7ss60x Manual
7ss60x Manual
7ss60x Manual
SIPROTEC 7SS60
V3.1
E50417-G1176-C132-A2
,QWURGXFWLRQ
'HVLJQ DQG &RQQHFWLRQ 6\VWHP
SIPROTEC
Centralized Numerical
Busbar Protection
7SS60
*HWWLQJ 6WDUWHG
&RQILJXUDWLRQ
)XQFWLRQV
3.1
&RQWURO LQ 2SHUDWLRQ
Manual
E50417-G1176-C132-A2
1
2
3
4
5
6
7
8
9
A
Preface
Aim of this manual
This manual describes the functions, operation, installation, and commissioning of the
device. In particular, you will find:
Description of the system configuration Chapter 4;
Description of the system functions and setting possibilities Chapter 5;
Hints on control during operation Chapter 6;
Instructions for installation and commissioning Chapter 7;
List of the technical data Chapter 9;
Summary of the most significant data for the experienced user in the Appendix.
Target audience
Protection engineers, commissioners, persons who are involved in setting, testing and
maintenance of protection, automation, and control devices, as well as operation personnel in electrical plants and power stations.
Validity of this
manual
Indication of Conformity
This product complies with the directive of the Council of the European Communities
on the approximation of the laws of the Member States relating to electromagnetic
compatibility (EMC Council Directive 89/336/EEC) and concerning electrical equipment for use within specified voltage limits (Low-voltage directive 73/23 EEC).
Conformity is proved by tests conducted by Siemens AG in accordance with Article 10
of the Council Directive in agreement with the generic standards EN 50081 and EN
50082 (for EMC directive) and the standards EN 60255-6 (for low-voltage directive).
The device is designed in accordance with the international standards of IEC 255 and
the German standards DIN 57 435 part 303 (corresponding to VDE 0435 part 303).
Additional support
For any questions concerning your SIPROTEC system, please contact your Siemens
representative.
Training courses
Individual course offers may be found in our Training Catalog, or questions can be directed to our training centre.
7SS60 Manual
E50417-G1176-C132-A2
Preface
Instructions and
warnings
The warnings and notes contained in this manual serve for your own safety and for an
appropriate lifetime of the device. Please observe them!
The following terms and definitions are used:
DANGER
indicates that death, severe personal injury or substantial property damage will result
if proper precautions are not taken.
Warning
indicates that death, severe personal injury or substantial property damage can result
if proper precautions are not taken.
Caution
indicates that minor personal injury or property damage can result if proper precautions are not taken. This is especially valid for damage on or in the device itself and
consequential damage thereof.
Note
indicates information about the device or respective part of the instruction manual
which is essential to highlight.
Warning!
Hazardous voltages are present in this electrical equipment during operation. Non
observance of the safety rules can result in severe personal injury or property damage.
Only qualified personnel shall work on and around this equipment after becoming thoroughly familiar with all warnings and safety notices of this manual as well as with the
applicable safety regulations.
The successful and safe operation of this device is dependent on proper handling, installation, operation, and maintenance by qualified personnel under observance of all
warnings and hints contained in this manual.
In particular the general erection and safety regulations (e.g. IEC, DIN, VDE, EN or
other national and international standards) regarding the correct use of hoisting gear
must be observed. Nonobservance can result in death, personal injury or substantial
property damage.
QUALIFIED PERSONNEL
For the purpose of this instruction manual and product labels, a qualified person is one
who is familiar with the installation, construction and operation of the equipment and
the hazards involved. In addition, he or she has the following qualifications:
Is trained and authorized to energize, de-energize, clear, ground and tag circuits
and equipment in accordance with established safety practices.
Is trained in the proper care and use of protective equipment in accordance with established safety practices.
Is trained in rendering first aid.
ii
7SS60 Manual
E50417-G1176-C132-A2
Preface
Typographical and
symbol
conventions
The following text formats are used when literal information from the device or to the
device appear in the text flow:
3DUDPHWHU QDPHV, i.e. designators of configuration or function parameters, which
may appear word-for-word in the display of the device or on the screen of a personal
computer (with DIGSI 3), are marked in bold letters of a monospace type style.
3DUDPHWHU RSWLRQV, i.e. possible settings of text parameters, which may appear
word-for-word in the display of the device or on the screen of a personal computer
(with DIGSI 3), are written in italic style, additionally. This applies also for options in
menus.
$QQXQFLDWLRQV, i.e. designators for information, which may be output by the relay
or required from other devices or from the switch gear, are marked in a monospace
type style in quotes.
Deviations may be permitted in drawings when the type of designator can be obviously
derived from the illustration.
@hushy
@hushy
UL1L2
FNo
3Sryrhr
FNo
Dev. TRIP
Parameter address
Parameter name
AVI8UDPI
2Q
2II
Parameter states
The other symbols used are mainly taken from the standards IEC 6061712 and
IEC 6061713, or derived from them.
Disclaimer of liability
Although we have carefully checked the contents of this
publication for conformity with the hardware and software
described, we cannot guarantee complete conformity
since errors cannot be excluded.
The information provided in this manual is checked at
regular intervals and any corrections which might become necessary are included in the next releases. Any
suggestions for improvement are welcome.
The contents of this manual is subject to change without
prior notice. Release 3.10.01
7SS60 Manual
E50417-G1176-C132-A2
Copyright
Copyright Siemens AG 2001 All Rights Reserved
This document shall not be transmitted or reproduced, nor shall its contents
be exploited or disclosed to third persons without prior written consent from
Siemens. Infringements shall entitle to damage claims. All rights reserved,
in particular in case of a patent grant or utility model registration.
Registered Trademarks
iii
Preface
iv
7SS60 Manual
E50417-G1176-C132-A2
Contents
1
Introduction....................................................................................................................................... 1-1
1.1
1.2
1.3
2.2
3.2
3.2.1
3.2.2
3.3
3.3.1
Operation from the user interface of the 7SS601 measuring system.................................. 3-5
3.3.2
3.3.3
3.4
4.2
4.2.1
4.2.2
4.2.2.1
4.2.2.2
4.2.2.3
4.2.3
4.2.3.1
4.2.3.2
4.2.3.3
4.2.3.4
7SS60 Manual
E50417-G1176-C132-A2
Contents
vi
4.2.3.5
4.2.4
4.2.4.1
4.2.4.2
4.2.4.3
4.2.5
4.2.5.1
4.2.5.2
Functions........................................................................................................................................... 5-1
5.1
5.2
5.3
5.3.1
5.3.2
5.3.3
5.3.4
5.4
5.4.1
5.4.2
5.4.3
5.4.4
5.5
5.5.1
5.5.2
5.5.3
5.5.4
5.6
5.6.1
5.6.2
5.6.3
6.1.1
6.2
6.3
7SS60 Manual
E50417-G1176-C132-A2
Contents
7.1.1
7.1.2
7.2
7.2.1
7.2.1.1
7.2.2
7.2.2.1
Check of the complete protection system with operating currents ...................................... 7-8
Directional check of the input currents ................................................................................ 7-8
General................................................................................................................................ 8-2
8.2
8.2.1
8.2.2
8.3
Troubleshooting................................................................................................................... 8-4
8.3.1
8.3.2
8.4
9.1.1
9.1.2
9.1.2.1
9.1.2.2
9.1.2.3
9.1.3
9.1.4
9.1.5
9.2
9.3
9.4
9.5
9.6
Dimensions........................................................................................................................ 9-15
7SS60 Manual
E50417-G1176-C132-A2
vii
Contents
viii
Appendix........................................................................................................................................... A-1
A.1
A.2
A.3
A.4
A.5
A.6
Operating tree....................................................................................................................A-14
A.7
A.8
7SS60 Manual
E50417-G1176-C132-A2
Introduction
The SIPROTEC 7SS60 device is introduced in this chapter. An overview of the application and characteristics of the 7SS60 is given.
7SS60 Manual
E50417-G1176-C132-A2
1.1
Overall function
1-2
1.2
Application scope
1-6
1.3
Features
1-8
1-1
Introduction
1.1
Overall function
Measuring
principle
The main function of the 7SS60 protection system is a busbar protection that operates
with the differential current measuring principle. The algorithm of the 7SS60 relies on
Kirchhoffs current law, which states that in fault-free condition the vectorial sum I
flowing into a closed busbar section must be zero. This summated current will be referred to in this chapter as differential current Id.
Restraint
Some slight deviations from this law may be caused by current transformer errors, inaccuracies in the matching of the transformation ratios and measuring inaccuracies.
Further errors, which may be due, for instance, to transformer saturation in case of
high-current external short-circuits, are counteracted by a load-dependent supplementary restraint. From the load condition the restraint current IR is derived. This restraint current is formed as the summated magnitudes of all currents in the peripheral
module 7TM700.
Detection of
measured values
The differential and the restraint current are fed into the 7SS601 measuring system.
In systems with multiple busbars or sectionalized busbars, each selective section uses
one 7SS601 measuring system (variant with summation current transformer) or three
measuring systems (phase-selective measurement). The correct allocation of the
feeder currents to the appropriate 7SS601 measuring system is ensured by the peripheral module 7TR710 (preferential treatment/isolator replica).
Pick-up
characteristic
The characteristic can be set in the parameters for Id> (pick-up value) and for the
k factor, which considers the linear and non-linear current transformer errors. The setting for the pick-up value must be chosen according to the smallest fault current to be
expected. Differential currents above the set characteristic lead to tripping. The
threshold for the differential current supervision is set in the parameter ID thr.
Differential current Id
Tripping zone
Restraint
zone
k = 0.80
.
.
.
.
.
.
.
.
k = 0,25
Pick-up
characteristics
Id>
Normal load line
ID thr
0
Figure 1-1
Selective tripping,
isolator replica
1-2
Restraint current IR
7SS60 Manual
E50417-G1176-C132-A2
Introduction
Functional
components
The 7SS60 digital busbar protection has two separate functional parts. One part is the
7SS601 measuring system. The measuring system detects and processes the measured values. It evaluates the restraint current IR and the differential current Id and
makes a tripping decision where required. The other part of the system, which will be
referred to as peripheral system, has the task of summating the feeder currents and
feeding the current sum into the measured value detection system. The current summation takes into account the switchgear status of the station.
If selective protection is desired for each phase, each phase is allocated its own measuring system. Otherwise, the three phase currents are combined in a summation current transformer, and the result processed. In that case only one measuring system is
required.
If a busbar is divided into two sections by a sectionalizing isolator or a bus coupler,
each section must have its own measuring system. Accordingly, six measuring systems are required for the phase-selective protection.
7SS601
measuring system
The 7SS601 measuring system can detect one alternating current Id and one pulsating direct current IR. The measuring inputs are galvanically isolated from the electronic
equipment by a current transformer or an optocoupler.
3 binary inputs are provided for the detection of external binary signals.
The system has 2 command relays with supervision. Command relay 1 consists of 2
relays connected in parallel. This relay cannot be marshalled; the function %3 7ULS
()1R ) is permanently allocated to it. Command relay 2 is available for having
command functions marshalled to it. All command relays have a NO contact.
It has also 3 signal relays with changeover contacts, one of which is used for output
of the device blocked annunciation. The relay functionality (NC or NO) can be selected
by a jumper setting. The module is equipped with a serial RS485 interface. The converter for the auxiliary power supply is integrated in the module.
Peripheral system
Depending on the type and size of the systems that are to be protected by the 7SS60
busbar protection, different types and numbers of peripheral modules are needed. The
peripheral modules are installed in a 7XP204 housing; the number of housings required is determined by the number of modules used. Each 7XP204 housing can hold
up to 4 peripheral modules.
The following modules are available for the different functions:
Restraint/command output module 7TM700
Preferential treatment/isolator replica module 7TR710
Command output module 7TS720
Restraint/command
output module
7TM700
This module comprises 5 units for the formation of restraint currents. It has also 5 independent TRIP command relays with 2 NO contacts each for multiplication of TRIP
commands generated by the 7SS601 measuring system.
The secondary current from the main current transformer of a feeder is normalized to
100 mA by a matching or summation current transformer and fed into the Id summation path of the associated measuring system. The summation current Id is thus equivalent to the vectorial addition of all feeder currents. Beside Id, the measuring system
requires a restraint value, which is formed by adding up the magnitudes of all currents.
The restraint units are used to form the current magnitudes. They rectify the feeder
currents and add them up in the IR summation path.
7SS60 Manual
E50417-G1176-C132-A2
1-3
Introduction
Isolator replica
module/preferential
treatment module
This module can be used to implement 2 different functions which will be presented in
the following.
Isolator replica
Preferential
treatment
If, during a changeover of a feeder in a double busbar system, both isolators of a feeder are closed for a short time, no selective protection of the two busbars is possible.
The same is true for busbar sections that are connected by closing a sectionalizing
isolator. Whereas each of the two sections has so far been protected by its own measuring system, the protection function is assumed by only one measuring system after
connecting the two sections. This is referred to as preferential treatment.
As several relays or modules may be involved in the switching action, there may be
an undefined allocation of the differential and restraint currents to the measuring systems during a few milliseconds caused by different relay switching times.
The blocking pulse required for system stability is generated automatically on the
module within the corresponding time.
Also an auxiliary relay is included with two changeover contacts.
Command output
module 7TS720
This module comprises 8 independent command relays with 2 NO contacts each for
multiplication of the TRIP command generated by the 7SS601 measuring system.
It is necessary to multiply the TRIP command if the two NO contacts of the 7TR710
modules are not sufficient for command output to the circuit breakers. The measuring
system initiates the TRIP command first through a NO contact. In the simplest case,
an auxiliary voltage is fed directly from this contact onto the 7TS720 module, where it
causes one or more relay coils to pick up.
Transformers
Figure 1-2
1-4
The differential current input Id of the 7SS60 is designed for 1 x In = 100 mA. Therefore, a transformer must be provided between the 7SS60 and the main current transformer. In phase-selective protection systems, matching transformers are used; otherwise there will be summation current transformers.
Principle diagram of transformers in the 7SS60 (one phase of a phase-selective protection system)
7SS60 Manual
E50417-G1176-C132-A2
Introduction
Wiring
The 7SS60 busbar protection system is suited for a large variety of power systems,
from single busbar configurations without sectionalizing isolators to double busbars
with sectionalizing isolators and transversal couplers. The summation currents Id and
IR are distributed among the measuring systems by relay modules that provide for
connection of nearly all relay contacts to connecting points. This provides for a high
degree of flexibility of the modules. One configuration task is to design the wiring between the modules, the modules and the 7SS601 measuring systems, and to the primary equipment, in accordance with the desired function.
Mounting
The 7SS60 busbar protection system is made up of individual components which are
then mounted station-specifically in cubicles or mounting panels.
7SS60 Manual
E50417-G1176-C132-A2
1-5
Introduction
1.2
Application scope
The 7SS60 busbar protection is an easily settable numerical differential current protection for busbars.
