Operator and Service Manual Om/Sm-Ah-Ce
Operator and Service Manual Om/Sm-Ah-Ce
Operator and Service Manual Om/Sm-Ah-Ce
Self-contained
Stainless Steel
Gas Heated
Floor Mounted
Stationary
THESE APPLIANCES HAVE BEEN CE MARKED ON THE BASIS OF COMPLIANCE WITH THE GAS
APPLIANCE DIRECTIVE, EMC AND LOW VOLTAGE DIRECTIVE FOR THE COUNTRIES, GAS
TYPES AND PRESSURES AS STATED ON THE DATA PLATE.
2
OM/SM-AH-CE
TABLE OF CONTENTS
Section Page
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.1 Model Numbers, Net Weights & Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.2 Siting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.3 Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.4 Ventilation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.5 Electrical Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.6 Gas Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.7 Water Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.8 Total Gas Rate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.9 Injector Diameters-Natural and Propane Gas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.10 Gas Pressure Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.11 Burner Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2 Assembly and Conditioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.1 Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.2 Gas Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.3 Electrical Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.4 Jacket Water Level/Jacket Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.5 Pre-Commissioning Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.6 Instruction to Installer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
3 Servicing and Conversion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.1 Conversion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3.2 Jacket Vacuum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3.3 Jacket Filling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3.4 Water Treatment Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3.5 Removal of Control Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.6 Removal of Spark Ignition Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.7 Removal of Low Water Level Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.8 Removal of Gas Control Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.9 ON/OFF Switch and Reset Button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.10 Removal of Neons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.11 Removal of Thermostat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
3.12 Removal of Pressure Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
3.13 Low Water Level Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
3.14 Removal of The Burner . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.15 Pilot Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.16 Removal of Pressure Gauge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.17 Removal of Sight Glass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.18 Safety Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.19 Filling Valve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.20 Fuse Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
4 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
5 User Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
5.1 Equipment Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
5.2 Lighting and Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
5.3 Cleaning and Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Parts Lists . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Service Log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
3
OM/SM-AH-CE
Introduction
These Appliances have been CE marked on Users should be conversant with appropriate
the basis of compliance with the Gas provisions of the Fire Precautions Act and the
Appliance Directive, EMC and Low Voltage requirements of the Gas Safety Regulations. In
Directive for the Countries, Gas Types and particular they should be aware of the need for
Pressures as stated on the Data Plate. regular servicing by a competent person to
ensure the continued safe and efficient
These appliances MUST BE installed by a performance of the Appliance.
competent person in conformity with the
INSTALLATION AND SERVICING Upon completion of the installation, the Owners
INSTRUCTIONS and National Regulations in Manual should be handed to the users and the
force at the time. Particular attention MUST be installer should instruct responsible person(s) in
paid to the following: the correct operation and maintenance of the
Appliance.
C I.E.E. Regulations for Electrical
Installations This equipment is ONLY FOR PROFESSIONAL
USE, and shall be operated by QUALIFIED
C Electricity at Work Regulations persons. It is the responsibility of the Supervisor
or equivalent to ensure that users wear
SUITABLE PROTECTIVE CLOTHING and to
C Gas Safety (Installation & Use)
draw attention to the fact that, some parts will,
Regulations
by necessity, become VERY HOT and will
cause burns if touched accidentally.
C Health and Safety at Work Act
The Groen Steam Jacketed Kettle you have just
C Fire Precautions Act purchased has been handcrafted from the finest
materials, meticulously inspected, and carefully
C Local and National Building tested to ensure that you receive the best
Regulations possible product. With reasonable care and
Furthermore, if a need arises to convert the periodic maintenance, it will provide years of
Appliance for use with another gas, a competent faithful service. It is recommended that you
person must be consulted. Parts which have establish a timetable for periodic maintenance
been protected by the manufacturer MUST NOT as outlined in this manual.
be adjusted by the User.
Section 1
Installation
UNLESS OTHERWISE STATED, PARTS PROTECTED BY THE MANUFACTURER ARE NOT TO BE
ADJUSTED BY THE INSTALLER.
4
OM/SM-AH-CE
1.2 Siting 1.5 Electrical Supply
Install the appliance on a level floor in a well-lit This unit is designed for connection to fixed
and draught-free position. Install the appliance in wiring. A suitably rated isolating switch with
accordance with local and/or national regulations contact separation of at least 3 mm on both poles
as listed in this manual. must be fitted to the installation and the wiring
executed in accordance with the regulations listed
1.3 Installing Clearances in this manual.
Minimum clearances of 150 mm from the sides of Cable entry is at the lower rear on right hand side
the appliance and 150 mm from the rear of the of the appliance. Access to the terminals is
appliance are required if the appliance is installed gained by removing relevant panels as described
next to combustible surfaces. in Section 3.5 of this manual.
