
400
5.5
0.7
0.8
3.00
93
10000
17500
4.00
3.00
98
15000
22450
2
3 INSULATION MATERIAL : CROSSLINKED POLYETHYLENE (XLPE)
4
5
6
INSULATION SCREENING : Extruded semiconducting compound followed by helically wrapped 0.050mm thick copper tape.
PVC FILLERS
INNER SHEATH : Extruded PVC
Electrical Parameters
SIZE
cross-sectional
area (Sq MM)
in K. Amps
Al
Cu
25
1.20
0.727
1.54
0.931
0.145
0.14
95
82
105
120
105
135
2.35
3.58
35
0.868
0.524
1.11
0.671
0.138
0.16
115
97
125
145
125
165
3.29
5.01
50
0.641
0.387
0.820
0.495
0.129
0.17
130
115
150
170
150
195
4.70
7.15
70
0.443
0.268
0.567
0.343
0.124
0.20
160
140
190
210
180
240
6.58
10.01
95
0.320
0.193
0.410
0.248
0.116
0.21
190
165
230
250
215
295
8.93
13.59
120
0.253
0.153
0.325
0.197
0.112
0.23
220
190
260
280
240
335
11.28
17.16
150
0.206
0.1240 0.265
0.159
0.108
0.25
245
210
295
310
270
380
14.10
21.45
185
0.164
0.0991 0.211
0.127
0.105
0.26
275
240
335
350
305
430
17.39
26.46
240
0.125
0.0754 0.162
0.0976
0.102
0.29
315
275
395
400
350
500
22.56
34.32
300
0.100
0.0601 0.130
0.0778
0.0999
0.32
355
310
450
445
390
570
28.20
42.90
400
0.0618
0.0954
0.35
400
350
520
500
440
650
37.60
57.20
Note : Normal current ratings are given in standard conditions (as given in page no - 40,41), if site conditions are different, current rating should be multiplied by
rating factor as given in page no. 42
35
Table -31 TECHNICAL DETAIL FOR HAVELLS 12.7/22 KV SINGLE CORE, AL/COPPER COND.,
XLPE INSULATED, ARMOURED CABLES
Ref. Spec. : IS :7098PART-2
Nominal
Minimum
Nominal Diameter
Minimum Thickness
Approx.
Approx.
cross- Sectional
Insulation
Inner Sheath
of Armour Wire
of Outer Sheath
Over all
cable wt ( kg /km)
area(Sqmm)
thickness
thickness
(mm)
(mm)
Diameter
With Al.
With Cu
mm
mm
( mm)
Cond.
Cond.
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
6.0
0.3
0.3
0.3
0.3
0.4
0.4
0.4
0.4
0.4
0.4
0.5
0.5
0.5
0.6
0.6
29
31
32
34
36
38
39
41
44
46
50
53
57
62
66
950
1050
1150
1300
1600
1700
1800
2000
2300
2600
3000
3600
4300
5000
5800
1100
1250
1500
1750
2200
2450
2750
3150
3800
4500
5500
6700
8200
9950
12000
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
1.60
1.60
1.60
1.60
2.00
2.00
2.00
2.00
2.00
2.00
2.00
2.50
2.50
2.50
2.50
1.40
1.40
1.56
1.56
1.56
1.56
1.56
1.56
1.72
1.72
1.88
1.88
2.04
2.20
2.36
INSULATION SCREENING : Extruded semiconducting compound followed by helically wrapped 0.050mm thick copper tape.
OUTER SHEATH : PVC TYPE ST-2 OF IS : 5831 OPTIONS : PVC TYPE ST-2/ FR TYPE/ FRLS TYPE
COLOUR OF OUTER SHEATH : BLACK . OPTIONS : ANY OTHER COLOURS AS PER REQUIREMENT
~ Tabulated approx. net weights of cables are only for guidelines for transportation / Loading/ Unloading Purpose.
