The PID Control Algorithm How It Works, How To Tune It, and How To Use It. 2nd Ed
The PID Control Algorithm How It Works, How To Tune It, and How To Use It. 2nd Ed
2nd Edition
John A. Shaw
Process Control Solutions
December 1, 2003
Introduction ii
Copyright 2003, John A. Shaw, All rights reserved. This work may not be resold,
either electronically or on paper. Permission is given, however, for this work to be
distributed, on paper or in digital format, to students in a class as long as this
copyright notice is included.
Introduction iii
Table of Contents
Chapter 1 Introduction.....................................................................1
1.1 The Control Loop ........................................................2
1.2 Role of the control algorithm .......................................3
1.3 Auto/Manual ...............................................................3
Chapter 2 The PID algorithm...........................................................5
2.1 Key concepts ...............................................................5
2.2 Action .........................................................................5
2.3 The PID responses.......................................................5
2.4 Proportional.................................................................6
2.5 Proportional—Output vs. Measurement .......................7
2.6 Proportional—Offset ...................................................7
2.7 Proportional—Eliminating offset with manual reset.....8
2.8 Adding automatic reset ................................................9
2.9 integral mode (Reset)................................................. 10
2.10 Calculation of repeat time.......................................... 11
2.11 Derivative.................................................................. 12
2.12 Complete PID response ............................................. 14
2.13 Response combinations ............................................. 14
Chapter 3 Implementation Details of the PID Equation.................. 15
3.1 Series and Parallel Integral and Derivative................. 15
3.2 Gain on Process Rather Than Error............................ 16
3.3 Derivative on Process Rather Than Error................... 16
3.4 Derivative Filter ........................................................ 16
3.5 Computer code to implement the PID algorithm ........ 16
Chapter 4 Advanced Features of the PID algorithm ....................... 20
4.1 Reset windup............................................................. 20
4.2 External feedback ...................................................... 21
4.3 Set point Tracking ..................................................... 21
Chapter 5 Process responses .......................................................... 23
5.1 Steady State Response ............................................... 23
5.2 Process dynamics ...................................................... 27
5.3 Measurement of Process dynamics ............................ 31
5.4 Loads and Disturbances ............................................. 33
Chapter 6 Loop tuning................................................................... 34
6.1 Tuning Criteria or “How do we know when its tuned”34
6.2 Mathematical criteria—minimization of index........... 35
6.3 Ziegler Nichols Tuning Methods ............................... 36
6.4 Cohen-Coon .............................................................. 40
6.5 Lopez IAE-ISE.......................................................... 41
6.6 Controllability of processes ....................................... 41
6.7 Flow loops................................................................. 42
Chapter 7 Multiple Variable Strategies .......................................... 44
Chapter 8 Cascade......................................................................... 45
8.1 Basics........................................................................ 45
Introduction iv
Table of Figures
Steam
TIC
Heated Water
Most processes contain many variables that need to be held at a set point and
many variables that can be manipulated. Usually, each controlled variable may be
affected by more than one manipulated variable and each manipulated variable
may affect more than one controlled variable. However, in most process control
systems manipulated variables and control variables are paired together so that
one manipulated variable is used to control one controlled variable. Each pair of
controlled variable and manipulated variable, together with the control algorithm,
is referred to as a control loop. The decision of which variables to pair is beyond
the scope of this publication. It is based on knowledge of the process and the
operation of the process.
In some cases control loops may involve multiple inputs from the process and
multiple outputs to the processes. The first part of this book will consider only
single input, single output loops. Later we will discuss some multiple loop control
methods.
There are a number of algorithms that can be used to control the process. The
most common is the simplest: an on/off switch. For example, most appliances use
a thermostat to turn the heat on when the temperature falls below the set point and
then turn it off when the temperature reaches the set point. This results in a
cycling of the temperature above and below the set point but is sufficient for most
common home appliances and some industrial equipment.
Introduction 2
To obtain better control there are a number of mathematical algorithms that
compute a change in the output based on the controlled variable. Of these, by far
the most common is known as the PID (Proportional, Integral, and Derivative)
algorithm, on which this publication will focus.
First we will look at the PID algorithm and its components. We will then look at
the dynamics of the process being controlled. Then we will review several
methods of tuning (or adjusting the parameters of) the PID control algorithm.
Finally, we will look as several ways multiple loops are connected together to
perform a control function.
• A final control element. A valve, air flow damper, motor speed controller, or
other device receives a signal from the controller and manipulates the process,
typically by changing the flow rate of some material.
• The process. The process responds to the change in the manipulated variable
with a resulting change in the measured variable. The dynamics of the process
response are a major factor in choosing the parameters used in the control
algorithm and are covered in detail in this publication.
Σ Algorithm Σ Process Σ
Output
Controller
Measurement
• The set point, the value to which the process variable will be controlled.
• One or more load variables, not manipulated by this control loop, but perhaps
manipulated by other control loops. In the steam water heater example, there
are several load variables. The flow of water through the heater is one that is
likely controlled by some other loop. The temperature of the cold water being
heated is a load variable. If the process is outside, the ambient temperature
and weather (rain, wind, sun, etc.) are load variables outside of our control. A
change in a load variable is a disturbance.
1.3 AUTO/MANUAL
Most control systems allow the operator to place individual loops into either
manual or automatic mode.
In manual mode the operator adjusts the output to bring the measured variable to
the desired value. In automatic mode the control loop manipulates the output to
hold the process measurements at their set points.
Introduction 4
Manual
Mode
Setpoint
e Output
∆ Control
Algorithm
Measured
Variable
Process
In most plants the process is started up with all loops in manual. During the
process startup loops are individually transferred to automatic. Sometimes during
the operation of the process certain individual loops may be transferred to manual
for periods of time.
In industrial process control, the most common algorithm used (almost the only
algorithm used) is the time-proven PID—Proportional, Integral, Derivative—
algorithm. In this chapter we will look at how the PID algorithm works from both
a mathematical and an implementation point of view.
• The PID control algorithm does not “know” the correct output that
will bring the process to the set point.
The PID algorithm merely continues to move the output in the direction that
should move the process toward the set point until the process reaches the set
point. The algorithm must have feedback (process measurement) to perform. If
the loop is not closed, that is, the loop is in manual or the path between the output
to the input is broken or limited, the algorithm has no way to “know” what the
output should be. Under these (open loop) conditions, the output is meaningless.
• The PID algorithm must be “tuned” for the particular process loop.
Without such tuning, it will not be able to function.
To be able to tune a PID loop, each of the terms of the PID equation must be
understood. The tuning is based on the dynamics of the process response and is
will be discussed in later chapters.
2.2 ACTION
The most important configuration parameter of the PID algorithm is the action.
Action determines the relationship between the direction of a change in the input
and the resulting change in the output. If a controller is direct acting, an increase
in its input will result in an increase in its output. With reverse action an increase
in its input will result in a decrease in its output.
The PID control algorithm is made of three basic responses, Proportional (or
gain), integral (or reset), and derivative. In the next several sections we will
discuss the individual responses that make up the PID controller.
In this book we will use the term called “error” for the difference between the
process and the set point. If the controller is direct acting, the set point is
subtracted from the measurement; if reverse acting the measurement is subtracted
from the set point. Error is always in percent.
