Crest Boiler Manual
Crest Boiler Manual
Crest Boiler Manual
Installation & Operation Manual Models: 1.5 - 2.0 - 2.5 - 3.0 - 3.5
WARNING This manual must only be used by a qualified heating installer / service technician. Read all instructions, including this manual and the Crest Service Manual, before installing. Perform steps in the order given. Failure to comply could result in severe personal injury, death, or substantial property damage.
Contents
HAZARD DEFINITIONS .................................................... 2 PLEASE READ BEFORE PROCEEDING ........................ 3 THE CREST -- HOW IT WORKS ................................... 4-5 RATINGS ........................................................................... 6 1. DETERMINE BOILER LOCATION Clearances ......................................................................... 7 Provide Air Openings to Room .......................................... 8 Flooring and Foundation ................................................... 8 Vent and Air Piping ............................................................ 8 Prevent Combustion Air Contamination ............................. 8 Using an Existing Vent System to Install a New Boiler ..... 9 Corrosive Contaminants and Sources ............................... 9 Removing a Boiler from Existing Common Vent.............. 10 Remove Boiler from Wood Pallet ..................................... 11 Combustion and Ventilation Air Requirements ........... 12-13 2. GENERAL VENTING Direct Venting Options - Sidewall Vent ............................ 14 Direct Venting Options - Vertical Vent .............................. 14 Direct Venting Options - Vert. Vent, Opt. Rm Air............. 14 Direct Venting Options - Vert. Vent, Sidewall Air ............. 14 Install Vent and Combustion Air Piping ........................... 15 Air Inlet Pipe Materials................................................ 15 Requirements for Installation in Canada .......................... 15 Vent and Air Piping .......................................................... 16 Air Intake / Vent Connections .......................................... 16 Min./Max. Combustion Air & Vent Piping Lengths ........... 17 Vent and Air Piping .......................................................... 17 Common Venting ............................................................. 18 3. VERTICAL DIRECT VENTING Vent/Air Termination - Vertical ......................................... 19 Determine Location..................................................... 19 Prepare Roof Penetrations ......................................... 19 Termination and Fittings ........................................ 19-20 Multiple Vent/Air Terminations .................................... 20 4. SIDEWALL DIRECT VENTING Vent/Air Termination - Sidewall ................................... 21-23 Determine Location................................................ 21-23 Prepare Wall Penetrations .......................................... 22 Termination and Fittings ............................................. 22 Multiple Vent/Air Terminations ............................... 22-23 Room Air ..................................................................... 23 5. HYDRONIC PIPING System Water Piping Methods ......................................... 24 Low Water Cutoff Device ................................................. 24 Chilled Water System....................................................... 24 Freeze Protection ............................................................. 24 General Piping Information .............................................. 24 Circulator Sizing ............................................................... 25 Near Boiler Piping Components .................................. 26-30 6. GAS CONNECTIONS Connecting Gas Supply Piping ........................................ 31 Natural Gas ...................................................................... 32 Pipe Sizing for Natural Gas ........................................ 32 Natural Gas Supply Pressure Requirements ............. 32 Propane Gas .................................................................... 32 Pipe Sizing for Propane Gas ...................................... 32 Propane Supply Pressure Requirements ................... 32 Check Inlet Gas Supply .............................................. 33-34 Gas Pressure ................................................................... 34 Gas Valve Replacement .................................................. 34 7. FIELD WIRING Line Voltage Connections ................................................ 35 Low Voltage Connections ................................................ 36 Wiring of the Cascade ...................................................... 37 8. CONDENSATE DISPOSAL Condensate Drain ............................................................ 39 9. STARTUP ............................................................... 40-45 10. OPERATING INFORMATION General........................................................................ 46-48 Cascade ........................................................................... 49 Sequence of Operation .................................................... 50 Status Screen ................................................................... 51 Main Screen ..................................................................... 52 11. MAINTENANCE Maintenance & Annual Startup .............................. 53-57 12. DIAGRAMS Ladder Diagrams ........................................................ 58 Wiring Diagram ........................................................... 59 Revision Notes .................................................. Back Cover
Hazard definitions
DANGER
The following defined terms are used throughout this manual to bring attention to the presence of hazards of various risk levels or to important information concerning the life of the product. DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or serious CAUTION indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate CAUTION used without the safety alert symbol indicates a potentially hazardous situation which, if not avoided, may result in property damage. NOTICE indicates special instructions on installation, operation, or maintenance that are important but not related to personal injury or property damage.
Boiler operation
Do not block flow of combustion or ventilation air to the boiler. Should overheating occur or gas supply fail to shut off, do not turn off or disconnect electrical supply to circulator. Instead, shut off the gas supply at a location external to the appliance. Do not use this boiler if any part has been under water. The possible damage to a flooded appliance can be extensive and present numerous safety hazards. Any appliance that has been under water must be replaced.
Boiler water
Thoroughly flush the system (without boiler connected) to remove sediment. The high-efficiency heat exchanger can be damaged by build-up or corrosion due to sediment. Do not use petroleum-based cleaning or sealing compounds in the boiler system. Gaskets and seals in the system may be damaged. This can result in substantial property damage. Do not use homemade cures or boiler patent medicines. Serious damage to the boiler, personnel, and/or property may result. Continual fresh make-up water will reduce boiler life. Mineral buildup in the heat exchanger reduces heat transfer, overheats the stainless steel heat exchanger, and causes failure. Addition of oxygen carried in by makeup water can cause internal corrosion in system components. Leaks in boiler or piping must be repaired at once to prevent the need for makeup water.
WARNING
Blowers
The blowers pull in air and gas through the venturis (item 34). Air and gas mix inside the blowers and are pushed into the burner, where they burn inside the combustion chamber.
5. 6.
7.
8.
9.
34. Venturis
Separate venturis control air and gas flow into two (2) independent burner sections.
(continued)
29
11
7 19
10
36
1
5
35
Front View
18
9 Rear View
15 34 16 23 19 29 21 22 25 26 28 30 31
37 3 34 33 12 13
20 12 27 4
17
14
32
Ratings
Other Specifications
Net I=B=R Ratings Water, MBH
(Note 2)
Input MBH
(Note 4)
Air Size
Vent Size
Weight w/Water
(lbs.)
(Note 3)
Max 1500 2000 2500 3000 3500 1380 1840 2300 2760 3220
*For LP models the minimum input is 420 MBH. NOTICE Notes: 1. 2. The ratings are based on standard test procedures prescribed by the United States Department of Energy. Net I=B=R ratings are based on net installed radiation of sufficient quantity for the requirements of the building and nothing need be added for normal piping and pickup. Ratings are based on a piping and pickup allowance of 1.15. Crest boilers require special gas venting. Use only the vent materials and methods specified in the Crest Installation and Operation Manual. Standard Crest boilers are equipped to operate from sea level to 4,500 feet only with no adjustments. High altitude Crest boilers are equipped to operate from 3,000 to 12,000 feet. High altitude models are manufactured with different control parameters for high altitude operation, but the sequence of operation given in this manual remains the same as the standard boilers. A high altitude label (as shown in FIG A.) is also afxed to the unit. The boiler will de-rate by 4% for each 1,000 feet above sea level up to 4,500 feet and 4.5% for each 1,000 feet above 4,500 feet. Ratings have been conrmed by the Hydronics Institute, Section of AHRI. Maximum allowed working pressure is located on the rating plate.
HIGH ALTITUDE
3,000 FT. TO 12,000 FT.
3.
4. 5.
6.
7.
Provide clearances:
NOTICE
2.
3.
Clearances from combustible materials - Hot water pipes........................................................ 1/4" - Sides .......................................................................... 0" - Rear........................................................................... 0" - Front ......................................................................... 0" - Top ........................................................................... 0" - Floor ....................................................... Combustible - Vent pipe - Follow special vent system manufacturers instructions Recommended clearances for service access - Sides .......................................................................... 24" - Rear........................................................................... 24" - Front ......................................................................... 30" - Top ........................................................................... 24" Figure 1-1 Recommended Service Clearances
1/4" (6 MM) MINIMUM CLEARANCE AROUND HOT WATER PIPES
Failure to keep boiler area clear WARNING and free of combustible materials, gasoline, and other flammable liquids and vapors can result in severe personal injury, death, or substantial property damage. 4. The Crest must be installed so that gas control system components are protected from dripping or spraying water or rain during operation or service. 5. If a new boiler will replace an existing boiler, check for and correct system problems, such as: System leaks causing oxygen corrosion or heat exchanger cracks from hard water deposits. Incorrectly-sized expansion tank. Lack of freeze protection in boiler water causing system and boiler to freeze and leak. 6. The appliance must be installed on a level floor, both front to back and side to side, for proper condensate drainage.
24" LEFT
24" TOP
CLOSED DOOR
30" FRONT
If flooding is possible, elevate the boiler sufficiently to prevent water from reaching the boiler. WARNING Assure that the floor and structure is sufficient to support the installed weight of the boiler, including the water content in the heat exchanger. If not, structural building failure will result, causing severe personal injury, death, or substantial property damage.
(continued)
Table 1A Corrosive Contaminants and Sources Products to avoid: Spray cans containing chloro/fluorocarbons Permanent wave solutions Chlorinated waxes/cleaners Chlorine-based swimming pool chemicals Calcium chloride used for thawing Sodium chloride used for water softening Refrigerant leaks Paint or varnish removers Hydrochloric acid/muriatic acid Cements and glues Antistatic fabric softeners used in clothes dryers Chlorine-type bleaches, detergents, and cleaning solvents found in household laundry rooms Adhesives used to fasten building products and other similar products Areas likely to have contaminants Dry cleaning/laundry areas and establishments
Check the following venting components before installing: Material - For materials listed for use with this appliance, see Section 2 - General Venting, Table 2A. For stainless steel venting, an adapter of the same manufacturer (Table 2B) may be used at the flue collar connection. Size - To ensure proper pipe size is in place, see Table 2C. Check to see that this size is used throughout the vent system. Manufacturer - Only use the listed manufacturers and their type product listed in Table 2A for CAT IV positive pressure venting with flue producing condensate. Supports - Non-combustible supports must be in place allowing a minimum 1/4" rise per foot. The supports should adequately prevent sagging and vertical slippage, by distributing the vent system weight. For additional information, consult the vent manufacturers instructions for installation. Terminations - Carefully review Sections 2 through 4 to ensure requirements for the location of the vent and air terminations are met and orientation of these fit the appropriate image from the Sidewall or Vertical options listed in the General Venting Section. Seal - With prior requirements met, the system should be tested to the procedure listed in parts (c) through (f) of the Removal of an Existing Boiler Section on page 10. With stainless steel vent, seal and connect all pipe and components as specified by the vent manufacturer used. If any of these conditions are not met, WARNING the existing system must be updated or replaced for that concern. Failure to follow all instructions can result in flue gas spillage and carbon monoxide emissions, causing severe personal injury or death.
Swimming pools Metal fabrication plants Beauty shops Refrigeration repair shops Photo processing plants Auto body shops Plastic manufacturing plants Furniture refinishing areas and establishments New building construction Remodeling areas Garages with workshops
WARNING
f.
At the time of removal of an existing boiler, the following steps shall be followed with each appliance remaining connected to the common venting system placed in operation, while the other appliances remaining connected to the common venting system are not in operation. a. Seal any unused openings in the common venting system. b. Visually inspect the venting system for proper size and horizontal pitch and determine there is no blockage or restriction, leakage, corrosion, or other deficiencies, which could cause an unsafe condition. c. Test vent system Insofar as is practical, close all building doors and windows and all doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dryers and any appliance not connected to the common venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan. Close fireplace dampers.
g. Any improper operation of the common venting system should be corrected so the installation conforms with the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and/or CAN/CSA B149.1, Natural Gas and Propane Installation Code. When resizing any portion of the common venting system, the common venting system should be resized to approach the minimum size as determined using the appropriate tables in Part 11 of the National Fuel Gas Code, ANSI Z223.1/NFPA 54 and/or CAN/CSA B149.1, Natural Gas and Propane Installation Code.
