SLC Wiring Manual
SLC Wiring Manual
SLC Wiring Manual
SLC
Wiring Manual
ECN 11-788
P1
A fire alarm system will not operate without any electrical power. If AC power fails, the system will operate from standby batteries only for a specified time and only if the batteries have been properly maintained and replaced regularly. Equipment used in the system may not be technically compatible with the control panel. It is essential to use only equipment listed for service with your control panel. Telephone lines needed to transmit alarm signals from a premise to a central monitoring station may be out of service or temporarily disabled. For added protection against telephone line failure, backup radio transmission systems are recommended. The most common cause of fire alarm malfunction is inadequate maintenance. To keep the entire fire alarm system in excellent working order, ongoing maintenance is required per the manufacturer's recommendations, and UL and NFPA standards. At a minimum, the requirements of NFPA 72 shall be followed. Environments with large amounts of dust, dirt or high air velocity require more frequent maintenance. A maintenance agreement should be arranged through the local manufacturer's representative. Maintenance should be scheduled monthly or as required by National and/or local fire codes and should be performed by authorized professional fire alarm installers only. Adequate written records of all inspections should be kept.
Limit-C1-2-2007
The amount of smoke present may be insufficient to alarm smoke detectors. Smoke detectors are designed to alarm at various levels of smoke density. If such density levels are not created by a developing fire at the location of detectors, the detectors will not go into alarm. Smoke detectors, even when working properly, have sensing limitations. Detectors that have photoelectronic sensing chambers tend to detect smoldering fires better than flaming fires, which have little visible smoke. Detectors that have ionizing-type sensing chambers tend to detect fast-flaming fires better than smoldering fires. Because fires develop in different ways and are often unpredictable in their growth, neither type of detector is necessarily best and a given type of detector may not provide adequate warning of a fire. Smoke detectors cannot be expected to provide adequate warning of fires caused by arson, children playing with matches (especially in bedrooms), smoking in bed, and violent explosions (caused by escaping gas, improper storage of flammable materials, etc.).
Installation Precautions
Adherence to the following will aid in problem-free installation with long-term reliability:
WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all sources of power before servicing. Control unit and associated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until manuals are read and understood. CAUTION - System Re-acceptance Test after Software Changes: To ensure proper system operation, this product must be tested in accordance with NFPA 72 after any programming operation or change in site-specific software. Reacceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring. All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified. This system meets NFPA requirements for operation at 0-49 C/32-120 F and at a relative humidity 93% 2% RH (noncondensing) at 32C 2C (90F 3F). However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15-27 C/60-80 F. Verify that wire sizes are adequate for all initiating and indicating device loops. Most devices cannot tolerate more than a 10% I.R. drop from the specified device voltage. Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to lightning induced transients. Although no system is completely immune from lightning transients and interference, proper grounding will reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes. Consult with the Technical Services Department if any problems are anticipated or encountered. Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits. Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer, or printed circuit board location. Do not tighten screw terminals more than 9 in-lbs. Overtightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal. This system contains static-sensitive components. Always ground yourself with a proper wrist strap before handling any circuits so that static charges are removed from the body. Use static suppressive packaging to protect electronic assemblies removed from the unit. Follow the instructions in the installation, operating, and programming manuals. These instructions must be followed to avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation.
Precau-D1-9-2005
FCC Warning
WARNING: This equipment generates, uses, and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause interference to radio communications. It has been tested and found to comply with the limits for class A computing devices pursuant to Subpart B of Part 15 of FCC Rules, which is designed to provide reasonable protection against such interference when devices are operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interference, in which case the user will be required to correct the interference at his or her own expense. Canadian Requirements This digital apparatus does not exceed the Class A limits for radiation noise emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications. Le present appareil numerique n'emet pas de bruits radioelectriques depassant les limites applicables aux appareils numeriques de la classe A prescrites dans le Reglement sur le brouillage radioelectrique edicte par le ministere des Communications du Canada.
LiteSpeed is a trademark; and FireLite Alarms is a registered trademark of Honeywell International Inc. Microsoft and Windows are registered trademarks of the Microsoft Corporation. 2011 by Honeywell International Inc. All rights reserved. Unauthorized use of this document is strictly prohibited.
Software Downloads
In order to supply the latest features and functionality in fire alarm and life safety technology to our customers, we make frequent upgrades to the embedded software in our products. To ensure that you are installing and programming the latest features, we strongly recommend that you download the most current version of software for each product prior to commissioning any system. Contact Technical Support with any questions about software and the appropriate version for a specific application.
Documentation Feedback
Your feedback helps us keep our documentation up-to-date and accurate. If you have any comments or suggestions about our online Help or printed manuals, you can email us. Please include the following information: Product name and version number (if applicable) Printed manual or online Help Topic Title (for online Help) Page number (for printed manual) Brief description of content you think should be improved or corrected Your suggestion for how to correct/improve documentation Send email messages to: FireSystems.TechPubs@honeywell.com Please note this email address is for documentation feedback only. If you have any technical issues, please contact Technical Services.