The most basic response is proportional, or gain, response. In its pure form, the
output of the controller is the error times the gain added to a constant known as
“manual reset”.
Output = E x G + k
where:
Output = the signal to the process
E = error (difference between the measurement and the set point.
G = Gain
k = manual reset, the value of the output when the measurement equals
the set point.
Manual
Reset
Setpoint
Output
∆ e Σ
Out = E * G
Measured
Variable
Process
The output is equal to the error time the gain plus manual reset. A change in the
process measurement, the set point, or the manual reset will cause a change in the
output. If the process measurement, set point, and manual reset are held constant
the output will be constant
Incr. Decr.
Gain
Valve
Process Measurement
One way to examine the response of a control algorithm is the open loop test. To
perform this test we use an adjustable signal source as the process input and
record the error (or process measurement) and the output.
As shown below, if the manual reset remains constant, there is a fixed relationship
between the set point, the measurement, and the output.
%
Output
%
Error
Time
2.6 PROPORTIONAL—OFFSET
Proportional only control produces an offset. Only the adjustment of the manual
reset removes the offset.
Take, for example, the tank in Figure 8 with liquid flowing in and flowing out
under control of the level controller. The flow in is independent and can be
considered a load to the level control.
The flow out is driven by a pump and is proportional to the output of the
controller.
The PID algorithm 8
Flow In
L3
L2 LC
L1
Flow out
Assume first that the level is at its set point of 50%, the output is 50%, and both
the flow in and the flow out are 500 gpm. Then let’s assume the flow in increases
to 600 gpm. The level will rise because more liquid is coming in than going out.
As the level increases, the valve will open and more flow will leave. If the gain is
2, each one percent increase in level will open the valve 2% and will increase the
flow out by 20 gpm. Therefore by the time the level reaches 55% (5% error) the
output will be at 60% and the flow out will be 600 gpm, the same as the flow in.
The level will then be constant. This 5% error is known as the offset.
Offset can be reduced by increasing gain. Let’s repeat the above “experiment” but
with a gain of 5. For each 1% increase in level will increase the output by 5% and
the flow out by 50 gpm. The level will only have to increase to 52% to result in a
flow out of 600 gpm, causing the level to be constant. Increasing the gain from 2
to 5 decreases the offset from 5% to 2%. However, only an infinite gain will
totally eliminate offset.
Gain, however, cannot be made infinite. In most loops there is a limit to the
amount of gain that can be used. If this limit is exceeded the loop will oscillate.
Offset can also be eliminated by adjusting manual reset. In the above example
(with a gain of two) if the operator increased the manual reset the valve would
open further, increasing the flow out. This would cause the level to drop. As the
level dropped, the controller would bring the valve closed. This would stabilize
the level but at a level lower than before. By gradually increasing the manual reset
the operator would be able to bring the process to the set point.
The PID algorithm 9
2.8 ADDING AUTOMATIC RESET
With proportional only control, the operator “resets” the controller (to remove
offset) by adjusting the manual reset:
Setpoint
Output = e × G + Manual Reset
∆ e × Gain
e×G
Σ
Measured
Variable
Process
If the process is to be held at the set point the manual reset must be changed every
time there is a load change or a set point change. With a large number of loops the
operator would be kept busy resetting each of the loops in response to changes in
operating conditions.
The manual reset may be replaced by automatic reset, a function that will
continue to move the output as long as there is any error:
The PID algorithm 10
Set Point
X Gain UL
LL
LAG
Process
This is called “Reset” or Integral Action. Note the use of the positive feedback
loop to perform integration. As long as the error is zero, the output will be held
constant. However, if the error is non-zero the output will continue to change until
it has reached a limit. The rate that the output ramps up or down is determined by
the time constant of the lag and the amount of the error and gain.
If we look only at the reset (or integral) contribution from a more mathematical
point of view, the reset contribution is:
Out = g × Kr × ⌠
⌡ e dt
where g = gain
At any time the rate of change of the output is the gain time the reset rate times
the error. If the error is zero the output does not change; if the error is positive the
output increases.
The PID algorithm 11
Shown below is an open loop trend of the error and output. We would obtain this
trend if we recorded the output of a controller that was not connected to a process
while we manipulated the error.
Output
%
+10
% 0
-10 Error
Time
Most controllers use both proportional action (gain) and reset action (integral)
together. The equation for the controller is:
Out = g ( e + Kr ⌠
⌡ e dt )
where g = gain
If we look an open loop trend of a PI controller after forcing the error from zero to
some other value and then holding it constant, we will have the trends shown in
Figure 12.
The PID algorithm 12
Reset effect
%
Output
Gain effect
% +10
Error 0
-10
Time
τr
1 “Repeat” time
We can see two distinct effects of the change in the error. At the time the error
changed the output also changed. This is the “gain effect” and is equal to the
product of the gain and the change in the error. The second effect (the “reset
effect”) is the ramp of the output due to the error. If we measure the time from
when the error is changed to when the reset effect is equal to the gain effect we
will have the “repeat time.” Some control vendors measure reset by repeat time
(or “reset time” or “integral time”) in minutes. Others measure reset by “repeats
per minute.” Repeats per minute is the inverse of minutes of repeat.
2.11 DERIVATIVE
Derivative is the third and final element of PID control. Derivative responds to the
rate of change of the process (or error). Derivative is normally applied to the
process only). It has also been used as a part of a temperature transmitter (“Speed-
Act™” - Taylor Instrument Companies) to overcome lag in transmitter
measurement. Derivative is also known as Preact™ (Taylor) and Rate.
de
Out = g × Kd ×
dt
where g is gain,
e is the error
The open loop response of controller with proportional and derivative is shown
graphically:
The PID algorithm 13
Derivative effect
%
Gain effect
Output
% +10
Error 0
-10
τd Time
Derivative time
This diagram compares the output of a controller with gain only (dashed line)
with the output of a controller with gain and derivative (solid line). The solid line
is higher than the dashed line for the time that the process is increasing due the
addition of the rate of change to the gain effect. We can also look at the solid line
as being “leading” the dashed line by some amount of time (τd).
The amount of time that the derivative action advances the output is known as the
“derivative time” (or Preact time or rate time) and is measured in minutes. All
major vendors measure derivative the same: in minutes.
The PID algorithm 14
Manual
Reset
d
dt
Setpoint
e e×G
∆ ×G
Σ Output
Measured
Variable dt
de
Out = G(e + R⌠
⌡edt + D )
dt
Where
G = Gain
R = Reset (repeats per minute)
D = Derivative (minutes)
This is a general form of the PID algorithm and is close to, but not identical to,
the forms actually implemented in industrial controllers. Modifications of this
algorithm are described in the next chapter.
The description of the PID algorithm shown on the previous page is a “text book”
form of the algorithm. The actual form of the algorithm used in most industrial
controllers differs somewhat from the equation and diagram of shown on the
previous page.
The form of the PID equation shown Figure 14, which is the way the PID is often
represented in text books, differs from most industrial implementations in the
basic structure. Most implementations place the derivative section in series with
the integral or reset section.
