Battery Sizing Sheet, As Per Ieee STD 485: Note
Battery Sizing Sheet, As Per Ieee STD 485: Note
Battery Sizing Sheet, As Per Ieee STD 485: Note
Basic Data Lowest Electrolytic Temperature End cell voltage during Equlisation Charging Minimum System voltage Maximum System voltage Minimum end cell Voltage 25 2.25 44.4 52.8
0
C V V V
minimum cell voltage=minimum battery voltage/no. of cells Number of cell per battery bank 23.46667 maximum system voltage/cell voltage required for Number of cell per battery bank selected 24 charging BATTERY SIZING CALCULATION 1 2 3 5 6 7 4 Time to end of Change in Cap at T min rate K Reqd sec size 36 = Period Load Duration of Period section (T) load Factor(Kt) (Nos) (amps) (mins) Rated Amp hour (mins) (hrs) (amps) Section 1 - First Period only 1 7.8 7.8 1 600 10 10.9 85.02 Sec 1 Total 85.02 The duty cycle of the battery tells us that it supplies only a load a continuos load of mentioned amplitude during its entire cycle of operation. 1.85 V Uncorrected size in Ah 85.02 Ageing factor 1.1 Design Margin 1 Tempertature Correction Factor 1.012 Hence Required Capacity 94.64426 Ah Selected Size 200 Ah Note : The temperature correction factor is provided either provided by the manufacturer or it is selected from the table provided in IEEE-485 BATTERY CHARGER SIZING CALCULATION FLOAT CHARGER Total continuos load 7.8 A Trickle current 0.4 A Load on Charger 8.2 A Hence Charger Capacity selected 20 A BOOST CHARGER 30 A 40 A