Kidde AEGIS
Conventional
Fire Alarm-Suppression
Control Unit
Installation, Operation, and
Maintenance Manual
O FF
ICE OF
FOREWORD
Note: This Manual, P/N 06-236716-001, is to be used by qualified and factory-trained personnel,
knowledgeable of NFPA standards and any other applicable standards in effect.
This Manual is intended to provide guidance to qualified technical professionals for the installation,
operation and maintenance of the Kidde AEGIS Conventional Fire Alarm-Suppression Control Unit.
Only qualified persons experienced and trained in the installation of this type of equipment should install
and configure the Kidde AEGIS. They must be familiar and experienced with the wiring diagrams and
components, electrical installation, and familiar not only with NEC, relevant NFPA and local codes but also
trained and qualified by Kidde-Fenwal, Inc. Kidde-Fenwal, Inc. is a manufacturer of the components that
make up the Kidde AEGIS system, and may not have the opportunity to visit the sites where the product
is installed or intended to be installed. It is the responsibility of the professional installer (described above)
to properly install and configure the systems. Under no circumstances will Kidde-Fenwal be liable for
improper installation or configuration of the systems.
The technical data contained herein is provided for informational purposes only, and should not be used as
a substitute for professional judgment. Although, Kidde-Fenwal believes this information to be true and
correct, it is published and presented without any guarantee or warranty whatsoever. Kidde-Fenwal
disclaims any liability for any use of the data other than as set out in this manual, foreword included.
Any questions concerning the information presented in this manual should be addressed to:
Kidde-Fenwal, Inc.
400 Main Street
Ashland, MA 01721
Phone: (508) 881-2000
Toll Free: (800) 872-6527
Technical Support: (866) 287-2531
Fax: (508) 881-8920
P/N 06-236716-001
August 2007
Centigrade
LCD:
F:
Farenheit
LED:
A:
Ampere
MEA:
AC:
Alternating Current
NAC:
ADA:
N.C.:
Normally Closed
AH:
Ampere Hour
NEC:
AHJ:
NFPA:
ARC:
N.O.:
Normally Open
AWG:
NYC:
CSFM:
PCB:
DACT:
pF:
Pico-farads
DC:
Direct Current
P/N:
Part Number
DET:
Detector
PSU:
EOLD:
RAM:
EOLR:
SLC:
FM:
Factory Mutual
TB:
Terminal Block
ft.:
Feet
UL/ULI:
HSD:
V:
Volts
Hz:
Hertz (Frequency)
Vac:
Volts AC
in.:
Inch
Vdc:
Volts DC
IRI:
VRMS:
CAUTION
WARNING
August 2007
ii
P/N 06-236716-001
SAFETY SUMMARY
This entire manual must be read and understood before installation.
Installation PrecautionsAdherence to the following will aid in problem-free installation with longterm reliability:
Several different sources of power can be connected to this fire alarm control unit.
Disconnect all sources of power before servicing. Control unit and associated
equipment may be damaged by servicing while the unit is energized. Do not
attempt to install, service, or operate this control unit until this manual is read
and understood.
WARNING
System Re-acceptance Test after Re-Programming: To ensure proper system operation, this
system must be retested in accordance with NFPA 72 Chapter 10 after any
programming change. Re-acceptance testing is also required after any addition or
deletion of system components, and after any modification, repair or adjustment to
system hardware or wiring.
CAUTION All components, circuits and system operations known to be affected by a change must
be 100% tested. In addition, to ensure that other operations are not inadvertently
affected, at least 10% of initiating devices that are not directly affected by the change,
up to a maximum of 50 devices, must also be tested and proper system operation
verified.
This system meets FM and ANSI/UL 864 requirements for operation at 32 to 120F (0 to 49C) and at a
relative humidity of 93% (non-condensing) @ 90F (32.2C). However, the useful life of the systems
standby batteries and the electronic components may be adversely effected by continuous operation at
these environmental limits. Therefore, it is recommended that this system and its peripherals be installed
in an environment with a nominal room temperature of 60-80F.
Like all solid state electronic devices, this system may operate erratically or can be damaged when
subjected to lightning induced transients. Although no system is completely immune from lightning
transients and interference, proper grounding will reduce susceptibility. The use of overhead or outside
aerial wiring is not recommended due to the increased susceptibility to nearby lightning strikes.
Consult with the Technical Support Department if any problems are anticipated or encountered.
Do not install electronic assemblies prior to mounting and attaching conduit for field wiring to the enclosure.
Before making modifications, verify that they will not interfere with battery and printed circuit board
locations. Do not overtighten screw terminals. Overtightening may damage threads, resulting in reduced
terminal contact pressure and difficulty with screw terminal removal.
This system contains static-sensitive components. Always ground yourself with a proper wrist strap before
handling any circuits so that static charges are removed from the body. Use static suppressive packaging
to protect electronic assemblies removed from the control unit.
Follow the instructions in this manual. These instructions must be followed to avoid damage to the control
unit and associated equipment. System operation and reliability depend upon proper installation.
Fire Alarm System Limitations While installing a fire alarm system may make lower insurance
rates possible, it is not a substitute for fire insurance!
An automatic fire alarm system typically made up of smoke detectors, heat detectors, manual pull stations,
notification appliances, and a fire alarm control unit with remote-notification capability can provide early warning
of a developing fire. Such a system, however, does not assure protection against property damage or loss of life
resulting from a fire.
Any fire alarm system may fail for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in walls,
on roofs, or on the other side of closed doors. Smoke detectors on one level also may not sense a fire on
P/N 06-236716-001
iii
August 2007
GENERAL SAFETY NOTICES The following must be observed to maintain personnel safety.
The following general safety notices supplement specific warnings and cautions appearing in the manual.
The safety precautions in this section must be understood and applied during operation and maintenance.
This manual is to be used by trained distributors/technicians. The entire manual should be read and fully
understood prior to installation.
FIRST AID
Any injury, no matter how slight, should never go unattended. Always obtain first aid or medical attention
immediately.
GENERAL PRECAUTIONS
The following general safety precautions are to be observed at all times:
1.
All electrical components associated with equipment shall be installed and grounded in accordance
with NEC and local regulatory requirements.
2.
Special precautionary measures are essential to prevent applying power to equipment at any time
maintenance work is in progress.
3.
Before working on electrical equipment, use a voltmeter to ensure that system is not energized.
4.
When working near electricity, do not use metal rulers, flashlights, metallic pencils, or any other
objects having exposed conductive material.
5.
When connecting a meter to terminals for measurement, use a voltage range higher than expected
voltage to be measured.
August 2007
iv
P/N 06-236716-001
Abort Mode 1* (UL) - Count down to 10 seconds and hold. Resume countdown at 10 seconds.
2.
Abort Mode 2 (Reset) - Reset to initial delay setting. Resume countdown for entire delay period.
3.
Abort Mode 3 (IRI) - Same as Mode 1, except disable abort function if countdown timer has started.
4.
5.
P/N 06-236716-001
August 2007
August 2007
vi
P/N 06-236716-001
TABLE OF CONTENTS
CHAPTER 1
1-1
1-2
1-3
1-4
GENERAL INFORMATION
Introduction ................................................................................................ 1-1
Listings and Approvals .................................................................................. 1-1
Codes and Standards .................................................................................... 1-2
Control Unit Description ................................................................................ 1-3
CHAPTER 2
2-1
2-2
2-3
2-4
2-5
2-6
2-7
2-8
2-9
INSTALLATION
Installation Materials..................................................................................... 2-1
Installation Guidelines................................................................................... 2-2
Installation Procedure ................................................................................... 2-4
Terminations And Wiring Diagrams ................................................................. 2-14
Installing the Bezel, P/N 06-220114-001 ......................................................... 2-21
Installing Optional Dead-Front Panel, P/N 06-220175-001.................................. 2-21
Installing the Enclosure Door (Standard Door).................................................. 2-21
Installing the Enclosure Door (Door with Switches) ........................................... 2-21
Completing the Installation ............................................................................ 2-23
CHAPTER 3
3-1
3-2
CONFIGURATION
Entering Site - Specific Configuration .............................................................. 3-1
Configuration Settings................................................................................... 3-3
CHAPTER 4
4-1
4-2
OPERATION
Introduction ................................................................................................ 4-1
Control Switch Functionality........................................................................... 4-2
CHAPTER 5
5-1
5-2
5-3
CHAPTER 6
6-1
6-2
6-3
TROUBLESHOOTING
Purpose ...................................................................................................... 6-1
Trouble Diagnostics ...................................................................................... 6-1
Trouble Codes and Corrective Action ............................................................... 6-1
CHAPTER 7
PARTS LIST
APPENDIX A
A-1
A-2
A-3
A-4
APPENDIX B
APPENDIX C
TECHNICAL SPECIFICATIONS
APPENDIX D
APPENDIX E
APPENDIX F
P/N 06-236716-001
vii
August 2007
August 2007
viii
P/N 06-236716-001
LIST OF FIGURES
Figure
1-1
1-2
Name
Page Number
Control Unit Components and Dimensions ............................................................... 1-3
Printed Circuit Board (PCB) ................................................................................... 1-5
2-1
2-2
2-3
2-4
2-5
2-6
2-7
2-8
2-9
2-10
2-11
2-12
2-13
2-14
2-15
2-16
2-17
2-18
3-1
5-1
5-2
E-1
F-1
P/N 06-236716-001
xi
August 2007
LIST OF TABLES
Table
1-1
1-2
1-3
Name
Page Number
Agency Listing/Approval by System Classification ..................................................... 1-1
Listed/Approved Suppression Systems.................................................................... 1-2
LED Indicator and Display Color ............................................................................. 1-6
2-1
2-2
2-3
3-1
4-1
A-1
A-2
A-3
A-4
B-1
B-2
B-3
B-4
P/N 06-236716-001
xiii
August 2007
General Information
CHAPTER 1
GENERAL INFORMATION
1-1
INTRODUCTION
The Kidde AEGIS is a versatile, flexible, microprocessor-based conventional fire control unit
which can be used in a wide range of fire alarm and suppression discharge applications.