10
(continued)
b.
The boiler can now be removed from the pallet using a lift truck lifting from the front or rear of the boiler. If lifting from the front, the lift truck forks must extend at least half way under the boiler heat exchanger to assure proper lifting technique Maintain minimum specified clearances for adequate operation. with no damage to the boiler. All installations must allow sufficient space for servicing the vent connections, water pipe connections, piping and other Failure to assure the truck forks are WARNING auxiliary equipment, as well as the appliance. The clearance long enough to extend at least halfway labels on each appliance note the same service and combustible under the boiler heat exchanger will clearance requirements as shown in this manual. result in the boiler tipping off the lift Multiple boilers may be installed side by side with no clearance truck, and potentially falling. This will between adjacent boilers because this boiler is approved for zero result in severe personal injury, death, or clearance from combustible surfaces; however, service access substantial property damage. will be limited from the sides. d. If lifting by crane is desired, remove the top access panels to gain access to the lifting lugs located on the Consult the Venting section of this manual for specific boiler (see FIG. 1-3). It is also recommended that the installation instructions for the appropriate type of venting upper and lower front panels along with both front system that you will be using. side panels be removed (no tools required). NOTICE Do not drop the boiler or bump the jacket on the floor or pallet. Damage to the boiler can result.
c.
FRONT
REAR
11
Combustion and ventilation air requirements for appliances drawing air from the equipment room
Provisions for combustion and ventilation air must be in accordance with Air for Combustion and Ventilation, of the latest edition of the National Fuel Gas Code, NFPA 54 / ANSI Z223.1, in Canada, the latest edition of CGA Standard B149 Installation Code for Gas Burning Appliances and Equipment, or applicable provisions of the local building codes. The equipment room MUST be provided with properly sized openings and/or be of sufficient volume to assure adequate combustion air and proper ventilation for all gas fired appliances in the equipment room to assure adequate combustion air and proper ventilation. The requirements shown are for the appliance only; additional gas fired appliances in the equipment room will require an increase in the net free area and/or volume to supply adequate combustion air for all appliances. No combustion air openings are needed when the appliance is installed in a space with a volume NO LESS than 50 cubic feet per 1,000 Btu/hr of all installed gas fired appliances and the building MUST NOT be of Tight Construction3. A combination of indoor and outdoor combustion air may be utilized by applying a ratio of available volume to required volume times the required outdoor air opening(s) size(s). This must be done in accordance with the National Fuel Gas Code, NFPA 54 / ANSI Z223.1.
Figure 1-5_Combustion Air Through Ducts 2. If combustion and ventilation air is taken from the outdoors using a duct to deliver the air to the equipment room, each of the two openings should be sized based on a minimum free area of one square inch per 2000 Btu/hr (11 cm2 per kW) of input (see FIG. 1-5).
Figure 1-6_Combustion Air from Interior Space 3. If air is taken from another interior space combined with the equipment room: (a) Two spaces on same story: Each of the two openings specified above should have a net free area of one square inch for each 1000 Btu/hr (22 cm2 per kW) of input, but not less than 100 square inches (645 cm2) (see FIG. 1-6). (b) Two spaces on different stories: One or more openings should have a net free area of two square inches per 1000 Btu/hr (44 cm2 per kW).
Figure 1-4_Combustion Air Direct from Outside 1. If air is taken directly from outside the building with no duct, provide two permanent openings to the equipment room each with a net free area of one square inch per 4000 Btu/hr input (5.5 cm2 per kW) (see FIG. 1-4).
12
1
4.
(continued)
CAUTION
Under no circumstances should the equipment room ever be under negative pressure. Particular care should be taken where exhaust fans, attic fans, clothes dryers, compressors, air handling units, etc., may take away air from the unit.
Combustion air requirements are based on the latest edition of the National Fuel Gas Code, NFPA 54 / ANSI Z223.1; in Canada refer to the latest edition of CGA Standard CAN/CSA B149.1. Check all local code requirements for combustion air. All dimensions based on net free area in square inches. Metal louvers or screens reduce the free area of a combustion air opening a minimum of approximately 25%. Check with louver manufacturers for exact net free area of louvers. Where two openings are provided, one must be within 12" (30 cm) of the ceiling and one must be within 12" (30 cm) of the floor of the equipment room. Each opening must have a net free area as specified in Table 1B. Single openings shall commence within 12" (30 cm) of the ceiling. The minimum dimension of air openings shall not be less than 3" (80 mm).
The combustion air supply must be completely free of any flammable vapors that may ignite or chemical fumes which may be corrosive to the appliance. Common corrosive chemical fumes which must be avoided are fluorocarbons and other halogenated compounds, most commonly present as refrigerants or solvents, such as Freon, trichlorethylene, perchlorethylene, chlorine, etc. These chemicals, when burned, form acids which quickly attack the stainless steel heat exchanger, headers, flue collectors, and the vent system. The result is improper combustion and a non-warrantable, premature appliance failure. EXHAUST FANS: Any fan or equipment which exhausts air from the equipment room may deplete the combustion air supply and/or cause a downdraft in the venting system. Spillage of flue products from the venting system into an occupied living space can cause a very hazardous condition that must be corrected immediately.
FIG. 1-4
*Outside Air from 2 Openings Directly from Outdoors1
Top Opening, in2 (cm2) Bottom Opening, in2 (cm2)
TABLE - 1B MINIMUM RECOMMENDED COMBUSTION AIR SUPPLY TO EQUIPMENT ROOM FIG. 1-5 FIG. 1-6
*Outside Air from 2 Ducts Delivered from Outdoors1
Top Opening, in2 (cm2) Bottom Opening, in2 (cm2)
FIG. 1-7
*Outside Air from 1 Opening Directly from Outdoors, in2 (cm2)1
Inside Air from 2 Ducts Delivered from Interior Space2 Same Story
Top Opening, in2 (cm2) Bottom Opening, in2 (cm2)
Model Number
Different Stories
Total Opening, in2 (cm2)
375 (2420) 500 (3226) 625 (4033) 750 (4839) 875 (5646)
375 (2420) 500 (3226) 625 (4033) 750 (4839) 875 (5646)
750 (4839) 1000 (6452) 1250 (8065) 1500 (9678) 1750 (11291)
750 (4839) 1000 (6452) 1250 (8065) 1500 (9678) 1750 (11291)
1500 (9678) 2000 (12904) 2500 (16129) 3000 (19355) 3500 (22581)
1500 (9678) 2000 (12904) 2500 (16129) 3000 (19355) 3500 (22581)
3000 (19355) 4000 (25807) 5000 (32258) 6000 (38710) 7000 (45162)
500 (3226) 667 (4304) 833 (5381) 1000 (6452) 1167 (7530)
The above requirements are for the appliance only; additional gas fired appliances in the equipment room will require an increase in the net free area and/or volume to supply adequate combustion air for all appliances. No combustion air openings are needed when the appliance is installed in a space with a volume NO LESS than 50 cubic feet per 1,000 Btu/hr of all installed gas fired appliances. Buildings MUST NOT be of *Tight Construction3.
1 2 3
Outside air openings shall directly communicate with the outdoors. Combined interior space must be 50 cubic feet per 1,000 Btu/hr input. Buildings MUST NOT be of *Tight Construction.
Tight Construction is defined as a building with less than 0.40 ACH (air changes per hour). For buildings of Tight Construction, provide air openings into the building from outside.
13
General venting
Direct venting
Sidewall
Vertical
Sidewall
Vertical
14
General venting
(continued)
b. c.
d.
The PVC, CPVC, or ABS air inlet pipe should be cleaned and sealed with the pipe manufacturers recommended solvents and standard commercial pipe cement for the material used. The ABS, PVC, CPVC, Dryer Vent or Flex Duct air inlet pipe should use a silicone sealant to ensure a proper seal at the appliance connection and the air inlet cap connection. Dryer vent or flex duct should use a screw type clamp to seal the vent to the appliance air inlet and the air inlet cap. Proper sealing of the air inlet pipe ensures that combustion air will be free of contaminants and supplied in proper volume.
15
General venting
Air intake/vent connections
1. Combustion Air Intake Connector (FIG. 2-1) - Used to provide combustion air directly to the unit from outdoors. A fitting is provided with the unit for final connection. Combustion air piping must be supported per guidelines listed in the National Mechanical Code, Section 305, Table 305.4 or as local codes dictate. Vent Connector (FIG. 2-1) - Used to provide a passageway for conveying combustion gases to the outside. A transition fitting is provided on the unit for final connection. Vent piping must be supported per the National Building Code, Section 305, Table 305.4 or as local codes dictate.
When a sidewall or vertical rooftop combustion air supply system is disconnected for any reason, the air inlet pipe must be resealed to ensure that combustion air will be free of contaminants and supplied in proper volume. DANGER Failure to properly seal all joints and seams as required in the air inlet piping may result in flue gas recirculation, spillage of flue products and carbon monoxide emissions causing severe personal injury or death.
2.
ADAPTER GASKET
NOTICE
NOTICE
NOTICE
CONNECTOR
The Crest uses model specific combustion air intake and vent piping sizes as detailed in Tables 2B and 2C on page 17. NOTICE Increasing or decreasing combustion air or vent piping to sizes not specified in this manual is not authorized.
16
General venting
AIR INLET
(continued)
Table 2B Direct Vent Minimum / Maximum Allowable Air / Vent Lengths VENT Vent Diameter
7" 8" 9" 10" 10"
Model
FB 1500 FB 2000 FB 2500 FB 3000 FB 3500
Table 2C Room Air Minimum / Maximum Allowable Air / Vent Lengths Model
FB 1500 FB 2000 FB 2500 FB 3000 FB 3500
Vent Diameter
7" 8" 9" 10" 10"
When determining equivalent combustion air and vent length, add 5 feet (1.5m) for each 90 elbow and 3 feet (.9 m) for each 45 elbow. EXAMPLE: 20 feet (6 m) of pipe + (4) 90 elbows + (3) 45 elbows = 49 equivalent feet (15 m) of piping.
Vent, air piping and termination: The Crest vent and air piping can be installed through the roof or through a sidewall. Follow the procedures in this manual for the method chosen. Refer to the information in this manual to determine acceptable vent and air piping length. Air contamination Pool and laundry products and common household and hobby products often contain fluorine or chlorine compounds. When these chemicals pass through the boiler, they can form strong acids. The acid can eat through the boiler wall, causing serious damage and presenting a possible threat of flue gas spillage or boiler water leakage into the building. Please read the information given in Table 1A, page 9, listing contaminants and areas likely to contain them. If contaminating chemicals will be present near the location of the boiler combustion air inlet, have your installer pipe the boiler combustion air and vent to another location, per this manual. If the boiler combustion air inlet is located WARNING in a laundry room or pool facility, for example, these areas will always contain hazardous contaminants. To prevent the potential of severe personal WARNING injury or death, check for areas and products listed in Table 1A, page 9 before installing the boiler or air inlet piping. If contaminants are found, you MUST: Remove products permanently. OR Relocate air inlet and vent terminations to other areas.
You must also install air piping from outside to the boiler air intake adapter. The resultant installation is direct vent (sealed combustion). You may use any of the vent/air piping methods covered in this manual. Do not attempt to install the Crest using any other means. DO NOT mix components from different WARNING systems. The vent system could fail, causing leakage of flue products into the living space. Use only approved stainless steel pipe and fittings.