Table of Contents
Section 1: Introduction............................................................................................................. 8
1.1: Scope..............................................................................................................................................................8 1.1.1: Reference Documentation ...................................................................................................................9 1.2: Overview......................................................................................................................................................10 1.3: Polling Protocols .........................................................................................................................................10 1.3.1: Available Protocols............................................................................................................................10 1.3.2: Protocol Use ......................................................................................................................................10 1.4: Devices ........................................................................................................................................................11 1.4.1: Isolator Module..................................................................................................................................11 1.4.2: Monitor Modules ...............................................................................................................................11 1.4.3: Control Modules ................................................................................................................................11 1.4.4: Relay Modules...................................................................................................................................11 1.4.5: Multiple Input/Output Modules.........................................................................................................11 1.4.6: Intelligent Detectors ..........................................................................................................................11 1.4.7: Manual Pull Station ...........................................................................................................................12 1.4.8: 300 Series Addressable Devices........................................................................................................12 1.5: SLC Capacity...............................................................................................................................................12 1.6: SLC Performance.........................................................................................................................................13 1.7: Surge Suppression........................................................................................................................................13 1.8: LED Operation.............................................................................................................................................13
Table of Contents
5.2: Installation....................................................................................................................................................31 5.2.1: Setting an SLC address for a Single Point Module ...........................................................................32 5.2.2: Setting an SLC address for a Multi-Point Module ............................................................................33 5.3: MMF-300 Wiring Diagrams ........................................................................................................................34 5.3.1: Wiring a NFPA Style B IDC with an MMF-300...............................................................................34 5.3.2: Wiring a NFPA Style D IDC with an MMF-300 ..............................................................................35 5.3.3: MMF-300 Wiring for Emergency Alarm System Applications ........................................................36 5.4: MMF-300-10 Wiring Diagrams...................................................................................................................37 5.4.1: Wiring a NFPA Style B IDC with an MMF-300-10 .........................................................................37 5.4.2: Wiring a NFPA Style D IDC with an MMF-300-10 .........................................................................38 5.5: MDF-300 Wiring Diagrams.........................................................................................................................39 5.5.1: Wiring a NFPA Style B IDC with an MDF-300 ...............................................................................39 5.6: MMF-302 Wiring Diagrams ........................................................................................................................40 5.6.1: Wiring a NFPA Style B IDC with an MMF-302...............................................................................40 5.6.2: Wiring a NFPA Style D IDC with an MMF-302 ..............................................................................41 5.7: MMF-302-6 Wiring Diagrams.....................................................................................................................42 5.7.1: Wiring a NFPA Style B IDC with an MMF-302-6 ...........................................................................42 5.7.2: Wiring a NFPA Style D IDC with an MMF-302-6 ...........................................................................43
Table of Contents
Section 1: Introduction
1.1 Scope
This document describes the operation, installation and wiring of various Signaling Line Circuit (SLC) devices when used with the Fire-Lite MS-9200/MS-9200E, MS-9600/MS-9600E, MS9600LS/MS-9600LSC/MS-9600LSE, MS-9600UDLS/MS-9600UDLSE, MS-9200UD/MS9200UDE, MS-9200UDLS/MS-9200UDLSE/MS-9200UDLSC, and MS-9050UD/MS9050UDC/MS-9050UDE control panels. It also provides basic information that applies to FireLite SLC loops in general, such as the branch resistance measurements.
NOTE: Any reference in this manual to the MS-9200, MS-9200UD, MS-9200UDLS, MS-9600, MS-9600LS, MS-9600UDLS, or MS-9050UD includes the MS-9200E, MS-9200UDE, MS-9200UDLSE, MS-9200UDLSC, MS-9600E, MS-9600LSE, MS-9600LSC, MS-9600UDLSE, MS-9050UDC, or MS-9050UDE respectively unless otherwise specified.
Additional information about the specific control panel and the modules and detectors referenced in this document can be found in the respective installation manual as listed in Table 1.1, Reference Documentation, on page 10. Currently, there are two styles of modules available, legacy version and newer version. The obvious difference between the two styles is the orientation of the rotary dials. Refer to the diagram below for an example of each.
NOTE: Only the MMF-300, MMF-302, CRF-300, CMF-300, and MDF-300 modules are available as newer type modules. Both the legacy and newer versions share the same part numbers. The newer version modules will be phased in, replacing the legacy version. This manual contains information and wiring diagrams for the newer version of the modules. Refer to Terminal Conversion Charts for New & Legacy Devices on page 67 for additional information.
Scope
Introduction
Currently, there are two styles of detector bases available, legacy version and newer version. The obvious difference between the two styles is the orientation of the screw terminals. Refer to Section 9 and Appendix D for an illustration of each.
NOTE: Only the B501 Detector Base, B210LP Detector Base (replacement base for B350LP), B224RB Relay Base, and B224BI Isolator Base are available as newer type bases. Both the legacy and newer versions share the same part numbers. The newer version bases will be phased in, replacing the legacy version. This manual contains information and wiring diagrams for the newer version of the bases. Refer to Intelligent Detector Base Layouts for Legacy Devices on page 71 for additional information.
Introduction
For information on... BEAM355(S) Addressable Beam Detector B210LP Plug-in Detector Base B501 Detector Base B501BH Sounder Detector Base B501BH-2 Sounder Detector Base B501BHT Temporal Sounder Detector Base B501BHT-2 Temporal Sounder Detector Base B200SR Sounder Detector Base B224RB Relay Detector Base B224BI Isolator Detector Base Refer to... Installation Instructions Installation Instructions Installation Instructions Installation Instructions Installation Instructions Installation Instructions Installation Instructions Installation Instructions Installation Instructions Installation Instructions
Overview
Part Number I56-2425 I56-3739 I56-0357 / I56-3738 I56-0491 I56-2813 I56-1367 I56-2819 I56-3387 I56-2815 / I56-3737 I56-0725 / I56-3736
1.2 Overview
Communication between the control panel and intelligent addressable monitor and control devices takes place through a Signaling Line Circuit (SLC), which can be wired to meet the requirements of NFPA Style 4, Style 6, or Style 7. At least one secondary surge protector must be used with each SLC wiring pair whenever SLC wiring runs outside the building. For detailed information refer to Surge Suppression on page 64.