1-2
Agency
Type
System Classification
Service
Signaling
Automatic
Manual
Waterflow
Sprinkler Supervisory
cUL3,4
FM2
CSFM
New York
City MEA
Automatic
Manual
Waterflow
Sprinkler Supervisory
DAC1
Non-Coded
Non-Coded
Automatic
Manual
Waterflow
Sprinkler Supervisory
DAC1
Non-Coded
Automatic
Manual
Waterflow
Sprinkler Supervisory
DAC1
Non-Coded
Automatic
Manual
Waterflow
Sprinkler Supervisory
DAC1
Non-Coded
Must be used with ANSI/UL 864 Listed/FM Approved Silent Knight DACT Model 5104B.
FM approved to FM requirements, ANSI/UL 864 9th edition, and CAN/ULC S527-99.
3 Per Canadian Building Code, not for use as a high-rise building fire alarm system.
4 For UL and cUL installation, must not exceed 24 hours standby and 5 minutes of alarm.
2
P/N 06-236716-001
1-1
August 2007
General Information
1-3
1-3.1
NFPA 12
NFPA 12A
NFPA 13
NFPA 15
NFPA 16
NFPA 17
NFPA 17A
NFPA 750
1-3.2
NFPA 2001
Other Standards
The designer/installer should also be familiar with the following (as applicable):
August 2007
NFPA Standard 75, Standard for the Protection of Electronic Computer/Data Processing
Equipment
NFPA Standard 110, Standard for Emergency and Standby Power Systems 2002 Edition
Underwriter Laboratories of Canada (cUL) ULC-S527-99, Standard of Control Units for Fire
Alarm Systems
FM Standards 1011 and 1012, Approval Standard for Deluge Systems and Preaction
Systems
FM Standard 3011, Central Station Service for Fire Alarms and Protective Equipment
Supervision
Any others mandated by the building owner and/or the local Authority Having Jurisdiction
(AHJ)
1-2
P/N 06-236716-001
General Information
1-4
19 in.
(483 mm)
SECONDARY
STANDBY
BATTERIES
ENCLOSURE
DOOR
1-4.1.1
1-4.1.2
P/N 06-236716-001
1-3
August 2007
General Information
1-4.2
Loss of AC input or if AC power falls below 85% of nominal. This causes an immediate
change-over to battery operation and a trouble signal after 30 seconds.
The battery monitoring circuit provides a trouble signal if any of the following occur:
1-4.3
Battery voltage falls below 19.5 V (this condition causes the battery to disconnect and can
only be cleared when primary AC main power is restored).
August 2007
Battery
System Outputs
Operator Interface
1-4
P/N 06-236716-001
General Information
SUPERVISORY
2
TB6
TB7
TROUBLE
MANUAL WATERFLOW/
ABORT RELEASE DETECTOR 3
SUPERVISORY
1
TB5
TB4
TB3
DETECTOR 2
TB2
TB8
TB1
RELAY 3
TB9
RELAY 2
TB10
RELAY 1
TB11
BATT OUT
TB12
AC IN
TB14
TB15
TB16
TB17
AUX
24 VDC
NAC 3
TB18
DETECTOR 1
NAC 1
NAC 2
TB13
RELEASE 1
ARC 1
RELEASE 2
ARC 2
1-4.3.1
OPERATOR INTERFACE
All alarms, troubles and supervisory signals are received at the control unit and displayed for
the operator. The Operator Interface consists of four main components and are visible and/or
audible through a transparent window:
LED Indicators
Control Switches
Digital Display
Buzzer
P/N 06-236716-001
1-5
August 2007
General Information
1-4.3.1.1
LED Indicators
The following is a list of control unit indicators and their LED display color.
Table 1-3. LED Indicator and Display Color
Indicator
Display Color
AC Power On
Green
System Alarm
Red
System Supervisory
Yellow
System Trouble
Yellow
Signal Silenced
Yellow
Agent Pre-Release
Red
Agent Releasing
Red
Agent Post-Release
Red
Input Activated
1-4.3.1.2
Input Trouble
Yellow
Yellow
Yellow
Ground Fault
Yellow
Yellow
Control Switches
There are four Control Switches on the Operator Interface. They are:
Acknowledge Silences the buzzer which sounds when a new supervisory, alarm, or
trouble is detected. Holding this control switch for five seconds, activates the control unit
Lamp Test. This control switch is also used in conjunction with the System Reset control
switch to enter the configuration mode.
Note: Microprocessor and PCB troubles are latching and cannot be silenced or reset. Refer to
Chapter 6, Troubleshooting.
August 2007
System Reset Disconnects power from all input and output circuits and the auxiliary
output for a period of five (5) seconds. This control switch is also used in conjunction with
the Acknowledge control switch to enter the configuration mode.
Output Disable Disables the release of agent, and as selected in the system
configuration, the activation of NAC outputs and/or Programmable Relays. This is used
when performing maintenance on the system.
1-6
P/N 06-236716-001
General Information
1-4.3.1.3
Digital Display
The three digit display is used for the following:
1-4.3.1.4
Buzzer
The buzzer will sound when an alarm, trouble or supervisory condition is present.
1-4.3.2
1-4.3.2.1
Detection Inputs
The control unit provides two dedicated initiating/detector input circuits, plus a third that can
be used as a Waterflow alarm or an independent initiating/detector input. Inputs from these
circuits are latching. Refer to Chapter 3, Configuration for configuration settings.
Certain jurisdictions require NAC outputs due to Waterflow input to be non-silenceable. The
configuration settings in Chapter 3, Configuration allows the user to select the specific mode
needed for a given application.
Each detector circuit is suitable for Class A or Class B wiring and is capable of operating with
up to 25 smoke/electronic heat detectors and a quantity of contact-closure type devices (up to
the limitation imposed by wiring resistance). For a list of compatible devices, refer to
Appendix B.
1-4.3.2.2
Manual Release
Operation of a manual release pull station activates the NACs and initiates the release
sequence. The configured time delay and agent release output is activated after the site
configured time delay. Manual release overrides any other time delay. The circuit is suitable
for either Class A or Class B wiring and any quantity of contact closure type manual release
stations subject to the limitations imposed by the wiring resistance. The manual release will
also override any activated abort switch.
1-4.3.2.3
Abort
Activation of the abort station temporarily delays the impending agent release. Operation of
the abort switch during non-alarm conditions will cause a trouble signal. However, if the Abort
switch is pressed and held during either a non-alarm condition or during a first alarm condition,
and remains held until an alarm pre-release condition exists occurs, the Abort function will
execute as normal, per the configuration setting. The following abort modes are configurable.
Abort Mode 1 (ANSI/UL 864) - When the abort input is received, the release timeout
continues and stops at ten (10) seconds. If the timeout was less than ten (10) seconds when
the abort signal is received, timeout is reset to ten (10) seconds. When the abort is released,
the timeout resumes. Successive aborts are permitted.
P/N 06-236716-001
1-7
August 2007
General Information
Abort Mode 2 (Reset) - When abort is activated, the timer is stopped and the full delay is
loaded into it. The timeout begins when the Abort control switch is released. Successive aborts
are permitted. If Mode 2 is selected with a zero (0) abort delay, the abort is disabled. Mode 2
does not comply with ANSI/UL 864s.
