7UT612 Manual V40R01 76
7UT612 Manual V40R01 76
7UT612 Manual V40R01 76
L Y
Manual
1 2 3 4 A
C53000G1176C1481
Liability statement We have checked the contents of this manual against the described hardware and software. Nevertheless, deviations may occur so that we cannot guarantee the entire harmony with the product. The contents of this manual will be checked in periodical intervals, corrections will be made in the following editions. We look forward to your suggestions for improvement. We reserve the right to make technical improvements without notice. 4.00.01
Copyright Copyright SIEMENS AG 2002. All rights reserved. Copying of this document and giving it to others and the use or communication of the contents thereof, are forbidden without express authority. Offenders are liable to the payment of damages. All rights are reserved, especially in the event or grant of a patent or registration of a utility model or design. Registered trademarks SIPROTEC, SINAUT, SICAM, and DIGSI are registered trademarks of SIEMENS AG. Other names and terms can be trademarks the use of which may violate the rights of thirds.
Preface
Aim of This Manual This manual describes the functions, operation, installation, and commissioning of the device. In particularly, you will find: Description of the device functions and setting facilities Chapter 2, Instruction for installation and commissioning Chapter 3, List of the technical data Chapter 4, As well as a compilation of the most significant data for experienced users in the Appendix. General information about design, configuration, and operation of SIPROTEC devices are laid down in the SIPROTEC 4 system manual, order no. E50417H1176 C151. Target Audience Protection engineers, commissioning engineers, persons who are involved in setting, testing and service of protection, automation, and control devices, as well as operation personnel in electrical plants and power stations. This manual is valid for SIPROTEC 7UT612 differential protection; firmware version 4.0. Indication of Conformity This product complies with the directive of the Council of the European Communities on the approximation of the laws of the member states relating to electromagnetic compatibility (EMC Council Directive 89/336/EEC) and concerning electrical equipment for use within specified voltage limits (Low-voltage Directive 73/23/EEC). This conformity has been proved by tests conducted by Siemens AG in accordance with Article 10 of the Council Directive in agreement with the generic standards EN 50081 and EN 50082 (for EMC directive) and the standards EN 60255-6 (for lowvoltage directive). This product is designed and manufactured for application in industrial environment. The product conforms with the international standards of IEC 60255 and the German standards DIN 57435 part 303 (corresponding to VDE 0435 part 303).
Further Standards
ANSI C37.90.*.
Preface
Additional Support
Should further information be desired or should particular problems arise which are not covered sufficiently for the purchasers purpose, the matter should be referred to the local Siemens representative. Individual course offerings may be found in our Training Catalogue, or questions may be directed to our training center. Please contact your Siemens representative. The warnings and notes contained in this manual serve for your own safety and for an appropriate lifetime of the device. Please observe them! The following terms are used:
Training Courses
DANGER
indicates that death, severe personal injury or substantial property damage will result if proper precautions are not taken.
Warning
indicates that death, severe personal injury or substantial property damage can result if proper precautions are not taken.
Caution
indicates that minor personal injury or property damage can result if proper precautions are not taken. This particularly applies to damage on or in the device itself and consequential damage thereof.
Note indicates information about the device or respective part of the instruction manual which is essential to highlight.
Warning!
Hazardous voltages are present in this electrical equipment during operation. Non observance of the safety rules can result in severe personal injury or property damage. Only qualified personnel shall work on and around this equipment after becoming thoroughly familiar with all warnings and safety notices of this manual as well as with the applicable safety regulations. The successful and safe operation of this device is dependent on proper handling, installation, operation, and maintenance by qualified personnel under observance of all warnings and hints contained in this manual. In particular the general erection and safety regulations (e.g. IEC, DIN, VDE, EN or other national and international standards) regarding the correct use of hoisting gear must be observed. Nonobservance can result in death, personal injury or substantial property damage.
QUALIFIED PERSONNEL
For the purpose of this instruction manual and product labels, a qualified person is one who is familiar with the installation, construction and operation of the equipment and the hazards involved. In addition, he has the following qualifications: Is trained and authorized to energize, de-energize, clear, ground and tag circuits and equipment in accordance with established safety practices.
ii
Preface
Is trained in the proper care and use of protective equipment in accordance with established safety practices. Is trained in rendering first aid. Typographic and Symbol Conventions The following text formats are used when literal information from the device or to the device appear in the text flow: 3DUDPHWHU QDPHV, i.e. designators of configuration or function parameters which may appear word-for-word in the display of the device or on the screen of a personal computer (with operation software DIGSI 4), are marked in bold letters of a monospace type style. 3DUDPHWHU RSWLRQV, i.e. possible settings of text parameters, which may appear word-for-word in the display of the device or on the screen of a personal computer (with operation software DIGSI 4), are written in italic style, additionally. $QQXQFLDWLRQV, i.e. designators for information, which may be output by the relay or required from other devices or from the switch gear, are marked in a monospace type style in quotation marks. Deviations may be permitted in drawings when the type of designator can be obviously derived from the illustration. The following symbols are used in drawings:
Earth fault
device-internal logical input signal device-internal logical output signal internal input signal of an analogue quantity external binary input signal with function number Fno external binary output signal with function number Fno
Earth fault
UL1L2
FNo 567
>Release
FNo 5432
Dev. Trip
Parameter address Parameter name
example of a parameter switch designated )81&7,21 with the address and the possible settings 2Q and 2II
Besides these, graphical symbols are used according to IEC 6061712 and IEC 6061713 or similar. Some of the most frequently used are listed below:
OR gate
iii
Preface
&
signal inversion
AND gate
=1
ExclusiveOR gate (antivalence): output is active, if only one of the inputs is active Coincidence gate (equivalence): output is active, if both input are active or inactive at the same time Dynamic inputs (edgetriggered) above with positive, below with negative edge Formation of one analogue output signal from a number of analogue input signals (example: 3)
!% Du33
Iph>
!%
T
UDu33
0
Timer (pickup delay T, example adjustable) with setting address and parameter designator (name)
S R
Q Q
Static memory (RSflipflop) with setting input (S), resetting input (R), output (Q) and inverted output (Q)
Furthermore, the graphic symbols according IEC 6061712 and IEC 6061713 or similar are used in most cases. n
iv
Table of Contents
Preface................................................................................................................................................... i
Introduction.......................................................................................................................................... 1 1.1 1.2 1.3 Overall Operation ................................................................................................................... 2 Applications ............................................................................................................................ 5 Features ................................................................................................................................. 7
Functions............................................................................................................................................ 13 2.1 2.1.1 2.1.2 2.1.2.1 2.1.2.2 2.1.3 2.1.3.1 2.1.3.2 2.1.4 2.1.4.1 2.2 2.2.1 2.2.2 2.2.3 2.2.4 2.2.5 2.2.6 2.2.7 2.2.8 2.2.9 General................................................................................................................................. 14 Configuration of the Scope of Functions .............................................................................. 14 Power System Data 1........................................................................................................... 20 Setting Overview .................................................................................................................. 28 Information Overview............................................................................................................ 30 Setting Groups ..................................................................................................................... 30 Setting Overview .................................................................................................................. 31 Information Overview............................................................................................................ 31 General Protection Data (Power System Data 2)................................................................. 32 Information Overview............................................................................................................ 32 Differential Protection ........................................................................................................... 33 Fundamentals of Differential Protection ............................................................................... 33 Differential Protection for Transformers................................................................................ 42 Differential Protection for Generators, Motors, and Series Reactors ................................... 48 Differential Protection for Shunt Reactors ............................................................................ 49 Differential Protection for Mini-Busbars, Branch-Points and Short Lines ............................. 50 Single-Phase Differential Protection for Busbars ................................................................. 52 Setting the Function Parameters .......................................................................................... 56 Setting Overview .................................................................................................................. 61 Information Overview............................................................................................................ 62
Table of Contents
2.3 2.3.1 2.3.2 2.3.3 2.3.4 2.4 2.4.1 2.4.1.1 2.4.1.2 2.4.1.3 2.4.1.4 2.4.1.5 2.4.1.6 2.4.2 2.4.2.1 2.4.2.2 2.4.3 2.4.4 2.5 2.5.1 2.5.1.1 2.5.1.2 2.5.1.3 2.5.1.4 2.5.1.5 2.5.2 2.5.3 2.5.4 2.6 2.6.1 2.6.2 2.6.3 2.6.4 2.7 2.7.1 2.7.2 2.7.3 2.7.4 2.7.5 2.7.6
Restricted Earth Fault Protection.......................................................................................... 64 Function Description ............................................................................................................. 66 Setting the Function Parameters .......................................................................................... 71 Setting Overview................................................................................................................... 72 Information Overview............................................................................................................ 72 Time Overcurrent Protection for Phase and Residual Currents ........................................... 73 Function Description ............................................................................................................. 73 Definite Time Overcurrent Protection ................................................................................... 73 Inverse Time Overcurrent Protection.................................................................................... 76 Manual Close Command ...................................................................................................... 79 Dynamic Cold Load Pickup................................................................................................... 79 Inrush Restraint .................................................................................................................... 79 Fast Busbar Protection Using Reverse Interlocking ............................................................. 81 Setting the Function Parameters .......................................................................................... 82 Phase Current Stages .......................................................................................................... 82 Residual Current Stages....................................................................................................... 88 Setting Overview................................................................................................................... 92 Information Overview............................................................................................................ 94 Time Overcurrent Protection for Earth Current..................................................................... 97 Function Description ............................................................................................................. 97 Definite Time Overcurrent Protection ................................................................................... 97 Inverse Time Overcurrent Protection.................................................................................... 99 Manual Close Command .................................................................................................... 101 Dynamic Cold Load Pickup................................................................................................. 101 Inrush Restraint .................................................................................................................. 101 Setting the Function Parameters ........................................................................................ 102 Setting Overview................................................................................................................. 106 Information Overview.......................................................................................................... 107 Dynamic Cold Load Pickup for Time Overcurrent Protection ............................................. 108 Function Description ........................................................................................................... 108 Setting the Function Parameters ........................................................................................ 111 Setting Overview................................................................................................................. 111 Information Overview.......................................................................................................... 112 Single-Phase Time Overcurrent Protection ........................................................................ 113 Function Description ........................................................................................................... 113 High-Impedance Differential Protection .............................................................................. 115 Tank Leakage Protection.................................................................................................... 117 Setting the Function Parameters ........................................................................................ 118 Setting Overview................................................................................................................. 121 Information Overview.......................................................................................................... 122
vi
Table of Contents
2.8 2.8.1 2.8.1.1 2.8.1.2 2.8.2 2.8.3 2.8.4 2.9 2.9.1 2.9.2 2.9.3 2.9.4 2.9.5 2.10 2.10.1 2.10.2 2.10.3 2.10.4 2.11 2.11.1 2.11.2 2.11.3 2.11.4 2.12 2.12.1 2.12.2 2.12.3 2.12.4 2.13 2.13.1 2.13.1.1 2.13.1.2 2.13.1.3 2.13.1.4 2.13.1.5 2.13.1.6 2.13.1.7 2.13.2 2.13.3 2.13.4
Unbalanced Load Protection .............................................................................................. 123 Function Description........................................................................................................... 123 Definite Time Stages .......................................................................................................... 123 Inverse Time Stage ............................................................................................................ 124 Setting the Function Parameters ........................................................................................ 126 Setting Overview ................................................................................................................ 129 Information Overview.......................................................................................................... 130 Thermal Overload Protection.............................................................................................. 131 Overload Protection Using a Thermal Replica ................................................................... 131 Hot-Spot Calculation and Determination of the Ageing Rate ............................................. 133 Setting the Function Parameters ........................................................................................ 137 Setting Overview ................................................................................................................ 141 Information Overview.......................................................................................................... 142 Thermoboxes for Overload Protection................................................................................ 143 Function Description........................................................................................................... 143 Setting the Function Parameters ........................................................................................ 143 Setting Overview ................................................................................................................ 145 Information Overview.......................................................................................................... 150 Circuit Breaker Failure Protection....................................................................................... 152 Function Description........................................................................................................... 152 Setting the Function Parameters ........................................................................................ 155 Setting Overview ................................................................................................................ 156 Information Overview.......................................................................................................... 156 Processing of External Signals........................................................................................... 157 Function Description........................................................................................................... 157 Setting the Function Parameters ........................................................................................ 158 Setting Overview ................................................................................................................ 158 Information Overview.......................................................................................................... 159 Monitoring Functions .......................................................................................................... 160 Function Description........................................................................................................... 160 Hardware Monitoring .......................................................................................................... 160 Software Monitoring............................................................................................................ 161 Monitoring of Measured Quantities..................................................................................... 161 Trip Circuit Supervision ...................................................................................................... 162 Fault Reactions .................................................................................................................. 165 Group Alarms ..................................................................................................................... 166 Setting Errors ..................................................................................................................... 167 Setting the Function Parameters ........................................................................................ 167 Setting Overview ................................................................................................................ 168 Information Overview ......................................................................................................... 169
vii
Table of Contents
2.14 2.14.1 2.14.2 2.14.3 2.14.4 2.14.5 2.15 2.15.1 2.15.1.1 2.15.1.2 2.15.1.3 2.15.1.4 2.15.1.5 2.15.1.6 2.15.2 2.15.3 2.15.4 2.15.5 2.15.6 2.16 2.16.1 2.16.2
Protection Function Control ................................................................................................ 171 Fault Detection Logic of the Entire Device.......................................................................... 171 Tripping Logic of the Entire Device..................................................................................... 172 Setting the Function Parameters ........................................................................................ 173 Setting Overview................................................................................................................. 174 Information Overview.......................................................................................................... 174 Ancillary Functions.............................................................................................................. 175 Processing of Messages..................................................................................................... 175 General ............................................................................................................................... 175 Event Log (Operating Messages) ....................................................................................... 177 Trip Log (Fault Messages).................................................................................................. 177 Spontaneous Annunciations ............................................................................................... 178 General Interrogation.......................................................................................................... 178 Switching Statistics ............................................................................................................. 178 Measurement during Operation .......................................................................................... 179 Fault Recording .................................................................................................................. 183 Setting the Function Parameters ........................................................................................ 183 Setting Overview................................................................................................................. 184 Information Overview.......................................................................................................... 185 Processing of Commands................................................................................................... 189 Types of Commands........................................................................................................... 189 Steps in the Command Sequence ...................................................................................... 190
2.16.3 Interlocking ......................................................................................................................... 191 2.16.3.1 Interlocked/Non-Interlocked Switching ............................................................................... 191 2.16.4 2.16.5 Recording and Acknowledgement of Commands............................................................... 194 Information Overview.......................................................................................................... 195
Installation and Commissioning..................................................................................................... 197 3.1 3.1.1 3.1.2 3.1.3 3.1.3.1 3.1.3.2 3.1.3.3 3.1.3.4 3.1.3.5 3.2 3.2.1 3.2.2 Mounting and Connections ................................................................................................. 198 Installation .......................................................................................................................... 198 Termination Variants........................................................................................................... 201 Hardware Modifications ...................................................................................................... 205 General ............................................................................................................................... 205 Disassembling the Device .................................................................................................. 207 Jumper Settings on Printed Circuit Boards......................................................................... 209 Interface Modules ............................................................................................................... 213 To Reassemble the Device................................................................................................. 217 Checking the Connections.................................................................................................. 218 Data Connections of the Serial Interfaces .......................................................................... 218 Checking Power Plant Connections ................................................................................... 220
viii
Table of Contents
3.3 3.3.1 3.3.2 3.3.3 3.3.4 3.3.5 3.3.6 3.3.7 3.3.8 3.3.9 3.3.10 3.3.11 3.4
Commissioning ................................................................................................................... 222 Testing Mode and Transmission Blocking.......................................................................... 223 Checking the System (SCADA) Interface........................................................................... 223 Checking the Binary Inputs and Outputs ............................................................................ 225 Checking the Setting Consistency...................................................................................... 227 Checking for Breaker Failure Protection............................................................................. 228 Symmetrical Current Tests on the Protected Object .......................................................... 230 Zero Sequence Current Tests on the Protected Object ..................................................... 236 Checking for Busbar Protection.......................................................................................... 240 Checking for Current Input I8 ............................................................................................. 242 Testing User Specified Functions....................................................................................... 243 Stability Check and Triggering Oscillographic Recordings................................................. 243 Final Preparation of the Device .......................................................................................... 245
Technical Data ................................................................................................................................. 247 4.1 4.1.1 4.1.2 4.1.3 4.1.4 4.1.5 4.1.6 4.1.7 4.1.8 4.1.9 4.2 4.2.1 4.2.2 4.2.3 4.2.4 4.3 4.4 4.5 4.6 4.7 4.8 General Device Data .......................................................................................................... 248 Analog Inputs ..................................................................................................................... 248 Power Supply ..................................................................................................................... 248 Binary Inputs and Outputs .................................................................................................. 249 Communications Interfaces ................................................................................................ 250 Electrical Tests ................................................................................................................... 253 Mechanical Stress Tests .................................................................................................... 255 Climatic Stress Tests.......................................................................................................... 256 Service Conditions.............................................................................................................. 256 Construction ....................................................................................................................... 257 Differential Protection ......................................................................................................... 258 General............................................................................................................................... 258 Transformers ...................................................................................................................... 259 Generators, Motors, Reactors ............................................................................................ 261 Busbars, Branch-Points, Short Lines.................................................................................. 262 Restricted Earth Fault Protection........................................................................................ 263 Time Overcurrent Protection for Phase and Residual Currents ......................................... 264 Time Overcurrent Protection for Earth Current................................................................... 271 Dynamic Cold Load Pickup for Time Overcurrent Protection ............................................. 272 Single-Phase Time Overcurrent Protection ........................................................................ 273 Unbalanced Load Protection .............................................................................................. 274
ix
Table of Contents
Thermal Overload Protection.............................................................................................. 275 Overload Protection Using a Thermal Replica.................................................................... 275 Hot Spot Calculation and Determination of the Ageing Rate.............................................. 277 Thermoboxes for Overload Protection................................................................................ 277 Circuit Breaker Failure Protection....................................................................................... 278 External Trip Commands .................................................................................................... 278 Monitoring Functions .......................................................................................................... 279 Ancillary Functions.............................................................................................................. 280 Dimensions ......................................................................................................................... 282
Appendix........................................................................................................................................... 285 A.1 A.1.1 A.2 A.2.1 A.2.2 A.3 A.4 A.5 A.6 A.7 A.8 A.9 Ordering Information and Accessories ............................................................................... 286 Accessories ........................................................................................................................ 288 General Diagrams............................................................................................................... 291 Panel Flush Mounting or Cubicle Mounting ........................................................................ 291 Panel Surface Mounting ..................................................................................................... 292 Connection Examples......................................................................................................... 293 Assignment of the Protection Functions to Protected Objects............................................ 304 Preset Configurations ......................................................................................................... 305 Protocol Dependent Functions .......................................................................................... 307 List of Settings .................................................................................................................... 308 List of Information ............................................................................................................... 323 List of Measured Values .................................................................................................... 340
Index.................................................................................................................................................. 343 n
Introduction
1
The SIPROTEC 4 devices 7UT612 are introduced in this chapter. An overview of the devices is presented in their application, features, and scope of functions. 1.1 1.2 1.3 Overall Operation Applications Features 2 5 7
1 Introduction
1.1
Overall Operation
The numerical differential protection device SIPROTEC 7UT612 is equipped with a powerful microcomputer system. This provides fully numerical processing of all functions in the device, from the acquisition of the measured values up to the output of commands to the circuit breakers. Figure 1-1 shows the basic structure of the device.
Analog Inputs
The measuring inputs MI transform the currents derived from the instrument transformers and match them to the internal signal levels for processing in the device. The device includes 8 current inputs.
MI
IL1S1 IL2S1 IL3S1 IL1S2 IL2S2 IL3S2
IA
AD
OA
ERROR RUN
I7 I8
(17(5
7 4 1 .
8 5 2 0
9 6 3 +/-
to PC
Time synchronization
radio clock
PC/modem/ thermobox
PS
Uaux
Power supply Serial system interface
to SCADA
Figure 1-1
Hardware structure of the numerical differential protection 7UT612 example for a twowinding transformer with sides S1 and S2
Three current inputs are provided for the input of the phase currents at each end of the protected zone, a further measuring input (I7) may be used for any desired current, e.g. the earth current measured between the starpoint of a transformer winding and ground. The input I8 is designed for highly sensitive current detection thus allowing, for example, the detection of small tank leakage currents of power transformers or reactors, or with an external series resistor processing of a voltage (e.g. for highimpedance unit protection). The analog signals are then routed to the input amplifier group IA. The input amplifier group IA ensures a high impedance termination for the measured signals. It contains filters which are optimized in terms of band width and speed with regard to the signal processing. The analog/digital converter group AD has a multiplexer, analog/digital converters and memory modules for the data transfer to the microcomputer system C. Microcomputer System Apart from processing the measured values, the microcomputer system C also executes the actual protection and control functions. In particular, the following are included: Filtering and conditioning of measured signals. Continuous supervision of measured signals. Monitoring of the pickup conditions of each protection function. Conditioning of the measured signals, i.e. conversion of currents according to the connection group of the protected transformer (when used for transformer differential protection) and matching of the current amplitudes. Formation of the differential and restraint quantities. Frequency analysis of the phase currents and restraint quantities. Calculation of the RMS-values of the currents for thermal replica and scanning of the temperature rise of the protected object. Interrogation of threshold values and time sequences. Processing of signals for the logic functions. Reaching trip command decisions. Storage of fault messages, fault annunciations as well as oscillographic fault data for system fault analysis. Operating system and related function management such as e.g. data recording, real time clock, communication, interfaces etc. The information is provided via output amplifier OA. Binary Inputs and Outputs The microcomputer system obtains external information through binary inputs such as remote resetting or blocking commands for protective elements. The C issues information to external equipment via the output contacts. These outputs include, in particular, trip commands to circuit breakers and signals for remote annunciation of important events and conditions.
1 Introduction
Front Elements
Light-emitting diodes (LEDs) and a display screen (LCD) on the front panel provide information such as targets, measured values, messages related to events or faults, status, and functional status of the 7UT612. Integrated control and numeric keys in conjunction with the LCD facilitate local interaction with the 7UT612. All information of the device can be accessed using the integrated control and numeric keys. The information includes protective and control settings, operating and fault messages, and measured values (see also SIPROTEC System Manual, order-no. E50417H1176C151). The settings can be modified as are discussed in Chapter 2. If the device incorporates switchgear control functions, the control of circuit breakers and other equipment is possible from the 7UT612 front panel.
Serial Interfaces
A serial operating interface on the front panel is provided for local communications with the 7UT612 through a personal computer. Convenient operation of all functions of the device is possible using the SIPROTEC 4 operating program DIGSI 4. A separate serial service interface is provided for remote communications via a modem, or local communications via a substation master computer that is permanently connected to the 7UT612. DIGSI 4 is required. All 7UT612 data can be transferred to a central master or main control system through the serial system (SCADA) interface. Various protocols and physical arrangements are available for this interface to suit the particular application. Another interface is provided for the time synchronization of the internal clock via external synchronization sources. Via additional interface modules further communication protocols may be created. The service interface may be used, alternatively, for connection of a thermobox in order to process external temperatures, e.g. in overload protection.
Power Supply
The 7UT612 can be supplied with any of the common power supply voltages. Transient dips of the supply voltage which may occur during short-circuit in the power supply system, are bridged by a capacitor (see Technical Data, Subsection 4.1.2).
1.2 Applications
1.2
Applications
The numerical differential protection 7UT612 is a fast and selective short-circuit protection for transformers of all voltage levels, for rotating machines, for series and shunt reactors, or for short lines and mini-busbars with two feeders. It can also be used as a single-phase protection for busbars with up to seven feeders. The individual application can be configured, which ensures optimum matching to the protected object. The device is also suited for two-phase connection for use in systems with 162/3 Hz rated frequency. A major advantage of the differential protection principle is the instantaneous tripping in the event of a short-circuit at any point within the entire protected zone. The current transformers limit the protected zone at the ends towards the network. This rigid limit is the reason why the differential protection scheme shows such an ideal selectivity. For use as transformer protection, the device is normally connected to the current transformer sets at the higher voltage side and the lower voltage side of the power transformer. The phase displacement and the interlinkage of the currents due to the winding connection of the transformer are matched in the device by calculation algorithms. The earthing conditions of the starpoint(s) can be adapted to the users requirements and are automatically considered in the matching algorithms. For use as generator or motor protection, the currents in the starpoint leads of the machine and at its terminals are compared. Similar applies for series reactors. Short lines or mini-busbars with two feeders can be protected either. Short means that the connection from the CTs to the device do not cause an impermissible burden for the current transformers. For transformers, generators, motors, or shunt reactors with earthed starpoint, the current between the starpoint and earth can be measured and used for highly sensitive earth fault protection. The seven measured current inputs of the device allow for a single-phase protection for busbars with up to seven feeders. One 7UT612 is used per phase in this case. Alternatively, (external) summation transformers can be installed in order to allow a busbar protection for up to seven feeders with one single 7UT612 relay. An additional current input I8 is designed for very high sensitivity. This may be used e.g. for detection of small leakage currents between the tank of transformers or reactors and earth thus recognizing even high-resistance faults. For transformers (including auto-transformers), generators, and shunt reactors, a high-impedance unit protection system can be formed using 7UT612. In this case, the currents of all current transformers (of equal design) at the ends of the protected zone feed a common (external) high-ohmic resistor the current of which is measured using the high-sensitive current input I8 of 7UT612. The device provides backup time overcurrent protection functions for all types of protected objects. The functions can be enabled for any side. A thermal overload protection is available for any type of machine. This can be complemented by the evaluation of the hot-spot temperature and ageing rate, using an external thermobox to allow for the inclusion of the oil temperature.
1 Introduction
An unbalanced load protection enables the detection of unsymmetrical currents. Phase failures and unbalanced loads which are especially dangerous for rotating machines can thus be detected. A version for 162/3 Hz two-phase application is available for traction supply (transformers or generators) which provides all functions suited for this application (differential protection, restricted earth fault protection, overcurrent protection, overload protection). A circuit breaker failure protection checks the reaction of one circuit breaker after a trip command. It can be assigned to any of the sides of the protected object.
1.3 Features
1.3
Features
Powerful 32-bit microprocessor system. Complete numerical processing of measured values and control, from sampling and digitizing of the analog input values up to tripping commands to the circuit breakers. Complete galvanic and reliable separation between internal processing circuits of the 7UT612 and external measurement, control, and power supply circuits because of the design of the analog input transducers, binary inputs and outputs, and the DC/DC or AC/DC converters. Suited for power transformers, generators, motors, branch-points, or smaller busbar arrangements. Simple device operation using the integrated operator panel or a connected personal computer running DIGSI 4.
Current restraint tripping characteristic. Stabilized against in-rush currents using the second harmonic. Stabilized against transient and steady-state fault currents caused e.g. by overexcitation of transformers, using a further harmonic: optionally the third or fifth harmonic. Insensitive against DC offset currents and current transformer saturation. High stability also for different current transformer saturation. High-speed instantaneous trip on high-current transformer faults. Independent of the conditioning of the starpoint(s) of the power transformer. High earth-fault sensitivity by detection of the starpoint current of an earthed transformer winding. Integrated matching of the transformer connection group. Integrated matching of the transformation ratio including different rated currents of the transformer windings.
Current restraint tripping characteristic. High sensitivity. Short tripping time. Insensitive against DC offset currents and current transformer saturation. High stability also for different current transformer saturation. Independent of the conditioning of the starpoint.
Current restraint tripping characteristic. Short tripping time. Insensitive against DC offset currents and current transformer saturation.
1 Introduction
High stability also for different current transformer saturation. Monitoring of the current connections with operation currents. Bus-Bar Protection Single-phase differential protection for up to seven feeders of a busbar. Either one relay per phase or one relay connected via interposed summation current transformers. Current restraint tripping characteristic. Short tripping time. Insensitive against DC offset currents and current transformer saturation. High stability also for different current transformer saturation. Monitoring of the current connections with operation currents. Restricted Earth Fault Protection Earth fault protection for earthed transformer windings, generators, motors, shunt reactors, or starpoint formers. Short tripping time. High sensitivity for earth faults within the protected zone. High stability against external earth faults using the magnitude and phase relationship of through-flowing earth current. High-Impedance Unit Protection Highly sensitive fault current detection using a common (external) burden resistor. Short tripping time. Insensitive against DC offset currents and current transformer saturation. high stability with optimum matching. Suitable for earth fault detection on earthed generators, motors, shunt reactors, and transformers, including auto-transformers. Suitable for any voltage measurement (via the resistor current) for application of high-impedance unit protection. Tank Leakage Protection For transformers or reactors the tank of which is installed isolated or high resistive against ground. Monitoring of the leakage current flowing between the tank and ground. Can be connected via a normal current input of the device or the special highly sensitive current input (3 mA smallest setting). Time Overcurrent Protection for Phase Currents and Residual Current Two definite time delayed overcurrent stages for each of the phase currents and the residual (threefold zero sequence) current, can be assigned to any of the sides of the protected object. Additionally, one inverse time delayed overcurrent stage for each of the phase currents and the residual current. Selection of various inverse time characteristics of different standards is possible, alternatively a user defined characteristic can be specified.
1.3 Features
All stages can be combined as desired; different characteristics can be selected for phase currents on the one hand and the residual current on the other. External blocking facility for any desired stage (e.g. for reverse interlocking). Instantaneous trip when switching on a dead fault with any desired stage. Inrush restraint using the second harmonic of the measured currents. Dynamic switchover of the time overcurrent parameters, e.g. during cold-load startup of the power plant. Time Overcurrent Protection for Earth Current Two definite time delayed overcurrent stages for the earth current connected at current input I7 (e.g. current between starpoint and earth). Additionally, one inverse time delayed overcurrent stage for the earth current. Selection of various inverse time characteristics of different standards is possible, alternatively a user defined characteristic can be specified. The stages can be combined as desired. External blocking facility for any desired stage (e.g. for reverse interlocking). Instantaneous trip when switching on a dead fault with any desired stage. Inrush restraint using the second harmonic of the measured current. Dynamic switchover of the time overcurrent parameters, e.g. during cold-load startup of the power plant. Single-Phase Time Overcurrent Protection Two definite time delayed overcurrent stages can be combined as desired. For any desired single-phase overcurrent detection. Can be assigned to the current input I7 or the highly sensitive current input I8. Suitable for detection of very small current (e.g. for high-impedance unit protection or tank leakage protection, see above). Suitable for detection of any desired AC voltage using an external series resistor (e.g. for high-impedance unit protection, see above). External blocking facility for any desired stage. Unbalanced Load Protection Processing of the negative sequence current of any desired side of the protected object. Two definite time delayed negative sequence current stages and one additional inverse time delayed negative sequence current stage. Selection of various inverse time characteristics of different standards is possible, alternatively a user defined characteristic can be specified. The stages can be combined as desired. Thermal Overload Protection Thermal replica of current-initiated heat losses. True RMS current calculation. Can be assigned to any desired side of the protected object.
1 Introduction
Adjustable thermal warning stage. Adjustable current warning stage. Alternatively evaluation of the hot-spot temperature according to IEC 60354 with calculation of the reserve power and ageing rate (by means of external temperature sensors via thermobox). Circuit Breaker Failure Protection With monitoring of current flow through each breaker pole of the assigned side of the protected object. Supervision of the breaker position possible (if breaker auxiliary contacts available). Initiation by each of the internal protection functions. Initiation by external trip functions possible via binary input. External Direct Trip Tripping of either circuit breaker by an external device via binary inputs. Inclusion of external commands into the internal processing of information and trip commands. With or without trip time delay. Processing of External Information Combining of external signals (user defined information) into the internal information processing. Pre-defined transformer annunciations for Buchholz protection and oil gassing. Connection to output relays, LEDs, and via the serial system interface to a central computer station. User Defined Logic Functions (CFC) Freely programmable linkage between internal and external signals for the implementation of user defined logic functions. All usual logic functions. Time delays and measured value set point interrogation. Commissioning; Operation Comprehensive support facilities for operation and commissioning. Indication of all measured values, amplitudes and phase relation. Indication of the calculated differential and restraint currents. Integrated help tools can be visualized by means of a standard browser: Phasor diagrams of all currents at all ends of the protected object are displayed as a graph. Connection and direction checks as well as interface check.
10
1.3 Features
Monitoring of the internal measuring circuits, the auxiliary voltage supply, as well as the hard- and software, resulting in increased reliability. Supervision of the current transformer secondary circuits by means of symmetry checks. Check of the consistency of protection settings as to the protected object and the assignment of the current inputs: blocking of the differential protection system in case of inconsistent settings which could lead to a malfunction. Trip circuit supervision is possible. Further Functions Battery buffered real time clock, which may be sychronized via a synchronization signal (e.g. DCF77, IRIG B via satellite receiver), binary input or system interface. Continuous calculation and display of measured quantities on the front of the device. Indication of measured quantities of all sides of the protected object. Fault event memory (trip log) for the last 8 network faults (faults in the power system), with real time stamps (ms-resolution). Fault recording memory and data transfer for analog and user configurable binary signal traces with a maximum time range of 5 s. Switching statistics: counter with the trip commands issued by the device, as well as record of the fault current and accumulation of the interrupted fault currents; Communication with central control and data storage equipment via serial interfaces through the choice of data cable, modem, or optical fibres, as an option. n
Monitoring Functions
11
1 Introduction
12
Functions
2
This chapter describes the numerous functions available on the SIPROTEC 7UT612 relay. The setting options for each function are explained, including instructions to determine setting values and formulae where required. 2.1 2.2 2.3 2.4 2.5 2.6 2.7 2.8 2.9 2.10 2.11 2.12 2.13 2.14 2.15 2.16 General Differential Protection Restricted Earth Fault Protection Time Overcurrent Protection for Phase and Residual Currents Time Overcurrent Protection for Earth Current Dynamic Cold Load Pickup for Time Overcurrent Protection Single-Phase Time Overcurrent Protection Unbalanced Load Protection Thermal Overload Protection Thermoboxes for Overload Protection Circuit Breaker Failure Protection Processing of External Signals Monitoring Functions Protection Function Control Ancillary Functions Processing of Commands 14 33 64 73 97 108 113 123 131 143 152 157 160 171 175 189
13
2 Functions
2.1
General
A few seconds after the device is switched on, the initial display appears in the LCD. In the 7UT612 the measured values are displayed. Configuration settings (Subsection 2.1.1) may be entered using a PC and the software program DIGSI 4 and transferred via the operating interface on the device front, or via the serial service interface. Operation via DIGSI 4 is described in the SIPROTEC 4 System Manual, order no. E50417H1176C151. Entry of password No. 7 (for setting modification) is required to modify configuration settings. Without the password, the settings may be read, but cannot be modified and transmitted to the device. The function parameters, i.e. settings of function options, threshold values, etc., can be entered via the keypad and display on the front of the device, or by means of a personal computer connected to the front or service interface of the device utilising the DIGSI 4 software package. The level 5 password (individual parameters) is required.
2.1.1
General
Note:
Available functions and default settings are depending on the ordering code of the relay (see ordering code in the Appendix for details). Configuration settings may be entered using a PC and the software program DIGSI 4 and transferred via the operating interface on the device front, or via the serial service interface. Operation via DIGSI 4 is described in the SIPROTEC system manual, order number E50417H1176C151 (Section 5.3).
14
2.1 General
Entry of password No. 7 (for setting modification) is required to modify configuration settings. Without the password, the settings may be read, but cannot be modified and transmitted to the device. Special Cases Many of the settings are self-explanatory. The special cases are described below. Appendix A.4 includes a list of the functions with the suitable protected objects. First determine which side of the protected object will be named side 1 and which one will be named side 2. Determination is up to you. If several 7UT612 are used, the sides should be denominated consistently to be able to assign them more easily later on. For side 1 we recommend the following: for transformers the upper voltage side, but, if the starpoint of the lower voltage side is earthed this side is preferred as side 1 (reference side); for generators the terminal side; for motors and shunt reactors the current supply side; for series reactors, lines and busbars there is no side which is preferred. Side determination plays a role for some of the following configuration settings. If the setting group change-over function is to be used, the setting in address *US &KJH 237,21 must be set to (QDEOHG. In this case, it is possible to apply up to four different groups of settings for the function parameters. During normal operation, a convenient and fast switch-over between these setting groups is possible. The setting 'LVDEOHG implies that only one function parameter setting group can be applied and used. The definition of the protected object (address 3527 2%-(&7) is decisive for the possible setting parameters and for the assignment of the inputs and outputs of the device to the protection functions: For normal power transformers with isolated windings set 3527 2%-(&7 = SKDVH WUDQVI regardless of the connection group (winding interconnection) and the earthing conditions of the starpoint(s). This is even valid if an earthing reactor is situated within the protected zone (cf. Figure 2-18, page 45). The option $XWRWUDQVI is selected for auto-transformers. This option is also applicable for shunt reactors if current transformers are installed at both sides of the connection points (cf. Figure 2-25 right side, page 50). For a SKDVH WUDQVI, the phase input L2 is not connected. This option is suited especially to single-phase power transformers with 162/3 Hz (traction transformers). Equal setting is valid for generators and motors. The option *HQHUDWRU0RWRU also applies for series reactors and shunt reactors which latter are equipped with current transformers at both sides. Select the option SK %XVEDU if the device is used for mini-busbars or branchpoints with two ends. This setting applies also for short lines which are terminated by two sets of current transformers. Short means that the current transformer leads between the CTs and the device do not form an impermissible burden for the CTs. The device can be used as single-phase differential protection for busbars with up to 7 feeders, either using one device per phase or one device connected via external summation CTs. Select the option SK %XVEDU in this case. You must inform the device about the number of feeders under address 180%(5 2) (1'6.
15
2 Functions
The measuring input I7 serves often to acquire a starpoint current. Carrying out configurations in address ,&7 &211(&7 the device will be informed on the side the current is assigned to. For transformers select the side where the starpoint is earthed and where the starpoint current is to be measured. For earthed generators and motors it is the side which is looking towards the earthed starpoint. For auto-transformers any side can be selected since there is only one starpoint current for both sides. If the starpoint current is not used for differential protection or for restricted earth fault protection, pre-set the following: QRW XVHG. If restricted earth fault protection is applied, it must be assigned to an earthed side in address 5() 3527. Otherwise this protection function has to be set to 'LVD EOHG. For auto-transformers any side can be used. The overcurrent time protection functions must also be assigned to a specific side of the protected object. For phase overcurrent time protection select the side relevant for this protection in address '07,'07 3KDVH. For generators usually the starpoint side is selected, for motors the terminal side. Otherwise, for single-side infeed we recommend the feeding side. Often, however, an external overcurrent time protection is used for the feeding side. The internal overcurrent time protection of 7UT612 should then be activated for the outgoing side. It is then used as backup protection for faults beyond the outgoing side. To select the characteristic group according to which the phase overcurrent time protection is to operate use address '07,'07 3+ &+. If it is only used as definite time overcurrent protection (DMT), set 'HILQLWH 7LPH. In addition to the definite time overcurrent protection an inverse time overcurrent protection may be configured, if required. The latter operates according to an IEC-characteristic (72& ,(&), to an ANSI-characteristic (72& $16,) or to a user-defined characteristic. In the latter case the trip time characteristic (8VHU 'HILQHG 38) or both the trip time characteristic and the reset time characteristic (8VHU GHI 5HVHW) are configured. For the characteristics please refer to the Technical Data. In address the zero sequence (residual) current time overcurrent protection '07,'07 , can be assigned to any side of the protected object. This does not have to be the same side as for phase overcurrent protection (address , see above). For characteristics the same options are available as for the phase overcurrent protection using address '07,'07 , &+. However, for zero sequence current time overcurrent protection the settings may be different to the settings selected for phase time overcurrent protection. This protection function always acquires the residual current 3I0 of the supervised side. This current is calculated from the sum of the corresponding phase currents. There is another earth current time overcurrent protection which is independent from the before-described zero sequence time overcurrent protection. This protection, to be configured in address '07,'07 (DUWK, acquires the current connected to the current measuring input I7. In most cases, it is the starpoint current of an earthed starpoint (for transformers, generators, motors or shunt reactors). No assignment to a specific side is necessary since this type of protection always acquires the I7 current, no matter where it originates from. For this protection you may select one of the characteristic groups using address '07,'07 ( &+5, the same way as for the phase time overcurrent protection. No matter which characteristic has been selected for the latter. A single-phase definite-time overcurrent protection '07 3+$6( for different userrequirements is available in address . The protection function offers two options.
16
2.1 General
It either acquires the measured current at the normal input I7 (XQVHQV &7) or at highly sensitive input I8 (VHQV &7). The latter case is very interesting since input I8 is able to detect even very small currents (from 3 mA at the input). This protection function is very suited e.g. for highly sensitive tank leakage protection (see also Subsection 2.7.3) or high-impedance unit protection (see also Subsection 2.7.2). This protection is not bound to a specific side or application. Usage is up to the users requirements. In address 81%$/$1&( /2$' the unbalanced load protection can be assigned to a specific side of the protected object, i.e. it supervises the negative sequence current and checks if there is any unbalanced load. The trip time characteristics can be set to definite time ('HILQLWH 7LPH) according to address 81%$/ /2$' &+5, additionally operate according to an IECcharacteristic (72& ,(&) or to an ANSI characteristic (72& $16,). For overload protection select the side whose currents are relevant for overload detection. Use address 7KHUP2YHUORDG. Since the cause for overload comes from outside of the protected object, the overload current is a traversing current. Therefore it does not necessarily have to be effective at the infeeding side. For transformers with tap changer the overload protection is assigned to the nonregulated side as it is the only side where we have a defined relation between rated current and rated power. For generators the overload protection usually is on the starpoint side. For motors and shunt reactors the overload protection is connected to the current transformers of the feeding side. For series reactors, lines and busbars there any side can be selected. Busbars and sections of overhead lines usually do not require overload protection since it is not reasonable to calculate the temperature rise. Climate and weather conditions (temperature, wind) change to quick. On the other hand, the current alarm stage is able to warn of menacing overload. In address 7KHUP2/ &+5 the user can additionally choose between two methods of overload detection: Overload protection with thermal replica according to IEC 60255-8 (FODVVLFDO), Overload protection with calculation of hot-spot temperature and the aging rate according to IEC 60354 (,(&), The first method is characterized by its easy handling and a low number of setting values. The second method requires detailed knowledge about the protected object, the environment it is located in and cooling. The latter one is useful for transformers with integrated temperature detectors. For more information see also Section 2.9. If overload protection with calculation of hot-spot temperature is used according to IEC 60354 (address 7KHUP2/ &+5 = ,(&), at least one thermobox must be connected to the service interface. The thermobox informs the device about the temperature of the coolant. The interface is set in address 57'%2; ,1387. For 7UT612 this is 3RUW &. The number of resistance temperature detectors and the way the thermobox(es) transmit information is set in address 57' &211(&7,21: 57' VLPSOH[ or 57' +'; (with 1 thermobox) or 57' +'; (with 2 thermoboxes). This must comply with the settings at the thermobox(es).
Note: The temperature measuring point relevant for the calculation of the hot-spot temperature should be fed via the first thermobox.
17
2 Functions
For the circuit breaker failure protection set in address %5($.(5 )$,/85( which side is to be monitored. This has to be the side feeding onto an internal fault. For the trip circuit supervision select in address 7ULS &LU 6XS whether it shall operate with 2 ( %LQDU\ ,QSXWV) or only 1 binary input ( %LQDU\ ,QSXW). The inputs have to be isolated.
Setting Options Disabled Enabled 3 phase Transformer 1 phase Transformer Autotransformer Generator/Motor 3 phase Busbar 1 phase Busbar 2
106 107
NUMBER OF SIDES
2 7
Number of Sides for Multi Phase Object Number of Ends for 1 Phase Busbar
NUMBER OF ENDS 3 4 5 6 7 I7-CT CONNECT. not used Side 1 Side 2 Disabled Enabled Disabled Side 1 Side 2 Disabled Enabled Disabled Side 1 Side 2 Definite Time only Time Overcurrent Curve IEC Time Overcurrent Curve ANSI User Defined Pickup Curve User Defined Pickup and Reset Curve Disabled Side 1 Side 2
108
not used
I7-CT connected to
112 113
Enabled Disabled
117 120
Disabled Disabled
121
DMT/IDMT PH. CH
122
DMT/IDMT 3I0
Disabled
18
2.1 General
Addr. 123
Setting Options Definite Time only Time Overcurrent Curve IEC Time Overcurrent Curve ANSI User Defined Pickup Curve User Defined Pickup and Reset Curve Disabled unsensitive Current Transformer I7 Definite Time only Time Overcurrent Curve IEC Time Overcurrent Curve ANSI User Defined Pickup Curve User Defined Pickup and Reset Curve Disabled unsensitive Current Transformer I7 sensitive Current Transformer I8
124
DMT/IDMT Earth
Disabled
125
DMT/IDMT E CHR.
127
DMT 1PHASE
Disabled
DMT 1Phase
140
UNBALANCE LOAD Disabled Side 1 Side 2 UNBAL. LOAD CHR Definite Time only Time Overcurrent Curve IEC Time Overcurrent Curve ANSI Therm.Overload Disabled Side 1 Side 2 classical (according IEC60255) according IEC354 Disabled Side 1 Side 2 Disabled Enabled Disabled with 2 Binary Inputs with 1 Binary Input Disabled Enabled Disabled Enabled Disabled Port C
Disabled
Unbalance Load (Negative Sequence) Unbalance Load (Neg. Sequ.) Characteris. Thermal Overload Protection
141
142
Disabled
143 170
181 182
Enabled Disabled
External Trip Function 1 External Trip Function 2 External Temperature Input Ext. Temperature Input Connection Type
RTD CONNECTION 6 RTD simplex operation 6 RTD half duplex operation 12 RTD half duplex operation
19
2 Functions
2.1.2
General
Rated Frequency
Phase sequence
L1
L1
L3
Clockwise G
L2
L2
Counter-clockwise G
L3
G!G"
G"G!
Figure 2-1
Phase sequence
Temperature Unit
The temperature of the hot-spot temperature calculation can be expressed in degrees &HOVLXV or )DKUHQKHLW. If overload protection with hot-spot temperature is used, set the desired temperature unit in address 7(03 81,7. Otherwise this setting can be ignored. Changing temperature units does not mean that setting values which are linked to these temperature units will automatically be converted. They have to be re-entered into their corresponding addresses. Transformer data are required if the device is used for differential protection for transformers, i.e. if the following was set with the configuration of the protection functions (Subsection 2.1.1, margin heading Special Cases): 3527 2%-(&7 (address ) SKDVH WUDQVI or $XWRWUDQVI or SKDVH WUDQVI. In cases other than that, these settings are not available. Please observe the assignment of the sides when determining winding 1, as abovementioned (Subsection 2.1.1, margin heading Special Cases). Generally, side 1 is the reference winding having a current phase angle of 0 and no vector group indicator. Usually this is the higher voltage winding of the transformer.
20
2.1 General
The device needs the following information: The rated voltage UN in kV (phase-to-phase) under address 8135, 6,'( . The starpoint condition under address 67$5317 6,'( : 6ROLG (DUWKHG or ,VRODWHG. If the starpoint is earthed via a current-limiting circuit (e.g. low-resistive) or via a Petersen-coil (high-reactive), set 6ROLG (DUWKHG, too. The mode of connection of the transformer windings under address &211(& 7,21 6. This is normally the capital letter of the vector group according to IEC. If the transformer winding is regulated then the actual rated voltage of the winding is not used as UN but rather the voltage which corresponds to the average current of the regulated range. The following applies: U max U min 2 U N = 2 ------------------------------- = ------------------------------U max + U min 1 1 ------------ + ----------U max U min where Umax, Umin are the voltages at the limits of the regulated range. Calculation example: Transformer YNd5 35 MVA 110 kV/20 kV Ywinding with tap changer 20 %
This results for the regulated winding (110 kV) in: maximum voltage Umax = 132 kV minimum voltage Umin = 88 kV Setting voltage (address ) 2 2 UN-PRI SIDE 1 = ------------------------------- = ---------------------------------------- = 105.6 kV 1 1 1 1 ------------ + --------------------------- + -------------132 kV 88 kV U max U min For the side 2, the same considerations apply as for the side 1: The rated voltage U N in kV (phase-to-phase) under address 8135, 6,'( , the starpoint condition under address 67$5317 6,'( , and the mode of connection of the transformer windings under address &211(&7,21 6. Additionally, the vector group numeral is set under address 9(&725 *53 6 which states the phase displacement of side 2 against the reference winding, side 1. It is defined according to IEC as the multiple of 30. If the higher voltage side is the reference (side 1), you may set the numeral directly, e.g. for vector group Yd5 or Dy5. Every vector group from 0 to 11 can be set provided it is possible (for instance, Yy, Dd and Dz allow only even, Yd, Yz and Dy allow only odd numerals). If not the higher voltage side is used as reference winding (side 1) it must be considered that the vector group changes: e.g. a Yd5 transformer is regarded from the lower voltage side as Dy7 (Figure 2-2).
21
2 Functions
Winding 1
L1 L2 L3
UL1N
Winding 2
L1 L2 L3
uL2N
Yd5
uL23 uL31 uL12 uL1N
Dy7
UL31
UL1N UL12
UL23
Winding 2
Figure 2-2
Winding 1
Change of the transformer vector group if the lower voltage side is the reference side example
The primary rated power 61 75$16)250(5 (address ) is the direct primary rated apparent power for transformers. The power must always be entered as a primary value, even if the device is generally configured in secondary values. The device calculates the rated current of the protected winding from this power. This is the reference for all referred values. The device automatically computes from the rated data of the protected transformer the current-matching formulae which are required to match the vector group and the different rated winding currents. The currents are converted such that the sensitivity of the protection always refers to the power rating of the transformer. Therefore, no circuity is required for matching of the vector group and no manual calculations for converting of rated current are normally necessary. Object Data with Generators, Motors and Reactors Using the 7UT612 for protection of generators or motors, the following must have been set when configuring the protection functions (see Subsection 2.1.1, address ): 3527 2%-(&7 = *HQHUDWRU0RWRU. These settings also go for series and shunt reactors if a complete set of current transformers is connected to both sides. In cases other than that, these settings are not available. With address 81 *(102725 you inform the device of the primary rated voltage (phase-to-phase) of the machine to be protected. The primary rated power 61 *(102725 (address ) is the direct primary rated apparent power of the machine. The power must always be entered as a primary value, even if the device is generally configured in secondary values. The device calculates the rated current of the protected object from this power and the rated voltage. This is the reference for all referred values. Object Data with Mini-Busbars, Branch-Points, Short Lines These data are only required if the device is used for differential protection of mini busbars or short lines with two ends. When configuring the protection functions (see Subsection 2.1.1, address ) the following must have been set: 3527 2%-(&7 = SK %XVEDU. In cases other than that, these settings are not available. With address 81 %86%$5 you inform the device of the primary rated voltage (phase-to-phase). This setting has no effect on the protective functions but influences the display of the operational measured values. 22
2.1 General
Since both sides or feeders may be equipped with current transformers of different rated primary currents, a uniform rated operational current , 35,0$5< 23 is defined as rated object current (address ) which will then be considered as a reference value for all currents. The currents are converted such that the settings of the protection function always refer to the rated operational current. In general, if current transformers differ, the higher rated primary current is selected for operational rated current. Object Data with Busbars with up to 7 Feeders Busbar data are only required if the device is used for single-phase busbar differential protection for up to 7 feeders. When configuring the protection functions (see Subsection 2.1.1, address ) following must have been set: 3527 2%-(&7 = SK %XV EDU. In cases other than that, these settings are not available. With address 81 %86%$5 you inform the device of the primary rated voltage (phase-to-phase). This setting has no effect on the protective functions but influences the displays of the operational measured values. Since the feeders of a busbar may be equipped with current transformers of different rated primary currents, a uniform operational nominal current , 35,0$5< 23 is defined as rated busbar current (address ) which will then be considered as a reference value for all currents. The feeder currents are converted such that the settings of the protection functions always refer to the rated operational current. Usually no external matching equipment is required. In general, if current transformers differ, the higher rated primary current of the feeders is selected for rated operational current. If the device is connected via summation transformers, the latter are to be connected between the current transformer set of each feeder and the device inputs. In this case the summation transformers can also be used for matching of currents. For the rated operational current of the busbar also use the highest of the rated primary currents of the feeders. Rated currents of each individual feeder are matched later on. If one 7UT612 is used per phase, set the same currents and voltages for all three devices. For the identification of the phases for fault annunciations and measured values each device is to be informed on the phase it is assigned to. This is to be set in address 3+$6( 6(/(&7,21, address . Current Transformer Data for 2 Sides The rated primary operational currents for the protected object derive from the object data before-described. The data of the current transformer sets at the sides of the protected object generally differ slightly from the object data before-described. They can also be completely different. Currents have to have a clear polarity to ensure that the differential protection applies the correct function. Therefore the device must be informed on the current transformer data. If there are 2 sides (i.e. all applications, except for single-phase busbar protection for up to 7 feeders), this is ensured by indication of rated currents and the secondary starpoint formation of the current transformer sets. In address ,135, &7 6 the rated primary current of the current transformer set of side 1 of the protected object is set. In address ,16(& &7 6 the rated secondary current is set. Please make sure that the sides were defined correctly (see Subsection 2.1.1, margin heading Special Cases, page 15). Please also make sure that the rated secondary transformer currents match the setting for the rated currents of the device (see also Subsection 3.1.3.3, margin heading Input/Output Board AI/ O3. Otherwise the device will calculate incorrect primary data, and malfunction of the differential protection may occur.
23
2 Functions
Indication of the starpoint position of the current transformers determines the polarity of the current transformers. To inform the device on the location of the starpoint in relation to the protected object use address 675317!2%- 6. Figure 2-3 shows some examples for this setting.
Side 2
Side 1
L1 L2 L3
675317!2%- 6 = 12 675317!2%- 6 = <(6
L1 L2 L3
Side 2
Side 1
L1
G
675317!2%- 6 = <(6 675317!2%- 6 = 12
L2 L3
Side 2
Side 1
L1
M
675317!2%- 6 = <(6 Figure 2-3 Position of the CT starpoints example 675317!2%- 6 = <(6
L2 L3
For side 2 of the protected object the same applies. For side 2 set the nominal primary current ,135, &7 6 (address ), nominal secondary current ,16(& &7 6 (address ) and the position of the current transformer starpoint 675317!2%- 6 (address ). Side 2 requires the same considerations as side 1. If the device is applied as transverse differential protection for generators or motors, special considerations must be observed for the CT connections: In a healthy operational state all currents flow into the protected object, i.e. in contrast to the other applications. Therefore you have to set a wrong polarity for one of the current transformer sets. The part windings of the machine windings correspond to the sides.
24
2.1 General
Figure 2-4 gives you an example: Although the starpoints of both current transformer sets are looking towards the protected object, the opposite setting is to be selected for side 2: 675317!2%- 6 = 12.
Side 2
Side 1
L1
L2
L3
675317!2%- 6 = 12 Figure 2-4
Current transformer sets in the feeders of a busbar can have different rated currents. Therefore, a uniform rated operational object current has been determined in the before-described paragraph Object Data with Busbars with up to 7 Feeders. The currents of each individual feeder have to be matched to this rated operational current. Indicate the rated primary transformer current for each feeder. The interrogation only applies to data of the number of feeders determined during the configuration according to 2.1.1 (address 180%(5 2) (1'6). If rated currents have already been matched by external equipment (e.g. by matching transformers), the rated current value, used as a base value for the calculation of the external matching transformers, is to be indicated uniform. Normally, it is the rated operational current. The same applies if external summation transformers are used. Hereinafter the parameters for rated primary currents: Address ,135, &7 , = rated primary transformer current for feeder 1, Address ,135, &7 , = rated primary transformer current for feeder 2, Address ,135, &7 , = rated primary transformer current for feeder 3, Address ,135, &7 , = rated primary transformer current for feeder 4, Address ,135, &7 , = rated primary transformer current for feeder 5, Address ,135, &7 , = rated primary transformer current for feeder 6, Address ,135, &7 , = rated primary transformer current for feeder 7. For rated secondary currents please make sure that rated secondary transformer currents match with the rated currents of the corresponding current input of the device. Rated secondary currents of a device can be matched according to 3.1.3.3 (see margin heading Input/Output Board AI/O3). If summation transformers are used, the rated current at the outgoing side is usually 100 mA. For rated secondary currents a value of A is therefore set for all feeders. Hereinafter the parameters for rated secondary currents: Address ,16(& &7 , = rated secondary transformer current for feeder 1, Address ,16(& &7 , = rated secondary transformer current for feeder 2,
25
2 Functions
Address ,16(& Address ,16(& Address ,16(& Address ,16(& Address ,16(& &7 &7 &7 &7 &7 , , , , ,
= rated secondary transformer current for feeder 3, = rated secondary transformer current for feeder 4, = rated secondary transformer current for feeder 5, = rated secondary transformer current for feeder 6, = rated secondary transformer current for feeder 7.
Indication of the starpoint position of the current transformers determines the polarity of the current transformers. Set for each feeder if the starpoint is looking towards the busbar or not. Figure 2-5 shows an example of 3 feeders in which the transformer starpoint in feeder 1 and feeder 3 are looking towards the busbar, unlike feeder 2.
Feeder 1
Feeder 2
Feeder 3 L1 L2 L3
I3 I2
7UT612 for L1
675317!%86 , = 12
I1
Hereinafter the parameters for the polarity: Address 675317!%86 , = transformer starpoint versus busbar for feeder 1, Address 675317!%86 , = transformer starpoint versus busbar for feeder 2, Address 675317!%86 , = transformer starpoint versus busbar for feeder 3, Address 675317!%86 , = transformer starpoint versus busbar for feeder 4, Address 675317!%86 , = transformer starpoint versus busbar for feeder 5, Address 675317!%86 , = transformer starpoint versus busbar for feeder 6, Address 675317!%86 , = transformer starpoint versus busbar for feeder 7. Current Transformer Data for Current Input I7 The current measuring input I7 is normally used for the detection of the starpoint current of an earthed winding of a transformer, shunt reactor, generator or motor. Only for single-phase busbar protection this is not available since I7 is reserved for feeder currents. I7 can be used for zero sequence current compensation when performing differential protection for transformers and/or restricted earth fault protection. It can be processed by the earth current time overcurrent protection, as an alternative or additionally. For matching the current magnitude set in address ,135, &7 , the rated primary current of the current transformer which is powered at this measuring input. The rated secondary current of this current transformer in address ,16(& &7 , has to be in correspondence with the rated device current for this measuring input.
26
2.1 General
Address ($57+ (/(&752' is relevant for the polarity of the current. In this address, set to which device terminal the side of the current transformer facing the earth electrode is connected, i.e. not the side facing the starpoint itself. Figure 2-6 shows the alternatives using an earthed transformer winding as an example.
L1 L2 L3 Q7 I7 Q8
L1 L2 L3
Q8 I7 Q7
7UT612
L l
7UT612
Note:
For devices in panel surface mounted case: Terminal Q7 corresponds to housing terminal 12 Terminal Q8 corresponds to housing terminal 27
The current measuring input I8 is a very sensitive input which enables to also acquire very weak currents (beginning with 3 mA at input). To also be able to indicate primary values for this measuring input (e. g. for setting in primary currents, for output of primary measured values), the conversion factor INprim/INsec of the current transformer connected is set in address )DFWRU ,. The minimum trip command duration 70LQ 75,3 &0' is set in address $. This duration is valid for all protection functions which can issue a trip command. This parameter can only be changed with DIGSI 4 under Additional Settings. Various protection and ancillary functions require information on the status of the circuit breaker for faultless operation. For the circuit breaker of side 1 of the protected object a current threshold %UHDNHU 6 ,! is to be set in address . When the circuit breaker is open, this threshold is likely to be undershot. The threshold may be very small if stray currents (e. g. due to induction) are excluded when the protected object is switched off. Otherwise the threshold value must be increased. Normally the pre-setting is sufficient. For the circuit breaker of side 2 of the protected object setting is done in address %UHDNHU 6 ,!.
27
2 Functions
2.1.2.1
Setting Overview
Note: The setting ranges and presettings listed in this table refer to a nominal current value IN = 1 A. For a secondary nominal current value IN = 5 A the current values are to be multiplied by 5. For setting primary values, the transformation ratio of the transformers must also be taken into consideration.
The presetting of the nominal frequency corresponds to the nominal frequency according to the device version.