NOTE: FACPs with more than one SLC loop must be programmed for only LiteSpeed or CLIP mode of operation. Communication protocols cannot be split between SLC loops.
When switching between polling protocols, the loop circuit must be powered down for at least 30 seconds to reset the devices.
10
Devices
Introduction
1.4 Devices
1.4.1 Isolator Module
The I300 Isolator Module permits a zone of detectors and modules to be fault isolated from the remainder of the SLC loop, allowing critical components to function in the event of a circuit fault. Isolator modules are required to meet the requirements of an NFPA Style 7 circuit.
Introduction
SLC Capacity
CP355 - An addressable ionization smoke detector which measures the level of combustion products in its chamber using the ionization principle. D350P - An addressable photoelectric duct detector. The D350RP includes an alarm relay. Air velocity rating is 500 to 4,000 feet per minute. D350PL -An addressable low flow photoelectric duct detector (D350PLA for Canada). The D350RPL includes an alarm relay (D350RPLA for Canada). Low Flow refers to the air velocity rating of 100 to 4,000 feet per minute (0.5 to 20.32 m/sec). D355PL - An addressable non-relay photoelectric low flow smoke detector. Low Flow refers to the air velocity rating of 100 to 4,000 feet per minute (0.5 to 20.32 m/sec). H3501 - An addressable detector using a thermistor sensing circuit for fast response. H350R incorporates a thermal rate of rise of 15F (9.4C)/minute. H3551 - An addressable 135 fixed temperature heat detector using a thermistor sensing circuit for fast response. H355R incorporates a thermal rate of rise of 15 F (9.4 C)/minute. H355HT1 - An addressable 190 fixed temperature heat detector using a thermistor sensing circuit for fast response. SD350 - An addressable photoelectric smoke detector which provides smoke sensing utilizing optical sense technology. The SD350T includes a 135 F fixed thermal sensor. SD355 - An addressable photoelectric smoke detector which provides smoke sensing utilizing optical sense technology. The SD355T includes a 135 F fixed thermal sensor. The SD355R is a low profile, intelligent, photoelectric sensor that is remote test capable. BEAM355 - An addressable long range projected beam smoke detector designed to provide open area protection. The BEAM355S has an integral sensitivity test feature that consists of a test filter attached to a servomotor inside the detector optics. DNR(W) - Innovair Flex, intelligent, non-relay, low flow, photoelectric duct detector housing. This requires the SD355R photoelectric smoke detector. Accomodates the installation of the CRF300 relay module. The DNRW is a watertight housing.
SLC Performance
Introduction
Wiring style requirements are determined by national and local codes. Consult with the Authority Having Jurisdiction before wiring the SLC. The table below (derived from NFPA 72-1999) lists the trouble conditions that result when a fault exists on an SLC.
Type of Fault Single Open Single Ground Short Short and open Short and ground Open and ground Communications loss Style 4 Trouble Alarm, Trouble (ground) Trouble Trouble Trouble Trouble Trouble Style 6 Alarm, Trouble Alarm, Trouble (ground) Trouble Trouble Trouble Alarm, Trouble Trouble Style 7 Alarm, Trouble Alarm, Trouble (ground) Alarm, Trouble Trouble Alarm, Trouble Alarm, Trouble Trouble
Trouble - The control panel will indicate a trouble condition for this type of fault. Alarm - The control panel must be able to process an alarm input signal in the presence of this type of fault.
13
MS-9200 = 1,000 feet (305 m) Untwisted, unshielded wire, inside conduit or not in conduit MS-9600, MS-9600LS(C) & MS-9600UDLS = 3,000 feet (914 m) MS-9200UD & MS-9200UDLS = 3,000 feet (914 m) MS-9050UD = 3,000 feet (914 m)
12 to 18 AWG
14
Wiring Requirements
Short Point
Branch
SLC-meas1.wmf
SLC Out
SLC-meas2.wmf
15
Wiring Requirements
B+ B A A+
16
Wiring Requirements
CAUTION: DO NOT LET THE SHIELD DRAIN WIRE OR THE SHIELD FOIL TOUCH THE SYSTEM CABINET OR BE CONNECTED TO EARTH GROUND AT ANY POINT.
MS-9600 MS-9600LS MS-9600UDLS MS-9200UD MS-9200UDLS MS-9050UD Shield Drain Wire Cabinet Shield Foil
MS-9200
Conduit
17
SLC-shieldterm.wmf
Wiring Requirements
2.4.1 MS-9200
TB4 provides three types of 24 VDC power; Unregulated, Nonresettable and Resettable. TB6 provides connections for the SLC wiring. 198 addresses are available per loop (99 detectors and 99 modules).
Unregulated Power Nonresettable Power Resettable Power
SHIELD
TB4
TB6
SLC Return
SLC Out
TB3
TB8
18
SLC-9600tb.wmf
Wiring Requirements
TB1
TB10
TB1
TB10
19
Wiring Requirements
2.4.5 MS-9050UD
24 VDC power may be supplied by a remote power supply such as the Fire-Lite FCPS-24FS6/8. TB2 provides connections for the SLC wiring. 50 addresses are available (any combination of detectors and modules).
20
Addressable Module
T-tapped Circuits
21
SLC Out
B+ B A A+
22
SLC-style6.cdrwmf
A Fault Isolator Module on both sides of a device, or the combination of Isolator Base and Isolator Module is required to comply with NFPA Style 7 requirements.
