Kodiak Recirculating Chillers: Technical Manual
Kodiak Recirculating Chillers: Technical Manual
Kodiak Recirculating Chillers: Technical Manual
RC006, RC009, RC011, RC022, RC030 and RC045 G03, H03 and J03 Series
TECHNICAL MANUAL
Lytron Inc., 55 Dragon Court, Woburn, MA 01801, USA Tel: +1-781-933-7305 Fax: +1-781-935-4529 www.Lytron.com
Lytron Inc., 2010
Manual # 820-0109, Rev. Y, 07/23/10
TABLE OF CONTENTS
TABLE OF CONTENTS....................................................................................................................................................... 1 REVISION HISTORY........................................................................................................................................................... 3 INTRODUCTION.................................................................................................................................................................. 4 SAFETY PRECAUTIONS .................................................................................................................................................... 5 LABELS AND SILKSCREEN MARKING......................................................................................................................... 6 PART NUMBER DESCRIPTION ....................................................................................................................................... 8 SPECIFICATIONS................................................................................................................................................................ 9 PERFORMANCE GRAPHS............................................................................................................................................... 10 GENERAL INFORMATION ............................................................................................................................................. 11 CONTROLLER DISPLAY PANEL FUNCTIONS .......................................................................................................... 12 REAR PANEL COMPONENTS ........................................................................................................................................ 13 OPTIONAL SYSTEM FEATURES................................................................................................................................... 14 CONTROLLER OPTIONS ................................................................................................................................................ 16 INSTALLATION REQUIREMENTS ............................................................................................................................... 17 INSTALLATION PROCEDURE ....................................................................................................................................... 18 PRIMING TURBINE AND CENTRIFUGAL PUMPS.................................................................................................... 19 CONNECTING POWER (FOR UNITS WITHOUT HEATER OPTION).................................................................... 20 CHILLER OPERATION .................................................................................................................................................... 21 SYSTEM MAINTENANCE AND SERVICE ................................................................................................................... 24 DRAINING PROCEDURE FOR KODIAK CHILLERS ................................................................................................ 26 COOLANT MAINTENANCE ............................................................................................................................................ 27 ERROR CODES................................................................................................................................................................... 28 TROUBLE SHOOTING GUIDE........................................................................................................................................ 29 KODIAK SPARE PARTS ................................................................................................................................................... 31 ACCESSORIES FOR THE KODIAK RECIRCULATING CHILLER......................................................................... 32 FRONT VIEW...................................................................................................................................................................... 33
-1-
Check Lytrons website www.Lytron.com for the most current technical information.
Kodiak Recirculating Chiller Technical Manual REAR VIEW (WITH PANEL)........................................................................................................................................... 34 TOP VIEW ........................................................................................................................................................................... 35 REAR VIEW (OPENED).................................................................................................................................................... 36 SIDE VIEW .......................................................................................................................................................................... 37 SIDE VIEW (WITH HIGH PRESSURE CUTOUT) ....................................................................................................... 38 CHILLER DIMENSIONS FOR RC011 AND RC022...................................................................................................... 40 CHILLER DIMENSIONS FOR RC030 AND RC045..................................................................................................... 41 WIRING DIAGRAM........................................................................................................................................................... 42 PLUMBING DIAGRAM..................................................................................................................................................... 42 PLUMBING DIAGRAM..................................................................................................................................................... 43 REFRIGERATION DIAGRAM ........................................................................................................................................ 44 HOST INTERFACE DATA LINK .................................................................................................................................... 44 HOST INTERFACE DATA LINK .................................................................................................................................... 45 LYTRON COOLING SYSTEMS SERVICE POLICY ................................................................................................... 48 LYTRON KODIAK RECIRCULATING CHILLER STANDARD WARRANTY ...................................................... 50 DECLARATION OF CONFORMITY.............................................................................................................................. 51
-2-
Check Lytrons website www.Lytron.com for the most current technical information.
REVISION HISTORY
REV Y ECN / DATE 17284 / 07/08/2010 REASON FOR CHANGE Updated Declaration of Conformity and safety symbols.
-3-
Check Lytrons website www.Lytron.com for the most current technical information.
Service Hotline
Lytron has a 24-hour per day, 7 day per week service hotline to help you with questions on the startup and operation of your Kodiak recirculating chiller. (Lytron recommends consulting the troubleshooting guide on page 29 before calling the service hotline.) Lytron service can be reached by dialing +1-781- 933-7300. To facilitate your call please have the model number and serial number (located on rear of the chiller) of the unit for the Lytron Service Technician.
