Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Kodiak Recirculating Chillers: Technical Manual

Download as pdf or txt
Download as pdf or txt
You are on page 1of 53

KODIAK RECIRCULATING CHILLERS

RC006, RC009, RC011, RC022, RC030 and RC045 G03, H03 and J03 Series

TECHNICAL MANUAL

Lytron Inc., 55 Dragon Court, Woburn, MA 01801, USA Tel: +1-781-933-7305 Fax: +1-781-935-4529 www.Lytron.com
Lytron Inc., 2010
Manual # 820-0109, Rev. Y, 07/23/10

Kodiak Recirculating Chiller Technical Manual

{THIS PAGE IS LEFT BLANK INTENTIONALLY}

Kodiak Recirculating Chiller Technical Manual

TABLE OF CONTENTS
TABLE OF CONTENTS....................................................................................................................................................... 1 REVISION HISTORY........................................................................................................................................................... 3 INTRODUCTION.................................................................................................................................................................. 4 SAFETY PRECAUTIONS .................................................................................................................................................... 5 LABELS AND SILKSCREEN MARKING......................................................................................................................... 6 PART NUMBER DESCRIPTION ....................................................................................................................................... 8 SPECIFICATIONS................................................................................................................................................................ 9 PERFORMANCE GRAPHS............................................................................................................................................... 10 GENERAL INFORMATION ............................................................................................................................................. 11 CONTROLLER DISPLAY PANEL FUNCTIONS .......................................................................................................... 12 REAR PANEL COMPONENTS ........................................................................................................................................ 13 OPTIONAL SYSTEM FEATURES................................................................................................................................... 14 CONTROLLER OPTIONS ................................................................................................................................................ 16 INSTALLATION REQUIREMENTS ............................................................................................................................... 17 INSTALLATION PROCEDURE ....................................................................................................................................... 18 PRIMING TURBINE AND CENTRIFUGAL PUMPS.................................................................................................... 19 CONNECTING POWER (FOR UNITS WITHOUT HEATER OPTION).................................................................... 20 CHILLER OPERATION .................................................................................................................................................... 21 SYSTEM MAINTENANCE AND SERVICE ................................................................................................................... 24 DRAINING PROCEDURE FOR KODIAK CHILLERS ................................................................................................ 26 COOLANT MAINTENANCE ............................................................................................................................................ 27 ERROR CODES................................................................................................................................................................... 28 TROUBLE SHOOTING GUIDE........................................................................................................................................ 29 KODIAK SPARE PARTS ................................................................................................................................................... 31 ACCESSORIES FOR THE KODIAK RECIRCULATING CHILLER......................................................................... 32 FRONT VIEW...................................................................................................................................................................... 33

Manual # 820-0109, Rev. Y, 07/08/10

-1-

Check Lytrons website www.Lytron.com for the most current technical information.

Kodiak Recirculating Chiller Technical Manual REAR VIEW (WITH PANEL)........................................................................................................................................... 34 TOP VIEW ........................................................................................................................................................................... 35 REAR VIEW (OPENED).................................................................................................................................................... 36 SIDE VIEW .......................................................................................................................................................................... 37 SIDE VIEW (WITH HIGH PRESSURE CUTOUT) ....................................................................................................... 38 CHILLER DIMENSIONS FOR RC011 AND RC022...................................................................................................... 40 CHILLER DIMENSIONS FOR RC030 AND RC045..................................................................................................... 41 WIRING DIAGRAM........................................................................................................................................................... 42 PLUMBING DIAGRAM..................................................................................................................................................... 42 PLUMBING DIAGRAM..................................................................................................................................................... 43 REFRIGERATION DIAGRAM ........................................................................................................................................ 44 HOST INTERFACE DATA LINK .................................................................................................................................... 44 HOST INTERFACE DATA LINK .................................................................................................................................... 45 LYTRON COOLING SYSTEMS SERVICE POLICY ................................................................................................... 48 LYTRON KODIAK RECIRCULATING CHILLER STANDARD WARRANTY ...................................................... 50 DECLARATION OF CONFORMITY.............................................................................................................................. 51

Manual # 820-0109, Rev. Y, 07/08/10

-2-

Check Lytrons website www.Lytron.com for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

REVISION HISTORY
REV Y ECN / DATE 17284 / 07/08/2010 REASON FOR CHANGE Updated Declaration of Conformity and safety symbols.

Manual # 820-0109, Rev. Y, 07/08/10

-3-

Check Lytrons website www.Lytron.com for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

INTRODUCTION Receiving the New Kodiak Chiller


Inspect the new chiller immediately upon receiving it. If the unit shows shipping damage, contact the transportation company and file a freight damage claim. Retain all cartons and packing material until the unit is operated and found to be in good condition. The chiller has been fully tested at the Lytron factory with clean water. Although the system has been drained, some residual fluid may remain. This will not hinder the performance of the chiller.

About the Warranty


All units returned for warranty claims must have an RMA (Return Material Authorization) number on the outside of the container. Call Lytron Customer Service at +1-781- 933-7300 for an RMA number. Refer to the end of manual for the chiller warranty. Units should be drained of all fluids and packaged in its original packaging.

Customer Service Support


Lytron is committed to servicing the customer, both during and after the sale. If you have any questions concerning the operation of your unit, contact our Application Engineering Department at +1-781- 933-7300. To facilitate your call, please have the model number and serial number of the unit (located on the rear of the chiller) for the Lytron Applications Engineer.

Service Hotline
Lytron has a 24-hour per day, 7 day per week service hotline to help you with questions on the startup and operation of your Kodiak recirculating chiller. (Lytron recommends consulting the troubleshooting guide on page 29 before calling the service hotline.) Lytron service can be reached by dialing +1-781- 933-7300. To facilitate your call please have the model number and serial number (located on rear of the chiller) of the unit for the Lytron Service Technician.

Kodiak is a registered trademark of Lytron, Inc.


Manual # 820-0109, Rev. Y, 07/08/10

-4-

Check Lytrons website www.Lytron.com for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

SAFETY PRECAUTIONS
This system is designed to provide fluid cooling only as specified in this manual. If this system is used in a manner other than as specified, the safety protection of the system may be impaired. Warnings are posted throughout the manual. Read and follow these important instructions. Failure to observe these instructions or use the chiller other than as specified may impair safety protection, void the warranty, and can result in permanent damage to the unit, significant property damage, personal injury, and/or death. Make sure you read, understand, and follow all instructions and safety precautions listed in this manual before operating your unit. If you have any questions concerning the operation of your unit or the information in this manual, please contact our Applications Engineering Department at +1-781- 933-7300. Always turn the unit "OFF" and disconnect the power cord from the power source before performing any service, maintenance procedures or before moving the unit. Do not operate equipment with damaged power cords. A qualified technician should perform Service and repairs. If the set point is 10 C (50 F) or below, a freezing point depressant, such as ethylene glycol, is required. This unit is equipped with a low flow switch. This feature will shut the chiller down during a low flow situation to prevent freezing. DO NOT USE AUTOMOTIVE ANTI-FREEZE IN THE CHILLER. The rust inhibitors in the automotive type may cause premature failure of the pump seals. Use of automotive anti-freeze in a Lytron chiller will void the warranty. Never place the unit in a location where excessive heat, moisture, or corrosive materials are present. The unit must be plugged into a properly grounded power source. Do not connect the SUPPLY or RETURN fitting to your building water supply or any pressurized source. DO NOT USE OR MAINTAIN THE CHILLER OUTDOORS. These units were not designed to withstand outdoor weather conditions. Performance of installation, operation, or maintenance procedures other than those described in this manual may result in a hazardous situation and may void the Lytron warranty. Transport the unit with care. Sudden jolts or drops can damage the unit. Drain the chiller of all water when transporting, shipping or leaving unused for long periods of time. This will prevent freezing and algae build up while idle. Observe all warning labels. Never remove warning labels. Do not operate damaged or leaking equipment. Do not operate the unit without fluid in the reservoir.

Manual # 820-0109, Rev. Y, 07/08/10

-5-

Check Lytrons website www.Lytron.com for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

LABELS AND SILKSCREEN MARKING


The symbol on this label is intended to alert the user to the presence of important operating and maintenance (servicing) instructions in the literature accompanying the equipment. This symbol on this label cautions the user against the risk of electrical shock. This label is mounted near of main voltages of the system.
EXTERNAL CONTACTS .5 AMPS MAX

External contacts have been installed.

FILTER CARTRIDGE HAS BEEN INSTALLED

Lets customer know element has been installed.

RS-232

RS232 has been installed.

OPEN TO PRIME - CLOSE TO RUN

PUMP PRIMING VALVE

Identifies the location of the pump priming valve.

RETURN SUPPLY

This silk-screen marking identifies the connection where heated fluid is returned from the users machine. This silk-screen marking identifies the connection where chilled fluid is supplied to the users machine.

Positive earth (ground) terminal.

The markings on this label certifies that the equipment has been certified to the UL standard 61010A-1 and CAN/CSA STD C22.2 No. 1010.1 standards.

The symbol on this label identifies that the equipment has been certified to regulations of the European Community.

Manual # 820-0109, Rev. Y, 07/08/10

-6-

Check Lytrons website www.Lytron.com for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

The product ID label identifies the model number, serial number, electrical information, pump type, refrigerant type, charge, and date of manufacture of the product.