CAUTION: MAXIMUM ADRESSABLE DEVICES If relay or sounder bases are not used, a maximum of 25 addressable devices can be connected between Isolator Modules and/or Bases. When relay or sounder bases are used, the maximum number of addressable devices that can be connected between Isolators is reduced to seven. Isolator modules will not function properly when these limits are exceeded. When more than 100 Isolator Modules are connected to an SLC loop, the address capacity of the loop is reduced by two (2) addresses for every isolator device in excess of 100.
B B+
24
SLC-style4iso.wmf
Isolator Module
Isolator Module
Section C
Section A
Isolator Module
Additional isolator module required when first device in the section is more than 20 feet from the control panel.
Isolator Module
Isolator Module
Isolator Module
SLC Out
SLC Return
Control Panel
SLC-style6iso.wmf
Isolator Module
Isolator Module
Isolator Module
Isolator Module
Isolator Module
Isolator Module
Isolator Module
Control Panel
26
SLC-style7iiso.wmf
FMMtpH.wmf
SLC SLC+
Rotary Switches
27
Monitor Modules
Descriptions
Style Y or Style Z Select Remove shunt for Style Z circuits Disable Address Place shunt in: Disable 1 position to disable highest module address Disable 2 position to disable highest two module addresses SLC Address Set rotary switches to base (first) address of modules
28
mmf-300-10.wmf
Descriptions
Monitor Modules
FZMtpH.wmf
24 VDC 24 VDC + IDC Return IDC Return + IDC Out + IDC Out -
SLC SLC+
Rotary Switches
29
Monitor Modules
Descriptions
+ +
T1 T0
T2
+ + + +
T3
+ + + +
T4
T6
T5
5 4 3 2 6 7 8 9 10 11 12 13 1 0 15 14
BASE ADDRESS
J1
SW1
5 4 3 2
BASE ADDRESS +4
10
BASE ADDRESS +0
BASE ADDRESS +1
BASE ADDRESS +2
BASE ADDRESS +3
BASE ADDRESS +5
6 7 8 9
Style Y or Style Z Select Remove shunt for Style Z circuits Disable Address Place shunt in: Disable 1 position to disable highest module address Disable 2 position to disable highest two module addresses SLC Address Set rotary switches to base (first) address of modules
30
Installation
Monitor Modules
Base Address
7L+ 6L
5.2 Installation
When installing any of these modules DO NOT mix the following services that the IDC provides: Fire alarm service Automatic and manual waterflow alarm service with normally open contact devices Sprinkler supervision with normally open contact devices
fmmtph.wmf
31
Monitor Modules
Installation
To set an SLC address, use a screwdriver to adjust the rotary switches on the module to the desired address. The module below is set at 35. When finished, mark the address on the module face in the place provided.
5 4 3 2
Modules with Rotary Switches in horizontal position Modules with Rotary Switches in vertical position
Breakaway Tab - Modules come with a raised breakaway tab on the TENS rotary switch. This tab must be removed when the module is on an FACP that uses more than 99 addresses.
Dual monitor modules: On dual monitor modules, only even numbers appear on the ONES rotary switch. The module takes both the selected address and the next-higher address.
32
SLC-setadd.cdr,SLC-setaddtpH.wmf, SLCbrktabs.wmf
Installation
Monitor Modules
To set an SLC address, use a common screwdriver to adjust the rotary switches on the module to the desired address. The module below is set at 28.
5 4 3 2 6 7 8 9 10 11 12 13 10 15 14
TENS
Plastic Stop
Rotary Switches
ONES
multroty.wmf
5 4 3 2 10 6 7 8 9
33
Monitor Modules
IDC
34
SLC-idcB1tpH.wmf
Monitor Modules
Manual pull station To Next IDC or Supervision Device SLC Heat detector MMF-300
IDC
SLC-idcD1tpH.wmf
35
Monitor Modules
SLC
+ -
IDC
SLC-emer.wmf
MMF-300 Module programmed for Tornado, Hazard, or Medical operation. Refer to the control panel installation manual.
36
Monitor Modules
24 VDC Power Filtered, Regulated, Resettable 47K ELR (supplied with module) Heat Detector
SLC
MMF-300-10
IDC Out
SLC-idcB4.wmf
37
Monitor Modules
IDC Return
IDC Out
SLC
MMF-300-10
SLC-idcD3.cdwmf
38
Monitor Modules
SLC-idcB3fdm1tph.wmf
T11 T10 T9 T8 T7 T6
T1 T2 T3 T4 T5
39
Monitor Modules
24 VDC Resettable power. 90 mA External 24 volt supply required 3.9K ELR (supplied with module)
SLC
MMF-302
40
SLC-idcB2tpH.wmf
IDC
Monitor Modules
IDC
SLC-idcD2tpH.wmf
41
Monitor Modules
42
Monitor Modules
+ + +
SLC
MMF-302-6
SLC-idcD4.wmf
+ +
T1 T0
T2
+ + + +
T3
+ + + +
T4
43
6.1 Description
The CMF-300 and CMF-300-6 modules are addressable modules that can be used for monitoring and switching 24 VDC Notification Appliance Circuit (NAC) power for NFPA Style Y (Class B) and NFPA Style Z (Class A) circuits. Ratings for the relay contacts on the module are:
Load Description Resistive Resistive Resistive Resistive Inductive (L/R = 5ms) Inductive (L/R = 2ms) Inductive (PF = 0.35) Application Non-Coded Coded Non-Coded Non-Coded Coded Coded Non-Coded Maximum Voltage 30 VDC 30 VDC 110 VDC 125 VAC (CMF-300) 70.7 VAC (CMF-300-6) 30 VDC 30 VDC 125 VAC (CMF-300) 70.7 VAC (CMF-300-6) Current Rating 3.0 A 2.0 A 0.9 A 0.9 A 0.5 A 1.0 A 0.5 A
NOTE: For more information on module specifications, refer to the Installation Instructions provided with these devices.