-4-
Check Lytrons website www.Lytron.com for the most current technical information.
SAFETY PRECAUTIONS
This system is designed to provide fluid cooling only as specified in this manual. If this system is used in a manner other than as specified, the safety protection of the system may be impaired. Warnings are posted throughout the manual. Read and follow these important instructions. Failure to observe these instructions or use the chiller other than as specified may impair safety protection, void the warranty, and can result in permanent damage to the unit, significant property damage, personal injury, and/or death. Make sure you read, understand, and follow all instructions and safety precautions listed in this manual before operating your unit. If you have any questions concerning the operation of your unit or the information in this manual, please contact our Applications Engineering Department at +1-781- 933-7300. Always turn the unit "OFF" and disconnect the power cord from the power source before performing any service, maintenance procedures or before moving the unit. Do not operate equipment with damaged power cords. A qualified technician should perform Service and repairs. If the set point is 10 C (50 F) or below, a freezing point depressant, such as ethylene glycol, is required. This unit is equipped with a low flow switch. This feature will shut the chiller down during a low flow situation to prevent freezing. DO NOT USE AUTOMOTIVE ANTI-FREEZE IN THE CHILLER. The rust inhibitors in the automotive type may cause premature failure of the pump seals. Use of automotive anti-freeze in a Lytron chiller will void the warranty. Never place the unit in a location where excessive heat, moisture, or corrosive materials are present. The unit must be plugged into a properly grounded power source. Do not connect the SUPPLY or RETURN fitting to your building water supply or any pressurized source. DO NOT USE OR MAINTAIN THE CHILLER OUTDOORS. These units were not designed to withstand outdoor weather conditions. Performance of installation, operation, or maintenance procedures other than those described in this manual may result in a hazardous situation and may void the Lytron warranty. Transport the unit with care. Sudden jolts or drops can damage the unit. Drain the chiller of all water when transporting, shipping or leaving unused for long periods of time. This will prevent freezing and algae build up while idle. Observe all warning labels. Never remove warning labels. Do not operate damaged or leaking equipment. Do not operate the unit without fluid in the reservoir.
-5-
Check Lytrons website www.Lytron.com for the most current technical information.
RS-232
RETURN SUPPLY
This silk-screen marking identifies the connection where heated fluid is returned from the users machine. This silk-screen marking identifies the connection where chilled fluid is supplied to the users machine.
The markings on this label certifies that the equipment has been certified to the UL standard 61010A-1 and CAN/CSA STD C22.2 No. 1010.1 standards.
The symbol on this label identifies that the equipment has been certified to regulations of the European Community.
-6-
Check Lytrons website www.Lytron.com for the most current technical information.
The product ID label identifies the model number, serial number, electrical information, pump type, refrigerant type, charge, and date of manufacture of the product.
The crossed out wheeled bin label requires that the product be disposed of or recycled with the requirements of local law.
The RoHS compliant label indicates that the product complies with the European union restriction of hazardous substances (RoHS) directive.
This label indicates that none of the six hazardous substances are present in the product above the maximum concentration values in its homogeneous form per China RoHS.
This label indicates which of the six hazardous substances are present in the product above the maximum concentration values in its homogeneous form and the environmental protection use period of the product per China RoHS.
-7-
Check Lytrons website www.Lytron.com for the most current technical information.
Electrical Configurations
Pump Options
Controller Configuration CONTROLLER PACKAGE #1 1. 2. 3. 4. 5. 6. Alarm Mute Audible Alarm Auto-Restart Calibration Offset Deg C / Deg F Toggle Digital Temperature Display 7. Low Flow Shut-Off Fault CONTROLLER PACKAGE #2: 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. Alarm Mute Audible Alarm Auto-Restart Calibration Offset Deg C / Deg F Toggle Digital Pressure Sensing & Display Digital Temperature Display Fault Shut-Off (toggle on/off) Low Flow Shut-Off Fault Low Level Fault Low Temp / High Temp Fault Relay Contacts
Std. Modification
G03 = 115V~/1ph/60Hz AA* = CP-15 Centrifugal Pump RC009 1,050 Watts H03 = 230V~/1ph/50Hz BB (CB) = 1.3 gpm RC011 1,650 Watts J03 = 230V~/1ph/60Hz Positive Displacement Pump RC022 2,400 Watts BC (CC) = 1.8 gpm Positive Displacement RC030 3,450 Watts Pump RC045 5,900 Watts BE (CE) = 2.3 gpm Positive Displacement Pump BG (CG) = 4.3 gpm Positive Displacement Pump DA* = CP-25 Centrifugal Pump EB* (FB) = 1/4 Hp Turbine Pump EC* (FB) = 1/6 Hp Turbine Pump Note: Cooling capacity and pump flows are rated at 60Hz. For 50Hz power capacity is reduced by 17%. Notes:
CONTROLLER PACKAGE #3: Same as "PKG 2" above with the addition of RS-232 communications.