We can modify the diagram shown above to reflect the series algorithm:
d
D dt R dt
Setpoint
Output
e Σ
∆ ×G Σ
e×G
Measured
Variable
The difference between this implementation and the parallel one is that the
derivative has an effect on the integration. The equation becomes:
R D de
Out = (RD+1)G(e + ⌠
⌡edt + )
(RD+1) (RD+1) dt
where R = the reset rate in repeats per minute,
The effect is to increase the gain by a factor of RD + 1, while reducing the reset
rate and derivative time by the same factor. Based on common tuning methods,
the derivative time is usually no more than about ¼ the reset time (1/R), therefore
the factor RD+1 is usually 1.25 or less.
Implementation Details of the PID Equation 16
Almost all analog controllers and most commercial digital control systems use the
series form. Such tuning methods as the Ziegler-Nichols methods (discussed in
Chapter 6 ) were developed using series form controllers.
The gain causes the output to change by an amount proportional to the change in
the error. Because the error is affected by the set point, the gain will cause any
change in the set point to change the output.
This can become a problem in situations where a high gain is used where the set
point may be suddenly changed by the operator, particularly where the operator
enters a new set point into a CRT. This will cause the set point, and therefore the
output, to make a step change.
In order to avoid the sudden output change when the operator changes the set
point of a loop, the gain is often applied only to the process. Set point changes
affect the output due to the loop gain and due to the reset, but not due to the
derivative.
The derivative acts on the output by an amount proportional to the rate of change
of the error. Because the error is affected by the set point, the derivative action
will be applied to the change in the set point.
This can become a problem in situations where the set point may be suddenly
changed by the operator, particularly in situations where the operator enters a new
set point into a CRT. This causes the set point to have a step change. Applying
derivative to a step change, even a small step change, will result in a “spike” on
the output.
In order to avoid the output spike when the operator changes the set point of a
loop, the derivative is often applied only to the process. Set point changes affect
the output due to the loop gain and due to the reset, but not due to the derivative.
There are many ways to implement the PID algorithm digitally. Two will be
discussed here. In each case, there will be a section of code (in structured Basic,
Implementation Details of the PID Equation 17
easily convertible to any other language) that will be executed by the processor
every second. (some other scan rate may be used, change the constant 60 to the
number of times per minute it is executed.) In each code sample there is an IF
statement to execute most of the code if the loop is in the auto mode. If the loop is
in manual mode only a few lines are executed in order to allow for bumpless
transfer to auto. Also, while the control loop is in manual, the output (variable
OutP) will be operator adjustable using the operator interface software.
One method of handling the integration and bumpless transfer to automatic mode
is an algorithm that calculates the change in output from one pass to the next
using the derivative of the PID algorithm, or:
dOut d 2 Error
= Gain × Re setRate × Error + Derivative ×
dt dt 2
This program is run every second. If the control loop is in manual, the output is
adjusted by the operator through the operator interface software. If the control
loop is in Automatic, the output is computed by the PID algorithm.
Each pass the output is changed by adding the change in output to the previous
pass output. That change is found by adding:
• the change in error (Err-ErrLast)
• the error multiplied by the reset rate, and
• the second derivative of the error (Err-2*ErrLast+ErrLastLast) times the
derivative.
This simple version of the PID controller work well in most cases, and can be
tuned by the standard PID tuning methods (some of which are discussed later). It
has “Parallel” rather than “Series” reset and derivative, and derivative is applied
to the error rather than the input only.
Variables:
Input Process input
InputD Process input plus derivative
InputLast Process input from last pass, used in deriv. calc.
Err Error, Difference between input and set point
ErrLast Error from last pass
ErrLastLast Error from next to last pass
OutP Output of PID algorithm
Mode value is ‘AUTO’ if loop is in automatic
Action value is ‘DIRECT’ if loop is direct acting
The only serious problem with this form of the algorithm occurs when the output
has reached an upper or lower limit. When it does, a change in the measurement
can unexpectedly pull the output away from the limit. For example, Figure 16
illustrates the set point, measurement, and output of an open loop direct acting
controller with a high gain and slow reset. When the input (blue line) rises above
the set point (red line) the output (green line) first increases due to the
proportional response and then continues to ramp up due to the reset response.
The ramp ends when the output is limited at 100%.
Note the spike (noise) in the input at about 5 minutes. That spike results in a spike
in the output, in the same direction. Compare this with the similar spike at about
61 minutes. Rather than cause an upward output spike as expected, the spike
causes the output to pull away from the upper limit. It slowly ramps back to the
limit. This is because the limit blocks the leading (increasing) side of the spike but
does nothing to the trailing (decreasing) side of the spike.
120
100
80
Input
60 Set Point
Output
40
20
0
1 5 9 13 17 21 25 29 33 37 41 45 49 53 57 61 65 69 73 77 81 85 89 93
Variables:
Input Process input
InputD Process input plus derivative
InputLast Process input from last pass, used in deriv. calc.
Err Error, Difference between input and set point
SetP Set point
OutPutTemp Temporary value of output
OutP Output of PID algorithm
Feedback Result of lag in positive feedback loop.
Mode value is ‘AUTO’ if loop is in automatic
Action value is ‘DIRECT’ if loop is direct acting
If external feedback is used, the variable “OutP” in line 11 is replaced with the
variable containing the external feedback.
Advanced Features of the PID algorithm 20
One problem with the reset function is that it may “wind up”. Because of the
integration of the positive feedback loop, the output will continue to increase or
decrease as long as there is an error (difference between set point and
measurement) until the output reaches its upper or lower limit.
This normally is not a problem and is a normal feature of the loop. For example, a
temperature control loop may require that the steam valve be held fully open until
the measurement reaches the set point. At that point, the error will be cross zero
and change signs, and the output will start decreasing, “throttling back” the steam
valve.
Sometime, however, reset windup may cause problems. Actually, the problem is
not usually the windup but the “wind down” that is then be required.
Input A Input B
EF EF
Output A Output B
The problem is that when conditions change and the override controller no longer
needs to hold the valve closed the primary controller’s output will be very far
above the override signal. Before the primary controller can have any effect on
the valve, it will have to “wind down” until its output equals the override signal.
Advanced Features of the PID algorithm 21
4.2 EXTERNAL FEEDBACK
The positive feedback loop that is used to provide integration can be brought out
of the controller. Then it is known as external feedback:
Setpoint
Output = G × e+EF
> UL
∆ e × Gain
e×G Σ < LL
Measured EF
LAG
Variable
Process
If there is a selector between the output of the controller and the valve (used for
override control) the output of the selector is connected to the external feedback
of the controller. This puts the selector in the positive feedback loop.
Setpoint
Output = G × e+EF
> UL
∆ e × Gain
e×G Σ < LL
Measured LAG
Variable EF
Process
If a loop is in manual and the set point is different from the process value, when
the loop is switched to auto the output will start moving, attempting to move the
process to the set point, at a rate dependent upon the gain and reset rate. Take for
example a typical flow loop, with a gain of 0.6 and a reset rate of 20. If difference
Advanced Features of the PID algorithm 22
between the set point and process is 50% at the time the loop is switched to
automatic the output will ramp at a rate of 10%/second.
Often, when a loop has been in manual for a period of time the value of the set
point is meaningless. It may have been the correct value before a process upset or
emergency shutdown caused the operator to place the loop into manual and
change the process operation. On a return to automatic the previous set point
value may have no meaning. However, to prevent a process upset the operator
must change the set point to the current process measurement before switching the
loop from manual to automatic.
Some industrial controllers offer a feature called “set point tracking” that causes
the set point to track the process measurement when the loop is not in automatic
control. With this feature when the operator switches from manual to automatic
the set point is already equal to the process, eliminating any bump in the process.