Electrical Parameters
SIZE
cross-sectional
area (Sq MM)
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778
0.0605
0.0469
0.0367
0.0291
0.727
0.524
0.387
0.268
0.193
0.153
0.1240
0.0991
0.0754
0.0601
0.0470
0.0366
0.0283
0.0221
0.0176
1.54
1.11
0.820
0.567
0.410
0.325
0.265
0.211
0.162
0.130
0.1023
0.0808
0.0648
0.0530
0.0444
0.931
0.671
0.495
0.343
0.248
0.197
0.159
0.127
0.098
0.078
0.0618
0.0489
0.0391
0.0319
0.0268
0.166
0.158
0.149
0.140
0.134
0.130
0.126
0.122
0.118
0.113
0.110
0.107
0.103
0.0997
0.097
0.13
0.15
0.16
0.18
0.20
0.22
0.23
0.25
0.27
0.30
0.32
0.36
0.40
0.46
0.52
100
120
140
170
200
225
250
280
315
345
385
415
450
485
510
90
105
120
150
175
195
215
240
275
300
330
360
385
415
435
120
145
175
220
265
300
340
385
450
500
570
640
720
790
850
130
155
180
215
255
285
310
345
390
420
455
480
510
540
550
115
135
155
190
220
245
270
300
335
360
395
415
440
460
475
155
185
225
280
335
380
430
485
560
620
690
750
820
840
940
in K. Amps
Al
Cu
2.35
3.29
4.70
6.58
8.93
11.28
14.10
17.39
22.56
28.20
37.60
47.00
59.22
75.20
94.00
3.58
5.00
7.15
10.01
13.59
17.16
21.45
26.46
34.32
42.90
57.20
71.50
90.10
114.40
143.00
Note : Normal current ratings are given in standard conditions (as given in page no- 40,41), if site conditions are different, current rating should be multiplied by
rating factor as given in page no. 42
36
Table -32 TECHNICAL DETAIL FOR HAVELLS 12.7/22 KV THREE CORES, AL/COPPER COND.,
XLPE INSULATED, ARMOURED CABLES
Ref. Spec. : IS :7098PART -2
sectional thickness
mm
area(Sqmm)
Approx.
cable wt kg /km)
Nominal
diameter
Minimum
outer Sheath
thickness
mm
thickness
mm
thickness
mm
Diameter
( mm)
With Al.
Cond.
With Cu
Cond.
of armour
wire (mm)
thickness
mm
Diameter
(mm)
With Al.
Cond.
With Cu
Cond.
25
6.0
0.5
0.8
2.04
53
3200
3650
2.50
2.20
56
4600
5050
35
6.0
0.6
0.8
2.04
56
3500
4150
2.50
2.20
59
5000
5650
50
6.0
0.6
0.8
2.20
59
3900
4850
2.50
2.36
61
5400
6350
70
6.0
0.6
0.8
2.36
63
4400
5700
2.50
2.36
65
6100
7400
95
6.0
0.7
0.8
2.36
67
5000
6800
3.15
2.52
72
7600
9350
120
6.0
0.7
0.8
2.52
70
5700
7950
3.15
2.68
75
8300
10550
150
6.0
0.7
0.8
2.68
74
6200
9000
3.15
2.68
78
9000
11800
185
6.0
0.7
0.8
2.68
77
6800
10250
3.15
2.84
83
9800
13250
240
6.0
0.7
0.8
2.84
83
7900
12350
4.00
3.00
90
12500
16950
300
6.0
0.7
0.8
3.00
88
8900
14500
4.00
3.00
93
13500
19100
400
6.0
0.7
0.8
3.00
95
10500
17950
4.00
3.00
102
15500
22950
2
INSULATION MATERIAL : CROSSLINKED POLYETHYLENE (XLPE)
3
4
5
INSULATION SCREENING : Extruded semiconducting compound followed by helically wrapped 0.050mm thick copper tape.
PVC FILLERS
Electrical Parameters
SIZE
cross-sectional
area (Sq MM)
Reactance of
cable at 50HZ
in ohms/km
(APPROX.)