Indicates high
purity compatible pump. NOTE: Refer to the product ID label on the on the rear of your chiller for the configuration you have purchased. The table above refers to Lytrons standard product offering for the Kodiak product line.
-8-
Check Lytrons website www.Lytron.com for the most current technical information.
SPECIFICATIONS1
RC006
Thermal Capacity2 Watts BTU/hr 115V~ 60Hz 1ph 230V~ 50Hz 1ph 230V~ 60Hz 1ph Full Load Amps3 G03 J03 H03 Compressor Size Refrigerant Type Temperature Stability Operating Environment Coolant Temperature Range4 Reservoir Capacity Dimensions5 Width Depth Height Connection Weight Process Coolant Delivery Pressure
1 2
RC009
60Hz 50Hz 1,050 875 3,585 2,988 G03 H03 J03
RC011
60Hz 50Hz 1,650 1,400 5,780 4,760 G03 H03 J03
RC022
60Hz 50Hz 2,400 2,150 8,755 7,310 N/A H03 J03
RC030
60Hz 50Hz 3,450 2,950 12,070 10,030 N/A H03 J03
RC045
60Hz 50Hz 5,900 4,950 20,230 16,830 N/A H03 J03
9.9 A --4.5 A Hp R134A 0.2F (0.1C) 50F to 95F (10C to 35C) 41F to 95F (5C to 35C) 1 gal (3.8 l)
12.2 A 5.8 A 5.3 A 1/3 Hp R134A 0.2F (0.1C) 50 F to 95F (10C to 35C) 41F to 95F (5C to 35C) 1 gal (3.8 l)
14.3 A 7.4 A 6.3 A Hp R134A 0.2F (0.1C) 50F to 95F (10C to 35C) 41F to 95F (5C to 35C) 2 gal (7.6 l)
--10.0 A 9.5 A Hp R134A 0.2F (0.1C) 50F to 95F (10C to 35C) 41F to 95F (5C to 35C) 2 gal (7.6 l)
--14.5 A 13.7 A 1 Hp R134A 0.2F (0.1C) 50F to 95F (10C to 35C) 41F to 95F (5C to 35C) 6 gal (22.6 l)
--19.6 A 17.2 A 1 Hp R134A 0.2F (0.1C) 50F to 95F (10C to 35C) 41F to 95F (5C to 35C) 6 gal (22.6 l)
12.5" (318) 19.0" (483) 22.0" (559) FNPT 97 lbs (44 kg)
12.5" (318) 19.0" (483) 22.0" (559) FNPT 100 lbs (45 kg)
14.8" (376) 24.5" (622) 26.5" (673) FNPT 122 lbs (55 kg)
14.8" (376) 24.5" (622) 26.5" (673) FNPT 166 lbs (75 kg)
21.4" (543) 27.8" (705) 31.0" (787) FNPT 260 lbs (118 kg)
21.4" (543) 27.8" (705) 31.0" (787) FNPT 270 lbs (123 kg)
Specifications are subject to change. Capacity is for 20C delivery water at a 20C ambient. 3 Full load amperage for air -cooled models with standard pumps without the optional heater. Standard pumps are the BB for the RC006, RC009, RC011, RC022 and BG for the RC030 and RC045. Contact Lytron for current draw of other models. 4 Chiller will shut down when coolant temperature reaches 10C above the coolant temperature range. 5 Dimensions do not include filters or external valves.
-9-
Check Lytrons website www.Lytron.com for the most current technical information.
PERFORMANCE GRAPHS
Temperature represents output temperature of water assuming 20C ambient air conditions. Performance subject to change due to variations such as: fluid type or operating conditions.
Manual # 820-0109, Rev. Y, 07/08/10
- 10 -
Check Lytrons website www.Lytron.com for the most current technical information.
GENERAL INFORMATION
Chiller System Description
Your chiller consists of a refrigeration system, a coolant loop, associated controls and plumbing. The pump draws coolant from the internal reservoir and pumps it out to cool the process equipment, and then the coolant flows back to the chiller. The fluid then flows through the evaporator, where the heat is removed, and then back to the reservoir.
