E380
E380
E380
Manual
SUNFARE380
PREFACE
Thank you very much for choosing E380 series of general purpose inverter. This manual provides guidance of using the inverter safely and carefully, containing introduction of installation, wiring, parameters list, routine maintenance, operating rules and cautions, etc. In order to make good use of the inverter properly and safely, please read this manual thoroughly before using. It may lead to abnormal operation and failure, reduce using life, even damage the equipment and cause personal injury if you use it wrongly. This manual is attachment together with the inverter. Please keep it well and it would be available to engineering and installation personnel, repairing and maintaining during the product functioning period. SUNFAR has the right to modify and ameliorate products, data and dimensions without notice, so this manual is updated and all the contents in this manual are subject to change without any notice.
SUNFARE380
Table of Contents
1 INTRODUCTION
6 5 6 1.1 Model explanation 5 5 1.2 Appearance description 6
7 1.3 Model of inverter 8 9 8 1.4 Specifications 10 2 INSTALLATION GUIDELINES 11 2.1 Environmental requirements 11 10 10 2.2 Disassembly and assembly of the panel11
11 2.3 Disassembly and assembly of the cover board 12 13 12 2.4 Dimension of inverter 15 3 WIRING PROCEDURE16 15 3.1 Precautions 16 16 3.2 Wiring of external components 15 18 17 19 3.4 Terminal of main circuit 18 3.3 Basic wiring
19 3.5 Terminal of Control circuit 20 22 21 OPERATIONS OF INVERTER AND SIMPLE RUNNING 21 4.1 Operation panel 22 23 4.2 Basic function of panel and methods of operation 22 25 4.3 List of state monitor parameter 26 27 4.4 Simple operation 26
28 27 42 37
37 6.1 Basic operation parameter unit 42 47 6.2 Primary application of parameter unit 41 45 6.3 Analog I/O parameter unit 50 53 6.4 Digital O/I parameter unit 48 51 6.5 Auxiliary running parameter unit 57 62 6.6 Multi-speed running parameter unit 56 58 6.7 Advanced running parameter unit 65 67 61 6.8 Wobble freq. running parameter unit 69 62 6.9 PID control parameter unit 71 6.10 Communication function parameter units 65
73 66 6.11 Special function parameter unit 75 69 FAULT DIAGNOSIS AND COUNTERMEASURES 69 7.1 Protective functions and countermeasures76 76 70 7.2 Fault record inquiry 70 7.3 Reset 77 77
E380 Serials of General Purpose Inverter Operation manual
SUNFARE380
8 MAINTENANCE 71
8.1 Daily Maintenance 71 8.2 Damageable parts maintenance 72 78 8.3 Storage 72 78 8.4 After sale services 72 78
9 USAGE EXAMPLE 73 79
9.1 Panel on-off control, Panel potentiometer setting frequency 73 79 9.2 External on-off control mode, external voltage setting frequency73 79 9.3 Multi-speed running, external on-off control mode 74 80 9.4 Panel on-off controlPanel potentiometer setting frequency and linkage control with inverters . 74 80
SUNFARE380
PRECAUTIONS
In order to use the inverter properly and safely, please read this manual carefully before using. And you should follow the requirements of this manual to move, install, run, operate and repair the inverter.
1. Opening
Please check any damage that may have occurred during transportation. Please check whether the nameplate data of inverter is in accordance with your order, if anything wrong, please contact supplier immediately.
Our product is manufactured, packed and transported in the strict quality system. But in case there is any error, please contact with our company or local agent, we will solve the problem as quickly as possible.
Fig-1 Nameplate
2. Safety regulations
There are four kinds of symbols being related with cautions as follows: Danger: If user does not operate according to requirements, it will lead to death, grievous bodily harm or severe property loss.
Warning: If user does not operate according to requirements, it will lead to injury or damage of inverter.
This symbol will hint some items that need to be noticed in operation.
SUNFARE380
2.1 Installing
2.1.1. 2.1.2. 2.1.3. Do not put the inverter on the combustible material. E380 series inverter cant install in the explosive ambient. Do not drop other material into the inverter. It is forbidden to disassemble and refit the inverter.
2.2 Wiring
2.2.1. 2.2.2. 2.2.3. 2.2.4. 2.2.5. It must be operated by professional worker when wiring. Please be sure to turn off the power supply at least 10 min before wiring. Inverter and motor must be grounded correctly. Be sure to wire or inspect the inverter after power-off at least10 minutes. Electron components are sensitive about static electricity, so do not drop other material in inverter or touch the main circuit. It is forbidden to connect an AC power supply with the U, V and W output terminals directly
2.3 Maintenance
1. 2. Do not touch the radiator after power-off at least 10 minutes. The earth terminal of inverter must be connected to ground reliably.
3. Attention Notes:
3.1. 3.2. 3.3. 3.4. Be sure to install the inverter in a well-ventilated ambient. The temperature at variable-frequency will be higher than at line-frequency, which is normal phenomenon. The ordinary motor cannot run in the low speed for a long time, so user should select the special motor for inverter or reduce the motor load under the low speed. When the altitude is over 1000m, the inverter will be valid to decrease the rated current, and the rated current will decrease 10% when the attitude is increased 1500m.
Be sure not to connect the output terminals of inverter with the filter capacitors and other surge absorbers.
4 Dispose:
When you dispose inverter and its parts, please pay attention to: Capacitor: The capacitors in inverter may explode when they are burned. Plastic: Poisonous gas may be generated when the front panel is burned, please pay attention to the waste gas when the plastic parts are burned. Method: Please dispose inverter as industry rubbish.
SUNFARE380
1.
1.1 Model explanation
INTRODUCTION
E380 4
Product E380 General purpose drive Sensorless vector low-power drive
0150
Applied motor capacityKW 0015 0022 0037 0055 0075 0110 0150 0185 0220 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22
C300
. . .
. . .
Operation panel
Upper cover
Mounting hole
SUNFARE380
Operation panel
Upper cover
WARNING
1.Refer to the instruction manual before installation and operation. 2.Do not connect AC power to output terminals UVW. 3.Do not remove any cover while applying power and at least 10min. after disconnecting power. 4.Securely ground(earth) the equipment.
Lower cover
Operation panel
WARNING
1.Refer to the instruction manual before installation and operation. 2.Do not connect AC power to output terminals UVW. 3.Do not remove any cover while applying power and at least 10min. after disconnecting power. 4.Securely ground(earth) the equipment.
Lower cover
Main terminal
R S T
POWER
(+) (-)
U V W
MOTOR
Operation panel
WARNING
1.Refer to the instruction manual before installation and operation. 2.Do not connect AC power to output terminals UVW. 3.Do not remove any cover while applying power and at least 10min. after disconnecting power. 4.Securely ground(earth) the equipment.
Lower Cover
R S T
POWER
(+) (-)
U V W
MOTOR
RUN
Hz
Operation panel
ES C
JO G
<<
FW D
SE T
R EV
UP
D OW N
ST OP
Right door
Left door
WARNING
1.Refer to the instruction manual before installation and operation. 2.Do not connect AC power to output terminals UVW. 3.Do not remove any cover while applying power and at least 10min . after disconnecting power. 4.Securely ground(ea rth) the equipment.
SUNFARE380
(-)
MOTOR
Model
E380-2S0015 E380-2S0022 E380-2S0037 E380-2T0015 E380-2T0022 E380-2T0037 E380-2T0055 E380-2T0075 E380-2T0110 E380-2T0150 E380-2T0185 E380-2T0220 E380-2T0300 E380-2T0370 E380-2T0450 E380-2T0550 E380-2T0750 E380-2T0900 E380-2T1100 E380-4T0015 E380-4T0022 E380-4T0037 E380-4T0055 E380-4T0075 E380-4T0110 E380-4T0150 E380-4T0185 E380-4T0220
Rated Power KVA 2.9 3.8 5.7 2.9 3.8 5.7 9.5 12.6 17.5 22.9 28.6 32.4 41.9 51.5 64.8 78.1 101 122 145 2.4 3.6 5.6 8.6 11 16.5 21.7 25.7 29.6
Rated output currentA 7.5 10 15 7.5 10 15 25 33 46 60 75 85 110 135 170 205 265 320 380 3.7 5.5 8.5 13 17 25 33 39 45
Applied Motor Power (KW) 1.5 2.2 3.7 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90 110 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22
10
SUNFARE380
39.5 49.4 60 73.7 98.7 116 138 171 204 237 253 276 313 352 395 428 480 60 75 91 112 150 176 210 260 310 360 385 420 475 535 600 650 730 30 37 45 55 75 90 110 132 160 185 200 220 250 280 315 350 400 49.4 60 73.7 98.7 116 138 171 204 237 253 276 313 352 395 424 480 513 75 91 112 150 176 210 260 310 360 385 420 475 535 600 645 730 800 37 45 55 75 90 110 132 160 185 200 220 250 280 315 350 400 450
E380-4T0300 E380-4T0370 E380-4T0450 E380-4T0550 E380-4T0750 E380-4T0900 E380-4T1100 E380-4T1320 E380-4T1600 E380-4T1850 E380-4T2000 E380-4T2200 E380-4T2500 E380-4T2800 E380-4T3150 E380-4T3500 E380-4T4000
1.4 Specifications
Three-voltage4T**** 380V 50/60Hz Three-voltage4T**** 300V460V Three-voltage0380 V 0 Hz 600Hz 110% rated current for long-term150% rated current for 1min 180% rated current for 2s VVVF control 0.1% of maximum output freq. 0.01Hz Within 0.2% of maximum output freq. Within 0.01% of setting freq. Reference freq. can be discretional set between 5 and 300Hz. And V/F curve with multimode can be discretional set. There are also three curves provided, constant torque curve, Dec torque curve 1 and Dec torque curve 2. Manual torque boost can be set between 0 and 20 percent Automatic torque boost can be set according to output current. It will determine automatically the current and voltage of stator of motor, which will be controlled within the allowable range. It is especial for the users with lower-power supply and voltage fluctuate frequently, even the voltage is lower than Permissible voltage, and the system will maintain the longest running time. Three-voltage2T**** 220V 50/60Hz Three-voltage4T**** 170V270V Single-voltage0220 V Single-voltage2S**** 220V 50/60Hz Three-voltage4T**** 170V270V
Rated voltage and freq. Input Permissible voltage fluctuation Voltage Output Frequency Over-loading Endurance Control System Freq. Control Analog Input Digital Input Analog Input Digital Input
External pulse 0.1% of maximum freq. Control V/F Curve Characteristics (Voltage-Frequency characteristics) Torque boost Automatic current/voltage Limiting Under voltage inhibit feature In running
SUNFARE380
Multi-speed selection And Wobble freq. running Embedded PID control
11
Up to 8 stages of programmable multi-speed control, 6 kinds of running mode and 15 stages of multi-speed. Wobble freq. function is composed of preset freq., center freq. adjusted and save state and restart when inverter just had power off. Optional inner bipolar PID controller, 5-pump voltage regulation control system (supply water or gas), with sleep/ wake up, a typical energy-saving function.
Through RS485 communication, master inverter is the role of synchronous controller linkage controlling proportion presupposition and trimming, slave inverter running RS485 communication and frequency superposition and trimming internal. In system of multi-gearing series use, synchronization control have load self-equalized function, all gearing load proportion according to pre-set to keep consistent strictly. Analog input Freq. Setting Digital input Output Signal Typical Functions Automatic energy saving running OC output Analog output Pulse input DC voltage 05V010VDC current 020mA Its amplitude value is between 5 and 30Vand its freq. is within 50.0KHz It can set by operation panel RS485 UP/DW terminal also can set multiple combinations with analogue input. Two OC output, As many as 16 species of choice, fault relay output similarly optional. Two 0~10V voltage or 0~20 mA current signal, Upper and lower limits can be set separately. The output current timely adjust output voltage and slip compensation, the motor has been working at the highest efficiency. According to the status of the scene automatic energy saving operation can set the depth. In particular, it suitable for ball-mill and other energy-saving field of micro-adjustment frequency. Three ways for selection: Dynamic voltage regulationStatic Voltage regulation No Voltage regulation, to get the most stable operating result 0.1Sec6000min Continuous set, S type linear mode for selection
Regenerative 75% above braking DC braking Start and stop can be select respectivelyaction freq. is from 0 to 50.0Hz To achieve Smoothing restart and instantaneous-stop restart function of running motor. Embedded one timer and one counter, which will help the systems integration. Upper and Lower frequency setting frequency skip operation Reversal operating restrictionSlip frequency compensationautomatic stable voltage operation RS485 communicationfrequency increasing/decreasing control, fault recovery operation.
Operation functions
Display
Running Output Freq.Output currentOutput voltageMotor rotate speedSetting Freq. Model temperaturePID settingPID feedbackAnalog I/O status Operation panel Last running parameters record: Last six fault recordOutput frequency of last display Alarm content fault tripSetting frequencyOutput currentOutput voltageDC voltageModel Temperature Over currentover voltage, under current, under voltageelectronic thermal overheating, extreme high temperatureshort circuit Phase-lacking of output internal memory fault -10C to +50C Under 90%non-condensing Indoorsno inflammable gasses or dust Lower than 1000m IP20 Fans cooling Hanging
Protection / Warning functions Ambient temperature Environmental Ambient humidity Conditions Ambient environment Altitude Configuration Enclosure rating Cooling method Installation
12
SUNFARE380
2. INSTALLATION GUIDELINES
2.1 Environmental requirements:
1. 2. 3. 4. 5. 6. 7. Be sure to install the inverter in a well-ventilated room. Ambient temperature is from -10 to 40. If the temperature is 40 to 50, please take out the lower cover to cool. Please avoid putting the inverter in a high temperature and moist location. The humidity is less than 90% and non-condensing. Keep away from combustible, explosive material and caustic gas or liquid. No dust, floating fiber and metal particles The inverter must be installed in a firm and no vibration location. The installation plane should be solid and not vibrant.
If users demand any special installation, please contract us firstly. E380 series inverter is hanging model, so it should be in vertical way. In order to ensure the air circulation around the inverter to aid in cooling, there should be enough space around the inverter shown as Fig. 2-1-A. Add the air deflector when apply the up-down installation shown as Fig. 2-1-B.
Fan ventilation
Above 120mm
E3 80
Inverter
Above 50mm
Above 50mm
WARNING
1.Refer to the instruction manual before installation and operation. 2.Do not connect AC power to output terminals UVW. 3.Do not remove any cover while applying power and at least 10min. after disconnecting power. 4.Securely ground(earth) the equipment.
Inverter
Above 120mm
Assembly
Aim the fixed hook to spring clip at bottom of operation panel, then press the fixed spring backward. Then push inward to the certain place. Shown as Fig. 2-2.
SUNFARE380
13
Panel base
Spring cilp
Disassembly
Put the finger into the portable hole, pull upward to move the cover form the shell, then pull downward, which will remove the cover board.
Assembly Lift the bottom of cover up to about 15, inserting the Fixed hook into the hold down groove, then press the cover down to hear a sound of Click, which means the cover board has already been mounted and shown as Fig. 2-3-A.
Fixed hook
Hole
Portable hole
2.3.2 Disassembly and assembly of lower cover board It is fit forE380-4T0110E380-4T0750/ E380-2T0055E380-2T0450
Disassembly
1. 2. Take two screws at bottom of lower cover board. Move the lower cover board downward.
14
SUNFARE380
Assembly
1. 2. 3. Put the lower cover board parallel with the interval. Move the lower cover board upward. Screw the bottom of lower cover board.
80 E3
H H1
H1
WARNING
1.Refer to the instruction manual before installation and operation. 2.Do not connect AC power to output terminals UVW. 3.Do not remove any cover while applying power and at least 10min. after disconnecting power. 4.Securely ground(earth) the equipment.