Abort Mode 3 (IRI) - This mode is only valid for cross-zoned release when both initiating
inputs are needed to cause the agent release activation (if selected for single zone, the abort
will be disabled). This mode is similar to Mode 1 with the exception that the abort will function
only if held after the receipt of the first alarm, but prior to the receipt of the second alarm.
Abort activation at any other time is ignored.
Abort Mode 4 (New York City) When the abort is activated, the timer is stopped and reset
to 120 seconds. The timer will not start as long as the Abort switch is held. The timeout restarts
when the Abort switch is released. Successive Abort switch operations resets the timer back to
the full 120 second delay. Selection of this mode does not have an over-ruling effect on any
programmed manual or auto-release delays, regardless of whether an abort has actually
occurred. In this mode, the delay from a manual release is forced to zero (0), and the autorelease delay is restricted to a maximum of 30 seconds. NYC Mode does not comply with
ANSI/UL 864.
WARNING
The setting of non-compliant delays with New York City Abort is not errortrapped or over-ruled by the control unit.
SUPERVISORY INPUTS
The Supervisory Circuits accept inputs from monitoring devices such as pressure switches on
agent cylinders or sprinkler systems.
1-4.4
System Outputs
The Kidde AEGIS has the following system outputs:
1-4.4.1
August 2007
Temporal
1-8
P/N 06-236716-001
General Information
Continuous
The three circuits are supervised, power-limited, and are compatible with conventional UL
listed, 24 Vdc notification appliances. They can also be used with the following synchronizable
horns and strobes:
NS series horn/strobes
NH series horns
The MT and NS series network appliances provide the option to use silencable horns and nonsilenceable strobes on the same NAC.
Multiple NAC circuits (connected to audible devices only) programmed with the same master
code pattern are synchronized, regardless of any differing starting times that preceded their
concurrent operation.
The control unit is designed for user selection of an intelligent synchronization feature. This
feature allows the silenceable horn to be shut off while the strobe continues to flash in
synchronized fashion. Each NAC is rated 1.5A at 24 Vdc and is suitable for polarized 24 Vdc
appliances only.
The maximum number of synchronized devices is 35.
1-4.4.2
1-4.4.3
PROGRAMMABLE/DEDICATED RELAYS
The Kidde AEGIS has three independently programmable relays and one dedicated Trouble
relay. The relays are Form-C type with contacts rated 3A @ 30 VDC / 120 VAC (resistive).
P/N 06-236716-001
1-9
August 2007
General Information
1-4.4.3.1
Programmable Relays
The three programmable relays are normally in the de-energized condition and will energize
upon receipt of one of the following listed conditions. These relays will latch on change of state
and shall remain latched until manually reset by the System Reset control switch.
Note: DET 3/WF will only be active if its part of the activation condition.
Note: SUPV 1 will only be active if its part of the activation condition.
1-4.4.3.2
Waterflow Input
Abort Input
Supervisory Input
Trouble Relay
The trouble relay is "normally energized with AC Power ON and will de-energize upon receipt
of a trouble condition. This change is non-latching and the relay will revert to its normal state
upon removal of the trouble state. For Central Station operation, especially with an intermittent
AC power supply, it may be desirable to delay the change of state of the trouble relay in case
of AC power failure. See Chapter 3, Configuration to enable this configuration.
1-4.4.4
August 2007
1-10
P/N 06-236716-001
Installation
CHAPTER 2
INSTALLATION
2-1
INSTALLATION MATERIALS
2-1.1
Materials Provided
Check and ensure that the received shipment of the Kidde AEGIS unit consists of:
Table 2-1. Kidde AEGIS Control Unit Contents
Description
Part Number
Quantity
06-220132-001
06-118394-001
06-220113-001
Bezel Assembly
06-220114-001
Hardware Kit
06-220147-001
Installation/Configuration Kit
06-220148-002
Operating Instructions
06-236719-002
06-250319-013
Quantity
10
2-1.2
Materials Required
The materials listed below are not supplied with the system, but are required for installation.
P/N 06-236716-001
2-1
August 2007
Installation
2-2
INSTALLATION GUIDELINES
2-2.1
Electrical Connections
Take special care when installing the system and follow the guidelines given in the following
paragraphs.
Install electrical conduit and wiring in accordance with applicable National Electrical Code,
NFPA Standard and state and local building code requirements.
The incoming AC voltage must be stable and within the permissible voltage range. This is
especially important in new construction where incoming power may be high or unstable, and
temporary connections may cause large inductive voltage spikes.
Most supervised circuits use voltage or current sensing circuits that are sensitive to induced
voltages on the sensor wiring.
CAUTION
2-2.2
Do not under any circumstances run AC power, speaker, PA, intercom or switch
control wiring with inductive loads in the same conduit or in the immediate vicinity
of sensor wiring. Control unit damage or malfunction may result.
CAUTION building entry. Arrestor circuitry and earth grounding should be in accordance with
article 250 of the National Electric Code.
August 2007
2-2
P/N 06-236716-001
Installation
2-2.3
2-2.4
2-2.5
Wire Gauge
12 AWG
1.588 ohms
14 AWG
2.525 ohms
16 AWG
4.016 ohms
18 AWG
6.385 ohms
DC Load Distribution
Operating power for all initiating and indicating circuits is provided by the power supply. 4-wire
24 Vdc smoke detectors and other listed, compatible external 24 Vdc loads may be powered
from the power auxiliary output. DC load calculations must be performed to determine if the
power supply is capable of providing the total system current demand. The calculations will
also determine the minimum standby battery capacity in accordance with applicable NFPA
codes. Refer to Appendix A for Battery Capacity Calculations.
2-2.6
Enclosure Location
Care should be taken in planning the enclosure location. The enclosure is intended only for
indoor use in a location free from rain, condensation, excessive dust, moisture or other
airborne contamination. The enclosure must not be exposed to ambient conditions outside
those specified in Appendix C.
CAUTION
Position the enclosure in a readily accessible and easily visible location. Ensure there is
1-1/2 ft. (457 mm) clearance or more in front and to the door hinge side of the enclosure for
the door to swing open completely.
The type of hardware is at the discretion of the installer, but must be in accordance with good
electrical and safety practices.
P/N 06-236716-001
2-3
August 2007
Installation
2-3
INSTALLATION PROCEDURE
2-3.1
19 in.
(483 mm)
66 in.
(1676 mm)
MAX.
FLOOR
August 2007
2-4
P/N 06-236716-001
Installation
14-1/4 in.
(362 mm)
13-1/8 in.
(333 mm)
9-1/8 in.
(232 mm)
5-1/8 in.
(130 mm)
1-1/8 in.
(29 mm)
1-1/2 in.
(38 mm)
9/32 in.
(7 mm)
5 in.
(127 mm)
7/16 in.
(11 mm)
TOP VIEW
1/2 in.
(13 mm)
TYP 2 PLACES
1 in.
(25 mm)
2-1/2 in.
(64 mm)
12-1/4 in.
(311 mm)
1 in.
(25 mm)
2 in.
(57 mm)
5 in.
(127 mm)
GROUND
STUD
8 in.
(203 mm)
18-13/16 in.
(978 mm)
17 in.
(432 mm)
19 in.
(483 mm)
GROUND
STUD
14-3/16 in.
(360 mm)
FRONT VIEW
5 in.
(127 mm)
SIDE VIEW
2-3.1.1
SURFACE MOUNTING
1. Mark and pre-drill holes for four mounting bolts using the dimensions shown in Figure 2-2.
The installer must supply the mounting bolts (No. 10 or 3/16-inch (5mm)). There are two
holes and two keyhole slots in the backbox that serve as a template for surface mounting.
The type of hardware to be used is at the discretion of the installer, but must be installed
in accordance with NFPA 70 (NEC).
2. Insert the upper two fasteners in the wall. Leave approximately 1/4-inch (6 mm)
protruding for both screws.
3. Slip upper keyholes of the back box over the two protruding screws. Tighten the screws.
4. Insert and tighten the two lower screws.
5. Attach wiring conduit to the enclosure via the enclosure knockouts, and pull the required
number of wires through the conduit to the enclosure. Leave approximately 2 to 3 feet (600
to 900 mm) of wire length in the enclosure for future internal connections.
P/N 06-236716-001
2-5
August 2007
Installation
2-3.1.2
SEMI-FLUSH MOUNTING
1. Cut and plumb an opening of dimensions as shown in Figure 2-3 in the wall on which the
control unit will be semi-flush mounted.
14-1/4 in.
(362 mm)
5 in.
(127 mm)
TOP VIEW
WALL CUTOUT
18-13/16 in.