17
General venting
Table 2D Flue Damper Kits
Common venting
Crest boilers may be common vented; however, the following criteria MUST BE followed: 1. Only Crest boilers may be connected to the common vent. DO NOT mix other manufacturers appliances or other Lochinvar models. Crest boilers connected to the common vent must all be of the same size. Each Crest boiler must have a Lochinvar supplied flue damper installed (see Table 2D). Only vertical venting may be used when common venting Crest boilers. Sidewall venting is not allowed. Crest boilers in a common vent must be connected and controlled with the integral Crest SMART TOUCH Cascade. a. The Leader may be controlled through the Crest SMART TOUCH control through BMS (external 0 - 10V signal), ModBus or its own internally calculated set point. b. The Cascade (Members) must be controlled by the Crest Leader boiler using the efficiency optimized Cascade.
Damper Size
7" 8" 9" 10" 10"
Kit Number
DRH30000 DRH30001 DRH30002 DRH30003 DRH30003
2.
3.
4.
5.
For approved common vent sizing, contact the factory. When Crest boilers are common vented, WARNING the criteria above MUST BE followed. Failure to follow all these requirements will result in severe personal injury, death, or substantial property damage.
18
WARNING
BIRD SCREEN [TYPICAL] VENT OUTLET 36" [914 MM] MINIMUM ABOVE AIR INLET 12" [305 MM] MINIMUM ABOVE ROOF / SNOW LINE
NOTICE
Determine location
Locate the vent/air terminations using the following guidelines: 1. The total length of piping for vent or air must not exceed the limits given in the General Venting Section on page 17 of this manual. 2. The vent must terminate at least 3 feet above the highest place in which the vent penetrates the roof and at least 2 feet above any part of a building within 10 horizontal feet. 3. The air piping must terminate in a down-turned 180 return pipe no further than 2 feet (.6 m) from the center of the vent pipe. This placement avoids recirculation of flue products into the combustion air stream. 4. The vent piping must terminate in an up-turned coupling as shown in FIG. 3-1. The top of the coupling or the rain cap must be at least 36" (914 mm) above the air intake. The air inlet pipe and vent pipe can be located in any desired position on the roof, but must always be no further than 2 feet (.6 m) apart and with the vent termination at least 36" (914 mm) above the air intake. WARNING Rooftop vent and air inlet terminations must terminate in the same pressure zone, unless vertical vent sidewall air is set up as shown in the General Venting - Vertical Vent, Sidewall Air Section.
5. Locate terminations so they are not likely to be damaged by foreign objects, such as stones or balls, or subject to buildup of leaves or sediment.
2.
3. Space the air and vent holes to provide the minimum spacing shown in FIG. 3-1. 4. Follow all local codes for isolation of vent pipe when passing through floors, ceilings, and roofs. 5. Provide flashing and sealing boots sized for the vent pipe and air pipe.
VENT
COMBUSTION AIR
19
3. The vent piping must terminate in an up-turned coupling as shown in FIG. 3-1. The top of the coupling or the rain cap must be at least 36" (914 mm) above the air intake. The air inlet pipe and vent pipe can be located in any desired position on the roof, but must always be no further than 2 feet (.6 m) apart and with the vent termination at least 36" (914 mm) above the air intake. 4. Maintain the required dimensions of the finished termination piping as shown in FIG. 3-1. 5. Do not extend exposed vent pipe outside of building more than shown in this document. Condensate could freeze and block vent pipe.
36 (914 MM)
12 (305 MM)
2. Place roof penetrations to obtain minimum clearance of 12 inches (305 mm) between edge of air intake elbow and adjacent vent pipe of another boiler for U.S. installations (see FIG. 3-3). For Canadian installations, provide clearances required by CSA B149.1 Installation Code. 3. The air inlet of a Crest boiler is part of a direct vent connection. It is not classified as a forced air intake with regard to spacing from adjacent boiler vents. Figure 3-3 Vertical Terminations with Multiple Boilers
36 (914 MM)
12 12 (305 MM) 12 (305 MM) (305 MM) 36 (914 MM) 12 12 (305 MM) 12 (305 MM) (305 MM)
20
WARNING
g.
WARNING Do not connect any other appliance to the vent pipe or multiple boilers to a common vent pipe except as noted in Section 2 on page 18. Failure to comply could result in severe personal injury, death, or substantial property damage. CAUTION Sidewall venting commercial products will result in large exhaust plumes in cold climates. Consideration should be taken when locating in proximity to windows, doors, walkways, etc. Installation must comply with local requirements and with the National Fuel Gas Code, NFPA 54 / ANSI Z223.1 for U.S. installations or CSA B149.1 for Canadian installations.
NOTICE
3.
Determine location
Locate the vent/air terminations using the following guidelines: 1. The total length of piping for vent or air must not exceed the limits given in the General Venting Section on page 17 of this manual. 2. You must consider the surroundings when terminating the vent and air: a. Position the vent termination where vapors will not damage nearby shrubs, plants or air conditioning equipment or be objectionable. b. The flue products will form a noticeable plume as they condense in cold air. Avoid areas where the plume could obstruct window views. c. Prevailing winds could cause freezing of condensate and water/ice buildup where flue products impinge on building surfaces or plants. d. Avoid possibility of accidental contact of flue products with people or pets. e. Do not locate the terminations where wind eddies could affect performance or cause recirculation, such as inside building corners, near adjacent buildings or surfaces, window wells, stairwells, alcoves, courtyards, or other recessed areas.
Maintain clearances as shown in FIG.s 4-1 thru 4-3, pages 21 and 22. The vent termination should not be located in traffic areas such as walkways, adjacent buildings, operable windows, or doors. Also maintain the following: a. Vent must terminate: At least 6 feet (1.8 m) from adjacent walls. Not less than 7 feet (2.1 m) above grade where located adjacent to public walkways. No closer than 12 inches (305 mm) below roof overhang. At least 3 feet (.9 m) above any forced air intake within 10 feet (3 m). No closer than 4 feet (1.2 m) horizontally from any door or window or any other gravity air inlet. b. Air inlet must terminate at least 12 inches (305 m) above grade or snow line; at least 36 inches (914 mm) below the vent termination. c. Do not terminate closer than 4 feet (1.2 m) horizontally from any electric meter, gas meter, regulator, relief valve, or other equipment. Never terminate above or below any of these within 4 feet (1.2 m) horizontally.
4. Locate terminations so they are not likely to be damaged by foreign objects, such as stones or balls, or subject to buildup of leaves or sediment.
21
1. The air termination must be oriented at least 12 inches above grade or snow line as shown in FIG. 4-1, page 21. 2. Maintain the required dimensions of the finished termination piping as shown in FIG. 4-1, page 21.
3. Do not extend exposed vent pipe outside of the building more than what is shown in this document. Condensate could freeze and block vent pipe. 4. Stainless steel terminations are designed to penetrate walls with a thickness up to 9.25 inches of standard construction.
36 MIN.
AIR TERMINATION
CAUTION
Sidewall venting commercial products will result in large exhaust plumes in cold climates. Consideration should be taken when locating in proximity to windows, doors, walkways, etc.
22
(continued)
2. Place wall penetrations to obtain minimum clearance of 12 inches (305 mm) between vent pipe and adjacent air inlet, as shown in FIG. 4-4 for U.S. installations. For Canadian installations, provide clearances required by CSA B149.1 Installation Code. 3. The air inlet of a Crest is part of a direct vent connection. It is not classified as a forced air intake with regard to spacing from adjacent boiler vents. Figure 4-4 Multiple Vent Terminations (must also comply with Figure 4-1)
Figure 4-6 Room Air (Direct Exhaust Terminations) ROOM AIR (DIRECT EXHAUST TERMINATIONS)
Vent Termination 23 Elbow
45 Elbow
VENT
90 Elbow
AIR
Room air
The Crest boiler may be installed with a single pipe carrying the flue products to the outside while using combustion air from the equipment room.
Follow the requirements in the General Venting, Sidewall Direct Venting, and Vertical Direct Venting sections for vent material specifications, vent length requirements, and vent termination requirements. Install the air inlet cover (shipped loose with the boiler) per FIG. 4-7. Combustion and ventilation air must be supplied to the equipment room per the requirements on pages 12 and 13 of this manual for proper operation of the Crest boiler when utilizing the single pipe method. Figure 4-7 Room Air Installation
Dryer Inlet
Straight
90 Elbow
Mitered
23 Elbow
23
Hydronic piping
General piping information
Basic steps are listed below along with illustrations on the following pages, which will guide you through the installation of the Crest (5-2 thru 5-5). 1. Connect the system return to the 4" flanged connection marked Inlet, make sure to install with a suitable gasket between flanges. Connect the system supply to the 4" flanged connection marked Outlet, make sure to install with a suitable gasket between flanges. Install purge and balance valve or shutoff valve and drain on system return to purge air out of each zone. Install a backflow preventer on the cold feed make-up water line. Install a pressure reducing valve on the cold feed make-up water line, (15 psi (103 kPa) nominal). Check temperature and pressure gauge, which should read a minimum pressure of 12 psi (83 kPa). Install the circulators as shown on the piping diagrams in this section. Make sure the circulators are properly sized for the system and friction loss. Install check valves with each boiler circulator. Install an expansion tank on the system supply. Consult the tank manufacturers instruction for specific information relating to tank installation. Size the expansion tank for the required system volume and capacity. Install an air elimination device on the system supply. This appliance is supplied with a relief valve sized in accordance with ASME Boiler and Pressure Vessel Code, Section IV (Heating Boilers). The safety relief valve is installed at the factory and is located on the rear of the boiler. Pipe the discharge of the safety relief valve to prevent injury in the event of pressure relief. Pipe the discharge to a drain. Provide piping that is the same size as the safety relief valve outlet. Never block the outlet of the safety relief valve.
2.
3. 4. 5.
7.
8. 9.
Freeze protection
Freeze protection for new or existing systems must use glycol that is specially formulated for this purpose. This includes inhibitors, which prevent the glycol from attacking the metallic system components. Make certain to check that the system fluid is correct for the glycol concentration and inhibitor level. The system should be tested at least once a year and as recommended by the producer of the glycol solution. Allowance should be made for the expansion of the glycol solution in the system piping. WARNING Use only inhibited propylene glycol solutions, which are specifically formulated for hydronic systems. Ethylene glycol is toxic and can attack gaskets and seals used in hydronic systems.
10. On any pre-existing system, it is good practice to install a field supplied strainer to prevent damage to the heat exchanger. See the piping illustrations included in this section, FIG.s 5-2 thru 5-5 for suggested guidelines in piping the Crest. NOTICE Please note that these illustrations are meant to show system piping concept only, the installer is responsible for all equipment and detailing required by local codes.
24
Hydronic piping
(continued)
Circulator sizing
The Crest heat exchanger does have a pressure drop, which must be considered in your system design. Refer to the graph in FIG. 5-1 for pressure drop through the Crest heat exchanger. Figure 5-1 Pressure Drop vs. Flow
150
200
250
300
350
Table 5A Sizing Information for Temperature Rise Applications_20F, 40F and 60F TEMPERATURE RISE APPLICATIONS Model
FB 1500 FB 2000 FB 2500 FB 3000 FB 3500
20F GPM
138 184 230 277 323
40F GPM
69 92 115 138 161
60F GPM
46 61 77 92 108
FT/HD
3.4 4.1 4.6 5.6 7.5
FT/HD
1.5 1.6 1.3 1.2 1.2
FT/HD
1.0 1.0 0.7 0.7 0.7
[Based on 92% AHRI Efciency] NOTICE The pressure drop reflected in FIG. 5-1 is for the boiler only. Additional allowances must be made for piping, especially if sizing pumps for Primary/Secondary applications. NOTICE It is required that boiler piping systems utilize Primary/Secondary or Fixed or Variable Flow Primary configurations as shown in FIG.s 5-2 thru 5-5. The use of other boiler piping configurations could result in improper building and system flow rates leading to inadvertent boiler high limit shutdowns and poor system performance.