It is suitable for all voltage levels and can be adapted to a large variety of busbar configurations. The components available are designed in particular for:
11/2 - circuit breaker systems
single busbars (with/without sectionalizing isolators)
double busbars with sectionalizing isolators, longitudinal couplers and transversal
couplers
These types of systems are shown in the following figures.
Single-phase measurement can be achieved by using external summation current
transformers. The use of matching transformers allows phase-selective measurement.
For extra security, an additional measuring system (check zone) can be implemented.
The busbar protection system is designed to be the successor of the 7SS1 static busbar protection. Where it replaces this system, the existing matching transformers and
summation current transformers can be used with the new system as well.
BB1
BB2
Figure 1-3
1-6
7SS60 Manual
E50417-G1176-C132-A2
Introduction
BB1A
Figure 1-4
BB1B
BB1A
BB1B
BB2A
BB2B
Figure 1-5
7SS60 Manual
E50417-G1176-C132-A2
1-7
Introduction
1.3
Features
The 7SS60 busbar protection has the following features:
Busbar protection operating on the differential current principle; one measuring system per busbar section or, depending on the configuration, per phase and zone; optionally one additional measuring system for the check zone (isolator-independent
measuring system)
Full galvanic and interference-immune isolation between the internal processing
circuits and the measuring, control and supply circuits of the system by screened
measuring transducers, binary input and output modules and dc voltage converters
Fully digital measured value processing and protection functions, from the sampling
and digitizing of the measured values to the TRIP decisions for the circuit breakers
High degree of security against overfunction, and detection of external faults even
with unfavourable transformer configuration
Differential current supervision of transformer circuits, with blocking option for TRIP
command
Blocking of TRIP command possible by fast binary input
Low demands on current transformers
Numerical system with powerful 16-bit microprocessor system
Easy menu-guided operation via integrated keypad and display panel or by connected PC using DIGSI
Storage of fault annunciations and of instantaneous values for fault recording
Continuous monitoring of the hardware and software of the 7SS601 measuring system, as well as of the primary current transformers and their supply conductors
Integrated commissioning aids
1-8
7SS60 Manual
E50417-G1176-C132-A2
This chapter describes the design and the connection system of the 7SS60. You will
find information on the available housing variants and on the types of connections
used.
This chapter also specifies recommended and reliable wiring data as well as suitable
accessories and tools.
7SS60 Manual
E50417-G1176-C132-A2
2.1
2-2
2.2
Peripheral modules
2-4
2-1
2.1
Housing
SIEMENS
31
Service/
Betrieb
Blocked/
Strung
1
2
30
28
4
26
24
22
20
18
16
14
E
Y/J
12
N
Reset
10
8
29
27
25
23
21
19
17
15
13
11
9
7
RS485
Busbar Protection
Sammelschinenschutz 2 ; 2,8 UH
IN = 1,9/100 mA
5 ,
fN = 50, 60 Hz
UH = 24, 48 V DC
!
Diagr.: C53000-B1174-C135-*
7SS6010-2EA00-0AA0/BB
F.-Nr.: BF 30.10.2000
III
Figure 2-1
Front view (left) and rear view (right) of the 7SS601 measuring system
2-2
7SS60 Manual
E50417-G1176-C132-A2
Connection system
Current connections (terminals 1 to 6)
Screw terminals (ring-type cable lug)
for bolts of 6 mm
13 mm
Type
2.7 to 6.6 mm
AWG 12 to 10
3.5 Nm
for bolts of 4 mm
9 mm
Type
1.0 to 2.6 mm
AWG 17 to 13
7SS60 Manual
E50417-G1176-C132-A2
1.8 Nm
2-3
2.2
Housing
Peripheral modules
The peripheral modules are accommodated in one or more 7XP204 housings. One
housing can hold up to 4 peripheral modules in any order.
Two angle brackets are required to fit the housing into a frame or cabinet.You can look
up the order number in chapter A.1 in the appendix.
The housing has a labelling strip inserted on its front for identification of the modules
contained in it.
The rear plate has cutouts for the connectors. The cutouts provided are sufficient for
the maximum degree of expansion. If the housing contains less modules, the cutouts
that are not required are closed by metal blanking plates.
An earthing area marked with an earth symbol has been provided at the housing rear.
At this area an earthing strip must be connected with two earthing screws in order to
ensure solid low-impedance earthing.
In addition, the housing bears a rating sticker with basic information.
SIEMENS
Pos. Module
SIPROTEC
7SS60
20
40 20
40 20
X1
X1
X1
A
40
20
40
X1
D
1
21
21
21
40
20
40
20
40 20
40 20
X2
X2
X2
Figure 2-2
21
21
21
X2
21
21
Front view (left) and rear view (right) of the 7XP204 housing for peripheral modules
The connector allocation depends on the type of peripheral module and is shown in
section A.2.
2-4
7SS60 Manual
E50417-G1176-C132-A2
Connection system
Each peripheral module is delivered with 8 plug-on connectors with screw terminals
and strain relief.
Connectors with screw terminals
Type
COMBICON system
of Messrs. PHOENIX CONTACT
MSTB 2,5/10-STZ-5,08
Stripping length
7 mm
0.5 to 0.6 Nm
Identification
of peripheral
modules
The peripheral modules are identified by a labelling strip on the housing front on which
the currently fitted modules are stated. This information should contain the designation
of the peripheral modules in accordance with their mounting position, and their voltage
ranges. Each peripheral module has a sticker with basic information that is placed on
the top of the housing after mounting into the peripheral housing.
To ensure the correct allocation of the plug-on connectors to the pins of the different
peripheral modules, the plug-on connectors must be marked with the self-adhesive labels provided. The marking system for this is shown in Figure 2-2.
Example:
The self-adhesive label with the pin names "11, 12, ..., 20" and the labels with the letters "A B C D X1 X2" is to be stuck onto the top plug-on connector at the left-hand side
of the mounting slot A. Make a cross in the field that corresponds to the pin connector.
In the following example, see Figure 2-3, fields "A" and "X1" have a cross.
If several peripheral devices are used, the housings must be identified in accordance
with the configuration documentation of the system.
7SS60 Manual
E50417-G1176-C132-A2
2-5
Mounting slots
peripheral modules
Self-adhesive Labels
Figure 2-3
Mounting slots
peripheral modules
Slot A
Slot C
Slot B
Figure 2-4
Slot D
Mounting slots for the peripheral modules in the 7XP204 housing (front view)
2-6
7SS60 Manual
E50417-G1176-C132-A2
Getting Started
This chapter describes the first steps that you should take after receiving your
SIPROTEC 7SS60 devices and modules. After unpacking, please check whether the
version and rated data match your requirements.
For an electrical check, you can navigate in the user interface without any measured
values. You can also connect the measuring system 7SS601 to a PC and operate it
from the computer using the DIGSI communication software.
In the last section you will find hints on what to observe for a long-term storage of the
system.
7SS60 Manual
E50417-G1176-C132-A2
3.1
3-2
3.2
3-3
3.3
User interface
3-5
3.4
Storage
3-8
3-1
Getting Started
3.1
3-2
7SS60 Manual
E50417-G1176-C132-A2
Getting Started
3.2
3.2.1
Ordering code
First of all, check the complete ordering code (MLFB) of the units and modules to ensure that the versions delivered comply with the required rated data and functions, and
that the necessary and desired accessories are complete. The complete ordering
code of the devices and modules can be found on their rating stickers.
The 7SS601 measuring system has its rating sticker on the front of the housing.
The peripheral modules come with a rating sticker that is placed the housing in which
the peripheral module is installed during assembly of the system.
The ordering code and the meaning of its digits are shown in Table A-1. The most important point is the matching of the rated device data to the station ratings. This information is found on the rating sticker. The measuring system is delivered with the binary inputs set in such a way that a dc voltage of the same level as the auxiliary supply
voltage is required for their activation. The jumper settings are listed in Appendix A.4.
The delivery status of the peripheral modules is shown in Appendix A.5.
3.2.2
Electrical check
The operating conditions must accord with VDE 0100 and VDE 0105 Part 1.
The unit should be in the final operating area for a minimum of two hours before the
power source is first applied. This time allows the device to attain temperature equilibrium, and prevents dampness and condensation.
Warning!
Some of the following checks are carried out in presence of hazardous voltages. They
must only be performed by qualified personnel which is thoroughly familiar with all
safety regulations and precautionary measures and pays due attention to them.
For a first electrical check of the system, it is sufficient to ensure a reliable earthing
and to connect the auxiliary supply voltage:
7SS60
overall system
q Connect an auxiliary supply voltage of the correct level and polarity to the inputs of
the unit via a switch or m.c.b. Please observe the connection diagrams in Appendix
A.2 and A.3.
q Close the protective switch or m.c.b. to apply the auxiliary supply voltage.
7SS60 Manual
E50417-G1176-C132-A2
3-3
Getting Started
7SS601
measuring system
q Connect the earth of the device to the protective earth of the location. Units for cubicle or panel flush mounting have the earthing screws on their back.
q The green Service/Betrieb LED on the front plate must light after at most 0.5 s, and
the red Blocked/Strung LED must go off after at most 10 s.
q After at most 15 s the start-up messages indicating the ordering code and the firmware version must disappear from the display. Instead, the measured values of the
differential current Id and the restraint current IR should appear. Depending on the
preset marshalling, some of the LEDs may light already.
3-4
7SS60 Manual
E50417-G1176-C132-A2
Getting Started
3.3
User interface
3.3.1
Membrane keypad/
display panel
Service/
Betrieb
Blocked/
Strung
1
2
3
4
+
E
Y/J
Reset
RS485
Busbar Protection
Sammelschinenschutz 2 ; 2,8 UH
IN = 1,9/100 mA
5 ,
fN = 50, 60 Hz
UH = 24, 48 V DC
!
Diagr.: C53000-B1174-C135-*
III
7SS6010-2EA00-0AA0/BB
F.-Nr.: BF 30.10.2000
Figure 3-1
Front view of the 7SS601 measuring system with keypad and display panel
7SS60 Manual
E50417-G1176-C132-A2
3-5
Getting Started
YES/NO keys:
Y/J
N
By depressing the N key, spontaneous fault alarms are reset and the quiescent-state
indications reactivated. The marshallable LEDs on the front light up during the reset,
so that the proper functioning of the LEDs can be checked as well.
3.3.2
Operation from a PC
You can make settings, start test procedures and read out data from a PC with the
DIGSI communication software in the same way as with the integrated keypad, with
the additional comfort of a monitor display and operator guidance through the menu.
All data can be stored on data carrier and read in from there (e.g. during configuration).
If a printer is connected, the data can be printed out for documentation.
When operating the firmware from a PC, please observe the relevant operating manuals. The DIGSI communication software is suited for processing protection data.
3-6
7SS60 Manual
E50417-G1176-C132-A2
Getting Started
3.3.3
Operating prerequisites
For most operational functions, the input of a password is necessary. This applies to
all entries via operator keypad or user interface which concern the functions of the
7SS601 measuring system, such as:
setting of operational parameters (thresholds, functions),
marshalling of command relays, alarms, binary inputs, LED indications,
system design parameters for operating language, interface and device configuration,
starting of test procedures.
The password is not required for readout of annunciations, operational data, fault data
and setting values.
The preparatory instructions in subsection 4.2.1 describe in detail how to enter the
password and to adapt the PC interface.
7SS60 Manual
E50417-G1176-C132-A2
3-7
Getting Started
3.4
Storage
If units or modules are to be stored, the following storage conditions should be observed:
SIPROTEC devices and modules should be stored in dry and clean rooms. For storage of devices, peripheral modules or related spare modules the applicable temperature range is between 25 C and +55 C (refer also to section 9.1 under Technical
Data).
It is recommended to limit the temperature range for storage to values between +10 C
and +35 C in order to avoid early ageing of the electrolytic capacitors in the power
supplies.
The relative humidity must not cause condensation or ice.
Furthermore it is recommended to connect the devices and modules to auxiliary voltage for about 1 or 2 days every two years, so that the electrolytic capacitors in the
power supplies are formatted. The same procedure should be followed before installing these devices. In case of extreme climatic conditions (tropical), this pre-heats the
device and avoids condensation.
The units and modules should be in the final operating area for a minimum of two
hours before the power source is first applied. This time allows the device to attain
temperature equilibrium, and prevents dampness and condensation.
3-8
7SS60 Manual
E50417-G1176-C132-A2
Configuration
The configuration of the SIPROTEC 7SS60 device comprises two parts.
The first part includes the selection and interconnection of the necessary components
according to the station configuration. The system configuration is dealt within a separate document. This chapter tells you, from the example of a single-busbar station
with sectionalizing isolator, which components you need to perform what tasks.
In the second part you will learn how to proceed for the configuration of the 7SS601
measuring system, in particular how to:
enter the password
change the operating language
detect/output annunciations and commands at the inputs/outputs
set the serial link
set the date and time
7SS60 Manual
E50417-G1176-C132-A2
4.1
4-2
4.2
4-4
4-1
Configuration
4.1
Figure 4-1
4-2
7SS60 Manual
E50417-G1176-C132-A2
Configuration
Note:
For the configuration of the entire system an extra manual is available.
The ordering code of the configuration manual can be found in Table A.1.
7SS60 Manual
E50417-G1176-C132-A2
4-3
Configuration
4.2
4.2.1
Entering a password
For most operational functions, the input of a password is necessary. The password
is a predefined key sequence which must be entered before any inputs can be made.
This applies for all entries via operator keypad or user interface which concern the
functions of the 7SS601 measuring system, such as:
system design parameters for operating language, interface and device configuration,
marshalling of command relays, alarms, binary inputs, LED indications,
setting of operational parameters (thresholds, functions),
starting of test procedures.
In order to indicate authorized operation and to prevent unintended alterations, the
password must be entered before any alteration can be performed.
When a menu item is selected which requires password input, press one of the keys
+ or to inform the system of the intended alteration. The display then shows the
prompt &: which indicates that the password is required. The password itself consists of the key sequence + .
The entered characters do not appear in the display; instead only a symbol # appears. After confirmation of the correct input with E the display responds with
&: 2.B. Press the key E again.
If the password is not correct, the display shows &: :521*. Pressing the keys + or
allows another attempt at password entry.
By pressing the enter key E one more time the menu item is displayed again, this time
with an underscore to indicate that alterations can now be made. Use the keys + or
in order to change the presented text or numerical values. A flashing cursor indicates
that the system operates now in alteration mode, starting with the first alteration and
ending after confirmation of the altered item with the enter key E. The alteration mode
is equally ended when the setting menu is left or after an internal waiting time.
Subsection 3.3.1 describes how to navigate in the operation tree.
4-4
7SS60 Manual
E50417-G1176-C132-A2
Configuration
4.2.2
4.2.2.1
Function description
The operating language can be changed in the parameter /$1*8$ (). The
available operating languages are currently English and German.
Block 71
When the system is delivered from the factory, the display shows function names and
outputs in the English language.
4.2.2.2
Hints on setting
The block 3$5$0( is reached from the initial display of the operative system by
pressing the
key once. Press
to change to the second level, which starts with
the address block 32:(5 6<67'$7 In this level, press the
key several times
until block 17 23 appears.