The set point tracking feature is typically used with loops that are tuned for fast
reset, where a change from manual to automatic could cause the output to rapidly
move, and for loops where the set point is not always the same. For example, the
temperature of a room or an industrial process usually should be held to some
certain value. The set point for the rate of flow of fuel to the heater is “whatever it
takes” to maintain the temperature at its set point. Therefore flow loops are more
likely to use set point tracking. However, this is a judgment that must be made by
persons knowledgeable in the operation of the process.
Process responses 23
Loops are tuned to match the response of the process. In this chapter we will
discuss the responses of the process to the control system.
The dynamic and steady state response of the process signal to changes in the
controller output. These responses are used to determine the gain, reset, and
derivative of the loop.
While discussing single loop control, we will consider the process response to be
the effect on the controlled variable cause by a change in the manipulated variable
(controller output).
The steady state process response to controller output changes is the condition of
the process after sufficient time has passed so that the process has settled to new
values.
The steady state response of the process to the controller output is characterized
primarily by process action, gain, and linearity.
Action describes the direction the process variable changes following a particular
change in the controller output. A direct acting process increases when the final
control element increases (typically, when the valve opens); a reverse acting
process decreases when the final control element increases.
Next to action, process gain is the most important process characteristic. The
process gain (not to be confused with controller gain) is the sensitivity of the
controlled variable to changes in a controller output. Gain is expressed as the ratio
of change in the process to the change in the controller output that caused the
process change.
From the standpoint of the controller, gain is affected by the valve itself, by the
process, and by the measurement transmitter. Therefore the size of the valve and
the span of the transmitter will affect the process gain.
Process responses 24
r ve
Cu
ss
Measured Variable
o ce
Pr
2%
1%
Output
(Valve Position)
The gain of the process often changes based on the value of the controller output.
That is, with the output at one value, a small change in the output will result in a
larger change in the process measurement than the same output change at some
other output value.
0.5%
Measured Variable
ve
2%
ur
sC
es
oc
Pr
1% 1%
Output
(Valve Position)
The process shown in Figure 21 is non linear. With controller output very low, a
1% increase in the output causes the measured variable to increase by 2%. When
Process responses 25
the output is very high, the same 1% output increase causes the process to
increase by only 0.5%. The process gain decreases when the output increases.
From the standpoint of controller tuning, the process linearity includes the
linearity of the process, the final control element, and the measurement. It also
includes any control functions between the PID algorithm and the output to the
valve.
Valves may be linear or non-linear. A linear valve is one in which the flow
through the valve is exactly proportional to the position of the valve (or the signal
from the control system). Valves may fall into three classes (illustrated in Figure
22): linear, equal percentage, and quick opening.
Linear valves have the same gain regardless of the valve position. That is, at any
point a given increase in the valve position will cause the same increase in the
flow as at any other point.
Equal percentage valves have a low gain when the valve is nearly closed, and a
higher gain when the valve is nearly open.
Quick opening valves have a high gain when the valve is nearly closed and a
lower gain when the valve is nearly open.
100
Flow vs. % Open
QO Linear
QO - Quick Opening
Flow 50 EP - Equal Percentage
Linear
EP
0
0 50 100
Valve Opening
Even a linear valve does not necessarily exhibit linear characteristics when
actually installed in a process. The characteristics described in the previous
section are based on a constant pressure difference across the flanges of the valve.
However, the pressure difference is not necessarily constant. When the pressure is
a function of valve position, the actual characteristics of the valve are changed.
Take for example the flow through a pipe and valve combination shown in Figure
23. Liquid flows from a pump with constant discharge pressure to the open air.
There is a pressure drop through the valve that is proportional to the square of the
Process responses 26
flow. Assume that with a valve position of 10% the flow is 100 gpm. Also assume
that with the particular size and length of the pipe 100 gpm causes a 10 psi
pressure drop across each section of pipe. This leaves a net pressure from of 80
psi across the valve.
Assume now that we wish to double the flow rate to 200 gpm. By doubling the
flow, we will increase the pipe pressure drop by a factor of four. With a pressure
drop of 40 psi across each section of pipe, we will only have a valve differential
pressure of only 20 psi. To make up for the loss of pressure, will have to increase
the valve opening by a factor of four to make up for the pressure loss and by a
factor of two to double the flow. Therefore, to double the flow rate we will have
to open the valve from 10% to 80%. The so called linear valve now has the
characteristics of a quick opening valve.
100
QO Flow vs. % Open
Linear
QO - Quick Opening
Flow 50 Linear EP EP - Equal Percentage
0
0 50 100
Valve Opening
The measured variable does not change instantly with the controller output
changes. Instead, there is usually some delay or lag between the controller output
change and the measured variable change. Understanding the dynamics of the
loop is required in order to know how to properly control a process.
There are two basic types of dynamics: simple lag and dead time. Most processes
are a combination of several individual lags, each of which can be classed as
simple lag or dead time.
Dead Time is the delay in the loop due to the time it takes material to flow from
one point to another. For example, in the temperature control loop shown below,
it takes some amount of time for the liquid to travel from the heat exchanger to
the point where the temperature is measured. If the temperature at the exchanger
outlet has been constant and then changes, there will be some period of time
before any change can be observed by the temperature measurement element.
Dead time is also called distance velocity lag and transportation lag.
Steam
TIC
Dead time is often considered to be the most difficult dynamic element to control.
This will become apparent in Chapter 6 , controller tuning.
Process responses 28
Output
Output
Process
Process
Process with pure dead time Process with lag and dead time
For most processes, as a variable increases it will tend to reduce its rate of
increase and eventually level off even without any change in the manipulated
variable. This is referred to as self regulation.
Self regulation does not usually eliminate the need for a controller, because
usually the value at which the variable will settle will be unacceptable. The
control system will need to act to bring the controlled variable back to its set
point.
An example of self regulation is a tank with flow in and out. The manipulated
variable is the liquid flow into a tank. The controlled variable is the flow out of
the tank. The load is the valve position of the discharge flow. With the valve
position constant, the flow out of the tank is determined by the valve position and
the level (actually the square of the level). As the level in the tank falls, the
pressure (or liquid head) decreases, decreasing the flow rate. Eventually the
discharge flow will decrease to the point that it equals the inlet flow, and the level
will maintain a constant value. Likewise, if the flow into the tank increases, the
level will begin to increase until the discharge flow equaled the inlet flow (unless
the tank became full and overflowed first).
This also occurs in temperature loops. Take example, a room with an electric
space heater with no thermostat. The room is too cool, so we turn on the space
heater. As more heat enters the room, the room temperature increases. However,
the flow of heat out through the walls is proportional to the difference between the
inside and the outside temperatures. As the room temperature increases, that
difference increases, and the heat flow from the room eventually equals the
amount of heat produced by the space heater. As the temperature increases the
rate of change decreases until the temperature levels off at a higher temperature.
Process responses 29
Sometimes the self regulation is sufficient to eliminate any need for feedback
control. However, more often the self regulation is not sufficient (the tank
overflows or the room becomes too hot), therefore control is still needed. Because
of self regulations, for at least some range of controller outputs there will be a
corresponding process value.
The self regulation is responsible for the curve shown in the dynamic response of
a controlled variable to a change in the measured variable.
