Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Battery Sizing Sheet, As Per Ieee STD 485: Note

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

BATTERY SIZING SHEET, AS PER IEEE STD 485

Basic Data Lowest Electrolytic Temperature End cell voltage during Equlisation Charging Minimum System voltage Maximum System voltage Minimum end cell Voltage 25 2.25 44.4 52.8
0

C V V V

minimum cell voltage=minimum battery voltage/no. of cells Number of cell per battery bank 23.46667 maximum system voltage/cell voltage required for Number of cell per battery bank selected 24 charging BATTERY SIZING CALCULATION 1 2 3 5 6 7 4 Time to end of Change in Cap at T min rate K Reqd sec size 36 = Period Load Duration of Period section (T) load Factor(Kt) (Nos) (amps) (mins) Rated Amp hour (mins) (hrs) (amps) Section 1 - First Period only 1 7.8 7.8 1 600 10 10.9 85.02 Sec 1 Total 85.02 The duty cycle of the battery tells us that it supplies only a load a continuos load of mentioned amplitude during its entire cycle of operation. 1.85 V Uncorrected size in Ah 85.02 Ageing factor 1.1 Design Margin 1 Tempertature Correction Factor 1.012 Hence Required Capacity 94.64426 Ah Selected Size 200 Ah Note : The temperature correction factor is provided either provided by the manufacturer or it is selected from the table provided in IEEE-485 BATTERY CHARGER SIZING CALCULATION FLOAT CHARGER Total continuos load 7.8 A Trickle current 0.4 A Load on Charger 8.2 A Hence Charger Capacity selected 20 A BOOST CHARGER 30 A 40 A

Capacity of Boost Charger Hence Charger Capacity selected

0.15C10 rating of the battery