25
Hydronic piping
A system supply sensor (factory supplied) MUST BE installed with Primary/Secondary systems for proper boiler operation.
10. Y-Strainer: Field supplied. A Y-strainer or equivalent multipurpose strainer is recommended at the inlet of the heat exchanger to remove system particles from older hydronic systems and protect newer systems. CAUTION The maximum allowable water flow rate through a single Crest boiler is 350 GPM. Exceeding this flow rate will result in damage to the heat exchanger and/or piping. Reference Table 5B1 for the minimum recommended flow rate through a single Crest boiler at full fire to maintain a 80F temperature rise. Reference Table 5B2 for the absolute minimum flow rate through a single Crest boiler.
NOTICE
Table 5B1 Minimum Flow Rate with the Boiler at Full Fire TEMPERATURE RISE APPLICATIONS MODEL FB(N,L)1500 FB(N,L)2000 FB(N,L)2500 FB(N,L)3000 FB(N,L)3500 FLOW RATE (GPM) 35 46 58 70 81
Table 5B2 Absolute Minimum Flow Rate ABSOLUTE MINIMUM FLOW RATE MODEL FB(N,L)1500 FB(N,L)2000 FB(N,L)2500 FB(N,L)3000 FB(N,L)3500 FLOW RATE (GPM) 25 25 25 25 45
26
Hydronic piping
(continued)
Figure 5-2 Single Boiler - Recommended - Primary / Secondary Piping with a Hot Water Generator
FROM SYSTEM
12" MAX HOT WATER GENERATOR RELIEF VALVE BALL VALVE (TYPICAL) AIR SEPERATOR DRAIN PORT (TYPICAL) SYSTEM SUPPLY SENSOR SYSTEM CIRCULATOR
MAKE UP WATER
NOTICE
System flow should always remain higher than the required flow for the boiler(s) when the boiler(s) is in operation to prevent short cycling and high limit issues. Please note that these illustrations are meant to show system piping concept only, the installer is responsible for all equipment and detailing required by local codes.
NOTICE
27
Hydronic piping
Number of Units 3 4 5 6 7 Recommended Common Header Pipe Sizes in Inches
4 5 5 6 6 5 5 6 7 7 5 6 7 7 8 6 7 7 8 10 6 7 8 10 10
Model
FB FB FB FB FB 1500 2000 2500 3000 3500
2
4 4 5 5 5
8
7 8 10 10 10
NOTICE
A system supply sensor (factory supplied) MUST BE installed for proper boiler operation.
Figure 5-3 Multiple Boilers - Common Header - Recommended - Primary / Secondary Flow
FROM SYSTEM SYSTEM RETURN SENSOR BALL VALVE (TYPICAL) AIR SEPARATOR DRAIN PORT (TYPICAL) SYSTEM SUPPLY SENSOR SYSTEM CIRCULATOR
RELIEF VALVE
TO SYSTEM
MAKE UP WATER BACK FLOW PREVENTER WATER GENERATOR CIRCULATOR BOILER DRAIN (TYPICAL) PRESSURE REDUCING VALVE PRESSURE GAUGE EXPANSION TANK Y-STRAINER (RECOMMENDED) BOILER PUMP (TYPICAL) FLOW CHECK VALVE (TYPICAL)
NOTICE NOTICE
System flow should always remain higher than the required flow for the boiler(s) when the boiler(s) is in operation to prevent short cycling and high limit issues. Please note that these illustrations are meant to show system piping concept only, the installer is responsible for all equipment and detailing required by local codes.
28
Hydronic piping
(continued)
Figure 5-4 Single Boiler - Alternate - Fixed or Variable Flow Primary System Piping
RELIEF VALVE
FROM SYSTEM
BOILER DRAIN
Y-STRAINER (RECOMMENDED)
TO SYSTEM
MAKE UP WATER
NOTICE
Please note that these illustrations are meant to show system piping concept only, the installer is responsible for all equipment and detailing required by local codes.
29
Hydronic piping
Figure 5-5 Multiple Boilers - Alternate - Common Header - Fixed or Variable Flow Primary
AIR SEPERATOR DRAIN PORT (TYPICAL) SYSTEM SUPPLY SENSOR SYSTEM CIRCULATOR Y-STRAINER (RECOMMENDED) (TYPICAL) TO SYSTEM EXPANSION TANK PRESSURE GAUGE BACK FLOW PREVENTER PRESSURE REDUCING VALVE
MAKE UP WATER
NOTICE
Please note that these illustrations are meant to show system piping concept only, the installer is responsible for all equipment and detailing required by local codes. When installing multiple Crest boilers in fixed or variable flow primary applications, utilize a reverse-return or other piping method to ensure balanced flow through each boiler.
NOTICE
30
Gas connections
For dual fuel models, reference the Crest Dual Fuel Supplemental Manual. 3. Purge all air from the gas supply piping. 4. Before placing the boiler in operation, check the boiler and its gas connection for leaks. a. The appliance must be disconnected from the gas supply piping system during any pressure testing of that system at a test pressure in excess of 1/2 PSIG (3.5 kPa). b. The appliance must be isolated from the gas supply piping system by closing a manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 PSIG (3.5 kPa). The appliance and its gas connection must be leak tested before placing it in operation. Do not check for gas leaks with an open flame use the bubble test. Failure to use the bubble test or check for gas leaks can cause severe personal injury, death, or substantial property damage.
1. Refer to FIG. 6-1 to pipe gas to the boiler. a. Install ground joint union for servicing, when required. b. In Canada When using manual main shutoff valves, it must be identified by the installer. Figure 6-1 Gas Supply Piping
GAS SUPPLY
c.
WARNING
UNION (FACTORY SUPPLIED) MANUAL SHUTOFF VALVE (FACTORY SUPPLIED)
5. Use pipe sealing compound compatible with propane gases. Apply sparingly only to male threads of the pipe joints so that pipe dope does not block gas flow.
SEDIMENT TRAP / DRIP LEG CLEAN OUT (FACTORY SUPPLIED)
WARNING Failure to apply pipe sealing compound as detailed in this manual can result in severe personal injury, death, or substantial property damage. Table 6A Gas Inlet Size Model Gas Inlet Size
1 1/2" 1 1/2" 2" 2" 2"
2. Support piping with hangers, not by the boiler or its accessories. The gas valve and blower will not support WARNING the weight of the piping. Do not attempt to support the weight of the piping with the boiler or its accessories. Failure to comply could result in severe personal injury, death, or substantial property damage.
31
Gas connections
Use two wrenches when tightening gas piping at boiler (FIG. 6-2), using one wrench to prevent the boiler gas line connection from turning. Failure to support the boiler gas connection pipe to prevent it from turning could damage gas line components. Natural gas supply pressure requirements 1. Pressure required at the gas valve inlet pressure port: Maximum 14 inches w.c. (3.5 kPa) with no flow (lockup) or with boiler on. Minimum 4 inches w.c. (.99 kPa) with gas flowing (verify during boiler startup). 2. Install 100% lockup gas pressure regulator in supply line if inlet pressure can exceed 14 inches w.c. (3.5 kPa) at any time. Adjust lockup regulator for 14 inches w.c. (3.5 kPa) maximum. WARNING Ensure that the high gas pressure regulator is at least 10 feet (3 m) upstream of the appliance.
WARNING
Propane Gas:
WARNING Check boiler rating plate to determine which fuel the boiler is set for. Crest boilers CAN NOT be field converted. Failure to comply could result in severe personal injury, death, or substantial property damage.
Pipe sizing for propane gas 1. Contact gas supplier to size pipes, tanks, and 100% lockup gas pressure regulator. Propane Supply Pressure Requirements
USE BACK UP WRENCH TO PREVENT PIPE FROM ROTATING
1. Adjust propane supply regulator provided by the gas supplier for 14 inches w.c. (3.5 kPa) maximum pressure. 2. Pressure required at gas valve inlet pressure port: Maximum 14 inches w.c. (3.5 kPa)with no flow (lockup) or with boiler on. Minimum 4 inches w.c. (.99 kPa) with gas flowing (verify during boiler startup). WARNING Ensure that the high gas pressure regulator is at least 10 feet (3 m) upstream of the appliance (FIG. 6-3).
NOTICE
Maximum inlet gas pressure must not exceed the value specified. Minimum value listed is for the purposes of input adjustment.
Natural gas:
WARNING Check boiler rating plate to determine which fuel the boiler is set for. Crest boilers CANNOT be field converted. Failure to comply could result in severe personal injury, death, or substantial property damage.
Pipe sizing for natural gas 1. Refer to Table 6B for pipe length and diameter. Based on rated boiler input (divide by 1,000 to obtain cubic feet per hour). a. Table 6B is only for natural gas with specific gravity 0.60 inches, with a pressure drop through the gas piping of 0.5 inches w.c. b. For additional gas pipe sizing information, refer to the National Fuel Gas Code, NFPA 54 / ANSI Z223.1 - latest edition, or in Canada CSA B149.1 Installation Code.
32
Gas connections
(continued)
TABLE - 6B
GAS PIPING SIZE CHART Nominal Iron Pipe Size Inches
1 2 2 3 4 Maximum Capacity of Pipe in Thousands of Btu/hr for 200 gas pressures of 14 Inches Water N/A Column (0.5 PSIG) or less and N/A a pressure drop of 0.5 Inch Water Column (Based N/A on NAT GAS, 1025 Btu/hr per 2,340 Cubic Foot of Gas and 0.60 4,720 Specific Gravity)
20
1,500 2,820 4,460 7,900
30
N/A
40
N/A
50
N/A 1,720 2,720 4,870
60
N/A 1,560
70
N/A N/A
80
N/A N/A
90
N/A N/A
100
N/A N/A
125
N/A N/A
150
N/A N/A
175
N/A N/A N/A
The gas piping must be sized for the proper flow and length of pipe, to avoid excessive pressure drop. Both the gas meter and the gas regulator must be properly sized for the total gas load. If you experience a pressure drop greater than 1 inch w.c. (249 Pa), the meter, regulator, or gas line is undersized or in need of service. Perform the steps below when checking inlet gas supply: 1. 2. 3. Turn the main power switch to the OFF position. Shut off gas supply at the manual gas valve in the gas piping to the appliance. Remove the 1/8" pipe plug on the flange to the factory supplied gas shutoff valve and install a suitable 1/8" fitting (field supplied) for the manometer tubing. Place the tubing of the manometer over the tap once the 1/8" fitting is installed as shown in FIG. 6-4.
7.
8.
9.
10. If the gas pressure is out of range, contact the gas utility, gas supplier, qualified installer or service agency to determine the necessary steps to provide proper gas pressure to the control. 11. Turn the power switch to the OFF position. 12. Shut off the gas supply at the manual gas valve in the gas piping to the appliance. 13. Remove the manometer from the pressure tap on top of the gas valve. Remove the 1/8" (3 mm) field supplied fitting and reinstall the pipe plug removed in Step 3.