Coolant Loop
Kodiak chillers are designed to operate with continuous coolant flow through a closed loop. This loop contains the system pump, temperature sensor, reservoir, internal and external plumbing lines and fittings, and the external heat load. The external plumbing and the heat loads are provided by the end user and are generally unique to the users process or location.
- 11 -
Check Lytrons website www.Lytron.com for the most current technical information.
Controller Display
Key
Turn on/off chiller Displays Pressure briefly
Operation
UP + DOWN +
Enter menu (press simultaneously and hold for 3 seconds and release) Push to display or change set point Increase set point temperature Decrease set point temperature Alarm Sound disabled or Muted (alarm will stay muted until error is corrected, then resets)
DESCRIPTION OF INDICATORS
Temperature Set Point Pressure Display Cooling Indicator Low Flow Indicator Alarm Indicator Low-Level Indicator Over Temperature Indicator Low Temperature Indicator Displays coolant temperature or set point in C or F. Displays outputs pump pressure in PSI/bar digitally for a few seconds. Solenoid valve is open and chiller is cooling the process fluid when this light is illuminated. Indicates that the minimum flow requirement of the chiller is not being satisfied. Illuminates to indicate an alarm fault condition. Illuminates to indicate a low fluid level in the tank. Illuminates to indicate water temperature is above high temperature alarm set point. Illuminates to indicate water temperature is below low temperature alarm set point.
- 12 -
Check Lytrons website www.Lytron.com for the most current technical information.
CIRCUIT BREAKER
POWER ENTRY
RS232
FLUID IN TO CHILLER
14 25
- 13 -
Check Lytrons website www.Lytron.com for the most current technical information.
Deionization Package
The Deionization Package consists of a factory-installed deionization cartridge. The deionization cartridge requires replacement only when the mixed bed is depleted. For replacement cartridges, Call Lytrons Customer Service at 781-933-7300. This package is offered for deionized water applications where the resistance of the water does not exceed 1 Mega-ohm-cm. The deionization package is not recommended with centrifugal pumps.
Remote Start
This option allows the Kodiak chiller to be started or stopped through a computer or a relay. The chiller can e run using a normally open circuit or normally closed. (Look under the section labeled Chiller Operation for more details) R.S. contacts are located on the rear left of the chiller shown previously. It is a six-pin connector with pins 1 and 2 controlling R.S. The mating connector is an Amp 350715-1 plastic housing. The pins are Amp 350547-1. The controlling relay should have SPDT type contacts rated for low current less than or equal to 5VDC at 0.1 milliamp.
- 14 -
Check Lytrons website www.Lytron.com for the most current technical information.
- 15 -
Check Lytrons website www.Lytron.com for the most current technical information.
- 16 -
Check Lytrons website www.Lytron.com for the most current technical information.
- 17 -
Check Lytrons website www.Lytron.com for the most current technical information.
Connecting Plumbing
To connect the fluid lines to the chiller and user equipment follow these steps: 1. Remove the plastic caps covering the supply and return ports on the rear panel of the unit. 2. Attach coolant lines to the supply and return ports on the rear panel. Fittings should either be brass, Never use steel or cast iron fittings, as the corrosion will damage stainless steel or nylon. the chiller. For chillers with de-ionization cartridges or high purity plumbing Lytron recommends the use of either stainless steel or nylon fittings. The supply port provides chilled coolant to the users equipment. The return port connects to the outlet of the users equipment. 3. Check that fittings are tight to prevent leaks. 4. Remove water filler cover on top of the unit to access the reservoir. 5. Fill the reservoir. Use the reservoir sight tube on the front of the unit to see the coolant level in the tank during filling. Be sure to allow for the volume of coolant needed to fill the cooling lines between the chiller and the equipment, if they were not filled with coolant before installation. 6. If the system is a water-cooled chiller, connect facility water to connections labeled "City Water In" and "City Water Out". Minimum flow rate of facility water is shown on page 15. Facility water flow must be started before chiller is turned on.
- 18 -
Check Lytrons website www.Lytron.com for the most current technical information.
Units equipped with priming valve. The priming valve circuit is located between the pump discharge plumbing line and the top of the tank. There is a valve labeled pump priming valve located in this line. To prime the pump simply open this valve prior to starting the chiller (photo a). Start the chiller. After flow is observed returning to the tank, close the priming valve (photo b). Units that do not have a priming valve. To prime pumps that do not have a priming valve, disconnect the supply line from the rear of the chiller. Allow time for the fluid to gravity feed into the pump housing. If there is difficulty priming the pump using this method, use a wet vac to assist in drawing the fluid from the tank into the pump housing.