The crossed out wheeled bin label requires that the product be disposed of or recycled with the requirements of local law.

The RoHS compliant label indicates that the product complies with the European union restriction of hazardous substances (RoHS) directive.

This label indicates that none of the six hazardous substances are present in the product above the maximum concentration values in its homogeneous form per China RoHS.

This label indicates which of the six hazardous substances are present in the product above the maximum concentration values in its homogeneous form and the environmental protection use period of the product per China RoHS.

Manual # 820-0109, Rev. Y, 07/08/10

-7-

Check Lytrons website www.Lytron.com for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

PART NUMBER DESCRIPTION RC006 G03 BB 1 MXXX

Basic Model No. RC006 - 825 Watts

Electrical Configurations

Pump Options

Controller Configuration CONTROLLER PACKAGE #1 1. 2. 3. 4. 5. 6. Alarm Mute Audible Alarm Auto-Restart Calibration Offset Deg C / Deg F Toggle Digital Temperature Display 7. Low Flow Shut-Off Fault CONTROLLER PACKAGE #2: 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. Alarm Mute Audible Alarm Auto-Restart Calibration Offset Deg C / Deg F Toggle Digital Pressure Sensing & Display Digital Temperature Display Fault Shut-Off (toggle on/off) Low Flow Shut-Off Fault Low Level Fault Low Temp / High Temp Fault Relay Contacts

Std. Modification

G03 = 115V~/1ph/60Hz AA* = CP-15 Centrifugal Pump RC009 1,050 Watts H03 = 230V~/1ph/50Hz BB (CB) = 1.3 gpm RC011 1,650 Watts J03 = 230V~/1ph/60Hz Positive Displacement Pump RC022 2,400 Watts BC (CC) = 1.8 gpm Positive Displacement RC030 3,450 Watts Pump RC045 5,900 Watts BE (CE) = 2.3 gpm Positive Displacement Pump BG (CG) = 4.3 gpm Positive Displacement Pump DA* = CP-25 Centrifugal Pump EB* (FB) = 1/4 Hp Turbine Pump EC* (FB) = 1/6 Hp Turbine Pump Note: Cooling capacity and pump flows are rated at 60Hz. For 50Hz power capacity is reduced by 17%. Notes:

* Water filter and DI


cartridge not recommended with Centrifugal & Turbine pumps.

CONTROLLER PACKAGE #3: Same as "PKG 2" above with the addition of RS-232 communications.

Indicates high
purity compatible pump. NOTE: Refer to the product ID label on the on the rear of your chiller for the configuration you have purchased. The table above refers to Lytrons standard product offering for the Kodiak product line.

Manual # 820-0109, Rev. Y, 07/08/10

-8-

Check Lytrons website www.Lytron.com for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

SPECIFICATIONS1
RC006
Thermal Capacity2 Watts BTU/hr 115V~ 60Hz 1ph 230V~ 50Hz 1ph 230V~ 60Hz 1ph Full Load Amps3 G03 J03 H03 Compressor Size Refrigerant Type Temperature Stability Operating Environment Coolant Temperature Range4 Reservoir Capacity Dimensions5 Width Depth Height Connection Weight Process Coolant Delivery Pressure
1 2

RC009
60Hz 50Hz 1,050 875 3,585 2,988 G03 H03 J03

RC011
60Hz 50Hz 1,650 1,400 5,780 4,760 G03 H03 J03

RC022
60Hz 50Hz 2,400 2,150 8,755 7,310 N/A H03 J03

RC030
60Hz 50Hz 3,450 2,950 12,070 10,030 N/A H03 J03

RC045
60Hz 50Hz 5,900 4,950 20,230 16,830 N/A H03 J03

60Hz 50Hz 825 685 2,800 2,330 G03 H03 NA

9.9 A --4.5 A Hp R134A 0.2F (0.1C) 50F to 95F (10C to 35C) 41F to 95F (5C to 35C) 1 gal (3.8 l)

12.2 A 5.8 A 5.3 A 1/3 Hp R134A 0.2F (0.1C) 50 F to 95F (10C to 35C) 41F to 95F (5C to 35C) 1 gal (3.8 l)

14.3 A 7.4 A 6.3 A Hp R134A 0.2F (0.1C) 50F to 95F (10C to 35C) 41F to 95F (5C to 35C) 2 gal (7.6 l)

--10.0 A 9.5 A Hp R134A 0.2F (0.1C) 50F to 95F (10C to 35C) 41F to 95F (5C to 35C) 2 gal (7.6 l)

--14.5 A 13.7 A 1 Hp R134A 0.2F (0.1C) 50F to 95F (10C to 35C) 41F to 95F (5C to 35C) 6 gal (22.6 l)

--19.6 A 17.2 A 1 Hp R134A 0.2F (0.1C) 50F to 95F (10C to 35C) 41F to 95F (5C to 35C) 6 gal (22.6 l)

12.5" (318) 19.0" (483) 22.0" (559) FNPT 97 lbs (44 kg)

12.5" (318) 19.0" (483) 22.0" (559) FNPT 100 lbs (45 kg)

14.8" (376) 24.5" (622) 26.5" (673) FNPT 122 lbs (55 kg)

14.8" (376) 24.5" (622) 26.5" (673) FNPT 166 lbs (75 kg)

21.4" (543) 27.8" (705) 31.0" (787) FNPT 260 lbs (118 kg)

21.4" (543) 27.8" (705) 31.0" (787) FNPT 270 lbs (123 kg)

Factory preset to 90 psig max (for PD and turbine pumps only)

Specifications are subject to change. Capacity is for 20C delivery water at a 20C ambient. 3 Full load amperage for air -cooled models with standard pumps without the optional heater. Standard pumps are the BB for the RC006, RC009, RC011, RC022 and BG for the RC030 and RC045. Contact Lytron for current draw of other models. 4 Chiller will shut down when coolant temperature reaches 10C above the coolant temperature range. 5 Dimensions do not include filters or external valves.

Manual # 820-0109, Rev. Y, 07/08/10

-9-

Check Lytrons website www.Lytron.com for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

PERFORMANCE GRAPHS

Temperature represents output temperature of water assuming 20C ambient air conditions. Performance subject to change due to variations such as: fluid type or operating conditions.
Manual # 820-0109, Rev. Y, 07/08/10

- 10 -

Check Lytrons website www.Lytron.com for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

GENERAL INFORMATION
Chiller System Description
Your chiller consists of a refrigeration system, a coolant loop, associated controls and plumbing. The pump draws coolant from the internal reservoir and pumps it out to cool the process equipment, and then the coolant flows back to the chiller. The fluid then flows through the evaporator, where the heat is removed, and then back to the reservoir.

Coolant Loop
Kodiak chillers are designed to operate with continuous coolant flow through a closed loop. This loop contains the system pump, temperature sensor, reservoir, internal and external plumbing lines and fittings, and the external heat load. The external plumbing and the heat loads are provided by the end user and are generally unique to the users process or location.

Refrigeration System and Hot Gas Bypass


The chiller uses a standard refrigeration system to keep the coolant at the process temperature set point. The compressor compresses the refrigerant vapor. The vapor then passes through the condenser where it is cooled and turns to a liquid. The refrigerant then passes through the evaporator. The coolant also flows into the evaporator, through passages separated by thin layers of metal from the refrigerant. The refrigerant evaporates, drawing heat from the coolant. The refrigerant vapor returns to the compressor and continues the cycle. Many refrigeration systems, such as those used in household refrigerators, control the temperature by turning the compressor on and off. This is a simple, inexpensive method of controlling the cooling, but its temperature control is not precise and the frequent on-off cycles causes wear on the compressor motor. Lytrons recirculating chillers use a better method for controlling the cooling rate: a hot-gas bypass system. This employs a liquid line solenoid valve and a hot-gas bypass valve to meter the refrigerant flow through the evaporator when cooling is needed. When the coolant reaches its set point temperature, the liquid line solenoid valve closes, causing the hot-gas bypass valve to open. The hotgas valve lets hot gas from the compressor discharge into the evaporator, adjusting the temperature in the evaporator to maintain the correct coolant temperature. When refrigeration is needed the liquid line solenoid valve opens, the hot-gas valve closes and the cycle starts again. This hot gas bypass control method provides precise temperature control. It also minimizes wear on the compressor motor, since the compressor runs continuously and does not experience the stress of repeated cycling.

Manual # 820-0109, Rev. Y, 07/08/10

- 11 -

Check Lytrons website www.Lytron.com for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

CONTROLLER DISPLAY PANEL FUNCTIONS

Controller Display

Key
Turn on/off chiller Displays Pressure briefly

Operation

UP + DOWN +

Enter menu (press simultaneously and hold for 3 seconds and release) Push to display or change set point Increase set point temperature Decrease set point temperature Alarm Sound disabled or Muted (alarm will stay muted until error is corrected, then resets)

UP arrow DOWN arrow

DESCRIPTION OF INDICATORS
Temperature Set Point Pressure Display Cooling Indicator Low Flow Indicator Alarm Indicator Low-Level Indicator Over Temperature Indicator Low Temperature Indicator Displays coolant temperature or set point in C or F. Displays outputs pump pressure in PSI/bar digitally for a few seconds. Solenoid valve is open and chiller is cooling the process fluid when this light is illuminated. Indicates that the minimum flow requirement of the chiller is not being satisfied. Illuminates to indicate an alarm fault condition. Illuminates to indicate a low fluid level in the tank. Illuminates to indicate water temperature is above high temperature alarm set point. Illuminates to indicate water temperature is below low temperature alarm set point.