SUNFARE380
15
H H1
!
WARNING
1.Refer to the instruction manual before installation and operation. 2.Do not connect AC power to output terminals UVW. 3.Do not remove any cover while applying power and at least 10min. after disconnecting power. 4.Securely ground(earth) the equipment.
E380
H H1
WARNING
1.Refer to the instru ction manual b efore installation an d operation. 2.Do not connect AC power to output terminals UVW. 3.Do not remove any cover while applying power an d at least 10min . after disconnecting power. 4.S ecurely ground(earth) the equipment.
16
SUNFARE380
Screw
M5 M6 M6 M8 M8 M8 M8 M10 M10
580
730
1103
1130
355
M10
SUNFARE380
17
3. WIRING PROCEDURE
3.1 Precautions
3.1.1. 3.1.2. 3.1.3. Installing a middle breaker between inverter and power supply in order to avoid enlarging the accident. Reducing the electromagnetic interference (EMI), please connect surge absorber to the coils of electromagnetic contactors, relays, etc. Frequency setting terminals (VC1, VC2, CC and PLS), Instrument circuit (AO1 and AO2), etc., 2 these analog signal wires should be over 0.3mm shield wire. Shield layer is connected with earth terminal GND and the length of wire should be than 30m. Wire of relay input and output circuit(X1 ~ X6 OC1 OC2 FWD REV RST) must be selected over 2 0.75mm shield wire. Shield layer should be connected to earth terminal CM and the length of wire should be shorter than 50m. Separating the main circuit wire from the signal/process circuit wiringparallelled wiring should be at a distance of over 10cm and crossed wiring should be vertical with each other. The wire must be less than 30m between motor and inverter. When the length of wire is over 30m, the carrier frequency of inverter should be reduced properly. All of leading wires should be tightened with the terminal adequately to ensure well-contact. The leading wire of main circuit had better use the cable or cuprum tier, and wiring had better be operated after the lug plate of corresponding sections cold pressing or welding. Compressive resistance of all the wire should match with the voltage grade of inverter.
It is not allowed that UVW of inverter connect with the surge absorber capacitor or other surge absorber equipment and shown as following Fig..
3.1.4.
3.1.8.
U Inverter V W
Motor
RC absorb device
AC Power P+ R / L1
RU N Hz A V
PB
E3 80
U V W
S / L2 T
!
ESC
JOG
<<
F WD
SET
REV
UP
DOWN
STO P
W A RN IN G
1.R efer to th e ins tructio n m anu rl b efo re ins talla tio n and o per atio n. 2.D o n ot con nect A C po w er to ou tpu t ter minals U V W. 3.D o n ot r emov e an y cov er w h ile ap ply in g po w er and at leas t 10 min. after dis co nnetin g po w er. 4.S ecur ely gro un d( earth) th e eq uip men t.
Circuit Breaker
AC electric Reactor
E380
Motor
18
SUNFARE380
Power Supply It is according to the rated input power specifications in manual Air-break switch 1. When the inverter is in maintenance or leave-unused, the air-break switch should isolate the inverter from power supply. 2. Input side of inverter takes place the fault of short-circuits or low-voltage, the air-break would take the protection. Contactor Control the power-on or power-off of inverter expediently. AC electric reactor 1. Improve the power factor. 2. Reduce the harmonic wave input for the electric network. 3. Weaken the imbalance effect on 3-phase power voltage. Brake resistor In the situation of regenerative braking, avoiding bringing voltage too highly.
Recommending specification of commanded equipment is shown as following table. Wire spec Applied MotorKW Air-break Model (Main circuit) A
G-load 1.5 2.2 3.7 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 P-load ------------------2.2 3.7 5.5 7.5 11 15 18.5 22 30 mm2 4 6 6 4 4 6 10 10 16 25 25 25 50 50 70 95 95 150 2.5 4 4 6 6 10 10 16 16 E380-2S0015 E380-2S0022 E380-2S0037 E380-2T0015 E380-2T0022 E380-2T0037 E380-2T0055 E380-2T0075 E380-2T0110 E380-2T0150 E380-2T0185 E380-2T0220 E380-2T0300 E380-2T0370 E380-2T0450 E380-2T0550 E380-2T0750 E380-2T0900 E380-4T0015 E380-4T0022 E380-4T0037 E380-4T0055 E380-4T0075 E380-4T0110 E380-4T0150 E380-4T0185 E380-4T0220 20 32 40 20 20 40 63 63 100 160 160 160 200 250 250 400 400 630 16 16 20 32 40 63 63 100 125
SUNFARE380
Applied MotorKW Model E380-4T0300 E380-4T0370 E380-4T0450 E380-4T0550 E380-4T0750 E380-4T0900 E380-4T1100 E380-4T1320 E380-4T1600 E380-4T1850 E380-4T2000 E380-4T2200 E380-4T2500 E380-4T2800 E380-4T3150 E380-4T3500 E380-4T4000 G-load 30 37 45 55 75 90 110 132 160 185 200 220 250 280 315 350 400 P-load 37 45 55 75 90 110 132 160 185 200 220 250 280 315 350 400 450 Wire spec (Main circuit) mm2 25 25 50 50 70 70 95 95 150 150 185 185 240 240 300 300 400 Air-break A 160 160 200 200 250 315 400 400 630 630 630 800 800 1000 1250 1250 1600 Magnetic contactor A 80 95 115 150 170 225 225 330 330 400 400 500 500 630 630 780 780
19
R S T X1 X2 X3
U V W E Ta Tb Tc P PPB
Motor M
Earth
Fault alarm
X4 X5 X6
CM
OC2 CM
20
SUNFARE380
P+
P-
PB
Earth
3.4.2
P+
P-
PB
Earth
3.4.3
Earth
3-phase power
3.4.4
IV model
P+
P-
Earth
3-phase power
3.4.5
V model
It is fit forE380-4T2200E380-4T2800
E a rth 3 -p h a s e p o w e r
P-
P+
E a rth
D C E le c tr ic R e a c to r
M o to r
B r a k e U n ite
SUNFARE380
21
3.4.6
VI model
It is fit forE380-4T3150E380-4T4000
T h re e P h a se P o w e r In p u t E a rth
P+
P-
E a rth
D C R e a c to r B r a k in g U n it M o to r
E a rth
Function
TA
TB
TC
X2
X4
22
SUNFARE380
FWD Control REV RST CM 24V AO1 Analog Output AO2 GND OC Output PLC output RS485 OC1 OC2 TA TB TC General , TA-TB is connectedTA-Tc is unconnected when TA-TB is unconnected and TA-TC is connectedF3.8 is valid. RS485 interface Grounding terminal FWD control command terminal REV control command terminal Fault reset input terminal Common terminal of control It provides +24V/50mA power and is grounded by CM. PLC voltage signal input terminal1. It is set by F2.13 and allowed to connect with external voltmeter. PLC voltage signal input terminal 2. It is set by F2.14 and allowed to connect with external voltmeter. Common terminal of AM1and AM2 PLC open-circuit collector output is set by F3.6 and F3.7 Those terminals are valid when it connects with CM. And running direction of panel control is controlled by FWD-CM state voltage signal output : 020mA/0~15V. Voltage signal output : 010V/1mA Switch JP2JP3 select voltage or current The maximum load-current is 50mA, while the maximum withstand voltage is 24V. CapacityAC 250V 1A Resistive load
Terminal
Interface ERH
Explanation about JP
JP1 1-2shortedInput +5V/50mA signal 2-3shortedInput +10V/10mA signal JP2 1-2 shortedAO1input voltage signal
VO2
2-3 shortedAO1 input current signal JP3 1-2 shortedAO2 input voltage signal 2-3 shortedAO2 input current signal
CO1
+10V
CO2
SUNFARE380
23
4.1Operation panel
4.1.1 Panel layout
Unit
Auxiliary LED
Main LED
V A
Unit
Hz
Return
Set
Return
ESC
JOG
<<
FWD
Switch Jog
Increasing Decreasing
Stop
Set
SET
REV
FWD REV
Increasing Decreasing
STOP
Stop
Fig.4-1-A
Panel layout
Fig.4-1-B
Function It displays current state and setting parameter. It displays current state and setting parameter. At the beginning of power supply, it displays inverters program version, and it will return normality in 2 second. Small panel layout doesnt have this auxiliary LED. The corresponding unit of current display Operation indicator light. The inverter is running and U, V and W output voltage. FWD key When F0.1 is 0 and press this key, the inverter will running forward to setting frequency according to appointed ACC or DEC curve.
Display
Keypad REV key When F0.1 is 1 and press this key, the inverter will be running backward to setting frequency according to appointed ACC or DEC curve.
24
SUNFARE380
Stop and Reset key When F0.4 is 000#, STOP is valid for panel control. If F0.4 is 001#, STOP is valid for all kinds of control methods. If inverter occur fault, press this key to reset it and return stop mode. If stop key is used together with copy and read-in of internal parameters will be done. Return key Press this key in normal modify state to enter query mode of not normal modify state /modify parameters to check running state. In any state, press this key to return the upper state. This key is used together with to perform Parameter read / backup. Set key This key is used together with Data modify key Keypad It is used to modify the function code and parameter. In state modify mode, if F0.1 is 0, press this key will modify the frequency instruction Jog key. It is valid when the state is only in operation panel control pattern
Shift key. In any state, press key to modify datas state. Press the key to modify the digital bit, the modification bit will be displayed blink. This key is used together with to perform Parameter read / backup.
Panel potentiometer.
This button is used for setting Inverters running freq.. Turning left the
button is to decrease running freq. ,turning right the button is to increase running freq.
This function provides to copy the internal parameter of inverter and saves it permanently. (Only limit to open internal parameter). So user can copy typical settings parameters to operate panel. These parameters dont affect inverter running, and are checked out and modified separately. Press and key simultaneously to enter parameter read / backup. Even if the inverter is running,
reading parameters is also carried though. When parameters are read, 0 is displayed blink from right to left. After parameters backup is finished, the display is normal. In process of parameters backup, it can be cancelled by pressing return the normal monitor state. (2) Parameter copy / write This function provides to copy the backup parameter of inverter and saves to inner storage of inverter. (Only limit to open internal parameter) So user can copy typical settings parameters to operate panel. Those parameters dont affect inverter running, and are checked and modified separately. Please set F6.16 as 1 and stop the inverter before write parameter. After writing, set F6.16 as 0 to prevent invalid parameters saving in inverter. And it had better copy the valid inner parameter to operation panel.
E380 Serials of General Purpose Inverter Operation manual
or
. And press
key to
SUNFARE380
25
Please stop the inverter and then press and key simultaneously to enter parameter copy / write under normal monitor mode. When parameters are writing, 0 is displayed blink from right to left. After parameters copy is finished, the display is normal. In process of parameters copy, it can be cancelled by pressing or . And press key to return the normal monitor state. (3) Modify and check the internal parameter Press key to enter Modify and check internal parameter mode under normal mode with general ways to check and modify data. (4) Modify and check the backup parameter 1 and 2 key simultaneously to enter Modify and check the backup parameter mode. When panel displays function code, F in the fourth place of main LED will be displayed blink, which means current modify and check parameters is backup parameter.
d-0
Return
+
State Parameter Main display: Inquiry d-5 Function code Output current Auxiliary display: 2.3
Parameter Inquiry
Main display:
383
+
Parameter Edit Main display: F0.0 Function code Parameter data Auxiliary display: 0
26
SUNFARE380
45.00
+
Parameter Inquiry Main display: F0.0 Function code Parameter data Auxiliary display: 0
Give up Modify
+
Parameter Inquiry Main display: F0.2 Function code Parameter data
Give up Modify
Parameter Inquiry
Main display:
45.00
+
Parameter Main display: 50.00 Auxiliary display: 2.3 Parameter data Output current
Modify
Parameter Storage
SUNFARE380
27
28
SUNFARE380
R S T
U V W E
Earth
Please wire as the Fig 4-1. Be sure that the wiring is correct and turn the power on, the inverter will display P.oFF and0. Auxiliary LED displays the program version transitorily. Be sure that F0.1 is 0. Please set parameters [F1.3] and [F1.4], according to the nameplate parameters of applied motor. Please press Please press key to start inverter, then the inverter will display 0.0Hz. key to increase input frequency and motor will run.
Observe the motor whether it runs normally or not. If abnormal, please stop running at once and turn off the power, and find out the reason, then restart. Press the key Press the key to decrease the setting frequency. to stop running. Then turn power supply off.
Carrier wave frequency is fixed value between 1.5 and 10 KHz. If motor does not take any load, it will a slight oscillate. So please decrease setting value of F0.16, Or setting Oscillatory inhibiting factor value of FC.11.
SUNFARE380
29
5. PARAMETERS LIST
Symbol description: means that this parameter can not be change during operation. means that this parameter is related to the inverters model.