(978 mm)
19-1/8 in.
(486 mm)
14-3/8 in.
(365 mm)
5 in.
(127 mm)
FRONT VIEW
SIDE VIEW
14-9/16 in.
(370 mm)
INSIDE
23-13/16 in.
(605 mm)
20-13/16 in.
(529 mm)
INSIDE
17-9/16 in.
(446 mm)
August 2007
2-6
P/N 06-236716-001
Installation
1. Ensure that the enclosure is semi-flush mounted as directed in Paragraph 2-3.1.2.
2. Prepare the surface of the wall for trim-ring installation by clearing all dirt and debris within
1-1/2 inches (38 mm) of the back-box perimeter. Ensure that this perimeter area is clean
and dry.
3. Install the trim ring by first removing the protective strips that cover the adhesive tape on
its back surface. Slip the trim ring over the back box with the adhesive-tape side toward
the wall. The trim ring has tabs on both sides that aid in aligning it with the back box. Press
all sides of the trim ring to the wall when it is correctly aligned and plumb with the back
box.
1-3/4 in.
(44 mm)
MIN.
WALL
TRIM RING
BACK BOX
COVER
2-3.2
CAUTION
Use a ground strap to prevent static discharge that could damage the power
supply.
1. Make sure the control unit location is dry and that the enclosure is free of construction dust
and metal shavings prior to installing the power supply.
2. Remove the power supply unit from its shipping carton.
3. The AEGIS unit is supplied with one of two equivalent power supplies. Compare the
terminal block wiring legend on the provided power supply with the diagrams in Figure 2-6
and connect the wiring harness as shown.
4. Connect the Power Supply Wiring Harness (P/N 06-220025-001) to the power supply unit.
Next connect the fork end of the green ground wire (P/N 06-129928-002) to the
earth-ground terminal of the power supply unit. Refer to Figure 2-6 and Figure 2-7 for wire
harness and earth-ground connections.
P/N 06-236716-001
2-7
August 2007
TO PSU J2
CONNECTOR ON
PCB
- 24 V
+ 24 V
LINE
NEUTRAL
GND
Installation
WHT/BLK
WHT
BLK
RED
GRN
LINE
NEUTRAL
GND
- V
- V
+V
+V
OR
TO PSU J2
CONNECTOR ON
PCB
WHT/BLK
WHT
BLK
RED
GRN
ATTENTION!
THE CONTROL UNIT IS SUPPLIED WITH ONE OF TWO EQUIVALENT
POWER SUPPLIES. COMPARE THE TERMINAL BLOCK WIRING LEGEND
ON THE PROVIDED POWER SUPPLY WITH THE DIAGRAMS AND
CONNECT THE WIRING HARNESS AS SHOWN IN THE APPLICABLE DIAGRAM.
2-8
P/N 06-236716-001
Installation
FASTENING TAB
FOR SCREW
230 V
115 V
RETENTION
TABS
TYP (2)
CAUTION
Use a ground strap to prevent static discharge that could damage sensitive
components on the Printed Control Board.
1. Make sure the control unit location is dry and that the enclosure is free of construction dust
and metal shavings prior to installing the PCB.
P/N 06-236716-001
2-9
August 2007
Installation
AC PROTECTIVE COVER
(WITH STANDOFF)
August 2007
2-10
P/N 06-236716-001
Installation
TB7
TB6
TB5
TB4
TB3
TB2
TB8
TB1
TB9
TB10
TB11
TB12
A
AC SUPPLY SELECT SWITCH (S6)
TB14
TB15
TB16
TB19
TB17
TB18
TB13
2-3.4
WARNING
2-3.4.1
Use caution when connecting AC power to the control unit. High-voltage and
AC-powered circuits are present in the control unit. Be sure to take suitable
precautions and to adequately ground the control unit to reduce the risk of
electrical shock.
CONNECTING AC POWER
AC power must be provided to the control unit using a 3-conductor 14 AWG cable. The AC
power cable shall be run through a one-inch conduit from a dedicated, 15-ampere circuit
breaker. The conduit must be attached to the left side of the enclosure through one of the
upper left corner knockouts.
Perform the following steps to connect AC power to the control unit.
1. Ensure the circuit breaker at the dedicated AC power source is in the OFF position.
2. To ensure correct AC supply supervision, for 110-120 Vac operation, move the AC Supply
Select Switch (S6) on the PCB to the 120 position. For 220-240 Vac operation, move it to
the 240 position.
3. Attach the 3-conductor AC power cable to TB13 on the PCB.
P/N 06-236716-001
2-11
August 2007
Installation
PROTECTIVE COVER
FOR AC POWER INPUT
ENCLOSURE WALL
POWER CONNECTIONS
FROM AC SUPPLY
WHITE (NEUTRAL)
BLACK (LINE/HOT)
GREEN (GREEN)
SUPERVISED
August 2007
2-12
P/N 06-236716-001
Installation
2-3.5
12 V
BATTERY
12 V
BATTERY
12 V
BATTERY
12 V
BATTERY
ADDITIONAL BATTERY
CABLES TYP (BY INSTALLER)
12 V
BATTERY
NOTE:
12 V
BATTERY
P/N 06-236716-001
2-13
August 2007
Installation
2-4
2-4.1
Terminal Blocks
The PCB provides the following input and output terminations as shown in Figure 2-12.
Detector 1 (TB1)
Detector 2 (TB2)
Waterflow/Detector 3 (TB3)
Abort (TB5)
Supervisory 1 (TB6)
AC IN (TB13)
PSU (J2)
Supervisory 2 (TB7)
SUPERVISORY
2
TB7
TROUBLE RELAY
SUPERVISORY
1
TB6
MANUAL WATERFLOW/
ABORT RELEASE DETECTOR 3
TB5
TB4
TB3
DETECTOR 2
TB2
TB8
TB1
PROGRAMMABLE RELAY 3
TB9
PROGRAMMABLE RELAY 2
TB10
PROGRAMMABLE RELAY 1
TB11
BATT OUT
TB12
AC IN
TB14
TB15
TB16
TB17
AUX
24 VDC
NAC 3
TB18
DETECTOR 1
NAC 1
NAC 2
TB13
RELEASE
ARC 1
RELEASE
ARC 2
August 2007
2-14
P/N 06-236716-001
Installation
2-4.2
3
2
1+ 2+ 2- 1-
EOL RESISTOR
5.1K, 0.5 W
P/N 06-129025-002
3
1
1+ 2+ 2- 1-
EOL RESISTOR
5.1K, 0.5 W
P/N 06-129025-002
P/N 06-236716-001
2-15
August 2007
Installation
EOL RESISTOR
5.1K, 0.5 W
P/N 06-129025-002
1+ 2+ 2- 1-
1+ 2+ 2- 1EOL RESISTOR
5.1K, 0.5 W
P/N 06-129025-002
LEGEND
SUPERVISED
POWER LIMITED
August 2007
2-16
P/N 06-236716-001
Installation
2-4.3
EOL RESISTOR
5.1K, 0.5 W
P/N 06-129025-002
1+ 2+ 2- 1-
1+ 2+ 2- 1-
EOL RESISTOR
5.1K, 0.5 W
P/N 06-129025-002
POWER LIMITED
P/N 06-236716-001
2-17
August 2007
Installation
2-4.4
BLK
RED
SOLENOID
P/N 06-220023-001
IN-LINE RELEASING DEVICE - MUST
BE INSTALLED CLOSE NIPPLED TO
SOLENOID ENCLOSURES
TB14 OR TB15
SOLENOID
August 2007
2-18
P/N 06-236716-001
Installation
TB14 OR TB15
BLK
RED
BLK
RED
SOLENOID
TB14 OR TB15
SOLENOID
P/N 06-236716-001
2-19
August 2007
Installation
TB14 OR TB15
BLACK
WHITE
N.C.
N.O.
Figure 2-15E. Agent Release Circuit for XV and CXV Control Heads
TB14 OR TB15
10 OHM LIMITING
RESISTOR
INITIATOR
August 2007
2-20
P/N 06-236716-001
Installation
2-5
2-6
DEAD-FRONT
PANEL
2-7
2-8
2-8.1
P/N 06-236716-001
2-21
August 2007
Installation
Note: Switch guard is keyed and can only be installed one way.
4. Install locking nut on the abort switch.
5. Install abort switch from back of enclosure door. Attach pushbutton switch guard and
tighten.