Addr. 270 Setting Title Rated Frequency Setting Options 50 Hz 60 Hz 16 2/3 Hz L1 L2 L3 L1 L3 L2 Degree Celsius Degree Fahrenheit 0.4..800.0 kV Solid Earthed Isolated Y (Wye) D (Delta) Z (Zig-Zag) 0.4..800.0 kV Solid Earthed Isolated Y (Wye) D (Delta) Z (Zig-Zag) 0..11 0.20..5000.00 MVA 0.4..800.0 kV 0.20..5000.00 MVA 0.4..800.0 kV 1..100000 A Phase 1 Phase 2 Phase 3 YES NO 1..100000 A Default Setting 50 Hz Comments Rated Frequency
Phase Sequence Unit of temparature measurement Rated Primary Voltage Side 1 Starpoint of Side 1 is Transf. Winding Connection Side 1
Rated Primary Voltage side 2 Starpoint of side 2 is Transf. Winding Connection Side 2
VECTOR GRP S2 SN TRANSFORMER UN GEN/MOTOR SN GEN/MOTOR UN BUSBAR I PRIMARY OP. PHASE SELECTION STRPNT->OBJ S1 IN-PRI CT S1
Vector Group Numeral of Side 2 Rated Apparent Power of the Transformer Rated Primary Voltage Generator/ Motor Rated Apparent Power of the Generator Rated Primary Voltage Busbar Primary Operating Current Phase selection
201 202
YES 200 A
28
2.1 General
Setting Title IN-SEC CT S1 STRPNT->OBJ S2 IN-PRI CT S2 IN-SEC CT S2 STRPNT->BUS I1 IN-PRI CT I1 IN-SEC CT I1 1A 5A YES NO
Setting Options
Comments CT Rated Secondary Current Side 1 CT-Strpnt. Side2 in Direct. of Object CT Rated Primary Current Side 2 CT Rated Secondary Current Side 2 CT-Starpoint I1 in Direction of Busbar CT Rated Primary Current I1 CT Rated Secondary Current I1
1..100000 A 1A 5A YES NO 1..100000 A 1A 5A 0.1A YES NO 1..100000 A 1A 5A 0.1A YES NO 1..100000 A 1A 5A 0.1A YES NO 1..100000 A 1A 5A 0.1A YES NO 1..100000 A 1A 5A 0.1A YES NO 1..100000 A 1A 5A 0.1A
YES 200 A 1A
YES 200 A 1A
YES 200 A 1A
YES 200 A 1A
YES 200 A 1A
29
2 Functions
Setting Options Terminal Q7 Terminal Q8 YES NO 1..100000 A 1A 5A 0.1A 1.0..300.0 0.01..32.00 sec 0.04..1.00 A 0.04..1.00 A 0.04..1.00 A
Comments Earthing Electrod versus CT-Starpoint I7 in Direction of Busbar CT Rated Primary Current I7 CT Rated Secondary Current I7
Factor I8 TMin TRIP CMD Breaker S1 I> Breaker S2 I> Breaker I7 I>
Factor: Prim. Current over Sek. Curr. I8 Minimum TRIP Command Duration Clos. Breaker Min. Current Thresh. S1 Clos. Breaker Min. Current Thresh. S2 Clos. Breaker Min. Current Thresh. I7
2.1.2.2
Information Overview
F.No. 05145 >Reverse Rot. 05147 Rotation L1L2L3 05148 Rotation L1L3L2
Alarm >Reverse Phase Rotation Phase Rotation L1L2L3 Phase Rotation L1L3L2
Comments
2.1.3
Setting Groups
In the 7UT612 relay, four independent setting groups (A to D) are possible. The user can switch between setting groups locally, via binary inputs (if so configured), via the operator or service interface using a personal computer, or via the system interface. A setting group includes the setting values for all functions that have been selected as (QDEOHG during configuration (see Subsection 2.1.1). Whilst setting values may vary among the four setting groups, the scope of functions of each setting group remains the same. Multiple setting groups allows a specific relay to be used for more than one application. While all setting groups are stored in the relay, only one setting group may be active at a given time.
30
2.1 General
If multiple setting groups are not required, Group A is the default selection, and the rest of this subsection is of no importance. If multiple setting groups are desired, address *US &KJH 237,21 must have been set to (QDEOHG in the relay configuration. Refer to Subsection 2.1.1. Each of these sets (A to D) is adjusted one after the other. You will find more details how to navigate between the setting groups, to copy and reset setting groups, and how to switch over between the setting groups during operation, in the SIPROTEC System Manual, order number E50417H1176C151. The preconditions to switch from one setting group to another via binary inputs is described in Subsection 3.1.2.
2.1.3.1
Setting Overview
Addr. 302
2.1.3.2
Information Overview
F.No. 00007 >Set Group Bit0 00008 >Set Group Bit1 Group A Group B Group C Group D
Alarm >Setting Group Select Bit 0 >Setting Group Select Bit 1 Group A Group B Group C Group D
Comments
31
2 Functions
2.1.4
2.1.4.1
Information Overview
Alarm
Comments Fault in configuration of the Protection >Manual close signal Manual close signal detected >CB1 aux. 3p Closed >CB1 aux. 3p Open >CB2 aux. 3p Closed >CB2 aux. 3p Open Relay PICKUP Relay GENERAL TRIP command >Quitt Lock Out: General Trip Lock Out: General TRIP Protection ON/OFF (via system port) Primary fault current IL1 side1 Primary fault current IL2 side1 Primary fault current IL3 side1 Primary fault current IL1 side2 Primary fault current IL2 side2 Primary fault current IL3 side2 Primary fault current I1 Primary fault current I2 Primary fault current I3 Primary fault current I4 Primary fault current I5 Primary fault current I6 Primary fault current I7
00561 Man.Clos.Detect 00410 >CB1 3p Closed 00411 >CB1 3p Open 00413 >CB2 3p Closed 00414 >CB2 3p Open 00501 Relay PICKUP 00511 Relay TRIP >QuitG-TRP G-TRP Quit 00126 ProtON/OFF 00576 IL1S1: 00577 IL2S1: 00578 IL3S1: 00579 IL1S2: 00580 IL2S2: 00581 IL3S2: 00582 I1: 00583 I2: 00584 I3: 00585 I4: 00586 I5: 00587 I6: 00588 I7:
32
2.2
Differential Protection
The differential protection represents the main feature of the device. It is based on current comparison. 7UT612 is suitable for unit protection of transformers, generators, motors, reactors, short lines, and (under observance of the available number of analog current inputs) for branch points (smaller busbar arrangements). Generator/transformer units may also be protected. 7UT612 can be used as a single-phase differential protection relay for protected objects with up to 7 sides, e.g. as busbars protection with up to 7 feeders. The protected zone is limited selectively by the current transformer sets.
2.2.1
Differential protection is based on current comparison. It makes use of the fact that a protected object (Figure 2-7) carries always the same current i (dashed line) at its two sides in healthy operation. This current flows into one side of the considered zone and leaves it again on the other side. A difference in current marks is a clear indication of a fault within this section. If the actual current transformation ratio is the same, the secondary windings of the current transformers CT1 and CT2 at the line ends can be connected to form a closed electric circuit with a secondary current I; a measuring element M which is connected to the electrical balance point remains at zero current in healthy operation.
i CT1
i1
i2
i CT2
Protected object
I I1 i1 + i2 I I2
M I1 + I 2 Figure 2-7 Basic principle of differential protection for two ends (single-line illustration)
33
2 Functions
When a fault occurs in the zone limited by the transformers, a current I1 + I2 which is proportional to the fault currents i1 + i2 flowing in from both sides is fed to the measuring element. As a result, the simple circuit shown in Figure 2-7 ensures a reliable tripping of the protection if the fault current flowing into the protected zone during a fault is high enough for the measuring element M to respond. Basic Principle with more than Two Sides For protected objects with three or more sides or for busbars, the principle of differential protection is extended in that the total of all currents flowing into the protected object is zero in healthy operation, whereas in case of a fault the total is equal to the fault current (see Figure 2-8 as an example for four ends).
Current Restraint
When an external fault causes a heavy current to flow through the protected zone, differences in the magnetic characteristics of the current transformers CT1 and CT2 under conditions of saturation may cause a significant current to flow through the measuring element M. If the magnitude of this current lies above the response threshold, the protection would issue a trip signal. Current restraint prevents such erroneous operation. In differential protection systems for protected objects with two terminals, a restraining quantity is normally derived from the current difference |I1 I2| or from the arithmetical sum |I1| + |I2|. Both methods are equal in the relevant ranges of the stabilization characteristics. The latter method is used in 7UT612 for all protected objects. The following definitions apply: a tripping effect or differential current IDiff = |I1 + I2| and a stabilization or restraining current IRest = |I1| + |I2| IDiff is calculated from the fundamental wave of the measured currents and produces the tripping effect quantity, IRest counteracts this effect. To clarify the situation, three important operating conditions should be examined (refer also to Figure 2-9):
34
i1 CT1
I1
i2 Protected object
I2
CT2
M I 1 + I2
Figure 2-9 Definition of current direction
a) Through-fault current under healthy conditions or on an external fault: I2 reverses its direction i.e. thus changes its sign, i.e. I2 = I1, and consequently |I2| = |I1| IDiff = |I1 + I2| = |I1 I1| = 0 IRest = |I1| + |I2| = |I1| + |I1| = 2|I1| no tripping effect (IDiff = 0); restraint (IRest) corresponds to twice the through flowing current. b) Internal fault, fed from each end e.g. with equal currents: In this case, I2 = I1, and consequently |I2| = |I1| IDiff = |I1 + I2| = |I1 + I1| = 2|I1| IRest = |I1| + |I2| = |I1| + |I1| = 2|I1| tripping effect (IDiff) and restraining (IRest) quantities are equal and correspond to the total fault current. c) Internal fault, fed from one end only: In this case, I2 = 0 IDiff = |I1 + I2| = |I1 + 0| = |I1| IRest = |I1| + |I2| = |I1| + 0 = |I1| tripping effect (IDiff) and restraining (IRest) quantities are equal and correspond to the fault current fed from one side. This result shows that for internal fault IDiff = IRest. Thus, the characteristic of internal faults is a straight line with the slope 1 (45) in the operation diagram as illustrated in Figure 2-10 (dash-dotted line).
35
2 Functions
I Diff ------------I N
10 9 8 7 6 5 4 3 2
Fault characteristic
Tripping
D C
Blocking
a 1 a
Figure 2-10
Saturation of the current transformers caused by high fault currents and/or long system time constants are uncritical for internal faults (fault in the protected zone), since the measured value deformation is found in the differential current as well in the restraint current, to the same extent. The fault characteristic as illustrated in Figure 2-10 is principally valid in this case, too. Of course, the fundamental wave of the current must exceed at least the pickup threshold (branch a in Figure 2-10). During an external fault which produces a high through-flowing fault current causing current transformer saturation, a considerable differential current can be simulated, especially when the degree of saturation is different at the two sides. If the quantities IDiff/IRest result in an operating point which lies in the trip area of the operating characteristic (Figure 2-10), trip signal would be the consequence if there were no special measures. 7UT612 provides a saturation indicator which detects such phenomena and initiates add-on stabilization measures. The saturation indicator considers the dynamic behaviour of the differential and restraint quantity. The dashed line in Figure 2-10 shows an example of the shape of the instantaneous quantities during a through-fault current with current transformer saturation at one side. Immediately after fault inception (A) the fault currents increase severely thus producing a high restraint quantity (twice the through-flowing current). At the instant of CT saturation (B) a differential quantity is produced and the restraint quantity is reduced. In consequence, the operating point IDiff/IRest may move into the tripping area (C). In contrast, the operating point moves immediately along the fault characteristic (D) when an internal fault occurs since the restraint current will barely be higher then the differential current.
36
Current transformer saturation during external faults is detected by the high initial restraining current which moves the operating point briefly into the add-on stabilization area (Figure 2-10). The saturation indicator makes its decision within the first quarter cycle after fault inception. When an external fault is detected, the differential protection is blocked for an adjustable time. This blocking is cancelled as soon as the operation point moves steadily (i.e. over at least one cycle) near the fault characteristic. This allows to detect evolving faults in the protected zone reliably even after an external fault with current transformer saturation. Harmonic Restraint When switching unloaded transformers or shunt reactors on a live busbar, high magnetizing (inrush) currents may occur. These inrush currents produce differential quantities as they seem like single-end fed fault currents. Also during paralleling of transformers, or an overexcitation of a power transformer, differential quantities may occur due to magnetizing currents cause by increased voltage and/or decreased frequency. The inrush current can amount to a multiple of the rated current and is characterized by a considerable 2nd harmonic content (double rated frequency) which is practically absent in the case of a short-circuit. If the second harmonic content exceeds a selectable threshold, trip is blocked. Besides the second harmonic, another harmonic can be selected to cause blocking. A choice can be made between the third and fifth harmonic. Overexcitation of the transformer iron is characterized by the presence of odd harmonics in the current. Thus, the third or fifth harmonic are suitable to detect such phenomena. But, as the third harmonic is often eliminated in power transformers (e.g. by the delta winding), the use of the fifth is more common. Furthermore, in case of converter transformers odd harmonics are found which are not present during internal transformer faults. The differential quantities are examined as to their harmonic content. Numerical filters are used to perform a Fourier analysis of the differential currents. As soon as the harmonic contents exceed the set values, a restraint of the respective phase evaluation is introduced. The filter algorithms are optimized with regard to their transient behaviour such that additional measures for stabilization during dynamic conditions are not necessary. Since the harmonic restraint operates individually per phase, the protection is fully operative even when e.g. the transformer is switched onto a single-phase fault, whereby inrush currents may possibly be present in one of the healthy phases. However, it is also possible to set the protection such that not only the phase with inrush current exhibiting harmonic content in excess of the permissible value is restrained but also the other phases of the differential stage are blocked (so called crossblock function). This crossblock can be limited to a selectable duration. Fast Unstabilized Trip with HighCurrent Faults High-current faults in the protected zone may be cleared instantaneously without regard of the magnitude of the restraining current, when the magnitude of the differential currents can exclude that it is an external fault. In case of protected objects with high direct impedance (transformers, generators, series reactors), a threshold can be found above which a through-fault current never can increase. This threshold (prima1 ry) is, e.g. for a power transformer, ---------------------------- I 1 t UD nsf . u
sc transf
The differential protection 7UT612 provides such unstabilized high-current trip stage. This can operate even when, for example, a considerable second harmonic is present in the differential current caused by current transformer saturation by a DC component
37
2 Functions
in the fault current which could be interpreted by the inrush restraint function as an inrush current. This high-current stage evaluates the fundamental wave of the currents as well as the instantaneous values. Instantaneous value processing ensures fast tripping even in case the fundamental wave of the current is strongly reduced by current transformer saturation. Because of the possible DC offset after fault inception, the instantaneous value stage operates only above twice the set threshold. Increase of Pickup Value on Startup The increase of pickup value is especially suited for motors. In contrast to the inrush current of transformers the inrush current of motors is a traversing current. Differential currents, however, can emerge if current transformers still contain different remanent magnetization before energization. Therefore, the transformers are energized from different operation points of their hysteresis. Although differential currents are usually small, they can be harmful if differential protection is set very sensitive. An increase of the pickup value on startup provides additional security against overfunctioning when a non-energized protected object is switched in. As soon as the restraining current of one phase has dropped below a settable value ,5(67 67$5783, the pickup value increase is activated. The restraint current is twice the traversing current in normal operation. Undershooting of the restraint current is therefore a criterion for the non-energized protected object. The pickup value ,',))! is now increased by a settable factor (see Figure 2-11). The other branches of the IDiff> stage are shifted proportionally. The return of the restraint current indicates the startup. After a settable time 7 67$57 0$; the increase of the characteristic is undone.
10
Startup characteristic
Tripping
Steady-state characteristic Increase of pickup
Blocking
1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
38
Tripping Characteristic
Figure 2-12 illustrates the complete tripping characteristic of the differential protection. The branch a represents the sensitivity threshold of the differential protection (setting ,',))!) and considers constant error current, e.g. magnetizing currents. Branch b takes into consideration current-proportional errors which may result from transformation errors of the main CTs, the input CTs of the relay, or from erroneous current caused by the position of the tap changer of the voltage regulator. In the range of high currents which may give rise to current transformer saturation, branch c causes stronger stabilization. Differential currents above the branch d cause immediate trip regardless of the restraining quantity and harmonic content (setting ,',))!!). This is the area of Fast Unstabilized Trip with High-Current Faults (see above). The area of Add-on stabilization is the operation area of the saturation indicator as described above under margin Add-on Stabilization during External Fault.
I Diff ------------IN
10 9
Fault characteristic
8 !" D9DAA33 7 6
Tripping
5 4 3 2
!! D9DAA3
!#" TGPQ@!
Blocking
!# TGPQ@
a 1 2
b 3 4 5 6 7 8 9
Add-on stabilization
!#! 76T@QPDIU
!## 76T@QPDIU!
10 11 12 13 14 15 16 17 18
I Rest ----------------I N
!$% D699PITU67
Figure 2-12
The quantities IDiff and IRest are compared by the differential protection with the operating characteristic according to Figure 2-12. If the quantities result into a locus in the tripping area, trip signal is given. Fault Detection, Drop-off Normally, a differential protection does not need a pickup or fault detection function since the condition for a fault detection is identical to the trip condition. But, 7UT612 provides like all SIPROTEC 4 devices a fault detection function which has the task to define the fault inception instant for a number of further features: Fault detection indicates the beginning of a fault event in the system. This is necessary to open the trip log buffer and the memory for oscillographic fault record data. But, also internal functions need the instant of fault inception even in case of an external fault, e.g. the saturation indicator which has to operate right in case of an external fault.
39
2 Functions
As soon as the fundamental wave of the differential current exceeds 70 % of the set value or the restraining current reaches 70 % of the add-on stabilization area, the protection picks up (Figure 2-13). Pickup of the fast high-current stage causes a fault detection, too.
Fault detection
D9DAA3
0.7 D9DAA3
Steady-state characteristic
0.7
D699PITU67
Figure 2-13
If the harmonic restraint is effective, the harmonic analysis is carried out (approx. one AC cycle) in order to examine the stabilizing conditions. Otherwise, tripping occurs as soon as the tripping conditions are fulfilled (tripping area in Figure 2-12). For special cases, the trip command can be delayed. Figure 2-14 shows a simplified tripping logic. Reset of pickup is initiated when, during 2 AC cycles, pickup is no longer recognized in the differential values, i.e. the differential current has fallen below 70 % of the set value, and no further trip conditions are present. If a trip command has not been initiated, the fault is considered to be over after reset. If a trip command has been formed, this is sealed for at least the minimum trip duration which is set under the general protection data, common for all protection function (refer to Subsection 2.1.2 under margin header Trip Command Duration, page 27).
40
FNo 05631
Diff picked up
Character.
1) Inrush restraint (2nd harmon.)
FNo 05644...05646
&
UD9DAA3
T
FNo 05681...05683
Diff> TRIP
1 1 1 1
FNo 05672
Diff
TRIP
FNo 05673
Diff
TRIP
FNo 05647...05649
FNo 05674
Diff
TRIP
1)
FNo 05684...05686
&
UD9DAA33
T
1
L1 L2
Meas. release Meas. release Meas. release
FNo 05692
Diff>>
L3
1)
FNo 05671
Diff TRIP
2)
FNo 05603
>Diff BLOCK
Diff BLOCKED
FNo 05617
&
9DAAQSPU
1
Diff ACTIVE
PI 7ypxryh PAA
&
FNo 05615
Diff OFF
Figure 2-14
41
2 Functions
2.2.2
Isolated Starpoint
Figure 2-15 illustrates an example for a power transformer Yd5 (wye-delta with 150 phase displacement) without any earthed starpoint. The figure shows the windings and the phasor diagrams of symmetrical currents and, at the bottom, the matrix equations. The general form of these equations is ( Im ) = k ( K ) ( I n ) where (Im) k (K) (In) matrix of the matched currents IA, IB, IC, constant factor, coefficient matrix, dependent on the vector group, matrix of the phase currents IL1, IL2, IL3.
On the left (delta) winding, the matched currents IA, IB, IC are derived from the difference of the phase currents IL1, IL2, IL3. On the right (wye) side, the matched currents are equal to the phase currents (magnitude matching not considered).
42
Winding 2 L1 L2 L3
Winding 1 L1 L2 L3 IL1
IA
IA
IL2
I L1 I L2 I L3
I A 1 0 0 IL1 I = 1 B 0 1 0 IL2 I 0 0 1 I C L3
Matching the transformer vector group, example Yd5 (magnitudes not considered)
Earthed Starpoint
Figure 2-16 illustrates an example for a transformer YNd5 with an earthed starpoint on the Yside. In this case, the zero sequence currents are eliminated. On the left side, the zero sequence currents cancel each other because of the calculation of the current differences. This complies with the fact that zero sequence current is not possible outside of the delta winding. On the right side, the zero sequence current is eliminated by the calculation rule of the matrix, e.g. 1 /3 (2 IL1 1 IL2 1 IL3) = 1/3 (3 IL1 IL1 IL2 IL3) = 1/3 (3 IL1 3 I0) = (IL1 I0). Zero sequence current elimination achieves that fault currents which flow via the transformer during earth faults in the network in case of an earth point in the protected zone (transformer starpoint or starpoint former by neutral earth reactor) are rendered harmless without any special external measures. Refer e.g. to Figure 2-17: Because of the earthed starpoint, a zero sequence current occurs on the right side during a network fault but not on the left side. Comparison of the phase currents, without zero sequence current elimination, would cause a wrong result (current difference in spite of an external fault).
43
2 Functions
Winding 2 L1 L2 L3
Winding 1 L1 L2 L3 IL1
IA
IA
IL2
I L1 I L2 I L3
I A 2 1 1 I L1 1 I = -- 1 2 1 I L2 B 3 I 1 1 2 I C L3
Matching the transformer vector group, example YNd5 (magnitudes not considered)
L1 L2 L3
L1 L2 L3
Figure 2-17
Example of an earth fault outside the protected transformer and current distribution
Figure 2-18 shows an example of an earth fault on the delta side outside the protected zone if an earthed starpoint former (zigzag winding) is installed within the protected zone. In this arrangement, a zero sequence current occurs on the right side but not on the left, as above. If the starpoint former were outside the protected zone (i.e. CTs between power transformer and starpoint former) the zero sequence current would not pass through the measuring point (CTs) and would not have any harmful effect. The disadvantage of elimination of the zero sequence current is that the protection becomes less sensitive (factor 2/3 because the zero sequence current amounts to 1/3) in case of an earth fault in the protected area. Therefore, elimination is suppressed in case the starpoint is not earthed (see above, Figure 2-15).
44
L1 L2 L3
L1 L2 L3
Figure 2-18
Example of an earth fault outside the protected transformer with a neutral earthing reactor within the protected zone
Higher earth fault sensitivity in case of an earthed winding can be achieved if the starpoint current is available, i.e. if a current transformer is installed in the starpoint connection to earth and this current is fed to the device (current input I7). Figure 2-19 shows an example of a power transformer the starpoint of which is earthed on the Yside. In this case, the zero sequence current is not eliminated. Instead of this, 1 /3 of the starpoint current ISP is added for each phase.
L1 L2 L3 ISP
Figure 2-19
L1 L2 L3 IL3
ISP corresponds to 3I0 but is measured in the starpoint connection of the winding and not in the phase lines. The effect is that the zero sequence current is considered in case of an internal fault (from I0 = 1/3 ISP), whilst the zero sequence current is eliminated in case of an external fault because the zero sequence current on the terminal side I0 = 1/3 (IL1 + IL2 + IL3) compensates for the starpoint current. In this way, full sensitivity (with zero sequence current) is achieved for internal earth faults and full elimination of the zero sequence current in case of external earth faults.
45
2 Functions
Even higher earth fault sensitivity during internal earth fault is possible by means of the restricted earth fault protection as described in Section 2.3. Use on AutoTransformers Auto-transformers can only be connected Y(N)y0. If the starpoint is earthed this is effective for both the system parts (higher and lower voltage system). The zero sequence system of both system parts is coupled because of the common starpoint. In case of an earth fault, the distribution of the fault currents is not unequivocal and cannot be derived from the transformer properties. Current magnitude and distribution is also dependent on whether or not the transformer is provided with a stabilizing winding.
L1 L2 L3
L1 L2 L3
Figure 2-20
The zero sequence current must be eliminated for the differential protection. This is achieved by the application of the matrices with zero sequence current elimination. The decreased sensitivity due to zero sequence current elimination cannot be compensated by consideration of the starpoint current. This current cannot be assigned to a certain phase nor to a certain side of the transformer. Increased earth fault sensitivity during internal earth fault can be achieved by using the restricted earth fault protection as described in Section 2.3 and/or by the highimpedance differential protection described in Subsection 2.7.2. Use on SinglePhase Transformers Single-phase transformers can be designed with one or two windings per side; in the latter case, the winding phases can be wound on one or two iron cores. In order to ensure that optimum matching of the currents would be possible, always two measured current inputs shall be used even if only one current transformer is installed on one phase. The currents are to be connected to the inputs L1 and L3 of the device; they are designated IL1 and IL3 in the following. If two winding phases are available, they may be connected either in series (which corresponds to a wye-winding) or in parallel (which corresponds to a delta-winding). The phase displacement between the windings can only be 0 or 180. Figure 2-21 shows an example of a single-phase power transformer with two phases per side with the definition of the direction of the currents.
46
L1 L3
L1 L3
Example of a single-phase transformer with current definition
Figure 2-21
Like with three-phase power transformers, the currents are matched by programmed coefficient matrices which simulate the difference currents in the transformer windings. The common form of these equations is ( Im ) = k ( K ) ( In ) where (Im) k (K) (In) matrix of the matched currents IA, IC, constant factor, coefficient matrix, matrix of the phase currents IL1, IL3.
Since the phase displacement between the windings can only be 0 or 180, matching is relevant only with respect to the treatment of the zero sequence current (besides magnitude matching). If the starpoint of the protected transformer winding is not earthed (Figure 2-21 left side), the phase currents can directly be used. If a starpoint is earthed (Figure 2-21 right side), the zero sequence current must be eliminated by forming the current differences. Thus, fault currents which flow through the transformer during earth faults in the network in case of an earth point in the protected zone (transformer starpoint) are rendered harmless without any special external measures. The matrices are (Figure 2-21): I A = 1 1 0 I L1 I 0 1 I C L3 I A = 1 1 1 - I 2 1 1 C I L1 I L3
The disadvantage of elimination of the zero sequence current is that the protection becomes less sensitive (factor 1/2 because the zero sequence current amounts to 1/2) in case of an earth fault in the protected area. Higher earth fault sensitivity can be achieved if the starpoint current is available, i.e. if a CT is installed in the starpoint connection to earth and this current is fed to the device (current input I7).
L1 L3 ISP
Figure 2-22
L1 L3
47
2 Functions
where ISP is the current measured in the starpoint connection. The zero sequence current is not eliminated. Instead of this, for each phase 1/2 of the starpoint current ISP is added. The effect is that the zero sequence current is considered in case of an internal fault (from I0 = 1/2 ISP), whilst the zero sequence current is eliminated in case of an external fault because the zero sequence current on the terminal side I0 = 1/2 (IL1 + IL3) compensates for the starpoint current. In this way, full sensitivity (with zero sequence current) is achieved for internal earth faults and full elimination of the zero sequence current in case of external earth faults.
2.2.3
L1 L2 L3
Figure 2-23 Definition of current direction with longitudinal differential protection
In 7UT612, all measured quantities are referred to the rated values of the protected object. The device is informed about the rated machine data during setting: the rated apparent power, the rated voltage, and the rated currents of the current transformers. Measured value matching is reduced to magnitude factors, therefore. A special case is the use as transverse differential protection. The definition of the current direction is shown in Figure 2-24 for this application. For use as a transverse differential protection, the protected zone is limited by the end of the parallel phases. A differential current always and exclusively occurs when the currents of two parallel windings differ from each other. This indicates a fault current in one of the parallel phases.
48
L1
L2
L3
Figure 2-24 Definition of current direction with transverse differential protection
The currents flow into the protected object even in case of healthy operation, in contrast to all other applications. For this reason, the polarity of one current transformer set must be reversed, i.e. you must set a wrong polarity, as described in Subsection 2.1.2 under Current Transformer Data for 2 Sides, page 23. Starpoint Conditioning If the differential protection is used as generator or motor protection, the starpoint condition need not be considered even if the starpoint of the machine is earthed (high- or low-resistant). The phase currents are always equal at both measuring points in case of an external fault. With internal faults, the fault current results always in a differential current. Nevertheless, increased earth fault sensitivity can be achieved by the restricted earth fault protection as described in Section 2.3 and/or by the high-impedance differential protection described in Subsection 2.7.2.
2.2.4
49
2 Functions
L1 L2 L3
L1 L2 L3
L1 L2 L3
L1 L2 L3
ISP
ISP
Figure 2-25
2.2.5
50
L1 L2 Busbar L3
Figure 2-26
L1 L2 L3
Figure 2-27 Definition of current direction at short lines
Whereas a high sensitivity of the differential protection is normally required for transformers, reactors, and rotating machines in order to detect even small fault currents, high fault currents are expected in case of faults on a busbar or a short line so that a higher pickup threshold (above rated current) is conceded here. This allows for a continuous monitoring of the differential currents on a low level. A small differential current in the range of operational currents indicates a fault in the secondary circuit of the current transformers. This monitor operates phase segregated. When, during normal load conditions, a differential current is detected in the order of the load current of a feeder, this indicates a missing secondary current, i.e. a fault in the secondary current leads (short-circuit or open-circuit). This condition is annunciated with time delay. The differential protection is blocked in the associated phase at the same time.
Another feature is provided for protection of mini-busbars or short lines. This feeder current guard monitors the currents of each phase of each side of the protected object. It provides an additional trip condition. Trip command is allowed only when at least one of these currents exceeds a certain (settable) threshold.
51
2 Functions
2.2.6
For each of the phases, a 7UT612 is used in case of single-phase connection. The fault current sensitivity is equal for all types of fault. The differential protection refers all measured quantities to the nominal current of the protected object. Therefore, a common nominal current must be defined for the entire busbar even if the feeder CTs have different nominal currents. The nominal busbar current and the nominal currents of all feeder CTs must be set on the relay. Matching of the current magnitudes is performed in the device. No external matching devices are necessary even if the current transformer sets at the ends of the protected zone have different primary current.
Feeder 1
Feeder 2
Feeder 7 L1 L2 L3
I1 I2
7UT612 Phase L1
I7
Figure 2-28
One single device 7UT612 is sufficient for a busbar with up to 7 feeders if the device is connected via summation current transformers. The phase currents of each feeder are converted into single-phase current by means of the summation CTs (Figure 229). Current summation is unsymmetrical; thus, different sensitivity is valid for different type of fault. A common nominal current must be defined for the entire busbar. Matching of the currents can be performed in the summation transformer connections if the feeder CTs have different nominal currents. The output of the summation transformers is normally designed for IM = 100 mA at symmetrical nominal busbar current.
52
Feeder 1
Feeder 2
Feeder 7 L1 L2 L3
L1 L2 L3
SCT
L1 L2 L3
SCT
L1 L2 L3
SCT
I1 I7
7UT612
I2
Figure 2-29
Different schemes are possible for the connection of the current transformers. The same CT connection method must be used for all feeders of a busbar. The scheme shown in Figure 2-30 is the most common. The input windings of the summation transformer are connected to the CT currents IL1, IL3, and IE (residual current). This connection is suitable for all kinds of systems regardless of the conditioning of the system neutral. It is characterized by an increased sensitivity for earth faults. For a symmetrical three-phase fault (where the earth residual component, IE = 0) the single-phase summation current is, as illustrated in Figure 2-30, 3 times the winding unit value. That is, the summation flux (ampere turns) is the same as it would be for single-phase current 3 times the value flowing through the winding with the least number of turns (ratio 1). For three-phase symmetrical fault currents equal to rated current IN, the secondary single-phase current is IM = 100 mA. All relay characteristic operating values are based on this type of fault and these currents.
IL1
2
SCT
IM
IL3
1
7UT612
IE L1 L2 L3
Figure 2-30
CT connection L1L3E
53
2 Functions
IL1
IL3
90
60
2 IL1 IM
30
IM = 2 IL1 + IL3
IL3
Figure 2-31
IL2
= 3 |I|
For the connection shown in Figure 2-30, the weighting factors W of the summation currents IM for the various fault conditions and the ratios to that given by the threephase symmetrical faults are shown in Table 2-1. On the right hand side is the complementary multiple of rated current which W/3 would have to be, in order to give the summation current IM = 100 mA in the secondary circuit. If the current setting values are multiplied with this factor, the actual pickup values result.
Table 2-1
Fault types and weighting factor for CT connection L1L3E W 3 2 1 1 5 3 4 W/3 1,00 1,15 0,58 0,58 2,89 1,73 2,31 I1 for IM = 100 mA 1.00 IN 0.87 IN 1.73 IN 1.73 IN 0.35 IN 0.58 IN 0.43 IN
Fault type L1L2L3 (sym.) L1L2 L2L3 L3L1 L1E L2E L3E
The table shows that 7UT612 is more sensitive to earth faults than to those without earth path component. This increased sensitivity is due to the fact that the summation transformer winding in the CT starpoint connection (IE, residual current, refer to Figure 2-30) has the largest number of turns, and thus, the weighting factor W = 3. If the higher earth current sensitivity is not necessary, connection according to Figure 2-32 can be used. This is reasonable in earthed systems with particularly low zero sequence impedance where earth fault currents may be larger than those under twophase fault conditions. With this connection, the values given in Table 2-2 can be recalculated for the seven possible fault conditions in solidly earthed networks.
54
IL1
2
SCT
IM
IL2
1
7UT612
IL3
3
L1 L2 L3
Figure 2-32 CT connection L1L2L3 with decreased earth fault sensitivity
IL1 2 IL1
IM = 2 IL1 + IL2 + 3 IL3 = 3 |I| 3 IL3
60
IL2
IL3
Figure 2-33
IL2
IM
Table 2-2
Fault types and weighting factor for CT connection L1L2L3 W 3 1 2 1 2 1 3 W/3 1,00 0,58 1,15 0,58 1,15 0,58 1,73 I1 for IM = 100 mA 1.00 IN 1.73 IN 0.87 IN 1.73 IN 0.87 IN 1.73 IN 0.58 IN
Fault type L1L2L3 (sym.) L1L2 L2L3 L3L1 L1E L2E L3E
Comparison with Table 2-1 shows that under earth fault conditions the weighting factor W is less than with the standard connection. Thus the thermal loading is reduced to 36 %, i.e. (1.73/2.89)2. The described connection possibilities are examples. Certain phase preferences (especially in systems with non-earthed neutral) can be obtained by cyclic or acyclic exchange of the phases. Further increase of the earth current can be performed by introducing an auto-CT in the residual path, as a further possibility. The type 4AM5120 is recommended for summation current transformer. These transformers have different input windings which allow for summation of the currents with the ratio 2:1:3 as well as matching of different primary currents of the main CTs to an certain extent. Figure 2-34 shows the winding arrangement.
55
2 Functions
The nominal input current of each summation CT must match the nominal secondary current of the connected main CT set. The output current of the summation CT (= input current of the 7UT612) amounts to IN = 0.1 A at nominal conditions, with correct matching.
A B 3
C D 6
E F 9
G H 18 500
K 24
L M 36
N O 90
4AM51203DA000AN2 IN = 1 A
Z
Y A B 1 C D 2 E F 3 G H 4 500 J 6 K L M 8 N O 12
4AM51204DA000AN2 IN = 5 A
Z
Figure 2-34
Whereas a high sensitivity of the differential protection is normally required for transformers, reactors, and rotating machines in order to detect even small fault currents, high fault currents are expected in case of faults on a busbar so that a higher pickup threshold (above rated current) is conceded here. This allows for a continuous monitoring of the differential currents on a low level. When, during normal load conditions, a differential current is detected in the order of the load current of a feeder, this indicates a missing secondary current, i.e. a fault in the secondary current leads (short-circuit or open-circuit). This condition is annunciated with time delay. The differential protection is blocked at the same time.
Another feature is provided for protection of busbars. This feeder current guard monitors the currents of each feeder of the busbar. It provides an additional trip condition. Trip command is allowed only when at least one of these currents exceeds a certain (settable) threshold.
2.2.7
General
56
Note:
When delivered from factory, the differential protection is switched 2)). The reason is that the protection must not be in operation unless at least the connection group (of a transformer) and the matching factors have been set before. Without proper settings, the device may show unexpected reactions (incl. tripping)!
Starpoint Conditioning
If there is a current transformer in the starpoint connection of an earthed transformer winding, i. e. between starpoint and earth electrode, the starpoint current may be taken into consideration for calculations of the differential protection (see also Subsection 2.2.2, margin heading Increasing the Ground Fault Sensitivity, page 45). Thus, the earth fault sensitivity is increased. In addresses $ ',))Z,(0($6 for side 1 or $ ',))Z,(0($6 for side 2 the user informs the device on whether the earth current of the earthed starpoint is included or not. This parameter can only be changed with DIGSI 4 under Additional Settings. With setting <(6 the corresponding earth current will be considered by the differential protection. This setting only applies for transformers with two separate windings. Its use only makes sense if the corresponding starpoint current actually is connected to the device (current input I7). When configuring the protection functions (see Subsection 2.1.1, page 16) address must have been set accordingly. In addition to that, the starpoint of the corresponding side has to be earthed (Subsection 2.1.2 under margin heading Object Data with Transformers, page 20, addresses and/or ).
With busbar protection differential current can be monitored (see Subsection 2.2.5 and 2.2.6). This function can be set to 21 and 2)) in address ,',))! 021. Its use only makes sense if one can distinguish clearly between operational error currents caused by missing transformer currents and fault currents caused by a fault in the protected object. The pickup value ,',))! 021 (address ) must be high enough to avoid a pickup caused by a transformation error of the current transformers and by minimum mismatching of different current transformers. The pickup value is referred to the rated current of the protected object. Time delay 7 ,',))! 021 (address ) applies to the annunciation and blocking of the differential protection. This setting ensures that blocking with the presence of faults (even of external ones) is avoided. The time delay is usually about some seconds.
With busbars and short lines a release of the trip command can be set if one of the incoming currents is exceeded. The differential protection only trips if one of the measured currents exceeds the threshold ,! &855 *8$5' (address ). The pickup value is referred to the rated current of the protected object. With setting (pre-setting) this release criterion will not be used.
57
2 Functions
If the feeder current guard is set (i. e. to a value of > 0), the differential protection will not trip before the release criterion is given. This is also the case if, in conjunction with very high differential currents, the extremely fast instantaneous value scheme (see Subsection 2.2.1, margin heading Fast Unstabilized Trip with High-Current Faults) has detected the fault already after a few milliseconds. Trip Characteristic Differential Current The parameters of the trip characteristic are set in addresses to $. Figure 2-35 illustrates the meaning of the different settings. The numbers signify the addresses of the settings. ,',))! (address ) is the pickup value of the differential current. This is the total fault current into the protected object, regardless of the way this is distributed between the sides. The pickup value is referred to the rated current of the protected object. You may select a high sensitivity (small pickup value) for transformers, reactors, generators, or motors, (presetting 0.2 INObj). A higher value (above nominal current) should be selected for lines and busbars. Higher measuring tolerances must be expected if the nominal currents of the current transformers differ extensively from the nominal current of the protected object. In addition to the pickup limit ,',))!, the differential current is subjected to a second pickup threshold. If this threshold ,',))!! (address ) is exceeded then tripping is initiated regardless of the magnitude of the restraint current or the harmonic content (unstabilized high-current trip). This stage must be set higher than ,',))!. If the protected object has a high direct impedance (transformers, generators, series reactors), a threshold can be found above which a through-fault current never can in1 crease. This threshold (primary) is, e.g. for a power transformer, ---------------------------- I 1 t UD nsf . u
sc transf
9 8 !" D9DAA33 7 6 5 4 3 2
!! D9DAA3
Tripping
!#" TGPQ@!
Blocking
!# TGPQ@
Add-on stabilization
1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
I Rest ----------------I NObj
Figure 2-35
58
The tripping characteristic forms two more branches (Figure 2-35) The slope of the first branch is determined by the address $ 6/23( , its base point by the address $ %$6( 32,17 . This parameter can only be changed with DIGSI 4 under Additional Settings. This branch covers current-proportional errors. These are mainly errors of the main current transformers and, in case of power transformers with tap changers, differential currents which occur due to the transformer regulating range. The percentage of this differential current is equal to the percentage of the regulating range provided the rated voltage is corrected according to Subsection 2.1.2 under margin Object Data with Transformers (page 20). The second branch produces a higher stabilization in the range of high currents which may lead to current transformer saturation. Its base point is set under address $ %$6( 32,17 and is referred to the rated object current. The slope is set under address $ 6/23( . The stability of the protection can be influenced by these settings. A higher slope results in a higher stability. This parameter can only be changed with DIGSI 4 under Additional Settings. Delay times In special cases it may be advantageous to delay the trip signal of the protection. For. this, an additional delay can be set. The timer $ 7 ,',))! is started when an internal fault is detected by the IDiff>stage and the trip characteristic. $ 7 , ',))!! is the delay for the IDiff>>stage. This parameter can only be changed with DIGSI 4 under Additional Settings. These settings are pure delay times which do not include the inherent operating time of the protection. The increase of the pickup value on startup serves as an additional safety against overfunctioning when a non-energized protection object is switched in. This function can be set to 21 or 2)) in address ,1&&+$567$57. Especially for motors or motor/transformer in block connection it should be set to 21. The restraint current value ,5(67 67$5783 (address $) is the value of the restraining current which is likely to be undershot before startup of the protected object takes place (i.e. in case of standstill). This parameter can only be changed with DIGSI 4 under Additional Settings. Please be aware of the fact that the restraint current is twice the traversing operational current. The pre-set value of 0.1 represents 0.05 times the rated current of the protected object. Address $ 67$57)$&725 determines by which factor the pickup value of the IDiff>stage is to be increased on startup. The characteristic of this stage increases by the same value. The IDiff>>stage is not affected. For motors or motor/transformer in block connection, a value of 2 is normally adequate. This parameter can only be changed with DIGSI 4 under Additional Settings. The increase of the pickup value is set back to its original value after time period 7 67$57 0$; (address ) has passed. Add-on Stabilization In systems with very high traversing currents a dynamic add-on stabilization is being enabled for external faults (Figure 2-35). The initial value is set in address $ , $'' 21 67$%. The value is referred to the rated current of the protected object. The slope is the same as for characteristic branch b (6/23( , address $). This parameter can only be changed with DIGSI 4 under Additional Settings. Please be aware of the fact that the restraint current is the arithmetical sum of the currents flowing into the protected object, i. e. it is twice the traversing current.
59
2 Functions
The maximum duration of the add-on stabilization after detection of an external fault is set to multiples of an AC-cycle (address $ 7 $'' 2167$%). This parameter can only be changed with DIGSI 4 under Additional Settings. The add-on stabilization is disabled automatically even before the set time period expires as soon as the device has detected that the operation point IDiff/IRest is located steadily (i. e. via at least one cycle) within the tripping zone. Harmonic Restraint Stabilization with harmonic content is available only when the device is used as transformer protection, i.e. 3527 2%-(&7 (address ) is set to SKDVH WUDQVI or $XWRWUDQVI or SKDVH WUDQVI. It is used also for shunt reactors if current transformers are installed at both sides of the connection points of the reactor (cf. example in Figure 2-25, right graph). The inrush restraint function can be switched 2)) or 21 under address ,1586+ +$50. It is based on the evaluation of the 2nd harmonic content of the inrush current. The ratio of the 2nd harmonic to the fundamental frequency +$5021,& (address ) is preset to I2fN/IfN = % and can, as a rule, be retained without change. This ratio can be decreased in order to provide for a more stable setting in exceptional cases under especially unfavourable switch-on conditions The inrush restraint can be extended by the Crossblock function. This means that not only the phase with inrush current exhibiting harmonic content in excess of the permissible value is stabilized but also the other phases of the differential stage IDiff> are blocked. The duration for which the crossblock function is active can be limited under address $ &5266% +$50. Setting is in multiple of the AC-cycle. This parameter can only be changed with DIGSI 4 under Additional Settings. If set to (presetting) the protection can trip when the transformer is switched on a single-phase fault even while the other phases carry inrush current. If set to the crossblock function remains active as long as harmonic content is registered in any phase. Besides the 2nd harmonic, 7UT612 provides stabilization with a further harmonic: the n-th harmonic. Address 5(675 Q+$50 allows to select the +DUPRQLF or the +DUPRQLF, or to switch this n-th harmonic restraint 2)). Steady-state overexcitation of transformers is characterized by odd harmonic content. The 3rd or 5th harmonic is suitable to detect overexcitation. As the 3rd harmonic is often eliminated in the transformer windings (e.g. in a delta connected winding group), the 5th harmonic is usually used. Converter transformers also produce odd harmonic content. The harmonic content which blocks the differential stage IDiff> is set under address Q +$5021,&. For example, if the 5th harmonic restraint is used to avoid trip during overexcitation, 30 % (presetting) is convenient. Harmonic restraint with the n-th harmonic operates individual per phase. But possibility exists as with the inrush restraint to set the protection such that not only the phase with harmonic content in excess of the permissible value is stabilized but also the other phases of the differential stage IDiff> are blocked (crossblock function). The duration for which the crossblock function is active can be limited under address $ &5266% Q+$50. Setting is in multiple of the AC-cycle. This parameter can only be changed with DIGSI 4 under Additional Settings. If set to (presetting) the crossblock function is ineffective, if set to the crossblock function remains active as long as harmonic content is registered in any phase.
60
2.2.8
Setting Overview
Note: Addresses which have an A attached to its end can only be changed in DIGSI 4, under Additional Settings.
Addr. 1201
Setting Options OFF ON Block relay for trip commands OFF ON OFF ON OFF 3. Harmonic 5. Harmonic OFF ON 0.20..2.00 I/InO; 0 NO YES NO YES 0.05..2.00 I/InO 0.00..60.00 sec; 0.5..35.0 I/InO; 0.00..60.00 sec; 0.10..0.50 0.00..2.00 I/InO 0.25..0.95 0.00..10.00 I/InO 0.00..2.00 I/InO 1.0..2.0
OFF ON OFF
Increase of Trip Char. During Start Inrush with 2. Harmonic Restraint n-th Harmonic Restraint
1208 1210 1211A 1212A 1221 1226A 1231 1236A 1241A 1242A 1243A 1244A 1251A 1252A
I-DIFF> MON. I> CURR. GUARD DIFFw.IE1-MEAS DIFFw.IE2-MEAS I-DIFF> T I-DIFF> I-DIFF>> T I-DIFF>> SLOPE 1 BASE POINT 1 SLOPE 2 BASE POINT 2 I-REST. STARTUP START-FACTOR
ON 0.00 I/InO NO NO 0.20 I/InO 0.00 sec 7.5 I/InO 0.00 sec 0.25 0.00 I/InO 0.50 2.50 I/InO 0.10 I/InO 1.0
Differential Current monitoring I> for Current Guard Diff-Prot. with meas. Earth Current S1 Diff-Prot. with meas. Earth Current S2 Pickup Value of Differential Curr. T I-DIFF> Time Delay Pickup Value of High Set Trip T I-DIFF>> Time Delay Slope 1 of Tripping Characteristic Base Point for Slope 1 of Charac. Slope 2 of Tripping Characteristic Base Point for Slope 2 of Charac. I-RESTRAINT for Start Detection Factor for Increasing of Char. at Start
61
2 Functions
Addr. 1253 1256A 1257A 1261 1262A 1271 1272A 1273A 1281 1282
Default Setting 5.0 sec 4.00 I/InO 15 Cycle 15 % 3 Cycle 30 % 0 Cycle 1.5 I/InO 0.20 I/InO 2 sec
Comments Maximum Permissible Starting Time Pickup for Add-on Stabilization Duration of Add-on Stabilization 2nd Harmonic Content in I-DIFF Time for Cross-blocking 2nd Harm. n-th Harmonic Content in I-DIFF Time for Cross-blocking n-th Harm. Limit IDIFFmax of n-th Harm.Restraint Pickup Value of diff. Current Monitoring T I-DIFF> Monitoring Time Delay
CROSSB. 2. HARM 2..1000 Cycle; 0; n. HARMONIC CROSSB. n.HARM IDIFFmax n.HM I-DIFF> MON. T I-DIFF> MON. 10..80 % 2..1000 Cycle; 0; 0.5..20.0 I/InO 0.15..0.80 I/InO 1..10 sec
2.2.9
Information Overview
F.No. 05603 >Diff BLOCK 05615 Diff OFF 05616 Diff BLOCKED 05617 Diff ACTIVE 05620 Diff Adap.fact. 05631 Diff picked up 05644 Diff 2.Harm L1 05645 Diff 2.Harm L2 05646 Diff 2.Harm L3 05647 Diff n.Harm L1 05648 Diff n.Harm L2 05649 Diff n.Harm L3 05651 Diff Bl. exF.L1 05652 Diff Bl. exF.L2 05653 Diff Bl. exF.L3 05657 DiffCrosBlk2HM
Alarm
Comments >BLOCK differential protection Differential protection is switched OFF Differential protection is BLOCKED Differential protection is ACTIVE Diff: adverse Adaption factor CT Differential protection picked up Diff: Blocked by 2.Harmon. L1 Diff: Blocked by 2.Harmon. L2 Diff: Blocked by 2.Harmon. L3 Diff: Blocked by n.Harmon. L1 Diff: Blocked by n.Harmon. L2 Diff: Blocked by n.Harmon. L3 Diff. prot.: Blocked by ext. fault L1 Diff. prot.: Blocked by ext. fault L2 Diff. prot.: Blocked by ext. fault.L3 Diff: Crossblock by 2.Harmonic
62
F.No. 05658 DiffCrosBlknHM 05662 Block Iflt.L1 05663 Block Iflt.L2 05664 Block Iflt.L3 05666 Diff in.char.L1 05667 Diff in.char.L2 05668 Diff in.char.L3 05670 Diff I-Release 05671 Diff TRIP 05672 Diff TRIP L1 05673 Diff TRIP L2 05674 Diff TRIP L3 05681 Diff> L1 05682 Diff> L2 05683 Diff> L3 05684 Diff>> L1 05685 Diff>> L2 05686 Diff>> L3 05691 Diff> TRIP 05692 Diff>> TRIP 05701 Dif L1 : 05702 Dif L2 : 05703 Dif L3 : 05704 Res L1 : 05705 Res L2 : 05706 Res L3 :
Alarm
Comments Diff: Crossblock by n.Harmonic Diff. prot.: Blocked by CT fault L1 Diff. prot.: Blocked by CT fault L2 Diff. prot.: Blocked by CT fault L3 Diff: Increase of char. phase L1 Diff: Increase of char. phase L2 Diff: Increase of char. phase L3 Diff: Curr-Release for Trip Differential protection TRIP Differential protection: TRIP L1 Differential protection: TRIP L2 Differential protection: TRIP L3 Diff. prot.: IDIFF> L1 (without Tdelay) Diff. prot.: IDIFF> L2 (without Tdelay) Diff. prot.: IDIFF> L3 (without Tdelay) Diff. prot: IDIFF>> L1 (without Tdelay) Diff. prot: IDIFF>> L2 (without Tdelay) Diff. prot: IDIFF>> L3 (without Tdelay) Differential prot.: TRIP by IDIFF> Differential prot.: TRIP by IDIFF>> Diff. curr. in L1 at trip without Tdelay Diff. curr. in L2 at trip without Tdelay Diff. curr. in L3 at trip without Tdelay Restr.curr. in L1 at trip without Tdelay Restr.curr. in L2 at trip without Tdelay Restr.curr. in L3 at trip without Tdelay
63
2 Functions
2.3
L1 L2 L3
L1 L2 L3
ISP
7UT612
Figure 2-36
L1 L2 L3
L1 L2 L3
Figure 2-37
Restricted earth fault protection on a non-earthed transformer winding with neutral reactor (starpoint former) within the protected zone
64
3I0 = ISP
ISP
7UT612
L1 L2 L3
3I0" = IL1 + IL2 + IL3
L1 L2 L3
7UT612
3I0 = ISP
ISP
Figure 2-38
Restricted earth fault protection on an earthed shunt reactor with CTs in the reactor leads
L1 L2 L3
L1 L2 L3
ISP
3I0 = ISP
7UT612
Figure 2-39
Restricted earth fault protection on an earthed shunt reactor with 2 CT sets (treated like an auto-transformer)
65
2 Functions
L1 L2 L3
L1 L2 L3
7UT612
Figure 2-40
2.3.1
Function Description
During healthy operation, no starpoint current ISP flows through the starpoint lead, the sum of the phase currents 3I0 = IL1 + IL2 + IL3 is zero, too. When an earth fault occurs in the protected zone (Figure 2-41), a starpoint current ISP will flow; depending on the earthing conditions of the power system a further earth current may be recognized in the residual current path of the phase current transformers. Since all currents which flow into the protected zone are defined positive, the residual current from the system will be more or less in phase with the starpoint current.
Basic Principle
L1 L2 L3
ISP IL3
L1 L2 L3
Figure 2-41
When an earth fault occurs outside the protected zone (Figure 2-42), a starpoint current ISP will flow equally; but the residual current of the phase current transformers 3I0 is now of equal magnitude and in phase opposition with the starpoint current.
66
L1 L2 L3
ISP Figure 2-42 IL3
L1 L2 L3
When a fault without earth connection occurs outside the protected zone, a residual current may occur in the residual current path of the phase current transformers which is caused by different saturation of the phase current transformers under strong through-current conditions. This current could simulate a fault in the protected zone. Wrong tripping must be avoided under such condition. For this, the restricted earth fault protection provides stabilization methods which differ strongly from the usual stabilization methods of differential protection schemes since it uses, besides the magnitude of the measured currents, the phase relationship, too. Evaluation of the Measured Quantities The restricted earth fault protection compares the fundamental wave of the current flowing in the starpoint connection, which is designated as 3I0 in the following, with the fundamental wave of the sum of the phase currents, which should be designated in the following as 3I0". Thus, the following applies (Figure 2-43): 3I0' = ISP 3I0" = IL1 + IL2 + IL3 Only 3I0' acts as the tripping effect quantity, during a fault within the protected zone this current is always present.
L1 L2 L3
ISP
7UT612
Figure 2-43
When an earth fault occurs outside the protected zone, another earth current 3I0" flows though the phase current transformers. This is, on the primary side, in counterphase with the starpoint 3I0' current and has equal magnitude. The maximum informa-
67
2 Functions
tion of the currents is evaluated for stabilization: the magnitude of the currents and their phase position. The following is defined: A tripping effect current IREF = |3I0| and the stabilization or restraining current IRest = k (|3I0' 3I0"| |3I0' + 3I0"|) where k is a stabilization factor which will be explained below, at first we assume k = 1. IREF is derived from the fundamental wave and produces the tripping effect quantity, IRest counteracts this effect. To clarify the situation, three important operating conditions should be examined: a) Through-fault current on an external earth fault: 3I0" is in phase opposition with 3I0' and of equal magnitude i.e. 3I0" = 3I0' IREF = |3I0'| IRest = |3I0' + 3I0"| |3I0' 3I0"| = 2|3I0'| The tripping effect current (IREF) equals the starpoint current; restraint (IRest) corresponds to twice the tripping effect current. b) Internal earth fault, fed only from the starpoint: In this case, 3I0" = 0 IREF = |3I0'| IRest = |3I0' 0| |3I0' + 0| = 0 The tripping effect current (IREF) equals the starpoint current; restraint (IRest) is zero, i.e. full sensitivity during internal earth fault. c) Internal earth fault, fed from the starpoint and from the system, e.g. with equal earth current magnitude: In this case, 3I0" = 3I0' IREF = |3I0'| IRest = |3I0' 3I0'| |3I0' + 3I0'| = 2 |3I0'| The tripping effect current (IREF) equals the starpoint current; the restraining quantity (IRest) is negative and, therefore, set to zero, i.e. full sensitivity during internal earth fault. This result shows that for internal fault no stabilization is effective since the restraint quantity is either zero or negative. Thus, small earth current can cause tripping. In contrast, strong restraint becomes effective for external earth faults. Figure 2-44 shows that the restraint is the strongest when the residual current from the phase current transformers is high (area with negative 3I0"/3I0'). With ideal current transformers, 3I0"/3I0' would be 1. If the starpoint current transformer is designed weaker than the phase current transformers (e.g. by selection of a smaller accuracy limit factor or by higher secondary burden), no trip will be possible under through-fault condition even in case of severe saturation as the magnitude of 3I0" is always higher than that of 3I0'.
68
IREF IREF> 4
Tripping
3
Blocking
-0.3
-0.2
-0.1
0.0
0.1
0.2
Figure 2-44
Tripping characteristic of the restricted earth fault protection depending on the earth current ratio 3I0"/3I0' (both currents in phase + or counter-phase ); IREF = tripping effect current; IREF> = setting value
It was assumed in the above examples that the currents 3I0" and 3I0 are in counterphase for external earth faults which is only true for the primary measured quantities. Current transformer saturation may cause phase shifting between the fundamental waves of the secondary currents which reduces the restraint quantity. If the phase displacement (3I0"; 3I0') = 90 then the restraint quantity is zero. This corresponds to the conventional method of direction determination by use of the vectorial sum and difference comparison (Figure 2-45).
+3I0"
3 I0"
3I0'
IRest for k = 1
Figure 2-45
69
2 Functions
The restraint quantity can be influenced by means of a factor k. This factor has a certain relationship to the limit angle limit. This limit angle determines, for which phase displacement between 3I0" and 3I0 the pickup value grows to infinity when 3I0" = 3I0, i.e. no pickup occurs. In 7UT612 is k = 2, i.e. the restraint quantity in the above example a) is redoubled once more: the restraint quantity IRest is 4 times the tripping effect quantity IREF. The limit angle is limit = 110. That means no trip is possible for phase displacement (3I0"; 3I0') 110. Figure 2-46 shows the operating characteristics of the restricted earth fault protection dependent of the phase displacement between 3I0" and 3I0', for a constant infeed ratio |3I0"| = |3I0'|.
IREF IREF> 4
Tripping
3
Blocking
1
120
110
100
90
80
70
(3Io";3Io')
Figure 2-46
Tripping characteristic of the restricted earth fault protection depending on the phase displacement between 3I0" and 3I0 at 3I0" = 3I0' (180 = external fault)
It is possible to increase the tripping value in the tripping area proportional to the arithmetic sum of all currents, i.e. with the sum of the magnitudes |I| = |IL1 | + |IL2 | + |IL3 | + |ISP | (Figure 2-47). The slope of this stabilization can be set.
I5()
" " TGPQ@
|I|
Figure 2-47 Increasing the pickup value
70
"
FNo 05817
DS@A3
REF picked up
IL1 IL1 IL1 I7 |3I0'| > k(|3I0'3I0"| |3I0'+3I0"|) |IL1 | + |IL2 | + |IL3 | + |ISt |
&
" !UD@9T3
T Meas. release 0
FNo 05816
REF T start
FNo 05821
REF TRIP
FNo 05812
FNo 05803
>BLOCK REF
REF BLOCKED
FNo 05813
S@AQSPU
1
& 1 &
REF ACTIVE
FNo 05811
PI 7ypxryh PAA
REF OFF
Figure 2-48
2.3.2
Note:
When delivered from factory, the restricted earth fault protection is switched 2)). The reason is that the protection must not be in operation unless at least the assigned side and the CT polarity have been set before. Without proper settings, the device may show unexpected reactions (incl. tripping)! The sensitivity of the restricted earth fault protection is determined by the pickup value ,5()! (address ). The earth fault current which flows through the starpoint lead of the protected object (transformer, generator, motor, shunt reactor) is decisive. A further earth current which may be supplied from the network does not influence the sensitivity. The setting value is referred to the nominal current of the protected side. The set value can be increased in the tripping quadrant depending on the arithmetic sum of the currents (stabilization by the sum of all current magnitudes) which is set under address $ 6/23(. This parameter can only be changed with DIGSI 4 under Additional Settings. The preset value is normally adequate. In special cases it may be advantageous to delay the trip signal of the protection. For. this, an additional delay can be set. The timer $ 7 ,5()! is started when an internal fault is detected. This setting is a pure delay time which does not include the inherent operating time of the protection.
71
2 Functions
2.3.3
Setting Overview
Note: Addresses which have an A attached to its end can only be changed in DIGSI 4, under Additional Settings.