Function Code F0. 0 Reserved 0Frequency setting by operation panel 1UP/DW Acc and Dec control 2RS485 interface 3Panel potentiometer 4External voltage signal VC10V~5V 5External voltage signal VC20V~10V 6External current signal CC0~20mA 7External pulse signal0.0~50.0KHz 8Combination setting 9External terminals 0.00~ the upper limit frequency The first part of LED(form right to left) 0Setting freq. will save after power down 1Setting freq. will not save after power down The second part of LED 0Setting freq. is to keep when stopping 1Setting freq. will save in F0.2 when stopping 2Setting freq. is clear when stopping The third and fourth part of LED(form right to left) Reserved The first part of LED (form right to left): 0 Panel control 1 External terminals control 2RS485 interface The second part of LEDFunction of key STOP 0It is valid for panel control. 1It is valid for all kinds of control method. The third and fourth part of LED(form right to left)Reserved 0Two-line mode 1 2Three-line mode 1Two-line mode 2 Name Setting range Minimum Manufactur Modify Setting Setting Limit 1 0000
F0. 1
0.01
F0. 3
0000
0000
F0.5
The first part of LED (form right to left): 0Running direction is consistent with setting direction 1Running direction is in contradiction to setting direction The second part of LED 0Prevention REV is valid 1Prevention REV is invalid The third and fourth part of LED(form right to left) External operation channel auxiliary function 0self-starting is forbidden when inverter is just power-on 1self-starting is allowed when inverter is just power-on The fourth part of LED(form right to left) Reserved 0.0 Hz~ [F0.8] [F0.7] ~ 400.00Hz
0100
F0.7 The lower limit frequency F0.8 The upper limit frequency F0.9 Reserved F0. 10 Acc time 1 F0. 11 Dec time 1
0.01 0.01
0.0 50.00
0.1 0.1
30
SUNFARE380
Name Setting range The first part of LED (form right to left): 0Beeline 1S curve The second part of LED 0Output freq. will be modified according to Acc/Dec time. 1Output freq. will be automatically modified according to lode. The third part of LEDUnit of Acc/Dec time 0 Sec 1Min The fourth part of LEDReserved 10 .0~ 50.0 % 10.0 ~ 80.0 % 0 General-purpose lode. 1 Fan and pump lode. 1.5~ 10.0 KHz The first part of LED (form right to left): Reserved The second part of LED 0Load carrier wave adjustment is invalid 1Load carrier wave adjustment is valid The third part of LED 0Heat carrier wave adjustment is invalid 1Heat carrier wave adjustment is valid The fourth part of LED 0Freq. relating carrier wave adjustment is Invalid 1Freq. relating carrier wave adjustment is valid 1Forbid to modify all parameter, except F0.2 and F0.18 2Forbid to modify all parameter, except F0.18 0Constant torque curve 1Low-freq. torque curve 1 2Low-freq. torque curve 2 3V/F user-defined curve 0.0~20.0 0Manual 1Automatic Minimum Manufactur Modify Setting Setting Limit
Function Code
F0. 12
0000
Acc/Dec initial section proportion Of S curve Acc/Dec ascending/decline section F0. 14 proportion of S curve F0. 13 F0. 15 Lode pattern selection F0. 16 Carrier wave frequency
20.0 60.0 0
1110
0 0 50.00 380 220V 0.0 0.0 0.0 0.0 0.0 0.0 50.0 0 0 0 25 100 1
F1. 1 Torque Boost F1. 2 Torque boost pattern F1. 3 Basic running frequency F1. 4 Max output voltage Primary applied parameter unit F1. 5 V/F freq. 3 F1. 6 V/F voltage 3 F1. 7 V/F freq. 2 F1. 8 V/F voltage 2 F1. 9 V/F freq. 1 F1. 10 V/F voltage 1 F1. 11 DC braking current when starting F1. 12 DC braking time when starting F1.13 Compensation for slipping freq. F1.14 Droop control F1.15 Initial level of droop control F1.16 Ending level of droop control F1.17 Droop control mode F1.18 Reserved
0.1 1 0.01 1 0.01 0.1 0.01 0.1 0.01 0.1 0.1 0.1 1 1 1 1 1Relative droop 1
5.00the upper limit frequency 200500V [F1.7] ~ [F1.3] [F1.8] ~ 100.0(%) [F1.9] ~ [F1.5] [F1.10] ~ [F1.6] 0.0 ~ [F1.7] [F1.1] ~ [F1.8] 0.0 100.0 0.0 20.0s 0150 0100 0150 10200 0Absolute droop 100250V
SUNFARE380
Function Code Name 0.0 V ~ [F2.1] [F2.0] ~ 5.0V 0.0V ~ [F2.3] [F2.2] ~ 10.0V 0.0mA~ [F2.5] [F2.4] ~ 20.0mA 0.0KHz~[F2.7] [F2.6]~50.0 KHz 0.0~[F2.9] Hz [F2.8]~300.0Hz The first part of LED (form right to left) (VC1channel) 0 positive characteristics 1Negative characteristics The second part of LED(VC2 channel) 0 positive characteristics 1Negative characteristics The third part of LED(CC channel) 0 positive characteristics 1Negative characteristics The fourth part of LED pulse channel 0 positive characteristics 1Negative characteristics 0.011.00s Refer to the explanations about F2.12 The first part of LED (form right to left) AO1output 0Output freq. 1Output current 2:Output voltage 3Rotate speed of applied motor 4PID setteng 5PID feedback The second part of LEDAO2 output 0Output freq. 1Output current 2Output voltage 3Rotate speed of applied motor 4PID setting 5PID feedback The third and fourth part of LEDReserved 0.0 V / 0.0mA[F2.15] [F2.14]12.0 V / 24.0mA 0.0V / 0.0mA [F2.17] [F2.16] 12.0V / 24.0mA Setting range
31
Minimum Manufactur Modify Setting Setting Limit 0.1 0.1 0.1 0.1 0.1 0.1 0.01 0.01 0.01 0.01 0.0V 5.0 V 0.0 V 10.0V 4.0mA 200 mA 0.0 10.0KHz 0.00Hz 50.00Hz
F2.0 VC1 input lower limit voltage F2.1 VC1 input upper limit voltage F2.2 VC2 input lower limit voltage F2.3 VC2 input upper limit voltage F2.4 CC input lower limit voltage F2.5 CC input upper limit voltage F2.6 The min pulse input F2.7 The max pulse input F2.8 Frequency with the min setting F2.9 Frequency with the max setting
F2.10
0000
External freq. set time constant of filtering F2.12 Combination setting mode F2.11
0.01 1
0.10 0
F2.13
0010
The lower limit of analog output AO1 The upper limit of analog output AO1 The lower limit of analog output AO2 The upper limit of analog output AO2
F2.18 Reserved
32
SUNFARE380
Name Function selection of input terminal 1 (0~26) Function selection of input terminal 2 (0~26) Setting range 0Control terminal is idle 1Multi-speed control terminal 1 2Multi-speed control terminal 2 3Multi-speed control terminal 3 4Wobble freq. is valid 5State of wobble freq. reset 6FWD jog control 7REV jog control 8Acc& Dec time selection terminal 1 9Acc& Dec time selection terminal 2 10Freq. setting channel selection 1 11Freq. setting channel selection 2 12Freq. setting channel selection 3 13Freq. is controlled gradually increase (UP) 14Freq. is controlled gradually decrease (DW) 15UP-DW freq. clear 16Uncontrolled stop control 17Fault signal of peripheral equipment input 18Three-line mode running control 19DC braking control 20Inner counter clear 21Inner counter timer 22PLC running valid 23PID running valid 24Internal timer trigger terminal 25PLC state reset after stopping 26Multi-speed control terminal 4 0In the running 1Frequency reaching 2Freq. level detection signalFDT 3Over-loading alarm 4External fault halt 5Output frequency reaches the upper-limit 6Output frequency reaches the lower-limit 7Running in zero speed 8Internal timer reaches the setting time 9PLC stage is end of run 10PLC periodic is end of run 11Internal timer arrive regular time 12Setting value of counter arrives 13Designated value of counter arrives 14Deceleration running 15Reserved 16Inverter fault 17Restrictions on wobble freq. of the upper and lower limit freq. 18Reserved 0.0~20.00Hz 0.0~the upper limit freq. 0.0~200.0s 0.0~the upper limit freq. 0.0~200.0s 50~200 0.0~20.0s Minimum Manufacture Modify Setting Setting Limit 1 1
F3.1
F3. 2
F3. 3
F3. 4
13
14
16
F3. 9
F3. 10 FDT setting 1 F3. 11 FDT output delay time 1 F3. 12 FDT setting 2 F3. 13 FDT output delay time 2 F3. 14 Over-loading alarm level F3.15 Over-loading alarm delay time F3. 16 Reserved
SUNFARE380
Function Code F4.0 Start mode F4.1 Start frequency F4.2 Start frequency duration F4.3 Stop mode F4.4 F4.5 F4.6 Initial freq. of DC braking when stopping Waiting time of DC braking when stopping Action time of DC braking when stopping Name 0Routine mode 0.010.00Hz 0.020.0s 0Decelerate mode 0.050.00Hz 0.05.0s 0.020.0s 0.0100 0.0100.00Hz 0.050.00Hz 0.0the upper limit freq. 110200 50110 1 Dynamic valid 3Deceleration invalid 1Valid 1Uncontrolled stop Setting range 1Detect speed and restart
33
Minimum Manufactur Modify Setting Setting Limit 1 0.01 0.1 1 0.01 0.1 0.1 0.1 0.01 0.01 0.01 1 1 1 1 1 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.01 1 1 0 0.5 0.0 0 3.00 0.0 0 50.0 0.0 0.50 10.00 165 110 0 0 60 0.0 10.00Hz 700V 60
F4.7 DC braking current when stopping F4.8 Running threshold of zero freq. F4.9 Return different of zero freq. F4.10 FWD jog frequency F4.11 Acc torque level Motor over-lode F4.12 protection coefficient Auxiliary running parameter unit
0Invalid F4.13 Automatic voltage regulationAVR 2Static valid F4.14 Energy-saving running F4.15 Intensify of energy-saving running F4.16 Dead time of FWD&REV F4.17 Acceleration time 2 F4.18 Deceleration time 2 F4.19 Acceleration time 3 F4.20 Deceleration time 3 F4.21 Acc time 4/Jog Acc time F4.22 Dec time 5/Jog Dec time 0Invalid 3090 0.05.0s 0.16000s/min 0.16000 s/min 0.16000 s/min 0.16000 s/min 0.16000 s/min 0.16000 s/min
F4.23 Modified rated of UP/DW terminals 0.01100.0Hz/Sec F4.24 Start voltage of dynamic braking F4.25 Action ratio of dynamic braking 600~750V 10~100 The first part of LED 0Invalid 1 Valid The second part of LED 0Routine mode 1Detect speed and restart mode The third and fourth part of LEDReserved
0010
F4.27
Waiting time of restart after power 0.010.0s down 0.0the upper limit freq.
0.1 0.01
0.5 10.00
34
SUNFARE380
Name Setting range The first part of LED(form right to left)Simple PLC selection 0Simple PLC is invalid. 1Simple PLC is valid 2Simple PLC is conditional valid The second part of LED Simple PLC running mode selection 0Single loop mode 1Single loop and stop mode 2Continuous loop mode 3Continuous loop and stop mode 4Keep the end value 5Keep the end value and stop mode The third part of LED 0Restart from the first stage freq. 1Restart from running freq., which is saved before running is break 2Restart from setting freq. when running is break. The fourth part of LEDPLC save state 0Non-save after power off 1Save after power off 0.0 ~ the upper limit freq. 0.0 ~ the upper limit freq. 0.0 ~ the upper limit freq. 0.0 ~ the upper limit freq. 0.0 ~ the upper limit freq. 0.0 ~ the upper limit freq. 0.0 ~ the upper limit freq. 0.0 ~ the upper limit freq. 0.0 ~ the upper limit freq. 0.0 ~ the upper limit freq. 0.0 ~ the upper limit freq. 0.0 ~ the upper limit freq. 0.0 ~ the upper limit freq. 0.0 ~ the upper limit freq. 0.0 ~ the upper limit freq. 0.06000s 0.06000s 0.06000s 0.06000s 0.06000s 0.06000s 0.06000s 0.06000s The first part of LED(form right to left) 0 Stage 1 FWD 1Stage 1 REV The second part of LED 0 Stage 2 FWD 1Stage 2 REV The third part of LED 0 Stage 3 FWD 1Stage 3 REV The fourth part of LED 0 Stage 4 FWD 1Stage 4 REV The first part of LED(form right to left) 0 Stage 5 FWD 1Stage 5 REV The second part of LED 0 Stage 6 FWD 1Stage 6 REV The third part of LED 0 Stage 7 FWD 1Stage 7 REV The fourth part of LED 0 Stage 8 FWD 1Stage 8 REV 0 Invalid 19999(min) timing running time Minimum Manufacture Modify Setting Setting Limit
Function Code
0000
F5.1 Multi-speed frequency 1 F5.2 Multi-speed frequency 2 F5.3 Multi-speed frequency 3 F5.4 Multi-speed frequency 4 F5.5 Multi-speed frequency 5 F5.6 Multi-speed frequency 6 Multi-speed running parameter unit F5.7 Multi-speed frequency 7 F5.8 Multi-speed frequency 8 F5. 9 Multi-speed frequency 9 F5.10 Multi-speed frequency 10 F5.11 Multi-speed frequency 11 F5.12 Multi-speed frequency 12 F5.13 Multi-speed frequency 13 F5.14 Multi-speed frequency 14 F5.15 Multi-speed frequency 15 F5.16 Running time of Multi-speed 1 F5.17 Running time of Multi-speed 2 F5.18 Running time of Multi-speed 3 F5.19 Running time of Multi-speed 4 F5.20 Running time of Multi-speed 5 F5.21 Running time of Multi-speed 6 F5.22 Running time of Multi-speed 7 F5.23 Running time of Multi-speed 8
0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.1 0.1 0.1 0.1 0.1 0.1 0.1 0.1
35.00 15.00 3.00 20.00 25.00 30.00 35.00 40.00 35.00 15.00 3.00 20.00 25.00 30.00 35.00 10.0 10.0 10.0 10.0 10.0 10.0 10.0 10.0
F5.24
0000
F5.25
0000
SUNFARE380
Function Code F6.0 Internal timer F6.1 Fault self-recovery time F6.2 Interval time of fault self-recovery Final value setup of F6.3 internal counter F6.4 Internal timer setup F6.5 Skip freq. 1 Amplitude accumulation of F6.6 Skip freq. 1 Advanced running parameter unit F6.7 Skip freq. 2 F6.8 Amplitude accumulation of Skip freq. 2 Name 0.16000.0s 012 0.220s 160000 160000 0.0the upper limit freq. 0.05.00Hz 0.0the upper limit freq. 0.05.00Hz 0.01100.0 0.01100.0 0.0110.00 011 011 0 ~ 9999 0Parameter initialization is off. 1Parameter initialization is on. 2Clean fault records 3complete initialization 0Copy forbidden 1Copy allowed 09999 09999 0 ~ 9999 The first part of LED (form right to left) 0Function of wobble freq. is invalid. 1Function of wobble freq. is valid. 2Function of wobble freq. is conditional valid. The second part of LED: restart mode 0 Restart according to parameters saved before stop 1 Restart The third part of LED: wobble freq. characteristics 0The wobble freq. is fixed 1The wobble freq. is changeable. The fourth part of LED: Storage characteristics of wobble freq. 0It will not save the running state of wobble freq. after power off 1It will save the running state of wobble freq. after power off 0.0 ~ the upper limit freq. 0.06000.0s 0.050.0 0.080.0 0.11000.0s 0.11000.0s 0.0 ~ the upper limit freq. Setting range
35
Minimum Manufactur Modify Setting Setting Limit 0.1 1 0.1 1 1 0.01 0.01 0.01 0.01 0.01 0.01 0.01 1 1 1 10.0 0 2.0 1 1 0 0 0 0 1.00 1.00 1.00 0 1 1700
F6.9 Linear speed coefficient setting Close-loop analog F6.10 coefficient setting F6.11 Rotator speed coefficient setting Monitor item selection F6.12 1 / Main display Monitor item selection F6.13 2 / Auxiliary display F6.14 Query or modify parameters
F6.16 Copy parameter function F6.17 Manufactory password F6.18 User password F6.19 Reference password
1 1 1 1
0 1500 0
1000
F7.1 Preset freq. of wobble freq. F7.2 Waiting time of preset freq. F7.3 Amplitude of wobble freq. F7.4 Jumping freq. F7.5 Triangular rise time F7.6 Triangular fall time F7.7 Preset center freq. of wobble freq. F7.8 Reserved
36
SUNFARE380
Name Setting range The first part of LED(form right to left) Inner PID control 0Inner PID control is invalid 1Inner PID control is valid 2Inner PID control is conditional valid. The second part of LED PID controller selection 0 proportion 1Integral 2Proportion and integral The third part of LED Regulating property of PID controller 0 positive interaction 1Reactor The fourth part of LED: 0: Single polar PID control 1: Bi-polar PID control Minimum Manufactur Modify Setting Setting Limit
Function Code
0020
The first part of LED(form right to left) 0Digital setting. It is set by parameter F8.2. 1Serials interface setting 2Panel potentiometer setting, it is on the operation panel. 3External voltage signal VC10V~5V 4External voltage signal VC20V~10V Inner PID setting and channel 5External current signal CC0~20mA F8.1 selection The second part of LED Reserved. The third part of LED It is used to set PID feedback channel. 0External voltage input VC1 1External voltage input VC2 2External current input CC 3Pulse input PLS 4VC1+CC 5VC1-CC 6Min (VC1, CC) 7Max (VC1, CC) . The fourth part of LED: Reserved. F8.2 Inner PID close-loop digital setting F8.3 Minimum fixed value F8.4 Maximum fixed value F8.5 Feedback of minimum fixed value 0.0010.00V 0.0[F8.4] [F8.3]10.00 0.010.00
0000
0.01 0.01 0.01 0.01 0.01 0.01 0.1 0.1 0.01 0.1 0.001 0.001 0.001 0.1 0.001 0.001
0.00 0.0 10.00 0.0 10.00 1.00 10.0 5.0 0.0 0.0 1.000 1. 000 0.0 300.0 1.000 0.0
F8.6 Feedback of maximum fixed value 0.010.00 F8.7 Proportion gain F8.8 Integral time constant F8.9 Allowable deviation limit F8.10 Preset freq. for close-loop F8.11 Holding time of preset freq. for close-loop 0.05.00 1.0100.0s 0.020.0 0.0the upper limit freq. 0.06000.0s 0.00120.000Mpa [F8.14]~[F8.12] 0.0~[F8.13] 5.0~500.0 Sec [F8.16]~[F8.12] Mpa 0.001 ~ [F8.15] Mpa
F8.12 Long-distance manometer range F8.13 Sleeping threshold F8.14 Awakening threshold Switching time of F8.15 Sleeping/Awakening mode F8.16 Upper limit pressure value F8.17 Lower limit pressure value F8.18 Reserved F8.24
SUNFARE380
Function Code Name Setting range The first part of LED(form right to left) It is used to set baud rate of serials communication. 0 Reserved 11200bps 2: 2400bps 3: 4800bps 4: 9600bps 5: 19200bps The second part of LED To set data format of serials communication. 0Close 1 Even 2Odd The third and fourth part of LED: Reserved. 030 01000ms
37
0014
1 1
0 5ms
The first part of LED(form right to left) 0The inverter is guest 1: The inverter is host The second part of LED Act selection after communication is lost 0Stop 1Keep Function setting of communication F9.3 The third part of LEDlinkage jog Auxiliary function 0jog synchronized 1jog asynchronous The fourth part of LEDlinkage control synchronized frequency source 0setting frequency 1output frequency F9.4 Checkout time of communication overtime 0.0100.0s 0.01010.000 0close 1Panel potentiometer Rectify channel 2External voltage signal VC1 0 ~ 5V Rectify channel 3External voltage signal VC2 0 ~ 10V Rectify channel 4External current signal CC 0 ~ 20mA 0no auxiliary freq. 1Panel potentiometer 2External voltage signal VC10 ~ 5V 3External voltage signal VC20 ~ 10V 4External current signal CC 0.025.00 Hz 0Invalid 0.502.00 0.05.00 360460V 660760V 150200 1Valid
0010
0.1 0.01
10.0 1.000
F9.6
F9.7
F9.8 Amplitude of auxiliary freq. F9.9 Load self-equilibrium function F9.10 F9.11 Special function parameter unit Load self- equilibrium proportion Trimming range of load selfequilibrium freq.