33
Gas connections
Gas Pressure
The gas pressure must remain between 4 inches w.c. (.99 kPa) minimum and 14 inches w.c. (3.5 kPa) maximum for Natural gas and between 4 inches w.c. (.99 kPa) minimum and 14 inches w.c. (3.5 kPa) maximum for LP gas during standby (static) mode and while in operating (dynamic) mode. If an in-line regulator is used, it must be a minimum of 10 feet (3 m) from the Crest boiler. It is very important that the gas line is properly purged by the gas supplier or utility company. Failure to properly purge the lines or improper line sizing, will result in ignition failure. Ignition problems are especially noticeable in NEW LP installations and also in empty tank situations. This can also occur when a utility company shuts off service to an area to provide maintenance to their lines.
Do not check for gas leaks with an open WARNING flame -- use the bubble test. Failure to use the bubble test or check for gas leaks can cause severe personal injury, death, or substantial property damage. 14. Turn on the gas supply at the manual gas valve. 15. Turn the power switch to the ON position. 16. Adjust the temperature set point on the control panel of the SMART TOUCH control module to the desired water temperature so the appliance will call for heat. 17. Check burner performance by cycling the system while you observe burner response. The burner should ignite promptly. Flame pattern should be stable. Turn system off and allow burner to cool, then cycle burner again to ensure proper ignition and flame characteristics. Figure 6-4 Inlet Gas Supply Check
WARNING
34
Field wiring
ELECTRICAL SHOCK HAZARD For your safety, turn off electrical power supply before making any electrical connections to avoid possible electric shock hazard. Failure to do so can cause severe personal injury or death. Wiring must be N.E.C. Class 1. If original wiring as supplied with boiler must be replaced, use only type 105C wire or equivalent. Boiler must be electrically grounded as required by National Electrical Code ANSI/NFPA 70 latest edition.
WARNING
NOTICE
CAUTION
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation.
120V SUPPLY
SYSTEM PUMP DRY CONTACT BOILER PUMP DRY CONTACT HWG PUMP DRY CONTACT
35
Field wiring
ModBus
The RS-485 ModBus cable is connected to the ModBus terminals. Use shielded, 2-wire twisted pair cable. If desired, the shield can be connected to ground by installing a jumper wire between terminals 1 and 3 on connector X5 on the ModBus interface module.
Generator
(HWG)
1. Connect the HWG tank thermostat to the Tank Thermostat terminals on the connection board (FIG. 7-3).
LOW VOLTAGE WIRING KNOCKOUTS
Enable
1. Connect the room thermostat or boiler enable contacts (isolated contact only) to terminals 7 and 8, as shown in FIG. 7-3. 2. If a thermostat is used, install the thermostat on the inside wall away from influences of drafts, hot or cold water pipes, lighting fixtures, television, sunlight, or fireplaces. 3. Thermostat anticipator (if applicable): a. If connected directly to boiler, set for 0.1 amps. b. If connected to relays or other devices, set to match total electrical power requirements of connected devices. See device manufacturers specifications and thermostat instructions for details.
Louver relay
If louvers need to operate before the boiler fires, they can be controlled by this output. Connect these terminals to a 24V relay coil, which is wired to operate the louvers (FIG. 7-3).
Rate output
This output provides a 0 - 10V signal that is proportional to the firing rate of the boiler. This may be used by a BMS system to monitor the actual rate of the boiler.
36
Field wiring
(continued)
2. For system supply sensor wiring information reference (FIG. 7-3). Unless a firing rate is being provided by NOTICE a BMS system, a system supply sensor (factory supplied) MUST BE installed with Primary/Secondary piping systems for proper boiler operation.
The location of the system supply sensor should be downstream of the boiler connections in the main system loop (FIG.s 5-5 and 5-6). The system supply sensor should be wired to the Low Voltage Connection Board at the terminals marked for the system supply sensor (see FIG. 7-3). The Leader control will use the water temperature at the system supply sensor to control the operation of the Cascade. If outdoor air reset is desired, the outdoor air sensor should be wired to the Low Voltage Connection Board at the terminals marked for the outdoor air sensor on the Leader boiler (FIG. 7-3). If the outdoor air sensor is connected, the Leader control will calculate the water temperature set point based on the programmed reset curve parameters. If the outdoor air sensor is not connected, the Leader control will maintain the fixed water temperature set point that is programmed into the control. If a Thermostat enable output is available, it should be wired to the Low Voltage Connection Board on the Leader boiler at the terminals marked Enable (FIG. 7-3). If the boilers are to run continuously, connect a jumper wire between the 7 and 8 terminals at the Enable input. This will initiate a call for heat on the Cascade. If the SMART TOUCH control is being controlled by a Boiler Management System (BMS), a call for heat may be initiated by the voltage applied to the BMS 0 - 10 VDC input instead. Communication between the Leader boiler and the Member boilers is accomplished by using shielded, 2-wire twisted pair communication cable. Connect one of the twisted pair wires to Cascade terminal A on each of the Low Voltage Connection boards, and the other wire of the twisted pair to Cascade terminal B on each of the Low Voltage Connection Boards. Connect the shield wires to one of the Cascade shield ground terminals on the Low Voltage Connection Boards (FIG. 7-3). If more than two boilers are on the Cascade, daisy chain the wiring from the Cascade terminals on the second boiler to the Cascade terminals on the third boiler, then from the third to the forth, and so on. The connections between boilers can be made in any order, regardless of the addresses of the boilers. Try to keep each cable as short as possible.
1. An external control may be connected to control either the firing rate or the set point of the boiler. Connect the 0 - 10 VDC terminals to the 0 - 10 VDC output of the external control. The SMART TOUCH control can be enabled using the Enable output (see page 38) or using the voltage applied to the 0 - 10 VDC input. Reference the Crest Service Manual for more details. 2. Make sure terminal #34 on the Low Voltage Connection Board is connected to the (-) or COM output terminal of the external control, and 0 - 10 VDC terminal #33 is connected to the 0 - 10 VDC terminal of the external control.
Runtime contacts
The SMART TOUCH control closes a set of dry contacts whenever the burner is running. This is typically used by Building Management Systems to verify that the boiler is responding to a call for heat.
Alarm contacts
The SMART TOUCH control closes another set of contacts whenever the boiler is locked out or the power is turned off. This can be used to turn on an alarm, or signal a Building Management System that the boiler is down.
37
38
B A SHIELD SHIELD A B B A SHIELD
Field wiring
FROM PREVIOUS BOILER TO NEXT BOILER 0-10V INPUT SYSTEM PUMP OUTDOOR SENSOR TANK SENSOR SYSTEM SUPPLY SENSOR SYSTEM RETURN SENSOR 0-10V OUTPUT BOILER PUMP
TANK THERMOSTAT
ALARM CONTACTS RUN TIME CONTACTS TANK THERMOSTAT ENABLE
ENABLING DEVICE
LOUVER PROVING LOUVER RELAY AUX SWITCH 1 AUX SWITCH 2
LOUVER RELAY
17 SHIELD
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
40 SHIELD 39 B CASCADE 38 A 37 SHIELD 36 - SYSTEM PUMP 35 + IN 34 BMS 33 + IN 32 OUTDOOR 31 SENSOR 30 TANK 29 SENSOR 28 SYSTEM SUPPLY 27 SENSOR 26 SYSTEM RETURN 25 SENSOR 24 - BOILER PUMP 23 + OUT 22 RATE 21 + OUT 20 SHIELD 19 B MODBUS 18 A
B A SHIELD
AUX SWITCH 1
AUX SWITCH 2
Condensate drain
Condensate disposal
9. Do not expose condensate line to freezing temperatures. NOTICE Use materials approved by the authority having jurisdiction. In the absence of other authority, PVC and CPVC pipe must comply with ASTM D1785 or D2845. Cement and primer must comply with ASME D2564 or F493. For Canada use CSA or ULC certified PVC or CPVC pipe, fittings, and cement. To allow for proper drainage on large horizontal runs, a second line vent may be required and tubing size may need to increase to 1 inch (25 mm). The condensate line must remain unobstructed, allowing free flow of condensate. If condensate is allowed to freeze in the line or if the line is obstructed in any other manner, condensate can exit from the boiler tee, resulting in potential water damage to property. 10. A condensate removal pump is required if boiler is below the drain. When installing a condensate pump, select one approved for use with condensing boilers and furnaces. The pump should have an overflow switch to prevent property damage from condensate spillage. The switch should be wired to the auxiliary device proving switch terminals on the low voltage connection board.
1. The Crest is a high efficiency appliance that produces condensate. 2. The rear of the boiler has a 1 inch (25.4 mm) stainless steel drain fitting and a 3/8 inch (9.8 mm) stainless steel vent line for connection to the condensate trap. 3. Connect the 1 inch (25.4 mm) fitting to the 1 inch (25.4 mm) fitting on the condensate trap with the factory supplied silicone hose. Secure the hose to the condensate trap and the boiler using the factory supplied hose clamps. 4. Connect the 3/8 inch (9.8 mm) fitting to the 3/8 inch (9.8 mm) fitting on the condensate trap (shipped loose) with the factory supplied silicone hose. Secure the hose to the condensate trap and the boiler using the factory supplied hose clamps. 5. The condensate trap must be installed at the same level or below the boiler base. 6. The condensate trap is sized for a 1" PVC outlet connection pipe. 7. Plug the wiring connection from the condensate trap into the connector located on the back of the unit. 8. Slope condensate tubing down and away from the boiler into a drain or condensate neutralizing filter. Condensate from the Crest will be slightly acidic (typically with a pH from 3 to 5). Install a neutralizing filter if required by local codes. A neutralizer kit (FIG. 8-1) is available from the factory (KIT40045). The neutralizer kit must be placed on a surface that is a minimum of 3 inches lower than the condensate trap. Figure 8-1 Condensate Disposal
NOTICE
39
Start-up
Do not use petroleum-based cleaning or sealing compounds in the boiler system. Damage to elastomer seals and gaskets in the system could occur, resulting in substantial property damage.
Hardness less than 7 grains 1. Consult local water treatment companies for hard water areas (above 7 grains hardness). Chlorine concentration less than 200 ppm 1. Do not fill boiler or operate with water containing chlorine in excess of 200 ppm. 2. Filling with chlorinated fresh water should be acceptable since drinking water chlorine levels are much lower. 3. Do not use the boiler to directly heat swimming pool or spa water. Test/replace freeze protection fluid 1. For systems using freeze protection fluids, follow fluid manufacturers instructions. 2. Freeze protection fluid must be replaced periodically due to degradation of inhibitors over time. Follow all fluid manufacturers instructions.
4. At initial fill and during boiler startup and testing, check system thoroughly for any leaks. Repair all leaks before proceeding further. WARNING Eliminate all system leaks. Continual fresh makeup water will reduce boiler life. Minerals can build up in the heat exchanger, reducing heat transfer, overheating the heat exchanger, and causing heat exchanger failure.
2. 3.
40
Start-up
(continued)
WARNING
Propane boilers only Your propane supplier mixes an odorant with the propane to make its presence detectable. In some instances, the odorant can fade, and the gas may no longer have an odor. Before startup (and periodically thereafter), have the propane supplier verify the correct odorant level in the gas.
DO NOT adjust or attempt to measure WARNING gas valve outlet pressure. The gas valve is factory set for the correct outlet pressure. This setting is suitable for natural gas and propane, requiring no field adjustment. Attempting to alter or measure the gas valve outlet pressure could result in damage to the valve, causing potential severe personal injury, death, or substantial property damage. Figure 9-1 Condensate Trap
41
Start-up
Check vent piping and air piping 1. Check for gastight seal at every connection, seam of air piping, and vent piping. WARNING Venting system must be sealed gastight to prevent flue gas spillage and carbon monoxide emissions, which will result in severe personal injury or death.
Check gas piping 1. Check around the boiler for gas odor following the procedure on page 31 of this manual (connecting gas supply piping). WARNING If you discover evidence of any gas leak, shut down the boiler at once. Find the leak source with a bubble test and repair immediately. Do not start the boiler again until corrected. Failure to comply could result in severe personal injury, death, or substantial property damage.