Manual # 820-0109, Rev. Y, 07/08/10

- 12 -

Check Lytrons website www.Lytron.com for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

REAR PANEL COMPONENTS


(Reference Spare Parts List in this manual)

CIRCUIT BREAKER

FLUID OUT OF CHILLER

POWER ENTRY

NOTCH INDICATES PIN 1

RS232

REMOTE START & CUSTOMER CONTACTS

FLUID IN TO CHILLER

14 25

Manual # 820-0109, Rev. Y, 07/08/10

- 13 -

Check Lytrons website www.Lytron.com for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

OPTIONAL SYSTEM FEATURES Coolant Water Filter


The factory installed water filter removes particulate from the coolant water. The water filter is not recommended with centrifugal pumps or turbine pumps. For replacement filters, call Lytrons Customer Service at 781-9337300.

Deionization Package
The Deionization Package consists of a factory-installed deionization cartridge. The deionization cartridge requires replacement only when the mixed bed is depleted. For replacement cartridges, Call Lytrons Customer Service at 781-933-7300. This package is offered for deionized water applications where the resistance of the water does not exceed 1 Mega-ohm-cm. The deionization package is not recommended with centrifugal pumps.

External Customer Contacts


This option will send a signal indicating there is a problem with the chiller. It can be wired to open on fault or close on fault. This connector is located on the rear left of the system. Pin 5 is the common, Pin 6 closes on fault, and pin 4 opens on fault. The mating connector is Amp part number 350715-1, and the pins for the connector are Amp part number 350547-1. These contacts are rated for 250 V, amp maximum.

External Manually Adjustable Flow Valve


This option allows the flow rate to the equipment to be controlled with a globe valve. Opening the valve allows the flow to bypass from the supply to the return. By adjusting the valve a precise flow rate can be set. To be sure the process equipment is receiving the appropriate flow install a flow meter at the outlet from the process equipment.

External Pressure Relief Valve


This option is for applications with a maximum allowable pressure. It can also be used where flow to the equipment being cooled needs to be shut off without stopping the chiller. In this case the pressure relief valve will open and allow the flow to bypass from the supply to the return. The standard valve has an adjustment range from 50 psi to 100 psi.

Fault Chiller Shut-off


This option will shut the chiller off in the event that there is an alarm condition. It will turn off the power to the pump and compressor and give an error signal on the front panel of the chiller. To reset the system after a fault the main power must be turned off at the circuit breaker.

Heater Package RC011, RC022, RC030 and RC045


The heater package is for applications requiring coolant temperature well above ambient temperature. This package is a single set point type. The heater is activated when the water temperature is 3F below set point. The heater option is not intended to provide tight temperature control, but to bring coolant temperature up to an application's requirement faster than the refrigeration cycle (hot gas bypass).

High Purity Plumbing


This option is intended for use with deionized water. Only stainless steel and/or plastic components and a nickel-brazed heat exchanger come in contact with the coolant. This option must be specified before the chiller is purchased. It cannot be upgraded in the field.

Remote Start
This option allows the Kodiak chiller to be started or stopped through a computer or a relay. The chiller can e run using a normally open circuit or normally closed. (Look under the section labeled Chiller Operation for more details) R.S. contacts are located on the rear left of the chiller shown previously. It is a six-pin connector with pins 1 and 2 controlling R.S. The mating connector is an Amp 350715-1 plastic housing. The pins are Amp 350547-1. The controlling relay should have SPDT type contacts rated for low current less than or equal to 5VDC at 0.1 milliamp.

Manual # 820-0109, Rev. Y, 07/08/10

- 14 -

Check Lytrons website www.Lytron.com for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

RS-232 Serial Port Communication


This option allows control of the chiller via a standard 9 pin serial port connected to a computer. Lytron software is available that simulates the front control panel and all its functions. Alternatively, software can be created to interface with the system described in the section labeled Host Interface Data Link.

Water Cooled Condenser RC011, RC022, RC030 and RC045


This feature replaces the standard condenser and fan with a water-cooled condenser. This requires cooling water to be supplied to the chiller at 75F (25C). The facility water pressure must be less than 100 psi. Minimum flow rates are as follows: Model RC011 RC022 RC030 RC045 Flow Rate (min) 1.4 gpm 1.4 gpm 1.9 gpm 3.4 gpm

Manual # 820-0109, Rev. Y, 07/08/10

- 15 -

Check Lytrons website www.Lytron.com for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

CONTROLLER OPTIONS CONTROLLER PACKAGES (1, 2, 3) FOR KODIAK CHILLERS


CONTROL PACKAGE #1:
1. 2. 3. 4. 5. Auto-Restart Calibration Offset Deg C / Deg F Toggle Digital Temperature Display Low Flow Fault Chiller Shut-Off

STANDARD OPTIONS FOR CONTROLLER PACKAGE #2:


1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. Alarm Mute Audible Alarm Auto-Restart Calibration Offset Deg C / Deg F Toggle Digital Pressure Sensing & Display Digital Temperature Display Fault Shut-Off (toggle on/off) Low Flow Fault Chiller Shut-Off Low Level Fault Low Temp / High Temp Fault Relay Contacts

STANDARD OPTIONS FOR CONTROLLER PACKAGE #3:


This option has the same features as Package 2 with the addition of: RS-232 Serial Port Communications

Manual # 820-0109, Rev. Y, 07/08/10

- 16 -

Check Lytrons website www.Lytron.com for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

INSTALLATION REQUIREMENTS Coolant Requirements


Lytron recommends using filtered clean water above 10C/50F as coolant. If the set point is 10C/50F or below, a freezing point depressant, such as ethylene glycol, is required. This unit is equipped with a low flow switch. This feature will shut the chiller down during a low flow situation to prevent freezing. Do not use automotive anti-freeze in the chiller. The rust inhibitors in the automotive type may cause premature failure of the pump seals. Use of automotive anti-freeze in a Lytron chiller will void the warranty. Avoid using water with a high mineral content. If the coolant is exposed to sunlight add an algaecide to control organic growth in lines.

Electrical Requirements (for units without heater option)


Refer to the Specification section and to the product ID label on the rear of the chiller for the specific electrical requirements of your unit. The chiller power module is configured with a standard international IEC320/C20 inlet. To safely operate the chiller, use an SJT cord set with an IEC 320/C19 receptacle and an inlet plug that is compatible to the local power grid and the power requirements of the chiller. All Kodiak chillers should use SJT 3 conductor 12 AWG minimum power cord.

Selecting Chiller Location


Do not operate or store Kodiak chillers outside. These systems are not intended for outdoor use. To minimize the heat gain and pressure drop through the connecting hoses, the chiller unit should be located as close as possible to the heat load (user equipment). This is more important for units with centrifugal pumps as they are not capable of high head pressures. Coolant lines are best run at or near the same level as the cooling system. Once the chiller is in position lock the casters. Airflow is critical to optimize performance of the chiller. The front and one side or the back of the unit MUST be kept clear and unobstructed. The remaining two sides or back must have minimum clearance of 18" (456 mm). The top clearance must be at least 6" (152 mm). Ensure that the hot air exiting the chiller does not recirculate into the inlet openings. The front of the unit must have a free supply of ambient-temperature air. Before moving the chiller cap all ports to prevent any coolant leakage. Unlock the casters and move to new location. Once in the new location lock the casters. To prevent freezing during storage drain water if the chiller is located in an area below 10C (50F).

Manual # 820-0109, Rev. Y, 07/08/10

- 17 -

Check Lytrons website www.Lytron.com for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

INSTALLATION PROCEDURE Selecting and Locating Hoses


The coolant ports are located on the rear of the system and are labeled as previously shown on page 13. To minimize the pressure loss in the coolant lines, use the largest practical diameter tubing. If substantial lengths of cooling lines are required, they should be pre-filled with coolant before connecting them to the chiller. To minimize heat gain, all lines should be as short as possible. Keep them away from heat sources such as radiators and hot water pipes. Lines that cannot be routed away from heat sources should be protected with thermal insulation, preferably at least 1/2" (12.7mm) thick. Flexible tubing should be of heavy wall or reinforced construction. All tubing should be rated to withstand 125 psig (9 bar) at 86F (30C). Make sure all tubing connections are secured and leak-tight. Also, whenever possible use opaque lines to prevent algae growth during prolonged non-operating periods.