Addr. 1301
Setting Options OFF ON Block relay for trip commands 0.05..2.00 I / In 0.00..60.00 sec; 0.00..0.95
Pick up value I REF> T I-REF> Time Delay Slope of Charac. I-REF> = f(I-SUM)
2.3.4
Information Overview
F.No. 05803 >BLOCK REF 05811 REF OFF 05812 REF BLOCKED 05813 REF ACTIVE 05836 REF Adap.fact. 05817 REF picked up 05816 REF T start 05821 REF TRIP 05826 REF D: 05827 REF S: 05830 REF Err CTstar 05835 REF Not avalia.
Alarm
Comments >BLOCK restricted earth fault prot. Restricted earth fault is switched OFF Restricted earth fault is BLOCKED Restricted earth fault is ACTIVE REF: adverse Adaption factor CT Restr. earth flt.: picked up Restr. earth flt.: Time delay started Restr. earth flt.: TRIP REF: Value D at trip (without Tdelay) REF: Value S at trip (without Tdelay) REF err.: No starpoint CT REF err: Not avaliable for this objekt
72
2.4
General
2.4.1
2.4.1.1
Function Description
Definite Time Overcurrent Protection The definite time stages for phase currents and residual current are always available even if an inverse time characteristic has been configured according to Subsection 2.1.1 (addresses and/or ).
Pickup, Trip
Two definite time stages are available for each the phase currents and the residual current (3I0). Each phase current and the residual current 3I0 are compared with the setting value ,!! (common setting for the three phase currents) and ,!! (independent setting for 3I0). Currents above the associated pickup value are detected and annunciated. When the respective delay time 7 ,!! or 7 ,!! is expired, tripping command is issued. The reset value is approximately 5 % below the pickup value for currents > 0.3 IN. Figure 2-49 shows the logic diagram for the high-current stages I>> and 3I0>>.
73
2 Functions
Dvh D3vh
&
Man. Close
!
IL1 IL2 IL3
D33
FNo 1762 ... 1764
I>>
! ! UD33
&
T 0
1 1
FNo 1800
I>> picked up
FNo 1805
L1 L2 L3
FNo 1721 Release meas. Release meas. Release meas.
I>> TRIP
FNo 1804
FNo 1852
>BLOCK I>>
FNo 1704
I>> BLOCKED
FNo 1752
! QC6T@P8
1
FNo 1753
2)) 21
"Dvh "D3vh
&
"D33
FNo 1766
Man. Close
!!
3I0
I>>
3I0>> picked up
!! !U"D33
&
FNo 1742 T 0
FNo 1903
3I0>> TRIP
FNo 1902
Release meas.
>BLOCK 3I0>>
FNo 1741
3I0> BLOCKED
FNo 1749
!!
1
"DP8
FNo 1750
2)) 21
Figure 2-49
Logic diagram of the high-set stages I>> for phase currents and residual current
74
Each phase current and the residual current 3I0 are, additionally, compared with the setting value ,! (common setting for the three phase currents) and ,! (independent setting for 3I0). When the set thresholds are exceeded, pickup is annunciated. But if inrush restraint is used (cf. Subsection 2.4.1.5), a frequency analysis is performed first (Subsection 2.4.1.5). If an inrush condition is detected, pickup annunciation is suppressed and an inrush message is output instead. When, after pickup without inrush recognition, the relevant delay times 7 ,! or 7 ,! are expired, tripping command is issued. During inrush condition no trip is possible but expiry of the timer is annunciated. The reset value is approximately 5 % below the pickup value for currents > 0,3IN. Figure 2-50 shows the logic diagram of the stages I> for phase currents, Figure 2-51 for residual current. The pickup values for each of the stages, I> (phase currents), 3I0> (residual current), I>> (phase currents), 3I0>> (residual current) and the delay times can be set individually.
Man. Close
(s. Fig. 2-56)
I> InRush PU
FNo 7565 ... 7567
Rush Blk L1
! " D3
IL1 IL2 IL3
I>
1
&
1 1
FNo 1810
I> picked up
FNo 1815
UD3 ! #
&
T 0
I> TRIP
L1 L2 L3
FNo 1722
1
Meas. release Meas. release Meas. release
FNo 1814
FNo 1851
>BLOCK I>
FNo 1704
I> BLOCKED
FNo 1752
! QC6T@P8
1
FNo 1753
2)) 21
Figure 2-50
75
2 Functions
"Dvh "D3vh
&
FNo 7569
3I0> InRush PU
FNo 7568
!! " "D3
3I0
& &
3I0 InRush PU
FNo 1766
I>
3I0> picked up
!! #U"D3
&
T 0
&
FNo 1906
3I0> TRIP
FNo 1905
>BLOCK 3I0>
FNo 1741
3I0> BLOCKED
FNo 1749
!!
1
"DP8 2)) 21
FNo 1750
Figure 2-51
2.4.1.2
Inverse Time Overcurrent Protection The inverse time overcurrent stages operate with a characteristic either according to the IEC- or the ANSI-standard or with a user-defined characteristic. The characteristic curves and their equations are represented in Technical Data (Figures 4-7 to 4-9 in Section 4.4). When configuring one of the inverse time characteristics, definite time stages I>> and I> are also enabled (see Section 2.4.1.1).
Pickup, Trip
Each phase current and the residual current (sum of phase currents) are compared, one by one, to a common setting value ,S and a separate setting ,S. If a current exceeds 1.1 times the setting value, the corresponding stage picks up and is signalled selectively. But if inrush restraint is used (cf. Subsection 2.4.1.5), a frequency analysis is performed first (Subsection 2.4.1.5). If an inrush condition is detected, pickup annunciation is suppressed and an inrush message is output instead. The RMS values of the basic oscillations are used for pickup. During the pickup of an Ip stage, the tripping time is calculated from the flowing fault current by means of an integrating measuring procedure, depending on the selected tripping characteristic. After the expiration of this period, a trip command is transmitted as long as no inrush current is detected or inrush restraint is disabled. If inrush restraint is enabled and inrush current is de-
76
tected, there will be no tripping. Nevertheless, an annunciation is generated indicating that the time has expired. For the residual current ,S the characteristic can be selected independent from the characteristic used for the phase currents. The pickup values for the stages Ip (phase currents), 3I0p (residual current) and the delay times for each of these stages can be set individually. Figure 2-52 shows the logic diagram of the inverse time stages for phase currents, Figure 2-53 for residual current. Dropout for IEC Curves Dropout of a stage using an IEC curves occurs when the respective current decreases below about 95 % of the pickup value. A renewed pickup will cause a renewed start of the delay timers. Using the ANSI-characteristics you can determine whether the dropout of a stage is to follow right after the threshold undershot or whether it is evoked by disk emulation. Right after means that the pickup drops out when the pickup value of approx. 95 % is undershot. For a new pickup the time counter starts at zero.
Man. Close
(s. Fig. 2-56)
Ip InRush PU
FNo 7565 ... 7567
Rush Blk L1
!!
IL1 IL2 IL3
1,1 Ip
!!$ D@88VSW@
&
1
!!!UD
t
1 1
FNo 1820
Ip picked up
FNo 1825
&
I
&
1 1
Ip TRIP
FNo 1824
L1 L2 L3
FNo 1723
Ip Time Out
>BLOCK Ip
FNo 1704
Ip BLOCKED
FNo 1752
! QC6T@P8
1
FNo 1753
2)) 21
Figure 2-52
Logic diagram of the inverse time overcurrent stages Ip for phase currents example for IECcurves
77
2 Functions
&
FNo 7570
3I0p InRush PU
FNo 7568
&
3I0 InRush PU
FNo 1766
!!!
3I0
"D
&
1,1I>
D@88VSW@ !!!!U"D
&
I
3I0p picked up
FNo 1909
3I0p TRIP
FNo 1908
&
3I0p TimeOut
FNo 1744 Meas. release FNo 1859
>BLOCK 3I0p
FNo 1741
3I0p BLOCKED
FNo 1749
!! "DP8
1
FNo 1750
2)) 21
Figure 2-53
Logic diagram of the inverse time overcurrent stage for residual current example for IECcurves
The disk emulation evokes a dropout process (time counter is decrementing) which begins after de-energization. This process corresponds to the back turn of a Ferrarisdisk (explaining its denomination disk emulation). In case several faults occur successively, it is ensured that due to the inertia of the Ferraris-disk the history is taken into consideration and the time behaviour is adapted. The reset begins as soon as 90 % of the setting value is undershot, in correspondence to the dropout curve of the selected characteristic. Within the range of the dropout value (95 % of the pickup value) and 90 % of the setting value, the incrementing and the decrementing processes are in idle state. If 5 % of the setting value is undershot, the dropout process is being finished, i.e. when a new pickup is evoked, the timer starts again at zero. The disk emulation offers its advantages when the grading coordination chart of the time overcurrent protection is combined with other devices (on electro-mechanical or induction base) connected to the system. User-Specified Curves The tripping characteristic of the user-configurable curves can be defined via several points. Up to 20 pairs of current and time values can be entered. With these values the device approximates a characteristic by linear interpolation. If required, the dropout characteristic can also be defined. For the functional description see Dropout for ANSI Curves. If no user-configurable dropout characteristic is desired, dropout is initiated when approx. a 95 % of the pickup value is undershot; when a new pickup is evoked, the timer starts again at zero.
78
2.4.1.3
Manual Close Command When a circuit breaker is closed onto a faulted protected object, a high speed re-trip by the breaker is often desired. The manual closing feature is designed to remove the delay from one of the time overcurrent stages when the breaker is manually closed onto a fault. The time delay is then bypassed via an impulse from the external control switch. This impulse is prolonged by a period of at least 300 ms (Figure 2-54). Addresses $ 0$18$/ &/26( and/or $ , 0$1 &/26( determine for which stages the delay is defeated under manual close condition.
FNo 00356
>Manual Close
50 ms 0 300 ms
FNo 00561
Man.Clos.
Man. Close (internal)
Figure 2-54
2.4.1.4
Dynamic Cold Load Pickup With the dynamic cold load pickup feature, it is possible to dynamically increase the pickup values of the time overcurrent protection stages when dynamic cold load overcurrent conditions are anticipated, i.e. when consumers have increased power consumption after a longer period of dead condition, e.g. in air conditioning systems, heating systems, motors, etc. By allowing pickup values and the associated time delays to increase dynamically, it is not necessary to incorporate cold load capability in the normal settings. Processing of the dynamic cold load pickup conditions is common for all time overcurrent stages, and is explained in Section 2.6 (page 108). The alternative values themselves are set for each of the stages.
2.4.1.5
Inrush Restraint When switching unloaded transformers or shunt reactors on a live busbar, high magnetizing (inrush) currents may occur. They can amount to a multiple of the rated current and, dependent on the transformer size and design, may last from several milliseconds to several seconds. Although overcurrent detection is based only on the fundamental harmonic component of the measured currents, false pickup due to inrush might occur since the inrush current may even comprise a considerable component of fundamental harmonic. The time overcurrent protection provides an integrated inrush restraint function which blocks the overcurrent stages I> and Ip (not I>>) for phase and residual currents in case of inrush detection. After detection of inrush currents above a pickup value special inrush signals are generated. These signals also initiate fault annunciations and 79
2 Functions
start the assigned trip delay time. If inrush current is still detected after expiration of the delay time, an annunciation is output. Tripping is suppressed. The inrush current is characterized by a considerable 2nd harmonic content (double rated frequency) which is practically absent in the case of a short-circuit. If the second harmonic content of a phase current exceeds a selectable threshold, trip is blocked for this phase. Similar applies for the residual current stages. The inrush restraint feature has an upper operation limit. Above this (adjustable) current blocking is suppressed since a high-current fault is assumed in this case. The lower limit is the operating limit of the harmonic filters (0.2 IN). Figure 2-55 shows a simplified logic diagram.
!# !C6SHQuhr
IL1 IL2 IL3
fN 2fN
&
L1 L2 L3
DHhDSQu !#!
FNo 07571
!! DSuSrQu
1
2)) 21
Figure 2-55
Logic diagram of the inrush restraint feature example for phase currents
Inrush det.. L1
Rush Blk L1
Inrush det.. L2
Rush Blk L2
Inrush det.. L3
8SPTT7GFQuhr !#"
1
U8SPTT7GFQu !##
Rush Blk L3
IP `@T
&
FNo 01843
INRUSH X-BLK
Figure 2-56
Since the harmonic restraint operates individually per phase, the protection is fully operative even when e.g. the transformer is switched onto a single-phase fault, whereby inrush currents may possibly be present in one of the healthy phases. However, it is
80
also possible to set the protection such that not only the phase with inrush current exhibiting harmonic content in excess of the permissible value is blocked but also the other phases of the associated stage are blocked (so called cross-block function). This cross-block can be limited to a selectable duration. Figure 2-56 shows the logic diagram. Crossblock refers only to the phase current stages against each other. Phase inrush currents do not block the residual current stages nor vice versa.
2.4.1.6
Fast Busbar Protection Using Reverse Interlocking Each of the overcurrent stages can be blocked via binary inputs of the relay. A setting parameter determines whether the binary input operates in the normally open (i.e. energize input to block) or the normally closed (i.e. energize input to release) mode. Thus, the overcurrent time protection can be used as fast busbar protection in star connected networks or in open ring networks (ring open at one location), using the reverse interlock principle. This is used in high voltage systems, in power station auxiliary supply networks, etc., in which cases a transformer feeds from the higher voltage system onto a busbar with several outgoing feeders (refer to Figure 2-57).
Application Example
Infeed direction
Idiff
I>
I>>
7UT612
T I> T I>>
3D33iypx
I>
I>
t1
t1
Trip
Trip
Trip
Trip
Trip
T I>
T I>>
t1
: :
Figure 2-57
81
2 Functions
The time overcurrent protection is applied to the lower voltage side. Reverse interlocking means, that the overcurrent time protection can trip within a short time TI>>, which is independent of the grading time, if it is not blocked by pickup of one of the next downstream time overcurrent relays (Figure 2-57). Therefore, the protection which is closest to the fault will always trip within a short time, as it cannot be blocked by a relay behind the fault location. The time stages I> or Ip operate as delayed backup stages.
2.4.2
2.4.2.1 General
Phase Current Stages In address 3+$6( 2& time overcurrent protection for phase currents can be switched 21 or 2)). Address $ 0$18$/ &/26( determines the phase current stage which is to be activated instantaneously with a detected manual close. Settings ,!! LQVWDQW and ,! LQVWDQW can be set independent from the type of characteristic selected. ,S LQVWDQW is only available if one of the inverse time stages is configured. This parameter can only be changed with DIGSI 4 under Additional Settings. If time overcurrent protection is applied on the supply side of a transformer, select the higher stage I>> which does not pick up during inrush conditions or set the manual close feature to ,QDFWLYH. In address ,Q5XVK5HVW 3K inrush restraint (restraint with 2nd harmonic) is enabled or disabled for all phase current stages of time overcurrent protection (excepted the I>> stage). Set 21 if one time overcurrent protection stage is to operate at the supply side of a transformer. Otherwise, use setting 2)). If you intend to set a very small pickup value for any reason, consider that the inrush restraint function cannot operate below 20 % nominal current (lower limit of harmonic filtering).
If I>>stage ,!! (address ) is combined with I>stage or Ipstage, a two-stage characteristic will be the result. If one stage is not required, the pickup value has to be set to . Stage ,!! always operates with a defined delay time. If time overcurrent protection is used on the supply side of a transformer, a series reactor, a motor or starpoint of a generator, this stage can also be used for current grad-
82
ing. Setting instructs the device to pick up on faults only inside the protected object but not for traversing fault currents. Calculation example: Power transformer feeding a busbar, with the following data: Power transformer YNd5 35 MVA 110 kV/20 kV usc = 15 % 200 A/5 A on the 110 kV side
Current transformers
The time overcurrent protection is assigned to the 110 kV side (= feeding side). The maximum possible three-phase fault current on the 20 kV side, assuming a constant voltage source on the 110 kV side, is: S 1 WUDQVI 1 35 MVA 1 1 I SROH PD[ = ----------------- I 1 WUDQVI = ----------------- ------------------ = ---------- ----------------------------- = 1224.7 A 0.15 3 110 kV u VF WUDQVI u V F WUDQVI 3U
1
Assumed a safety margin of 20 %, the primary setting value results: Setting value I>> = 1.2 1224.7 A = 1470 A For setting in primary values via PC and DIGSI 4 this value can be set directly. For setting with secondary values the currents will be converted for the secondary side of the current transformer. Secondary setting value: 1470 A Setting value I>> = ------------------ 5 A = 36.7 A 200 A i.e. for fault currents higher than 1470 A (primary) or 36.7 A (secondary) the fault is in all likelihood located in the transformer zone. This fault can immediately be cleared by the time overcurrent protection. Increased inrush currents, if their fundamental oscillation exceeds the setting value, are rendered harmless by delay times (address 7 ,!!). The inrush restraint does not apply to stages I>>. Using reverse interlocking (Subsection 2.4.1.6, see also Figure 2-57) the multi-stage function of the time overcurrent protection offers its advantages: Stage 7 ,!! e. g. is used as accelerated busbar protection having a short safety delay ,!! (e. g. 50 ms). For faults at the outgoing feeders the stage I>> is blocked. Stages ,S or ,! serve as backup protection. The pickup values of both stages (,! or ,S and ,!!) are set equal. Time delay 7 ,! or 7 ,S (IEC characteristic) or ' ,S (ANSI characteristic) is set such that it overgrades the delay for the outgoing feeders. If fault protection for motors is applied, you have to make sure that the setting value ,!! is smaller than the smallest (two-pole) fault current and higher than the highest startup current. Since the maximum appearing startup current is usually below 1.6 x the rated startup current (even with unfavourable conditions), the following setting is adequate for fault current stage I>>: 1.6 Istartup > ,!! < Isc2-pole The increased startup current possibly caused by overvoltage is already considered with factor 1.6. Stage I>> can trip instantaneously (7 ,!! = V) since there is no saturation of shunt reactance for motors, other than for transformers.
83
2 Functions
The settable time 7 ,!! is an additional time delay and does not include the operating time (measuring time, dropout time). The delay can be set to infinity . If set to infinity, the pickup of this function will be indicated but the stage will not trip after pickup. If the pickup threshold is set to , neither a pickup annunciation nor a trip is generated. Definite Time Overcurrent Stages I> For setting the time overcurrent stage ,! (address ) the maximum appearing operational current is relevant. A pickup caused by an overload must be excluded, as the device operates in this mode as fault protection with correspondingly short tripping times and not as overload protection. For lines or busbars a rate of approx. 20 % above the maximum expected (over)load is set, for transformers and motors a rate of approx. 40 %. The settable time delay (address 7 ,!) results from the grading coordination chart defined for the network. The settable time is an additional time delay and does not include the operating time (measuring time, dropout time). The delay can be set to infinity . If set to infinity, the pickup of the corresponding function will be signalled but the stage will not issue a trip command. If the pickup threshold is set to , neither a pickup annunciation nor a trip is generated. Inverse Time Overcurrent Stages Ip with IEC curves The inverse time stages, depending on the configuration (Subsection 2.1.1, address ), enable the user to select different characteristics. With the IEC characteristics (address '07,'07 3+ &+ = 72& ,(&) the following is made available in address ,(& &859(: 1RUPDO ,QYHUVH (type A according to IEC 602553), 9HU\ ,QYHUVH (type B according to IEC 602553), ([WUHPHO\ ,QY (type C according to IEC 602553), and /RQJ ,QYHUVH (type B according to IEC 602553). The characteristics and equations they are based on are listed in the Technical Data (Section 4.4, Figure 4-7). If the inverse time trip characteristic is selected, it must be noted that a safety factor of about 1.1 has already been included between the pickup value and the setting value. This means that a pickup will only occur if a current of about 1.1 times of the setting value is present. The function will reset as soon as the value undershoots 95 % of the pickup value. The current value is set in address ,S. The maximum operating current is of primary importance for the setting. A pickup caused by an overload must be excluded, as the device operates in this mode as fault protection with correspondingly short tripping times and not as overload protection. The corresponding time multiplier is accessible via address 7 ,S. The time multiplier must be coordinated with the grading coordination chart of the network. The time multiplier can also be set to . If set to infinity, the pickup of this function will be indicated but the stage will not trip after pickup. If the Ipstage is not required, select address '07,'07 3+ &+ = 'HILQLWH 7LPH when configuring the protection functions (Subsection 2.1.1). Inverse Time Overcurrent Stages Ip with ANSI curves The inverse time stages, depending on the configuration (Subsection 2.1.1, address ), enable the user to select different characteristics. With the ANSI characteristics
84
85
2 Functions
For inverse-time overcurrent protection the user may define his own tripping and dropout characteristic. For configuration in DIGSI 4 a dialog box is to appear. Enter up to 20 pairs of current value and tripping time value (Figure 2-58). In DIGSI 4 the characteristic can also be viewed as an illustration, see the right part of Figure 2-58.
Figure 2-58
To create a user-defined tripping characteristic, the following must be set for configuration of the functional scope (Subsection 2.1.1): address '07,'07 3+ &+, option 8VHU 'HILQHG 38. If you also want to specify the dropout characteristic, set 8VHU GHI 5HVHW. Value pairs are referred to the setting values for current and time. Since current values are rounded in a specific table before they are processed in the device (see Table 2-3), we recommend to use exactly the same preferred current values you can find in this table. .
Table 2-3 ,,S 1.00 1.06 1.13 1.19 1.25 1.31 1.38 1.44 Preferred values of the standard currents for user specified trip characteristics WR 1.50 1.56 1.63 1.69 1.75 1.81 1.88 1.94 ,,S 2.00 2.25 2.50 2.75 3.00 3.25 WR 3.50 3.75 4.00 4.25 4.50 4.75 ,,S 5.00 5.25 5.50 5.75 6.00 6.25 WR 6.50 6.75 7.00 7.25 7.50 7.75 ,,S 8.00 9.00 10.00 11.00 12.00 13.00 14.00 WR 15.00 16.00 17.00 18.00 19.00 20.00
86
T/Tp
Largest current point Smallest current point
Reset
Trip
20
I/Ip
Currents greater than the current value of the greatest characteristic point do not lead to a reduction of the tripping time. The pickup characteristic (see Figure 2-59, right side) goes parallel to the current axis, beginning with the greatest characteristic point. For specification of a dropout characteristic please observe the following: For currents select the values from Table 2-4 and add the corresponding time values. Deviating values I/Ip are rounded. This, however, will not be indicated. Currents greater than the current value of the greatest characteristic point do not lead to a prolongation of the dropout time. The dropout characteristic (see Figure 259, left side) goes parallel to the current axis, up to the greatest characteristic point. Currents smaller than the current value of the smallest characteristic point do not lead to a reduction of the dropout time. The dropout characteristic (see Figure 2-59, left side) goes parallel to the current axis, beginning with the smallest characteristic point.
87
2 Functions
Currents smaller than 0.05 times the setting value of currents lead to an immediate dropout. .
Table 2-4 ,,S 1.00 0.99 0.98 0.97 0.96 0.95 0.94 Preferred values of the standard currents for user specified reset characteristics WR 0.93 0.92 0.91 0.90 0.89 0.88 0.86 ,,S 0.84 0.83 0.81 0.80 0.78 0.77 WR 0.75 0.73 0.72 0.70 0.69 0.67 ,,S 0.66 0.64 0.63 0.61 0.59 0.56 WR 0.53 0.50 0.47 0.44 0.41 0.38 ,,S 0.34 0.31 0.28 0.25 0.22 0.19 WR 0.16 0.13 0.09 0.06 0.03 0.00
Inrush Restraint
In address ,Q5XVK5HVW 3K of the general settings (page 82, margin heading General) the inrush restraint can be enabled (21) or disabled (2))). Especially for transformers and if overcurrent time protection is used on the supply side, this inrush restraint is required. Function parameters of the inrush restraint are set in Inrush. It is based on an evaluation of the 2nd harmonic present in the inrush current. The ratio of 2nd harmonics to the fundamental +$50 3KDVH (address ) is set to I2fN/ IfN = % as default setting. It can be used without being changed. To provide more restraint in exceptional cases, where energizing conditions are particularly unfavourable, a smaller value can be set in the address before-mentioned. If the current exceeds the value indicated in address , 0D[ ,Q5U 3K, no restraint will be provoked by the 2nd harmonic. The inrush restraint can be extended by the so-called cross-block function. This means that if the harmonic component is only exceeded in one phase, all three phases of the I> or Ipstages are blocked. In address &5266 %/.3KDVH the crossblock function is set to 21 or 2)). The time period for which the crossblock function is active after detection of inrushes is set at address 7 &5266 %/.3K.
2.4.2.2 General
Residual Current Stages In address , 2&, time overcurrent protection for residual current can be set to 21 or 2)). Address $ , 0$1 &/26( determines which residual current stage is to be activated instantaneously with a detected manual close. Settings ,!! LQVWDQW and ,! LQVWDQW can be set independent from the type of characteristic selected. ,S LQVWDQW is only available if one of the inverse time stages is configured. This
88
89
2 Functions
The inverse time stage, depending on the configuration (Subsection 2.1.1, address ), enables the user to select different characteristics. With the IEC characteristics (address '07,'07 , &+ = 72& ,(&) the following is made available in address ,(& &859(: 1RUPDO ,QYHUVH (type A according to IEC 602553), 9HU\ ,QYHUVH (type B according to IEC 602553), ([WUHPHO\ ,QY (type C according to IEC 602553), and /RQJ ,QYHUVH (type B according to IEC 602553). The characteristics and equations they are based on are listed in the Technical Data (Section 4.4, Figure 4-7). If the inverse time trip characteristic is selected, it must be noted that a safety factor of about 1.1 has already been included between the pickup value and the setting value. This means that a pickup will only occur if a current of about 1.1 times of the setting value is present. The function will reset as soon as the value undershoots 95 % of the pickup value. The current value is set in address ,S. The most relevant for this setting is the minimum appearing earth fault current. The corresponding time multiplier is accessible via address 7 ,S. This has to be coordinated with the grading coordination chart of the network. For earth currents with earthed network, you can mostly set up a separate grading coordination chart with shorter delay times. If you set a very small pickup value, consider that the inrush restraint function cannot operate below 20 % nominal current (lower limit of harmonic filtering). An adequate time delay could be reasonable. The time multiplier can also be set to . If set to infinity, the pickup of this function will be indicated but the stage will not be able to trip after pickup. If the Ipstage is not required, select address '07,'07 , &+ = 'HILQLWH 7LPH when configuring the protection functions (Subsection 2.1.1).
The inverse time stages, depending on the configuration (Subsection 2.1.1, address ), enable the user to select different characteristics. With the ANSI characteristics (address '07,'07 , &+ = 72& $16,) the following is made available in address $16, &859(: 'HILQLWH ,QY, ([WUHPHO\ ,QY, ,QYHUVH, /RQJ ,QYHUVH, 0RGHUDWHO\ ,QY, 6KRUW ,QYHUVH, and 9HU\ ,QYHUVH. The characteristics and the equations they are based on are listed in the Technical Data (Section 4.4, Figures 4-8 and 4-9). If the inverse time trip characteristic is selected, it must be noted that a safety factor of about 1.1 has already been included between the pickup value and the setting value. This means that a pickup will only occur if a current of about 1.1 times of the setting value is present. The current value is set in address ,S. The most relevant for this setting is the minimum appearing earth fault current.
90
91
2 Functions
I2fN/IfN = %. It can be used without being changed. To provide more restraint in exceptional cases, where energizing conditions are particularly unfavourable, a smaller value can be set in the address before-mentioned. If the current exceeds the value indicated in address , 0D[ ,Q5U ,, no restraint will be provoked by the 2nd harmonic.
2.4.3
Setting Overview
The following list indicates the setting ranges and the default settings of a rated secondary current IN = 1 A. For a rated secondary current of IN = 5 A these values have to be multiplied by 5. For settings in primary values, a conversion rate from current transformers has to be considered additionally.
Note: Addresses which have an A attached to their end can only be changed in DIGSI 4, Section Additional Settings.
Phase Currents
Addr. 2001 2002 2008A Setting Title PHASE O/C InRushRest. Ph MANUAL CLOSE ON OFF ON OFF I>> instantaneously I> instantaneously Ip instantaneously Inactive 0.10..35.00 A; 0.00..60.00 sec; 0.10..35.00 A; 0.00..60.00 sec; 0.10..35.00 A; 0.00..60.00 sec; 0.10..35.00 A; 0.00..60.00 sec; 0.10..4.00 A 0.05..3.20 sec; 0.50..15.00; Instantaneous Disk Emulation Setting Options Default Setting OFF OFF I>> instantaneously Comments Phase Time Overcurrent InRush Restrained O/C Phase O/C Manual Close Mode
2011 2012 2013 2014 2111 2112 2113 2114 2021 2022 2023 2024
I>> T I>> I> T I> I>> T I>> I> T I> Ip T Ip D Ip TOC DROP-OUT
2.00 A 0.00 sec 1.00 A 0.50 sec 10.00 A 0.00 sec 2.00 A 0.30 sec 1.00 A 0.50 sec 5.00 Disk Emulation
I>> Pickup T I>> Time Delay I> Pickup T I> Time Delay I>> Pickup T I>> Time Delay I> Pickup T I> Time Delay Ip Pickup T Ip Time Dial D Ip Time Dial TOC Drop-out characteristic
92
Addr. 2025
Setting Options Normal Inverse Very Inverse Extremely Inverse Long Inverse Very Inverse Inverse Short Inverse Long Inverse Moderately Inverse Extremely Inverse Definite Inverse 0.10..4.00 A 0.05..3.20 sec; 0.50..15.00; 1.00..20.00 I / Ip; 0.01..999.00 Time Dial 0.05..0.95 I / Ip; 0.01..999.00 Time Dial 10..45 % 0.30..25.00 A
Comments
2026
ANSI CURVE
Very Inverse
ANSI Curve
Ip T Ip D Ip I/Ip PU T/Tp MofPU Res T/Tp 2.HARM. Phase I Max InRr. Ph.
Ip Pickup T Ip Time Dial D Ip Time Dial Pickup Curve I/Ip - TI/TIp Multiple of Pickup <-> TI/TIp
2nd harmonic O/C Ph. in % of fundamental Maximum Current for Inr. Rest. O/C Phase CROSS BLOCK O/C Phase CROSS BLOCK Time O/C Phase
Residual Current
Addr. 2201 2202 2208A Setting Title 3I0 O/C InRushRest. 3I0 3I0 MAN. CLOSE ON OFF ON OFF 3I0>> instantaneously 3I0> instantaneously 3I0p instantaneously Inactive 0.05..35.00 A; 0.00..60.00 sec; 0.05..35.00 A; 0.00..60.00 sec; 0.05..35.00 A; Setting Options Default Setting OFF OFF 3I0>> instantaneously Comments 3I0 Time Overcurrent InRush Restrained O/C 3I0 O/C 3I0 Manual Close Mode
3I0>> Pickup T 3I0>> Time Delay 3I0> Pickup T 3I0> Time Delay 3I0>> Pickup
93
2 Functions
Setting Title T 3I0>> 3I0> T 3I0> 3I0p T 3I0p D 3I0p TOC DROP-OUT IEC CURVE
Setting Options 0.00..60.00 sec; 0.05..35.00 A; 0.00..60.00 sec; 0.05..4.00 A 0.05..3.20 sec; 0.50..15.00; Instantaneous Disk Emulation Normal Inverse Very Inverse Extremely Inverse Long Inverse Very Inverse Inverse Short Inverse Long Inverse Moderately Inverse Extremely Inverse Definite Inverse 0.05..4.00 A 0.05..3.20 sec; 0.50..15.00; 1.00..20.00 I / Ip; 0.01..999.00 Time Dial 0.05..0.95 I / Ip; 0.01..999.00 Time Dial 10..45 % 0.30..25.00 A
Default Setting 0.00 sec 1.50 A 0.30 sec 0.20 A 0.20 sec 5.00 Disk Emulation Normal Inverse
Comments T 3I0>> Time Delay 3I0> Pickup T 3I0> Time Delay 3I0p Pickup T 3I0p Time Dial D 3I0p Time Dial TOC Drop-out Characteristic IEC Curve
2226
ANSI CURVE
Very Inverse
ANSI Curve
3I0p T 3I0p D 3I0p I/I0p PU T/TI0p MofPU ResT/TI0p 2.HARM. 3I0 I Max InRr. 3I0
3I0p Pickup T 3I0p Time Dial D 3I0p Time Dial Pickup Curve 3I0/3I0p - T3I0/ T3I0p Multiple of Pickup <-> T3I0/ T3I0p
15 % 7.50 A
2nd harmonic O/C 3I0 in % of fundamental Maximum Current for Inr. Rest. O/C 3I0
2.4.4
General
F.No.
Information Overview
Comments
94
Phases Currents
F.No. Alarm Comments >BLOCK Phase time overcurrent >BLOCK time overcurrent Phase InRush Time Overcurrent Phase is OFF Time Overcurrent Phase is BLOCKED Time Overcurrent Phase is ACTIVE Phase L1 InRush detected Phase L2 InRush detected Phase L3 InRush detected Cross blk: PhX blocked PhY Time Overcurrent Phase L1 picked up Time Overcurrent Phase L2 picked up Time Overcurrent Phase L3 picked up Phase L1 InRush picked up Phase L2 InRush picked up Phase L3 InRush picked up >BLOCK I>> I>> BLOCKED I>> picked up I>> Time Out I>> TRIP >BLOCK I> I> BLOCKED I> picked up I> InRush picked up I> Time Out I> TRIP >BLOCK Ip Ip BLOCKED Ip picked up Ip InRush picked up Ip Time Out Ip TRIP O/C Phase Not avali. for this objekt
01704 >BLK Phase O/C 07571 >BLK Ph.O/C Inr 01751 O/C Phase OFF 01752 O/C Phase BLK 01753 O/C Phase ACT 07581 L1 InRush det. 07582 L2 InRush det. 07583 L3 InRush det. 01843 INRUSH X-BLK 01762 O/C Ph L1 PU 01763 O/C Ph L2 PU 01764 O/C Ph L3 PU 07565 L1 InRush PU 07566 L2 InRush PU 07567 L3 InRush PU 01721 >BLOCK I>> 01852 I>> BLOCKED 01800 I>> picked up 01804 I>> Time Out 01805 I>> TRIP 01722 >BLOCK I> 01851 I> BLOCKED 01810 I> picked up 07551 I> InRush PU 01814 I> Time Out 01815 I> TRIP 01723 >BLOCK Ip 01855 Ip BLOCKED 01820 Ip picked up 07553 Ip InRush PU 01824 Ip Time Out 01825 Ip TRIP 01860 O/C Ph. Not av.
95
2 Functions
Residual Current
F.No. 01741 >BLK 3I0 O/C 07572 >BLK 3I0O/C Inr 01748 O/C 3I0 OFF 01749 O/C 3I0 BLK 01750 O/C 3I0 ACTIVE 01766 O/C 3I0 PU 07568 3I0 InRush PU 01742 >BLOCK 3I0>> 01858 3I0>> BLOCKED 01901 3I0>> picked up 01902 3I0>> Time Out 01903 3I0>> TRIP 01743 >BLOCK 3I0> 01857 3I0> BLOCKED 01904 3I0> picked up 07569 3I0> InRush PU 01905 3I0> Time Out 01906 3I0> TRIP 01744 >BLOCK 3I0p 01859 3I0p BLOCKED 01907 3I0p picked up 07570 3I0p InRush PU 01908 3I0p TimeOut 01909 3I0p TRIP 01861 O/C 3I0 Not av. Alarm Comments >BLOCK 3I0 time overcurrent >BLOCK time overcurrent 3I0 InRush Time Overcurrent 3I0 is OFF Time Overcurrent 3I0 is BLOCKED Time Overcurrent 3I0 is ACTIVE Time Overcurrent 3I0 picked up 3I0 InRush picked up >BLOCK 3I0>> time overcurrent 3I0>> BLOCKED 3I0>> picked up 3I0>> Time Out 3I0>> TRIP >BLOCK 3I0> time overcurrent 3I0> BLOCKED 3I0> picked up 3I0> InRush picked up 3I0> Time Out 3I0> TRIP >BLOCK 3I0p time overcurrent 3I0p BLOCKED 3I0p picked up 3I0p InRush picked up 3I0p Time Out 3I0p TRIP O/C 3I0 Not avali. for this objekt
96
2.5
L1 L2 L3
L1 L2 L3
ISP
I7
7UT612
Time overcurrent prot. for earth current
Figure 2-60
Time overcurrent protection as backup protection for restricted earth fault protection
2.5.1
2.5.1.1
Function Description
Definite Time Overcurrent Protection The definite time stages for earth current are always available even if an inverse time characteristic has been configured according to Subsection 2.1.1 (address ).
Pickup, Trip
Two definite time stages are available for the earth current IE. The current measured at the input I7 is compared with the setting value ,(!!. Current above the pickup value is detected and annunciated. When the delay time 7 ,(!! is expired, tripping command is issued. The reset value is approximately 5 % below the pickup value for currents > 0.3 IN.
97
2 Functions
Figure 2-61 shows the logic diagram for the high-current stage IE>>.
&
Man. Close
!#
I7
D@33
FNo 1831
IE>> picked up
I>>
&
!# !UD@33
&
T 0
FNo 1833
IE>> TRIP
FNo 1832
>BLOCK IE>>
FNo 1714
IE>> BLOCKED
FNo 1757
!# @6SUCP8
1
FNo 1758
2)) 21
Figure 2-61
The current detected at the current measuring input I7 is additionally compared with setting value ,(!. An annunciation is generated if the value is exceeded. But if inrush restraint is used (cf. Subsection 2.5.1.5), a frequency analysis is performed first (Subsection 2.5.1.5). If an inrush condition is detected, pickup annunciation is suppressed and an inrush message is output instead. If there is no inrush or if inrush restraint is disabled, a tripping command will be output after expiration of delay time 7 ,(!. If inrush restraint is enabled and inrush current is detected, there will be no tripping. Nevertheless, an annunciation is generated indicating that the time expired. The dropout value is approx. a 95 % of the pickup value for currents greater than 0.3 IN. Figure 2-62 shows the logic diagram of the earth overcurrent stage IE>. The pickup values for each of the stages IE> and IE>> and the delay times can be set individually.
98
D@vh D@3vh
(s. Fig. 2-54)
&
FNo 7552
IE> InRush PU
FNo 7564
&
Earth InRush PU
FNo 1765
!# " D@3
I7
&
I>
IE> picked up
!# #UD@3
&
T 0
&
FNo 1836
IE> TRIP
FNo 1835
>BLOCK IE>
FNo 1714
IE> BLOCKED
FNo 1757
!# @6SUCP8
1
FNo 1758
2)) 21
Figure 2-62
2.5.1.2
Inverse Time Overcurrent Protection The inverse-time overcurrent stage operates with a characteristic either according to the IEC- or the ANSI-standard or with a user-defined characteristic. The characteristic curves and their equations are represented in Technical Data (Figures 4-7 to 4-9 in Section 4.4). If one of the inverse time characteristics is configured, the definite time stages IE>> and IE> are also enabled (see Subsection 2.5.1.1).
Pickup, Trip
The current detected at the current measuring input I7 is compared with setting value ,(S. If the current exceeds 1.1 times the set value, the stage picks up and an annunciation is made. But if inrush restraint is used (cf. Subsection 2.5.1.5), a frequency analysis is performed first (Subsection 2.5.1.5). If an inrush condition is detected, pickup annunciation is suppressed and an inrush message is output instead. The RMS value of the fundamental is used for the pickup. During the pickup of an ,Ep stage, tripping time is calculated from the flowing fault current by means of an integrating measuring procedure, depending on the selected tripping characteristic. After expiration of this time period, a trip command is output as long as no inrush current is detected or inrush restraint is disabled. If inrush restraint is enabled and inrush current is detected, there will be no tripping. Nevertheless, an annunciation is generated indicating that the time expired.
99
2 Functions
Figure 2-63 shows the logic diagram of the inverse time overcurrent protection.
D@vh D@3vh
(s. Fig. 2-54)
&
FNo 7554
IEp InRush PU
FNo 7564
&
Earth InRush PU
FNo 1765
!#!
3I0
D@
&
1,1I>
D@88VSW@ !#!!UD@
&
I
IEp picked up
FNo 1839
IEp TRIP
FNo 1838
&
IEp TimeOut
FNo 1726 Meas. release FNo 1856
>BLOCK IEp
FNo 1714
IEp BLOCKED
FNo 1757
!# @6SUCP8
1
FNo 1758
2)) 21
Figure 2-63
Logic diagram of the inverse time overcurrent protection stage IEp example for IECcurves
Dropout of the stage using an IEC curves occurs when the respective current decreases below about 95 % of the pickup value. A renewed pickup will cause a renewed start of the delay timers. Using the ANSI-characteristics you can determine whether the dropout of the stage is to follow right after the threshold undershot or whether it is evoked by disk emulation. Right after means that the pickup drops out when the pickup value of approx. 95 % is undershot. For a new pickup the time counter starts at zero. The disk emulation evokes a dropout process (time counter is decrementing) which begins after de-energization. This process corresponds to the back turn of a Ferrarisdisk (explaining its denomination disk emulation). In case several faults occur successively, it is ensured that due to the inertia of the Ferraris-disk the History is taken into consideration and the time behaviour is adapted. The reset begins as soon as 90 % of the setting value is undershot, in correspondence to the dropout curve of the selected characteristic. Within the range of the dropout value (95 % of the pickup value) and 90 % of the setting value, the incrementing and the decrementing processes are in idle state. If 5 % of the setting value is undershot, the dropout process is being finished, i.e. when a new pickup is evoked, the timer starts again at zero.
100
The disk emulation offers its advantages when the grading coordination chart of the time overcurrent protection is combined with other devices (on electro-mechanical or induction base) connected to the system. Use Specified Curves The tripping characteristic of the user-configurable characteristic can be defined via several points. Up to 20 pairs of current and time values can be entered. With these values the device approximates a characteristic by linear interpolation. If required, the dropout characteristic can also be defined. For the functional description see Dropout for ANSI Curves. If no user-configurable dropout characteristic is desired and if approx. a 95 % of the pickup value is undershot, dropout is initiated. When a new pickup is evoked, the timer starts again at zero.
2.5.1.3
Manual Close Command When a circuit breaker is closed onto a faulted protected object, a high speed re-trip by the breaker is often desired. The manual closing feature is designed to remove the delay from one of the time overcurrent stages when the breaker is manually closed onto a fault. The time delay is then bypassed via an impulse from the external control switch. This impulse is prolonged by a period of at least 300 ms (Figure 2-54, page 79). Address $ ,( 0$1 &/26( determines for which stages the delay is defeated under manual close condition.
2.5.1.4
Dynamic Cold Load Pickup Dynamic changeover of pickup values is available also for time overcurrent protection for earth current as it is for the time overcurrent protection for phase currents and residual current (Section 2.4). Processing of the dynamic cold load pickup conditions is common for all time overcurrent stages, and is explained in Section 2.6 (page 108). The alternative values themselves are set for each of the stages.
2.5.1.5
Inrush Restraint Earth current time overcurrent protection provides an integrated inrush restraint function which blocks the overcurrent stages IE> and IEp (not IE>>) in case of detection of an inrush on a transformer. If the second harmonic content of the earth current exceeds a selectable threshold, trip is blocked.
101
2 Functions
The inrush restraint feature has an upper operation limit. Above this (adjustable) current blocking is suppressed since a high-current fault is assumed in this case. The lower limit is the operating limit of the harmonic filter (0.2 IN). Figure 2-64 shows a simplified logic diagram.
!## !C6SH@hu
IE
fN 2fN
&
Rush blk E
E
FNo 07573
DHhDS@
!##!
Meas. release
!#! DSuSr@hu
1
2)) 21
Figure 2-64
2.5.2
General
If ,(!!stage (address ) is combined with the IE>stage or the IEpstage, a twostage characteristic will be the result. If this stage is not required, the pickup value shall be set to . Stage ,(!! always operates with a defined delay time.
102
Current and time setting shall exclude pickup during switching operations. This stage is applied if you want to create a multi-stage characteristic together with stage IE> or IEp (below described). With a certain degree of exactness, current grading can also be achieved, similar to the corresponding stages of the time overcurrent protection for phase and residual currents (Subsection 2.4.2). However, zero sequence system quantities must be taken into consideration. In most cases, this stage operates instantaneously. A time delay, however, can be achieved by setting address 7 ,(!!. The set time is an additional time delay and does not include the operating time (measuring time, dropout time). The delay can be set to infinity . If set to infinity, the pickup of this function will be indicated but the stage will not be able to trip after pickup. If the pickup threshold is set to , neither a pickup annunciation nor a trip is generated. Definite Time Overcurrent Stage IE> Using the time overcurrent stage ,(! (address ) earth faults can also be detected with weak fault currents. Since the starpoint current originates from one single current transformer, it is not affected by summation effects evoked by different current transformer errors like, for example, the zero sequence current derived from phase currents. Therefore, this address can be set to very sensitive. Consider that the inrush restraint function cannot operate below 20 % nominal current (lower limit of harmonic filtering). An adequate time delay could be reasonable for very sensitive setting if inrush restraint is used. Since this stage also picks up with earth faults in the network, the time delay (address 7 ,(!) has to be coordinated with the grading coordination chart of the network for earth faults. Mostly, you may set shorter tripping times than for phase currents since a galvanic separation of the zero sequence systems of the connected power system sections is ensured by a transformer with separate windings. The set time is an additional time delay and does not include the operating time (measuring time, dropout time). The delay can be set to infinity . If set to infinity, the pickup of this function will be indicated but the stage will not trip after pickup. If the pickup threshold is set to , neither a pickup annunciation nor a trip is generated. Inverse Time Overcurrent Stages IEp with IEC curves The inverse time stage, depending on the configuration (Subsection 2.1.1, address ), enables the user to select different characteristics. With the IEC characteristics (address '07,'07 ( &+5 = 72& ,(&) the following is made available in address ,(& &859(: 1RUPDO ,QYHUVH (type A according to IEC 602553), 9HU\ ,QYHUVH (type B according to IEC 602553), ([WUHPHO\ ,QY (type C according to IEC 602553), and /RQJ ,QYHUVH (type B according to IEC 602553). The characteristics and equations they are based on are listed in the Technical Data (Section 4.4, Figure 4-7). If the inverse time trip characteristic is selected, it must be noted that a safety factor of about 1.1 has already been included between the pickup value and the setting value. This means that a pickup will only occur if a current of about 1.1 times of the setting value is present. The function will reset as soon as the value undershoots 95 % of the pickup value. Using the time overcurrent stage ,(S (address ) earth faults can also be detected with weak fault currents. Since the starpoint current originates from one single cur-
103
2 Functions
rent transformer, it is not affected by summation effects evoked by different current transformer errors like, for example, the zero sequence current derived from phase currents. Therefore, this address can be set to very sensitive. Consider that the inrush restraint function cannot operate below 20 % nominal current (lower limit of harmonic filtering). An adequate time delay could be reasonable for very sensitive setting if inrush restraint is used. Since this stage also picks up with earth faults in the network, the time multiplier (address 7 ,(S) has to be coordinated with the grading coordination chart of the network for earth faults. Mostly, you may set shorter tripping times than for phase currents since a galvanic separation of the zero sequence systems of the connected power system sections is ensured by a transformer with separate windings. The time multiplier can also be set to . If set to infinity, the pickup of this function will be indicated but the stage will not trip after pickup. If the IEpstage is not required, select address '07,'07 ( &+5 = 'HILQLWH 7LPH when configuring the protection functions (Subsection 2.1.1). Inverse Time Overcurrent Stages Ip with ANSI curves The inverse time stages, depending on the configuration (Subsection 2.1.1, address ), enable the user to select different characteristics. With the ANSI characteristics (address '07,'07 ( &+5 = 72& $16,) the following is made available in address $16, &859(: 'HILQLWH ,QY, ([WUHPHO\ ,QY, ,QYHUVH, /RQJ ,QYHUVH, 0RGHUDWHO\ ,QY, 6KRUW ,QYHUVH, and 9HU\ ,QYHUVH. The characteristics and the equations they are based on are listed in the Technical Data (Section 4.4, Figures 4-8 and 4-9). If the inverse time trip characteristic is selected, it must be noted that a safety factor of about 1.1 has already been included between the pickup value and the setting value. This means that a pickup will only occur if a current of about 1.1 times of the setting value is present. Using the time overcurrent stage ,(S (address ) earth faults can also be detected with weak fault currents. Since the starpoint current originates from one single current transformer, it is not affected by summation effects evoked by different current transformer errors like, for example, the zero sequence current derived from phase currents. Therefore, this address can be set to very sensitive. Consider that the inrush restraint function cannot operate below 20 % nominal current (lower limit of harmonic filtering). An adequate time delay could be reasonable for very sensitive setting if inrush restraint is used. Since this stage also picks up with earth faults in the network, the time multiplier (address ' ,(S) has to be coordinated with the grading coordination chart of the network for earth faults. Mostly, you may set shorter tripping times than for phase currents since a galvanic separation of the zero sequence systems of the connected power system sections is ensured by a transformer with separate windings. The time multiplier can also be set to . If set to infinity, the pickup of this function will be indicated but the stage will not trip after pickup. If the IEpstage is not required, se-
104
105
2 Functions
2.5.3
Setting Overview
The following list indicates the setting ranges and the default settings of a rated secondary current IN = 1 A. For a rated secondary current of IN = 5 A these values have to be multiplied by 5. For settings in primary values, a conversion rate of the current transformers has to be considered additionally.
Note: Addresses which have an A attached to their end can only be changed in DIGSI 4, Section Additional Settings.
Addr. 2401 2402 2408A Setting Title EARTH O/C InRushRestEarth IE MAN. CLOSE Setting Options ON OFF ON OFF IE>> instantaneously IE> instantaneously IEp instantaneously Inactive 0.05..35.00 A; 0.00..60.00 sec; 0.05..35.00 A; 0.00..60.00 sec; 0.05..35.00 A; 0.00..60.00 sec; 0.05..35.00 A; 0.00..60.00 sec; 0.05..4.00 A 0.05..3.20 sec; 0.50..15.00; Instantaneous Disk Emulation Normal Inverse Very Inverse Extremely Inverse Long Inverse Very Inverse Inverse Short Inverse Long Inverse Moderately Inverse Extremely Inverse Definite Inverse 0.05..4.00 A 0.05..3.20 sec; Default Setting OFF OFF IE>> instantaneously Comments Earth Time Overcurrent InRush Restrained O/C Earth O/C IE Manual Close Mode
2411 2412 2413 2414 2511 2512 2513 2514 2421 2422 2423 2424 2425
IE>> T IE>> IE> T IE> IE>> T IE>> IE> T IE> IEp T IEp D IEp TOC DROP-OUT IEC CURVE
0.50 A 0.10 sec 0.20 A 0.50 sec 7.00 A 0.00 sec 1.50 A 0.30 sec 0.20 A 0.20 sec 5.00 Disk Emulation Normal Inverse
IE>> Pickup T IE>> Time Delay IE> Pickup T IE> Time Delay IE>> Pickup T IE>> Time Delay IE> Pickup T IE> Time Delay IEp Pickup T IEp Time Dial D IEp Time Dial TOC Drop-out Characteristic IEC Curve
2426
ANSI CURVE
Very Inverse
ANSI Curve
2521 2522
IEp T IEp
106
Setting Title D IEp I/IEp PU T/TEp MofPU Res T/TEp 2.HARM. Earth I Max InRr. E
Setting Options 0.50..15.00; 1.00..20.00 I / Ip; 0.01..999.00 Time Dial 0.05..0.95 I / Ip; 0.01..999.00 Time Dial 10..45 % 0.30..25.00 A
Comments D IEp Time Dial Pickup Curve IE/IEp - TIE/TIEp Multiple of Pickup <-> TI/TIEp
15 % 7.50 A
2nd harmonic O/C E in % of fundamental Maximum Current for Inr. Rest. O/C Earth
2.5.4
Information Overview
F.No. 01714 >BLK Earth O/C 07573 >BLK E O/C Inr 01756 O/C Earth OFF 01757 O/C Earth BLK 01758 O/C Earth ACT 01765 O/C Earth PU
Alarm
Comments >BLOCK Earth time overcurrent >BLOCK time overcurrent Earth InRush Time Overcurrent Earth is OFF Time Overcurrent Earth is BLOCKED Time Overcurrent Earth is ACTIVE Time Overcurrent Earth picked up Earth InRush picked up >BLOCK IE>> IE>> BLOCKED IE>> picked up IE>> Time Out IE>> TRIP >BLOCK IE> IE> BLOCKED IE> picked up IE> InRush picked up IE> Time Out IE> TRIP >BLOCK IEp IEp BLOCKED IEp picked up IEp InRush picked up IEp Time Out IEp TRIP
07564 Earth InRush PU 01724 >BLOCK IE>> 01854 IE>> BLOCKED 01831 IE>> picked up 01832 IE>> Time Out 01833 IE>> TRIP 01725 >BLOCK IE> 01853 IE> BLOCKED 01834 IE> picked up 07552 IE> InRush PU 01835 IE> Time Out 01836 IE> TRIP 01726 >BLOCK IEp 01856 IEp BLOCKED 01837 IEp picked up 07554 IEp InRush PU 01838 IEp TimeOut 01839 IEp TRIP
107
2 Functions
2.6
Note:
Dynamic cold load pickup is in addition to the four setting groups (A to D) which are configured separately. The dynamic cold load pickup feature operates with the time overcurrent protection functions described in the sections 2.4 and 2.5. A set of alternative values can be set for each stage.
2.6.1
Function Description
There are two primary methods used by the device to determine if the protected equipment is de-energized: Via a binary input, an auxiliary contact in the circuit breaker can be used to determine if the circuit breaker is open or closed. The current flow monitoring threshold may be used to determine if the equipment is de-energized. You may select one of these criteria for the time overcurrent protection for phase currents (Section 2.4) and for that for residual current (Section 2.4). The device assigns automatically the correct side for current detection or the breaker auxiliary contact. The time overcurrent protection for earth current (Section 2.5) allows the breaker criterion only if it is assigned to a certain side of the protected object (address , see also Section 2.1.1 under margin header Special Cases, page 16); otherwise exclusively the current criterion can be used. If the device recognizes the protected equipment be de-energized via one of the criteria above, then the alternative pickup values will become effective for the overcurrent stages once a specified time delay has elapsed. Figure 2-66 shows the logic diagram for dynamic cold load pickup function. The time &% 2SHQ 7LPH controls how long the equipment can be de-energized before the dynamic cold load pickup function is activated. When the protected equipment is re-energized (i.e. the device receives input via a binary input that the assigned circuit breaker is closed or the assigned current flowing through the breaker increases above the current flow monitoring threshold), the active time $FWLYH 7LPH is initiated. Once the active time has elapsed, the pickup values of the overcurrent stages return to their normal settings. The active time controls how long dynamic cold load pickup settings remain in place once the protect-
108
ed object is re-energized. Upon re-energizing of the equipment, if the measured current values are below the normal pickup settings, an alternative time delay referred to as the 6WRS 7LPH is also initiated. As in the case with the active time, once this time has elapsed, the pickup values of overcurrent stages change from the dynamic cold load pickup values to their normal settings. The 6WRS 7LPH controls how long dynamic cold load pickup settings remain in place given that measured currents are below the normal pickup settings. To defeat this time from switching the overcurrent stages pickup settings back to normal, it may be set to or blocked via the binary input !%/. &/3 VWS7LP.
Circuit breaker
closed open
Operating state
DCP settings active normal settings active
Figure 2-65
109
2 Functions
If an overcurrent stage picks up while the dynamic settings are enabled, elapse of the active time $FWLYH 7LPH will not restore the normal pickup settings until drop out of the overcurrent stage occurs based on the dynamic settings. If the dynamic cold load pickup function is blocked via the binary input !%/2&. &/3, all triggered timers will be immediately reset and all normal settings will be restored. If blocking occurs during an on-going fault with dynamic cold load pickup functions enabled, the timers of all overcurrent stages will be stopped, and then restarted based on their normal duration. During power up of the protective relay with an open circuit breaker, the time delay &% 2SHQ 7LPH is started, and is processed using the normal settings. Therefore, when the circuit breaker is closed, the normal settings are effective. Figure 2-65 shows a timing diagram, Figure 2-66 describes the logic for cold load pickup function.
FNo 1995 CLP BLOCKED FNo 1996 CLP running FNo 1994 CLP OFF
&
Meas. release
&
87PrUvr
0 FNo 1998
& 1
I Dyn.set. ACT
FNo 1999
&! Th8GQQuhr
1
7rhxr8hp I8r
3I0 Dyn.set.ACT
FNo 2000
SQ & & R
IE Dyn.set. ACT
Processing of the cold load pickup values in the overcurrent stages
283
7rhxrT D3
<
& ! 6pvrUvr
T 0
Exceeding one of the the dynamic cold load pick-up thresholds of the overcurrent stages
&
Figure 2-66
Logic diagram for dynamic cold load pickup feature illustrated for phase overcurrent protection stage on side 1
110
2.6.2
General
The current criterion takes the currents of that side where the corresponding protective function is assigned to. When using the breaker position criterion, the auxiliary contact of the assigned side must inform the device via a binary input about the breaker position. The time overcurrent protection for earth current allows only the current criterion because it cannot assigned to any circuit breaker. (address 6WDUW &/3 (DUWK is always 1R &XUUHQW). Timers There are no specific procedures on how to set the time delays at addresses &% 2SHQ 7LPH, $FWLYH 7LPH and 6WRS 7LPH. These time delays must be based on the specific loading characteristics of the equipment being protected, and should be selected to allow the brief overloads associated with dynamic cold load conditions. The dynamic pickup values and time delays associated with the time overcurrent stages are set in the related addresses of these stages themselves.
2.6.3
Setting Overview
Setting Title COLDLOAD PICKUP Start CLP Phase Start CLP 3I0 Start CLP Earth CB Open Time Active Time OFF ON
Setting Options
Default Setting OFF No Current No Current No Current 3600 sec 3600 sec
Comments Cold-Load-Pickup Function Start Condition CLP for O/C Phase Start Condition CLP for O/C 3I0 Start Condition CLP for O/C Earth Circuit Breaker OPEN Time Active Time
No Current Breaker Contact No Current Breaker Contact No Current Breaker Contact 0..21600 sec 1..21600 sec
111
2 Functions
Addr. 1713
Comments
2.6.4
Information Overview
Comments
01731 >BLK CLP stpTim 01994 CLP OFF 01995 CLP BLOCKED 01996 CLP running 01998 I Dyn.set. ACT 01999 3I0 Dyn.set.ACT 02000 IE Dyn.set. ACT
>BLOCK Cold-Load-Pickup stop timer Cold-Load-Pickup switched OFF Cold-Load-Pickup is BLOCKED Cold-Load-Pickup is RUNNING Dynamic settings O/C Phase are ACTIVE Dynamic settings O/C 3I0 are ACTIVE Dynamic settings O/C Earth are ACTIVE
112
2.7
2.7.1
Function Description
The measured current is filtered by numerical algorithms. Because of the high sensitivity a particular narrow band filter is used. For the single-phase I>> stage, the current measured at the configured current input (I7 or I8) is compared with the setting value 3KDVH ,!!. Current above the pickup value is detected and annunciated. When the delay time 7 3KDVH ,!! has expired, tripping command is issued. The reset value is approximately 5 % below the pickup value for currents > 0.3 IN. For the single-phase I> stage, the current measured at the configured current input is compared with the setting value 3KDVH ,!. Current above the pickup value is detected and annunciated. When the delay time 7 3KDVH ,! has expired, tripping command is issued. The reset value is approximately 5 % below the pickup value for currents > 0.3 IN. Both stages form a two-stage definite time overcurrent protection whose tripping characteristic is illustrated in Figure 2-67. When high fault current occurs, the current filter can be bypassed in order to achieve a very short tripping time. This is automatically done when the instantaneous value of the current exceeds the set value I>> by the factor 22. The logic diagram of the single-phase time overcurrent protection is shown in Figure 2-68.
113
2 Functions
Tripping 7 ,!