The most common dynamic element is the simple lag. If a step change is made in
the controller output , the process variable will change as shown in Figure 28.
Output
Process
An example of a process dominated by one loop is shown in Figure 29. The flow
of the liquid out of the vessel is proportional to the level. If the inlet valve is
opened, increasing the flow into the vessel, the level will rise. As the level rises,
the flow output will rise, slowing the rate of increase in the level. Eventually, the
level will be at the point where the flow out will be equal to the flow in.
LT
Most processes have more than one lag, although some of the lags may be
insignificant. Lags are not additive. A response of a multiple lag is illustrated in
Figure 30.
The process measured variable begins to change very slowly, and the rate of
change increases up to a point, known as the point of inflection, where the rate of
change decreases as the measurement approaches its asymptote.
Point of inflection
The first part of the curve, where the rate of change is increasing, is governed
primarily by the second largest lag. The second part of the curve, beyond the point
of inflection, is governed primarily by the largest lag.
Often processes have been described as first order, second order, etc., based on
the number of first order linear lags included in the process dynamics. It can be
argued that all processes are of a higher order, with a minimum of three lags and a
dead time. These lags, which are present in all processes, include the lag inherent
in the sensing device, the primary lag of the process, and the time that the valve
(or other final control element) takes to move. However, in many processes the
smaller lags are so much smaller than the largest lag that their contributions to the
process dynamics are negligible.
Dead time is also present in all processes. With pneumatic control, there is some
dead time due to the transmission of the pressure signal from the process to the
controller, and from the controller to the valve. This is eliminated by electronic
controls (unless one considers the transmission of the electric signal, usually a
few microseconds or less). With digital controls, there is an effective dead time
equal to one half the loop scan rate [2]. In most cases, the loop will be scanned
fast enough so that this dead time is insignificant. In some cases, such as liquid
flow loops, this dead time is significant and affects the amount of gain that can be
used.
Rather than consider a process to be first order, second order, etc., it may be better
to consider all loops to be higher order to a degree. As an alternative to process
Process responses 31
order, we will characterize processes by the degree to which one first order lag
dominates the other lags in the process (not considering any true dead time).
Dominant-lag processes are those that consist of a dead time plus a single
significant lag, with all other lags small compared to the major lag. Multiple-lag
or non-dominant-lag processes are those in which the longest lag is not
significantly longer than the next longest lag. One measure of the dominance of a
single lag is the value of the process measurement at which the point of inflection
(POI) occurs.(see Figure 31) In the most extreme case (only a single lag) the POI
occurs at the initial process value. With about three equal, non-interacting lags the
POI occurs at about 33% of the difference between the initial and the final process
value.[7]
Output
%
Process DT + 1 lag
%
DT + multiple lags
Points of Inflection
Process dynamics usually consist of several lags and dead time. The dynamics
differ from one loop to another. The dynamics can be expressed by a detailed list
of all of the lags and the dead time of the loop, or they can be approximated using
a simpler model.
One such model is a dead time and a first order lag. Graphically, the process
response of such a model is:
Process responses 32
Output
%
Process
%
Td τ
Several tuning methods (such as the Ziegler-Nichols open loop method) are based
on an approximation of the process as a combination of a single first order lag and
a dead time, known as the First Order Plus Dead Time (FOPDT) model. These
methods identify the process by making a step change in the controller output.
The process trend is recorded and graphical or mathematical methods are used to
determine the process gain, dead time, and first order lag.
Process gain is the ratio of the change in the process to the change in the
controller output signal. It depends upon the range of the process measurement
and includes effects of the final control element.
Pseudo dead time (Td) is the time between the controller output change and the
point at which the tangent line crosses the original process value. The pseudo
dead time is influenced by the dead time and all of the lags smaller than the
longest lag in the process.
Process time constant (τ) is the rate of change of the process measurement at the
point at which the rate of change is the highest. The time constant is strongly
influenced by the longest lag in a multiple lag process.
The ratio of the pseudo dead time to the process time constant is often referred to
as an “uncontrollability” factor (Fc) that is an indication of the quality of control
that can be expected. The gain (for a P, PI, and PID controller) at which
oscillation will become unstable is inversely proportional to this factor. Smith,
Murrill, and Moore, [5] proposed that the factor be modified by adding one half of
the sample time to the dead time for digital controllers.
Process responses 33
5.4 LOADS AND DISTURBANCES
The process measurement is affected not only by the output of the control loop
but by other factors called loads. These can include such factors as the weather,
the position of other valves, and many other factors.
Flow In
LT LIC
101 101
Flow Out
In a steam heater, the temperature is controlled by the valve on the steam line.
However, the temperature is also affected by the temperature of the air around the
vessel, although not nearly as much as by the steam valve. This temperature
outside of the vessel is also a load.
The changes in a load are called disturbances. Almost all processes contain
disturbances. They can be as major as the effect of the inlet flow on the vessel or
as minor as the effect of weather on the temperature loop.
Loop tuning 34
Once a loop is configured and started up, in order for it to work correctly someone
has to put the correct gain, reset, and derivative values into the PID control
algorithm.
One of the most important, and most ignored, facets of loop tuning is the
determination of the proper tuning of a loop.
The loop performance must fall between two extremes. First, the loop must
respond to a change in set point and to disturbances. That is, an error, or
difference in the process and the set point, must eventually result in the
manipulation of the output so that the error is eliminated. If the gain, reset, and
derivative of the loop are turned to zero there will be no response.
The other extreme is instability. An unstable loop will oscillate without bound. A
set point change will cause the loop to start oscillating, and the oscillations will
continue. At worst, the oscillations will grow (or diverge).
Proper tuning of a loop will allow the loop to respond to set point changes and
disturbances without causing instability.
There are several rules of thumb for determining how the quality of the tuning of
a control loop.
4
1
Traditionally, quarter wave decay has been considered to be the optimum decay
ratio. This criterion is used by the Ziegler Nichols tuning method, among others.
There is no single combination of tuning parameters that will provide quarter
wave decay. If the gain is increased and the reset rate decreased by the correct
amount the decay ratio will remain the same.
Loop tuning 35
Quarter wave decay is not necessarily the best tuning for either disturbance
rejection or set point response. However, it is a good compromise between
instability and lack of response.
For some loops the objective of the tuning is to minimize the overshoot following
a set point change.
e rejection.
For other loops the primary concern is the reduction of the effect of disturbances.
Disturbance
The choice of methods depends upon the loop’s place in the process and its
relationship with other loops.
+ +
—
—
There are several criteria for evaluating tuning that are based on integrating the
error following a disturbance or set point change. These methods are not used to
test control loops in actual plant operation because the usual process noise and
Loop tuning 36
random disturbances will affect the outcome. There are used in control theory
education and research using simulated processes. The indices provide a good
method of comparing different methods of controller tuning and different control
algorithm.
Of these methods, the IAE and ISE are the most common.
The Ziegler Nichols methods provide quarter wave decay tuning for most types of
process loops. This tuning does not necessarily provide the best ISE or IAE tuning
but does provide stable tuning that is a reasonable compromise among the various
objectives. If the process does actually consist of a true dead time plus a single
first order lag, the Z-N methods will provide quarter wave decay. If the process
has no true dead time but has more than two lags (resulting in a “pseudo dead
time”) the Z-N methods will usually provide stable tuning but the tuning will
require on-line modification to achieve quarter wave decay.