Connecting Plumbing
To connect the fluid lines to the chiller and user equipment follow these steps: 1. Remove the plastic caps covering the supply and return ports on the rear panel of the unit. 2. Attach coolant lines to the supply and return ports on the rear panel. Fittings should either be brass, Never use steel or cast iron fittings, as the corrosion will damage stainless steel or nylon. the chiller. For chillers with de-ionization cartridges or high purity plumbing Lytron recommends the use of either stainless steel or nylon fittings. The supply port provides chilled coolant to the users equipment. The return port connects to the outlet of the users equipment. 3. Check that fittings are tight to prevent leaks. 4. Remove water filler cover on top of the unit to access the reservoir. 5. Fill the reservoir. Use the reservoir sight tube on the front of the unit to see the coolant level in the tank during filling. Be sure to allow for the volume of coolant needed to fill the cooling lines between the chiller and the equipment, if they were not filled with coolant before installation. 6. If the system is a water-cooled chiller, connect facility water to connections labeled "City Water In" and "City Water Out". Minimum flow rate of facility water is shown on page 15. Facility water flow must be started before chiller is turned on.

Manual # 820-0109, Rev. Y, 07/08/10

- 18 -

Check Lytrons website www.Lytron.com for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

PRIMING TURBINE AND CENTRIFUGAL PUMPS


Running centrifugal and turbine pumps dry for even a few seconds can permanently damage the pump. This style of pump must be primed prior to operation. Pump priming must be performed under the following conditions: a. At initial start-up. b. The system is drained of its fluid. c. A new pump is installed. Centrifugal and turbine pumps are classified as non-self priming pumps. This means that the pump will not displace the air inside the pump housing, which prevents fluid from being drawn in. Each must be primed prior to operation. Priming simply means to manually introduce fluid into the pump housing prior to operation. In a typical chiller installation, the flow of fluid through the pump suction hose into the pump is prevented by the presence of trapped air. Without a way for the air to escape, the fluid has no way of entering the pump housing. The following are recommended procedures to prime a turbine or centrifugal pump.

a. Valve in open position


1.

b. Valve in closed position

Units equipped with priming valve. The priming valve circuit is located between the pump discharge plumbing line and the top of the tank. There is a valve labeled pump priming valve located in this line. To prime the pump simply open this valve prior to starting the chiller (photo a). Start the chiller. After flow is observed returning to the tank, close the priming valve (photo b). Units that do not have a priming valve. To prime pumps that do not have a priming valve, disconnect the supply line from the rear of the chiller. Allow time for the fluid to gravity feed into the pump housing. If there is difficulty priming the pump using this method, use a wet vac to assist in drawing the fluid from the tank into the pump housing.

2.

Note: If the pump has failed to prime turn the chiller off and contact Lytrons Service Department - 781-933-7300.

Manual # 820-0109, Rev. Y, 07/08/10

- 19 -

Check Lytrons website www.Lytron.com for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

CONNECTING POWER (FOR UNITS WITHOUT HEATER OPTION)


In order to avoid an electrical potential at the chiller frame due to insulation failure, a proper ground connection to the system must be provided. Failure to do so could result in damage to the equipment, personal injury, and/or death. Connect a 3-conductor SJT type power cord with an IEC 320/C19 receptacle to the inlet power to the module on the rear of the unit and to an appropriate AC power source. All chillers should use a 12-gauge power cord.

Startup Procedure
1. Turn "ON" the circuit breaker on the rear of the unit. The controller will go through a diagnostic test. Turn on the chiller unit using the top left key located on the Keypad Display panel. The controller displays "OFF" for 8 seconds. The delay prevents rapid cycling of the compressor using the "ON" and "OFF" switch. If your chiller is equipped with control package 2 or 3 the fault shut off may prevent the chiller from starting up. If the chiller displays an alarm after pushing the ON button disable the fault shutoff on the customer menu and restart the chiller. 2. Adjust the temperature set point using the controls on the keypad display as follows: Press the SET key once to display the current coolant temperature set point. Press the UP or DOWN arrow key until the desired coolant temperature set point appears on the LED display. Press the SET key again to accept the set point and return to normal operation. 3. Operate the chiller for a short time and then check the coolant level in the reservoir. If the level drops, add more coolant. 4. Check all fittings and hoses for fluid leaks. If a leak exists turn chiller off, disconnect power and take necessary action to repair the leak.

Please Note:
During initial start up the temperature display may occasionally appear to be dim. This is a normal occurrence and does not indicate that there is problem with the chiller. After 10 seconds the display will brighten to its normal level.

Manual # 820-0109, Rev. Y, 07/08/10

- 20 -

Check Lytrons website www.Lytron.com for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

CHILLER OPERATION
The following sections explain how to perform other operations with the chillers controller, using the keys and display on the front of the unit. Refer to the Controller Display Panel Functions section in this manual. In normal operation the display shows the current temperature of the coolant (or the current temperature with an offset applied).

Customer Menu Options


Display Abbreviation
DEGC

Function
English or Metric Units Changes the temperature readings on the display from C to F and pressure from Bar to PSI. Calibration Offset Adjusts the reading on the display by the offset that you enter, from -4C to 4C (-7F to 7F). Auto Restart When enabled this allows the chiller to start automatically in the event of a power failure. Over temperature Fault Indication (option) Indicator illuminates when the coolant temperature exceeds the overtemperature set point. The over-temperature set point should be at least 3C (6F) above the coolant set point to prevent nuisance alarms. Low-temperature Fault Indication (option) Indicator illuminates when the coolant temperature falls below the lowtemperature set point. The low-temperature set point should be at least 3C (6F) below the coolant set point to prevent nuisance alarms. Audible alarm (option) When this is enabled, an audible alarm sounds when any fault occurs. *Fault chiller shutoff (option) When enabled, this turns off the chiller when any fault occurs. Remote Start (option) Allows the chiller to be started and stopped with a dry contact. Pressure Units (option) Allows the chiller to display the pressure in units of bar or psi. When bar is ON pressure is displayed in units of bar, in the format X.XX b. When bar is off, the pressure will be shown in psi, in the format XX p.

CAL

Ar

Ot

Lt

AL

FS

rS

bAr

*Low flow shutoff cannot be disabled.

Manual # 820-0109, Rev. Y, 07/08/10

- 21 -

Check Lytrons website www.Lytron.com for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

ALAudible Alarm (option)


1. 2. 3. 4. 5. To enter the menu, press and hold both the UP and DOWN arrow keys for 3 seconds. Use the SET key to scroll to AL. The display toggles between AL and its current setting. Use UP or "DOWN" arrow key to toggle between ON and OFF. Press, SET to accept the setting on the display and continue to the next feature.

Ar - Auto Restart Feature (standard)


If auto restart is enabled (ON): If the chiller is running and the power is interrupted due to power outage, tripped circuit breaker, etc., the chiller will automatically start when the power is restored. If auto restart is enabled (OFF): If the chiller is running and the power is interrupted due to power outage, tripped circuit breaker, etc., the chiller will stay off when the power is restored. Push ON to restart the chiller.

To activate the auto restart feature:


1. 2. 3. 4. 5. Enter the customer menu by holding both the UP and DOWN arrow keys for 3 seconds. Use the SET key to scroll to Ar. The display toggles between Ar and its current setting. Use UP or DOWN arrow key to toggle between ON and OFF.. Press, SET to accept the setting on the display and continue to the next feature.

CAL - Calibration offset (standard)


1. 2. 3. 4. 5. To enter the menu, press and hold both the UP and DOWN arrow keys for 3 seconds and release. Use the SET key to scroll to CAL. The display toggles between CAL and current offset setting. Use UP or DOWN arrows to change the calibration offset, which must be between -4C and +4C. If you do not want to use an offset set it to zero (0). Press, SET to accept the setting on the display and exit the menu.

DEGC - Temperature scale (standard)


1. To enter the menu, press and hold both the UP and DOWN arrow keys for 3 seconds and release. 2. The first option to change will be DEGC. 3. The display toggles between DEGC and current setting. Use UP or DOWN arrows to turn the degree Celsius display on and off. This will automatically change the pressure scale to psi or to bar. 4. Press, SET to accept the setting on the display and exit the menu.

FSFault Chiller Shutoff (option)


1. 2. 3. 4. 5. To enter the menu, press and hold both the UP and DOWN arrow keys for 3 seconds. Use the SET key to scroll to FS. The display toggles between FS and its current setting. Use UP or "DOWN" arrow key to toggle between ON and OFF. Press, SET to accept the setting on the display and continue to the next feature.

Lt Low temperature indication (option)


To enter the menu, press and hold both the UP and DOWN arrow keys for 3 seconds. Use the SET key to scroll to Lt. The display toggles between Lt and current over-temperature set point Use UP or DOWN arrows to change the low temperature set point, which should be at least 3C (6F) below the coolant set point temperature. 5. Press, SET to accept the setting on the display and continue to the next feature. 1. 2. 3. 4.