Pressing the
key brings you within the block to the parameter /$1*8$, where
the operating language can be changed.
The available languages can be called up by repeatedly pressing the + or key. Each
language is spelled in the corresponding national language. The required language is
selected with the enter key E.
4.2.2.3
DIGSI
addr.
7101
Overview of parameters
Parameter
71LANGUA
Possible settings
ENGLISH
DEUTSCH
Default setting
ENGLISH
Explanation
4.2.3
4.2.3.1
Introduction
Block 60
When the device is delivered from the factory, the LED indicators on the front cover,
the binary inputs and the output relays have already information assigned to them.
The assignment of most items of information can, however, be rearranged to adapt
them to the on-site conditions.
The marshalling procedure assigns certain items of information which the system generates or requires to certain physical interfaces (e.g. input and output units), or to logical interfaces.
The user decides which information will be linked with which interface of the system.
In addition, certain properties can be allocated to information and to interfaces.
7SS60 Manual
E50417-G1176-C132-A2
4-5
Configuration
Note:
Annunciation of previous events can be lost during marshalling. Therefore, the operational and the fault annunciation buffer should be read out before alterations are
made later on.
Before you begin with the marshalling procedure, you should have a concept that
matches the required input and output information to the number of physically available inputs and outputs of the device.
Marshalling of the inputs, outputs and LEDs is performed by means of the integrated
user interface or via the serial link. The operation of the user interface is described in
detail in section 3.3.1. Marshalling begins at the address block .
The input of the password is required for marshalling (refer to section 4.2.1). Without
password entry, parameters can be read out but not changed. A flashing cursor indicates that the system operates now in alteration mode, starting with the first alteration
after entering the password and ending with the end of the marshalling procedure.
Example for
binary outputs
A fault is registered by the differential current supervision function. This event is generated in the device as a logical annunciation signal and should be available at certain
terminals of the unit as a NO contact. Since specific unit terminals are hard-wired to a
specific (physical) signal relay, e.g. to the signal relay 2, the processor must be advised that the logical signal ,GV IOW should be transmitted to the signal relay 2.
Thus, when marshalling is performed two statements of the operator are important:
which (logical) annunciation should trigger which (physical) signal relay? Up to 20
logical annunciations can trigger one (physical) signal relay.
Example for
binary inputs
A similar situation applies to binary inputs. In this case external information (e.g.
!%3 EOR) is connected to the unit via a (physical) input module and should initiate
a (logical) function, namely blocking. The corresponding question to the operator is
then: which signal from a (physical) input relay should initiate which reaction in the
device?
Logical annunciation functions can be used in multiple manner. For instance, one annunciation function can trigger several signal relays, several command relays, additionally be indicated by LEDs, and be controlled by a binary input unit.
The marshalling procedure is set up such that for each (physical) input or output unit
(binary input, signal relay, LED or command relay) the operator will be asked which
(logical functions should be allocated.
The offered logical functions are tabulated in the following sections.
With the device operative, the marshalling blocks are reached from the initial display
as follows:
q press key
q press key
4-6
7SS60 Manual
E50417-G1176-C132-A2
Configuration
the next input, output or LED position. In the display the physical input/output unit
forms the heading.
Key
leads to the 5th level, in which the logical functions are actually selected for
assignment. The display shows, in the upper line, the physical input/output unit, this
time with a one to two digit index number. The second display line shows the logical
function which is presently allocated.
Table 4-1
Extract from the operation structure and illustration of selection of the marshalling blocks
1st level
2nd level
3rd level
4th level
5th level
0$56+
%,1,13
0$56+
%,
%,
66
9
3$5$0(
32:(5
6<67'$7
0$56+
:
continue for
marshalling of
signal relays,
LEDs and command relays
%,
0$56+
%,
%,
%,
0$56+
%,
%,
%,
On this 5th level all marshallable input and output functions can be paged through after
password input by repeated used of the key +. Backscrolling is possible with the key .
When the required function appears, press the enter key E. After this, further functions
can be assigned to the same physical input or output module (with further index numbers) by using key
. Each selection must be confirmed by pressing the E key. If a
selection place is to be assigned to no function, selection is made with the function
QRW DOO (not allocated).
You can leave the selection level by pressing the key . The display shows again the
previous selection level. Now you can scroll with key
to the next (physical) input/
output module or with
to the previous one to repeat the selection procedure, as
above.
7SS60 Manual
E50417-G1176-C132-A2
4-7
Configuration
In the following paragraphs, allocation possibilities for binary inputs, binary outputs
and LED indicators are given. The function numbers and designations are listed completely in the Appendix A.7.
If one tries to leave an item or operation level by pressing one of the arrow keys without having confirmed the allocation with the enter key E, the display will show the
question 6$9( 1(: 6(77,1* ". Confirm with the YES key Y/J that the new settings shall become valid now. The next text is displayed now. If you press the NO key
N instead, all alterations which have been changed since the E key was last pressed
are lost, and the old text is displayed. Thus, erroneous alterations can be made ineffective. Press the arrow key again in order to change really the operating item or level.
When the marshalling procedure is terminated by pressing the enter key E, the allocations are permanently secured in EEPROMs and protected against power outage.
4.2.3.2
Block 61
4-8
7SS60 Manual
E50417-G1176-C132-A2
Configuration
The assignment of the binary inputs as delivered from the factory is shown in the block
diagram in Appendix A.2. Table 4-3 shows all binary inputs as preset from the factory. .
Table 4-2
FNo.
1
5
7701
7900
7901
Table 4-3
4.2.3.3
Logical functions
not all.
>LED r.
>LO Res
>BP blo
>BP bPu
not allocated
>Reset LED indicators
>Lock Out Reset
>Block busbar protection
>Busbar protection blocking pulse
4th level
5th level
MARSHALLING
MARSH. BIN.INP
FNo.
Remark
Block heading
61 MARSH BI 1
61BI1 1
>LED r.
61 MARSH BI 2
6 1B I 2 1
>BP bPu
7901
61 MARSH BI 3
61BI3 1
not all.
not allocated
Block 62
The unit contains signal outputs relays. Signal relay 1 has Dev.OK (device operative)
permanently allocated. This signal is output when no disturbance has been detected
by the self-monitoring function of the unit.
The signal relays SR 2 and SR 3 can be marshalled in address block . The block is
reached from the initial display in level 1 as follows: press the key
(forwards), move
to the 2nd operation level by key
(next level); press the key
repeatedly until
block appears in the display. Key
leads to operation level 3 with address block
0$56+ 6,*5(/. The selection procedure is carried out as described in
subsection4.2.3.1.
Multiple allocating is possible, i.e a logical signal can be marshalled to more than one
signal relay (refer to subsection 4.2.3.1).
Table 4-4 shows a complete list of all signal functions with their associated function
number (FNo.).
The assignment of the signal relays as delivered from the factory is shown in Appendix
A.3. Table 4-5 shows all signal relays as preset from the factory.
Following password input, all marshallable functions can be scrolled through on the
display by repeated use of the key +. Backscrolling in the offered suggestions is possible with the key . When the required function appears, press the enter key E. After
this, further functions can be allocated to signal relay 1 (with further index numbers 1
to 20) by using the key
. Each selection must be confirmed by pressing the key E.
7SS60 Manual
E50417-G1176-C132-A2
4-9
Configuration
If a selection place is to be assigned to physical unit, selection is made with the function QRW DOO (not allocated).
Leave the selection level for signal relay 1 with key
signal relay with the arrow key
.
Table 4-4
FNo.
1
5
7701
7721
7900
7901
7910
7911
7914
7920
7921
Table 4-5
4-10
Logical functions
not all.
>LED r.
>LO Res
Lockout
>BP blo
>BP bPu
BP blk.
BP act.
BP Trip
IdS act
IdS flt
Not allocated
>Reset LED indicators
>Lock Out reset
Lock Out state
>Block busbar protection
>Busbar protection blocking pulse
Busbar protection blocked
Busbar protection active
Busbar protection: Trip
IDIFF supervision active
IDIFF supervision: fault detected
4th level
5th level
MARSHALLING
Signal relays
FNo.
Remark
Block heading
62 MARSH SIG.RE 2
62SIG2 1
BP Trip
7914
62 MARSH SIG.RE 3
62SIG3 1
BP blk.
7910
7SS60 Manual
E50417-G1176-C132-A2
Configuration
4.2.3.4
Block 63
The unit contains 6 LEDs for optical indications, 4 of which can be marshalled. They
are designated LED 1 to LED 4 and can be marshalled in address block . The block
is reached from the initial display in level 1 as follows: press the key
(forwards),
move to the 2nd operation level by key
(next level); press the key
repeatedly
until block appears in the display. Key
leads to operation level 3 with address
block 0$56+ /(' ,1'
The selection procedure is carried out as described in Subsection 4.2.3.1.
Multiple allocation is possible, i.e a logical signal can be marshalled to more than one
LED (refer to Subsection 4.2.3.1).
Apart from the logical functions, each LED can be marshalled to operate either in the
memorized mode or non-memorized mode. Each annunciation function is displayed
with the index 0 (0 = memorized).
The marshallable annunciation functions are the same as those listed in Table 4-4.
Table 4-6 shows all LED indicators as they are preset from the factory.
The selected function must be confirmed by the enter key E.
Following password input, all marshallable output functions can be scrolled through on
the display by repeated use of the key +. Backscrolling in the offered suggestions is
possible with the key . When the required function appears, press the enter key E.
After this, further functions can be allocated to LED 1 (with further index numbers 1 to
20) by using the key
. Each selection must be confirmed by pressing the key E. If a
selection place is to be assigned to physical unit, selection is made with the function
QRW DOO (not allocated).
Leave the selection level for LED 1 with key
arrow key .
Table 4-6
7SS60 Manual
E50417-G1176-C132-A2
4th level
5th level
MARSHALLING
LEDs
FNo.
Remark
Block heading
63 MARSH LED 1
63LED1 1
BP Trip
7914
63 MARSH LED 2
63LED2 1
Ids flt
7921
IDIFF supervision:
Fault detected
63 MARSH LED 3
63LED3 1
BP blk
7910
63 MARSH LED 4
63LED4 1
not all.
not allocated
4-11
Configuration
4.2.3.5
Block 64
4th level
5th level
MARSHALLING
Command relays
64 MARSH CMD.RE 2
4-12
64CMD2 1
Ids flt
FNo.
Remark
Block heading
7921
IDIFF supervision:
fault detected
7SS60 Manual
E50417-G1176-C132-A2
Configuration
4.2.4
Serial interface
4.2.4.1
Function description
Block 72
The 7SS601 measuring system is equipped with a serial RS485 interface. To adapt it
to a PC interface, an RS485/RS232 converter is required. Communication via this
interface requires some data arrangements such as identification of the device, transmission format and transmission rate.
These data are entered to the device in address block . password input is necessary (refer to section 4.2.1). The data must be matched to the connected devices.
4.2.4.2
Hints on setting
Device address
The identification number of the device within the substation can be set in parameter
'(9,&( (). The number can be chosen at liberty, but must be used only once
within the plant system. Setting values between 1 and 254 are possible.
If several modules are series-connected, each 7SS601 device must be assigned a
different address in the protection and the PC before operation with the DIGSI PC is
started.
Feeder address
The feeder address is understood to be the unique number of the feeder within the
substation. It is set in parameter )(('(5 (). Setting values between 1 and 254
are possible.
Substation address
In case more than one substation is addressed, an identification number for each substation can be assigned in parameter 68%67$ (). Setting values between 1
and 254 are possible.
Data format
In the parameter 3&6( () the data format of the serial interface can be
matched to the application. The recommended data format for the Siemens protection
data processing program is ',*6, 9. The other setting option is $6&,,, e.g. for terminal programs.
Transmission gaps
The setting of the GAPS in the parameter *$36 () is relevant only when the
device is intended to communicate via a modem. The setting is the maximum time period which is tolerated by the device when gaps occur during transmission of a telegram. Gaps may occur, when modems are used, by compression of data, error correction, and differences of the baud rate. Setting values between 0.0 s and 5.0 s are
possible. With good transmission quality between the modems, 1.0 s is recommended. The value should be increased when transmission quality is not so good. It must
be noted that GAPS must be smaller than the setting of reaction time protection relay
in the protection software DIGSI V3. Recommended value:
Reaction time protection relay
GAPS ------------------------------------------------------------------------------2
Higher values for reaction time protection relay reduce the transmission speed in
case of transmission errors. If the interface is connected directly to a personal computer, GAPS may be set to 0.0 s.
7SS60 Manual
E50417-G1176-C132-A2
4-13
Configuration
Baud rate
In the parameter %$8' () the baud rate for serial transmission can be
changed. The baud rate can be selected by repeatedly pressing the key + or .
Character format
The format for the characters transmitted in a telegram can be set in parameter
3$5,7< () to match the following transmission media:
',*6, 9 with even parity and 1 stop bit
Transmission with odd parity and 1 stop bit (2)
Transmission with no parity and 2 stop bits (1)
Transmission with no parity and 1 stop bit (1)
4.2.4.3
Addr.
Overview of parameters
Parameter
Possible settings
Default setting
Explanation
7201
72DEVICE
minimum setting:.........1
maximum setting:....254
7202
72FEEDER
minimum setting:.........1
maximum setting:....254
7203
72SUBSTA
minimum setting:.........1
maximum setting:....254
7211
72 PC-INT
DIGSI V3
ASCII
DIGSI V3
7214
72 GAPS
minimum setting:.....0.0 s
maximum setting:....5.0 s
1.0 s
7215
72PCBAUD
1200 Baud
2400 Baud
4800 Baud
9600 Baud
19200 Baud
9600 Baud
7216
72 PARITY
DIGSI V3
8O1
8N2
8N1
DIGSI V3
4-14
7SS60 Manual
E50417-G1176-C132-A2
Configuration
4.2.5
4.2.5.1
Function description
The date and time should not be set until the device is finally installed and connected
to the supply voltage, because an outage of the auxiliary voltage resets the clock.
The address block for this setting is reached from the initial display. Press the key
three times until the block $'',7,21 )81&7,21 is displayed. Key
is pressed to
change to the next operation level with the block 7,0( 6(77,1*. Change to the next
operation level with key . The date and time are displayed now. Scroll on with key
to find the setting blocks for date and time.
After the relay has been switched on, first the date 01.01.95 appears and the time
since the start-up of the processor system (connection of the supply voltage).
No password is required to change the date and time. Day, month and year can be
altered using the keys + and . Press the key
to move between the day, month
and year. Each time a value is changed, the enter key E must be pressed before the
next number can be changed. Proceed in analog manner to change the time.
Note:
When the day is changed, the display firstly allows 31 days. Only when the month and
year is changed can the relay check the plausibility of the complete date (leap year or
not). After confirmation with the enter key E, the day may be reduced to an existing
number.
4.2.5.2
Hints on setting
Date
In the parameter '$7( a new date can be entered in the order day, month, year.