MANUAL RELEASE
SWITCH
GUARD
MANUAL
RELEASE
SWITCH
ABORT
SWITCH
LOCKING
NUT
INTERNAL
TOOTH
LOCKWASHER
AND LOCKING RING
LOCKING
NUT
PUSHBUTTON
SWITCH
GUARD
ABORT
SIDE VIEW
FRONT VIEW
CAUTION
August 2007
Power-limited wiring from the front cover Manual Release and Abort switches
to their respective terminal blocks on the PCB must be routed to maintain a
1/4-inch distance from non-power-limited wiring. Refer to Appendix F for more
details.
2-22
P/N 06-236716-001
Installation
- WHITE WIRES
TO TB5
- BLACK WIRES
TO TB4
BLACK WIRES
FROM SWITCH
WIRE HARNESS
CABLE CLAMP
AND 8-32 KEP NUT
(SUPPLIED)
(TYP 3 PLACES)
MANUAL
RELEASE
SWITCH
ABORT
SWITCH
SWITCH WIRE
HARNESS
REAR VIEW
2-9
P/N 06-236716-001
2-23
August 2007
Installation
August 2007
2-24
P/N 06-236716-001
Configuration
CHAPTER 3
CONFIGURATION
3-1
3-1.1
Step
Description
Press and hold the Acknowledge control switch and within five (5) seconds,
press the System Reset control switch.
Display
The control unit exits the configuration mode upon status change, or if more than five (5)
minutes have expired since the last control switch press. Only saved changes are retained by
the control unit.
P/N 06-236716-001
3-1
August 2007
Configuration
3-1.2
Enter the Temporary Password in the same manner as entering a regular Password.
When the password has been accepted (and the first configuration item is being displayed
"00x", where x is the left most digit of the Temporary Password), you should:
1. either press the Signal Silence control switch in order to accept and save the current
Temporary Password as a Permanent Password; OR
2. enter the desired Password in configuration items 0, 1, and 2, and then press the Signal
Silence control switch in order to accept and save it.
August 2007
3-2
P/N 06-236716-001
Configuration
3-2
CONFIGURATION SETTINGS
This section describes the configuration settings for the AEGIS unit. Use Table 3-1 to set the
configuration settings.
To advance to the next selection for an item, press the Output Disable control switch.
To accept a configuration setting change and exit the Configuration menu at any step in
the process, press the Signal Silence control switch. Check the configuration by starting
the configuration process again, checking all items, and exiting by pressing System Reset
after inspecting the last item.
To exit the configuration menu at any time, press the System Reset control switch. This
reverts the control unit to its previous state.
Note: The control unit takes about five (5) seconds to boot up after exiting the configuration
menu.
POSITION
2
Configuration Item
00
09
01
09
02
09
03
Default
Mode
P/N 06-236716-001
3-3
August 2007
Configuration
Table 3-1. Configuration Settings
Configuration
Number
(Position 1, 2)
04
Configuration Item
Application Mode Release Circuit 2
Default
Mode
05
06
2 Mode 2, (Reset)
3 Mode 3 (IRI)
4 Mode 4 (NYC)
5 Mode 0 (Disable the Abort)
07
Input Circuit 3
1 Detector (DET 3)
Programmable Relay 1
August 2007
3-4
P/N 06-236716-001
Configuration
Table 3-1. Configuration Settings
Configuration
Number
(Position 1, 2)
Configuration Item
Programmable Relay 2
Default
Mode
4
Programmable Relay 3
Trouble Relay
2 10 seconds
3 20 seconds
4 30 seconds
13
2 10 seconds
3 20 seconds
4 30 seconds
P/N 06-236716-001
3-5
August 2007
Configuration
Table 3-1. Configuration Settings
Configuration
Number
(Position 1, 2)
14
Configuration Item
Automatic Time Delay Release Circuit 1
Default
Mode
7
2 10 seconds
3 20 seconds
4 30 seconds (select for NYC)
5 40 seconds
6 50 seconds
7 60 seconds
15
1 0 seconds
2 10 seconds
3 20 seconds
4 30 seconds (select for NYC)
5 40 seconds
6 50 seconds
7 60 seconds
16
17
18
19
20
Trouble Latching
August 2007
3-6
P/N 06-236716-001
Configuration
Table 3-1. Configuration Settings
Configuration
Number
(Position 1, 2)
21
22
23
Configuration Item
Latching for
Supervisory 1
1 SUPV 1 is non-latching
Latching for
Supervisory 2
1 SUPV 2 is non-latching
Outputs Disabled by
Isolate Button
Default
Mode
1
2 SUPV 2 is latching
1 Disables ARCs
24
NAC 1 relationship to
ARCs
1 ARC 1 only
2 ARC 2 only
3 Both ARC 1 and ARC 2 (see note 5)
4 Neither ARC 1 nor ARC 2 (see note 6)
5 NAC 1 Not Used (see note 1)
25
NAC 2 relationship to
ARCs
1 ARC 1 only
2 ARC 2 only
3 Both ARC 1 and ARC 2 (see note 5)
4 Neither ARC 1 nor ARC 2 (see note 6)
5 NAC 2 Not Used (see note 1)
26
NAC 3 relationship to
ARCs
1 ARC 3 only
2 ARC 3 only
3 Both ARC 1 and ARC 2 (see note 5)
4 Neither ARC 1 nor ARC 2 (see note 6)
5 NAC 3 Not Used (see note 1)
27
0 60 bpm Non-Silenceable
1 60 bpm Silenceable
2 120 bpm Non-Silenceable
3 120 bpm Silenceable
4 Steady Non-Silenceable
5 Steady Silenceable
6 Temporal Non-Silenceable
8 Temporal Silenceable
8 Intelligent Synchronization - Non-Silenceable
9 Intelligent Synchronization - Silenceable (Horn &
Strobe)
A Intelligent Synchronization - Silenceable (Horn Only
Off)
C NAC 1 Off (see note 7)
P/N 06-236716-001
3-7
August 2007
Configuration
Table 3-1. Configuration Settings
Configuration
Number
(Position 1, 2)
28
Configuration Item
NAC 1 Pre-Release
(see note 9)
Default
Mode
1 60 bpm Silenceable
2 120 bpm Non-Silenceable
3 120 bpm Silenceable
4 Steady Non-Silenceable
5 Steady Silenceable
6 Temporal Non-Silenceable
7 Temporal Silenceable
8 Intelligent Synchronization - Non-Silenceable
9 Intelligent Synchronization - Silenceable (Horn &
Strobe)
A Intelligent Synchronization - Silenceable (Horn Off)
C NAC 1 Off (see note 7)
29
NAC 1 Releasing
(see note 10)
0 60 bpm Non-Silenceable
1 60 bpm Silenceable
2 120 bpm Non-Silenceable
3 120 bpm Silenceable
4 Steady Non-Silenceable
5 Steady Silenceable
6 Temporal Non-Silenceable
7 Temporal Silenceable
8 Intelligent Synchronization - Non-Silenceable
9 Intelligent Synchronization - Silenceable (Horn &
Strobe)
A Intelligent Synchronization - Silenceable (Horn Off)
C NAC 1 Off (see note 7)
August 2007
3-8
P/N 06-236716-001
Configuration
Table 3-1. Configuration Settings
Configuration
Number
(Position 1, 2)
30
Configuration Item
NAC 2 First Alarm
(see note 8)
Default
Mode
1
1 60 bpm Silenceable
2 120 bpm Non-Silenceable
3 120 bpm Silenceable
4 Steady Non-Silenceable
5 Steady Silenceable
6 Temporal Non-Silenceable
8 Temporal Silenceable
8 Intelligent Synchronization - Non-Silenceable
9 Intelligent Synchronization - Silenceable (Horn &
Strobe)
A Intelligent Synchronization - Silenceable (Horn Only
Off)
C NAC 2 Off (see note 7)
31
NAC 2 Pre-Release
(see note 9)
0 60 bpm Non-Silenceable
1 60 bpm Silenceable
2 120 bpm Non-Silenceable
3 120 bpm Silenceable
4 Steady Non-Silenceable
5 Steady Silenceable
6 Temporal Non-Silenceable
7 Temporal Silenceable
8 Intelligent Synchronization - Non-Silenceable
9 Intelligent Synchronization - Silenceable (Horn &
Strobe)
A Intelligent Synchronization - Silenceable (Horn Off)
C NAC 2 Off (see note 7)
P/N 06-236716-001
3-9
August 2007
Configuration
Table 3-1. Configuration Settings
Configuration
Number
(Position 1, 2)
32
Configuration Item
NAC 2 Releasing
(see note 10)
Default
Mode
1 60 bpm Silenceable
2 120 bpm Non-Silenceable
3 120 bpm Silenceable
4 Steady Non-Silenceable
5 Steady Silenceable
6 Temporal Non-Silenceable
7 Temporal Silenceable
8 Intelligent Synchronization - Non-Silenceable
9 Intelligent Synchronization - Silenceable (Horn &
Strobe)
A Intelligent Synchronization - Silenceable (Horn Off)
C NAC 2 Off (see note 7)
33
0 60 bpm Non-Silenceable
1 60 bpm Silenceable
2 120 bpm Non-Silenceable
3 120 bpm Silenceable
4 Steady Non-Silenceable
5 Steady Silenceable
6 Temporal Non-Silenceable
8 Temporal Silenceable
8 Intelligent Synchronization - Non-Silenceable