Capecitance
of cable
in microF/KM
(APPROX.)
in K. Amps
Al
Cu
25
1.20
0.727
1.54
0.931
0.148
0.13
90
85
110
120
100
135
2.35
3.58
35
0.868
0.524
1.11
0.671
0.141
0.15
110
100
130
145
120
165
3.29
5.01
50
0.641
0.387
0.820
0.495
0.132
0.16
130
115
155
170
150
200
4.70
7.15
70
0.443
0.268
0.567
0.343
0.125
0.18
160
140
190
205
180
245
6.58
10.01
95
0.320
0.193
0.410
0.248
0.119
0.20
190
170
230
245
215
300
8.93
13.59
120
0.253
0.153
0.325
0.197
0.114
0.22
215
190
265
275
245
340
11.28
17.16
150
0.206
0.1240 0.265
0.159
0.111
0.23
240
215
300
305
275
385
14.10
21.45
185
0.164
0.0991 0.211
0.127
0.107
0.25
270
240
340
345
305
435
17.39
26.46
240
0.125
0.0754 0.162
0.098
0.104
0.27
310
275
400
395
350
510
22.56
34.32
300
0.100
0.0601 0.130
0.078
0.102
0.30
350
310
455
440
390
580
28.20
42.90
400
0.0618
0.097
0.32
395
355
530
495
440
660
37.60
57.20
Note : Normal current ratings are given in standard conditions (as given in page no - 40,41), if site conditions are different, current rating should be multiplied by
rating factor as given in page no. 42
37
Table -33 TECHNICAL DETAIL FOR HAVELLS 19/33 KV SINGLE CORE, AL/COPPER COND.,
XLPE INSULATED, ARMOURED CABLES
Cable Code : A2XWaY/2XWaY ( 33KV - EARTHED GRADE)
Physical Parameters
SIZE
Nominal
Minimum
Nominal Diameter
Minimum Thickness
Approx.
Approx.
cross- Sectional
Insulation
Inner Sheath
of Armour Wire
of Outer Sheath
Over all
cable wt ( kg /km)
area(Sqmm)
thickness
thickness
(mm)
(mm)
Diameter
With Al.
mm
mm
(mm)
Cond.
Cond.
8.80
8.80
8.80
8.80
8.80
8.80
8.80
8.80
8.80
8.80
8.80
8.80
8.80
8.80
8.80
0.40
0.40
0.40
0.40
0.40
0.40
0.40
0.50
0.50
0.50
0.50
0.60
0.60
0.60
0.70
36
38
39
40
43
44
46
47
50
53
57
60
64
70
74
1400
1500
1600
1800
2000
2100
2300
2500
2800
3300
3800
4300
4900
6000
6900
1450
1600
1800
2100
2500
2700
3130
3550
4200
5050
6200
7300
8800
10500
13000
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
2.00
2.00
2.00
2.00
2.00
2.00
2.00
2.00
2.00
2.50
2.50
2.50
2.50
3.15
3.15
1.56
1.56
1.56
1.56
1.72
1.72
1.72
1.72
1.88
2.04
2.04
2.20
2.20
2.36
2.52
With Cu
INSULATION SCREENING : Extruded semiconducting compound followed by helically wrapped 0.050mm thick copper tape.
OUTER SHEATH : PVC TYPE ST-2 OF IS : 5831 OPTIONS : PVC TYPE ST-2/ FR TYPE/ FRLS TYPE
COLOUR OF OUTER SHEATH : BLACK . OPTIONS : ANY OTHER COLOURS AS PER REQUIREMENT
~ Tabulated approx. net weights of cables are only for guidelines for transportation / Loading/ Unloading Purpose.
Electrical Parameters
SIZE
cross-sectional
area (Sq MM)
25
35
50
70
95
120
150
185
240
300
400
500
630
800
1000
1.20
0.868
0.641
0.443
0.320
0.253
0.206
0.164
0.125
0.100
0.0778
0.0605
0.0469
0.0367
0.0291
0.727
0.524
0.387
0.268
0.193
0.153
0.1240
0.0991
0.0754
0.0601
0.0470
0.0366
0.0283
0.0221
0.0176
1.54
1.11
0.820
0.567
0.410
0.325
0.265
0.211
0.162
0.130
0.1023
0.0808
0.0648
0.0530
0.0444
0.931
0.671
0.495
0.343
0.248
0.197
0.159
0.127
0.098
0.078
0.0618
0.0489
0.0391
0.0319
0.0268
Reactance of
cable at 50HZ
in ohms/km
(Approx).
Capecitance
of cable
in microF/KM
(Approx).