Time
In the parameter 7,0( a new time can be entered. First the hour is entered, then the
minutes. The seconds are not changed. They are automatically set to zero when the
enter key is pressed.
7SS60 Manual
E50417-G1176-C132-A2
4-15
Configuration
4-16
7SS60 Manual
E50417-G1176-C132-A2
Functions
This chapter explains the various functions of the SIPROTEC 7SS60 and shows the
setting possibilities for each function. It also gives information and - where required formulae for determination of the setting values.
7SS60 Manual
E50417-G1176-C132-A2
5.1
Measurement method
5-2
5.2
5-7
5.3
5-14
5.4
Busbar protection
5-16
5.5
5-20
5.6
5-22
5-1
Functions
5.1
Measurement method
Basic principle
The measurement method by which the 7SS60 numerical busbar protection detects a
short-circuit in the protected zone relies on Kirchhoffs current law. This law states that
the vectorial sum of all currents flowing into a closed area must be zero.
Figure 5-1
Assuming that the currents J1, J2, J3 to Jn flow in the feeders connected to the busbar,
the following equation applies in the fault-free condition (the currents flowing towards
the busbar are defined as positive, and the currents flowing away from the busbar as
negative):
J1 + J2 + J3 ... + Jn = 0
If this equation is not fulfilled, there must be some other - impermissible - path through
which a current flows. This means that there is a fault in the busbar region.
This law is superior, as the basis for busbar protection, to any other known way of
measurement. Its simplicity is unequalled: a single quantity, the sum of currents,
characterizes, and can be used to detect, faulty conditions. This sum of all currents
can be formed at any time, even over a whole cycle, and if formed as such, using
instantaneous current values, full use of above law can be made.
The above considerations apply strictly to the primary-side conditions in a high-voltage
switching station. Protection systems, however, cannot carry out direct measurements
of currents in high-voltage systems. Protection equipment measurement systems,
performing the current comparisons, are connected through current transformers. The
secondary windings provide the currents scaled down according to the transformation
ratio while retaining the same phase relation. Furthermore, the current transformers,
due to the isolation of their secondary circuits from the high-voltage system and by
appropriate earthing measures, can keep dangerous high voltages away from the
protection system.
The characteristics of the current transformers are an important factor for the correct
operation of the protection. Their physical locations mark the limits of the protection
zone covered by the protection system.
Since the current transformers proportionally transform the primary currents flowing in
the system, a single-phase busbar protection that monitors the summated feeder
currents would have the basic circuit shown in Figure 5-2.
5-2
7SS60 Manual
E50417-G1176-C132-A2
Functions
Figure 5-2
For simplicitys sake, it is assumed that the current transformers of all feeders have
the same transformation ratio. Although such a busbar protection would certainly
detect any short-circuit inside the protection zone, the transformation errors of the
current transformers, which are unavoidable to some degree, are also liable to cause
spurious tripping as a result of an external short-circuit. In that case, for instance with
a close-up fault on one of the feeder bays, the current flowing into the short-circuit is
shared on the infeed side by several bays. The current transformers in the infeeding
bays carry only a fraction of the total fault current while the current transformer in the
faulted feeder bay carries the full current in its primary winding. If the fault current is
very high, this set of current transformers may therefore be saturated, so tending to
deliver only a fraction of the actual current on the secondary side while the rest of the
current transformers, due to the distribution of currents among several bays, perform
properly. Although the sum of the currents is zero on the primary side, the sum of the
currents in Figure 5-2 is now no longer zero.
In conventional differential protection systems where the sum of the currents is zero
on the primary side, for busbars and similar objects, this difficulty is countered by
employment of the so-called stabilization (restraining) devices.
If the short-circuit does not occur at the voltage peak of the cycle, a dc component is
initially superimposed on the short-circuit current which decays with a time constant
= L / R of the impedance from source to fault. With the growing output ratings of the
generator units, these time constants in the supply system tend to grow longer. A
superimposed dc component speeds up the magnetic saturation in the transformer
cores, thus considerably affecting the transformation task.
Several measures have been introduced into the 7SS601 measuring system of the
7SS60 busbar protection to cope with these problems. It was thus possible to give the
7SS60 busbar protection system a maximum degree of security against spurious
operation for external short-circuits while ensuring, in the event of internal shortcircuits, that a tripping signal is initiated within a very short time.
The measuring circuit of the 7SS60 busbar protection system is characterized by the
following features:
7SS60 Manual
E50417-G1176-C132-A2
Basic principle
Restraint
5-3
Functions
Basic circuit,
supervision
The simple circuit shown in Figure 5-2 is sufficient to derive the sum of all feeder
currents in one phase, provided that the current transformers of all feeders have the
same transformation ratio. In most cases, however, the current transformers of the
feeders in a power system will have different transformation ratios because the
incoming and outgoing lines carry different rated currents and the transformers are
matched to these currents. To provide the uniform transformation ratio required by the
busbar protection, matching CTs are installed upstream of the protection system input;
these transformers are designed to convert the input from the main current
transformers into an identical transformation ratio for all feeders. In the 7SS60 system
the matchting CTs are also responsible for matching to the nominal current of the
measuring inputs. The output current of the matching CTs is 100 mA with a primary
nominal current.
To the single-phase protection circuit shown in Figure 5-2, matching CTs would be
added, as shown in Figure 5-3.
Main CT
Matching CT
7SS60
Figure 5-3
5-4
7SS60 Manual
E50417-G1176-C132-A2
Functions
Restraint
The restraint (stabilization) has the function of reducing the influence on the
measurement of transformation inaccuracies (e.g. for transformer saturation) in the
various feeders to such a degree that spurious behaviour of the protection system is
prevented.
The vectorial sum Id of all feeder currents acts as tripping quantity.
Id = | I1 + I2 + ... + In |
The value sum of the all feeders is counterbalanced by the restraint quantity IR.
IR = | I1 | + | I2 | + ... + | In |
The restraint R is determined by setting the restraint factor.
R = k . IR
Measuring
System
"k-factor"
Figure 5-4
Differential current measuring circuit with restraint in the 7SS60 busbar protection
system
For an explanation of the circuit shown in Figure 5-4, let us consider first the conditions
at a given point in time. The n feeders of the busbars carry the currents J1, J2 ... Jn.
These are defined as positive as they flow towards the busbar. The secondary
currents I1, I2 ... In from the current transformers, which are proportional to the primary
currents if we assume (for the moment) an ideal transmission behaviour, flow
individually through the primary windings of the measuring transducers MS and
summated through the primary winding of the measuring transducer MD. On the
secondary side, each transducer MS of the restraint module feeds a measuring
rectifier GS. Regardless of the direction of the individual currents in the measuring
transducers, the current direction at the output of the measuring rectifiers is fixed and
the same at the considered and any other point in time.
The input Id thus detects the vectorial sum of the currents, and the input IR the
summated magnitudes of the currents.
Check zone
The safety of operation of the busbar protection system 7SS60 can be further increased by an additional so-called check zone.
This requires an additional measuring system which - regardless of the position of the
isolator - monitors the current sums of all busbar feeders. Possible tripping failures
originating from faulty information sent to the real state of the isolator are thus excluded.
When a busbar fault occurs, a TRIP-command decision is only given if both the measuring system belonging to the faulty busbar section and the check zone measuring
system gives the decision for tripping (2 out of 2 decision).
7SS60 Manual
E50417-G1176-C132-A2
5-5
Functions
An even higher degree of safety can be achieved by using separate transformer cores
for the check zone.
To avoid over-restraint, address N IDF in the check zone measuring system has to be a lower level (see Subsection 5.4.2).
5-6
7SS60 Manual
E50417-G1176-C132-A2
Functions
5.2
7SS60 Manual
E50417-G1176-C132-A2
5-7
Functions
The following sections deal with circuit examples for the version with summation
current transformers.
The input current transformer (summation current transformer) has several primary
windings and one secondary winding. The primary windings have different numbers
of turns, which allows to connect the three phase currents with a ratio of e.g. 2 : 1 : 3.
Depending on the station operating conditions and the requirements that the
protection must meet, there are two different circuits for connecting the summation
current transformer to the main transformers.
Differential Current
Restraint Current
Figure 5-5
Increased earth
current sensitivity
Figure 5-6 shows that the windings with the ratio of turns 2 ("ratio-2 winding") and 1
("ratio-1 winding") are each connected to one of the three phase currents, and the third
winding (the "ratio-3 winding") is connected to the neutral conductor.
This is the most frequently used circuit. It is used in power systems where system
faults involving earth currents are likely to induce relatively small fault currents. One
of their characteristics is that the fault detection thresholds for 2-phase short-circuits
have a ratio of 1 : 2. With any other winding ratio than 1 : 2 between the windings in
the phases, the fault detection thresholds would differ by more than the ratio 1 : 2. This
ratio is thus an optimum. In comparison with the fault-free, symmetrical 3-phase
current, the ratio is 2 / 3 = 1.15.
A second characteristic of this connection circuit is its increased sensitivity to earth
faults, which is due to the connection of the "ratio-3 winding" to the earth current path.
The ratio of turns 2 : 1 : 3 (sequence of the currents L1, L3, N) yields, in the connection
circuit shown in Figure 5-6, the effective number of turns and fault detection thresholds
listed in the following table.
5-8
7SS60 Manual
E50417-G1176-C132-A2
Functions
Figure 5-6
Effective
number
of windings
in turn
Figure 5-7
Short-circuit
Affected phases
Effective number
of turns
3-phase
L1L2L3
0.20 to 2.50
2-phase
L1L2
L2L3
L3L1
2
1
1
0.18 to 2.17
0.35 to 4.33
0.35 to 4.33
1-phase
L1E
L2E
L3E
5
3
4
0.07 to 0.87
0.12 to 0.72
0.09 to 1.08
The values stated for 1-phase earth faults apply in the first place for power systems
that have starpoints with solid or low-resistant earthing. They apply also to double
earth faults in isolated-neutral systems and systems with earth fault neutralizing if the
considered busbar is fed from one side only and the second fault is located outside
the protected zone, between the power source and the busbar equipped with a
differential protection.
If the starpoints of the transformers that are fed by the protected busbar have a solid
or low-resistant earthing but all supply transformers have an isolated starpoint, an
earth fault in phase L2 within the protected zone, with the connection circuit shown in
Figure 5-6, would lead to a lower fault characteristic than shown.
7SS60 Manual
E50417-G1176-C132-A2
5-9
Functions
For a better understanding of this, Figure 5-8 shows the distribution of the currents
between the three phase conductors and the earth conductor on the line from the
supply transformer to the earth-faulted busbar and on the line between the busbar and
an earthed transformer. The currents are shown as arrows.
Figure 5-9 shows the electric loading of the summation current transformer.
Depending on the phase that is involved in the earth fault, the electric loading will vary
on the supply side. On the busbar side towards the earthed transformer, the current
distribution is independent of the affected phase.
Figure 5-8
Figure 5-9
Current distribution during a 1-pole earth fault in a power system with earthing
only on the consumer side
Summation transformer currents in a 1-pole earth fault in a power system with earthing only on the consumer
side; connection as per 5-8
Trip value
Restraint value
Id
Is
Id / I s
L1
3 + 12
3 + 12
15/15 = 1.0
L2
3 + 12
3 + 12
9/15 = 0.6
L3
0 + 12
0 + 12
12/12 = 1.0
If an earth fault occurs in phase L2 within the protected zone, the fault characteristic
has thus only a slope of 0.6 instead of 1. With such unfavourable conditions, a lower
restraint factor should be selected to ensure reliable tripping of the protection in case
of internal faults.
5-10
7SS60 Manual
E50417-G1176-C132-A2
Functions
Normal earth
current sensitivity
In a connection circuit as shown in Figure 5-10, the sensitivity to the earth current is
less pronounced than in the circuit shown in Figure 5-6. It should be considered for
power systems with low-resistant or solid earthing of the starpoints where due to the
transformer design sufficiently high short-circuit currents can be expected in case of
1-phase earth faults.
more
devices
Figure 5-10
The effective number of turns in the winding and fault detection ranges are listed in the
following table.
Short-circuit
Affected phases
Effective number
of turns
Fault detection
range
Multiple of IN
3-phase
L1L2L3
0.20 to 2.50
2-phase
L1L2
L2L3
L3L1
1
2
1
0.35 to 4.33
0.18 to 2.17
0.35 to 4.33
1-phase
L1E
L2E
L3E
2
1
3
0.18 to 2.17
0.35 to 4.33
0.12 to 0.72
Figure 5-11 Summation transformer currents in a 1-pole earth fault in a power system with earthing only on the consumer
side; connection as per 5-10
7SS60 Manual
E50417-G1176-C132-A2
5-11
Functions
This circuit yields the following conditions in the differential measuring circuit for power
systems with earthing only on the consumer side:
Trip value
Id
Restraint value
Is
Id / I s
L1
0+6
0+6
6/6 = 1.0
L2
3 + 6
3+6
3/9 = 0.33
L3
3+6
3+6
9/9 = 1.0
Phase
If an earth fault occurs in phase L2 within the protected zone, the fault characteristic
has thus only a slope of 0.33 instead of 1.
This circuit is thus not suitable for power systems with earthing only on the consumer
side.
Summation current
matching
transformers
5-12
Figure 5-12
Figure 5-13
7SS60 Manual
E50417-G1176-C132-A2
Functions
Matching
transformers
7SS60 Manual
E50417-G1176-C132-A2
Figure 5-14
Figure 5-15
5-13
Functions
5.3
5.3.1
Function description
The 7SS601 measuring system requires some basic data of the power system and the
switchgear so that it can match its functions to these data and to its application.
These data are found in block 32:(5 6<67'$7 and in the switchgear data.
Rated frequency
The parameter )5(4 () is used to set the rated system frequency.
Minimum TRIP
command duration
The parameter for the minimum TRIP command duration 7753 () ensures
that all connected circuit breakers are reliably tripped as required.
The minimum TRIP command duration can also prevent damage to the TRIP command contacts of the protection system, which could occur if these contacts were
opened before the auxiliary contacts of the circuit breaker(s) have interrupted the flow
of current through the trip coil. With the parameter 775,3 () the minimum
duration of the TRIP command can be extended long enough to ensure that the flow
of current through the trip coil of the circuit breaker is reliably interrupted.
Lockout function
The parameter /2XW () causes the TRIP command to be memorized until
it is manually reset. A TRIP command that is memorized by the lockout function is not
even reset by an auxiliary power outage; it drops off, however, for as long as the
auxiliary voltage failure persists, as it has no supply voltage.
>Figure 5-16
5-14
7SS60 Manual
E50417-G1176-C132-A2
Functions
5.3.2
Hints on setting
Rated system
frequency
The default setting is +]; it needs to be changed only for a system frequency of
+].
16.7 Hz are available in a version with separate order no.
Note:
The parameter )5(4 () can only be called up in versions for 50 Hz or 60 Hz.
In systems with a rated frequency of 16.7 Hz, the parameter )5(4 () is not
displayed at all.
Lockout function
5.3.3
DIGSI
addr.