Because of their simplicity and because they provides adequate tuning for most
loops, the Ziegler Nichols methods are still widely used.
The Ziegler Nichols method, as well as several other methods for controller
tuning, rely on a model of the process that comprises one first order lag plus dead
time. The FOPDT model parameters can be determined from the actual process
using a simple process reaction test. The output from the controller is increased
(or decreased) in a step change, and the reaction of the process is recorded. The
process gain is the ratio of the change in the process (in percent) to the change
that had been made in the controller output.
Loop tuning 37
Several methods have been proposed to calculate the pseudo dead time, and time
constant from the reaction curve.
Ziegler and Nichols proposed a graphical method (Figure 38) using a tangent line
drawn through the steepest part of the curve (the point of inflection). The line
continues below the original process value. The time between the output change
and the point at which the tangent line crosses the original process line is called
the lag (the term Pseudo Dead Time will be used in this paper). The slope of the
line is then calculated. The original Ziegler-Nichols formulas used the slope or the
rate of change rather than the time.
Output
%
Process
POI
%
R
Output
%
Process
%
Td τ
These two methods will provide identical results when applied perfectly, that is,
no error in the drawing of the line and no noise in the process signal.
Loop tuning 38
Two additional methods are the mathematical equivalent of the previous two only
if the process dynamics really did comprise only a single order lag and a dead
time. When the process differs from this model, the following two methods will
provide different results that may actually provide better tuning.
Output
%
Process 100%
% 63.2%
Td τ
Another variation is the “two point method”, proposed by C. Smith [3, p141],
illustrated in Figure 41. This method does not require the drawing of a tangent
line but measures the times at which the process changes by 28.3% (t1) and
63.2% (t2) of the total process change. Then two formulas are used to calculate
the pseudo dead time and the process time constant.
process time constant τ = 1.5(t1 - t2)
pseudo dead time T d = t1 - τ
Loop tuning 39
Output
%
Process 100%
% 63.2%
28.3%
Td τ
One advantage of the two point method is that it does not require drawing the
tangent line. This improves the accuracy, particularly for processes with noise.
This method will provide the same pseudo dead time and time constant when the
process dynamics are dominated by a true dead time and single lag. Like the
tangent and point method, the two point method provides different values for the
pseudo dead time and the process time constant when the process dynamics
comprise multiple lags. When used with the multiple lag processes, the one point
and two point methods also provide better tuning. In table 3, tests within each set
all result in the same pseudo dead time and time constant using the tangent line
method. However, using the two point method the pseudo dead time and time
constant are different. For multiple lag processes the two point method results in a
longer dead time and shorter time constant than tangent methods. This provides
more conservative tuning using any of the FOPDT tuning methods.
The first method is the open loop method, also known as the “reaction curve”
method. This method calculates the actual values of the of the assumed process
model (the gain, pseudo dead time, and lag).
For this method to work the process must be “lined out”, that is, not changing.
With the controller in manual, the output is changed by a small amount. The
process is then monitored.
The following values are calculated using one of the methods described above:
Kp Process Gain
The closed loop (or ultimate gain method) determines the gain that will cause the
loop to oscillate at a constant amplitude. Most loops will oscillate if the gain is
increased sufficiently.
P
U
6.4 COHEN-COON
Integral Absolute Error and Integral Squared Error are two methods of judging the
tuning of a control loop. (see below). A method of selecting tuning coefficients to
minimize the IAE or ISE criteria for disturbances was developed by Lopez, et. al.
[5].
This method uses the FOPDT model parameters and a set of equations (Table 9)
to calculate the tuning parameters. Tests show that the parameters provide results
close to the minimum IAE or ISE, particularly when the actual process dynamics
are similar to the FOPDT model (the process contains a true dead time and one
lag). When the process has multiple lags the equations do not provide the best
possible tuning, but they still provide better tuning (lower IAE and ISE indices)
than the other methods.
The gain at which a loop will oscillate depends upon the dynamics of the loop. In
general, a loop that has no dynamic elements other than one first order lag will not
oscillate at any gain. A loop with dead time or with multiple lags will oscillate at
some gain.
If we refer to the model used on the Ziegler Nichols open loop test, the gain at
which a loop will exhibit undamped, sustained oscillations (the ultimate gain in
Loop tuning 42
the Ziegler Nichols closed loop test) will depend upon the ratio of the process
time constant (τ) to the pseudo dead time (Td).
Output
%
Process
%
Td τ
The importance of this fact goes beyond finding the best tuning parameters. There
is an advantage to a loop that can have a higher gain. If a loop can have a higher
gain it will have greater rejection of disturbances and will respond more rapidly to
set point changes. Therefore, it is advantageous to be able to increase the gain if
doing so will not cause the loop to become unstable.
Remember that the time constant is proportional to the largest lag in the system.
The pseudo dead time is based on the dead time and all other lags. The allowable
gain (and the gain required for quarter wave decay) can be increased by
t
increasing the ratio . An increase in either dead time or in any lag other than
Td
the longest lag will decrease the ratio and therefore decrease the allowable gain.
The loop scan period has the effect of process dead time. Increasing the scan
period will decrease the ratio and the allowable gain. Also, adding any lag smaller
than the longest lag, (for example, adding a large well to a thermocouple or a
filter to a noisy loop) will decrease the allowable gain.
Flow loops are too fast to use the standard methods of analysis and tuning. The
speed of the loop compared to the update rate of the display prevents collection of
the data for either the open loop or closed loop methods. However, there are some
rules of thumb regarding the tuning of flow loops.
The guidelines above are based on digital controller such as that used in
Distributed Control Systems. Some flow loops using analog controllers are tuned
with higher gain. However, the same loop may go unstable if a digital controller is
used.
While normally a digital control system will provide response very similar to that
of an analog control system, the performance can be quite different with fast loops
such as flow. With an analog controller, the flow loop has a time constant (τ) of a
few seconds and pseudo dead time much smaller than one second. However, with
a digital controller, the scan rate of the controller can be considered dead time.
Although this dead time is small, it is large enough when compared to τ to cause
instability when the gain is higher than one.
Multiple Variable Strategies 44
Ratio Control (Chapter 9 ) maintains a single control loop (a flow loop) at its set
point, however that set point is manipulated to maintain that flow at a desired
ratio to another flow.
CHAPTER 8 CASCADE
Cascade is the most common form of multiple variable control. In cascade control
the controller manipulates the set point of another controller rather than a final
control element. In this chapter we will discuss when it is used, how it is applied,
and how it is tuned.
8.1 BASICS
In many processes there some process variables that we want to hold at a specific
desired value, and other intermediate variables that change as necessary to hold
the first type of variable at its desired set point. For example, in Figure 44 the
temperature of liquid leaving the heat exchanger is our controlled variable, the
one we want to hold at a set point, and we will do so by manipulating the steam
valve. The flow of steam to the exchanger directly affects the temperature, but we
do not care how much is flowing as long as the temperature is controlled.
The amount of steam required will depend upon the flow rate of process fluid and
the difference between the inlet temperature and the set point of the outlet
temperature.
Cascade 46
We can control the temperature using a single PID controller with the temperature
as its input and its output connected to the steam valve, as shown in Figure 45.