7 ,!! ,! Figure 2-67 ,!! I Two-stage tripping characteristic of the single-phase time overcurrent protection
!&"
QuhrD33
I7 I8
I>>
1
!&# U QuhrD33
FNo 5977
22I>>
&
Meas. release
O/C 1Ph PU
FNo 5967
FNo 5953
!&
1
QuhrP8 2)) 21
!&%
QuhrD3
I>
!&& U QuhrD3
&
FNo 5975
FNo 5952
FNo 5966
Figure 2-68
Logic diagram of the single-phase time overcurrent protection example for detection of the current at input I8
114
2.7.2
Application Example
L1 L2 L3
L1 L2 L3
R
Figure 2-69 Earth fault protection according to the high-impedance scheme
High-Impedance Principle
The high-impedance principle is explained on the basis of an earthed transformer winding (Figure 2-70). No zero sequence current will flow during normal operation, i.e. the starpoint current is ISP = 0 and the line currents are 3I0 = IL1 + IL2 + IL3 = 0. With an external earth fault (Figure 2-70, left side), whose fault current is supplied via the earthed starpoint, the same current flows through the transformer starpoint and the phases. The corresponding secondary currents (all current transformers having the same transformation ratio) compensate each other, they are connected in series. Across resistance R only a small voltage is generated. It originates from the inner resistance of the transformers and the connecting cables of the transformers. Even if any current transformer experiences a partial saturation, it will become low-ohmic for the period of saturation and creates a low-ohmic shunt to the high-ohmic resistor R.
115
2 Functions
Thus, the high resistance of the resistor also has an stabilizing effect (the so-called resistance stabilization).
L1 L2 L3
L1 L2 L3
ISP
ISP
Figure 2-70
In case there is an earth fault in the protection zone (Figure 2-70, right side), a starpoint current ISP will be present for sure. The earthing conditions in the rest of the network determine how strong a zero sequence current from the system is. A secondary current which is equal to the total fault current tries to pass through the resistor R. Since the latter is high-ohmic, a high voltage emerges immediately. Therefore, the current transformers get saturated. The RMS voltage across the resistor approximately corresponds to the knee-point voltage of the current transformers. Resistance R is dimensioned such that, even with the very lowest earth fault current to be detected, it generates a secondary voltage which is equal to the half knee-point voltage of current transformers (see also notes on dimensioning in Subsection 2.7.4). High-Impedance Protection with 7UT612 With 7UT612 the sensitive measuring input I8 is used for high-impedance protection. As this is a current input, the protection detects current through the resistor instead of the voltage across the resistor R. Figure 2-71 shows the connection example. The 7UT612 is connected in series to resistor R and measures its current. Varistor V limits the voltage when inner faults occur. High voltage peaks emerging with transformer saturation are cut by the varistor. At the same time, voltage is smoothed without reduction of the mean value. For protection against overvoltages it is also important that the device is directly connected to the earthed side of the current transformers so that the high voltage at the resistor can be kept away from the device. For generators, motors and shunt reactors high-impedance protection can be used analogously. All current transformers at the overvoltage side, the undervoltage side and the current transformer at the starpoint have to be connected in parallel when using auto-transformers. In principle, this scheme can be applied to every protected object. When applied as busbar protection, for example, the device is connected to the parallel connection of all feeder current transformers via the resistor.
116
L1 L2 L3
7UT612
Figure 2-71
Connection scheme for earth fault protection according to the high-impedance principle
2.7.3
Application Example
I8
7UT612
isolated
Figure 2-72
I8
117
2 Functions
2.7.4
General
When used as high-impedance protection, only the pickup value of the single-phase overcurrent protection is set on the 7UT612 to detect overcurrent at the current input I8. Consequently, during configuration of the protective functions (Subsection 2.1.1 under Special Cases, page 16), address is set '07 3+$6( = VHQV &7. But, the entire function of the high-impedance unit protection is dependent on the coordination of the current transformer characteristics, the external resistor R and the voltage across R. The following three header margins give information about these considerations.
All current transformers must have identical transformation ratio and nearly equal knee-point voltage. This is usually the case if they are of equal design and identical rated data. If the knee-point voltage is not stated, it can be approximately calculated from the rated data of a CT as follows: PN U KPV = R i + ------- ALF I N 2 IN where UKPV Ri PN IN ALF = = = = = knee-point voltage of the CT Internal burden of the CT rated power of the CT rated secondary current of the CT rated accuracy limit factor of the CT
The rated current, rated power and accuracy limit factor are normally stated on the rating plate of the current transformer, e.g.
118
Current transformer 800/5; 5P10; 30 VA That means IN = 5 A (from 800/5) ALF = 10 (from 5P10) PN = 30 VA The internal burden is often stated in the test report of the current transformer. If not it can be derived from a DC measurement on the secondary winding. Calculation example: Current transformer 800/5; 5P10; 30 VA with Ri = 0.3 PN 30 VA U KPV = R i + ------- ALF I N = 0.3 + --------------- 10 5 A = 75 V 2 2 IN (5 A) or Current transformer 800/1; 5P10; 30 VA with Ri = 5 PN 30 VA U KPV = R i + ------- ALF I N = 5 + --------------- 10 1 A = 350 V 2 2 IN (1 A) Besides the CT data, the resistance of the longest connection lead between the CTs and the 7UT612 device must be known. Stability with HighImpedance Protection The stability condition is based on the following simplified assumption: If there is an external fault, one of the current transformers gets totally saturated. The other ones will continue transmitting their (partial) currents. In theory, this is the most unfavourable case. Since, in practice, it is also the saturated transformer which supplies current, an automatic safety margin is guaranteed. Figure 2-73 shows a simplified equivalent circuit. CT1 and CT2 are assumed as ideal transformers with their inner resistances Ri1 and Ri2. Ra are the resistances of the connecting cables between current transformers and resistor R. They are multiplied by 2 as they have a go- and a return line. R a2 is the resistance of the longest connecting cable. CT1 transmits current I1. CT2 shall be saturated. Because of saturation the transformer represents a low-resistance shunt which is illustrated by a dashed short-circuit line. R >> (2Ra2 + Ri2) is a further prerequisite.
Ri1
2Ra1
2Ra2
Ri2
CT1
I1
CT2
Figure 2-73
Simplified equivalent circuit of a circulating current system for high-impedance differential protection
119
2 Functions
The voltage across R is then UR I1 (2Ra2 + Ri2 ) It is assumed that the pickup value of the 7UT612 corresponds to half the knee-point voltage of the current transformers. In the balanced case results UR = UKPV/2 This results in a stability limit ISL, i.e. the maximum through-fault current below which the scheme remains stable: U KPV 2 ISL = ------------------------------2 R a2 + R i2 Calculation example: For the 5 A CT like above with UKPV = 75 V and Ri = 0.3 longest CT connection lead 22 m with 4 mm2 cross-section, results in Ra 0,1 U KPV 2 37.5 V I SL = ------------------------------- = ------------------------------------------- = 75 A 2 R a2 + R i2 2 0.1 + 0.3 that is 15 rated current or 12 kA primary. For the 1 A CT like above with UKPV = 350 V and Ri = 5 longest CT connection lead 107 m with 2.5 mm2 cross-section, results in Ra 0.75 U KPV 2 175 V I SL = ------------------------------- = ----------------------------------------- = 27 A 2 R a2 + R i2 2 0.75 + 5 that is 27 rated current or 21,6 kA primary. Sensitivity with High Impedance Protection As before mentioned, high-impedance protection is to pick up with approximately half the knee-point voltage of the current transformers. Resistance R can be calculated from it. Since the device measures the current flowing through the resistor, resistor and measuring input of the device are to be connected in series (see also Figure 2-71). Since, furthermore, the resistance shall be high-ohmic (condition: R >> 2Ra2 + Ri2, as above mentioned), the inherent resistance of the measuring input can be neglected. The resistance is then calculated from the pickup current Ipu and the half knee-point voltage: U KPV 2 R = -------------------I pu
Calculation example: For the 5 A CT like above with required pickup value Ipu = 0.1 A (corresponding to 16 A primary) U KPV 2 75 V 2 R = -------------------- = ------------------ = 375 I pu 0.1 A For the 1 A CT like above required pickup value Ipu = 0.05 A (corresponding to 40 A primary) U KPV 2 350 V 2 R = -------------------- = ---------------------- = 3500 I pu 0.05 A
120
The required short-term power of the resistor is derived from the knee-point voltage and the resistance: PR
2 U KPV ( 75 V ) = ---------------- = ------------------- = 15 W R 375 2 2
As this power only appears during earth faults for a short period of time, the rated power can be smaller by approx. factor 5. The varistor (see also Figure 2-71) must be dimensioned such that it remains highohmic up to the knee-point voltage, e.g. approx. 100 V for the 5 A CT example, approx. 500 V for the 1 A CT example. For 7UT612, the pickup value (0.1 A or 0.05 A in the example) is set in address 3KDVH ,!. Stage I>> is not required (Address 3KDVH ,!! = ). The trip command of the protection can be delayed in address 7 3KDVH ,!. This time delay is usually set to 0. If a higher number of current transformers is connected in parallel, e.g. when using as busbar protection with several feeders, the magnetizing currents of the transformers connected in parallel cannot be neglected anymore. In this case, the magnetizing currents at the half knee-point voltage (corresponds to the setting value) have to be summed. These magnetizing currents reduce the current through the resistor R. Therefore the actual pickup value will be correspondingly higher. Use as Tank Leakage Protection If the single-phase time overcurrent protection is used as tank leakage protection, merely the pickup value for the current at the input I8 is set on 7UT612. Consequently, during configuration of the protective functions (Subsection 2.1.1 under Special Cases, page 16) had been set under address : '07 3+$6( = VHQV &7. The tank leakage protection is a highly sensitive overcurrent protection which detects the leakage current between the isolated transformer tank and earth. Its sensitivity is set in address 3KDVH ,!. The I>> stage is not used (address 3KDVH ,!! = ). The trip command can be delayed under address 7 3KDVH ,!. Normally, this delay time is set to .
2.7.5
Setting Overview
The following list indicates the setting ranges and the default settings of a rated secondary current IN = 1 A. For a rated secondary current of IN = 5 A these values have to be multiplied by 5. For settings in primary values, a conversion rate of the current transformers has to be considered additionally.
121
2 Functions
Setting Title 1Phase O/C 1Phase I>> 1Phase I>> T 1Phase I>> 1Phase I> 1Phase I> T 1Phase I> OFF ON
Setting Options
Default Setting OFF 0.50 A 0.300 A 0.10 sec 0.20 A 0.100 A 0.50 sec
Comments 1Phase Time Overcurrent 1Phase O/C I>> Pickup 1Phase O/C I>> Pickup T 1Phase O/C I>> Time Delay 1Phase O/C I> Pickup 1Phase O/C I> Pickup T 1Phase O/C I> Time Delay
2.7.6
Information Overview
F.No. 05951 >BLK 1Ph. O/C 05952 >BLK 1Ph. I> 05953 >BLK 1Ph. I>> 05961 O/C 1Ph. OFF 05962 O/C 1Ph. BLK 05963 O/C 1Ph. ACT 05966 O/C 1Ph I> BLK
Alarm
Comments >BLOCK Time Overcurrent 1Phase >BLOCK Time Overcurrent 1Ph. I> >BLOCK Time Overcurrent 1Ph. I>> Time Overcurrent 1Phase is OFF Time Overcurrent 1Phase is BLOCKED Time Overcurrent 1Phase is ACTIVE Time Overcurrent 1Phase I> BLOCKED Time Overcurrent 1Phase I>> BLOCKED Time Overcurrent 1Phase picked up Time Overcurrent 1Phase TRIP Time Overcurrent 1Phase I> picked up Time Overcurrent 1Phase I> TRIP Time Overcurrent 1Phase I>> picked up Time Overcurrent 1Phase I>> TRIP Time Overcurrent 1Phase: I at pick up
05967 O/C 1Ph I>> BLK 05971 O/C 1Ph PU 05972 O/C 1Ph TRIP 05974 O/C 1Ph I> PU 05975 O/C 1Ph I> TRIP 05977 O/C 1Ph I>> PU 05979 O/C1Ph I>> TRIP 05980 O/C 1Ph I:
122
2.8
General
2.8.1
Function Description
The unbalanced load protection of 7UT612 uses numerical filters to dissect the phase currents into their symmetrical components. If the negative sequence component of the phase currents is at least 10 % of the nominal device current, and all phase currents are less than four times the nominal device current, then the negative sequence current is fed into the current detector elements.
2.8.1.1
Definite Time Stages The definite time characteristic is of two-stage design. When the negative sequence current exceeds the set threshold ,! the timer 7 ,! is started and a corresponding pickup message is output. When the negative sequence current exceeds the set threshold ,!! of the high-set stage the timer 7 ,!! is started and a corresponding pickup message is output. When a delay time is expired trip command is issued (see Figure 2-74).
123
2 Functions
Tripping
T I2>
T I2>>
I2>>
I2/IN
2.8.1.2
Inverse Time Stage The inverse time overcurrent stage operates with a tripping characteristic either according to the IEC- or the ANSI-standard. The characteristic curves and the corresponding equations are represented in the Technical Data (Figures 4-7 and 4-8 in Section 4.4). The inverse time characteristic superposes the definite time stages I2>> and I2> (see Subsection 2.8.1.1).
Pickup, Trip
The negative sequence current I2 is compared with setting value ,S. When negative sequence current exceeds 1.1 times the setting value, a pickup annunciation is generated. The tripping time is calculated from the negative sequence current according to the characteristic selected. After expiration of the time period a tripping command is output. Figure 2-75 shows the qualitative course of the characteristic. In this figure the overlapping stage I2>> is represented as a dashed line. Dropout of the stage using an IEC curves occurs when the current decreases below about 95 % of the pickup value. A renewed pickup will cause a renewed start of the delay timers. Using the ANSI-characteristics you can determine whether the dropout of the stage is to follow right after the threshold undershot or whether it is evoked by disk emulation. Right after means that the pickup drops out when the pickup value of approx. 95 % is undershot. For a new pickup the time counter starts at zero. The disk emulation evokes a dropout process (time counter is decrementing) which begins after de-energization. This process corresponds to the back turn of a Ferrarisdisk (explaining its denomination disk emulation). In case several faults occur successively, it is ensured that due to the inertia of the Ferraris-disk the History is taken into consideration and the time behaviour is adapted. This ensures a proper simulation
124
of the temperature rise of the protected object even for extremely fluctuating unbalanced load values. The reset begins as soon as 90 % of the setting value is undershot, in correspondence to the dropout curve of the selected characteristic. Within the range of the dropout value (95 % of the pickup value) and 90 % of the setting value, the incrementing and the decrementing processes are in idle state. If 5 % of the setting value is undershot, the dropout process is finished, i.e. when a new pickup is evoked, the timer starts again at zero.
Tripping
T I2>>
I2>>
I2/IN
Trip characteristic of the inverse time unbalanced load protection (with superimposed definite time stage)
Logic
Figure 2-76 shows the logic diagram of the unbalanced load protection. The protection may be blocked via a binary input. That way, pickups and time stages are reset. When the tripping criterion leaves the operating range of the overload protection (all phase currents below 0.1 IN or at least one phase current is greater than 4 IN), the pickups of all unbalanced load stages drop off.
125
2 Functions
FNo 5166
I2p picked up
I2
I2
FNo 5165
I2> picked up
#! D!3
I2>
#" UD!3
T 0 FNo 5170
I2 TRIP
## D!33
#$ UD!33
T 0 FNo 5159
I2>>
I2>> picked up
D@88VSW@
FNo 5143 Meas. release FNo 5152
>BLOCK I2
I2 BLOCKED
#
1
VI76G6I8@GP69 PI PAA
FNo 5153
I2 ACTIVE
FNo 5151
I2 OFF
Figure 2-76
Logic diagram of the unbalanced load protection illustrated for IEC characteristic
2.8.2
General
A two-stage characteristic enables the user to set a short time delay (address 7 ,!!) for the upper stage (address ,!!) and longer time delay (address 7 ,!) for the lower stage (address ,!). Stage I2>, for example, can be used as alarm stage, stage I2>> as tripping stage. Setting ,!! to a percentage higher than 60 % makes sure that no tripping is performed with stage I2>> in case of phase failure.
126
The magnitude of the negative sequence current when one phase is lost, is 1 I 2 = ------ I = 0.58 I 3 On the other hand, with more than 60 % negative sequence current, a two-phase fault in the system may be assumed. Therefore, the delay time 7 ,!! must be coordinated with the time grading of the system. On line feeders, negative sequence protection may serve to identify low-current unsymmetrical faults below the pickup values of the time overcurrent protection. In this case: a two-phase fault with fault current I produces a negative sequence current 1 I 2 = ------ I = 0.58 I 3 a single-phase fault with fault current I produces a negative sequence current 1 I 2 = -- I = 0.33 I 3 With more than 60 % negative sequence current, a two-phase fault can be assumed. The delay time 7 ,!! must be coordinated with the time grading of the system. For a power transformer, negative sequence protection may be used as sensitive protection for low magnitude phase-to-ground and phase-to-phase faults. In particular, this application is well suited for delta-wye transformers where low side phase-toground faults do not generate a high side zero sequence current. The relationship between negative sequence currents and total fault current for phaseto-phase faults and phase-to-ground faults are valid for the transformer as long as the turns ratio is taken into consideration. Considering a power transformer with the following data: Rated apparent power Nominal high side voltage Nominal low side voltage Transformer connection SNT = 16 MVA UHS = 110 kV ULS = 20 kV Dyn5
the following faults may be detected at the lower-voltage side: If the pickup setting (PU) of the device on the high side is set to ,! = 0.1 A, then a phase-to-ground fault current of I = 3 (110 kV/20 kV) ,! = 3 0.1 100 A = 165 A and a phase-to-phase fault of 3 (110/20) 0.1 100 A = 95 A can be detected on the low side. This corresponds to 36 % and 20 % of the power transformer rating. To prevent false operation for faults in other zones of protection, the delay time 7 ,! must be coordinated with the time grading of other relays in the system. For generators and motors, the setting depends on the permissible unbalanced load of the protected object. It is reasonable to set the I2> stage to the continuously permissible negative sequence current and a long time delay in order to obtain an alarm stage. The I2>> stage is then set to a short-term negative sequence current with the delay time permitted here.
127
2 Functions
Example: Motor INmotor I2prim / INmotor I2prim /INmotor INprim / INsec I2> I2>> TI2>> = 545A = 0,11 continuous = 0,55 for Tmax = 1s = 600 A/1 A = 0.11 0.11 = 0.55 0,55 =1s 545 545 545 545 A = 60 A primary or A (1/600) = 0.10 A secondary A = 300 A primary or A (1/600) = 0.50 A secondary
To achieve a better adaptation to the protected object, use the additional inverse-time stage. Inverse Time Stage I2p with IEC curves Having selected an inverse time tripping characteristic the thermal load of a machine caused by unbalanced load can be simulated easily. Use the characteristic which is most similar to the thermal unbalanced load curve of the machine manufacturer. With the IEC-characteristics (address 81%$/ /2$' &+5 = 72& ,(&, see also Subsection 2.1.1) the following characteristics are made available in address ,(& &859(: 1RUPDO ,QYHUVH (type A according to IEC 602553), 9HU\ ,QYHUVH (type B according to IEC 602553), ([WUHPHO\ ,QY (type C according to IEC 602553). The characteristics and equations they are based on are listed in the Technical Data (Section 4.4, Figure 4-7). If an inverse-time characteristic is selected, it must be noted that a safety factor of about 1.1 has already been included between the pickup value and the setting value. This means that a pickup will only occur if an unbalanced load of about 1.1 times the setting value of ,S (Address ) is present. The function will reset as soon as the value undershoots 95 % of the pickup value. The corresponding time multiplier is accessible via address 7 ,S. The time multiplier can also be set to . If set to infinity, the pickup of this function will be indicated but the stage will not be able to trip after pickup. If the inverse time stage is not required, select address 81%$/ /2$' &+5 = 'HILQLWH 7LPH when configuring the protection functions (Subsection 2.1.1). The above mentioned definite time stages can be used in addition to the inverse-time stage as alarm and tripping stages (see margin heading Definite Time Stages I2>>, I2>). Inverse Time Stage I2p with ANSI curves Having selected an inverse-time tripping characteristic the thermal load of a machine caused by unbalanced load can be simulated easily. Use the characteristic which is most similar to the thermal unbalanced load curve of the machine manufacturer. With the ANSI characteristics (address 81%$/ /2$' &+5 = 72& $16,) the following is made available in address $16, &859(:
128
2.8.3
Setting Overview
Note: The following list indicates the setting ranges and default settings for a rated secondary current of IN = 1 A. For a rated secondary current of IN = 5 A, these values must be multiplied by 5. When performing settings in primary values, the current transformer ratios have to be taken into consideration.
Setting Title UNBALANCE LOAD OFF ON I2> T I2> I2>> T I2>> IEC CURVE
Setting Options
Default Setting OFF 0.10 A 1.50 sec 0.50 A 1.50 sec Extremely Inverse
Comments Unbalance Load (Negative Sequence) I2> Pickup T I2> Time Delay I2>> Pickup T I2>> Time Delay IEC Curve
0.10..3.00 A 0.00..60.00 sec; 0.10..3.00 A 0.00..60.00 sec; Normal Inverse Very Inverse Extremely Inverse Extremely Inverse Inverse Moderately Inverse Very Inverse
4007
ANSI CURVE
Extremely Inverse
ANSI Curve
129
2 Functions
Setting Title
Comments
2.8.4
Information Overview
F.No. 05143 >BLOCK I2 05151 I2 OFF 05152 I2 BLOCKED 05153 I2 ACTIVE 05159 I2>> picked up 05165 I2> picked up 05166 I2p picked up 05170 I2 TRIP 05172 I2 Not avalia.
Alarm
Comments >BLOCK I2 (Unbalance Load) I2 switched OFF I2 is BLOCKED I2 is ACTIVE I2>> picked up I2> picked up I2p picked up I2 TRIP I2 Not avaliable for this objekt
130
2.9
2.9.1
Principle
with
currently valid temperature rise referred to the final temperature rise for the maximum permissible phase current k INobj, th thermal time constant for heating up, k kfactor which states the maximum permissible continuous current, referred to the rated current of the protected object, I currently valid RMS current, INobj rated current of protected object.
The solution of this equation under steady-state conditions is an efunction whose asymptote shows the final temperature rise end. When the temperature rise reaches the first settable temperature threshold alarm, which is below the final temperature rise, a warning alarm is given in order to allow an early load reduction. When the second temperature threshold, i.e. the final temperature rise or tripping temperature, is reached, the protected object is disconnected from the network. The overload protection can, however, also be set on $ODUP 2QO\. In this case only an alarm is output when the final temperature rise is reached. The temperature rises are calculated separately for each phase in a thermal replica from the square of the associated phase current. This guarantees a true RMS value measurement and also includes the effect of harmonic content. The maximum calculated temperature rise of the three phases is decisive for evaluation of the thresholds. The maximum permissible continuous thermal overload current Imax is described as a multiple of the rated current INobj:
131
2 Functions
Imax = k INobj INobj is the rated current of the protected object: For power transformers, the rated power of the assigned winding is decisive. The device calculates this rated current from the rated apparent power of the transformer and the rated voltage of the assigned winding. For transformers with tap changer, the non-regulated side must be used. For generators, motors, or reactors, the rated object current is calculated by the device from the set rated apparent power and the rated voltage. For short lines or busbars, the rated current was directly set. In addition to the kfactor, the thermal time constant th as well as the alarm temperature rise alarm must be entered into the protection. Apart from the thermal alarm stage, the overload protection also includes a current overload alarm stage Ialarm, which can output an early warning that an overload current is imminent, even when the temperature rise has not yet reached the alarm or trip temperature rise values. The overload protection can be blocked via a binary input. In doing so, the thermal replica are also reset to zero. Extension of the Time Constant for Machines The differential equation mentioned above assumes a constant cooling represented by the thermal time constant th = Rth Cth (thermal resistance times thermal capacitance). But, the thermal time constant of a self-ventilated machine during stand-still differs substantially from that during operation because of the missing ventilation. Thus, in this case, two time constants exist. This must be considered in the thermal replica. Stand-still of the machine is assumed when the current drops below the threshold %UHDNHU 6 ,! or %UHDNHU 6 ,! (depending on the assigned side for overload protection, refer also to Circuit Breaker Status in Subsection 2.1.2). Motor Startup Recognition On startup of electrical machines the temperature rise calculated by the thermal replica may exceed the alarm temperature rise or even the trip temperature rise. To avoid an alarm or trip, the starting current is acquired and the increase of temperature rise deriving from it is suppressed. This means that the calculated temperature rise is kept constant as long as the starting current is detected. When machines must be started for emergency reasons, operating temperatures above the maximum permissible operating temperatures are allowed (emergency start). Then exclusively the tripping signal can be blocked via a binary input (!(PHU6WDUW 2/). After startup and dropout of the binary input, the thermal replica may still be greater than the trip temperature rise. Therefore the thermal replica features a settable run-on time (7 (0(5*(1&<) which is started when the binary input drops out. It also suppresses the trip command. Tripping by the overload protection will be defeated until this time interval elapses. This binary input only affects the trip command. There is no effect on fault recording, nor does the thermal replica reset.
132
D6G6SH #!$
1
#!# 6G6SH
FNo 01515
&
O/L I Alarm
FNo 01516
max
=0
100 % (fix)
O/L Alarm
&
DHPUPSTU6SU #!( #!& FA68UPS
CB closed
FNo 01521
ThOverload TRIP
FNo 01517
&
FNo 01503
FNo 01512
>BLK ThOverload
Th.Overload BLK
FNo 01513
#! UurPW@SGP69
PAA
1
Th.Overload
FNo 01511
Th.Overload OFF
PI 6yhPy
#!' U@H@SB@I8`
FNo 01507
>Emer.Start O/L
Figure 2-77
2.9.2
133
2 Functions
Cooling Methods
The hot-spot calculation is dependent on the cooling method. Air cooling is always available. Two different methods are distinguished: AN (Air Natural): natural air circulation and AF (Air Forced): forced air circulation (ventilation). If liquid coolants are used in combination with the two cooling methods above-described, the following types of coolants are available: ON (Oil Natural = naturally circulating oil): Because of emerging differences in temperature the coolant (oil) moves within the tank. The cooling effect is not very intense due to its natural convection. This cooling variant, however, is almost noiseless. OF (Oil Forced = forced oil circulation): An oil pump makes the coolant (oil) move within the tank. The cooling effect of this method is therefore more intense than with the ON method. OD (Oil Directed = forced-directed oil circulation): The coolant (oil) is directed through the tank. Therefore the oil flow is intensified for sections which are extremely temperature-sensitive. Therefore, the cooling effect is very good. This method has the lowest temperature rise. Figures 2-78 to 2-80 show examples of the cooling methods.
ONAN cooling
ONAF cooling
134
OFAN cooling
Figure 2-79
OD cooling
Figure 2-80
Hot-Spot Calculation
The hot-spot temperature of the protected object is an important value of status. The hottest spot relevant for the life-time of the transformer is usually situated at the insulation of the upper inner turn. Generally the temperature of the coolant increases from the bottom up. The cooling method, however, affects the rate of the temperature drop. The hot-spot temperature is composed of two parts: the temperature at the hottest spot of the coolant (included via thermobox), the temperature rise of the winding turn caused by the transformer load. Thermobox 7XV566 can be used to acquire the temperature of the hottest spot. It converts the temperature value into numerical signals and sends them to the corresponding interface of device 7UT612. The thermobox is able to acquire the temperature at up to 6 points of the transformer tank. Up to two thermoboxes of this types can be connected to a 7UT612.
135
2 Functions
The device calculates the hot-spot temperature from these data and the settings of the characteristical properties. When a settable threshold (temperature alarm) is exceeded, an annunciation and/or a trip is generated. Hot-spot calculation is done with different equations depending on the cooling method. For ONcooling and OFcooling: h = o + H gr k with h o Hgr k Y
Y
hot-spot temperature top oil temperature hot-spot to top-oil gradient load factor I/IN (measured) winding exponent
For ODcooling: h = o + H gr k
Y Y Y
The life-time of a cellulose insulation refers to a temperature of 98 C or 208.4 F in the direct environment of the insulation. Experience shows that an increase of 6 K means half of the life-time. For a temperature which defers from the basic value of 98 C (208.4 F), the relative ageing rate V is given by Ageing at h ( h 98 ) 6 V = ----------------------------------------- = 2 Ageing at 98 C The mean value of the relative ageing rate L is given by the calculation of the mean value of a certain period of time, i.e. from T1 to T2:
T2
1 L = ------------------ T 2 T1
V dt
T1
With constant rated load, the relative ageing rate L is equal to 1. For values greater than 1, accelerated ageing applies, e.g. if L = 2 only half of the life-time is expected compared to the life-time under nominal load conditions. According to IEC, the ageing range is defined from 80 C to 140 C (176 F to 284 F). This is the operating range of the ageing calculation in 7UT612: Temperatures below 80 C (176 F) do not extent the calculated ageing rate; values greater than 140 C (284 F) do not reduce the calculated ageing rate. The above-described relative ageing calculation only applies to the insulation of the winding and cannot be used for other failure causes. Output of Results The hot-spot temperature is calculated for the winding which corresponds to the side of the protected object configured for overload protection (Subsection 2.1.1, address ). The calculation includes the current of that side and the cooling temperature measured at a certain measuring point. There are two thresholds which can be set. They output a warning (Stage 1) and an alarm (Stage 2) signal. When the alarm signal is assigned to a trip output, it can also be used for tripping the circuit breaker(s).
136
For the middle ageing rate, there is also a threshold for each of the warning and the alarm signal. The status can be read out from the operational measured values at any time. The information includes: hot-spot temperature for each winding in C or F (as configured), relative ageing rate expressed in per unit, load backup up to warning signal (Stage 1) expressed in per cent, load backup up to alarm signal (Stage 2) expressed in per cent.
2.9.3
General
137
2 Functions
kFactor
The rated current of the protected object is taken as the base current for detecting an overload. The setting factor k is set under address .)$&725. It is determined by the relation between the permissible thermal continuous current and this rated current: I max k = ----------I Nobj When using the method with a thermal replica, it is not necessary to evaluate any absolute temperature nor the trip temperature since the trip temperature rise is equal to the final temperature rise at k INobj. Manufacturers of electrical machines usually state the permissible continuous current. If no data are available, k is set to 1.1 times the rated current of the protected object. For cables, the permissible continuous current depends on the cross-section, the insulation material, the design and the method of installation, and can be derived from the relevant tables. When using the method with hot-spot evaluation according to IEC 60354, set k = 1 since all remaining parameters are referred to the rated current of the protected object.
The thermal time constant th is set under the address 7,0( &2167$17. This is also to be stated by the manufacturer. Please note that the time constant is set in minutes. Quite often other values for determining the time constant are stated which can be converted into the time constant as follows: 1s current 2 th 1 permissible 1s current -------- = ----- -------------------------------------------------------------------------------- 60 permissible continuous current min permissible current for application time other than 1 s, e.g. for 0.5 s 2 th 0.5 permissible 0.5s current -------- = ------- -------------------------------------------------------------------------------- min 60 permissible continuous current t6time; this is the time in seconds for which a current of 6 times the rated current of the protected object may flow th -------- = 0.6 t 6 min
Calculation examples: Cable with permissible continuous current 322 A permissible 1s current 13.5 kA th 2 1 13500 A 2 1 -------- = ----- ---------------------- = ----- 42 = 29.4 min 60 322 A 60 Setting value 7,0( &2167$17 = min. Motor with t6time 12 s th -------- = 0.6 12 s = 7.2 min Setting value 7,0( &2167$17 = min. For rotating machines, the time constant as set under address 7,0( &2167$17 is valid as long as the machine is running. The machine will cool down extensively
138
slower during stand-still or running down if it is self-ventilated. This phenomenon is considered by a higher stand-still time constant .)$&725 (address $) which is set as a factor of the normal time constant. Stand-still of the machine is assumed when the currents fall below the threshold %UHDNHU 6 ,! or %UHDNHU 6 ,!, depending on the side to which the overload protection is assigned, (see margin Circuit Breaker Status in Subsection 2.1.2). This parameter can only be changed with DIGSI 4 under Additional Settings. If it not necessary to distinguish between different time constants, leave the factor . )$&725 at (default setting). Alarm Stages with Thermal Replica By setting a thermal alarm stage $/$50 (address ) an alarm can be output before the tripping temperature is reached, so that a trip can be avoided by early load reduction or by switching over. The percentage is referred to the tripping temperature rise. Note that the final temperature rise is proportional to the square of the current. Example: kfactor = 1.1 Alarm shall be given when the temperature rise reaches the final (steady-state) temperature rise at nominal current. 1 alarn = ---------- = 0.826 2 1.1 Setting value $/$50 = %. The current overload alarm setpoint , $/$50 (address ) is stated in amps (primary or secondary) and should be set equal to or slightly below the permissible continuous current k INobj. It can also be used instead of the thermal alarm stage. In this case the thermal alarm stage is set to 100 % and thus practically ineffective. Emergency Start for Motors The run-on time value to be entered at address $ 7 (0(5*(1&< must ensure that after an emergency start and dropout of the binary input !(PHU6WDUW 2/ the trip command is blocked until the thermal replica has fallen below the dropout threshold. This parameter can only be changed with DIGSI 4 under Additional Settings. The startup itself is only recognized if the startup current , 02725 67$57 set in address $ is exceeded. Under each load and voltage condition during motor start, the value must be overshot by the actual startup current. With short-time permissible overload the value must not be reached. For other protected objects the setting will not be changed. Thus the emergency start is disabled. Temperature Detectors For the hot-spot calculation according to IEC 60354 the device must be informed on the type of resistance temperature detectors that will be used for measuring the oil temperature, the one relevant for the hot-spot calculation and ageing determination. Up to 6 sensors can be used with one thermobox 7XV566, with 2 boxes up to 12 sensors. In address 2,/'(7 57' the identification number of the resistance temperature detector decisive for hot-spot calculation is set. The characteristic values of the temperature detectors are set separately, see Section 2.10.
139
2 Functions
Hot-Spot Stages
There are two annunciation stages for the hot-spot temperature. To set a specific hotspot temperature value (expressed in C) which is meant to generate the warning signal (Stage 1), use address +27 6327 67 . Use address +27 6327 67 to indicate the corresponding alarm temperature (Stage 2). Optionally, it can be used for tripping of circuit breakers if the outgoing message 2/ KVSRW 75,3 (FNo ) is allocated to a trip relay. If address 7(03 81,7 = )DKUHQKHLW is set (Subsection 2.1.2, margin heading Temperature Unit), thresholds for warning and alarm temperatures have to be expressed in Fahrenheit (addresses and ). If the temperature unit is changed in address after having set the thresholds for temperature, these thresholds for the temperature unit changed must be set again in the corresponding addresses.
Ageing Rate
For ageing rate L thresholds can also be set, i.e. for the warning signal (Stage 1) in address $* 5$7( 67 and for alarm signal (Stage 2) in address $* 5$7( 67 . This information is referred to the relative ageing, i.e. L = 1 is reached at 98 C or 208 F at the hot spot. L > 1 means an accelerated ageing, L < 1 a delayed ageing. Set in address 0(7+ &22/,1* which cooling method is used: 21 = Oil Natural for natural cooling, 2) = Oil Forced for oil forced cooling or 2' = Oil Directed for oil directed cooling. For definitions see also Subsection 2.9.2, margin heading Cooling Methods. For hot-spot calculation the device requires the winding exponent Y and the hot-spot to top-oil gradient Hgr which is set in addresses <:,1'(;321(17 and +276327 *5. If the corresponding information is not available, it can be taken from the IEC 60354. An extract from the corresponding table of the standard with the technical data relevant for this project can be found hereinafter (Table 2-5).
Table 2-5
Thermal characteristics of power transformers Distribution transformers ONAN 1.6 23 Medium and large power transformers ON.. OF.. OD.. 1.8 26 1.8 22 2.0 29
140
2.9.4
Setting Overview
Note: The following list indicates the setting ranges and default settings for a rated secondary current of IN = 1 A. For a rated secondary current of IN = 5 A, these values must be multiplied by 5. When setting the device using primary values, the current transformer ratios have to be taken into consideration. Note: Addresses which have an A attached to its end can only be changed in DIGSI 4, under Additional Settings.
Addr. 4201
Setting Options OFF ON Alarm Only 0.10..4.00 1.0..999.9 min 50..100 % 0.10..4.00 A 1.0..10.0 10..15000 sec 0.60..10.00 A; 1..6 98..140 C 208..284 F 98..140 C 208..284 F 0.125..128.000 0.125..128.000 ON (Oil-Natural) OF (Oil-Forced) OD (Oil-Directed) 1.6..2.0 22..29
4202 4203 4204 4205 4207A 4208A 4209A 4221 4222 4223 4224 4225 4226 4227 4231
K-FACTOR TIME CONSTANT ALARM I ALARM K-FACTOR T EMERGENCY I MOTOR START OIL-DET. RTD HOT SPOT ST. 1 HOT SPOT ST. 1 HOT SPOT ST. 2 HOT SPOT ST. 2 AG. RATE ST. 1 AG. RATE ST. 2 METH. COOLING
1.10 100.0 min 90 % 1.00 A 1.0 100 sec A 1 98 C 208 F 108 C 226 F 1.000 2.000 ON (Oil-Natural)
K-Factor Time Constant Thermal Alarm Stage Current Overload Alarm Setpoint Kt-FACTOR when motor stops Emergency Time Current Pickup Value of Motor Starting Oil-Detector conected at RTD Hot Spot Temperature Stage 1 Pickup Hot Spot Temperature Stage 1 Pickup Hot Spot Temperature Stage 2 Pickup Hot Spot Temperature Stage 2 Pickup Aging Rate STAGE 1 Pickup Aging Rate STAGE 2 Pickup Method of Cooling
4232 4233
Y-WIND.EXPONENT HOT-SPOT GR
1.6 22
141
2 Functions
2.9.5
Information Overview
F.No.
Alarm
Comments >BLOCK Thermal Overload Protection >Emergency start Th. Overload Protection Thermal Overload Protection OFF Thermal Overload Protection BLOCKED Thermal Overload Protection ACTIVE Th. Overload Current Alarm (I alarm) Thermal Overload Alarm Thermal Overload picked up Thermal Overload TRIP Thermal Overload hot spot Th. Alarm Thermal Overload hot spot Th. TRIP Thermal Overload aging rate Alarm Thermal Overload aging rate TRIP Th. Overload No temperature mesured Th. Overload Not avaliable for this obj.
01503 >BLK ThOverload 01507 >Emer.Start O/L 01511 Th.Overload OFF 01512 Th.Overload BLK 01513 Th.Overload ACT 01515 O/L I Alarm 01516 O/L Alarm 01517 O/L Th. pick.up 01521 ThOverload TRIP 01541 O/L ht.spot Al. 01542 O/L h.spot TRIP 01543 O/L ag.rate Al. 01544 O/L ag.rt. TRIP 01545 O/L No Th.meas. 01549 O/L Not avalia.
142
2.10
143
2 Functions
for RTD2 address $ address $ address address for RTD3 address $ address $ address address for RTD4 address $ address $ address address for RTD5 address $ address $ address address for RTD6 address $ address $ address address 57' 57' 57' 57' 57' 57' 57' 57' 57' 57' 57' 57' 57' 57' 57' 57' 57' 57' 57' 57' 7<3(, /2&$7,21, 67$*( (in C) or 57' 67$*( (F), 67$*( (in C) or 57' 67$*( (F); 7<3(, /2&$7,21, 67$*( (in C) or 57' 67$*( (F), 67$*( (in C) or 57' 67$*( (F); 7<3(, /2&$7,21, 67$*( (in C) or 57' 67$*( (F), 67$*( (in C) or 57' 67$*( (F); 7<3(, /2&$7,21, 67$*( (in C) or 57' 67$*( (F), 67$*( (in C) or 57' 67$*( (F); 7<3(, /2&$7,21, 67$*( (in C) or 57' 67$*( (F), 67$*( (in C) or 57' 67$*( (F);
If two thermoboxes are connected, information for further temperature detectors can be set: for RTD7 address $ address $ address address for RTD8 address $ address $ address address for RTD9 address $ address $ address address for RTD address $ address $ address address for RTD address $ address $ address address for RTD address $ address $ address address 57' 57' 57' 57' 57' 57' 57' 57' 57' 57' 57' 57' 7<3(, /2&$7,21, 67$*( (in C) or 57' 67$*( (F), 67$*( (in C) or 57' 67$*( (F); 7<3(, /2&$7,21, 67$*( (in C) or 57' 67$*( (F), 67$*( (in C) or 57' 67$*( (F); 7<3(, /2&$7,21, 67$*( (in C) or 57' 67$*( (F), 67$*( (in C) or 57' 67$*( (F); 7<3(, /2&$7,21, 67$*( (in C) or 57' 67$*( (F), 67$*( (in C) or 57' 67$*( (F); 7<3(, /2&$7,21, 67$*( (in C) or 57' 67$*( (F), 67$*( (in C) or 57' 67$*( (F); 7<3(, /2&$7,21, 67$*( (in C) or 57' 67$*( (F), 67$*( (in C) or 57' 67$*( (F).
57' 57' 57' 57' 57' 57' 57' 57' 57' 57' 57' 57'
144
9012A
RTD 1 LOCATION
Oil
RTD 1: Location
RTD 1 STAGE 1 RTD 1 STAGE 1 RTD 1 STAGE 2 RTD 1 STAGE 2 RTD 2 TYPE
RTD 1: Temperature Stage 1 Pickup RTD 1: Temperature Stage 1 Pickup RTD 1: Temperature Stage 2 Pickup RTD 1: Temperature Stage 2 Pickup RTD 2: Type
9022A
RTD 2 LOCATION
Other
RTD 2: Location
RTD 2 STAGE 1 RTD 2 STAGE 1 RTD 2 STAGE 2 RTD 2 STAGE 2 RTD 3 TYPE
RTD 2: Temperature Stage 1 Pickup RTD 2: Temperature Stage 1 Pickup RTD 2: Temperature Stage 2 Pickup RTD 2: Temperature Stage 2 Pickup RTD 3: Type
9032A
RTD 3 LOCATION
Other
RTD 3: Location
RTD 3: Temperature Stage 1 Pickup RTD 3: Temperature Stage 1 Pickup RTD 3: Temperature Stage 2 Pickup RTD 3: Temperature Stage 2 Pickup
145
2 Functions
Addr. 9041A
Setting Options not connected Pt 100 Ohm Ni 120 Ohm Ni 100 Ohm Oil Ambient Winding Bearing Other -50..250 C; -58..482 F; -50..250 C; -58..482 F; not connected Pt 100 Ohm Ni 120 Ohm Ni 100 Ohm Oil Ambient Winding Bearing Other -50..250 C; -58..482 F; -50..250 C; -58..482 F; not connected Pt 100 Ohm Ni 120 Ohm Ni 100 Ohm Oil Ambient Winding Bearing Other -50..250 C; -58..482 F; -50..250 C; -58..482 F; not connected Pt 100 Ohm Ni 120 Ohm Ni 100 Ohm
Comments
9042A
RTD 4 LOCATION
Other
RTD 4: Location
RTD 4 STAGE 1 RTD 4 STAGE 1 RTD 4 STAGE 2 RTD 4 STAGE 2 RTD 5 TYPE
RTD 4: Temperature Stage 1 Pickup RTD 4: Temperature Stage 1 Pickup RTD 4: Temperature Stage 2 Pickup RTD 4: Temperature Stage 2 Pickup RTD 5: Type
9052A
RTD 5 LOCATION
Other
RTD 5: Location
RTD 5 STAGE 1 RTD 5 STAGE 1 RTD 5 STAGE 2 RTD 5 STAGE 2 RTD 6 TYPE
RTD 5: Temperature Stage 1 Pickup RTD 5: Temperature Stage 1 Pickup RTD 5: Temperature Stage 2 Pickup RTD 5: Temperature Stage 2 Pickup RTD 6: Type
9062A
RTD 6 LOCATION
Other
RTD 6: Location
RTD 6 STAGE 1 RTD 6 STAGE 1 RTD 6 STAGE 2 RTD 6 STAGE 2 RTD 7 TYPE
RTD 6: Temperature Stage 1 Pickup RTD 6: Temperature Stage 1 Pickup RTD 6: Temperature Stage 2 Pickup RTD 6: Temperature Stage 2 Pickup RTD 7: Type
146
Addr. 9041A
Setting Options not connected Pt 100 Ohm Ni 120 Ohm Ni 100 Ohm Oil Ambient Winding Bearing Other -50..250 C; -58..482 F; -50..250 C; -58..482 F; not connected Pt 100 Ohm Ni 120 Ohm Ni 100 Ohm Oil Ambient Winding Bearing Other -50..250 C; -58..482 F; -50..250 C; -58..482 F; not connected Pt 100 Ohm Ni 120 Ohm Ni 100 Ohm Oil Ambient Winding Bearing Other -50..250 C; -58..482 F; -50..250 C; -58..482 F; not connected Pt 100 Ohm Ni 120 Ohm Ni 100 Ohm
Comments
9042A
RTD 4 LOCATION
Other
RTD 4: Location
RTD 4 STAGE 1 RTD 4 STAGE 1 RTD 4 STAGE 2 RTD 4 STAGE 2 RTD 5 TYPE
RTD 4: Temperature Stage 1 Pickup RTD 4: Temperature Stage 1 Pickup RTD 4: Temperature Stage 2 Pickup RTD 4: Temperature Stage 2 Pickup RTD 5: Type
9052A
RTD 5 LOCATION
Other
RTD 5: Location
RTD 5 STAGE 1 RTD 5 STAGE 1 RTD 5 STAGE 2 RTD 5 STAGE 2 RTD 6 TYPE
RTD 5: Temperature Stage 1 Pickup RTD 5: Temperature Stage 1 Pickup RTD 5: Temperature Stage 2 Pickup RTD 5: Temperature Stage 2 Pickup RTD 6: Type
9062A
RTD 6 LOCATION
Other
RTD 6: Location
RTD 6 STAGE 1 RTD 6 STAGE 1 RTD 6 STAGE 2 RTD 6 STAGE 2 RTD 7 TYPE
RTD 6: Temperature Stage 1 Pickup RTD 6: Temperature Stage 1 Pickup RTD 6: Temperature Stage 2 Pickup RTD 6: Temperature Stage 2 Pickup RTD 7: Type
147
2 Functions
Addr. 9072A
Setting Options Oil Ambient Winding Bearing Other -50..250 C; -58..482 F; -50..250 C; -58..482 F; not connected Pt 100 Ohm Ni 120 Ohm Ni 100 Ohm Oil Ambient Winding Bearing Other -50..250 C; -58..482 F; -50..250 C; -58..482 F; not connected Pt 100 Ohm Ni 120 Ohm Ni 100 Ohm Oil Ambient Winding Bearing Other -50..250 C; -58..482 F; -50..250 C; -58..482 F; not connected Pt 100 Ohm Ni 120 Ohm Ni 100 Ohm
RTD 7 STAGE 1 RTD 7 STAGE 1 RTD 7 STAGE 2 RTD 7 STAGE 2 RTD 8 TYPE
RTD 7: Temperature Stage 1 Pickup RTD 7: Temperature Stage 1 Pickup RTD 7: Temperature Stage 2 Pickup RTD 7: Temperature Stage 2 Pickup RTD 8: Type
9082A
RTD 8 LOCATION
Other
RTD 8: Location
RTD 8 STAGE 1 RTD 8 STAGE 1 RTD 8 STAGE 2 RTD 8 STAGE 2 RTD 9 TYPE
RTD 8: Temperature Stage 1 Pickup RTD 8: Temperature Stage 1 Pickup RTD 8: Temperature Stage 2 Pickup RTD 8: Temperature Stage 2 Pickup RTD 9: Type
9092A
RTD 9 LOCATION
Other
RTD 9: Location
RTD 9 STAGE 1 RTD 9 STAGE 1 RTD 9 STAGE 2 RTD 9 STAGE 2 RTD10 TYPE
RTD 9: Temperature Stage 1 Pickup RTD 9: Temperature Stage 1 Pickup RTD 9: Temperature Stage 2 Pickup RTD 9: Temperature Stage 2 Pickup RTD10: Type
9102A
Other
RTD10: Location
148
Setting Title RTD10 STAGE 1 RTD10 STAGE 1 RTD10 STAGE 2 RTD10 STAGE 2 RTD11 TYPE
Setting Options -50..250 C; -58..482 F; -50..250 C; -58..482 F; not connected Pt 100 Ohm Ni 120 Ohm Ni 100 Ohm
Comments RTD10: Temperature Stage 1 Pickup RTD10: Temperature Stage 1 Pickup RTD10: Temperature Stage 2 Pickup RTD10: Temperature Stage 2 Pickup RTD11: Type
9112A
RTD11 LOCATION Oil Ambient Winding Bearing Other RTD11 STAGE 1 RTD11 STAGE 1 RTD11 STAGE 2 RTD11 STAGE 2 RTD12 TYPE -50..250 C; -58..482 F; -50..250 C; -58..482 F; not connected Pt 100 Ohm Ni 120 Ohm Ni 100 Ohm
Other
RTD11: Location
RTD11: Temperature Stage 1 Pickup RTD11: Temperature Stage 1 Pickup RTD11: Temperature Stage 2 Pickup RTD11: Temperature Stage 2 Pickup RTD12: Type
9122A
RTD12 LOCATION Oil Ambient Winding Bearing Other RTD12 STAGE 1 RTD12 STAGE 1 RTD12 STAGE 2 RTD12 STAGE 2 -50..250 C; -58..482 F; -50..250 C; -58..482 F;
Other
RTD12: Location
RTD12: Temperature Stage 1 Pickup RTD12: Temperature Stage 1 Pickup RTD12: Temperature Stage 2 Pickup RTD12: Temperature Stage 2 Pickup
149
2 Functions
150
Alarm
Comments Fail: RTD11 (broken wire/shorted) RTD11 Temperature stage 1 picked up RTD11 Temperature stage 2 picked up Fail: RTD12 (broken wire/shorted) RTD12 Temperature stage 1 picked up RTD12 Temperature stage 2 picked up
14212 RTD11 St.1 p.up 14213 RTD11 St.2 p.up 14221 Fail: RTD12 14222 RTD12 St.1 p.up 14223 RTD12 St.2 p.up
151
2 Functions
2.11
&
TBF
0 BF Trip
7UT612
Figure 2-81
Simplified function diagram of circuit breaker failure protection with current flow monitoring
Normally, the breaker will open and interrupt the fault current. The current monitoring stage CBI> resets and stops the timer TBF. If the trip command is not carried out (breaker failure case), current continues to flow and the timer runs to its set limit. The breaker failure protection then issues a command to trip the backup breakers and interrupt the fault current. The reset time of the feeder protection is not relevant because the breaker failure protection itself recognizes the interruption of the current.
152
Please make sure that the measuring point of the current and the supervised circuit breaker belong together! Both must be located at the supply side of the protected object. In Figure 2-81 the current is measured at the busbar side of the transformer (= supply side), therefore the circuit breaker at the busbar side is supervised. The adjacent circuit breakers are those of the busbar illustrated. With generators the breaker failure protection usually affects the network breaker. In cases other than that, the supply side must be the relevant one. Initiation Figure 2-82 shows a logic diagram of the circuit breaker failure protection. The breaker failure protection can be initiated by two different sources: Internal protective function of the 7UT612, e.g. trip commands of protective functions or via CFC (internal logic functions), External trip signals via binary input. In both cases, the breaker failure protection checks the continuation of current flow. Additionally, the breaker position (read from the auxiliary contact) can be checked. The current criterion is fulfilled if at least one of the three phase currents exceeds a set threshold value: %UHDNHU 6 ,! or %UHDNHU 6 ,!, depending on the side to which the breaker failure protection is assigned, see also Subsection 2.1.2 under margin Circuit Breaker Status (page 27). Processing of the auxiliary contact criterion depends on which auxiliary contacts are available and how they are arranged to the binary inputs of the device. If both the normally closed (NC) as well as the normally open (NO) auxiliary contacts are available, an intermediate position of the breaker can be detected. In this case, disappearance of the current flow is always the only criterion for the breaker response. Initiation can be blocked via the binary input !%/2&. %NU)DLO (e.g. during testing of the feeder protection relay). Delay Time and Breaker Failure Trip For each of the two sources, a unique pickup message is generated, a unique time delay is initiated, and a unique tripping signal is generated. The setting value for the delay applies to both sources. When the associated time has elapsed, trip command is issued. The two commands are combined with an ORgate and form the output information %UN)DLOXUH 75,3 which is used to trip the adjacent breakers so that the fault current will be interrupted. The adjacent breakers are those which can feed the same busbar or busbar section to which the breaker is connected.
153
2 Functions
ux7SF8PIU68U PAA 1 PI
&
CB open configured CB closed configured
Error
&
=
& 1
& &
Internal initiation source
&$USDQUvr
Device Trip
& >
&
87Tvqr D3283
Max. of IL1, IL2, IL3
&$USDQUvr
FNo 1431 >BrkFail extSRC
& &
87Tvqr D3283
Max. of IL1, IL2, IL3
>
FNo 1471 BrkFailure TRIP
Figure 2-82
154
Fault inception Normal fault clearance time Prot. trip CB operating time Reset CB I> Initiation breaker failure protection Time delay TBF of breaker failure protection CB operating time (adjacent CBs) Safety margin
Figure 2-83
Time sequence example for normal clearance of a fault, and with circuit breaker failure
155
2 Functions
Comments
01431 >BrkFail extSRC 01451 BkrFail OFF 01452 BkrFail BLOCK 01453 BkrFail ACTIVE 01456 BkrFail int PU 01457 BkrFail ext PU 01471 BrkFailure TRIP 01480 BkrFail intTRIP 01481 BkrFail extTRIP 01488 BkrFail Not av.
>Breaker failure initiated externally Breaker failure is switched OFF Breaker failure is BLOCKED Breaker failure is ACTIVE Breaker failure (internal) PICKUP Breaker failure (external) PICKUP Breaker failure TRIP Breaker failure (internal) TRIP Breaker failure (external) TRIP Breaker failure Not aval. for this obj.
156
2.12
FNo 04536
Ext 1 picked up
FNo 04526
U9@G6`
>Ext trip 1
&
FNo 04537
FNo 04523
>BLOCK Ext 1
Ext 1 BLOCKED
Figure 2-84
Transformer Messages
In addition to the external trip commands as described above, some typical messages from power transformers can be incorporated into the processing of the 7UT612 via binary inputs. This prevents the user from creating user specified annunciations. These messages are the Buchholz alarm, Buchholz trip and Buchholz tank alarm as well as gassing alarm of the oil.
Sometimes for transformers so-called sudden pressure relays (SPR) are installed in the tank which are meant to switch off the transformer in case of a sudden pressure increase. Not only transformer failures but also high traversing fault currents originating from external faults can lead to a pressure increase. External faults are quickly recognized by 7UT612 (refer also to Subsection 2.2.1, margin heading Add-on Stabilization during External Fault, page 36). A blocking signal can be created by means of a CFC logic in order to prevent from erroneous trip of the SPR. Such a logic can be created according to Figure 2-85, for example.
157
2 Functions
"IN: 7ypxThG
"OUT: 7ypxTQSDTQ"
Figure 2-85
Setting Options
Comments External Trip Function 1 Ext. Trip 1 Time Delay External Trip Function 2 Ext. Trip 2 Time Delay
158
F.No. 04523 >BLOCK Ext 1 04526 >Ext trip 1 04531 Ext 1 OFF 04532 Ext 1 BLOCKED 04533 Ext 1 ACTIVE 04536 Ext 1 picked up 04537 Ext 1 Gen. TRIP 04543 >BLOCK Ext 2 04546 >Ext trip 2 04551 Ext 2 OFF 04552 Ext 2 BLOCKED 04553 Ext 2 ACTIVE 04556 Ext 2 picked up 04557 Ext 2 Gen. TRIP F.No. 00390 >Gas in oil 00391 >Buchh. Warn 00392 >Buchh. Trip 00393 >Buchh. Tank
Comments
External trip 1 is switched OFF External trip 1 is BLOCKED External trip 1 is ACTIVE External trip 1: General picked up External trip 1: General TRIP >BLOCK external trip 2 >Trigger external trip 2 External trip 2 is switched OFF External trip 2 is BLOCKED External trip 2 is ACTIVE External trip 2: General picked up External trip 2: General TRIP Alarm Comments >Warning stage from gas in oil detector >Warning stage from Buchholz protection >Tripp. stage from Buchholz protection >Tank supervision from Buchh. protect.
159
2 Functions
2.13
Monitoring Functions
The device incorporates comprehensive monitoring functions which cover both hardware and software; the measured values are continuously checked for plausibility, so that the CT circuits are also included in the monitoring system to a large extent. Furthermore, binary inputs are available for supervision of the trip circuit.
Memory Modules
160
Sampling Frequency
The sampling frequency is continuously monitored. If deviations cannot be corrected by another synchronization, the device sets itself out of operation and the red LED Blocked lights up; the Device OK relay drops off and signals the malfunction by its healthy status contact.
2.13.1.2 Software Monitoring Watchdog For continuous monitoring of the program sequences, a watchdog timer is provided in the hardware (hardware watchdog) which will reset and completely restart the processor system in the event of processor failure or if a program falls out of step. A further software watchdog ensures that any error in the processing of the programs will be recognized. Such errors also lead to a reset of the processor. If such an error is not eliminated by restarting, another restart attempt is initiated. If the fault is still present after three restart attempts within 30 s, the protection system will take itself out of service, and the red LED Blocked lights up. The Device OK relay drops off and signals the malfunction by its healthy status contact.
2.13.1.3 Monitoring of Measured Quantities The device detects and signals most of the interruptions, short-circuits, or wrong connections in the secondary circuits of current transformers (an important commissioning aid). For this the measured values are checked in background routines at cyclic intervals, as long as no pickup condition exists. Current Balance In healthy network operation it can be expected that the currents will be approximately balanced. The monitoring of the measured values in the device checks this balance for each side of a three-phase object. For this the lowest phase current is set in relation to the highest. An unbalance is detected, e.g. for side 1, when |Imin | / |Imax | Imax / IN < %$/ )$&7 , 6 provided that > %$/ , /,0,7 6 / IN
Imax is the highest, Imin the lowest of the three phase currents. The balance factor %$/ )$&7 , 6 represets the degree of unbalance of the phase currents, the limiting value %$/ , /,0,7 6 is the lower threshold of the operating range of this monitoring function (see Figure 2-86). Both parameters can be set. The resetting ratio is approx. 97 %.
161
2 Functions
Imin IN
Slope:
76GA68UPSD
AhvyDihyhpr
76GDGDHDU
Figure 2-86 Current balance monitoring
Imax IN
Current balance monitoring is available separate for each side of the protected object. It has no meaning with single-phase busbar protection and does not operate in this case. Unsymmetrical condition is indicated for the corresponding side with the alarm )DLO ,V\P (FNo ) or )DLO ,V\P (FNo ). The common message )DLO , EDODQFH (FNo ) appears in both cases. Phase Sequence To detect swapped connections in the current input circuits, the direction of rotation of the phase currents for three-phase application is checked. Therefore the sequence of the zero crossings of the currents (having the same sign) is checked for each side of the protected object. For single-phase differential busbar protection and single-phase transformers this function would not be of any use and is thus disabled. Especially the unbalanced load protection requires clockwise rotation. If rotation in the protected object is reverse, this must be considered for the configuration of the Power System Data 1 (Subsection 2.1.2, margin heading Phase sequence). Phase rotation is checked by supervising the phase sequence of the currents. IL1 before IL2 before IL3 Supervision of current rotation requires a maximum current of |IL1|, |IL2|, |IL3| > 0.5 IN. If the rotation measured differs from the rotation set, the annunciation )DLO3K6HT , 6 (FNo ) or )DLO3K6HT , 6 (FNo ) is output. At the same time, the following annunciation appears: )DLO 3K 6HT , (FNo ).
2.13.1.4 Trip Circuit Supervision The differential protection relay 7UT612 is equipped with an integrated trip circuit supervision. Depending on the number of available binary inputs that are not connected to a common potential, supervision modes with one or two binary inputs can be selected. If the allocation of the necessary binary inputs does not comply with the selected monitoring mode, an alarm is given.
162
If two binary inputs are used, they are connected according to Figure 2-87, one in parallel to the assigned command relay contact of the protection and the other parallel to the circuit breaker auxiliary contact. A precondition for the use of the trip circuit supervision is that the control voltage for the circuit breaker is higher than the total of the minimum voltages drops at the two binary inputs (UCtrl > 2UBImin). As at least 19 V are needed at each binary input, supervision can be used with a control voltage higher than 38 V.