Manual # 820-0109, Rev. Y, 07/08/10

- 22 -

Check Lytrons website www.Lytron.com for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

Ot Over temperature indication (option)


1. 2. 3. 4. To enter the menu, press and hold both the UP and DOWN arrow keys for 3 seconds and release. Use the SET key to scroll to Ot. The display toggles between Ot and current over temperature set point. Use UP or DOWN arrows to change the over temperature set point, which should be at least 3C (6F) above the coolant set point temperature. 5. Press, SET to accept the setting on the display and continue to the next feature.

bArPressure Units
1. 2. 3. 4. To enter the menu, press and hold both the UP and DOWN arrow keys for 3 seconds. Use the SET key to scroll to bAr. The display toggles between bAr and its current setting. Use UP or "DOWN" arrow key to toggle between ON and OFF. ON will display the units in bar and OFF will display the units in psi. 5. Press, SET to accept the setting on the display and continue to the next feature.

rSRemote Start Feature (option)


When it is set to off the chiller acts as if it does not have the remote start feature. By setting this feature toNC (normally closed or run on closed) the chiller will start when pins 1 and 2 on the six-pin connector on the rear of the chiller are closed. The chiller will shut off when pins 1 and 2 are open. By setting this feature to NO (normally open or run on open) the chiller will start when pins 1 and 2 are open. The chiller will shut off when pins 1 and 2 are closed. When the remote start feature is enabled within the user menu and the chiller is in the off state, the chiller cannot be turned on from the front control panel and rS will appear on the display. When the remote start feature is enabled within the user menu and the chiller is operating, turning the chiller off from the front panel will result in an Err 05 on the front display. This can be cleared by pressing the On/Off button again or cycling the remote contact. 1. 2. 3. 4. 5. To enter the menu, press and hold both the UP and DOWN arrow keys for 3 seconds. Use the SET key to scroll to rS. The display toggles between rS and its current setting. Use UP or "DOWN" arrow key to toggle between OFF, nO, and nC. Press, SET to accept the setting on the display and continue to the next feature.

Manual # 820-0109, Rev. Y, 07/08/10

- 23 -

Check Lytrons website www.Lytron.com for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

SYSTEM MAINTENANCE AND SERVICE


A qualified service technician must perform all service and maintenance internal to the chiller. Unqualified individuals conducting service on the chiller could result in damage to the equipment, personal injury and/or death. After your Kodiak Recirculating Chiller is up and running, it takes only a small amount of care and maintenance to keep it running well. Every installation is unique, and the operating conditions determine how often the equipment should be inspected and maintenance be performed. The following are some guidelines.

Periodic Inspections
Noise Level
Any abnormal sounds or a substantial increase in noise level since the last weekly inspection may indicate the following: impending pump, fan or coolant blockage problem. Investigate the cause and perform the necessary service. Refer to the troubleshooting guide in this manual.

Leakage
If you notice coolant on the floor near the chiller or dripping from the chiller enclosure turn off the chiller. Disconnect the power cord. Find and repair any leaks immediately.

Coolant Level
Any significant drop in the coolant level should be investigated further. If there is no visible system leak, then the loss may be due to equipment leakage elsewhere.

Pump / Motor
Some pumps may require lubrication. If the pump needs lubrication, lubricate annually with 20-30 drops of SAE Oil.

Fan Assembly
No maintenance is required on the fan. Listen for any abnormal sounds.

Condenser Fin
Remove the front grill by sliding it upward, pulling the bottom out and pulling it straight down. For maximum performance the condenser fin should be free of dust and debris. Use a vacuum cleaner or compressed air to remove any debris and keep the fin clean.

Water Filter
With a new system the filter quickly accumulates foreign matter introduced during system setup. This can lead to a decrease in system performance in a short period of time. Inspect the filter cartridge one day after you set up a new system to ensure the filter is clean and the system runs at maximum capacity. After this initial filter inspection, check the filter weekly. For replacement filters contact Lytrons Customer Service at 781-933-7300.

Deionization Package
The cartridge life is a function of the users application. Check the water resistively weekly and change the cartridge as required. For replacement filters contact Lytrons Customer Service at 781-933-7300.

Low Level Switch


The level switch protects the pump in the event of accidental fluid loss. Since this switch is "passive" during normal operation, it is advisable to check it every 6 months. Open the tank cover and push down on the switch to see if the low level alarm is activated.

Manual # 820-0109, Rev. Y, 07/08/10

- 24 -

Check Lytrons website www.Lytron.com for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

Algae
Lytron recommends the use of an algae inhibitor to prevent growth in the reservoir.

Cleaning the System and Reservoir


To clean the unit follow these steps: 1. 2. 3. 4. 5. 6. Drain the entire unit including the hoses and equipment being cooled. Replace the coolant with clean water. Run the unit with the clean water for 10 minutes. Drain the unit again. Replace all filters. Refill unit with either water or a water and freezing point depressant.

Pump Strainer
All positive displacement pumps have a strainer to protect the vanes inside the pump. For pumps less than 2.5 gpm it is located in the pump housing. For larger PD pumps it is installed in the hose between the pump and the tank. Periodically inspect and clean the pump strainer. If it becomes fouled the flow rate will decrease and the pump may wear prematurely. The strainer can be cleaned by rinsing it in warm water and brushing it gently. For a detailed procedure in cleaning the pump strainer visit the Maintenance and Troubleshooting section of Lytrons website at www.Lytron.com.

Pumps
As a precaution, the pump must be periodically replaced. This will avoid damaging the unit and the cost associated with excessive downtime. Typical operating life of the pump depends on pump type.

Pump Model Positive Displacement Centrifugal Turbine Note: Please contact Lytron for pump pricing and delivery.

Typical Operating Life 7,000 Hours 28,000 Hours 28,000 Hours

Manual # 820-0109, Rev. Y, 07/08/10

- 25 -

Check Lytrons website www.Lytron.com for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

DRAINING PROCEDURE FOR KODIAK CHILLERS


Always disconnect power to chiller when performing service. Failure to do so could result in damage to the equipment, personal injury and/or death. A container should be available to hold the fluid removed from the chiller. This container should be labeled in accordance with OSHA rules and regulations concerning handling of the fluid being removed from the chiller. Failure to do so could result in personal injury. Reference the MSDS sheet for the fluid being removed from the chiller for further handling, storage, and disposal instructions. Disposal of fluid removed from the Lytron chiller should be in accordance with all Local and Federal disposal laws. Failure to do so could result in personal injury. Not following this procedure may result in extensive damage to the chiller. It is extremely important to completely drain the chiller when not in use for extended period of time, shipping outside of its current location, during certain repairs, and for scheduled fluid maintenance. Failure to fully drain the system could result in damage of the equipment. Lytron recommends method #1 as the most efficient way to remove fluid from the chiller. Method #1- Recommended 1. Lytron recommends using a wet/vac to thoroughly remove fluid from the chiller. Remove plastic cap from top of the clean fluid reservoir. Vacuum this tank until it is completely free of any fluid. Keep reservoir cap removed from reservoir until step #5. 2. Using wet/vac, first vacuum the supply connection located at the rear of the chiller. After all the fluid has been removed from the supply side, move vacuum to the return connection. Vacuum this connection until all fluid has been removed. 3. Remove side panel of chiller to expose the tank drain hose. The drain line is a braided hose terminated with a white PVC cap. The drain line branches off from a tee on the chiller return line. 4. Remove plastic cap plug and place vacuum at the end of the hose. Vacuum any remaining fluid from the system. (Note: make sure reservoir cap is removed, allowing air to enter system). 5. Install plastic cap plug to the end of the drain hose. Install side panel. Attach plastic cap to the clean fluid reservoir. Install chiller cover. Method #2- without access to wet/vac 1. Remove chiller cover. Remove reservoir plastic cap. Keep reservoir cap removed from reservoir until step #4. Remove side panel of chiller to expose the tank drain hose. The drain line is a braided hose terminated with a white PVC cap. The drain line branches off from a tee on the chiller return line. 2. If possible, elevate the chiller approximately 3 off the ground. This will allow you to drain the system into a 5-gallon bucket. 3. Remove the plastic cap plug from the end of the hose. (Note: make sure reservoir cap is removed, allowing air to enter system). Drain the system into a 5-gallon bucket. Because this process is relying on gravity, it may take a few minutes to completely drain the system. If the volume of your system exceeds 5 gallons, have a second bucket nearby. 4. Install plastic cap plug to the end of the drain hose. Install side panel. Attach plastic cap to the clean fluid reservoir. Install chiller cover.

Manual # 820-0109, Rev. Y, 07/08/10

- 26 -

Check Lytrons website www.Lytron.com for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

COOLANT MAINTENANCE Recommended coolant for use in Lytron systems


Clean water is recommended for most systems. Systems ordered with the deoinized plumbing package require that deoinized water be used. Use of deoinized water in systems with brass components may cause premature failure of the system. If the set point temperature is below 50F/10C, Ethylene or Propylene Glycol should be added to the water with a mix ratio of 30% Ethylene or Propylene Glycol to 70% water. Do not use automotive antifreeze as the rust inhibitors may cause premature failure of the pump seals. Avoid using water with a high mineral content. If the chiller is exposed to sunlight, add an algaecide to control organic growth in the coolant. A mixture of 30% Ethylene or Propylene Glycol can also be used to control algae growth.

Checking coolant level


There is a coolant level site tube on the front of the unit. Coolant should be added as soon as this indicator approaches the half-full mark. Reducing the coolant volume may reduce the chillers cooling capacity. Inspect coolant level weekly or whenever the chiller is powered on.

Flush & replace coolant periodically


In order to avoid electric shock, be sure to wipe up all fluid spills in the unit before applying electrical power. Failure to do so could result in damage to the equipment, personal injury and/or death. Depending on the environmental conditions, the coolant should be flushed and replaced as necessary, depending on the amount of particulate matter that has been found in the system during planned maintenance inspections. If the pump strainer and coolant is found to have little or no contamination after the first inspection, replacing the coolant and cleaning the strainer can be done less frequently. The pump strainer may be located in one of two places. Refer to the strainer cleaning procedures under System Maintenance and Service. When the strainer is cleaned or replaced, the electrical power must be disconnected and the system drained of all coolant.