FC.0 Under voltage protection level FC.1 Over voltage limit level FC.2 Current amplitude limiting level FC.3 Reserved FC.4
38
SUNFARE380
Name Setting range the first part of LED(form right to left) Cooling fan control 0Cooling fan run after inverter run. 1Cooling fan will automatic run when inverter is power on. The second part of LED Variable speed control of cooling fan 0Invalid 1Valid Cooling fan always keep the max speed. The third part of LED Voltage over modulation 0Invalid 1Valid the first part of LED(form right to left) Forbid modify parameters function 0Invalid 1Valid The second part of LEDInput terminal effective level 0:Low level (terminals is connected) 1:High level (terminals is disconnected ) The third part of LED: Reserved The fourth part of LEDselection of rotate speed display proportion 0: the coefficient of rotate speed display is valid 1: the deceleration proportion is valid Minimum Manufacture Modify Setting Setting Limit
Function Code
0000
0000
FC.7 Reserved FC.8 Agency password FC.9/F Reserved C.10 FC.11 Oscillatory inhibiting factor FC.12 Reserved FC.13 Program version 16001699 1 0.010.00 0.01 0.00 0 ~ 9999 1 100
SUNFARE380
39
It is used for selecting input channel of frequency instruction. 0 Frequency setting by operation panel Frequency of inverter is set by parameter F0.2 as well as by the key and on the operation panel in normal monitor mode. 1 UP/DW Acc and Dec control Running frequency is set by terminals UP and DW. And controlled terminals UP and DW can be selected by parameters [F3.0]~[F3.5]. When UP is on, the running frequency will increase. When UP is on, the running frequency will decrease. When UP and DW is on or off together with CM, running frequency will fix. The rate of modified frequency of terminals UP and DW is set by parameter F4.23. 2 RS485 interface Through serial communication, it receives instruction of setting frequency from PC or the master. 3 Panel potentiometer Running frequency can be set by potentiometer on the operation panel. 4 External voltage signal VC1 Running frequency is set by external voltage signal VC1. (VC1 is form 0.0 to 5.0V) Please set the VC1 referring to the parameters F2.0 and F2.1. 5 External voltage signal VC2 Running frequency is set by external voltage signal VC2. (VC2 is form 0.0 to 10.0V) Please set the VC2 referring to the parameters F2.2 and F2.3. 6 External current signal CC Running frequency is set by external current signal CC. (CC is form 0.0 to 20.0mA) Please set the CC referring to the parameters F2.4 and F2.5. 7 External pulse signal Running frequency is set by external pulse signal. (It is form 0.0 to 350.0KHz, and the amplitude accumulation is form 5 to 30V) Please set the pulse signal referring to the parameters F2.6 and F2.7. 8 Combination setting Running frequency is set by linear combination of each channel, and combination mode is decided by parameter F02.12. 9 External terminals
E380 Serials of General Purpose Inverter Operation manual
40
SUNFARE380
External terminals set input channel of frequency. And it can be set by parameters F3.0F3.5.
Freq. Setting terminal 3 0 0 0 0 1 1 1 1 Freq. Setting terminal 2 0 0 1 1 0 0 1 1 Freq. Setting terminal 1 0 1 0 1 0 1 0 1 Freq. Setting channel Frequency setting by operation panel UP/DW Acc and Dec control RS485 interface Panel potentiometer External voltage signal VC1 External voltage signal VC2 External current signal CC External pulse signal
When F0.1 is 0, Frequency digital setting controls output frequency of inverter. In normal monitor state, user can use the key and to modify this parameter. As for F0.1 is 1 or F0.1 is 2, the frequency will save in parameter F0.3 after power off, if F0.3 is 00#0. F0.3 Auxiliary control of freq. digital setting Setting range0000 ~ 0021
It is used for making sure that the frequency is set under the stopping or power off situation. When F0.1 is 0, 1 or 2, set parameter F0.3 to ensure that setting freq. is or not be saved in F0.2. The first part of LED(form right to left) 0 Inverter will run in setting freq. that is storage in F0.2 after stopping 1 Setting freq. will lost after stopping. And inverter will run in 0.0Hz when restarting The second part of LED(form right to left) 0Setting freq. is kept when stopping 1Setting freq. will save in F0.2 when stopping 2Setting freq. is cleared when stopping The third and fourth part of LED(form right to left)Reserved. F0.4 Operation channel selection Setting range 0000 ~ 0012
It is used for selecting operation channel of inverter and function of key . The first part of LED (form right to left): to select operation channel of inverter. 0 Keypad control The inverter is controlled by key , , and on the keypad. And FWD state will affect output phase sequence of inverter. When FWD is on with CM, output phase sequence will reverse with setting sequence, contrariwise, output phase sequence will go the same way with setting sequence. 1 External terminals control The inverter receives running instruction form external terminals FWD, REV and CM. The manufacture setting is shown as follows.
Instruction Terminals State Stop instruction
FWD REV CM
FWD
FWD REV CM FWD REV CM
REV
FWD REV CM
2 RS485 interface Through serial communication, it receives instruction of setting frequency from PC or the master.
SUNFARE380
41
The second part of LED (form right to left): to select function of the key . 0 It is valid for panel control. When F0.4 is 0, Stop key on the operation panel is available. 1 It is valid for all kinds of control method. When F0.4 is not 0 and press stop key, inverter will emergency stop and twinkling display Fu.16. The third and fourth part of LED(form right to left)Reserved. F0.5 Combination methods of instruction terminals Setting range0 ~ 2
FWD
FWD REV CM
REV
FWD REV CM
0Two-line mode 2
Instruction Terminals State Stop instruction
FWD CM
FWD CM
FWD
REV CM
REV
REV CM
2Three-line mode Please select a three-line mode terminal to set three-line mode. (Refer to description of parameters F3.0 ~ F3.5) Xis three-line mode terminalsand it is any one among terminals X1 ~ X6. Switch function is shown as follow 1. SW1 Stop trigger switch of inverter 2. SW2 FWD trigger switch 3. SW3 REV trigger switch
SW1
Output freq.
X?
SW2
FWD
SW3
REV CM
F0. 6
It is used for changing the output phase-sequence of inverter, which changes the operating direction of motor (set by binary system). The third part of LEDExternal operation channel auxiliary function 0Self-starting is forbidden when inverter is just power-on
42
SUNFARE380
1Self-starting is allowed when inverter is just power-on When [F0.6]=#0##when inverter is just power-oneven though the control terminal is in runningthe inverter will not self-starting. In order to operate inverter, you should first give a stop signal, then a start-up instruction. This parameter is used for modifying the present output phase sequence of inverter, which modifies the running motor direction. Control effect of panel control method is shown as following table.
Parameter F0.4 is valid together with direction control of external terminals. FWD-CM OFF ON OFF OFF ON ON [F0.6] ##1# ##1# ##00 ##01 ##00 ##01 Direction FWD FWD FWD REV REV FWD
F0.7 F0.8
When setting freq. is lower than lower limit freq., the inverter will run in lower limit freq. But the parameters F4.8 and F4.9 are priority over F0.7 and F0.8. F0.9 F0.10 F0.11 Reserved Acc time 1 Dec time 1 Setting range0.1 ~ 6000 Sec/Min Setting range0.1 ~ 6000 Sec/Min
Acc time 1 is the time of output frequency accelerating from 0.0 Hz to 50.00Hz. Dec time 1 is the time of output frequency decelerating from 50.00 Hz to 0.00Hz. Units of Acc and Dec are set by parameter F0.12. F0.12 character parameter of Acc and Dec Setting range0000 ~ 0111
The first part of LED(form right to left)It is used for setting curve type when inverter is accelerating or decelerating, shown as fig6-3. 0 Beeline Output freq. of inverter will increase or decrease according to fixed rated. 1 S curve Output freq. of inverter will increase or decrease according to graded rated. Characteristic of S curve is set by parameter F0.13 and F0.14. The second part of LEDTo set Acc/Dec method 0 Output freq. will be modified according to Acc/Dec time. 1 Output freq. will be automatically modified according to load. The third part of LED It is used for setting unit of Acc/Dec time, namely unit of parameters F0.10, F0.11, F4.17, F4.18, F4.19, F4.20, F4.21 and F4.22. 0 Sec. 1 Minute O utput freq. H z The fourth part of LEDReserved.
Beeline
S curve T Sec/min
[F0.13][F0.14]
SUNFARE380
43
F0.13 F0.14
Acc/Dec initial section proportion of S curve Acc/Dec ascending/decline section proportion of S curve
Parameters F0.13 and F0.14 define characteristic of S curve. It is totally divide into three sections, shown as fig6-3. Acc/Dec initial section is process that slope of output freq. is gradual increase form 0. The slope will fix in Acc/Dec ascending/decline section. And the slope will gradual decrease to 0 in end section. F0.15 Load pattern selection 0 General purpose load. 1 Fan and pump load. F0.16 Carrier wave frequency Setting range 1.5 ~ 10.0 KHz Setting range01
Carrier wave frequency influences audio-frequency noise and calorific effect in running. When environmental temperature is too high and motors load is too heavy, carrier frequency should be decreased properly to improve the heat thermal performance. F0.17 Carrier wave characteristics Setting range0000 ~ 1110
It is used for setting correlated characteristics about carrier wave. The first part of LED (form right to left): Reserved The second part of LEDLoad relating carrier wave adjustment. If this function is valid, when load current is too high, it will automatically reduce the carrier frequency to ensure operation safety of inverter. 0Invalid 1Valid The third part of LEDHeat relating carrier wave adjustment If this function is valid, when environmental temperature is too high, the inverter will automatically reduce the carrier wave frequency. 0Invalid 1Valid The fourth part of LEDFreq. relating carrier wave adjustment If this function is valid, the inverter will automatically reduce the carrier frequency in low-frequency running. 0Invalid 1Valid AttentionWhen the inverter automatically adjusts carrier freq., the running noise will increase. F0.18 Parameter write-protect Setting range12
It is used for preventing error modify about data. 1Forbid to modify all parameter, except F0.2 and F0.18 2Forbid to modify all parameter, except F0.18
In running, some parameters cannot be, modified. At this time , if try to modify these parameters, the inverter will display , please turn off the inverter before modify those parameters.
44
SUNFARE380
The output voltage of inverter is conic with the output frequency, which is suited to the constant power load, such as fan, pump, etc. If there is some unstable phenomenon in light-load running, please switch to run in the decreasing torque curve 1. 3: V/F user-defined curve It is used for setting user-defined curve which user need.
Voltage [F1.4] The max output voltage
[F.1.3]
F1.1
It is used for improving the low-frequency torque character. In low-frequency running, it will make boost compensation for the output voltage of inverter, as shown in Fig.6-5. Boost voltage = [F1.1] 200
[F1.4] Voltage [F1.4] Voltage
[F1.4]
[F1.1]
Boost voltage
f [F1.3]
F1.2
Setting range0 1
0Manual Torque boost voltage is completely controlled by F1.1. There are two features: voltage will steady boost. And motor will easily magnetic saturation when light-load. 1Automatic Torque boost voltage is changed with the stator current of motor. The boost voltage is higher with the stator current higher. [F1.1] 200
Inverters output Current 2inverters rated current
Boost voltage =
[F1.4]
Auto torque boost can prevent the magnetic saturation, as the boost voltage is too high with light load, which can avoid the over-heat phenomenon of motor in low frequency running.
E380 Serials of General Purpose Inverter Operation manual
SUNFARE380
45
F1.3 F1.4
Setting range 5.00 ~ the upper frequency Setting range 200 ~ 500V/100~250V
Basic running frequency is corresponding to minimum frequency when output voltage of inverter is the highest. Usually, it is rated frequency of motor. Max output voltage is corresponding to output voltage when inverter outputs the basic running frequency. Usually, it is rated voltage of motor. F1.5 V/F freq. 3 F1.6 V/F voltage 3 F1.7 V/F freq. 2 F1.8 V/F voltage 2 F1.9 V/F freq. 1 F1.10 V/F voltage 1
Voltage [F1.4] [F1.6]
Setting range F1.7] ~ [F1.3] Setting range[F1.8] ~ 100% Setting range [F1.9] ~ [F1.5] Setting range[F1.10] ~ [F1.6] Setting range0.0 ~ [F1.7] Setting range[F1.1] ~ [F1.8]
Those parameters are used for setting user-defined curve which user need. Shown as Fig.6-6 below:
F1.11 DC braking current when starting F1.12 DC braking time when starting
Those parameters are fit for the occasion that inverter needs brake before start.
DC braking current when starting F1.11= Rated current of inverter 100%
When rated current of motor is lower than rated current of inverter, please pay attention to set F1.11.Make sure that DC braking current is lower than rated current of motor.
Parameter F1.12 defines duration that inverter output DC braking current. When F1.12 is 0, DC braking is Output Freq. invalid when starting.
Starting freq. [F1.12] [F4.1] Output current [F4.4] DC braking
[F4.7]
Instruction
46
SUNFARE380
F1.13
The inverter will modify output freq. automatically to offset effects that is act on rotate speed of motor form load. Output freq. Compensation for slip freq. is 100%
After
Droop control Initial level of droop control Ending level of droop control
Droop control is a special control mode to poise output power when multi-inverters inverter the same load or rotator speed of motor will change with the load. It will poise power and torque by setting those parameters, when multi-inverters inverter the same load. If those parameters are appropriate set, applied asynchronous motor will have the same characteristic with torque motor. Shown as fig6-9.