1. Turn the main power off to the boiler by placing the On/Off switch in the OFF position. 2. Remove the flue temperature sensor from the flue collector. Note: Combustion measurements will be made at this point. 3. Turn the main power on to the boiler by placing the On/Off switch in the ON position.
42
Start-up
(continued)
If you cannot reach your gas supplier, call the fire department. C. Use only your hand to turn the gas control knob. Never use tools. If the handle will not turn by hand, dont try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion. D. Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the applianc e and to replace any part of the control system and any gas control which has been under water.
OPERATING INSTRUCTIONS
1. STOP! Read the safety information above on this label. 2. Set the thermostat to lowest setting. 3. Turn off all electric power to the applianc e. 4. This appliance is equipped with an ignition device which automatically lights the burner. Do not try to light the burner by hand. 5. Remove front door. 6. Turn gas shutoff valve counterclockwise to OFF. Handle will be perpendicular to pipe. Do not force. 7. Wait five (5) minutes to clear out any gas. If you then smell gas, STOP! Follow B in the safety information above this label. If you dont smell gas, go to next step. 8. 9. Turn gas shutoff valve clockwise to ON. Handle will be parallel to pipe. Install front door.
10. Turn on all electric power to applianc e. 11. Set thermostat to desired setting. 12. If the appliance will not operate, follow the instructions To Turn Off Gas To Appliance and call your service technician or gas supplier.
43
Start-up
Set space heating operation
Verify space heat circulator mode The system pump output can be programmed to never run (OFF), run only when a space heating demand is present (ON), or run continuously except during warm weather shutdown (WWSD). If the boiler is not heating an indirect HW (Hot Water) tank, it also turns on the boiler pump. After the space heating call for heat ends, and the system pump is programmed as ON, the system pump continues to run for a short period of time. If the boiler pump was running, it continues to run for a short period of time as well. These pump delays are factory set to 30 seconds. If different delays are desired, the appropriate parameters in the control must be changed. See the Crest Service Manual for a detailed explanation of this procedure. Set space heating set point temperature During normal operation, space heating set point temperatures can be adjusted from the Set Points Menu. Press the following buttons to navigate to the Set Points Menu from the Home Screen: O2 >> >>
Gas Valve
1 - High 3.5% - 5.5% 11.2% - 14.8% 5.1% - 6.8% 10.5% - 13.2% 2 - High 7.8% - 8.6% 5.6% - 7.1% 9.4% - 11.0% 4.1% - 6.6%
8. After Gas Valve 1 is set, repeat the same procedure for the second gas train by selecting Set Gas Valve 2 - High on the Service Screen. 9. Once the heater analysis is complete, test the safety shutoff device by turning the manual shutoff valve to the OFF position and ensuring that the heater shuts down and registers an alarm. Open the manual shutoff valve and reset the control. 10. Turn the main power off to the boiler and replace the flue temperature sensor into the flue pipe connection. 11. Place the boiler back into normal operation. WARNING You must replace the flue gas temperature sensor to prevent flue gas spillage into the room. Failure to comply could result in severe personal injury, death, or substantial property damage.
After pressing SETUP, the Password Screen will appear. Entering the correct password will allow access to all Installer Level adjustable parameters. Press ENTER without a password to access the User Level parameters. 1. To change a set point, use the arrows to highlight a user set point parameter and press the SELECT button. The description of the selected parameter and its current setting will appear at the bottom of the screen. To adjust the set point, press the following buttons to change the value being displayed: or 4. Once the set point has been adjusted to the desired setting press the SAVE button to change the set point. Once all the necessary adjustments have been made, press the HOME button to return to the Home Screen.
2.
3.
5.
Note: The SAVE button must be pressed to ensure proper programming of the controls. Failure to press the SAVE button will require all changes to be reprogrammed.
44
Start-up
(continued)
Configuration of the cascade When installed in a Cascade system, the individual controls must be programmed for cascade operation. To program the cascade parameters, access the Cascade Menu found in the Setup Menu by pressing the following buttons: >> >> >>
After pressing SETUP, the correct installer password MUST BE entered. 1. Once in the Cascade Setup Menu select the appropriate parameter using the arrows and press the SELECT button. 2. The description of the selected parameter and its current setting will appear at the bottom of the screen. 3. To adjust the parameter, press the + or - buttons to change the value being displayed.
4. Make the correct adjustments and then press the SAVE button. 5. Once all the parameters have been adjusted press the BACK button. This will return you to the Cascade Screen. Note: The SAVE button must be pressed to ensure proper programming of the controls. Failure to press the SAVE button will require all changes to be reprogrammed.
After pressing SETUP, the Password Screen will appear. Entering the correct password will allow access to all Installer Level adjustable parameters. Press ENTER without a password to access the User Level parameters. The SMART TOUCH control has a built-in clock that it uses for its night setback feature and for logging events. This clock must be set when the boiler is installed, and anytime the boiler has been powered off for more than one day. Use the following procedure to set the clock: 1. To set the clock, highlight Clock using the arrows and press the SELECT button. Use the left and right arrows to select hours, minutes, AM/PM and the up and down arrows to set. To set the date, highlight Date using the arrows and press the SELECT button. Use the left and right arrows to select the day of the week and the up and down arrows to set.
2.
45
10
Operating information
HWG priority The SMART TOUCH control module allows connection of a HW thermostat or sensor to the low voltage connection board. When the HW thermostat or sensor calls for heat, the control module activates the HW pump, shuts down the boiler pump, and immediately sets the target outlet water temperature to 180F (82.2C). This provides automatic priority heat allocation to the HW Generator for maximum response and recovery. The HW pump continues for 60 seconds after the heating cycle to deliver the most possible heat. The control module can be programmed to limit the firing rate of the boiler during a HW call for heat. Controlling sensor The control module is programmed to use the outlet sensor as the control sensor by default. If a system supply sensor is connected, the control automatically uses it as the control sensor. The control module may be programmed to use the inlet sensor as the control sensor instead. In this case, the control will use the system return sensor if it is connected. Anti-cycling After a space heating demand has been satisfied, the control will delay the next space heating call for a set time period (time is adjustable by the installer). The time delay will be bypassed if the inlet water temperature drops too far during the delay. Boiler, system, and HW pump control When a space heating call for heat starts and no HWG call is on, the boiler pump is turned on. The system pump will turn on also if it is programmed to do so. If a HWG call for heat is on, the boiler pump will wait to turn on until just before the HWG pump turns off. After the space heating call for heat ends, the boiler pump will run for an additional period of time. When a HWG call for heat starts, the HWG pump is turned on. If a space heating call for heat is on, the boiler pump will turn off a few seconds after the HWG pump turns on. Louver When the boiler needs to control combustion air louvers, connect a 24 VAC louver relay to the two (2) Louver Relay terminals. Connect the Louver End Switch to the Louver Proving Switch input on the Low Voltage Connection Board.
General
How the boiler operates
The Crest uses an advanced stainless steel heat exchanger and electronic control module that allows fully condensing operation. The blowers pull in air and push flue products out of the boiler through the heat exchanger and flue piping. The control module regulates blower speeds to control the boiler firing rate. The gas valves sense the amount of air flowing into the boiler and allow only the right amount of gas to flow.
Temperature control
Modulation The Crest is capable of modulating its firing rate from a minimum of 4 - 6% (model specific) to a maximum of 100%. The firing rate is dictated by the call for heat (i.e., space heating or hot water generation), the heating load, ramp delay (if enabled), and various other temperature limitations.
46
10
Operating information
(continued)
Gradient limiting If during operation of the boiler the outlet water temperature is rising too quickly, the control will reduce the firing rate to its lowest setting. Outdoor air reset If an outdoor air sensor is connected, the control module will calculate the set point based on the programmed reset curve. The installer can change the slope of the reset curve by several adjustable parameters. The user can limit the maximum set point for the system using the space heating set point. Boost function If outdoor air reset is active, the boost temperature is not 0, a space heating demand has been active continuously for a set period of time (time adjustable by installer) and there has been no HWG demands, the control will increase the set point by a fixed number of degrees (adjustable by installer). This process will continue until the space heating demand ends, the set point reaches the programmed set point or a maximum of 20 increases has occurred. Once the system heat demand is satisfied, the set point will revert to the value determined by the reset curve. Night setback The controller may be programmed to reduce the space heating set point and/or Hot Water Generator set point for each demand during a certain time each day. A start and stop time for each demand can be programmed for each day of the week. The controller can be programmed to reduce the tank set point as well. A different set of start and stop times can be programmed each day of the week. Flame current support To prevent nuisance shutdowns when the boiler is firing at minimum rates, the control will increase the firing rate when the flame signal drops too low. ModBus The Crest boiler can be connected to and controlled by a Building Automation System through the ModBus interface. Connect the A and B wires to the A and B terminals. If connecting another cable (in a daisy chain), connect the shield wire of the first cable to one of the shield terminals, and the shield wire of the second cable to the other shield terminal. If it is desired to ground the cable shield at the heater, connect the shield wire to one of the shield terminals, and install a jumper across the two (2) terminals in connector X5 on the ModBus interface board. 0-10V Rate output A 0-10V signal which indicates the firing rate of the heater is available. This output may be connected to a Building Management System (BMS) to allow it to monitor the actual firing rate. Connect the - terminal to the COM or - terminal on the BMS, and connect the + terminal to the 0 - 10V or + terminal on the BMS.
Ramp Delay For systems with lower flow, the SMART TOUCH can limit the firing rate (when enabled) when a space heating call for heat starts, or when switching from a DHW call for heat to a space heating call for heat. There are six (6) limits that can be programmed, as well as six (6) time intervals corresponding to each limit. The sixth limit will also limit the firing rate for the rest of the call for heat.
Protection features
Outlet temperature, flue temperature, and temperature rise limiting The outlet water temperature is monitored by the boiler outlet temperature sensor. When the outlet temperature exceeds 185F, the unit will reduce the fan speed. If the outlet water temperature exceeds 195F (90C) the control will shut the unit down until the minimum off time has expired and the outlet drops 10F (5.5C). The control module monitors the flue temperature by a sensor located in the flue exhaust. If the flue temperature exceeds 350F (176C) the control will reduce the maximum fan speed. If the flue temperature exceeds 400F (204C) the control will shut the unit down. The unit will restart automatically once the flue temperature drops 50F (27C) and the minimum off time has expired. The control monitors the temperature difference between the inlet and the outlet sensor. If this difference exceeds 80F (27C) the control will reduce the fan speed. If the temperature difference exceeds 90F (32C) the control will shut the unit down. The unit will restart automatically once the temperature difference has dropped below 50F (28C) and the minimum off time has expired. Freeze protection DO NOT install the boiler in a room likely to freeze. The following integral feature of the SMART TOUCH control module provides some protection for the boiler only -- not for the system. The SMART TOUCH control module provides freeze-up protection as follows when the boiler water temperature drops below 45F (7C): Below 45F (7C), the boiler and system pumps (if enabled) operate constantly. Below 37F (3C), the boiler turns on. Boiler and pumps turn off if boiler water temperature rises above 43F (6C). This feature of the SMART TOUCH control module does not eliminate the possibility of freezing. The installation must still use recognized design, installation and maintenance practice to prevent freeze potential for the boiler and system.