Manual # 820-0109, Rev. Y, 07/08/10

- 27 -

Check Lytrons website www.Lytron.com for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

ERROR CODES
There are a few different error codes that can occur during the operation of the chiller. These error codes are displayed on the front keypad of the system. See below for an explanation of each error code.

Err 01 Controller Initialization Error


This error code signifies an error in the controller software initialization during power up. Contact the Lytron Service Department to resolve this type of error.

Err 02 RTD Error


This error codes means that the resistance temperature device (RTD) is disconnected or damaged. The controller will display error 02 when the resistance of the RTD is outside of the expected range. A cut wire, a short to the RTD, and an internal malfunction in the RTD, can cause this or if the wires are disconnected. Contact the Lytron Service Department for a replacement part number.

Err 03 Controller Operational Error


This error code signifies an error in the controller software while the chiller is running. Contact the Lytron Service Department to resolve this type of error.

Err 04 Low Flow Error


This error code signifies a low flow condition exists. The low flow light, the alarm light and the audible alarm will all sound when an error 04 occurs. The controller will also shutdown the pump, compressor, and fan. See the trouble shooting section for suggestions on how to clear this alarm code.

Err 05 Remote Start


This error code signifies that chiller has been turned off from the front panel while the remote start feature is enabled within the user menu. This can be cleared by pressing the On/Off button again or cycling the remote contact.

Err 07 Auto Temperature Shut Down


This error code signifies that the process fluid temperature is above the highest allowable temperature for this chiller. This feature is design to shut the chiller down when the process fluid temperature reaches 10C above the highest allowable chiller set point. All standard chillers (including part numbers ending in Mxxx) built after 09/24/07 have this feature enabled. Part numbers ending in Cxxx chillers will have this feature enabled upon request of the customer.

Manual # 820-0109, Rev. Y, 07/08/10

- 28 -

Check Lytrons website www.Lytron.com for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

TROUBLE SHOOTING GUIDE


Problem Possible Cause Recommended Remedy
Make sure the unit is plugged in. Verify power to the unit. Turn circuit breaker to the "ON" ( I ) position. Turn on the unit with the ON ( I ) key on the keypad. Disable fault shutoff. Start unit. Enable shutoff after it is running, if desired. Fill external line prior to start up. Pump is not Primed See Pg. 19. Have a qualified electrician check the electrical service to the unit. Reduce the cooling load on the unit. Reset the set point to the proper temperature. Remove the lower grill and vacuum the coil face clean. Remove air obstructions from around the unit; manually reset the high-pressure control (Inside rear of unit, this is a blue button on a white box. Press to reset.) Let the unit cool. The overload will reset itself, normally in 30 minutes or less. This should go away after the system runs for a few minutes. Manually reset the high-pressure control inside rear of unit, this is a white plastic button on the box. Press to reset. Verify power source; check electrical service. This should go away after the system runs for a few minutes. Replace pump. Use either larger hoses or a shorter line length to reduce the pressure drop to equipment to be cooled. Replace pump with new one. Contact Lytron Service Department for part number and pricing. Verify and correct the voltage to the chiller. Shut down unit, clear obstructions and restart unit. Add more fluid to reservoir to full mark. Clean the reservoir and level switch. Replace level switch.

No power to the unit, circuit breaker "off" or tripped.

Fault shutoff enabled. Low flow shut off will cause the chiller to stop after 10 seconds. Unit does not start or shuts off shortly after starting. Low Voltage. Cooling load exceeds cooling capacity. Controller set point temperature is too high. Condenser coil fouled with dust or debris. Unit has tripped the high-pressure cutout (RC030, RC045 and water cooled units only.) (See Pg. 38) Compressor has tripped its internal overload. Liquid refrigerant in the suction line to the compressor. Unit has tripped the high-pressure cutout (RC030, RC045 and water cooled units only.) (See Pg. 38) Low voltage or wrong voltage to unit. Noisy compressor Unit stored in cool environment for a long period may have collected liquid refrigerant in the compressor. Pump shaft seal damage Noisy pump motor Excessive pressure drop. Positive displacement pump is worn out. Pump motor overheats Audible alarm stays on (Control Package II and III only) Improper voltage to the system. Obstruction in pump head. Low level in reservoir Level switch is stuck. Level switch is damaged.

Excessive noise on startup Excessive Pressure in facility water (water-cooled unit only)

Manual # 820-0109, Rev. Y, 07/08/10

- 29 -

Check Lytrons website www.Lytron.com for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

Problem

Possible Cause
Low temperature alarm is set too close to cooling set point temperature. High temperature alarm is set too close to cooling temperature set point. Pump suction strainer is clogged. (Positive displacement pumps only.) Low coolant level or no coolant in the reservoir. Water filter dirty or clogged. Pressure relief on the pump is set too low. (Positive displacement and turbine pumps only.) Restriction in coolant lines external to the chiller. Pump overload has tripped. Leaks in external piping. Pump motor shaft is bound. Damaged pump. Shutoff feature is enabled in the controller set up menu. (Controllers with options II and III)

Recommended Remedy
Adjust low temperature alarm set point. Adjust high temperate alarm set point. Remove strainer, clean and reassemble. Check for leaks. Repair any leaks and fill reservoir. Change filter cartridge. Adjust the pressure relief to 90 psig. For a high-pressure application (over 90 psig) contact Lytron Applications Engineering. Eliminate restrictions in the lines. Open any valves. Turn unit off. Wait for overload to cool. It will reset on its own in 30 minutes or less. Repair leaks. Replace pump motor. Replace pump. Find out and correct the fault that is causing the shutoff. Disable shutoff feature (see controller set up). See Low Coolant Flow Process fluid temperature has reach a temperature higher than the systems design temperature. Verify values in the controller, including offset. Reset as necessary. Reset temperature offset. Reduce line length or increase line diameter. Reset pressure relief to 90 psig. Wait 5 to 10 seconds and the display will brighten to its normal level.

Low coolant flow

Low coolant flow

Chiller shuts down during operation

Low flow switch tripped. Auto Temperature alarm has tripped.

Temperature display reads incorrectly Recirculating pressure is too high Temperature display dim at start up.

Temperature set point is not set properly. Offset incorrectly set. Pressure drop through system is too large. Pump internal pressure relief is set too high. This is a normal part of the start up process. It does not indicate that there is a problem.

Manual # 820-0109, Rev. Y, 07/08/10

- 30 -

Check Lytrons website www.Lytron.com for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

KODIAK SPARE PARTS


Item #
1 3 4 5 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26

Description
Controller PCB Circuit Breaker 115V Circuit Breaker 230V2 Pump and Compressor Relay Pressure Transducer, Brass Pressure Transducer, Stainless Steel Pressure Transducer, Plastic Temperature Sensor (RTD) Tank Low Level Switch Upper Front Panel Keypad Cover Access Panel Side Panel Front Grille Casters with lock Casters without lock Rear Panel Hot Gas Bypass Valve Solenoid Valve Heat Exchanger Capillary Tube Liquid Line Filter Dryer Condenser Compressor Condenser Fan Flow Switch

RC006/RC009

Model# Series RC011/RC022 Lytron Part Number

RC030/RC045

230-0874-P1 230-0593 230-0588 230-0592 101903-03 230-1006 230-1007 230-0603 250-0072 340-0020 340-0018 230-0892 340-0012 340-0014 230-0947 330-1139-06 330-1165-06 330-0880-06 330-1138-06 330-1166-06 340-0013 340-0015 531-0026 531-0027 330-1141 330-1167

N/A 230-0591

340-0019 340-0016 330-1172-06 330-1173-06 340-0017 531-0016 531-0017 330-1174

All of these parts require service by a qualified refrigeration technician. Please contact Lytron if you have any problems with one of these parts.

Contact Lytron for replacement fan part number. 250-0136 230-0912

Please include model and serial number when ordering the controller PCB so they may be correctly programmed. Chillers with a heater require a different circuit breaker. Contact Lytrons Customer Service at +1-781-933-7300 for additional information.
2

Manual # 820-0109, Rev. Y, 07/08/10

- 31 -

Check Lytrons website www.Lytron.com for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

Item #

Pumps and Motors


1.3 gpm Brass Pump Kit 1.8 gpm Brass Pump Kit 2.3 gpm Brass Pump Kit 4.3 gpm Brass Pump Kit 1.3 gpm Stainless Steel Pump Kit 1.8 gpm Stainless Steel Pump Kit 2.3 gpm Stainless Steel Pump Kit 4.3 gpm Stainless Steel Pump Kit 1/4 Hp 115 V Motor 1/4 Hp 230 V Motor 1/3 Hp 115/230 V Motor 1/2 Hp 115/230 V Motor 1/20 Hp Centrifugal Pump 115 V 1/20 Hp Centrifugal Pump 230 V 1/4 Hp Centrifugal Pump 115 V 1/4 Hp Centrifugal Pump 230 V 1/2 Hp Turbine Pump 115/230 V 1/6 Hp Turbine Pump 115V EC 1/6 Hp Pump 230V EC

(All Models) Part Number


205-0004 205-0005 205-0006 205-0007 205-0009 205-0010 205-0105 205-0011 230-0202 230-0214 230-0215 230-0203 410-0196 410-0197 101773-06 101773-05 410-0229 410-0336 410-0337

* 6A1

ACCESSORIES FOR THE KODIAK RECIRCULATING CHILLER


Description
5 Water Filters (min order 10) Air Filter RC006/RC009 Air Filter RC011/RC022 Air Filter RC030/RC045 Water Filter Kit External Pressure Relief Kit (0-50 psig) External Pressure Relief Kit (50-100 psig)

Lytron Part Number


330-0022 330-0053 330-0692 330-0683 200-0441 200-0196 200-0080

Item 6A refers to Pump & Motor combination.