Allow 1000 mm minimum clearance between the Provide 230 VAC, 50 Hz, 1 Phase, service. Rated
top rim of kettle and any overlying surface. input: 0.17 Amps, or 40 Watts. The electrical
schematic is located in the service compartment
1.4 Ventilation and in this manual.
5
OM/SM-AH-CE
1.8 Total Gas Rate NOTE: With reference to the gas rate, pressure
Natural Propane adjustments and conversions, this appliance is
Natural Propane CE-approved for use with the following gases:
Model (G20& (G31)
BTU/hr BTU/hr
G25) KW KW
AH-20 22 75,100 22 75,100 a) G20 natural gas may be supplied to the
appliance in Austria, Belgium, Denmark,
AH-40 25 85,300 22 75,100
Finland, France, Germany, Greece, Iceland,
AH-60 & Ireland, Italy, Luxembourg, Norway, Portugal,
40 136,500 40 136,500
AH-80 Spain, Sweden, Switzerland and the United
Kingdom.
1.9 Injector Diameters-Natural & Propane Gas
Natural Natural Propane No. of b) G25 natural gas may be supplied to the
Model Gas G20 Gas G25 Gas G31 Orifices appliance in Belgium, France and the
(mm) (mm) (mm) (Injectors) Netherlands.
AH-20 4.39 4.70 2.64 1
AH-40 4.57 4.90 2.64 1 c) G31 propane gas may be supplied to the
AH-60 & appliance in France, Germany, Ireland, the
5.94 6.75 3.57 1 Netherlands, Portugal, Spain, Switzerland,
AH-80
and the United Kingdom.
1.10 Gas Pressure Adjustment
A pressure test point is fitted on the burner Use of the appliance with non-approved gases in a
manifold and on the gas control valve. listed country, or use in other countries will void CE
certification.
AH-60 &
Model AH-20 AH-40
AH-80 1.11 Burner Adjustment
NATURAL mbar 8.75 8.75 8.75
GAS G20 in. WC 3.5 3.5 3.5 The burner has a primary air adjustment. The gap
NATURAL mbar 8.75 8.75 7.0 should be 1/4" (6.35 mm) to 3/8" (9.53 mm).
GAS G25 in. WC 3.5 3.5 2.8
PROPANE mbar 25 25 25
GAS G31 in. WC 10 10 10
Section 2
Assembly and Commissioning
2.1 Assembly 2.3 Electrical Supply
a) Unpack the appliance. Before commissioning the appliance, ensure that the
electrical installation has been carried out to the
b) Place on a firm, level floor. Adjust and fix relevant regulations. (Paragraph 1.5)
feet.
THIS APPLIANCE MUST BE EARTHED.
Caution: Shipping straps are under tension and
can snap back when cut. Take care to avoid 2.4 Jacket Water Level/Jacket Pressure
personal injury or damage to the unit by staples
left in the walls of the carton. a) Ensure the water level is correct in the jacket, by
confirming that the level is between the marks on
2.2 Gas Supply the gauge glass. If the water is low, follow the
instructions under "Jacket Filling" in the servicing
Connect the unit to the gas supply and test for gas section of this manual.
soundness. For the part of the integral gas supply
down stream of the gas valve, leak detection b) Check the pressure gauge. If the gauge does not
spray or some solution may be used with the show 20 or more inches of vacuum (that is, a
burners lit. reading of 20 to 30 below zero) see "Jacket
Vacuum" in the servicing section of this manual.
Caution: Ensure that the pan contains liquid when
the burners are alight. 2.5 Pre-Commissioning Check
6
OM/SM-AH-CE
a) Prior to operation, clean kettle pan with hot f) Remove governor cap screw on gas control
water and detergent. Rinse thoroughly. valve. See figure for governor position on valve.
b) Remove all literature and packing materials g) Governor is suitable for natural and propane gas.
from the interior and exterior of the unit.
h) To increase pressure turn the screw inside the
c) Ensure the open end or the elbow at the governor turret clockwise, or anti-clockwise to
safety valve outlet is pointed down. If not, turn reduce pressure. Check the burner pressure
the elbow to the correct position. See Safety again after 15 minutes and adjust if necessary.
Valve Operation Instructions on Page 8.
i) Disconnect pressure gauge from the test point.