CAUTION
47
10
Operating information
High limit operations The Crest SMART TOUCH control has two (2) integral limits, one auto reset and one manual reset. The Crest also has one auxiliary manual reset high limit. The integral and auxiliary high limits are UL353 certified. When the outlet temperature exceeds 195F (90.6C) (Installer Adjustable Parameter), integral auto reset high limit action occurs. The boiler will shut down until the outlet water cools down and the timer expires. If the outlet temperature exceeds 200F (93.3C) (User Adjustable Dial), auxiliary manual reset high limit action occurs. The boiler will shut down until the outlet water cools down and the boiler is reset through the user interface. If the outlet temperature exceeds 205F (93.3C) (Installer Adjustable Parameter), integral manual reset high limit action occurs. The boiler will shut down until the outlet water cools down and the boiler is reset through the user interface. Low water cutoff protection A low water cutoff device with test and reset functionality is provided in the boiler as standard equipment. Flow sensing device The SMART TOUCH control module uses temperature sensing of both supply and return temperatures of the heat exchanger. If the flow rate is too low or the outlet temperatures too high, the control module modulates down and will shut the boiler off. This ensures boiler shutdown in the event of low flow conditions. NOTICE If a mechanical flow switch is required to meet local code requirements the Crest boiler can be equipped with a field supplied outlet switch. Please reference page 38 of this manual for more information.
Monitor external limits Connections are provided on the connection board for external limits such as an additional high limit. The SMART TOUCH control will shut off the burner and inhibit relighting whenever any of these external limits open. Run-time and alarm outputs The boiler provides dry contacts for indicating when the boiler is running, and when it is unable to operate. Run-time and cycle counting The control uses four timers to monitor the total hours of burner operation: 75 - 100% 50 - 75% 25 - 50% <25% The control uses four (4) ignition counters to monitor the amount of boiler cycles. The first counter counts all ignitions of the control. The second counter counts only ignition attempts that have failed. The third and fourth counters are the same as the first and second respectively, but can be reset by the installer. Service reminder The control can be programmed for service reminder notification. This notification will become active when either a set amount of time has expired, or a set amount of running hours or cycles has expired (all adjustable by the installer). The service reminder notification can be reset by the installer. The service companys name and phone number can be programmed to display when service is due. Error logging The control will hold in memory the last 10 blocking faults as well as the last 10 lockout faults. The date and time of the occurrence will be recorded as well. Only the 10 most recent occurrences will be held in memory.
48
10
Operating information
(continued)
Cascade
When multiple boilers are installed, they can be wired together in a cascade sequence. A maximum of eight boilers can be controlled from a single control. In this application one boiler would be designated as the Leader control and all others would be designated as Member controls. Once the Leader boiler receives a call for heat from the Enable input, the 0 - 10 VDC input, or ModBus, the control will determine what the set point will be. If outdoor air reset is desired, connect the outdoor air sensor to the terminals on the Low Voltage Connection Board on the Leader boiler. The set point will be calculated based on the programmed reset curve parameters. See the Crest Service Manual to program the reset curve. If outdoor air reset is not desired, do not connect the outdoor air sensor. A fixed temperature set point can be programmed into the control, or provided through the ModBus interface. If the water temperature at the controlling sensor is less than the set point + the turn-off offset - the off-on differential, the control will initiate a call for heat on the Cascade (see the Crest Service Manual for an explanation of the offset and differential). The Leader will energize the lead boiler on the Cascade. For a new startup this will be the Leader boiler. The boiler will fire at its ignition speed and will then modulate its firing rate to maintain the set point. If the first boiler reaches 80% of its firing rate, the Leader will calculate the rate at which the first and second boiler should fire to meet the load. At this point, the Leader will fire the second boiler on the Cascade. For a new startup, this would be the first Member boiler. The boiler will fire at its ignition speed, and then both the Leader and the Member boilers will modulate together to a firing rate to maintain set point. If the set point cannot be met, the Leader will continue firing additional Members until either the heat demand is met or all boilers on the Cascade are firing. As additional Member boilers are fired, the running boilers in the Cascade will modulate together to meet load. As the heat demand decreases, the boilers firing in the Cascade will modulate down together until they reach a minimum of 10% of its firing rate, where the last boiler will shut down and the remaining boilers will modulate together to meet load. As the heat demand decreases further, the second to last boiler will shut down. This will continue until the demand is satisfied and all boilers are shut off.
Sequence of the cascade To equalize the run time of all boilers on the Cascade, the firing sequence will automatically be changed at set intervals. For the first 24 hours after initializing the Cascade, the sequence will be changed every hour. After that the sequence will be changed once every 24 hours. HW operation with cascade For HW operation any boiler(s) in the Cascade can be selected to provide heat for a HW call. Select a boiler to be designated as the HW boiler. Connect the HW thermostat or sensor to the terminals on the Low Voltage Connection Board marked for the HW Thermostat or sensor. When the boiler receives a HW call, the Leader control will take that boiler out of the Cascade sequence. If another boiler is available, the Leader will start it up to take its place. The HW boiler will adjust its set point to the programmed HW set point and will adjust its firing rate to maintain this. Once the HW call has been satisfied, the Leader control will place that boiler back into the Cascade sequence. Night Setback and Ramp Delay operations with cascade Night Setback and Ramp Delay operation of the boilers within the Cascade are available. Programming will be done through the Leader boiler. Refer to the Crest Service Manual for information regarding Night Setback and Ramp Delay.
49
10
Operating information
Sequence of operation
Note: This unit is equipped with two (2) gas train systems. Gas Train 1 will fire first. If the demand cannot be met by the first gas train, the second gas train (Gas Train 2) will fire.
1. 2. 3. 4. 5. 6. 7. 8.
Upon a call for heat, the control turns on the appropriate pumps (system and boiler pumps for a space heating call, HW pump for a domestic hot water call). The control confirms that the low water cutoff contacts are closed and energizes the louvers (optional) and damper (optional) relays. The control confirms that the gas pressure switch, blocked drain switch, limits, louver proving switch (optional) and damper proving switch (optional) contacts close. The Pre-Purge cycle begins. The control confirms both blowers come up to the desired speed, both blower proving switches close, and the air pressure switch is closed. Once the Pre-Purge cycle is complete, the control lowers the blower speeds, initiates sparking of the ignition electrode, and opens Gas Valve 1. After a short wait, the control stops sparking and checks for the presence of flame current through the flame sense electrode. If the control does not detect flame current, the control will lockout indefinitely, until the RESET button on the touch screen LCD is pressed. Models FB 1500 - 2500 will have one retry. If the control detects flame current, the control will hold the blower speed constant for a few seconds to allow the flame to stabilize, then begin modulating the firing rate in order to maintain the controlling sensor to the desired set point temperature. If the current call for heat is for space heating and a HW call for heat becomes active, the control will turn on the HW pump relay output, then turn off the boiler pump. It will then modulate the blower speed in order to maintain the outlet temperature to the desired HW outlet set point temperature. If the first combustion system in the boiler is unable to maintain the desired set point temperature, the second combustion system in the boiler will be started. Both blowers will modulate to a set speed, and the second gas valve will be energized. The second combustion system will light from the first combustion system. The second flame will be monitored much like the first. Once both combustion systems are firing, the control will work in synchronization to maintain the desired set point temperature. If the heat load should decrease sufficiently, the second combustion system will be shut down. Once both the space heating and HW calls for heat are satisfied, the control will turn off the gas valve(s) and begin the Post-Purge cycle. Any pumps that are running will begin their respective Pump Delay cycles. At the end of the Post-Purge cycle, the louver relay contacts will de-energize. The control verifies that the blowers stop running and the blower proving switches open. At the end of the Pump Delay cycle(s), the pump(s) will be turned off.
9.
10.
50
10
Operating information
(continued)
When the ON/OFF switch is turned to the ON position, the first screen visible on the LCD display will be the Home Screen. This screen displays the current status of the Crest boiler. The following items can be viewed or interacted with on the Home Screen: On/Off button - Pressing this button allows the boiler to be placed in either Manual Shutdown Mode or Standby Mode. Status - This line shows the current operating status of the Crest boiler and the current set point. Outlet Water Temperature - This is the boiler outlet temperature. Inlet Water Temperature - This is the boiler inlet temperature. System Supply Temperature - This is the water temperature as measured by the system supply sensor located in the downstream piping (if connected). System Return Temperature - This is the water temperature measured by the system return sensor located in the upstream piping (if connected). Outside Air Temperature - This is the outdoor air temperature (if connected).
DHW Temperature - This is the temperature as measured by the tank sensor in the hot water storage tank (if connected). Flue Temperature - Temperature measured by the flue sensor. Time - The time is displayed in the lower left-hand corner of the display. Reference the Crest Service Manual for Night Setback parameters and more information regarding adjusting the date and time. Boiler Status button - Pressing this button brings up the Boiler Status Screen. This screen shows the status of the various safeties, inputs, and outputs to the control module. Reference the Boiler Status Screen section in the Crest Service Manual for more information regarding this screen. Main Menu button - Pressing this button brings up the Main Menu Screen. From this screen navigation to nine (9) other screens is possible. Reference the Main Menu Screen section on page 52 of this manual for more information regarding this screen. Modulation button - Pressing this button brings up the Modulation Screen. This screen shows overall boiler modulation, individual fan speeds, and flame currents. Modulation Percentage - Displays the current boiler firing rate.
51
10
Operating information
Use the Main Menu Screen (FIG. 10-2) to access the screens necessary to set temperatures, operating conditions, and monitor boiler operation. The Crest is equipped with a SMART TOUCH control system. All menu options are accessed by touching the screen with your finger or a stylus from a PDA. Figure 10-2 Main Menu Screen
The Main Menu Screen allows navigation to nine (9) additional screens which are used to set temperatures, operating conditions, and monitor boiler operation. These screens are as follows: Home - Navigates back to the Home Screen. Setup - Allows access to 12 other screens for the adjustment of the control parameters. Cascade - Shows the status of multiple boilers connected together in a cascade arrangement (Leader only). Modulation - Shows the status of the two (2) gas train systems used in the boiler. BMS - Shows the information from a Building Integration System. Pumps - Allows the installer to configure the boiler, system, and DHW pumps. History - Shows the operating and fault history of the control module. Graphs - Allows the selection of items to be graphed on a chart. Service - Allows the installer to control the fan speed of the individual combustion systems for the purposes of combustion analysis. Service Mode will override all other heat demands, however, all limits will remain active.
Reference the Crest Service Manual for more information regarding the nine (9) accessible screens.
52
11
Maintenance
Service technician
(see the following pages for instructions) General:
Address reported problems, if any Inspect interior; clean and vacuum if necessary; Clean condensate trap and fill with fresh water Check for leaks (water, gas, flue, condensate) Verify flue and air lines in good condition and sealed tight Check system water pressure/system piping/expansion tank
Owner maintenance
Daily
ANNUAL START-UP
Check control settings Check the ignition and both flame sense electrodes (sand off any deposits; clean and reposition) Check wiring and connections Perform start-up checkout and performance verification per Section 9. Flame inspection (stable, uniform) Check both flame signals (at least 10 microamps at high fire) Clean the heat exchanger Test low water cutoff (reference the Crest Service Manual).
Monthly
Check air and vent termination screens Check relief valve Check condensate drain system
Every 6 months
Reset button (low water cutoff) Check boiler piping (gas and water) for leaks Operate relief valve
Shut boiler down (unless boiler used for domestic hot water)
53
11
Maintenance
Follow the service and maintenance procedures given throughout this manual and in component literature shipped with the boiler. Failure to perform the service and maintenance could result in damage to the boiler or system. Failure to follow the directions in this manual and component literature could result in severe personal injury, death, or substantial property damage.