0.175
0.169
0.161
0.152
0.145
0.140
0.135
0.130
0.126
0.122
0.117
0.113
0.111
0.105
0.102
0.10
0.11
0.12
0.14
0.15
0.16
0.18
0.19
0.21
0.23
0.25
0.27
0.29
0.34
0.37
100
120
140
170
200
225
250
280
315
345
385
415
450
485
510
90
105
120
150
175
195
215
240
275
300
330
360
385
415
435
120
145
175
220
265
300
340
385
450
500
570
640
720
790
850
130
155
180
215
255
285
310
345
390
420
455
480
510
540
550
115
135
155
190
220
245
270
300
335
360
395
415
440
460
475
155
185
225
280
335
380
430
485
560
620
690
750
820
840
940
in K. Amps
Al
Cu
2.35
3.29
4.70
6.58
8.93
11.28
14.10
17.39
22.56
28.20
37.60
47.00
59.22
75.20
94.00
3.58
5.00
7.15
10.00
13.59
17.16
21.45
26.46
34.32
42.90
57.20
71.50
90.10
114.40
143.00
Note : Normal current ratings are given in standard conditions (as given in page no - 40,41), if site conditions are different, current rating should be multiplied by
rating factor as given in page no. 42
38
Table -34
Physical Parameters
SIZE
cross-
sectional thickness
mm
area(Sqmm)
thickness
mm
thickness
mm
thickness
mm
Diameter
( mm)
With Al.
Cond.
With Cu
Cond.
Nominal
diameter
Minimum
outer Sheath
of armour
wire (mm)
thickness
mm
Diameter
( mm)
With Al.
Cond.
With Cu
Cond.
25
8.80
0.70
0.8
2.36
67
4700
5150
3.15
2.68
72
7400
7850
35
8.80
0.70
0.8
2.52
70
5100
5750
3.15
2.68
75
7800
8450
50
8.80
0.70
0.8
2.52
72
5500
6450
3.15
2.68
77
8200
9150
70
8.80
0.70
0.8
2.68
76
6100
7400
3.15
2.84
81
9000
10300
95
8.80
0.70
0.8
2.84
80
6800
8550
3.15
3.00
86
10000
11750
120
8.80
0.70
0.8
2.84
84
7500
9750
4.00
3.00
90
12000
14250
150
8.80
0.70
0.8
3.00
87
8100
10900
4.00
3.00
94
12700
15500
185
8.80
0.70
0.8
3.00
90
8800
12250
4.00
3.00
97
13500
16950
240
8.80
0.70
0.8
3.00
95
9900
14350
4.00
3.00
103
15000
19450
300
8.80
0.70
0.8
3.00
100
11000
16600
4.00
3.00
106
16000
21600
400
8.80
0.70
0.8
3.00
108
12500
19950
4.00
3.00
114
18000
25450
OUTER SHEATH : PVC TYPE ST-2 OF IS : 5831 OPTIONS : PVC TYPE ST-2/ FR TYPE/ FRLS TYPE
COLOUR OF OUTER SHEATH : BLACK . OPTIONS : ANY OTHER COLOURS AS PER REQUIREMENT
~ Tabulated approx. net weights of cables are only for guidelines for transportation / Loading/ Unloading Purpose.
Electrical Parameters
SIZE
cross-sectional
area (Sq MM)
Reactance of
cable at 50HZ
in ohms/km
(APPROX.)
Capecitance
of cable
in microF/KM
(APPROX.)