24 VDC Nonresettable Power () 24 VDC Nonresettable Power (+) Style Z NAC (+) Style Z NAC () Style Y/Z NAC () Style Y/Z NAC (+) NOTE: Module polarities are shown in alarm condition.
FCMFZMtph.wmf
Control Modules
45
SLC-nacY.wmf
Control Modules
CMF-300-6 Installation
See Power Considerations on page 61 for information on monitoring 24 VDC power. Each module can control 2 amps of resistive load (on electronic devices) or 1 amp of inductive load (on mechanical bells and horns). 24 VDC power must be provided from a UL listed power supply for fire protection use. A power supervision relay is required only on the last module of the power run. Do not T-tap or branch a Style Z circuit. Do not loop wiring under the screw terminals of any notification appliance. To maintain supervision, break the wire run at each device.
NOTE: A power supervision relay is required only on the last module of the power. 24 VDC Nonresettable power 24 VDC notification appliances CMF-300 SLC
SLC-nacZtpH.wmf
CMF-300-6 Installation
Control Modules
In Style Z operation alternate module points are paired together, resulting in a total of three module points. For example, if the base address is set to 28, then 30 and 32 will be automatically assigned to the remaining module points and 29, 31 and 33 are available to be used for other modules on the SLC. DO NOT set the lowest address above 154 (45 for the MS-9050UD, 94 for the MS-9200, MS9200UD, and MS-9200UDLS), as the other module points will be assigned to nonexistent addresses.
NOTE: The MS-9050UD can support addresses 01 - 50. The MS-9200, MS-9200UD, and MS9200UDLS can support module addresses of 01 - 99. The MS-9600, MS-9600LS, MS-9600LSC, and MS-9600UDLS can support module addresses 01 - 159.
To set an SLC address, use a common screwdriver to adjust the rotary switches on the module to the desired address. See Figure 6.4 on page 48.
NOTE: For use with the MS-9600, MS-9600LS, MS-9600LSC, and MS-9600UDLS, remove the stop on the upper rotary switch.
J1
SLC-disable1.wmf
47
Control Modules
CMF-300-6 Installation
#1
#2
#3
#4
#5
#6
Disable Address Place shunt onto required pins. Select Style Y (Class B) or Style Z (Class A) Remove shunt for Style Z (Class A).
SLC Address Set rotary switches to address required. Short Circuit Protection - Remove shunt from the corresponding pins to enable. Shunt #1 for first address, #2 for second address, etc.
48
CMF-300-6.wmf
Status Indicators Green LEDs are controlled by FACP to indicate status of each module address.
Control Modules
See Power Considerations on page 61 for information on monitoring 24 VDC power. Each module can control 2 amps of resistive load (on electronic devices) or 1 amp of inductive load (on mechanical bells and horns). 24 VDC power must be provided from a UL listed power supply for fire protection use. A power supervision relay is required only on the last module of the power run. Do not T-tap or branch a Style Y circuit. Terminate the circuit across the last device using an End-of-Line Resistor 47K, 1/2-watt, P/N SSD A2143-00 (ELR-47K in Canada). Do not loop wiring under the screw terminals of any notification appliance. To maintain supervision, break the wire run at each device.
Power Supervision Relay (EOLR-1) 24 VDC nonresettable power
CMF-300-6
T0 +0 + +
+
T1
+1
T2
+2
T3
+3
T4
+4
+5
T10
T11
T12
T13
T14
T15 T16
SLC-nacY2.wmf
T5
49
Control Modules
See Power Considerations on page 61 for information on monitoring 24 VDC power. Each module can control 2 amps of resistive load (on electronic devices) or 1 amp of inductive load (on mechanical bells and horns). 24 VDC power must be provided from a UL listed power supply for fire protection use. A power supervision relay is required only on the last module of the power run. Do not T-tap or branch a Style Z circuit. Do not loop wiring under the screw terminals of any notification appliance. To maintain supervision, break the wire run at each device.
CMF-300-6
50
SLC-nacZ3.cwmf
NOTE: For more information on the module specifications refer to the Installation Instructions provided with these devices.
C NC NO C NC
NO
SLC-frmCtpH.wmf
Relay Modules
T102
+ +
5 4 3 2
6 7 8 9 10 11 12 13 1 0 1514
BASE ADDRESS
ADDRESS DISABLE
J1
SW1
5 4 3 2 1 0 6 7 8 9
Status Indicators Green LEDs are controlled by FACP to indicate status of each module address. SLC Address Set rotary switches to address required.
52
Relay Modules
J1
Shunt Storage Location
Relay Connections
CRF-300-6
+ +
SLC-fmC1.wmf
SLC-disable2.wmf
+
53
NOTE: For more information on the module specifications refer to the Installation Instructions provided with these devices.