2.5.1 Lighting Sequence
j) Re-seal the pressure test point and test for gas
From Initial Start Up: soundness.
a) Put a small amount of water in the kettle pan. k) Replace governor cap screw, lid and panels.
b) Ensure gas and electricity mains are “on.” 2.5.3 Checking Performance of Controls
c) Switch the toggle switch to the "on" position. a) Light the unit (Paragraph 2.5.1). Check that the
controls produce a healthy spark from the
d) Turn thermostat dial to desired setting. electrode to the earthing post and that ignition is
smooth and without delay.
e) Observe that the burners ignite by the pilot
lamp illuminating. b) Turn thermostat off and then on. Check that
burners go out when switched off and ignite
f) If the unit does not ignite, it will lock-out. Turn smoothly and quickly when switched back on.
the unit off and wait for one or two minutes Repeat several times.
before again attempting to switch it on.
c) If the unit fails to respond as described above
g) Press reset lock-out switch and repeat steps contact an authorized Groen service agent.
(b) to (e).
2.6 Instruction to Installer
h) To switch unit off, flip toggle (On/Off) switch
to the “off” position. IMPORTANT
After installing and commissioning the
i) Turn gas and electricity mains off. appliance, the installer should hand the user's
instructions to the user or purchaser. Ensure that
2.5.2 Setting The Gas Pressure the instructions for lighting, turning off, correct
use and cleaning are properly understood.
a) Check gas pressure during commissioning. Emphasis should be made with regard to the
Connect a pressure gauge to the pressure test location of the main gas isolating valve. The
point on the burner manifold or the gas control emergency shut down procedure should be
valve. See figure for test points. demonstrated.
b) When checking pressure at gas valve test
points, undo the screw a half turn and slip
tube over the nipple.
7
OM/SM-AH-CE
Section 3
Servicing and Conversion
IMPORTANT
BEFORE ATTEMPTING ANY SERVICING, ENSURE THAT THE ISOLATING COCK IS TURNED OFF
AND CANNOT BE INADVERTENTLY TURNED ON, AND THAT THE ELECTRICITY SUPPLY IS
DISCONNECTED.
AFTER ANY MAINTENANCE TASK, CHECK THE APPLIANCE TO ENSURE THAT IT PERFORMS
CORRECTLY AND CARRY OUT ANY NECESSARY ADJUSTMENTS AS DETAILED IN SECTION 1.
ALWAYS CHECK FOR GAS SOUNDNESS AFTER CARRYING OUT ANY SERVICING OR
EXCHANGE OF GAS CARRYING COMPONENTS !
NOTE: When replacing wiring connections refer to the wiring diagram on the unit and in this manual.
8
OM/SM-AH-CE
body, testing must be performed more often. A e. Use pipe compound sparingly, or tape, on
“try lever test” must also be performed at the external threads only.
end of any non-service period.
f. DO NOT USE A PIPE WRENCH! Use
Test at or near maximum operating pressure by proper type and size wrench on wrench
holding the test lever fully open for at least five pads only.
seconds to flush the valve seat free of sediment
and debris. Release the lever and let the valve g. This valve must be mounted in a vertical,
snap shut. If lift lever does not activate, or there upright position directly to a clean, tapped
is no evidence of discharge, discontinue use of opening in the top of the boiler or
equipment immediately and contact a licensed equipment. Under no circumstances should
contractor or qualified service personnel. there be a flow restriction or valve of any
type between the safety relief valve and the
Neither Conbraco Industries, Inc. nor its agents pressure vessel.
assume any liability for valves improperly
installed or maintained. h. WARNING! During operation this valve
may discharge large amounts of steam
and/or hot water. Therefore, to reduce the
potential for bodily injury and property
damage, a discharge line MUST be installed
that:
9
OM/SM-AH-CE
i. See appropriate ASME Boiler and Pressure 3.3 Jacket Filling
Vessel Code for additional installation
instructions. The jacket has been charged at the factory with
the proper amount of treated distilled water. You
3.1 Conversion — NOTE: See Para 1.9 may need to restore the jacket water to its
and 1.10 (Page 6) for important gas proper level, either because water was lost as
conversion information. VERIFY steam during venting or because treated water
THE TYPE OF GAS TO BE USED. In was lost by draining.
the countries listed in Paragraph 1.10
all conversions must be for approved The procedure for adding water is as follows:
gas.
a. If you are replacing water lost as steam use
To change the type of gas used (e.g. G20 to distilled water. If you are replacing treated
G25 or G31 or the like), change the following: water that was removed from the jacket,
Burner injector prepare more as directed below.
Pilot orifice
Pressure setting b. Allow the kettle to cool completely. Using
Data Plate the proper sized spanner, remove the pipe
plug from above the globe valve.
