Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Summation CT

Download as pdf or txt
Download as pdf or txt
You are on page 1of 13
At a glance
Powered by AI
Summation current transformers are used to add together currents from multiple sources for measurement purposes. They allow summing currents with similar phases but differing loads or voltages.

The secondary connections of each main transformer are connected to the allocated primary inputs of the summation current transformer. The number of windings are proportioned according to the primary nominal current and total nominal current being connected.

Additional information like test certificates, excitation curves, expanded frequency ranges, alternative enclosures, and custom mounting options can be requested when ordering current transformers.

Technical documenTaTion

Summation current transformers, type KSu/SuSK

DEIF A/S Frisenborgvej 33 DK-7800 Skive Tel.: +45 9614 9614 Fax: +45 9614 9615 info@deif.com www.deif.com Document no.: 4921210113B

current transformers overview


click on a product name or check mark to jump to information page. Page Primary nominal current A 1 2.5 5 10 15 20 25 30 40 50 60 75 80 100 125 150 200 250 300 400 500 600 750 800 1000 1200 1250 1500 1600 1800 2000 2500 3000 3200 4000 5000 6000 7500 Primary conductor in mm Round conductor in mm Transform. width in mm 57 57 65 65 65 65 65 65 5 KSU 2
3 3

6 KSU 3
3 3

7 SUSK 3
3 3

8 SUSK 4
3 3

9 SUSK 5
3 3

10 SUSK 6
3 3

11 SUSK 7
3 3

12 SUSK 8
3 3

Current Current Current Current Current Current Current Current curcuits curcuits curcuits curcuits curcuits curcuits curcuits curcuits

Page Primary nominal current A 1 2.5 5 10 15 20 25 30 40 50 60 75 80 100 125 150 200 250 300 400 500 600 750 800 1000 1200 1250 1500 1600 1800 2000 2500 3000 3200 4000 5000 6000 7500 Primary conductor in mm Round conductor in mm Transform. width in mm

* For the current transformers above, click-on mountings are available for fitment onto 35mm DIN-rails (DIN 50022).

www.deif.com

Guidance when ordering summation current transformers


Summation current transformers are suitable for the summation of several synchronized alternating currents with similar phases but with differing load phase shifts. It is also possible to have the summation of currents with varied nominal voltages of similar phase positions. These measurements cannot be used for tariff applications, as the existing voltage differences are recorded as errors. With the counter connection of the main transformer to the summation current transformer, it is possible to receive secondary currents which are proportional to the differences of the primary input currents. The built-in technical know-how enables the summation current transformers to add secondary currents of varying nominal transmissions from the main transformer. The secondary connections of each main transformer are connected to the allocated primary inputs of the summation current transformers. The number of windings of individual partially wound primary circuits of the summation current transformer is proportionally aligned to the ratio of the primary nominal current of the corresponding main transformer, and to the sum of the nominal currents of all the summation current transformers being connected to the main transformer. For the visual display of the current, a measuring unit can be used with a measuring range similar to the secondary nominal current of the summation current transformers. It is irrelevant for the main transformers with similar nominal transmission ratios, to which primary circuit of the summation current transformer the connection is made. With main transformers of different nominal transmission ratios, care must be taken to adhere to the assigned connection to the terminals of the summation current transformers. Is the current flow in the main transformer interrupted, the secondary circuit of the main transformer must neither be short-circuited nor be connected to the summation current transformer, or to the main transformer. Summation current transformers with unallocated primary circuits must remain open for a later connection to an additional main transformer. The secondary output current of the summation current transformer is in this instance lower than the secondary nominal current of the summation current transformer by a quantity equal to the ratio of the primary nominal current of this missing main transformer and the sum of all the primary nominal currents of the main transformer. The nominal secondary current of a main transformer must be equal to the nominal primary current of the input allocation of the summation current transformer.

www.deif.com

Guidance when ordering summation current transformers


Please find below an example for the correct selection of measuring components for summation current transformers. example: Actual situation:

3 transmission ratios

Overall current Burden: 1 current meter 1 power recorder

1000 / 5 VA 800 / 5 VA 600 / 5 VA 2400 / 5 VA

Looking for:

1 summation current transformer and the VA power of an individual main transformer

Required active performance of the summation current transformer: Current meter Performance recorder Measurement conductor loss consumption Po summation ct Interim result 1.5 VA 7.0 VA 1.5 VA 4.0 VA 14.0 VA

The individual transformer must provide its VA share from this 14.0 VA corresponding to its ratio to the total transmission. Consideration must also be given to the respective power loss between the main transformer and the summation transformer plus other possible losses. 1000 14.0 = 5.83 VA + additional possible losses 2400 800 14.0 = 4.67 VA + additional possible losses 2400 600 14.0 = 3.50 VA + additional possible losses 2400

1. Main transformer 1000 / 5

2. Main transformer 800 / 5A

3. Main transformer 600 / 5A

The VA values of the main transformers are to be rounded up to the corresponding VA values in our charts. The ratio of the primary current of a main transformer to the sum of the primary currents of all main current transformers the ratio must not exceed 1:8.

important indication to the power measuring Too many rising deviation can prevent the measuring transformer acting as a current transformer from fulfilling its protective function with regard to the connected measuring units, as in normal operation its functions is well below its saturation limit, and in the event of over currents, the saturation limit is reached considerably later and takes the function almost as a protection current transformer. If there is too much of a decrease, the measuring transformer, as a result of the continuous excess demands will reach the saturation limit too soon and indirectly function as a switch, rendering a measuring impossible.

www.deif.com

Summation current transformer


Secondary current Primary current A Burden VA 5 10 15 20 25 30 5 10 15 20 25 30

KSu 2
5a
Accuracy class 1 0.5 Art.-no. Art.-no.
3 3 3 3 3 3 3 3 3 3 3 3 3 3 3

1a
Accuracy class 1 0.5 Art.-no. Art.-no.
3 3 3 3 3 3 3 3 3 3 3 3 3 3 3

Type

1+1

2
5 7.0(2.24)

5+5

3 3 3

3 3 3

5 5.0(2.16) 7 2.0(2.83) 8 7.0(3.42)

1 27.0(5 .00)

K AK
9 0.0(3.54)

K AL BL CL

9 3.5(3.68)

BK CK
2 9.8(1.17) 1 9.4(0.76)

xxx xx xxxxx xxx xxx xxx xxx

5 0.0(1.96) 8 0.0(3.15)

Connection example for different ratios AK-AL BK-BL CK-CL = = = 1000/5 800/5 600/5

Weight Security factor DIN rail mounting Sealed shutter Primary


www.deif.com

0.300-1.100kg (0.66-2.43lbs) FS 5 Not available Type: 59041 (x2)

Summation current transformer


Secondary current Primary current A 1+1+1 Burden VA 5 10 15 30 5 10 15 30

KSu 3
5a
Accuracy class 1 0.5 Art.-no. Art.-no.
3 3 3 3 3 3 3 3 3 3 3 3 3 3

1a
Accuracy class 1 0.5 Art.-no. Art.-no.
3 3 3 3 3 3 3 3 3 3 3 3 3 3

Type 3

5+5+5

5 7.0(2.24)

5 5.0(2.16) 7 2.0(2.83) 8 7.0(3.42)

1 27.0(5 .00)

K AK
9 0.0(3.54)

K AL BL CL

9 3.5(3.68)

BK CK
2 9.8(1.17) 1 9.4(0.76)

xxx xx xxxxx xxx xxx xxx xxx

5 0.0(1.96) 8 0.0(3.15)

Connection example for different ratios AK-AL BK-BL CK-CL = = = 1000/5 800/5 600/5

