1.1 Purpose This document describes the Power Distribution Unit (PDU) Model TAB-DC in terms of its functions, structure, and technical specifications.
2012-04-24
HUAWEI Confidential
Page6, Total10
PDU Board.pdf
(1) Positive copper bar (2) DC input power wiring terminal (3) DC output MCB (Breakers)
2012-04-24 HUAWEI Confidential Page7, Total10
(4) DC Surge protector (5) Bank A (6) Bank B (7) Ground Terminal (8) Cable organizer (9) Stoppers for breakers
4.2 Power Distribution Principles of the PDU Model TAB-DC The power distribution principles of the PDU are as follows: The input (+) power is led into the PDU Model TAB-DC through the input terminal 35mm and then divided into 12 outputs through the copper bar to supply power to power consumption devices. The input (-) power is led into the PDU Model TAB-DC directly through the breakers The grounding of the PDU Model TAB-DC is implemented through the XXX grounding screw. For further information about breakers:
IT B icino M T btdin..pdf
4.3 Surge Protection Principle of the PDU Model TAB-DC The surge protector principle of the PDU is as follow: The surge protector unit provides protection to Bank A where NodeB and RRU are connected. For further information about surge protector:
ASC-MA15.pdf
The technical specifications of the PDU consist of the engineering specifications, electrical specifications and surge protection specifications. 5.1 Engineering Specifications of the PDU This describes the engineering specifications of the PDU in terms of the weight, dimensions, and installation modes.
Table 1 Engineering specifications of the DCDU-03 Item Weight Dimensions (width x height x depth) Installation mode Specification 2.2 kg 483 mm 133 mm 140 mm Remarks -
In a 19-inch rack The PDU Model TAB-DC is installed in a space 19-inch space; the space for the two mounting ears is included into the board. The panel of the PDU occupies 3 unit racks.
5.2 Electrical Specifications of the PDU The electrical specifications of the PDU consists of the DC input characteristics and DC output characteristics.
Table 2 Electrical specifications of the DPU Item DC Sub-Item Rated input voltage -48 V DC
HUAWEI Confidential
Specification
2012-04-24
Item input
Sub-Item
Specification
Remarks -
Input voltage range -38.4 V DC to -57 V DC Maximum input current 250 A -48 V DC -38.4 V DC to -57 V DC 10 A Over current protection and short-circuiting protection enabled for the Bank A outputs
DC output
Rated output voltage Output voltage range Output MCB configurations Output protection
5.3 Surge Protection Specifications of the PDU The PDU provides surge protection for the DC input power. Table 3 Surge protection specifications of the DCDU-03 Item Surge protection class Specification Protection requirement (8/20 s): 18 KA Maximum leakage current: <0.3 mA Maximum continuous operating current: 15A Maximum attenuation (typical): -55dB@100MHz Weight: 100gr Dimensions (w,d,h): 79mm x 25mm x 93mm
2012-04-24
HUAWEI Confidential
Page10, Total10