The governor spring does not need to be
changed- only the pressure setting. c. Open the globe valve and pour distilled or
treated water in the pipe plug orifice. (See
3.2 Jacket Vacuum “Water Treatment Procedure,” Paragraph
3.4). Hold the safety valve open while you
When the kettle is cold, a reading that is pour, to let air escape from the jacket.
positive or near zero on the pressure/vacuum
gauge indicates excess air in the jacket. Air in d. Air introduced to the jacket during the filling
the jacket slows down the heating of the kettle. operation must be removed to obtain
efficient heating. (See "Jacket Vacuum"
To remove air: section 3.2).
a. Light the unit (see Section 2.5.1). See detailed Instructions on Page 8 pertaining
to Safety Valve installation and operation.
b. When the pressure/vacuum gauge reaches
a positive reading of five PSIG, release air 3.4 Water Treatment Procedure
and steam by lifting the lever on the safety
valve for about 1 second. Repeat this WARNING
process a few times, then let the valve snap READ AND FOLLOW ALL PRECAUTIONS
back into the closed position. STATED ON THE LABEL OF THE WATER
TREATMENT COMPOUND TO AVOID
See detailed Instructions on Page 8 pertaining
INJURY.
to Safety Valve installation and operation.
Jacket
WARNING Kettle
Model Capacity
AVOID ANY EXPOSURE TO THE STEAM Capacity
(Approx)
BLOWING OUT OF THE SAFETY VALVE.
AH-20 75.7 Liters 17 Liters
AH-40 151.4 Liters 26.5 Liters
AH-60 227.1 Liters 35.9 Liters
AH-80 302.8 Liters 43.5 Liters
10
OM/SM-AH-CE
b. Hang a strip of pH test paper on the rim of c. Replace in reverse order.
the container, with about 3 cm of the strip
extending below the surface of the water. Ensure the low water level control is correctly
oriented when repositioned.
c. Measure the water treatment compound you
will be using. (One way is to add the 3.8 Removal of Gas Control Valve - (Turn the
compound to the water from a small gas and electricity mains off)
measuring cup).
a. Remove control panel (Paragraph 3.5)
d. Stir the water continuously, while you slowly
add water treatment compound, until the b. Disconnect electrical leads from control
water reaches a pH between 10.5 and 11.5. valve.
Judge the pH by frequently comparing the
color of the test strip with the color chart c. Undo fittings on each side of control valve.
provided in the pH test kit.
d. Remove mounting screws from valve.
e. Record the exact amounts of water and
treatment compound used. These amounts e. Remove control valve from control cabinet.
may be used again, if the same sources of
water and compound are employed to refill f. Replace in reverse order.
the jacket in the future. However, it is
advisable to check the pH every time water 3.9 Removal of ON/OFF Switch and Reset
is prepared for the jacket. Button - (Turn the gas and electricity
b. Remove panel
c. Remove retaining screws securing spark b. Disconnect electrical leads from the On/Off
ignition module. switch or reset button.
d. Withdraw spark ignition module from c. Undo and remove retaining collar which
supporting bracket. secures the On/Off switch to the outer
surface of the control cabinet, and the reset
e. Replace in reverse order. button to its inner surface.
3.7 Removal of Low Water Level Control d. Withdraw the On/Off switch or the reset
(Turn the gas and electricity mains off) button as required.
11
OM/SM-AH-CE
3.10 Removal of Neons - (Turn the gas
and electricity mains off)
d. Remove thermostat control knob and b. Disconnect the electrical leads from the
disconnect electrical leads. pressure switch.
e. Remove the two mounting screws that c. Tilt the kettle slightly to move the water in
secure the thermostat to the control the jacket away from the pressure switch
cabinet. pipe fitting.
f. Replace in reverse order. Ensure that an d. Remove and withdraw the pressure switch
adequate sealant is used to seal the from the fitting.
thermostat Phial Boss.
e. Replace in reverse order.
Always refer to wiring diagram when c. Tilt the kettle slightly to move the water in
reconnecting electrical leads. (See Page 23). the jacket away from the sensor coupling on
the jacket
12
OM/SM-AH-CE
d. Remove the low water sensor from the g. Once the burners ignite, ensure that the
jacket. sparking sequence stops and the burners
remain lit.
e. Replace in reverse order.
h. If the burners do not light, or ignite but do
f. Ensure a suitable sealant is used to seal the not remain lit, then adjustment to the
low water level sensor coupling. sparking or sensing electrode is required.
g. Once the low water level sensor is in place, 3.16 Removal of Pressure Gauge - (Turn
check the jacket water level. See Paragraph the gas and electricity mains off)
3.3, Jacket Fillings.
a. Remove control panel (Paragraph 3.5).