Rotate speedRelative value
100
100-[FC.14]
[FC.15]
[FC.16]
Fig6-9
They are nameplate parameters of applied motor. The running performance will improve if those parameters are input correctly. F1.17 Droop control mode Setting range 01
Droop control is a special control mode that is used for poising output power when multi-inverters inverter the same load. Output power will decrease automatically when output torque or current of a certain inverter is heavier than usual. Some load will off, so the power will be poised. The adjustment range of frequency changed with the load will decide by parameters FC.14, FC.15 and FC.16. 0: Absolute droop
Actual output freq. of inverter= Setting freq. Actual output torque levelinitial level of droop Ending level of droopInitial level of droop Base running frequency [F1.3]
The max of actual freq. of inverter is setting freq.. When setting freq. of inverter is lower than base-running freq., ending level of inverter will reduce to 0 before inverter run to ending level of droop. 1Relative droop
Actual output freq. of inverter= Setting freq. Actual output torque levelinitial level of droop Ending level of droopInitial level of droop Setting frequency
SUNFARE380
47
The max of actual freq. of inverter is setting freq.. If output torque is beyond initial level of droop, output freq. will decrease. When output torque arrives ending level of droop, actual output freq. will reduce to 0.
F1.18
Reserved
[F2.0] and [F2.1] define the range of analog input voltage channel VC1, and it should be set according to the actual input signal. [F2.2] and [F2.3] define the range of analog input voltage channel VC2, and it should be set according to the actual input signal. [F2.4] and [F2.5] define the range of analog input current channel CC, and it should be set according to the actual input signal. [F2.6] and [F2.7] define the freq. range of external pulse signal. Setting range 0.0Hz ~ [F2.9] Setting range [F2.8] ~ 600.0Hz
F2.8 F2.9
frequency with the min setting frequency with the max setting
They define the Corresponding relation between analog input (pulse input) and setting frequency. Shown as fig.6-10. F2.10 Character selection of input channel Setting channel 0000 ~ 1111
It is used for selecting input character of external analog value or pulse value. The first part of LED (form right to left):It defines character of voltage signal analog input VC1. 0 positive character 1Negative character The second part of LED (form right to left): It defines character of voltage signal analog input VC2. 0 positive character 1Negative character The third part of LED (form right to left): It defines character of current signal analog input CC. 0 positive character 1Negative character The fourth part of LED (form right to left): It defines character of pulse signal analog input PLS. 0 positive character 1Negative character The corresponding relation is shown as fig.6-10 between input signal and setting freq.
48
SUNFARE380
Freq. Output freq.
[F2.9]
[F2.8] [F2.9] [F2.8]
Analog value Analog value Input upper Input lower limit limit Positive character
Analog value Analog value Input upper Input lower limit limit Negative character
F2.11
Setting freq. set by external analog input will be filtered to eliminate fluctuation. Time constant of filtering have to appropriate set according to fluctuate of external input signal. F2.12 Combination setting mode Setting range0 ~ 29
The parameter is valid only when the frequency input channel F0.1 is set as 8.
Setting Value 0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 Setting Value 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29
Combination setting mode External voltageVC1 + External current CC External voltageVC2 + External current CC External voltageVC1 + External voltageVC2 External voltageVC1 + pulse setting External voltageVC2+ External current CC+ pulse setting External voltageVC1 + panel setting + pulse setting External voltage1 + panel setting + digital setting External voltage2 + panel setting + digital setting External current + panel setting + digital setting Serials interface setting + External voltage1 Serials interface setting + External current + pulse setting Serials interface setting + External voltage1 + panel setting External voltage2 + External current + panel setting The max of external voltage1 and external voltage2 Nonzero valid of External voltage1and External voltage2
Combination setting mode External voltageVC1 - External current CC External voltageVC2 - External current CC External voltageVC1 - External voltage VC2 External voltageVC1 - pulse setting External voltageVC2+ External current CC- pulse setting External voltageVC1+ panel setting - pulse setting External voltage1 - panel setting + digital setting External voltage2 - panel setting + digital setting External current - panel setting + digital setting Serials interface setting - External voltage1 Serials interface setting - External current + pulse setting Serials interface setting + External voltage2 - panel setting External voltage2+ External current - panel setting + digital setting The max among External voltage1, External voltage2 and External current Nonzero valid External voltage1, External voltage2 and External current CC
F2.13
It defines meaning of AO1AO2. The first part of LED: it defines the meaning of analog output terminal AO1. The second part of LED: it defines the meaning of analog output terminal AO2. 0Output freq.
SUNFARE380
49
Amplitude accumulation of AO1 and AO2 are in direct ratio to the output frequency. F2.15 and F2.17 are corresponding to the upper limit freq. 1Output current Amplitude accumulation of AO1 and AO2 are in direct ratio to the output current. F2.15 and F2.17 are twice rated current of inverter. 2Output voltage Amplitude accumulation of AO1 and AO2 are in direct ratio to the output voltage. F2.15 and F2.17 are corresponding to [F1.4] and [F1.14]. 3Rotate speed of applied motor Amplitude accumulation of AO1 and AO2 are in direct ratio to the motor rotate speed of inverter. F2.15 and F2.17 are corresponding rotate speed that is corresponded the upper limit freq.. 4PID setting Amplitude accumulation of AO1 and AO2 are in direct ratio to the setting value of PID. F2.15 and F2.17 are corresponding to feedback of 10.00. 5PID feedback Amplitude accumulation of AO1 and AO2 are in direct ratio to the PID feedback. F2.15 and F2.17 are corresponding to feedback of 10.00. The third and fourth part of LED: Reserved. F2.14 F2.15 F2.16 F2.17 the lower limit of analog output AO1 the upper limit of analog output AO1 the lower limit of analog output AO2 the upper limit of analog output AO2
AO1/AO2
Setting range 0.0 V/0.0mA ~ [F2.15] Setting range [F2.14] ~ 12.0 V/24.0mA Setting range 0.0 V/0.0 mA ~ [F2.17] Setting range [F2.16] ~ 12.0 V/24.0mA
Those parameters define the max and min value of analog output AO1and AO2, shown as fig 6-11.
[F2.15] [F2.17] [F2.14] [F2.16] 1 2 3 4 5 6 Upper limit voltage Output freq. Output current Output voltage Rotor speed PID setting 10.00 10.00 PID
AO1 and AO2 provide voltage signal form 0 to 12V or current signal form 0 to 24 mA. Two kinds of output signal can be selected by JP (JP1 and JP2) switch. JP1 and JP2 are shown as fig.6-12.
2-3 shortedAO1output current signal JP3 1-2 shortedAO2 output voltage signal 2-3 shortedAO2 output voltage signal
CO1
+10V
CO2
50
SUNFARE380
F2. 18
Reserved
0 Control terminal is idle 1 Multi-speed control terminal 1 2 Multi-speed control terminal 2 3 Multi-speed control terminal 3 26 Multi-speed control terminal 4 Combination of multi-speed control terminals is used for selecting output freq. of multi-speed. 4 Wobble freq. is valid When F7.0 is ###2 and any of those parameters is set 4, wobble freq. is valid. 5 State of wobble freq. reset When inverter is stop and F7.0 is ##0#, forcible reset will work by setting those parameters. 6 FWD jog control 7 REV jog control When F0.4 is ###1 and any of those parameters is set 6 or 7, external jog signal is valid. 8 Acc& Dec time selection terminal 1 9 Acc& Dec time selection terminal 2 They are used for selecting external terminals Acc/Dec time 1~4. 10 Freq. setting channel selection 1 11 Freq. setting channel selection 2 12 Freq. setting channel selection 3 When F0.1 is 9, Frequency input channel is set by terminals state of 10, 11 and 12. See the explanation about parameter F0.1. 13Freq. is controlled gradually increase (UP) 14: Freq. is controlled gradually decrease (DW) 15: UP-DW freq. clear When F0.3 is##0#, one of terminal X1~X6 defined by this parameter have function of forcible clear. 16 Uncontrolled stop control If one of terminal X1~X6 defined by this parameter is connected with CM, the inverter will lock output signal and applied motor will uncontrolled stop. Then inverter will detect speed and restart after terminal is disconnected with CM. 17 Fault signal of peripheral equipment input When one of terminal X1~X6 is defined by this parameter is connected with CM, peripheral equipment is fault. The inverter will lock output signal and display FU.16. 18 Three-line mode running control When F0.5 is 2, one of external terminal X1~X6 defined by this parameter is stop trigger switch of inverter. See explanation about F0.5. 19 DC braking control When inverter stops and one of external terminals X1~X6 defined by this parameter is connected with CM and output freq. is lower than Initial freq. of DC braking, function of DC braking is valid until terminal is disconnected with CM. Refer to explanation about F4.4~F4.7. 20 Inner counter clear 21 Inner counter timer
E380 Serials of General Purpose Inverter Operation manual
SUNFARE380
51
Only terminal X6 is used for Inner timer, namely parameter F3.5 is 21. 22 PLC running valid When F5.0 is ###2 and any of those parameters is set 22, PLC running is valid. 23 PID running valid When F8.0 is ###2 and any of those parameters is set 23, PID running is valid. 24 Internal timer trigger terminal The terminals is defined to be the internal timer trigger terminal 25 PLC state reset after stopping If F5.0 is set as #1##, the PLC state will keep fix. But external terminals will force reset, which is set by this function. F3.6 F3.7 F3.8 Output terminal OC1 Output terminal OC2 TA, TB and TC of relay contacts Setting range0 ~ 18 Setting range0 ~ 18 Setting range0 ~ 18
It defines expression content of relay contact and terminals OC1 and OC 2 when collector is open-circuit. Shown as fig.6-13. When TA is on with TC, setting functions will available.
D 1
While connecting the external inductance cell (For example, Relay coil), it must connect the parallel fly-wheel diode D.
0In the running When the inverter is in the running state, it will output the valid signal. While the inverter is in stop mode, it will output the invalid signal. 1Frequency reaching When the output frequency of inverter approaches the certain range of the setting frequency. (The range is decided by parameter F3.9), it outputs valid signal, otherwise, outputs the invalid signal (High-resistance).
OC High resistance [F3.9]
f
Setting freq. Output freq. Output freq.
2Freq. level detection signalFDT When the output frequency of inverter is over FDT Frequency level, the inverter will output the valid signal (Low electrical level) after the setting delay time. When the output frequency of inverter is lower than FDT frequency level, after the same delay time, it will output the invalid signal (High resistance).
52
SUNFARE380
OC1 High resistance High resistance Setting frequency FDT Level
f
[F3.10] [F3.12]
[F3.11] [F3.13]
[F3.11] [F3.13]
3Over-loading alarm When the output current of inverter is over the over-loading alarm level, it will output the valid signal (Low level) after the setting alarm delay time. When the output current is lower than the over-loading alarm level, it will output the invalid signal (High resistance) after the same delay time.
O u tp u t c u rr e n t A la r m le v e l
OC H ig h r e s is t a n c e [F 3 .1 5 ] [F 3 .1 5 ] H ig h r e s is ta n c e t
4External fault halt When the external fault input signal is valid and it will lead to stop-machine, the terminal will output the valid signal (Low level), otherwise it will output the invalid signal (High resistance). 5Output frequency reaches the upper-limit When the output frequency reaches the upper-limit frequency, the terminal will output the valid signal (Low level). Otherwise, it will output the invalid signal (High resistance). 6Output frequency reaches the lower-limit When the output frequency reaches the lower-limit frequency, the terminal will output the valid signal (Low level). Otherwise, it will output the invalid signal (High resistance) 7 Running in zero speed Running instruction is valid and output freq. is 0, if inverter is input freq., the terminal will output the valid signal (Low electrical level). If inverter is not input freq., the terminal will output the invalid signal ( High resistance). 8Internal timer reaches the setting time When the internal timer reaches the setting time, the terminal will output the valid pulse signal of 0.5 Sec pulse widths. (Low electrical level) 9 PLC stage is end of run When simple PLC is valid and current stage is end, this port will output pulse signal with 0.5s pulse width. 10PLC periodic is end of run When simple PLC is valid and current period is end, this port will output pulse signal with 0.5s pulse width. 11Internal timer arrive regular time If the internal timer arrive regular time, the corresponding port will output 0.5s width pulse signal. 12Setting value of counter arrives See the explanation about parameter F6.3.
E380 Serials of General Purpose Inverter Operation manual
SUNFARE380
53
13Designated value of counter arrives See the explanation about parameter F6.4. 14Deceleration running 15Reserved 16Inverter fault When inverter is running with fault, it will output available signal (low level). 17Restrictions on wobble freq. of the upper and lower limit freq. When parameters setting about wobble freq. result in that running freq. is beyond the upper and lower limit freq., this port will output available signal (lower lever). Generally, this port output high resistance. 18Reserved F3. 9 Frequency reach the checkout amplitude Setting range0.0 ~ 20.00Hz
If output freq. of inverter is within setting value that is set by F3.9, selected terminal will output valid signal. Shown as fig.6-15. Setting range0.0 ~ upper limit freq. Setting range0.0 ~ 200.0 s Setting range0.0 ~ Setting range Setting range0.0 ~ 200.0 s
F3.10 FDT setting 1 F3.11 FDT output delay time 1 F3.12 FDT setting 2 F3.13 FDT output delay time 2
The parameter is used for setting the frequency detection level. When output frequency is higher than the setting value of FDT, after the setting delay time, terminals will output the valid signal, shown as fig.6-15. Parameters F3.10 and F3.11 are used for setting FDT of OC1, parameters F3.12 and F3.13 are used for setting FDT of OC2. F3.14 F3.15 Overload alarm level Overload alarm delay time Setting range50 ~ 200% Setting range0.0 ~ 20.0s
If output freq. beyond the setting value set by parameter F3.14, after the setting delay time set by parameter F3.15, terminals output valid signal, shown as fig.6-16. F3.16 Reserved
Those parameters are used for defining characteristic with relation to start mode, shown as fig6-17. The explanation of F4.0 is shown as follows. 0 Routine mode It is fit for mostly load, which have not special demand. 1Detect speed and restart It is fit for fault reset and restart occasion, or, power off and restart occasion. Inverter will judge automatically running speed and direction of motor. Motor, which have not stop, will start up directly according to detect result. Start frequency It is fit for system, which is big inertia, heavy load and high start torque.