in K. Amps
Al
Cu
25
1.20
0.727
1.54
0.931
0.160
0.10
90
85
110
120
100
135
2.35
3.58
35
0.868
0.524
1.11
0.671
0.153
0.11
110
100
130
145
120
165
3.29
5.01
50
0.641
0.387
0.820
0.495
0.146
0.12
130
115
155
170
150
200
4.70
7.15
70
0.443
0.268
0.567
0.343
0.138
0.14
160
140
190
205
180
245
6.58
10.01
95
0.320
0.193
0.410
0.248
0.130
0.15
190
170
230
245
215
300
8.93
13.59
120
0.253
0.153
0.325
0.197
0.125
0.16
215
190
265
275
245
340
11.28
17.16
150
0.206
0.1240 0.265
0.159
0.122
0.18
240
215
300
305
275
385
14.10
21.45
185
0.164
0.0991 0.211
0.127
0.118
0.19
270
240
340
345
305
435
17.39
26.46
240
0.125
0.0754 0.162
0.098
0.113
0.21
310
275
400
395
350
510
22.56
34.32
300
0.100
0.0601 0.130
0.078
0.111
0.23
350
310
455
440
390
580
28.20
42.90
400
0.106
0.25
395
355
530
495
440
660
37.60
57.20
Note : Normal current ratings are given in standard conditions (as given in page no - 40,41), if site conditions are different, current rating should be multiplied by
rating factor as given in page no. 42
39
SCOPE
The current ratings of cables as indicated in various tables have been calculated on certain assumed conditions.
In actual practice these conditions may be different. Therefore to determine the actual current ratings as per installation conditions, the tabulated
ratings shall be multiplied with appropriate factors
a)
iv)
v)
Thermal resistivity of Dielectric 650C cm/W for PVC, 350C cm/W for XLPE
vi)
Depth of laying - for 1.1KV cables - 750mm, 3.3KV to 11KV-900MM, Above 11KV-1050mm
vii)
viii)
b)
i)
RATING FACTORS
Rating factors related to variation in ambient air temperature
Air temperature in Deg. C20
Rating factors
ii)
25
30
35
40
45
50
55
Normal PVC
1.32
1.25
1.16
1.09
1.00
0.90
0.80
0.80
HRPVC
1.22
1.17
1.12
1.06
1.00
0.94
0.87
0.80
XLPE
1.20
1.16
1.11
1.06
1.00
0.95
0.88
0.81
30
35
40
45
50
iii)
20
Normal PVC
1.17
1.12
1.06
1.00
0.94
0.
0.79
0.71
HRPVC
1.13
1.09
1.04
1.00
0.95
0.90
0.85
0.80
XLPE
1.12
1.08
1.04
1.00
0.96
0.91
0..87
0.82
Rating factors related to variation in ground thermal resistivity of soil for 3 single core cables laid direct in ground. (Average value)
Thermal Res. in oC.Cm/W
Rating factors
iv)
100
120
150
200
250
300
1.20
1.10
1.00
0.90
0.81
0.74
Rating factors related to variation in ground thermal resistivity of soil for multi core cables laid direct in ground. (Average value)
Thermal Res. in oC.Cm/W
Rating factors
v)
25
100
120
150
200
250
300
1.16
1.08
1.00
0.90
0.82
0.76
vi)
40
90
105
120
150
1.00
0.99
0.98
0.97
0.96
0.95
105
120
150
Rating factors
0.97
0.96
0.94
0.93
105
120
150
Rating factors
0.96
0.95
0.92
0.91
120
0.98
150
0.96
1.00
1.00
0.98
0.97
Rating factors related to variation in depth of laying for 3.3kv to 11kv cables
Depth of laying (cm) >
Rating factors
vii)
75
75
90
1.00
105
0.99
Rating factors related to variation in depth of laying for above 11kv cables
Depth of laying (cm) >
75
90
105
120
150
Rating factors
1.00
0.99
0.98
0.96
No of cables/
circuits in groups
2
3
4
5
6
7
8
9
10
11
12
S=30CM
0.87
0.79
0.75
0.72
0.69
0.67
0.66
0.65
0.64
0.63
0.62
S=45CM
0.90
0.83
0.80
0.77
0.75
0.73
0.72
0.71
0.70
0.70
0.69
Touching S=15CM
0.80
0.85
0.70
0.78
0.64
0.73
0.59
0.70
0.55
0.67
0.53
0.65
0.51
0.64
0.49
0.63
0.48
0.63
0.47
0.62
0.46
0.61
S=30CM
0.90
0.85
0.81
0.79
0.77
0.76
0.76
0.74
0.74
0.73
0.73
S=45CM
0.92
0.88
0.86
0.84
0.83
0.82
0.82
0.81
0.81
0.80
0.80
S=60CM
0.95
0.91
0.89
0.88
0.87
0.86
0.86
0.85
0.85
0.84
0.84
No. of cables/
circuits in groups
No. of Tier
2
3
4
5
6
7
8
9
10
11
12
1
1
2
2
2
3
3
3
4
4
4
S=15CM
S=30CM
S=45CM
S=60CM
0.80
0.68
0.6
0.55
0.51
0.48
0.46
0.44
0.42
0.41
0.4
0.84
0.74
0.66
0.61
0.57
0.54
0.51
0.48
0.47
0.46
0.45
0.87
0.79
0.73
0.68
0.63
0.59
0.56
0.53
0.52
0.50
0.49
0.90
0.83
0.77
0.71
0.67
0.63
0.6
0.57
0.55
0.54
0.53
0.91
0.86
0.79
0.73
0.69
0.64
0.61
0.58
0.56
0.55
0.54
No.