This arrangement will control the temperature. However, there are some problems
in the control:
The steam header pressure may change, causing a sudden reduction in the steam
flow to the exchanger. The temperature controller will bring the temperature back
to its set point, but, because of the slow tuning required of the temperature
controller, the correction will take longer than desired.
The temperature loop, likely containing multiple lags and dead time, is a more
difficult loop to tune. Non-linearities in the valve will further complicate the
tuning.
Use of cascade control, as shown in Figure 46, will correct both of these
problems. If the header pressure changes, causing a change in the flow, that
change will be detected by the flow measurement and immediately corrected.
Cascade 47
Steam
FT
100
Process Fluid
The “outer” loop of a cascade loop pair is called the primary loop. This loop
controls the variable that must be held at a specific set point. The “inner” loop of
the pair is called the secondary loop. This loop controls the variable that will
influence the primary variable. The primary and secondary loops are sometimes
referred to as the “master” and “slave” loops.
Primary Setpoint
Primary Secondary
Controller Controller
Primary Secondary
Process Process
• A variable that has a great influence over the primary variable exists,
• This variable has a dynamic time at least four times faster than the primary
loops dynamics,
Cascade 48
• The variable can easily be controlled.
Other factors that will influence the decision to use cascade are:
• If there are time in which the operator will need to control the secondary
variable directly (such as during startup), the secondary loop will be
needed, so, as long as the guidelines above are met, cascade may as well
be implemented.
At one time there was a greater cost of cascade, and it caused more complexity for
the operator. However, with modern DCS and other digital control systems the
only cost of cascade is the cost of measuring the secondary variable, and the
operational complexity can be reduced.
In most cases a cascade loop does not always operate in full cascade operation,
just as a simple PID loop is not always in automatic.
Some manufactures provide, in the PID block, a single mode “switch” with the
options of Manual, Auto, and Cascade (or remote set point). Other manufacturers
provide two switches, Manual/Auto and Local set point/Remote set point. Either
way, the operator will have the ability to place the control loop into manual, and
manipulate the output to the valve directly; auto, with the ability to manipulate the
set point of the secondary loop; and cascade (or remote set point) to allow the
primary controller to operate in automatic and control the process.
Cascade 49
A) Manual Mode Secondary set point
Steam tracks secondary Primary output
measurement tracks secondary set
FT
100 point
Process Fluid
Shell and Tube Heat
Exchanger
B) Auto Mode
Steam Primary output
tracks secondary set
FT
100 point
Process Fluid
Shell and Tube Heat
Exchanger
C) Cascade Mode
Steam
Operator
FT
100 manipulates set
point of primary
Steam FIC TIC
Temperature
Valve 100 101
Controller
Flow Controller
(primary)
(secondary)
TT Temperature
101 Measurement
Process Fluid
Shell and Tube Heat
Exchanger
In Figure 48 B, while the operator adjusts the set point of the flow controller the
output of the temperature controller continues to track the flow set point. So when
the operator switches the flow control to cascade (see Figure 48 C) the output of
the temperature controller is already at the correct value for that time, and there is
no immediate change in the flow set point or the output to the valve. After the
switch to cascade, if the operator adjusts the temperature set point or there are
load changes, the temperature controller will manipulate the flow controller to
increase or decrease the steam flow as needed.
8.4.2 Windup
Windup is caused when the reset function of a controller causes the output of the
controller to continue to change even though the change in output has no effect on
the process. (see Section 4.1).
This affect cascade control when the output of the primary controller drives the
set point of the secondary controller above the highest possible process
measurement. The valve is opened fully, but the set point of the primary is not
satisfied, so the output of the primary, and the set point of the secondary,
continues to increase.
To use the example of the heat exchanger, suppose that the process liquid being
heated enters the exchanger colder than normal. The temperature controller
increases the steam flow set point, causing the steam valve fully open. Assume
that the upper limit of the range of the steam flow set point is greater than the
maximum steam flow with the valve fully open, and that with the valve fully
open, there is not enough steam to heat the process fluid to its set point. The
temperature controller will continue to ramp up its output until the output reaches
a limit, typically 100%. At this point the temperature controller is “asking” the
flow controller to provide more steam than is possible. The temperature controller
is “wound up”.
Even if the temperature almost reaches its set point, this windup will eventually
occur because the reset action of the controller will continue to ramp up the output
until the temperature reaches or exceeds its set point.
At this point, the only problem that has occurred is the deviation in the set point.
The windup is not yet an issue. However, suppose that the temperature of the
process fluid flowing to the heat exchanger increases. The full flow of steam is
now more than sufficient to heat the fluid to its set point, and the temperature will
increase. Once the temperature crosses the set point the output will begin to
decrease. However, it will have to decrease from 100% to the value (in percent) of
the actual steam flow before the valve will begin to close. By the time this occurs
the temperature may well have climbed to well above the set point. It is this “wind
down” that is the problem with reset windup.
Cascade 51
Reset windup in this case could be prevented by setting a limit on the output of
the controller to the value that corresponds to the maximum steam flow. However,
in some cases the maximum steam flow is not always the same. In the next
section we will examine another, more general, method of preventing reset
windup in cascade loops.
One method of eliminating reset windup in the primary loop is to connect the
secondary loop’s process variable (converted from measurement units to percent)
to the external feedback of the primary controller. (See section 4.2).
Steam
FT
100
External
Feedback
Steam FIC TIC
Temperature
Valve 100 101
Controller
Flow Controller (primary)
(secondary)
TT Temperature
101 Measurement
Process Fluid
Because the output of the primary controller is the error multiplied by the gain,
the primary controller will be “asking” the secondary controller for more steam
than is actually flowing if the temperature is too low, but will “ask” for less steam
one the temperature rises above its set point. The secondary controller will
respond by beginning to close the valve at that point.
Cascade 52
Set Point
X Gain UL
LL
LAG
Controller
Set Point
X Gain UL
LL
LAG
Controller
Temperature Flow
Measurement Measurement
Flow
Valve
The secondary loop is tuned first, using the tuning methods described in Chapter 6
When the loops is tuned, careful attention should be paid to the response to set
point changes. The primary loop is left in manual while the secondary loop is
tuned.
After the secondary loop is tuned, the primary loop is tuned with the secondary
loop in automatic.
Ratio 53
CHAPTER 9 RATIO
Ratio is another common form of multiple loop control. The object of ratio
control is to maintain two or more flows at a constant ratio even when the flows
are changing. Most often, the flows being control are blended, that is, mixed
together. However, there are some situations where flows not mixed together are
controlled by ratio control. For example, we may wish to maintain a flow of steam
to the reboiler of a distillation column in ratio with the feed to the column even
though the two never mix. For most examples and discussion here we will use the
flow mixing example.
9.1 BASICS
Ratio control usually involves the control of one flow (known as the “controlled
flow”) in ratio to another flow (known as the “wild flow”). The wild flow may be
controlled; if so it is controlled by an unrelated loop.
FT FF
101 102
Wild Flow
Remote
Set Point
FIC
102
Mixed Flow
FT
102
Controlled Flow
In actual implementation on most control systems, the remote set point to the
controlled flow controller (FIC-102) is expecting a percentage signal (100% will
result in a set point at the maximum range of the controller). Therefore the ratio
unit (FF-102) will multiply the actual flow by the ratio and then convert the signal
to a percentage based on the range of FIC-120. In some cases, the controller may
be able to accept a remote set point in engineering units, requiring no
Ratio 54
normalization. In most cases the operator will be able to adjust the ratio in FF-
102.