2.
Note: If the pump has failed to prime turn the chiller off and contact Lytrons Service Department - 781-933-7300.
- 19 -
Check Lytrons website www.Lytron.com for the most current technical information.
Startup Procedure
1. Turn "ON" the circuit breaker on the rear of the unit. The controller will go through a diagnostic test. Turn on the chiller unit using the top left key located on the Keypad Display panel. The controller displays "OFF" for 8 seconds. The delay prevents rapid cycling of the compressor using the "ON" and "OFF" switch. If your chiller is equipped with control package 2 or 3 the fault shut off may prevent the chiller from starting up. If the chiller displays an alarm after pushing the ON button disable the fault shutoff on the customer menu and restart the chiller. 2. Adjust the temperature set point using the controls on the keypad display as follows: Press the SET key once to display the current coolant temperature set point. Press the UP or DOWN arrow key until the desired coolant temperature set point appears on the LED display. Press the SET key again to accept the set point and return to normal operation. 3. Operate the chiller for a short time and then check the coolant level in the reservoir. If the level drops, add more coolant. 4. Check all fittings and hoses for fluid leaks. If a leak exists turn chiller off, disconnect power and take necessary action to repair the leak.
Please Note:
During initial start up the temperature display may occasionally appear to be dim. This is a normal occurrence and does not indicate that there is problem with the chiller. After 10 seconds the display will brighten to its normal level.
- 20 -
Check Lytrons website www.Lytron.com for the most current technical information.
CHILLER OPERATION
The following sections explain how to perform other operations with the chillers controller, using the keys and display on the front of the unit. Refer to the Controller Display Panel Functions section in this manual. In normal operation the display shows the current temperature of the coolant (or the current temperature with an offset applied).
Function
English or Metric Units Changes the temperature readings on the display from C to F and pressure from Bar to PSI. Calibration Offset Adjusts the reading on the display by the offset that you enter, from -4C to 4C (-7F to 7F). Auto Restart When enabled this allows the chiller to start automatically in the event of a power failure. Over temperature Fault Indication (option) Indicator illuminates when the coolant temperature exceeds the overtemperature set point. The over-temperature set point should be at least 3C (6F) above the coolant set point to prevent nuisance alarms. Low-temperature Fault Indication (option) Indicator illuminates when the coolant temperature falls below the lowtemperature set point. The low-temperature set point should be at least 3C (6F) below the coolant set point to prevent nuisance alarms. Audible alarm (option) When this is enabled, an audible alarm sounds when any fault occurs. *Fault chiller shutoff (option) When enabled, this turns off the chiller when any fault occurs. Remote Start (option) Allows the chiller to be started and stopped with a dry contact. Pressure Units (option) Allows the chiller to display the pressure in units of bar or psi. When bar is ON pressure is displayed in units of bar, in the format X.XX b. When bar is off, the pressure will be shown in psi, in the format XX p.
CAL
Ar
Ot
Lt
AL
FS
rS
bAr
- 21 -
Check Lytrons website www.Lytron.com for the most current technical information.
- 22 -
Check Lytrons website www.Lytron.com for the most current technical information.
bArPressure Units
1. 2. 3. 4. To enter the menu, press and hold both the UP and DOWN arrow keys for 3 seconds. Use the SET key to scroll to bAr. The display toggles between bAr and its current setting. Use UP or "DOWN" arrow key to toggle between ON and OFF. ON will display the units in bar and OFF will display the units in psi. 5. Press, SET to accept the setting on the display and continue to the next feature.
- 23 -
Check Lytrons website www.Lytron.com for the most current technical information.
Periodic Inspections
Noise Level
Any abnormal sounds or a substantial increase in noise level since the last weekly inspection may indicate the following: impending pump, fan or coolant blockage problem. Investigate the cause and perform the necessary service. Refer to the troubleshooting guide in this manual.
Leakage
If you notice coolant on the floor near the chiller or dripping from the chiller enclosure turn off the chiller. Disconnect the power cord. Find and repair any leaks immediately.
Coolant Level
Any significant drop in the coolant level should be investigated further. If there is no visible system leak, then the loss may be due to equipment leakage elsewhere.
Pump / Motor
Some pumps may require lubrication. If the pump needs lubrication, lubricate annually with 20-30 drops of SAE Oil.