If the Lockout function is set to 21, the lockout state can only be reset via a binary
input. If 21EXWW is set, the lockout can be reset with the N key or with a binary input.
Overview of parameters
Parameter
Possible settings
Default setting
Explanation
1101
01 FREQ
50 Hz
60 Hz
50 Hz
1134
01 T-TRP
0.01 s to 32.00 s
0.15 s
1135
01 L.Out
OFF
ON
ON/key
OFF
Lockout function
5.3.4
FNo.
7721
Annunciations
Text on LC display
LockOut
7SS60 Manual
E50417-G1176-C132-A2
Logical functions
Lockout state
5-15
Functions
5.4
Busbar protection
5.4.1
Function description
The busbar protection function generates the TRIP command that is then multiplied
by means of peripheral modules to enable the output to all tripping circuit breakers. It
makes the r.m.s. values of the differential current Id and of the restraint current IR
available for display, stores events in the form of operational annunciations, fault
annunciations or spontaneous annunciations and outputs these via LED indicators or
signal relays. Measured values and annunciations are furthermore made available at
the RS485 interface for operation by PC using the DIGSI communication software.
The 7SS601 measuring system processes the externally formed sums of the
differential current Id and of the restraint current IR. By means of these two measured
values, the protection function recognizes the presence of a fault in its associated
protection zone. Figure 5-17 shows the trip characteristic of the protection. The
characteristic is divided into a horizontal portion and a portion with a steadily rising
slope. Only value pairs of a differential and a restraint current that are both above the
characteristic constitute busbar faults that lead to a TRIP command. The level of the
horizontal portion of the characteristic is determined by the parameter ,G! ().
The slope of the rising portion can be varied by the setting of the parameter . IDF
(). The parameter ,' WKU () constitutes the selectable threshold for the
differential current supervision.
The algorithm of the 7SS601 measuring system is optimized for the fastest possible
tripping in case of a busbar short-circuit. The stability of the protection against external
faults is ensured if the transformer saturation occurs not before 3 ms.
ifferential current Id
Tripping zone
Restraint
zone
k = 0.80
.
.
.
.
.
.
.
.
k = 0,25
Pick-up
characteristics
Id>
Normal load line
ID thr
0
Figure 5-17
5-16
Restraint current IR
7SS60 Manual
E50417-G1176-C132-A2
7SS60 Manual
E50417-G1176-C132-A2
Figure 5-18
10 BPStat
1501
1505
13 Id sup
1802
10 Id>
10 K fac
1506
7911
BP act.
Id sampl. values
TRIP command
Busbar protection
algorithm
IR sampl. values
Blocking of
TRIP command
Blocking
via binary input
1511
Diff-current
supervision
10 T Trip
1801
13Id sup
1135
Diff-current
supervision
release logic
Q
7701
>LO Res
LockOutLogic
1134
&
tp
>1
>1
7914
BP Trip
7910
BP blk.
5-17
Functions
>1
7900
>BP blo
7721
LockOut
Blocking pulse
7901
>BP bPu
L.Out
Functions
5.4.2
Hints on setting
Busbar protection
The parameter %3VWDW () is used to activate (21) or deactivate (2))) the
busbar protection function. It can also be set to block the command and signal relays
while the protection function is active (%/2753).
For fault detection and tripping the protection only uses the normalized currents Id and
IR which exceed the threshold set in ,G! (). The fault detection is reset when
the value drops below the threshold again.
The threshold ,G! () has an influence on the sensitivity of the protection for
small fault currents. Where low supply conditions or the type of the starpoint earthing
create only earth fault currents in the load range, ,G! () would have to be set
below the nominal value to respond to them. It must be borne in mind, though, that
with a high load the failure of one current transformer might then cause a trip of the
busbar. In this case additional criteria must ensure the stability (e.g. additional release
via the displacement voltage by means of a feeder protection device).
A time delay is implemented between the protection algorithm initiating the tripping
and the output of the actual TRIP command. This time step causes the delayed
initialization of the TRIP command (if a tripping time other than zero is specified). The
TRIP command is only executed if during the entire time step the tripping is issued by
the protection algorithm. The time step will be reset prematurely if the protection
algorithm assumes the tripping conditions to be no longer fulfilled. The delay time of
the TRIP command can be specified as the parameter 10 TrpDly (1511). Due to the
system configuration the timer accuracy is 10 ms.
Restraint factor
The restraint factor . IDF () allows to adapt the stability of the protection to
service conditions.
Although a high setting for this factor improves the stability with regard to faults outside
the protected zone, it reduces the sensitivity for the detection of busbar faults.
. IDF () should therefore be chosen as low as possible and as high as
necessary.
If the measuring system is to be used for zone-selective protection, which will be the
case in most applications, it is advisable to use the default setting of
. IDF ().
Where a measuring system is used for protection of the so-called check zone, a lower
value for . IDF is recommended to avoid that the load currents of the nonfaulted busbar sections cause an over-restraint. The recommended settings for .
IDF () can be summarized as follows:
Zone-selective protection
Condition
5-18
Setting of
10 K fac (1506)
0.6
7SS60 Manual
E50417-G1176-C132-A2
Functions
Setting of
10 K fac (1506)
none
5.4.3
DIGSI
addr.
0.3
Overview of parameters
Parameter
Possible settings
Default setting
Explanation
1501
10BUSBAR
PROTECT.
ON
OFF
BLO.TRP
ON
1505
10Id>
1.00 Ino1
1506
10K fac
0.25 to 0.80
0.60
1511
10 TrpDly
0.00 to 10.00
0.00
1 Ino: normalized rated current; Ino=100mA with a symmetrical rated current flowing on the primary side
5.4.4
FNo.
Annunciations
Text on LC display
Logical functions
7721
LockOut
7911
BP act.
7914
BP Trip
7915
BP Tdel
7922
BIPulS.
7SS60 Manual
E50417-G1176-C132-A2
5-19
Functions
5.5
5.5.1
Function description
The 7SS60 also allows to supervise the external transformer circuits. The supervision
picks up when the threshold ,G WKU () is exceeded. This response comes
with a delay after the protection function.
The differential current supervision function is available in block 13. It has the task of
detecting malfunctions during operation and blocking so that they do not jeopardize
the stability of the system against external faults. This supervision function recognizes
transformer failures, e.g. due to phase failures, and sends an alarm. The differential
current supervision is able to block the protection if set before.
Figure 5-19
5.5.2
Hints on setting
Differential current
supervision
The parameter ,G VXS () is used to activate and deactivate the differential
current supervision function. The following setting options are offered for the differential current supervision: blocking of the busbar protection till the release (EOUHO%3),
blocking till the acknowledgement (EODFN%3), or only output an alarm ($/50RQO\).
With 2)) the function can be deactivated.
Pick-up threshold
In each measuring cycle, i.e. every 0.5 ms, it is checked whether the peak of the differential current exceeds the threshold ,G 6XS taking into consideration
a hysteresis. In this case, the counter is increased by 1. Once the counter has reached
a value of 5000, the differential current supervision picks up. If no threshold was exceeded, the counter is reset to zero.
5-20
7SS60 Manual
E50417-G1176-C132-A2
Functions
5.5.3
DIGSI
addr.
Overview of parameters
Parameter
Possible settings
Default setting
Explanation
1801
13Id Sup
bl/relBP
bl/ackBP
ALRMonly
OFF
bl/relBP
1802
13Id thr
0.15 Ino1
1 Ino: normalized rated current; Ino=100 mA with a symmetrical rated current flowing on the primary side
5.5.4
FNo.
7921
Annunciations
Text on LC display
IdS Flt
7SS60 Manual
E50417-G1176-C132-A2
Logical functions
IDIFF supervision: fault detected
5-21
Functions
5.6
5.6.1
Function description
The 7SS601 protection system has a fault recording function that stores the
instantaneous values of the differential and the restraint current in a buffer. This
function is available in block .
The instantaneous values of the measured quantities are sampled every 0.5 ms (50,
60 and 16.7 Hz).
In the event of a fault, the data are stored during a settable period. The available buffer
has a recording capacity of 7.1 s.
Up to 8 fault events can be stored in this buffer. New fault events are always entered
in the fault record buffer. Older records are overwritten by the new data.
The data can be read out to a personal computer via the serial interface, and
processed using the DIGSI / SIGRA software. The measured values are prepared for
a graphical display. In addition, signals are represented as binary traces, e.g. "%XVEDU
SURWHFWLRQ 7ULS" and "/RFN 2XW VWDWH".
Part of the fault recording memory in the 7SS601 is buffered against voltage failures.
The buffered portion has a capacity of 5 s. It contains always the most recent fault
events.
A fault event starts with tripping by a protection function and ends with the reset of the
last tripping by a protection function. Fault records in the 7SS601 always cover this
span of time (plus the pre-fault and the post-fault time).
5.6.2
Hints on setting
The actual storage time starts with the pre-fault time 735( () that precedes
the reference point and ends when the post-fault time 7326 () following the
disappearance of the storage criterion has elapsed. The maximum permissible total
storage time per fault record is set in 70$; (). A total of 7.1 s is available
for fault recording.
Times
5.6.3
DIGSI
addr.
Overview of parameters
Parameter
Possible settings
Default setting
Explanation
7410
74-T MAX
0.20 s to 5.00 s
1.50 s
7411
74 T-PRE
0.05 s to 1.50 s
0.30 s
7412
74 T-POS
0.05 s to 1.50 s
0.20 s
5-22
7SS60 Manual
E50417-G1176-C132-A2
Control in Operation
This chapter deals with the control of the SIPROTEC 7SS60 system while it is in operation. It describes how to obtain information from the system, to set the date and
time and to check the status of the binary inputs.
Detailed knowledge of the functioning of the system is not required. A prerequisite for
control is, however, that the system settings have been made as described in Chapter
4, and especially that the input and output functions have been marshalled.
7SS60 Manual
E50417-G1176-C132-A2
6.1
Read-out of information
6-2
6.2
6-5
6.3
6-6
6-1
Control in Operation
6.1
Read-out of information
General
The device provides the following information for local readout or for transmission to
DIGSI:
Operational annunciations
Fault annunciations
Measured values
The following section describes in detail how this information is called up, and explains
the individual items of information.
6.1.1
LEDs
Output relays
6-2
Annunciations that have been marshalled to output relays (refer to chapter 4) are
transmitted by means of a signal voltage. They are then available for a station control
or telecontrol system.
7SS60 Manual
E50417-G1176-C132-A2
Control in Operation
The procedure for reading out the operational and fault annunciation buffer and the
measured values using the DIGSI communication software is described in the manual
for the communication software.
From the initial state, the block $1181& () is reached by pressing the
twice.
key
Operational annunciations are information that the device generates during operation
and that concerns the operation. They are available in block 81. Important events and
status changes are listed there in chronological order with the time of their occurrence.
Up to 30 operational events are stored. If more events are issued, the oldest are overwritten.
You can move from block 23(5 $1181& () to the operational events buffer
by pressing the
key.
The events are stored in lists. After selecting the desired block, you can scroll the visible part of the list on the display up and down using the
and
keys, as shown in
the following example.
7SS60 Manual
E50417-G1176-C132-A2
6-3
Control in Operation
Annunciation
buffer
PV
Display
)$8/7
PV
)7 GHW
PV
',) 7US
Faults in the primary switchgear are indicated only with Fault and a consecutive fault
number. Detailed information on the sequence of events during a fault is contained in
the block Fault annunciations.
Fault
annunciations
Block 82
Here the annunciations of the last eight faults can be read out. These are sorted from
the newest to the oldest in a subordinate level of block 82. When a ninth fault arrives,
the system deletes the data of the oldest one. Each of the eight fault buffer can store
up to 30 annunciations. If more events are issued, the oldest are overwritten.
As long as the date and time of the device have not been set, the date and time displayed are the relative date and time since the last startup of the processor system.
Next, the fault events are displayed in the chronological order of their detection, with
a relative time referred to the moment at which the fault started.
Pressing the
key brings you from block )$8/7 $1181& () to the fault
annunciations, where you can call up successively all fault annunciations using the
and
keys.
To move from the selected fault annunciation to the fault annunciation buffer, press
the
key.
Just like the operational annunciations, the fault annunciations are stored in lists. Use
the
and
keys to scroll though the lists.
Measured values
Block 84
Measured values for the differential and restraint current can be displayed in block 84.
Values are shown in percent of the nominal values. A prerequisite for correct display
is that the nominal data have been correctly set in block 00.
Pressing the
key brings you from block 0($6 9$/8(6 () to the measured values, which can now be called up successively using the
and
keys.
The values are updated during the read-out. When scrolling within the block with the
or
key, the updated values are displayed.
6-4
7SS60 Manual
E50417-G1176-C132-A2
Control in Operation
6.2
7SS60 Manual
E50417-G1176-C132-A2
. This is de-
6-5
Control in Operation
6.3
Testing the
binary inputs
Press
once again to move to the address for testing the status of the binary inputs
%,67$7 ().
After actuating the ENTER key E you are asked whether you want to interrogate the
status of the binary inputs. If you press the N key, the action is aborted, and you can
move to the next test item with
.
If you actuate Y/J, the status of the 3 binary inputs (BI) is shown as a matrix which has
the following meaning:
:
:
:
:
BI 1 is activated (energized)
BI 2 is activated (energized)
BI 3 is activated (energized)
The BI is not activated
%,67$7
Press
to move to the address for testing the status of the signal and command
relays 5(67$7 ().
After actuating the ENTER key E you are asked whether you want to interrogate the
status of the signal and command relays. If you press the N key, the action is aborted,
and you can move to the next test item with
.
If you actuate Y/J, the status of the 2 signal relays (S) and of the 2 command relays
(T) is shown as a matrix which has the following meaning:
: S 1 or T 1 has picked up
: S 2 or T 2 has picked up
: The relay has not picked up
RE-STAT
S1-- T-2
6-6
7SS60 Manual
E50417-G1176-C132-A2
Control in Operation
Press
().
to move to the address for testing the status of the LEDs /(' 67$786
After actuating the ENTER key E you are asked whether you want to interrogate the
status of the LEDs. If you press the N key, the action is aborted, and you can move to
the next test item with .
If you actuate Y/J, the status of the 4 LEDs is shown as a matrix which has the following meaning:
:
:
:
:
:
LED 1 is activated
LED 2 is activated
LED 3 is activated
LED 4 is activated
The LED is not activated
LED STATUS
-2-4
7SS60 Manual
E50417-G1176-C132-A2
6-7
Control in Operation
6-8
7SS60 Manual
E50417-G1176-C132-A2
This section is primarily for personnel who are experienced in installing, testing, and
commissioning protective and control systems, and are familiar with applicable safety
rules, safety regulations, and the operation of the power system. Some modifications
of the hardware to the station data may be necessary. For primary tests, the switchgear must be isolated to perform switching operations.
7SS60 Manual
E50417-G1176-C132-A1
7.1
7-2
7.2
Commissioning
7-5
7-1
7.1
Warning!