3.14 Removal of Burners - (Turn the gas
and electricity mains off) b. Using the correctly sized spanner remove
the pressure gauge from the top of the sight
a. Undo union on gas pipe to burner manifold. glass.
b. Remove the two retaining nuts securing the c. Replace with new pressure gauge ensuring
burner manifold to the combustion chamber. that an adequate sealing compound is used.
c. Carefully support the weight of the burner d. Once the pressure gauge has been
manifold and lower the assembly to a safe replaced, the kettle jacket will need to be
position. vented. See Paragraph 3.2, Jacket
Vacuum.
d. The burner is accessible and the orifice can
be changed as required. 3.17 Removal of Sight Glass - (Turn the
gas and electricity mains off)
e. Replace in reverse order.
a. Remove control panel (Paragraph 3.5).
Always check for gas soundness when any part
of the gas circuit has been disturbed. b. Remove sight glass protection bars.
3.15 Removal of Pilot Assembly c. Undo top and bottom compression fittings.
(Spark/Sensing Electrodes) - (Turn
the gas and electricity mains off) d. Allow the water in the sight glass to drain.
a. Undo the compression fitting on the pilot e. Remove the sight glass.
line attached to the burner.
f. Replace in reverse order.
b. Remove the two retaining screws securing
the spark electrode/pilot bracket on the g. Once the sight glass has been replaced,
burner. the lost jacket water needs to be replaced.
See Paragraph 3.3. Jacket Filling.
c. Withdraw the pilot assembly from the burner
chamber. The pilot orifice can now be 3.18 Removal of Safety Valve - (Turn the
changed as required gas and electricity mains off)
d. Disconnect the high temperature lead wire See detailed Instructions on Page 8 pertaining
connection to the sparking electrode or the to Safety Valve installation and operation.
sensing electrode as required.
a. Remove the elbow from the safety valve.
e. Replace in reverse order.
b. Remove the safety valve from kettle jacket
f. Ensure that there is an adequate spark at pipework.
the sparking electrode and that the burners
light smoothly and without delay. c. Replace in reverse order
13
OM/SM-AH-CE
d. Ensure an adequate sealing compound is d. Once the fill valve has been replaced the
used to seal the safety valve. jacket will need to be vented. See Section
3.2 Jacket Vacuum.
e) Once the safety valve has been replaced
the jacket will need to be vented. See 3.20 Fuse Replacement - (Turn the gas
Paragraph 3.2 Jacket Vacuum. and electricity mains off)
3.19 Removal of Filling Valve - (Turn the a. Remove control panel (Paragraph 3.5).
gas and electricity mains off)
b. Remove fuse from vertical fuse holder.
a. Remove filling valve from kettle jacket
pipework. c. Replace fuse (identical to fuse removed
14
OM/SM-AH-CE
4. Troubleshooting
Your Groen kettle is designed to operate smoothly and efficiently if properly maintained. However, the
following are checks to make in the event of a problem. Wiring diagrams are inside the service panel.
USE OF ANY REPLACEMENT PARTS OTHER THAN THOSE SUPPLIED BY GROEN OR THEIR
AUTHORIZED DISTRIBUTORS CAN CAUSE INJURY TO THE OPERATOR AND DAMAGE TO THE
EQUIPMENT AND WILL VOID ALL WARRANTIES.
15
OM/SM-AH-CE
SYMPTOM WHO WHAT TO CHECK
Pilot lights, but main burner will not Auth a. Sensor cable, to make certain that there are secure
come on, the spark stays on. Service attachments to terminal “13" and the sensor.Y
Rep Only b. Sensor ceramic for cracks.Y
c. That cable is not grounded out. If it is, correct the
ground.Y
d. Sensor cable for continuity and condition of
insulation.Y
e. (1) Check the gas pressure.Y
(2) Clean the pilot Assembly.Y
(3) Tighten mechanical and electrical connections.Y
16
OM/SM-AH-CE
5. User Instructions
Regulations and Safety Precautions
5.1
Equipment Description
5.1.1 General The kettle is charged at the factory with treated,
distilled water. The steam source provides kettle
Groen AH models are stainless steel, steam- temperatures of 65° C to 134° C. Controls for the
jacketed, floor mounted, stationary kettles with a unit include a thermostat, pressure gauge, gauge
self-contained, gas heated steam source. The glass, safety valve, pressure limit control, low
kettle body is welded into one piece and is water cut-off, on/off switch, and a multi-
sheathed in stainless steel and insulated with functional gas control valve.
