HVAC Ventilation
HVAC Ventilation
HVAC Ventilation
1-31-07
Bill Greco
The following concerns Pharmaceutical production areas, research areas and other areas where
annoying or dangerous vapors can be released. Many times vapors are not controlled by special ventilation
apparatus such as hoods or carbon filtration. Vapors can be caused by laboratory accidents, use of cleaning
solvents applied outside of the influence of the exhaust system or by special adhoc procedures conjured up
by jury rigged processes. The primary general HVAC system often becomes the last line of defense to confine and
dilute these vapors which have escaped into a conditioned space. A primary general HVAC system is
meant to serve as supply and exhaust of air to control comfort or specifically produce a controlled environment
within regulated room classification requirements. If vapors are re-circulated and confined within a
primary general HVAC system, only outside air will dilute the unwanted vapor. Unfortunately opening
a window in most cases is not a possibility.
A prime function of many substances especially solvents is to evaporate into the local atmosphere
leaving behind a physically or chemically transformed material formerly associated with it. Evaporation
of many substances cause fumes, gases, vapors and / or mists. It is nearly always possible to
estimate the rate or use of total liquid composition, to determine the rate of evaporation.
This makes it especially simple, to handle vapor ventilation problems on a quantitative basis with relation to time.
The following could be used to calculate any concentration of vapor or could be representative of the
differential of a mixture of some substance being added over a time period in a tank of fluid through which
fresh fluid is being added and continuously removed. The procedure can be applied to any case where air is
initially charged with contaminant and it is desired to estimate the conditions in the space in relation to time.
Assume evaporation of one pound of turpentine C10 H16 which has a molecular weight of 136.23
that has evaporated over a period of one hour. The total volume of vapor per hour is :
2.839 cuft/ hour or 0.047 cuft/min or a generation rate (G) of 0.047 cfm
Page 2 of 4
1-31-07
Bill Greco
Vapor Dilution with respect to Outside Air over a period of Time
An increase in the quantity of vapor in the space during the time interval dt, is equal to the
rate of vapor being added to the space minus the removal rate of vapor leaving the space.
The relation between the ratio of concentration of vapor c and time t can be developed
from the equation:
where:
Q = Ventilation Rate, cfm (air exhausted)
G = Vapor generation rate, cfm
c = Ratio of substance vapor to air in parts per million expressed as a fraction at time t
c_initial = Initial ratio of substance vapor parts per million at time t=0
P = Cubic Displacement of the space
c t
which becomes:
solving for t =
and:
Simplifying:
Changing signs:
Page 3 of 4
1-31-07
Bill Greco
Vapor Dilution with respect to Outside Air over a period of Time
:
Multiply by P =
Divide by 0.435Q =
Rearranging =
Example-1:
Assume a research lab 30 feets long x 15 feet wide with a 10 foot high ceiling.
A repetitive procedure is being performed in which a lab technician is using 1 pound of acetone on
a lab bench for 30 minutes during each process, the procedure must be conducted outside of the
labs hood area. The primary general HVAC system as shown in Figure-1 supplies conditioned air
to the space, 170 cfm is being exhausted from the room. The room temperature is controlled
to 700 F. The procedure is started with 0 parts per million (ppm) in the room.
How long will the procedure be allowed to continue prior to reaching acetone’s threshold level
of 1,000 parts per million ?
If the process is stopped at 1,000 ppm, how long will it take the room air in example-1 to
dilute and reach 500 ppm ?
Refernce:
Hemeon, W.C.L. Plant and Process Ventilation Second Edition pp 228-232