54
SUNFARE380
f
Setting freq. Decelerate stop with no DC braking
[F4.1]
[F4.2]
Free stop
t
Start
F4.3
Stop mode
Setting range0 ~ 1
0 Decelerate mode Inverter will gradually decrease output freq. to 0 according to Dec time when stopping. 1 Uncontrolled stop Inverter will output zero freq. and lock output signal when stop, so motor will uncontrolled stop. If user needs restart motor before motor complete stop, function of detect speed and restart must be valid when inverter is uncontrolled stop. Start mode and stop mode is shown as fig6-16. F4.4 Initial freq. of DC braking when stopping F4.5 Waiting time of DC braking when stopping F4.6 Action time of DC braking when stopping F4.7 DC braking current when stopping Setting range0.00 ~ 50.00 Hz Setting range0.0 ~ 5.0 S Setting range0.0 ~ 20.0 S Setting range0.0 ~ 100 ( % )
It is used for setting DC braking parameters when stopping, shown as fig6-7. When output freq. is lower than setting freq. of Parameter F4.4, inverter will lock output and start DC braking function after waiting setting time of parameter F4.5. DC braking when stopping is invalid while F4.6 is 0. DC braking current when stopping is the percentage of rated current of inverter. When capability of applied motor is lower than inverter capability, please be sure to set F4.7. F4.8 F4.9 Running threshold of zero freq. Return different of zero freq. Setting range0.00 ~ 100.00Hz Setting range0.00 ~ 50.00Hz
Those parameters define characteristic of freq. zero-crossing. When inverter takes analog input freq. to set freq., analog signal will fluctuate around zero to cause astable input. Those parameters have lagging function to avoid fluctuating around zero. Appropriate set Function of sleep and awakening will be work, if those parameters are appropriate set. For example analog input channel VC2 is shown as fig6-18. VC input
[F2.1]
[F4.9]
SUNFARE380
55
Jog running is special running method of inverter. Whatever the initial state of inverter is stop or run, jog signal will be received. The transition form initial running freq. to jog freq. is ac8 according to parameters F4.21 and F4.22.
f
Jog Acc time [F4.21] FWDJog Freq. [F4.10] Jog Dec time [F4.22]
t
Jog signal
f
Jog Acc time [F4.22] Jog Dec time [F4.21]
t
Jog signal
F4.11
It is used for setting permissible output level of torque current under motor acceleration state. The restriction on torque level is set by F4.11. It is percentage of rated current of inverter. For example, F4.11 set 150% that means the max output current is 150 percentage of rated current. When output current of inverter is beyond setting value of F4.11, inverter will prolong Acc/Dec time to inhibit output current in setting value of F4.11. Shown as fig6-20.
f
Modified Dec time
t
Fig6-20 Acc torque level
F4.12
The parameter is used for setting the sensitivity of thermal relay protection for applied motor. When the rated current of applied motor doesnt match with the rated current of inverter, it can accomplish the correct heat protection for the motor to set this parameter. The setting value of this parameter can be set by the following formula: [F4.13]= Rated current of motor Inverters rated output current
E380 Serials of General Purpose Inverter Operation manual
100
56
SUNFARE380
While one inverter parallel running with multi-motors, the thermal relay protection of inverter will be invalid, in order to protect the motor, please install the thermal relay on inlet terminals the motor.
F4.13
Setting range0 ~ 3
The function of Automatic voltage regulation is to ensure the output voltage of inverter not to fluctuate with the input voltage. When the range of fluctuation of power supply voltage is too heavy, and expect to motor have the stabilized stator voltage and current, this function should be open. 0Invalid 1 Dynamic valid 2 Static valid 3Deceleration invalid When user selects dynamic voltage regulation, fast dynamic voltage regulation can inhibit form increasing current cause by DC voltage in motor deceleration. But it easy brings current resonance. In acceleration and stabilization state, automatic voltage regulation is valid; but in deceleration state, it is invalid. F4.14 Energy-saving running Setting range0 ~ 1
0Valid 1Invalid When F4.15 is 0, inverter will check motor load automatically and real-time rectify output voltage. Energy-saving running works high efficiency under occasions that the range of freq. is small and the range of speed is wide. Because fan or pump has a specific relationship with rotation speed, it can compendiary judge load state according output freq.. Low-freq. torque curve V/F is a typical example in energy-saving running. When user takes low-freq. torque curve (F0.1 is 1 or2), function of energy-saving running neednt valid. F4.15 Intensity of energy-saving running Setting range30 ~ 90
It is used for setting the voltage regulating strength in energy-saving running. When inverter is in energy-saving running state, output voltage will be automatically adjusted with load, to enable the motor running in the most efficient state. If the parameter is set larger, the energy-saving effect is better, and the running stability will be worse. The client can set the parameter according to currently state. F4.16 Dead time of FWD&REV Setting time0.0 ~ 5.0 Sec
The parameter means that the duration at zero frequency when the inverter changes its running direction, and it is shown as the following fig.6-20. FWD and REV dead time is set for the big inertia load which has the mechanical dead zone.
Output frequency
t
[F3.10]
Acceleration time 2 Deceleration time 2 Acceleration time 3 Deceleration time 3 Acc time 4/Jog Acc time Dec time 5/Jog Dec time
Setting range0.1 ~ 6000 Sec Setting range0.1 ~ 6000 Sec Setting range0.1 ~ 6000 Sec Setting range0.1 ~ 6000 Sec Setting range0.1 ~ 6000Sec Setting range0.1 ~ 6000Sec
SUNFARE380
57
Jog frequency has the highest priority. In any state, as long as Jog instruction is input, the inverter will transit to run at Jog frequency according to the setting Acc and Dec time.
f
Acc/Dec terminal 1 Acc/Dec terminal 2 Acc/Dec time 1 Acc/Dec time 2 Acc/Dec time 3
F4.23
It defines rate that terminals UP/DW modify setting freq. Speed of F4.23 isnt controlled by Acc/Dec time. Setting range600 ~ 750 V Setting range10 ~ 100%
F4.24 F4.25
Those parameters are valid for inverter with the inner brake unit. And they define the action parameter of inner brake unit. When inner DC voltage of inverter is higher than the start voltage of dynamic braking, the inner brake unit will act. If inverter connects external brake resistance, DC energy of inverter will be release by it to decline DC voltage. When DC voltage declines to the certain value ([F4.24]-50V), inner brake unit of inverter will be off, shown as Fig.6-23. Brake unit action ratio is used for defining the voltage on brake resistor, and the voltage on brake unit is Voltage PWP. Duty cycle equals brake action ratio. The ratio is larger, and the energy is consumed more quickly, at the same time, the power of brake resistor is bigger. User can set parameter according to the resistance and power of resistor and actual brake effect.
DC Voltage [F4.24] [F4.24]-50V
F4.26 F4.27
Restart after power down setting waiting time of restart after power down
Parameter F4.26 The first part of LED 0Invalid 1 Valid When restart after power down setting is invalid, the inverter will clear automatically all running command and run according to new command after power on. When restart after power down setting is valid, the inverter will save all running command and run according to the save command after power on.
E380 Serials of General Purpose Inverter Operation manual
58
SUNFARE380
Please make sure that other equipments in system are ready before using function of restart after power down. The second part of LED Applied motor is still running when user select restart. Here, user have to select function of checking speed and restarting. The third and fourth part of LED: reserved. F4.28 REV jog frequency Setting range0.0 ~ Upper limit
6.6
F5.24 F5.25
Parameter F5.0 is multi-speed running mode. It is used for setting basic characteristic of multi-speed running. The first part of LED(form right to left)Simple PLC selection 0Simple PLC is invalid. 1 Simple PLC is valid. If priority of freq. channel is permit after starting, inverter will run at simple PLC state. 2Simple PLC is conditional valid. If external X1~X6 terminals is valid (F3.0~F3.5 is set as 22), inverter will run at simple PLC state.
SUNFARE380
59
Setting freq.
JOG freq. Wobble freq. running PID output PLC multi-speed freq.
External terminals select multi-speed freq. Freq. setting channel selectionParameter [F0.1]
The second part of LEDSimple PLC running mode selection 0Single loop mode The inverter will run in setting freq of the first stage and in turn output freq. of each stage according to setting running time. If setting running time of a certain stage is 0, the inverter will skip this stage. When a cycle operation is end of run, inverter will stop input until user input available running instrument to restart a next cycle. 1Single loop and stop mode Its function has an analogy with single loop mode. The difference is that output freq. is be reduced to 0 within the given decelerate time after a certain stage is end of run and inverter will run next stage. 2Continuous loop mode Inverter will run eight stages in turn. If the eighth stage is end of run, the inverter will run the next cycle form the first stage. 3Continuous loop and stop mode Its function has an analogy with Continuous loop mode. The difference is that output freq. is be reduced to 0 within the given decelerate time after a certain stage is end of run and inverter will run next stage. 4Keep the end value Its function has an analogy with single loop mode. The difference is that inverter will run in the last stage with non-zero speed. 5Keep the end value and stop mode Its function has an analogy with keep the end value. The difference is that inverter will reduce the output freq. to 0 after arriving setting value of Acc time after a certain stage is end of run and, then inverter will run the next stage. The third part of LED 0Restart from the first stage freq. When inverter stop, caused by fault or receiving stop instrument in PLC running, it will clear current running state and restart form the first stage freq. 1Restart from running freq., which is saved before the running is breaking. When inverter stop, caused by fault or receiving stop instrument in PLC running, inverter will restart from running time and freq. that is saved before the running is breaking. 2Restart from setting freq. when the running is breaking. When inverter stop, caused by fault or receiving stop instrument in PLC running, setting of running time and freq. of a certain stage will be saved. And inverter will restart form setting of running time and freq. the different between mode 1 and mode 2 is initial freq.. Shown as fig6-24. The fourth part of LEDPLC save state 0 Non-save after power off It will not be saved PLC running state after power off. Inverter will run form the stage 1 when power is on. 1Save after power off It will save PLC running state after power off. Inverter will run form the stage 1 when power is on.
60
SUNFARE380
Freq.
Freq.
[F5.3] [F5.8] [F5.2] [F5.1] [F5.14] [F5.13]
Stop
[F5.6] [F5.5]
[F5.9]
[F5.10]
[F5.11]
[F5.16]
[F5.9]
[F5.11]
Instruction
[F5.3] [F5.8]
Stop
[F5.1] t [F5.16]
[F5.9]
[F5.11]
[F5.1][F5.15] Multi-speed freq.115 Those parameters are used for setting output freq. of multi-speed. [F5.16][F5.23] Running time of Multi-speed 1~8 Those parameters are used for confirming running time of each stage. [F5.24][F5.25] Running direction of PLC multi-speed Those parameters are used for defining running direction of PLC multi-speed. [F5. 24] The first part of LED(form right to left) 0 Stage 1 FWD 1Stage 1 REV The second part of LED 0 Stage 2 FWD 1Stage 2 REV The third part of LED 0 Stage 3 FWD 1Stage 3 REV The fourth part of LED 0 Stage 4 FWD 1Stage 4 REV [F5. 25] The first part of LED(form right to left) 0 Stage 5 FWD 1Stage 5 REV The second part of LED 0 Stage 6 FWD 1Stage 6 REV The third part of LED 0 Stage 7 FWD 1Stage 7 REV The fourth part of LED 0 Stage 8 FWD 1Stage 8 REV F5.26 PLC timing running shutdown Setting range00009999min
When PLC multi-speed running function is valid, it is used for setting PLC multi-speed running, beyond the time, it will automatically shutdown. To recovery operations, first give a shutdown instruction, and then give a start-up instruction. When the parameter equals 0, timing running shutdown function is invalid.
6.7
F6.0
SUNFARE380
61
It is used for setting the internal timer. The internal timer is triggering start-upped by external terminals X1 X6, external terminals X1X6 should be set as 24(explained by parameters F3.0F3.5). Internal timer arrives the regular time, OC1OC2 or TATBTC will output 0.5s width pulse (set by F3.6 F3.8). The function can realize the timing operation shutdown. F6.1 F6.2 Fault self-recovery time Interval time of fault self-recovery Setting range0 ~ 2 Setting range0.2 ~ 20.0s
F6.1 is used for resetting some faults and run again. F6.2 defines interval time between fault starting and fault recovery. If inverter cant recover in setting value of F6.1, it will output fault signal. Inverter will check speed and restart.
Inverter cant self-recovery about overheat or overload protect.
F6.3 F6.4
The parameter defines the counting action of internal counter, and the clock terminals of counter is selected by parameter F1.6. The counting value of counter for the external clock reaches the value appointed by parameter F3.5, and the corresponding Terminal OC outputs a valid signal of same width with the external clock cycle. When the counting value of counter for external clock reached the value appointed by Parameter F6.3, the corresponding Terminal OC will output the valid signal, Go on counting to the value provided by parameter F6.4, which will lead to reset and the output valid signal will be withdrawn. The clock cycle of counter should be over 5ms and the min width should be 2ms.
[F6.3] [F6.4]
Pluse OC OC
Skip freq. 1 Amplitude accumulation of Skip freq. 1 Skip freq.2 Amplitude accumulation of Skip freq.
Setting range 0.0 ~ upper frequency Setting range0.0 ~ 5.00Hz Setting range0.0 ~ upper frequency Setting range0.0 ~ 5.00Hz
It is used for avoiding resonance point of mechanical load. Shown as fig. 6-26.
Adjusted setting freq.
Skip freq. 2
Amplitude accumulation of Skip freq. 2
Skip freq. 1
Fig.6-26
Skip freq.
62
SUNFARE380
F6.9
This parameter is used for confirming the diapaly value of running linear speed and setting linear speed, and displaying other value being positive ratio with the output frequency. Running linear velocityd-10= F6.9 output frequency (d-0) Setting linear velocityd-11= F6.9 Setting frequency (d-6)
PID feedback valued.9= F6.10 actual feedback value PID setting valued.8= F6.10 setting value
F6.11
It is used for rectifying the display value of rotator speed. rotator speedd.3= F6.11 actual output rotator speed
F6.12 F6.13
Monitor item selection 1 / Main display Monitor item selection 2 / Auxiliary display
This parameter is used for confirming display content of operation panel in state monitor mode.
It is used for getting check code to query or modify parameters. F6.15 parameter initialization Setting range0 ~ 3
It is used for modifying inverters parameters to manufacture setting. 0Parameter initialization is off. 1Parameter initialization is on. Parameter F0F9 return to manufacture setting. The following parameters cant be initialized [F0.0]Reserved [F0.1]Frequency input channel / mode selection [F0.4]Operation channel selection [F6.17]Manufactory password [F6.18]User password [F6.19]Reference password 2Clean fault records 3Complete initialization Except the following parameters, Parameters F0 FC return to manufacture setting and clean fault records. [F0.0]Reserved [F6.17]Manufactory password [F6.19]Reference password
E380 Serials of General Purpose Inverter Operation manual
SUNFARE380
63
[FC.3]Reserved [FC.4]Reserved [FC.8]Agency password [FC.13]Program version F6.16 Copy parameter function Setting range0 ~ 1
0Forbid It is forbidden to copy the backup data form operation panel to inverter, but this function doesnt affect the copy and read parameter function. 1Allow F6.17 manufactory password Dont modify this parameter without our permission. F6.18 user password It is used for getting some special power for user. F6.19 reference password Setting range0 ~ 9999 Setting range0 ~ 9999 Setting range0 ~ 9999
It is used for setting basic characteristic of wobble freq. running. The first part of LED (form right to left) 0 Function of wobble freq. is invalid. 1 Function of wobble freq. is valid. When inverter receives running instruction, inverter will run in setting freq. of F7.1. Then inverter will in wobble freq. running mode after arriving setting time of F7.2. 2 Function of wobble freq. is conditional valid. When external input terminals are valid (namely one of F3.0~F3.5 is 4), the inverter will run in wobble freq. running mode. When external input terminals are invalid, the inverter will run in preset freq. of wobble freq. (F7.1) The second part of LED: restart mode 0 Restart according to parameters saved before stop 1 Restart The third part of LED: wobble freq. characteristicSee explanation about parameter F7.3 0The wobble freq. is fixed 1The wobble freq. is changeable. The fourth part of LED: Storage characteristic of wobble freq. 0It will not save the running state of wobble freq. after power off 1It will save the running state of wobble freq. after power off F7.1 Preset freq. of wobble freq. F7.2 waiting time of preset freq. Setting range0.0 ~ the upper limit freq. Setting range0.0 ~ 6000.0s
Preset freq. of wobble freq. is running freq. before inverter is in or out wobble freq. mode. When [F7.0]###1inverter will start and run in preset freq. of wobble freq., then run in wobble freq. mode after the setting time of F7.2. When [F7.0]###2 and the terminals of wobble freq. is valid (F3.0~F3.5 is 4)the inverter will run in wobble freq. mode. When [F7.0]###2 and the terminals of wobble freq. is invalid, inverter will output preset freq. [F7.1].