Weight Security factor DIN rail mounting Sealed shutter Primary


6

0.300-0.750kg (0.66-1.65lbs) FS 5 Not available Type: 59041 (x2)

www.deif.com

Summation current transformer


Secondary current Primary current A 1+1+1 Burden VA 5 10 15 30 5 10 15 30

SuSK 3
5a
Accuracy class 1 0.5 Art.-no. Art.-no.
3 3 3 3 3 3 3 3 3 3 3 3 3 3 3

1a
Accuracy class 1 0.5 Art.-no. Art.-no.
3 3 3 3 3 3 3 3 3 3 3 3 3

Type 3

5+5+5

6 5 .0 (2 .5 5 )

6 0 .0 (2 .3 6 )

AL BL

EL FL GL HL

1 40 .0 (5 .5 1 )

1 36 .5 (5 .3 7 )

CL DL

5 4 .0 (2 .1 2 )

xxxxx xx xxxx xxx xxx xxx

9 5 .0 (3 .7 4 ) 1 2 2 .0 (4.80 ) 1 5 6 .0 (6.14 )

Weight Security factor DIN rail mounting Sealed shutter Primary Sealed shutter Primary
www.deif.com

0.480-1.130kg (1.06-2.49lbs) FS 5 Not available Type: 59041 (x2) Type: 59042

Summation current transformer


Secondary current Primary current A 1+1+1+1 Burden VA 5 10 15 25 30 5 10 15 25 30

SuSK 4
5a
Accuracy class 1 0.5 Art.-no. Art.-no.
3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3

1a
Accuracy class 1 0.5 Art.-no. Art.-no.
3 3 3 3 3 3

Type

5+5+5+5

3 3 3 3 3

3 3 3

6 5 .0 (2 .5 5)

6 0 .0 (2 .3 6)

AL BL

EL FL GL HL

1 40 .0 (5 .5 1 )

1 36 .5 (5 .3 7 )

CL DL

5 4 .0 (2 .1 2 )

xxxxx xx xxxx xxx xxx xxx

9 5 .0 (3 .7 4 ) 1 2 2 .0 (4.80 ) 1 5 6 .0 (6.14 )

Weight Security factor DIN rail mounting Sealed shutter Primary Sealed shutter Primary
8

0.500-1.210kg (1.10-2.67lbs) FS 5 Not available Type: 59041 (x2) Type: 59042

www.deif.com

Summation current transformer


Secondary current Primary current A 1+1+1+1+1 Burden VA 5 10 15 30 5 10 15 30

SuSK 5
5a
Accuracy class 1 0.5 Art.-no. Art.-no.
3 3 3 3 3 3 3 3 3 3 3 3 3 3 3

1a
Accuracy class 1 0.5 Art.-no. Art.-no.
3 3 3 3 3 3 3 3 3 3 3 3 3

Type 5

5+5+5+5+5

6 5 .0 (2 .5 5)

6 0 .0 (2 .3 6)

AL BL

EL FL GL HL

1 4 0 .0 (5 .5 1 )

1 3 6 .5 (5 .3 7 )

CL DL

5 4 .0 (2 .1 2 )

xxxxx xx xxxx xxx xxx xxx

9 5 .0 (3 .7 4 ) 1 2 2 .0 (4.80 ) 1 5 6 .0 (6.14 )

Weight Security factor DIN rail mounting Sealed shutter Primary Sealed shutter Primary
www.deif.com

0.500-1.240kg (1.10-2.73lbs) FS 5 Not available Type: 59041 (x2) Type: 59042

Summation current transformer


Secondary current Primary current A 1+1+1+1+1+1 Burden VA 5 10 15 30 5 10 15 30

SuSK 6
5a
Accuracy class 1 0.5 Art.-no. Art.-no.
3 3 3 3 3 3 3 3 3 3 3 3 3 3 3

1a
Accuracy class 1 0.5 Art.-no. Art.-no.
3 3 3 3 3 3 3 3 3 3 3 3 3

Type 6

5+5+5+5+5+5

6 5 .0 (2 .5 5 )

6 0 .0 (2 .3 6 )

AL BL

EL FL GL HL

1 40 .0 (5 .5 1 )

