Process Control Lab Manual
Process Control Lab Manual
PROCESSCONTROLLABMANUAL
EXPERIMENT:-1
Aim of the Experiment: To study the V-I Characteristic of SCR using PEC16M1A. Apparatus Required: 1. PEC16M1A Trainer 2. Ammeter (0-200mA) MC 2Nos. 3. Voltmeter (0-30V) MC. 4. Patch chords Theory: An SCR is a type of rectifier, controlled by a logic gate signal. It is a four-layer, three-terminal device. A p-type layer acts as an anode and an n-type layer as a cathode; the p-type layer closer to the n-type (cathode) acts as a gate. In the normal "off" state, the device restricts current to the leakage current. When the gate to cathode voltage exceeds a certain threshold, the device turns "on" and conducts current. The device will remain in the "on" state even after gate current is removed so long as current through the device remains above the holding current. Once current falls below the holding current for an appropriate period of time, the device will switch "OFF". If the applied voltage increases rapidly enough, capacitive coupling may induce enough charge into the gate to trigger the device into the "on" state; this is referred to as "dv/dt triggering." This is usually prevented by limiting the rate of voltage rise across the device, perhaps by using a snubber. "dv/dt triggering" may not switch the SCR into full conduction rapidly and the partially-triggered SCR may dissipate more power than is usual, possibly harming the device. SCRs can also be triggered by increasing the forward voltage beyond their rated breakdown voltage (also called as break over voltage), but again, this does not rapidly switch the entire device into conduction and so may be harmful so this mode of operation is also usually avoided. Also, the actual breakdown voltage may be substantially higher than the rated breakdown voltage, so the exact trigger point will vary from device to device. SCRs are made with voltage ratings of up to 7500 volts, and with current ratings up to 3000 RMS amperes per device. Some of the larger ones can take over 50 kA in single-pulse operation. SCRs are
Connection Procedure: Connect the SCR anode, cathode, gate terminal to SCR Characteristic circuit Connect the ammeter in anode terminal as indicated in the connection diagram
Result: Thus the V-I = ------------------------= ------------------------= ------------------------= ------------------------characteristic of SCR were drawn and note down the following values from the graph sheet. 1. Latching current (IL) 2. Holding current (IH) 3. Gate Current (IG) 4. Break over Voltage (VAK)
Connection Procedure: Connect the MT2 terminal of TRIAC is positive w.r.t. MT1 and gate current also positive. Connect the ammeter in anode terminal as indicated in the connection diagram. Connect the ammeter is gate terminal as indicated in the connection diagram. Connect the voltmeter in between TRIAC MT1 and MT2.
Experimental Procedure: 1. Now switch on the 230V AC Supply. 2. Now vary the pot3 and set the gate current IG. 3. Now slowly increase the MT1 and MT2 voltage by varying the pot4 till the TRIAC is turned on and note the voltage (VMT1) , current (IF) readings as shown in table. 4. Now measure the break over voltage VBO1. 5. Further increase MT1 - MT2 voltage and note the current IA . 6. Plot the VF Vs IF in a graph sheet.
Model Graph:
Result: Thus the V-I Characteristics of TRIAC were studied and notedown the following values from the graph sheet. Latching Current (IL) Holding Current (IH) Gate Current (IG) Break Over Voltage (VAK) = ________________________ = ________________________ = ________________________ = ________________________
10
Procedure: 1. Made Connections as per the the circuit diagram. 2. Vary the voltage linearly by varying the input dc voltage till the DIAC get turned ON. 3. Note down the ammeter (IA) and voltmeter (VA) readings and note down the break over voltage 4. Plo the VA Vs IA in graph sheet. 5. Now change the DIAC MT2 is positive with respect to MT1. 6. Repeat the same procedure and plot the graph. Tabulation: SL. NO. VOLTAGE(VA) CURRENT(IA)
11
12
13
14
measured value to reduce the deviation. Deviation = Set value Measured value. Deviation operates the system and there is a power gain. Procedure:1. Make the connections as per the front panel diagram as shown in the figure. 2. Keep the process fast/slow switch (SW4) in slow position. 3. Change the set value, and note the corresponding changes on set value and measured value meters and also note down the deviation. 4. Then apply a voltage of approximately 1 v to the load disturbance socket. 5. Note down the changes in measured value and deviation.
15
Conclusion:When change in set value is made the measured value changes, but somewhat slower than the set value and the measured value is not as same as the set value. When load disturbance is applied to both the measured value and the deviation changes. The delay in the change of the measured value is due to lags in the process.
16
17
Tabulation:% PB Peak overshoot MP Rise time t r Peak time t p Damping Ratio Setting time ts
18
19
20
Conclusion:By suitable adjustment of an integrator section output the steady state deviation can be reduced to zero. In consequence the measured value becomes much closer to set value. Too much integral term however causes the system to go into oscillation. Generally speaking an increase in integral time reduces the steady state deviation but increases the time of the system takes to settle.
21
Procedure:1. Connections are given as shown in figure. 2. Set the process fast/slow switch (SW4) and controller fast/slow switch (SW3) in fast position. 3. Keep the set value pot to zero. 4. Apply a square wave of 2V P-P at around 50 Hz. 5. Now patch I and I and adjust the integral time until the steady state deviation is zero.
22
23
With
24
Procedure: 1. Interface the heater, blower, Thermistor with VTCS-02 2. Keep the ON-OFF/ PID switch in ON-OFF position, SW-1 should be in downward direction. 3. Keep the overlap POT at minimum position 4. Set the desired temperature (35-95oC) by varying the set value POT 5. Switch on the heater and blower. Blower should not be switched on before heater switching. 6. Tune the overlap to maintain the process variable at set point. 7. View the response for different set points and throttle opening. Results: Thus the ON-OFF control action on temperature process control system was studied.
25
Controller Output = kp (Err) + Bias. PB = (Full Scale Deviation / KC) 100 Offset, the sustained deviation always present in proportional control is dependent on the proportional bandwidth. As proportional band is decreased, deviation is reduced until a point is reached at which the system become unstable.
26
Supply Disturbance: A step change in set point is produced by SW-2 toggle, switch and immediate change in controller output and delayed responses in measured value due to distance/ velocity and transfer lag. Results: Thus the proportional control action on temperature process control system was studied.
27
CO = K p ( Err) + ( Err)dt +
0
d ( Err) + Bias dt
The three mode controller contains the stability of proportional control and the ability to eliminate offset because of reset (integral). Control and the ability provide an immediate correction for the magnitude of a disturbance because of rate (derivative) control.
Procedure: 1. Interface the heater, blower, Thermistor with VTCS-02 2. Keep the ON-OFF/ PID switch in PID position, SW-2 should be in downward direction.
28
Supply Disturbance: A step change in set point is produced by SW-2 toggle, switch and immediate change in controller output and delayed responses in measured value due to distance/ velocity and transfer lag. Results: Thus the proportional control action on temperature process control system was studied.
29
The relation between flow and steam position for a valve installed in a process line will be called the effective valve characteristic.
31
Air to Close: Scale of control valve Flow rate in LPH %ge of Lift %ge of Flow
Conclusion The control valve CV1 was found to be Linear one where the valve CV2 equal percentage type.
32