L+
7UT612
AI%'$! AI%'$"
TR
Legend: TR CB TC Aux.1 Aux.2 UCtrl UBI1 UBI2 Trip relay contact Circuit breaker Circuit breaker trip coil Circuit breaker auxiliary contact (make) Circuit breaker auxiliary contact (break)
UBI2
CB
TC
Aux.1
Aux.2
Control voltage (trip voltage) Input voltage of 1st binary input Input voltage of 2nd binary input
L
Figure 2-87
Depending on the state of the trip relay and the circuit breakers auxiliary contact, the binary inputs are triggered (logic state H in Table 2-6) or short-circuited (logic state L). A state in which both binary inputs are not activated (L) is only possible in intact trip circuits for a short transition period (trip relay contact closed but circuit breaker not yet open). This state is only permanent in the event of interruptions or short-circuits in the trip circuit or a battery voltage failure. Therefore, this state is the supervision criterion.
Table 2-6 No 1 2 3 4
Status table of the binary inputs depending on TR and CB Trip relay open open closed closed Circuit breaker CLOSED OPEN CLOSED OPEN Aux.1 closed open closed open Aux.2 open closed open closed BI 1 H H L L BI 2 L H L H
The states of the two binary inputs are interrogated periodically, approximately every 500 ms. Only after n = 3 of these consecutive state queries have detected a fault an
163
2 Functions
alarm is given (see Figure 2-88). These repeated measurements result in a delay of this alarm and thus avoid that an alarm is given during short-time transient periods. After the fault is removed in the trip circuit, the fault message is reset automatically after the same time delay.
AI%'$!
>TripC trip rel
AI%'$"
>TripC brk rel.
&
T approx. 1 to 2 s
Figure 2-88
Logic diagram of the trip circuit supervision with two binary inputs
The binary input is connected in parallel to the respective command relay contact of the protection device according to Figure 2-89. The circuit breaker auxiliary contact is bridged with the help of a high-ohmic substitute resistor R. The control voltage for the circuit breaker should be at least twice as high as the minimum voltage drop at the binary input (UCtrl > 2UBImin). Since at least 19 V are necessary for the binary input, this supervision can be used with a control voltage higher than 38 V. An calculation example for the substitute resistance of R is shown in Subsection 3.1.2, margin Trip Circuit Supervision.
L+
7UT612
AI%'$!
TR
Legend: TR CB TC Aux.1 Aux.2 R UCrtl UBI UR Trip relay contact Circuit breaker Circuit breaker trip coil Circuit breaker auxiliary contact (make) Circuit breaker auxiliary contact (break) Substitute resistor
R
UR
CB
TC
Aux.1
Aux.2
Control voltage (trip voltage) Input voltage of binary input Voltage across the substitute resistor
L
Figure 2-89
In normal operation the binary input is energized when the trip relay contact is open and the trip circuit is healthy (logic state H), as the monitoring circuit is closed via the auxiliary contact (if the circuit breaker is closed) or via the substitute resistor R. The binary input is short-circuited and thus deactivated only as long as the tripping relay is closed (logic state L). If the binary input is permanently deactivated during operation, an interruption in the trip circuit or a failure of the (trip) control voltage can be assumed.
164
As the trip circuit supervision is not operative during a system fault condition (pickedup status of the device), the closed trip contact does not lead to an alarm. If, however, the trip contacts of other devices are connected in parallel, the alarm must be delayed (see also Figure 2-90). After the fault in the trip circuit is removed, the alarm is reset automatically after the same time.
AI%'$!
>TripC trip rel Gen Fault Detection
T approx. 300 s
&
Figure 2-90
Logic diagram of the trip circuit supervision with one binary input
2.13.1.5 Fault Reactions Depending on the kind of fault detected, an alarm is given, the processor is restarted or the device is taken out of operation. If the fault is still present after three restart attempts the protection system will take itself out of service and indicate this condition by drop-off of the Device OK relay, thus indicating the device failure. The red LED Blocked on the device front lights up, provided that there is an internal auxiliary voltage, and the green LED RUN goes off. If the internal auxiliary voltage supply fails, all LEDs are dark. Table 2-7 shows a summary of the monitoring functions and the fault reactions of the device.
Table 2-7
Summary of the fault reactions of the device Possible causes External (aux. voltage) Internal (converter) Internal (converter or sampling) internal (offset) Fault reaction Device out of operation alarm, if possible Protection out of operation, alarm Protection out of operation, alarm Device out of operation Restart attempt 1) Restart attempt 1), Restart abort device out of operation Restart attempt 1) Restart attempt 1) Alarm All LEDs dark LED ERROR (UURU $'FRQY LED ERROR (UURU 2IIVHW LED ERROR LED ERROR LED flashes DOK Output
2)
drops off
DOK2) drops off DOK2) drops off DOK2) drops off DOK2) drops off DOK2) drops off
Hardware watchdog Internal (processor failure) Software watchdog Working memory Internal (program flow) Internal (RAM)
After three unsuccessful attempts the device is put out of operation DOK = Device OK relay
165
2 Functions
Table 2-7
Summary of the fault reactions of the device Possible causes 1/5/0.1 A jumper wrong Fault reaction Alarms Protection out of operation Alarm Using default values Alarm Alarm Alarms Protection out of operation Alarm No overload protection with RTD Alarm (UURU$$ZURQJ LED ERROR $ODUP 12 FDOLEU )DLO %DWWHU\ &ORFN 6\QF(UURU (UURU %RDUG ... and if applicable (UURU $'FRQY )DLO 57'%R[ or )DLO 57'%R[
2
Supervision 1 A/5 A/0.1 A setting Calibration data Backup battery Time clock Modules
Internal (device not calibrated) Internal (backup battery) Time synchronization Module does not comply with ordering number Thermobox not connected or number does not match External (system or current transformers) External (system or connections) External (trip circuit or control voltage)
as allocated
Alarm with identification )DLO ,V\P or of the side )DLO ,V\P , )DLO , EDODQFH Alarm with identification )DLO3K6HT , 6 or of the side )DLO3K6HT , 6, )DLO 3K 6HT , Alarm )$,/ 7ULS FLU
as allocated
Phase sequence
as allocated
as allocated
After three unsuccessful attempts the device is put out of operation DOK = Device OK relay
2.13.1.6 Group Alarms Certain messages of the monitoring functions are already combined to group alarms. Table 2-8 shows an overview of these group alarms an their composition.
Table 2-8
FNo 00161
FNo 00571 00572 00265 00266 00161 00068 00177 00193 00198 00199
Composed of Designation Fail. Isym 1 Fail. Isym 2 FailPh.Seq I S1 FailPh.Seq I S2 Fail I Superv. Clock SyncError Fail Battery Alarm NO calibr Err. Module B Err. Module C
00160
166
Table 2-8
FNo
Composed of Designation Error A/D-conv. Error Board 0 Error Board 1 Error1A/5Awrong Fail I Superv. Error Offset Fail: RTD-Box 1 Fail: RTD-Box 2
00140
2.13.1.7 Setting Errors If setting of the configuration and function parameters is carried out according to the order they appear in this chapter, conflicting settings may be avoided. Nevertheless, changes made in settings, during allocation of binary inputs and outputs or during assignment of measuring inputs may lead to inconsistencies endangering proper operation of protective and supplementary functions. The device 7UT612 checks settings for inconsistencies and reports them. For instance, the restricted earth fault protection cannot be applied if there is no measuring input for the starpoint current between the starpoint of the protected object and the earth electrode. These inconsistencies are output with the operational and spontaneous annunciations. Table 3-10 (Subsection 3.3.4, page 227) gives an overview.
167
2 Functions
Address %$/ , /,0,7 6 determines the threshold current for side 1 above which the current balance supervision is effective (also see Figure 2-86). Address %$/ )$&7 , 6 is the associated balance factor, i.e. the gradient of the balance characteristic (Figure 2-86). Trip Circuit Supervision When address 7ULS &LU 6XS was configured (Subsection 2.1.1), the number of binary inputs per trip circuit was set. If the trip circuit supervision function is not used at all, 'LVDEOHG is set there. If the routing of the binary inputs required for this does not comply with the selected supervision mode, an alarm is output (7ULS& 3URJ )DLO). The trip circuit supervision can be switched 21 or 2)) in address 75,3 &LU 683.
Setting Options
Comments Current Balance Supervision Phase Rotation Supervision Current Balance Monitor Side 1 Balance Factor for Current Monitor S1 Current Balance Monitor Side 2 Balance Factor for Current Monitor S2 Comments TRIP Circuit Supervision
PHASE ROTATION ON OFF BAL. I LIMIT S1 BAL. FACT. I S1 BAL. I LIMIT S2 BAL. FACT. I S2 0.10..1.00 A 0.10..0.90 0.10..1.00 A 0.10..0.90
Addr. 8201
Setting Options
168
F.No. SysIntErr. Error FMS1 Error FMS2 00110 Event Lost 00113 Flag Lost
Alarm Error Systeminterface Error FMS FO 1 Error FMS FO 2 Event lost Flag Lost Error with a summary alarm Error: A/D converter Error Board 0 Error Board 1
Comments
00140 Error Sum Alarm 00181 Error A/D-conv. 00190 Error Board 0 00183 Error Board 1 00192 Error1A/5Awrong 00191 Error Offset 00264 Fail: RTD-Box 1 00267 Fail: RTD-Box 2 00160 Alarm Sum Event 00193 Alarm NO calibr 00177 Fail Battery 00068 Clock SyncError 00198 Err. Module B 00199 Err. Module C
Error:1A/5Ajumper different from setting Error: Offset Failure: RTD-Box 1 Failure: RTD-Box 2 Alarm Summary Event Alarm: NO calibration data available Failure: Battery empty Clock Synchronization Error Error: Communication Module B Error: Communication Module C
169
2 Functions
F.No. 06851 >BLOCK TripC 06852 >TripC trip rel 06853 >TripC brk rel. 06861 TripC OFF
Alarm
Comments >BLOCK Trip circuit supervision >Trip circuit supervision: trip relay >Trip circuit supervision: breaker relay Trip circuit supervision OFF Trip circuit supervision is BLOCKED Trip circuit supervision is ACTIVE Trip Circuit blk. Bin. input is not set Failure Trip Circuit
06862 TripC BLOCKED 06863 TripC ACTIVE 06864 TripC ProgFail 06865 FAIL: Trip cir.
170
2.14
Note, that the overload protection does not have a pickup comparable to the other protective functions. The general device pickup time is started with the trip signal, which starts the trip log.
171
2 Functions
FNo 00511
Trip commands
(from protection functions)
S CB open & R
Relay TRIP
UHvUSDQ8H9 !'
&
Figure 2-91
Reclosure Interlocking
When tripping the circuit breaker by a protection function the manual reclosure must often be blocked until the cause for the protection function operation is found. Using the user-configurable logic functions (CFC) an automatic reclosure interlocking function can be created. The default setting of 7UT612 offers a pre-defined CFC logic which stores the trip command of the device until the command is acknowledged manually. The CFC-block is illustrated in Appendix A.5, margin heading Preset CFC Charts (page 306). The internal output *753 4XLW must be additionally assigned to the tripping output relays which are to be sealed. Acknowledgement is done via binary input !4XLW*753. With default configuration, press function key F4 at the device front to acknowledge the stored trip command. If the reclosure interlocking function is not required, delete the allocation between the internal single-point indication *753 4XLW and the source CFC in the configuration matrix.
172
No Trip no Flag
The storage of fault messages allocated to local LEDs and the availability of spontaneous displays can be made dependent on the device sending a trip command. Fault event information is then not output when one or more protection functions have picked up due to a fault but no tripping occurred because the fault was removed by another device (e.g. on a different feeder). The information is thus limited to faults on the protected line (so-called no trip no flag feature). Figure 2-92 shows the logic diagram of this function.
UhtrUSDQ
&
Figure 2-92
CB Operation Statistics
The number of trips caused by the device 7UT612 is counted. Furthermore, the current interrupted for each pole is acquired, provided as an information and accumulated in a memory. The levels of these counted values are buffered against auxiliary voltage failure. They can be set to zero or to any other initial value. For further information refer to the SIPROTEC 4 System Manual, order no. E50417H1176C151.
173
2 Functions
Addr. 7110
Setting Options
Default Setting
Comments
Display Targets on every Display Targets on Fault Display on LED / LCD Pickup every Pickup Display Targets on TRIP only
F.No. 00003 >Time Synch 00005 >Reset LED 00060 Reset LED 00015 >Test mode Test mode 00016 >DataStop DataStop UnlockDT >Light on 00051 Device OK 00052 ProtActive 00055 Reset Device 00056 Initial Start 00067 Resume
Alarm
Comments >Synchronize Internal Real Time Clock >Reset LED Reset LED >Test mode Test mode >Stop data transmission Stop data transmission Unlock data transmission via BI >Back Light on Device is Operational and Protecting At Least 1 Protection Funct. is Active Reset Device Initial Start of Device Resume Daylight Saving Time Clock Synchronization Setting calculation is running Settings Check Level-2 change Frequency out of range Chatter ON Hardware Test Mode
00069 DayLightSavTime SynchClock 00070 Settings Calc. 00071 Settings Check 00072 Level-2 change 00109 Frequ. o.o.r. 00125 Chatter ON HWTestMod
174
2.15
Ancillary Functions
The auxiliary functions of the 7UT612 relay include: processing of messages, processing of operational measured values, storage of fault record data.
175
2 Functions
Events and states can be obtained from the LCD on the front plate of the device. A personal computer can be connected to the front interface or the service interface for retrieval of information. In the quiescent state, i.e. as long as no system fault is present, the LCD can display selectable operational information (overview of the operational measured values). In the event of a system fault, information regarding the fault, the so-called spontaneous displays, are displayed instead. The quiescent state information is displayed again once the fault messages have been acknowledged. The acknowledgement is identical to the resetting of the LEDs (see above). The device in addition has several event buffers for operational messages, switching statistics, etc., which are saved against loss of auxiliary supply by means of a battery buffer. These messages can be displayed on the LCD at any time by selection via the keypad or transferred to a personal computer via the serial service or PC interface. The retrieval of events/alarms during operation is extensively described in the SIPROTEC 4 System Manual, order no. E50417H1176C151. With a PC and the protection data processing program DIGSI 4 it is also possible to retrieve and display the events with the convenience of visualisation on a monitor and a menu-guided dialogue. The data may be printed or stored for later evaluation.
If the device has a serial system interface, the information may additionally be transferred via this interface to a centralized control and monitoring system. Several communication protocols are available for the transfer of this information. You may test whether the information is transmitted correctly with DIGSI 4. Also the information transmitted to the control centre can be influenced during operation or tests. For on-site monitoring, the IEC protocol 608705103 offers the option to add a comment saying test mode to all annunciations and measured values transmitted to the control centre. It is then understood as the cause of annunciation and there is no doubt on the fact that messages do not derive from real disturbances. Alternatively, you may disable the transmission of annunciations to the system interface during tests (transmission block). To influence information at the system interface during test mode (test mode and transmission block) a CFC logic is required. Default settings already include this logic (see Appendix A.5, margin heading Preset CFCCharts, page 306). For information on how to enable and disable the test mode and the transmission block see for the SIPROTEC 4 System Manual E50417H1176C151.
Structure of Messages
The messages are categorized as follows: Event Log: these are operating messages that can occur during the operation of the device. They include information about the status of device functions, measurement data, system data, and similar information. Trip Log: these are fault messages from the last eight network faults that were processed by the device. Switching statistics; these messages count the trip commands initiated by the device, values of accumulated circuit currents and interrupted currents. A complete list of all message and output functions that can be generated by the device, with the associated information number (FNo), can be found in the Appendix. The lists also indicate where each message can be sent. The lists are based on a
176
2.15.1.2 Event Log (Operating Messages) Operating messages contain information that the device generates during operation and about the operation. Up to 200 operating messages are stored in chronological order in the device. New messages are added at the end of the list. If the memory has been exceeded, then the oldest message is overwritten for each new message. Operational annunciations come in automatically and can be read out from the device display or a personal computer. Faults in the power system are indicated with 1HW ZRUN )DXOW and the present fault number. The fault messages (Trip Log) contain details about the history of faults. This topic is discussed in Subsection 2.15.1.3.
2.15.1.3 Trip Log (Fault Messages) Following a system fault, it is possible to for example retrieve important information regarding its progress, such as pickup and trip. The start of the fault is time stamped with the absolute time of the internal system clock. The progress of the disturbance is output with a relative time referred to the instant of fault detection (first pickup of a protection function), so that the duration of the fault until tripping and up to reset of the trip command can be ascertained. The resolution of the time information is 1 ms. A system fault starts with the recognition of the fault by the fault detection, i.e. first pickup of any protection function, and ends with the reset of the fault detection, i.e. dropout of the last protection function, or after the expiry of the auto-reclose reclaim time, so that several unsuccessful auto-reclose cycles are also stored cohesively. Accordingly a system fault may contain several individual fault events (from fault detection up to reset of fault detection). Spontaneous Displays The spontaneous messages appear automatically in the display, after a general pickup of the device. The most important data about a fault can be viewed on the device front in the sequence shown in Figure 2-93.
Protection function that had picked up, e.g. differential protection, with phase information; Protection function that had tripped, e.g. differential protection; Elapsed time from pickup until dropoff; Elapsed time from pickup until the first trip command of a protection function.
177
2 Functions
Retrieved messages
The messages for the last eight network faults can be retrieved. Altogether up to 600 indications can be stored. Oldest data are erased for newest data when the buffer is full.
2.15.1.4 Spontaneous Annunciations Spontaneous annunciations contain information on new incoming annunciations. Each new incoming annunciation appears immediately, i.e. the user does no have to wait for an update or initiate one. This can be a useful help during operation, testing and commissioning. Spontaneous annunciations can be read out via DIGSI 4. For further information see the SIPROTEC 4 System Manual (order-no. E50417H1176C151).
2.15.1.5 General Interrogation The present condition of a SIPROTEC device can be examined by using DIGSI 4 to view the contents of the General Interrogation annunciation. All of the messages that are needed for a general interrogation are shown along with the actual values or states.
2.15.1.6 Switching Statistics The messages in switching statistics are counters for the accumulation of interrupted currents by each of the breaker poles, the number of trips issued by the device to the breakers. The interrupted currents are in primary terms. Switching statistics can be viewed on the LCD of the device, or on a PC running DIGSI 4 and connected to the operating or service interface. The counters and memories of the statistics are saved by the device. Therefore the information will not get lost in case the auxiliary voltage supply fails. The counters, however, can be reset back to zero or to any value within the setting range. A password is not required to read switching statistics; however, a password is required to change or delete the statistics. For further information see the SIPROTEC 4 System Manual (order-no. E50417H1176C151).
178
179
2 Functions
Table 2-9
Operational measured values (magnitudes primary, secondary, percent) Measured values primary A; kA A; kA A; kA A; kA A; kA A; kA A; kA A; kA A V; kV; MV kVA; MVA; GVA Hz secondary A A A A A A A A mA Hz % referred to Operating nominal current 1) Operating nominal current 1) Operating nominal current 1) Operating nominal current 1) Operating nominal current 1) Operating nominal current 1) Operating nominal current 1) Operating nominal current 1) Operating nominal current 1) 2) Rated frequency
3
IL1S1, IL2S1, IL3S1 ) Phase currents of side 1 3I0S1 3) I1S1, I2S1 3) Residual current of side 1 Positive and negative sequence component currents of side 1
IL1S2, IL2S2, IL3S2 3) Phase currents of side 2 3I0S2 3) I1S2, I2S2 3) I7 3) I1 ... I7 4) I8 Umeas 5) S f
1
Residual current of side 2 Positive and negative sequence component currents of side 2 Current at current input I7 Currents at the current inputs Current at current input I8 Voltage from current at I7 or I8 Apparent power Frequency
6)
) for transformers acc. to addresses !#, !#", and !#( (see Subsection 2.1.2) IN = SN /(3UN) or IN = SN / UN (1-phase) for generators/motors/reactors acc. to addresses !$ and !$! (see Subsection 2.1.2) IN = SN /(3UN); for busbars and lines acc. to address !%$ (see Subsection 2.1.2) 2 ) with consideration of the factor address !"$AhpD' (see Subsection 2.1.2)
3 4
) only for three-phase objects ) only for single-phase busbar protection if configured and prepared in CFC calculated from phase currents and nominal voltage or measured voltage Umeas
5) 6)
Table 2-10
Operational measured values (phase relationship) Measured values Dimension %Conversion 5) 0 = 0 % 360 = 100 % 0 = 0 % 360 = 100 % 0 = 0 % 360 = 100 % 0 = 0 % 360 = 100 %
5)
3)
Phase angle of the currents of side 1, towards IL1S1 Phase angle of the currents of side 2, towards IL1S1 Phase angle of the currents at the current inputs, towards I1 Phase angle of the current at the current input I7, towards I1
180
Table 2-11
Thermal values Measured values Dimension %Conversion 5) % % p.u. % % C or F C or F 0 C = 0 % 500 C = 100 % 0 F = 0 % 1000 F = 100 %
5
) only for overload protection with thermal replica (IEC 602558): address #" UurPG8CS = FODVVLFDO (Subsection 2.1.1) 2 ) only for overload protection with hot-spot calculation (IEC 60354): address #" UurPG8CS = ,(& (Subsection 2.1.1) 3) only if thermobox(es) available (Section 2.10)
The differential and restraining values of the differential protection and the restricted earth fault protection are listed in Table 2-12.
Table 2-12
Values of the differential protection Measured values % referred to Operating nominal current 1) Operating nominal current 1) Operating nominal current 1) Operating nominal current 1)
Calculated differential currents of the three phases Calculated restraining currents of the three phases Calculated differential current of the restricted earth fault protection Calculated restraining current of the restricted earth fault protection
) for transformers acc. to addresses !#, !#", and !#((see Subsection 2.1.2) IN = SN /(3UN) or IN = SN / UN (1-phase); for generators/motors/reactors acc. to addresses !$ and !$! (see Subsection 2.1.2) IN = SN /(3UN); for busbars and lines acc. to address !%$ (see Subsection 2.1.2)
The IBS-Tool
The commissioning help IBS-tool offers a wide range of commissioning and monitoring functions that allows a detailed illustration of the most important measured values via a personal computer equipped with a web-browser. For more details refer to the Online Help for the IBS-tool. The Online Help can be downloaded from the INTERNET.
181
2 Functions
This tool allows to illustrate the measured values of all ends of the protected object during commissioning and during operation. The currents appear as vector diagrams and are indicated as numerical values. Figure 2-94 shows an example. Additionally the position of the differential and restraint values can be viewed in the pickup characteristic.
Secondary Values
Currents: Side 1 +90 Currents: Side 2 +90
180
0 180
90
90
Figure 2-94
Measured values of the sides of the protected object example for through-flowing currents
In SIPROTEC 7UT612, set-points can be configured for measured and metered values. If, during operation, a value reaches one of these set-points, the device generates an alarm which is indicated as an operational message. As for all operational messages, it is possible to output the information to LED and/or output relay and via the serial interfaces. The set-points are supervised by the processor system in the background, so they are not suitable for protection purposes. Set-points can only be set if their measured and metered values have been configured correspondingly in CFC (see SIPROTEC 4 System Manual, ordering number E50417H1176C151).
182
183
2 Functions
address 32:(5 &$/&8/ to = ZLWK 9 PHDVXU, for the latter case ZLWK 9 VHWWLQJ. Waveform Capture The settings pertaining to waveform capture are found under the 26&)$8/7 5(& sub-menu of the 6(77,1*6 menu. Distinction is made between the starting instant (i.e. the instant where time tagging is T = 0) and the criterion to save the record (address :$9()25075,**(5). With the setting 6DYH Z 3LFNXS, the starting instant and the criterion for saving are the same: the pickup of any protective element. The option 6DYH Z 75,3 means that also the pickup of a protective function starts fault recording but the record is saved only if the device issues a trip command. The final option for address is 6WDUW Z 75,3: A trip command issued by the device is both the starting instant and the criterion to save the record. An oscillographic record includes data recorded prior to the time of trigger, and data after the dropout of the recording criterion. You determine the length of pre-trigger time and post-dropout time to be included in the fault record with the settings in Address 35( 75,* 7,0( and address 3267 5(& 7,0( The maximum length of time of a record is entered in address 0$; /(1*7+. The largest value here is 5 seconds. A total of 8 records can be saved. However the total length of time of all fault records in the buffer may not exceed 5 seconds. Once the capacity of the buffer is exceeded the oldest fault is deleted, whereas the new fault is saved in the buffer. An oscillographic record can be triggered and saved via a binary input or via the operating interface connected to a PC. The trigger is dynamic. The length of a record for these special triggers is set in address %LQ,Q &$377,0( (upper bound is address ). Pre-trigger and post-dropout settings in Addresses and are included. If address is set for , then the length of the record equals the time that the binary input is activated (static), or the 0$; /(1*7+ setting in address , whichever is shorter.
Fault Recording
Addr. 401 Setting Title WAVEFORMTRIGGER MAX. LENGTH Setting Options Save with Pickup Save with TRIP Start with TRIP 0.30..5.00 sec Default Setting Save with Pickup Comments Waveform Capture
403
1.00 sec
184
Setting Title PRE. TRIG. TIME POST REC. TIME BinIn CAPT.TIME
Comments Captured Waveform Prior to Trigger Captured Waveform after Event Capture Time via Binary Input
00409 >BLOCK Op Count 01020 Op.Hours= 01000 # TRIPs= 30607 IL1S1: 30608 IL2S1: 30609 IL3S1: 30610 IL1S2: 30611 IL2S2: 30612 IL3S2: 30620 I1: 30621 I2: 30622 I3: 30623 I4: 30624 I5: 30625 I6: 30626 I7:
Measured Values
F.No. 00721 IL1S1= 00722 IL2S1= 00723 IL3S1= 30640 3I0S1= 30641 I1S1= Alarm Comments Operat. meas. current IL1 side 1 Operat. meas. current IL2 side 1 Operat. meas. current IL3 side 1 3I0 (zero sequence) of side 1 I1 (positive sequence) of side 1
185
2 Functions
F.No. 30642 I2S1= 00724 IL1S2= 00725 IL2S2= 00726 IL3S2= 30643 3I0S2= 30644 I1S2= 30645 I2S2= 30646 I1= 30647 I2= 30648 I3= 30649 I4= 30650 I5= 30651 I6= 30652 I7= 30653 I8= 07740 IL1S1= 07741 IL2S1= 07749 IL3S1= 07750 IL1S2= 07759 IL2S2= 07760 IL3S2= 30633 I1= 30634 I2= 30635 I3= 30636 I4= 30637 I5= 30638 I6= 30639 I7= 30656 Umeas.= 00645 S = 00644 Freq=
Alarm
Comments I2 (negative sequence) of side 1 Operat. meas. current IL1 side 2 Operat. meas. current IL2 side 2 Operat. meas. current IL3 side 2 3I0 (zero sequence) of side 2 I1 (positive sequence) of side 2 I2 (negative sequence) of side 2 Operat. meas. current I1 Operat. meas. current I2 Operat. meas. current I3 Operat. meas. current I4 Operat. meas. current I5 Operat. meas. current I6 Operat. meas. current I7 Operat. meas. current I8 Phase angle in phase IL1 side 1 Phase angle in phase IL2 side 1 Phase angle in phase IL3 side 1 Phase angle in phase IL1 side 2 Phase angle in phase IL2 side 2 Phase angle in phase IL3 side 2 Phase angle of current I1 Phase angle of current I2 Phase angle of current I3 Phase angle of current I4 Phase angle of current I5 Phase angle of current I6 Phase angle of current I7 Operat. meas. voltage Umeas. S (apparent power) Frequency
186
Thermal Values
F.No. 00801 /trip = 00802 /tripL1= 00803 /tripL2= 00804 /tripL3= 01060 leg 1= 01061 leg 2= 01062 leg 3= 01063 Ag.Rate= 01066 ResWARN= 01067 ResALARM= 01068 RTD 1 = 01069 RTD 2 = 01070 RTD 3 = 01071 RTD 4 = 01072 RTD 5 = 01073 RTD 6 = 01074 RTD 7 = 01075 RTD 8 = 01076 RTD 9 = 01077 RTD10 = 01078 RTD11 = 01079 RTD12 = Alarm Comments Temperat. rise for warning and trip Temperature rise for phase L1 Temperature rise for phase L2 Temperature rise for phase L3 Hot spot temperature of leg 1 Hot spot temperature of leg 2 Hot spot temperature of leg 3 Aging Rate Load Reserve to warning level Load Reserve to alarm level Temperature of RTD 1 Temperature of RTD 2 Temperature of RTD 3 Temperature of RTD 4 Temperature of RTD 5 Temperature of RTD 6 Temperature of RTD 7 Temperature of RTD 8 Temperature of RTD 9 Temperature of RTD10 Temperature of RTD11 Temperature of RTD12
Diff-Values
F.No. 07742 IDiffL1= 07743 IDiffL2= 07744 IDiffL3= 07745 IRestL1= 07746 IRestL2= 07747 IRestL3= 30654 IdiffREF= 30655 IrestREF= Alarm Comments IDiffL1(I/Inominal object [%]) IDiffL2(I/Inominal object [%]) IDiffL3(I/Inominal object [%]) IRestL1(I/Inominal object [%]) IRestL2(I/Inominal object [%]) IRestL3(I/Inominal object [%]) Idiff REF (I/Inominal object [%]) Irest REF (I/Inominal object [%])
187
2 Functions
Set-Points
F.No. 00272 SP. Op Hours> Alarm Set Point Operating Hours Comments
Fault Recording
F.No. Alarm >Trigger Waveform Capture Waveform data deleted Fault Recording Start Comments
Puls metering
F.No. 00888 Wp(puls) 00889 Wq(puls)
if configured (CFC)
Alarm Pulsed Energy Wp (active) Pulsed Energy Wq (reactive) Comments
188
2.16
General
Processing of Commands
In addition to the protective functions described so far, control command processing is integrated in the SIPROTEC 7UT612 to coordinate the operation of circuit breakers and other equipment in the power system. Control commands can originate from four command sources: Local operation using the keypad on the local user interface of the device, Local or remote operation using DIGSI 4, Remote operation via system (SCADA) interface (e.g. SICAM), Automatic functions (e.g. using a binary inputs, CFC). The number of switchgear devices that can be controlled is basically limited by the number of available and required binary inputs and outputs. For the output of control commands it has be ensured that all the required binary inputs and outputs are configured and provided with the correct properties. If specific interlocking conditions are needed for the execution of commands, the user can program the device with bay interlocking by means of the user-defined logic functions (CFC). The configuration of the binary inputs and outputs, the preparation of user defined logic functions, and the procedure during switching operations are described in the SIPROTEC 4 System Manual, order no. E50417H1176C151.
189
2 Functions
Acknowledgment and resetting commands for setting and resetting internal buffers. Status information commands for setting / deactivating the information status for the information value of an object: Controlling activation of binary input status, Blocking binary outputs.
190
2.16.3 Interlocking
Interlocking is executed by the user-defined logic (CFC). The interlocking checks of a SICAM/SIPROTEC-system are classified into: System interlocking checked by a central control system (for interbay interlocking) Zone controlled/bay interlocking checked in the bay device (for the feeder-related intelocking) System interlocking relies on the system data base in the central control system. Zone controlled/bay interlocking relies on the status of the circuit breaker and other switches that are connected to the relay. The extent of the interlocking checks is determined by the configuration and interlocking logic of the relay. Switchgear which is subject to system interlocking in the central control system is identified with a specific setting in the command properties (in the routing matrix). For all commands the user can select the operation mode with interlocking (normal mode) or without interlocking (test mode): for local commands by reprogramming the settings with password check, for automatic commands via command processing with CFC, for local / remote commands by an additional interlocking command via Profibus.
2.16.3.1 Interlocked/Non-Interlocked Switching The command checks that can be selected for the SIPROTEC-relays are also referred to as standard interlocking. These checks can be activated (interlocked) or deactivated (non interlocked) via DIGSI 4. Deactivated interlock switching means the configured interlocking conditions are bypassed in the relay. Interlocked switching means that all configured interlocking conditions are checked in the command check routines. If a condition could not be fulfilled, the command will be rejected by a message with a minus added to it (e.g. CO-), followed by an operation response information. Table 2-13 shows some types of commands and messages. For
191
2 Functions
the device the messages designated with *) are displayed in the event logs, for DIGSI 4 they appear in spontaneous messages.
Table 2-13
Control issued Manual tagging (positive / negative) Input blocking Output blocking Control abortion
The plus sign indicated in the message is a confirmation of the command execution: the command execution was as expected, in other words positive. The minus is a negative confirmation, the command was rejected. Figure 2-95 shows the messages relating to command execution and operation response information for a successful operation of the circuit breaker. The check of interlocking can be programmed separately for all switching devices and tags that were set with a tagging command. Other internal commands such as manual entry or abort are not checked, i.e. carried out independent of the interlocking.
(9(17 /2* 4 &2 FORVH 4 )% FORVH
Figure 2-95 Example of a message when closing the circuit breaker Q0
Standard Interlocking
The standard interlocking includes the checks for each device which were set during the configuration of inputs and outputs. An overview for processing the interlocking conditions in the relay is shown by Figure 2-96.
192
Device with Source of Command = LOCAL SAS REMOTE ), DIGSI AUTO Switching Authority (Local/Remote)
1
Switching Mode
&
Local
Local
&
&
Remote
&
&
Switching Authority DIGSI DIGSI
DIGSI
or
&
Remote
Non-Interlocked
&
Switching Mode Remote
or
SCHEDULED=ACT .y/n
Interlocked
&
or
SCHEDULED=ACT.y/n System Interlock. y/n Field Interlocking y/n Protection Blockingy/n Double Oper. Blocky/n SW. Auth. LOCA> y/n Sw. Auth. REMOTEy/n
or
Event Condition
1)
LOCAL
Figure 2-96
REMOTE Command via telecontrol system to substation controller and from substation controller to device.
The display shows the configured interlocking reasons. The are marked by letters explained in the following Table 2-14.
Table 2-14
Control authorization System interlock Zone controlled Target state = present state (check switch position) Block by protection
193
2 Functions
Figure 2-97 shows all interlocking conditions (which usually appear in the display of the device) for three switchgear items with the relevant abbreviations explained in Table 2-14. All parameterized interlocking conditions are indicated (see Figure 2-97).
For zone controlled/field interlocking, control logic can be programmed, using the CFC. Via specific release conditions the information released or bay interlocked are available.
194
Commands and information feedback are also recorded in the event list. Normally the execution of a command is terminated as soon as the feedback information (FB+) of the relevant switchgear arrives or, in case of commands without process feedback information, the command output resets. The plus appearing in a feedback information confirms that the command was successful, the command was as expected, in other words positive. The minus is a negative confirmation and means that the command was not executed as expected. Command Output and Switching Relays The command types needed for tripping and closing of the switchgear or for raising and lowering of transformer taps are described in the SIPROTEC 4 System Manual, order no. E50417H1176C151.
Comments
195
2 Functions
196
This chapter is primarily for personnel who are experienced in installing, testing, and commissioning protective and control systems, and are familiar with applicable safety rules, safety regulations, and the operation of the power system. Installation of the 7UT612 is described in this chapter. Hardware modifications that might be needed in certain cases are explained. Connection verifications required before the device is put in service are also given. Commissioning tests are provided. Some of the tests require the protected object (line, transformer, etc.) to carry load.
Mounting and Connections Checking the Connections Commissioning Final Preparation of the Device
197
3.1
Warning!
The successful and safe operation of the device is dependent on proper handling, installation, and application by qualified personnel under observance of all warnings and hints contained in this manual. In particular the general erection and safety regulations (e.g. IEC, ANSI, DIN, VDE, EN or other national and international standards) regarding the correct use of hoisting gear must be observed. Non-observance can result in death, personal injury, or substantial property damage.
Preconditions
Verification of the ratings of the 7UT612 as well as matching to ratings of the power equipment must have been completed.
3.1.1
Installation
q Remove the 4 covering caps located on the corners of the front cover, reveal the
4 slots in the mounting flange.
q Insert the device into the panel cut-out and fasten with four screws. Refer to Figure
4-13 in Section 4.15 for dimensions.
q Replace the four covers. q Connect the ground on the rear plate of the device to the protective ground of the
panel. Use at least one M4 screw for the device ground. The cross-sectional area of the ground wire must be greater than or equal to the cross-sectional area of any other control conductor connected to the device. Furthermore, the cross-section of the ground wire must be at least 2.5 mm2. vice according to the wiring diagram for the panel. When using forked lugs or directly connecting wires to screwed terminals, the screws must be tightened so that the heads are even with the terminal block before the lugs or wires are inserted. A ring lug must be centred in the connection chamber so that the screw thread fits in the hole of the lug. The System Manual (orderno. E50417H1176C151) has pertinent information regarding wire size, lugs, bending radii, etc. Installation notes are also given in the brief reference booklet attached to the device.
q Connect the plug terminals and/or the screwed terminals on the rear side of the de-
198
Elongated holes
SIEMENS
RUN
SIPROTEC
ERROR
7UT612
MENU
LED
ESC
ENTER
F1 F2 F3 F4
7 4 1
8 5 2 0
9 6 3 +/-
Figure 3-1
To install the device in a frame or cubicle, two mounting brackets are required. The ordering codes are stated in the Appendix A in Subsection A.1.1.
q Loosely screw the two mounting brackets in the rack with four screws. q Remove the 4 covers at the corners of the front cover. The 4 slots in the mounting
flange are revealed and can be accessed.
q Fasten the device to the mounting brackets with four screws. q Replace the four covers. q Tighten the mounting brackets to the rack using eight screws. q Connect the ground on the rear plate of the device to the protective ground of the
rack. Use at least one M4 screw for the device ground. The cross-sectional area of the ground wire must be greater than or equal to the cross-sectional area of any other control conductor connected to the device. Furthermore, the cross-section of the ground wire must be at least 2.5 mm2. vice according to the wiring diagram for the rack. When using forked lugs or directly connecting wires to screwed terminals, the screws must be tightened so that the heads are even with the terminal block before the lugs or wires are inserted. A ring lug must be centred in the connection chamber so that the screw thread fits in the hole of the lug. The System Manual (orderno. E50417H1176C151) has pertinent information regarding wire size, lugs, bending radii, etc. Installation notes are also given in the brief reference booklet attached to the device.
q Connect the plug terminals and/or the screwed terminals on the rear side of the de-
199
Mounting bracket
SIEMENS
RUN
SIPROTEC
ERROR
7UT612
MENU
LED
ESC
ENTER
F1 F2 F3 F4
7 4 1
8 5 2 0
9 6 3 +/-
Mounting bracket
Figure 3-2
q Secure the device to the panel with four screws. Refer to Figure 4-14 in Section
4.15 for dimensions.
q Connect the ground of the device to the protective ground of the panel. The crosssectional area of the ground wire must be greater than or equal to the cross-sectional area of any other control conductor connected to the device. Furthermore, the cross-section of the ground wire must be at least 2.5 mm2. be connected to the grounding surface on the side. Use at least one M4 screw for the device ground.
q Solid, low-impedance operational grounding (cross-sectional area 2.5 mm2) must q Connect the screwed terminals on the top and bottom of the device according to the
wiring diagram for the panel. Optical connections are made on the inclined housings on the top and/or bottom of the case. The System Manual (orderno. E50417 H1176C151) has pertinent information regarding wire size, lugs, bending radii, etc. Installation notes are also given in the brief reference booklet attached to the device.
200
3.1.2
Termination Variants
General diagrams are shown in Appendix A.2. Connection examples for current transformer circuits are provided in Appendix A.3. It must be checked that the settings for configuration (Subsection 2.1.1) and the power system data (Subsection 2.1.2) match the connections to the device.
Protected Object
The setting 3527 2%-(&7 (address ) must correspond to the object to be protected. Wrong setting may cause unexpected reaction of the device. Please note that auto-transformers are identified as 3527 2%-(&7 = $XWRWUDQVI, not SKDVH WUDQVI. For SKDVH WUDQVI, the centre phase L2 remains unconnected.
Currents
Connection of the CT currents depends on the mode of application. With three-phase connection the three phase currents are allocated to each side of the protected object. For connection examples see Appendix A.3, Figures A-3 to A-6 and A-9 to A-13 referring to the protected object types. With two-phase connection of a single-phase transformer the centre phase will not be used (IL2). Figure A-7 in Appendix A.3 shows a connection diagram. Even if there is only one current transformer, both phases will be used (IL1 and IL3), see the right part of Figure A-8. For single-phase busbar protection every measuring input (except I8) is allocated to a busbar feeder. Figure A-14 in Appendix A.3 illustrates an example for one phase. The other phases are to be connected correspondingly. If the device is connected via summation transformers, see Figure A-15. With the latter case you have to take into consideration that the rated output current of the summation transformers is usually 100 mA. The measuring inputs of the device have to be matched accordingly (refer also to Subsection 3.1.3). The allocation of the current inputs I7 and I8 is to be checked. Connections also differ according to the application the device is used for. The Appendix offers some connection examples (e.g. Figures A-4 to A-7 and A-11 to A-15) which refer to different applications. Also check the rated data and the matching factors for the current transformers. The allocation of the protection functions to the sides must be consistent. This particularly goes for the circuit breaker failure protection whose measuring point (side) must correspond with the side of the circuit breaker to be monitored.
The connections to the power plant depend on the possible allocation of the binary inputs and outputs, i.e. how they are assigned to the power equipment. The preset allocation can be found in Tables A-2 and A-3 in Section A.5 of Appendix A. Also check that the labels on the front panel correspond to the configured message functions. It is also very important that the feedback components (auxiliary contacts) of the circuit breaker monitored are connected to the correct binary inputs which correspond to the assigned side of the circuit breaker failure protection.
201
If binary inputs are used to switch setting groups, note: Two binary inputs must be dedicated to the purpose of changing setting groups when four groups are to be switched. One binary input must be set for !6HW *URXS %LW , the other input for !6HW *URXS %LW . If either of these input functions is not assigned, then it is considered as not controlled. To control two setting groups, one binary input set for !6HW *URXS %LW is sufficient since the binary input !6HW *URXS %LW , which is not assigned, is considered to be not controlled. The status of the signals controlling the binary inputs to activate a particular setting group must remain constant as long as that particular group is to remain active. Table 3-1 shows the relationship between !6HW *URXS %LW , !6HW *URXS %LW , and the setting groups A to D. Principal connection diagrams for the two binary inputs are illustrated in Figure 3-3. The figure illustrates an example in which both Set Group Bits 0 and 1 are configured to be controlled (actuated) when the associated binary input is energized (high).
Table 3-1
Binary Input Events !6HW *URXS %LW !6HW *URXS %LW no yes no yes
no = not energized yes= energized
no no yes yes
L+
L+
A B C D
7UT612
L
Binary input set for: ' 3TrB7v , High
Figure 3-3
Connection diagram (example) for setting group switching with binary inputs
202
It must be noted that two binary inputs or one binary input and one bypass resistor R must be connected in series. The pick-up threshold of the binary inputs must therefore be substantially below half the rated control DC voltage. If two binary inputs are used for the trip circuit supervision, these binary inputs must be volt-free i.o.w. not be commoned with each other or with another binary input. If one binary input is used, a bypass resistor R must be employed (refer to Figure 34). This resistor R is connected in series with the second circuit breaker auxiliary contact (Aux2). The value of this resistor must be such that in the circuit breaker open condition (therefore Aux1 is open and Aux2 is closed) the circuit breaker trip coil (TC) is no longer picked up and binary input (BI1) is still picked up if the command relay contact is open.
L+
7UT612
>TripC trip rel
RTC
Legend:
R CB
TC Aux1 Aux2
RTC CB TC Aux1
Relay Tripping Contact Circuit Breaker Circuit breaker Trip Coil Circuit breaker Auxiliary contact (closed when CB is closed) Aux2 Circuit breaker Auxiliary contact (closed when CB is open) R Bypass Resistor UCTR Control voltage (trip voltage) UBI Input voltage for Binary Input
L
Figure 3-4
This results in an upper limit for the resistance dimension, Rmax, and a lower limit Rmin, from which the optimal value of the arithmetic mean should be selected. R max + R min R = --------------------------------2 In order that the minimum voltage for controlling the binary input is ensured, Rmax is derived as: U CRT U BI min R max = ------------------------------------- R CBTC I BI (High) So the circuit breaker trip coil does not remain energized in the above case, R min is derived as: U CTR U TC (LOW) R min = R TC ---------------------------------------------- U TC (LOW)
203
Constant current with BI on (=1.7 mA) Minimum control voltage for BI =19 V for delivery setting for nominal voltage of 24/48/60 V = 73 V for delivery setting for nominal voltage of 110/125/220/250 V Control voltage for trip circuit DC resistance of circuit breaker trip coil Maximum voltage on the circuit breaker trip coil that does not lead to tripping
If the calculation results that Rmax < Rmin, then the calculation must be repeated, with the next lowest switching threshold UBI min, and this threshold must be implemented in the relay using plug-in bridges (see Subsection 3.1.3). For the power consumption of the resistor: 2 U CTR 2 P R = I R = --------------------------- R R + R CBTC
Example:
IBI (HIGH) UBI min UCTR RCBTC 1.7 mA (from SIPROTEC 7UT612) 19 V for delivery setting for nominal voltage 24/48/60 V 73 V for delivery setting for nominal voltage 110/125/220/250 V 110 V from trip circuit (control voltage) 500 from trip circuit (resistance of CB trip coil)
UCBTC (LOW) 2 V from trip circuit (max. voltage not to trip breaker)
110 V 19 V R max = --------------------------------- 500 1.7 mA Rmax = 53 k 110 V 2 V R min = 500 ----------------------------- 500 2V Rmin = 27 k R max + R min R = ------------------------------- = 40 k 2 The closed standard value of 39 k is selected; the power is:
2 110 V P R = --------------------------------------- 39 k 39 k + 0.5 k
P R 0.3 W Thermoboxes If the overload protection operates with processing of the coolant temperature (overload protection with hot-spot calculation), one or two thermoboxes 7XV5662 can be connected to the serial service interface at port C.
204
3.1.3
3.1.3.1
Hardware Modifications
General Hardware modifications might be necessary or desired. For example, a change of the pickup threshold for some of the binary inputs might be advantageous in certain applications. Terminating resistors might be required for the communication bus. In either case, hardware modifications are needed. If modifications are done or interface modules are replaced, please observe the details in Subsections 3.1.3.2 to 3.1.3.5.
There are different input ranges for the power supply voltage. Refer to the data for the 7UT612 ordering numbers in Section A.1 of Appendix A. The power supplies with the ratings 60/110/125 VDC and 110/125/220/250 VDC / 115/230 VAC are interconvertible. Jumper settings determine the rating. The assignment of these jumpers to the supply voltages are illustrated below in Section 3.1.3.3 under margin Processor Board ACPU. When the relay is delivered, these jumpers are set according to the name-plate sticker. Generally, they need not be altered. Jumper settings determine the rating of the current input transducers of the device. When the relay is delivered, these jumpers are set according to the name-plate sticker to 1 A or 5 A, for the current inputs I1 to I7; the input I8 is independent of the rated current. If the current transformer sets have different rated secondary currents at the sides of the protected object and/or of current input I7, the device must be adapted to it. The same applies for the current transformers of the busbar feeders when single-phase busbar protection is applied. Using single-phase busbar protection with summation transformers interconnected, rated currents for current inputs I1 to I7 are usually 100 mA. The physical arrangements of these jumpers that correspond to the different current ratings are described below in Subsection 3.1.3.3 under margin Input/Output Board AI/O3. When performing changes, please make sure that the device is always informed about them: Using three-phase applications and single-phase transformers, changes for side 1 are to be set in address ,16(& &7 6 and changes for side 2 in address ,16(& &7 6 in the Power System Data (refer to Subsection 2.1.2, margin heading Current Transformer Data for 2 Sides, page 23). Using three-phase applications and single-phase transformers, changes for current input I7 are to be performed in address ,16(& &7 , (refer to Subsection 2.1.2, margin heading Current Transformer Data for Current Input I7, page 26). Using single-phase busbar protection, changes are made in addresses ,1 6(& &7 , to ,16(& &7 , (refer to Subsection 2.1.2, margin heading Current Transformer Data for Single-phase Busbar Protection, page 25). The current measuring input I8 disregarding the rated current of the device is suited for highly sensitive current measurement (approx. 3 mA to 1.6 A).
Nominal Currents
205
When the device is delivered from the factory, the binary inputs are set to operate with a voltage that corresponds to the rated voltage of the power supply. In general, to optimize the operation of the inputs, the pickup voltage of the inputs should be set to most closely match the actual control voltage being used. Each binary input has a pickup voltage that can be independently adjusted; therefore, each input can be set according to the function performed. A jumper position is changed to adjust the pickup voltage of a binary input. The physical arrangement of the binary input jumpers in relation to the pickup voltages is explained below in Section 3.1.3.3, margin heading Processor Board ACPU.
Note:
If the 7UT612 performs trip circuit monitoring, two binary inputs, or one binary input and a resistor, are connected in series. The pickup voltage of these inputs must be less than half of the nominal DC voltage of the trip circuit.
The processor module ACPU contains 2 output relays the contact of which can be set as normally closed or normally open contact. Therefore it might be necessary to rearrange a jumper. Subsection 3.1.3.3, margin heading margin Processor Board A CPU describes to which type of relays in which boards this applies. The serial interface modules can be replaced. Which kind of interfaces and how the interfaces can be replaced is described in Replacing Interface Modules, Section 3.1.3.4. If the device is equipped with a serial RS 485 port, the RS 485 bus must be terminated with resistors at the last device on the bus to ensure reliable data transmission. For this purpose, terminating resistors are provided on the interface modules. The physical arrangement and jumper positions on the interface modules see Subsection 3.1.3.4, margin heading RS485 Interface. Spare parts may be the backup battery that maintains the data in the battery-buffered RAM when the voltage supply fails, and the miniature fuse of the internal power supply. Their physical location is shown in Figure 3-6. The ratings of the fuse are printed on the module next to the fuse itself. When exchanging the fuse, please observe the hints given in the System Manual (order no. E50417H1176C151) in Chapter Maintenance.
Interface Modules
Spare Parts
206
3.1.3.2
WARNING!
For the following steps it is assumed that the device is not in operating state. Since dangerous voltages and laser radiation may develop, do not connect the device to auxiliary voltage, measured values or optical fibres! If changes to jumper settings are required to modify the rating of the power supply, the nominal rating of the current inputs, the pickup voltage of binary inputs, or the state of the terminating resistors, proceed as follows:
Caution!
Jumper-setting changes that affect nominal values of the device render the ordering number and the corresponding nominal values on the name-plate sticker invalid. If such changes are necessary, the changes should be clearly and fully noted on the device. Self adhesive stickers are available that can be used as replacement nameplates.
Prepare area of work. Provide a grounded mat for protecting components subject to damage from electrostatic discharges (ESD). The following equipment is needed: screwdriver with a 5 to 6 mm wide tip, 1 Philips screwdriver size Pz1, 4.5 mm socket or nut driver.
o o o o
Unfasten the screw-posts of the D-subminiature connector on the back panel at location A. This activity does not apply if the device is for surface mounting. If the device has more communication interfaces on the rear, the screws located diagonally to the interfaces must be removed. This activity is not necessary if the device is for surface mounting. Remove the four caps on the front cover and loosen the screws that become accessible. Carefully pull off the front cover. The front cover is connected to the CPU board with a short ribbon-cable. Refer to Figure 3-5 for the physical arrangement of the printed boards.
Caution!
Electrostatic discharges through the connections of the components, wiring, plugs, and jumpers must be avoided. Wearing a grounded wrist strap is preferred. Otherwise, first touch a grounded metal part.
207
o o o o
Disconnect the ribbon-cable between the front cover and the ACPU board () at the cover end. To disconnect the cable, push up the top latch of the plug connector and push down the bottom latch of the plug connector. Carefully set aside the front cover. Disconnect the ribbon-cables between the ACPU board () and the AI/O3 board (). Remove the boards and set them on the grounded mat to protect them from electrostatic damage. A greater effort is required to withdraw the ACPU board, especially in versions of the device for surface mounting, because of the plug connectors. Check the jumpers according to Figures 3-6 and 3-7 and the following notes. Change or remove the jumpers as necessary.
1 2
Processor printed circuit board ACPU Prozessorbaugruppe Input/output printed circuit board AI/O3
Slot 5
1
Slot 19
2
BI1 to BI3
Figure 3-5
Front view of the device after removal of the front cover (simplified and scaled down)
208
3.1.3.3
Jumper Settings on Printed Circuit Boards The design of a jumper setting for the processor board ACPU is shown in Figure 3-6. The preset rated voltage of the integrated power supply is checked according to Table 3-2, the pickup voltages of the binary inputs BI1 through BI3 are checked according to Table 3-3, and the quiescent state of the binary outputs (BO1 and BO2) is checked according to Table 3-4.
Mini-fuse
F1
Battery
G1
Figure 3-6
Processor board ACPU (without interface modules) with representation of the jumper settings required for the module configuration
X51 3 21
2 1 2 1
X53 L H L H
1 2 3 4 3 2 1 X52
X23
209
Table 3-2
Jumper settings for the nominal voltage of the integrated power supply on the processor board ACPU Nominal voltage
Jumper 24 to 48 VDC X51 X52 X53 not fitted not fitted not fitted 60 to 125 VDC 12 12 and 34 12 110 to 250 VDC; 115 to 230 VDC 23 23 23
Table 3-3
Jumper settings for the pickup voltages of the binary inputs BI1 through BI3 on the processor board ACPU Jumper X21 X22 X23 17 VDC pickup 1) 12 12 12 73 VDC pickup 2) 23 23 23
settings for devices with power supply voltages of 24 VDC to 125 VDC Factory settings for devices with power supply voltages of 110 V to 250 VDC and 115 to 230 VAC
Table 3-4
Jumper setting for the quiescent state of the Binary Outputs on the processor-
board ACPU
For BO1 BO2 Jumper X41 X42 Open in the quiescent state Closed in the quiescent state (NO contact) (NC contact) 12 12 23 23 Presetting 12 12
210
The design of a jumper setting for the processor board AI/O3 is shown in Figure 3-7.
X66 0.1A
X65 0.1A
5A 1A 1A 5A 5A 1A
5A 1A
IL2S2 I5
IL1S2 I4
IL3S2 I6
I8
IL2S1 I2
undef
undef
IL3S1 I3
1A 1A
IL1S1 I1
I7
Figure 3-7
The rated current settings of the input current transformers are checked on the AI/O3 board. With default settings all jumpers (X61 to X70) are set to the same rated current (according to the order number of the device). However, rated currents can be changed for each individual input transformer. To do so you have to change the location of the jumpers next to the transformers. Additionally, settings of the common jumpers X68 to X70 must be changed correspondingly. Table 3-5 shows the assignment of the jumpers to the current measuring inputs.
5A
5A
X63 0.1A
X64 0.1A
Input/output board AI/O3 with representation of the jumper settings required for the module configuration
5A
5A
211
Table 3-5
Assignment of the jumpers to the measuring inputs Application Jumper Individual X61 X62 X63 X65 X66 X67 X64 X70 X69 X68 Common I1 I2 I3 I4 I5 I6 I7 I8
1-phase
212
3.1.3.4
Interface Modules The interface modules are located on the processor board ACPU. Figure 3-8 shows the CPU board and the location of the interface modules.
System Interface
Figure 3-8
Please note the following: Interface modules can only be exchanged for devices with flush mounting housing. Interface modules for devices with surface mounting housing must be exchanged in our manufacturing centre. Use only interface modules that can be ordered as an option of the device (see also Appendix A.1).
213
Table 3-6
Exchange interface modules for devices with flush mounting housing Mounting Port Replacing Module RS232 RS485 Optical 820 nm Profibus FMS RS485 Profibus FMS single ring
Interface
System Interface
Profibus FMS double ring Profibus DP RS485 Profibus DP double ring Modbus RS485 Modbus 820 nm DNP 3.0 RS485 DNP 3.0 820 nm RS232
The ordering numbers of the exchange modules are listed in Appendix A.1.1, (Accessories). RS232 Interface The RS232 interface can be transformed into a RS485 interface according to Figure 3-10. Figure 3-8 shows the PCB of the ACPU with the location of the modules. Figure 3-9 shows how jumpers of interface RS232 are located on the interface module. Here, terminating resistors are not required. They are always disabled.
X3 X6 X7 X4 X5
1 2 3
X13 C53207A324-B180
8X
1 2 3
1 2 3
Figure 3-9
214
With jumper X11 the flow control which is important for modem communication is enabled. Jumper settings are explained in the following: Jumper setting 23: The modem control signals CTS (Clear-To-Send) according to RS232 are not available. This is a standard connection via star coupler or optical fibre converter. They are not required since the connection to the SIPROTEC devices is always operated in the half-duplex mode. Please use connection cable with order number 7XV51004. Jumper setting 12: Modem signals are made available. For a direct RS232 connection between the device and the modem this setting can be selected optionally. We recommend to use a standard RS232 modem connection cable (converter 9-pole on 25-pole).
Jumper setting for CTS (Clear-To-Send) on the interface module /CTS from RS232 interface 12 /CTS controlled by /RTS 23
RS485 Interface
The interface RS485 can be transformed into interface RS232 according to Figure 39. Using interfaces with bus capability requires a termination for the last device at the bus, i.e. terminating resistors must be switched to the line. The terminating resistors are connected to the corresponding interface module that is mounted to the processor input/output board ACPU. Figure 3-8 shows the printed circuit board of the ACPU and the allocation of the modules. The module for the RS485 interface is illustrated in Figure 3-10, for the profibus interface in Figure 3-11. The two jumpers of a module must always be plugged in the same position. When the module is delivered, the jumpers are plugged so that th resistors are disconnected. Exception: Connecting one or two temperature measuring devices 7XV566 to the service interface, the terminating resistors are switched onto the line since this is the standard for this application. This only goes for Port C for devices with order number 7UT612*****24*** (position 12 = 2; position 13 = 4).
215
X13 C53207A324-B180
Figure 3-10
2 3 4 B100 B101
X4 3 2 1
Disconnected 23 *) 23 *)
3 2 1 X3
Figure 3-11
Terminating resistors can also be implemented outside the device (e.g. in the plug connectors). In that case the terminating resistors provided on the RS485 or Profibus interface module must be switched out.
Figure 3-12
216
3.1.3.5
Carefully insert the boards into the housing. The installation locations of the boards are shown in Figure 3-5. For the model of the device designed for surface mounting, use the metal lever to insert the ACPU board. The installation is easier with the lever. First insert the plug connectors on the ribbon cable in the input/output board AI/O3 and then on the processor board ACPU. Be careful not to bend any of the connecting pins! Do not use force! Insert the plug connector of the ribbon cable between the processor board ACPU and the front cover in the socket on the front cover. Press the latches of the plug connectors together. Replace the front cover and secure to the housing with the screws. Replace the covers. Re-fasten the interfaces on the rear of the device housing. This activity is not necessary if the device is for surface mounting.
o o o o o o
217
3.2
3.2.1
5 9 6 1
Operating Interface at the Front Side
1 6 9 5
1 6 9 5
Time Synchronization Interface at the Rear Side (Panel Flush Mounting)
Serial Interface at the Rear Side Figure 3-13 9-pin D-subminiature sockets
When the recommended communication cable is used, correct connection between the SIPROTEC device and the PC is automatically ensured. See the Appendix A, Subsection A.1.1 for an ordering description of the cable. When a serial interface of the device is connected to a central substation control system, the data connection must be checked. A visual check of the transmit channel and the receive channel is important. Each connection is dedicated to one transmission direction. The data output of one device must be connected to the data input of the other device, and vice versa. The data cable connections are designated in sympathy with DIN 66020 and ISO 2110 (see also Table 3-8): TxD RxD RTS CTS DGND Data Transmit Data Receive Request to Send Clear to Send Signal/Chassis Ground
The cable shield is to be grounded at only both ends. For extremely EMC-loaded environments the GND may be integrated into a separate individually shielded wire pair to improve the immunity to interference.
218
P-Slave AME
Pin-assignments of the D-subminiature ports Operating Interface RxD TxD GND RTS CTS RS232 Profibus FMS Slave, RS485 Profibus DP Slave, RS485 Screen (with screen ends electrically connected) RS485 A/A' (RxD/TxDN) C/C' (GND) *) B/B' (RxD/TxDP) B/B' (RxD/TxDP) CNTRA (TTL) C/C' (GND) +5 V (max. load 100 mA) A/A' (RxD/TxDN) Modbus RS485 DNP3.0 RS485 A RTS (TTL level) GND1 VCC1 B
*) Pin 7 also may carry the RS232 RTS signal on an RS485 interface. Pin 7 must therefore not be connected!