Fan Assembly
No maintenance is required on the fan. Listen for any abnormal sounds.
Condenser Fin
Remove the front grill by sliding it upward, pulling the bottom out and pulling it straight down. For maximum performance the condenser fin should be free of dust and debris. Use a vacuum cleaner or compressed air to remove any debris and keep the fin clean.
Water Filter
With a new system the filter quickly accumulates foreign matter introduced during system setup. This can lead to a decrease in system performance in a short period of time. Inspect the filter cartridge one day after you set up a new system to ensure the filter is clean and the system runs at maximum capacity. After this initial filter inspection, check the filter weekly. For replacement filters contact Lytrons Customer Service at 781-933-7300.
Deionization Package
The cartridge life is a function of the users application. Check the water resistively weekly and change the cartridge as required. For replacement filters contact Lytrons Customer Service at 781-933-7300.
- 24 -
Check Lytrons website www.Lytron.com for the most current technical information.
Algae
Lytron recommends the use of an algae inhibitor to prevent growth in the reservoir.
Pump Strainer
All positive displacement pumps have a strainer to protect the vanes inside the pump. For pumps less than 2.5 gpm it is located in the pump housing. For larger PD pumps it is installed in the hose between the pump and the tank. Periodically inspect and clean the pump strainer. If it becomes fouled the flow rate will decrease and the pump may wear prematurely. The strainer can be cleaned by rinsing it in warm water and brushing it gently. For a detailed procedure in cleaning the pump strainer visit the Maintenance and Troubleshooting section of Lytrons website at www.Lytron.com.
Pumps
As a precaution, the pump must be periodically replaced. This will avoid damaging the unit and the cost associated with excessive downtime. Typical operating life of the pump depends on pump type.
Pump Model Positive Displacement Centrifugal Turbine Note: Please contact Lytron for pump pricing and delivery.
- 25 -
Check Lytrons website www.Lytron.com for the most current technical information.
- 26 -
Check Lytrons website www.Lytron.com for the most current technical information.
- 27 -
Check Lytrons website www.Lytron.com for the most current technical information.
ERROR CODES
There are a few different error codes that can occur during the operation of the chiller. These error codes are displayed on the front keypad of the system. See below for an explanation of each error code.
- 28 -
Check Lytrons website www.Lytron.com for the most current technical information.
Fault shutoff enabled. Low flow shut off will cause the chiller to stop after 10 seconds. Unit does not start or shuts off shortly after starting. Low Voltage. Cooling load exceeds cooling capacity. Controller set point temperature is too high. Condenser coil fouled with dust or debris. Unit has tripped the high-pressure cutout (RC030, RC045 and water cooled units only.) (See Pg. 38) Compressor has tripped its internal overload. Liquid refrigerant in the suction line to the compressor. Unit has tripped the high-pressure cutout (RC030, RC045 and water cooled units only.) (See Pg. 38) Low voltage or wrong voltage to unit. Noisy compressor Unit stored in cool environment for a long period may have collected liquid refrigerant in the compressor. Pump shaft seal damage Noisy pump motor Excessive pressure drop. Positive displacement pump is worn out. Pump motor overheats Audible alarm stays on (Control Package II and III only) Improper voltage to the system. Obstruction in pump head. Low level in reservoir Level switch is stuck. Level switch is damaged.
Excessive noise on startup Excessive Pressure in facility water (water-cooled unit only)
- 29 -
Check Lytrons website www.Lytron.com for the most current technical information.
Problem
Possible Cause
Low temperature alarm is set too close to cooling set point temperature. High temperature alarm is set too close to cooling temperature set point. Pump suction strainer is clogged. (Positive displacement pumps only.) Low coolant level or no coolant in the reservoir. Water filter dirty or clogged. Pressure relief on the pump is set too low. (Positive displacement and turbine pumps only.) Restriction in coolant lines external to the chiller. Pump overload has tripped. Leaks in external piping. Pump motor shaft is bound. Damaged pump. Shutoff feature is enabled in the controller set up menu. (Controllers with options II and III)
Recommended Remedy
Adjust low temperature alarm set point. Adjust high temperate alarm set point. Remove strainer, clean and reassemble. Check for leaks. Repair any leaks and fill reservoir. Change filter cartridge. Adjust the pressure relief to 90 psig. For a high-pressure application (over 90 psig) contact Lytron Applications Engineering. Eliminate restrictions in the lines. Open any valves. Turn unit off. Wait for overload to cool. It will reset on its own in 30 minutes or less. Repair leaks. Replace pump motor. Replace pump. Find out and correct the fault that is causing the shutoff. Disable shutoff feature (see controller set up). See Low Coolant Flow Process fluid temperature has reach a temperature higher than the systems design temperature. Verify values in the controller, including offset. Reset as necessary. Reset temperature offset. Reduce line length or increase line diameter. Reset pressure relief to 90 psig. Wait 5 to 10 seconds and the display will brighten to its normal level.