9 Intelligent Synchronization - Silenceable (Horn &
Strobe)
A Intelligent Synchronization - Silenceable (Horn Only
Off)
C NAC 3 Off (see note 7)
August 2007
3-10
P/N 06-236716-001
Configuration
Table 3-1. Configuration Settings
Configuration
Number
(Position 1, 2)
34
Configuration Item
NAC 3 Pre-Release
(see note 9)
Default
Mode
3
1 60 bpm Silenceable
2 120 bpm Non-Silenceable
3 120 bpm Silenceable
4 Steady Non-Silenceable
5 Steady Silenceable
6 Temporal Non-Silenceable
7 Temporal Silenceable
8 Intelligent Synchronization - Non-Silenceable
9 Intelligent Synchronization - Silenceable (Horn &
Strobe)
A Intelligent Synchronization - Silenceable (Horn Off)
C NAC 3 Off (see note 7)
35
NAC 3 Releasing
(see note 10)
0 60 bpm Non-Silenceable
1 60 bpm Silenceable
2 120 bpm Non-Silenceable
3 120 bpm Silenceable
4 Steady Non-Silenceable
5 Steady Silenceable
6 Temporal Non-Silenceable
7 Temporal Silenceable
8 Intelligent Synchronization - Non-Silenceable
9 Intelligent Synchronization - Silenceable (Horn &
Strobe)
A Intelligent Synchronization - Silenceable (Horn Off)
C NAC 3 Off (see note 7)
36
1 NAC #1
2 NAC #2
3 NAC #1 & NAC #2
4 NAC #3
5 NAC #1 and NAC #3
6 NAC #2 & NAC #3
7 NAC #1 & NAC #2 & NAC #3
8 None (No General Alarm)
P/N 06-236716-001
3-11
August 2007
Configuration
Table 3-1. Configuration Settings
Configuration
Number
(Position 1, 2)
Configuration Item
37
Default
Mode
1 60 bpm Silenceable
2 120 bpm Non-Silenceable
3 120 bpm Silenceable
4 Steady Non-Silenceable
5 Steady Silenceable
6 Temporal Non-Silenceable
7 Temporal Silenceable
8 Intelligent Synchronization - Non-Silenceable
9 Intelligent Synchronization - Silenceable (Horn &
Strobe)
A Intelligent Synchronization - Silenceable (Horn Off)
C NAC 3 Off (see note 7)
38
0 60 bpm Non-Silenceable
1 60 bpm Silenceable
2 120 bpm Non-Silenceable
3 120 bpm Silenceable
4 Steady Non-Silenceable
5 Steady Silenceable
6 Temporal Non-Silenceable
7 Temporal Silenceable
8 Intelligent Synchronization - Non-Silenceable
9 Intelligent Synchronization - Silenceable (Horn &
Strobe)
A Intelligent Synchronization - Silenceable (Horn Off)
C NAC 3 Off (see note 7)
August 2007
3-12
P/N 06-236716-001
Configuration
Table 3-1. Configuration Settings
Configuration
Number
(Position 1, 2)
Configuration Item
39
Default
Mode
1 60 bpm Silenceable
2 120 bpm Non-Silenceable
3 120 bpm Silenceable
4 Steady Non-Silenceable
5 Steady Silenceable
6 Temporal Non-Silenceable
7 Temporal Silenceable
8 Intelligent Synchronization - Non-Silenceable
9 Intelligent Synchronization - Silenceable (Horn &
Strobe)
A Intelligent Synchronization - Silenceable (Horn Off)
C NAC 3 Off (see note 7)
NOTES:
1.
If "circuit not used" is selected, do NOT install an EOL as the control unit needs to see open
circuit. Using an EOL will cause trouble.
2.
DET 1, DET 2, and DET 3/WF will activate first alarm ONLY IF it is part of the ARC activation
condition.
3.
SUPV 1 will activate first alarm ONLY IF it is part of the ARC activation condition.
4.
If Initiator is selected for any Release circuit output, the respective Power-Limited switch setting
is ignored.
5.
The NAC will be driven by both ARC 1 and ARC 2. However the first ARC to reach each state is
given precedence. Once its cycle is complete, the other ARC, if active, will gain control.
6.
The NAC may be related to neither ARC if the control unit is used for non-suppression
applications. Also see notes 8 to 10.
7.
An OFF condition is different from NOT USED and will require that an EOL be installed.
8.
In addition to being selectable for NACx First Alarm, the various tones are also selectable in the
condition that both ARCs are not used and one of DET 1, DET 2 or DET 3/WF is in alarm.
9.
In addition to being selectable for NACx Pre-Release, the various tones are also selectable in the
condition that both ARCs are not used and two of DET 1, DET 2 or DET 3/WF are in alarm.
10. In addition to being selectable for NACx Releasing, the various tones are also selectable in the
condition that both ARCs are not used and all of DET 1, DET 2 and DET 3/WF are in alarm.
P/N 06-236716-001
3-13
August 2007
Configuration
August 2007
3-14
P/N 06-236716-001
Operation
CHAPTER 4
OPERATION
4-1
INTRODUCTION
This chapter explains how to read the control unit display, interpret the LEDs, and how to reset
the unit. The following are the operational modes of the control unit:
4-1.1
Normal Mode
Alarm Signal
Supervisory Signal
Normal Mode
In the normal mode, the control unit continuously monitors all inputs and outputs for any
change of state. In the normal mode the Green AC ON LED is the only illuminated LED. The
buzzer and NACs are silent, The Programmable Relays are de-energized, and the Trouble relay
is energized.
4-1.2
DET 1, or
DET 2, or
Manual Release
Manual Release
3. Releasing caused when the pre-release countdown timer has counted down to zero. In
this state, the control unit is actively in the process of activating its Agent Release
Circuit(s).
4. Post-Release condition when the control unit has released Agent.
P/N 06-236716-001
4-1
August 2007
Operation
4-1.3
Supervisory Signal
In the supervisory state, the control unit has detected a change in state of one or both of its
supervisory input circuits, or its PCB mounted Output Disable switch. A flashing LED indicates
one or more unacknowledged supervisory events. A steady LED indicates all supervisory
events have been acknowlwdged. The LED turns off when the AEGIS receives supervisory-off
messages from all initiating devices that reported supervisory conditions.
4-1.4
4-2
4-2.1
Acknowledge
Pressing the Acknowledge control switch during an active trouble, supervisory, or alarm allows
the operator to signal the AEGIS that a new event currently being displayed is understood. The
AEGIS control units buzzer will silence and all flashing Alarm, Trouble, or Supervisory LEDs
will light steady.
Table 4-1. Acknowledge
Event
Buzzer
Alarm
Steady
Steady
Off
Trouble
Steady
Steady
Off
Supervisory
Steady
Steady
Off
Event Clear
Off
Off
Off
Event Recurrence
Flash
Flash
On Steady - Alarm
On Pulsed - Trouble/Supervisory
4-2.2
Signal Silence
Pressing the Signal Silence control switch at any alarm state will turn on the Signal Silenced
LED and silence all NACs unless configured otherwise (non-silenceable).
4-2.3
System Reset
Resets the system including turning off outputs and interrupting power to all input and output
circuits for a period of five (5) seconds.
August 2007
4-2
P/N 06-236716-001
Operation
4-2.4
Output Disable
Disables the release of agent, and as selected in the system configuration, the activation of
NAC outputs and/or Programmable Relays. This is used when performing maintenance on the
system. When the control switch is engaged, it creates a System Supervisory condition.
Pressing the control switch momentarily toggles in and out of the disable mode.
P/N 06-236716-001
4-3
August 2007
Operation
August 2007
4-4
P/N 06-236716-001
CHAPTER 5
TESTING AND MAINTENANCE
5-1
MAINTENANCE REQUIREMENTS
The Kidde AEGIS must be inspected, tested and maintained in accordance with the
requirements of NFPA 72 (latest edition), and/or the local Authority Having Jurisdiction (AHJ).
WARNING
Two different sources of power can be connected to the control unit. Disconnect
both sources of power and critical components such as special extinguishing
systems and relays controlling facility-power shutoff before servicing the
control unit. The control unit and associated equipment may be damaged by
connecting or disconnecting wiring while the control unit is energized.