Termination
The RS485 interface is capable of half-duplex service with the signals A/A and B/B with a common reference potential C/C (DGND). Verify that only the last device on the bus has the terminating resistors connected, and that the other devices on the bus do not. Jumpers for the terminating resistors are on the interface module RS 485 (Figure 3-10) or on the Profibus module (Figure 3-11). It is also possible that the terminating resistors are arranged externally (Figure 3-12). If the bus is extended, make sure again that only the last device on the bus has the terminating resistors switched in, and that all other devices on the bus do not.
Time Synchronization
Either 5 VDC, 12 VDC or 24 VDC time synchronization signals can be processed if the connections are made as indicated in Table 3-9. .
Table 3-9 Pin-No. 1 2 3 4 5 6 7 8 9 Pin-assignments of the D-subminiature port of the time synchronization interface Designation P24_TSIG P5_TSIG M_TSIG M_TSYNC*) Screen P12_TSIG P_TSYNC*) Screen Signal Meaning Input 24 V Input 5 V Return Line Return Line *) Screen potential Input 12 V Input 24 V *) Screen potential
219
Optical Fibres
Signals transmitted over optical fibres are unaffected by interference. The fibres guarantee electrical isolation between the connections. Transmit and receive connections are identified with the symbols for transmit and for receive. The character idle state for the optical fibre interface is Light off. If this setting is to be changed, use the operating program DIGSI 4, as described in the SIPROTEC System Manual, order-no. E50417H1176C151.
Warning!
Laser injection! Do not look directly into the fibre-optic elements!
Thermoboxes
If one or two thermoboxes 7XV566 are connected for considering the coolant temperature when using overload protection with hot-spot calculation, check this connection at the service interface (Port C). Check also for the termination: The terminating resistors must be connected to the device 7UT612 (see Subsection 3.1.3.4, margin heading RS485 Interface). For notes concerning the 7XV566 see for the instruction manual attached to the device. Check the transmission parameters at the temperature measuring device. Besides Baud-rate and parity also the bus number is of primary importance. For the connection of 1 thermobox 7XV566: bus number = 0 with Simplex-transmission (to be set at 7XV566), bus number = 1 with Duplex-transmission (to be set at 7XV566), For the connection of 2 thermoboxes 7XV566: bus number = 1 for the 1st thermobox (to be set at 7XV566 for RTD1 to 6), bus number = 2 for the 2nd thermobox (to be set at 7XV566 for RTD7 to 12).
3.2.2
Warning!
Some of the following test steps will be carried out in presence of hazardous voltages. They shall be performed only by qualified personnel which is thoroughly familiar with all safety regulations and precautionary measures and pay due attention to them.
Caution!
Operating the device on a battery charger without a connected battery can lead to impermissibly high voltages and consequently, the destruction of the device. For limit values see Subsection 4.1.2 in the Technical Data. Before the device is energized for the first time, the device should be in the final operating environment for at least 2 hours to equalize the temperature and to minimize hu-
220
midity and avoid condensation. Connection are checked with the device at its final location. The plant must first be switched off and grounded. Connection examples for the current transformer circuits are given in the Appendix Section A.3. Please observe the plant diagrams, too.
o o
Protective switches (e.g. test switches, fuses, or miniature circuit breakers) for the power supply must be opened. Check the continuity of all current transformer connections against the switch-gear and connection diagrams:
q Are the current transformers grounded properly? q Are the polarities of the current transformers the same for each CT set? q Is the phase relationship of the current transformers correct? q Is the polarity for current input I7 correct (if used)? q Is the polarity for current input I8 correct (if used)?
o
Check the functions of all test switches that may be installed for the purposes of secondary testing and isolation of the device. Of particular importance are test switches in current transformer circuits. Be sure these switches short-circuit the current transformers when they are in the test mode (open). The short-circuit feature of the current circuits of the device are to be checked. An ohmmeter or other test equipment for checking continuity is needed.
q Remove the front panel of the device (see Figure 3-5). q Remove the ribbon cable connected to the AI/O3 board and pull the board out q At the terminals of the device, check continuity for each pair of terminals that receives current from the CTs.
until there is no contact between the board and the rear connections of the device.
q Firmly re-insert the board. Carefully connect the ribbon cable. Do not bend any connector pins! Do not use force!
q Check continuity for each of the current terminal-pairs again. q Attach the front panel and tighten the screws.
o o o o o o o o o
7UT612 Manual C53000G1176C1481
Connect an ammeter in the supply circuit of the power supply. A range of about 2.5 A to 5 A for the meter is appropriate. Close the protective switches to apply voltage to the power supply of the device. Check the polarity and magnitude of the voltage at the device terminals. The measured steady-state current should correspond to the quiescent power consumption of the device. Transient movement of the ammeter merely indicates the charging current of capacitors. Remove the voltage from the power supply by opening the protective switches. Disconnect the measuring equipment; restore the normal power supply connections. Check the trip circuits to the power system circuit breakers. Verify that the control wiring to and from other devices is correct. Check the signalling connections. Close the protective switches to apply voltage to the power supply.
221
3.3
Commissioning
Warning!
Hazardous voltages are present in this electrical equipment during operation. Non observance of the safety rules can result in severe personal injury or property damage. Only qualified personnel shall work on and around this equipment after becoming thoroughly familiar with all warnings and safety notices of this manual as well as with the applicable safety regulations. Particular attention must be drawn to the following: The earthing screw of the device must be connected solidly to the protective earth conductor before any other electrical connection is made. Hazardous voltages can be present on all circuits and components connected to the supply voltage or to the measuring and test quantities. Hazardous voltages can be present in the device even after disconnection of the supply voltage (storage capacitors!). Wait for at least 10 s after having disconnected the supply voltage before you reapply the voltage in order to achieve defined initial conditions. The limit values stated in the Technical Data must not be exceeded at all, not even during testing and commissioning.
When testing the device with secondary test equipment, make sure that no other measurement quantities are connected. Take also into consideration that the trip and close commands to the circuit breakers and other primary switches are disconnected from the device unless expressly stated.
DANGER!
Current transformer secondary circuits must have been short-circuited before the current leads to the device are disconnected! If test switches are installed that automatically short-circuit the current transformer secondary circuits, it is sufficient to place them into the Test position provided the short-circuit functions has been previously tested. For the commissioning switching operations have to be carried out. A prerequisite for the prescribed tests is that these switching operations can be executed without danger. They are accordingly not meant for operational checks.
Warning!
Primary tests must only be carried out by qualified personnel, who are familiar with the commissioning of protection systems, the operation of the plant and the safety rules and regulations (switching, earthing, etc.).
222
3.3 Commissioning
3.3.1
3.3.2
Preliminary Notes
DANGER!
The transmission and reception of messages via the system (SCADA) interface by means of the testing mode is the real exchange of information between the SIPROTEC4 device and the substation. Connected equipment such as circuit breakers or disconnectors can be operated as a result of these actions!
Note:
After termination of this test, the device will reboot. All annunciation buffers are erased. If required, these buffers should be extracted with DIGSI 4 prior to the test. The system interface test is carried out 2QOLQH using DIGSI 4:
q Double-click on the 2QOLQH directory to open the required dialogue box. q Click on 7HVW and the functional options appear on the right side of the window.
Double-click on 7HVWLQJ 0HVVDJHV IRU 6\VWHP ,QWHUIDFH shown in the list view. The dialogue box *HQHUDWH ,QGLFDWLRQV opens (refer to Figure 3-14). Structure of the Dialogue Box In the column ,QGLFDWLRQ, all message texts that were configured for the system interface in the matrix will then appear. In the column 6(732,17 VWDWXV you to define the value for the messages to be tested. Depending on the type of message different
223
Figure 3-14
Clicking for the first time onto one of the field in column $FWLRQ you will be asked for password no. 6 (for hardware test menus). Having entered the correct password messages can be issued. To do so, click on 6HQG. The corresponding message is issued and can be read out either from the event log of the SIPROTEC4 device as well as from the central master computer. As long as the windows is open, further tests can be performed.
For all information that is transmitted to the central station the following is to be checked under 6(732,17 VWDWXV:
q Make sure that each checking process is carried out carefully without causing any
danger (see above and refer to DANGER!). station and shows the desired reaction.
q Click on 6HQG and check whether the transmitted information reaches the central
Exiting the Test Mode Test in Command Direction To end the system interface test, click on &ORVH. The device is briefly out of service while the processor system starting up. The dialogue box closes. Information in command direction must be sent by the central station. Check whether the reaction is correct.
224
3.3 Commissioning
3.3.3
Preliminary Notes
DANGER!
Changing the status of a binary input or output using the test feature of DIGSI 4 results in an actual and immediate corresponding change in the SIPROTEC device. Connected equipment such as circuit breakers or disconnectors will be operated as a result of these actions!
Note: After termination of the hardware test, the device will reboot. Thereby, all annunciation buffers are erased. If required, these buffers should be extracted with DIGSI 4 prior to the test.
The hardware test can be done using DIGSI 4 in the online operating mode:
q Open the 2QOLQH directory by double-clicking; the operating functions for the device appear.
q Click on 7HVW; the function selection appears in the right half of the screen. q Double-click in the list view on +DUGZDUH 7HVW. The dialogue box of the same
name opens (see Figure 3-15).
Figure 3-15
225
q Ensured that the switching of the output relay can be executed without danger (see
above under DANGER!). alog box.
q Each output relay must be tested via the corresponding 6FKHGXOHGcell in the diq The test sequence must be terminated (refer to margin heading Exiting the Procedure), to avoid the initiation of inadvertent switching operations by further tests. Test of the Binary Inputs To test the wiring between the plant and the binary inputs of the 7UT612 the condition in the plant which initiates the binary input must be generated and the response of the device checked. To do this, the dialogue box +DUGZDUH 7HVW must again be opened to view the physical state of the binary inputs. The password is not yet required.
q Each state in the plant which causes a binary input to pick up must be generated. q The response of the device must be checked in the 6WDWXVcolumn of the dialogue
box. To do this, the dialogue box must be updated. The options may be found below under the margin heading Updating the Display. If however the effect of a binary input must be checked without carrying out any switching in the plant, it is possible to trigger individual binary inputs with the hardware test function. As soon as the first state change of any binary input is triggered and the
226
3.3 Commissioning
password nr. 6 has been entered, all binary inputs are separated from the plant and can only be activated via the hardware test function.
q Terminate the test sequence (see above under the margin heading Exiting the Procedure). Test of the LEDs The LEDs may be tested in a similar manner to the other input/output components. As soon as the first state change of any LED has been triggered, all LEDs are separated from the internal device functionality and can only be controlled via the hardware test frunction. This implies that no LED can be switched on anymore by e.g. a protection function or operation of the LED reset key. When the dialog box +DUGZDUH 7HVW is opened, the present conditions of the hardware components at that moment are read in and displayed. An update occurs: for each harware component, if a command to change the condition is successfully performed, for all hardware components if the 8SGDWH button is clicked, for all hardware components with cyclical updating if the $XWRPDWLF 8SGDWH VHF field is marked. Exiting the Procedure To end the hardware test, click on &ORVH. The dialog box closes. The device becomes unavailable for a brief start-up period immediately after this. Then all hardware components are returned to the operating conditions determined by the plant settings.
3.3.4
Table 3-10
Annunciations on Inconsistencies FNo 00192 05620 05836 Description Setting of the rated secondary currents on Input/Output Board AI/O3 inconsistent The matching factor of the current transformers for differential protection is too great or too small. The matching factor of the current transformers for restricted earth fault protection is too great or too small. See Section 2.1.2 3.1.3.3 2.1.2 2.2 2.1.2 2.1.1
Message Error1A/ 5Awrong Diff Adap.fact. REF Adap.fact. REF Err CTstar
05830* There is no measuring input assigned for restricted earth fault protection
227
Table 3-10
Message REF Not avalia. O/C Ph. Not av. O/C 3I0 Not av. I2 Not avalia.
05835* Restricted earth fault protection is not available for the configured protected 2.1.1 object 01860* Time overcurrent protection for phase currents is not available for the configured protected object 01861* Time overcurrent protection for residual current is not available for the configured protected object 05172* Unbalanced load protection is not available for the configured protected object 2.1.1 2.1.1 2.1.1 2.1.1 2.9.3 2.1.1
O/L No Th.meas. 01545* Temperature reception for overload protection is missing (from thermobox) O/L Not avalia. BkrFail Not av. TripC ProgFail Fault Configur.. 01549* Overload protection is not available for the configured protected object
01488* Breaker failure protection is not available for the configured protected object 2.1.1 06864 00311 For trip circuit supervision the number of binary inputs was set incorrectly Group indication of fault annunciations marked with *. 2.13.1.4 3.1.2
In the operational or spontaneous annunciations also check if there are any fault annunciations from the device.
3.3.5
Caution!
Tripping of the complete busbar or busbar section may occur even during tests at the local feeder breaker. Therefore, it is recommended to interrupt the tripping commands to the adjacent (busbar) breakers e.g. by switch-off of the associated control voltage. Nevertheless ensure that trip remains possible in case of a real primary fault if parts of the power plant are in service. The following lists do not claim to cover all possibilities. On the other hand, they may contain items that can be bypassed in the actual application.
228
3.3 Commissioning
The circuit breaker auxiliary contact(s) form an essential part of the breaker failure protection system in case they have been connected to the device. Make sure that the correct assignment has been checked (Subsection 3.3.3). Make sure that the measured currents for breaker failure protection (CTs), the tested circuit breaker, and its auxiliary contact(s) relate to the same side of the protected object. If the breaker failure protection is intended to be initiated by external protection devices, each of the external initiation conditions must be checked. At least the tested phase of the device must be subjected to a test current to enable initiation of the breaker failure protection. This may be a secondary injected current.
q Start by trip command of the external protection: q Following initiation the message %NU)DLO
7LPHU (address ).
Binary input !%UN)DLO H[W65& (FNo ); look up in the trip log or spontaneous messages. H[W 38 (FNo ) must appear in the fault annunciations (trip log) or in the spontaneous messages.
q Trip command of the circuit breaker failure protection after the delay time 75,3
Switch off test current. The following applies if initiation without current flow is possible:
q Close tested circuit breaker while the disconnectors at both sides open. q Start by trip command of the external protection: q Following initiation the message %NU)DLO
7LPHU (address ).
Binary input !%UN)DLO H[W65& (FNo ); look up in the trip log or spontaneous messages. H[W 38 (FNo ) must appear in the fault annunciations (trip log) or in the spontaneous messages.
q Trip command of the circuit breaker failure protection after the delay time 75,3
Reopen the local circuit breaker. Busbar Trip The most important thing is the check of the correct distribution of the trip commands to the adjacent circuit breakers in case the local breaker fails. The adjacent circuit breakers are those of all feeders which must be tripped in order to ensure interruption of the fault current should the local breaker fail. In other words, the adjacent breaker are those of all feeders which may feed the same busbar or busbar section as the faulty feeder. In case of a power transformer, the adjacent breakers may include the breaker of the other side of the transformer. The identification of the adjacent feeders depends widely on the topology of the busbar and its possible arrangement or switching states. That is why a generally detailed test description cannot be specified. In particular if multiple busbars are concerned the trip distribution logic to the other breakers must be checked. It must be verified for each busbar section that all breakers connected to the same section are tripped in case the concerned feeder breaker fails, and no other breakers.
229
After completion of the tests, re-establish all provisory measures which might have been taken for the above tests. Ensure that the states of all switching devices of the plant are correct, that interrupted trip commands are reconnected and control voltages are switched on, that setting values which might have been altered are reverted to correct values, and that protective function are switched to the intended state (on or off).
3.3.6
Note:
It must be taken into consideration that tripping may occur if connections were made wrong. The measured quantities of the following tests can be read out from the PC using DIGSI 4 or a web browser via the IBS-Tool. This provides comfortable read-out possibilities for all measured values with visualisation using phasor diagrams. If you choose to work with the IBS-Tool, please note the Help files referring to the IBSTool. The IPaddress neede for the browser depends on the poert where the PC is connected: Connection to the front operation interface: IPaddress 141.141.255.160 Connection to the rear service interface: IPaddress 141.143.255.160 The following descriptions refer to read-out using DIGSI 4. Preparation of Symmetrical Current Tests At first commissioning, current checks must be performed before the protected object is energized for the first time. This ensures that the differential protection is operative as a short-circuit protection during the first excitation of the protected object with voltage. If current checks are only possible with the protected object under voltage (e.g. power transformers in networks when no low-voltage test equipment is available), it is imperative that a backup protection, e.g. time overcurrent protection, be commissioned before, which operates at least at the feeding side. The trip circuit of other protection devices (e.g. Buchholz protection) must either remain operative. The test arrangement varies dependent on the application.
DANGER!
Operations in the primary area must be performed only with plant sections voltage-free and earthed! Perilous voltages may occur even on voltage-free plant sections due to capacitive influence caused by other live sections.
230
3.3 Commissioning
On network power transformers and asynchronous machines, a low-voltage test equipment is preferably used. A low-voltage source is used to energize the protected object, which is completely disconnected from the network (see Figure 3-16). On transformers, the test source is normally connect at the primary side. A short-circuit bridge which is capable to carry the test current, is installed outside of the protected zone and allows the symmetrical current to flow. On a motor, its star point enables current flow.
M
400 V 400 V
3~
7UT612
3~
7UT612
400 V
400 V
Test source
Figure 3-16
Test source
Current test with low-voltage test source examples for a transformer and a motor
On power station unit transformers and synchronous machines, the checks are performed during the current tests. The generator itself forms the test current source (see Figure 3-17). The current is produced by a three-pole short-circuit bridge which is installed outside of the protected zone and is capable to carry rated current for a short time.
7UT612 7UT612
Figure 3-17
7UT612
On busbars, branch points, and short lines, a low-voltage test source can be used. Alternatively, load current test is possible. In the latter case the above hint about backup protection must be observed! With the single-phase differential protection for busbars with more than 2 feeders, symmetrical current test is not necessary (but permissible, of course). The test can be carried out using a single-phase current source. But, current tests must be performed for each possible current path, e.g. feeder 1 against feeder 2, feeder 1 against feeder
231
3, etc. Please read at first the notes about Checking for Busbar Protection, Subsection 3.3.8 (page 240). Realization of Symmetrical Current Tests For this commissioning tests, the test current must be at least 2 % of the rated relay current for each phase. This test cannot replace visual inspection of the correct current transformer connections. Therefore, the inspection according to Section 3.2.2 is a prerequisite. Since 7UT612 offers comprehensive commissioning aids commissioning can be performed quickly and without external instrumentation. The following indices are used for the display of measured values: The equation symbol for current (I, ) is followed by the phase identifier L and by a number that identifies the side (e.g. the transformer winding). Example: IL1S1 current in phase L1 on Side 1. The following procedure applies to three-phase protected objects. For transformers it is assumed that side 1 is the overvoltage side of the transformer.
Switch on the test current, or start up the generator and bring it to nominal speed and excite it to the required test current. None of the measurement monitoring functions in the device must respond. If there was a fault message, however, the Event Log or spontaneous messages could be checked to investigate the reason for it. Refer also to the SIPROTEC 4 System Manual, order-no. E50417H1176C151. Read out the current magnitudes: Compare the measured values under 0HDVXUHPHQW 6HFRQGDU\ 9DOXHV 2SHUDWLRQDO YDOXHV VHFRQGDU\ with the real values: I L1S1 = I L2S1 = I L3S1 = 3I0S1 = I L1S2 = I L2S2 = I L3S2 = 3I0S2 =
Note: The IBS Tool provides comfortable read-out possibilities for all measured values with visualisation using phasor diagrams (Figure 3-18).
If deviations occur which cannot be explained by measuring tolerances, an error can be assumed in the device connections or in the test arrangement.
q Switch off the test source and the protected object (shut down the generator) and
earth it.
q Re-check the plant connections to the device and the test arrangement and correct
them. If a substantial zero sequence current 3I0 occurs one two of the currents of the corresponding side must have a wrong polarity. 3I0 phase current one or two phase currents are missing, 3I0 doubled phase current one or two phase currents have a reversed polarity.
232
3.3 Commissioning
Secondary Values
Currents: Side 1 +90 Currents: Side 2 +90
180
0 180
90
90
Figure 3-18
Measured values on the sides of the protected object example for through-flowing currents
Phase angle measurement for side 1 with test current: Read out the phase angles under 0HDVXUHPHQW 6HFRQGDU\ 9DOXHV $QJOHV of side 1 of the protected object. All angles are referred to I L1S1. The following values must result approximately for a clockwise phase rotation: L1S1 0 L2S1 240 L3S1 120 If the angles are wrong, reverse polarity or swapped phase connections on side 1 of the protected object may be the cause.
q Switch off the test source and the protected object (shut down the generator) and
earth it. them.
q Re-check the plant connections to the device and the test arrangement and correct q Repeat test and re-check the current angles.
o
Phase angle measurement for side 2 with test current: Read out the phase angles under 0HDVXUHPHQW 6HFRQGDU\ 9DOXHV $QJOHV of side 2 of the protected object. All angles are referred to I L1S1.
233
Consider that always the currents flowing into the protected object are defined as positive. That means that, with through-flowing in-phase currents, the currents leaving the protected object at side 2, have reversed polarity (180 phase displacement) against the corresponding in-flowing currents at side 1. Exception: With transverse differential protection, the currents of the corresponding phase have equal phase! For clockwise phase rotation, approximately the values according to Table 3-11 result.
Table 3-11
Phase indication dependent on the protected object (three-phase) Generator/Motor/ Busbar/Line 180 60 300 0 1 2 Transformer with connection group numeral 1) 3 90 4 60 5 30 6 0 7 8 9 10 11
The stated angles are valid if the high-voltage winding is side 1. Otherwise read 360 minus the stated angle
If considerable deviations occur, reversed polarity or swapped phases are expected on side 2.
q Deviation in individual phases indicates reversed polarity in the related phase current connection or acyclically swapped phases.
q If all phase angles differ by the same value, phase current connections of side 2 are
cyclically swapped or the connection group of the transformer differs from the set group. In the latter case, re-check the matching parameters (Subsection 2.1.2 under margin Object Data with Transformers, page 20) under addresses , , and .
q If all phase angles differ by 180, the polarity of the complete CT set for side 2 is
wrong. Check and correct the applicable power system data (cf. Subsection 2.1.2 under Current Transformer Data for 2 Sides, page 23): address 675317!2%- 6 for side 1, address 675317!2%- 6 for side 2.
For single-phase busbar protection refer to Subsection 2.1.2 under header margin Current Transformer Data for Single-phase Busbar Protection. If connection errors are assumed:
q Switch off the test source and the protected object (shut down the generator) and
earth it. them.
q Re-check the plant connections to the device and the test arrangement and correct q Repeat test and re-check the current angles.
Measuring Differential and Restraint Currents Before the tests with symmetrical currents are terminated, the differential and restraint currents are examined. Even though the above tests with symmetrical current should have widely detected connection errors, nevertheless, errors are possible concerning current matching and the assignment of the connection group cannot be completely excluded.
234
3.3 Commissioning
The differential and restraint currents are referred to the nominal currents of the protected object. This must be considered when they are compared with the test currents.
Read out the differential and restraint currents under 0HDVXUHPHQW 3HUFHQW 9DOXHV 'LIIHUHQWLDO DQG 5HVWUDLQW &XUUHQWV. In the IBS-Tool, the differential and restraint currents are displayed as a graph in a characteristics diagram. An example is illustrated in Figure 3-19.
Tripping Characteristics
Diff.-Current I/InO
3
Rest.-Current I/InO
1 2 3
Diff.-Current IDiffL1 = IDiffL2 = IDiffL3 = 0.03 I/InO 0.02 I/InO 0.10 I/InO
Rest.-Current IRestL1 = 0.80 I/InO IRestL2 = 0.74 I/InO IRestL3 = 0.78 I/InO 0.3 7.5 I/InO I/InO
q The differential currents must be low, at least one scale less than the currents flowing through.
235
q If there are differential currents in the size of the restraint currents (approximately
twice the through-flowing test current), you may assume a polarity reversal of the current transformer(s) at one side. Check the polarity again and set it right after short-circuiting all the six current transformers. If you have modified these current transformers, also perform an angle test.
q If there are differential currents which are nearly equal in all three phases, matching
of the measured values may be erroneous. Wrong connection group of a power transformer can be excluded because they should have been detected during the phase angle test. Re-check the settings for current matching. These are mainly the data of the protected object: For all kind of power transformers, addresses , and under Object Data with Transformers, (page 20) and addresses , , and under Current Transformer Data for 2 Sides (page 23). For generators, motors, reactors, addresses and under Object Data with Generators, Motors and Reactors (page 22) and addresses , and under Current Transformer Data for 2 Sides (page 23). For mini-busbars, address under Object Data with Mini-Busbars, BranchPoints, Short Lines (page 22) and addresses , , and under Current Transformer Data for 2 Sides (page 23). For single-phase busbar protection, addresses and under Object Data with Busbars with up to 7 Feeders (page 23) and addresses to under Current Transformer Data for Single-phase Busbar Protection (page 25). If interposed summation transformers are used, matching errors can be caused by wrong connections at the summation CTs.
o o
Finally, switch off the test source and the protected object (shut down the generator). If parameter settings have been changed for the tests, reset them to the values necessary for operation.
3.3.7
Note:
It must be taken into consideration that tripping may occur if connections were made wrong.
236
3.3 Commissioning
Zero sequence current measurements are always performed from that side of the protected object where the starpoint is earthed, on auto-transformers from the high-voltage side. Power transformers shall be equipped with a delta winding (dwinding or compensating winding). The side which is not included in the tests remains open as the delta winding ensures low-ohmic termination of the current path. The test arrangement varies with the application. Figures 3-20 to 3-24 show schematic examples of arrangements.
DANGER!
Operations in the primary area must be performed only with plant sections voltage-free and earthed! Perilous voltages may occur even on voltage-free plant sections due to capacitive influence caused by other live sections.
~ Test source
7UT612
Figure 3-20 Zero sequence current measurement on a star-delta transformer
~ Test source
7UT612
Figure 3-21 Zero sequence current measurement on a star-star transformer with compensation winding
237
~ Test source
7UT612
Figure 3-22 Zero sequence current measurement on a zig-zag-winding
~ Test source
7UT612
Figure 3-23 Zero sequence current measurement on a delta winding with neutral earthing reactor within the protected zone
~ Test source
7UT612
Figure 3-24 Zero sequence current measurement on an earthed single-phase transformer
238
3.3 Commissioning
For this commissioning tests, the zero sequence current must be at least 2 % of the rated relay current for each phase, i.e. the test current at least 6 %. This test cannot replace visual inspection of the correct current transformer connections. Therefore, the inspection according to Section 3.2.2 is a prerequisite.
o o
Switch on test current. Read out the current magnitudes under 0HDVXUHPHQW 6HFRQGDU\ 9DOXHV 2SHUDWLRQDO YDOXHV VHFRQGDU\ and compare them with the real values: All phase currents of the tested side correspond to approximately 1/3 of the test current (1/2 with single-phase transformers). 3I0 of the tested side corresponds to the test current. Phase currents and zero sequence current of the other side are, on transformers, nearly 0. Current I7 correspond to the test current. Deviation can practically occur only for the current I7 because the phase currents had been tested already during the symmetrical tests. When deviations are in I7:
q Switch off the test source and the protected object (shut down the generator) and
earth it.
q Re-check the I7 connections and the test arrangement and correct them. q Repeat test and re-check the current magnitudes.
Measuring Differential and Restraint Currents The differential and restraint currents are referred to the nominal currents of the protected object. This must be considered when they are compared with the test currents. Switch on test current. Read out the differential and restraint currents under 0HDVXUHPHQW 3HUFHQW 9DOXHV 'LIIHUHQWLDO DQG 5HVWUDLQW &XUUHQWV.
o o
q The differential current of the restricted earth fault protection IDiffREF must be low,
at least one scale less than the test current.
q The restraint current IRestREF corresponds to twice the test current. q If the differential current is in the size of the restraint current (approximately twice
the test current), you may assume a polarity reversal of the current transformer for I7. Check the polarity again and compare it with the setting in address ($57+ (/(&752' (cf. also Subsection 2.1.2 under margin Current Transformer Data for Current Input I7 (page 26). the matching factor for I7 may be incorrect. Check the setting relevant for current matching. These are mainly the data of the protected object (Subsection 2.1.2):
q If there is a differential current which does not correspond to twice the test current,
addresses and under Object Data with Transformers, (page 20) and addresses and under Current Transformer Data for Current Input I7 (page 26).
239
q The differential currents of the differential protection must either be low, at least one
Starpoint conditioning of a transformer: addresses 67$5317 6,'( , 67$5317 6,'( , Subsection 2.1.2 under margin Object Data with Transformers, (page 20), as well as the assignment of the starpoint current transformer to the input I7: address ,&7 &211(&7, Subsection 2.1.1 under Special Cases (page 16).
scale less than the test current. If considerable differential currents occur, re-check the settings for the starpoints:
IRest L3 are equally small. If all tests have been successful until now, this should be ensured.
Finally, switch off the test source and the protected object (shut down the generator). If parameter settings have been changed for the tests, reset them to the values necessary for operation.
3.3.8
General
If summation transformers are used, different connection possibilities exist. The following clarification are based on the normal connection mode L1L3E according to Figure 3-25. Figure 3-26 applies for connection L1L2L3. Single-phase primary tests are to be preferred, since they evoke clearer differences in the measured currents. They also detect connecting errors in the earth current path. The measured current to be read out in the operational measured values only corresponds to the testing current if three-phase symmetrical check is performed. In other
240
3.3 Commissioning
cases there are deviations which are listed in the figures as factor of the testing current.
IL1
2
SCT
IM
Test Current L1L2L3 (sym.) L1L2 L2L3 L3L1 L1E L2E L3E
IL3
1
3I0 L1 L2 L3
Figure 3-25
CT connection L1L3E
IL1
2
SCT
IM
Test Current L1L2L3 (sym.) L1L2 L2L3 L3L1 L1E L2E L3E
IL2
1
IL3
3
L1 L2 L3
Figure 3-26 CT connection L1L2L3
Deviations which cannot be explained by measuring tolerances may be caused by connection errors or matching errors of the summation transformers:
q Switch off the test source and the protected object and earth it. q Re-check the connections and the test arrangement and correct them. q Repeat test and re-check the current magnitudes.
The phase angles must be 180 in all cases. Check the differential and restraint currents. If single-phase primary checks cannot be carried out but only symmetrical operational currents are available, polarity or connecting errors in the earth current path with summation transformer connection L1L3E according to Figure 3-25 will not be detected with the before-mentioned checks. In this case, asymmetry is to be achieved by secondary manipulation. Therefore the current transformer of phase L2 is short-circuited. See Figure 3-27.
241
DANGER!
All precautionary measures must be observed when working on the instrument transformers! Secondary connections of the current transformers must have been short-circuited before any current lead to the relay is interrupted!
IL1
2
SCT
IM
IL3
1
3I0 L1 L2 L3
Figure 3-27 Unsymmetrical test with summation CT connection L1L3E
The measured current is now 2.65 times the current of the symmetrical test. This test must be carried out for each summation CT.
3.3.9
242
3.3 Commissioning
243
Figure 3-28
As the pickup signal of the protection is not stabilized, the inrush current will start fault recording automatically provided the pickup threshold is reached. Conclusions as to the effectiveness of the inrush restraint can be drawn from the recording of the differential currents and the harmonic contents. If necessary the inrush current restraint effect can be increased (smaller value of +$5021,&, address ) when trip occurs or when the recorded data show that the second harmonic content does not safely exceed the restraining threshold (address ). A further method to increase inrush stability is to set the crossblock function effective or to increase the duration of the crossblock function (address $ &5266% +$50). For further detail refer to Subsection 2.2.7 under Harmonic Restraint, page 60).
Note:
Do not forget to switch the differential protection 21 (address ) after completion of the test.
244
3.4
Caution!
Do not use force! The permissible tightening torques must not be exceeded as the threads and terminal chambers may otherwise be damaged!
Verify that all service settings are correct. This is a crucial step because some setting changes might have been made during commissioning. The protective settings under device configuration, input/output configuration are especially important as well as the power system data, and activated Groups A through D (if applicable). All desired elements and functions must be set 21. See (Chapter 2). Keep a copy of all of the in-service settings on a PC. Check the internal clock of the device. If necessary, set the clock or synchronize the clock if it is not automatically synchronized. For assistance, refer to the system manual. The annunciation memory buffers should be cleared, particularly the operational messages (event log) and fault messages (trip log). Future information will then only apply for actual system events and faults. To clear the buffers, press 0$,1 0(18 $Q QXQFLDWLRQ 6HW5HVHW. Refer to the system manual if further assistance is needed. The numbers in the switching statistics should be reset to the values that were existing prior to the testing, or to values in accordance with the users practices. Set the statistics by pressing 0$,1 0(18 $QQXQFLDWLRQ 6WDWLVWLF. Press the
ESC
Clear the LEDs on the front panel by pressing the LED key. Any output relays that were picked up prior to clearing the LEDs are reset when the clearing action is performed. Future indications of the LEDs will then apply only for actual events or faults. Pressing the LED key also serves as a test for the LEDs because they should all light when the button is pushed. Any LEDs that are lit after the clearing attempt are displaying actual conditions. The green 581 LED must be on. The red (5525 LED must not be lit. Close the protective switches. If test switches are available, then these must be in the operating position. The device is now ready for operation.
245
246
Technical Data
This chapter provides the technical data of the SIPROTEC 4 7UT612 device and its individual functions, including the limiting values that must not be exceeded under any circumstances. The electrical and functional data of fully equipped 7UT612 devices are followed by the mechanical data, with dimensional drawings.
4.1 4.2 4.3 4.4 4.5 4.6 4.7 4.8 4.9 4.10 4.11 4.12 4.13 4.14 4.15
General Device Data Differential Protection Restricted Earth Fault Protection Time Overcurrent Protection for Phase and Residual Currents Time Overcurrent Protection for Earth Current Dynamic Cold Load Pickup for Time Overcurrent Protection Single-Phase Time Overcurrent Protection Unbalanced Load Protection Thermal Overload Protection Thermoboxes for Overload Protection Circuit Breaker Failure Protection External Trip Commands Monitoring Functions Ancillary Functions Dimensions
248 258 263 264 271 272 273 274 275 277 278 278 279 280 282
247
4 Technical Data
4.1
4.1.1
Current Inputs
Nominal current
Current overload capability per input I1 to I7 thermal (rms) 100 IN for 1 s 30 IN for 10 s 4 IN continuous dynamic (pulse) 1250 A (half cycle) Current overload capability for high-sensitivity input I8 thermal (rms) 300 A for 1 s 100 A for 10 s 15 A continuous dynamic (pulse) 750 A (half cycle) Current Transformer Requirements Underburden factor PN + Pi n' = n -----------------P' + P i max. ratio of nominal primary current of the current transformers to nominal object current I kd max n 4 ----------------I N prim I kd max n 5 ----------------I N prim for 100 ms for > 100 ms
I Nprim transf 4 for phase currents --------------------------- I Nprim obj 8 for earth current at I7
4.1.2
Power Supply
Voltage supply via integrated DC/DC converter:
Nominal power supply direct voltage UNDC Permissible voltage ranges Nominal power supply direct voltage UNDC Permissible voltage ranges
Direct Voltage
248
Power consumption quiescent energized Bridging time for failure/short-circuit of the power supply Alternating Voltage
Power consumption quiescent energized Bridging time for failure/short-circuit of the power supply
4.1.3
Binary Inputs
Binary Outputs
Signalling/command relays (see also General Diagrams in Section A.2 of Appendix A) Number: Switching capability MAKE BREAK 4, each with 1 NO contact (volt-free) (allocatable) 1000 W/VA 30 VA 40 W ohmic 25 W for L/R 50 ms 1, with 1 NO or NC contact (reconnectable) MAKE BREAK 1000 W/VA 30 VA 40 W ohmic 25 W for L/R 50 ms 250 V
Switching voltage
249
4 Technical Data
4.1.4
Communications Interfaces
Connection front panel, non-isolated, RS 232 9-pin DSUB socket for connecting a personal computer with DIGSI 4 min. 4 800 Baud; max. 115200 Baud factory setting: 38400 Baud; parity: 8E1 15 m (50 ft) isolated interface for data transfer for operation with DIGSI 4 or connection of a thermobox
Operation Interface
Operation Transmission speed Maximum transmission distance Service/Modem Interface (optional) RS232/RS485/Optical acc. ordered version RS232 Connection for flush mounted case for surface mounted case
rear panel, mounting location C 9-pin DSUB socket at the inclined housing on the case bottom shielded data cable
Test voltage Transmission speed Maximum transmission distance RS485 Connection for flush mounted case for surface mounted case
500 V; 50 Hz min. 4 800 Baud; max. 115200 Baud factory setting: 38400 Baud 15 m (50 ft)
rear panel, mounting location C 9-pin DSUB socket at the inclined housing on the case bottom shielded data cable
Test voltage Transmission speed Maximum transmission distance Optical fibre Connector Type for flush mounted case for surface mounted case
500 V; 50 Hz min. 4800 Baud; max. 115200 Baud factory setting: 38400 Baud 1000 m (3300 ft)
STconnector rear panel, mounting location C at the inclined housing on the case bottom
250
Permissible optical signal attenuation max. 8 dB using glass fibre 62.5/125 m Maximum transmission distance Character idle state System (SCADA) Interface (optional) RS232/RS485/Optical Profibus RS485/Profibus Optical acc. to ordered version RS232 Connection for flush mounted case for surface mounted case Test voltage Transmission speed Maximum transmission distance RS485 Connection for flush mounted case for surface mounted case Test voltage Transmission speed Maximum transmission distance Optical fibre Connector Type for flush mounted case for surface mounted case Optical wavelength Laser class 1 acc. EN 608251/ 2 STconnector rear panel, mounting location B at the inclined housing on the case bottom = 820 nm using glass fibre 50/125 m or using glass fibre 62.5/125 m rear panel, mounting location B 9-pin DSUB socket at the inclined housing on the case bottom 500 V, 50 Hz min. 4800 Bd, max. 38400 Bd factory setting: 19200 Bd 1000 m (3300 ft) rear panel, mounting location B 9-pin DSUB socket at the inclined housing on the case bottom 500 V; 50 Hz min. 4800 Bd, max. 38400 Bd factory setting: 19200 Bd 15 m (50 ft) 1.5 km (1 mile) selectable; factory setting: Light off isolated interface for data transfer to a master terminal
Permissible optical signal attenuation max. 8 dB using glass fibre 62.5/125 m Maximum transmission distance Character idle state Profibus RS485 (FMS and DP) Connectionfor flush mounted case for surface mounted case Test voltage rear panel, mounting location B 9-pin DSUB socket at the inclined housing on the case bottom 500 V; 50 Hz 1.5 km (1 mile) selectable; factory setting: Light off
251
4 Technical Data
up to 1.5 MBd 1000 m (3300 ft) 500 m (1640 ft) 200 m (660 ft) at 93.75 kBd at 187.5 kBd at 1.5 MBd
Profibus Optical (FMS and DP) Connector Type STplug FMS: single ring or twin ring depending on ordered version DP: twin ring only rear panel, mounting location B at the inclined housing on the case bottom to 1.5 MBd > 500 kBd = 820 nm using glass fibre 50/125 m or using glass fibre 62.5/125 m
Connection for flush mounted case for surface mounted case Transmission speed recommended: Optical wavelength Laser class 1 acc. EN 608251/ 2
Permissible optical signal attenuation max. 8 dB using glass fibre 62.5/125 m Maximum transmission distance DNP3.0 RS485 Connectionfor flush mounted case for surface mounted case Test voltage Transmission speed Maximum transmission distance DNP3.0 Optical Connector Type Connection for flush mounted case for surface mounted case Transmission speed Optical wavelength Laser class 1 acc. EN 608251/ 2 STplug transmitter/receiver rear panel, mounting location B at the inclined housing on the case bottom up to 19200 Bd = 820 nm using glass fibre 50/125 m or using glass fibre 62.5/125 m rear panel, mounting location B 9-pin DSUB socket at the inclined housing on the case bottom 500 V; 50 Hz up to 19200 Bd 1000 m (3300 ft) 1.5 km (1 mile)
Permissible optical signal attenuation max. 8 dB using glass fibre 62.5/125 m Maximum transmission distance MODBUS RS485 Connection for flush mounted case for surface mounted case Test voltage rear panel, mounting location B 9-pin DSUB socket at the inclined housing on the case bottom 500 V; 50 Hz 1.5 km (1 mile)
252
Transmission speed Maximum transmission distance MODBUS LWL Connector Type Connection for flush mounted case for surface mounted case Transmission speed Optical wavelength Laser class 1 acc. EN 608251/ 2
STplug transmitter/receiver rear panel, mounting location B at the inclined housing on the case bottom up to 19200 Bd = 820 nm using glass fibre 50/125 m or using glass fibre 62.5/125 m
Permissible optical signal attenuation max. 8 dB using glass fibre 62,5/125 m Maximum transmission distance Time Synchronization Signal type Connection for flush mounted case for surface mounted case Nominal signal voltages Signal level and burden:
5V Nominal signal input voltage 12 V 24 V
1.5 km (1 mile) DCF77/IRIG B-Signal rear panel, mounting location A 9-pin DSUB socket at the terminal on the case bottom optional 5 V, 12 V or 24 V
6.0 V
15.8 V 1.4 V at IILow = 0.25 mA 4.5 mA to 9.3 mA 1930 at UI = 8.7 V 1700 at UI = 15.8 V
4.1.5
Electrical Tests
Standards: IEC 60255 (Product standards) ANSI/IEEE C37.90.0; C37.90.0.1; C37.90.0.2 DIN 57435 Part 303 See also standards for individual tests IEC 602555 and 6087021 2.5 kV (rms); 50 Hz
Specifications
Insulation Tests
Standards: High voltage test (routine test) all circuits except power supply, binary inputs, and communication/time sync. interfaces
253
4 Technical Data
High voltage test (routine test) only power supply and binary inputs High Voltage Test (routine test) only isolated communication /time sync. interfaces Impulse voltage test (type test) all circuits except communication /time sync. interfaces, class III EMC Tests; Interference Immunity (Type Tests) Standards:
5 kV (peak); 1.2/50 s; 0.5 Ws; 3 positive and 3 negative impulses in intervals of 5 s IEC 602556 and 22 (Product standards) EN 500822 (Generic standard) DIN 57435 Part 303 2.5 kV (Peak); 1 MHz; = 15 s; 400 surges per s; test duration 2 s Ri = 200 8 kV contact discharge; 15 kV air discharge, both polarities; 150 pF; Ri = 330
High frequency test IEC 60255221, class III and VDE 0435 part 303, class III Electrostatic discharge IEC 60255222 class IV and IEC 6100042, class IV
Irradiation with HF field, non-modulated10 V/m; 27 MHz to 500 MHz IEC 60255223 (report) class III Irradiation with HF field, amplitude 10 V/m; 80 MHz to 1000 MHz; 80 % AM; modulated; IEC 6100043, class III 1 kHz Irradiation with HF field, 10 V/m; 900 MHz; repetition frequency pulse modulated 200 Hz; duty cycle of 50 % IEC 6100043/ENV 50204, class III Fast transient disturbance/burst IEC 60255224 and IEC 6100044, class IV High energy surge voltages (SURGE), IEC 6100045 installation class 3 power supply analogue inputs, binary inputs and outputs 4 kV; 5/50 ns; 5 kHz; burst length = 15 ms; repetition rate 300 ms; both polarities; Ri = 50 ; test duration 1 min impulse: 1.2/50 s 2 kV; 12 ; 9 F 1 kV; 2 ; 18 F 2 kV; 42 ; 0.5 F 1 kV; 42 ; 0.5 F
Line conducted HF, amplitude 10 V; 150 kHz to 80 MHz; 80 % AM; 1 kHz modulated; IEC 6100046, class III Power system frequency magnetic field; IEC 6100048, class IV; IEC 602556 30 A/m continuous; 300 A/m for 3 s; 50 Hz 0.5 mT; 50 Hz
Oscillatory surge withstand capability 2.5 to 3 kV (peak value); 1 to 1.5 MHz ANSI/IEEE C37.90.1 decaying wave; 50 surges per s; duration 2 s; Ri = 150 to 200 Fast transient surge withstand capability, ANSI/IEEE C37.90.1 4 kV to 5 kV; 10/150 ns; 50 surges per s; both polarities; duration 2 s; Ri = 80
Radiated electromagnetic interference 35 V/m; 25 MHz to 1000 MHz ANSI/IEEE Std C37.90.2 amplitude and pulse modulated 254
Damped oscillations IEC 60694, IEC 61000412 EMC Tests; Interference Emission (Type Tests) Standard: Conducted interference, only power supply voltage IECCISPR 22 Radio interference field strength IECCISPR 22
2.5 kV (peak value), polarity alternating; 100 kHz, 1 MHz, 10 MHz and 50 MHz; Ri = 200 EN 50081* (Generic standard) 150 kHz to 30 MHz limit class B 30 MHz to 1000 MHz limit class B
4.1.6
Shock IEC 60255212, class 1 IEC 60068227 Seismic vibration IEC 60255213, class 1 IEC 6006833
255
4 Technical Data
half-sine shaped acceleration 10 g; duration 16 ms; 1000 shocks in each direction of 3 orthogonal axes
4.1.7
Ambient Temperatures
recommended operating temperature 5 C to +55 C limiting temporary (transient) operating temperature limiting temperature during storage limiting temperature during transport 20 C to +70 C (4 F to 158 F)
Visibility of display may be impaired above +55 C/130 F in quiescent state, i.e. no pickup and no indications
Storage and transport of the device with factory packaging! Humidity Permissible humidity mean value p. year 75 % relative humidity on 56 days per year up to 93 % relative humidity; condensation not permissible!
All devices shall be installed such that they are not exposed to direct sunlight, nor subject to large fluctuations in temperature that may cause condensation to occur.
4.1.8
Service Conditions
The device is designed for use in an industrial environment or an electrical utility environment, for installation in standard relay rooms and compartments so that proper installation and electromagnetic compatibility (EMC) is ensured. In addition, the following are recommended: All contactors and relays that operate in the same cubicle, cabinet, or relay panel as the numerical protective device should, as a rule, be equipped with suitable surge suppression components. For substations with operating voltages of 100 kV and above, all external cables should be shielded with a conductive shield grounded at both ends. The shield must be capable of carrying the fault currents that could occur. For substations with lower operating voltages, no special measures are normally required. Do not withdraw or insert individual modules or boards while the protective device is energized. When handling the modules or the boards outside of the case, standards for components sensitive to electrostatic discharge (ESD) must be observed. The modules, boards, and device are not endangered when the device is completely assembled.
256
4.1.9
Construction
Housing Dimensions Weight (mass), approx. in flush mounted case, size 1/2 in surface mounted case, size 1/2 Degree of protection acc. IEC 60529 for the device in surface mounted case in flush mounted case front rear for human safety 7XP20 see drawings, Section 4.15 5.1 kg (111/4 lb) 9.6 kg (211/4 lb)
257
4 Technical Data
4.2
4.2.1
Differential Protection
General
Differential current High-current stage Pickup on switch-on (factor of IDIFF>) Add-on stabilization on external fault (IRest > set value) Iadd-on/INobj action time Trip characteristic Tolerances (at preset parameters) IDIFF> stage and characteristic IDIFF>> stage IDIFF>/INobj IDIFF>>/INobj 0.05 to 2.00 (steps 0.01)
Pickup Values
0.5 to 35.0 (steps 0.1) or (stage ineffective) 1.0 to 2.0 (steps 0.1)
2.00 to 15.00 (steps 0.01) 2 to 250 cycles (steps 1 cycle) or (effective until dropoff) see Figure 4-1 5 % of set value 5 % of set value 0.00 s to 60.00 s or (no trip) 0.00 s to 60.00 s or (no trip) (steps 0.01 s) (steps 0.01 s)
Time Delays
TI-DIFF> TI-DIFF>>
1 % of set value or 10 ms
10 9
Fault Characteristic
D9DAA33
8 7 6 5 4 3 2 1
Legend: Differential current = |I1 + I2 | Idiff Istab Stabilizing current = |I1 | + |I2 | INobj Nominal current of prot. object
Tripping Blocking
Add-on Stabilization
D9DAA3
1
76T@QPDIU
10
11
12
13
14
15
16
17
76T@QPDIU!
D699PITU67
Figure 4-1
258
4.2.2
Transformers
Inrush restaint ratio (2nd harmonic) 10 % to 80 % see also Figure 4-2 (steps 1 %) (steps 1 %)
Harmonic Restraint
I2fN/IfN
Stabilization ratio further (n-th) harmonic 10 % to 80 % (optional 3. or 5.) InfN/IfN see also Figure 4-3 Crossblock function max. action time for Crossblock
can be activated / deactivated 2 to 1000 AC cycles (steps 1 cycles) or 0 (crossblock deactivated) or (active until dropout)
Operating Times
Dropout ratio, approx. Current Matching for Transformers Frequency Matching of vector group Star point conditioning Frequency correction in the range Frequency influence
earthed or non-earthed (for each winding) 0.9 f/fN 1.1 see Figure 4-4
IfN INobj
Blocking
settable e.g. 2nd Harmonic = 15 %
Legend: Idiff Differential current = |I1 + I2 | INobj Nominal current of protected object Current with nominal IfN frequency I2f Current with twice nominal frequency I2f IfN
0.1
0.2
0.3
0.4
0.5
259
4 Technical Data
IfN INobj
/I1REM = 5
settable e.g. n-th Harmonic = 40 % Legend: Idiff Differential current = |I1 + I2 | INobj Nominal current of protected object IfN Current with nominal frequency Current with n-fold Inf nominal frequency (n = 3 or 4) Inf IfN
Blocking
0.2 0.1 0
Figure 4-3
0.1
0.2
0.3
0.4
0.5
0.2
0.4
0.6
0.8
1.0
1.2
1.4
f/fN
260
4.2.3
Operating Times
Dropout ratio, approx. Frequency Frequency correction in the range Frequency influence
IXf INobj 2
Legend: Differential current = |I1 + I2 | Idiff INobj Nominal current of the protected object Current with any frequency IXf in operating range
Tripping
0.2
0.4
0.6
0.8
1.0
1.2
1.4
f/fN
261
4 Technical Data
4.2.4
Dropout ratio, approx. Frequency Frequency correction in the range Frequency influence
262
4.3
Settings
IREF>/INobj REF
(steps 0.01)
TREF
(steps 0.01 s)
Operating Times Pickup time at frequency at 1.5 setting value IEDS>, approx. at 2.5 setting value IEDS>, approx. Dropout time, approx. Dropout ratio, approx. Frequency Frequency influence 0.7 50 Hz 40 ms 37 ms 40 ms 60 Hz 38 ms 32 ms 40 ms
162/3 Hz 100 ms 80 ms 80 ms
IREF IREF> 4
Tripping
3
Blocking
-0.3
-0.2
-0.1
0.0
0.1
0.2
Figure 4-6
Tripping characteristic of the restricted earth fault protection dependent on zero sequence current ratio 3I0"/3I0 (both current in phase or counter-phase)
263
4 Technical Data
4.4
Characteristics
Current Stages
High-current stages
currents times
264
currents times
(acc. ANSI)
times
Pickup time/dropout time phase current stages Pickup time at frequency without inrush restraint, min. without inrush restraint, typical with inrush restraint, min. with inrush restraint, typical Dropout time, typical 50 Hz 20 ms 25 ms 40 ms 45 ms 30 ms 60 Hz 18 ms 23 ms 35 ms 40 ms 30 ms 162/3 Hz 30 ms 45 ms 85 ms 100 ms 80 ms
Pickup time/dropout time residual current stages Pickup time at frequency without inrush restraint, min. without inrush restraint, typical with inrush restraint, min. with inrush restraint, typical Dropout time, typical Drop-out Ratios Inrush Blocking Current stages Inrush blocking ratio (2nd harmonic) Lower operation limit Max. current for blocking Crossblock function between phases max. action time for crossblock
1)
50 Hz 40 ms 45 ms 40 ms 45 ms 30 ms
60 Hz 35 ms 40 ms 35 ms 40 ms 30 ms
approx. 0.95 for I/IN 0.5 10 % to 45 % I2fN/IfN I > 0.2 A 1) 0.03 A to 25.00 A 1) (steps 0.10 A) (steps 1 %)
can be activated/deactivated 0.00 s to 180 s (steps 0.01 s) 1 % in the range 0.9 f/fN 1.1
Frequency
Frequency influence
265
4 Technical Data
100 t [s] 30 20 10
5
3 2 1 0.5 0.3 0.2 0.1 0.05 1
Inverse: (type A)
5
1.6 0.8 0.4 0.2 0.1 0.05 3 2 1 0.5 0.3 0.2 0.2 0.1 0.05 2 3 5 7 10 I/Ip 20
[s]
0.1
0, 14 t = ---------------------------------- T p 0.02 1 (I I ) p
100 t [s]
20 10 5 3 2 1 0.5 0.3 0.2 0.8 0.1 0.05 1 2 3 5 0.05 10 I/Ip 0.1 0.2 20 0.4 1.6 Tp 3.2
200 100
50
30 20 10 5 3 2 1 0.5 1 2 3 5 7 10 I/Ip 0.05 20
[s]
Extremely inverse: (type C) t Tp I Ip tripping time set time multiplier fault current set pickup value
Notes: Shortest trip time for 162/3 Hz is 100 ms. For residual current read 3I0p instead of Ip and T3I0p instead of Tp for earth current read IEp instead of Ip and TIEp instead of Tp for unbalanced load read I2p instead of Ip and TI2p instead of Tp
120 t = --------------------------- T p 1 ( I Ip ) 1
Figure 4-7
Trip time characteristics of inverse time overcurrent protection and unbalanced load protection, according IEC
266
100 t [s] 30 20 10
5
10 3 5 3 2 1 0,5 0,3 0,2 0,1 0,05 1 2 3 5 0,5 10 1 I/Ip 20
Inverse
D [s] 15 10 5
Extremely inverse
20 I/Ip
100 t [s] 50
100 t [s] 30
20 10
D [s] 15 10 5
5
3 2 1 0.5 D [s] 15 10 5
0.3 0.2 0.1 0.05 2 1 0.5 1 2 3 5 10 20 I/Ip 3.992 t = --------------------------- + 0.0982 D [s] 2 ( I Ip ) 1 2
10
Moderately inverse t D I Ip tripping time set time dial fault current set pickup value
I/Ip
20
Very inverse
Notes: Shortest trip time for 16 /3 Hz is 100 ms. For residual current read 3I0p instead of Ip for earth current read IEp instead of Ip for unbalanced load read I2p instead of Ip
Figure 4-8
Trip time characteristics of inverse time overcurrent protection and unbalanced load protection, according ANSI/IEEE
267
4 Technical Data
100 t [s] 30 20 10 5 3 2 1 0.5 0.3 0.2 0.1 0.05 1 2 3 5 10 20 I/Ip 0.4797 t = ---------------------------------------- + 2.1359 D 1.5625 1 ( I Ip ) 2 1 0.5
100 t [s] 50 D [s] 15 10 20 5 10 5 D [s] 15 10 5 3 2 0.5 1 0.5 0.3 0.2 0.1 0.05 1 2 3 5 10 I/Ip
[s] Long inverse 5.6143 t = ------------------------ + 2.18592 D [s] (I I ) 1 p
2 1
20
Definite inverse
100
t [s]
50 30 20 10 5 3 2 1 0.5 0.3 0.2 0.1 t D I Ip tripping time set time dial fault current set pickup value
D [s] 15 10 5
Notes: Shortest trip time for 162/3 Hz is 100 ms. For residual current read 3I0p instead of Ip for earth current read IEp instead of Ip a
0.5
0.05
1 5 10 I/Ip 20
Short inverse
Figure 4-9
268
500 t [s] t [s] 200 100 50 30 20 2 10 1 5 3 2 1 0.5 0.3 0.2 0.1 0.05 0.05 0.1 0.2 0.3 0.5 I/Ip
[s]
500 D [s] D [s] 15 10 50 5 30 20 10 5 0.5 3 2 1 0.5 0.3 0.2 0.1 0.05 1.0 Inverse 0.05 0.1 0.2 0.3 0.5 I/Ip
[s]
200 100
15
10 5 2 1 0.5
1.0
Extremely inverse
5.82 t = --------------------------- D 2 ( I Ip ) 1
500 t [s] 200 100 50 30 20 10 5 3 2 1 0.5 0.3 0.2 0.1 0.05 0.05 0.1 0.2 0.3 0.5 1.0 I/Ip 0.97 Moderately inverse t = ---------------------------- D [s] 2 ( I I p ) 1 t reset time D set time dial I interrupted current Ip set pickup value 2 1 0.5 D [s] 15 10 5
500 t [s] 200 D [s] 100 50 30 20 10 5 3 2 1 0.5 0.3 0.2 0.1 0.05 0.05 0.1 0.2 0.3 0.5
[s]
15 10 5 2 1 0.5
1.0
Very inverse
Notes: For residual current read 3I0p instead of Ip for earth current read IEp instead of Ip for unbalanced load read I2p instead of Ip
4.32 t = --------------------------- D 2 ( I I p ) 1
I/Ip
Figure 4-10
Reset time characteristics of inverse time overcurrent protection and unbalanced load protection with disk emulation, according ANSI/IEEE
269
4 Technical Data
500 t [s] t [s] 200 100 50 30 20 10 5 3 2 1 1 0.5 0.5 0.3 0.2 0.1 0.05 0.05 0.1 0.2 0.3 0.5 I/Ip Definite inverse
1.0394 t = ---------------------------------------- D 1.5625 1 ( I Ip ) [s]
500 200 100 50 D [s] 15 10 5 5 2 3 2 1 0.5 0.3 0.2 0.1 0.05 1.0 30 20 10
D [s]
15
10 5 2 1 0.5
0.05
0.1
0.2 0.3
0.5 I/Ip
1.0
Long inverse
500 t [s] 200 100 50 30 20 10 5 3 2 1 0.5 0.3 0.2 0.1 0.05 0.05 0.1 0.2 0.3 0.5 I/Ip 1.0 2 1 0.5 0,5 D [s] 15 10 5
t D I Ip reset time set time dial interrupted current set pickup value
Notes: For residual current read 3I0p instead of Ip for earth current read IEp instead of Ip
Short inverse
[s]
Figure 4-11
Reset time characteristics of inverse time overcurrent protection with disk emulation, according ANSI/IEEE
270
4.5
Characteristics
Current Stages
High-current stage
IE>> TIE>>
IE> TIE>
Inverse time stages (acc. IEC) Inverse time stages (acc. ANSI)
Tolerances definite time currents times Tolerances inverse time currents (acc. IEC times
3 % of set value or 1 % of nominal current 1 % of set value or 10 ms Pickup at 1.05 I/IEP 1.15 5 % 15 ms at fN = 50/60 Hz 5 % 45 ms at fN = 162/3 Hz for 2 I/IEP 20 and TIEP/s 1 5 % 15 ms at fN = 50/60 Hz 5 % 45 ms at fN = 162/3 Hz for 2 I/IEP 20 and DIEP/s 1
(acc. ANSI)
times
271
4 Technical Data
Pickup time/dropout time Pickup time at frequency without inrush restraint, min. without inrush restraint, typical with inrush restraint, min. with inrush restraint, typical Dropout time, typical 50 Hz 20 ms 25 ms 40 ms 45 ms 30 ms 60 Hz 18 ms 23 ms 35 ms 40 ms 30 ms 162/3 Hz 30 ms 45 ms 85 ms 100 ms 80 ms
Current stages Inrush blocking ratio (2nd harmonic) Lower operation limit Max. current for blocking
1)
approx. 0.95 for I/IN 0.5 10 % to 45 % I2fN/IfN I > 0.2 A 1) 0.30 A to 25.00 A 1) (steps 0.01 A) (steps 1 %)
Frequency
Frequency influence
4.6
Time Control
Accelerated dropout time TStop Time Setting Ranges and Changeover Values Dynamic parameters of current pickups and delay times or time multipliers
1 s to 600 s (= 10 min) (steps 1 s) or (no accelerated dropout) Setting ranges and steps are the same as for the functions to be influenced
272
4.7
Current Stages
3 % of set value or 1 % of nominal current at IN = 1 A or 5 A; 5 % of set value or 3 % of nominal current at IN = 0.1 A 1 % of set value or 10 ms
times
The set definite times are pure delay times.
1) 2)
Secondary values based on IN = 1 A; for IN = 5 A they must be multiplied by 5. Secondary values for high-sensitivity current input I7, independent of nominal current.