fiber bat insulation. The interior and exterior are
given a bright buff finish. Service connections are required for gas and
230-V, single phase 50-Hz electricity. See
The unit is ASME shop inspected and registered Paragraph 3.4 - Water Treatment.
with the National Board for working pressure up
to 30 PSIG. Kettle controls are contained in an IMPORTANT
enclosed stainless steel enclosure. The unit rests
on tubular legs with adjustable ball feet. AH Prior to operation, clean out the kettle pan
kettles come standard with stainless steel covers thoroughly using hot water and detergent.
and two inch (five cm) sanitary tangent draw-off Rinse out and dry completely.
valve.
17
OM/SM-AH-CE
The gas burners are protected by an
electronic flame failure device which
incorporates automatic ignition of the
burners and instant shut-off of the gas
supply to the burners should a gas supply
interruption occur.
3. Water filler with swing spout and BEFORE REPLACING ANY PARTS,
DISCONNECT THE UNIT FROM THE
bracket.
ELECTRIC POWER SUPPLY AND CLOSE
THE MAIN GAS COCK. ALLOW FIVE
4. Kettle brush kit.
MINUTES FOR UNBURNED GAS TO VENT.
5.1.2 Operational and Maintenance Safety
TO PREVENT SHOCKS, ALL APPLIANCES
WHETHER GAS OR ELECTRIC, MUST BE
CAUTION EARTHED.
BE SURE ALL OPERATORS READ,
UNDERSTAND AND FOLLOW OPERATING
INSTRUCTIONS, CAUTIONS AND SAFETY
INSTRUCTIONS IN THIS MANUAL.
After the AH Kettle has been installed according 6. Switch the On/Off switch to the "On"
to service and installation instructions, perform position. The "power on" neon will
initial start-up as a test to ensure that the unit is illuminate.
operating correctly. Follow the steps below.
Refer to the picture for identification of AH 7. Turn the thermostat dial to the required
controls and indicators. setting.
1. Remove all literature and packing 8. After 10-15 seconds the burners should
material from the interior and exterior of light. The "burners on" neon will
the unit. illuminate.
2. Make sure gas and electricity supplies 9. In the event the burners do not light, or
are switched on. go out as indicated by the illumination of
the lockout indicating neon, turn the unit
3. Ensure that the kettle is filled with water off. Wait approx 1 minute. Press lockout
before lighting. reset switch and repeat steps (4) to (8).
18
OM/SM-AH-CE
POWER
ON NEON POWER ON
BURNERS HEAT
ON NEON
LOCKOUT
LOCKOUT
INDICATING
NEON
THERMOSTAT
POWER ON
SWITCH
ON
POWER
OFF
LOCKOUT
RESET
SWITCH
RESET
19
OM/SM-AH-CE
5.2.2 To Shut Down Kettle 1. Low-water cutoff relay that will shut off
the gas supply to all burners until the
1. Turn the thermostat dial to the Off water level is corrected.
position.
2. High pressure switch, set to open at
2. Switch the On/Off switch to the Off about 27 PSIG and shut down the
position. burners until jacket pressure is
decreased.
3. For a prolonged shut down follow steps
1 and 2, and turn the gas and electricity 3. Pop safety valve, which will release
supplies off. steam if the jacket pressure exceeds 30
PSIG.
5.2.3 Filling the Kettle
See detailed Instructions on Page 8 pertaining to
Prior to operation of the unit, clean out the kettle Safety Valve installation and operation.
pan thoroughly, using hot water and detergent.
When the kettle reaches the set temperature,
Kettle Capacities: the thermostat switch opens, stopping the signal
to the gas control valve and causing the valve to
Model Capacity shut off all gas flow. When the kettle cools below
the set temperature, the thermostat switch
AH-20 75.7 Liters
closes and starts another heating cycle. On-off
AH-40 151.4 Liters cycling continues and maintains the kettle at the
AH-60 227.1 Liters desired temperature.
AH-80 302.8 Liters
5.2.6 To Empty Kettle
Note that these are maximum capacities. Groen Turn the handle on the tangent draw off valve
recommends that no more than 80% of the anti-clockwise. After approximately 3½ turns the
maximum capacity be used during operation. valve handle can be pulled forward and full flow
achieved. To close the tangent draw off valve,
5.2.4 Users Thermostat push the valve handle inward until the threads
on the valve stem engage. Turn the handle
The thermostat provides automatic control of the clockwise until the valve is closed. Do not over
Kettle Jacket temperature at selected settings to tighten the valve since over-tightening may
a maximum of 134° C. damage the valve seat.