E380 Serials of General Purpose Inverter Operation manual
64
SUNFARE380
F7.3
F7.3 is rate of amplitude of wobble freq. When F7.0 is [F7.0]#0## Amplitude of wobble freq. [F7.3]the upper limit freq. [F0.8] When F7.0]#1## Amplitude of wobble freq. [F7.3]Preset center freq. of wobble freq. [F7.7] + External setting freq. F7.4 Jumping freq. Setting range0.0 ~ 80.0 %
When freq. arrives the upper limit freq. , the freq. will fast decline. Or when freq. arrives the lower limit freq., the freq. will fast ascend. Jumping freq. is amplitude, which freq. is ascend or decline. Shown as fig6-27. Actual jumping freq. = [F7.4]Amplitude of wobble freq. [F7.3] F7.5 F7.6 Triangular rise time Triangular fall time Setting range0.1 ~ 1000.0 s Setting range0.1 ~ 1000.0 s
F7.5 defines the running time form lower limit freq. to upper limit freq. of wobble freq., namely Acc time F7.5 defines the running time form upper limit freq. to lower limit freq. of wobble freq., namely Dec time The sum of F7.5 and F7.6 is running cycle of wobble freq.
F7.5 and F7.6 define slope of Acc and Dec in wobble freq.
F7.7
Center freq. of wobble freq. is central value of output freq. when inverter is in wobble freq. mode. sum of setting value of F7.7 and F0.1 is actual center freq. Running process of wobble freq. is shown as fig6-28.
Running freq. [F7.4] Amplitude of wobble freq.
Running freq.
[F7.1]
t
[F7.2]
Wobble freq.
F7.8 Reserved
The first part of LED(form right to left) 0Inner PID control is invalid
2 Inner PID control is conditional valid. Inner PID is set by external terminals X1 X6 ( Parameters F3.0~F3.5) . The second part of LED 0 proportion PID controller selection 2Proportion and integral 1Integral
SUNFARE380
65
It is used for setting inner PID and feedback channel. The first part of LED(form right to left)It is used for setting PID channel 0Digital setting. It is set by parameter F8.2. 1Serials interface setting 2Panel potentiometer setting, it is on the operation panel. 3External voltage signal VC10V~5V 4External voltage signal VC20V~10V 5External current signal CC0~20mA The second part of LED Reserved. The third part of LED It is used for setting PID feedback channel. 0External voltage input VC1 is as feedback channel, which is in the range of 0~5V. 1External voltage input VC2 is as feedback channel, which is in the range of 0~10V. 2External current input CC is as feedback channel, which is in the range of 0~20mA. 3Pulse input PLS is as feedback channel, which is in the range of 0~50KHz. 4VC1+CC Feedback value is composed of VC1 and CC. 5VC1-CC Feedback value is that VC1 minus CC. 6Min (VC1, CC) Feedback value is min value between VC1and CC. 7Max (VC1, CC) Feedback value is max value between VC1and CC. The fourth part of LED: Reserved. F8.2 Inner PID close-loop digital setting Setting range0.0 ~ 10.00V
If F8.1 is 0#00, setting value will be set by F8.2. F8.3 F8.4 F8.5 F8.6 Minimum fixed value Maximum fixed value Feedback of minimum fixed value Feedback of maximum fixed value Setting range0.0 ~ [F8.4] Setting range[F8.3] ~ 10.00 Setting range0.0 ~ 10.00 Setting range0.0 ~ 10.00
Parameters F8.3 and F8.4 define the upper and lower limit value of PID setting. Parameters F8.5 and F8.6 define corresponding relation with PID feedback value. Shown as fig.6-29.
Expected feedback value [F8.6]
Fig.6-29 Relation between PID fixed value and expected feedback value
F8.7 F8.8
66
SUNFARE380
F8.9
The parameter is the allowable deviation value relative to the setting max value. When the difference between feedback value and the setting value is lower than this setting value, PID controller will stop. Shown as fig.6-30. This function is mainly suited for the system that has lower control precision and needs to avoid adjusting frequently, for example, water-supply with constant pressure system.
f PID action PID feedback [F8.9]
PID setting
PID action t
F8.10 Preset freq. for close-loop F8.11 Holding time of preset freq. for close-loop
Setting range 0.00 ~ the upper limit freq. Setting range0.0 ~ 6000.0s
Those parameters define freq. and running time of inverter before actual PID control is valid. In some control systems, inverters will forcible output a certain freq. (F8.10) and keep it in setting time (F8.11) for controlled object arrives fast targeted value. When controlled object almost arrives targeted value, PID controller will be valid to improve response speed. Setting range0.0020.000Mpa
It defines measuring range of long-distance manometer, user have to input it. F8.13 Sleeping threshold Setting range [F8.14]~[F8.12]
It defines feedback value while inverter goes sleep state. When actual feedback value is larger than setting value and inverter arrives lower limit value, the inverter will go sleep. F8.14 Awakening threshold Setting range 0.0~[F8.13]
It defines feedback value while inverter is in the state of sleeping. When actual feedback value is less than setting value, the inverter will be in the sleepy state. The inverter will wait [F8.15] to switch modes, if the inverter receives satisfied sleep or awakening condition. Shown as fig.6-31.
PID feedback value [F8.13] PID setting [F8.14] Output freq. Lower limit freq. [F0.7] Sleep Awakening [F8.15] Awakening threshold Sleeping threshold
[F8.15]
F8.15
SUNFARE380
67
When PID controller operates, switching time of sleeping/awakening mode is shown as fig.6-31. F8.16 upper limit pressure value F8.17 Lower limit pressure value It is used for setting the upper and lower limit pressure value. F8.18F8.24 Reserved Setting range[F8.13]~[F8.12] Mpa Setting range0.001 ~ [F8.14] Mpa
6.10
F9.0
The first part of LED(form right to left) It is used for setting baud rate of serials communication. 0 Reserved 11200bps 2: 2400bps 3: 4800bps 4: 9600bps 5: 19200bps To make sure both sides have the same baud rate, when client use serials communication. The second part of LED To set data format of serials communication. 0Close 1 Even 2Odd To make sure both sides have the same data format, when client use serials communication. The third and fourth part of LED: Reserved. F9.1 Local address Setting range0 ~ 30
F9.2
It defines waiting time, which is the time form local receives correctly code to send response data frames. F9.3 Function setting of communication Auxiliary function Setting range0000 ~ 1111
The first part of LED(form right to left) 0 The inverter is slave 1 The inverter is master The second part of LED Act selection after communication is lost 0 Stop 1Keep The third part of LEDLinkage jog 0Jog synchronized 1Jog asynchronous The fourth part of LEDLinkage control synchronized frequency source 0Setting frequency 1Output frequency F9.4 Checkout time of communication overtime Setting range0.0 ~ 100.0 Sec
If the machine itself dosent receive correct data signals in regulate time, the communication is fault. Inverter will keep on running or stop according to setting of parameter F9.3. F9.5 F9.6 linkage setting proportion Rectify channel of linkage setting proportion Setting range 0.010 ~ 10.000 Setting range 0 ~ 4
It is used for setting proportion of output freq. between master and slave, when takes linkage setting control. When F9.6 is 0, rectify channel of linkage setting proportion is invalid. Slave freq. = Master freq. [F9.5]
68
SUNFARE380
When F9.6 is 1, 2, 3 or 4, rectify channel of linkage setting proportion is valid. When the lower limit value of rectify channel is selected, The rectify coefficient is 0.5; when the upper limit value of rectify channel is selected, the rectify coefficient is 2.0 , Slave freq. = Master freq. [F9.5]rectify coefficient0.502.00 F9.6 is used for selecting rectify channel. Rectify channel 1Panel potentiometer Rectify channel 2External voltage signal VC10 ~ 5V Rectify channel 3External voltage signal VC20 ~ 10V Rectify channel 4External current signal CC0 ~ 20mA F9.7 F9.8 Setting channel of guest inverter auxiliary freq. Amplitude of auxiliary freq. Setting range04 Setting range0.025.00 Hz
It is used for selecting the setting channel of guest inverter auxiliary freq. and amplitude of auxiliary freq.
Auxiliary freq.
[F9.8]
[F9.8]
When the input value of auxiliary freq. setting channel is middle valueauxiliary freq. is 0, Slave output freq.= master instruction freq.linkage proportionauxiliary freq. (Linkage proportion is set by [F9.5] [F9.6]) F9.9 Load self- equilibrium function F9.10 Load self- equilibrium proportion F9.11 Trimming range of load self- equilibrium freq Setting range01 Setting range0.502.00 Setting range0.05.00
These parameters are used for setting load self-equilibrium function in linkage synchronous running mode, master inverter is equals an inverter plus a high-precision synchronizer, usually can get high-precision freq. synchronous. In some application field, load of inverter group should keep balanced so that all the transmission chain tension or velocity strict agreement. E380 serial of inverter has loaded self- equilibrium function when inverters are in linkage running mode. When the load self- equilibrium function is valid, master inverter will transfer the load information to every slave inverter, and every slave inverter will adjust the load instructions according the master. When the certain slave inverter should to bear a heavier load, it could change through [F9.10]. The value is greater, the load capacity is heavier. Load self- equilibrium below 5Hz, the effect limited. Only if each master and slave inverter has good linkage ratio coefficient, the self- equilibrium function is valid. If the adjust is not obvious, please increase parameter [F9.11].
SUNFARE380
69
It defines lower limit voltage which terminals P+ and P- are allow while inverter is working normally. For some low voltage conditions, user can decrease under voltage protection level to ensure that inverter is running normally. FC.1 over voltage limit level Setting range 660V ~ 760V
It defines threshold of voltage stall protection while motor is decelerating. If DC voltage caused by decelerating is beyond setting value of FC.1, deceleration time will automatic prolong. Shown as fig6-33.
f
Adjust Dec time
DC voltage
[FC.1]
Fig.6-33
FC.2
It defines the max output current which is permitted by inverter. Whatever the operation mode is, inverter will adjust output freq. to inhibit current within the range of regulation, when output current of inverter is beyond setting value of FC.2. FC.3 FC.4 Reserved Reserved
It is used for setting some coefficients with special function in running process. Generally, user neednt set. The first part of LED(form right to left) Under voltage compensation intensity The second part of LED Over voltage inhibit intensity The third part of LED Over current inhibit intensity The fourth part of LEDSelf-adapting braking torque adjust intensity FC.5 Action function selection Setting range 0000 ~ 0111
The first part of LED(form right to left) Cooling fan control 0Cooling fan run after inverter run. Cooling fan will stop after inverter stop. When temperature is above 40the cooling fan also will also run. 1Cooling fan will automatic run when inverter is power on. The second part of LEDReserved. The third part of LED Voltage over modulation 0Invalid 1Valid The fourth part of LEDReserved. FC.6 Auxiliary functions Setting range00000011
The first part of LED(form right to left)Forbid to modify parameter. 0Invalid. 1Valid. When it forbids modifying parameter is valid, [F0.18] will be invalid, if you want to get new password, please
E380 Serials of General Purpose Inverter Operation manual
70
SUNFARE380
ask for our service department. This function is used for preventing modify parameter wrongly. The second part of LEDInput terminal effective level . 0Low level (terminals is connected) 1High level (terminals is disconnected) The third part of LED: Reserved The fourth part of LEDSelection of rotate speed display proportion 0: the coefficient of rotational speed display is valid Rotational speed display=Rotational speed Rotator speed coefficient setting(F6.11) 1: the deceleration proportion is valid Rotational speed display=Rotate speed Rotator speed coefficient setting(F6.11) FC.7 FC.8 FC.9 FC.10 FC.11 FC.12 . FC.13 Reserved Agency password Reserved Reserved Oscillatory inhibiting factor Reserved Program version Range 1600 ~ 1699 Setting range 0 .0~ 2.00 Setting range0 ~ 9999
It is read-only parameter.
SUNFARE380
71
Fu.1
Over-current Acc
Deceleration time is too short. 1. Load occurs mutation 2. Power grid voltage is too low 1.Input voltage is too high 2. Power supply is switched on or off frequently. 1. Deceleration time is too short. 2. Input-voltage is abnormal 1. Power supply is abnormal 2. There are energy feedback load Power supply is abnormal
Fu.4
Fu.5
Fu.9
1. Power supply is abnormal 1. Check power supply voltage 2. There is great fluctuation of load into electric 2. Provide the power supply separately network. 1. Check wiring protective action of 1. Output is short-circuit or ground 2. Reduce the load inverterr 2. Load is too heavy 3. Check whether brake resistor is short-circuit Output grounding 1. Check the connecting wire 1.The output terminal of inverter grounds 2. The wire is too long between inverter and motor 2. Shorten the connection wire or reduce the and the carrier frequency is too high. carrier frequency. Fault action caused by disturbance of electromagnetism Add absorb circuit around inverter
Fu.10
Fu.11
Interfere of inverter
1. Reduce the load or replace with higher 1. Load is too heavy. capacity inverter. 2. Acceleration time is too short. 2. Prolong Acc time. 3. Torque boost is too high or V/F curve is not 3. Decrease the torque boost or adjusting Fu.12 Inverter over-loading suitable. V/F curve. 4. Voltage of Power supply is too low 4. Check Voltage of Power supply 5. User start rotating motor, but doesnt set 5. To set function of detect speed and function of detecting speed and restart. restart 1. Reduce the load 1. Load is too heavy. 2. Prolong Acc time 2. Acceleration time is too short. 3. Increase the over-loading protection factor Fu.13 Motor over-loading 3. The setting of protection factor is too small 4. Torque boost is too high or V/F curve is not of motor [F4.13] suitable. 4. Decrease torque boost voltage and adjust V/F curve.
72
SUNFARE380
1. Wind hole is blocked 2. Environmental temperature is too high 3. Fan is damaged 1. Clear air duct or improve the air condition. 2. Improve ventilation condition or decrease carrier frequency. 3. Replace fan.
Fu.14 Inverter overheat Fu.15 Reserved Fu.16 External equipment failure Fu.17 Reserved Fu.18 Reserved Fu.19 Reserved Fu.20 Current checking error
There is signal input on the peripheral. Equipment Check the signal source and the pertinent fault input terminal of Inverter equipments.
1.The current detecting equipment or circuit is Contract Us damaged 2.Auxiliary power supply has problem 1. Signal line of temperature is poor contact 2. Temperature sensor is damage. 1. Check jack 2. Contract Us
Inner data of storage Read and write errors of the control parameter is wrong.
Contract Us
7.3 Reset
Be sure to check the fault cause and exclude it before reset, otherwise, which may lead to the inverter, permanent damaged. If the inverter can not be reset or occur the fault again after reset, please find out the reason. Continuous reset will damage the inverter Over-load or over-heat protective action should delay 5 minutes to reset. When the inverter occurs the fault, you can reset the inverter to resume the normal running by any way as follows: I. II. III. IV. External reset input-terminal RST and GND terminal are closed, and then off. While the fault code is displayed, press key. It will send fault reset instrument by RS485 interface. Turn the power source off.
E380 Serials of General Purpose Inverter Operation manual
SUNFARE380
73
8MAINTENANCE
As a result of ambient temperature, humidity, dust, vibration and aging of internal components of inverter, the inverter will probably appear the potential problem during running. In order to ensure the inverter to run steadily for a long time, the inverter should be checked up once at 3 to 6 months.
First of all, turn the inverters power off. And professional worker performs maintenance.
Running Environment
Cooling system
Inverter
1. Vibration smooth, the temperature of air outlet is normal. 2. Not abnormal voice and no peculiar smell 3. Fastening screw is not loosed. 1. Running smooth, and temperature is normal
Motor
Input/output Parameters
Inverter has done the electric insulating experiment before leave-factory, so user dont need to do the withstand voltage test. Do the insulation test to the inverter if necessary, all of I/O terminals must be connected in short-circuit (R, S, T,L1,L2, U, V, W, P, P-, PB). Strictly prohibit from doing the insulation test for the single terminal. Please use 500V Meg-ohmmeter to perform this test. Control circuit can not be used the Meg-ohmmeter to test. For insulation test to motor, the connection wire between motor and inverter should be disassembled.