Operating Times
Pickup time/dropout time Pickup time at frequency minimum typical Dropout time, typical 50 Hz 20 ms 30 ms 30 ms 60 Hz 18 ms 25 ms 27 ms 162/3 Hz 35 ms 80 ms 80 ms
approx. 0.95 for I/IN 0.5 1 % in the range 0.9 f/fN 1.1
273
4 Technical Data
4.8
Characteristics
Reset characteristics (IT) (acc. ANSI with disk emulation) Operating range
1
Current Stages
High-current stage
I2>> TI2>>
(steps 0.01 A) (steps 0.01 s) (steps 0.01 A) (steps 0.01 s) (steps 0.01 A) (steps 0.01 s) (steps 0.01 A) (steps 0.01 s)
I2> TI2>
Inverse time stages (acc. IEC) Inverse time stages (acc. ANSI)
Tolerances definite time currents times Tolerances inverse time currents (acc. IEC times
3 % of set value or 1 % of nominal current 1 % of set value or 10 ms Pickup at 1.05 I2/I2P 1.15; 5 % 15 ms at fN = 50/60 Hz 5 % 45 ms at fN = 162/3 Hz for 2 I2/2IP 20 and TI2P/s 1 5 % 15 ms at fN = 50/60 Hz 5 % 45 ms at fN = 162/3 Hz for 2 I2/2IP 20 and DI2P/s 1
(acc. ANSI)
times
The set definite times are pure delay times. 1) Secondary values based on I = 1 A; for I = 5 A they must be multiplied by 5. N N
Pickup time/dropout time Pickup time at frequency minimum typical Dropout time, typical 50 Hz 50 ms 55 ms 30 ms 60 Hz 45 ms 50 ms 30 ms 162/3 Hz 100 ms 130 ms 70 ms
approx. 0.95 for I2/IN 0.5 1 % in the range 0.9 f/fN 1.1
7UT612 Manual C53000G1176C1481
4.9
4.9.1
Setting Ranges
Cooling down factor at motor stand-still (for motors) Kfactor Thermal alarm stage Current alarm stage Start-up recognition (for motors) alarm/trip Ialarm Istart-up
(steps 0.01 A)
Dropout Ratios
dropout at alarm approx. 0.99 approx. 0.97 2 % or 10 mA 1); class 2 % acc. IEC 60 2558
Tolerances
1)
275
4 Technical Data
100 t [min] 50
Parameter: Setting Value Time Constant
100 t [min] 50
30 [min] 20 1000
30 20
10
500
10
5
200 3 2 100
[min] 1000
3 2
500
1 50
1 200
0.5 100
0.3 0.2
50
0.1 5
0.1 20
0.05 1 2 3 4
1 5
2 6 7 8 10 12 I / (kIN)
0.05 1 2
2 3 4
5 5
10 6 7 8 10 12
without preload:
2 I ------------- k I N t = ln ------------------------------- [min] 2 I ------------- 1 k I N
with 90 % preload:
2
I / (kIN)
Figure 4-12
I pre 2 I ------------- ------------- - k I k I N N t = ln --------------------------------------------------- [min] 2 I ------------- 1 k I N Trip time characteristics of the overload protection with thermal replica
276
4.9.2
Temperature Detectors
For hot-spot calculation one temperature detector must be connected. Cooling Cooling method ON (oil natural) OF (oil forced) OD (oil directed) Y 1.6 to 2.0 22 to 29 98 C to 140 C 208 F to 284 F 98 C to 140 C 208 F to 284 F 0.125 to 128.000 0.125 to 128.000 (steps 0.1) (steps 1) (steps 1 C) (steps 1 F) (steps 1 C) (steps 1 F) (steps 0.001) (steps 0.001)
Oil exponent
Hot-spot to top-oil gradient Hgr Annunciation Thresholds Warning temperature hot-spot or Alarm temperature hot-spot or Warning aging rate Alarm aging rate
4.10
Temperature Detectors
Annunciation Thresholds
For each measuring point: Warning temperature (stage 1) or Alarm temperature (stage 2) or 50 C to 250 C 58 F to 482 F or (no warning) 50 C to 250 C 58 F to 482 F or (no alarm) (steps 1 C) (steps 1 F) (steps 1 C) (steps 1 F)
277
4 Technical Data
4.11
(steps 0.01 A)
approx. 0.9 for I 0.25 A 1) 5 % of set value or 0.01 A 1) binary input for CB auxiliary contact
internal trip external trip (via binary input) approx. 3 ms with measured quantities present; approx. 20 ms after switch-on of measured quantities, fN = 50/60 Hz; approx. 60 ms after switch-on of measured quantities, fN = 16 2/3 Hz 30 ms at fN = 50/60 Hz, 90 ms at fN = 16 2/3 Hz 0.00 s to 60.00 s; (steps 0.01 s) 1 % of setting value or 10 ms
Reset time (incl. output relay) Delay times for all stages Time tolerance
4.12
2 approx. 12.5 ms min. approx. 25 ms typical approx. 25 ms 0.00 s to 60.00 s (steps 0.01 s) 1 % of set value or 10 ms
Transformer Annunciations
External annunciations
278
4.13
Monitoring Functions
Current symmetry (for each side) BAL. FAKT. I BAL. I LIMIT Phase rotation | Imin | / |Imax | < %$/ )$.7 , if Imax / IN > %$/ , /,0,7 / IN 0.10 to 0.90 (steps 0.01) (steps 0.01 A) 0.10 A to 1.00 A 1) IL1 before IL2 before IL3 (clockwise) or IL1 before IL3 before IL2 (counter-clockwise) if |IL1|, |IL2|, |IL3| > 0.5 IN 1 with 1 binary input or with 2 binary inputs
Measured Quantities
279
4 Technical Data
4.14
Ancillary Functions
Operational measured values of currents 3-phase for each side Tolerance at IN = 1 A or 5 A Tolerance at IN = 0.1 A IL1; IL2; IL3 in A primary and secondary and % of INobj 1 % of measured value or 1 % of IN 2 % of measured value or 2 % of IN
Operational measured values of currents 3I0; I1; I2 3-phase for each side in A primary and secondary and % of INobj Tolerance 2 % of measured value or 2 % of IN Operational measured values of currents I1 to I7; 1-phase for each feeder in A primary and secondary and % of INobj Tolerance 2 % of measured value or 2 % of IN Operational measured values of currents I8 for high-sensitivity input in A primary and mA secondary Tolerance 1 % of measured value or 2 mA Phase angles of currents 3-phase for each side Tolerance Phase angles of currents 1-phase for each feeder Tolerance Operational measured values of frequency Range Tolerance Operational measured values of power with applied or nominal voltage Operational measured values for thermal value Operational measured values (Temperature acc. IEC 60354) Measured values of differential protection (IL1); (IL2); (IL3) in referred to (IL1) 1 at rated current (IL1) to (IL7) in referred to (IL1) 1 at rated current f in Hz and % of fN 10 Hz to 75 Hz 1 % within range fN 10 % at I = IN S (apparent power) in kVA; MVA; GVA primary L1; L2; L3; res referred to tripping temperature rise trip RTD1 to RTD12 in C or F relative aging rate, load reserve IDIFFL1; IDIFFL2; IDIFFL3; IREST L1; IRESTL2; IRESTL3 in % of operational rated current 2 % of meas. value or 2 % of IN (50/60 Hz) 3 % of meas. value or 3 % of IN (162/3 Hz) IdiffREF; IRestREF in % of operational rated current 2 % of meas. value or 2 % of IN (50/60 Hz) 3 % of meas. value or 3 % of IN (162/3 Hz) with a total of max. 200 messages
Tolerance (with preset values) Measured values of restricted earth fault protection Tolerance (with preset values) Fault Event Data Log Storage of the messages of the last 8 faults
280
Fault Recording
Number of stored fault records Storage period (start with pickup or trip) Sampling rate at fN = 50 Hz Sampling rate at fN = 60 Hz Sampling rate at fN = 162/3 Hz
Statistics
Number of trip events caused by 7UT612 Total of interrupted currents caused by 7UT612 Operating hours criterion segregated for each pole and each side Up to 7 decimal digits Excess of current threshold (%UHDNHU 6 ,! or %UHDNHU 6 ,!) 1 ms 1 ms 3 V/1 Ah, type CR 1/2 AA Self-discharging time approx. 10 years
Resolution for operational messages Resolution for fault messages Buffer battery
Time Synchronization
Operation modes: Internal IEC 608705103 Time signal IRIG B Time signal DCF77 Time signal synchro-box Pulse via binary input Internal via RTC External via system interface (IEC 608705103) External via IRIG B External, via time signal DCF77 External, via synchro-box External with pulse via binary input
Processing times for function blocks: Block, Basic requirements 5 TICKS Beginning with the 3rd additional input for generic blocks per input 1 TICK Logic function with input margin 6 TICKS Logical function with output margin 7 TICKS In addition to each chart 1 TICK Maximum number of TICKS in sequence levels: 0:B%($5% (processing of meas. values) 3/&B%($5% (slow PLC processing) 3/&B%($5% (fast PLC processing) 6)6B%($5% (switchgear interlocking) 1200 TICKS 255 TICKS 90 TICKS 1000 TICKS
281
4 Technical Data
4.15
Dimensions
29.5
34
29.5
29 30 150 145
266
244
266
244
2
Q
34
Rear View
146 +2
5 or M4
0.3
255.8
245
+1
Dimensions in mm
5.4
13.2 7.3
105
131.5
0.5 0.3
Panel Cut-Out
Figure 4-13
282
4.15 Dimensions
165 144
31 46 45 60
10.5
260 29.5
1 16
15 30
266
150
Dimensions in mm
Figure 4-14
Thermobox
58 48 25 16.5 3 105
61.8
90
116
45
Side view 3 Locks (Locked) for Snap-on Mounting on Standard Rail Dimensions in mm 140 Front view 3 Locks (Unlocked) for Wall Mounting with Screws Lock Hole 4.2 mm
Figure 4-15
98
283
4 Technical Data
284
Appendix
A
This appendix is primarily a reference for the experienced user. This Chapter provides ordering information for the models of 7UT612. General diagrams indicating the terminal connections of the 7UT612 models are included. Connection examples show the proper connections of the device to primary equipment in typical power system configurations. Tables with all settings and all information available in a 7UT612 equipped with all options are provided.
Ordering Information and Accessories General Diagrams Connection Examples Assignment of the Protection Functions to Protected Objects Preset Configurations Protocol Dependent Functions List of Settings List of Information List of Measured Values
285
A Appendix
A.1
Differential Protection
Rated Current IN = 1 A IN = 5 A Auxiliary Voltage (Power Supply, Pick-up Threshold of Binary Inputs) DC 24 V to 48 V, binary input threshold 17 V 2) DC 60 V to 125 V 1), binary input threshold 17 V 2) DC 110 V to 250 V 1), AC 115 to 230 V, binary input threshold 73 V 2) Housing / Number of In- and Outputs BI: Binary Inputs, BO: Binary Outputs Surface mounting housing with two-tier terminals, 1/3 19", 3 BI, 4 BO, 1 life contact Flush mounting housing with plug-in terminals, 1/3 19", 3 BI, 4 BO, 1 life contact Flush mounting housing with screwed terminals, 1/3 19", 3 BI, 4 BO, 1 life contact Region-Specific Default / Language Settings and Function Versions Region GE, 50/60 Hz, 16 2/3 Hz, language German (language can be changed) Region world, 50/60 Hz, 16 2/3 Hz, language English, (language can be changed) Region US, 60/50 Hz, language US-English (language can be changed) Region world, 50/60 Hz, 16 2/3 Hz, language Spanish (language can be changed) System Interface: Functionality and Hardware (Port B) No system interface IEC Protocol, electrical RS232 IEC Protocol, electrical RS485 IEC Protocol, optical 820 nm, ST-plug Profibus FMS Slave, electrical RS485 Profibus FMS Slave, optical, single-ring, ST-connector Profibus FMS Slave, optical, double-ring, ST-connector For further interfaces see additional specification L
7UT612
A0
1 5
2 4 5
B D E
A B C E
0 1 2 3 4 5 6 9 + L 0
Additional Specification L Profibus DP Slave, RS485 Profibus DP Slave, optical 820 nm, double-ring, ST-connector Modbus, RS485 Modbus, optical 820 nm, ST-connector DNP, RS485 DNP, optical 820 nm, STconnector DIGSI / Modem Interface / Thermobox (Port C) No DIGSI interface on the rear side DIGSI / Modem, electrical RS232 DIGSI / Modem / Thermobox, electrical RS485 DIGSI / Modem / Thermobox, optical 820 nm, ST-connector
1) 2
A B D E G H
0 1 2 3
with plug-in jumper one of 2 voltage ranges can be selected ) for each binary input one of 2 pickup threshold ranges can be selected with plug-in jumpers see page A-3
286
Differential Protection
Functionality Measured Values Basic measured values Basic measured values, transformer monitoring functions (connection to thermobox / hot spot, overload factor) Differential Protection + Basic Functions Differential protection for transformer, generator, motor, busbar (87) Overload protection according to IEC for 1 winding (49) Lock out (86) Time overcurrent protection phases (50/51): I>, I>>, Ip (inrush stabilization) Time overcurrent protection 3I0 (50N/51N): 3I0>, 3I0>>, 3I0p (inrush stabilization) Time overcurrent protection earth (50G/51G): IE>, IE>>, IEp (inrush stabilization)
7UT612
9 10 11 12
13 14 15 16
A0
1 4 A
Differential Protection + Basic Functions + Additional Functions Restricted earth fault protection, low impedance (87G) Restricted earth fault protection, high impedance (87G without resistor and varistor), O/C 1-phase Trip circuit supervision (74TC) Unbalanced load protection (46) Breaker failure protection (50BF) High-sensitivity time overcurrent protection / tank leakage protection (64), O/C 1-phase Ordering example: 7UT61214EA911AA0 +L0A Differential protection here: pos. 11 = 9 pointing at L0A, i.e. version with Profibus-interface DP Slave, RS485
287
A Appendix
A.1.1
Accessories
For up to 6 temperature measuring points (at most 2 devices can be connected to 7UT612)
Name Thermobox, UN = 24 to 60 V AC/DC Thermobox, UN = 90 to 240 V AC/DC Order No. 7XV56622AD10 7XV56625AD10
Thermobox
Interface Modules
Covering cap for terminal block type 18 terminal voltage block, 12 terminal current block 12 terminal voltage block, 8 terminal current block
Short-Circuit Links
Short-circuit links for purpose / terminal type Voltage block, 18 terminal, 12 terminal Current block,12 terminal, 8 terminal Order No. C73334-A1C341 C73334-A1C331
288
Battery
Lithium battery 3 V/1 Ah, Type CR 1/2 AA VARTA Order No. 6127 101 501
Interface Cable
An interface cable is necessary for the communication between the SIPROTEC device and a computer. Requirements for the computer are Windows 95 or Windows NT4 and the operating software DIGSI 4.
Interface cable between PC or SIPROTEC device Cable with 9-pin male / female connections Order No. 7XV51004
Software for graphical visualization, analysis, and evaluation of fault data. Option package of the complete version of DIGSI 4
Graphical analysis program DIGRA Full version with license for 10 machines Order No. 7XS54100AA0
Graphic Tools
Software for graphically supported configuration of characteristic curves and provide zone diagrams for overcurrent and distance protection devices. (Option package for the complete version of DIGSI 4)
Graphic Tools 4 Full version with license for 10 machines Order No. 7XS54300AA0
DIGSI REMOTE 4
Software for remotely operating protection devices via a modem (and possibly a star connector) using DIGSI 4. (Option package for the complete version of DIGSI 4).
DIGSI REMOTE 4 Full version with license for 10 machines Order No. 7XS54401AA0
289
A Appendix
SIMATIC CFC 4
Software for graphical configuration of interlocking (latching) conditions and creating additional functions in SIPROTEC 4 devices. (Option package for the complete version of DIGSI 4).
SIMATIC CFC 4 Full version with license for 10 machines Order No. 7XS54500AA0
Varistor
290
A.2
A.2.1
General Diagrams
Panel Flush Mounting or Cubicle Mounting
7UT612D/E
Q1 Q2 Q3 Q4 Q5 Q6 Q7 Q8 R1 R2 R3 R4 R5 R6 R7 R8 F14 F15 F16 F17 F18 IL1S1/I1 IL2S1/I2 BO2 IL3S1/I3 I7 IL1S2/I4 IL2S2/I5 IL3S2/I6 I8 Lifecontact Power supply
+
(~)
BO1
1 2 3 2
1 2 3 2
BO3 BO4
F3 F4 F5 F1 F2
Time synchronization
Interference suppression capacitors at the relay contacts, Ceramic, 4.7 nF, 250 V
Figure A-1
Assignment of Pins of Interfaces see Table 3-8 and 3-9 in Subsection 3.1.3
291
A Appendix
A.2.2
7UT612B
15 30 14 29 13 28 12 27 9 24 8 23 7 22 6 21 48 32 47 31 46 IL1S1/I1 IL2S1/I2 BO2 IL3S1/I3 I7 IL1S2/I4 IL2S2/I5 IL3S2/I6 I8 Life contact Power supply
+
(~)
BO1
1 2 3 2 1 2 3 2
39 54 38 53 35 50 34 49
BO3 BO4
52 36 51 10 11 Earthing terminal (16) 2 17 3 18 4 19 1 IN SYNC IN 12 V COM SYNC COMMON IN 5 V IN 24 V Screen Assignment of Pins of Interfaces seeTable 3-8 in Subsection 3.1.3 Interference suppression capacitors at the relay contacts, Ceramic, 4.7 nF, 250 V 7UT612 Manual C53000G1176C1481
Time synchronization
Figure A-2
292
A.3
Connection Examples
Side 2 Side 1
L1 L2 L3
P2
P1
P1
P2
L1 L2 L3
S2
S1
S1
S2
24 8
R2 R3
Q2 Q3
30 14
23 7
R4 R5
IL2S2
IL2S1
Q4 Q5
29 13
22
R6
IL3S2
IL3S1
Q6
28
7UT612
L1 L2 L3
Side 2
P2
P1
P1
P2
Side 1
L1 L2 L3
S2
S1
S1
S2
24 8
R2 R3
Q2 Q3
30 14
23 7
R4 R5
IL2S2
IL2S1
Q4 Q5
29 13
22
R6
IL3S2
IL3S1
Q6
28
7UT612
Figure A-3
Connection example 7UT612 for a three-phase power transformer without (above) and with (below) earthed starpoint
293
A Appendix
L1 L2 L3
Side 2
P2
P1
P1
P2
Side 1
L1 L2 L3
S2
S1 P1 S1
S1
S2
P2
S2
27 Q8 Q1 IL1S1 15
Q2 Q3
30 14
23 7
R4 R5
IL2S1
Q4 Q5
29 13
22
R6
IL3S2 7UT612
IL3S1
Q6
28
Figure A-4
Connection example 7UT612 for a three-phase power transformer with current transformer between starpoint and earthing point
294
Side 2
L1 L2 L3
P2
P1
P1
P2
Side 1
L1 L2 L3
S2
S1
S1
S2
P2 S2
P1 S1
27 Q8 Q1 IL1S1 15
Q2 Q3
30 14
23 7
R4 R5
IL2S1
Q4 Q5
29 13
22
R6
IL3S2 7UT612
IL3S1
Q6
28
Figure A-5
Connection example 7UT612 for a three-phase power transformer with neutral earthing reactor and current transformer between starpoint and earthing point
295
A Appendix
L1 L2 L3
Side 2
P2
P1 P1 P2
Side 1
L1 L2
S2 S1 P1 S1 S1 S2
L3
P2
S2
27 Q8 Q1 IL1S1 15
Q2 Q3
30 14
23 7
R4 R5
IL2S1
Q4 Q5
29 13
22
R6
IL3S2 7UT612
IL3S1
Q6
28
Figure A-6
Connection example 7UT612 for a three-phase auto-transformer with current transformer between starpoint and earthing point
L1 L3
Side 2
P2
P1 P1
Side 1
P2
L1 L3
S2
S1 P1 S1 S1 S2
P2
S2
27 Q8 Q1 IL1S1 15
Q2 Q3
30 14
23 7
R4 R5
IL2S1
Q4 Q5
29 13
22
R6
IL3S2 7UT612
IL3S1
Q6
28
Figure A-7
Connection example 7UT612 for a single-phase power transformer with current transformer between starpoint and earthing point
296
L1 L3
Side 2
P2
P1
P1 S1
P2 S2
Side 1
L1 L3
S2
S1
24 8
R2 R3
Q2 Q3
30 14
23 7
R4 R5
IL2S2
IL2S1
Q4 Q5
29 13
22
R6
IL3S2 7UT612
IL3S1
Q6
28
Figure A-8
Connection example 7UT612 for a single-phase power transformer with only one current transformer (right side)
Side 2
P2
P1
P1
P2
Side 1
L1 L2 L3
S2
S1
S1
S2
24 8
R2 R3
Q2 Q3
30 14
23 7
R4 R5
IL2S2
IL2S1
Q4 Q5
29 13
22
R6
IL3S2
IL3S1
Q6
28
7UT612
Figure A-9
297
A Appendix
Side 2
P2 P1
Side 1P2
P1
L1
L2
S2
S1
L3
S2
S1
24 8
R2 R3
Q2 Q3
30 14
23 7
R4 R5
IL2S2
IL2S1
Q4 Q5
29 13
22
R6
IL3S2
IL3S1
Q6
28
7UT612
Figure A-10
Connection example 7UT612 as transversal differential protection for a generator with two windings per phase
298
Side 2
L1 L2 L3
P2
P1
P1
P2
Side 1
L1 L2 L3
S2
S1
S1
S2
P1
S1
P2
S2
12 Q7
27 Q8 Q1 I7 IL1S1 15
24 8
R2 R3
Q2 Q3
30 14
23 7
R4 R5
IL2S2
IL2S1
Q4 Q5
29 13
22
R6
IL3S2 7UT612
IL3S1
Q6
28
Figure A-11
Connection example 7UT612 for an earthed shunt reactor with current transformer between starpoint and earthing point
299
A Appendix
P1
P2
L1 L2 L3
S1 P1 S1
S2
V
P2 S2
R 27 Q8 Q1 15
24 8
R2 R3
IL1S1
Q2 Q3
30 14
23 7
R4 R5
IL2S2
IL2S1
Q4 Q5
29 13
22
R6
IL3S2 7UT612
IL3S1
Q6
28
Figure A-12
Connection example 7UT612 as high-impedance protection on a transformer winding with earthed starpoint (the illustration shows the partial connection of the high-impedance protection)
300
L1 L2 L3
Side 2
P2
P1
P1
P2
P1
P2
Side 1
L1 L2 L3
S2
S1 P1 S1
S1
S2
S1
S2
P2 P1
S2 S1
P2
S2
R 27 Q8 6 R7 21 R8 Q1 I7 I8 IL1S1 Q2 Q3 30 14 15
24 8
R2 R3
23 7
R4 R5
IL2S2
IL2S1
Q4 Q5
29 13
22
R6
IL3S2 7UT612
IL3S1
Q6
28
Figure A-13
Connection example 7UT612 for a three-phase power transformer with current transformers between starpoint and earthing point, additional connection for high-impedance protection
301
A Appendix
Feeder 1
Feeder 2
Feeder 3
Feeder 4
Feeder 5
Feeder 6
Feeder 7 L1 L2 L3
P1
S1
P1
S1
P1
S1
P1
S1
P1
S1
P1
S1
P1
S1
P2
S2
P2
S2
P2
S2
P2
S2
P2
S2
P2
S2
P2
S2
30 14
Q2 Q3
R2 R3
24 8
29 13
Q4 Q5
I2
I5
R4 R5
23 7
28
Q6
I3
I6
R6 Q7
22 12
I7 7UT612
Q8
27
Figure A-14
302
Feeder 1
Feeder 2
Feeder 7 L1 L2 L3
P1
S1 S2
P1
S1 S2
P1
S1 S2
P2
P2
P2
L1 SCT
L2
L3
L1 SCT
L2
L3
L1 SCT
L2
L3
30 14
Q2 Q3
R2 R3
24 8
29 13
Q4 Q5
I2
I5
R4 R5
23 7
28
Q6
I3
I6
R6 Q7
22 12
I7 7UT612
Q8
27
Figure A-15
Connection example 7UT612 as busbar protection, connected via external summation current transformers (SCT) partial illustration for feeders 1, 2 and 7
303
A Appendix
A.4
Table A-1
Overview of protection functions available in protected objects Two-Winding Transformer X X X X X X X X X X X X X X X X Function available 1-Phase AutoTransformer Transformer X X X X X X X X X X X X X X X X X X X X X X X X X X X Generator / Motor X X X X X X X X X X X X X X X Busbar 3-phase X X X X X X X X X X X X X X Busbar 1-phase X X X X X X X
Protection Function Differential protection Restricted earth fault protection Time overcurrent protection phases Time overcurrent protection 3I0 Time overcurrent protection earth Time overcurrent protection 1-phase Unbalanced load protection Overload protection IEC 602558 Overload protection IEC 60354 Circuit breaker failure protection Measured value monitoring Trip circuit supervision External trip command 1 External trip command 2 Measured values Legend:
304
A.5
Preset Configurations
Binary Inputs
Table A-2 Preset binary inputs LCD Text >Reset LED >Buchh. Trip FNo 00005 00392 Remarks Reset of latched indications, Hactive Buchholz protection trip, Hactive No presetting Binary Input BI1 BI2 BI3
Preset binary outputs LCD Text Relay TRIP Relay PICKUP >Buchh. Trip Error Sum Alarm Alarm Sum Event FNo 00511 00501 00392 00140 00160 Remarks Device (general) trip command, non-latched Device (general) pickup, non-latched Buchholz protection trip, non-latched Group alarm of errors and disturbances, non-latched
LED Indicators
Table A-4 LED LED1 LED2 LED3 LED4 LED5 LED6 LED7 Preset LED indicators LCD Text Relay TRIP Relay PICKUP >Buchh. Trip Error Sum Alarm Alarm Sum Event Fault Configur. FNo 00511 00501 00392 00140 00160 00311 Remarks Device (general) trip command, latched Device (general) pickup, latched Buchholz protection trip, latched no presetting no presetting Group alarm of errors and disturbances, non-latched Errors during configuration or setting (inconsistent settings), non-latched
305
A Appendix
Preset CFCCharts
7UT612 provides worksheets with preset CFC-charts. Figure A-16 shows a chart which changes binary input !'DWD6WRS from single point indication (SP) to internal single point indication (IntSP). According to Figure A-17 an reclosure interlocking will be produced. It interlocks the closure of the circuit breaker after tripping of the device until manual acknowledgement.
"IN: 9rvpr39hhTTQ"
"OUT: 9rvprVypx9UDTQ"
Figure A-16
"OUT: BUSQRvD"
Figure A-17
306
A.6
Protocol Profibus FMS Profibus DP DNP3.0 Modbus ASCII/RTU Additional Service Interface (optional) Yes Yes Yes
IEC 608705103
Function Yes Yes Yes Yes No Only via additional service interface No Only via additional service interface User-defined annunciations in CFC (pre-defined) Via protocol; DCF77/IRIG B; Interface; Binary inputs Yes No No Only via additional service interface User-defined annunciations in CFC (pre-defined) Via DCF77/IRIG B; Interface; Binary inputs No Only via additional service interface Yes Yes Yes Yes
Yes
Metered Values
Yes
Fault Recording
Yes
Protection Setting from Remote Yes User-defined annunciations in CFC (pre-defined) Via DCF77/IRIG B; Interface; Binary inputs No
Yes
Yes Yes
User-specified annunciations and switching objects Via protocol; DCF77/IRIG B; Interface; Binary inputs Yes
Yes
Time Synchronization
Yes
Yes
Yes
Generate Test Annunciations Asynchronous cyclical / event Up to 1.5 MBaud RS485 Optical fibre Single ring Double ring cyclical Up to 1.5 MBaud RS485 Optical fibre Double ring Asynchronous
Yes
No
Yes
Physical Mode
Asynchronous
Transmission Mode
cyclical / event
Baudrate
4800 to 38400
Type
Yes
307
A Appendix
A.7
Notes:
List of Settings
Depending on the version and the variant ordered some addresses may be missing or have different default settings. The setting ranges and presettings listed in the following table refer to a nominal current value IN = 1 A. For a secondary nominal current value IN = 5 A the current values are to be multiplied by 5. For setting primary values the transformation ratio of the transformer also must be taken into consideration. Addresses which have an A attached to its end can only be changed in DIGSI 4, under Additional Settings.
Addr.
103
Setting Title
Grp Chge OPTION Disabled Enabled Disabled Enabled
Setting Options
Default Setting
Disabled
Comments
Setting Group Change Option
103
Disabled
105
PROT. OBJECT
3 phase Transformer 1 phase Transformer Autotransformer Generator/Motor 3 phase Busbar 1 phase Busbar 3 phase Transformer 1 phase Transformer Autotransformer Generator/Motor 3 phase Busbar 1 phase Busbar 2 2 3 4 5 6 7 3 4 5 6 7 not used Side 1 Side 2 not used Side 1 Side 2 Disabled Enabled Disabled Enabled Disabled Side 1 Side 2
3 phase Transformer
Protection Object
105
PROT. OBJECT
3 phase Transformer
Protection Object
2 2 7
Number of Sides for Multi Phase Object Number of Sides for Multi Phase Object Number of Ends for 1 Phase Busbar
107
NUMBER OF ENDS
108
I7-CT CONNECT.
not used
I7-CT connected to
108
I7-CT CONNECT.
not used
I7-CT connected to
112
DIFF. PROT.
Enabled
Differential Protection
112
DIFF. PROT.
Enabled
Differential Protection
113
REF PROT.
Disabled
308
Addr.
113
Setting Title
REF PROT. Disabled Side 1 Side 2 Disabled Enabled Disabled Enabled Disabled Side 1 Side 2 Disabled Side 1 Side 2
Setting Options
Default Setting
Disabled
Comments
Restricted earth fault protection
117
Coldload Pickup
Disabled
117
Coldload Pickup
Disabled
120
DMT/IDMT Phase
Disabled
120
DMT/IDMT Phase
Disabled
121
DMT/IDMT PH. CH
Definite Time only Time Overcurrent Curve IEC Time Overcurrent Curve ANSI User Defined Pickup Curve User Defined Pickup and Reset Curve Definite Time only Time Overcurrent Curve IEC Time Overcurrent Curve ANSI User Defined Pickup Curve User Defined Pickup and Reset Curve Disabled Side 1 Side 2 Disabled Side 1 Side 2 Definite Time only Time Overcurrent Curve IEC Time Overcurrent Curve ANSI User Defined Pickup Curve User Defined Pickup and Reset Curve Definite Time only Time Overcurrent Curve IEC Time Overcurrent Curve ANSI User Defined Pickup Curve User Defined Pickup and Reset Curve Disabled unsensitive Current Transformer I7 Disabled unsensitive Current Transformer I7 Definite Time only Time Overcurrent Curve IEC Time Overcurrent Curve ANSI User Defined Pickup Curve User Defined Pickup and Reset Curve Definite Time only Time Overcurrent Curve IEC Time Overcurrent Curve ANSI User Defined Pickup Curve User Defined Pickup and Reset Curve Disabled unsensitive Current Transformer I7 sensitive Current Transformer I8 Disabled unsensitive Current Transformer I7 sensitive Current Transformer I8
121
DMT/IDMT PH. CH
122
DMT/IDMT 3I0
Disabled
122
DMT/IDMT 3I0
Disabled
123
DMT/IDMT 3I0 CH
123
DMT/IDMT 3I0 CH
124
DMT/IDMT Earth
Disabled
124
DMT/IDMT Earth
Disabled
125
DMT/IDMT E CHR.
125
DMT/IDMT E CHR.
127
DMT 1PHASE
Disabled
DMT 1Phase
127
DMT 1PHASE
Disabled
DMT 1Phase
309
A Appendix
Addr.
140
Setting Title
UNBALANCE LOAD Disabled Side 1 Side 2 Disabled Side 1 Side 2
Setting Options
Default Setting
Disabled
Comments
Unbalance Load (Negative Sequence)
140
UNBALANCE LOAD
Disabled
141
Definite Time only Time Overcurrent Curve IEC Time Overcurrent Curve ANSI Definite Time only Time Overcurrent Curve IEC Time Overcurrent Curve ANSI Disabled Side 1 Side 2 Disabled Side 1 Side 2 classical (according IEC60255) according IEC354 classical (according IEC60255) according IEC354 Disabled Side 1 Side 2 Disabled Side 1 Side 2 Disabled Enabled Disabled Enabled Disabled with 2 Binary Inputs with 1 Binary Input Disabled with 2 Binary Inputs with 1 Binary Input Disabled Enabled Disabled Enabled Disabled Enabled Disabled Enabled Disabled Port C Disabled Port C 6 RTD simplex operation 6 RTD half duplex operation 12 RTD half duplex operation 6 RTD simplex operation 6 RTD half duplex operation 12 RTD half duplex operation
141
142
Therm.Overload
Disabled
142
Therm.Overload
Disabled
143
Therm.O/L CHR.
143
Therm.O/L CHR.
170
BREAKER FAILURE
Disabled
170
BREAKER FAILURE
Disabled
181
M.V. SUPERV
Enabled
181
M.V. SUPERV
Enabled
182
Disabled
182
Disabled
186
EXT. TRIP 1
Disabled
186
EXT. TRIP 1
Disabled
187
EXT. TRIP 2
Disabled
187
EXT. TRIP 2
Disabled
190
RTD-BOX INPUT
Disabled
190
RTD-BOX INPUT
Disabled
191
RTD CONNECTION
191
RTD CONNECTION
310
Addr .
201
Setting Title
STRPNT->OBJ S1
Function
Power System Data 1
Setting Options
YES NO 1..100000 A 1A 5A YES NO 1..100000 A 1A 5A YES NO 1..100000 A 1A 5A 0.1A YES NO 1..100000 A 1A 5A 0.1A YES NO 1..100000 A 1A 5A 0.1A YES NO 1..100000 A 1A 5A 0.1A YES NO 1..100000 A 1A 5A 0.1A YES NO 1..100000 A 1A 5A 0.1A Terminal Q7 Terminal Q8
Default Setting
YES
Comments
CT-Strpnt. Side1 in Direct. of Object
202 203
IN-PRI CT S1 IN-SEC CT S1
200 A 1A
206
STRPNT->OBJ S2
YES
207 208
IN-PRI CT S2 IN-SEC CT S2
2000 A 1A
211
STRPNT->BUS I1
YES
212 213
IN-PRI CT I1 IN-SEC CT I1
200 A 1A
214
STRPNT->BUS I2
YES
215 216
IN-PRI CT I2 IN-SEC CT I2
200 A 1A
217
STRPNT->BUS I3
YES
218 219
IN-PRI CT I3 IN-SEC CT I3
200 A 1A
221
STRPNT->BUS I4
YES
222 223
IN-PRI CT I4 IN-SEC CT I4
200 A 1A
224
STRPNT->BUS I5
YES
225 226
IN-PRI CT I5 IN-SEC CT I5
200 A 1A
227
STRPNT->BUS I6
YES
228 229
IN-PRI CT I6 IN-SEC CT I6
200 A 1A
230
EARTH. ELECTROD
Terminal Q7
311
A Appendix
Addr .
231
Setting Title
STRPNT->BUS I7
Function
Power System Data 1
Setting Options
YES NO 1..100000 A 1A 5A 0.1A 1.0..300.0
Default Setting
YES
Comments
CT-Starpoint I7 in Direction of Busbar
232 233
IN-PRI CT I7 IN-SEC CT I7
200 A 1A
235
Factor I8
60.0
Factor: Prim. Current over Sek. Curr. I8 Rated Primary Voltage Side 1 Starpoint of Side 1 is
240 241
0.4..800.0 kV Solid Earthed Isolated Y (Wye) D (Delta) Z (Zig-Zag) 0.4..800.0 kV Solid Earthed Isolated Y (Wye) D (Delta) Z (Zig-Zag) 0..11 0.20..5000.00 MVA
242
CONNECTION S1
Y (Wye)
243 244
245
CONNECTION S2
Y (Wye)
246 249
0 38.10 MVA
Vector Group Numeral of Side 2 Rated Apparent Power of the Transformer Rated Primary Voltage Generator/ Motor Rated Apparent Power of the Generator Rated Primary Voltage Busbar Primary Operating Current Phase selection
251
UN GEN/MOTOR
0.4..800.0 kV
21.0 kV
252
SN GEN/MOTOR
0.20..5000.00 MVA
70.00 MVA
0.4..800.0 kV 1..100000 A Phase 1 Phase 2 Phase 3 50 Hz 60 Hz 16 2/3 Hz L1 L2 L3 L1 L3 L2 Degree Celsius Degree Fahrenheit 0.01..32.00 sec 0.04..1.00 A 0.04..1.00 A 0.04..1.00 A Group A Group B Group C Group D Binary Input Protocol
270
Rated Frequency
50 Hz
Rated Frequency
271
PHASE SEQ.
L1 L2 L3
Phase Sequence
276
TEMP. UNIT
Degree Celsius
TMin TRIP CMD Breaker S1 I> Breaker S2 I> Breaker I7 I> CHANGE
Power System Data 1 Power System Data 1 Power System Data 1 Power System Data 1 Change Group
Minimum TRIP Command Duration Clos. Breaker Min. Current Thresh. S1 Clos. Breaker Min. Current Thresh. S2 Clos. Breaker Min. Current Thresh. I7 Change to Another Setting Group
312
Addr .
401
Setting Title
WAVEFORMTRIGGER
Function
Oscillographic Fault Records
Setting Options
Save with Pickup Save with TRIP Start with TRIP 0.30..5.00 sec
Default Setting
Save with Pickup
Comments
Waveform Capture
403
MAX. LENGTH
Oscillographic Fault Records Oscillographic Fault Records Oscillographic Fault Records Oscillographic Fault Records Differential Protection
1.00 sec
404
0.05..0.50 sec
0.10 sec
405
0.05..0.50 sec 0.10..5.00 sec; OFF ON Block relay for trip commands OFF ON OFF ON OFF 3. Harmonic 5. Harmonic OFF ON 0.20..2.00 I/InO; 0 NO YES NO YES 0.05..2.00 I/InO 0.00..60.00 sec; 0.5..35.0 I/InO; 0.00..60.00 sec; 0.10..0.50 0.00..2.00 I/InO 0.25..0.95 0.00..10.00 I/InO 0.00..2.00 I/InO 1.0..2.0 0.0..180.0 sec 2.00..15.00 I/InO 2..250 Cycle; 10..80 % 2..1000 Cycle; 0; 10..80 % 2..1000 Cycle; 0;
0.10 sec
406
BinIn CAPT.TIME
0.50 sec
1201
DIFF. PROT.
OFF
Differential Protection
1205
INC.CHAR.START
Differential Protection
OFF
1206
INRUSH 2.HARM.
Differential Protection
ON
1207
RESTR. n.HARM.
Differential Protection
OFF
1208
I-DIFF> MON.
Differential Protection
ON
1210 1211A
0.00 I/InO NO
1212A
DIFFw.IE2-MEAS
Differential Protection
NO
1221 1226A 1231 1236A 1241A 1242A 1243A 1244A 1251A 1252A 1253 1256A 1257A 1261 1262A 1271 1272A
I-DIFF> T I-DIFF> I-DIFF>> T I-DIFF>> SLOPE 1 BASE POINT 1 SLOPE 2 BASE POINT 2 I-REST. STARTUP START-FACTOR T START MAX I-ADD ON STAB. T ADD ON-STAB. 2. HARMONIC CROSSB. 2. HARM n. HARMONIC CROSSB. n.HARM
Differential Protection Differential Protection Differential Protection Differential Protection Differential Protection Differential Protection Differential Protection Differential Protection Differential Protection Differential Protection Differential Protection Differential Protection Differential Protection Differential Protection Differential Protection Differential Protection Differential Protection
0.20 I/InO 0.00 sec 7.5 I/InO 0.00 sec 0.25 0.00 I/InO 0.50 2.50 I/InO 0.10 I/InO 1.0 5.0 sec 4.00 I/InO 15 Cycle 15 % 3 Cycle 30 % 0 Cycle
Pickup Value of Differential Curr. T I-DIFF> Time Delay Pickup Value of High Set Trip T I-DIFF>> Time Delay Slope 1 of Tripping Characteristic Base Point for Slope 1 of Charac. Slope 2 of Tripping Characteristic Base Point for Slope 2 of Charac. I-RESTRAINT for Start Detection Factor for Increasing of Char. at Start Maximum Permissible Starting Time Pickup for Add-on Stabilization Duration of Add-on Stabilization 2nd Harmonic Content in I-DIFF Time for Cross-blocking 2nd Harm. n-th Harmonic Content in I-DIFF Time for Cross-blocking n-th Harm.
313
A Appendix
Addr .
1273A 1281
Setting Title
IDIFFmax n.HM I-DIFF> MON.
Function
Differential Protection Differential Protection
Setting Options
0.5..20.0 I/InO 0.15..0.80 I/InO
Default Setting
1.5 I/InO 0.20 I/InO
Comments
Limit IDIFFmax of n-th Harm.Restraint Pickup Value of diff. Current Monitoring T I-DIFF> Monitoring Time Delay Restricted Earth Fault Protection
1282 1301
1..10 sec OFF ON Block relay for trip commands 0.05..2.00 I / In 0.00..60.00 sec; 0.00..0.95
2 sec OFF
1311
I-REF>
Restricted Earth Fault Protection Restricted Earth Fault Protection Restricted Earth Fault Protection Cold Load Pikkup
0.15 I / In
1312A
T I-REF>
0.00 sec
1313A
SLOPE
0.00
1701
COLDLOAD PIKKUP
OFF ON No Current Breaker Contact No Current Breaker Contact No Current Breaker Contact 0..21600 sec 1..21600 sec 1..600 sec; ON OFF ON OFF I>> instantaneously I> instantaneously Ip instantaneously Inactive 0.10..35.00 A; 0.00..60.00 sec; 0.10..35.00 A; 0.00..60.00 sec; 0.10..4.00 A 0.05..3.20 sec; 0.50..15.00; Instantaneous Disk Emulation
OFF
Cold-Load-Pickup Function
1702
No Current
1703
No Current
1704
No Current
Cold Load Pikkup Cold Load Pikkup Cold Load Pikkup Time overcurrent Phase Time overcurrent Phase Time overcurrent Phase
Circuit Breaker OPEN Time Active Time Stop Time Phase Time Overcurrent
2002
InRushRest. Ph
OFF
2008A
MANUAL CLOSE
I>> instantaneously
2011
I>>
Time overcurrent Phase Time overcurrent Phase Time overcurrent Phase Time overcurrent Phase Time overcurrent Phase Time overcurrent Phase Time overcurrent Phase Time overcurrent Phase
2.00 A
I>> Pickup
2012
T I>>
0.00 sec
2013
I>
1.00 A
I> Pickup
2014
T I>
0.50 sec
2021
Ip
1.00 A
Ip Pickup
2022
T Ip
0.50 sec
T Ip Time Dial
2023
D Ip
5.00
D Ip Time Dial
2024
TOC DROP-OUT
Disk Emulation
314
Addr .
2025
Setting Title
IEC CURVE
Function
Time overcurrent Phase
Setting Options
Normal Inverse Very Inverse Extremely Inverse Long Inverse Very Inverse Inverse Short Inverse Long Inverse Moderately Inverse Extremely Inverse Definite Inverse 1.00..20.00 I / Ip; 0.01..999.00 Time Dial 0.05..0.95 I / Ip; 0.01..999.00 Time Dial 10..45 %
Default Setting
Normal Inverse IEC Curve
Comments
2026
ANSI CURVE
Very Inverse
ANSI Curve
2031
I/Ip PU T/Tp
Time overcurrent Phase Time overcurrent Phase Time overcurrent Phase Time overcurrent Phase Time overcurrent Phase Time overcurrent Phase Time overcurrent Phase Time overcurrent Phase Time overcurrent Phase Time overcurrent Phase Time overcurrent Phase Time overcurrent Phase Time overcurrent Phase Time overcurrent 3I0
2032
2041
2.HARM. Phase
15 %
2nd harmonic O/C Ph. in % of fundamental Maximum Current for Inr. Rest. O/C Phase CROSS BLOCK O/C Phase
2042
0.30..25.00 A
7.50 A
2043
CROSS BLK.Phase
NO YES 0.00..180.00 sec 0.10..35.00 A; 0.00..60.00 sec; 0.10..35.00 A; 0.00..60.00 sec; 0.10..4.00 A 0.05..3.20 sec; 0.50..15.00; ON OFF ON OFF 3I0>> instantaneously 3I0> instantaneously 3I0p instantaneously Inactive 0.05..35.00 A; 0.00..60.00 sec; 0.05..35.00 A; 0.00..60.00 sec; 0.05..4.00 A 0.05..3.20 sec; 0.50..15.00;
NO
2044
T CROSS BLK.Ph
0.00 sec
2111
I>>
10.00 A
I>> Pickup
2112
T I>>
0.00 sec
2113
I>
2.00 A
I> Pickup
2114
T I>
0.30 sec
2121
Ip
1.50 A
Ip Pickup
2122
T Ip
0.50 sec
T Ip Time Dial
2123
D Ip
5.00
D Ip Time Dial
2201
3I0 O/C
OFF
2202
InRushRest. 3I0
OFF
2208A
3I0>> instantaneously
Time overcurrent 3I0 Time overcurrent 3I0 Time overcurrent 3I0 Time overcurrent 3I0 Time overcurrent 3I0 Time overcurrent 3I0 Time overcurrent 3I0
0.50 A 0.10 sec 0.20 A 0.50 sec 0.20 A 0.20 sec 5.00
3I0>> Pickup T 3I0>> Time Delay 3I0> Pickup T 3I0> Time Delay 3I0p Pickup T 3I0p Time Dial D 3I0p Time Dial
315
A Appendix
Addr .
2224
Setting Title
TOC DROP-OUT
Function
Time overcurrent 3I0
Setting Options
Instantaneous Disk Emulation Normal Inverse Very Inverse Extremely Inverse Long Inverse Very Inverse Inverse Short Inverse Long Inverse Moderately Inverse Extremely Inverse Definite Inverse 1.00..20.00 I / Ip; 0.01..999.00 Time Dial 0.05..0.95 I / Ip; 0.01..999.00 Time Dial 10..45 %
Default Setting
Disk Emulation
Comments
TOC Drop-out Characteristic
2225
IEC CURVE
Normal Inverse
IEC Curve
2226
ANSI CURVE
Very Inverse
ANSI Curve
2231
I/I0p PU T/TI0p
2232
MofPU ResT/TI0p
2241
2.HARM. 3I0
15 %
2nd harmonic O/C 3I0 in % of fundamental Maximum Current for Inr. Rest. O/C 3I0 3I0>> Pickup T 3I0>> Time Delay 3I0> Pickup T 3I0> Time Delay 3I0p Pickup T 3I0p Time Dial D 3I0p Time Dial Earth Time Overcurrent
2242
0.30..25.00 A 0.05..35.00 A; 0.00..60.00 sec; 0.05..35.00 A; 0.00..60.00 sec; 0.05..4.00 A 0.05..3.20 sec; 0.50..15.00; ON OFF ON OFF IE>> instantaneously IE> instantaneously IEp instantaneously Inactive 0.05..35.00 A; 0.00..60.00 sec; 0.05..35.00 A; 0.00..60.00 sec; 0.05..4.00 A 0.05..3.20 sec; 0.50..15.00; Instantaneous Disk Emulation
7.50 A
Time overcurrent 3I0 Time overcurrent 3I0 Time overcurrent 3I0 Time overcurrent 3I0 Time overcurrent 3I0 Time overcurrent 3I0 Time overcurrent 3I0 Time overcurrent Earth Time overcurrent Earth Time overcurrent Earth
7.00 A 0.00 sec 1.50 A 0.30 sec 1.00 A 0.50 sec 5.00 OFF
2402
InRushRestEarth
OFF
2408A
IE MAN. CLOSE
IE>> instantaneously
2411
IE>>
Time overcurrent Earth Time overcurrent Earth Time overcurrent Earth Time overcurrent Earth Time overcurrent Earth Time overcurrent Earth Time overcurrent Earth Time overcurrent Earth
0.50 A
IE>> Pickup
2412
T IE>>
0.10 sec
2413
IE>
0.20 A
IE> Pickup
2414
T IE>
0.50 sec
2421
IEp
0.20 A
IEp Pickup
2422
T IEp
0.20 sec
2423
D IEp
5.00
2424
TOC DROP-OUT
Disk Emulation
316
Addr .
2425
Setting Title
IEC CURVE
Function
Time overcurrent Earth
Setting Options
Normal Inverse Very Inverse Extremely Inverse Long Inverse Very Inverse Inverse Short Inverse Long Inverse Moderately Inverse Extremely Inverse Definite Inverse 1.00..20.00 I / Ip; 0.01..999.00 Time Dial 0.05..0.95 I / Ip; 0.01..999.00 Time Dial 10..45 %
Default Setting
Normal Inverse IEC Curve
Comments
2426
ANSI CURVE
Very Inverse
ANSI Curve
2431
I/IEp PU T/TEp
Time overcurrent Earth Time overcurrent Earth Time overcurrent Earth Time overcurrent Earth Time overcurrent Earth Time overcurrent Earth Time overcurrent Earth Time overcurrent Earth Time overcurrent Earth Time overcurrent Earth Time overcurrent Earth Time overcurrent 1Phase Time overcurrent 1Phase Time overcurrent 1Phase Time overcurrent 1Phase Time overcurrent 1Phase Time overcurrent 1Phase Time overcurrent 1Phase Unbalance Load (Negative Sequence) Unbalance Load (Negative Sequence) Unbalance Load (Negative Sequence)
2432
2441
2.HARM. Earth
15 %
2nd harmonic O/C E in % of fundamental Maximum Current for Inr. Rest. O/C Earth IE>> Pickup
2442
I Max InRr. E
0.30..25.00 A 0.05..35.00 A; 0.00..60.00 sec; 0.05..35.00 A; 0.00..60.00 sec; 0.05..4.00 A 0.05..3.20 sec; 0.50..15.00; OFF ON 0.05..35.00 A; 0.003..1.500 A; 0.00..60.00 sec; 0.05..35.00 A; 0.003..1.500 A; 0.00..60.00 sec; OFF ON 0.10..3.00 A 0.00..60.00 sec;
7.50 A
2511
IE>>
7.00 A
2512
T IE>>
0.00 sec
2513
IE>
1.50 A
IE> Pickup
2514
T IE>
0.30 sec
2521
IEp
1.00 A
IEp Pickup
2522
T IEp
0.50 sec
2523
D IEp
5.00
2701
1Phase O/C
OFF
2702
1Phase I>>
0.50 A
2703
1Phase I>>
0.300 A
2704
T 1Phase I>>
0.10 sec
2705
1Phase I>
0.20 A
2706
1Phase I>
0.100 A
2707
T 1Phase I>
0.50 sec
4001
UNBALANCE LOAD
OFF
4002
I2>
0.10 A
I2> Pickup
4003
T I2>
1.50 sec
317
A Appendix
Addr .
4004
Setting Title
I2>>
Function
Unbalance Load (Negative Sequence) Unbalance Load (Negative Sequence) Unbalance Load (Negative Sequence)
Setting Options
0.10..3.00 A 0.00..60.00 sec; Normal Inverse Very Inverse Extremely Inverse Extremely Inverse Inverse Moderately Inverse Very Inverse 0.10..2.00 A 0.50..15.00; 0.05..3.20 sec; Instantaneous Disk Emulation OFF ON Alarm Only 0.10..4.00
Default Setting
0.50 A
Comments
I2>> Pickup
4005
T I2>>
1.50 sec
4006
IEC CURVE
Extremely Inverse
IEC Curve
4007
ANSI CURVE
Extremely Inverse
ANSI Curve
4008
I2p
Unbalance Load (Negative Sequence) Unbalance Load (Negative Sequence) Unbalance Load (Negative Sequence) Unbalance Load (Negative Sequence) Thermal Overload Protection
0.90 A
I2p Pickup
4009
D I2p
5.00
4010
T I2p
0.50 sec
4011
I2p DROP-OUT
Instantaneous
4201
OFF
4202
K-FACTOR
Thermal Overload Protection Thermal Overload Protection Thermal Overload Protection Thermal Overload Protection Thermal Overload Protection Thermal Overload Protection Thermal Overload Protection Thermal Overload Protection Thermal Overload Protection Thermal Overload Protection Thermal Overload Protection Thermal Overload Protection Thermal Overload Protection Thermal Overload Protection Thermal Overload Protection
1.10
K-Factor
4203
1.0..999.9 min
100.0 min
Time Constant
4204
50..100 %
90 %
4205
0.10..4.00 A
1.00 A
4207A
K-FACTOR
1.0..10.0
1.0
4208A
T EMERGENCY
Emergency Time
4209A
I MOTOR START
4221
OIL-DET. RTD
4222
4223
4224
4225
4226
4227
0.125..128.000
2.000
4231
METH. COOLING
ON (Oil-Natural)
Method of Cooling
318
Addr .
4232
Setting Title
Y-WIND.EXPONENT
Function
Thermal Overload Protection Thermal Overload Protection Breaker Failure Protection Breaker Failure Protection Breaker Failure Protection Device
Setting Options
1.6..2.0
Default Setting
1.6
Comments
Y-Winding Exponent
4233
HOT-SPOT GR
22..29
22
7001
BREAKER FAILURE
OFF ON OFF ON 0.06..60.00 sec; Display Targets on every Pickup Display Targets on TRIP only with V setting with V measuring ON OFF ON OFF 0.10..1.00 A
OFF
7004
OFF
7005
TRIP-Timer
0.25 sec
TRIP-Timer
7110
FltDisp.LED/LCD
7601
POWER CALCUL.
Measurement
with V setting
Calculation of Power
8101
BALANCE I
Measurement Supervision Measurement Supervision Measurement Supervision Measurement Supervision Measurement Supervision Measurement Supervision Trip Circuit Supervision External Trip Functions External Trip Functions External Trip Functions External Trip Functions RTD-Box
OFF
8102
PHASE ROTATION
OFF
8111
BAL. I LIMIT S1
0.50 A
8112
BAL. FACT. I S1
0.10..0.90
0.50
8121
BAL. I LIMIT S2
0.10..1.00 A
0.50 A
8122
BAL. FACT. I S2
0.10..0.90
0.50
8201
ON OFF ON OFF 0.00..60.00 sec; ON OFF 0.00..60.00 sec; not connected Pt 100 Ohm Ni 120 Ohm Ni 100 Ohm Oil Ambient Winding Bearing Other -50..250 C; -58..482 F; -50..250 C; -58..482 F;
OFF
8601
EXTERN TRIP 1
OFF
8602
T DELAY
1.00 sec
8701
EXTERN TRIP 2
OFF
8702
T DELAY
1.00 sec
9011A
RTD 1 TYPE
Pt 100 Ohm
RTD 1: Type
9012A
RTD 1 LOCATION
RTD-Box
Oil
RTD 1: Location
RTD 1: Temperature Stage 1 Pickup RTD 1: Temperature Stage 1 Pickup RTD 1: Temperature Stage 2 Pickup RTD 1: Temperature Stage 2 Pickup
319
A Appendix
Addr .
9021A
Setting Title
RTD 2 TYPE
Function
RTD-Box
Setting Options
not connected Pt 100 Ohm Ni 120 Ohm Ni 100 Ohm Oil Ambient Winding Bearing Other -50..250 C; -58..482 F; -50..250 C; -58..482 F; not connected Pt 100 Ohm Ni 120 Ohm Ni 100 Ohm Oil Ambient Winding Bearing Other -50..250 C; -58..482 F; -50..250 C; -58..482 F; not connected Pt 100 Ohm Ni 120 Ohm Ni 100 Ohm Oil Ambient Winding Bearing Other -50..250 C; -58..482 F; -50..250 C; -58..482 F; not connected Pt 100 Ohm Ni 120 Ohm Ni 100 Ohm Oil Ambient Winding Bearing Other -50..250 C; -58..482 F; -50..250 C; -58..482 F;
Default Setting
not connected
Comments
RTD 2: Type
9022A
RTD 2 LOCATION
RTD-Box
Other
RTD 2: Location
RTD 2 STAGE 1 RTD 2 STAGE 1 RTD 2 STAGE 2 RTD 2 STAGE 2 RTD 3 TYPE
RTD 2: Temperature Stage 1 Pickup RTD 2: Temperature Stage 1 Pickup RTD 2: Temperature Stage 2 Pickup RTD 2: Temperature Stage 2 Pickup RTD 3: Type
9032A
RTD 3 LOCATION
RTD-Box
Other
RTD 3: Location
RTD 3 STAGE 1 RTD 3 STAGE 1 RTD 3 STAGE 2 RTD 3 STAGE 2 RTD 4 TYPE
RTD 3: Temperature Stage 1 Pickup RTD 3: Temperature Stage 1 Pickup RTD 3: Temperature Stage 2 Pickup RTD 3: Temperature Stage 2 Pickup RTD 4: Type
9042A
RTD 4 LOCATION
RTD-Box
Other
RTD 4: Location
RTD 4 STAGE 1 RTD 4 STAGE 1 RTD 4 STAGE 2 RTD 4 STAGE 2 RTD 5 TYPE
RTD 4: Temperature Stage 1 Pickup RTD 4: Temperature Stage 1 Pickup RTD 4: Temperature Stage 2 Pickup RTD 4: Temperature Stage 2 Pickup RTD 5: Type
9052A
RTD 5 LOCATION
RTD-Box
Other
RTD 5: Location
RTD 5: Temperature Stage 1 Pickup RTD 5: Temperature Stage 1 Pickup RTD 5: Temperature Stage 2 Pickup RTD 5: Temperature Stage 2 Pickup
320
Addr .
9061A
Setting Title
RTD 6 TYPE
Function
RTD-Box
Setting Options
not connected Pt 100 Ohm Ni 120 Ohm Ni 100 Ohm Oil Ambient Winding Bearing Other -50..250 C; -58..482 F; -50..250 C; -58..482 F; not connected Pt 100 Ohm Ni 120 Ohm Ni 100 Ohm Oil Ambient Winding Bearing Other -50..250 C; -58..482 F; -50..250 C; -58..482 F; not connected Pt 100 Ohm Ni 120 Ohm Ni 100 Ohm Oil Ambient Winding Bearing Other -50..250 C; -58..482 F; -50..250 C; -58..482 F; not connected Pt 100 Ohm Ni 120 Ohm Ni 100 Ohm Oil Ambient Winding Bearing Other -50..250 C; -58..482 F; -50..250 C; -58..482 F;
Default Setting
not connected
Comments
RTD 6: Type
9062A
RTD 6 LOCATION
RTD-Box
Other
RTD 6: Location
RTD 6 STAGE 1 RTD 6 STAGE 1 RTD 6 STAGE 2 RTD 6 STAGE 2 RTD 7 TYPE
RTD 6: Temperature Stage 1 Pickup RTD 6: Temperature Stage 1 Pickup RTD 6: Temperature Stage 2 Pickup RTD 6: Temperature Stage 2 Pickup RTD 7: Type
9072A
RTD 7 LOCATION
RTD-Box
Other
RTD 7: Location
RTD 7 STAGE 1 RTD 7 STAGE 1 RTD 7 STAGE 2 RTD 7 STAGE 2 RTD 8 TYPE
RTD 7: Temperature Stage 1 Pickup RTD 7: Temperature Stage 1 Pickup RTD 7: Temperature Stage 2 Pickup RTD 7: Temperature Stage 2 Pickup RTD 8: Type
9082A
RTD 8 LOCATION
RTD-Box
Other
RTD 8: Location
RTD 8 STAGE 1 RTD 8 STAGE 1 RTD 8 STAGE 2 RTD 8 STAGE 2 RTD 9 TYPE
RTD 8: Temperature Stage 1 Pickup RTD 8: Temperature Stage 1 Pickup RTD 8: Temperature Stage 2 Pickup RTD 8: Temperature Stage 2 Pickup RTD 9: Type
9092A
RTD 9 LOCATION
RTD-Box
Other
RTD 9: Location
RTD 9: Temperature Stage 1 Pickup RTD 9: Temperature Stage 1 Pickup RTD 9: Temperature Stage 2 Pickup RTD 9: Temperature Stage 2 Pickup
321
A Appendix
Addr .