of
racks
25mm
WALL
S = dia of cable
300mm
WALL
1
1.00
1.00
1.00
1.00
2
0.98
0.95
0.94
0.93
3
0.96
0.93
0.92
0.90
6
0.93
0.90
0.89
0.87
t = touching
300mm
1
1.00
1.00
1.00
1.00
2
0.84
0.80
0.78
0.76
3
0.80
0.76
0.74
0.72
6
0.75
0.71
0.70
0.65
9
0.73
0.69
0.68
0.66
WALL
No. of Racks
1
2
3
4
2d
300mm
No. of
Tier
2
3
4
5
6
7
8
9
10
11
12
1
1
2
2
2
3
3
3
4
4
4
No. co cables/
circuits in group
S=15CM
0.84
0.74
0.66
0.61
0.57
0.54
0.51
0.48
0.47
0.46
0.45
S=30CM
0.87
0.79
0.73
0.68
0.63
0.59
0.56
0.53
0.52
0.50
0.49
1
2
3
4
3
1.00
0.78
0.74
0.70
1.00
0.80
0.76
0.71
P.V.C. Cables
Single
Phase
Three
Phase
XLPE Cables
Single
Phase
Three
System
1.5
43.44
37.62
46.34
40.13
2.5
29.04
25.15
30.98
26.83
17.78
15.40
18.98
16.44
11.06
9.58
11.80
10.22
10
7.40
6.41
7.88
6.82
16
4.58
3.97
4.9
4.24
25
2.89
2.50
3.08
2.67
35
2.10
1.80
2.23
1.94
50
1.55
1.30
1.65
1.44
70
1.10
0.94
1.15
1.00
95
0.79
0.68
0.83
0.70
120
0.63
150
0.52
0.55
0.66
0.56
0.46
0.55
0.48
185
0.42
0.37
0.44
0.40
240
0.34
0.30
0.35
0.30
300
0.28
0.26
0.30
0.26
400
0.24
0.22
0.24
0.22
500
0.23
0.20
0.23
0.20
630
0.20
0.18
0.21
0.18
800
0.19
0.20
1000
0.18
0.18
S=60CM
0.91
0.86
0.79
0.73
0.69
0.64
0.61
0.58
0.56
0.55
0.54
4
1.00
0.76
0.72
0.68
S=45CM
0.90
0.83
0.77
0.71
0.67
0.63
0.60
0.57
0.55
0.54
0.53
SCOPE
The conductor size in the cables for any installation is also governed by its ability to carry short circuit current of
system. For L.V. distribution cable may be selected on the basis of continuous load current. But in case of MV/HV
distribution it is always safer to select the cable on the basis of ability of conductor to carry expected short circuit
current. Short circuit current rating of cable should in line with short circuit capacity of damping apparatus such as
circuit breakers, Transformers & reactor etc. beside its capacity to carry desired load current. Short circuit ratings
of cables each size are given in relevant tables & have been calculated on the basis of IEC-949 & IEC-986 & on the
following assumption
FOR EXAMPLE
11KV
25KA
0.5 SEC
= 25 X
0.5
=
0.94
=
188
Hence nearest higher size 240sqmm is required
Ish X
t
=
25 X
0.5
0.143
0.143
=
124
Hence nearest higher size 150sqmm is required
42
UN-ARMOURED
STRIP ARMOURED
UP TO 150SQMM-1000
185 TO 1000sqmm-500
UP TO 150SQMM-1000
185 to 1000sqmm-500
UP TO 150SQMM-1000
185 to 1000sqmm-500
~ TWO CORE
UP TO 50SQMM-1000
70 to 630sqmm-500
UP TO 50SQMM-1000
70 to 630sqmm-500
UP TO 50SQMM-1000, 70 TO 500sqmm
500, 630sqmm-250
~ THREE CORE
UP TO 50SQMM-1000
UP TO 50SQMM-1000