WARNING
WARNING The boiler should be inspected annually only by a qualified service technician. In addition, the maintenance and care of the boiler designated in Table 11A and explained on the following pages must be performed to assure maximum boiler efficiency and reliability. Failure to service and maintain the boiler and system could result in equipment failure. WARNING Electrical shock hazard Turn off power to the boiler before any service operation on the boiler except as noted otherwise in this instruction manual. Failure to turn off electrical power could result in electrical shock, causing severe personal injury or death. Figure 11-1 Condensate Trap
1. Inspect all water and gas piping and verify to be leak free. 2. Look for signs of leaking lines and correct any problems found. 3. Check gas line using the procedure found in Section 6 - Gas Connections.
54
11
1.
Maintenance
(continued)
WARNING
2.
WARNING
Safety relief valves should be re-inspected AT LEAST ONCE EVERY THREE YEARS, by a licensed plumbing contractor or authorized inspection agency, to ensure that the product has not been affected by corrosive water conditions and to ensure that the valve and discharge line have not been altered or tampered with illegally. Certain naturally occurring conditions may corrode the valve or its components over time, rendering the valve inoperative. Such conditions are not detectable unless the valve and its components are physically removed and inspected. This inspection must only be conducted by a plumbing contractor or authorized inspection agency not by the owner. Failure to re-inspect the boiler relief valve as directed could result in unsafe pressure buildup, which can result in severe personal injury, death, or substantial property damage. Following installation, the valve lever must be operated AT LEAST ONCE A YEAR to ensure that waterways are clear. Certain naturally occurring mineral deposits may adhere to the valve, rendering it inoperative. When manually operating the lever, water will discharge and precautions must be taken to avoid contact with hot water and to avoid water damage. Before operating lever, check to see that a discharge line is connected to this valve directing the flow of hot water from the valve to a proper place of disposal. Otherwise severe personal injury may result. If no water flows, valve is inoperative. Shut down the boiler until a new relief valve has been installed.
WARNING
2. After following the above warning directions, if the relief valve weeps or will not seat properly, replace the relief valve. Ensure that the reason for relief valve weeping is the valve and not over-pressurization of the system due to expansion tank waterlogging or undersizing.
55
11
Maintenance
and flame
Shut down the boiler: - Follow the To Turn Off Gas to Appliance instructions for the boiler in Section 9 - Startup. - Do not drain the boiler unless it will be exposed to freezing temperatures. If using freeze prevention fluid in system, do not drain. 3. Allow time for the boiler to cool to room temperature if it has been firing. 4. Remove the top access panel to remove the gas/air manifold assembly. 5. Remove the nuts securing the burner to the burner mounting plate. Remove the burner (FIG. 11-2). 6. When replacing the burner, ensure gaskets are in good condition and positioned correctly (FIG. 11-2). 7. When securing the burner, be sure to tighten the nuts, but DO NOT over-tighten. Tighten the nuts to a torque setting of no more than 6.2 ft.-lbs. When securing the burner mounting plate be sure to tighten the nuts, but DO NOT over-tighten. Tighten the nuts to a torque setting of no more than 15.5 ft.-lbs. Figure 11-2 Burner Assembly
INSULATION
1. Remove the ignition and both flame sense electrodes from the burner plate. 2. Remove any deposits accumulated on the ignition/ flame sense electrodes using sandpaper. If the electrodes cannot be cleaned satisfactorily, replace with new ones. 3. Replace ignition/flame sense electrodes, making sure the gaskets are in good condition and correctly positioned.
AIR/GAS MANIFOLD MANIFOLD GASKET BURNER ASSEMBLY BURNER GASKET BURNER PLATE
FIBERBOARD
56
11
Maintenance
(continued)
1. Review the Crest Users Information Manual with the owner. 2. Emphasize the need to perform the maintenance schedule specified in the Crest Users Information Manual (and in this manual as well). 3. Remind the owner of the need to call a licensed contractor should the boiler or system exhibit any unusual behavior. 4. Remind the owner to follow the proper shutdown procedure and to schedule an annual start-up at the beginning of the next heating season.
15. Replace the burner mounting plate assembly and gas/air manifold assembly. Ensure gaskets are in good condition and positioned properly. Restore boiler to operation. 16. Perform start-up and check-out procedures in the Check Flame and Combustion - Section 9 - Startup on pages 42 and 44 of this manual.
57
12
Diagrams
120VAC
INTEGRATED CONTROL
X1-3 ON/OFF SWITCH X1-6 F2 3.15 A F4 5.0 A SYSTEM PUMP RELAY
BOILER PUMP RELAY DHW PUMP RELAY
TERMINAL STRIP
GROUND
X1-2
INTEGRATED CONTROL
X8-20 X8-10 X4-1 X4-2 X4-3
X6-3 CN6-3
X1-4
MODBUS BOARD
X6-1 CN6-2 X6-2 CN6-1 CN3-6 CN3-7 CN3-14 CN3-13 CN3-12 CN3-11 CN3-10 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40
SHIELD A B
SHIELD
X10-1
X10-2
0-10V 0-10V
+ + -
X10-6
X10-5
0-10V 0-10V
+ + A B
SHIELD
CASCADE
SHIELD
INLET SENSOR
-T
X8-2
-T
OUTLET SENSOR (S1) X8-4 LARGE BLOWER LARGE BLOWER RELAY 3 FLUE SENSOR 1 2 X8-9
-T -T
3 X7-5
MODBUS
X1-3
PRE-MIX SENSOR 2 (S14) FLUE DAMPER 1 X6-18 X6-9 3 X6-17 24V TRANSFORMER X6-8 4 5 1 J3-6 LWCO PROBE TEST SWITCH LWCO RESET J3-3 J2-1 J2-2 J3-5 J3-2 X13-2 X13-3 2 4 5 X4 RIBBON CABLE LARGE BLOWER 1 SMALL BLOWER 2 2
LWCO BOARD
J3-4
INTEGRATED CONTROL
X6-5 GPS1 GPS2 GPS3 X6-15 BLOWER PROVING SWITCH (LARGE) BLOWER PROVING SWITCH (SMALL) BLOCKED FLUE SWITCH BLOCKED DRAIN SWITCH X3-3 X6-12 X3-4 X13-1 X3-1 X3-2 CN1-5 CN1-6 CN1-12 CN1-10 X6-11 X6-2 X6-14 CN1-11 CN1-9 CN1-8 CN1-7 X6-13 X6-4 HIGH LIMIT SWITCH CN1-1 CN1-2 CN1-3 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
CN1
CN3
LCD DISPLAY
DU941
ALARM CONTACTS RUN-TIME CONTACTS TANK THERMOSTAT R W ENABLE LOUVER PROVING 24 VAC LOUVER RELAY COIL AUX SWITCH 1 AUX SWITCH 2
X6-6 X5-1 X5-7 X5-2 X5-8 X5-3 X5-9 X5-4 X5-10 X5-5 X5-41 X5-6 X5-12
Notes: 1. All wiring must be installed in accordance with: local, state, provincial and national code requirements per either N.E.C. in USA or C.S.A. in Canada. 2. If any original equipment wire as supplied with the appliance must be replaced, it must be replaced with wire having same wire gauge (AWG) and rated for a minimum of 105C. Exceptions: Replacement high voltage spark lead and ribbon cables must be purchased from the factory. Use of a non-approved spark lead or ribbon cables can lead to operational problems which could result in non-repairable damage to the integrated controller or other components. 3. Actual connector block locations may vary from those shown on diagrams. Refer to actual components for proper connector block locations when using diagrams to troubleshoot unit.
LADDER DIAGRAM LBL20182 REV A
58
12
Diagrams
(continued)
MODBUS OPTION
A B
SHIELD
RATE + 0-10V OUT BOILER + 0-10V PUMP OUT SYSTEM RETURN SENSOR SYSTEM SUPPLY SENSOR TANK SENSOR OUTDOOR SENSOR BMS + IN SYSTEM + PUMP IN SHIELD A B
0-10V 0-10V
CASCADE
SHIELD
17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40
GY R PR
X1-1 X1-2 X1-3 X6-3 X6-1 X6-2 X4-1 X4-2 X4-3 BL R BL R BR W OR OR/W P W BL BK Y
-T
INTEGRATED CONTROL
BK T X8-20 X8-10
CN3-6 CN3-7 CN3-14 CN3-13 CN3-12 CN3-11 CN3-10 CN3-9 CN3-8 CN3-1 CN3-2 CN3-3 CN3-4
X7-8 X7-7 X8-13 X8-14 X8-12 X8-11 X8-5 X8-15 X8-6 X8-16 X8-7 X8-17 X8-18 X8-1 BL X8-3
120V SUPPLY
GND L N
INLET SENSOR
-T
JUNCTION BOX
X8-8
X8-2 BK
W FLUE SENSOR
-T
X8-4
ON/OFF SWITCH X1-6 X1-3 X1-12 X10-1 X10-4 X1-1 X1-2 X1-4 X10-2 X10-5 X10-3 X10-6 X6-18 X6-8 X1-8 BK W G
X8-9
LCD DISPLAY
-T
X7-1
X7-5
X7-2
X7-6
DU941
CN1
X4
1 2 3
BLOWER (SMALL)
CN1-4 CN1-5 CN1-6 CN1-12 CN1-10 CN1-11 CN1-9 CN1-8 CN1-7 CN1-1 CN1-2 CN1-3
R R OR OR BL BK BR R Y OR BL R
X3-3 X3-4 X3-1 X3-2 X6-1 X6-11 X6-2 X6-14 X6-10 X6-13 X6-4
12345
X6-9 X6-17 X2-4 T BK/W LARGE BLOWER RELAY G/W W T
R/W
1 2 3
BLOWER (LARGE)
12345
BK/W X13-2 X13-3 W/BK T
LWCO BOARD
J3-6 J3-5 J3-4 J3-3 J3-2 J2-1 J2-2 OR GPS2 OR BLOWER PROVING SWITCH (LARGE) T BLOWER PROVING SWITCH (SMALL) PR BLOCKED FLUE SWITCH BK BLOCKED DRAIN SWITCH X6-6 X13-1 24V TRANSFORMER X6-12 GPS3 X6-15 X13-4 X2-3 X1-7 X1-10 X1-5 R R R P SPARK GENERATOR FLAME SENSE 2 SPARK ROD FLAME SENSE 1 FLUE DAMPER TRANSFORMER X2-5 OR GPS1 BR X6-5 BL Y OR BK FLUE DAMPER
1
OR
X6-3
GND
M
2 3
X5-1 X5-7 X5-2 X5-8 X5-3 X5-9 X5-4 X5-10 X5-5 X5-41 X5-6 X5-12
Notes: 1. All wiring must be installed in accordance with: local, state, provincial and national code requirements per either N.E.C. in USA or C.S.A. in Canada. 2. If any original equipment wire as supplied with the appliance must be replaced, it must be replaced with wire having same wire gauge (AWG) and rated for a minimum of 105C. Exceptions: Replacement high voltage spark lead and ribbon cables must be purchased from the factory. Use of a non-approved spark lead or ribbon cables can lead to operational problems which could result in non-repairable damage to the integrated controller or other components. 3. Actual connector block locations may vary from those shown on diagrams. Refer to actual components for proper connector block locations when using diagrams to troubleshoot unit.
59
Revision Notes: Revision A (ECO #C07970) initial release. Revision B (ECO #C08023) reflects changes made to FIG. 6-3 on page 32 for Mass approval and changes made to FIG. 5-3 on page 28. Revision C (ECO #C08179) reflects the addition of three (3) new vent manufacturers (pg. 16 - Table 2A). Revision D (ECO #C08585) reflects edits made to FIG. 4-4 and the addition of Fixed or Variable Flow Primary in place of Full Flow. Revision E (ECO #C08841) reflects changes made to #3 on page 42 additional information added to the humidity warning on page 7, along with references to the Dual Fuel Supplemental Manual. FB-I-O Rev E 9/11