Trouble free and safe use of this SIPROTEC device depends on proper transport,
storage, installation, and application of the device according to the warnings in this instruction manual.
Of particular importance are the general installation and safety regulations for work in
a high-voltage environment (for example, ANSI, IEC, EN, DIN, or other national and
international regulations.) These regulations must be observed. Failure to observe
these precautions can result in death, personal injury, or severe damage of property.
Prerequisites
7.1.1
The rated data of the device have been checked as described in section 3.2.1, and
their conformity with the station data has been verified. Please note also the prerequisites stated in section 9.4.
Measuring system
Panel flush
mounting or
cubicle mounting
q Slip away the covering caps at the top and bottom of the front panel, making accessible 4 elongated holes.
q Insert the unit into the panel cutout or cubicle mounting frame and fix with four
screws (a dimension drawing is shown in Figure 9-1.
housings rear wall using at least one of the two M4 screws. Earth tapes according
to DIN 72333 Form A are suitable for this.
q Make electrical connections via the screw terminals of the housing. Special atten-
tion has to paid to the designations of the connection modules, the permissible conductor cross-sections and tightening torque (refer also to chapter 2). Use copper
conductors only!
Three different ranges of auxiliary voltage can be delivered (refer to chapter 9 and
A.4). If, for exceptional reasons, the rated voltage of the supply input is to be changed
to adapt it to the station conditions, it must be taken into account that the models for
rated auxiliary voltage 60/110/125 Vdc and 220/250 Vdc differ from each other by different plug jumpers. The assignment of the jumpers to the rated voltage levels, and
their location on the p.c.b., is shown in Figure A-5.
The model for 220/250 Vdc is suitable for 115 Vac, too. When the device is delivered,
all the jumpers are correctly located and matched to the specification given on the rating plate, so that normally none of them need to be altered.
When the device is delivered from the factory, the binary inputs are set to operate with
a dc control voltage in the whole operating range between 17 V and 288 V. If the station control voltage has a higher rating ( 110 Vdc), it may be useful to set a higher
pick-up threshold of the binary inputs to increase the static signal-to-noise ratio. This
helps to avoid spurious pick-up by interference voltages that may be caused e.g. by
earth fault monitoring systems operating in parallel to the device.
7-2
7SS60 Manual
E50417-G1176-C132-A1
To increase the pick-up threshold of a binary input to approx. 74 V, one jumper position per input must be changed. Figure A-5 shows the assignment of the jumpers to
the binary inputs, and their location on the p.c.b.
q Slip away the covering caps at the top and bottom of the front panel, making accessible one screw each in the top and bottom center. Unscrew these two screws.
Warning!
Electrostatic discharges via the component connections, the p.c.b. tracks or the connecting pin must be avoided under all circumstances by previously touching an
earthed metal surface.
q Pull out the module by taking it at the front cover and place it on a surface which is
suited to electrostatically endangered components (EEC).
Peripheral modules
Panel flush
mounting or
cubicle mounting
q Slip away the covering caps at the top and bottom of the housing front, making accessible 4 elongated holes.
q Insert the unit into the panel cutout or cubicle mounting frame and fix with four
screws (a dimension drawing is shown in Figure 9-2).
q Unscrew the screws next to the fixing screws to remove the front cover.
q A solid low-resistant and low-inductive operating earth has to be connected to the
housings rear wall using at least one of the two M4 screws. Earth tapes according
to DIN 72333 Form A are suitable for this.
The peripheral modules are selected in accordance with the station configuration, refer to section 4.1. It may be necessary to adapt the auxiliary voltage of the modules or
the required contact (NC/NO contact) to the particular station conditions.
Warning!
Electrostatic discharges via the component connections, the p.c.b. tracks or the connecting pin must be avoided under all circumstances by previously touching an
earthed metal surface.
7SS60 Manual
E50417-G1176-C132-A1
7-3
Auxiliary voltage
Both the 7TM70 restraint/command output module and the 7TS720 command output
module have three input voltage ranges for the auxiliary voltage: 48/60 Vdc, 110/
125 Vdc and 220/250 Vdc (refer to Chapter 9 and Appendix A.5). The voltage range
can be selected by changing the jumper settings on the module. The assignment of
the jumpers to the rated voltage levels, and their location on the p.c.b., is shown in figures A-6 and A-8. Before mounting the peripheral module, check whether the selected
auxiliary voltage matches the substation conditions.
Relay contacts
(NC/NO contacts)
On the 7TR71 preferential treatment/isolator replica module some of the relay contacts can be set either as NC or NO contacts. The relay contacts must be matched to
the configurations. The assignment of the jumpers to the respective functions is shown
in the block diagram A.3. The physical location of the jumpers on the p.c.b. is shown
in Figure A-7.
q Insert the peripheral modules into their slots and secure them with a screw from the
back of the housing. The slots are numbered and color-coded, refer to Figure 2-4.
q The peripheral modules are identified by a labelling strip on which the current configuration is stated. The configuration information should contain the designation of
the peripheral modules in accordance with their mounting position, and their voltage
ranges. Each peripheral module housing has a rating sticker that should be placed
on the top of the housing after installing the peripheral modules.
q Make electrical connections via the screw-type connection modules. Special attention has to paid to the designations of the connection modules, the permissible conductor cross-sections and tightening torques (refer also to chapter 2). Use copper
conductors only!
Note:
As the plug-on connectors and pins of the different peripheral modules are not coded,
the plug-on connectors must be marked to make their allocation to the appropriate pin
connectors on the peripheral modules possible. The marking system for this is shown
in Figure 2-2. The marking should contain the following information:
Number of the peripheral module housing
Slot identification (A, B, C, D) of the module
Top connector (X1) or bottom connector (X2)
Terminals on the connector (1-10, 11-20, 21-30, 31-40)
7-4
7SS60 Manual
E50417-G1176-C132-A1
7.2
Commissioning
Warning!
Hazardous voltages are present in this electrical equipment during operation. Non
observance of the safety rules can result in severe personal injury or property damage.
Only qualified personnel shall work on and around this equipment after becoming thoroughly familiar with all warnings and safety notices of this manual as well as with the
applicable safety regulations.
Particular attention must be drawn to the following:
The earthing screw of the device must be connected solidly to the protective earth
conductor before any other electrical connection is made.
Hazardous voltages can be present on all circuits and components connected to the
supply voltage or to the measuring and test quantities.
Hazardous voltages can be present in the device even after disconnection of the
supply voltage (storage capacitors!).
After switching of the auxiliary voltage, 10 s should be allowed to elapse before
switching the auxiliary voltage on again, in order to ensure defined start-up conditions.
The limit values stated in chapter 9.1 must not be exceeded at all, not even during testing and commissioning.
When performing tests with secondary test equipment, attention must be paid that no
other measuring values are applied and that the trip command lines to the circuit
breakers are interrupted, unless explicitly stated otherwise.
DANGER!
The CT secondary terminals must be short-circuited on the CTs before the current supply conductors to the device are interrupted!
Where a testing switch is provided which short-circuits the CT secondary lines automatically, it is sufficient to set it to Test position, provided that the short-circuiters
have been checked previously.
The commissioning procedure requires to perform switching operations. The tests described assume that they can be performed safely. Therefore, they are not suited for
checks during operation.
Warning!
Primary test may only be carried out by qualified personnel, who are familiar with the
commissioning of protection systems, the operation of the plant and the safety rules
and regulations (switching, earthing, etc.).
7SS60 Manual
E50417-G1176-C132-A1
7-5
7.2.1
7.2.1.1
Trip circuits
q Check the trip circuits for controlling the circuit breakers. Where service conditions
do not allow to trip a circuit breaker, you can proceed e.g. by switching off the
breaker control voltage and checking the trip function as far as the circuit breaker
coil.
Isolator status
feedback signals
Isolator replica
q Check that isolator states are correctly detected. To do so, perform an isolator
switching operation and check the feedback signal in OPEN position. If there is no
checkback signal (because of wire break or auxiliary power outage), the isolator is
assumed to be CLOSED, so that instabilities of the measuring system when a current flows are efficiently counteracted.
q Check the correct allocation of the feeder currents to the measuring system (isolator
replica) using load currents or secondary test equipment.
Current
transformer
circuits
In this context, it must be checked that the busbar protection is normalized, i.e. that
it provides a uniform transformation ratio in all output circuits. Where current transformers have different transformation ratios, the primary rated current is set to a value
between 70 and 100% of the rated maximum primary current of the existing current
transformers by means of suitable matching or summation current matching transformers.
For the check of the connection circuits, the currents that are fed by the CTs onto the
protection are short-circuited at the terminals of the protection. They are proportional
to the respective primary-side currents. The equivalent of the normalized primary rated on the secondary side of the matching or summation current transformers is a current of 100 mA. The correct current ratio must be checked by measurements in each
feeder or coupler bay with a primary current that should be at least 20 % of the normalized rated current.
7-6
7SS60 Manual
E50417-G1176-C132-A1
In models with a summation current transformer input, this measurement does not
check that the summation current transformer winding that lies in the residual current
path is correctly connected. With a symmetrical current and if all devices are correctly
connected, the residual current flowing in the neutral conductor is practically zero, so
that an interruption or polarity reversal in that circuit is not detected.
Feeders which do not carry a sufficient load current should instead be checked with
primary testing equipment.
DANGER!
Manipulations on the measuring current transformers must be performed with the utmost precaution! Short-circuit the current transformers before disconnecting any current supply leads to the device!
4AM5120-3DA00-0AN2
4AM5120-4DA00-0AN2
Figure 7-1
To allow an electrical check of this circuit as well, an artificial asymmetry of the connections is created. This is achieved by short-circuiting in the tested bay successively
the secondary windings of either the main current transformers or of the matching
transformers in phases L2 and L3, and by disconnecting their outgoing leads, so that
the current L1 flows only through the primary winding of L1 and the winding N in the
zero current path of the summation current transformers.
In this circuit, the rated current on the primary side of the main current transformer corresponds to a current of approx. 300 mA on the secondary side of the summation current transformer. If the N-winding were connected with reversed polarity, the rated primary current would yield only approx. 60 mA instead of approx. 300 mA. The correct
connection of the input windings of the summation current transformers can also be
checked by verifying, either visually or with a continuity test, the external connection
circuit and then injecting a suitable current, e.g. 1 A or 5 A, directly into the series-connected winding of the L1 and the summation current path. This allows to perform the
test without a primary load.
7SS60 Manual
E50417-G1176-C132-A1
7-7
7.2.2
7.2.2.1
7-8
7SS60 Manual
E50417-G1176-C132-A1
This chapter describes the maintenance procedures that are necessary and recommended to ensure the continuous reliability of the SIPROTEC 7SS60 protection system. It tells you which components should be checked and/or replaced on a routine
basis and what to do in case of malfunctions of the device. The chapter is intended
both for personnel in charge of operation and for protection engineers.
7SS60 Manual
E50417-G1176-C132-A2
8.1
General
8-2
8.2
Routine checks
8-3
8.3
Troubleshooting
8-4
8.4
Repair/Return
8-6
8-1
8.1
General
7SS601 measuring
system
Peripheral
modules
8-2
The current transformer circuits are permanently monitored by the differential current
supervision, which can be set to high sensitivity. Faults in the current transformer circuit are detected under the condition that the feeder current is at least 10 % of the normalized rated current Ino (rated current of the transformer with the highest transformation ratio).
7SS60 Manual
E50417-G1176-C132-A2
8.2
Routine checks
Routine checks of characteristics or pick-up values are not necessary as they are part
of the continuously supervised firmware programs. The planned maintenance intervals for checking and maintenance of the plant can be used to perform operational
tests of the protection equipment. This maintenance serves mainly for checking the
interfaces of the unit, i.e. the coupling with the plant.
The following procedure is recommended. If the result of one or more of the above
steps suggests that there is a fault, please proceed as described in chapter 8.4.
8.2.1
q Check that the green LED Service/Betrieb on the front panel of the 7SS601 measuring system is on and that the red LED Blocked/Strung is off.
q Check whether the LED indications on the front panel show a plausible current status of the measuring system and the station.
q Press the N key. All LEDs (with the exception of the red LED Blocked/Strung)
light up.
q Read out the measured values (refer to Section 6.1). The differential current must
be low, and the restraint current must be equal to the summated amounts of the currents of all feeders that are connected to the measuring system.
q Read out the operational annunciations (refer to Section 6.1). Check that they do
not contain any entries on faults in the system, in the measured values, or any other
kind of implausible information.
8.2.2
Peripheral modules
Trip circuits
q Check the trip circuits for controlling the circuit breakers. Where service conditions
do not allow to trip a circuit breaker, you can proceed e.g. by switching off the
breaker control voltage and checking the trip function as far as the circuit breaker
coil.
Isolator status
feedback signals
Isolator replica
q Check that isolator states are correctly detected. To do so, perform an isolator
switching operation and check the feedback signal in OPEN position. If there is no
checkback signal (because of wire break or auxiliary power outage), the isolator is
assumed to be CLOSED, so that instabilities of the measuring system when a current flows are efficiently counteracted.
q Check the correct allocation of the feeder currents to the measuring system (isolator
replica) using load currents or secondary test equipment.
Current
transformer
circuits
7SS60 Manual
E50417-G1176-C132-A2
The transformer currents of feeders which do not carry a sufficient load current should
instead be checked with primary testing equipment.
8-3
8.3
Troubleshooting
8.3.1
tude, connected to the correct terminals (block circuit diagrams are given in Appendix A.2 and A.3)?
q Has the mini-fuse in the power supply section blown? If required, replace the minifuse according to the section Replacing the mini-fuse below.
If the red fault indicator LED is on and the green ready LED remains dark, re-initialization could be tried by switching the auxiliary voltage off and on again.
This, however, results in loss of parameter settings in a parameterizing process has
not yet been completed. Additionally, date and time must be set again (refer to chapter
4.2.5).
Replacing the minifuse
q Select a replacement fuse 5 x 20 mm (refer to Section A.4). Ensure that the rated
value, time lag (slow) and code letters are correct.
q Prepare the area of work: provide a conductive surface for the module.
q Slip away the covering caps at the top and bottom of the housing, making accessible one screw each in the top and bottom center. Unscrew these two screws.
Warning!
Hazardous voltages can be present in the device even after disconnection of the supply voltage (storage capacitors!).
q Pull out the module by taking it at the front panel and place it on the conductive surface.
..
Warning!
Electrostatic discharges via the component connections, the p.c.b. tracks or the connecting pin must be avoided under all circumstances by previously touching an
earthed metal surface.
8-4
7SS60 Manual
E50417-G1176-C132-A2
8.3.2
Peripheral modules
A general detailed testing specification cannot be given.
Please observe the plans for the switchgear and the block diagrams of the peripheral
modules given in Appendix A.3.
7SS60 Manual
E50417-G1176-C132-A2
8-5
8.4
Repair/Return
It is recommended to refrain strictly from repairing units or modules, because they
contain especially selected components, which must be handled according to the regulations for EED (electrostatic endangered devices). In the first place, special techniques are required for working with the printed circuit boards, so that the flow-soldered boards and sensitive components are not damaged.