54
NC C NO NC C NO
Normally Closed Common Normally Open Normally Closed Common Normally Open
fdrm-1.wmf
55
The B501 and B210LP bases are standard plug-in detector bases. The B501BH, B501BHT, B501BH-2, B501BHT-2, and B200SR Sounder Detector Bases include a horn that will sound when the sensors visible LEDs are latched on for approximately 10 seconds. On the MS-9200 Control Panel, the sounder will activate when the sensors visible LEDs are latched on for approximately 10 seconds (Alarm Verification does not delay sounder). If the MS-9600, MS-9600LS, MS-9600UDLS, MS-9200UD, MS-9200UDLS, or MS-9050UD Control Panel is set with Alarm Verification ON, the sounder will activate at the end of the verification cycle, providing an alarm is verified, approximately 10 seconds after the sensors LEDs are latched on. If Alarm Verification is OFF, the sounder will activate when the sensors visible LEDs are latched on for approximately 10 seconds. The B224RB Relay Detector Base includes Form-C latching relay contacts for the control of an auxiliary function. The relay operates 12 seconds (nominally) after activation of the sensor head remote annunciator output. The B224BI Isolator Detector Base prevents an entire communications loop from being disabled when a short circuit occurs.
NOTE: For more information, refer to the Installation Instructions provided with these devices.
56
NOTE: The B210LP base wiring is identical to the B501. B501 is the flangeless model.
SLC-B5012wire.wmf
57
SLC In
Conduit
slc-224bi2wire.wmf
+-
SLC
+-
58
slc-b224rb2wire.wmf
+-
SLC
+-
+ -
NOTE: For more detailed wiring on the sounder base, refer to the devices installation instructions.
slc-b200srwire.wmf
59
10.2 Installation
10.2.1 Setting an SLC address
Each unit is factory preset with an address of 00. To set an SLC address refer to Setting an SLC address for a Single Point Module on page 32.
+
SLC
US PAT 4440991
SLC-bg12lx2.wmf
60
For NACs:
(Vms - Vom) Rmax = (Nb)(Ib)
Where: Rmax = maximum resistance of the 24 VDC wires Vms = minimum supply voltage Vom = minimum operating voltage of the detector or end-of-line relay, whichever is greater, in volts N = total number of detectors on the 24 VDC supply circuit Is = detector current in standby Na = number of detectors on the 24 VDC power circuit which must function at the same time in alarm Ia = detector current in alarm Ir = end-of-line relay current Nb = number of Notification Appliance Devices Ib = Notification Appliance current when activated
NOTE: This simplified equation assumes that the devices are at the end of a long wire run.
The minimum supply voltages produced by FireLite power supplies are listed below:
FACP MS-9200 MS-9600 MS-9200UD/MS-9200UDLS MS-9050UD Vms 16.0 16.0 19.05 18.75 Power Supply FCPS-24F FCPS-24FS6/FCPS-24FS8 Vms 19.1 19.1
61
Power Considerations
ELR 47K
Supervised NAC
62
SLC-psrtpH.cdr
Power Considerations
ELR 47K
Supervised NAC
MMF-300
SLC-psr-2addresstpH.wmf
63
There are three (3) primary surge protectors that are approved for use with the MS-9200, MS9200UD, MS-9200UDLS, MS-9600, MS-9600LS, MS-9600UDLS, and MS-9050UD. DTK-2LVLP-F (727) 812-5000 SLCP-30 Diversified Technology Group, Inc. 1720 Starkey Rd. Largo, FL 33771
PLP-42N Northern Technologies, Inc. 23123 E. Madison Ave. Liberty Lake, WA 99019 (800) 727-9119
NOTE: For detailed information, refer to the Installation Instructions supplied with the unit.
One primary surge protector must be used with each SLC wiring pair whenever SLC wiring runs outside the building. Install primary protection only as shown in this document. Refer to NEC Article 800 and local building code requirements.
Additional primary surge suppressors may be added as required by the NEC. Add these additional suppressors in series with the SLC wiring at the building entry/exit. Wiring connected to the surge suppressor output must remain within the building while wiring connected to the surge suppressor input may be routed outside the building as shown below.
Building #2 Building #1
P P = Primary S = Secondary
P FACP S
Surge Suppressor
B.2 Installation
Mounting of the surge suppressor must be inside the FACP enclosure or in a separate enclosure listed for fire protective signaling use. Locate on an available stud and secure with nut. Unit is connected in series with the SLC Loop to protect the Control Panel. Provide a common ground to eliminate the possibility of a differential in ground potentials.
64
SLC-ssbuild1.wmf
Installation
Surge Suppression
IN
2LVLP-F
PLP-42N Connections
PLP-42N
GRND
L4 L4
OUTPUT
INPUT
L3
L2
L1
L1
L2
L3
PLP-42N
NOTE: Use 12AWG (3.25mm2) to 18AWG (0.75mm2) wire with crimp-on connectors to connect the units ground terminal to equipment ground. Wire length must be minimized to provide best protection.
SLCP-30 Connections
2LCP-30
L1
SLC Loop
IN SLC Loop +
OUT
2LCP-30
IN
OUT
SLC-slcp1.wmf
SLC-plpn1.wmf
OUTPUT
INPUT
L3
L2
L1
L2
L3
GRND
L4
L4
SLC-lvlp1.wmf
65
Surge Suppression
Installation
B.2.2 Wiring Diagram for MS-9600, MS-9600LS, MS-9600UDLS, MS-9200UD, MS-9200UDLS, and MS-9050UD
DTK-2LVLP-F Connections
2LVLP-F
IN
OUT
2LVLP-F
PLP-42N Connections
PLP-42N
GRND
L4
L4
OUTPUT
INPUT
L2
L1
L1
L2
L3
L3
OUTPUT
INPUT
L3
L3
+
SLC Loop
NOTE: Use 12AWG (3.25mm2) to 18AWG (0.75mm2) wire with crimp-on connectors to connect the units ground terminal to equipment ground. Wire length must be minimized to provide best protection.