For inspection, testing and maintenance of the associated extinguishing system, refer to the
manufacturers instructions and the standards and codes that apply to that systems.
Prior to any testing or maintenance on the AEGIS, perform the following:
1. Disable ARCs and NACs via the Output Disable control switch.
2. Physically disconnect the wiring to initiator assemblies (if used) from the release-circuit
terminals, short the leads together, and wrap the leads in insulating tape
3. Physically disconnect all control heads (if used) from their associated agent-storagecontainer discharge valves
4. Physically disconnect the wiring to solenoid valves (if used) for pre-action/deluge sprinkler
systems
5. Ensure that emergency operations controlled by this system such as facility power shutoff
are bypassed
6. Notify personnel in the facility and at off-premises monitoring locations that you are
working on the system and that you will inform them when servicing has ended.
5-2
TESTING FREQUENCY
The frequency shall be per NFPA 72 (latest edition) stated below, or as required by the local
Authority Having Jurisdiction (AHJ), whichever is more stringent.
P/N 06-236716-001
5-1
August 2007
TESTING
5-3.1
5-3.2
Battery Test
The following sequence will display the battery open circuit voltage and charge current:
1. Press and hold Acknowledge and Signal Silence control switches simultaneously for five
(5) seconds. As long as both keys are pressed, the battery voltage is displayed for three
(3) seconds, and then the battery current. These alternate every three (3) seconds.
2. The battery test will exit if either control switch is released, or if a control unit status
change occurs.
5-3.2.1
5-3.2.2
5-3.3
August 2007
5-2
P/N 06-236716-001
Lamp Test
Use the following procedures to perform the lamp/buzzer test.
1. Verify that the control unit is in normal standby mode with no alarms, troubles or
supervisory conditions.
2. Press and hold the Acknowledge control switch for a period of five (5) seconds. The LEDs
and the digital display characters will illuminate, and the buzzer will sound. This will
continue until the Acknowledge control switch is released, or there is a status change to
the control unit. This will enable malfunctioning LEDs/segments to be visually sighted.
P/N 06-236716-001
5-3
August 2007
August 2007
5-4
P/N 06-236716-001
Troubleshooting
CHAPTER 6
TROUBLESHOOTING
6-1
PURPOSE
This chapter provides diagnostic information, probable causes, and the method(s) to return the
Kidde AEGIS to proper operating conditions.
Prior to taking corrective action or performing any maintenance functions, you must refer to
Paragraph 5-1 and follow the instructions specified there.
6-2
TROUBLE DIAGNOSTICS
Diagnostics allow the operator to determine the cause of trouble. To access the diagnostic
function, the control unit needs to have at least one active trouble condition. Perform the
following:
Step
Description
Press and hold the Signal Silence control switch for five (5) seconds. A 3-digit
Trouble code will be displayed until the Signal Silence control switch is
released (sample on right).
If multiple troubles exist, the display will blink one second on, one second off,
and the trouble codes will sequence to the next code every time the display
illuminates. When all codes have been displayed, the sequence will repeat until
the Signal Silence control switch is released (sample on right).
6-3
Display Examples
Code
Trouble
Corrective Action
000
Microprocessor or PCB
001
Ground
002
003
Check power supply connector, from the power supply to main PCB
(PSU J2).
Replace the power supply assembly.
004
005
P/N 06-236716-001
6-1
August 2007
Troubleshooting
Code
Trouble
Corrective Action
006
Low Battery
Check battery voltage, must be greater than 20.5 Vdc in the absence
of primary power. When voltage drops as low as 19.5 Vdc, the
charger will disconnect and the outputs will be isolated.
007
Reversed Battery
008
009
010
011
013
014
Invalid Abort
015
016
017
018
019
020
021
022
023
024
025
026
027
028
August 2007
6-2
P/N 06-236716-001
Parts List
CHAPTER 7
PARTS LIST
Description
Part Number
84-732001-001
84-732001-201
Installation/Configuration Kit
06-220148-002
Operating Instructions
06-236719-002
06-220149-001
06-220172-002
06-220174-002
06-220176-001
06-220150-001
06-118394-002
Trim Ring
76-600000-007
06-220023-001
Battery Enclosure
76-100010-001
Dead-Front Panel
06-220175-001
06-220151-001
Spare Key
06-118013-001
06-129924-001
06-129963-002
Battery Harness
06-129925-002
P/N 06-236716-001
7-1
August 2007
Parts List
August 2007
7-2
P/N 06-236716-001
APPENDIX A
BATTERY CAPACITY CALCULATIONS
A-1
Standby
Alarm
Local or Central Station (Protected Premises) Fire Alarm Systems per NFPA 72
24 hours
5 minutes
Clean Agent Suppression Systems per NFPA 12, 12A, 12B, and 2001
24 hours
5 minutes
90 hours
10 minutes
A-2
Number
Component
100.00
240.00
1000.00 Max.
1000.00 Max.
Programmable Relays
0.00
20.00
0.07
70.00
0.07
70.00
0.00
70.00
NACs 1, 2, and 34
0.00
1500.00 each
0.00
Refer to Appendix B
0.00
0.00
Release - Initiators6
0.00
0.00
10
1
The standby and alarm values for the AEGIS include the Trouble Relay.
The Auxiliary Power Output current value stated is the maximum allowed.
3 The Standby current stated for Ionization, Photoelectric, Electronic Heat, Duct and Contact Heat Detectors is
for each detector. The Alarm current is for the Detection Circuit.
4 The current value stated for the Notification Appliance Circuits is the maximum each.
5
For the Alarm current values of Steady Release Solenoids, refer to Appendix B.
6
Momentary Agent Release Solenoids and Initiators are negligible in their current requirements and do not
need to be included in the calculation.
2
P/N 06-236716-001
A-1
August 2007
A-3.1
Procedure
1. Insert the actual count of components and devices into the Standby Quantity column.
2. Insert the quantity of these components devices which can be in alarm into the Alarm
Quantity column.
3. Multiply the quantity count by the Each Standby and Alarm Power and insert these
values into the Total column.
4. Calculate the sum of the values in the Total Standby and Total Alarm columns to arrive
at the Total Standby Power and Total Alarm Power in milliamperes.
5. Divide the mA values for Total Power in Amperes.
Table A-3. Standby and Alarm Calculation Guide
Number
Component
Qty
Each
Total
Qty
Each
Total
100.00
100.00
240.00
240.00
Programmable Relays2
0.00
0.00
20.00
0.00
0.00
70.00
Ionization Detectors
0.07
0.00
Photoelectric Detectors
0.07
0.00
0.07
0.00
0.07
0.00
0.00
0.00
0.00
10
NACs 1, 2, and 34
0.00
0.00
1500.00
11
Release Solenoids5
0.00
0.00
0.00
1000.00
1000.00
Total Power in mA
Total Power in Amperes
1
The Auxiliary Power Output current value stated is the maximum allowed. See Note 6 below.
The value stated for the Programmable Relays is for each individual relay when energized.
3 Standby currents should be considered for all Ionization, Photoelectric, Duct and Heat Detectors in the three
Detection Circuits. However, since only one detector can be in Alarm, the Alarm current should only be considered for the entire Detection Circuit.
4
The value stated for the NACs is the maximum for each. See Note 6 below.
5 For the Alarm current values of Steady Release Solenoids, refer to Appendix B.
6 Since the Power Supply of the Kidde AEGIS unit is rated at 5.4 Amps, the system designer should ensure
that the system circuits are loaded so as to keep the calculated alarm current equal to or less than 5.4
Amps.
2
August 2007
A-2
P/N 06-236716-001
Multiply
By
Duration
(Hours)
Equals
Ampere-Hour (AH)
(must be greater than or equal to required battery AH and lower than 68 AH)
Note: 1. The above battery capacity calculation and subsequent selection assumes that the
battery is installed in ambient room temperatures. If installed in below ambient, consult
the battery manufacturer for requirement of additional deration factors not considered
above.