9101A
Setting Title
RTD10 TYPE
Function
RTD-Box
Setting Options
not connected Pt 100 Ohm Ni 120 Ohm Ni 100 Ohm Oil Ambient Winding Bearing Other -50..250 C; -58..482 F; -50..250 C; -58..482 F; not connected Pt 100 Ohm Ni 120 Ohm Ni 100 Ohm Oil Ambient Winding Bearing Other -50..250 C; -58..482 F; -50..250 C; -58..482 F; not connected Pt 100 Ohm Ni 120 Ohm Ni 100 Ohm Oil Ambient Winding Bearing Other -50..250 C; -58..482 F; -50..250 C; -58..482 F;
Default Setting
not connected
Comments
RTD10: Type
9102A
RTD10 LOCATION
RTD-Box
Other
RTD10: Location
RTD10 STAGE 1 RTD10 STAGE 1 RTD10 STAGE 2 RTD10 STAGE 2 RTD11 TYPE
RTD10: Temperature Stage 1 Pickup RTD10: Temperature Stage 1 Pickup RTD10: Temperature Stage 2 Pickup RTD10: Temperature Stage 2 Pickup RTD11: Type
9112A
RTD11 LOCATION
RTD-Box
Other
RTD11: Location
RTD11 STAGE 1 RTD11 STAGE 1 RTD11 STAGE 2 RTD11 STAGE 2 RTD12 TYPE
RTD11: Temperature Stage 1 Pickup RTD11: Temperature Stage 1 Pickup RTD11: Temperature Stage 2 Pickup RTD11: Temperature Stage 2 Pickup RTD12: Type
9122A
RTD12 LOCATION
RTD-Box
Other
RTD12: Location
RTD12: Temperature Stage 1 Pickup RTD12: Temperature Stage 1 Pickup RTD12: Temperature Stage 2 Pickup RTD12: Temperature Stage 2 Pickup
322
A.8
List of Information
F.No.
Description
Function
00003 >Synchronize Internal Real Time Clock (>Time Synch) 00004 >Trigger Waveform Capture (>Trig.Wave.Cap.) 00005 >Reset LED (>Reset LED) 00007 >Setting Group Select Bit 0 (>Set Group Bit0) 00008 >Setting Group Select Bit 1 (>Set Group Bit1) 00015 >Test mode (>Test mode) 00016 >Stop data transmission (>DataStop) 00051 Device is Operational and Protecting (Device OK) 00052 At Least 1 Protection Funct. is Active (ProtActive) 00055 Reset Device (Reset Device) 00056 Initial Start of Device (Initial Start) 00060 Reset LED (Reset LED)
Device
SP_Ev
LED BI
BO
135
48
SP
LED BI
BO
135
49
SP SP
* *
* *
LED BI LED BI
BO BO
135 135
50 51
1 1
Change Group
SP
LED BI
BO
135
52
SP SP OUT
* * ON OFF ON OFF * ON ON
* * *
BO BO BO
53 54 81
1 1 1
GI GI
Device
IntSP
LED
BO
176
18
* * *
BO BO BO
4 5 19
5 5 1
00067 Resume (Resume) 00068 Clock Synchronization Error (Clock SyncError) 00069 Daylight Saving Time (DayLightSavTime) 00070 Setting calculation is running (Settings Calc.) 00071 Settings Check (Settings Check) 00072 Level-2 change (Level-2 change)
Device Supervision
* *
LED LED
BO BO
135
97
Device
OUT
LED
BO
Device
OUT
LED
BO
176
22
Device Device
OUT OUT
* *
LED LED
BO BO
Device
OUT
LED
BO
Supervision
LED
BO
135
130
Supervision Device
ON ON OFF
* *
LED LED
BO BO
135 135
136 145
1 1
323
General Interrogation GI GI GI GI GI GI GI GI GI
Type of Information
Log-Buffers
Configurable in Matrix
IEC 60870-5-103
Chatter Blocking
Information-No
Binary Output
Function Key
Binary Input
Type
LED
A Appendix
F.No.
Description
Function
00126 Protection ON/OFF (via system port) (ProtON/OFF) 00140 Error with a summary alarm (Error Sum Alarm) 00160 Alarm Summary Event (Alarm Sum Event) 00161 Failure: General Current Supervision (Fail I Superv.) 00163 Failure: Current Balance (Fail I balance) 00175 Failure: Phase Sequence Current (Fail Ph. Seq. I) 00177 Failure: Battery empty (Fail Battery)
IntSP
ON OFF *
LED
BO
OUT
LED
BO
176
47
Supervision
OUT
LED
BO
176
46
OUT
ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON
LED
BO
OUT
LED
BO
135
183
OUT
LED
BO
135
191
OUT
LED
BO
135
193
Supervision
OUT
LED
BO
135
178
Supervision
OUT
LED
BO
135
171
Supervision
OUT
LED
BO
135
210
Supervision
OUT
LED
BO
00192 Error:1A/5Ajumper different from setting (Error1A/5Awrong) 00193 Alarm: NO calibration data available (Alarm NO calibr) 00198 Error: Communication Module B (Err. Module B) 00199 Error: Communication Module C (Err. Module C) 00203 Waveform data deleted (Wave. deleted) 00264 Failure: RTD-Box 1 (Fail: RTD-Box 1)
Supervision
OUT
LED
BO
135
169
Supervision
OUT
LED
BO
135
181
Supervision
OUT
LED
BO
135
198
Supervision
OUT
LED
BO
135
199
OUT_ Ev OUT
LED
BO
135
203
LED
BO
135
208
00265 Failure: Phase Sequence I side 1 (FailPh.Seq I S1) 00266 Failure: Phase Sequence I side 2 (FailPh.Seq I S2) 00267 Failure: RTD-Box 2 (Fail: RTD-Box 2)
OUT
LED
BO
OUT
LED
BO
OUT
LED
BO
135
209
00272 Set Point Operating Hours (SP. Op Hours>) 00311 Fault in configuration of the Protection (Fault Configur.)
OUT
LED
BO
135
229
OUT
LED
BO
324
General Interrogation GI GI GI GI GI GI GI GI GI GI GI GI GI GI GI
Type of Information
Log-Buffers
Configurable in Matrix
IEC 60870-5-103
Chatter Blocking
Information-No
Binary Output
Function Key
Binary Input
Type
LED
F.No.
Description
Function
SP
LED BI
BO
150
SP
ON OFF
LED BI
BO
00391 >Warning stage from Buchholz protec- External Annunciation (>Buchh. Warn) tions of Transformer 00392 >Tripp. stage from Buchholz protection (>Buchh. Trip) External Annunciations of Transformer External Annunciations of Transformer Statistics
SP
ON OFF
LED BI
BO
150
41
SP
ON OFF
LED BI
BO
150
42
SP
ON OFF
LED BI
BO
150
43
00409 >BLOCK Op Counter (>BLOCK Op Count) 00410 >CB1 aux. 3p Closed (>CB1 3p Closed) 00411 >CB1 aux. 3p Open (>CB1 3p Open)
SP
LED BI
BO
Power System Data 2 Power System Data 2 Power System Data 2 Power System Data 2 Power System Data 2 Power System Data 2 Power System Data 2 Measurement Supervision Measurement Supervision Power System Data 2 Power System Data 2 Power System Data 2 Power System Data 2 Power System Data 2 Power System Data 2
SP
LED BI
BO
150
80
SP
LED BI
BO
150
81
00413 >CB2 aux. 3p Closed (>CB2 3p Closed) 00414 >CB2 aux. 3p Open (>CB2 3p Open)
SP
LED BI
BO
150
82
SP
LED BI
BO
150
83
OUT
ON
LED
BO
150
151
00511 Relay GENERAL TRIP command (Relay TRIP) 00561 Manual close signal detected (Man.Clos.Detect) 00571 Fail.: Current symm. supervision side 1 (Fail. Isym 1) 00572 Fail.: Current symm. supervision side 2 (Fail. Isym 2) 00576 Primary fault current IL1 side1 (IL1S1:) 00577 Primary fault current IL2 side1 (IL2S1:) 00578 Primary fault current IL3 side1 (IL3S1:) 00579 Primary fault current IL1 side2 (IL1S2:) 00580 Primary fault current IL2 side2 (IL2S2:) 00581 Primary fault current IL3 side2 (IL3S2:)
OUT
ON
LED
BO
150
161
OUT
ON
LED
BO
150
211
OUT
ON OFF ON OFF *
LED
BO
OUT
LED
BO
OUT
150
193
OUT
150
194
OUT
150
195
OUT
150
190
OUT
150
191
OUT
150
192
325
General Interrogation GI GI GI GI GI GI GI GI GI GI
Type of Information
Log-Buffers
Configurable in Matrix
IEC 60870-5-103
Chatter Blocking
Information-No
Binary Output
Function Key
Binary Input
Type
LED
A Appendix
F.No.
Description
Function
Power System Data 2 Power System Data 2 Power System Data 2 Power System Data 2 Power System Data 2 Power System Data 2 Power System Data 2 Energy
OUT
OUT
OUT
OUT
OUT
OUT
OUT
PMV
00889 Pulsed Energy Wq (reactive) (Wq(puls)) 01000 Number of breaker TRIP commands (# TRIPs=) 01020 Counter of operating hours (Op.Hours=) 01403 >BLOCK Breaker failure (>BLOCK BkrFail) 01431 >Breaker failure initiated externally (>BrkFail extSRC) 01451 Breaker failure is switched OFF (BkrFail OFF) 01452 Breaker failure is BLOCKED (BkrFail BLOCK) 01453 Breaker failure is ACTIVE (BkrFail ACTIVE) 01456 Breaker failure (internal) PICKUP (BkrFail int PU) 01457 Breaker failure (external) PICKUP (BkrFail ext PU) 01471 Breaker failure TRIP (BrkFailure TRIP) 01480 Breaker failure (internal) TRIP (BkrFail intTRIP) 01481 Breaker failure (external) TRIP (BkrFail extTRIP) 01488 Breaker failure Not aval. for this obj. (BkrFail Not av.)
Energy
PMV
BI
133
56
Statistics
OUT
Statistics
OUT
Breaker Failure Protection Breaker Failure Protection Breaker Failure Protection Breaker Failure Protection Breaker Failure Protection Breaker Failure Protection Breaker Failure Protection Breaker Failure Protection Breaker Failure Protection Breaker Failure Protection Breaker Failure Protection
SP
LED BI
BO
166
103
SP
LED BI
BO
166
104
OUT
LED
BO
166
151
OUT
ON OFF *
LED
BO
166
152
OUT
LED
BO
166
153
OUT
ON OFF ON OFF ON M
LED
BO
166
156
OUT
LED
BO
166
157
OUT
LED
BO
166
171
OUT
ON
LED
BO
166
180
OUT
ON
LED
BO
166
181
OUT
ON
LED
BO
326
General Interrogation GI GI GI GI GI GI GI GI GI GI
Type of Information
Log-Buffers
Configurable in Matrix
IEC 60870-5-103
Chatter Blocking
Information-No
Binary Output
Function Key
Binary Input
Type
LED
F.No.
Description
Function
01503 >BLOCK Thermal Overload Protection (>BLK ThOverload) 01507 >Emergency start Th. Overload Protection (>Emer.Start O/L) 01511 Thermal Overload Protection OFF (Th.Overload OFF) 01512 Thermal Overload Protection BLOKKED (Th.Overload BLK) 01513 Thermal Overload Protection ACTIVE (Th.Overload ACT) 01515 Th. Overload Current Alarm (I alarm) (O/L I Alarm) 01516 Thermal Overload Alarm (O/L Alarm) 01517 Thermal Overload picked up (O/L Th. pick.up) 01521 Thermal Overload TRIP (ThOverload TRIP) 01541 Thermal Overload hot spot Th. Alarm (O/L ht.spot Al.) 01542 Thermal Overload hot spot Th. TRIP (O/L h.spot TRIP) 01543 Thermal Overload aging rate Alarm (O/L ag.rate Al.)
Thermal Overload Protection Thermal Overload Protection Thermal Overload Protection Thermal Overload Protection Thermal Overload Protection Thermal Overload Protection Thermal Overload Protection Thermal Overload Protection Thermal Overload Protection Thermal Overload Protection Thermal Overload Protection Thermal Overload Protection
SP
LED BI
BO
167
SP
LED BI
BO
167
OUT
LED
BO
167
11
OUT
ON OFF *
LED
BO
167
12
OUT
LED
BO
167
13
OUT
LED
BO
167
15
OUT
LED
BO
167
16
OUT
LED
BO
167
17
OUT
ON OFF *
LED
BO
167
21
OUT
LED
BO
167
41
OUT
LED
BO
167
42
OUT
LED
BO
167
43
01544 Thermal Overload aging rate TRIP (O/ Thermal Overload L ag.rt. TRIP) Protection 01545 Th. Overload No temperature mesured (O/L No Th.meas.) 01549 Th. Overload Not avaliable for this obj. (O/L Not avalia.) 01704 >BLOCK Phase time overcurrent (>BLK Phase O/C) 01714 >BLOCK Earth time overcurrent (>BLK Earth O/C) 01721 >BLOCK I>> (>BLOCK I>>) Thermal Overload Protection Thermal Overload Protection Time overcurrent Phase Time overcurrent Earth Time overcurrent Phase Time overcurrent Phase Time overcurrent Phase Time overcurrent Earth Time overcurrent Earth
OUT
LED
BO
167
44
OUT
LED
BO
OUT
ON
LED
BO
SP
LED BI
BO
SP
LED BI
BO
SP
LED BI
BO
60
SP
LED BI
BO
60
SP
LED BI
BO
60
SP
LED BI
BO
60
SP
LED BI
BO
60
327
General Interrogation GI GI GI GI GI GI GI GI GI GI GI GI GI GI GI GI GI GI
Type of Information
Log-Buffers
Configurable in Matrix
IEC 60870-5-103
Chatter Blocking
Information-No
Binary Output
Function Key
Binary Input
Type
LED
A Appendix
F.No.
Description
Function
SP
LED BI
BO
60
01730 >BLOCK Cold-Load-Pickup (>BLOCK CLP) 01731 >BLOCK Cold-Load-Pickup stop timer (>BLK CLP stpTim) 01741 >BLOCK 3I0 time overcurrent (>BLK 3I0 O/C) 01742 >BLOCK 3I0>> time overcurrent (>BLOCK 3I0>>) 01743 >BLOCK 3I0> time overcurrent (>BLOCK 3I0>) 01744 >BLOCK 3I0p time overcurrent (>BLOCK 3I0p) 01748 Time Overcurrent 3I0 is OFF (O/C 3I0 OFF) 01749 Time Overcurrent 3I0 is BLOCKED (O/C 3I0 BLK) 01750 Time Overcurrent 3I0 is ACTIVE (O/C 3I0 ACTIVE) 01751 Time Overcurrent Phase is OFF (O/C Phase OFF) 01752 Time Overcurrent Phase is BLOCKED (O/C Phase BLK) 01753 Time Overcurrent Phase is ACTIVE (O/C Phase ACT) 01756 Time Overcurrent Earth is OFF (O/C Earth OFF) 01757 Time Overcurrent Earth is BLOCKED (O/C Earth BLK)
SP
LED BI
BO
SP
ON OFF *
ON OFF *
LED BI
BO
60
243
Time overcurrent 3I0 Time overcurrent 3I0 Time overcurrent 3I0 Time overcurrent 3I0 Time overcurrent 3I0 Time overcurrent 3I0 Time overcurrent 3I0 Time overcurrent Phase Time overcurrent Phase Time overcurrent Phase Time overcurrent Earth Time overcurrent Earth
SP
LED BI
BO
SP
LED BI
BO
60
SP
LED BI
BO
60
10
SP
LED BI
BO
60
11
OUT
LED
BO
60
151
OUT
ON OFF *
LED
BO
60
152
OUT
LED
BO
60
153
OUT
LED
BO
60
21
OUT
ON OFF *
LED
BO
60
22
OUT
LED
BO
60
23
OUT
LED
BO
60
26
OUT
ON OFF *
LED
BO
60
27
01758 Time Overcurrent Earth is ACTIVE (O/ Time overcurrent C Earth ACT) Earth 01761 Time Overcurrent picked up (Overcur- General O/C rent PU) 01762 Time Overcurrent Phase L1 picked up (O/C Ph L1 PU) 01763 Time Overcurrent Phase L2 picked up (O/C Ph L2 PU) 01764 Time Overcurrent Phase L3 picked up (O/C Ph L3 PU) 01765 Time Overcurrent Earth picked up (O/ C Earth PU) 01766 Time Overcurrent 3I0 picked up (O/C 3I0 PU) Time overcurrent Phase Time overcurrent Phase Time overcurrent Phase Time overcurrent Earth Time overcurrent 3I0
OUT
LED
BO
60
28
OUT
LED
BO
60
69
OUT
LED
BO
60
112
OUT
LED
BO
60
113
OUT
LED
BO
60
114
OUT
LED
BO
60
67
OUT
LED
BO
60
154
328
General Interrogation GI GI GI GI GI GI GI GI GI GI GI GI GI GI GI GI GI GI GI GI
Type of Information
Log-Buffers
Configurable in Matrix
IEC 60870-5-103
Chatter Blocking
Information-No
Binary Output
Function Key
Binary Input
Type
LED
F.No.
Description
Function
01791 Time Overcurrent TRIP (OvercurrentTRIP) 01800 I>> picked up (I>> picked up)
General O/C
OUT
ON
LED
BO
60
68
Time overcurrent Phase Time overcurrent Phase Time overcurrent Phase Time overcurrent Phase Time overcurrent Phase Time overcurrent Phase Time overcurrent Phase Time overcurrent Phase Time overcurrent Phase Time overcurrent Earth Time overcurrent Earth Time overcurrent Earth Time overcurrent Earth Time overcurrent Earth Time overcurrent Earth Time overcurrent Earth Time overcurrent Earth Time overcurrent Earth Time overcurrent Phase Time overcurrent Phase Time overcurrent Phase
OUT
ON OFF *
LED
BO
60
75
OUT
LED
BO
60
49
OUT
ON
LED
BO
60
70
OUT
ON OFF *
LED
BO
60
76
OUT
LED
BO
60
53
OUT
ON
LED
BO
60
71
OUT
ON OFF *
LED
BO
60
77
OUT
LED
BO
60
57
OUT
ON
LED
BO
60
58
OUT
ON OFF *
LED
BO
60
59
OUT
LED
BO
60
60
OUT
ON
LED
BO
60
61
OUT
ON OFF *
LED
BO
60
62
OUT
LED
BO
60
63
OUT
ON
LED
BO
60
72
OUT
ON OFF *
LED
BO
60
64
OUT
LED
BO
60
65
OUT
ON
LED
BO
60
66
01843 Cross blk: PhX blocked PhY (INRUSH X-BLK) 01851 I> BLOCKED (I> BLOCKED)
OUT
LED
BO
OUT
ON OFF ON OFF
LED
BO
60
105
OUT
LED
BO
60
106
329
General Interrogation GI GI GI GI GI GI GI GI GI GI GI GI GI GI GI GI GI GI GI GI GI
Type of Information
Log-Buffers
Configurable in Matrix
IEC 60870-5-103
Chatter Blocking
Information-No
Binary Output
Function Key
Binary Input
Type
LED
A Appendix
F.No.
Description
Function
Time overcurrent Earth Time overcurrent Earth Time overcurrent Phase Time overcurrent Earth Time overcurrent 3I0 Time overcurrent 3I0 Time overcurrent 3I0 Time overcurrent Phase Time overcurrent 3I0 Time overcurrent 3I0 Time overcurrent 3I0 Time overcurrent 3I0 Time overcurrent 3I0 Time overcurrent 3I0 Time overcurrent 3I0 Time overcurrent 3I0 Time overcurrent 3I0 Time overcurrent 3I0 Cold Load Pickup
OUT
LED
BO
60
107
OUT
LED
BO
60
108
OUT
LED
BO
60
109
OUT
LED
BO
60
110
OUT
LED
BO
60
159
OUT
LED
BO
60
155
OUT
LED
BO
60
163
01860 O/C Phase Not avali. for this objekt (O/C Ph. Not av.) 01861 O/C 3I0 Not avali. for this objekt (O/C 3I0 Not av.) 01901 3I0>> picked up (3I0>> picked up)
OUT
LED
BO
OUT
ON
LED
BO
OUT
ON OFF *
LED
BO
60
156
OUT
LED
BO
60
157
OUT
ON
LED
BO
60
158
OUT
ON OFF *
LED
BO
60
160
OUT
LED
BO
60
161
OUT
ON
LED
BO
60
162
OUT
ON OFF *
LED
BO
60
164
OUT
LED
BO
60
165
OUT
ON
LED
BO
60
166
01994 Cold-Load-Pickup switched OFF (CLP OFF) 01995 Cold-Load-Pickup is BLOCKED (CLP BLOCKED) 01996 Cold-Load-Pickup is RUNNING (CLP running) 01998 Dynamic settings O/C Phase are ACTIVE (I Dyn.set. ACT)
OUT
LED
BO
60
244
OUT
ON OFF *
LED
BO
60
245
OUT
LED
BO
60
246
OUT
ON OFF
LED
BO
60
248
330
General Interrogation GI GI GI GI GI GI GI GI GI GI GI GI GI GI GI GI GI GI GI GI
Type of Information
Log-Buffers
Configurable in Matrix
IEC 60870-5-103
Chatter Blocking
Information-No
Binary Output
Function Key
Binary Input
Type
LED
F.No.
Description
Function
01999 Dynamic settings O/C 3I0 are ACTIVE (3I0 Dyn.set.ACT) 02000 Dynamic settings O/C Earth are ACTIVE (IE Dyn.set. ACT) 04523 >Block external trip 1 (>BLOCK Ext 1)
OUT
ON OFF ON OFF *
ON OFF ON OFF *
LED
BO
60
249
OUT
LED
BO
60
250
External Trip Functions External Trip Functions External Trip Functions External Trip Functions External Trip Functions External Trip Functions External Trip Functions External Trip Functions External Trip Functions External Trip Functions External Trip Functions External Trip Functions External Trip Functions External Trip Functions Unbalance Load (Negative Sequence) Power System Data 1 Power System Data 1 Power System Data 1 Unbalance Load (Negative Sequence)
SP
LED BI
BO
SP
LED BI
BO
51
126
04531 External trip 1 is switched OFF (Ext 1 OFF) 04532 External trip 1 is BLOCKED (Ext 1 BLOCKED) 04533 External trip 1 is ACTIVE (Ext 1 ACTIVE) 04536 External trip 1: General picked up (Ext 1 picked up) 04537 External trip 1: General TRIP (Ext 1 Gen. TRIP) 04543 >BLOCK external trip 2 (>BLOCK Ext 2) 04546 >Trigger external trip 2 (>Ext trip 2)
OUT
LED
BO
51
131
OUT
ON OFF *
LED
BO
51
132
OUT
LED
BO
51
133
OUT
ON OFF ON
LED
BO
51
136
OUT
LED
BO
51
137
SP
LED BI
BO
SP
LED BI
BO
51
146
04551 External trip 2 is switched OFF (Ext 2 OFF) 04552 External trip 2 is BLOCKED (Ext 2 BLOCKED) 04553 External trip 2 is ACTIVE (Ext 2 ACTIVE) 04556 External trip 2: General picked up (Ext 2 picked up) 04557 External trip 2: General TRIP (Ext 2 Gen. TRIP) 05143 >BLOCK I2 (Unbalance Load) (>BLOCK I2)
OUT
LED
BO
51
151
OUT
ON OFF *
LED
BO
51
152
OUT
LED
BO
51
153
OUT
ON OFF ON
LED
BO
51
156
OUT
LED
BO
51
157
SP
LED BI
BO
70
126
05145 >Reverse Phase Rotation (>Reverse Rot.) 05147 Phase Rotation L1L2L3 (Rotation L1L2L3) 05148 Phase Rotation L1L3L2 (Rotation L1L3L2) 05151 I2 switched OFF (I2 OFF)
SP
LED BI
BO
71
34
OUT
LED
BO
70
128
OUT
LED
BO
70
129
OUT
LED
BO
70
131
331
General Interrogation GI GI GI GI GI GI GI GI GI GI GI GI GI GI GI GI GI GI GI
Type of Information
Log-Buffers
Configurable in Matrix
IEC 60870-5-103
Chatter Blocking
Information-No
Binary Output
Function Key
Binary Input
Type
LED
A Appendix
F.No.
Description
Function
Unbalance Load (Negative Sequence) Unbalance Load (Negative Sequence) Unbalance Load (Negative Sequence) Unbalance Load (Negative Sequence) Unbalance Load (Negative Sequence) Unbalance Load (Negative Sequence) Unbalance Load (Negative Sequence) Differential Protection Differential Protection Differential Protection Differential Protection Differential Protection Differential Protection Differential Protection Differential Protection Differential Protection Differential Protection Differential Protection Differential Protection Differential Protection
OUT
ON OFF
ON OFF
LED
BO
70
132
OUT
ON OFF
LED
BO
70
133
OUT
ON OFF
LED
BO
70
138
OUT
ON OFF
LED
BO
70
150
OUT
ON OFF
LED
BO
70
141
OUT
ON
LED
BO
70
149
OUT
ON
LED
BO
05603 >BLOCK differential protection (>Diff BLOCK) 05615 Differential protection is switched OFF (Diff OFF) 05616 Differential protection is BLOCKED (Diff BLOCKED) 05617 Differential protection is ACTIVE (Diff ACTIVE) 05620 Diff: adverse Adaption factor CT (Diff Adap.fact.) 05631 Differential protection picked up (Diff picked up) 05644 Diff: Blocked by 2.Harmon. L1 (Diff 2.Harm L1) 05645 Diff: Blocked by 2.Harmon. L2 (Diff 2.Harm L2) 05646 Diff: Blocked by 2.Harmon. L3 (Diff 2.Harm L3) 05647 Diff: Blocked by n.Harmon. L1 (Diff n.Harm L1) 05648 Diff: Blocked by n.Harmon. L2 (Diff n.Harm L2) 05649 Diff: Blocked by n.Harmon. L3 (Diff n.Harm L3) 05651 Diff. prot.: Blocked by ext. fault L1 (Diff Bl. exF.L1)
SP
LED BI
BO
OUT
LED
BO
75
15
OUT
ON OFF *
LED
BO
75
16
OUT
LED
BO
75
17
OUT
LED
BO
OUT
LED
BO
75
31
OUT
LED
BO
75
44
OUT
LED
BO
75
45
OUT
LED
BO
75
46
OUT
LED
BO
75
47
OUT
LED
BO
75
48
OUT
LED
BO
75
49
OUT
LED
BO
75
51
332
General Interrogation GI GI GI GI GI GI GI GI GI GI GI GI GI GI GI GI GI
Type of Information
Log-Buffers
Configurable in Matrix
IEC 60870-5-103
Chatter Blocking
Information-No
Binary Output
Function Key
Binary Input
Type
LED
F.No.
Description
Function
05652 Diff. prot.: Blocked by ext. fault L2 (Diff Bl. exF.L2) 05653 Diff. prot.: Blocked by ext. fault.L3 (Diff Bl. exF.L3) 05657 Diff: Crossblock by 2.Harmonic (DiffCrosBlk2HM) 05658 Diff: Crossblock by n.Harmonic (DiffCrosBlknHM) 05662 Diff. prot.: Blocked by CT fault L1 (Block Iflt.L1) 05663 Diff. prot.: Blocked by CT fault L2 (Block Iflt.L2) 05664 Diff. prot.: Blocked by CT fault L3 (Block Iflt.L3) 05666 Diff: Increase of char. phase L1 (Diff in.char.L1) 05667 Diff: Increase of char. phase L2 (Diff in.char.L2) 05668 Diff: Increase of char. phase L3 (Diff in.char.L3) 05670 Diff: Curr-Release for Trip (Diff IRelease) 05671 Differential protection TRIP (Diff TRIP)
Differential Protection Differential Protection Differential Protection Differential Protection Differential Protection Differential Protection Differential Protection Differential Protection Differential Protection Differential Protection Differential Protection Differential Protection Differential Protection Differential Protection Differential Protection Differential Protection Differential Protection Differential Protection Differential Protection Differential Protection Differential Protection Differential Protection
OUT
ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF *
LED
BO
75
52
OUT
LED
BO
75
53
OUT
LED
BO
OUT
LED
BO
OUT
LED
BO
75
62
OUT
LED
BO
75
63
OUT
LED
BO
75
64
OUT
LED
BO
OUT
LED
BO
OUT
LED
BO
OUT
LED
BO
OUT
LED
BO
176
68
05672 Differential protection: TRIP L1 (Diff TRIP L1) 05673 Differential protection: TRIP L2 (Diff TRIP L2) 05674 Differential protection: TRIP L3 (Diff TRIP L3) 05681 Diff. prot.: IDIFF> L1 (without Tdelay) (Diff> L1) 05682 Diff. prot.: IDIFF> L2 (without Tdelay) (Diff> L2) 05683 Diff. prot.: IDIFF> L3 (without Tdelay) (Diff> L3) 05684 Diff. prot: IDIFF>> L1 (without Tdelay) (Diff>> L1) 05685 Diff. prot: IDIFF>> L2 (without Tdelay) (Diff>> L2) 05686 Diff. prot: IDIFF>> L3 (without Tdelay) (Diff>> L3) 05691 Differential prot.: TRIP by IDIFF> (Diff> TRIP)
OUT
LED
BO
176
86
OUT
LED
BO
176
87
OUT
LED
BO
176
88
OUT
LED
BO
75
81
OUT
LED
BO
75
82
OUT
LED
BO
75
83
OUT
LED
BO
75
84
OUT
LED
BO
75
85
OUT
LED
BO
75
86
OUT
LED
BO
75
91
333
General Interrogation GI GI GI GI GI GI GI GI GI GI GI GI
Type of Information
Log-Buffers
Configurable in Matrix
IEC 60870-5-103
Chatter Blocking
Information-No
Binary Output
Function Key
Binary Input
Type
LED
A Appendix
F.No.
Description
Function
05692 Differential prot.: TRIP by IDIFF>> (Diff>> TRIP) 05701 Diff. curr. in L1 at trip without Tdelay (Dif L1 :) 05702 Diff. curr. in L2 at trip without Tdelay (Dif L2 :) 05703 Diff. curr. in L3 at trip without Tdelay (Dif L3 :) 05704 Restr.curr. in L1 at trip without Tdelay (Res L1 :) 05705 Restr.curr. in L2 at trip without Tdelay (Res L2 :) 05706 Restr.curr. in L3 at trip without Tdelay (Res L3 :) 05803 >BLOCK restricted earth fault prot. (>BLOCK REF) 05811 Restricted earth fault is switched OFF (REF OFF) 05812 Restricted earth fault is BLOCKED (REF BLOCKED) 05813 Restricted earth fault is ACTIVE (REF ACTIVE) 05816 Restr. earth flt.: Time delay started (REF T start) 05817 Restr. earth flt.: picked up (REF pikked up) 05821 Restr. earth flt.: TRIP (REF TRIP)
Differential Protection Differential Protection Differential Protection Differential Protection Differential Protection Differential Protection Differential Protection Restricted Earth Fault Protection Restricted Earth Fault Protection Restricted Earth Fault Protection Restricted Earth Fault Protection Restricted Earth Fault Protection Restricted Earth Fault Protection Restricted Earth Fault Protection Restricted Earth Fault Protection Restricted Earth Fault Protection Restricted Earth Fault Protection Restricted Earth Fault Protection Restricted Earth Fault Protection Time overcurrent 1Phase Time overcurrent 1Phase Time overcurrent 1Phase
OUT
ON
LED
BO
75
92
OUT
75
101
OUT
75
102
OUT
75
103
OUT
75
104
OUT
75
105
OUT
75
106
SP
OUT
LED
BO
76
11
OUT
ON OFF *
LED
BO
76
12
OUT
LED
BO
76
13
OUT
ON OFF ON OFF ON M
LED
BO
76
16
OUT
LED
BO
76
17
OUT
LED
BO
176
89
05826 REF: Value D at trip (without Tdelay) (REF D:) 05827 REF: Value S at trip (without Tdelay) (REF S:) 05830 REF err.: No starpoint CT (REF Err CTstar) 05835 REF err: Not avaliable for this objekt (REF Not avalia.) 05836 REF: adverse Adaption factor CT (REF Adap.fact.) 05951 >BLOCK Time Overcurrent 1Phase (>BLK 1Ph. O/C) 05952 >BLOCK Time Overcurrent 1Ph. I> (>BLK 1Ph. I>) 05953 >BLOCK Time Overcurrent 1Ph. I>> (>BLK 1Ph. I>>)
OUT
76
26
OUT
76
27
OUT
ON
OUT
ON
LED
BO
OUT
ON
LED
BO
SP
LED BI
BO
SP
LED BI
BO
SP
LED BI
BO
334
General Interrogation GI GI GI GI GI GI
Type of Information
Log-Buffers
Configurable in Matrix
IEC 60870-5-103
Chatter Blocking
Information-No
Binary Output
Function Key
Binary Input
Type
LED
F.No.
Description
Function
05961 Time Overcurrent 1Phase is OFF (O/C 1Ph. OFF) 05962 Time Overcurrent 1Phase is BLOKKED (O/C 1Ph. BLK) 05963 Time Overcurrent 1Phase is ACTIVE (O/C 1Ph. ACT) 05966 Time Overcurrent 1Phase I> BLOKKED (O/C 1Ph I> BLK) 05967 Time Overcurrent 1Phase I>> BLOKKED (O/C 1Ph I>> BLK) 05971 Time Overcurrent 1Phase picked up (O/C 1Ph PU) 05972 Time Overcurrent 1Phase TRIP (O/C 1Ph TRIP) 05974 Time Overcurrent 1Phase I> picked up (O/C 1Ph I> PU)
Time overcurrent 1Phase Time overcurrent 1Phase Time overcurrent 1Phase Time overcurrent 1Phase Time overcurrent 1Phase Time overcurrent 1Phase Time overcurrent 1Phase Time overcurrent 1Phase
OUT
LED
BO
76
161
OUT
ON OFF *
LED
BO
76
162
OUT
LED
BO
76
163
OUT
LED
BO
76
166
OUT
LED
BO
76
167
OUT
LED
BO
76
171
OUT
LED
BO
76
172
OUT
ON OFF ON M
LED
BO
76
174
05975 Time Overcurrent 1Phase I> TRIP (O/ Time overcurrent C 1Ph I> TRIP) 1Phase 05977 Time Overcurrent 1Phase I>> picked up (O/C 1Ph I>> PU) 05979 Time Overcurrent 1Phase I>> TRIP (O/C1Ph I>> TRIP) 05980 Time Overcurrent 1Phase: I at pick up (O/C 1Ph I:) 06851 >BLOCK Trip circuit supervision (>BLOCK TripC) 06852 >Trip circuit supervision: trip relay (>TripC trip rel) 06853 >Trip circuit supervision: breaker relay (>TripC brk rel.) 06861 Trip circuit supervision OFF (TripC OFF) 06862 Trip circuit supervision is BLOCKED (TripC BLOCKED) 06863 Trip circuit supervision is ACTIVE (TripC ACTIVE) 06864 Trip Circuit blk. Bin. input is not set (TripC ProgFail) 06865 Failure Trip Circuit (FAIL: Trip cir.) Time overcurrent 1Phase Time overcurrent 1Phase Time overcurrent 1Phase
OUT
LED
BO
76
175
OUT
ON OFF ON M
LED
BO
76
177
OUT
LED
BO
76
179
OUT
ON OFF * LED BI BO
76
180
Trip Circuit Supervi- SP sion Trip Circuit Supervi- SP sion Trip Circuit Supervi- SP sion Trip Circuit Supervi- OUT sion Trip Circuit Supervi- OUT sion Trip Circuit Supervi- OUT sion Trip Circuit Supervi- OUT sion Trip Circuit Supervi- OUT sion Time overcurrent Phase Time overcurrent Earth OUT
LED BI
BO
170
51
LED BI
BO
170
52
LED
BO
170
53
ON OFF *
LED
BO
153
16
LED
BO
153
17
LED
BO
170
54
LED
BO
170
55
ON OFF ON OFF
LED
BO
60
80
OUT
LED
BO
60
81
335
General Interrogation GI GI GI GI GI GI GI GI GI GI GI GI GI GI GI GI GI GI GI GI
Type of Information
Log-Buffers
Configurable in Matrix
IEC 60870-5-103
Chatter Blocking
Information-No
Binary Output
Function Key
Binary Input
Type
LED
A Appendix
F.No.
Description
Function
Time overcurrent Phase Time overcurrent Earth Time overcurrent Earth Time overcurrent Phase Time overcurrent Phase Time overcurrent Phase Time overcurrent 3I0 Time overcurrent 3I0 Time overcurrent 3I0 Time overcurrent Phase Time overcurrent 3I0 Time overcurrent Earth Time overcurrent Phase Time overcurrent Phase Time overcurrent Phase RTD-Box
OUT
ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF *
LED
BO
60
82
OUT
LED
BO
60
83
07564 Earth InRush picked up (Earth InRush PU) 07565 Phase L1 InRush picked up (L1 InRush PU) 07566 Phase L2 InRush picked up (L2 InRush PU) 07567 Phase L3 InRush picked up (L3 InRush PU) 07568 3I0 InRush picked up (3I0 InRush PU)
OUT
LED
BO
60
88
OUT
LED
BO
60
89
OUT
LED
BO
60
90
OUT
LED
BO
60
91
OUT
LED
BO
60
95
07569 3I0> InRush picked up (3I0> InRush PU) 07570 3I0p InRush picked up (3I0p InRush PU) 07571 >BLOCK time overcurrent Phase InRush (>BLK Ph.O/C Inr) 07572 >BLOCK time overcurrent 3I0 InRush (>BLK 3I0O/C Inr) 07573 >BLOCK time overcurrent Earth InRush (>BLK E O/C Inr) 07581 Phase L1 InRush detected (L1 InRush det.) 07582 Phase L2 InRush detected (L2 InRush det.) 07583 Phase L3 InRush detected (L3 InRush det.) 14101 Fail: RTD (broken wire/shorted) (Fail: RTD) 14111 Fail: RTD 1 (broken wire/shorted) (Fail: RTD 1) 14112 RTD 1 Temperature stage 1 picked up (RTD 1 St.1 p.up) 14113 RTD 1 Temperature stage 2 picked up (RTD 1 St.2 p.up) 14121 Fail: RTD 2 (broken wire/shorted) (Fail: RTD 2) 14122 RTD 2 Temperature stage 1 picked up (RTD 2 St.1 p.up) 14123 RTD 2 Temperature stage 2 picked up (RTD 2 St.2 p.up)
OUT
LED
BO
60
96
OUT
LED
BO
60
97
SP
LED BI
BO
60
98
SP
LED BI
BO
60
99
SP
LED BI
BO
60
100
OUT
LED
BO
OUT
LED
BO
OUT
LED
BO
OUT
LED
BO
RTD-Box
OUT
LED
BO
RTD-Box
OUT
LED
BO
RTD-Box
OUT
LED
BO
RTD-Box
OUT
LED
BO
RTD-Box
OUT
LED
BO
RTD-Box
OUT
LED
BO
336
General Interrogation GI GI GI GI GI GI GI GI GI GI GI GI
Type of Information
Log-Buffers
Configurable in Matrix
IEC 60870-5-103
Chatter Blocking
Information-No
Binary Output
Function Key
Binary Input
Type
LED
F.No.
Description
Function
14131 Fail: RTD 3 (broken wire/shorted) (Fail: RTD 3) 14132 RTD 3 Temperature stage 1 picked up (RTD 3 St.1 p.up) 14133 RTD 3 Temperature stage 2 picked up (RTD 3 St.2 p.up) 14141 Fail: RTD 4 (broken wire/shorted) (Fail: RTD 4) 14142 RTD 4 Temperature stage 1 picked up (RTD 4 St.1 p.up) 14143 RTD 4 Temperature stage 2 picked up (RTD 4 St.2 p.up) 14151 Fail: RTD 5 (broken wire/shorted) (Fail: RTD 5) 14152 RTD 5 Temperature stage 1 picked up (RTD 5 St.1 p.up) 14153 RTD 5 Temperature stage 2 picked up (RTD 5 St.2 p.up) 14161 Fail: RTD 6 (broken wire/shorted) (Fail: RTD 6) 14162 RTD 6 Temperature stage 1 picked up (RTD 6 St.1 p.up) 14163 RTD 6 Temperature stage 2 picked up (RTD 6 St.2 p.up) 14171 Fail: RTD 7 (broken wire/shorted) (Fail: RTD 7) 14172 RTD 7 Temperature stage 1 picked up (RTD 7 St.1 p.up) 14173 RTD 7 Temperature stage 2 picked up (RTD 7 St.2 p.up) 14181 Fail: RTD 8 (broken wire/shorted) (Fail: RTD 8) 14182 RTD 8 Temperature stage 1 picked up (RTD 8 St.1 p.up) 14183 RTD 8 Temperature stage 2 picked up (RTD 8 St.2 p.up) 14191 Fail: RTD 9 (broken wire/shorted) (Fail: RTD 9) 14192 RTD 9 Temperature stage 1 picked up (RTD 9 St.1 p.up) 14193 RTD 9 Temperature stage 2 picked up (RTD 9 St.2 p.up) 14201 Fail: RTD10 (broken wire/shorted) (Fail: RTD10)
RTD-Box
OUT
ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF
LED
BO
RTD-Box
OUT
LED
BO
RTD-Box
OUT
LED
BO
RTD-Box
OUT
LED
BO
RTD-Box
OUT
LED
BO
RTD-Box
OUT
LED
BO
RTD-Box
OUT
LED
BO
RTD-Box
OUT
LED
BO
RTD-Box
OUT
LED
BO
RTD-Box
OUT
LED
BO
RTD-Box
OUT
LED
BO
RTD-Box
OUT
LED
BO
RTD-Box
OUT
LED
BO
RTD-Box
OUT
LED
BO
RTD-Box
OUT
LED
BO
RTD-Box
OUT
LED
BO
RTD-Box
OUT
LED
BO
RTD-Box
OUT
LED
BO
RTD-Box
OUT
LED
BO
RTD-Box
OUT
LED
BO
RTD-Box
OUT
LED
BO
RTD-Box
OUT
LED
BO
337
General Interrogation
Type of Information
Log-Buffers
Configurable in Matrix
IEC 60870-5-103
Chatter Blocking
Information-No
Binary Output
Function Key
Binary Input
Type
LED
A Appendix
F.No.
Description
Function
14202 RTD10 Temperature stage 1 picked up (RTD10 St.1 p.up) 14203 RTD10 Temperature stage 2 picked up (RTD10 St.2 p.up) 14211 Fail: RTD11 (broken wire/shorted) (Fail: RTD11) 14212 RTD11 Temperature stage 1 picked up (RTD11 St.1 p.up) 14213 RTD11 Temperature stage 2 picked up (RTD11 St.2 p.up) 14221 Fail: RTD12 (broken wire/shorted) (Fail: RTD12) 14222 RTD12 Temperature stage 1 picked up (RTD12 St.1 p.up) 14223 RTD12 Temperature stage 2 picked up (RTD12 St.2 p.up) 30607 Accumulation of interrupted curr. L1 S1 (IL1S1:) 30608 Accumulation of interrupted curr. L2 S1 (IL2S1:) 30609 Accumulation of interrupted curr. L3 S1 (IL3S1:) 30610 Accumulation of interrupted curr. L1 S2 (IL1S2:) 30611 Accumulation of interrupted curr. L2 S2 (IL2S2:) 30612 Accumulation of interrupted curr. L3 S2 (IL3S2:) 30620 Accumulation of interrupted curr. I1 (I1:) 30621 Accumulation of interrupted curr. I2 (I2:) 30622 Accumulation of interrupted curr. I3 (I3:) 30623 Accumulation of interrupted curr. I4 (I4:) 30624 Accumulation of interrupted curr. I5 (I5:) 30625 Accumulation of interrupted curr. I6 (I6:) 30626 Accumulation of interrupted curr. I7 (I7:) >Back Light on (>Light on)
RTD-Box
OUT
LED
BO
RTD-Box
OUT
LED
BO
RTD-Box
OUT
LED
BO
RTD-Box
OUT
LED
BO
RTD-Box
OUT
LED
BO
RTD-Box
OUT
LED
BO
RTD-Box
OUT
LED
BO
RTD-Box
OUT
LED
BO
Statistics
OUT
Statistics
OUT
Statistics
OUT
Statistics
OUT
Statistics
OUT
Statistics
OUT
Statistics
OUT
Statistics
OUT
Statistics
OUT
Statistics
OUT
Statistics
OUT
Statistics
OUT
Statistics
OUT
Device
SP
ON OFF
LED BI
BO
338
General Interrogation
Type of Information
Log-Buffers
Configurable in Matrix
IEC 60870-5-103
Chatter Blocking
Information-No
Binary Output
Function Key
Binary Input
Type
LED
F.No.
Description
Function
IntSP
LED BI
FK
BO
IntSP_ Ev IntSP
LED
BO
ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF *
LED
101
85
IntSP
LED
101
86
IntSP
LED
OUT
LED
BO
Supervision
OUT
LED
BO
Supervision
IntSP
LED
BO
IntSP
LED
BO
Group A (Group A)
IntSP
LED
BO
176
23
Group B (Group B)
Change Group
IntSP
LED
BO
176
24
Group C (Group C)
Change Group
IntSP
LED
BO
176
25
Group D (Group D)
Change Group
IntSP
LED
BO
176
26
Device
IntSP
LED
BO
IntSP
LED
BO
IntSP
LED
BO
176
20
Device
IntSP
LED
BO
176
21
Threshold-Switch
IntSP
LED BI
FK
BO
CB
Device
IntSP
LED
BO
339
General Interrogation GI GI GI GI GI GI GI GI
Type of Information
Log-Buffers
Configurable in Matrix
IEC 60870-5-103
Chatter Blocking
Information-No
Binary Output
Function Key
Binary Input
Type
LED
A Appendix
A.9
F.No.
Information-No
Function type
Compatibility
Position 1 5 3 2 6 4 1 2 3 4 5 6 7 8 9 10 11 12
00644 00645 00721 00722 00723 00724 00725 00726 00801 00802 00803 00804 01060 01061 01062 01063 01066 01067 01068 01069 01070 01071 01072 01073 01074 01075 01076 01077 01078 01079 07740 07741 07742
Frequency (Freq=) S (apparent power) (S =) Operat. meas. current IL1 side 1 (IL1S1=) Operat. meas. current IL2 side 1 (IL2S1=) Operat. meas. current IL3 side 1 (IL3S1=) Operat. meas. current IL1 side 2 (IL1S2=) Operat. meas. current IL2 side 2 (IL2S2=) Operat. meas. current IL3 side 2 (IL3S2=) Temperat. rise for warning and trip ( /trip =) Temperature rise for phase L1 ( /tripL1=) Temperature rise for phase L2 ( /tripL2=) Temperature rise for phase L3 ( /tripL3=) Hot spot temperature of leg 1 ( leg 1=) Hot spot temperature of leg 2 ( leg 2=) Hot spot temperature of leg 3 ( leg 3=) Aging Rate (Ag.Rate=) Load Reserve to warning level (ResWARN=) Load Reserve to alarm level (ResALARM=) Temperature of RTD 1 ( RTD 1 =) Temperature of RTD 2 ( RTD 2 =) Temperature of RTD 3 ( RTD 3 =) Temperature of RTD 4 ( RTD 4 =) Temperature of RTD 5 ( RTD 5 =) Temperature of RTD 6 ( RTD 6 =) Temperature of RTD 7 ( RTD 7 =) Temperature of RTD 8 ( RTD 8 =) Temperature of RTD 9 ( RTD 9 =) Temperature of RTD10 ( RTD10 =) Temperature of RTD11 ( RTD11 =) Temperature of RTD12 ( RTD12 =) Phase angle in phase IL1 side 1 (IL1S1=) Phase angle in phase IL2 side 1 (IL2S1=) IDiffL1(I/Inominal object [%]) (IDiffL1=)
Measurement Measurement Measurement Measurement Measurement Measurement Measurement Measurement Thermal Measurement Thermal Measurement Thermal Measurement Thermal Measurement Thermal Measurement Thermal Measurement Thermal Measurement Thermal Measurement Thermal Measurement Thermal Measurement Thermal Measurement Thermal Measurement Thermal Measurement Thermal Measurement Thermal Measurement Thermal Measurement Thermal Measurement Thermal Measurement Thermal Measurement Thermal Measurement Thermal Measurement Thermal Measurement Measurement Measurement Diff- and Rest. Measurement 134 134 134 134 134 134 134 134 134 134 134 134 146 146 146 146 146 146 146 146 146 146 146 146 priv priv priv priv priv priv priv priv priv priv priv priv 9 9 9 9 9 9 9 9 9 9 9 9 134 134 134 134 134 134 139 139 139 139 139 139 priv priv priv priv priv priv 9 9 9 9 9 9
340
CFC
CFC CD CFC CD CFC CD CFC CD CFC CD CFC CD CFC CD CFC CD CFC CD CFC CD CFC CD CFC CD CFC CD CFC CD CFC CD CFC CD CFC CD CFC CD CFC CD CFC CD CFC CD CFC CD CFC CD CFC CD CFC CD CFC CD CFC CD CFC CD CFC CD CFC CD CFC CD CFC CD CFC CD
F.No.
Description
Function
Information-No
Function type
Compatibility
Position
07743 07744 07745 07746 07747 07749 07750 07759 07760 30633 30634 30635 30636 30637 30638 30639 30640 30641 30642 30643 30644 30645 30646 30647 30648 30649 30650 30651 30652 30653 30654 30655 30656
IDiffL2(I/Inominal object [%]) (IDiffL2=) IDiffL3(I/Inominal object [%]) (IDiffL3=) IRestL1(I/Inominal object [%]) (IRestL1=) IRestL2(I/Inominal object [%]) (IRestL2=) IRestL3(I/Inominal object [%]) (IRestL3=) Phase angle in phase IL3 side 1 (IL3S1=) Phase angle in phase IL1 side 2 (IL1S2=) Phase angle in phase IL2 side 2 (IL2S2=) Phase angle in phase IL3 side 2 (IL3S2=) Phase angle of current I1 (I1=) Phase angle of current I2 (I2=) Phase angle of current I3 (I3=) Phase angle of current I4 (I4=) Phase angle of current I5 (I5=) Phase angle of current I6 (I6=) Phase angle of current I7 (I7=) 3I0 (zero sequence) of side 1 (3I0S1=) I1 (positive sequence) of side 1 (I1S1=) I2 (negative sequence) of side 1 (I2S1=) 3I0 (zero sequence) of side 2 (3I0S2=) I1 (positive sequence) of side 2 (I1S2=) I2 (negative sequence) of side 2 (I2S2=) Operat. meas. current I1 (I1=) Operat. meas. current I2 (I2=) Operat. meas. current I3 (I3=) Operat. meas. current I4 (I4=) Operat. meas. current I5 (I5=) Operat. meas. current I6 (I6=) Operat. meas. current I7 (I7=) Operat. meas. current I8 (I8=) Idiff REF (I/Inominal object [%]) (IdiffREF=) Irest REF (I/Inominal object [%]) (IrestREF=) Operat. meas. voltage Umeas. (Umeas.=) Operating hours greater than (OpHour>)
Diff- and Rest. Measurement Diff- and Rest. Measurement Diff- and Rest. Measurement Diff- and Rest. Measurement Diff- and Rest. Measurement Measurement Measurement Measurement Measurement Measurement Measurement Measurement Measurement Measurement Measurement Measurement Measurement Measurement Measurement Measurement Measurement Measurement Measurement Measurement Measurement Measurement Measurement Measurement Measurement Measurement Diff- and Rest. Measurement Diff- and Rest. Measurement Measurement
CFC CFC CFC CFC CFC CFC CFC CFC CFC CFC CFC CFC CFC CFC CFC CFC CFC CFC CFC CFC CFC CFC CFC CFC CFC CFC CFC CFC CFC CFC CFC CFC CFC CFC CFC
341
A Appendix
n
342
Index
A
Accessories 288 Acknowledgement of commands 194 Additional support ii Ageing rate 136 Alternating voltage 249 Ambient temperatures 256 Applicability of manual i Applications 5 Auto-transformers 15, 46 Auxiliary contacts of the CB 108, 153, 163, 203, Command sequence 190 Command types 189 Commissioning 222 Communication interfaces 250 Configuration 14 Scope of functions 14 Conformity i Connection examples 293 Construction 257 Control and numeric keys 4 Copyright ii Cubicle mounting 199 Current balance supervision 161 Current comparison 33 Current grading 82 Current guard 51, 56 Current restraint 34 Current transformer data 23, 25, 26, 27, 118 Current transformer requirements 248
229
Auxiliary voltage supervision 160
B
Backup battery 160 Battery 160, 281, 289 Binary inputs 3, 249 Binary outputs 3, 175, 249 Block data transmission 223 Branch-points 15, 22, 50, 262 Breaker failure protection 152, 228, 278 Buffer battery 281, 289 Busbar protection 50, 52, 81 Busbars 15, 22, 23, 50, 52, 262
D
Danger (definition) ii DCF77 281 Definite time overcurrent protection 73, 97 Differential current monitoring 51, 56 Differential protection 33, 258 for branch-points 50, 262 for busbars 50, 52, 262 for generators 48, 261 for lines 50, 262 for mini-busbars 50, 262 for motors 48, 261 for reactors 48, 49, 261 for series reactors 48 for short lines 50, 262 for shunt reactors 49 for transformers 42 restricted earth fault protection 64, 263 Differential protection values 181 DIGSI 4 289 DIGSI REMOTE 4 289 Dimensions 282
C
Caution (definition) ii CFC 10, 281, 290 Changeover of setting groups 202 Circuit breaker auxiliary contacts 108, 153, 163,
203, 229
Circuit breaker failure protection 152, 228, 278 Circuit breaker status 27, 108 Climatic tests 256 Cold load pickup 108, 272 Command acknowledgement 194 Command duration 27 Command processing 189
343
Index
Direct trip 278 Direct voltage 248 Disassembling the device 207 Disk emulation 78, 100, 124 Display of measured values 179 Dynamic cold load pickup 108, 272
Hardware structure 2 Harmonic restraint 37 High-current trip 37 High-impedance differential protection 115 High-impedance principle 115 High-impedance protection 118 Hot-spot calculation 135, 277 Humidity 256
E
Earthing reactor (starpoint former) 15, 44, 45, 49,
64
Electrical tests 253 EMC tests 254, 255 Emergency starting 132 Event log 177 External signals 278 External trip 278
I
IBS-tool 181 Increase of pickup value on startup 38, 108 Information list 323 Inrush current 37, 79, 101 Inrush restraint 37, 79, 101 Installation 198 in cubicles 199 in panels (flush) 198 in racks 199 on panels (surface) 200 Insulation tests 253 Interface cable 289 Interface modules 213, 288 Interlocking 191 Inverse time overcurrent protection 76, 99 IRIG B 281
F
Fault detection 39, 171 Fault detection logic 171 Fault messages 177 Fault reactions 165 Fault recording 183, 281 Features 7 Feeder current guard 51, 56 Flush mounting 198 Front elements 4 Function control 171
L
LCD 4 LED 4 Lines 15, 22, 42, 50, 262 List of information 323 List of measured values 340 List of settings 308 Lock-out 172
G
General diagrams 291 General fault detection 171 General interrogation 178 General pickup 171 General protection data 32 General tripping 172 Generators 15, 22, 48, 261 Graphic tools 289 Graphical analysis program SIGRA 289 Graphical symbols iii Group alarms 166
M
Manual close 79, 101 Measured quantities supervision 161 Measured values 179, 180, 280 Mechanical tests 255 Memory modules 160 Mini-busbars 15, 22, 50, 262 Modem interface 250 Monitoring functions 160, 279 Motors 15, 22, 48, 261 Mounting brackets 289
H
Hardware modifications 205 Hardware monitoring 160
344
Index
N
No trip no flag 173 Nominal current 23, 24, 25, 26, 248 Nominal currents, alteration 205, 211 Nominal frequency 20 Note (definition) ii
R
Rack mounting 199 Rated current 23, 24, 25, 26, 248 Rated currents, alteration 205, 211 Rated frequency 20 Reactions to fault 165 Reactors 15, 22, 48, 49, 261 Reassembling the device 217 Reclosure interlocking 172 Relative ageing 136 Reset time curves time overcurrent protection (ANSI) 269 unbalanced load protection (ANSI) 269 user defined 16, 87 Resistance stabilization 116 Resistance temperature detector 17 Restraint add-on stabilization 36 current stabilization 34 differential protection 34 harmonic restraint 37 inrush restraint 37, 79, 101 resistance stabilization 116 restricted earth fault protection 67 Restricted earth fault protection 64, 263 Reverse interlocking 81 RTD 17
O
Operating interface 4, 250 Operating measured values 180 Operating messages 177 Operating software DIGSI 289 Ordering code 286 Ordering information 286 Ordering number 286 Output relays 175, 249 Overload protection 131, 275
P
Panel flush mounting 198 Panel surface mounting 200 Parameter names iii Parameter options iii Phase sequence 20, 162 Phase sequence supervision 162 Pickup of the entire device 171 Plug-in socket boxes 289 Power supply 4, 205, 248 Power system data 1 20 Power system data 2 32 Power transformers 15, 20, 42, 259 auto-transformers 15, 46 single-phase transformers 15, 46 with isolated windings 15 Preset configurations 305 Processing of commands 189 Processing of messages 175 Protection function control 171 Protocol dependent functions 307
S
Sampling frequency 161 SCADA interface 4, 251 Scope of functions 7, 14 Serial interfaces 4 Series reactors 15, 22, 48, 261 Service conditions 256 Service interface 4, 250 Set-points 182 Setting consistency 167, 227 Setting errors 167 Setting groups 30 Changeover 202 Setting list 308 Shock and vibration 255 Short lines 15, 22, 50, 262 Short-circuit links 288 Shunt reactors 15, 22, 49, 261 SIGRA 4 289 Single-phase differential protection 52 Single-phase time overcurrent protection 113, 273 Single-phase transformers 15, 46
Q
Qualified personnel (definition) ii
345
Index
Software monitoring 161 Spare parts 206 Spontaneous annunciations 178 Spontaneous displays 171, 177 Standard interlocking 192 Starpoint condition 21, 26, 42, 46, 47, 57 Starpoint former (earthing reactor) 15, 44, 45, 49,
64
Startup 38, 108, 132 Statistics 173, 178, 281 Sudden pressure relays 157 Summation CTs 52 Support ii Surface mounting 200 Symbol conventions iii System interface 4, 251
T
Tank leakage protection 117, 121 Target audience of manual i Temperature unit 20 Temperatures 256 Terminal block covering caps 288 Termination variants 201 Test operation 223 Test recordings 243 Thermal differential equation 131 Thermal overload protection 131, 275 Thermal replica 131, 275 Thermal set-points 143 Thermal time constant 131 Thermal values 181 Thermobox 17, 143, 250, 277, 288 Time overcurrent protection cold load pickup 108 for earth current 97 for phase currents 73 for residual current 73 for starpoint current 97 single-phase 113, 273 Time synchronization 4, 253 Traction transformers 15, 46 Transformer messages 157 n
Transformers 15, 20, 42, 259 auto-transformers 15, 46 power transformers 42 single-phase transformers 15, 46 with isolated windings 15 Transmission blocking 223 Transmission of measured values 179 Transverse differential protection 48 Trip circuit supervision 162, 203 Trip command duration 27 Trip log 177 Tripping characteristic differential protection 39, 258 restricted earth fault protection 69, 263 thermal overload protection 276 time overcurrent protection (ANSI) 267, 268 time overcurrent protection (IEC) 266 unbalanced load protection (ANSI) 267 unbalanced load protection (IEC) 266 Tripping logic 172 Types of commands 189 Typographic conventions iii
U
Unbalanced load protection 123, 274 User defined functions 10, 281 User defined reset time curves 16, 87 User defined set-points 182 User specified curves 86, 105
V
Vibration and shock 255 Voltage measurement 179
W
Warning (definition) ii Watchdog 161
346
Corrections
To Siemens AG Dept. PTD PA D DM D13623 Berlin Germany Dear reader, printing errors can never be entirely eliminated: therefore, should you come across any when reading this manual, kindly enter them in this form together with any comments or suggestions for improvement that you may have. Corrections/Suggestions Address: Company/Dept.: From Name:
Phone no.:
Fax no.:
Copying of this document and giving it to others and the use or communication of the contents thereof, are forbidden without express authority. Offenders are liable to the payment of damages. All rights are reserved in the event of the grant of a patent or the registration of a utility model or design. Order-no.: C53000G1176C1481 Available from: LZF Frth-Bislohe Printed in Germany/Imprim en Allemagne AG 0202 0.3 FO 358 En
Siemens Aktiengesellschaft