SLCP-30 Connections
2LCP-30
IN SLC Loop +
2LCP-30
IN
OUT
66
SLC-slcp4.wmf
SLC-plpn4.wmf
GRND
L4
L2
L1
L1
L2
L4
SLC-lvlp4.wmf
Legacy Module (V-Type) Legacy Module Terminal Number (V-Type) 1 2 3 4 5 6 7 8 9 N/A N/A
Terminal Function SLC SLC + Unused Normally Open (1) Normally Closed (1) Relay Common (1) Normally Open (2) Normally Closed (2) Relay Common (2) Unused Unused
67
SLC SLC +
Terminal Function SLC SLC + VDC VDC + Unused Solenoid B/A Solenoid B/A + Solenoid A + Solenoid A Unused Unused
68
MMF-300
C.3 MMF-300
Class A Supervision Class A Supervision+ Class A/B Supervision + Class A/B Supervision -
SLC SLC +
Class A Supervision Class A Supervision+ Class A/B Supervision + Class A/B Supervision -
SLC SLC +
Terminal Function SLC SLC + Unused Unused Unused Class A/B Supervision Class A/B Supervision + Class A Supervision + Class A Supervision Unused Unused
69
MDF-300
C.4 MDF-300
Address +1 (H) Address +1 (H) + Base Address (L) + Base Address (L) LOOP LOOP
9 8 7
6 5
5 4 3 2
TENS
6 7 8 910 11 12 13 1 0 1514 8
0
1 2
SLC SLC +
4
2
ONES
3
0
4
ADDRESS ADDRESS
Address +1 (H) Address +1 (H) + Base Address (L) + Base Address (L) -
SLC SLC +
Terminal Function SLC SLC + Unused Unused Unused Base Address (L) Base Address (L) + Address +1 (H) + Address +1 (H) Unused Unused
70
2(+)
1()
NOTE: The B350LP base wiring is identical to the B501, except there is no shield terminal.
71
SLC-B501wire.wmf
SLC In
Conduit
SLC-224BIwire.wmf
SLC
72
b224rb.wmf
SLC +
SLC -
Figure D.4 Wiring the Legacy B501BH(-2) and B501BHT(-2) Sounder Bases
slc-b501bhwiring.wmf
73
SD350/SD355
SD350A/SD355A
SD350T/SD355T H350/H355
SD350TA/SD355TA H350A/H355A
H350R/H355R H355HT
H350RA/H355RA H355HTA
Monitor and Zone Interface Modules MMF-300 MMF-300A Used for normally open contact alarm initiating devices, such as manual pull stations, four-wire smoke detectors, heat detectors, waterflow, and supervisory devices. Used to interface with two-wire smoke detectors in addition to normally open contacts. Two independent 2-wire Initiating Device Circuits (IDCs) at two separate, consecutive addresses. Wire supervised IDCs as NFPA Style B (Class B) or Style D (Class A) circuits. The modules come with a thermoplastic cover for mounting to a 4-inch (10.16 cm) square mounting box. Functionally similar to the MMF-300 Monitor Module, but offered in a smaller package for mounting directly in the electrical box of the device being monitored. (Class B input circuit only.) An addressable manual pull station with key-lock reset feature. The addressable module is housed within the pull station.
MMF-302 MDF-300
MMF-302A MDF-300A
MMF-301
MMF-301A
BG-12LX
CMF-300A
Control Module, NAC: Addressable Control Module used as Notification Appliance Circuits (NACs) to power and supervise compatible, UL-listed notification appliances. Wired supervised NACs as NFPA Style Y (Class B) or Style Z (Class A). The modules come with a thermoplastic cover for mounting to a 4-inch (10.16 cm) square mounting box.
74
Multi-input/output modules MMF-300-10 MMF-302-6 CDRM-300 CMF-300-6 CRF-300-6 MMF-300-10A MMF-302-6A CDRM-300A CMF-300-6A CRF-300-6A Supervises ten Class-B addressable Initiating Device Circuits (IDC) which monitor normally open contact initiating devices. Monitors six zones of conventional two-wire detectors. Dual Class B monitor / Form-C relay module. Similar in operation to the CMF-300, except it can activate six (6) Style Y (Class B) or three (3) Style Z (Class A) NACs. Similar in operation to the CRF-300, except it provides six (6) FormC relays.