70 to 500sqmm-500
630sqmm-250
UP TO 50SQMM-1000, 70 TO 300sqmm
70 to 630sqmm-500
~ THREE & HALF CORE
70 to 630sqmm-500
UP TO 50SQMM-1000
70 to 400sqmm-500
500 to 630sqmm-250
UP TO 50SQMM-1000
70 to 500sqmm-500
630sqmm-250
UP TO 50SQMM-1000
70 to 400sqmm-500
500 to 630sqmm-250
~ SINGLE CORE
UP TO 150SQMM-1000
185 TO 630sqmm-500
800 to 1000sqmm-250
UP TO 150SQMM-1000
185 to 630sqmm-500
800 to 1000sqmm-250
UP TO 150SQMM-1000
185 to 630sqmm-500
800 to 1000sqmm-250
~ TWO CORE
UP TO 10SQMM-1000
16 to 300sqmm-500
400 to 630sqmm-250
UP TO 10SQMM-1000
16 to 300sqmm-500
400 to 630sqmm-250
UP TO 10SQMM-1000, 70 TO 500sqmm
500
500, 300 to 630sqmm-250
~ THREE CORE
UP TO 10SQMM-1000
UP TO 10SQMM-1000
16 to 240sqmm-500
240sqmm-400sqmm-250
UP TO 10SQMM-1000, 16 TO 185sqmm
16 to 185sqmm-500
500, 240 to 400sqmm-250
300 to 400sqmm-250
UP TO 10SQMM-1000
16 to 240sqmm-500
240 to 400sqmm-250
UP TO 10SQMM-1000, 16 TO 150sqmm
16 to 185sqmm-500
500, 185 to 400sqmm-250
UP TO 10SQMM-1000
16 to 240sqmm-500
300 to 400sqmm-250
UP TO 10SQMM-1000
16 to 150sqmm-500
240 to 400sqmm-250
UP TO 10SQMM-1000, 16 to 150sqmm
FOUR CORE
UP TO 50SQMM-1000
300 to 400sqmm-250
~ THREE & HALF CORE
FOUR CORE
UP TO 10SQMM-1000
~ Control cables more than FOUR CORES shall be supplied in 500 mts length
DESCRPITON OF CABLE
6.35/11KV GRADE
1/11KV GRADE
19/33KV GRADE
~ SINGLE CORE-A2XWaY
UP TO 150SQMM-1000
185 to 1000sqmm-500
UP TO 150SQMM-1000
185 to 1000sqmm-500
UP TO 150SQMM-1000
185 to 1000sqmm-500
~ THREE CORE-A2XFY
25 TO 300SQMM-500
25 TO 185SQMM-500
25 TO 95SQMM-500
400sqmm-250
240 to 400sqmm-250
120 to 400sqmm-250
25 TO 150SQMM-500
185 to 300sqmm-250
400sqmm-200
25 TO 95SQMM-500
120 to 240sqmm-250
300 to 400sqmm-200
25 TO 50SQMM-250
70 to 120sqmm-250
185 to 400sqmm-200
~ THREE CORE-A2XWY
43
Quality control
Test
It has been rightly said that Quality is never an accident, it is always the
follows :
Routine Tests :
achieve quality. For a quality end products, control starts from proper
Tests carried out on each cable to check the requirements which are
design of the product. All raw materials are selected carefully and only
materials of high quality are used in production. Having done this,
stage wise inspection is done to ensure conformity with the
Tests carried out to prove conformity with the specification. These are
i)
ii)
Wire-Drawing
Stranding of Wires:
: Wire diameter
Surface
Shape
Quality of joints in the wire
cable.
Acceptance Tests :
Tests carried out on samples taken from a lot for the purpose of
acceptance of the lot.