5.2.5 Sequence of Operation
20
OM/SM-AH-CE
5.3.2 Precautions
Before cleaning, shut off the burner by
turning the thermostat dial to "OFF". If water
or cleaning/sanitizing solution will be
sprayed, shut off all electric power to the Use a brush, sponge, cloth, plastic or rubber
unit at a remote switch such as the circuit to remove materials stuck to the surface.
breaker.
plastic or rubber scraper, or plastic wool
along with the detergent solution. To
WARNING minimize the effort required in washing,
KEEP WATER AND SOLUTIONS OUT OF let the detergent solution sit in the kettle
CONTROLS. NEVER SPRAY OR HOSE and soak into the residue, or briefly heat
DOWN THE CONTROL CONSOLE. the detergent solution.
5.3.3 Procedure Do not use any abrasive materials or
metal implement that might scratch the
1. Clean all food contact surfaces as soon surface because scratches make the
as possible after use, preferably while surface hard to clean and provide places
the kettle is still hot. If the unit is in for bacteria to grow. DO NOT use steel
continuous use, thoroughly clean and wool, which may leave particles
sanitize both interior and exterior at imbedded in the surface and cause
least once every 12 hours. eventual corrosion and pitting.
2. Scrape and flush out large amounts of
food residues. Be careful not to scratch
the kettle with metal implements.
21
OM/SM-AH-CE
7. When equipment needs to be sanitized, 5.3.4 Safety Precautions
use a solution equivalent to one that
supplies 200 parts per million available A stopcock will be fitted in the gas pipe
chlorine. Obtain advice on the best supplying the appliance. The user must be
sanitizing agent from your products familiar with its location and operation so that it
supplier. Follow the supplier’s may be turned off in an emergency. If there is a
instructions and apply the agent after the smell of gas, turn off the gas, ventilate the area
unit has been cleaned and drained. and call the gas supplier. Do not search for gas
Thoroughly rinse off the sanitizing agent. leaks with naked flames.
22
OM/SM-AH-CE
23
OM/SM-AH-CE
Parts Lists
24
OM/SM-AH-CE
Parts Lists
Key Description Part No. Key Description Part No.
7 Foot, Adjustable Bullet 013275 43 Switch Push Button (momentary) 122003
9 Bracket Burner Support, AH/1-60, -80 000388 44 Thermostat 012313
9 Bracket Burner Support, AH/1-20, -40 000336 45 Thermostat Adapter (shaft bushing) 107172
10 Bracket Burner Head AH/1-60, -80 000389 46 Screw, Rnd Hd slotted 8-32 x 3/8 lg 009697
10 Bracket Burner Head AH/1-20, -40 000337 47 Knob, Thermostat 122000
11* Burner Assy. (Natural G20) (80 60) 117730A 48 Electrical Panel Assembly 117732
11* Burner Assy. (Natural G20) (40) 117795A 50 Label, Wiring Diagram 113077
11* Burner Assy. (Natural G20) (20) 117731A Wire Harness ** 117727
11* Burner Assy. (Natural G25) (80 60) 117730C 54 Water Level Electrode 074665
11* Burner Assy. (Natural G25) (40) 117795C 56 Boot Electrode 010390
11* Burner Assy. (Natural G25) (20) 117731C 57 Pressure Switch, High Limit 108559
11* Burner Assy. (Propane G31) (80, 60) 117730B 58 TDO Kit replacement parts 100573
11* Burner Assy. (Propane G31) (40) 117795B 58a Valve Stem 009048
11* Burner Assy. (Propane G31) (20) 117731B 58b Bonnet 009047
11* Burner Injector (Natural G20) (80 60) 000399 58c O-Ring 009034
11* Burner Injector (Natural G20) (40) 000280 58d Hex Nut 009354
11* Burner Injector (Natural G20) (20) 000480 58e Handle 009029
11* Burner Injector (Natural G25) (80 60) 127386 58f Wing Nut 009028
11* Burner Injector (Natural G25) (40) 127385 59 Bracket, Faucet Mounting 009054
11* Burner Injector (Natural G25) (20) 127384 61 Data Plate, CE Mark Kettles 114504
11* Burner Injector (PropaneG31) (80 60) 000403 62 Nameplate, Groen, Large 055450
11* Burner Injector (Propane G31) (40) 000281 68 Cover Assy w/Power Aid AH/1-80** 047694
11* Burner Injector (Propane G31) (20) 000281 68 Cover Assy w/Power Aid AH/1-60** 049884
13 Radiation Shield Assy, AH/1-60, -80 000445 68 Cover Assy w/Power Aid AH/1-40** 067417