Manual # 820-0109, Rev. Y, 07/08/10

- 32 -

Check Lytrons website www.Lytron.com for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

FRONT VIEW
(Reference Spare Parts List in this manual)

ACCESS PANEL 13

COVER 12

KEYPAD 11 UPPER FRONT 10

SIDE 14

FRONT GRILLE 15 CASTERS 16

Manual # 820-0109, Rev. Y, 07/08/10

- 33 -

Check Lytrons website www.Lytron.com for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

REAR VIEW (WITH PANEL)


(Reference Spare Parts List in this manual)

CIRCUIT BREAKER 3

REAR PANEL 17

Manual # 820-0109, Rev. Y, 07/08/10

- 34 -

Check Lytrons website www.Lytron.com for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

TOP VIEW
(Reference Spare Parts List in this manual) PUMP AND COMPRESSOR RELAY 4

PUMP PRESSURE TRANSDUCE 5 TEMP SENSOR 7 6 6A

TANK 8

MOTOR 2

FLOW SWITCH 9

Manual # 820-0109, Rev. Y, 07/08/10

- 35 -

Check Lytrons website www.Lytron.com for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

REAR VIEW (OPENED)


(Reference Spare Parts List in this manual) HOT GAS BYPASS VALVE 18 FLOW SWITCH 26

20 HEAT EXCHANGER

21 CAPILLARY TUBE

Manual # 820-0109, Rev. Y, 07/08/10

- 36 -

Check Lytrons website www.Lytron.com for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

SIDE VIEW
(Reference Spare Parts List in this manual)

FLOW SWITCH 26

COMPRESSOR 24 25

19 SOLENOID VALVE

22 LIQUID LINE FILTER DRYER

23 CONDENSER

Manual # 820-0109, Rev. Y, 07/08/10

- 37 -

Check Lytrons website www.Lytron.com for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

SIDE VIEW (WITH HIGH PRESSURE CUTOUT)

RESET BUTTON

HIGH PRESSURE CUTOUT

Manual # 820-0109, Rev. Y, 07/08/10

- 38 -

Check Lytrons website www.Lytron.com for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

CHILLER DIMENSIONS FOR RC006 AND RC009

Manual # 820-0109, Rev. Y, 07/08/10

- 39 -

Check Lytrons website www.Lytron.com for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

CHILLER DIMENSIONS FOR RC011 AND RC022

Manual # 820-0109, Rev. Y, 07/08/10

- 40 -

Check Lytrons website www.Lytron.com for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

CHILLER DIMENSIONS FOR RC030 AND RC045

Manual # 820-0109, Rev. Y, 07/08/10

- 41 -

Check Lytrons website www.Lytron.com for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

WIRING DIAGRAM

Manual # 820-0109, Rev. Y, 07/08/10

- 42 -

Check Lytrons website www.Lytron.com for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

PLUMBING DIAGRAM

Manual # 820-0109, Rev. Y, 07/08/10

- 43 -

Check Lytrons website www.Lytron.com for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

REFRIGERATION DIAGRAM

Manual # 820-0109, Rev. Y, 07/08/10

- 44 -

Check Lytrons website www.Lytron.com for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

HOST INTERFACE DATA LINK Control Package 3 only


1.0 Host Interface Data Link
The chiller supports basic host control capability through the Chiller RS-232 port.

1.1 Port Settings


The host port runs at 9600 baud, 8 data bits, 1 stop bit, and no parity.

1.2 Flow Control


The chiller negates the Chiller RTS (output from Chiller) line whenever the Chiller is busy in a non-interruptible process. The Chiller ignores the Host CTS line. No software (Xon/Xoff) flow control is provided. It is the responsibility of the host to issue only a single command for which a response from the Chiller Control is required until the response is received from the Chiller Control. Inter and intra message timeout is defined as 1 second. (Typical response times and character pacing will be baud rate limited.)

1.3 Encoding
All characters are to be ASCII characters. All messages from the host to the control and from the control to the host will have 0x10 (ASCII Line Feed) as a start-of-message delimiter, and 0x0D (ASCII Carriage return) as an end-of-message delimiter. Permitted message characters are in the range of 0x20 through 0x7F (hexadecimal).

1.4 Numeric Representation


Hexadecimal numbers, using ASCII characters 0 9 & A F, will represent all numeric values. When the Chiller Control returns multiple variables or parameters they will be white space separated (using ASCII 0x20). The host should recognize and use comma, tab and space as white space characters.

1.5 Units
All temperature values will be communicated in two byte hex values of Cx100 (.01 C). Resolution of temperature values is .1 degree. All pressure values will be communicated in integer psi with no offset.

1.6 Commands 1.6.1 1.6.2 The following host Control messages are defined: Read Chiller Status
This command (R) will cause the Chiller Control to return a complete status string with the following form: ^JR ControlFlags AlarmFlags PlantTemp SetTemp Pressure ^M Where: ControlFlags Status in Bit encoded Byte (2 chars). Assignments are: Bit 7: Bit 6: Bit 5: Bit 4: Bit 3: Bit 2: Bit 1: Bit 0: (MSB); Machine on: Expansion Relay2 on: Expansion Relay1 on: Heater on: Autopilot: Condenser Relay on: Cool Valve On: (LSB); Celsius Display on: Lights the temperature display and pressure indicator bar Not used by host program Not used by host program Not used by host program Not used by host program Not used by host program Light the Cool Status Determines the display in Low resolution

Manual # 820-0109, Rev. Y, 07/08/10

- 45 -

Check Lytrons website www.Lytron.com for the most current technical information.

Kodiak Recirculating Chiller Technical Manual Where: Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit0 Alarm Flags Status in Bit encoded Byte (2 chars). Assignments are: (MSB) Over Temp: Over Temperature Alarm is lit Lo Temp: Low Temperature Alarm is lit Low Flow: Low Flow Alarm is lit Low Level: Low Level Alarm is lit Not used: Not used Not used: Not used Audible Alarm on: Alarm transistor (Al toggle) (LSB); Summary Alarm on: Beeps computer

PlantTemp and SetTemp encoded (2-byte hex (Cx100) Pressure encoded is integer value (hex 1-byte)

1.6.3

Read Plant Temperature


This command (T) will cause the Chiller Control to return the plant temperature in a status string with the following form: ^JT PlantTemp^M Where: PlantTemp Plant Temperature Value (2-byte hex (Cx100) ^J ^M Ascii Linefeed and Carriage Return

1.6.4

Read Set Point Temperature


This command (S) will cause the Chiller Control to return the current setpoint temperature in a status string with the following form: ^JS SetTemp^M Where: SetTemp Setpoint Temperature Value (2-byte hex (Cx100) ^J ^M Ascii Linefeed and Carriage Return

1.6.5

Read User Menu Configuration


This command (U) will cause the Chiller Control to return the current User Menu configuration information in a status string with the following form: ^JU UserControlFlags OverTempAlmLmt LowTempAlmLmt OffsetCal^M Where: UserControlFlags Status in Bit encoded Byte (2 chars). Audible Alarm Enable & Fault Chiller Shutoff are encoded in this byte as follows: Bit 7: Bit 6: Bit 5: Bit 4: Bit 3: Bit 2: Bit 1: Bit 0: (MSB): Chiller PowerOn : Host signal to turn on Chiller PowerOff: Host signal to turn off Chiller F/C: Host Signal to toggle F/C Fault Chiller Shut Off : Fault chiller shutoff is enabled, lights host window Audible Alarm Enable: Audible Alarm is enabled Not used Remote Start NC: Remote start contact closure to run, else Off (LSB); Remote Start NO:Remote start contact open to run, else Off

OverTempAlmLmt: High Temp Limit Setpoint (2-byte hex (Cx100) LowTempAlmLmt: Low Temp Limit Setpoint (2-byte hex (Cx100) OffsetCal Plant Temp Offset (2-byte hex (Cx100) ^J ^M Ascii Linefeed and Carriage Return

Manual # 820-0109, Rev. Y, 07/08/10

- 46 -

Check Lytrons website www.Lytron.com for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

1.6.6

Set Chiller Control Plant Setpoint Temperature


This command (P) from the host will set the Chiller Control Temperature Setpoint. The Host command is of the form: ^JP SetTemp^M Where: SetTemp Setpoint Temperature Value (2-byte hex (Cx100) ^J ^M ASCII Linefeed and Carriage Return