Optional Tests :
Special tests required for FRLS Cables can also be carried out at our
iii)
Insulation :
iv)
Curing
(for XLPE Insulation)
works i.e. Halogen gas generation test to IEC - 754 Part - I, Smoke
generation test to ASTMD 2843, Oxygen index test and Temperature
index test to ASTMD - 2863, Flammability test to
v)
v)
vi)
Screening
: Dimension over screen, thick of
(for H.T. Screened cables)
screen visual examination of
surface/defects.
Laying Up
Inner Sheath
vii) Armouring
: Sequence of Cores
Direction of lay
Diameter over laid up cores
Circularity
: Thickness of Sheath
Diameter over Sheath
Surface Uniformity
Circularity
Porosity
: Diameter of Wires/
Dimensions of Strips
Direction of lay
Coverage
Quality of Joints of Wires
44
Selection guide
List of Tests as per IS:1554(Part - I): 1988, IS:1554 (Part- II):1988,
IS:7098 (Part - I):1988 and IS:7098 (Part-II) : 1985
1.
2.
4.
5.
Routine Tests :
a)
b)
help in finding out as to what type of cable will be available for particular
c)
d)
operate will decide its protective covering. Thus once voltage grade of
Type Tests :
a)
b)
decided. The first and foremost criteria for the size of conductor is
c)
continuous current rating for the present load. There after the same
d)
e)
f)
g)
h)
I)
j)
k)
Flammability Test
l)
m)
n)
o)
p)
q)
Acceptance Tests :
should be checked for short circuit, voltage drop, over load capacities
and future expansions. Once decided the selection of next higher size
compared to what is essential for the requirement, will always be
worthwhile.
Economic considerations are also necessary.
INFORMATION REQUIRED WITH ENQUIRY & ORDER
The following information should be included in an enquiry :
i)
Voltage Grade.
ii)
a)
b)
c)
d)
e)
f)
g)
h)
I)
j)
Optional Tests :
a)
b)
c)
Handling &&Storage
HANDLING
STORAGE
Handling (Unloading at site) : On receipt of cable drums visual
inspection of drums should be made ensuring drum packing is original.
While unloading the cables certain precautions are to be taken to
ensure the safety of the cables.
1. The cable drums should not be dropped or thrown from railway
wagons or trucks during unloading operations as the shock may
cause serious damage to cable layers. A crane should be used
for unloading cable drums. When lifting drums with the crane, it is
recommended that the lagging should be kept in place to prevent
the flanges from curshing on to the cable. If the crane is not
available, a ramp should be prepared with approximate inclination
of 1:3 or 1:4. The cable drum should be rolled over the ramp by
means of ropes and winches. Additionally a sand bed at the foot
of the ramp may be prepared to brake the rolling the cable drum.
2. Cable should not be dragged along the earth surface.
3. Cable ends should always be sealed by means of suitable end
sealing materials to prevant moisturisation of cores and armour.
4. Drums should be rolled in direction of arrow marked on the drum.
Storage :
Cables should be stored in a dry covered place to prevent exposure to
climatic conditions and wear and tear of wooden drums and it should
preferably on a concrete surface/firm surface which will not cause the
drums to sink and thus lead to flange rot and extreme difficulty in
moving the drums.
All drums should be stored in such a manner as to leave sufficient
space between them for air circulation. It is desirable for drums to
stand on battens placed directly under the flanges.
In no case should the drums be stored, "On the Flat", i.e., with flange
horizontal.
Laying :
For laying of cables special cares to be taken to prevent sharp bending,
kinking, twisting. Cable should be unwound from drum by proper
mounting the cable drum on a cable wheel making sure the spindle is
strong enough to carry the weight without bending and that it is lying
horizontally in the bearings so as to prevent the drum creeping to one
side or the other while it is rotating.
TESTING
INSULATION RESISTANCE MEASUREMENT OF CABLE
The voltage rating of I.R. Tester (Megger) should be chosen as
following table :
Voltage grade
Rating of IR
Voltage grade
Rating of IR
of cable
Tester (Megger)
of cable
Tester (Magger)
1.1 KV
500 V
11 KV
1000 V
3.3 KV
1000 V
22 KV
2500 V
6.6 KV
1000 V
33 KV
2500 V