13 Radiation Shield Assy, AH/1-20, -40 000448 68 Cover Assy w/Power Aid AH/1-20** 047695
17 Cover Panel, AH/1-80 117721 Users Manual** 122039
17 Cover Panel, AH/1-60 117720 71 Assembly, Equipotential Terminal 122021
17 Cover Panel, AH/1-40 117719 73 Wire Assembly, Supplementary 122013
17 Cover Panel, AH/1-20 117718 74 Wire Assembly, Flame Rod 122034
21 Insulator, Pilot Burner Access 008201 79 Adapter 1/2” BSPT (M) x1/2"NPT (F) 116392
22 Door, Pilot Burner Access 004035 80 Pilot Ignition Controller 113060
23 Hinge, Pilot Door 004114 81 Liquid Level Control Relay 117737
32 Safety Valve & Water Fill Assembly 097010 82 Liquid Level Control Relay Base 117738
33 Plate with Chain Assembly 008332 83 Terminal Block 003119
34 Water Gauge Fitting 004071 84 Fuse (Three Amp) 079965
37 Sight tube, 5/8” Diameter x 4-3/4” lg 008742 85 Fuse Block 077854
38 Pressure Gauge 2-1/2“dia (dual scale) 084208 86 Pilot Burner & Orifice Assy (Natural) 117704
39 Overlay, Panel 117716+ 87 Pilot Burner & Orifice Assy (Propane) 117705
40 Switch, Toggle, DPST 122004 88 Pilot Burner Mounting Bracket 004425
41 Light Indicator Red, 240V 116381 89 Water Treatment Kit 110324
42 Light Indicator, Amber 240V 116382
*NOTE: See Para 1.10 (Page 6) for permissible conversions.
** Not Shown
25
OM/SM-AH-CE
Parts Lists
Keyed to Parts Listing on Page 29
16
11
30E
13 1
6
10
5
7
2
18
4 1
12
14
26
OM/SM-AH-CE
Parts List
Keyed to Parts Listing on Page 29
16
13
11
B
30E
12
18
8
1 1
C 5
10
5
7
2
14
27
OM/SM-AH-CE
Parts List
Keyed to Parts Listing on Page 29
11
11
5
10
17
3 16
14
15 B
30E
12
7
8
13
28
OM/SM-AH-CE
Parts List
29
OM/SM-AH-CE
Service Log
The Groen Steam Jacketed Kettle you have just purchased has been handcrafted from the finest materials,
meticulously inspected, and carefully tested to ensure that you receive the best possible product. With
reasonable care and periodic maintenance, it will provide years of faithful service. It is recommended that
you establish a timetable for periodic maintenance with an Authorized Groen Service Agency. Space has
been provided in the manual for a Maintenance & Service Log. Keep it up-to-date and on file.
30
Limited Warranty To Commercial Purchasers*
(for Areas Outside of the U.S. and Canada)
Groen Foodservice Equipment ("Groen Equipment") has been skillfully manufactured, carefully inspected
and packaged to meet rigid standards of excellence. Groen warrants its Equipment to be free from defects
in material and workmanship for ( 12) twelve months from date of installation or ( 18) eighteen months from
date of shipment with the following conditions and subject to the following limitations.
I. This parts warranty is limited to Groen Equipment sold to the original commercial purchaser/users
(but not original equipment manufacturers), at its original place of installation, in areas outside the
U.S. and Canada.
II. Damage during shipment is to be reported to the carrier, is not covered under this warranty, and is
the sole responsibility of the purchaser/user.
III. Groen, or an authorized service representative, will repair or replace parts, at Groen's sole election,
for any Groen Equipment, including but not limited to, draw-off valves, safety valves, gas and
electric components, found to be defective during the warranty period.
IV. This warranty does not cover boiler maintenance, calibration, or periodic adjustments as specified in
operating instructions or manuals, and consumable parts such as scraper blades, gaskets, packing,
etc., or labor costs incurred for removal of adjacent equipment or objects to gain access to Groen
Equipment. This warranty does not cover defects caused by improper installation, abuse, careless
operation, or improper maintenance of equipment. This warranty does not cover damage caused by
poor water quality or improper boiler maintenance.
VI. Groen Equipment is for commercial use only. If sold as a component of another (O.E.M.)
manufacturer's equipment or if used as a consumer product, such Equipment is sold AS IS and
without any warranty.