1.6.7

Set Optional Over-temperature Limit


This command (X) from the host will set the Chiller Optional Over-temperature Limit. Note that it is the hosts responsibility to determine if this option is active. The Host command is of the form: ^JX OverTempAlmLmt ^M Where: OverTempAlmLmtHigh Temp Limit Setpoint (2-byte hex (Cx100) ^J ^M ASCII Linefeed and Carriage Return

1.6.8

Set Low Temperature Alarm Limit


This command (Y) from the host will set the Chiller Optional Low-temperature Limit. Note that it is the hosts responsibility to determine if this option is active. The Host command is of the form: ^JY LowTempAlmLmt ^M Where: LowTempAlmLmt Low Temp Limit Setpoint (2-byte hex (Cx100) ^J ^M ASCII Linefeed and Carriage Return

1.6.9

Set Offset Calibration


This command (Z) from the host will set the Chiller Plant Temperature Offset Calibration. The Host command is of the form: ^JZ OffsetCal ^M Where: OffsetCal Offset Calibration (2-byte hex (Cx100) ^J ^M ASCII Linefeed and Carriage Return

1.6.10 Set User Control Flags


This command (W) from the host will set the Chiller User Control Flags. As noted in the bit descriptions above, the host may use the Power-On and Power-off bits to force the Chiller On/Off. The Host command is of the form: ^JW UserControlFlags ^M Where: UserControlFlags in Bit encoded Byte (2 chars) Bit 7: (MSB); Chiller On Bit 6: Chiller Off Bit 5: F/C degree display toggle (not active in .1 display mode) Bit 4: Fault Chiller shutoff enable Bit 3: Audible alarm enable Bit 2: Not used Bit 1: Auto Start with NC Bit 0: (LSB); Auto Start with NO ^J ^MASCII Linefeed and Carriage Return

Manual # 820-0109, Rev. Y, 07/08/10

- 47 -

Check Lytrons website www.Lytron.com for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

LYTRON COOLING SYSTEMS SERVICE POLICY


Lytrons cooling systems are the product of over 40 years of thermal engineering and manufacturing experience. We designed them to provide superior reliability, easy maintenance, and worry-free operation. However, occasionally a system may need repair. To ensure your process is back up and running quickly, Lytron has implemented the following cooling system service policy. Lytron's Standard Warranty Lytron's warranty is set forth at the end of the cooling system manual sent with each product. Diagnostic Consultation: At no cost, Lytron will attempt to diagnose the problem over the phone. Our service department can be reached by calling +1-781-933-7305 and following the menu. Service technicians are available 24 hours/7 days for consultation. Lytron strongly encourages customers to take advantage of this service before returning a cooling system to Lytron for evaluation. Often a problem with a system can be fixed quickly in-house or is an application problem. By working with Lytrons service department to troubleshoot a cooling system, you do not have the downtime and expense associated with returning the system to our factory. Phone diagnosis can be difficult and may actually be a trial and error process. Lytron will not assume any liability for misdiagnosis when diagnosing over the phone. Warranty and Non-warranty Returns: To return a cooling system, a Lytron Return Material Authorization (RMA) number must be obtained from Lytrons service department, which can be reached by calling +1-781-933-7305 and following the menu. Prior to calling, the system part number, serial number, and a detailed description of the problem must be recorded, as this information is required to assign an RMA number. A Purchase Order, (PO), is also required for the evaluation and repair charges if Lytron determines the system is not defective as defined by the warranty (see below for more details). The RMA number should be indicated on the outside packaging of the returned unit. Systems must be returned clean, dry, and free from chemicals to Lytrons factory, shipping costs prepaid. Lytron is not responsible for any damage incurred in the return shipment. Lytron ordinarily will evaluate the unit within 2 or 3 business days of receipt. Lytron will use reasonable effort to repair the unit promptly, in most cases within one week of receiving all the required parts. If upon examination Lytron determines the system is not defective as defined by the warranty, an evaluation fee of $375 to $595, depending upon the system type will be charged. The evaluation fee will be charged regardless of disposition (i.e.: scrap). In order to expedite the repair process for both warranty and non-warranty repair returns, a PO is required with recommended limits that will be determined when calling for the RMA. The amount suggested will cover the evaluation fee and most repair charges for non-warranty repairs. Lytron will proceed with the repair unless the total charges (evaluation and repair) exceed the amount of the PO. If this is the case, Lytron will provide a quote before proceeding with the repair. Repairs determined to be covered under warranty will not have any charges posted against the PO.

Manual # 820-0109, Rev. Y, 07/08/10

- 48 -

Check Lytrons website www.Lytron.com for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

Debit memos should not be issued for warranty and non-warranty repairs unless the unit is returned as a result of an out-of-box (new) failure. Lytron will warranty the repair for one year from the repair date under the terms of our standard warranty or for the balance of the original warranty, whichever is longer. Return Shipments: Lytrons warranty covers payment for standard, ground return shipment of warranted repairs. The incremental difference for expedited return shipments, if requested, are the responsibility of the customer. After non-warranty repair, Lytron will ship the system back using the customers preferred shipping method. Field Service/Installation Charges Where available, Lytron can arrange field service for cooling system installation or repair. Under no circumstances does Lytrons warranty cover on-site service. All on-site service must be arranged through Lytrons service department. The charges for this service are as follows: $250 administrative fee Plus the following: $100/hr for on-site services provided* Any related travel charges Parts not covered under warranty. * The hourly labor rate may vary depending upon city. Contact Lytrons service department for current rates in effect at the time.

All requests for On-Site Services require a PO or credit card in the amount of $800 before services will be scheduled. When using Lytron-arranged, on-site service, Lytron warranties the replacement parts and repair labor for 90 days from the repair date under the terms of our standard warranty or for the balance of the original warranty, whichever is longer. If non-authorized labor repairs the system or installs replacement parts, Lytron does not warranty the parts or work and this action potentially voids any remaining warranty. Lytron is expanding its worldwide service presence. Please contact the Service Department for the latest areas where on site service is available. Replacement Parts: Replacement parts can be ordered using a credit card or purchase order. Parts being returned from systems under warranty should be returned using a Lytron issued RMA number. If the parts are found to be defective and the claim is within the warranty period, credit will be issued for the price of the parts and one-way ground shipping charges. If the parts are not defective or indicate end user damage, no credit will be issued. Lytron will not cover the incremental cost of air shipment of replacement parts, regardless of warranty status. In-stock parts normally will be shipped the next business day; non-stocked parts will be shipped as quickly as reasonably possible. This policy is subject to change. Please check with Lytrons service department for the current policy.
Form F4.3.25 Rev D, 7/21/04

Manual # 820-0109, Rev. Y, 07/08/10

- 49 -

Check Lytrons website www.Lytron.com for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

LYTRON KODIAK RECIRCULATING CHILLER STANDARD WARRANTY


Lytron agrees that the apparatus manufactured by it will be free from defects in materials and workmanship for the warranty period under normal use and service and when properly installed. The warranty period for recirculating chillers is two years from date of shipment of such apparatus to the original purchaser, maintenance items excluded, and one year from date of shipment of such apparatus to the original purchaser for all other products Lytron sells. Lytrons obligation under this agreement is limited solely to repair or replacement, at its option, at its factories, of any part or parts thereof, returned to Lytron with transportation charges prepaid, which examination shall disclose to Lytrons satisfaction to have been defective. THE FOREGOING EXPRESS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING BUT NOT LIMITED TO WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE. LYTRON'S OBLIGATION UNDER THIS WARRANTY IS STRICTLY AND EXCLUSIVELY LIMITED TO THE REPAIR OR REPLACEMENT OF DEFECTIVE COMPONENT PARTS AND LYTRON DOES NOT ASSUME OR AUTHORIZE ANYONE TO ASSUME FOR IT ANY OTHER OBLIGATION. LYTRON ASSUMES NO RESPONSIBILITY FOR INCIDENTAL, CONSEQUENTIAL, OR OTHER DAMAGES INCLUDING, BUT NOT LIMITED TO LOSS OR DAMAGE TO PROPERTY, LOSS OF PROFITS OR REVENUE, LOSS OF THE UNIT, LOSS OF TIME, OR INCONVENIENCE. Lytrons liability does not include any labor charges for replacement of parts, adjustments, repairs, or any other work done outside its factories and its liability does not include any resulting damage to persons, property, equipment, goods or merchandise arising out of any defect in or failure of its apparatus. Lytrons obligation to repair or replace shall not apply to any apparatus which shall have been repaired or altered outside of its factory in any way, or which has been subject to negligence, to misuse, or to pressures in excess of stated limits. On parts not of Lytrons manufacture, such as motors, controls, etc., Lytron extends only those warranties given to Lytron, Inc. to the extent Lytron can do so. Lytrons agreement hereunder runs only to the immediate purchaser from Lytron, Inc. and does not extend, expressly or by implication, to any other person.
Form F4.3.18 Rev E June 6, 2003

Manual # 820-0109, Rev. Y, 07/08/10

- 50 -

Check Lytrons website www.Lytron.com for the most current technical information.

Kodiak Recirculating Chiller Technical Manual

DECLARATION OF CONFORMITY

Manual # 820-0109, Rev. Y, 07/08/10

- 51 -

Check Lytrons website www.Lytron.com for the most current technical information.

You might also like