Therefore, if a defect cannot be eliminated by the operations described in chapter 6,
it is recommended to send the complete device or individual peripheral modules back
to the manufacturer. Use the original transport packaging for return. If alternative
packaging is used, this must provide the degree of protection against mechanical
shock as laid down in IEC 255-21-1 Class 2 and IEC 255-21-2 Class 1.
Note:
Before returning the device, all configuration and setting parameters should be read
out and stored. If the location of jumpers on the p.c.b.s has been changed, the
changed setting should be noted as well.
When a device is returned to you after a successful repair, all jumpers on the p.c.b.
are in the initial state defined by the ordering code (MLFB). The configuration and setting parameters are also reset to the initial delivery state.
In case it is unavoidable to replace single modules, the EED-regulations have to be
followed (handling of electrostatic endangered devices).
Before you extract the peripheral modules from the housing, pull off the plug-on connectors and unscrew the securing screw on the rear.
Warning!
Hazardous voltages can be present in the device even after disconnection of the supply voltage (storage capacitors!).
Caution!
Electrostatic discharges via the component connections, the p.c.b. tracks or the connecting pin must be avoided under all circumstances by previously touching an
earthed metal surface. This applies equally for the replacement of removable components, such as EPROM or EEPROM chips. For transport and returning of individual
modules, electrostatic protective packing material must be used.
Modules fitted in the unit are not endangered.
8-6
7SS60 Manual
E50417-G1176-C132-A2
Technical Data
7SS60 Manual
E50417G1176C132A2
9.1
General data
9-2
9.2
Electrical tests
9-10
9.3
Mechanical tests
9-12
9.4
9-13
9.5
Service conditions
9-14
9.6
Dimensions
9-15
9-1
Technical Data
9.1
General data
9.1.1
Measuring input Id
Rated current
100 mA
Rated frequency
Measuring input IR
Isolating voltage
2.5 kV (rms)
0 to 240 %
Measuring dynamics
Rated current
1.9 mA
250 x IN for 10 ms
Auxiliary voltage
9-2
Isolating voltage
2.5 kV (rms)
Measuring dynamics
0 to 200 x IN
24/48 Vdc
60/110/125 Vdc
220/250 Vdc
115 Vdc
Superimposed ac voltage
peak to peak
15 % of rated voltage
(19 to 58 Vdc)
(48 to 150 Vdc)
(176 to 300 Vdc)
(92 to 133 Vac)
Power consumption
quiescent
energized
approx. 3 W
approx. 5 W
50 ms at UH 100 Vdc
20 ms at UH 48 Vdc
7SS60 Manual
E50417G1176C132A2
Technical Data
Binary inputs
Number
3 (can be marshalled)
24 to 250 Vdc
approx. 2.5 mA
independent of operating voltage
can be changed by setting jumpers
Pick-up threshold
rated aux. voltage 48/60 Vdc
Upick-up
17 Vdc
Udrop-off
< 8 Vdc
rated aux. voltage 110/125/220/250 Vdc
Upick-up
74 Vdc
Udrop-off
< 45 Vdc
Command contacts
Signal contacts
max. voltage
300 Vdc
approx. 40 ms
Number of relays
Switching capacity
MAKE
BREAK
1000 W/VA
30 W/VA
Switching voltage
250 V ac/dc
permissible current
continuous
0.5 s
5A
30 A
Number of relays
3 (2 can be marshalled)
Contacts
Switching capacity
MAKE
BREAK
1000 W/VA
30 W/VA
Switching voltage
250 V ac/dc
permissible current
continuous
0.5 s
5A
30 A
Standard
isolated
RS485
Test voltage
3.5 kVdc
Connection
Transmission rate
Serial interface
7SS60 Manual
E50417G1176C132A2
1 (2 NO contacts)
1 (1 NO contact)
9-3
Technical Data
Housing
Differential current
protection
Housing
Dimensions
Weight
approx. 4.0 kg
IP 51
IP 2X
5 % of setpoint
Times
Minimum fault detection time 50/60 Hz 1) 10 ms
Typical fault detection time 50/60 Hz 1) 12 ms (rapid measurement)
40 ms (repeated measurement)
Minimum fault detection time 16.7 Hz 1) 12 ms
Typical fault detection time 16.7 Hz 1)
14 ms (rapid measurement)
40 ms (repeated measurement)
Reset time 2)
28 ms at 50 Hz
26 ms at 60 Hz
70 ms at 16.7 Hz
1)
2)
Lockout function
Additional
functions
until reset
Reset
IDIFF, ISTAB
0 to 240% Ino
5% of rated value
Fault logging
Time stamping
Resolution for operational annunc.
Resolution for fault annunc.
Fault recording (max. 8 faults)
Recording time (from fault detection)
max. length per record
Pre-fault time
Post-fault time
Sampling frequency
9-4
7SS60 Manual
E50417G1176C132A2
Technical Data
9.1.2
Peripheral modules
9.1.2.1
Measuring input Is
Rated current
100 mA
Rated frequency
16.7Hz, 50 Hz, 60 Hz
48/60 Vdc
(38 to 72 Vdc)
110/125 Vdc
(88 to 150 Vdc)
220/250 Vdc
(176 to 300 Vdc)
settable, see Figure A-5
As delivered: 220/250 Vdc
Power
consumption
Command contacts
Number of relays
2 NO contacts
48 V
60 V
110 V
125 V
220 V
250 V
0.7 W
1.0 W
1.9 W
2.4 W
3.1 W
3.9 W
approx. 7 ms
Switching capacity
MAKE
BREAK
1000 W/VA
30 W/VA
Switching voltage
250 V ac/dc
Permissible currents
continuous
0.5 s
5A
30 A
Weight
approx. 2.0 kg
1)
7SS60 Manual
E50417G1176C132A2
9-5
Technical Data
9.1.2.2
Isolator replica
Preferential
treatment
Auxiliary voltage
Number of feeders
(single busbar and double busbar)
Number of isolators
(per 1 auxiliary contact) per feeder
3 changeover contacts
Switching time
< 20 ms
2 changeover contacts
48/60 Vdc
(38 to 72 Vdc)
110/125 Vdc
(88 to 150 Vdc)
220/250 Vdc
(176 to 300 Vdc)
depending on the ordering number,
see Chapter A.1
Power
consumption
Relay contacts
Weight
9-6
Relay
K1/K2, K3/K4
48 V
60 V
110 V
125 V
220 V
250 V
1.5 W
1.9 W
1.8 W
2.1 W
1.8 W
2.1 W
K5
48 V
60 V
110 V
125 V
220 V
250 V
0.4 W
0.5 W
0.5 W
0.6 W
1.1 W
1.2 W
Switching capacity
MAKE
BREAK
1000 W/VA
30 W/VA
Switching voltage
250 V ac/dc
Permissible current
continuous
0.5 s
5A
10 A
approx. 0.6 kg
7SS60 Manual
E50417G1176C132A2
Technical Data
9.1.2.3
Auxiliary voltage
48/60 Vdc
(38 to 72 Vdc)
110/125 Vdc
(88 to 150 Vdc)
220/250 Vdc
(176 to 300 Vdc)
settable, see Figure A-8
as delivered: 220/250 Vdc
Power
consumption
Command contacts
Number of relays
2 NO contacts
48 V
60 V
110 V
125 V
220 V
250 V
0.7 W
1.0 W
1.9 W
2.4 W
3.1 W
3.9 W
approx. 7 ms
Switching capacity
MAKE
BREAK
1000 W/VA
30 W/VA
Switching voltage
250 V ac/dc
permissible current
continuous
0.5 s
5A
30 A
Weight
approx. 0.5 kg
1)
9.1.3
Design
Housing
Dimensions
Weight
approx. 3.5 kg
7SS60 Manual
E50417G1176C132A2
IP 51 (front)
IP 20 (rear)
IP 2X (if all connectors and blanking plates
are fitted)
9-7
Technical Data
9.1.4
Matching transformers
4AM5120-1DA00-0AN2
for connection to current
transformers with a
rated current IN of
1A
Rated frequency fN
45-60 Hz
Winding
Number of turns
A-B
1
B-C
2
D-E
4
E-F
8
G-H
16
H-J
32
Y-Z
500
6.8
0.4
6.8
0.8
6.8
1.6
6.8
3.2
6.8
6.4
6.8
12.8
0.85
200
A
V
4AM5120-2DA00-0AN2
for connection to current
transformers with a
rated current IN of
5A
Rated frequency fN
45-60 Hz
Winding
Number of turns
A-B
1
B-C
2
D-E
4
E-F
8
Y-Z
500
26
0.4
26
0.8
26
1.6
26
3.2
0,85
200
Thermal overload
capability
Weight
9-8
A
V
max. thermal overload capability for all 2 transformer types under simultaneous load
of all turns
for 10 s
8 x IN
for 1 s
20 x IN
approx. 3.7 kg
7SS60 Manual
E50417G1176C132A2
Technical Data
9.1.5
4AM5120-3DA00-0AN2
for connection to current
transformers with a
rated current IN of
1A
Rated frequency fN
45-60 Hz
Winding
Number of turns
A-B
3
C-D
6
E-F
9
G-H
18
J-K
24
L-M
36
N-O
90
Y-Z
500
0.85
1.2
2.4
3.6
7.2
9.6
14.4
36
200
Max. current,
continuous
Max. voltage
4AM5120-4DA00-0AN2
for connection to current
transformers with a
rated current IN of
5A
Rated frequency fN
45-60 Hz
Winding
Number of turns
A-B
1
C-D
2
E-F
3
G-H
4
J-K
6
L-M
8
N-O
12
Y-Z
500
17.5
17.5
17.5
17.5
17.5
17.5
8.0
0.85
0.4
0.8
1.2
1.6
2.4
3.2
4.8
200
Max. current,
continuous
Max. voltage
Thermal overload
capability
Weight
7SS60 Manual
E50417G1176C132A2
max. thermal overload capability for all 2 transformer types under simultaneous load
of all turns
for 10 s
8 x IN
for 1 s
20 x IN
approx. 3.7 kg
9-9
Technical Data
9.2
Electrical tests
CE conformity,
regulations
9-10
2.5 kV (rms); 50 Hz
3.5 kVdc
High-frequency test
IEC 60255-22-1,
DIN VDE 0435 part 303;
class III
7SS60 Manual
E50417G1176C132A2
Technical Data
High-energy pulse
(SURGE), IEC 61000-4-5, installation
class 3
Auxiliary voltage
Longitudinal test 2 kV; 12 ; 9 F
Transversal test 1 kV; 2 ; 18 F
Measuring inputs, binary inputs and relay
outputs:
Longitudinal test: 2 kV; 42 ; 0.5 F
Transversal test: 1 kV; 42 ; 0.5 F
HF on lines, amplitude-modulated
IEC 61000-4-6; class III
7SS60 Manual
E50417G1176C132A2
Damped oscillations
IEC 61000-4-12
IEC 60694
9-11
Technical Data
9.3
Mechanical tests
Vibration
IEC 60255-21-1, class II
IEC 60068-2-6
Shock
IEC 60255-21-2, class I
IEC 60068227
Seismic vibration
IEC 60255-21-3, class 1
IEC 60068-3-3
horizontal axis
vertical axis
sinusoidal
10 to 60 Hz, 0.075 mm amplitude
60 to 150 Hz; 1 g acceleration
sweep rate 1 octave/min
20 cycles in 3 orthogonal axes
half sinusoidal
acceleration 5 g; duration 11 ms
3 shocks in each direction of the
3 orthogonal axes
sinusoidal
1 to 8 Hz: 3.5 mm amplitude
8 to 35 Hz: 1 g acceleration
1 to 8 Hz: 1.5 mm amplitude
8 to 35 Hz: 0.5 g acceleration
frequency sweep 1 octave/min
1 cycle in 3 orthogonal axes
Vibration
IEC 60255-21-1, class II
IEC 60068-2-6
Shock
IEC 60255-21-2, class 1
IEC 60068-2-27
Continuous shock
IEC 60255-21-2, class 1
IEC 60068-2-29
9-12
sinusoidal
5 to 8 Hz: 7.5 mm Amplitude
8 to 150 Hz: 2 g acceleration sweep rate
1 octave/min
20 cycles in 3 orthogonal axes
half sinusoidal
acceleration 15 g; duration 11 ms
3 shocks in each direction of the
3 orthogonal axes
half sinusoidal
acceleration 10 g; duration 16 ms
1000 shocks in each direction of the
3 orthogonal axes
7SS60 Manual
E50417G1176C132A2
Technical Data
9.4
-20 to +45 C
for storage
-25 to +55 C
during transport
-25 to +70 C
We recommend to install the devices so that they are not subject to direct sunlight and strong fluctuations in temperature
which could lead to moisture condensation.
7SS60 Manual
E50417G1176C132A2
9-13
Technical Data
9.5
Service conditions
The relay is designed for use in industrial environment, for installation in standard relay rooms and
compartments so that with proper installation electro-magnetic compatibility (EMC) is ensured. the following
should also be heeded:
All contactors and relays which operate in the same cubicle or on the same relay panel as the digital
protection equipment should, as a rule, be fitted with suitable spike quenching elements.
All external connection leads in substations from 100 kV upwards should be screened with a screen
capable of carrying power currents and earthed at both sides. No special measures are normally
necessary for substations of lower voltages.
It is not permissible to withdraw or insert individual modules under voltage. In the withdrawn condition.,
some components are electrostatically endangered; during handling the standards for electrostatically
endangered components must be observed. The modules are not endangered when plugged in.
Warning!
The device is not designed for used in residential environment as defined in EN 50081.
9-14
7SS60 Manual
E50417G1176C132A2
Technical Data
9.6
Dimensions
Measuring system
29.5
172
Mounting plate
37
75
70
71 +2
245 + 1
255.8 0.3
244
266
5 or
M4
5.4
Rear view
7.3
56.5 0.3
Side view
Dimensions in mm
Figure 9-1
7SS60 Manual
E50417G1176C132A2
Panel cutout
Housing 7XP20 of the 7SS601 measuring system for panel or cubicle flush
mounting
9-15
Technical Data
Peripheral module
housing
172
2
225
220
244
266
Mounting plate
57
Side view
Rear view
221 +2
Dimensions in mm
245 + 1
255.8 0.3
5 or M4
5.4
13.2
180 0.5
7.3
206.5 0.3
Panel cutout
Figure 9-2
9-16
Housing 7XP204 of the peripheral modules for panel or cubicle flush mounting
7SS60 Manual
E50417G1176C132A2
Technical Data
Matching
transformers /
Summation current
matching
transformers
Dimensions in mm
5.8
102.5
4AM5120-1DA00-0AN2
Figure 9-3
7SS60 Manual
E50417G1176C132A2
4AM5120-2DA00-0AN2
4AM5120-3DA00-0AN2
4AM5120-4DA00-0AN2
9-17
Technical Data
9-18
7SS60 Manual
E50417G1176C132A2
Appendix
This appendix is mainly a reference for experienced users. It contains ordering information, general diagrams and connection diagrams, and tabular listings of all settings
and system data for the full scope of device functions.