75
Index
Numerics
24 VDC detectors 61 24 VDC NAC power 44 24 VDC power MS-9200, MS-9600 18 address setting 46 circuit board 48 installation 46 short circuit protection 47 Style selection 47 wiring 49 common ground 64 communication protocol 10 conduit, close nippled 26 connectors, crimp-on 65, 66 Control Modules 11 Overview 74 control panel 8 CP350 Detector 11 CP355 12 CP355 Detector 56 CRF-300 Relay Module 11, 51 wiring 51 CRF-300-6 Relay Module 11, 51 address disabling 53 address setting 53 circuit board 52 wiring 52, 53
A
AD350 Detector 11 AD355 Detector 11, 56 address capacity 23 addressable modules 11, 27 addressable devices 23 Addressable Modules (Overview) 74 Addressable Monitor Modules 27 Alarm Verification 56 analog intelligent devices 10 Authority Having Jurisdiction 13 auxiliary devices 11
B
B200SR Sounder Detector Base 56 B210LP 56 B224BI Isolator Detector Base 23, 56 B224RB Relay Detector Base 56 B350LP Detector Base 71 B501 Detector Base 56, 71 B501BH Sounder Detector Base 56 B501BH-2 Sounder Detector Base 56 B501BHT Temporal Sounder Detector Base 56 B501BHT-2 Temporal Sounder Detector Base 56 base 57, 58, 59 BEAM355 12 BEAM355S 12 BG-12LX 12, 60 building entry/exit 64
D
D350P Detector 12 D350RP Detector 12 D355PL detector 12 DC resistance 15, 16 detector bases 56 detector bases, wiring of 57 detectors 56 detector bases 74 listing 11, 74 devices addressable 23 auxiliary 11 maximum number between isolators 23 supervised 62 document sources 9 drain wire 17 dry-contact 11 DTK-2LVLP-F 64 Dual Monitor Module 31
C
CDRM-300 54 CDRM-300 Multiple Input/Output Module wiring 55 circuit fault 11 Classic Loop Interface Protocol 10 CLIP (Classic Loop Interface Protocol) 10 CLIP Mode 12 close nippled conduit 26 CMF-300 Control Module 11, 44, 45, 46 installation 44 wiring 45 CMF-300-6 Control Module 11, 44, 49, 50 address disabling 47
76
E
electrical interference 14 emergency signaling circuit 36 End-of-Line Resistor 45, 49
Index
FP
F
fault 13, 25 fault condition 23 Fault Isolator Module 23 FCPS-24F 61 Fire alarm service 31 foil 17 Form-C contacts 54 Form-C relay contacts 11, 51, 56 four-wire configuration 46, 50
G
ground terminal 65, 66
H
H350 Detector 12 H350R Detector 12 H355 Detector 12, 56 H355HT Detector 12 H355R Detector 12 Heat Detector 56
MMF-301 Mini Monitor Module 11, 31 MMF-302 Zone Interface Module 11, 29, 40, 41 wiring 40 MMF-302-6 Interface Module 11, 30, 42, 43 wiring 42 module circuits 27 modules addressable 11 control 11 isolator 11 monitor 11 relay 11 Monitor Modules 11, 27 Overview 74 Multicriteria Detector 56 multiple input/output module 54 Multi-Point Module 33
N
NAC 11 NAC power 44, 62 NAC wiring 44 NEC Article 800 64 NFPA Style 4 wiring of 21 with I300 24 NFPA Style 6 wiring of 22 with I300 25 NFPA Style 7 23 with isolator modules 26 NFPA Style B IDC wiring 34, 37, 39, 40, 42 NFPA Style D IDC wiring 35, 38, 41, 43 NFPA Style Y 44 wiring of 45, 49 NFPA Style Z 44 wiring of 46, 50 Nonresettable power 18 normally closed contacts 62 Notification Appliance Circuit 11
I
I300 Isolator Module 11, 23 Initiating Device Circuits 27, 34, 37, 39 integral relay 23 Ionization Detector 56 isolator base 23 isolator base, wiring of 58 Isolator Module 11, 25, 26 how it works 23 wiring of 23
K
key-lock reset 60
L
LEDs 56 LiteSpeed 10 local building code 64 loop resistance 15, 16 loops 16
O
older version and newer version modules 8, 9
M
MDF-300 Dual Monitor Module 11, 31, 39 wiring 39 metal conduit 17, 25 Mini Monitor Module 31 minimum resistance 61 MMF-300 Monitor Module 11, 27, 34, 35, 36 wiring 34 MMF-300-10 Monitor Module 11, 28, 37, 38 wiring 37
FireLite SLC Wiring Manual P/N 51309:P1 10/12/2011
P
performance 13 Photoelectric Detector 56 PLP-42N 64 Polling Protocols 10 power run 61, 62 power supervision relay 45, 46, 49, 50, 62 power supplies 61 proper gauge wire 61
77
RZ
Index
R
RA100Z 57 RA400Z 57 rate of rise 12 ratings, relay contact 44, 51, 54 relay base 23 wiring of 58 relay contact ratings 44, 51, 54 Relay Module 11 relays Form-C 11 Remote LED Annunciator 57 Resettable power 18 resistance 15, 16 rotary switches 32, 38, 39, 40, 41, 42, 43, 56
U
Unregulated power 18
V
verification cycle 56
W
Waterflow alarm service, automatic and manual 31 wire length 15, 16 wire size 14 wiring I300 23 MDF-300 39 MMF-300 34 MMF-300-10 37 MMF-302 40 MMF-302-6 42 NACs 44 wiring pair 64 wiring requirements 14 wiring style requirements 13
S
SD350 Detector 12 SD350T Detector 12 SD355 Detector 12, 56 SD355R Detector 12 SD355T Detector 12 sensing circuit, thermistor 12 short circuit 23 Signaling Line Circuit 10 Single Point Module 32 SLC address, setting of 32, 56 SLC connections 18 SLC terminal block 17 SLC wiring 34, 35, 36, 37, 38, 39, 40, 41, 42, 43 SLCP-30 64 Smoke Detectors 56 sounder base 23 sounder base, wiring of 59 Sprinkler supervision 31 supervised circuit 62 devices 62 supplying power 61 suppressors, surge 64 surge protector 10, 13, 64 switching 44
Z
Zone Interface Module 29
T
terminal blocks 18 termination of shield 17 Thermal Detector 56 thermistor sensing circuit 12 trouble conditions 13, 23 T-tapping 15, 21, 22, 25, 26 twisted-pair shielded wiring 14
78 FireLite SLC Wiring Manual P/N 51309:P1 10/12/2011
Warn-HL-08-2009.fm
79
World Headquarters 1 Firelite Place Northford, CT 06472-1653 USA 203-484-7161 fax 203-484-7118 www.firelite.com