1 36 .5 (5 .3 7 )

CL DL

5 4 .0 (2 .1 2 )

xxxxx xx xxxx xxx xxx xxx

9 5 .0 (3 .7 4 ) 1 2 2 .0 (4.80 ) 1 5 6 .0 (6.14 )

Weight Security factor DIN rail mounting Sealed shutter Primary Sealed shutter Primary
10

0.500-1.250kg (1.10-2.76lbs) FS 5 Not available Type: 59041 (x2) Type: 59042

www.deif.com

Summation current transformer


Secondary current Primary current A 1+1+1+1+1+1+1 Burden VA 5 10 15 30 5 10 15 30

SuSK 7
5a
Accuracy class 1 0.5 Art.-no. Art.-no.
3 3 3 3 3 3 3 3 3 3 3 3 3 3 3

1a
Accuracy class 1 0.5 Art.-no. Art.-no.
3 3 3 3 3 3 3 3 3 3 3 3 3

Type 7

5+5+5+5+5+5+5

6 5 .0 (2 .5 5 )

6 0 .0 (2 .3 6 )

AL BL

EL FL GL HL

1 4 0 .0 (5 .5 1 )

1 36 .5 (5 .3 7 )

CL DL

5 4 .0 (2 .1 2 )

xxxxx xx xxxx xxx xxx xxx

9 5 .0 (3 .7 4 ) 1 2 2 .0 (4.80 ) 1 5 6 .0 (6.14 )

Weight Security factor DIN rail mounting Sealed shutter Primary Sealed shutter Primary
www.deif.com

0.500-1.200kg (1.10-2.65lbs) FS 5 Not available Type: 59041 (x2) Type: 59042

11

Summation current transformer


Secondary current Primary current A 1+1+1+1+1+1+1+1 Burden VA 5 10 15 30 5 10 15 30

SuSK 8
5a
Accuracy class 1 0.5 Art.-no. Art.-no.
3 3 3 3 3 3 3 3 3 3 3 3 3 3 3

1a
Accuracy class 1 0.5 Art.-no. Art.-no.
3 3 3 3 3 3 3 3 3 3 3 3 3

Type 8

5+5+5+5+5+5+5+5

6 5 .0 (2 .5 5)

6 0 .0 (2 .3 6)

AL BL

EL FL GL HL

1 4 0 .0 (5 .5 1 )

1 3 6 .5 (5 .3 7 )

CL DL

5 4 .0 (2 .1 2 )

xxxxx xx xxxx xxx xxx xxx

9 5 .0 (3 .7 4 ) 1 2 2 .0 (4.80 ) 1 5 6 .0 (6.14 )

Weight Security factor DIN rail mounting Sealed shutter Primary Sealed shutter Primary
12

0.710-1.280kg (1.57-2.82lbs) FS 5 Not available Type: 59041 (x2) Type: 59042

www.deif.com

current transformers

accessories for dcT

Test certificate On request, we can provide you with a test certificate for a specific current transformer along with the CT. Please inform us when placing your order. Sealed shutter On request, we can supply a transparent plastic cover. The cover seals the connections on the CT in a way that leaves the type label visible. Please check availability on each individual data sheet.

excitation curve On request, we can provide you with an excitation curve for a specific current transformer along with the CT. Please inform us when placing your order. optional frequency Frequency range for a standard CT is 50-60Hz. On request, we can provide you with a frequency range from 16 2/3 400Hz. Please inform us when placing your order. cast resin Cast resin is standard for all CTs with a nominal current >4,000A. On request, all CTs with a nominal current <4,000A can be produced with cast resin. Please inform us when placing your order. The min. and max. weight specification for each type refers to standard versions. The specification is different if cast resin is ordered for CTs <4,000A. mounting Foot angle for screw mounting and busbar mounting screws with isolating protection caps are supplied along with the CT. DIN-rail mounting for tubes, plug-ins and protection transformers is available on request for certain CT types. Please check availability on each individual data sheet.

www.deif.com

13

You might also like