Temperature display reads incorrectly Recirculating pressure is too high Temperature display dim at start up.
Temperature set point is not set properly. Offset incorrectly set. Pressure drop through system is too large. Pump internal pressure relief is set too high. This is a normal part of the start up process. It does not indicate that there is a problem.
- 30 -
Check Lytrons website www.Lytron.com for the most current technical information.
Description
Controller PCB Circuit Breaker 115V Circuit Breaker 230V2 Pump and Compressor Relay Pressure Transducer, Brass Pressure Transducer, Stainless Steel Pressure Transducer, Plastic Temperature Sensor (RTD) Tank Low Level Switch Upper Front Panel Keypad Cover Access Panel Side Panel Front Grille Casters with lock Casters without lock Rear Panel Hot Gas Bypass Valve Solenoid Valve Heat Exchanger Capillary Tube Liquid Line Filter Dryer Condenser Compressor Condenser Fan Flow Switch
RC006/RC009
RC030/RC045
230-0874-P1 230-0593 230-0588 230-0592 101903-03 230-1006 230-1007 230-0603 250-0072 340-0020 340-0018 230-0892 340-0012 340-0014 230-0947 330-1139-06 330-1165-06 330-0880-06 330-1138-06 330-1166-06 340-0013 340-0015 531-0026 531-0027 330-1141 330-1167
N/A 230-0591
All of these parts require service by a qualified refrigeration technician. Please contact Lytron if you have any problems with one of these parts.
Please include model and serial number when ordering the controller PCB so they may be correctly programmed. Chillers with a heater require a different circuit breaker. Contact Lytrons Customer Service at +1-781-933-7300 for additional information.
2
- 31 -
Check Lytrons website www.Lytron.com for the most current technical information.
Item #
* 6A1
- 32 -
Check Lytrons website www.Lytron.com for the most current technical information.
FRONT VIEW
(Reference Spare Parts List in this manual)
ACCESS PANEL 13
COVER 12
SIDE 14
- 33 -
Check Lytrons website www.Lytron.com for the most current technical information.
CIRCUIT BREAKER 3
REAR PANEL 17
- 34 -
Check Lytrons website www.Lytron.com for the most current technical information.
TOP VIEW
(Reference Spare Parts List in this manual) PUMP AND COMPRESSOR RELAY 4
TANK 8
MOTOR 2
FLOW SWITCH 9
- 35 -
Check Lytrons website www.Lytron.com for the most current technical information.
20 HEAT EXCHANGER
21 CAPILLARY TUBE
- 36 -
Check Lytrons website www.Lytron.com for the most current technical information.
SIDE VIEW
(Reference Spare Parts List in this manual)
FLOW SWITCH 26
COMPRESSOR 24 25
19 SOLENOID VALVE
23 CONDENSER
- 37 -
Check Lytrons website www.Lytron.com for the most current technical information.
RESET BUTTON
- 38 -
Check Lytrons website www.Lytron.com for the most current technical information.
- 39 -
Check Lytrons website www.Lytron.com for the most current technical information.
- 40 -
Check Lytrons website www.Lytron.com for the most current technical information.
- 41 -
Check Lytrons website www.Lytron.com for the most current technical information.
WIRING DIAGRAM
- 42 -
Check Lytrons website www.Lytron.com for the most current technical information.
PLUMBING DIAGRAM
- 43 -
Check Lytrons website www.Lytron.com for the most current technical information.
REFRIGERATION DIAGRAM
- 44 -
Check Lytrons website www.Lytron.com for the most current technical information.
1.3 Encoding
All characters are to be ASCII characters. All messages from the host to the control and from the control to the host will have 0x10 (ASCII Line Feed) as a start-of-message delimiter, and 0x0D (ASCII Carriage return) as an end-of-message delimiter. Permitted message characters are in the range of 0x20 through 0x7F (hexadecimal).
1.5 Units
All temperature values will be communicated in two byte hex values of Cx100 (.01 C). Resolution of temperature values is .1 degree. All pressure values will be communicated in integer psi with no offset.