74
SUNFARE380
The lifetime of all the cooling fans in the inverter is about 15000 hours (that inverter is used continuously about two years). If the fan happens to abnormal noise or vibration, it should be replaced immediately.
8.3 Storage
If the inverter dont used for a long time, please notice the following items: 1 2 To avoid storing the inverter at the environment with high-temperaturehumidity, vibration or metal dust, and ensure the well ventilation. If the inverter is not used for a long time, it should be energized to resume the capability of electrolyte capacitor once at 2 yearsat the same time, check the functions of inverter. When the inverter is electrified, its voltage should be increased by an autotransformer step by step and the time should not be less than 5 hours.
If inverter is not used for a long time, the performance of internal filter capacitor will descend.
In guarantee time, if the faults are caused by the following cases, certain service cost would be charged. Malfunction caused by not following the operation manual or over the standard specification; Malfunction caused by repair or refitting by oneself without grant. Malfunction caused by the bad-storage. Malfunction due to application of inverter for abnormal functional needs. Damage caused by the fire, salt-corrode, gas-corrode, earthquake, storm, flood, thunder, voltage abnormal or other force majored.
Even if over guarantee time, our company will provide the paid service forever.
SUNFARE380
75
9. USAGE EXAMPLE
9.1 Panel on-off control, Panel potentiometer setting frequency
9.1.1 Parameters setting 1. 2. When F0.4 is 00#0, panel control is valid. When F0.1 is 3, panel potentiometer is valid.
Power Supply
R S T
U V W E
Direction control
9.1.3 Operation Notes: Press key to start the inverter, and then rotate the button of panel potentiometer in clockwise to increase setting frequency step by step. Contrarily, rotate in anti-clockwise to decrease setting frequency step by step. Press key to stop the inverter.
FWD REV
10K
76
SUNFARE380
9.2.3 Operation FWD-CM is offthe motor will run forward. REV-CM is off, the motor will run backward. FWD-CM and REVCM are off or on at the same time, the inverter will stop. Setting frequency is set by external voltage signal VC2.
Control method of terminals FWD and REV is set by parameter F0.5. See the explanation about parameter F0.5.
Power Supply
FWD REV
9.3.3 Operation Notes: FWD-CM is offthe motor will run forward. REV-CM is off, the motor will run backward. FWD-CM and REV-CM are off or on at the same time, the inverter will stop. If X1, X2 and X3 are all open with CM, the multi-speed running is invalid. The inverter will run as the setting instruction speed. (The setting frequency channel is selected by parameter F0.1) If one terminal or all of X1, X2 and X3 are connected with CM terminal, the inverter will run as the multi-speed frequency selected by X1, X2 and X3.
9.4 Panel on-off controlPanel potentiometer setting frequency and linkage control with inverters
9.4.1 Initial setting Master setting 1. Freq. setting channel is panel potentiometer mode. Namely F0.1 is 3. 2. Operation channel selection is panel control, namely F0.4 is 00#0.
SUNFARE380
77
3. Communication setting (Parameter F9.0) is default. 4. If F9.3 is 0001, the inverter is master. Slave setting 1. Freq. setting channel is RS485 interface. Namely F0.1 is 2. 2. Operation channel selection isRS485 interface. Namely F0.4 is 00#2. 3. Communication setting (Parameter F9.0) is default. 4. If F9.3 is 0000, the inverter is slave. 5. Linkage setting proportion (Parameter F9.5) will be set by user needs. 6. Rectify channel of linkage setting proportion is external voltage signal VC1. Namely F9.6 is 2 9.4.2 Basic wiring
Power Supply 3-phase Breaker R S T U V W E Motor
Host
Guest
VS VC2 GND RS485 B
Motor
Guest
VS VC2 GND RS485 B
9.4.3 Operation Notes: Running freq. of slave has a certain proportion with master. Linkage setting proportion is set by parameter F9.5. In this example, freq. proportion of master and slaves can get across by VC1 channel.
78
SUNFARE380
SUNFARE380
79
1 bit start-bit , 8-bit data bits, 1 bit stop-bit and odd check. 1 bit start-bit , 8-bit data bits, 1 bit stop bit and even check. It is also manufacture setting. 2.2.2. Baud rate There are five kinds of baud rate, 1200bps, 2400 bps, 4800 bps, 9600 bps and 19200 bps. 2.2.3. Communication mode 1 Point to point communication mode, which is master Polling and slave Responding. 2 Setting the series interface communication parameters by the keypad of inverter. These parameters include local address, baud rate and data format.
Master must set the same baud rate and data format of inverter
2.2.4. Communication rule 1 There are at least 5-byte startup interval time between data frames, only the message with the stated startup internal time is valid. (2) The waiting time of master, with the longest responding time of inverter is 8-byte input time. If not, determined as a failure. 3 If inverter doesnt receive any message during setting time of F9.4, it will be occurred the wire-break fault. Running state of slaves is decided by setting value of F9.3. 2.3. Message structure The length of each message is between 11 and 18 bytes. The type of character are ASC code and hex.
1
3800H is shown as ASC code. Data list DataASC 9 Setting Data 33 10 Setting Data 38 11 Setting Data 30 12 Setting Data 30
3800H is shown as hex. Data list 9 Setting Data 0 10 Setting Data 0 11 Setting Data 38 12 Setting Data 00
DataHex
Sending Sequence
Definition Header
Sending Sequence
Definition
0 1 2 3 4 5 6 7 8
Slave addr. Slave addr Type of order Operation order Operation order Type of data Data addr. Data addr.
Slave addr.
Order area
Addr. area
9 10 11 12 13 14 15 16 17
Setting data Setting data Setting data Setting data Check sum Check sum Check sum Check sum Tail 0DH Check area Data area
80
SUNFARE380
0 1 2 3 4 5 6 7 8 2.4.
9 10 11 12 13 14 15 16 17
Running data Running data Running data Running data Check sum Check sum Check sum Check sum Tail 0DH Check area Data area
2.4.1. Header This communication protocol defines that both 2AH (ASC code of character and 5AH are available. When header is 2AH, all of data behind header is ASC code. When header is 5AH, all of data behind header is hex code and invalid byte fill 0. Unaided headers of 2AH and 5AH arent rightful header. There need waiting time above five bytes before sending header. 2.4.2. Slave address Slave address is inverter address. The address range of slave machine is 0~30, 31 (1FH) is broadcast communication address. 2.4.3. Type of order Type of order is only in master command frame and defines task of the data in this frame. Length of each frame is different according to different order. Type of order is shown as following table.
Data 0 1 2 3 4 5 6F Operation Read the state and information of slaves Read the running parameter of slaves Read code parameter Modify code parameter in RAM, it will not save after power down Send control order Modify code parameter in EPROM, it will save after power down Reserved
2.4.4. Operation order Master gives a control order to slaves. It exists in all messages and is shown as following table.
Data 00H 01H 02H 03H 04H 05H 06H 20H 21H Operation Invalid instrument Start with FWD Start with REV Stop Slave will FWD running when jog Slave will REV running when jog Jog running is stop Slave will fault reset Slave will emergency stop Data 10H 11H 12H 13H 14H 15H 16H 30H 31H Operation To set running freq. of slave Start with FWD and setting freq. Start with REV and setting freq. Stop with Start setting freq. Slave will FWD running with setting freq. when jog Slave will REV running with setting freq. when jog Slave will JOG running with setting freq. Reserved Reserved
When user need not send operation order, please send invalid order 00H.
SUNFARE380
81
2.4.5.
Slave responding
3 Slave responding
4 0
5 0
6 Check Sum
7 Check Sum
8 Check Sum
9 Check sum
10 Tail 0DH
Order/responding area
Check area
2.4.6.
State feedback
Slave gives a running state about slave to master, and state feedback exists in all messages. It is shown as following table.
Data 00H 01H 02H 03H 04H 05H 06H 20H Operation DC voltage of slave is not ready Slave is FWD running Slave is REV running Slave is stop Slave will FWD running when jog Slave will REV running when jog Reserved Slave is in fault state Data 10H 11H 12H 13H 14H 15H 16H 21H Reserved Accelerating with FWD Accelerating with REV Abruptly stop and restart Decelerating with FED Decelerating with REV Slave is in DC braking state. Slave is emergency Operation
When slave occurs fault (data of state feedback is 20H), the seventh and eighth of feedback rata frame is fault code.
2.4.7. Check sum The sum of ASCor hex form slave address to setting data (running data) is check sum. 2.4.8. Frame Tail 0DH is hex, namely ASCof CR is 0DH.
82
SUNFARE380
Slave responding
Sending Sequence
0 1 2 3 4 5 6 7 8
Header Slave addr. Slave addr Slave responding State feedback State feedback Data type Character information Character information.
9 10 11 12 13 14 15 16 17
Character information Character information Character information Character information Check sum Check sum Check sum Check sum Tail
Slave will give different characters information to master according to different data type in master message.
Data Type (master sending) Character information (slave responding) 6 7 8 9 10 11 12 Read slave inf. about Voltage 0 0 Power Power Power Power inverter model level Read slave inf. about 1 Reserved Reserved Reserved Reserved Reserved Reserved inverter series Read slave inf. about 2 Reserved Reserved # # # # program version Read slave inf. about Master Setting freq. 3 Reserved Reserved Reserved Reserved control information control of master 4F Reserved # # # # # #
For example, if data type is 0, slave return 400185. 4 means voltage level. 0185 means power, 18.5Kw. 2 Orderis used for reading running parameter of slave
0 Master Sending 1 2 3 4 5 6 7 8 9
10
11
12
13
Header
Data Data Check Check Check Check Tail subentry subentry Sum Sum Sum Sum
Slave responding
Sending Sequence
0 1 2 3 4
Header Slave addr. Slave addr. Slave responding Slave responding State feedback
9 10 11 12 13
Running data Running data Running data Running data Sending Sequence Check sum
SUNFARE380
83
5 6 7 8
14 15 16 17
Refer to the explanation about state monitor parameter in the fourth chapter.
Slave responding
Sending Sequence
0 1 2 3 4 5
6 7 8
Header Slave addr. Slave addr Slave responding State feedback State feedback Data type Data addr. Data addr.
9 10 11 12 13 14 15 16 17
Parameter data Parameter data Parameter data Parameter data Check sum Check sum Check sum Check sum Tail
4order is used for modifying parameter of code in RAM. order is used for modifying parameter of code in EPROM.
84
SUNFARE380
Master Sending Sending Sequence
0 1 2 3 4 5 6 7 8
Header Slave addr. Slave addr 3 or 5 Operation order Operation order Data type Data addr. Data addr.
9 10 11 12 13 14 15 16 17
Setting data Setting data Setting data Setting data Check sum Check sum Check sum Check sum Tail
Slave responding
Sending Sequence
0 1 2 3 4 5 6 7 8
Parameter unit Data type
Header Slave addr. Slave addr Slave responding State feedback State feedback Data type Data addr. Data addr.
9 10 11 12 13 14 15 16 17
Setting data Setting data Setting data Setting data Check sum Check sum Check sum Check sum Tail
For example, data address of F0.8, F1.8 and F#.8 are 8. But data type of them is different. AttentionWhen slaves dont accomplish order form master, setting data is 0000. 5Orderis used for sending control order. It is fit for routine operation for inverter.
Master Sending Sending Sequence
0 1 2 3 4 5 6 7 0 1 2 3 4 5
Header Slave addr. Slave addr 4 Operation order Operation order Setting data Setting data Slave responding Header Slave addr. Slave addr Slave responding State feedback State feedback
8 9 10 11 12 13 14
Setting data Setting data Check sum Check sum Check sum Check sum Tail Sending Sequence
9 10 11 12 13 14
Running data Running data Running data Running data Check sum Check sum
SUNFARE380
85
6 15 0 Check sum 7 16 Monitor item Check sum 8 17 Monitor item Tail Setting data in master sending is setting freq., which is send form master to slave. Setting data in slave responding is running parameter, which is send form master. It is set by parameter F6.12.
4. Usage example
4.1. Order To read slave model of 0 master will send
#.
2A 30 30 30 30 31 30 30 30 30 31 38 31 0D 5A 00 00 00 00 01 00 00 00 00 00 00 01 0D
Slave will respondInverter with 4T0150KW
2A 30 30 30 30 33 30 32 30 30 30 30 34 30 32 34 39 0D 5A 00 00 00 00 03 00 02 00 00 00 00 04 00 00 00 09 0D
4.2. Order To read running parameter of 0 master will send
#
2A 30 30 30 30 31 30 34 30 30 31 35 30 30 32 34 42 0D 5A 00 00 00 00 01 00 04 00 00 00 01 50 00 00 00 56 0D
Slave will respondReturn current DC voltage of generatrix is 285V
2A 30 30 30 30 31 30 30 30 33 45 37 30 32 36 30 0D 5A 00 00 00 00 01 00 00 00 00 00 03 E7 00 00 00 EB 0D
4.3. Order To read code parameter of 0 slavenamely parameter F0.16 master will send
#
2A 30 30 32 30 31 30 30 31 30 31 38 34 0D 5A 00 00 02 00 01 00 00 01 00 00 00 04 0D
86
SUNFARE380
Appendix OPTIONS
1. Operation panel
Sometimes users need to take operation panel out of the inverter or control cabinet, if users purchase panel base and wire, it is convenient to install and debug. Wire between operation panel and inverter should be less than 15m. If the length is above 15m, long-distance control line is needed. 1.1 Appearance of panel base
Fig-D Hole dimension of small panel base Fig-C Dimension of small panel base
It is recommended that users take Fig-B and Fig-D Hole dimension of panel base.
SUNFARE380
87
1.3 Installation of panel base Open a hole on the control cabinet according to dimension of panel base. And put the panel horizontally into the hole. Then four locks in panel base will lock. There is an interface on the bottom of base, please insert the long-distance control wire into it.
2. Brake resistance
The brake resistance is shown following table.
Power of brake resistance Kw 0.4 0.6 1 0.5 0.65 1.0 1.5 2.0 2.5 3.6 4.5 5.5 6.5 8.5 12 15 18 18 25 30 36 42 45 50 60 60 75 75 90 Brake resistance 75 50 35 300 200 125 85 65 50 35 30 25 20 15 12 10 8 8 6 5 4 3.5 3 3 2.5 2.5 2 2 1.5
Model E380-2S0015 E380-2S0022 E380-2S0037 E380-4T0015 E380-4T0022 E380-4T0037 E380-4T0055 E380-4T0075 E380-4T0110 E380-4T0150 E380-4T0185 E380-4T0220 E380-4T0300 E380-4T0370 E380-4T0450 E380-4T0550 E380-4T0750 E380-4T0900 E380-4T1100 E380-4T1320 E380-4T1600 E380-4T1850 E380-4T2000 E380-4T2200 E380-4T2500 E380-4T2800 E380-4T3150 E380-4T3500 E380-4T4000
Applied motorKw 1.5 2.2 3.7 1.5 2.2 3.7 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90 110 132 160 185 200 250 250 280 315 350 400
Brake torque 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
If the braking effect is not obvious, please decrease brake resistance and increase power of brake resistance according to proportion.
88
SUNFARE380
Floor 5 2nd floor, Zhonghang Shahe Industrial Park, Nanshan District, Shenzhen, PRC. TEL +86-755-26919258 FAX +86-755-26919882 Commercial Hotline +86-755-26609885, 26606885 Commercial FAX +86-755-26912599 After-service Hotline +86-755-26910928