7SS60 Manual
E50417-G1176-C132-A2
A.1
A-2
A.2
A-5
A.3
A-6
A.4
A-10
A.5
A-12
A.6
Operating tree
A-16
A.7
Overview of parameters
A-21
A.8
List of information
A-23
A-1
Appendix
A.1
Table A-1
Measuring system
7SS601
Rated current/frequency
100 mA, ac 50, 60 Hz
Mechanical design
In 7XP20 1/6 19" housing, for panel or cubicle flush mounting
Measuring system
Standard measuring system
Order No.
Restraint/
command output module
7TM700
Order No.
Preferential treatment/
Isolator replica module
7TR710
A-2
7SS60 Manual
E50417-G1176-C132-A2
Appendix
Order No.
7TS720
Order No.
7SS60 Manual
E50417-G1176-C132-A2
7XP204
A-3
Appendix
Accessories
Order No.
Copper cable
between PC (9-pin female connector)
and converter/protection device
7XV5100-2
7XV5700-0AA0
7XV5700-1AA0
Converter
Full duplex fiber optic cable - RS485
Auxiliary voltage: 24 Vdc to 250 Vdc, 110/230 Vac
Line converter
FSMA plug
7XV5650-0AA0
ST plug
7XV5650-0BA0
FSMA plug
7XV5651-1AA0
ST plug
7XV5651-1BA0
Cascade converter
7XS5400-0AA00
7XS5410-0AA00
7XS5440-0AA00
4AM5120-3DA00-0AN2
5 A, 50/60 Hz
4AM5120-4DA00-0AN2
Matching transformer
1 A, 50/60 Hz
4AM5120-1DA00-0AN2
5 A, 50/60 Hz
4AM5120-2DA00-0AN2
1 A, 16.7 Hz
4AM5120-1DB00-0AN2
5 A, 16.7 Hz
4AM5120-7BA00-0AN0
W73078-B9004-A710
Angle bracket
C73165-A63-C200-3
E50417-G1100-C132-A2
English
E50417-G1176-C132-A2
E50417-P1100-C155-A1
English
E50417-P1176-C155-A1
A-4
7SS60 Manual
E50417-G1176-C132-A2
Appendix
A.2
7SS601
1)
1)
1)
1)
1)
1)
1)
1)
1)
1)
1)
Figure A-1
Block diagram of the 7SS601 measuring system (default setting of binary inputs, command and
signal relays as delivered)
7SS60 Manual
E50417-G1176-C132-A2
A-5
Appendix
A.3
Restraint/
command output
module 7TM700
Attention!
All relay coils
depend on polarity
Figure A-2
A-6
7SS60 Manual
E50417-G1176-C132-A2
Appendix
Preferential
treatment/
isolator replica
module 7TR710
L+ internal
X2:1
L+ internal
Start +
blocking pulse 1 - X2:2
K1
X8
X2:5
X15
X2:8
X2:25
X2:22
L- internal
X2:4
X2:26
+
X2:21 - Blocking pulse 1
to
binary input
L- internal
measuring system
X7
X6
X5
X16
X4
X17 X3
+
K2
X2:9
X2:7
X2:15
X2:16
X2:17
X2:12
X2:13
X2:11
L+ internal
X1:19
L+ internal
Start +
blocking pulse 2 - X1:20
K3
+
X1:40 - Blocking pulse 2
to
binary input
L- internal
measuring system
X14
X1:17
X1:16
X1:5
X1:36
X1:39
L- internal
Attention!
All relay coils
depend on polarity
X1:35
X13
X12
X18 X11
X19
X10
X20 X9
+
K4
X1:4
X1:6
X1:13
X1:12
X1:14
X1:8
X1:9
X1:10
L-
X1:2
X2:38
X1:23
Figure A-3
7SS60 Manual
E50417-G1176-C132-A2
+
K5
X2:19
L+
X2:39
X2:40
X1:22
X1:21
A-7
Appendix
Command output
module 7TS720
Attention!
All relay coils
depend on polarity
Figure A-4
A-8
7SS60 Manual
E50417-G1176-C132-A2
Appendix
A.4
7SS601
L
H
X28
X6
F1
L
H
1
2
3
X7
L
H
X20
X8
3
2
1
1 2
X21
X11
1
2
3
4
X30
1
2
3
X12
Figure A-5
7SS60 Manual
E50417-G1176-C132-A2
A-9
Appendix
Jumper
X11
empty
12
23
X12
23
23
12
X30
empty
12, 34
23
Binary input
Jumper
17 V
73 V
X6
X7
X8
Jumper
RS485 interface
without terminator
with terminator
X20
12
23
X21
12
23
Jumper
A-10
Pick-up threshold
Signal relay 1
NO contact
NC contact
X28
12
23
Rated voltage
Fuse F1
acc. to IEC 60127
24/48 Vdc
T1.6H250V
60/110/125 Vdc
T1H250V
220/250 Vdc
T1H250V
115 Vac
T1H250V
7SS60 Manual
E50417-G1176-C132-A2
Appendix
A.5
Restraint/
command output
module 7TM700
X1
X2
1
2
3
4
48/60V
110/125V
220/250V
X21
Figure A-6
1
2
3
4
48/60V
110/125V
220/250V
X22
1
2
3
4
48/60V
110/125V
220/250V
X23
1
2
3
4
48/60V
110/125V
220/250V
X24
1
2
3
4
48/60V
110/125V
220/250V
X25
Location of the jumpers on the 7TM700 restraint/command output module (delivery status)
Jumper
7SS60 Manual
E50417-G1176-C132-A2
X21
12
23
34
X22
12
23
34
X23
12
23
34
X24
12
23
34
X25
12
23
34
A-11
Appendix
Preferential
treatment/
isolator replica
module 7TR710
X1
X2
X9
X10
X11
Figure A-7
X20
X19
X18
X12
X13
X14
X6
X7
X8
X17
X16
X15
X3
X4
X5
Refer to Figure A-3 for the function of the jumpers. The jumper assignment depends
on the configuration.
A-12
7SS60 Manual
E50417-G1176-C132-A2
Appendix
Command output
module 7TS720
X1
X2
1
2
3
4
48/60V
110/125V
220/250V
X21
1
2
3
4
48/60V
110/125V
220/250V
X22
1
2
3
4
48/60V
110/125V
220/250V
X23
1
2
3
4
48/60V
110/125V
220/250V
X24
1
2
3
4
1
2
3
4
48/60V
110/125V
220/250V
X25
48/60V
110/125V
220/250V
X26
1
2
3
4
48/60V
110/125V
220/250V
X27
1
2
3
4
48/60V
110/125V
220/250V
X28
Figure A-8
Location of the jumpers on the 7TS720 command output module (delivery status)
Jumper
7SS60 Manual
E50417-G1176-C132-A2
X21
12
23
34
X22
12
23
34
X23
12
23
34
X24
12
23
34
X25
12
23
34
X26
12
23
34
X27
12
23
34
X28
12
23
34
A-13
Appendix
A.6
Operating tree
The following operating tree gives you an overview of the address blocks and setting
parameters of the 7SS601 busbar protection system. It shows the operating sequences that must be followed to make a specific selection.
Table A-2
1st level
2nd level
66
9
66
3$5$0(
32:(5
6<67'$7
3rd level
4th level
5th level
0$56+
%,
%,
)5(4
7753
/2XW
%86%$5
3527(&7
%36WDW
,G!
. IDF
7US'O\
,',))
683(59
,G VXS
,G WKU
0$56+
0$56+
%,1,13
%,
A-14
7SS60 Manual
E50417-G1176-C132-A2
Appendix
Table A-2
1st level
2nd level
3rd level
4th level
5th level
0$56+
%,
%,
%,
0$56+
%,
%,
%,
0$56+
6,*5(/
0$56+
6,*5(
6,*
6,*
0$56+
6,*5(
6,*
6,*
0$56+
/('
0$56+
/('
/('
/('
0$56+
/('
/('
/('
0$56+
/('
/('
/('
7SS60 Manual
E50417-G1176-C132-A2
A-15
Appendix
Table A-2
1st level
2nd level
3rd level
4th level
5th level
0$56+
/('
/('
/('
0$56+
&0'5(/
0$56+
&0'5(
&0'
&0'
,1723
/$1*8$
,17(5
)$&(
'(9,&(
)(('(5
68%67$
3&,17
*$36
3&%$8'
3$5,7<
)$8/7
5(&25'(5
70$;
735(
7326
A-16
7SS60 Manual
E50417-G1176-C132-A2
Appendix
Table A-2
1st level
2nd level
$1181&
23(5
$1181&
)$8/7
$1181&
3rd level
4th level
5th level
OVW
)$8/7
QG
)$8/7
UG
)$8/7
WK
)$8/7
WK
)$8/7
WK
)$8/7
WK
)$8/7
WK
)$8/7
0($6
9$/8(6
,G
,V
7SS60 Manual
E50417-G1176-C132-A2
A-17
Appendix
Table A-2
1st level
2nd level
3rd level
$'',7,21
)81&7,21
7,0(
6(77,1*
7,0(
6(77,1*
4th level
5th level
'$7(
7,0(
7(67
$,'6
,2 67$7
%,67$7
5(67$7
/('
67$786
021,725
A-18
7SS60 Manual
E50417-G1176-C132-A2
Appendix
A.7
DIGSI
addr.
Overview of parameters
Parameter
Possible settings
Default setting
Explanation
1101
01 FREQ
50 Hz
60 Hz
50 Hz
1134
01 T-TRP
0.01s to 32.00 s
0.15 s
1135
01 L.Out
OFF
ON
ON/butt.
OFF
Lockout function
1501
10BUSBAR
PROTECT.
ON
OFF
BLO.TRP
ON
1505
10Id>
1.00 Ino1
1506
10K fac
0.25 to 0.80
0.60
1511
10 TrpDly
0.00 to 10.00 s
0.00 s
1801
13Id Sup
bl/relBP
bl/ackBP
ALRMonly
OFF
bl/relBP
1802
13Id thr
0.15 Ino1
7101
71LANGUA
ENGLISH
DEUTSCH
ENGLISH
7201
72DEVICE
7202
72FEEDER
7203
72SUBSTA
7211
72 PC-INT
DIGSI V3
ASCII
DIGSI V3
7214
72 GAPS
minimum setting:.....0.0 s
maximum setting:....5.0 s
1.0 s
7215
72PCBAUD
1200 Baud
2400 Baud
4800 Baud
9600 Baud
19200 Baud
9600 Baud
7216
72 PARITY
DIGSI V3
8O1
8N2
8N1
DIGSI V3
7410
74-T MAX
0.20 s to 5.00 s
1.50 s
7411
74 T-PRE
0.05 s to 1.50 s
0.30 s
7412
74 T-POS
0.05 s to 1.50 s
0.20 s
1 Ino: normalized rated current; Ino = 100 mA with a symmetrical rated current flowing at the primary side
7SS60 Manual
E50417-G1176-C132-A2
A-19
Appendix
A.8
List of information
Abbreviation
Meaning
FNo.
Op/Ft
Operational/fault annunciation
C/CG
Measurand
BT
GI
Table A-3
FNo.
Text
Meaning
not all.
Not allocated
>LED r.
Op
Ft
GI
51
DEv.OK
Device operative/healthy
52
operat.
60
LED res
LED reset
110
ANNlost
111
PCannLT
113
TAGlost
115
ANNovfl
203
REC del
301
Sys.Flt
302
FAULT
608
ID=
609
IR=
7701
>LO Res
7721
LockOut
CG
7900
>BP blo
CG
7901
>BP bPu
7910
BP blk.
CG
7911
BP act.
CG
7914
BP Trip
7915
BP Tdel
7920
IdS act
CG
7921
IdS Flt
CG
7922
BIPulS.
CG
1
2
BT
X
C
C
CG
O
CG
X
X
A-20
7SS60 Manual
E50417-G1176-C132-A2
Index
A
Dimensions
Matching transformers 9-17
Measuring system 9-15
Peripheral modules housing 9-16
Summation current transformers 9-17
Accessories A-2
Application scope 1-6
Auxiliary voltage 7-2, 7-4
F
Fault events 6-4
Fault recording
Times 5-22
Features 1-8
Feeder address 4-13
C
Character format 4-14
Check
Electrical 3-3
Isolator replica 7-6
Isolator status feedback signals 7-6
Rated data 3-3
Trip circuits 7-6
Checking
Current transformer circuits 7-6
Infeed circuits 7-6
Climatic stress test 9-13
Codeword entry 4-4
Commissioning 7-5
Control voltage for binary inputs 7-2
7SS60 Manual
E50417-G1176-C132-A2
Gertedaten
9-2
I
Indication i
Indication of conformity i
Input currents
Directional check 7-8
Installation
Measuring system 7-2
Peripheral modules 7-3
Instructions ii
J
Jumper settings
Measuring system A-9
Peripheral modules A-11
D
Data format 4-13
Date and time
Setting 4-15
Date/time
Readout 6-5
Design 1-3
Device address 4-13
Differential current
Pick-up value 5-18
Differential current supervision
Pick-up threshold 5-20
L
LEDs 6-2
List of information A-20
Lockout function 5-14
M
5-20
Manual
Aim i
Scope of validity
Index-1
Index
Target audience i
Marshalling
Binary inputs 4-8
Command relays 4-12
General 4-5
LEDs 4-11
Signal relays 4-9
Matching transformers 5-12,
Measured values 6-4
Measurement method
Basic principle 5-2
Output circuit 5-4
Restraint 5-5
Supervision 5-4
Measuring principle 1-2
Measuring system
Connection system 2-3
Housing 2-2
Q
Qualified personnel
R
Rated frequency 5-14
Rated system frequency 5-15
Repair 8-6
Replacing the mini-fuse 8-4
Restraint 1-2
Restraint factor 5-18
Return of device to factory 8-6
Routine checks 8-3
5-13
S
Serial interface 4-13
Service conditions 9-14
Storage 3-8
Substation address 4-13
Support
Additional support i
Symbol conventions iii
O
Operating language
Change 4-5
Operating tree A-14
Operation
from a PC 3-6
from membrane keypad 3-6
from the keyboard 3-5
Prerequisites 3-7
Operational annunciations 6-3
Ordering code 3-3
Ordering data A-2
Output of events and measured values
Overview of parameters A-19
6-2
P
Peripheral modules
Allocation of connectors to plugs
Connection system 2-5
Housing 2-4
Identification 2-5
Slots 2-6
Pick-up characteristic 1-2
Index-2
ii
2-5
Testing
Binary inputs 6-6
LEDs 6-7
Signal relays 6-6
Tests
Electrical 9-10
Mechanical 9-12
Training courses i
Transmission gaps 4-13
Troubleshooting
Measuring system 8-4
Peripheral modules 8-5
Typographic conventions iii
U
Unpacking and repacking
3-2
W
Warnings
ii
7SS60 Manual
E50417-G1176-C132-A2