1.6 Commands 1.6.1 1.6.2 The following host Control messages are defined: Read Chiller Status
This command (R) will cause the Chiller Control to return a complete status string with the following form: ^JR ControlFlags AlarmFlags PlantTemp SetTemp Pressure ^M Where: ControlFlags Status in Bit encoded Byte (2 chars). Assignments are: Bit 7: Bit 6: Bit 5: Bit 4: Bit 3: Bit 2: Bit 1: Bit 0: (MSB); Machine on: Expansion Relay2 on: Expansion Relay1 on: Heater on: Autopilot: Condenser Relay on: Cool Valve On: (LSB); Celsius Display on: Lights the temperature display and pressure indicator bar Not used by host program Not used by host program Not used by host program Not used by host program Not used by host program Light the Cool Status Determines the display in Low resolution
- 45 -
Check Lytrons website www.Lytron.com for the most current technical information.
Kodiak Recirculating Chiller Technical Manual Where: Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit0 Alarm Flags Status in Bit encoded Byte (2 chars). Assignments are: (MSB) Over Temp: Over Temperature Alarm is lit Lo Temp: Low Temperature Alarm is lit Low Flow: Low Flow Alarm is lit Low Level: Low Level Alarm is lit Not used: Not used Not used: Not used Audible Alarm on: Alarm transistor (Al toggle) (LSB); Summary Alarm on: Beeps computer
PlantTemp and SetTemp encoded (2-byte hex (Cx100) Pressure encoded is integer value (hex 1-byte)
1.6.3
1.6.4
1.6.5
OverTempAlmLmt: High Temp Limit Setpoint (2-byte hex (Cx100) LowTempAlmLmt: Low Temp Limit Setpoint (2-byte hex (Cx100) OffsetCal Plant Temp Offset (2-byte hex (Cx100) ^J ^M Ascii Linefeed and Carriage Return
- 46 -
Check Lytrons website www.Lytron.com for the most current technical information.
1.6.6
1.6.7
1.6.8
1.6.9
- 47 -
Check Lytrons website www.Lytron.com for the most current technical information.
- 48 -
Check Lytrons website www.Lytron.com for the most current technical information.
Debit memos should not be issued for warranty and non-warranty repairs unless the unit is returned as a result of an out-of-box (new) failure. Lytron will warranty the repair for one year from the repair date under the terms of our standard warranty or for the balance of the original warranty, whichever is longer. Return Shipments: Lytrons warranty covers payment for standard, ground return shipment of warranted repairs. The incremental difference for expedited return shipments, if requested, are the responsibility of the customer. After non-warranty repair, Lytron will ship the system back using the customers preferred shipping method. Field Service/Installation Charges Where available, Lytron can arrange field service for cooling system installation or repair. Under no circumstances does Lytrons warranty cover on-site service. All on-site service must be arranged through Lytrons service department. The charges for this service are as follows: $250 administrative fee Plus the following: $100/hr for on-site services provided* Any related travel charges Parts not covered under warranty. * The hourly labor rate may vary depending upon city. Contact Lytrons service department for current rates in effect at the time.
All requests for On-Site Services require a PO or credit card in the amount of $800 before services will be scheduled. When using Lytron-arranged, on-site service, Lytron warranties the replacement parts and repair labor for 90 days from the repair date under the terms of our standard warranty or for the balance of the original warranty, whichever is longer. If non-authorized labor repairs the system or installs replacement parts, Lytron does not warranty the parts or work and this action potentially voids any remaining warranty. Lytron is expanding its worldwide service presence. Please contact the Service Department for the latest areas where on site service is available. Replacement Parts: Replacement parts can be ordered using a credit card or purchase order. Parts being returned from systems under warranty should be returned using a Lytron issued RMA number. If the parts are found to be defective and the claim is within the warranty period, credit will be issued for the price of the parts and one-way ground shipping charges. If the parts are not defective or indicate end user damage, no credit will be issued. Lytron will not cover the incremental cost of air shipment of replacement parts, regardless of warranty status. In-stock parts normally will be shipped the next business day; non-stocked parts will be shipped as quickly as reasonably possible. This policy is subject to change. Please check with Lytrons service department for the current policy.
Form F4.3.25 Rev D, 7/21/04
- 49 -
Check Lytrons website www.Lytron.com for the most current technical information.
- 50 -
Check Lytrons website www.Lytron.com for the most current technical information.
DECLARATION OF CONFORMITY
- 51 -
Check Lytrons website www.Lytron.com for the most current technical information.