2. 5 minutes = 0.083 hours
10 minutes = 0.167 hours
P/N 06-236716-001
A-3
August 2007
August 2007
A-4
P/N 06-236716-001
APPENDIX B
LIST OF AGENCY LISTED COMPATIBLE DEVICES
B-1
Model
Part Number
CPD-7051
70-510000-001
CPD-7051D
70-510000-060
CPD-7054
70-540000-001
CPD-7054D
70-540000-002
PSD-7155
71-550000-001
PSD-7155D
71-550000-060
PSD-7155P
71-550000-002
PSD-7156
71-560000-001
PSD-7157
71-570000-001
PSD-7157D
71-570000-002
THD-7052
70-520000-001
THD-7053
70-530000-001
2WB
70-501000-001
2WRLT
70-501000-002
2WRB
70-501000-005
2WRM
70-500000-004
DH-60-2W
70-600000-200
DH-60-2CPD
70-600000-251
DH-60-2ACD
70-600000-254
DH-60-2PSD
70-600000-255
DH-60-2APD
70-600000-257
4WRB
70-501000-101
DH-60
70-600000-000
DH-60-CPD
70-600000-051
DH-60-ACD
70-600000-054
DH-60-PSD
70-600000-155
DH-60-APD
70-600000-157
P/N 06-236716-001
B-1
August 2007
Resistance
(Max.)
Ohms
On Time
12
AWG
14
AWG
16
AWG
18
AWG
Max.
Number per
Circuits
Agency
890181
2.4
10
Momentary
300
200
120
1 or 2
UL, FM
895630
2.0
12
Momentary
300
200
120
1 or 2
UL, FM
899175
2.20
10.8
Momentary
300
200
120
1 or 2
UL, FM
48650001
0.24
103
Steady
3000
2000
1200
800
1 or 2
UL, FM
06-118329-001
0.225
108
Steady
3000
2000
1200
800
1 or 2
FM
06-118384-001
0.52
46
Steady
1440
760
480
340
1 or 2
UL
38-509834-001
0.632
38
Steady
1050
550
330
240
1 or 2
UL, FM
38-509837-001
0.4
60
Steady
2300
1460
915
570
1 or 2
UL, FM
81-100000-001
0.44
59
Steady
2300
1460
915
570
1 or 2
UL, FM
87-120099-001*
12
Momentary
360
240
140
1 or 2
UL, FM
60-120099-001*
12
Momentary
360
240
140
1 or 2
UL, FM
87-120099-600*
12
Momentary
360
240
140
1 or 2
UL, FM
897494-000
1.5
14.2
Steady
380
240
150
UL, FM
897494-530
1.5
14.2
Steady
380
240
150
UL, FM
12
Momentary
360
240
140
1 or 2
UL, FM
0.458
52
Steady
1440
760
480
340
FM
FM Group B, D
0.7
34
Steady
940
500
300
220
FM
FM Group E, G
0.42
57
Steady
1570
760
525
370
FM
Device
90-487100-001*
FM Group A
FM Group F
FM
FM Group I
FM
FM Group J
Viking Model No. 11591, 11592, 11595, and 11596, 24 Vdc, 10 Watts
FM
FM Group K
FM
* Must be used in conjunction with Microswitch P/N 87-120039-001 for momentary operation.
Device
83-131025-001
I (Min.)
Amps
Resistance
(Max.) Ohms
On Time
Max. Number
per Circuits
Momentary
Agency
* The maximum circuit resistance for this device must be 10 ohms, regardless of the number used. The firing current will be
2.5 Amps.
August 2007
B-2
Model Number
Supplier/Mfg.
5104B
Silent Knight
P/N 06-236716-001
Technical Specifications
APPENDIX C
TECHNICAL SPECIFICATIONS
Item
A
NUMBER OF HAZARDS
POWER
AC Main Input
Description
One (1)
Current Consumption
120 Vac:
240 Vac:
C
C.1
3.2 Amps
1.6 Amps
Required Breaker
15 Amps
6 Amps @ 27 Vdc
Battery Capacity
Up to 68 AH @ 24 Vdc
18.6 Vdc
Battery Transfer
Input Circuits
Detection Circuits
Three (3)
- Two (2) for Suppression Input
- Third configurable as either independent Detection Circuit or
for Waterflow
Compatible Devices
Circuit Type
Circuit Voltage
70 mA
End-of-Line Resistor
P/N 06-236716-001
C-1
August 2007
Technical Specifications
Item
C.2
Manual Release
Description
One (1)
Compatible Devices
Circuit Type
C.3
Circuit Voltage
Maximum Current
10 mA
End-of-Line Resistor
Abort Input
One (1)
Compatible Devices
Circuit Type
C.4
Circuit Voltage
Maximum Current
10 mA
End-of-Line Resistor
Supervisory Input
Two (2)
Compatible Devices
Circuit Type
Circuit Voltage
Maximum Current
10 mA
End-of-Line Resistor
August 2007
C-2
P/N 06-236716-001
Technical Specifications
Item
D
D.1
Description
OUTPUT CIRCUITS
Notification Appliance
Three (3)
- NAC 1: First Alarm Condition
- NAC 2: Pre-Release Condition
- NAC 3: Release Condition
Compatible Devices
Circuit type
D.2
Circuit Voltage
2V
End-of-Line Resistor
Output Relays
Four (4)
- Programmable: Three (3), normally de-energized with power on
- Trouble: One (1), normally energized with power on
D.3
Relay Type
Contact Rating
Releasing Circuits
Two (2)
- ARC 1
- ARC 2
Compatible Devices
Releasing Configurations
Circuit Type
Operating Voltage
End-of-Line Resistor
Not required
P/N 06-236716-001
C-3
August 2007
Technical Specifications
Item
E
Description
ENCLOSURE
Degree of Protection
NEMA 1
Material of Construction
Color
Red
Assembled Dimensions
- With Standard Door
- With Switch-Door
18 lbs. (8 kg)
- Standard Shipping
21 lbs. (9 kg)
4 lbs. (2 kg)
19 lbs. (8 kg)
21 lbs. (10 kg)
OPERATING ENVIRONMENT
Temperature
Relative Humidity
93% RH @ 90F
August 2007
C-4
P/N 06-236716-001
APPENDIX D
FM RULES FOR PREACTION/DELUGE SYSTEMS
Kidde AEGIS applications which require Factory Mutual (FM) approved Pre-Action and/or
Deluge Systems must conform to the following guidelines:
Detection Zone 1 (Det1), Detection Zone 2 (Det2) and Waterflow (W'Flow) Initiating
Circuits must be configured for Class A, Style D wiring.
The Battery backup system must provide for 90 hours of Standby operation followed by 10
minutes of Alarm operation. Refer Appendix A for calculations.
The Agent Release Output must be configured for Deluge Solenoid activation. The Solenoid
Activation Time must be set either for:
10 minutes, or
15 minutes, or
On-until-reset.
The wiring connection of the Control Unit to the Deluge Solenoids must be as detailed in the
Installation section of this Manual.
P/N 06-236716-001
D-1
August 2007
August 2007
D-2
P/N 06-236716-001
APPENDIX E
CENTRAL STATION OPERATION
The Kidde AEGIS should be configured for Central Station operation as follows:
One of the three (3) Programmable Relays should be configured for any alarm. For
example:
2,
3, OR
4
The Trouble Relay should be set to delay AC Failure Response by a period acceptable to
the local AHJ. For example:
15
4.7K
1 2 3 4 5 6 7 8 9 10 1112
TROUBLE
RELAY
NO NC C
TB 8
PROGRAMMABLE
RELAYS
4.7K
NO NC C
TB 9, TB10, or TB11
SUPERVISORY
PROGRAMMABLE
RELAYS
4.7K
NO NC C
TB 9, TB10, or TB11
PROGRAMMED FOR
GENERAL ALARM
CONTROL PANEL
P/N 06-236716-001
E-1
August 2007
August 2007
E-2
P/N 06-236716-001
APPENDIX F
ROUTINGS FOR POWER-LIMITED AND
NON-POWER-LIMITED WIRING
This appendix provides guidelines for power-limited and non-power-limited wiring requirements.
The following wiring requirements shall be observed:
All power-limited wiring must be separated by at least 1/4-inch (6 mm) from any
non-power-limited wiring
Power-limited and non-power-limited wiring cannot enter and exit the control-unit
enclosure through the same knockout or conduit.
Figure F-1 shows typical wiring for power-limited and non-power-limited circuits.
TB7
TB6
TB5
TB4
TB3
TB2
TB8
TB1
TB9
TB10
TB11
TB12
TB14
TB15
TB16
TB17
TB18
TB13
RELEASE CIRCUITS
(TB14 AND TB15) CAN BE
WIRED AS POWER-LIMITED
OR NON-POWER-LIMITED
BATTERY WIRING
P/N 06-236716-001
F-1
August 2007
August 2007
F-2
P/N 06-236716-001
These instructions do not purport to cover all the details or variations in the equipment
described, nor do they provide for every possible contingency to be met in connection with
installation, operation and maintenance. All specifications subject to change without notice. Should further information be desired or should particular problems arise which are
not covered sufficiently for the purchasers purposes, the matter should be referred to
KIDDE-FENWAL INC., Ashland, Massachusetts