Test Summary
Valve: Trial Balikpapan Test: 4/13/2012 9:17:24 AM Error = 0.05 % Ave. Sample Time = 0.90 sec Offset = 0.02 % Max speed up not computed Max speed down not computed Lag = 15.84 sec FAIL Cycles/Min = 0.00 Overshoot = 1.04 T86 = 3.04 sec FAIL Friction = 0.12 psi Friction% = 1.01 % Friction(Position) not computed Spring Range Low = 8.59 psi Spring Range High= 20.59 psi
FAIL
Possible Causes of Exceptions Possible bad positioner tuning Possible air supply problem Possible air leak Possible packing damage/loss Possible stem wear Possible process condition change
Trend
Valve: Trial Balikpapan Test: 4/13/2012 9:17:24 AM
Step Response
Valve: Trial Balikpapan Test: 4/13/2012 9:17:24 AM Overshoot = 1.04 T86 = 3.04 sec
Friction
Valve: Trial Balikpapan Test: 4/13/2012 9:17:24 AM Friction = 0.12 psi Friction% = 1.01 % Friction(from Position) = 0.00 % Spring Range Low = 8.59 psi Spring Range Low = 20.59 psi