Just as in the case of cascade loops, the operator will have a choice of operating
the controlled flow controller in manual, adjusting the valve position directly,
placing the flow controller in automatic and adjusting the set point, or placing the
controlled flow controller into remote set point (cascade) mode and allowing the
ratio control to take place. This mode change will likely take place during the
startup of the process.
In order to prevent a “bump”, or sudden change in the set point of the flow
controller when the operator switches from local set point to remote set point
(ratio control) the ratio is often recomputed, either continuously while the
controller is in local set point or when the switch to ratio control is made, so that
the ratio at the time of the switch is the actual ratio. After the switch to ratio
control the operator can then adjust the ratio.
Remote
FT FF Ratio Adjustment
101 102
Wild Flow
AIC
103
Remote
Set Point Physical Property
FIC Measurement
102
Mixed Flow
FT
102
Controlled Flow
A special case of ratio control is the air/fuel ratio in the combustion controls for a
boiler or furnace.
The fuel flow is typically measured in gallons per minute for fuel oil or standard
cubic feet per minute for gas. The air is not usually measured and indicated in any
particular engineering units. The measurement range for the air is the range that
corresponds to the range for the fuel (for example, if the fuel flow is at 75% of its
range, the corresponding air flow will also be 75% of its range).
Normally a slight excess of air is supplied to the boiler. As the demand for heat
(the firing rate) increases and decreases, the boiler master will increase and
decrease the set points of the air and fuel flows simultaneously. To adjust the ratio
of air to fuel, the typical scheme places a multiplier in the air loop between the
input from the air flow signal and the air flow controller. To increase the air/fuel
ratio, the value of the multiplier is decreased, causing the flow controller to “see”
a reduced air flow and open the damper.
Ratio 56
Air Header Fuel
O2 Flow Flow
Pressure
AT FT PT FT
102 101 100 102
AIC FFY
102 101 PIC Boiler
100 Master
Air/Fuel
Ratio
Control
FIC FIC
101 102
Remote Remote
Set Point Set Point
As shown in Figure 53, the air/fuel ratio can be a multiplier adjusted by the
operator or it can be a cascade with the remote signal from the output of an O2
controller. This controller will measure the O2 in the stack gas and manipulate the
ratio to keep the stack O2 at the correct value.
Override 57
CHAPTER 10 OVERRIDE
In most cases the manipulation of a valve will be done by a control loop to hold
one particular process variable at its set point. However, there are situations where
there are other factors that may be more important than keeping the particular
control valve at its set point.
For example, we may have a control loop that admits the correct amount of steam
into a heat exchange to produce hot water at the correct temperature. However,
we might then decide that we must prevent the pressure in the steam header from
falling below a given value even if doing so prevents the water from being heated
to its set point.
We might also have a flow loop that draws a desired amount of water from a tank.
But we decide that if the tank level is too low, we will cut back on the water we
draw, even below the set point for water flow, to protect the pump from low level.
To implement this control we add a second controller (PIC-102) and a low signal
selector (a device or software function block with two inputs. The output is equal
to the lowest of the two inputs), shown in the diagram as a circle with a “less
than” symbol (<).
The set point of PIC-200 is the low limit for the steam header pressure. If the
header pressure is above the set point the output of the controller will remain
high, not affecting TIC-101 and its manipulation of the valve. However, if the
header pressure drops below the set point of PIC-200, the output of the pressure
controller will decrease below the output of TIC-101, taking over the control of
the valve.
Override 58
Steam Header
PT
102
Pressure
Steam PIC Controller
to Heater 102
Temperature
TIC Controller
< 101
TT
101
External Feedback
Hot Water
In our example when the pressure controller takes control of the steam valve away
from the temperature controller the temperature will fall below its set point. The
temperature controller will respond by increasing its set point in an attempt to
open the valve. However, because the pressure controller and low selector
prevents the temperature controller from opening the valve, the temperature
controller will be open loop. In its vain attempt to open the steam valve the reset
of the temperature controller will drive its output up to 100% (or other limit). This
is known as reset windup.
If, in our example in the previous section, the temperature controller does not
have control of the steam valve the temperature falls below its set point, the
integral action in the controller will cause the output to continue to increase until
it reaches 100%. This is known as reset windup.
The problem with reset windup is that after the header pressure reaches its set
point and the pressure controller output increases, the valve will continue to open.
The temperature controller will not begin to close the valve until the temperature
rises above its set point. Then, as the temperature rises above its set point the
controller will lower the output. This "reset winddown" will cause an overshoot in
the temperature set point.
Override 59
10.2.1 One solution: External Feedback.
If the PID algorithm uses a positive feedback loop for integration, then that
positive feedback loop can use the output of the selector (the signal to the valve)
as the feedback.
The external feedback (EF on the diagram) is the output of the low selector. The
output of the temperature controller is the gain multiplied by the error added to
the external feedback. If the error is positive (temperature below set point) the
output of the temperature controller is higher than the output of the selector.
However, when the temperature rises and equals the set point, the error will be
zero and the controller output will equal the selector output.
As soon as the temperature exceeds the set point (negative error) the output of the
controller will be less than the output of the selector, decreasing the output of the
selector and closing the valve.
A special case of override control is the “cross limiting” feature shown in Figure
56. (This is normally part of the combustion control shown in Figure 53 but was
left off for simplicity)
If the measured fuel flow exceeds the firing rate demand (output from the
pressure control) the high selector will pass the measured fuel flow (in percent)
rather than the firing rate to the set point of the air flow control. If the measured
air flow is below the firing rate demand signal the low selector will pass the air
flow signal rather than the firing rate demand to the set point of the fuel flow.
This will assure that the fuel flow will not exceed the air flow even if either flow
is slow to respond to its controller.
Override 60
Air Header Fuel
O2 Flow Flow
Pressure
AT FT PT FT
102 101 100 102
AIC FFY
102 101 PIC Boiler
100 Master
Air/Fuel
Ratio
Control
FIC
101 > < FIC
102
Remote Remote
Set Point Set Point
CHAPTER 11 FEEDFORWARD
If instead we can measure the loads and change the manipulated variable to
anticipate the effect of the load change we might keep the controlled variable
from departing from the set point (or, at least, keep the error short). This strategy
is called feedforward control.
Steam
FT
103
FT TT
102 100 Shell and Tube Heat Feedforward
Exchanger Calculation
In the example shown in Figure 57 the feed forward calculation block calculates
the amount of steam needed to heat the process fluid to the set point based on the
flow and inlet temperature. This calculation is known as the “feed forward
calculation”.
Because there are usually disturbances that cannot be measured and the feed
forward calculation is not perfect, the calculation will not result in the exact
amount of steam flow. Therefore the output of the feedback controller is added to
the feed forward calculation to continuously trip the steam flow set point to keep
the temperature at its set point.
Bibliography 62
CHAPTER 12 BIBLIOGRAPHY
6. H. Wade, Course notes for Principles of Applied Automatic Control (an ISA short course),
Instrument Society of America, 1992.
7. J. Shaw, Analysis of Traditional PID Tuning Methods, presented at the Instrument Society
of America conference, Chicago, IL, September, 1993.